Upload
eyad-a-feilat
View
226
Download
0
Embed Size (px)
Citation preview
8/12/2019 T2 Load Characterstics
http://slidepdf.com/reader/full/t2-load-characterstics 1/19
Loads and Load Duration
2.0 Introduction
Unlike transmission systems, distribution systems are directly connected to loads. As
a result, the nature of the load often has a large influence on operational and planningdecisions concerning the distribution system.
Loads are characterized into the following customer classes:o Residentialo Commercialo Industrialo Agricultural (rural commercial)
Customer class loads are normally assessed at the feeder, substation, region, orsystem level, and at this level, end-users of a given class tend to use electrical energy
in much the same manner.
2.1 Load curves The load curve is a plot of load (or load per end-user) variation as a function of time
for a defined group of end-users.
The end-user grouping may be by electrical proximity, e.g., by feeder, substation,
region, or system level. Alternatively, it may be by end-user class.
Daily, weekly, monthly, and yearly load curves are commonly developed and used in
order to gain insight into the usage behavior of a group of end-users.
Fig. 1 shows a daily load curve for a single residential end-user. The multiplicity of
high peaks is due to the intermittent operation of large appliances such as
refrigerators, air conditioners, and stoves, where the highest peaks are a result ofsimultaneous operation of such devices.
Fig. 1: Daily load curve for single residential end-user [1]
8/12/2019 T2 Load Characterstics
http://slidepdf.com/reader/full/t2-load-characterstics 2/19
Fig. 1 is not very useful for understanding the usage behavior of residential end-users
as a class. To do this, we develop a load curve for multiple residential end-users. To
provide a basis for comparison, we plot the load per end-user rather than the totalload. Fig. 2 illustrates daily load curves for 2, 5, 20, and 100 end-users, respectively.
24-hour demand curve for Customer # 1 and 2
24-hour demand curve for Customer # 3 and 4
Fig. 2: Daily load curves for groups of end-users [1]
We observe the smoothing effect on the curves. We also observe the peak load per
end-user decreases as the number of end-users in the group increases. This is because
at any given moment, some end-users will incur a peak while others do not, so that
the average load at any given moment will always be less than the highest individual
peaks for that moment.
This aggregation of load curves across multiple end-users is done for each of thedifferent end-user classes, except the load curves are given in terms of percent of
peak rather than load per end-user.
Fig. 3 illustrates such load curves for the various end-user classes, including a
“miscellaneous” class (mainly sales to other utilities) and also the aggregation of
these class-specific load curves into a system load curve.
8/12/2019 T2 Load Characterstics
http://slidepdf.com/reader/full/t2-load-characterstics 3/19
Fig. 3: Class-specific load curves and system load curve
Some observations from Fig. 3 follow:
1. Urban and rural residential loads
- Have three peaks: once at 8 am, once at noon, and once at 6 pm,
- Have two valleys, once at 5 am and once at 3 pm,
- Differ in that the urban load does not fall off so steeply after 7 pm.
2. Commercial loads (rural and urban) peak at about 11 am, dip slightly at noon, and
then are rise slightly until about 5 pm after which they drop sharply.3. The industrial load curves are similar to the commercial except that the valley’s
only dip to about 50% of peak rather than 20% in the case of commercial. This is
the case since many industrial end-users operate 24 hours a day.
2.2 Load duration curves
It is often of interest to know the percent of time that the load in a system, flowing
through a substation, or flowing on a feeder exceeds some particular level.
For example, we might determine that at 90% of peak, the losses are unacceptably
large for the existing amount of voltage switched capacitors. Purchasing and
installing more voltage switched capacitors would solve the problem. This may be a
good investment if the load exceeds 90% of peak for more than 5% of the time.
Otherwise, it is not a good investment. So how do we tell the % of time the load
exceeds a particular value?
One tool for doing this is the so-called load duration curve, which is formed as
follows.
8/12/2019 T2 Load Characterstics
http://slidepdf.com/reader/full/t2-load-characterstics 4/19
Consider that we have obtained, either through historical data or through forecasting,
a plot of the load vs. time for a period T, as shown in Fig. 4 below.
L o a d ( M
W )
Time T
Fig. 4: Load curve (load vs. time)
Of course, the data characterizing Fig. 4 will be discrete, as illustrated in Fig. 5.
L o a d ( M W )
Time T
Fig. 5: Discretized Load Curve
We now divide the load range into intervals, as shown in Fig. 6.
T
10
9
8
7
6
5
4
3
2
1
0
L o a d ( M W )
Time
Fig. 6: Load range divided into intervals
8/12/2019 T2 Load Characterstics
http://slidepdf.com/reader/full/t2-load-characterstics 5/19
11
10
9
8
7
65
4
3
2
1
00 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
Probability(Load > L)
L ( M W )
Fig. 7: CDF with axes switched
If the horizontal axis is scaled by the time duration of the interval over which the
original load data was taken, T, we obtain the load duration curve.
This curve provides the number of time intervals that the load equals, or exceeds,
a given load level. For example, if the original load data had been taken over a
day, then the load duration curve would show the number of hours out of that year
for which the load could be expected to equal or exceed a given load level,
11109
87
654
3
210
2.4 4.8 7.2 9.6 12.0 14.4 16.8 19.2 21.6 24.0
Number of hours that Load > L
L ( M W )
Fig. 8: Load duration curve
Load duration curves are useful in that they provide guidance for judging different
alternatives. In our example of unacceptable losses at loads exceeding 90%, we
see from Fig. 8 that this situation occurs for 1.2 hours/day (or 5% of the time).
8/12/2019 T2 Load Characterstics
http://slidepdf.com/reader/full/t2-load-characterstics 6/19
Chapter 2
Load Characteristics
Basic Definitions
Demand
The demand of an installation or system is the load at the receiving
terminals averaged over a specified interval of time. Measured in kW, kVA,
kA or A
Demand IntervalIt is the period over which the load is averaged. This selected period may
be 15 min, 30 min, 1 hr, or even longer, denoted as t Δ . Of course, theremay be situations where the 15-and 30-min demands are identical
Maximum DemandThe maximum demand of an installation or system is the greatest of all
demands which have occurred during the specified period of time.
Diversified demand (or coincident demand) It is the demand of the composite group, as a whole, of somewhat unrelated
loads over a specified period of time.
Noncoincident Demand The sum of the demands of a group of loads with no restrictions on the
interval to which each demand is applicable
Demand Factor It is the ratio of the maximum demand of a system to the total connected
load of the system. Therefore, the demand factor (DF) is
demand connected total
demands DF
.max≅
8/12/2019 T2 Load Characterstics
http://slidepdf.com/reader/full/t2-load-characterstics 7/19
7
Connected LoadIt is the sum of the continuous ratings of the load-consuming apparatus
connected to the system or any part thereof.
Utilization FactorIt is the ratio of the maximum demand of a system to the rated capacity of
the system. Therefore, the utilization factor (Fu) is
Systemtheof Capacity Rated
demand F u
.max≅
Plant FactorIt is the ratio of the total actual energy produced or served over a designated
period of time to the energy that would have been produced or served if the
plant (or unit) had operated continuously at maximum rating. It is also
known as the capacity factor or the use factor . Therefore,
T rating plant
T served or produced energyactual
factor Plant ×
×
= max
It is mostly used in generation studies. For example,
T rating plant
generationannualactual factor Plant Annual
×=
max
Or
8760max ×=
rating plant
generationenergyannualactual
Load FactorIt is the ratio of the average load over a designated period of time to the
peak load occurring on that period. Therefore, the load factor FLD is
8/12/2019 T2 Load Characterstics
http://slidepdf.com/reader/full/t2-load-characterstics 8/19
8
load peak
load averageF LD ≅
T load peak
T load averageF LD
×
×≅
T load peak
served units
×≅
Where T = time, in days, weeks, months, or years. The longer the period Tis the smaller the resultant factor.
8760factorloadAnnual
×=
load peak annual
energyannualtotal
Diversity factor
It is the ratio of the sum of the individual maximum demands of the varioussubdivisions of a system to the maximum demand of the whole system.
Therefore, the diversity factor FD is
demand coincident
demandsindividualof sumF D
max
max=
Or
g
n
D D
D D D DF
++++=
...321
Or
8/12/2019 T2 Load Characterstics
http://slidepdf.com/reader/full/t2-load-characterstics 9/19
g
n
i
i
D D
D
F
∑=
=1
Where
Di = maximum demand of load i, disregarding time of occurrence
demand ent noncoincid class
peak groupsystemof timeat demand classcwhere Dc D i
n
i
iigmax
)(
1
=×=∑=
= Coincident maximum demand of group of n loads
The diversity factor can be equal to or greater than 1.0.
The demand factor is:
demand connected total
demands DF
max≅
Or
Maximum demand = total connected demand x DF
The diversity factor can also be given as
g
n
i
ii
D D
DF TCD
F
∑=
×
=1
Where TCDi = Total Connected Demand of group, or class, i load
DFi = Demand Factor of group, or class, i load
Coincidence Factor
It is the ratio of the maximum coincident total demand of a group ofconsumers to the sum of the maximum power demands of individual
8/12/2019 T2 Load Characterstics
http://slidepdf.com/reader/full/t2-load-characterstics 10/19
consumers comprising the group both taken at the same point of supply for
the same time. Therefore, the coincidence factor (FC ) is
demandsindividualof sumdemand coincident F c
maxmax≅
Thus, the coincidence factor is the reciprocal of diversity factor; that is,
∑=
=n
ii
g
c
D
DF
1
8/12/2019 T2 Load Characterstics
http://slidepdf.com/reader/full/t2-load-characterstics 11/19
Primary Feeder Load Data
Time
Load, kW
Street
lightingResidential Commercial
Total
Demand
12 A.M 100 200 200 500
1 100 200 200 500
2 100 200 200 500
3 100 200 200 500
4 100 200 200 500
5 100 200 200 500
6 100 200 200 500
7 100 300 200600
8 0 400 300 700
9 0 500 500 1000
10 0 500 1000 1500
11 0 500 1000 1500
12 noon 0 500 1000 1500
1 0 500 1000 1500
2 0 500 1200 1700
3 0 500 1200 17004 0 500 1200 1700
5 0 600 1200 1800
6 100 700 800 1600
7 100 800 400 1300
8 100 1000 400 1500
9 100 1000 400 1500
10 100 800 200 1100
11 100 600 200 90012 P.M. 100 300 200 600
8/12/2019 T2 Load Characterstics
http://slidepdf.com/reader/full/t2-load-characterstics 12/19
8/12/2019 T2 Load Characterstics
http://slidepdf.com/reader/full/t2-load-characterstics 13/19
Load DiversityIt is the difference between the sum of the peaks of two or more individual
loads and the peak of the combined load. Therefore, the load diversity (LD)
is
∑=
−≅n
i
gi D D LD1
)(
Contribution FactorDefines Ci as the contribution factor of the i
th load to the group maximum
demand. It is given in per unit of the individual maximum demand of the ith
load. Therefore,
nn332211g D cDcD cDcD ×…+×+×+×=
Substituting
∑=
=n
1i
i
g
c
D
DF
Or
∑
∑
=
=
×
=n
i
i
n
i
ii
C
D
Dc
F
1
1
8/12/2019 T2 Load Characterstics
http://slidepdf.com/reader/full/t2-load-characterstics 14/19
Loss FactorIt is the ratio of the average power loss to the peak-load power loss during a
specified period of time. Therefore, the loss factor (FLS) is
load peak at loss power
loss power averageF LS ≅
Here is an approximate formula to relate the loss factor to the load factor:
2
7.03.0 LD LD LS F F F += Where
FLS = loss factor, pu
FLD = load factor, pu.
Plotting the Load Duration Curve
The load duration curve is the plot of load demand v.s. the period or time
for which the load persists on the system. Usually the duration of the load isexpressed as percentage of the total time.
Example #1:
Draw the daily load duration curve for certain substation that has the
following demand data during 24 hours.
Period 0 to
7
7 to
9
9 to
11
11 to
13
13 to
16
16 to
22
22 to
24
Load in
(MW)
20 100 45 70 40 85 30
The following Table helps drawing the required curve:
1- Build a Table that has 3 columns and number of rows equal to the
number of the periods in your given data.2- The first column contains the load demand in a descending order.
8/12/2019 T2 Load Characterstics
http://slidepdf.com/reader/full/t2-load-characterstics 15/19
3- The second column contains the total time for which each load
persists.
4- The third column contains the percentage of each load duration or
period to the total time.
5- Draw the curve according to the firs column (on the vertical axis) and
the second column (on the horizontal axis).
6- Then you may approximate your curve following the ordinary
methods of curve fitting.
As follows:
Load demand in
(MW)
Duration of the load
in (hrs)
Duration of the load
in (% of the total time)
100 2 8.33
85 2+6=8 33.30
70 8+2=10 41.67
45 10+2=12 50.00
40 12+3=15 62.50
30 15+2=17 70.83
20 17+7=24 100.00Daily Load Duration Curve
0
20
40
60
80
100
120
8.33 33.3 41.67 50 62.5 70 100
% Time
L o a d i n
( M W )
8/12/2019 T2 Load Characterstics
http://slidepdf.com/reader/full/t2-load-characterstics 16/19
Load factor
The ratio of the average demand over a time interval to the maximum
demand over the same time interval.
peak
avg
LD
P
PF =
The load factor always falls between 0 and 1. It indicates how peaked the
load curve is.
Maximum coincident demand
The maximum coincident demand for a time interval is the maximum of the
sum of the demands imposed by a group of loads over that time interval.
The maximum coincident demand is also called the peak demand. We will
use P peak to represent this.
The difference between maximum demand and maximum coincidentdemand is that the former refers to a single load and the latter to a group of
loads.
Consider sub X that supplies 5 feeders. At 17:15-17:30, the demand on each
feeder was
Example 1:
F1 F2 F3 F4 F5
F1: 120 kW
F2: 80 kWF3: 100 kW
F4: 110 kW
F5: 90 kW
Total: 500 kW
If this was the maximum total loading for the day at this substation, we
would say that “The maximum coincident demand seen at Sub X for
Monday occurred between 17:15 and 17:30 and was 500 kW, i.e., Monday’s
peak demand at Sub X was 500 kW.”
Maximum non-coincident demand
The sum of maximum demands on the individual groups over a time
interval, without restriction that the maximum demands occur at the same
time. We will use Pncpeak to represent this.
16
8/12/2019 T2 Load Characterstics
http://slidepdf.com/reader/full/t2-load-characterstics 17/19
Example 1:
Consider sub X again.
Feeder 1 sees its daily peak at 16:45-17:00 and it is 150kW.
Feeder 2 sees its daily peak at 18:00-18:15 and it is 150 kW.
Feeder 3 sees its daily peak at 16:30-16:45 and it is 110 kW.
Feeders 4 and 5 all see their daily peak between 17:15 and 17:30 and are
110 kW and 90 kW, respectively.
F1 F2 F3 F4 F5
Summarizing,
F1 peak : 150 kW
F2 peak : 150 kW
F3 peak : 110 kW
F4 peak : 110 kW
F5 peak : 90 kW
Total: 610 kW
The total is 610 kW. So we would say that “The maximum noncoincident
demand seen at Sub X was 610 kW.”
Note: the maximum non-coincident demand is always larger than the
maximum coincident demand, and comparing the two provides an
indication of the extent to which diversification of usage is helping to reduce
the peak for the load group.
Load diversity
Load diversity is the difference between the noncoincident maximum
demand and the coincident maximum demand. In the above example, the
load diversity is 110 kW.
LD = Pncpeak - P peak =610 -
Demand Factor
The demand factor DF k for device or group k is the ratio of the maximum
coincident demand P peak,k to the total connected load for device k .
k
k peak k
L
P DF ,=
The total connected load Lk for device k is the sum of the ratings of all load
components.
17
8/12/2019 T2 Load Characterstics
http://slidepdf.com/reader/full/t2-load-characterstics 18/19
The total connected load Lk is an upper bound for the non-coincident
maximum demand:
- Total connected load depends only on connected equipment.
- Non-coincident maximum demand depends on how equipment is
operated.
Note that 0<DFk <1.0.
So what does a small demand factor mean?
Lots of load but peak is small, therefore load operates
nonsimultaneously.
What does large demand factor mean?
Peak is close to total connected load therefore most of load operates
simultaneously.
Utilization factor
Utilization factor for device k , UF k , is often computed for transformers or
feeders. It is the ratio of the maximum coincident kVA demand on the
component to the rating of the component:
k
k peak
Uk Rating
PF
,=
The utilization factor provides an indication of how well the component is
being utilized.
Example 3:
Consider that a transformer serving five feeders is rated 550kVA and that
the maximum coincident demand on the transformer for the year is 525kW
at a power factor of 0.9. What is the utilization factor?
061.1
550
3.583
550
9.0/525===U F
Components with high utilization factors (close to or greater than 1) may
need to be replaced or reinforced in the near future.
18
8/12/2019 T2 Load Characterstics
http://slidepdf.com/reader/full/t2-load-characterstics 19/19
Diversity factor
The diversity factor for device or group k , F Dk , is the ratio of the maximum
noncoincident demand to the maximum coincident demand:
k peak
k ncpeak
Dk P
P
F ,
,=
If we know the diversity factor, and we know the maximum noncoincident
demand (from each customer’s bill), we may compute the maximum
coincident demand from
Dk
k ncpeak
k peak
F
PP
,
, =
19