SYSTEMS-72.pdf

Embed Size (px)

Citation preview

  • 7/29/2019 SYSTEMS-72.pdf

    1/6

    A Methodology for the Efficient Application of Controlled Switching to

    Current Interruption Cases in High-Voltage Networks

    C. D. TSIREKIS

    Hellenic TransmissionSystem Operator

    Kastoros 72, Piraeus

    GREECE

    [email protected]

    F. D. KANELLOS

    Hellenic TransmissionSystem Operator

    Kastoros 72, Piraeus

    GREECE

    [email protected]

    G. J. TSEKOURAS

    Dept. of Electrical & Computer ScienceHellenic Naval Academy

    Terma Hatzikyriakou, Piraeus

    GREECE

    [email protected]

    Abstract: - Transients produced upon the opening operation of a circuit-breaker may be harmful for the

    network elements and the switching device. A modern countermeasure for the reduction of such

    transients is controlled switching. Fundamental requirement for all controlled switching applications

    is the precise definition of the desired switching times. In this paper a new methodology is proposed

    for the calculation of the optimum switching instants, taking into account circuit-breakers statisticalscatters in the contact operation time and the slope of the contact gap voltage withstand characteristic.

    Key-Words: -Controlled Switching, Switching Transients, ATP-EMTP Simulation, Circuit-Breaker

    1 IntroductionControlled switching is a technique that

    automatically adjusts the circuit-breaker mechanism

    in such a way that switching operation takes place at

    a point-on-wave which minimizes switching

    transients, such as the phase-to-earth overvoltage,

    the inrush current and the transient recovery voltage

    (TRV) across the breaker poles [1, 2, 3].

    One of the most significant requirements for

    proper controlled switching performance is to

    reduce the statistical variations of contact operation

    times, since they may affect the success of this

    method [1, 2, 3, 4]. Circuit-breaker technology has

    improved these statistical scatters, allowing thus

    utilities and manufacturers to achieve contact

    operation times quite close to the preferable ones.

    This means that a precise definition of the desired

    switching times is required, taking into account the

    effects of parameter changes (such as the trappedcharge in a capacitor bank or the impedance of a

    load) and the circuit-breaker characteristics (such as

    the statistical variations of the contacts operating

    times and the contacts gap characteristic of

    dielectric strength) on the optimum switching

    instant.

    In this paper a methodology for the calculation of

    the optimum circuit-breaker opening instants is

    proposed. Specific restrictions, such as contacts gap

    voltage withstand characteristic and variations in

    contacts operating times are considered. With the

    aid of numerical techniques, the optimum switchinginstants can be easily calculated.

    2 Operation Principles2.1 Controlled Switching Arrangement

    In general, a typical controlled switching

    arrangement consists of the following main parts:

    The circuit-breaker, with an independent poleoperation capability.

    Devices for the measurement of the instantvalues of the circuit-breaker currents.

    A controller, which after receiving the switchingcommand, processes the signals from the

    measuring devices, determines the suitable

    reference phase angles and sends the breaking

    commands to each breaker pole, so that the

    breaking occurs at the optimum instant.

    According to this, a typical controlled switching

    layout is shown in the following figure:

    LOAD

    SIDE

    INTERFACE

    SIDE

    SOURCE

    CONTROLLER

    Fig.1: Main parts of a typical controlled switching

    arrangement.

    Recent Researches in System Science

    ISBN: 978-1-61804-023-7 429

  • 7/29/2019 SYSTEMS-72.pdf

    2/6

    2.2 Operation in an Ideal Circuit-BreakerFor the analysis of each part of the operation

    sequence during the controlled opening, the

    definition of the ideal circuit-breaker is introduced.

    Its main characteristics are the following:

    No arc is developed during the openingoperation. Therefore, current breaking occurs

    simultaneously to the mechanical separation of

    the contacts.

    The probability of reignition is zero.

    The sequence of each partial operation during

    controlled opening of an ideal circuit-breaker is

    illustrated in the next figure. In this figure and all

    the next ones, t and T represent time instants

    and time intervals, respectively:

    Current acrosscontacts

    Breakingcommand (User)

    Operatingcommand to poles

    Breaking

    w delay

    breaktt command

    T + Toperat ing

    startt Fig.2: Operation sequence during controlled

    opening of an ideal circuit-breaker

    Toperating corresponds to the time intervalbetween the sending of the opening command from

    the controller (tstart) and the starting of the contacts

    mechanical separation. Since Toperating is very short,

    it can be neglected and considered that current

    breaking occurs instantly and simultaneously to the

    command sending from the controller and the

    contacts mechanical separation (tstart = tbreak).

    Therefore, the corresponding time delay Tdelay for

    each phase is given by the following equation:

    Tdelay = tbreak Tw (1)

    2.3 Application to a Real Circuit-BreakerIn practical applications, contact gap has a finite

    dielectric strength. This affects the controlled

    opening operation. In a real HV circuit-breaker,

    current breaking (instant tbreak in Fig.2) does not

    occur simultaneously to the instant of the contacts

    mechanical separation (instant tseparate). The current

    flow after the instant of tseparate is kept through the

    electric arc developed between the opening contacts

    and is broken at one of the next physical current

    zeros, since at those instants the energy absorbedby the arc, maintaining it, is zero. However, as

    current approaches the physical zero points, the

    arc comes to an instable mode. As a result, current

    becomes zero slightly before a physical zero

    instant (current chopping). Therefore, opening

    switching transients are independent of the phase

    angle corresponding to the instant of contacts

    mechanical separation and controlled opening

    cannot reduce this kind of transients directly.

    Immediately after the arc extinguishing, a

    transient recovery voltage (TRV) is installed across

    the contacts gap. The initial rate of rise of recovery

    voltage (RRRV) may be quite high, especially in

    inductive currents interruption [5]. As a result, it is

    strongly probable for TRV to exceed once or

    multiple times gap dielectric strength, with the

    subsequent occurrence of a number of reignitions.

    Each reignition, is equivalent to a temporary

    reclosing of the circuit, which generally occursunder more adverse conditions than the closing with

    zero initial conditions, due to the accumulated

    energy. In any case, reignitions must be avoided, so

    that more dangerous transients, such as voltage

    escalation, are prevented.

    The key for the prevention of restrikes is the

    relation between the magnitude of TRV and the gap

    dielectric strength. The slope of the latter (Rate of

    Rise of Dielectric Strength - RRDS), which depends

    on the contacts separation velocity and the gap

    dielectric behavior, may be quite smaller than

    RRRV. However, it appears earlier (at the instant ofcontacts mechanical separation), while TRV is

    established at the instant of electric breaking, as it is

    illustrated in the next figure:

    Current's "physical zero"

    Characteristic of gapdielectric strength

    Current Chopping

    Breaking current

    (TRV)recovery voltage

    Transient

    Grid phase voltage

    separatet breaktarcingT

    Fig.3: Successive inductive current interruption. No

    reignition due to a long arcing duration (Tarcing)

    As mentioned previously, electric breaking

    occurs slightly before one of the current zeros after

    contacts mechanical separation. Therefore, a

    maximum arcing duration (Tarcing) is needed for the

    prevention of a reignition. This means that contacts

    mechanical separation should occur immediately

    after a current zero, so that even when electricbreaking occurs near the first current zero, arcing

    Recent Researches in System Science

    ISBN: 978-1-61804-023-7 430

  • 7/29/2019 SYSTEMS-72.pdf

    3/6

    duration Tarcing is quite long (just shorter than a half-

    cycle) and the gap dielectric strength is high enough

    to avoid reignition. All the above are illustrated in

    Fig. 3 and 4, for inductive current interruption

    without and with reignition, respectively:

    Reignit ion

    separatet breaktarcingT

    Characteristic of gapdielectric strength

    Grid phase voltage

    Current's "physical zero"Current Chopping

    Breaking current

    (TRV)recovery voltage

    Transient

    Fig.4: The same inductive current interruption, but

    with reignition, due to the short arcing duration(Tarcing)

    The general result is that the aim of the

    controlled switching application in current breaking

    cases is the avoidance of reignitions. The sequence

    of the various operations is illustrated in Fig.5:

    Current acrosscontacts

    Breaking commandfrom User

    to breaker poles &starting of contacts

    breaktt command t separate

    arcingTT + w delay

    Current breaking

    Operating command

    separation

    Fig.5: Operation sequence during controlled

    opening of a real circuit-breaker

    2.4 Statistical DeviationsA variety of factors, like environment conditions

    (ambient temperature, humidity .), the utilizationfrequency of the circuit-breaker and the whole

    device, the age of the arrangement and the

    corresponding equipment strain and wear, contribute

    to the appearing of statistical deviations in the

    operational characteristics of the controlled

    switching arrangement, such as the following ones:

    The waiting duration w

    The time delay delay

    The time between the sending of the commandfrom the controller to the circuit-breaker and the

    starting of contacts movement The time between the starting of contacts

    movement and their mechanical separation

    The velocity of contacts separation

    The RRDS due to the gaps stochastic nature.

    The third and the fourth time intervals are quite

    short, so that their statistical deviations can be

    neglected. Deviations ofw and delay contribute to a

    total deviation to the instant of starting of contactsmovement. Finally, the last two deviations

    contribute to the slope of dielectric strength

    characteristic. Therefore, the basic statistical

    deviations which should be always considered,

    despite of their source, can be condensed to the

    following two:

    Deviation of the starting instant of contactsmovement (), depending only on the

    performance of the controller.

    Deviation of RRDS, depending only on the

    performance of the circuit-breaker.

    The maximum deviations can be estimated with

    a great probability (up to 99.99%) by the

    manufacturers. In particular, a controller with a

    maximum of 2 ms is easily constructed. The

    same is valid for a maximum of 1 ms, but with

    higher cost, while there is no reference for a

    reduction of below 0.7 ms. On the other side, a

    deviation of RRDS due to contacts velocity does not

    exceed 5%, while the deviation due to the gaps

    stochastic nature is higher (up to 20%).

    The existence of a deviation

    causes abilateral parallel shift to the gap dielectric strength

    characteristic, creating an area of possible instants

    of contacts mechanical separation as wide as 2,

    as shown in Fig.6. This results in the reduction of

    the arcing duration (Tarcing). The deviation of RRDS

    contributes to a further increase of the probability of

    a reignition, as shown in the same figure.

    Breaking current

    (TRV)Recovery Voltage

    Transient

    TT

    Fig.6: Effect of and RRDS deviation to the

    instant of contacts mechanical separation

    3 Calculation MethodsFrom the preceded analysis, it became obviousthat calculation of the optimum switching instants in

    Recent Researches in System Science

    ISBN: 978-1-61804-023-7 431

  • 7/29/2019 SYSTEMS-72.pdf

    4/6

    real networks is quite complicated. In practically all

    cases, the current breaking instant (opening instant)

    does not coincide with the instant of mechanical

    separation of the circuit-breaker contacts (target

    instant). The presence of statistical deviations leads

    to the claim that instead of a simple optimum

    opening instant and the respective target instant, it is

    more realistic to talk about an optimum window

    of target instants. Furthermore, three-phase

    operation of the network leads to the final

    conclusion that we should talk about optimum

    combination of target instants windows.

    From all the above mentioned, it is obvious that a

    systematic calculation of the optimum target instants

    windows combinations, taking into account all

    network parameters, circuit-breaker electrical

    characteristics and various statistical deviations. It is

    also necessary to assess the controlled switchingperformance for the prevention of reignitions. Both

    of these aims are met successfully through the

    application of the algorithms described in the next

    paragraphs.

    3.1 Basic Steps of the AlgorithmThe first step of the algorithm run is the precise

    calculation of the waveforms of breaking currents

    and TRVs, as they are derived after successful

    (without reignition) breaking of the currents in the

    preceded phases. It should be noted, that except thewaveform of the breaking current of the first phase,

    the waveforms of the rest phases depend in general

    on the instants of electric breaking in the preceded

    phases. However, if the peak value of the breaking

    current is well higher than the chopping level, the

    electric breaking in each phase occurs exactly at the

    chopping instant and consequently, it is independent

    of the instant of contacts mechanical separation.

    Therefore, for each combination of values of

    chopping level and the electric parameters of the

    grid, the waveforms of the current and TRV in each

    phase are precisely defined and independent of theinstant of contacts mechanical separation in this

    case. This is not valid if chopping level is at least of

    the same order of magnitude with the peak value of

    the breaking current, since electric breaking may

    occur even simultaneously to the instant of contacts

    mechanical separation. As a consequence, in this

    case the waveforms of the breaking current of the

    two last breaking phases, as well as of all TRV, are

    functions of the instants of contacts mechanical

    separation in the preceded phases.

    In the next stage, the user defines the variation

    step of the possible instants of contacts mechanical

    separation (tstep), which is set equal for the three

    phases for minimization of the number of

    parameters, as well as the total number of steps. In

    addition, the user defines the vectors of the possible

    values of RRDS, of the deviation of the velocity of

    contacts separation () and of the deviation of the

    slope of gap dielectric strength characteristic due to

    its stochastic nature (s). Finally, the user defines

    the shape of the gap dielectric strength characteristic

    through appropriate polynomial factors. Considering

    that the left end of the optimum instants window of

    contacts mechanical separation is the first discrete

    instant after current zero (equal to the sum of

    current zero instant and tstep), the calculation of the

    optimum instants window is based on the right limit

    of the gap dielectric strength characteristic (see Fig.

    6). Therefore, for the slope of this characteristic the

    deviation given are those which provided for the

    right limit of the instants window of the contactsmechanical separation, since this is the most adverse

    one. For instance, if the dielectric strength

    characteristic is straight, its formula is:

    )tt()s1(RRDS)t,t(V separateseparateright = (2)

    In the above formula, tseparate is the step-varied

    instant of contacts mechanical separation.

    Starting from current zero instant in the first

    phase (to), the instant of contacts mechanical

    separation increase gradually by tstep, until gap

    dielectric strength characteristic intersects therectified TRV waveform. Assuming that this takes

    place for an instant of contacts mechanical

    separation tseparate = tlast. The optimum instants

    window for contacts mechanical separation for the

    first phase is then [to, tlast - tstep] and the mean value

    of this window combined with maximum T is used

    for its designation. Considering that deviation is

    bilateral, the absolute value of the maximum , so

    that the reignition is avoided, is derived from the

    following equation:

    2tttT osteplast = (3)

    In case that chopping level is of the same order

    of magnitude with the breaking current peak value,

    the process in this stage is modified, so that the left

    end of the optimum instants window of contacts

    mechanical separation does not necessarily coincide

    to current zero. The optimum instants window starts

    from the first instant of contacts mechanical

    separation which does not lead to reignition.

    The same process is repeated for the rest phases.

    Finally, the minimum value among the maximumallowed derived for the three phases is chosen as

    Recent Researches in System Science

    ISBN: 978-1-61804-023-7 432

  • 7/29/2019 SYSTEMS-72.pdf

    5/6

    the maximum allowed for the whole system. The

    combination of the optimum instants windows of

    contacts mechanical separation, as well as the

    maximum allowed DT, depend on the combination

    of the values of the grid parameters, the chopping

    level (only when it is well lower than current peak

    value), the circuit-breaker dielectric characteristics

    and the corresponding deviations.

    Any common programming package (Matlab,

    Mathcad, C, Fortran etc.) can be used for the

    application of this algorithm.

    3.2 Calculation MethodsAs mentioned in the previous sections, for the

    application of the algorithm of the optimum instants

    of contacts mechanical separation, the calculation of

    the breaking current in each phase is required. Thiscalculation can be performed via either analytical or

    numerical methods. Analytical methods comprise

    the solution of systems of differential equations

    describing the transient behaviour of the network.

    The Current Injection Method is such a method,

    which is proposed for the application of the

    algorithm. On the other side, the most conventional

    method for the numerical solution of the network

    during transient conditions is the use of programs

    like ATP/EMTP [6, 7]. The application of both

    methods is described in the next paragraphs.

    3.2.1 Current Injection Method

    The widely known Current Injection Method is

    used for the network solution in current breaking

    cases, assuming a linear network [4, 8]. According

    to this technique, the calculation of the transients is

    based on the fact that the current elimination at the

    instant of its breaking (tbreak) is equivalent to the

    injection of the same magnitude and opposite

    polarity to the breaking current, as shown in Fig.7.

    Therefore, the transient voltages and currents in all

    network places are derived from the superimposition

    of their instant values which they would havewithout the breaking and the respective values

    obtained after the aforementioned current injection

    at the instant tbreak. The application of the method

    can be summarized in the following steps:

    1. Calculation of the steady-state voltages andcurrents in various network places before the

    breaking of the first phase.

    2. Development of an equivalent network after thereplacement of voltage and current sources with

    open- and short-circuits, respectively. The

    breaker pole to open is replaced with a current

    source, connected at the instant tbreak, with the

    same magnitude and opposite polarity to the

    breaking current.

    3. Calculation of voltages and currents in theequivalent network after the instant tbreak.

    4. Results of step 3 are superimposed to those ofstep 1, for the total expressions of the voltages

    and currents after the breaking of the first phase.

    5. The process is repeated for the breaking of therest phases, using the voltages and currents after

    step 4 after the breaking of the preceded phase

    instead of the respective steady-state quantities.

    Breakingcurrent

    Injectedcurrent

    Superimposition ofthe two currents

    breakt

    Result(actual current)

    Fig.7: Current injection method

    The advantage of Current Injection Method

    against the direct network solution is that there is no

    need for the (often hard) calculation of the initial

    conditions, since their effect is taken into account

    through the superimposition. However, its results

    are valid only for networks consisting exclusively of

    linear elements. Another disadvantage is that the

    calculation of the transients are usually quite

    complicated, due to a plenty of reasons, like the

    unsymmetrical three-phase networks in the

    intermediate steps (different breaking instant in each

    phase), the inductive and/or capacitive coupling

    between the three phases, as well as the existence of

    elements with distributed parameters or complicated

    models (lines, cables, transformers). For these

    reasons, the application of the Current InjectionMethod is just used for the comprehensive approach

    of the relative switching phenomena and the

    assessment of the performance of controlled

    switching application to a specific current breaking

    case. In any case, the use of numerical methods is

    necessary for a more precise assessment.

    3.2.2 Use of ATP/EMTP Program

    For the numerical solution of the network in

    transient conditions, the widely known ATP/

    program is used. The model of Statistical Switch

    included in this program is the most suitable circuit-breaker model for controlled switching simulations.

    Recent Researches in System Science

    ISBN: 978-1-61804-023-7 433

  • 7/29/2019 SYSTEMS-72.pdf

    6/6

    The use of this model causes automatically the

    repeated run of the simulation for different

    combinations of instants of contacts mechanical

    separation in each phase, following a uniform

    probability distribution with user-defined mean time

    and standard deviation (see Fig.8), since the interest

    is focused on the most adverse transients and not on

    the probability of their occurrence.

    Fig.8: Probability distribution of opening time Tf(T): Density function, T : Mean time,

    : Standard deviation

    For instance, in the usual case of the desired

    instants window of contacts mechanical separation

    corresponds to a 50 Hz half-cycle (10ms), it is

    derived that = 2.887 ms.

    According to the general principle followed by

    ATP/, electric breaking is achieved at the first

    instant after contacts mechanical separation at which

    current criterion is met. As current criterion is

    defined the condition, at which the absolute instantvalue of breaking current is lower than a user-defined

    current margin, according to the following figure. It

    is obvious, that the above current margin represents

    the chopping level.

    Fig.9: Illustration of application of current

    criterion in an EMTP switch during current

    breaking

    In the majority of the current breaking cases, a

    number of automatic re-runs between 100000 and

    150000 is enough for the precise assessment of the

    optimum instants windows of contacts mechanical

    separation.

    The use of any similar numerical software, such

    as ATP/EMTP, aims to the precise evaluation of the

    performance of controlled switching application, but

    it does not ensure the thorough investigation of the

    problem. For this reason, it would be better that

    such software is used in a second stage, after the

    application of an analytical method, such as

    Current Injection Method to a simplified network

    model, which is more suitable for the identification

    of the possible issues.

    4 ConclusionsIn this paper, a new methodology has been

    proposed, for the calculation of the optimum

    switching instants for current interruption cases. The

    methodology is based on the Current Injection

    Method that eliminates the need for exhaustive

    simulations for an initial assessment of the

    performance of a possible controlled switching

    application. Circuit-breakers characteristics, like

    contact operation time scatter and deviation of theslope of the contact gap voltage withstand

    characteristic are taken into account in this method.

    References:

    [1] CIGRE WG13.07, Controlled Switching ofHVAC Circuit-Breakers - Planning,

    Specification and Testing of Controlled

    Switching Systems,Electra No 197, pp. 23-33,

    August 2001.

    [2] CIGRE WG13.07, Controlled Switching of

    HVAC Circuit-Breakers - Guide forApplication Lines, Reactors, Capacitors,

    Transformers, 1st

    Part: Electra No 183, April

    1999 - 2nd

    Part:Electra No 185, August 1999.

    [3] CIGRE Task Force 13.00.1, ControlledSwitching: A State-of-the-Art Survey, 1

    stPart:

    Electra No 163, December 1995 - 2nd

    Part:

    Electra No 164, February 1996.

    [4] C.D. Tsirekis, N.D. Hatziargyriou, B.C.Papadias, Controlled Switching Based on the

    Injection Method, International Conference on

    Power Systems Transients (IPST 97), Vol. II,

    pp. 405-410, Rio de Janeiro, Brazil, June 2001.

    [5] CIGRE WG13.02, Interruption of SmallInductive Currents - Chapter 3, Part A, Electra

    No 75, March 1981.

    [6] Leuven EMTP Center, ATP Rule Book, June1993, Leuven (Belgium).

    [7] Bonneville Power Administration, EMTPTheory Book, Oregon (Portland), 1986.

    [8] W.M.C. Van Den Heuvel, B.C. Papadias,Interaction Between Phases in Three-Phase

    Reactor Switching, 1st

    Part:Electra No 91, pp.

    11-50, Dec. 1983 - 2

    nd

    Part: Electra No 112,pp. 57-81, May 1987.

    iSWITCH

    t

    Switch opens

    Current forced to zero in next step

    Current margin

    Current margin

    Current

    3

    f(T)

    32

    1

    + 3

    Recent Researches in System Science

    ISBN: 978-1-61804-023-7 434