SystemResponse Resonance

Embed Size (px)

Citation preview

  • 7/24/2019 SystemResponse Resonance

    1/23

    0

    System Response Characteristics

    AC Resonance

  • 7/24/2019 SystemResponse Resonance

    2/23

    1

    System Response Characteristics

    There are three primary variables affecting thesystem response characteristics,

    the system impedance,

    the presence of a capacitor bank,

    the amount of resistive loads in the system.

  • 7/24/2019 SystemResponse Resonance

    3/23

    2

    System Impedance

    Where:

    Zsc = short-circuit impedance

    Rsc = short-circuit resistanceXsc = short-circuit reactance

    kV = Line-Line voltage, kVMVAsc

    = 3-Phase short-circuit MVA, MVA

    Isc

    = short-circuit current, A

    scsc

    scscscI

    kV

    MVA

    kVjXRZ

    3

    10002

  • 7/24/2019 SystemResponse Resonance

    4/23

    3

    System Impedance

    ZSC

    is a complex quantity, consisting of both resistance andreactance. For industrial power systems and most utility

    systems, the impedance is assumed purely reactive.

    The inductive reactance portion of the impedance changeswith frequency. The reactance at the hth

    harmonic is

    determined from the fundamental impedance reactanceX1by:Xh=hX1

    .

    Generally, in most power systems, the resistance does not

    change significantly when studying the effects of harmonics

    less than the ninth.

  • 7/24/2019 SystemResponse Resonance

    5/23

    4

    System Impedance

    At utilization voltages, such as industrial power systems, theequivalent system reactance is often dominated by the servicetransformer impedance. A good approximation forXSC

    may bebased on the impedance of the service entrance transformer only:

    Xsc= XTX

    Transformer impedance in ohms can be determined from thepercent impedanceZtx

    found on the nameplate by:

    where MVA3ph

    is the kVA

    rating of the transformer. This assumes

    that the impedance is predominantly reactive. For example for a1500-kVA, 6 % transformer, the equivalent impedance on the480-V side is

    100/; (%))()(

    3

    2

    )( TXpuTXpuTX

    ph

    TX XXXMVA

    kVX

    0092.006.0

    5.1

    48.02

    )(

    3

    2

    )( puTX

    ph

    TX X

    MVA

    kVX

  • 7/24/2019 SystemResponse Resonance

    6/23

    5

    Capacitor Impedance

    Shunt capacitors, either at the customer location for power factorcorrection or on the distribution system for voltage control,

    dramatically alter the system impedance variation with

    frequency.

    Capacitors do not create harmonics, but severe harmonic

    distortion can sometimes be attributed to their presence.

    While the reactance of inductive components increases

    proportionately to frequency, capacitive reactance XC

    decreases

    proportionately:

    Power capacitors are rated in terms of kvar

    or Mvar

    at a given

    voltage. The equivalent line-to-neutral capacitive reactance at

    fundamental frequency for a capacitor bank can be determined

    by:

    fCCXC

    2

    11

    MVAR

    kVXC

    2

  • 7/24/2019 SystemResponse Resonance

    7/23

    System Response Characteristics

    Harmonic ResonanceNatural Resonant Frequencyfo = 1/2 LC

    fh = fo Resonance

    Voltage and Current will be dominated by the resonantfrequency and can be highly distorted.

    The true impact of the nonlinear load on harmonic voltage

    distortion can be determined from the response of the powersystem at each harmonic.

    Power System Harmonic Resonance

    Series ResonanceParallel Resonance

  • 7/24/2019 SystemResponse Resonance

    8/23

    7

    Parallel Resonance

    Parallel Resonance

    Parallel combination of power system inductance andpower factor correction capacitor at the nonlinear load

    The highest voltage distortion is at the nonlinear load

  • 7/24/2019 SystemResponse Resonance

    9/23

    8

    Parallel Resonance

    At the resonant frequency, the apparent impedance of the

    parallel combination of the equivalent inductance XL and

    and

    capacitance XC and as seen from the harmonic current source

    becomes very large, i.e.,

    LCL

    p

    LpCpLC

    CL

    LCCLCp

    XR

    R

    X

    R

    XQ

    XQXQR

    XX

    hXhXjR

    XXhXjRjhXRhXjZ

    ;

    )()//(

  • 7/24/2019 SystemResponse Resonance

    10/23

    9

    Parallel Resonance

    Qp: is the quality factor of a resonantcircuit that determines the sharpness of

    the frequency response.

    During parallel resonance, a small

    harmonic currentIh can cause a large

    voltage drop across the apparent

    impedance, Vp=QpIhXL=QpIhXC and

    IC=QpIh=IL

    The voltage near the capacitor bank will

    be magnified and heavily distorted.

    Currents flowing in the capacitor bank

    and through the transformer will also be

    magnified Q times. This phenomenon

    will likely cause capacitor failure, fuse

    blowing, or transformer overheating.,

  • 7/24/2019 SystemResponse Resonance

    11/23

    10

    Parallel Resonance

    Power systems analysts typically do not haveL and C readilyavailable and prefer to use other forms of this relationship.

    They commonly compute the resonant harmonic hrbased on

    fundamental frequency impedances and ratings using one of thefollowing:

    wherehr: resonant harmonic order

    XC: Capacitor reactance

    Xsc: System short-circuit reactance

    MVAsc: System short-circuit MVA

    MVARcap(kVARcap) : MVAR (kVAR) rating of capacitor bank

    kVATX: kVA

    rating of step-down transformer

    ZTX: step-down transformer impedance

    (%)

    100

    TXcap

    TX

    cap

    sc

    L

    Cr

    ZkVAR

    kVA

    MVAR

    MVA

    X

    Xh

  • 7/24/2019 SystemResponse Resonance

    12/23

    11

    An industrial load bus where the transformer impedance is

    dominant, the resonant harmonic for a 1500-kVA, 6 %transformer and a 500-kvar capacitor bank is approximately

    Parallel Resonance

    ExampleExample

    harmonic

    ZkVAR

    kVAh

    th

    TXcap

    TXr

    707.7

    6500

    1001500100

    (%)

  • 7/24/2019 SystemResponse Resonance

    13/23

    12

    Parallel Resonance

    Effect of Capacitor Size on the Impedance seen by the

    Harmonic Source

  • 7/24/2019 SystemResponse Resonance

    14/23

    13

    Series Resonance

    There are certain instances when a shunt capacitor and theinductance of a transformer or distribution line may appear as

    a seriesLC circuit to a source of harmonic currents.

    If the resonant frequencyfr corresponds to a characteristicharmonic frequencyhf1 of the nonlinear load, theLC circuit

    will attract a large portion of the harmonic current that is

    generated in the distribution system.

    A customer having no nonlinear load, but utilizing power

    factor correction capacitors, may in this way experience high

    harmonic voltage distortion due to neighboring harmonic

    sources.

  • 7/24/2019 SystemResponse Resonance

    15/23

    14

    Series Resonance

    Series ResonanceThe system inductance and capacitors are in series with

    respect to the nonlinear load

    The highest voltage distortion is at a remote point or on an

    adjacent feeder served by the same substation transformer.

  • 7/24/2019 SystemResponse Resonance

    16/23

    15

    Series Resonance

    During resonance, the power factor correction capacitor forms aseries circuit with the transformer and harmonic sources. The

    harmonic source represents the harmonics produced by a nonlinear

    load. The series combination of the transformer inductance and the

    capacitor bank is very small (theoretically zero) and only limited by

    its resistance.

    Thus the harmonic current corresponding to the resonant frequency

    will flow freely in this circuit. The voltage at the power factorcorrection capacitor is magnified and highly distorted. This is

    apparent from the following equation

    hXhXXRX

    RhX

    RhXQ

    VQV

    VR

    hXVhXhXjR

    hXjV

    cLrrLc

    s

    hsc

    hc

    h

    cL

    cc

    ;

    )(

  • 7/24/2019 SystemResponse Resonance

    17/23

    16

    Series Resonance

    where Vh and Vc are the harmonic voltage corresponding to theharmonic currentIh, and the voltage at the power factor

    capacitor bank, respectively. The resistanceR of the series

    resonant circuit is small compared to the reactance.

    The negligible impedance of the series resonant circuit can be

    exploited to absorb desired harmonic currents. This is indeedthe principle in designing a notch filter.

  • 7/24/2019 SystemResponse Resonance

    18/23

    17

    Series Resonance

    In many systems with potential series resonance problemsparallel resonance also arises due to the circuit topology.

    One of these is shown, where the parallel resonance is formed

    by the parallel combination betweenXsource

    and a seriesbetweenXT andXC. The resulting parallel resonant frequency

    is always smaller than its series resonant frequency due to the

    source inductance contribution.

    The parallel resonant frequency can be represented by the

    following equation:

    sourceTX

    Cr

    XX

    Xh

  • 7/24/2019 SystemResponse Resonance

    19/23

    18

    Series Resonance

    Frequency response of a circuit with series resonance

  • 7/24/2019 SystemResponse Resonance

    20/23

    19

    Frequency Impedance Scan

    Peaks Parallel Resonance

    Valleys Series Resonance

  • 7/24/2019 SystemResponse Resonance

    21/23

    20

    Effect of Resistance & Resistive Load

    The damping provided by resistance in the system is oftensufficient to prevent catastrophic voltages and currents.

    Variation of the parallel resonant circuit impedancecharacteristic for various amounts of resistive load in parallel

    with the capacitance is shown below. As little as 10 percentresistive loading can have a significant beneficial impact onpeak impedance.

    Effect of resistive loads on parallel resonance

  • 7/24/2019 SystemResponse Resonance

    22/23

    21

    Effect of Resistance & Resistive Load

    Likewise, if there is a significant length of lines or cablesbetween the capacitor bus and the nearest upline

    transformer, the

    resonance will be suppressed.

    Lines and cables can add a significant amount of the resistance to

    the equivalent circuit.

    Loads and line resistances are the reasons why catastrophic

    harmonic problems from capacitors on utility distribution feeders

    are seldom seen.

    The most troublesome resonant conditions occur when capacitorsare installed on substation buses, either utility substations or

    in

    industrial facilities.

  • 7/24/2019 SystemResponse Resonance

    23/23

    22

    Effect of Resistance & Resistive Load

    In these cases, where the transformer dominates the system impedance

    and has a highX/R ratio, the relative resistance is low and the

    corresponding parallel resonant impedance peak is very sharp and

    high.

    This is a common cause of capacitor, transformer, or load equipment

    failure.

    While utility distribution engineers may be able to place feeder

    banks

    with little concern about resonance, studies should always be performed

    for industrial capacitor applications and for utility substation

    applications.

    Utility engineers familiar with the problems indicate that about

    20

    percent of industrial installations for which no studies are performed

    have major operating disruptions or equipment failure due to resonance.

    In fact, selecting capacitor sizes from manufacturers

    tables to correct the

    power factor based on average monthly billing data tends to result in a

    combination that tunes the system near the fifth harmonic. This is one of

    the worst harmonics to which to be tuned because it is frequently thelargest component in the system.