Upload
eyad-a-feilat
View
233
Download
0
Embed Size (px)
Citation preview
7/24/2019 SystemResponse Resonance
1/23
0
System Response Characteristics
AC Resonance
7/24/2019 SystemResponse Resonance
2/23
1
System Response Characteristics
There are three primary variables affecting thesystem response characteristics,
the system impedance,
the presence of a capacitor bank,
the amount of resistive loads in the system.
7/24/2019 SystemResponse Resonance
3/23
2
System Impedance
Where:
Zsc = short-circuit impedance
Rsc = short-circuit resistanceXsc = short-circuit reactance
kV = Line-Line voltage, kVMVAsc
= 3-Phase short-circuit MVA, MVA
Isc
= short-circuit current, A
scsc
scscscI
kV
MVA
kVjXRZ
3
10002
7/24/2019 SystemResponse Resonance
4/23
3
System Impedance
ZSC
is a complex quantity, consisting of both resistance andreactance. For industrial power systems and most utility
systems, the impedance is assumed purely reactive.
The inductive reactance portion of the impedance changeswith frequency. The reactance at the hth
harmonic is
determined from the fundamental impedance reactanceX1by:Xh=hX1
.
Generally, in most power systems, the resistance does not
change significantly when studying the effects of harmonics
less than the ninth.
7/24/2019 SystemResponse Resonance
5/23
4
System Impedance
At utilization voltages, such as industrial power systems, theequivalent system reactance is often dominated by the servicetransformer impedance. A good approximation forXSC
may bebased on the impedance of the service entrance transformer only:
Xsc= XTX
Transformer impedance in ohms can be determined from thepercent impedanceZtx
found on the nameplate by:
where MVA3ph
is the kVA
rating of the transformer. This assumes
that the impedance is predominantly reactive. For example for a1500-kVA, 6 % transformer, the equivalent impedance on the480-V side is
100/; (%))()(
3
2
)( TXpuTXpuTX
ph
TX XXXMVA
kVX
0092.006.0
5.1
48.02
)(
3
2
)( puTX
ph
TX X
MVA
kVX
7/24/2019 SystemResponse Resonance
6/23
5
Capacitor Impedance
Shunt capacitors, either at the customer location for power factorcorrection or on the distribution system for voltage control,
dramatically alter the system impedance variation with
frequency.
Capacitors do not create harmonics, but severe harmonic
distortion can sometimes be attributed to their presence.
While the reactance of inductive components increases
proportionately to frequency, capacitive reactance XC
decreases
proportionately:
Power capacitors are rated in terms of kvar
or Mvar
at a given
voltage. The equivalent line-to-neutral capacitive reactance at
fundamental frequency for a capacitor bank can be determined
by:
fCCXC
2
11
MVAR
kVXC
2
7/24/2019 SystemResponse Resonance
7/23
System Response Characteristics
Harmonic ResonanceNatural Resonant Frequencyfo = 1/2 LC
fh = fo Resonance
Voltage and Current will be dominated by the resonantfrequency and can be highly distorted.
The true impact of the nonlinear load on harmonic voltage
distortion can be determined from the response of the powersystem at each harmonic.
Power System Harmonic Resonance
Series ResonanceParallel Resonance
7/24/2019 SystemResponse Resonance
8/23
7
Parallel Resonance
Parallel Resonance
Parallel combination of power system inductance andpower factor correction capacitor at the nonlinear load
The highest voltage distortion is at the nonlinear load
7/24/2019 SystemResponse Resonance
9/23
8
Parallel Resonance
At the resonant frequency, the apparent impedance of the
parallel combination of the equivalent inductance XL and
and
capacitance XC and as seen from the harmonic current source
becomes very large, i.e.,
LCL
p
LpCpLC
CL
LCCLCp
XR
R
X
R
XQ
XQXQR
XX
hXhXjR
XXhXjRjhXRhXjZ
;
)()//(
7/24/2019 SystemResponse Resonance
10/23
9
Parallel Resonance
Qp: is the quality factor of a resonantcircuit that determines the sharpness of
the frequency response.
During parallel resonance, a small
harmonic currentIh can cause a large
voltage drop across the apparent
impedance, Vp=QpIhXL=QpIhXC and
IC=QpIh=IL
The voltage near the capacitor bank will
be magnified and heavily distorted.
Currents flowing in the capacitor bank
and through the transformer will also be
magnified Q times. This phenomenon
will likely cause capacitor failure, fuse
blowing, or transformer overheating.,
7/24/2019 SystemResponse Resonance
11/23
10
Parallel Resonance
Power systems analysts typically do not haveL and C readilyavailable and prefer to use other forms of this relationship.
They commonly compute the resonant harmonic hrbased on
fundamental frequency impedances and ratings using one of thefollowing:
wherehr: resonant harmonic order
XC: Capacitor reactance
Xsc: System short-circuit reactance
MVAsc: System short-circuit MVA
MVARcap(kVARcap) : MVAR (kVAR) rating of capacitor bank
kVATX: kVA
rating of step-down transformer
ZTX: step-down transformer impedance
(%)
100
TXcap
TX
cap
sc
L
Cr
ZkVAR
kVA
MVAR
MVA
X
Xh
7/24/2019 SystemResponse Resonance
12/23
11
An industrial load bus where the transformer impedance is
dominant, the resonant harmonic for a 1500-kVA, 6 %transformer and a 500-kvar capacitor bank is approximately
Parallel Resonance
ExampleExample
harmonic
ZkVAR
kVAh
th
TXcap
TXr
707.7
6500
1001500100
(%)
7/24/2019 SystemResponse Resonance
13/23
12
Parallel Resonance
Effect of Capacitor Size on the Impedance seen by the
Harmonic Source
7/24/2019 SystemResponse Resonance
14/23
13
Series Resonance
There are certain instances when a shunt capacitor and theinductance of a transformer or distribution line may appear as
a seriesLC circuit to a source of harmonic currents.
If the resonant frequencyfr corresponds to a characteristicharmonic frequencyhf1 of the nonlinear load, theLC circuit
will attract a large portion of the harmonic current that is
generated in the distribution system.
A customer having no nonlinear load, but utilizing power
factor correction capacitors, may in this way experience high
harmonic voltage distortion due to neighboring harmonic
sources.
7/24/2019 SystemResponse Resonance
15/23
14
Series Resonance
Series ResonanceThe system inductance and capacitors are in series with
respect to the nonlinear load
The highest voltage distortion is at a remote point or on an
adjacent feeder served by the same substation transformer.
7/24/2019 SystemResponse Resonance
16/23
15
Series Resonance
During resonance, the power factor correction capacitor forms aseries circuit with the transformer and harmonic sources. The
harmonic source represents the harmonics produced by a nonlinear
load. The series combination of the transformer inductance and the
capacitor bank is very small (theoretically zero) and only limited by
its resistance.
Thus the harmonic current corresponding to the resonant frequency
will flow freely in this circuit. The voltage at the power factorcorrection capacitor is magnified and highly distorted. This is
apparent from the following equation
hXhXXRX
RhX
RhXQ
VQV
VR
hXVhXhXjR
hXjV
cLrrLc
s
hsc
hc
h
cL
cc
;
)(
7/24/2019 SystemResponse Resonance
17/23
16
Series Resonance
where Vh and Vc are the harmonic voltage corresponding to theharmonic currentIh, and the voltage at the power factor
capacitor bank, respectively. The resistanceR of the series
resonant circuit is small compared to the reactance.
The negligible impedance of the series resonant circuit can be
exploited to absorb desired harmonic currents. This is indeedthe principle in designing a notch filter.
7/24/2019 SystemResponse Resonance
18/23
17
Series Resonance
In many systems with potential series resonance problemsparallel resonance also arises due to the circuit topology.
One of these is shown, where the parallel resonance is formed
by the parallel combination betweenXsource
and a seriesbetweenXT andXC. The resulting parallel resonant frequency
is always smaller than its series resonant frequency due to the
source inductance contribution.
The parallel resonant frequency can be represented by the
following equation:
sourceTX
Cr
XX
Xh
7/24/2019 SystemResponse Resonance
19/23
18
Series Resonance
Frequency response of a circuit with series resonance
7/24/2019 SystemResponse Resonance
20/23
19
Frequency Impedance Scan
Peaks Parallel Resonance
Valleys Series Resonance
7/24/2019 SystemResponse Resonance
21/23
20
Effect of Resistance & Resistive Load
The damping provided by resistance in the system is oftensufficient to prevent catastrophic voltages and currents.
Variation of the parallel resonant circuit impedancecharacteristic for various amounts of resistive load in parallel
with the capacitance is shown below. As little as 10 percentresistive loading can have a significant beneficial impact onpeak impedance.
Effect of resistive loads on parallel resonance
7/24/2019 SystemResponse Resonance
22/23
21
Effect of Resistance & Resistive Load
Likewise, if there is a significant length of lines or cablesbetween the capacitor bus and the nearest upline
transformer, the
resonance will be suppressed.
Lines and cables can add a significant amount of the resistance to
the equivalent circuit.
Loads and line resistances are the reasons why catastrophic
harmonic problems from capacitors on utility distribution feeders
are seldom seen.
The most troublesome resonant conditions occur when capacitorsare installed on substation buses, either utility substations or
in
industrial facilities.
7/24/2019 SystemResponse Resonance
23/23
22
Effect of Resistance & Resistive Load
In these cases, where the transformer dominates the system impedance
and has a highX/R ratio, the relative resistance is low and the
corresponding parallel resonant impedance peak is very sharp and
high.
This is a common cause of capacitor, transformer, or load equipment
failure.
While utility distribution engineers may be able to place feeder
banks
with little concern about resonance, studies should always be performed
for industrial capacitor applications and for utility substation
applications.
Utility engineers familiar with the problems indicate that about
20
percent of industrial installations for which no studies are performed
have major operating disruptions or equipment failure due to resonance.
In fact, selecting capacitor sizes from manufacturers
tables to correct the
power factor based on average monthly billing data tends to result in a
combination that tunes the system near the fifth harmonic. This is one of
the worst harmonics to which to be tuned because it is frequently thelargest component in the system.