Jay Giri Manu Parashar Douglas Wilson IEEE General Meeting Smart Grid Panel Edwin Liu Chair July 28 th , 2011 Synchrophasor PMU data analysis for enhanced control center operations Copyright ALSTOM Grid

Synchrophasor PMU data analysis for enhanced … is SynchroPhasor Technology? − Next generation measurement technology. (voltages, currents, frequency, frequency rate-of-change,

  • Upload
    lethu

  • View
    236

  • Download
    5

Embed Size (px)

Citation preview

Page 1: Synchrophasor PMU data analysis for enhanced … is SynchroPhasor Technology? − Next generation measurement technology. (voltages, currents, frequency, frequency rate-of-change,

Jay Giri

Manu Parashar

Douglas Wilson

IEEE General Meeting

Smart Grid Panel

Edwin Liu – Chair

July 28th, 2011

Synchrophasor PMU data analysis

for enhanced control center operations

Copyright ALSTOM Grid

Page 2: Synchrophasor PMU data analysis for enhanced … is SynchroPhasor Technology? − Next generation measurement technology. (voltages, currents, frequency, frequency rate-of-change,

V4

V1

Synchrophasor Measurement

Full per-cycle detail

GPS

Timestamp

Phase

V4, V1

Magnitude

1 2 3 4

Synchrophasors: Key Features

Synchronised V, I & Frq measurements

50/60Hz data captures dynamics

3-phase measurements

Real-time streaming

Time

Phasor format

Angle Difference increases with

• Power flow

• Impedance (weakened network)

Page 3: Synchrophasor PMU data analysis for enhanced … is SynchroPhasor Technology? − Next generation measurement technology. (voltages, currents, frequency, frequency rate-of-change,

What is SynchroPhasor Technology?

− Next generation measurement technology.(voltages, currents, frequency, frequency rate-of-change, etc)

− Higher resolution scans (e.g. 30 samples/second).─ Improved visibility into dynamic

grid conditions.

─ Early warning detection alerts.

− Precise GPS time stamping.─ Wide-area Situational Awareness.─ Faster Post-Event Analysis.

“MRI quality (3-D color) visibility of power system, compared to X-ray (2-D b/w) quality

visibility of SCADA” – Terry Boston (PJM) »PMU Resolution

»SCADA Resolution

Phasor Measurement Units (PMUs)

Page 4: Synchrophasor PMU data analysis for enhanced … is SynchroPhasor Technology? − Next generation measurement technology. (voltages, currents, frequency, frequency rate-of-change,

The changing landscape

Synchrophasor measurement devices are being deployed aggressively in the US and globally

− By 2012, will be a five-fold increase in PMUs across US –over 1000 PMUs deployed

− Each PMU provides 10-12 separate sub-second measurements

− Measurements include voltages, currents and frequencies − Augments traditional 2-4 second SCADA

Facilitates wide-area monitoring systems (WAMS) and future wide area control (WAC) - self-healing grid

This is the next SCADA frontier –“fast, sub-second measurements and fast, automated controls”

Copyright ALSTOM Grid

Page 5: Synchrophasor PMU data analysis for enhanced … is SynchroPhasor Technology? − Next generation measurement technology. (voltages, currents, frequency, frequency rate-of-change,

NASPInet – Future Vision for North American SynchroPhasor Network

GOAL: Develop an “industry grade” secure, standardized & distributed data communications infrastructure to support SynchroPhasor applications in North America.

Source: NASPI Website (www.naspi.org)

By 2015,

Almost all utilities, TOs & ISOs will have access to

1000+ real-time PMU data

from across the North America

Page 6: Synchrophasor PMU data analysis for enhanced … is SynchroPhasor Technology? − Next generation measurement technology. (voltages, currents, frequency, frequency rate-of-change,

Phasor Measurements…

Changing Grid Measurements to: higher resolution, more accurate readings.

Benefits:

• More accurate Control Center understanding of the Grid’s state• Faster operator alerts and improved visibility of fast, dynamic

grid conditions • Maximize utilization of congested corridors by operating closer

to 'true' operational limits• Prompt identification of un-damped grid oscillations to prevent

outages• Quick identification of grid disturbance location(s) increasing

speed of response• Quicker post-event re-creation of actual disturbance scenarios

6

Page 7: Synchrophasor PMU data analysis for enhanced … is SynchroPhasor Technology? − Next generation measurement technology. (voltages, currents, frequency, frequency rate-of-change,

Synchrophasor Impact on Grid Operations

“An Unprecedented Transformational Change

to help operate the grid

More efficiently, reliably and

to facilitate integration of Green energy resources”

Copyright ALSTOM Grid

Page 8: Synchrophasor PMU data analysis for enhanced … is SynchroPhasor Technology? − Next generation measurement technology. (voltages, currents, frequency, frequency rate-of-change,

Holistic Generalized Grid Security Analysis

Control Center -PDC

PMU

MEASUREMENT-BASED

Analysis

(PhasorPoint)

Traditional

MODEL-BASED

Analysis

(EMS)

SCADA

& AlarmsWAMS

State

Estimator

State

Measurement

Other EMS

Applications

New

Applications

Small Signal

Stability

Oscillation

Monitoring

Transient

& Voltage

Stability

Stability

Monitoring

& Control

Copyright ALSTOM Grid

Page 9: Synchrophasor PMU data analysis for enhanced … is SynchroPhasor Technology? − Next generation measurement technology. (voltages, currents, frequency, frequency rate-of-change,

Wide Area Situational Awareness - WASA

Grid Security Monitor

Wide Area Security

Situation AwarenessWide Area Visualization

Steady State

Security

DynamicSecurity

UI Navigation

WAMSAlerts

UI Navigation

PMU angles &

Oscillation

Monitoring

EMS RT

Network

Analysis

Small signal

Voltage

Transient

Local

UI &

Storage

PMU-based Apps Network Model-based Apps

Correlation

Non-operational

Data

Condition monitoringWeather information

Power system Grid

Copyright ALSTOM Grid

Copyright ALSTOM Grid

Page 10: Synchrophasor PMU data analysis for enhanced … is SynchroPhasor Technology? − Next generation measurement technology. (voltages, currents, frequency, frequency rate-of-change,

Dynamic Security Assessment

Transient Stability Analysis

Small Signal Stability Analysis

Voltage Stability Analysis

EMS Integrated with SynchroPhasor Solutions

G G

SynchroPhasor Applications

Framework – Oscillatory Stability Monitoring

– Disturbance Detection

– Composite Events

– Islanding/Restoration/Blackstart

– Post-Event Analysis, Baselining

PMU Data

(30-60 per second)

PMUs

PMUs

PMUs

PMU Data

(1 per second)

Wid

e-Area A

dvan

ced V

isualizatio

n

Energy Management System (EMS)– Improved State Estimation

–Grid Security Assessment

–SynchroPhasor State Estimator

SE snapshot (1 per min)

PMU based Information/Alerts (few seconds)

FACTS

Damping

control

IEC 61850

Real-Time

Controls

Copyright ALSTOM Grid

Phasor Data

Concentrator

PDC

Page 11: Synchrophasor PMU data analysis for enhanced … is SynchroPhasor Technology? − Next generation measurement technology. (voltages, currents, frequency, frequency rate-of-change,

Online Stability SolutionsIntegrated measurement-based and model-based stability

PMU measurement-based analyses

identify problems immediatelyPREDICT & MITIGATE

EDGE

MONITOR

OPERATING POINT

Model-based analyses

provide the corrective actions

Copyright ALSTOM Grid

Page 12: Synchrophasor PMU data analysis for enhanced … is SynchroPhasor Technology? − Next generation measurement technology. (voltages, currents, frequency, frequency rate-of-change,

ALSTOM Solutions

Model-based dynamic analyses:

-Voltage Stability Analysis (VSAT)

-Small Signal Stability Analysis (SSAT)

-Transient Stability Analysis (TSAT)

PMU Measurement-based Analyses

PhasorPoint :

Synchrophasor Framework

Synchrophasor Applications

Copyright ALSTOM Grid

EMS

Applications

Page 13: Synchrophasor PMU data analysis for enhanced … is SynchroPhasor Technology? − Next generation measurement technology. (voltages, currents, frequency, frequency rate-of-change,

Combined Measurement- & Model-based Approach for Model Validation

0.6Hz mode record including PSS testMeasured

Modelled

Page 14: Synchrophasor PMU data analysis for enhanced … is SynchroPhasor Technology? − Next generation measurement technology. (voltages, currents, frequency, frequency rate-of-change,

Why PMU-based analysis?

Improve Security

EARLY WARNING OF

INSTABILITY

SITUATIONAL

AWARENESS

ISLANDING RECOVERY

BLACKSTART

SELF-HEALING GRID

Increase Transfer

RELIEVE DAMPING

CONSTRAINTS

STATE ESTIMATION &

CONTINGENCY ANALYSIS

IDENTIFY LINE

PARAMETERS

System Analysis

PSS TUNING

PLANT COMMISSIONING

POST-EVENT ANALYSIS

IMPACT OF RENEWABLES

IDENTIFY DYNAMICS

ISSUES

PSS

ENABLED

PSS

DISABLED

Page 15: Synchrophasor PMU data analysis for enhanced … is SynchroPhasor Technology? − Next generation measurement technology. (voltages, currents, frequency, frequency rate-of-change,

Synchrophasor Applications Framework and Products

Products Main Features / Options Delivery

Server Central PDC (optional)

Historian

Standard Applications

Advanced Applications

Integration

Software

Regional PDC Local Archive (supports automatic data gap filling) Software

Substation PDC Local Archive (supports automatic data gap filling) Firmware & Software

Controller Protection/Control Applications Firmware & Software

Page 16: Synchrophasor PMU data analysis for enhanced … is SynchroPhasor Technology? − Next generation measurement technology. (voltages, currents, frequency, frequency rate-of-change,

Oscillatory Stability Management

1/F MODE FREQUENCY

MODE AMPLITUDE

A

MODE DECAY TIME

EXP(-t/ )

MODE PHASE

Mode Frequency

Mode Amplitude

Mode decay time

Mode Phase

Exp(-t/)

Measured P / f /

Simultaneous multi-oscillation detection and characterisation direct from measurements

For each oscillation detected, alarm on:

mode damping and/or

mode amplitude for

Operations

Planning & Analysis, Plant Performance

Unlimited oscillation frequency sub-bands

Individual alarm profiles for each sub-band

Post-event analysis

Dynamic model validation

Damping controller performance assessment

Dynamic performance baselining

Early warning of poor damping (2 level alarms)

Fast Modal Analysis: Alarms

Trend Modal Analysis: Analysis

Wide area mode alarms Mode locus plot with alarm thresholds

Copyright ALSTOM Grid

Page 17: Synchrophasor PMU data analysis for enhanced … is SynchroPhasor Technology? − Next generation measurement technology. (voltages, currents, frequency, frequency rate-of-change,

Congestion Relief

Australia

Queensland – NSW

Interconnector

Great Britain

Scotland – England

Interconnector

Transmission Corridor

Net Transfer Capacity

+300MW

+300MW Damping Measurement for Real-Time Constraints

• Modelling uncertainty requires large margin

• Use margin as long as observed damping is good

• Reduce transfer if poor inter-area mode damping occurs

Model limit with margin

Limit with measured damping

Thermal limitAREA 1

AREA 2

Page 18: Synchrophasor PMU data analysis for enhanced … is SynchroPhasor Technology? − Next generation measurement technology. (voltages, currents, frequency, frequency rate-of-change,

Improved Reliability: Operator Guidance

Opposing phase

oscillations

Coherent phase

oscillations

Oscillation

Power Path

Identify contributions to oscillations

from regions

“Regions” can be any size

All region boundaries monitored

Identify sources of oscillation problems

Choose remedial action

Define longer term performance improvements

Oscillation observability is not

sufficient for taking corrective

action – you need to know what is

contributing to the oscillation’s

power flow across the grid

Page 19: Synchrophasor PMU data analysis for enhanced … is SynchroPhasor Technology? − Next generation measurement technology. (voltages, currents, frequency, frequency rate-of-change,

Islanding, Resynchronisation & Blackstart

Identify islanding quickly

Alarm raised

Islands clearly visualised

Keep customers connected

Reduce time to resynchronise

Improve system visibility in blackstart

Page 20: Synchrophasor PMU data analysis for enhanced … is SynchroPhasor Technology? − Next generation measurement technology. (voltages, currents, frequency, frequency rate-of-change,

Use PMUs and SCADA data to triangulate &

precisely locate the origin of the disturbance

A sudden disturbance causes a traveling wave that can be detected by PMU data across the grid:

Source: VirginiaTech FNET

Disturbance Location

Disturbance Location

Page 21: Synchrophasor PMU data analysis for enhanced … is SynchroPhasor Technology? − Next generation measurement technology. (voltages, currents, frequency, frequency rate-of-change,

Model Validation

Governor controller tests:

Sensitivity of mode damping /

amplitude to governor

parameter changes

55

57

59

61

63

65

67

69

0 2 4 6 8 10 12 14

Time [s]

Active

po

we

r [p

u]

AVR

AVR_b

Modelled response

Mode Sensitivity to Governor Parameters

AVR/PSS Model Parameter Identification & Sensitivity

Simulation

Simulated & Measured Response: Time & frequency

domain comparison of expected & measured response

Measurement

Page 22: Synchrophasor PMU data analysis for enhanced … is SynchroPhasor Technology? − Next generation measurement technology. (voltages, currents, frequency, frequency rate-of-change,

AVR, PSS and Governor Tuning

Mo

de

Am

pli

tud

e (

MW

)

Mode Decay Time Constant (sec)

1.2Hz Mode

Before PSS tuning

After PSS tuning

Oscillatory Stability

Management:

• Wide area real-time damping

visualisation and alarms

• Dynamics baselining & trending

• Wide area event analysis

Real-time on-line and off-line tools that de-risk, simplify and speed-up the tuning process

Page 23: Synchrophasor PMU data analysis for enhanced … is SynchroPhasor Technology? − Next generation measurement technology. (voltages, currents, frequency, frequency rate-of-change,

Wide-Area Composite Alarms

Grid Alarms− Synchronised data synchronised alarms− Logical combinations wide-area alarms− Flexible logic combine alarms to notify significant threats− Applicable to voltage stability alarms

»Composite Event Status

»Event History

»Event Logic

Example: Voltage Instability

IF (ANY Sustained voltage slide OR N+ low voltage detections)

AND ANY High Q flow

Page 24: Synchrophasor PMU data analysis for enhanced … is SynchroPhasor Technology? − Next generation measurement technology. (voltages, currents, frequency, frequency rate-of-change,

Control Center Deployments

Real-time dynamics monitoring in

control rooms since 1997

• Transfer constraint updates

• System separations avoided

• Identified and sustained island operation

Clear, Actionable Information

Page 25: Synchrophasor PMU data analysis for enhanced … is SynchroPhasor Technology? − Next generation measurement technology. (voltages, currents, frequency, frequency rate-of-change,

Eskom, South Africa - 2009

Pilot project complete, next stage 4200 phasor system

Key features

− Flexible user configurable displays (e.g. wallboard) − Flexible alarms (level, ROC, composite) & notification (via EMS)

− Oscillatory stability− Disturbance capture & analysis− High availability

Exploring new application areas e.g.− Constraining by angle− Bush fire alerts

MULDERSVLE

I

Droerivier

Bacchus

GROOTVLEI

PEGASUS

Drakensburg

Leander

0.05Hz Common Mode0.3Hz SAPP Mode

MULDERSVLE

I

Droerivier

Bacchus

GROOTVLEI

PEGASUS

Drakensburg

Leander

0.7Hz Interarea Mode

Local Modes (various)

MULDERSVLE

I

Droerivier

Bacchus

GROOTVLEI

PEGASUS

Drakensburg

Leander

»MULDERSVLE»I

»Droerivier

»Bacchus

»GROOTVLEI

»PEGASUS

»Drakensburg

»Leander

Page 26: Synchrophasor PMU data analysis for enhanced … is SynchroPhasor Technology? − Next generation measurement technology. (voltages, currents, frequency, frequency rate-of-change,

Landsnet, Iceland 2007

Oscillations & PSS Tuning

Governor stability

Disturbance analysis

Islanding & Resynchronisation

Planned - Wide Area Defence

Before PSS tuning

After PSS tuning»0.8Hz Mode

»Mode Decay Time Constant (sec)

»M

od

e

Am

pli

tud

e (

MW

)

Page 27: Synchrophasor PMU data analysis for enhanced … is SynchroPhasor Technology? − Next generation measurement technology. (voltages, currents, frequency, frequency rate-of-change,

Iceland - 2007PSS Tuning & Dynamic Model Validation

Copyright ALSTOM Grid

Page 28: Synchrophasor PMU data analysis for enhanced … is SynchroPhasor Technology? − Next generation measurement technology. (voltages, currents, frequency, frequency rate-of-change,

MPP Application in Iceland

Opposing phase oscillations

Coherent phase oscillations

Oscillation

Power Path

Regional View

Line View

Substation View

Page 29: Synchrophasor PMU data analysis for enhanced … is SynchroPhasor Technology? − Next generation measurement technology. (voltages, currents, frequency, frequency rate-of-change,

XM, Colombia - 2009

Identifying & resolving frequency instability

Governor testing & tuning

Islanding, Resynchronisation & Blackstart

Control room warning/response

Planned

− Generator Modelling & Test tools− Wide Area Defence Scheme

61Hz

60Hz

59Hz

System

Frequency

Cycle 15 sec

22 Minutes

WAMS FOR DIAGNOSIS

& OPERATIONAL MONITORING

Page 30: Synchrophasor PMU data analysis for enhanced … is SynchroPhasor Technology? − Next generation measurement technology. (voltages, currents, frequency, frequency rate-of-change,

XM Colombia - 2009Modes Observed in Colombia (Inter-Area and Common-mode)

Ecuador Mode 0.49Hz

Governor Mode 0.06Hz

Inter-area mode at 0.49Hz

(Colombia-Ecuador).

Opposing phase in South

Governor common-mode:

whole system oscillates in

coherent phase

Copyright ALSTOM Grid

Page 31: Synchrophasor PMU data analysis for enhanced … is SynchroPhasor Technology? − Next generation measurement technology. (voltages, currents, frequency, frequency rate-of-change,

Powerlink Australia - 2000Transfer Constraint Relief

0 100 200 300 400 500-1200

-900

-600

-300

0

Time (sec)

Pow

er T

rans

fer

(MW

)

Thermal Limit

Transient / Voltage

Stability Limits

True Damping Limit

Model Damping Limit

with Margin

Available

Transfer

Capacity (MW)

Capacity available

provided measured

damping is acceptable

Area 1

Area 2

Model Damping Limit

Applied in

Australia & UK

+300MW

Australia

Queensland – NSW

Interconnector

+300MW

Copyright ALSTOM Grid

Page 32: Synchrophasor PMU data analysis for enhanced … is SynchroPhasor Technology? − Next generation measurement technology. (voltages, currents, frequency, frequency rate-of-change,

Baselining for Assessment and Issue identification

Governor mode:

whole system oscillates in

coherent phase

Characteristic behaviour pattern

Issue Identification: Governor Stability

Assessment: Dynamic Performance Reporting

Baselining:

Monthly reports identify normal & unusual oscillation behavior

and patterns.

Page 33: Synchrophasor PMU data analysis for enhanced … is SynchroPhasor Technology? − Next generation measurement technology. (voltages, currents, frequency, frequency rate-of-change,

Reporting, Alarm Configuration, Operator Guidance

− Monthly dynamics reporting− Event reporting

Reporting Alarm configuration studies

Dynamics interpretation &

response guidelines

1-Month Review, 0.26Hz Mode

EVENT

Poor damping

Raised amplitude

100s

8MW

10mHz

Page 34: Synchrophasor PMU data analysis for enhanced … is SynchroPhasor Technology? − Next generation measurement technology. (voltages, currents, frequency, frequency rate-of-change,

Control System Tuning

Generator Test Signal I/O

and Visualisation

Continuous read-out of

key generator data

(P, Q, V, )

WAMS observation of

system stability

Isolation, amplification and manual

over-ride of injected test signal

AVR, PSS & Governor Controller Tuning

• System survey and prioritising tuning work

• Model building & validation

• Control system commissioning testing

• Performance review

Page 35: Synchrophasor PMU data analysis for enhanced … is SynchroPhasor Technology? − Next generation measurement technology. (voltages, currents, frequency, frequency rate-of-change,

PG&E SynchroPhasor Project – 2010 to 2013Technical Lead: Vahid Madani, PG&E

Strategic Team: PG&E, ALSTOM, GE, Mississippi State Univ., Quanta

Academic & Testing Partners: GeorgiaTech, Omnicron/VirginiaTech, Washington State Univ.

SynchroPhasor Applications for the Control Center IEC61850 Backbone for Wide Area Automation

Control & Asset Management Centers

PDC

IEDsPMUsPMUs

Substation

IEC 61850

IEC 61850

IEC 61850

Page 36: Synchrophasor PMU data analysis for enhanced … is SynchroPhasor Technology? − Next generation measurement technology. (voltages, currents, frequency, frequency rate-of-change,

Wide Area Situational Awareness Visualization

NYISO - August, 2010

Query: station voltages

Flyout: SCADA 1-lines

Power flow animation

Dynamic Dashboard, Trends, Pie Charts

Contour: area Voltage

Trend Charts

Page 37: Synchrophasor PMU data analysis for enhanced … is SynchroPhasor Technology? − Next generation measurement technology. (voltages, currents, frequency, frequency rate-of-change,

Voltage Stability AssessmentVoltage Contours, MW Margins, Weak Elements, Remedial Actions

Identify weak elements (i.e. regions most prone

to voltage instability)

MW Transfer Margins

Control Recommendations

Copyright ALSTOM Grid

Page 38: Synchrophasor PMU data analysis for enhanced … is SynchroPhasor Technology? − Next generation measurement technology. (voltages, currents, frequency, frequency rate-of-change,

Small Signal Stability Modes shapes, amplitudes, damping, frequency, etc

Real-time alerts on poorly damped oscillations

Identify regions where inter-area oscillations are observable

Track oscillatory

stability in real-time.

Copyright ALSTOM Grid

Page 39: Synchrophasor PMU data analysis for enhanced … is SynchroPhasor Technology? − Next generation measurement technology. (voltages, currents, frequency, frequency rate-of-change,

»GRID