Synchrophasor-Based Monitoring, Analysis, and Control

Roy Moxley Schweitzer Engineering Laboratories, Inc.

Page 2: Synchrophasor-Based Monitoring, Analysis, and Control · Synchrophasors Are Standard SEL-421 IEEE C37.118 SEL-451. SEL-487E. SEL-787. SEL-734 SEL Fast Message. SEL-311A, B, C. SEL-311L

The Power System Is Changing

Photo Courtesy of Shawn Jacobs, OG&E

Page 3: Synchrophasor-Based Monitoring, Analysis, and Control · Synchrophasors Are Standard SEL-421 IEEE C37.118 SEL-451. SEL-487E. SEL-787. SEL-734 SEL Fast Message. SEL-311A, B, C. SEL-311L

‘02 ’03 8/03 ‘05 ‘06 ’06 ’07 ’07+

Synch

roph

asor

s in a

Mete

r

Synch

roph

asor

s on t

he W

eb

IEEE P

rotoc

ol in

a Rela

y

Synch

roph

asor

s in a

Rela

y

Retrofi

t Syn

chro

phas

ors

In a R

elay

Utility

Grade

PDC

SCADA Syn

chro

phas

ors

Real-T

ime C

ontro

l in

a Rela

y (Mex

ico)

SEL Synchrophasor Vision

0

5

10

15

20

25

AG10AB10BCG10ABC10

AG50AB50BCG50ABC50

AG80AB80BCG80ABC80

AG90AB90BCG90ABC90

Fault Type and Distance

Tim

e (m

s)

Local side trip times WITHOUT synchrophasors Local side trip times WITH synchrophasors

Real-T

ime V

ecto

r

Proce

ssor

Page 4: Synchrophasor-Based Monitoring, Analysis, and Control · Synchrophasors Are Standard SEL-421 IEEE C37.118 SEL-451. SEL-487E. SEL-787. SEL-734 SEL Fast Message. SEL-311A, B, C. SEL-311L

Synchrophasors Are StandardSEL-421

IEEE C37.118

SEL-451SEL-487ESEL-787SEL-734 SEL Fast Message

SEL-311A, B, CSEL-311LSEL-351SEL-351SSEL-351A

Page 5: Synchrophasor-Based Monitoring, Analysis, and Control · Synchrophasors Are Standard SEL-421 IEEE C37.118 SEL-451. SEL-487E. SEL-787. SEL-734 SEL Fast Message. SEL-311A, B, C. SEL-311L

Protection AND Synchrophasors

0

5

10

15

20

25

AG90AB90BCG90ABC90

AG50AB50BCG50ABC50

AG20AB20BCG20ABC20

AG10AB10BCG10ABC10

Fault Type and Distance

Tim

e (m

s)

Remote side trip times WITHOUT synchrophasors Remote side trip times WITH synchrophasors

0

5

10

15

20

25

AG10AB10BCG10ABC10

AG50AB50BCG50ABC50

AG80AB80BCG80ABC80

AG90AB90BCG90ABC90

Fault Type and Distance

Tim

e (m

s)

Local side trip times WITHOUT synchrophasors Local side trip times WITH synchrophasors

Synchrophasors do not hurt relay performance

Page 6: Synchrophasor-Based Monitoring, Analysis, and Control · Synchrophasors Are Standard SEL-421 IEEE C37.118 SEL-451. SEL-487E. SEL-787. SEL-734 SEL Fast Message. SEL-311A, B, C. SEL-311L

Relaying Has No Impact on PMCU Function

No lostdata

4 4.1 4.2 4.3 4.4 4.5 4.6 4.7 4.8 4.90

1

2

3

Local bus side phase A voltage synchrophasorSynchrophasor data check

Time (s)

Page 7: Synchrophasor-Based Monitoring, Analysis, and Control · Synchrophasors Are Standard SEL-421 IEEE C37.118 SEL-451. SEL-487E. SEL-787. SEL-734 SEL Fast Message. SEL-311A, B, C. SEL-311L

Relays Are Right for Synchrophasors

Phasor measurement and control unit(PMCU) ≥ PMU

Minimal incremental cost

Reduced current and voltage connections

High-accuracy measurements

High reliability and availability

Future control applications

Relays are everywhere

Page 8: Synchrophasor-Based Monitoring, Analysis, and Control · Synchrophasors Are Standard SEL-421 IEEE C37.118 SEL-451. SEL-487E. SEL-787. SEL-734 SEL Fast Message. SEL-311A, B, C. SEL-311L

SEL Synchrophasor Equipped Devices Worldwide !

North AmericaNorth America>20,000 units>20,000 units

South AmericaSouth America>2,000 units>2,000 units

Europe/AsiaEurope/Asia>3,000 units>3,000 units

Africa/Middle EastAfrica/Middle East>1,000 units>1,000 units

Asia Asia PacificPacific

>5,000 units>5,000 units

Page 9: Synchrophasor-Based Monitoring, Analysis, and Control · Synchrophasors Are Standard SEL-421 IEEE C37.118 SEL-451. SEL-487E. SEL-787. SEL-734 SEL Fast Message. SEL-311A, B, C. SEL-311L

Application Options – Not “One Size Fits All”

SEL-5078 Visualization

SEL-5077, SEL-5078 Archiving

System Operator, Reliability Council

SEL-3306 Hardware PDC SEL-5077 Software PDC

SEL-3378 Vector Processor

PMU’s

Page 10: Synchrophasor-Based Monitoring, Analysis, and Control · Synchrophasors Are Standard SEL-421 IEEE C37.118 SEL-451. SEL-487E. SEL-787. SEL-734 SEL Fast Message. SEL-311A, B, C. SEL-311L

Protection and Control Time Frame

~1.0 Second ~30 Seconds

Relay Action Human ActionControl Action

Page 11: Synchrophasor-Based Monitoring, Analysis, and Control · Synchrophasors Are Standard SEL-421 IEEE C37.118 SEL-451. SEL-487E. SEL-787. SEL-734 SEL Fast Message. SEL-311A, B, C. SEL-311L

METER PM 13:22

Page 12: Synchrophasor-Based Monitoring, Analysis, and Control · Synchrophasors Are Standard SEL-421 IEEE C37.118 SEL-451. SEL-487E. SEL-787. SEL-734 SEL Fast Message. SEL-311A, B, C. SEL-311L

Monitor a Gen Drop Test (New Zealand)

Page 13: Synchrophasor-Based Monitoring, Analysis, and Control · Synchrophasors Are Standard SEL-421 IEEE C37.118 SEL-451. SEL-487E. SEL-787. SEL-734 SEL Fast Message. SEL-311A, B, C. SEL-311L

49.1

49.3

49.5

49.7

49.9

50.1

50.3

Timestamp 5/3/2007 3:10:18.6805/3/2007 3:11:06.6805/3/2007 3:11:54.6805/3/2007 3:12:42.6805/3/2007 3:13:30.6805/3/2007 3:14:18.6805/3/2007 3:15:06.680

Whakamaru_Frequency Huntly_Frequency

Test Shows System Remains Stable When 400 MW Dropped

Frequency recordings at both ends perfectly overlap and align in time.

Page 14: Synchrophasor-Based Monitoring, Analysis, and Control · Synchrophasors Are Standard SEL-421 IEEE C37.118 SEL-451. SEL-487E. SEL-787. SEL-734 SEL Fast Message. SEL-311A, B, C. SEL-311L

Malin – Round Mt. 500 kV Trips June 18, 2007

Page 15: Synchrophasor-Based Monitoring, Analysis, and Control · Synchrophasors Are Standard SEL-421 IEEE C37.118 SEL-451. SEL-487E. SEL-787. SEL-734 SEL Fast Message. SEL-311A, B, C. SEL-311L

“The MRI of Power Systems”

NERC press release on Florida outage

Feb. 26, 2008:

Synchrophasors are “Like the MRI of bulk power

systems”

Page 16: Synchrophasor-Based Monitoring, Analysis, and Control · Synchrophasors Are Standard SEL-421 IEEE C37.118 SEL-451. SEL-487E. SEL-787. SEL-734 SEL Fast Message. SEL-311A, B, C. SEL-311L

Synchrophasor-Based Control – Now a Reality

Page 17: Synchrophasor-Based Monitoring, Analysis, and Control · Synchrophasors Are Standard SEL-421 IEEE C37.118 SEL-451. SEL-487E. SEL-787. SEL-734 SEL Fast Message. SEL-311A, B, C. SEL-311L

Big Creek Controls Rector Static VAR Compensator

Page 18: Synchrophasor-Based Monitoring, Analysis, and Control · Synchrophasors Are Standard SEL-421 IEEE C37.118 SEL-451. SEL-487E. SEL-787. SEL-734 SEL Fast Message. SEL-311A, B, C. SEL-311L

SCE Uses C37.118 From Relays and PMU

SCADAMaster

DNP3

IEEE C37.118

InformationProcessor

(Harris 5000/6000, IEC 60870-103, Modbus, SEL Fast Message, SES 92, Telegyr 8979, Conitel 2020, GETAC, Recon 1.1, CoDeSys, OPC, …)

Page 19: Synchrophasor-Based Monitoring, Analysis, and Control · Synchrophasors Are Standard SEL-421 IEEE C37.118 SEL-451. SEL-487E. SEL-787. SEL-734 SEL Fast Message. SEL-311A, B, C. SEL-311L

Impact of the Rector SVC: 6-14-07 (pre-SVC) vs. 8-30-07 (post-SVC)

Magunden Substation Voltage Comparison(Rector Substation Events 6-14-07 and 8-30-07)

220

222

224

226

228

230

232

234

236

238

240

-5.00 0.00 5.00 10.00 15.00 20.00 25.00

Time (seconds)

Mag

unde

n Vo

ltage

(kV)

Rector 8-30-2007 event (POST-SVC) Rector 6-14-2007 event (PRE-SVC)

The Rector SVC had the apparent effect of reducing the magnitude & duration of the fault-induced slow voltage

recovery…

6-14-2007 (pre-SVC)

8-30-2007 (post-SVC)

NOTE: Voltages shown were measured ~70 miles south of Rector Substation (actual low voltage event was of greater

magnitude at Rector substation itself)

Page 20: Synchrophasor-Based Monitoring, Analysis, and Control · Synchrophasors Are Standard SEL-421 IEEE C37.118 SEL-451. SEL-487E. SEL-787. SEL-734 SEL Fast Message. SEL-311A, B, C. SEL-311L

Effect of SVC Operation on Big Creek Before -

Page 21: Synchrophasor-Based Monitoring, Analysis, and Control · Synchrophasors Are Standard SEL-421 IEEE C37.118 SEL-451. SEL-487E. SEL-787. SEL-734 SEL Fast Message. SEL-311A, B, C. SEL-311L

Effect of SVC Operation on Big Creek After -

Page 22: Synchrophasor-Based Monitoring, Analysis, and Control · Synchrophasors Are Standard SEL-421 IEEE C37.118 SEL-451. SEL-487E. SEL-787. SEL-734 SEL Fast Message. SEL-311A, B, C. SEL-311L

Synchronous Vector ProcessingSystem

MeasurementFunction

CalculationOutput

Designation

Send Control to System(Application)

f(x)

Page 23: Synchrophasor-Based Monitoring, Analysis, and Control · Synchrophasors Are Standard SEL-421 IEEE C37.118 SEL-451. SEL-487E. SEL-787. SEL-734 SEL Fast Message. SEL-311A, B, C. SEL-311L

Apply the

Collect synchronous phasor measurements

Collect logical inputs

Perform vector and scalar math

Make decisions

Produce outputs

Report data

Page 24: Synchrophasor-Based Monitoring, Analysis, and Control · Synchrophasors Are Standard SEL-421 IEEE C37.118 SEL-451. SEL-487E. SEL-787. SEL-734 SEL Fast Message. SEL-311A, B, C. SEL-311L

Select Quantities From Each PMU

PMU1PMU2PMU3

Analogs| V1 |∠V1

| I1 |∠I1

FreqPSV42TE (time error)

Binary dataStatusTriggers

Page 25: Synchrophasor-Based Monitoring, Analysis, and Control · Synchrophasors Are Standard SEL-421 IEEE C37.118 SEL-451. SEL-487E. SEL-787. SEL-734 SEL Fast Message. SEL-311A, B, C. SEL-311L

Integrate Wide-Area Protection and Control

Static Var Control

SEL-421

SEL-421

SEL-421

Page 26: Synchrophasor-Based Monitoring, Analysis, and Control · Synchrophasors Are Standard SEL-421 IEEE C37.118 SEL-451. SEL-487E. SEL-787. SEL-734 SEL Fast Message. SEL-311A, B, C. SEL-311L

Apply Flexible Function Calculations

IEC 61131 engineMathTrigDifferentials

Preprogrammed blocksPowerAngle differenceModal analysisStation topology check

Page 27: Synchrophasor-Based Monitoring, Analysis, and Control · Synchrophasors Are Standard SEL-421 IEEE C37.118 SEL-451. SEL-487E. SEL-787. SEL-734 SEL Fast Message. SEL-311A, B, C. SEL-311L

Combine Pre-Configured with Custom Functions

Page 28: Synchrophasor-Based Monitoring, Analysis, and Control · Synchrophasors Are Standard SEL-421 IEEE C37.118 SEL-451. SEL-487E. SEL-787. SEL-734 SEL Fast Message. SEL-311A, B, C. SEL-311L

Provides Function Blocks

Page 29: Synchrophasor-Based Monitoring, Analysis, and Control · Synchrophasors Are Standard SEL-421 IEEE C37.118 SEL-451. SEL-487E. SEL-787. SEL-734 SEL Fast Message. SEL-311A, B, C. SEL-311L

Map PMU Quantities to Phase Angle Difference Monitor

Page 30: Synchrophasor-Based Monitoring, Analysis, and Control · Synchrophasors Are Standard SEL-421 IEEE C37.118 SEL-451. SEL-487E. SEL-787. SEL-734 SEL Fast Message. SEL-311A, B, C. SEL-311L
Page 31: Synchrophasor-Based Monitoring, Analysis, and Control · Synchrophasors Are Standard SEL-421 IEEE C37.118 SEL-451. SEL-487E. SEL-787. SEL-734 SEL Fast Message. SEL-311A, B, C. SEL-311L

Improve Local Measurements

V A

Substation State and Topology Processor

Refined Is, Vs, Alarms,

and Topology52

52

52

52 52 52

Page 32: Synchrophasor-Based Monitoring, Analysis, and Control · Synchrophasors Are Standard SEL-421 IEEE C37.118 SEL-451. SEL-487E. SEL-787. SEL-734 SEL Fast Message. SEL-311A, B, C. SEL-311L

Identify and Quarantine Bad Data

Measurements Measurements+

Calculate Median

Measurements+

Calculate Median+

Flag and Quarantine

Set Flag

Page 33: Synchrophasor-Based Monitoring, Analysis, and Control · Synchrophasors Are Standard SEL-421 IEEE C37.118 SEL-451. SEL-487E. SEL-787. SEL-734 SEL Fast Message. SEL-311A, B, C. SEL-311L
Page 34: Synchrophasor-Based Monitoring, Analysis, and Control · Synchrophasors Are Standard SEL-421 IEEE C37.118 SEL-451. SEL-487E. SEL-787. SEL-734 SEL Fast Message. SEL-311A, B, C. SEL-311L

Line Trip…Stable

System Separation

Line Trip and Generation

Loss…Unstable

Real-Time Modal Analysis Monitor Predicts System Disturbances

Page 35: Synchrophasor-Based Monitoring, Analysis, and Control · Synchrophasors Are Standard SEL-421 IEEE C37.118 SEL-451. SEL-487E. SEL-787. SEL-734 SEL Fast Message. SEL-311A, B, C. SEL-311L

Use Oscillation Frequency and Damping Ratio

For the complex Eigen value pair:

Oscillation frequency is:

Damping ratio is:

djω±σ=λ

πω

=2

f dosc

d

i

ωσσς+

=2

–2

Page 36: Synchrophasor-Based Monitoring, Analysis, and Control · Synchrophasors Are Standard SEL-421 IEEE C37.118 SEL-451. SEL-487E. SEL-787. SEL-734 SEL Fast Message. SEL-311A, B, C. SEL-311L

Modal Analysis Shows System Response

Page 37: Synchrophasor-Based Monitoring, Analysis, and Control · Synchrophasors Are Standard SEL-421 IEEE C37.118 SEL-451. SEL-487E. SEL-787. SEL-734 SEL Fast Message. SEL-311A, B, C. SEL-311L

Develop Custom ApplicationsVoltage Collapse Detection

Instability of Distributed Generation

Complex Power Swings

Others ?

Page 38: Synchrophasor-Based Monitoring, Analysis, and Control · Synchrophasors Are Standard SEL-421 IEEE C37.118 SEL-451. SEL-487E. SEL-787. SEL-734 SEL Fast Message. SEL-311A, B, C. SEL-311L

Operating Point

Bifurcation Point

Utilities Are Operating Closer to the Edge

PU Nominal Load

Operating Point

Bifurcation Point

MarginMargin

1.61.51.31.00.0

0.5

1.0

Page 39: Synchrophasor-Based Monitoring, Analysis, and Control · Synchrophasors Are Standard SEL-421 IEEE C37.118 SEL-451. SEL-487E. SEL-787. SEL-734 SEL Fast Message. SEL-311A, B, C. SEL-311L

Long Island: Monitor Angles Between Transmission Distribution Buses to Detect and Prevent Voltage Collapse

( )X)θcos(2V)θsin(1S 2

2s

max−=

S = P + jQ

ZL = R + jX

δ∠rV

0VS ∠

Page 40: Synchrophasor-Based Monitoring, Analysis, and Control · Synchrophasors Are Standard SEL-421 IEEE C37.118 SEL-451. SEL-487E. SEL-787. SEL-734 SEL Fast Message. SEL-311A, B, C. SEL-311L

Calculate Voltage Stability Index (VSI)

SVP calculates maxima: P, Q, and S

Calculate margins:

QQQ maxmargin −=

⎟⎠

⎞⎜⎝

⎛=

max

margin

max

margin

max

margin

SS

,QQ

,PP

minVSI

PPP maxginmar −=

SSS maxmargin −=

Page 41: Synchrophasor-Based Monitoring, Analysis, and Control · Synchrophasors Are Standard SEL-421 IEEE C37.118 SEL-451. SEL-487E. SEL-787. SEL-734 SEL Fast Message. SEL-311A, B, C. SEL-311L

Improve Power Swing Detection

Actual Swing from 2003 Blackout

Page 42: Synchrophasor-Based Monitoring, Analysis, and Control · Synchrophasors Are Standard SEL-421 IEEE C37.118 SEL-451. SEL-487E. SEL-787. SEL-734 SEL Fast Message. SEL-311A, B, C. SEL-311L

Wide-Area Measurement Is Better than Traditional “Blinder” Methods

Impedance Loci

Wide-Area Measurement

Replace and improve on local out of step

What if load or source impedance changes?

Page 43: Synchrophasor-Based Monitoring, Analysis, and Control · Synchrophasors Are Standard SEL-421 IEEE C37.118 SEL-451. SEL-487E. SEL-787. SEL-734 SEL Fast Message. SEL-311A, B, C. SEL-311L

Delta/Delta-Dot Phase Plane Analysis

-20 0 20 40 60 80 100 120 140 160 180-200

-100

0

100

200

300

400

500

Angle Difference δ (deg)

Slip

(de

g/se

c)

Page 44: Synchrophasor-Based Monitoring, Analysis, and Control · Synchrophasors Are Standard SEL-421 IEEE C37.118 SEL-451. SEL-487E. SEL-787. SEL-734 SEL Fast Message. SEL-311A, B, C. SEL-311L

Delta-Dot Delta-Doubledot Phase Plane

0 0.5 1 1.5 2 2.5 3 3.5 4-40

-30

-20

-10

0

10

20

30

40

Slip (Hz)

Acc

eler

atio

n (H

z/se

c)

Page 45: Synchrophasor-Based Monitoring, Analysis, and Control · Synchrophasors Are Standard SEL-421 IEEE C37.118 SEL-451. SEL-487E. SEL-787. SEL-734 SEL Fast Message. SEL-311A, B, C. SEL-311L

Use Fast Operate Control Blocks for Closed-Loop Control

Page 46: Synchrophasor-Based Monitoring, Analysis, and Control · Synchrophasors Are Standard SEL-421 IEEE C37.118 SEL-451. SEL-487E. SEL-787. SEL-734 SEL Fast Message. SEL-311A, B, C. SEL-311L

Synchrophasors Are StandardSEL-421

IEEE C37.118

SEL-451SEL-487ESEL-787SEL-734 SEL Fast Message

SEL-311A, B, CSEL-311LSEL-351SEL-351SSEL-351A

Page 47: Synchrophasor-Based Monitoring, Analysis, and Control · Synchrophasors Are Standard SEL-421 IEEE C37.118 SEL-451. SEL-487E. SEL-787. SEL-734 SEL Fast Message. SEL-311A, B, C. SEL-311L

Synchrophasors Provide New and Improved Capabilities

Angle measurement

Disturbance analysis

Modal analysis

Out-of-step detection

Real-time control

What Else Can They Do For You?