49
Symmetrical fault and protection Olof Samuelsson Lightning test in lab

Symmetrical fault and protection Olof Samuelsson - IEA€“ Transmission lines: ... transformers, lines, busbars • Generators • i ... • Relay 2 is primary protection and provides

Embed Size (px)

Citation preview

Page 1: Symmetrical fault and protection Olof Samuelsson - IEA€“ Transmission lines: ... transformers, lines, busbars • Generators • i ... • Relay 2 is primary protection and provides

Symmetrical fault and protection

Olof Samuelsson

Lightning test in lab

Page 2: Symmetrical fault and protection Olof Samuelsson - IEA€“ Transmission lines: ... transformers, lines, busbars • Generators • i ... • Relay 2 is primary protection and provides

Outline

• Three-phase short-circuit fault current• Network representation• Circuit breakers and disconnectors• Measurement transformers• Fuses and protection relays• Relay coordination

• Short-circuit fault current transient

2EIEN15 Electric Power Systems L3

Page 3: Symmetrical fault and protection Olof Samuelsson - IEA€“ Transmission lines: ... transformers, lines, busbars • Generators • i ... • Relay 2 is primary protection and provides

Open-circuit faults (Sw. avbrott)Also series fault• A fault for which the impedances of each of the three

phases are not equal, usually caused by the interruption of one or two phases. (IEC definition)

Examples• One phase of circuit breaker stuck open• Conductor falling down

Short-circuit faults more common

3EIEN15 Electric Power Systems L3

Page 4: Symmetrical fault and protection Olof Samuelsson - IEA€“ Transmission lines: ... transformers, lines, busbars • Generators • i ... • Relay 2 is primary protection and provides

Short-circuit faults (Sw. kortslutningar)Also shunt fault• A fault that is characterized by the flow of current

between two or more phases or between phase(s) and earth… (IEC definition)

Examples• Lightning• Dirt/salt on insulators• Flashover (Sw. överslag) line-line (wind) or line to tree• Tower/pole or conductor falls• Objects fall on conductors• Cable insulation failure

4EIEN15 Electric Power Systems L3

Page 5: Symmetrical fault and protection Olof Samuelsson - IEA€“ Transmission lines: ... transformers, lines, busbars • Generators • i ... • Relay 2 is primary protection and provides

Lightning most common

Statistically80 % of faults onoverhead lines are due to lightning

5EIEN15 Electric Power Systems L3

Page 6: Symmetrical fault and protection Olof Samuelsson - IEA€“ Transmission lines: ... transformers, lines, busbars • Generators • i ... • Relay 2 is primary protection and provides

Power lines and trees400 kV 50 kV

10 kV

Distribution lines most affected6EIEN15 Electric Power Systems L3

400 kV lines unaffected by Gudrun

Page 7: Symmetrical fault and protection Olof Samuelsson - IEA€“ Transmission lines: ... transformers, lines, busbars • Generators • i ... • Relay 2 is primary protection and provides

Effects of short-circuit current

• Arc (Sw. ljusbåge)– Compare with welding

• Heating– Fire and explosion (movie transformer blast)

• Vibration due to magnetic forces – Parallel conductors are attracted (F=B·i·l)

7EIEN15 Electric Power Systems L3

Page 8: Symmetrical fault and protection Olof Samuelsson - IEA€“ Transmission lines: ... transformers, lines, busbars • Generators • i ... • Relay 2 is primary protection and provides

Heating

• Resistive losses RI2 heat energy = RI2dt = RI2t • Temperature rises with stored heat energy (if no cooling)• Same I2t gives equal heating

8EIEN15 Electric Power Systems L3

Time=1/I2

Current

Overload

Short-circuit fault

I2t=constantSafe = no time lim

it

Page 9: Symmetrical fault and protection Olof Samuelsson - IEA€“ Transmission lines: ... transformers, lines, busbars • Generators • i ... • Relay 2 is primary protection and provides

Symmetrical 3-phase short-circuit

9EIEN15 Electric Power Systems L3

VTH

ZTH

ISC

VF=VTH

ZTH

IF+

+

ISC=VTH/ZTH IF =VF/ZTH=VTH/ZTH

•Thévenin gives only IF and not the prefault load current•Prefault voltage VF often assumed same at all buses

Page 10: Symmetrical fault and protection Olof Samuelsson - IEA€“ Transmission lines: ... transformers, lines, busbars • Generators • i ... • Relay 2 is primary protection and provides

3-phase short-circuit: Currents

10EIEN15 Electric Power Systems L3

System

I

System

I

+

–VF

+

–VF

= Systemsources

at VF

IPrefault

+

–VF

= +

Current during fault I = Iprefault + IF

Prefault current often << IF and neglected

System

IF

+

–VF

sourcesat 0

IF

Page 11: Symmetrical fault and protection Olof Samuelsson - IEA€“ Transmission lines: ... transformers, lines, busbars • Generators • i ... • Relay 2 is primary protection and provides

Network during fault

• Standard simplifications to find fault current– Transformers: Only Xeq, no phase shift– Transmission lines: Only series reactance– Generators: Eg behind X”d, no saliency, Ra or saturation

– Large motors: Like generators– Small motors: Neglected– Non-rotating loads: Neglected

11EIEN15 Electric Power Systems L3

Page 12: Symmetrical fault and protection Olof Samuelsson - IEA€“ Transmission lines: ... transformers, lines, busbars • Generators • i ... • Relay 2 is primary protection and provides

Series impedances limit S-C currentsAll transformer x to same base:• 400/130 kV, x=0.1 p.u. @ 750 MVA

– 0.013 p.u. @ 100 MVA base

• 130/20 kV, x=0.1 p.u. @ 40 MVA– 0.25 p.u. @ 100 MVA base– 18.75 x 0.013 p.u.

• 20/0.4 kV, x=0.1 p.u. @ 0.8 MVA– 12.5 p.u. @ 100 MVA base– 50 x 0.25 p.u. and 937.5 x 0.013 p.u.

• The last transformer dominates ZTH

VTH

ZTH400

~ 400 kV 130 kV 20 kV 0.4 kV

j0.013 j0.25 j12.5

Page 13: Symmetrical fault and protection Olof Samuelsson - IEA€“ Transmission lines: ... transformers, lines, busbars • Generators • i ... • Relay 2 is primary protection and provides

S-C currents at different voltage levelsTry 0 fault at 0.4 kV. Assume Z=20 p.u. ISC=0.05 p.u.• Ibase400=100MVA/(3400kV)=144 A

– 0.05144A=7.2 A

• Ibase130=100MVA/(3130kV)=444 A– 0.05444A= 22 A

• Ibase30=100MVA/(320kV)=2.9 kA– 0.052.9 kA= 145 A

• Ibase0.4=100MVA/(30.4kV)=144 kA– 0.05144 kA= 7200 A

VTH

ZTH400

~ 400 kV 130 kV 20 kV 0.4 kV

j0.013 j0.25 j12.5

Page 14: Symmetrical fault and protection Olof Samuelsson - IEA€“ Transmission lines: ... transformers, lines, busbars • Generators • i ... • Relay 2 is primary protection and provides

Interrupting large currents

• Fuses (Sw. säkringar)– Use the melting effect of the fault current (arc)

• Circuit breakers (Sw. effektbrytare) interrupt kA in ms– Extinguish arc using pressurized air (arc energy),

vacuum, oil etc.

• Circuit breaker operation– Automatic by relay protection– Manual remote control from control center

14EIEN15 Electric Power Systems L3

Page 15: Symmetrical fault and protection Olof Samuelsson - IEA€“ Transmission lines: ... transformers, lines, busbars • Generators • i ... • Relay 2 is primary protection and provides

Disconnector/Isolator not for short-circuits(Sw. frånskiljare)

• Visible interruption• Motorized or manual (rural MV)• Interrupts < Load current

– OK: Youtube 110 kV disconnector closes and opens– Too large current: Youtube 138 kV Elkford

• Design challenge: Weather

Sweden USA

Open Closed

15EIEN15 Electric Power Systems L3

Open Closed

Source: Nicklasson

Page 16: Symmetrical fault and protection Olof Samuelsson - IEA€“ Transmission lines: ... transformers, lines, busbars • Generators • i ... • Relay 2 is primary protection and provides

Circuit breaker

• Interrupts large current– Perhaps 63 kA in 20 ms– Short-circuit current– Hidden contacts

• Control– Protection systems– Manual remote

• Design challenge– Speed and current

Sweden USA

Open Closed

Sour

ce:A

BB

16EIEN15 Electric Power Systems L3

Page 17: Symmetrical fault and protection Olof Samuelsson - IEA€“ Transmission lines: ... transformers, lines, busbars • Generators • i ... • Relay 2 is primary protection and provides

Disconnecting circuit breaker• Combines breaker and disconnector• More reliable and compact

17EIEN15 Electric Power Systems L3

Lindome 400 kV station, also in Lund

Breaker

Disconnector

Line

Line Combinedbreaker

Page 18: Symmetrical fault and protection Olof Samuelsson - IEA€“ Transmission lines: ... transformers, lines, busbars • Generators • i ... • Relay 2 is primary protection and provides

More compact switchgear

AirSF6

Source: Lakervi

• Disconnecting circuit breaker in air insulated station• Gas Insulated Switchgear (GIS) uses SF6 gas

– Isolates much better than air - reduces size– SF6 a greenhouse gas – alternatives are sought for

18EIEN15 Electric Power Systems L3

Page 19: Symmetrical fault and protection Olof Samuelsson - IEA€“ Transmission lines: ... transformers, lines, busbars • Generators • i ... • Relay 2 is primary protection and provides

Protection for automatic fault clearing

Need– Detect fault– Isolate faulted component– Restore service for unfaulted components

Aims– Continued supply for rest of system– Protect faulted part from damage

(A fuse does this, but needs manual replacement)

19EIEN15 Electric Power Systems L3

Page 20: Symmetrical fault and protection Olof Samuelsson - IEA€“ Transmission lines: ... transformers, lines, busbars • Generators • i ... • Relay 2 is primary protection and provides

Basic fault clearing system(Sw. felbortkopplingssystem)

• The protection relay takes CB trip decision based on inputs• Many relays can operate same breaker• Initially relays were electro-mechanical, then electronic

and now use a microprocessor/DSP and GPS20EIEN15 Electric Power Systems L3

Relay

PT

CT CB

CB - Circuit BreakerCT - Current TransformerPT - Potential Transformer

Batteries for CB operationPossible communication

Page 21: Symmetrical fault and protection Olof Samuelsson - IEA€“ Transmission lines: ... transformers, lines, busbars • Generators • i ... • Relay 2 is primary protection and provides

Current transformer (Sw. strömtransf.)

• Reduces current– Typically 1000/2 A

• Current monitored– Control center– Protection equipment– P, Q transducers

Sour

ce:A

BB

21EIEN15 Electric Power Systems L3

Page 22: Symmetrical fault and protection Olof Samuelsson - IEA€“ Transmission lines: ... transformers, lines, busbars • Generators • i ... • Relay 2 is primary protection and provides

Voltage/potential transformer(Sw. spänningstransformator)

• Reduces voltage– Typically x kV/110 V

• Voltage monitored– Control center– Protection equipment– P, Q transducers

• Also C voltage divider

Sour

ce:A

BB

22EIEN15 Electric Power Systems L3

Page 23: Symmetrical fault and protection Olof Samuelsson - IEA€“ Transmission lines: ... transformers, lines, busbars • Generators • i ... • Relay 2 is primary protection and provides

Surge arrester/lightning arrester(Sw. ventilavledare)

• Passive overvoltage protection• Alternative to air gap• Nonlinear resistance gives

short-circuits at high voltages• Sends lightning to ground

Source: ABB23EIEN15 Electric Power Systems L3

Page 24: Symmetrical fault and protection Olof Samuelsson - IEA€“ Transmission lines: ... transformers, lines, busbars • Generators • i ... • Relay 2 is primary protection and provides

24EIEN15 Electric Power Systems L3

Layout DisconnectorCurrent transformerCircuit breakerDisconnectorBusbar

Voltage transformer

Surge arrester

Page 25: Symmetrical fault and protection Olof Samuelsson - IEA€“ Transmission lines: ... transformers, lines, busbars • Generators • i ... • Relay 2 is primary protection and provides

Protection system tasksDetect fault – Is there a fault?

– Short-circuit or only high load?– ISC=5-7 p.u. of synchronous generators simplifies this!– ISC of power electronic “generators” only about 1.2 p.u.!

Isolate fault – Open (“trip”) circuit breaker(s) (CB)Many alternatives Coordination required

– Which protection unit should react and open which CB?– Isolate as small area as possible– Isolation must happen also if one component fails

25EIEN15 Electric Power Systems L3

Page 26: Symmetrical fault and protection Olof Samuelsson - IEA€“ Transmission lines: ... transformers, lines, busbars • Generators • i ... • Relay 2 is primary protection and provides

• Differential protection where |Iin-Iout |>0 means fault– Lines– Transformers– Busbars– Generators

• Overcurrent protection– Lines in radial (distribution) systems

• Overcurrent relay with directional sensitivity– Lines in meshed (transmission) systems– Generators

Different protection for different objects

26EIEN15 Electric Power Systems L3

Iin

Iin

Iin

Iout

Iout

Iout1

Iout2

Page 27: Symmetrical fault and protection Olof Samuelsson - IEA€“ Transmission lines: ... transformers, lines, busbars • Generators • i ... • Relay 2 is primary protection and provides

Current differential protection

• Compare iin and iout

• |iin– iout|≈0 no internal fault• |iin– iout|>>0 internal fault: Trip CB

• Applicable to generators, transformers, lines, busbars• Generators

• iin and iout of each winding• Communication needed for lines

27EIEN15 Electric Power Systems L3

MG

Page 28: Symmetrical fault and protection Olof Samuelsson - IEA€“ Transmission lines: ... transformers, lines, busbars • Generators • i ... • Relay 2 is primary protection and provides

Protection zones• Defined for protected objects

– Dedicated protection for each zone• Zone border where current is measured• Zones overlap with CB in overlap zones• Isolated at fault anywhere inside• Perfect for differential protection

MG

28EIEN15 Electric Power Systems L3

Page 29: Symmetrical fault and protection Olof Samuelsson - IEA€“ Transmission lines: ... transformers, lines, busbars • Generators • i ... • Relay 2 is primary protection and provides

Time-delay overcurrent relay for line

• Detect overcurrent – Wait delay time T – Trip CB

• Multiple overcurrent relays can be co-ordinated

– Different delays decide tripping order– Few fixed delay times practical, e.g. 0, 0,25, 1 s

29EIEN15 Electric Power Systems L3

Time

Relative overcurrent

1

T

Trip Constant delaycharacteristic

Page 30: Symmetrical fault and protection Olof Samuelsson - IEA€“ Transmission lines: ... transformers, lines, busbars • Generators • i ... • Relay 2 is primary protection and provides

Time-delay overcurrent relay for line

• Detect overcurrent – Wait delay time T(I) – Trip CB

• Fuses also have 1/t characteristic– Easy to co-ordinate inverse time relays with fuses

30EIEN15 Electric Power Systems L3

Time

Relative overcurrent

1

Trip Inverse 1/t characteristic

Page 31: Symmetrical fault and protection Olof Samuelsson - IEA€“ Transmission lines: ... transformers, lines, busbars • Generators • i ... • Relay 2 is primary protection and provides

Example: Co-ordination radial system

CB1

CB2Load1

Load2

R2

•ISC increases when approaching source•R1 has higher current setting than R2

Time

Relative overcurrent

R1R2

31EIEN15 Electric Power Systems L3

R1

Page 32: Symmetrical fault and protection Olof Samuelsson - IEA€“ Transmission lines: ... transformers, lines, busbars • Generators • i ... • Relay 2 is primary protection and provides

» R1 and R2 detect overcurrent

– Delay of R2 smallest

» R2 operates CB2 first

– Isolates fault + Load 2

– No overcurrent R1 reset

– Fault clearing selective» If R2 or CB2 fails

– R1 not reset

– Extra delay of R1 before it operates CB1

– Isolates fault + Load 2 but also Load 1

– Fault clearing non-selective

Example: Fault in radial system

CB1

CB2L1

Load2

R2

Time

Current

R1R2

32EIEN15 Electric Power Systems L3

R1

Page 33: Symmetrical fault and protection Olof Samuelsson - IEA€“ Transmission lines: ... transformers, lines, busbars • Generators • i ... • Relay 2 is primary protection and provides

» Both F1 and F2 detect overcurrent

» Delay of F2

» Fuse F2 blows first

– Isolates fault and Me

– Selective fault clearing

» If fuse F2 fails

– Extra delay of F1

– F1 blows

– Isolates fault + Me but also Neighbor

– Non-selective fault clearing

Fault in radial system: At home

Me

F1

F2

Time

Current

F1F2

Neighbor

F3

33EIEN15 Electric Power Systems L3

Page 34: Symmetrical fault and protection Olof Samuelsson - IEA€“ Transmission lines: ... transformers, lines, busbars • Generators • i ... • Relay 2 is primary protection and provides

Co-ordination (Sw. selektivplanering)

Relays 1 and 2 coordinated in example:For the line,• Relay 2 is primary protection and provides selective fault

clearing (Sw: selektiv felbortkoppling)• Relay 1 is backup protection and provides non-selective

fault clearing (Sw: reservbortkoppling)Always true (regardless of I) since t(I) curves do not cross

Rule: Longer delay close to source

34EIEN15 Electric Power Systems L3

Page 35: Symmetrical fault and protection Olof Samuelsson - IEA€“ Transmission lines: ... transformers, lines, busbars • Generators • i ... • Relay 2 is primary protection and provides

Line fed from both ends

– Rule not applicable due to many sources– Use directional relays:

» R1 and R3 only trip for fault to their right

» R2 and R4 only trip for fault to their left

– Direction is obtained from phase difference of V and I measured by relay

GGR1 R2 R3 R4

35EIEN15 Electric Power Systems L3

Page 36: Symmetrical fault and protection Olof Samuelsson - IEA€“ Transmission lines: ... transformers, lines, busbars • Generators • i ... • Relay 2 is primary protection and provides

Impedance relay

Let relay measure V/I=Z=R+jXNormally load makes Z > Zline (Think Thévenin!)Fault on line makes Z < Zline TRIP!

36EIEN15 Electric Power Systems L3

Trip

R

X

Radius=|Zline |

Page 37: Symmetrical fault and protection Olof Samuelsson - IEA€“ Transmission lines: ... transformers, lines, busbars • Generators • i ... • Relay 2 is primary protection and provides

Impedance relay types

37EIEN15 Electric Power Systems L3

Trip

R

X

Trip

R

X

Directional Admittance or “MHO”Trip limit a certain admittance

Zline

Page 38: Symmetrical fault and protection Olof Samuelsson - IEA€“ Transmission lines: ... transformers, lines, busbars • Generators • i ... • Relay 2 is primary protection and provides

Distance protection (Sw. distansskydd)

– Series impedance ~ distance along line– |Z|<0.8|Zline| equivalent to

» Zero fault within 80% of line length

» The reach of the relay is 80%

38EIEN15 Electric Power Systems L3

Page 39: Symmetrical fault and protection Olof Samuelsson - IEA€“ Transmission lines: ... transformers, lines, busbars • Generators • i ... • Relay 2 is primary protection and provides

Distance protection zones

– Zone 1 relay at A, Primary: 80%, no delay– Zone 2 relay at A, Backup 1: 120%, delay– Zone 3 relay at A, Backup 2: 120+100%, longer delay

39EIEN15 Electric Power Systems L3

GGA B C D

Distance

Time

Zone 1

Zone 2

Zone 3

Page 40: Symmetrical fault and protection Olof Samuelsson - IEA€“ Transmission lines: ... transformers, lines, busbars • Generators • i ... • Relay 2 is primary protection and provides

Time

Distance

Distance protection coordination

• Shown faultPrimary protection from Zone 1 at C and D Backup protection from Zone 3 at A

40EIEN15 Electric Power Systems L3

GA B C D

Distance

Time

Page 41: Symmetrical fault and protection Olof Samuelsson - IEA€“ Transmission lines: ... transformers, lines, busbars • Generators • i ... • Relay 2 is primary protection and provides

Protection system performance

High “dependability”– Always isolate targeted fault– High sensitivity good

High “security”– Only react to targeted faults– High sensitivity bad

Fast– Good for (transient) stability– Safety

41EIEN15 Electric Power Systems L3

Compromise

Page 42: Symmetrical fault and protection Olof Samuelsson - IEA€“ Transmission lines: ... transformers, lines, busbars • Generators • i ... • Relay 2 is primary protection and provides

When lights go out in radial system

2a. An upstream fuse/relay detects fault

42EIEN15 Electric Power Systems L3

1. A fault occurs. Voltages go low or zero.

2b. Fuse or breaker isolates downstream system.Voltage of unfaulted parts recover.

4. Automatic reclosing after delay (successful if fault not permanent) or manual replacement of fuseVoltage of faulted parts recover.

3. Fault is removed

(Youtube blackout sandy jersey city)

Page 43: Symmetrical fault and protection Olof Samuelsson - IEA€“ Transmission lines: ... transformers, lines, busbars • Generators • i ... • Relay 2 is primary protection and provides

Short-circuit transients

43EIEN15 Electric Power Systems L3

R L

SW

i(t)

E(t) 2E sin(t )

Usually transients are steps and sinusoids are stationary…

AC power system (equivalent)

SW closes at t=0Determine i(t)

Page 44: Symmetrical fault and protection Olof Samuelsson - IEA€“ Transmission lines: ... transformers, lines, busbars • Generators • i ... • Relay 2 is primary protection and provides

R-L transients – Math

44EIEN15 Electric Power Systems L3

L di(t)dt

Ri(t) 2E sin(t ) with i(0) 0

iAC(t) 2EZ

sin(t )

i(t) istationary(t) itransient (t) iAC(t) iDC(t)

iDC(t) 2EZ

sin( )e

tT

RLTRLLRZ / );/(tan ;)( 122

Page 45: Symmetrical fault and protection Olof Samuelsson - IEA€“ Transmission lines: ... transformers, lines, busbars • Generators • i ... • Relay 2 is primary protection and provides

R-L transients – Power eng.

Avoid dependence– Use worst case: =(-/2)

Avoid instantaneous values– Use rms: IAC=E/Z– Treat IDC as constant

– where is time in cycles

45EIEN15 Electric Power Systems L3

IRMS(t) IAC2 IDC (t) 2 IAC

2 2IACe t /T 2

IAC 1 2e2 t /T 2tT 2

f RL 4

X / R

iDC(t) 2EZ

e

tT

K()

Page 46: Symmetrical fault and protection Olof Samuelsson - IEA€“ Transmission lines: ... transformers, lines, busbars • Generators • i ... • Relay 2 is primary protection and provides

Exponential component

• Depends on initial condition• Different in the three phases

– Asymmetrical current• Slow decay for high L/R (low losses)• Increases peak current

– IRMS up to IAC

46EIEN15 Electric Power Systems L3

3

Page 47: Symmetrical fault and protection Olof Samuelsson - IEA€“ Transmission lines: ... transformers, lines, busbars • Generators • i ... • Relay 2 is primary protection and provides

Summary

• Compute short-circuit fault current with…• Circuit breaker is used for…• Disconnector is used for…• Fault clearing system includes protective relay with

– Sensors:…– Actuator:…

• 3 protection types:…, …, …• Backup protection acts after delay if … protection fails• Deenergizing minimum area = … fault clearing• S-C current transient = ….. + …..

47EIEN15 Electric Power Systems L3

Page 48: Symmetrical fault and protection Olof Samuelsson - IEA€“ Transmission lines: ... transformers, lines, busbars • Generators • i ... • Relay 2 is primary protection and provides

Summary

• Compute short-circuit fault current with Thévenin equivalent• Circuit breaker is used for interrupting fault current• Disconnector is used for interrupting load current or less• Fault clearing system includes protective relay with

– Sensors: Current and voltage/potential transformers– Actuator: Circuit breaker

• 3 protection types: differential, overcurrent, distance protection• Backup protection acts after delay if primary protection fails• Deenergizing minimum area = selective fault clearing• S-C current transient = sinusoidal AC + expontial DC

48EIEN15 Electric Power Systems L3

Page 49: Symmetrical fault and protection Olof Samuelsson - IEA€“ Transmission lines: ... transformers, lines, busbars • Generators • i ... • Relay 2 is primary protection and provides