H
T
S
S
B
M
?
HWR
HWS
HPR
D
CD
HPS
MV
AV
F
P
UC 1"
SYMBOLABBREVIATIONS DESCRIPTION
REFERENCE SYMBOLS
SYMBOL DESCRIPTION
PIPING DESIGNATIONS
MECHANICAL GENERAL NOTESMECHANICAL LEGEND AND ABBREVIATIONS
KEY NOTE DESIGNATION
REVISION DESIGNATION
ACCESS DOORA.D.
SPLIT ELBOW WITH TURNING VANES
RECTANGULAR ELBOW WITH TURNING VANES
RECTANGULAR BRANCH FROM RECTANGULAR DUCT
RECTANGULAR TO RECTANGULAR TRANSITION
TRANSITION (RISE OR DROP) IN DUCT ELEVATION IN
RECTANGULAR BRANCH FROM RECTANGULAR DUCT
RECTANGULAR TO RECTANGULAR TRANSITION
DIRECTION OF AIR FLOW
COMBINATION FIRE & SMOKE DAMPER
DUCT MOUNTED SMOKE DETECTOR
EXHAUST AIR GRILLE/REGISTER
RIGID DUCTWORK TERMINATION
RETURN AIR GRILLE/REGISTER
DOOR UNDERCUT WITH HEIGHT
MANUAL VOLUME DAMPER
EXHAUST AIR DUCT DOWN
RECTANGULAR ELBOW WITHOUT TURNING VANES
RECTANGULAR ELBOW WITH TURNING VANES
FLEXIBLE CONNECTION
LINEAR DIFFUSER
RADIUS ELBOW
SINGLE LINE DUCTWORK
ACCESS PANEL
SUPPLY AIR DIFFUSER
SPIN-IN FITTING
MOTORIZED DAMPER
SPIN-IN FITTING W/MVD
BACKDRAFT DAMPER
ROUND ELBOW
SUPPLY AIR DUCT DOWN
RETURN AIR DUCT DOWN
RETURN AIR DUCT UP
SUPPLY AIR DUCT UP
EXHAUST AIR DUCT UP
TEMPERATURE SENSOR
HUMIDISTAT
THERMOSTAT
SMOKE DAMPER
DIRECTION OF FLOW
FLEXIBLE DUCTWORK
FIRE DAMPER
SUPPLY AIR
RETURN AIR
R
D
RECTANGULAR TO ROUND TRANSITION
POINT OF CONNECTION OF NEW TO EXISTING
ENLARGED PLAN DESIGNATION
NORTH ARROW
EXHAUST AIR / OUTSIDE AIR RISER DESIGNATION
WATER RISER DESIGNATION
BASEBOARD RADIATION TAG / PLENUM LENGTH TAG
AIR DEVICE DESIGNATION
EQUIPMENT DESIGNATION
ITEM TO DEMOLISH
HEAT PUMP LOOP WATER RETURN
FLEXIBLE PIPE CONNECTION
PIPE SLEEVE
PIPE CAP
HEAT PUMP LOOP WATER SUPPLY
PRESSURE GAUGE W/ GAUGE COCK
TEMPERATURE & PRESSURE TEST PLUG
HEAT TRACE
PRESSURE SWITCH
FLOW SWITCH
PIPE DROP
PIPING RISER
THERMOMETER
STRAINER W/ BLOWOFF VALVE
AUTOMATIC AIR VENT
TEMPERATURE CONTROL VALVE 3-WAY
TEMPERATURE CONTROL VALVE 2-WAY
PRESSURE REDUCING VALVE
HOSE END DRAIN VALVE
GAS COCK
IN-LINE PUMP
SOLENOID VALVE
T&P RELIEF VALVE
MANUAL AIR VENT
BALANCING VALVE
BUTTERFLY VALVE
SWING CHECK VALVE
GATE VALVE
GLOBE VALVE
BALL VALVE
UNION
DRAIN
HEATING WATER SUPPLY
HEATING WATER RETURN
CONDENSATE DRAIN
FLOW METER FITTING
P.O.C.
FOB
FOT
(E)
(N)
AP
UC
BDD
MD
MVD/VD
POINT OF CONNECTION OF NEW TO EXISTING
EXISTING
FLAT ON TOP TRANSITION
FLAT ON BOTTOM TRANSITION
BACKDRAFT DAMPER
MOTORIZED DAMPER
ACCESS PANEL
MANUAL VOLUME DAMPER
DOOR UNDERCUT WITH HEIGHT
COMBINATION FIRE & SMOKE DAMPER
RETURN AIRRA
EA EXHAUST AIR
SA
HSTAT
FSD
TSTAT
FD
SD
FLEX
HUMIDISTAT
SUPPLY AIR
FIRE DAMPER
FLEXIBLE DUCTWORK
SMOKE DAMPER
THERMOSTAT
PRESSURE GAUGE W/ GAUGE COCK
TEMPERATURE & PRESSURE TEST PLUG
U
FC
D
UNION
FLEXIBLE CONNECTION
DRAIN
PG
FS
PS
TP
FLOW SWITCH
PRESSURE SWITCH
PRESSURE REDUCING VALVEPRV
GC
AV
MV
T&P
GAS COCK
AUTOMATIC AIR VENT
MANUAL AIR VENT
T&P RELIEF VALVE
NEW
POINT OF DISCONNECTP.O.D.
DN DOWN
HEAT PUMP LOOP WATER RETURN
HEAT PUMP LOOP WATER SUPPLY
HPR
HPS
HEATING WATER SUPPLY
HEATING WATER RETURN
HWS
HWR
ABOVE FINISH FLOORAFF
AIR HANDLING UNITAHU
CUBIC FEET PER MINUTECFM
CLEAN OUTCO
CONDENSATE DRAINCD
DRY BULBDB
DRAWINGDWG
ENTERING AIR TEMPERATUREEAT
ELECTRICAL CONTRACTOREC
ENTERING WATER TEMPERATUREEWT
FLOORFLR
GENERAL CONTRACTORGC
GALLONS PER MINUTEGPM
LEAVING AIR TEMPERATURELAT
LEAVING WATER TEMPERATURELWT
MAKE-UP AIR UNITMAU
MIXED AIRMA
MIXED AIR TEMPERATUREMAT
THOUSAND BRITISH THERMAL UNITSMBH
MECHANICAL CONTRACTORMC
NORMALLY CLOSEDN.C.
NORMALLY OPENN.O.
NOT TO SCALENTS
OUTSIDE AIROA, OSA
OUTSIDE AIR TEMPERATUREOAT
OPPOSED BLADE DAMPEROBD
PLUMBING CONTRACTORPC
STATIC PRESSURESP
TRANSFER AIRTA
TYPICALTYP
WET BULBWB
HEAT PUMPHP
FAN COIL UNITFCU
EXHAUST FANEF
PERCENT RELATIVE HUMIDITY%RH
?
???
?
???
?
???
X
X
XSIZE
CFM
??
LENGTH
TAG
TAG
1. ALL WORK SHALL COMPLY WITH THE LATEST ADOPTED STATE AND
LOCAL CODES, AS WELL AS FEDERAL, STATE, AND MUNICIPAL
REGULATIONS.
THE MECHANICAL CONTRACTOR IS RESPONSIBLE FOR COORDINATING
ALL WORK UNDER THIS CONTRACT WITH ALL OTHER BUILDING TRADES.
NOTIFY THE ARCHITECT OF ALL DISCREPANCIES OR QUESTIONS
PERTAINING TO EXTENT OF WORK PRIOR TO BIDDING.
THE WORK REQUIRED CONSISTS OF PERFORMING ALL LABOR AND
FURNISHING ALL MATERIALS, DEVICES AND EQUIPMENT REQUIRED TO
PROVIDE A COMPLETE INSTALLATION OF ALL MECHANICAL SYSTEMS AS
INDICATED IN THE CONTRACT DOCUMENTS. IT SHALL FURTHER INCLUDE
FURNISHING AND INSTALLING ALL ASSOCIATED ITEMS REQUIRED FOR THE
PROPER OPERATION OF ALL MECHANICAL SYSTEMS.
THE INFORMATION INDICATED WITHIN THESE DRAWINGS IS DIAGRAMMATIC
IN NATURE, CONTAINING INFORMATION TO A DEGREE OF DETAIL
CONSISTENT WITH THEIR SCALE, ADEQUATE TO CONVEY THE DESIGN
INTENT AND THEREFORE DOES NOT INDICATE EVERY REQUIRED OFFSET,
FITTING OR SLOPE. PROVIDE EQUIPMENT, MATERIALS AND METHODS NOT
SHOWN OR SPECIFIED BUT REQUIRED TO PROVIDE A COMPLETE AND
COORDINATED INSTALLATION.
THE CONTRACTOR IS RESPONSIBLE FOR VERIFICATION OF ALL FIELD
DIMENSIONS, LOCATIONS AND CONDITIONS PRIOR TO THE INSTALLATION
OF ANY MATERIALS AND COMMENCEMENT OF WORK. NOTIFY THE
ARCHITECT OF ALL DISCREPANCIES THAT WILL AFFECT THE WORK FOR
RESOLUTION.
EQUIPMENT, DEVICES AND MATERIALS SHOWN ON DRAWINGS ARE BASED
ON MANUFACTURER'S PUBLISHED DATA, AND ARE, IN THE DESIGNER'S
PROFESSIONAL OPINION, REPRESENTATIVE OF TYPICAL SIZES. ALL
EQUIPMENT, DEVICES AND MATERIALS PROVIDED SHALL FIT WITHIN THE
SPACE PROVIDED.
ALL EQUIPMENT AND SERVICEABLE DEVICES SHALL BE INSTALLED WITH
ACCESS AND CLEARANCE FOR MAINTENANCE, REPLACEMENT AND/OR
USE. COORDINATE WITH THE GENERAL CONTRACTOR AND OTHER TRADES
TO PROVIDE THIS ACCESS AND CLEARANCE. INSTALL ALL EQUIPMENT,
DEVICES AND MATERIALS PER MANUFACTURER’S INSTRUCTIONS.
IF EQUIPMENT, DEVICES AND MATERIALS, OTHER THAN THOSE SCHEDULED
OR SPECIFIED, ARE APPROVED AND PROVIDED, IT IS THE
RESPONSIBILITY OF THE CONTRACTOR TO COORDINATE AND PROVIDE
REVISED UTILITIES AND SERVICE CONNECTIONS AND VERIFY THE SPACE
ALOTTED IS ADEQUATE TO MAINTAIN THE CLEARANCE REQUIREMENTS
REQUIRED BY THE MANUFACTURER AND FOR ACCESS AND
MAINTAINABILITY AS INDICATED ON THE CONSTRUCTION DOCUMENTS.
PROVIDE STARTERS FOR ALL EQUIPMENT UNLESS SPECIFICALLY
IDENTIFIED AS BEING PROVIDED BY THE ELECTRICAL CONTRACTOR.
WHERE DUCTS PASS THROUGH FIRE-RATED CONSTRUCTION, PROVIDE
DAMPER AND SEAL WITH CODE REQUIRED MATERIALS. WHERE PIPES
PASS THROUGH FIRE-RATED CONSTRUCTION, SEAL WITH CODE REQUIRED
MATERIALS. REFER TO ARCHITECTURAL DRAWINGS FOR LOCATION OF
ALL FIRE RATED CONSTRUCTION.
ACCESS DOORS AND/OR PANELS SHALL BE PROVIDED AT ALL
MAINTENANCE AND SERVICE LOCATIONS FOR CONCEALED EQUIPMENT,
VALVES, DAMPERS AND DEVICES. UNLESS A SIZE IS SPECIFICALLY
NOTED, PANELS SHALL BE SIZED TO SERVICE EQUIPMENT/DEVICE BUT
SHALL NOT BE LESS THAN 12” x 12”. DOORS AND PANELS SHALL HAVE
THE SAME FIRE RATING AS THE WALL OR CEILING IN WHICH THEY ARE
INSTALLED. ACCESS DOORS AND/OR PANELS ARE NOT REQUIRED
WHERE ADJUSTMENT, MAINTENANCE AND REPLACEMENT ARE POSSIBLE
THROUGH LAY-IN SUSPENDED CEILING.
INSULATION AND VAPOR BARRIER SHALL BE PROVIDED ON ALL PIPING
AND EQUIPMENT SUBJECT TO HEAT LOSS, CONDENSATION, OR
CONSTITUTING A POTENTIAL BURN HAZARD.
PIPE, DUCT AND EQUIPMENT INSULATION SHALL NOT BE CRUSHED OR
COMPRESSED THROUGH INTERFERENCE WITH SYSTEMS INSTALLED BY
OTHER TRADES OR BUILDING CONSTRUCTION.
ALL PIPING SHALL BE INSTALLED IN SUCH A MANNER AS TO AVOID
FREEZING. NO PIPING SHALL BE INSTALLED WITHIN EXTERIOR WALLS
EXCEPT AT CONDENSATE TERMINATION POINTS.
ROUTE ALL CONDENSATE ABOVE CEILING AS HIGH AS POSSIBLE.
PROVIDE CONDENSATE PUMP WHERE GRAVITY SLOPED PIPING IS NOT
POSSIBLE.
ALL FINISHED CONSTRUCTION AND/OR EXISTING BUILDING AND SITE
FEATURES NOT BEING ALTERED BY THIS PROJECT ARE TO BE
PROTECTED FROM DAMAGE. CONTRACTOR SHALL REPAIR ALL
DAMAGE OCCURING TO FINISHED AND/OR EXISTING CONSTRUCTION
CAUSED BY THE CONTRACTOR’S OPERATIONS AT HIS/HER EXPENSE TO
THE COMPLETE SATISFACTION OF THE OWNER.
ALL DUCTWORK SIZES ARE CLEAR INSIDE DIMENSIONS. INCREASE
DUCTWORK SIZE FOR ACOUSTICAL LINER WHERE SPECIFIED.
ALL SPIN-IN FITTINGS SHOWN ARE TO BE INSTALLED PER SMACNA AND
MANUFACTURER'S RECOMMENDATIONS. ALL DUCTWORK IS TO BE OF
SHEEETMETAL CONSTRUCTION PER SMACNA STANDARDS FOR LOW AND
MEDIUM PRESSURE DISTRIBUTION.
ALL MECHANICAL SYSTEMS SHALL BE TESTED, BALANCED, AND
ADJUSTED. COORDINATE AND PROVIDE BALANCING DEVICE
REQUIREMENTS WITH TEST AND BALANCE SERVICE TO ASSURE ADEQUATE
DAMPERS AND VALVES ARE PROVIDED FOR FLOW CONTROL.
MECHANICAL CONTRACTOR TO PROVIDE ALL MANUAL VOLUME
DAMPERS WHERE SHOWN ON DRAWINGS AND WHERE REQUESTED BY
BALANCING CONTRACTOR TO PROVIDE A COMPLETE AND FUNCTIONING
SYSTEM.
ALL ELBOWS IN RECTANGULAR SUPPLY DUCTS SHALL HAVE TURNING
VANES OR SHALL BE RADIUSSED.
DUCT CONNECTION TO EQUIPMENT SHALL BE FABRICATED AFTER
EQUIPMENT HAS BEEN SET IN PLACE AND DIMENSIONS VERIFIED.
ALL BRANCH DUCTWORK AND FLEX TO INDIVIDUAL DIFFUSERS SHALL BE
THE SAME SIZE AS THE NECK OF THE DIFFUSER UNLESS OTHERWISE NOTED.
COORDINATED DIFFUSER AND GRILLE PLACEMENT IS SHOWN ON THE
P400 SERIES DRAWINGS AND ARCHITECTURAL REFLECTED CEILING
PLANS. COORDINATE DIFFUSER AND GRILLE PLACEMENT WITH LIGHTING
AND OTHER CEILING DEVICE INSTALLATIONS FOR A CONSISTENT,
FUNCTIONAL AND SYMMETRICAL PATTERN.
MOUNT ALL THERMOSTATS WITH TOP OF THERMOSTAT AT 48 INCHES
ABOVE FINISH FLOOR.
MAINTAIN ONE SET OF RED-LINED AS-BUILT DRAWINGS ON JOB SITE.
SUBMIT TO ARCHITECT AT THE COMPLETION OF ALL WORK.
FLEXIBLE DUCTWORK MAXIMUM LENGTH SHALL NOT EXCEED 8’-0”.
BALANCING CONTRACTOR SHALL CALIBRATE ALL THERMOSTATS AND
SENSORS AT THE COMPLETION OF THE PROJECT.
PROVIDE NOISE AND VIBRATION ISOLATION FOR ALL EQUIPMENT.
PROVIDE FLEX CONNECTIONS AT ALL INLET AND OUTLET DUCT
CONNECTIONS.
ALL INSULATION SHALL MEET THE TEMPERATURE AND SMOKE RATINGS AS
REQUIRED BY NFPA FOR THE INTENDED USE.
COORDINATE ALL DUCTWORK, DEVICE, PIPING AND EQUIPMENT
LOCATIONS WITH GENERAL CONTRACTOR PRIOR TO STARTING ANY
WORK. COORDINATE WITH GENERAL CONTRACTOR, AND ALL TRADES,
ALL REQUIREMENTS FOR INSTALLATION, INCLUDING SERVICE UTILITY
CONNECTIONS, POINT LOADS, CHASES, SLEEVES, SUPPORTING DEVICES,
OPENINGS AND CUT-OUTS, AND PENETRATIONS OF WALLS, CEILINGS OR
SHAFTS.
(THESE NOTES APPLY TO ALL MECHANICAL DRAWINGS)
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
21.
22.
23.
24.
25.
26.
27.
28.
29.
30.
PR
INT
DA
TE
:
FIL
E IN
FO
:
PROGRESSDRAWINGNOT FOR
CONSTRUCTION
for
PSU# 09-12181.00 PSU Building # 0804-000
Keyplan
APArchitects, LLCAssociate ArchitectThe EDGE GroupLandscape ArchitectSweetland EngineeringCivil EngineerKORDA EngineeringStructural Engineer
Reese EngineeringMEP EngineerCD+M Lighting Design GroupLighting DesignerCode Consultants, IncCode ConsultantRider Levett BucknallCost Estimator
Phone: (614) 461-4664
Fax: (614) 280-8881
300 Spruce Street
Suite 300
Columbus, Ohio 43215 www.moodynolan.com
DRAWN BY: CHECKED BY: APPROVED BY:
9/7
/20
12 1
0:3
1:2
3 A
M
C:\U
sers
\dcarlson\D
ocum
ents
\20
101
59_M
EP
_dcarlson.r
vt
11279.00
9/7/2012
IM BUILDING ADDITION AND RENOVATION
THE PENNSYLVANIASTATE UNIVERSITY
50% Construction Documents
University Park, Pennsylvania 16802
Mechanical Legend AndGeneral Notes
M001
N.J.B. J.K.G. J.K.G.
# Date Change Description
T
T
T
T
T
KEY NOTES
GENERAL NOTES (THIS SHEET ONLY)
1
PROVIDE FIRE�RATED DAMPERS AT ALL DUCT PENETRATIONS OF
FIRE�RATED CONSTRUCTION. RE: ARCHITECTURAL DRAWINGS FOR
RATED CONSTRUCTION INFORMATION.
A.
HORIZONTAL, CONCEALED FAN COIL UNIT INSTALLED ABOVE CEILING
WITH VIBRATION ISOLATION. PROVIDE CDP�1 WITH 3/4" CD PIPING
ROUTED TO NEAREST JANITOR'S CLOSET. TERMINATE PIPING WITH 2"
AIR GAP OVER FLOOR DRAIN. INTERLOCK FCU�1 COOLING CONTROL
WITH (E) RE�HEAT COIL HEATING VALVE SERVING THIS SPACE TO
PREVENT SIMULTANEOUS HEATING/COOLING.
WALL�MOUNTED, HORIZONTAL SPLIT�SYSTEM INSTALLED AS HIGH AS
POSSIBEL IN SPACE. PROVIDE CDP�1 WITH 3/4" CD PIPING ROUTED
TO FLOOR DRAIN IN ADJACENT MECHANICAL ROOM. TERMINATE
PIPING WITH 2" AIR GAP.
(N) 24x6 EA UP TO LEVEL ABOVE.
INSTALL 8x8 TYPE 'C' EXHAUST GRILLE AND 6"ø TYPE 'B' SUPPLY
DIFFUSER IN (N) CEILING. EXTEND DUCT BRANCHES DOWN TO (N)
CEILING HEIGHT. BALANCE TO 110CFM AND 75 CFM, RESPECTIVELY.
40x20
20x12 24x12
24x12
14x12
20x16
16"ø
16"ø
20
x16
28x14
Mechanical
M004
Storage
005
Lower Level Hall �South
C000
ElevatorEquipment
M008
Women'sRestroom
007
Storage
009A
MultipurposeRoom
009
Classroom
010
Lower Level Hall �East
C001
Stair 01
Z001
Adaptive PE
011
Storage
003
A10"ø
0
���D
22x10
A10"ø
0
B8"ø
0���
E22x10
A10"ø
0
A10"ø
0
���D
22x10
(TYP. 2)
Family Restroom
001
40x20
UHT�1
2
Lower Level Hall �West
203D
A10"ø
0(TYP. 4)
A10"ø
0(TYP. 9)
56x16
VAV�1
VAV�4
VAV�3
VAV�2
16x16
56x16
22"ø
18"ø 16"ø
56x16
20x12 10x8
20x10
ACF�1
4
3
FCU�1
A10"ø
0(TYP. 3)
���D
22x22
1
H10"ø
0(TYP. 10)
C24x24
0
C12x12
0
C24x24
1000
24x6
3
C18x18
1000
4
CRAC�1 2
2 CRAC�1
CDP�1
CDP�1
CDP�1
PR
INT
DA
TE
:
FIL
E IN
FO
:
PROGRESSDRAWINGNOT FOR
CONSTRUCTION
for
PSU# 09 12181.00 PSU Building # 0804 000
Keyplan
BASEMENT
APArchitects, LLCAssociate ArchitectThe EDGE GroupLandscape ArchitectSweetland EngineeringCivil EngineerKORDA EngineeringStructural Engineer
Reese EngineeringMEP EngineerCD+M Lighting Design GroupLighting DesignerCode Consultants, IncCode ConsultantRider Levett BucknallCost Estimator
Phone: (614) 461 4664
Fax: (614) 280 8881
300 Spruce Street
Suite 300
Columbus, Ohio 43215 www.moodynolan.com
DRAWN BY: CHECKED BY: APPROVED BY:
9/7
/2012 3
:24:0
8 P
M
C:\U
sers
\ssnyder\
Docum
ents
\2010159_M
EP
_ssnyder.
rvt
11279.00
9/7/2012
IM BUILDING ADDITION AND RENOVATION
THE PENNSYLVANIASTATE UNIVERSITY
50% Construction Documents
University Park, Pennsylvania 16802
Basement Level MechanicalPlan
M111
N.J.B. J.K.G. J.K.G.M111 SCALE: 1/8" = 1'�0"
1 BASEMENT LEVEL MECHANICAL PLAN
# Date Change Description
T
T
T
T
T
T
T
T
TT
T
T
T
T
T
KEY NOTES
GENERAL NOTES (THIS SHEET ONLY)
1
PROVIDE FIRE�RATED DAMPERS AT ALL DUCT PENETRATIONS OF
FIRE�RATED CONSTRUCTION. RE: ARCHITECTURAL DRAWINGS FOR
RATED CONSTRUCTION INFORMATION.
A.
ALL DUCTWORK, PIPING, AND ACCESSORIES ABOVE THE CEILING
PANEL LEVEL TO BE PAINTED WHITE.
(N) 24x6 EA DUCT UP TO LEVEL ABOVE.
14x12
46x12
18x1236x12
14x12
14x12
14x12
46x12
MultipurposeRoom
124
MultipurposeRoom
125
Storage
124A
Storage
123
Corridor
C104
Storage
126
Corridor
C104
Main Level Hall
C113
Day Lockers
121
Stair 03
Z103 EquipmentCheckout
129
Vending
104
Storage
125A
Janitor
J127
Women'sRestroom
R127
Men's Restroom
R128
Office
101B
Office
101A
Offices
101
Break Room
101D
Office
101E
Office
101F
Office
101G
Office
101H
Office
101J
Office
101K
Director
101L
Workroom
101N
Conference Room
101M
Electric
P102
A B
Elevator
V101
A10"ø
0(TYP. 3)
A10"ø
0
A10"ø
0
A10"ø
0
A10"ø
0A
10"ø
0
A10"ø
0
���E
22x10
���E
22x10
���E
22x10
���E
22x10
���E
22x10
���E
22x10
A10"ø
0(TYP. 3)
A10"ø
0
A10"ø
0(TYP. 5)
���E
22x10
A10"ø
0
A10"ø
0
���D
22x10
���E
22x10
A10"ø
0
C18x18
0
M
Stair 8
124B60x18 60x18
60x18
24x20
24x20
M
H10"ø
300(TYP. 12)
16"ø 16"ø
24"ø
24"ø
20
"ø
16"ø
20"ø
1
1
H10"ø
300(TYP. 12)
BA
VAV�516x20 24x20 24x20 16x20
���E
22x10
VAV�6
10x12
12x10
16x16
16x16
���E
22x10
���E
22x10
���E
22x10
14x12
VAV�11 VAV�25
12"ø A10"ø
0(TYP. 2)
VAV�13
J48x12
0(TYP. 2)
14x12
14x12
VAV�14
VAV�18
VAV�17
VAV�12
A10"ø
0(TYP. 5)
A10"ø
0(TYP. 2)
14x12
VAV�10
10x12
J48x12
0(TYP. 2)
���D
22x10
VAV�9
���D
22x22
(TYP. 4)
VAV�16
M M
���E
22x10
VAV�8
���E
22x10
C18x18
0(TYP. 2)
2
2
PR
INT
DA
TE
:
FIL
E IN
FO
:
PROGRESSDRAWINGNOT FOR
CONSTRUCTION
for
PSU# 09'12181.00 PSU Building # 0804'000
Keyplan
A
APArchitects, LLCAssociate ArchitectThe EDGE GroupLandscape ArchitectSweetland EngineeringCivil EngineerKORDA EngineeringStructural Engineer
Reese EngineeringMEP EngineerCD+M Lighting Design GroupLighting DesignerCode Consultants, IncCode ConsultantRider Levett BucknallCost Estimator
Phone: (614) 461'4664
Fax: (614) 280'8881
300 Spruce Street
Suite 300
Columbus, Ohio 43215 www.moodynolan.com
DRAWN BY: CHECKED BY: APPROVED BY:
9/7
/2012 3
:24:2
4 P
M
C:\U
sers
\ssnyder\
Docum
ents
\2010159_M
EP
_ssnyder.
rvt
11279.00
9/7/2012
IM BUILDING ADDITION AND RENOVATION
THE PENNSYLVANIASTATE UNIVERSITY
50% Construction Documents
University Park, Pennsylvania 16802
Main Level Mechanical Plan 'Area A
M121
N.J.B. J.K.G. J.K.G.M121 SCALE: 1/8" = 1'�0"
1 MAIN LEVEL MECHANICAL PLAN � AREA A
# Date Change Description
T
T
T
T
T
T
KEY NOTES
GENERAL NOTES (THIS SHEET ONLY)
1
PROVIDE FIRE�RATED DAMPERS AT ALL DUCT PENETRATIONS OF FIRE�
RATED CONSTRUCTION. RE: ARCHITECTURAL DRAWINGS FOR RATED
CONSTRUCTION INFORMATION.
A.
CONTINUOUS SLOT DIFFUSER WITH 5'�0" BLANK�OFF SECTIONS
BETWEEN ACTIVE SECTIONS.
24x12
18x12
Lobby
F102
Control Desk
F103
Vestibule
F101
Landscape
41
Corridor
C104
Main Level Hall
C113
Corridor
C104
Stair 04
Z104
Fitness ControlDesk
F102a
Fitness
103
Fitness
103D
Lounge
C101
Stair 01
Z101
A/V/ Storage
103C
Fitness Office
103A
Stair 05
Z105
A B
BA
Corridor
103B
A10"ø
0
A10"ø
0
���E
22x10
CUH�1
Stair 02
Z102
60x18
44x16
40x16
44x16
44x16
40x16
VAV�15
14x12
F6"ø
0(TYP. 10)
14x12
J48x12
0(TYP. 2)
14x12
40x16
G60x4
0(TYP. 3)
L12"ø
0(TYP. 5)
L12"ø
0(TYP. 10)
L12"ø
0(TYP. 8)
L12"ø
0(TYP. 18)
44x16
44x16
12x12
12x12
G60x4
0(TYP. 18)
12x12
CUH�2
1 1
B6"ø
0
PR
INT
DA
TE
:
FIL
E IN
FO
:
PROGRESSDRAWINGNOT FOR
CONSTRUCTION
for
PSU# 09�12181.00 PSU Building # 0804�000
Keyplan
B
APArchitects, LLCAssociate ArchitectThe EDGE GroupLandscape ArchitectSweetland EngineeringCivil EngineerKORDA EngineeringStructural Engineer
Reese EngineeringMEP EngineerCD+M Lighting Design GroupLighting DesignerCode Consultants, IncCode ConsultantRider Levett BucknallCost Estimator
Phone: (614) 461�4664
Fax: (614) 280�8881
300 Spruce Street
Suite 300
Columbus, Ohio 43215 www.moodynolan.com
DRAWN BY: CHECKED BY: APPROVED BY:
9/7
/2012 3
:24:3
7 P
M
C:\U
sers
\ssnyder\
Docum
ents
\2010159_M
EP
_ssnyder.
rvt
11279.00
9/7/2012
IM BUILDING ADDITION AND RENOVATION
THE PENNSYLVANIASTATE UNIVERSITY
50% Construction Documents
University Park, Pennsylvania 16802
Main Level Mechanical Plan �Area B
M122
N.J.B. J.K.G. J.K.G.M122 SCALE: 1/8" = 1'�0"
1 MAIN LEVEL MECHANICAL PLAN � AREA B
# Date Change Description
T
18x18
28x14
18x16
34x30
60x40
26x20
34x20
26x20
86x28
28x14
28x14
18x16
46x12
40x20
KEY NOTES
GENERAL NOTES (THIS SHEET ONLY)
1
PROVIDE MOTORIZED DAMPERS FOR ALL DUCT CONNECTIONS TO
INTAKE/EXHAUST PLENUMS AT LOUVERS.
PROVIDE FIRE#RATED DAMPERS AT ALL DUCT PENETRATIONS OF FIRE#
RATED CONSTRUCTION. RE: ARCHITECTURAL DRAWINGS FOR RATED
CONSTRUCTION INFORMATION.
A.
(N) 24x6 EA DUCT UP AND CONNECTED TO (E) 24x6 IN ATTIC.
PROVIDE TWO ROWS OF THIS TYPE 'K' RETURN GRILLE (TOTAL OF
24" IN GRILLE HEIGHT) IN THE SOFFIT SIDEWALL ENCLOSING THE RA
DUCT FOR THE LENGTH LISTED.
PROVIDE 13 MOTORIZED DAMPERS BEHIND THIS RETURN GRILLE IN
THE SIDEWALL OF THE RETURN DUCT. DAMPERS TO BE 24" TALL
AND 48" WIDE.
PROVIDE 12 MOTORIZED DAMPERS BEHIND THIS RETURN GRILLE IN
THE SIDEWALL OF THE RETURN DUCT. DAMPERS TO BE 24" TALL
AND 48" WIDE.
Mechanical
M202
Track
201
Mezzanine HallLanding Elevator
C202
Workroom
203B
Landscape
43
Fitness
203
A B
BA
Elevator
V201
RAF#5
RAF#1
RAF#4
RAF#2
RAF#3EFN#1
B.
50x30
ACF#4
ACF#2
ACF#3
50
x30 28"ø
28"ø
28"ø
14"ø 10"øVAV#23
VAV#22
VAV#21
J20x6
0(TYP. 6)
A10"ø
0(TYP. 3)
68x36 68x36
VAV#26
J18x6
0(TYP. 4)
40x20
16x16
14x12
###K
868x242 2
###K
796x24
1
3 4
2
3
4
PR
INT
DA
TE
:
FIL
E IN
FO
:
PROGRESSDRAWINGNOT FOR
CONSTRUCTION
for
PSU# 09�12181.00 PSU Building # 0804�000
Keyplan
A
APArchitects, LLCAssociate ArchitectThe EDGE GroupLandscape ArchitectSweetland EngineeringCivil EngineerKORDA EngineeringStructural Engineer
Reese EngineeringMEP EngineerCD+M Lighting Design GroupLighting DesignerCode Consultants, IncCode ConsultantRider Levett BucknallCost Estimator
Phone: (614) 461�4664
Fax: (614) 280�8881
300 Spruce Street
Suite 300
Columbus, Ohio 43215 www.moodynolan.com
DRAWN BY: CHECKED BY: APPROVED BY:
9/7
/2012 3
:24:4
8 P
M
C:\U
sers
\ssnyder\
Docum
ents
\2010159_M
EP
_ssnyder.
rvt
11279.00
9/7/2012
IM BUILDING ADDITION AND RENOVATION
THE PENNSYLVANIASTATE UNIVERSITY
50% Construction Documents
University Park, Pennsylvania 16802
Mezzanine Level MechanicalPlan � Area A
M131
N.J.B. J.K.G. J.K.G.M131 SCALE: 1/8" = 1'#0"
1 MEZZANINE LEVEL MECHANICAL PLAN � AREA A
# Date Change Description
T
T T
KEY NOTES
GENERAL NOTES (THIS SHEET ONLY)
1
PROVIDE FIRE�RATED DAMPERS AT ALL DUCT PENETRATIONS OF
FIRE�RATED CONSTRUCTION. RE: ARCHITECTURAL DRAWINGS FOR
RATED CONSTRUCTION INFORMATION.
A.
PROVIDE TWO ROWS OF THIS TYPE 'K' RETURN GRILLE (TOTAL OF
24" IN GRILLE HEIGHT) IN THE SOFFIT SIDEWALL ENCLOSING THE RA
DUCT FOR THE LENGTH LISTED.
PROVIDE 20 MOTORIZED DAMPERS BEHIND THIS RETURN GRILLE IN
THE SIDEWALL OF THE RETURN DUCT. DAMPERS TO BE 24" TALL
AND 48" WIDE.
WALL�MOUNTED, HORIZONTAL SPLIT�SYSTEM INSTALLED AS HIGH AS
POSSIBEL IN SPACE. PROVIDE CDP�1 WITH 3/4" CD PIPING ROUTED
DOWN TO LEVEL BELOW AND OUT TO EXTERIOR. TERMINATE WITH
COPPER ELBOW AT 12" AFG.
Mezzanine HallLanding East Stair
C201
Track
201
Fitness
203
Fitness
203
A B
BA
Stair 05
Z205
Telecom
203A
68x36
28"ø
68x36 10x10
28"ø
28"ø28"ø
28"ø
28"ø
28"ø
28"ø
28"ø
28"øJ
20x6
0(TYP. 8)
J20x6
0(TYP. 14)
J20x6
0(TYP. 9)
���K
1306x241
2
2
CRAC�1
CDP�1
3
3
PR
INT
DA
TE
:
FIL
E IN
FO
:
PROGRESSDRAWINGNOT FOR
CONSTRUCTION
for
PSU# 09�12181.00 PSU Building # 0804�000
Keyplan
B
APArchitects, LLCAssociate ArchitectThe EDGE GroupLandscape ArchitectSweetland EngineeringCivil EngineerKORDA EngineeringStructural Engineer
Reese EngineeringMEP EngineerCD+M Lighting Design GroupLighting DesignerCode Consultants, IncCode ConsultantRider Levett BucknallCost Estimator
Phone: (614) 461�4664
Fax: (614) 280�8881
300 Spruce Street
Suite 300
Columbus, Ohio 43215 www.moodynolan.com
DRAWN BY: CHECKED BY: APPROVED BY:
9/7
/2012 3
:24:5
7 P
M
C:\U
sers
\ssnyder\
Docum
ents
\2010159_M
EP
_ssnyder.
rvt
11279.00
9/7/2012
IM BUILDING ADDITION AND RENOVATION
THE PENNSYLVANIASTATE UNIVERSITY
50% Construction Documents
University Park, Pennsylvania 16802
Mezzanine Level MechanicalPlan � Area B
M132
N.J.B. J.K.G. J.K.G.M132 SCALE: 1/8" = 1'�0"
1 MEZZANINE LEVEL MECHANICAL PLAN � AREA B
# Date Change Description
KEY NOTES
GENERAL NOTES (THIS SHEET ONLY)
1
PROVIDE MOTORIZED DAMPERS FOR ALL DUCT CONNECTIONS TO
INTAKE/EXHAUST PLENUMS AT LOUVERS.
PROVIDE FIRE-RATED DAMPERS AT ALL DUCT PENETRATIONS OF FIRE-
RATED CONSTRUCTION. RE: ARCHITECTURAL DRAWINGS FOR RATED
CONSTRUCTION INFORMATION.
A.
PROVIDE SEVEN (N) SEMI-CUSTOM, HEATING/COOLING AHU'S WITH
FOOTPRINTS TO MATCH (E) EQUIPMENT FOOTPRINTS. THIS WORK
WILL INCLUDE PATCH/REPAIR OF ANY ARCHITECTURAL DEMOLITION
REQUIRED FOR REMOVAL OF (E) EQUIPMENT. EXTEND 6" CHWS/R TO
THESE PENTHOUSES TO SERVE THE (N) AHU'S. AHU'S SHALL HAVE
HEATING CAPACITY TO PROVIDE 95 DEGREE LAT AND COOLING
CAPACITY TO PROVIDE 50 DEGREE LAT AT FULL AIRFLOW. THE
AIRFLOWS ARE AS FOLLOWS:
HV-4 = 30,000 CFM
HV-5 = 23,000 CFM
HV-6 = 14,400 CFM
HV-7 = 14,400 CFM
HV-8 = 23,000 CFM
HV-9 = 30,000 CFM
HV-10 = 3,200 CFM
THREE EA DUCTS MANIFOLDED AND CONNECTED TO ROOF EXHAUST
FAN. PROVIDE 1" DUCT LINER FOR EA DUCTS FROM POINT OF
CONNECTION TO RA MAIN UP TO EFN-2 ON ROOF.
B.
11
EFN-2EFN-2EFN-2EFN-2
24"x10"
GIH-2 GIH-3GIH-1
2
44"x24"
52"x24"
2
44"x24"
52"x24"
2
44"x24"
52"x24"
2
44"x24"
52"x24"
2
PR
INT
DA
TE
:
FIL
E IN
FO
:
PROGRESSDRAWINGNOT FOR
CONSTRUCTION
for
PSU# 09-12181.00 PSU Building # 0804-000
Keyplan
APArchitects, LLCAssociate ArchitectThe EDGE GroupLandscape ArchitectSweetland EngineeringCivil EngineerKORDA EngineeringStructural Engineer
Reese EngineeringMEP EngineerCD+M Lighting Design GroupLighting DesignerCode Consultants, IncCode ConsultantRider Levett BucknallCost Estimator
Phone: (614) 461-4664
Fax: (614) 280-8881
300 Spruce Street
Suite 300
Columbus, Ohio 43215 www.moodynolan.com
DRAWN BY: CHECKED BY: APPROVED BY:
9/7
/20
12 1
0:3
2:2
8 A
M
C:\U
sers
\dcarlson\D
ocum
ents
\20
101
59_M
EP
_dcarlson.r
vt
11279.00
9/7/2012
IM BUILDING ADDITION AND RENOVATION
THE PENNSYLVANIASTATE UNIVERSITY
50% Construction Documents
University Park, Pennsylvania 16802
Mechanical Penthouse LevelMechanical Plan
M140
N.J.B. J.K.G. J.K.G.M140 SCALE: 1/16" = 1'-0"
1 MECHANICAL PENTHOUSE LEVEL MECHANICAL PLAN
# Date Change Description
KEY NOTES
GENERAL NOTES (THIS SHEET ONLY)
1
PROVIDE MOTORIZED DAMPERS FOR ALL DUCT CONNECTIONS TO
INTAKE/EXHAUST PLENUMS AT LOUVERS.
PROVIDE FIRE-RATED DAMPERS AT ALL DUCT PENETRATIONS OF FIRE-
RATED CONSTRUCTION. RE: ARCHITECTURAL DRAWINGS FOR RATED
CONSTRUCTION INFORMATION.
A.
EQUIPMENT ON ROOF CURB.
EQUIPMENT ON BASE RAIL WITH VIBRATION ISOLATION.
B.
EFN-2 EFN-2 EFN-2 EFN-2
GIH-2 GIH-3GIH-1
AC-1
AC-1
AC-1
2
1111
1 11
2
2
2
PR
INT
DA
TE
:
FIL
E IN
FO
:
PROGRESSDRAWINGNOT FOR
CONSTRUCTION
for
PSU# 09-12181.00 PSU Building # 0804-000
Keyplan
APArchitects, LLCAssociate ArchitectThe EDGE GroupLandscape ArchitectSweetland EngineeringCivil EngineerKORDA EngineeringStructural Engineer
Reese EngineeringMEP EngineerCD+M Lighting Design GroupLighting DesignerCode Consultants, IncCode ConsultantRider Levett BucknallCost Estimator
Phone: (614) 461-4664
Fax: (614) 280-8881
300 Spruce Street
Suite 300
Columbus, Ohio 43215 www.moodynolan.com
DRAWN BY: CHECKED BY: APPROVED BY:
9/7
/20
12 1
0:3
2:3
5 A
M
C:\U
sers
\dcarlson\D
ocum
ents
\20
101
59_M
EP
_dcarlson.r
vt
11279.00
9/7/2012
IM BUILDING ADDITION AND RENOVATION
THE PENNSYLVANIASTATE UNIVERSITY
50% Construction Documents
University Park, Pennsylvania 16802
Roof Mechanical PlanM150
N.J.B. J.K.G. J.K.G.M150 SCALE: 1/16" = 1'-0"
1 ROOF MECHANICAL PLAN
# Date Change Description
KEY NOTES
GENERAL NOTES (THIS SHEET ONLY)
1
GENERAL NOTE #1.A.
EXTEND 8" HWS/R TO BACKFEED (E) HW PUMPS IN (E) BASEMENT
MECHANICAL ROOM, (N) HW COIL IN (E) HV"2, AND (N) HW TUBE
BUNDLE AT (E) DOMESTIC HOT WATER GENERATOR.
INSTALL (N) HW PRE"HEAT COIL IN (E) HV"2. COIL CAPACITIES ARE
AS FOLLOWS: 15,035 CFM; EAT=29; LAT=49; EWT=180; LWT=160;
AIRSIDE PRESSURE DROP = 0.13". SIZE COIL TO MATCH (E) HV"2
CABINET DIMENSIONS. COIL TO BE USA COIL " HW58, OR EQUAL.
EXTEND 1" CHWS/R AND 1" HWS/R FROM (N) MECHANICAL ROOM TO
(N) FCU"1 ABOVE CEILING.
Mechanical
M004
Storage
005
Lower Level Hall �South
C000
ElevatorEquipment
M008
Women'sRestroom
007
Storage
009A
MultipurposeRoom
009
Classroom
010
Lower Level Hall �East
C001
Stair 01
Z001
Adaptive PE
011
Family Restroom
001
ET"1
AS"1
UHT"1
Lower Level Hall �West
203D
CWP"1
CWP"2
HWP"1
HWP"2
CWP"4
CWP"3
ACF"1
PRV"1
VAV"1
CRAC"1
VAV"4
VAV"2
VAV"3
CRAC"1
CDP"1
FCU"1
2
3
2
1
1
CDP"1
CDP"1
3
PR
INT
DA
TE
:
FIL
E IN
FO
:
PROGRESSDRAWINGNOT FOR
CONSTRUCTION
for
PSU# 09 12181.00 PSU Building # 0804 000
Keyplan
BASEMENT
APArchitects, LLCAssociate ArchitectThe EDGE GroupLandscape ArchitectSweetland EngineeringCivil EngineerKORDA EngineeringStructural Engineer
Reese EngineeringMEP EngineerCD+M Lighting Design GroupLighting DesignerCode Consultants, IncCode ConsultantRider Levett BucknallCost Estimator
Phone: (614) 461 4664
Fax: (614) 280 8881
300 Spruce Street
Suite 300
Columbus, Ohio 43215 www.moodynolan.com
DRAWN BY: CHECKED BY: APPROVED BY:
9/7
/2012 3
:25:1
3 P
M
C:\U
sers
\ssnyder\
Docum
ents
\2010159_M
EP
_ssnyder.
rvt
11279.00
9/7/2012
IM BUILDING ADDITION AND RENOVATION
THE PENNSYLVANIASTATE UNIVERSITY
50% Construction Documents
University Park, Pennsylvania 16802
Basement Level MechanicalPiping Plan
M211
N.J.B. J.K.G. J.K.G.
M211 SCALE: 1/8" = 1'"0"
1 BASEMENT LEVEL MECHANICAL PIPING PLAN
# Date Change Description
KEY NOTES
GENERAL NOTES (THIS SHEET ONLY)
XX
GENERAL NOTE #1.A.
KEY NOTE #1.
MultipurposeRoom
124
MultipurposeRoom
125
Storage
124AStorage
123
Corridor
C104
Storage
126
Corridor
C104
Main Level Hall
C113
Day Lockers
121
Stair 03
Z103 EquipmentCheckout
129
Vending
104Storage
125A
Janitor
J127Women'sRestroom
R127
Men's Restroom
R128
Office
101B
Office
101A
Offices
101
Break Room
101D
Office
101E
Office
101FOffice
101G
Office
101H
Office
101J
Office
101K
Director
101L
Workroom
101N
Conference Room
101M
Electric
P102
A B
Stair 8
124B
BA
VAV�5
VAV�6
VAV�16
VAV�8
VAV�7
VAV�9
VAV�10
FTR�1FTR�1
FTR�1FTR�1
FTR�1FTR�1
FTR�1FTR�1
VAV�11
VAV�25
VAV�13
VAV�12
VAV�17
VAV�18
VAV�14
PR
INT
DA
TE
:
FIL
E IN
FO
:
PROGRESSDRAWINGNOT FOR
CONSTRUCTION
for
PSU# 09&12181.00 PSU Building # 0804&000
Keyplan
A
APArchitects, LLCAssociate ArchitectThe EDGE GroupLandscape ArchitectSweetland EngineeringCivil EngineerKORDA EngineeringStructural Engineer
Reese EngineeringMEP EngineerCD+M Lighting Design GroupLighting DesignerCode Consultants, IncCode ConsultantRider Levett BucknallCost Estimator
Phone: (614) 461&4664
Fax: (614) 280&8881
300 Spruce Street
Suite 300
Columbus, Ohio 43215 www.moodynolan.com
DRAWN BY: CHECKED BY: APPROVED BY:
9/7
/2012 3
:25:2
7 P
M
C:\U
sers
\ssnyder\
Docum
ents
\2010159_M
EP
_ssnyder.
rvt
11279.00
9/7/2012
IM BUILDING ADDITION AND RENOVATION
THE PENNSYLVANIASTATE UNIVERSITY
50% Construction Documents
University Park, Pennsylvania 16802
Main Level Mechanical PipingPlan & Area A
M221
N.J.B. J.K.G. J.K.G.M221 SCALE: 1/8" = 1'�0"
1 MAIN LEVEL MECHANICAL PIPING PLAN � AREA A
# Date Change Description
KEY NOTES
GENERAL NOTES (THIS SHEET ONLY)
XX
GENERAL NOTE #1.A.
KEY NOTE #1.
Lobby
F102
Control Desk
F103
Vestibule
F101
Landscape
41
Corridor
C104
Main Level Hall
C113
Corridor
C104
Stair 04
Z104
Fitness ControlDesk
F102a
Fitness
103
Fitness
103D
Lounge
C101
Stair 01
Z101
A/V/ Storage
103C
Fitness Office
103A
Stair 05
Z105
A B
Stair 02
Z102
Corridor
103B
BA
VAV�15
FTR�1FTR�1
FTR�1FTR�1
VAV�20
VAV�19
FTR�1
FTR�1
FTR�1
FTR�1
FTR�1
FTR�1
FTR�1
VAV�24
CUH�2
CUH�1
PR
INT
DA
TE
:
FIL
E IN
FO
:
PROGRESSDRAWINGNOT FOR
CONSTRUCTION
for
PSU# 09�12181.00 PSU Building # 0804�000
Keyplan
B
APArchitects, LLCAssociate ArchitectThe EDGE GroupLandscape ArchitectSweetland EngineeringCivil EngineerKORDA EngineeringStructural Engineer
Reese EngineeringMEP EngineerCD+M Lighting Design GroupLighting DesignerCode Consultants, IncCode ConsultantRider Levett BucknallCost Estimator
Phone: (614) 461�4664
Fax: (614) 280�8881
300 Spruce Street
Suite 300
Columbus, Ohio 43215 www.moodynolan.com
DRAWN BY: CHECKED BY: APPROVED BY:
9/7
/2012 3
:25:3
9 P
M
C:\U
sers
\ssnyder\
Docum
ents
\2010159_M
EP
_ssnyder.
rvt
11279.00
9/7/2012
IM BUILDING ADDITION AND RENOVATION
THE PENNSYLVANIASTATE UNIVERSITY
50% Construction Documents
University Park, Pennsylvania 16802
Main Level Mechanical PipingPlan � Area B
M222
N.J.B. J.K.G. J.K.G.M222 SCALE: 1/8" = 1'�0"
1 MAIN LEVEL MECHANICAL PIPING PLAN � AREA B
# Date Change Description
KEY NOTES
GENERAL NOTES (THIS SHEET ONLY)
XX
GENERAL NOTE #1.A.
KEY NOTE #1.
Mechanical
M202
Track
201
Mezzanine HallLanding Elevator
C202
Workroom
203B
Landscape
43
Fitness
203
A B
BA
Elevator
V201
ACF�4
ACF�3ACF�2
VAV�21
VAV�22
VAV�23
FTR�1 FTR�1
VAV�26
PR
INT
DA
TE
:
FIL
E IN
FO
:
PROGRESSDRAWINGNOT FOR
CONSTRUCTION
for
PSU# 09�12181.00 PSU Building # 0804�000
Keyplan
A
APArchitects, LLCAssociate ArchitectThe EDGE GroupLandscape ArchitectSweetland EngineeringCivil EngineerKORDA EngineeringStructural Engineer
Reese EngineeringMEP EngineerCD+M Lighting Design GroupLighting DesignerCode Consultants, IncCode ConsultantRider Levett BucknallCost Estimator
Phone: (614) 461�4664
Fax: (614) 280�8881
300 Spruce Street
Suite 300
Columbus, Ohio 43215 www.moodynolan.com
DRAWN BY: CHECKED BY: APPROVED BY:
9/7
/2012 3
:25:5
0 P
M
C:\U
sers
\ssnyder\
Docum
ents
\2010159_M
EP
_ssnyder.
rvt
11279.00
9/7/2012
IM BUILDING ADDITION AND RENOVATION
THE PENNSYLVANIASTATE UNIVERSITY
50% Construction Documents
University Park, Pennsylvania 16802
Mezzanine Level MechanicalPiping Plan � Area A
M231
N.J.B. J.K.G. J.K.G.M231 SCALE: 1/8" = 1'�0"
1 MEZZANINE LEVEL MECHANICAL PIPING PLAN � AREA A
# Date Change Description
KEY NOTES
GENERAL NOTES (THIS SHEET ONLY)
XX
GENERAL NOTE #1.A.
KEY NOTE #1.
Mezzanine HallLanding East Stair
C201
Track
201
Fitness
203 Fitness
203
A B
BA
Stair 05
Z205
Telecom
203A
CRAC�1
FTR�1
FTR�1
FTR�1
FTR�1FTR�1
FTR�1
FTR�1
FTR�1
FTR�1
FTR�1
CDP�1
PR
INT
DA
TE
:
FIL
E IN
FO
:
PROGRESSDRAWINGNOT FOR
CONSTRUCTION
for
PSU# 09�12181.00 PSU Building # 0804�000
Keyplan
B
APArchitects, LLCAssociate ArchitectThe EDGE GroupLandscape ArchitectSweetland EngineeringCivil EngineerKORDA EngineeringStructural Engineer
Reese EngineeringMEP EngineerCD+M Lighting Design GroupLighting DesignerCode Consultants, IncCode ConsultantRider Levett BucknallCost Estimator
Phone: (614) 461�4664
Fax: (614) 280�8881
300 Spruce Street
Suite 300
Columbus, Ohio 43215 www.moodynolan.com
DRAWN BY: CHECKED BY: APPROVED BY:
9/7
/2012 3
:25:5
9 P
M
C:\U
sers
\ssnyder\
Docum
ents
\2010159_M
EP
_ssnyder.
rvt
11279.00
9/7/2012
IM BUILDING ADDITION AND RENOVATION
THE PENNSYLVANIASTATE UNIVERSITY
50% Construction Documents
University Park, Pennsylvania 16802
Mezzanine Level MechanicalPiping Plan � Area B
M232
N.J.B. J.K.G. J.K.G.M232 SCALE: 1/8" = 1'�0"
1 MEZZANINE LEVEL MECHANICAL PIPING PLAN � AREA B
# Date Change Description
KEY NOTES
GENERAL NOTES (THIS SHEET ONLY)
XX
GENERAL NOTE #1.A.
KEY NOTE #1.
PR
INT
DA
TE
:
FIL
E IN
FO
:
PROGRESSDRAWINGNOT FOR
CONSTRUCTION
for
PSU# 09-12181.00 PSU Building # 0804-000
Keyplan
APArchitects, LLCAssociate ArchitectThe EDGE GroupLandscape ArchitectSweetland EngineeringCivil EngineerKORDA EngineeringStructural Engineer
Reese EngineeringMEP EngineerCD+M Lighting Design GroupLighting DesignerCode Consultants, IncCode ConsultantRider Levett BucknallCost Estimator
Phone: (614) 461-4664
Fax: (614) 280-8881
300 Spruce Street
Suite 300
Columbus, Ohio 43215 www.moodynolan.com
DRAWN BY: CHECKED BY: APPROVED BY:
9/7
/20
12 1
0:3
3:3
9 A
M
C:\U
sers
\dcarlson\D
ocum
ents
\20
101
59_M
EP
_dcarlson.r
vt
11279.00
9/7/2012
IM BUILDING ADDITION AND RENOVATION
THE PENNSYLVANIASTATE UNIVERSITY
50% Construction Documents
University Park, Pennsylvania 16802
Mechanical Penthouse LevelMechanical Piping Plan
M240
N.J.B. J.K.G. J.K.G.M240 SCALE: 1/16" = 1'-0"
1 MECHANICAL PENTHOUSE LEVEL MECHANICAL PIPING PLAN
# Date Change Description
PR
INT
DA
TE
:
FIL
E IN
FO
:
PROGRESSDRAWINGNOT FOR
CONSTRUCTION
for
PSU# 09-12181.00 PSU Building # 0804-000
Keyplan
APArchitects, LLCAssociate ArchitectThe EDGE GroupLandscape ArchitectSweetland EngineeringCivil EngineerKORDA EngineeringStructural Engineer
Reese EngineeringMEP EngineerCD+M Lighting Design GroupLighting DesignerCode Consultants, IncCode ConsultantRider Levett BucknallCost Estimator
Phone: (614) 461-4664
Fax: (614) 280-8881
300 Spruce Street
Suite 300
Columbus, Ohio 43215 www.moodynolan.com
DRAWN BY: CHECKED BY: APPROVED BY:
9/7
/20
12 1
1:1
9:1
1 A
M
C:\U
sers
\dcarlson\D
ocum
ents
\20
101
59_M
EP
_dcarlson.r
vt
11279.00
9/7/2012
IM BUILDING ADDITION AND RENOVATION
THE PENNSYLVANIASTATE UNIVERSITY
50% Construction Documents
University Park, Pennsylvania 16802
Mechanical SchedulesM701
N.J.B. J.K.G. J.K.G.
AIR DEVICE SCHEDULE
1. COORDINATE MOUNTING TYPE WITH CEILING OR WALL TYPE AS SPECIFIED ON ARCHITECTURAL DRAWINGS.
2. 18”x18” BACK PAN.
3. 9”x9” BACK PAN.
4. TWO 1SLOTS, TYPE '1B' FLANGE BORDER, CONCEALED MOUNTING, END CAPS, SPLINE ALIGNMENT CLIPS.
5. BORDER TYPE '11', ONE SLOT, END CAPS, SPLINE CLIPS.
6. PROVIDE SPLINE CLIPS FOR ALIGNEMENT ALONG CONTINUOUS LENGTH.
PUMP SCHEDULE
1. PROVIDE VFD FOR EACH PUMP.
2. BASE MOUNTED END SUCTION PUMP.
3. PROVIDE WITH HIGH EFFICIENCY SUPER LOW E MOTOR COMPATIBLE WITH VFD.
4. PROVIDE SAFETY SWITCH, 6-FOOT POWER CORD, INLINE CHECK VALVE AND MOTOR WITH THERMAL OVERLOAD PROTECTION.
EXHAUST / SUPPLY FAN SCHEDULE
AIR SEPARATOR SCHEDULE
1. ASME RATED.
2. PROVIDE AUTOMATIC AIR VENT.
EXPANSION TANK SCHEDULE
1. ASME RATED.
2. PROVIDE BASE RING FLOOR SUPPORT.
DESIG. SERVICE TYPE GPM TDH (FT) RPM HP
NONOVERLOADING
BHP
ELECTRICALIMPELLERSIZE (IN) EFFIC. (%)
OPERATINGWEIGHT MANUFACTURER MODEL NOTESVOLTS Ø HZ
CDP-1 CONDENSATE
DISPOSAL PUMP
INLINE 1 10 0 1/30 0 120 1 60 0 0 LITTLE GIANT VCMX-20ULST 4
CWP-1 EXISTING BUILDING BASE MOUNTED 780 80 1750 25 19 480 3 60 9.63 84 BELL & GOSSETT 1510 5E 1, 2, 3
CWP-2 EXISTING BUILDING BASE MOUNTED 780 80 1750 25 19 480 3 60 9.63 84 BELL & GOSSETT 1510 5E 1, 2, 3
CWP-3 PHASE I BASE MOUNTED 350 80 1750 15 9 480 3 60 9.25 76 BELL & GOSSETT 1510 5E 1, 2, 3
CWP-4 PHASE I BASE MOUNTED 350 80 1750 15 9 480 3 60 9.25 76 BELL & GOSSETT 1510 3BC 1, 2, 3
HWP-1 PRIMARY LOOP BASE MOUNTED 1433 35 1750 20 17 480 3 60 7.875 74 BELL & GOSSETT 1510 6BC 1, 2, 3
HWP-2 PRIMARY LOOP BASE MOUNTED 1433 35 1750 20 17 480 3 60 7.875 74 BELL & GOSSETT 1510 6BC 1, 2, 3
HWP-3 EXISTING BUILDING BASE MOUNTED 900 40 1750 15 12 480 3 60 7.875 80 BELL & GOSSETT 1510 5BC 1, 2, 3
HWP-4 EXISTING BUILDING BASE MOUNTED 900 40 1750 15 12 480 3 60 7.875 80 BELL & GOSSETT 1510 5BC 1, 2, 3
HWP-5 PHASE I BASE MOUNTED 270 60 1750 10 6 480 3 60 8 73 BELL & GOSSETT 1510 3BC 1, 2, 3
HWP-6 PHASE I BASE MOUNTED 270 60 1750 10 6 480 3 60 8 73 BELL & GOSSETT 1510 3BC 1, 2, 3
PLANCODE SERVICE TYPE
AIR FLOW(CFM)
S.P. (INW.G. @
S.L.)
MOTOR
FAN RPMOPERATING
WEIGHT (LBS) MANUFACTURER MODEL NOTESHP WATTS VOLTS Ø HZ
EFN-1 GENERAL EXHAUST INLINE 1700 1.50 3/4 120 1 60 0 100 GREENHECK SQ-130-VG
EFN-2 0 0.00 0 120 1 60 0 0
RAF-1 AHU-1 INLINE 10000 1.50 7-1/2 480 3 60 0 700 GREENHECK TCB-1-30-75
RAF-2 AHU-2 INLINE 8000 1.50 5 480 3 60 0 700 GREENHECK TCB-1-30-50
RAF-3 AHU-3 INLINE 6000 1.50 5 480 3 60 0 400 GREENHECK TCB-2-22-50
RAF-4 AHU-4 INLINE 14000 1.50 10 480 3 60 0 850 GREENHECK TCB-1-36-100
RAF-5 AHU-5 INLINE 20000 1.50 15 480 3 60 0 1300 GREENHECK 36-TCF-1-I
PLAN CODE TYPE & SERVICE NECK SIZE FACE SIZE FINISHVOLUMEDAMPER MATERIAL MANUFACTURER MODEL NOTES
A SUPPLY DIFFUSER AS NOTED 24 x 24 #26 WHITE Yes STEEL TITUS TDC 1, 2
B SUPPLY DIFFUSER AS NOTED 12 x 12 #26 WHITE Yes STEEL TITUS TDC 1, 3
C EXHAUST GRILLE AS NOTED NECK + 1-3/4" #26 WHITE Yes STEEL TITUS 355RL 1
D RETURN GRILLE 22 x 22 24 x 24 #26 WHITE No STEEL TITUS PAR 1
E RETURN GRILLE 22 x 10 24 x 12 #26 WHITE No STEEL TITUS PAR 1
F SUPPLY SLOT DIFFUSER AS NOTED 4'-0" #26 WHITE Yes STEEL TITUS ML-39 1, 4
G SUPPLY SLOT DIFFUSER AS NOTED 5'-0" BY ARCHITECT Yes ALUMINUM TITUS FL-20HT 1, 5
H SUPPLY DIFFUSER AS NOTED VARIES #26 WHITE Yes STEEL TITUS TMRA 1
J SUPPLY DIFFUSER AS NOTED NECK + 1-3/4" #26 WHITE Yes STEEL TITUS 300RL 1
K RETURN GRILLE AS NOTED 11-5/8" x LENGTH BY ARCHITECT No ALUMINUM TITUS LL-1 1, 6
L SUPPLY SLOT DIFFUSER AS NOTED 8'-0" #26 WHITE Yes STEEL TITUS ML-39 1, 4
M RETURN GRILLE AS NOTED NECK + 1-3/4" #26 WHITE Yes STEEL TITUS 355RL 1
PLANCODE SERVICE
WATERTEMP. (˚F)
TANK VOL.(GAL)
ACCEPT VOL.(GAL)
SIZE (INCHES)
MANUFACTURER MODEL NOTESDIA H
ET-1 HOT WATER LOOP 180 528 528 48 85 AMTROL 2000-L 1, 2
PLANCODE SERVICE GPM
WPD(FT. HD.) STRAINER
SIZE (INCHES) OPERATINGWEIGHT (LBS) MANUFACTURER MODEL NOTESDIA H
AS-1 HOT WATER LOOP 1400 0 Yes 24 80 1500 SPIROTHERM VDT1200/VDN1200 1, 2
PLANCODE
PRESSURE STEAMCAPACITY(LBS/HR) SIZE (IN) MANUFACTURER MODEL NOTES
UP STREAM(PSIG)
DOWN STREAM(PSIG)
PRV-1 150 --- 13,800 --- MAXI-THERM MC-BH-06 1, 2
STEAM PRV/HTX SCHEDULE
1. CARBON STEEL UNIT WITH 1/2" COPPER TUBE HEAT EXCHANGER.
2. HW FLOW = 1,400 GPM; WATER SIDE DELTA T = 20 DEGREES F.
PLANCODE
HEATINGCAPACITY AWT (˚F) GPM WPD (FT)
COVER
MANUFACTURER MODEL NOTESMOUNTINGHEIGHT (IN)
H(IN)
W(IN) STYLE
FTR-1 1261 170 --- --- 12 9 5 --- RUNTAL R2F-3 1
BASEBOARD RADIATION SCHEDULE
1. PROVIDE IN CUSTOM COLOR SELECTED BY ARCHITECT.
2. PROVIDE END TRIM, END CAPS, CENTER TRIM AND CORNER TRIM TO PROVIDE WALL-TO-WALL TRIM AND CONCEAL
ALL PIPING.
INTAKE HOOD SCHEDULE
1. PROVIDE WITH ROOF CURB.
PLANCODE SERVICE
HEATINGCAPACITY
(MBH)
AIRFLOW(CFM)
EWT˚F
LWT˚F
FLOW(GPM)
WPD(FT)
MOTOR ELECTRICAL SIZE (INCHES) OPERATING
WEIGHT (LBS) MANUFACTURER MODEL NOTESHP VOLTS Ø HZ L W H
CUH-1 STAIRS 0.1 180 180 160 .5 .03 1/15 115 1 60 35 9 25 97 STERLING W-02 1, 2, 3, 5
CUH-2 FOYER 0.1 0 180 160 0 115 1 60 24 24 10 0 TRANE FFEB060
UHT-1 MECHANICAL ROOM 0.7 2200 180 160 1.1 1.1 1/4 115 1 60 25 14 29 29 STERLING HS-180 1, 4
UNIT HEATER & CABINET UNIT HEATER SCHEDULE
PLANCODE SERVICE CFM
FAN MOTOR(AMPS)
ELECTRICAL MIN. TOTALCAPACITY (MBH)
EAT SIZE (IN) WEIGHT(LBS) MANUFACTURER MODEL NOTESVOLTS Ø HZ DB (˚F) WB (˚F) L W H
CRAC-1 TELECOM / ELEC. 635 0.53 120 1 60 24.0 80 67 51-1/2 26-3/4 8-1/2 75 MITSUBISHI MR. SLIM PCA-A24GA 1, 2, 3
SPLIT SYSTEM AIR CONDITIONING INDOOR UNIT SCHEDULE
1. WALL MOUNTED INDOOR UNIT.
2. PROVIDE MANUFACTURER'S REMOTE MOUNTED UNIT CONTROLLER MATCHED TO UNIT.
3. PROVIDE WITH CONDENSATE OVERFLOW SWITCH.
PLANCODE
MAX AMBIENTTEMP. (˚F)
MIN. AMBIENTTEMP. (˚F) FANS
NO.COMPRESSORS SEER
ELECTRICAL
MCA MOCP
SIZE (IN) WEIGHT(LBS) MANUFACTURER MODEL NOTESVOLTS Ø HZ L W H
AC-1 95 0 1 1 13.4 480 3 60 18 30 37-1/2 13 37 75 MITSUBISHI PUY-A24-NHA 1, 2, 3
SPLIT SYSTEM AIR CONDITIONING OUTDOOR UNIT SCHEDULE
1. OUTDOOR UNIT SHALL BE MATCHED TO INDOOR UNIT.
2. LOW AMBIENT TEMPERATURE OPERATION TO 0 DEGREES.
3. PROVIDE REFRIGERANT CHARGE REQUIRED FOR ACTUAL REFRIGERANT PIPING LENGTHS. REFRIGERANT TO BE R410A.
PLANCODE
PSUCODE SERVICE
PRIMARY AIRFLOW RANGE
WIDE OPENSP (" WC)
INLET SIZE (IN)
OUTLET SIZE
(IN)OUTLETSIZE (IN)
HEATING COIL
HEATING COIL
HEATING COIL
HEATING COIL
HEATING
COIL
HEATING
COIL
HEATING
COILHEATING
COIL HEATING COIL RADIATEDNC AT 1"
SP
DISCHARGE NC AT 1"
SP
SIZE(IN)
SIZE(IN)
SIZE(IN)
MANUFACTURER MODEL NOTESMAX. CFM MIN. CFM W H D W H CFMMBHMIN.
COILROWS
GPMMAX.
EWT(˚F)
EAT(˚F)
LAT(˚F)
MAX. WPD(FT W.G.)
BRANCH PIPESIZE (IN) L W H
VAV-1 --- BASEMENT -
BATHROOM
500 0 0 16 24 18 0 0 0 0 0 0 0 0 1 23 22 19 31 18 TRANE VCWF06 1-6, 8-10
VAV-2 --- BASEMENT - MP 5000 0 0 16 24 18 0 0 0 0 0 0 0 0 1 23 22 19 31 18 TRANE VCWF24 1-6, 8-10
VAV-3 --- BASEMENT
CLASSROOM
3500 0 0 24 16 24 16 0 0 0 0 0 0 0 0 1 23 22 18 45 18 TRANE VCWF16 1-6, 8-10
VAV-4 --- BASEMENT -
CORRIDOR
1000 0 0 8 14 12 0 0 0 0 0 0 0 0 1 23 22 19 21 12 TRANE VCWF10 1-6, 8-10
VAV-5 --- MAIN - MP 4000 0 0 24 16 24 16 0 0 0 0 0 0 0 0 1 23 22 18 45 18 TRANE VCWF16 1-6, 8-10
VAV-6 --- MAIN - MP 4000 0 0 24 16 24 16 0 0 0 0 0 0 0 0 1 23 22 18 45 18 TRANE VCWF16 1-6, 8-10
VAV-7 --- MAIN - OFFICE 800 0 0 8 14 12 0 0 0 0 0 0 0 0 1 23 22 19 21 12 TRANE VCWF08 1-6, 8-10
VAV-8 --- MAIN - BREAK
ROOM
300 0 0 8 14 12 0 0 0 0 0 0 0 0 1 23 22 19 21 12 TRANE VCWF05 1-6, 8-10
VAV-9 --- MAIN - OFFICE 800 0 0 8 14 12 0 0 0 0 0 0 0 0 1 23 22 19 21 12 TRANE VCWF08 1-6, 8-10
VAV-10 --- MAIN - OFFICE 800 0 0 8 14 12 0 0 0 0 0 0 0 0 1 23 22 19 21 12 TRANE VCWF08 1-6, 8-10
VAV-11 --- MAIN - OFFICE 800 0 0 8 14 12 0 0 0 0 0 0 0 0 1 23 22 19 21 12 TRANE VCWF08 1-6, 8-10
VAV-12 --- MAIN - WORKROOM 300 0 0 8 14 12 0 0 0 0 0 0 0 0 1 23 22 19 21 12 TRANE VCWF05 1-6, 8-10
VAV-13 --- MAIN - OFFICE 300 0 0 8 14 12 0 0 0 0 0 0 0 0 1 23 22 19 21 12 TRANE VCWF05 1-6, 8-10
VAV-14 --- MAIN - CONFERENCE 400 0 0 8 14 12 0 0 0 0 0 0 0 0 1 23 22 19 21 12 TRANE VCWF06 1-6, 8-10
VAV-15 --- MAIN - LOBBY 600 0 0 24 16 24 16 0 0 0 0 0 0 0 0 1 23 22 18 45 18 TRANE VCWF08 1-6, 8-10
VAV-16 --- MAIN - CORRIDOR 300 0 0 8 14 12 0 0 0 0 0 0 0 0 1 23 22 19 21 12 TRANE VCWF05 1-6, 8-10
VAV-17 --- MAIN - VENDING 200 0 0 8 14 12 0 0 0 0 0 0 0 0 1 23 22 19 21 12 TRANE VCWF04 1-6, 8-10
VAV-18 --- MAIN - CONTROL
DESK
400 0 0 8 14 12 0 0 0 0 0 0 0 0 1 23 22 19 21 12 TRANE VCWF06 1-6, 8-10
VAV-19 --- MAIN FITNESS 6000 0 0 42 16 42 16 0 0 0 0 0 0 0 0 1 23 22 18 45 18 TRANE VCWF24 1-10
VAV-20 --- MAIN FITNESS 4000 0 0 42 16 42 16 0 0 0 0 0 0 0 0 1 23 22 18 45 18 TRANE VCWF24 1-10
VAV-21 --- MEZZ. - FITNESS 6000 0 0 24 18 24 18 0 0 0 0 0 0 0 0 1 23 22 18 45 18 TRANE VCWF24 1-10
VAV-22 --- MEZZ. - FITNESS 6000 0 0 24 18 24 18 0 0 0 0 0 0 0 0 1 23 22 18 45 18 TRANE VCWF24 1-10
VAV-23 --- MEZZ. - FITNESS 5000 0 0 24 18 24 18 0 0 0 0 0 0 0 0 1 23 22 18 45 18 TRANE VCWF24 1-10
VAV-24 --- MAIN - OFFICE 1000 0 0 12 12 12 12 0 0 0 0 0 0 0 0 1 23 22 21 19 12 TRANE VCWF10 1-6, 8-10
VAV-25 --- MAIN - OFFICE 800 0 0 8 14 12 0 0 0 0 0 0 0 0 1 23 22 19 21 12 TRANE VCWF05 1-6, 8-10
VAV-26 --- MEZZANINE -
WORKROOM
800 0 0 8 14 12 0 0 0 0 0 0 0 0 1 23 22 19 21 12 TRANE VCWF08 1-6, 8-10
PLANCODE AREA SERVED
SUPPLY FAN HEATING COIL COOLING COIL FILTER SIZE (IN)
OPERATINGWEIGHT
(LBS) MANUFACTURER MODEL NOTESCFMDESIGN OA
(CFM)MINIMUM OA
(CFM)EXT. SP(IN WG)
FANRPM BHP HP
ELECTRICAL
TOTAL CAP.(MBH)
EAT DB(˚F)
LAT DB(˚F) ROWS FINS/FT GPM
EWT(˚F)
LWT(˚F)
MAX. AIR PD(IN W.G.)
MAX. WATER PD(FT. W.G.)
TOTAL CAP.(MBH)
SENS. CAP.(MBH)
EAT LAT
ROWS FINS/FT
MAX.FACE VEL.
(FPM)
MAX.AIR PD
(IN W.G.) GPMEWT(˚F)
LWT(˚F)
MAX.WATER PD(FT. W.G.)
EFFIC.MERV TYPE L W HVOLTS Ø HZ
DB(˚F)
WB(˚F)
DB(˚F)
WB(˚F)
ACF-1 BASEMENT 5000 3500 0 0.00 0 15 480 3 60 358 0 0 2 0 36 180 160 0.00 0 386 0 0 0 55 0 4 0 0 0.00 64 42 54 0 14 PLEATED 203 62 38 0 TRANE PERFORMANCE CLIMATE CHANGER - 10 1-6
ACF-2 MAIN SUPPORT 8500 2500 0 0.00 0 10 480 3 60 286 0 0 2 0 29 180 160 0.00 0 309 0 0 0 55 0 6 0 0 0.00 51 42 54 0 14 PLEATED 204 72 49 0 TRANE PERFORMANCE CLIMATE CHANGER - 17 1-6
ACF-3 MAIN
MULTIPURPOSE
11000 5600 0 0.00 0 7.5 480 3 60 214 0 0 2 0 21 180 160 0.00 0 232 0 0 0 55 0 6 0 0 0.00 38 42 54 0 14 PLEATED 204 80 53 0 TRANE PERFORMANCE CLIMATE CHANGER - 21 1-6
ACF-4 FITNESS 30000 9000 0 0.00 0 20 480 3 60 716 0 0 2 0 72 180 160 0.00 0 772 0 0 0 55 0 6 0 0 0.00 128 42 54 0 14 PLEATED 265 126 86 0 TRANE PERFORMANCE CLIMATE CHANGER - 57 1-6
AIR CONDITIONING FAN SCHEDULE
1. VARIABLE AIR VOLUME AIR HANDLING UNIT WITH INVERTER DUTY MOTOR. PROVIDE WITH VFD AND INTEGRAL DISCONNECT.
2. DOUBLE WALL CONSTRUCTION.
3. PROVIDE WITH SEPARATE MIXING BOX DAMPERS SIZED FOR MINIMUM VENTILATION AIR AND ECONOMIZER DUTY AND DAMPER TO ISOLATE AIR PATH BETWEEN OUTSIDE AIR AND RELIEF AIR MIXING BOXES.
4. SEE SPECIFICATION FOR UNIT ACCESSORIES.
5. UNIT COMPONENTS AND ORDER SHALL BE AS FOLLOWS: AIR MIXING MODULE, FILTER MODULE, AIR BLENDER, HEATING COIL MODULE, ACCESS/TURNING MODULE, COOLING COIL MODULE AND SUPPLY FAN MODULE.
6. PROVIDE GROUNDING FOR ALL MOTOR SHAFTS VIA MEANS SUCH AS GROUNDING BRUSHES, SLIP RINGS OR GROUNDING RINGS.
1. PROVIDE COMBINATION STARTER DISCONNECT.
2. PROVIDE MOTORIZED DAMPER.
VAV TERMINAL SCHEDULE
PLANCODE CFM
AIR P.D.(IN WC)
NECKSIZE
SIZE (IN)
MANUFACTURER MODEL NOTESL W H
GIH-1 14,400 0 84x60 98 74 42 GREENHECK WIH 1
GIH-2 14,400 0 84x60 98 74 42 GREENHECK WIH 1
GIH-3 3,170 0 36x36 50 50 20 GREENHECK WIH 1
# Date Change Description
1. PRESSURE INDEPENDENT DDC CONTROL, SINGLE DUCT VAV BOX W/ 2-ROW REHEAT COIL (MIN). PROVIDE ACCESS PANEL IN DUCT AT COIL DISCHARGE FOR CLEANING AND INSPECTION OF COIL.
2. DUAL MAXIMUM SET POINT CONTROL.
3. 1" FOIL FACED INSULATION IN CABINET AND PRESSURE INDEPENDENT DDC CONTROL.
4. PROVIDE WITH BAS MANUFACTURER CONTROLLER PER THE SPECIFICATIONS.
5. NC RATINGS ARE FOR MAX CFM SCHEDULED
6. WIDE OPEN SP LOSS IS AT MAX CFM SCHEDULED AND INCLUDES COIL AIR PRESSURE DROP.
7. VAV TERMINAL UNIT SHALL BE CAPABLE OF 100% SHUTDOWN IN ADDITION TO MIN. CFM SETTING FOR OUTSIDE AIR TO ACCOMMODATE HYBRID VENTILATION MODE.
8. PROVIDE WITH DISCHARGE AIR TEMPERATURE SENSOR.
9. EQUIPMENT SHALL BE IDENTIFIED BY PSU CODE.
10. PROVIDE CO2 SPACE SENSOR ADJACENT TO WALL THERMOSTAT.
FAN COIL UNIT SCHEDULE
1. PROVIDE SINGLE POINT ELECTRICAL CONNECTION.
2. PROVIDE CONDENSATE OVERFLOW SWITCH IN UNIT DRAIN PAN.
3. HORIZONTAL CONCEALED STYLE.
4. PROVIDE 1" THROWAWAY FILTERS.
5. PROVIDE FACTORY INSTALLED DISCONNECT SWITCH.
6. PROVIDE 3-WAY MODULATING CONTROL VALVE KIT FROM MANUFACTURER.
7. FOUR PIPE FAN COIL, 3 AND 1 SPLIT COIL WITH SAME END CONNECTIONS.
PLANCODE
AREASERVED/TYPE
SUPPLY FAN COOLING COIL HEATING COIL SIZE (IN) OPERATINGWEIGHT
(LBS) MANUFACTURER MODEL NOTESCFM @ ALT.ESP @ S.L. (IN
WG)POWER
(WATTS/HP)
ELECTRICAL TOTAL CAP.(MBH)
SENS. CAP.(MBH)
EAT LAT
ROWSEWT(°F)
LWT(°F)
MAX. WATERPD (FT. W.G.) GPM
TOTAL CAP.(MBH)
EAT(°F)
LAT(°F) ROWS GPM
EWT(°F)
LWT(°F)
MAX. WATERPD (FT. W.G.) L W HVOLTS Ø HZ DB (°F) WB (°F) DB (°F) WB (°F)
FCU-1 ADAPTIVE PE 921 0.4 115 1 60 28.8 20.4 75 63 56 55 3 42 54 28 70 98 1 180 160 74 28 10 0 TRANE FCCB120 1-7
1. PROVIDE FACTORY MOUNTED DISCONNECT, UNIT MOUNTED THERMOSTAT AND FAN SPEED SWITCH.
2. PROVIDE TAMPER RESISTANT LATCHES ON ALL ACCESS DOORS AND PANELS.
3. COLOR TO BE AS SELECTED BY ARCHITECT FROM MANUFACTURER'S SELECTION OF DECORATOR COLORS.
4. FACTORY MOUNTED FAN GUARD.
5. FLUSH WALL-MOUNTED UNIT WITH HIGH CAPACITY 2-ROW COIL.
AREA OF RECTANGULAR
CONNECTION TO MATCH
AREA OF ROUND DUCT
MAIN AIR DUCT
SHOP FABRICATED
RECTANGULAR TO ROUND
TRANSITION
6" MIN.
ROUND DUCT SECTION
WITH LOCKING BALANCING
DAMPER
MAIN AIR DUCT
RETURN / EXHAUST AIR SUPPLY AIR
MIN. 1.33 W
45° LENGTH SHALL BE
EQUAL TO (W/4) 4" MIN.
W
SUPPLY AIR FLOWRETURN / EXHAUST AIR FLOW
STRAP HANGER
(TYPICAL)
1.5DMIN.
NYLON STRAP
FASTENER (TYP.)
FLEX DUCT MAX.
LENGTH: 8'-0"
CONICAL SPIN-IN OR
RECTANGULAR TO ROUND
TRANSITION WITH LOCKING
BALANCING DAMPER.
NOTES:
1. ENTIRE DAMPER INSTALLATION SHALL BE ACCORDING TO THE UL LISTING
AND LOCAL JURISDICTIONAL REQUIREMENTS.
2. DUCTWORK OVER 48" WIDE REQUIRES TWO (2) ACCESS DOORS.
12" x 12" ACCESS PANEL
CONTINUOUS METAL ANGLE
ALL SIDES OF DAMPER
SLEEVE, FASTEN TO WALL AND
SLEEVE PER UL LISTING
BREAKAWAY CONNECTIONS
SHEETMETAL DUCTWORK
TRANSITION DUCT TO FAN
OUTLET SIZE
FLEXIBLE CONNECTION (TYP.)
SUSPEND FROM STRUCTURE (TYP.)
PROVIDE VIBRATION
ISOLATION AS SPECIFIED
TRANSITION DUCT TO
FAN INLET SIZE
TYP. HVAC ROOF TOP UNIT
STD. FACTORY CURB WITH
PERIMETER WOOD NAILER AND
GASKET. LEVEL CURB WITH
WOOD BLOCKING OR STEEL
ANGLES.
R-19 BATT INSULATION BY M.C.
FULL HEIGHT OF CURB
RIGID BOARD INSULATION BY
MECHANICAL CONTRACTOR
FULL DEPTH OF NAILER STRIP
SUPPORT. RE: STRUCTURAL
ROOF INSULATION
ROOFING
FLASHING BY G.C.
MINIMUM HEIGHT OF 12"
SHEET METAL COUNTER FLASHING
BY M.C. WHERE HVAC UNIT IS NOT
SELF FLASHING.
ROOF DECK
ROOF INSULATION
ROOF MEMBRANE
MINIMUM HEIGHT OF 12"
EXTERIOR INSULATION AND
JACKETING
ALUMINUM STRAP AROUND
DUCT FASTENED TO
HORIZONTAL ANGLE ON EACH
SIDE OF DUCT
SUPPORT BLOCKING FOR CURBING
PRE-FABRICATED SUPPORT CURB WITH BASE
PLATE
3/8" LAG SCREW WITH NEOPRENE WASHER
2" x 2" x 1/8" ANGLE IRON SUPPORTS
NOTE:
ALL DUCTWORK TO BE SUPPORTED A MINIMUM OF 12" ABOVE ROOF.
DUCTWORK
2" RIGID BOARD INSULATION
WITH OPTIONAL SPOT ADHESIVE
MECHANICAL FASTENERS (TYP.)
- ANCHOR PINS AND SPEED
WASHERS 3" MAX. FROM END
JOINTS AND 16" O.C.
VAPOR RETARDER MASTIC AT EACH
JOINT AND PENETRATION (TYP.)
ALUMINUM JACKET WITH
CONTINUOUS MOISTURE BARRIER.
ALL JOINTS TO BE WATER TIGHT
WITH MASTIC SEALANT.
SLOPE DUCT ENCLOSURE TO
PREVENT WATER ACCUMULATION.
AUTO AIR VENT W/
1/2" DRAIN LINE
TO FLOOR DRAIN
AIR SEPARATOR
W/ STRAINER
INSTALL WATER METER IN
WITH PULSE READ-OUT
CONNECTED TO BAS
T & P RELIEF VALVE
SHUT-OFF VALVE W/
LOCK SHIELD
UNION
EXPANSION TANK
DRAIN LINE TO FLOOR DRAIN
FULL SIZE DRAIN
VALVE W/ HOSE END
MAKE-UP WATER
TO PUMPS
PR
INT
DA
TE
:
FIL
E IN
FO
:
PROGRESSDRAWINGNOT FOR
CONSTRUCTION
for
PSU# 09-12181.00 PSU Building # 0804-000
Keyplan
APArchitects, LLCAssociate ArchitectThe EDGE GroupLandscape ArchitectSweetland EngineeringCivil EngineerKORDA EngineeringStructural Engineer
Reese EngineeringMEP EngineerCD+M Lighting Design GroupLighting DesignerCode Consultants, IncCode ConsultantRider Levett BucknallCost Estimator
Phone: (614) 461-4664
Fax: (614) 280-8881
300 Spruce Street
Suite 300
Columbus, Ohio 43215 www.moodynolan.com
DRAWN BY: CHECKED BY: APPROVED BY:
9/7
/20
12 1
0:3
5:3
1 A
M
C:\U
sers
\dcarlson\D
ocum
ents
\20
101
59_M
EP
_dcarlson.r
vt
11279.00
9/7/2012
IM BUILDING ADDITION AND RENOVATION
THE PENNSYLVANIASTATE UNIVERSITY
50% Construction Documents
University Park, Pennsylvania 16802
Mechanical DetailsM801
N.J.B. J.K.G. J.K.G.
SCALE: NONEM801
1 TRANSITION DUCT TAP DETAIL
SCALE: NONEM801
2 BRANCH DUCT TAKE-OFF DETAIL
SCALE: NONEM801
3 FLEXIBLE DUCT INSTALLATION DETAIL
SCALE: NONEM801
4 HORIZONTAL FIRE DAMPER DETAIL
SCALE: NONEM801
6 INLINE FAN DETAIL
SCALE: NONEM801
7 ROOF MOUNTED EQUIPMENT CURB DETAIL
SCALE: NONEM801
8 ROOF MOUNTED DUCT DETAIL
SCALE: NONEM801
9 EXTERIOR DUCT ENCLOSURE DETAIL
M801 SCALE: 1/8" = 1'-0"
5 AIR SEPARATOR AND EXPANSION TANK DETAIL
# Date Change Description
SCALE:
SCALE:
SCALE:
SCALE:
SCALE:
SCALE:
SCALE:
T
TRIPLE-DUTY VALVE.
MAY BE REPLACED WITH
VALVES ON DISCHARGE
BALANCING VALVE -
GROUTED TO PAD
HOUSEKEEPING PAD
FLOOR
HOSE END DRAIN
STRAINER
WITH VANES AND
SUCTION DIFFUSER
FLEXIBLE CONN. (TYP.)
WITH SNUBBER (TYP.)
PRESSURE GAUGE
CHECK VALVE
SPRING LOADED
COUPLING GUARD
PUMP BASE ANCHORED &
4" CONCRETE
SECURE TO PAD
ADJUSTABLE PIPE STAND,FLOOR DRAIN
DISCHARGE TO
PIPE FULL SIZE
SHUT-OFF VALVE
(REFER TO SPEC.)
VIBRATION ISOLATORS
PIPE HANGERS WITH
AND SERVICES
FOR PIPE SIZES
SEE PLANS
SPRING ISOLATORS
CONCRETE BASE W/
CONCENTRIC REDUCER
ECCENTRIC REDUCER
DUCTING FOR "B" TYPE
CONNECTIONS
BREAKAWAY
FIRE DAMPER
SLEEVE, FASTEN TO WALL
ALL SIDES OF DAMPER
CONTINUOUS METAL ANGLE
AND SLEEVE PER UL
LISTING (TYPICAL)
DUCTING FOR "A" TYPE
PROVIDE ACCESS DOOR IN DUCTWORK ON ONE SIDE OF
ENTIRE DAMPER INSTALLATION SHALL BE ACCORDING TO
THE UL LISTING AND LOCAL JURISDICTIONAL REQUIREMENTS.
FIRE DAMPER. DUCTWORK OVER 48" WIDE REQUIRES
FIRE DAMPER
TWO (2) ACCESS DOORS
NOTES:
OF SIZE INDICATED
METAL COLLAR
SHOP FABRICATED
SHEETMETAL PLENUM
LINER ON ALL SIDES
1" ACOUSTICAL
LINEAR DIFFUSER
OF PLENUM
2" (MIN)
COLLAR
HEIGHT + 2"
(MIN)
COORDINATE FRAME TYPE,
MOUNTING SURFACE OPENING
DIMENSION, AND THICKNESS
WITH GENERAL
CONTRACTOR TO ASSURE NO
GAPS OCCUR
THROW INTO INTERIOR OF SPACE
AND ONE SLOT FOR HORIZONTAL
VERTICAL THROW @ EXTERIOR
TO DISCHARGE ONE SLOT TO
POSITION PATTERN CONTROLLER
PRE-FABRICATED SUPPORT CURB WITH
SUPPORT BLOCKING FOR CURBINGROOF INSULATION
ROOF DECK
ROOF MEMBRANE
RE: STRUCTURAL DRAWINGS
BASE PLATE
STRAINER
VALVE
SHUT-OFF
BALANCING VALVE
HWS / CWS
HWR / CWR
AV
DRAIN CONNECTION
CAPPED AND VALVED
PLUG
TEST
T&P
THERMOMETER
AIR VENT
AUTOMATIC
UNION (TYP.)
COIL
CONTROL VALVE.
2-WAY MODULATING TEMPERATURE
NOTES:
1. HEATING CONTROL VALVES SHALL FAIL OPEN TO THE COIL.
2. COOLING CONTROL VALVES SHALL FAIL CLOSED TO THE COIL.
3. BALANCING VALVES REQUIRED ON HYDRONIC HOT WATER ONLY.
4. CHILLED WATER COIL WITH BYPASS SHALL HAVE SECOND STRAINER,
UNIONS, CONTROL VALVE AND ADDITIONAL SHUT-OFF VALVE. RE:
1/M6.0.
T&P TEST PLUG
CAPPED AND VALVED
DRAIN CONNECTION
HANGER RODS WITH
VIBRATION ISOLATORS
THERMOSTAT
LINE VOLTAGE
HWS
AUTOMATIC
AIR VENT
UNION
AV
HWR
TWO-WAY
CONTROL
VALVE
CIRCUIT
SETTER
SHUT-OFF
VALVE
NOTE:
1. ALL SHUT-OFF VALVES SHALL BE BALL VALVES.
BASE MOUNTED END SUCTION PUMP DETAIL
VERTICAL FIRE DAMPER DETAIL
DP SENSOR DETAIL
LINEAR SLOT PLENUM DETAIL
ROOF MOUNTED BASE RAIL DETAIL
AIR HANDLING UNIT
SINGLE HYDRONIC COIL DETAIL
HORIZONTAL UNIT HEATER DETAIL
M802
4
NONE
M802
3
NONE
DP
P-T PORT AT
MAIN PIPE NEAR
DP SENSOR, TYP.
PRESSURE GAUGE.
INSTALL IN BOTTOM OF
TUBING OR PIPE TO
PREVENT TRAPPED AIR,
TYPICAL OF ALL.
MANUAL VALVE FOR AIR
VENTING REQUIRED FOR
EACH DP SENSOR
INSTALLATION
1/4" TUBING TO DP
SENSOR AND
PRESSURE GAUGES.
CONNECT TUBING TO SIDE OF
MAIN TO PREVENT AIR FROM
ENTERING TUBING. SIDE TAPS
REQUIRED FOR ALL
PRESSURE GAUGES AND
SENSORS.
DP SENSOR IN INVERTED
TRAP PIPING TO PREVENT
AIR ACCUMULATION.
M802
5
NONE
HPS HPR
M802
6
NONE
M802
7
NONE
M802
8
NONE
M802
9
NONE
3/4"
3/4"
SHUTOFF VALVE
UNION
SIGHT GLASS
REMOVABLE LID
POT FEEDER
FULL SIZE DRAIN VALVE
TO FLOOR DRAIN
SOCKET WRENCH
MOUNTING BRACKET: SECURE
TO WALL, BULKHEAD FRAMING,
ETC. ABOVE FINISHED,
ACCESSIBLE CEILING.
LOCKING RACK & PINION
OPERATOR
FLEXIBLE CASING AND WIRE
(50'-0" MAXIMUM)
SINGLE BLADE ROUND DAMPER
OR RECTANGULAR OPPOSED
BLADE DAMPER AS INDICATED
NOTE:
1. UTILIZE DUCT MOUNTED VOLUME DAMPER FOR
THE MAJORITY OF BALANCING OF AIRFLOW.
REGISTER/DIFFUSER DAMPER SHALL BE NO
MORE THAN 50% CLOSED UPON CONCLUSION OF
TESTING AND BALANCING OPERATIONS.
PR
INT
DA
TE
:
FIL
E IN
FO
:
PROGRESSDRAWINGNOT FOR
CONSTRUCTION
for
PSU# 09-12181.00 PSU Building # 0804-000
Keyplan
APArchitects, LLCAssociate ArchitectThe EDGE GroupLandscape ArchitectSweetland EngineeringCivil EngineerKORDA EngineeringStructural Engineer
Reese EngineeringMEP EngineerCD+M Lighting Design GroupLighting DesignerCode Consultants, IncCode ConsultantRider Levett BucknallCost Estimator
Phone: (614) 461-4664
Fax: (614) 280-8881
300 Spruce Street
Suite 300
Columbus, Ohio 43215 www.moodynolan.com
DRAWN BY: CHECKED BY: APPROVED BY:
9/7
/20
12 1
0:3
5:3
5 A
M
C:\U
sers
\dcarlson\D
ocum
ents
\20
101
59_M
EP
_dcarlson.r
vt
11279.00
9/7/2012
IM BUILDING ADDITION AND RENOVATION
THE PENNSYLVANIASTATE UNIVERSITY
50% Construction Documents
University Park, Pennsylvania 16802
Mechanical DetailsM802
N.J.B. J.K.G. J.K.G.
SCALE: NONEM802
1 CHEMICAL POT FEEDER DETAIL
SCALE: NONEM802
2
MANUAL CABLE OPERATED DAMPER
DETAIL - PLENUM MOUNT
# Date Change Description
SCALE:
SCALE:
SCALE:
SCALE:
SCALE:
SCALE:
SCALE:
D
AT EACH COIL
MV
AV
AT EACH COIL
AUTOMATIC AIR VENT
COIL
2-WAY MODULATING
CONTROL VALVE.
COIL
UNION (TYP.)
THERMOMETER
T&P
TEST
PLUG
CAPPED AND VALVED
DRAIN CONNECTION
HWR / CWR
HWS / CWS
BALANCING VALVE
SHUT-OFF
VALVE
STRAINER
NOTES:
1. HEATING CONTROL VALVES SHALL FAIL OPEN TO THE COIL.
2. COOLING CONTROL VALVES SHALL FAIL CLOSED TO THE COIL.
3. BALANCING VALVES REQUIRED ON HYDRONIC HOT WATER ONLY.
FLEXIBLE CONNECTION
NOTES:
FILTER
1. PROVIDE UL LISTED CONDENSATE OVERFLOW SWITCH.
OUTDOOR AIR
DUCT WITH
MANUAL
VOLUME
DAMPER
PLENUM EQUAL TO UNIT
CONNECTION SIZE; MIN.
12" LONG.
AC CONDENSATE
DRAIN
DUCT TRANSITION TO
SIZE INDICATED ON
THE PLANS.
HYDRONIC PIPING CONNECTION.
CEILING
FLEXIBLE
CONNECTION
NOTE:
HEATING CONTROL VALVES SHALL FAIL OPEN TO THE COIL.
SHUT-OFF
VALVE
RETURN
2-WAY
AIR VENT
MANUAL
CONTROL VALVE.
TEMPERATURE
CIRCUIT SETTER
SUPPLY
STRAINER
UNION
CAPPED AND VALVED
DRAIN CONNECTION
COIL
TRANSITION TO
DEVICE INLET AT
30%%127 MAX ANGLE
WHERE REQUIRED.
FLEX CONNECTION
PROVIDED ON DISCHARGE
OF ALL FAN TERMINAL UNITS
RIGID SUPPLY
AIR DUCT
LOW PRESSURE
SUPPLY AIR
DUCTWORK
VAV BOX MEDIUM PRESSURE
SUPPLY AIR DUCT
HORIZONTAL AND VERTICAL ALIGNMENT
OF UNIT INLET COLLAR AND SUPPLY
AIR DUCT SHALL BE AS FOLLOWS:
DUCT SIZES 4" THROUGH 10": 1" FROM
INLET CENTERLINE TO DUCT CENTERLINE.
DUCT SIZES 12" THROUGH 18": 2" FROM
INLET CENTERLINE TO DUCT CENTERLINE.
SLOPE DUCT
SLOPE 1"
EXTRUDED LOUVER
FRAME, DRAINABLE
ALUM. SCREEN
AND CONFIGURATION WILL
FOR REFERENCE, SHAPE
LOUVER BY G.C. SHOWN
VARY. REFER TO ARCH.
DWGS. FOR SIZE
WEATHER SEAL
AROUND FOR
SILICONE CAULK
PLENUM TO
CONFORM TO
SHAPE OF LOUVER
18"
TYPICAL
INSULATE PLENUM AND
5'-0" OF DUCTWORK
MV
DOUBLE HYDRONIC COIL DETAIL
AIR HANDLING UNIT
HORIZONTAL RECESSED FAN COIL DETAIL
BUILDING WALL PENETRATION DETAIL
VAV REHEAT COIL DETAIL
VAV BOX DETAIL
AIR HANDLING UNIT ELEVATION DETAIL
INTAKE AND EXHAUST LOUVER DETAIL
REVERSE RETURN PIPING
M803
1
NONE
M803
2
NONE
BLIND FLANGE
3/4" AIR VENT BALL
VALVE WITH PLUG
(INTALLED IN TOP OF PIPE)
5/8" THREADED
ROD (TYP.); MIN. 4
PROVIDE MASONRY ANCHOR
AS REQUIRED (TYP.)
EXTERIOR WALL
MJ-FLG ENTREY
PIPE (6 LF)
CAMPUS CHILLED
WATER PIPING.
SEE SITE PLAN
FOR CONTINUATION
INTERLOCKING
MECHANICAL SEAL
ASSEMBLY (LINKSEAL)
EXTERIOR WALL
HIGH PERFORMANCE
BUTTERFLY VALVE
DUCTILE LUG (TYP.) MIN. 4
SADDLE TAP FITTING
1-1/2" BALL DRAIN
VALVE WITH PLUG
(INSTALLED IN
BOTTOM OF PIPE)
4"
(TYP.)
M803
3
NONE
M803
4
NONE
M803
5
NONE
4" HOUSEKEEPING PAD MIN. OA
DAMPER/INLET
OPPOSITE SIDE
MERV 13
FILTER
MODULE
HEATING COIL
MODULE
COOLING COIL
MODULE
ACCESS/MAINTENANCE
MODULE
SA OUTLET100% OA INLET
WITH DAMPER
RA INLET
M803
6
1/2" = 1'-0"
M803
7
NONE
SUPPLY FAN
MODULE
AIR BLENDER
MODULE
AIR MIXING
MODULE
ACCESS
DOOR
(TYPICAL)
PR
INT
DA
TE
:
FIL
E IN
FO
:
PROGRESSDRAWINGNOT FOR
CONSTRUCTION
for
PSU# 09-12181.00 PSU Building # 0804-000
Keyplan
APArchitects, LLCAssociate ArchitectThe EDGE GroupLandscape ArchitectSweetland EngineeringCivil EngineerKORDA EngineeringStructural Engineer
Reese EngineeringMEP EngineerCD+M Lighting Design GroupLighting DesignerCode Consultants, IncCode ConsultantRider Levett BucknallCost Estimator
Phone: (614) 461-4664
Fax: (614) 280-8881
300 Spruce Street
Suite 300
Columbus, Ohio 43215 www.moodynolan.com
DRAWN BY: CHECKED BY: APPROVED BY:
9/7
/20
12 1
0:3
5:3
8 A
M
C:\U
sers
\dcarlson\D
ocum
ents
\20
101
59_M
EP
_dcarlson.r
vt
11279.00
9/7/2012
IM BUILDING ADDITION AND RENOVATION
THE PENNSYLVANIASTATE UNIVERSITY
50% Construction Documents
University Park, Pennsylvania 16802
Mechanical DetailsM803
N.J.B. J.K.G. J.K.G.
# Date Change Description