Surgelogic ® Surge Protective Device I-Line ® Plug-On Unit Series Catalog 1310CT0201R05/09 2009 Class 1310 CONTENTS Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page Product Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Application Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Selection and Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Replacement Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Dimensions and Weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Surgelogic Surge Protective Device - Leading Distributor of

  • Upload
    others

  • View
    6

  • Download
    0

Embed Size (px)

Citation preview

Surgelogic® Surge Protective DeviceI-Line® Plug-On Unit Series

Catalog1310CT0201R05/09

2009Class 1310

CONTENTS

Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PageProduct Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2Application Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3Selection and Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4Replacement Parts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6Dimensions and Weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Surgelogic® Surge Protective DeviceProduct Description

© 2009 Schneider ElectricAll Rights Reserved

206/2009

Product Description

Surge protective device (SPD) units protect electronic equipment from transients. The I-Line® Plug-On Unit with Surgelogic® Surge Protective Device (SPD) is a modular parallel surge protective device designed for service entrance, distribution, or branch panel applications. The device is a multi-stage suppression circuit consisting of field-proven, fast-acting 34 mm metal oxide varistors (MOVs). Each MOV is thermally protected for low current faults, and each module is fused.

The I-Line plug-on unit with a Surgelogic surge protective device is a high performance surge suppressor package incorporating individual modules for each phase. Modes of protection include:

• Line-to-Neutral (L–N)• Line-to-Ground (L–G)• Neutral-to-Ground (N–G)• Line-to-Line (L–L)

A filter provides EMI/RFI noise filtering. The suppression elements are encapsulated in a UL® Recognized thermosetting epoxy material—another performance element that provides additional protection.

Each surge suppression module is individually fused and uses circuitry with thermal cutouts to isolate the SPD and ensure shutdown in the event of MOV damage during severe overvoltages—even when operated on high fault current power systems. Online diagnostics continuously monitor the unit status, and LEDs signal a loss of a suppression circuit. An audible alarm with an enable/disable feature and dry contacts are included in the standard diagnostic package.

Design Features

• Same easy installation as I-Line circuit breakers• Requires 13.50 in. (343 mm) of mounting space• FC units mount in the same mounting slots as FA circuit breakers. FI units

mount in the same mounting slots as KA circuit breakers• Can be applied in a six-disconnect panel or switchboard (SPD counts as

one disconnect)• High-energy parallel design for ANSI/IEEE C62.41 and C62.45

category B and C3 applications.

I-Line Plug-On Unit with Surgelogic SPD

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Surgelogic® Surge Protective DeviceApplication Information

306/2009© 2009 Schneider Electric

All Rights Reserved

Application Information

The effects of lightning and the damage caused by lightning-generated transients are well known. The failure of electronic equipment in a facility located in a high lightning area can easily be attributed directly to lightning-generated transients. Transient protection can be installed on the power distribution system to protect this equipment from these externally generated transients. Lower magnitude transients generated within a facility and their effect on microprocessor-based equipment are less obvious than the transients induced by lightning. Transient voltage generated from inductive motors, pumps, electric welders, etc., may not be large enough to cause immediate damage, but they can cause equipment to malfunction.

A damaging transient voltage can enter a facility from several locations. The highest level of protection should be provided at the service entrance. A second level of protection should be provided at distribution points serving critical areas, for example, computer rooms, accounting areas, and laboratories. Other facility entry points that should be protected include panels serving outdoor lights, or outdoor equipment such as motors. Protection should also be provided for critical areas with equipment essential to the company.

Square D® brand SPD products offered by Schneider Electric provide protection at every level of the electrical distribution system. Typical applications include:

• Banking• Education• Government• Petrochemical• Military• Publishing

• Transportation• Wastewater/Sanitation• Medical• Financial• Telecommunications• Automated Manufacturing

• Retail• Utility• Insurance• Data Processing

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Surgelogic® Surge Protective DeviceSelection and Specifications

© 2009 Schneider ElectricAll Rights Reserved

406/2009

Selection and Specifications

Model Number Format

The model number format consists of: Device Type, Voltage Code, SPD Model, Surge Current Rating Code, and Option Code. The possible device types and codes are shown in the tables below.

In the example at left, FC4IMA16C is an integral suppressor for 480Y/ 277 Vac 3-phase 4-wire 160 kA surge capacity with surge counter.

Specifications

Device Types, Interrupting Ratings, and Continuous Current Ratings

Device Type

Interrupting Rating Continuous Current Ratingat 240 Vac at 480 Vac at 600Y/347 Vac

FC 100 kA 65 kA — 60 A

FI 200 kA 200 kA 100 kA 60 A

Voltage Codes and Systems

Voltage Code Voltage System

1 120/240 Vac 1-phase, 3-wire

2 208Y/120 Vac 3-phase, 3- or 4-wire

3 240/120 Vac 3-phase, 4-wire (high leg Delta)

4 480Y/277 Vac, 3-phase, 3- or 4-wire

7 380Y/220 or 415Y/240 Vac, 3-phase, 3- or 4-wire

8 600Y/347 Vac, 3-phase, 3- or 4-wire

Surge Current Rating Codes and Surge Capacities

Surge Current Rating Code Per PhasePer Mode

L–N L–G N–G

12 120 kA 60 kA 60 kA 120 kA

16 160 kA 80 kA 80 kA 120 kA

24 240 kA 120 kA 120 kA 120 kA

Descriptions and Option Codes

Option Description Option Code

Surge counterDisplays the combined total number of transient voltage surges detected from L–N, L–G, N–G, and L–L since the counter was last reset.

C

Remote monitorDisplays the alarm status of the surge protective device up to 1000 ft (305 m) away from the unit. This option uses the dry contacts.

Order catalog number

TVS12RMU

Dry contacts Provides available Form C type contacts. Standard

Audible alarm with enable/disable switch

Provides audible indication that there is a loss of protection. Standard

FC 4 CIMA 16

Voltage CodeDevice Type

SPD Model (IMA only)Surge Current Rating CodeOption Code

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Surgelogic® Surge Protective DeviceSelection and Specifications

506/2009© 2009 Schneider Electric

All Rights Reserved

UL Suppression Voltage Ratings

IMA Series Voltage Specifications UL Suppression Voltage Rating (SVR)

Partial Catalog Number

Voltage Service L–N L–G N–G L–L MCOV▲

FC1IMAFI1IMA

120/240 Vac, 1-phase, 3-wire 400 400 400 800 150

FC2IMAFI2IMA

208Y/120 Vac,3-phase, 3- or 4-wire 400 400 400 800 150

FC3IMAFI3IMA

240/120 Vac,3-phase, 4-wire(high leg Delta)

800/400 800/400 400 1500/800 275/150

FC4IMAFI4IMA

480Y/277 Vac,3-phase, 3- or 4-wire 800 800 800 1600 320

FC7IMAFI7IMA

380Y/220 Vac3-phase, 3- or 4-wire 800 800 800 1600 320

FI8IMA ■ 600Y/347 Vac,3-phase, 3- or 4-wire 1200 1200 1200 2000 420

▲ MCOV = Maximum Continuous Operating Voltage.■ Not available as FC device.

Standard Features and Descriptions

Feature Description

Environmental

Relative humidity: 0 to 95% non condensing

Operating frequency: 47–63 Hz

Surge suppression operating temperature: -40–+65 °C (-40–+149 °F) ✪

Storage temperature: -40–+65 °C (-40–+149 °F)

Compliancestandards(SPD unit only)

UL 1449, Second Edition, UL 1283

cULus Listed as a circuit breaker in compliance with UL 489/CSA C22.2 No. 0.5

Meets 2002 NEC® Article 285.6

Fused suppression paths

Fused with individual surge-rated fuses (200 kAIR)

Thermal protection Thermal cutout for low current faults

Diagnostics

On-line test functions

Indication per phase

Service indicator shown on the front panel of each SPD unit

Replaceable modules

Separate, replaceable modules for each phase

Self-contained suppression circuits and filtering for each module

LED indicators Indication of loss of protection

Suppression modules Individually-fused

Solid state Bi-directional

Front panel alarm Includes an enable/disable switch

High-energy parallel design Category A, B, and C3 applications

EMI/RFI Filtering Up to -50 dB (100 kHz to 100 MHz)

Short-circuit current rating 200 kA (SPD modules only)

Duty cycle testedANSI C62.41 C3,10 kA 20 kV

Minimum 5000 impulses

Warranty Ten years

✪ Surge counter liquid crystal display may not indicate at temperatures less than -20 °C (-4 °F).

Surgelogic® I-Line® Plug-on SPD Unit

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Surgelogic® Surge Protective DeviceReplacement Parts

© 2009 Schneider ElectricAll Rights Reserved

606/2009

Replacement Parts

MA Module Replacements

Voltage System ● Peak SurgeCurrent Rating

Catalog Number

Phase A Phase B Phase C

120/240 Vac, 1-phase, 3-wire

120 kA MA1IMA12 Empty MA1IMA12

160 kA MA1IMA16 Empty MA1IMA16

240 kA MA1IMA24 Empty MA1IMA24

208Y/120 Vac, 3-phase, 3- or 4-wire

120 kA MA1IMA12 MA1IMA12 MA1IMA12

160 kA MA1IMA16 MA1IMA16 MA1IMA16

240 kA MA1IMA24 MA1IMA24 MA1IMA24

240/120 Vac, 3-phase, 4-wire (high leg Delta) ▼

120 kA MA1IMA12 MA3IMA12 MA1IMA12

160 kA MA1IMA16 MA3IMA16 MA1IMA16

240 kA MA1IMA24 MA3IMA24 MA1IMA24

480Y/277 Vac, 3-phase, 3- or 4-wire

120 kA MA4IMA12 MA4IMA12 MA4IMA12

160 kA MA4IMA16 MA4IMA16 MA4IMA16

240 kA MA4IMA24 MA4IMA24 MA4IMA24

380Y/ 220 or 415Y/240 Vac,3-phase, 3- or 4-wire

120 kA MA7IMA12 MA7IMA12 MA7IMA12

160 kA MA7IMA16 MA7IMA16 MA7IMA16

240 kA MA7IMA24 MA7IMA24 MA7IMA24

600Y/347 Vac, 3-phase, 3- or 4-wire

120 kA MA8IMA12 MA8IMA12 MA8IMA12

160 kA MA8IMA16 MA8IMA16 MA8IMA16

240 kA MA8IMA24 MA8IMA24 MA8IMA24

● With all system voltages, SPD devices must be grounded in accordance with all applicable standards.

▼ Phase B modules are different than Phase A and Phase C modules.

Surgelogic® Device Mounted in Panel with 4-Piece Trim Installed

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Surgelogic® Surge Protective DeviceDimensions and Weights

706/2009© 2009 Schneider Electric

All Rights Reserved

Dimensions and Weights

FC I-Line® Plug-On Unit (Front View)

FI I-Line Plug-On Unit (Front View)

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

1310CT0201R05/09 © 2009 Schneider Electric All Rights Reserved Replaces 1310CT0201R5/07 dated May 2007.