Super-MMS Super Modular Multi System Engineering Data Book

Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

  • Upload
    others

  • View
    1

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

Super-MMSS u p e r M o d u l a r M u l t i S y s t e m

EngineeringData Book

Page 2: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

1

1

The engineering data book details all relevant data, charts

and drawings to enable you to get the best performance

from the Toshiba Super Modular Multi System for the

various applications.

The information is aimed to assist you by providing greater

detail of the system and the wider applications that the

system will cover.

It is recommended the use of the data book is used in

accordance with the following as references.

Design manual : File No.A03-008

Installation manual : File No.A03-012

Service manual : File No.A03-009

ForewordForeword 1

Page 3: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

2

2

2 ForewordContents

1 Foreword ..................................................................1

2 Contents ...................................................................2

3 Introduction ..............................................................5

4 System overview .........................................................9

5 Capacity compensation chart .....................................21

6 Piping requirements ...................................................29

7 Refrigerant cycle diagram ..........................................35

8 Sensible capacity table ..............................................45

9 Part load performance ...............................................71

10 Wiring guideline ........................................................85

11 Wiring diagram ..........................................................95A. Connection schematic (field wiring)B. Inner circuit

12 Controls ...................................................................111

13 Fan characteristics ..................................................133A. Static pressureB. Air velocity profile (Air throw distance chart)

14 Sound characteristics (NC curve) .............................143

15 Dimensional drawing ...............................................163A. Indoor unitsB. Outdoor units

16 Specifications ..........................................................1891. 50Hz models2. 60Hz models

Appendix High Wall Type (2 series)

1-Way Air Discharge Cassette Type (2 series)

Slim Duct Type

Page 4: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

3

Introduction

3

Page 5: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

4

Page 6: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

5

60

55

40

20 30 3835251735

50

45

300

250

100

50

200

150

3

3 ForewordIntroduction

World,s Best Technology for Energy Saving System

Toshiba has attained the pinnacle of world technology in all aspects of efficiency, durability, andcomfort.

High performance new bell mouth(Smooth bell mouth)

Enlarged suction R

Enlarged suction R allows smoother flow.

High speed calculation vectorcontrol inverter

High output/high efficiencyDC motor

+ Output 600W+ Sine wave drive

New large diameter propeller fan(Flash wing fan)

Reversed circular blade

Enlarged fan diameter

The reversed circular form reduces theinterference of the flow between the blades,and the backward vortex.

High efficiency heat transfer pipeR410A

Configuration of heat transfer pipe

AI dual inverter systemHigh efficiency DC twin rotary

compressor

World,s first core technology: each module (singular outdoor unit) is installed with two (dual)

DC twin rotary compressors that work effectively with the highly efficient refrigerant R410A.The system operates in the most optimum pattern for both energy saving and reliability.

-Installation Work: Less Piping Material and Higher Efficiency

Smaller piping diameters than ever before.This is due to the all inverter type dual compressors, Automatic configuration of outdoor unit.

Improved reliability with identical casing

Each outdoor unit (1 module)is of the same size anddesign. Therefore the basicinstallation work will beidentical.The unit has been designedfor your convenience, so it ispossible to fit the unitcomfortably into a standardsize elevator.

* All our compressors are inverter type

Numbers used are expected numbers.

Cost Saving of Piping Material

Less piping work

Efficient Installation Work

Automatic low-noise mode, only possible wheredual inverter type compressors are used.

Froom the weather data of the Japanese Mechanical andElectrical Engineers building in the year 2000.Tokyo (8:00 21:00) remote control temperature setting at 27

Time generated(Hours/year) Outside noise(dB)

Automaticlow noise mode

Outside temperature(oC)

Time generatedOutdoor unit noise

High efficiency DC fan motor

Page 7: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

6

20 40 60 80 100

OFFONOFF

3 4

ON

1 2

3 41 2

3

1

4

4

1

2

2

3

ON ON

INVComp

INVComp

INVComp

INVComp

TOSHIBA

1 Piping

System, 30m

(8 floors)

4)Max from

1st Branch

65m

Super MMS 175m 150m 50m 40m 30m 65m 300m 48units

Max Equivalent

Length

Max Actual Length

Height Difference Max Indoors

Difference

Max from 1st Branch

Total Extension

Max Connectable Indoor Units

Upper Outdoor Unit

Lower Outdoor Unit

1) 2) 3) 4)

Addition of extra indoor unit

Header branch Y joint

Y joint

Header branch

Y joint

Super-MMS (8HP) 4.10high-level

61%

67%

2)Height D

ifference - Upper O

utdoor Unit

- Lower O

utdoor Unit

3)Max Indoors D

ifference30m

50m

*1

Top

3High efficiency DC twin rotary compressor

DC twin rotary compressors are most congenial with R410A and are used withinthe outdoor units. (Conversion to all inverter type)

DCfan motor

DC twin rotary compressor installed on all the outdoorunits for combined use!(Conversion to all inverter type)

Active oil control

Oil control is the key to the reliability.

Outlet

compressorunit

disk

motor

roller

oil flowoil

Large space

Top

Bottom

Compression structure by the rotation of the rollers insidethe fixed cylinder allows the easy supply of oil to theswaying surface. The compressing rollers move in thesame direction as the rotary shaft. This creates a force inthe direction of compression even at high compression.Thus high efficiency and reliability are attained.

Weight(Compared with the conventional unit)

Volume(Compared with the conventional unit)

Congenial with highpressure refrigerant R410A

Force on the vertical shaft(roller) is small.

Range of rotation

Compressor efficiency

Oil discharge(ratio)

15-120rps

See diagram onthe right

1/40(of the conventional unit)

High-speedCalculation Vector

Control Inverter

This difference isthe energy saving

Comparison of compressor efficiencies

Tota

l com

pres

sor e

ffici

ency

(%)

Rotation(rps)

Scroll

Twin rotary

Therefore, all the compressor units can operate equally.

e.g. in case of a workloadof 2 compressor units;

Super MMS

No Need

Higher COPEqual start chance

As both heat exchangers on the2 outdoor units are usable,higher energy-saving(higher efficiency) can be achieved.

The sequence of the firstcompressors start up, changeswhenever switching on.

today

tomorrow

the dayaftertomorrow

Master/Follower

Part load COP

Compressor start

Through avoiding concentration of the load at an individual unit,prevention of failure and improvement of reliability are achieved.

COP

Super-MMS (410A) *1

10HP System 3.80

20HP System 3.55

Leading the world with high efficiency and high COPin both 1:1 system and VRF system.

-Design Work:Flexible to meet the sophisticated condition of buildings or various customer requirements

The longest piping in the industry enablinga flexible floor design.

1) Max Equivalent Length175m

(Max Actual Length 150m)

8 storey building can becovered by one piping system.

Super MMS enable flexible branching.You may change branching at installation sites.

"Header branch after Y joint"according to original plan, but ....

Super MMS can quickly satisfy such a requirement as addition of extra indoor unit(s)...

Easy "Y joint branch after headerbranch" solution in this example.

Uniquetechnology

High level, Energy saving VRF SystemSuper MMS will offer the best solution for thecustomers requirements as well as consideration ofecology, with the unique technologies and advantages.

Page 8: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

7

4

System overview

Page 9: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

8

Page 10: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

9

MMS Only

Super MMSOnly

Super MMSOnly

8F

7F

2F

1F

4

4 ForewordSystem overview

1. OUTLINE OF TOSHIBA SUPER MMS (Super Modular Multi System)

The Combination of line and header branching is highly flexible.Following the shortest design route possible, thereby savingon installation time and cost. Line/header branching after theheader branching is only available with TOSHIBA Super MMS.

Shortest route design by free branching

Line branching

Header branching

Line + Header branching

Header branching after header branching

Line branching after header branching

Outdoor unit

Branching joint

Indoor unit

Branchingheader

Indoor unit

Outdoor unit

Outdoor unit

Branching joint Indoorunit

Branching joint

Header

Outdoor unit

Indoor unit

Header

Header

Header

Indoor unit

Outdoor unit

Page 11: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

10

b1 b2 b3 b4

Outdoor unit

Outdoor unit

a1 a2 a3 a4

U1 U2

U1 U2 U1 U2 U1 U2

4

8F

7F

2F

1F

Non-polarized control wiringbetween the outdoor and indoor units

Outdoor unit

Indoor unit

1st branchingsection

Allowable pipe length :175m equivalent length

Piping

Outdoorunit

From 1st branching to thefurthest indoor unit : 65m

Wiring diagnosis system

Use the switches on the micro processorP.C.B of the outdoor unit.

Detect wiring to the indoor unit b4 whichshould not be in system A.b4 is missing in the system B.

Wiring Indoor unit

Asystem

Bsystem

Hei

ght d

iffer

ence

bet

wee

n in

door

unit

and

outd

oor u

nit :

50m

Hei

ght d

iffer

ence

bet

wee

n in

door

unit

and

indo

or u

nit :

30m

Page 12: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

11

4

Compact designThe design of the modular TOSHIBA Super MMS outdoor unit allows for easy manoeuvering of the unit.The unit will fit into any standard size lift.The compactness of the unit allows for it to be installed into a limited space.

Largest system capacityTOSHIBA Super MMS can be combined up to 48 HP (135kW) as one refrigerant system.

Energy savingNo. 1 COP in VRF industry. Compared with a conventional chiller fan coil system a large energysaving can be achieved.

Advanced bus communication systemWiring between indoor and outdoor units is a simple 2 core wire system.Communication of addresses is also automatically configured.A default test mode operation is available.

Self diagnostics systemComprehensive troubleshooting codes allows for a timely identification of possible problems arising.

High lift designEquivalent pipe length of 175m and vertical lift of 50m is possible with TOSHIBA Super MMS.The maximum vertical lift between indoor units is 30m, this being the highest in the industry.This allows for greater flexibility within the building design of the system.

Multiplied indoor unitsIndoor units with different capacities and configurations can be combined up to a maximum of135% of the outdoor units capacity.A maximum of 48 indoor units can be combined with the 30 _ 48 HP outdoor units.

Intelligent controlTOSHIBA Super MMS intelligent controls and modulating valves deliver the required capacity,according to the load variation from 50% to 100%.The intelligent controls and modulating valves limit or increase the cooling capacity dynamically sohumidity and temperature are kept within the comfort zone.

Conforms to building control lawIAQ (Indoor Air Quality) is also achieved by combining various accessories required by the BuildingControl Law.

Wide control applicationsArtificial Intelligence Network system.Central control and monitoring system available.Weekly schedule operation through weekly timer.

Integration with Building Management System (BMS) is available.

Page 13: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

12

5 HP 6 HP 8 HP 10 HP 12 HP

MMY- MAP0501HT8 MAP0601HT8 MAP0801HT8 MAP1001H8 MAP1201HT8

MMY- MAP0501HT7 MAP0601HT7 MAP0801HT7 MAP1001HT7 MAP1201HT7

MMY- MAP0501T8 MAP0601T8 MAP0801T8 MAP1001T8 MAP1201T8

14.0 16.0 22.4 28.0 33.5

16.0 18.0 25.0 31.5 37.5

5 HP 6 HP 8 HP 10 HP 12 HP 14 HP 16 HP 18 HP 20 HP 22 HPMMY- MAP0501HT8 MAP0601HT8 MAP0801HT8 MAP1001HT8 MAP1201HT8 AP1401HT8 AP1601HT8 AP1801HT8 AP2001HT8 AP2201HT8MMY- MAP0501HT7 MAP0601HT7 MAP0801HT7 MAP1001HT7 MAP1201HT7 AP1401HT7 AP1601HT7 AP1801HT7 AP2001HT7 AP2201HT7MMY- MAP0501T8 MAP0601T8 MAP0801T8 MAP1001T8 MAP1201T8 AP1401T8 AP1601T8 AP1801T8 AP2001T8 AP2201T8

14.0 16.0 22.4 28.0 33.5 38.4 45.0 50.4 56.0 61.516.0 18.0 25.0 31.5 37.5 43.0 50.0 56.5 63.0 69.05 HP 6 HP 8 HP 10 HP 12 HP 8 HP 8 HP 10 HP 10 HP 8 HP

6 HP 8 HP 8 HP 10 HP 8 HP6 HP

8 10 13 16 20 23 27 30 33 37

22 HP 24 HP 24 HP 26 HP 28 HP 30 HP 32 HP 32 HP 34 HP 34 HPMMY- AP2211HT8 AP2401HT8 AP2411HT8 AP2601HT8 AP2801HT8 AP3001HT8 AP3201HT8 AP3211HT8 AP3401HT8 AP3411HT8MMY- AP2211HT7 AP2401HT7 AP2411HT7 AP2601HT7 AP2801HT7 AP3001HT7 AP3201HT7 AP3211HT7 AP3401HT7 AP3411HT7MMY- AP2211T8 AP2401T8 AP2411T8 AP2601T8 AP2801T8 AP3001T8 AP3201T8 AP3211T8 AP3401T8 AP3411T8

61.5 68.0 68.0 73.0 78.5 84.0 90.0 90.0 96.0 96.069.0 76.5 76.5 81.5 88.0 95.0 100.0 100.0 108.0 108.0

12 HP 8 HP 12 HP 10 HP 10 HP 10 HP 8 HP 12 HP 10 HP 12 HP10 HP 8 HP 12 HP 8 HP 10 HP 10 HP 8 HP 10 HP 8 HP 12 HP

8 HP 8 HP 8 HP 10 HP 8 HP 10 HP 8 HP 10 HP8 HP 8 HP

37 40 40 43 47 48 48 48 48 48

36 HP 36 HP 38 HP 40 HP 42 HP 44 HP 46 HP 48 HPMMY- AP3601HT8 AP3611HT8 AP3801HT8 AP4001HT8 AP4201HT8 AP4401HT8 AP4601HT8 AP4801HT8MMY- AP3601HT7 AP3611HT7 AP3801HT7 AP4001HT7 AP4201HT7 AP4401HT7 AP4601HT7 AP4801HT7MMY- AP3601T8 AP3611T8 AP3801T8 AP4001T8 AP4201T8 AP4401T8 AP4601T8 AP4801T8

101.0 101.0 106.5 112.0 118.0 123.5 130.0 135.0113.0 113.0 119.5 126.5 132.0 138.0 145.0 150.010 HP 12 HP 10 HP 10 HP 12 HP 12 HP 12 HP 12 HP10 HP 12 HP 10 HP 10 HP 10 HP 12 HP 12 HP 12 HP 8 HP 12 HP 10 HP 10 HP 10 HP 10 HP 12 HP 12 HP 8 HP 8 HP 10 HP 10 HP 10 HP 10 HP 12 HP

48 48 48 48 48 48 48 48

Max.4branches

Max.8branches

o/ 9.5 1o/ 9.5 to o/ 22.2 1

o/ 15.9 to o/ 41.3 1

2. SUMMARY OF SYSTEM EQUIPMENTSEquipment

Corresponding HP

1. Outdoor units

4

Inverter unitAppearance

Modelname

Heat pump

Heat pump

Cooling only

Cooling capacity (kW)

Heating capacity (kW)

2. Outdoor units (Combination of outdoor units)Corresponding HP

CombinedModel

Cooling capacity(kW)Heating capacity(kW)

Combinedoutdoor units

No. of connectableindoor units

Corresponding HP

CombinedModel

Cooling capacity(kW)Heating capacity(kW)

Combinedoutdoor units

No. of connectableindoor units

No. of connectableindoor units

Combinedoutdoor units

Cooling capacity(kW)Heating capacity(kW)

CombinedModel

3. Branching joints and headers

Y-shape branchingjoint (*3)

Corresponding HP

4-branching header(*4)8-branching header(*4) (*5)

T-shape branchingjoint(For connection ofoutdoor units)

Model name Usage Appearance

1 set of 3 types of T-shape joint pipes as described below:The required quantity is arranged and they are combined at the site.

Connection piping Corresponded dia. (mm) Qty

Balance pipePiping at liquid sidePiping at gas side

*1 ‘‘Capacity code’’ can be obtained. (Capacity code is not actual capacity)

*2 If total capacity code value of indoor unit exceeds that of outdoor unit, apply capacity code of outdoor unit.

*3 When using Y-shape branching joint for 1st branching, select according to the capacity code of the outdoor unit.

*4 Max. capacity code of 6.0 in total can be connected.

*5 If capacity code of outdoor unit is 26 or more, it is not used for 1st branching.

*6 Model names for outdoor and indoor units described in this guide are shortened because of the space constraint.

RBM-BY53ERBM-BY103ERBM-BY203ERBM-BY303ERBM-HY1043ERBM-HY2043ERBM-HY1083ERBM-HY2083E

Indoor unit capacity code (*1) : Total below 6.4Indoor unit capacity code (*1) : Total 6.4 or more and below 14.2 (*2)Indoor unit capacity code (*1) : Total 14.2 or more and below 25.2 (*2)Indoor unit capacity code (*1) : Total 25.2 or more (*2)Indoor unit capacity code (*1) : Total below 14.2Indoor unit capacity code (*1) : Total 14.2 or more and below 25.2Indoor unit capacity code (*1) : Total below 14.2Indoor unit capacity code (*1) : Total 14.2 or more and below 25.2

RBM-BT13E

Page 14: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

13

MMY_ M AP T 8

4

Super Modular Multi System Outdoor Unit : List of Product and Combined Model Name

Cooling Only model50Hz

HP(Capacity

code)Model name

MMY-

No. ofcombined

units

Inverter5 HP

MMY-UsedQty

Inverter6 HP

MMY-UsedQty

Inverter8HP

MMY-

Inverter10HPMMY-

UsedQty

UsedQty

UsedQty

1. Allocation standard of model name

Inverter12HPMMY-

Power supply specifications, 3O/ 380_415 V, 50Hz ....... 8

T : Capacity variable unit

Development series No.

Capacity rank HP x 10

New refrigerant R410A

M : Single module unit, No mark : Combined Model name

Modular Multi

2. Range of combined capacityNo. of combined units: 1 to 4 unitsCapacity of combined units: 14 HP (140 type) to 48 HP (480 type)

3. Rated conditions (Rated mode : Condition)Cooling: Indoor air temperature 27oC DB/19oC WB, Outdoor air temperature 35oC DB

5HP ( 5)

6HP ( 6)

8HP ( 8)

10HP (10)

12HP (12)

14HP (14)

16HP (16)

18HP (18)

20HP (20)

22HP (22)

22HP (22)

24HP (24)

24HP (24)

26HP (26)

28HP (28)

30HP (30)

32HP (32)

32HP (32)

34HP (34)

34HP (34)

36HP (36)

36HP (36)

38HP (38)

40HP (40)

42HP (42)

44HP (44)

46HP (46)

48HP (48)

MAP0501T8

MAP0601T8

MAP0801T8

MAP1001T8

MAP1201T8

AP1401T8

AP1601T8

AP1801T8

AP2001T8

AP2201T8

AP2211T8

AP2401T8

AP2411T8

AP2601T8

AP2801T8

AP3001T8

AP3201T8

AP3211T8

AP3401T8

AP3411T8

AP3601T8

AP3611T8

AP3801T8

AP4001T8

AP4201T8

AP4401T8

AP4601T8

AP4801T8

1

1

1

1

1

2

2

2

2

3

2

3

2

3

3

3

4

3

4

3

4

3

4

4

4

4

4

4

MAP0501T8 1

MAP0601T8

MAP0601T8

MAP0601T8

1

1

1

MAP0801T8

MAP0801T8

MAP0801T8

MAP0801T8

MAP0801T8

MAP0801T8

MAP0801T8

MAP0801T8

MAP0801T8

MAP0801T8

MAP0801T8

MAP0801T8

1

1

2

1

2

3

2

1

4

3

2

1

1

1

2

1

1

2

3

2

1

1

2

3

4

3

2

1

1

1

2

1

2

3

1

2

3

4

MAP1001T8

MAP1001T8

MAP1001T8

MAP1001T8

MAP1001T8

MAP1001T8

MAP1001T8

MAP1001T8

MAP1001T8

MAP1001T8

MAP1001T8

MAP1001T8

MAP1001T8

MAP1001T8

MAP1001T8

MAP1001T8

MAP1201T8

MAP1201T8

MAP1201T8

MAP1201T8

MAP1201T8

MAP1201T8

MAP1201T8

MAP1201T8

MAP1201T8

MAP1201T8

Page 15: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

14

1 1

1 1

1 1

1 1

1 1

2 1 1

2 2

2 1 1

2 2

3 1 2

2 1 1

3 3

2 2

3 2 1

3 1 2

3 3

4 4

3 2 1

4 3 1

3 1 2

4 2 2

3 3

4 1 3

4 4

4 3 1

4 2 2

4 1 3

4 4

MMY_ M AP T 8H

4

Heat Pump model 50Hz

HP(Capacity

code)Model name

MMY-

No. ofcombined

units

Inverter5 HP

MMY-UsedQty

UsedQty

UsedQty

UsedQty

UsedQty

Inverter6 HP

MMY-

Inverter8 HP

MMY-

Inverter10 HPMMY-

Inverter12 HPMMY-

1. Allocation standard of model name

Power supply specifications, 3O/ 380_415 V, 50Hz ....... 8

T : Capacity variable unit

Capacity rank HP x 10

New refrigerant R410A

M : Single module unit, No mark : Combined Model name

Modular Multi

2. Range of combined capacityNo. of combined units: 1 to 4 unitsCapacity of combined units: 14 HP (140 type) to 48 HP (480 type)

3. Rated conditions (Rated mode : Condition)Cooling : Indoor air temperature 27oC DB/19oC WB, Outdoor air temperature 35oC DBHeating : Indoor air temperature 20oC DB, Outdoor air temperature 7oC DB/6oC WB

Development series No.

H : Heat pump

5HP ( 5)

6HP ( 6)

8HP ( 8)

10HP (10)

12HP (12)

14HP (14)

16HP (16)

18HP (18)

20HP (20)

22HP (22)

22HP (22)

24HP (24)

24HP (24)

26HP (26)

28HP (28)

30HP (30)

32HP (32)

32HP (32)

34HP (34)

34HP (34)

36HP (36)

36HP (36)

38HP (38)

40HP (40)

42HP (42)

44HP (44)

46HP (46)

48HP (48)

MAP0501HT8

MAP0601HT8

MAP0801HT8

MAP1001HT8

MAP1201HT8

AP1401HT8

AP1601HT8

AP1801HT8

AP2001HT8

AP2201HT8

AP2211HT8

AP2401HT8

AP2411HT8

AP2601HT8

AP2801HT8

AP3001HT8

AP3201HT8

AP3211HT8

AP3401HT8

AP3411HT8

AP3601HT8

AP3611HT8

AP3801HT8

AP4001HT8

AP4201HT8

AP4401HT8

AP4601HT8

AP4801HT8

MAP0501HT8

MAP0601HT8

MAP0601HT8

MAP0601HT8

MAP0801HT8

MAP0801HT8

MAP0801HT8

MAP0801HT8

MAP0801HT8

MAP0801HT8

MAP0801HT8

MAP0801HT8

MAP0801HT8

MAP0801HT8

MAP0801HT8

MAP0801HT8

MAP1001HT8

MAP1001HT8

MAP1001HT8

MAP1001HT8

MAP1001HT8

MAP1001HT8

MAP1001HT8

MAP1001HT8

MAP1001HT8

MAP1001HT8

MAP1001HT8

MAP1001HT8

MAP1001HT8

MAP1001HT8

MAP1001HT8

MAP1001HT8

MAP1201HT8

MAP1201HT8

MAP1201HT8

MAP1201HT8

MAP1201HT8

MAP1201HT8

MAP1201HT8

MAP1201HT8

MAP1201HT8

MAP1201HT8

Page 16: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

15

1 1

1 1

1 1

1 1

1 1

2 1 1

2 2

2 1 1

2 2

3 1 2

2 1 1

3 3

2 2

3 2 1

3 1 2

3 3

4 4

3 2 1

4 3 1

3 1 2

4 2 2

3 3

4 1 3

4 4

4 3 1

4 2 2

4 1 3

4 4

MMY_ M AP T 7H

Heat Pump model 60Hz

Super Modular Multi System Outdoor Unit : List of Product and Combined Model Name

HP(Capacity

code)Model name

MMY-

No. ofcombined

units

Inverter5 HP

MMY-UsedQty

UsedQty

UsedQty

UsedQty

UsedQty

Inverter6 HP

MMY-

Inverter8 HP

MMY-

Inverter10 HPMMY-

Inverter12 HPMMY-

1. Allocation standard of model name

Power supply specifications, 3O/ 380 V, 60Hz ....... 7

T : Capacity variable unit

Capacity rank HP x 10

New refrigerant R410A

M : Single module unit, No mark : Combined Model name

Modular Multi

2. Range of combined capacityNo. of combined units: 1 to 4 unitsCapacity of combined units: 14 HP (140 type) to 48 HP (480 type)

3. Rated conditions (Rated mode : Condition)Cooling : Indoor air temperature 27oC DB/19oC WB, Outdoor air temperature 35oC DBHeating : Indoor air temperature 20oC DB, Outdoor air temperature 7oC DB/6oC WB

Development series No.

H : Heat pump

5HP ( 5)

6HP ( 6)

8HP ( 8)

10HP (10)

12HP (12)

14HP (14)

16HP (16)

18HP (18)

20HP (20)

22HP (22)

22HP (22)

24HP (24)

24HP (24)

26HP (26)

28HP (28)

30HP (30)

32HP (32)

32HP (32)

34HP (34)

34HP (34)

36HP (36)

36HP (36)

38HP (38)

40HP (40)

42HP (42)

44HP (44)

46HP (46)

48HP (48)

MAP0501HT7

MAP0601HT7

MAP0801HT7

MAP1001HT7

MAP1201HT7

AP1401HT7

AP1601HT7

AP1801HT7

AP2001HT7

AP2201HT7

AP2211HT7

AP2401HT7

AP2411HT7

AP2601HT7

AP2801HT7

AP3001HT7

AP3201HT7

AP3211HT7

AP3401HT7

AP3411HT7

AP3601HT7

AP3611HT7

AP3801HT7

AP4001HT7

AP4201HT7

AP4401HT7

AP4601HT7

AP4801HT7

MAP0501HT7

MAP0601HT7

MAP0601HT7

MAP0601HT7

MAP0801HT7

MAP0801HT7

MAP0801HT7

MAP0801HT7

MAP0801HT7

MAP0801HT7

MAP0801HT7

MAP0801HT7

MAP0801HT7

MAP0801HT7

MAP0801HT7

MAP0801HT7

MAP1001HT7

MAP1001HT7

MAP1001HT7

MAP1001HT7

MAP1001HT7

MAP1001HT7

MAP1001HT7

MAP1001HT7

MAP1001HT7

MAP1001HT7

MAP1001HT7

MAP1001HT7

MAP1001HT7

MAP1001HT7

MAP1001HT7

MAP1001HT7

MAP1201HT7

MAP1201HT7

MAP1201HT7

MAP1201HT7

MAP1201HT7

MAP1201HT7

MAP1201HT7

MAP1201HT7

MAP1201HT7

MAP1201HT7

4

Page 17: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

16

4

4. Indoor unitType Appearance Model name Capacity rank Capacity code Cooling

capacity (kW)Heating

capacity (kW)

4-way Air DischargeCassette Type

2-way Air DischargeCassette Type

1-way Air DischargeCassette Type

Slim Duct Type

Concealed DuctStandard Type

Concealed DuctHigh StaticPressure Type

Under Ceilling Type

MMU-AP0091HMMU-AP0121HMMU-AP0151HMMU-AP0181HMMU-AP0241HMMU-AP0271HMMU-AP0301HMMU-AP0361HMMU-AP0481HMMU-AP0561HMMU-AP0071WHMMU-AP0091WHMMU-AP0121WHMMU-AP0151WHMMU-AP0181WHMMU-AP0241WHMMU-AP0271WHMMU-AP0301WHMMU-AP0481WH*1)

MMU-AP0071YHMMU-AP0091YHMMU-AP0121YHMMU-AP0151SHMMU-AP0181SHMMU-AP0241SHMMU-AP0152SHMMU-AP0182SHMMU-AP0242SHMMD-AP0071SPHMMD-AP0091SPHMMD-AP0121SPHMMD-AP0151SPHMMD-AP0181SPHMMD-AP0071SPH(SH)-C*1)

MMD-AP0091SPH(SH)-C*1)

MMD-AP0121SPH(SH)-C*1)

MMD-AP0151SPH(SH)-C*1)

MMD-AP0181SPH(SH)-C*1)

MMD-AP0071SPH-K*3)

MMD-AP0091SPH-K*3)

MMD-AP0121SPH-K*3)

MMD-AP0151SPH-K*3)

MMD-AP0181SPH-K*3)

MMD-AP0071BHMMD-AP0091BHMMD-AP0121BHMMD-AP0151BHMMD-AP0181BHMMD-AP0241BHMMD-AP0271BHMMD-AP0301BHMMD-AP0361BHMMD-AP0481BHMMD-AP0561BHMMD-AP0181HMMD-AP0241HMMD-AP0271HMMD-AP0361HMMD-AP0481HMMD-AP0721HMMD-AP0961HMMC-AP0151HMMC-AP0181HMMC-AP0241HMMC-AP0271HMMC-AP0361HMMC-AP0481H

009 type012 type015 type018 type024 type027 type030 type036 type048 type056 type007 type009 type012 type015 type018 type024 type027 type030 type048 type007 type009 type012 type015 type018 type024 type015 type018 type024 type007 type009 type012 type015 type018 type007 type009 type012 type015 type018 type007 type009 type012 type015 type018 type007 type009 type012 type015 type018 type024 type027 type030 type036 type048 type056 type018 type024 type027 type036 type048 type072 type096 type015 type018 type024 type027 type036 type048 type

1.001.251.702.002.503.003.204.005.006.000.8

1.001.251.702.002.503.003.205.000.801.001.251.702.002.501.702.002.500.801.001.251.702.000.801.001.251.702.000.801.001.251.702.000.801.001.251.702.002.503.003.204.005.006.002.002.503.004.005.008.00

10.001.702.002.503.004.005.00

2.83.64.55.67.18.09.0

11.214.016.0

2.22.83.64.55.67.18.09.0

14.02.22.83.64.55.67.14.55.67.12.22.83.64.55.62.22.83.64.55.62.22.83.64.55.62.22.83.64.55.67.18.09.0

11.214.016.0

5.67.18.0

11.214.022.428.0

4.55.67.18.0

11.214.0

3.24.05.06.38.09.0

10.012.516.018.0

2.53.24.05.06.38.09.0

10.016.0

2.53.24.05.06.38.05.06.38.02.53.24.05.06.32.53.24.05.06.32.53.24.05.06.32.53.24.05.06.38.09.0

10.012.516.018.0

6.38.09.0

10.016.025.031.5

5.06.38.09.0

12.516.0

*1) China market only *2) European market only *3) Korea market only

16-1

Page 18: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

17

4

16-2

Type Appearance Model name Capacity rank Capacity code Coolingcapacity (kW)

Heatingcapacity (kW)

Floor StandingCabinet Type

Floor StandindConcealed Type

Floor Standind Type

*1) China market only *2) European market only

MMK-AP0071HMMK-AP0091HMMK-AP0121HMMK-AP0151HMMK-AP0181HMMK-AP0241HMMK-AP0072H*2)

MMK-AP0092H*2)

MMK-AP0122H*2)

MML-AP0071HMML-AP0091HMML-AP0121HMML-AP0151HMML-AP0181HMML-AP0241HMML-AP0071HMML-AP0091HMML-AP0121HMML-AP0151HMML-AP0181HMML-AP0241HMMF-AP0151HMMF-AP0181HMMF-AP0241HMMF-AP0271HMMF-AP0361HMMF-AP0481HMMF-AP0561H

007 type009 type012 type015 type018 type024 type007 type009 type012 type007 type009 type012 type015 type018 type024 type007 type009 type012 type015 type018 type024 type015 type018 type024 type027 type036 type048 type056 type

0.801.001.251.702.002.500.801.001.250.801.001.251.702.002.500.801.001.251.702.002.501.702.002.503.004.005.006.00

2.22.83.64.55.67.12.22.83.62.22.83.64.55.67.12.22.83.64.55.67.14.55.67.18.0

11.214.016.0

2.53.24.05.06.38.02.53.24.02.53.24.05.06.38.02.53.24.05.06.38.05.06.38.09.0

10.016.018.0

*3) Korea market only

High Wall Type(2 series)

High Wall Type(1 series)

4. Indoor unit

Page 19: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

18

4

16-3

UNIT

SET CL

SETTING

UNIT No.

CODE No.

TEST

SET DATA

R.C. No.

ûCûF

TESTSETTING

5. Remote controller

Name Modelname Appearance FunctionApplication

Wir

ed r

emo

te c

on

tro

ller

Sim

ple

wir

ed r

emo

te c

on

tro

ller

RB

C-A

X22

CE

RB

C-A

X22

CE

2T

CB

-AX

21U

(W)-

ET

CB

-AX

21U

(W)-

E2

RB

C-A

S21

E/R

BC

-AS

21E

2R

BC

-AM

T21

E/R

BC

-AM

T31

ET

CB

-AX

21E

TC

B-A

X21

E2W

irel

ess

rem

ote

co

ntr

olle

r ki

t

Connected to indoor unit

Connected to indoor unit

Connected to indoor unit

Simple remote controller

Wired remotecontroller

Wired remote controller(In case of control by2 remote controllers)

Start / Stop Mode Change Temperature setting Change of air flow Timer function

On or off timer operation, setting in 30minute increments.Automatic Off function.Combined with the weekly timer, weeklyschedule operation can be operated.

Filter sign Displays automatically maintenance time of indoor filter. Filter sign flashes. Self-diagnosis function Pressing‘‘CHECK’’ button displays cause of fault on the check code. Control by 2 remote controllers is available. Two remote controllers can be connected to one indoor unit. The indoor unit can be separately operated from a different location.

1

2

Start / Stop Temperature setting Change of air flow Check code display

Start / Stop Mode change Temperature setting Change of air flow Timer function On or off timer operation, setting in 30 minute increments. Automatic Off function. Control by 2 remote controllers is available. Two wireless remote controllers can operate one indoor unit. The indoor unit can be separately operated from a different location. Check code display TCB-AX21U(W)-E (for 4-way airdischarge cassette) RBC-AX22CE (for under ceiling) TCB-AX21-E (for other units except for the concealsed duct high static pressure)

Page 20: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

19

ON

8:00 12:00 13:00 18:00 19:00 21:00

OFF OFFON ON OFF

WEEKLY TIMER

ERROR

SuMoTuWeTh Fr SaPROGRAM1

PROGRAM2

PROGRAM3

SELECT ZONE

CL SET

GROUP

CODE No.

UNIT No.

No.R.C.

TEST

ZONEALLZONEGROUP

SETTING

1234

SET DATA

5

3

Name

Wee

kly

tim

er

Modelname Appearance Application Performance

RB

C-E

XW

21E

RB

C-E

XW

21E

2

Cen

tral

rem

ote

co

ntr

olle

r

TC

B-S

C64

2TL

E T

CB

-SC

642T

LE

2

Connected to centralremote controller or

wired remote controller

Connected to outdoor unit,indoor unit

Wiredremote controller

Weeklytimer

Outdoor unit

Centralremote controller

Weeklytimer

Header

Centralremote controller

Indoor remotecontroller

Centralremote

controller

Weekly schedule operation

Setting different start / stop time foreach day of the week

ON / OFF can be set 3 times a day.

1

2

‘‘CHECK’’ ‘‘PROGRAM’’ ‘‘DAY’’button copying of setting easy.

Two different schedules for aweek can be specified.(Summer schedule and winterschedule, etc.)

4

‘‘CANCEL’’ ‘‘DAY’’ button enablesholiday setting.

If power supply fails, the settingcontents are stored in the memoryfor 100 hours.

6

Individual control up to 64 indoor units.

Individual control for max. 64 indoorunits divided into 4 zones.

Up to 16 indoor unitsfor each zone

Up to 16 outdoor header units areconnectable.

4 type central control setting toinhibit individual operation by remotecontroller can be selected.

Setting for one of 1 to 4 zones is available.

Can be used with other central control devices (Up to 10 central control devices with in one control circuit)

Two selectable control modesCentral controller modeRemote controller mode

Setting of simultaneous ON/OFF 3 times for each day of the week combined with a weekly timer.

Follower

Outdoor unit

17

4

Page 21: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

20

Name Modelname Appearance Application Performance

ON

-OF

F c

on

tro

ller

TC

B-C

C16

3TL

ET

CB

-CC

163T

LE

2

Connected to outdoor unit,indoor unit

Outdoor unit

Header

Indoorremote controller

Follower

Outdoor unit

ON-OFFcontroller

ON-OFFcontroller

Setting of simultaneous ON/OFF 3 times for each day of the week when combined with a weekly timer.

Individual control up to 16 indoor units.

Connected to 2 remote controllers ispossible.

18

Page 22: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

19

Capacity compensation chart

5

Page 23: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

20

Foreword

Page 24: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

21

5

5 ForewordCapacity compensation chart

3. Cooling/heating capacity characteristics

1. Cooling capacity calculation method : Required cooling capacity = Cooling capacity x Factor ( ) kW, , , , *11 2 3 4 5

Indoor air wet bulb temperature vs. capacity correction value1

15

1.2

1.1

1.0

0.9

0.820 24

1.1

1.0

0.980 90 100 110 120

-5 0 5 10 15 20 25 30 35 40 43

1.2

1.1

1.0

0.9

Cap

acity

cor

rect

ion

valu

e

Indoor air wet bulb temp. ( )

Cap

acity

cor

rect

ion

valu

e

Outdoor air dry bulb temp. ( )

Air flow variation ratio (%)Cap

acity

cor

rect

ion

valu

e

Outdoor air dry bulb temperature vs.capacity correction value2

Air flow variation ratio of indoor unit vs. capacity correction (For concealed duct type only)3

*1 : Coefficient to use for the correction of the outdoor unit capacity when the total capacity of the indoor units are not equal to the outdoor unit capacity.

Page 25: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

22

Outdoor unit

Indoor unit

L' is the longest one of (l'o + l'a, l'o + l'b, l'o + l'c)

H = ho + (Largest one of ha, hb, and hc)

Aha

hbhc

ho l'o

l'a

l'b

l'cB

C

0

80

60

40

20

20 40 60 80 100 120 135

120

100

100

50

40

30

20

10

0

-10

-20

-4020 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170

-30

98%

100

92 90 8488 86 82 80 78 76 759 94

100 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160-40

-20

-10

0

10

20

30

40

50

-30

100%

7678808690 8894 9298 96 74 7284 82

5

Connecting pipe length and lift difference between indoor and outdoor units vs. capacity correction value

*1 : Coefficient to use for the correction of the outdoor unit capacity when the total capacity of the indoor units are not equal to the outdoor unit capacity.

Hei

ght o

f out

doo

r un

it H

(m)

Pipe length (Equivalent length) L (m)

Outdoor unit (5 to 44HP)

Outdoor unit (46 to 48HP)

Hei

ght o

f out

doo

r un

it H

(m)

Pipe length (Equivalent length) L (m)

Cor

rect

ion

(%)

Indoor units total capacity ratio (%)Standard capacity ratio

Correction of outdoor unit diversity

Page 26: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

23

0.815 20 24

0.9

1.0

1.1

1.2

0.5

0.6

0.7

0.8

0.9

1.0

1.1

1.2

-15 -10 -5 0 5 10 15

0.9

1.0

1.1

80 90 100 110 120

5

Foreword

2. Heating capacity calculation method: Required heating capacity = Heating capacity x Factor ( )kW

Indoor air dry bulb temperature vs. capacity correction value1

*1 : Coefficient to use for the correction of the outdoor unit capacity when the total capacity of the indoor units are not equal to the outdoor unit capacity.

*2 : Refer to item 3

Outdoor air wet bulb temperature vs. capacity correction value2

Air flow variation ratio of indoor unit vs. capacity correction (For concealed duct type only)3

Cap

acity

cor

rect

ion

valu

e

Indoor air dry bulb temp. ( )

Cap

acity

cor

rect

ion

valu

e

Outdoor air wet bulb temp. ( )

Air flow variation ratio (%)Cap

acity

cor

rect

ion

valu

e

Page 27: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

24

Outdoor unit

Indoor unit

L' is the longest one of (l'o + l'a, l'o + l'b, l'o + l'c)

H = ho + (Largest one of ha, hb, and hc)

Aha

hbhc

ho l'o

l'a

l'b

l'cB

C

0

80

60

40

20

20 40 60 80 100 120 135

120

100

100 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170-40

-20

-10

0

10

20

30

40

50

-30

100%

9293949697989 91 90 89955

Connecting pipe length and lift difference between indoor and outdoor units vs. capacity correction value4

*1 : Coefficient to use for the correction of the outdoor unit capacity when the total capacity of the indoor units are not equal to the outdoor unit capacity.

Correction of outdoor unit diversity5

Hei

ght o

f out

doo

r un

it H

(m)

Pipe length (Equivalent length) L (m)

Outdoor unit (5 to 48HP)

Cor

rect

ion

(%)

Indoor units total capacity ratio (%)Standard capacity ratio

Page 28: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

25

3025 28201510-10

-5

0

5

10

15

20

25

30

35

40

45

-20

-15

-10

-5

0

5

10

15

20

5 10 15 20 25 30

0.8

0.9

1.0

-15 -10 -5 0 5 10

5

3. Capacity correction in case of frost on the outdoor heat exchanger when in heatingCorrect the heating capacity when frost can be found on the outdoor heat exchanger.

Capacity correction in case of frost on the outdoor heat exchanger6

Heating capacity = Capacity after correction of outdoor unit x Correction value of capacity resulted from frost (Capacity after correction of outdoor unit : Heating capacity calculated in the above item 2.)

Cap

acity

cor

rect

ion

valu

e

Outdoor air wet bulb temp. ( )

4. Capacity calculation for each indoor unit

5. Operating temperature range

Capacity for each indoor unit= Capacity after correction of outdoor unit x

Total value of standard indoor unit capacityRequired standard capacity of indoor unit

In cooling time In heating time

Out

doo

r ai

r d

ry b

ulb

tem

p.

()

Indoor air wet bulb temp. ( )

Out

doo

r ai

r w

et b

ulb

tem

p.

()

Indoor air dry bulb temp. ( )

Continuouslyoperable

range

Usa

ble

ran

ge(in

pul

l dow

n)

Usa

ble

ran

ge(in

war

min

g-u

p)

Continuouslyoperable

range

6. Rated conditionsCooling : Indoor air temperature 27 DB/19.0 WB, Outdoor air temperature 35 DBHeating : Indoor air temperature 20 DB, Outdoor air temperature 7 DB/6 WB

* The unit can be operated even if outdoor tem- perature gets down to -20 . However, note that the warranty covers only up to -15 because operation beyond that temperature is out of specification.

* When outdoor air temperature falls below -15 , it may cause shortening of the products lifetime.

Page 29: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

26

Page 30: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

27

Piping requirements

6

Page 31: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

28

Foreword

Page 32: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

29

4 units

48 HP

48 units

H2 <15 135%

H2 >15 105%

300 mLA + LB + La + Lb + Lc + Ld + L1 + L2 + L3 + L4+L5 + L6 + L7 + a + b + c + d + e + f + g + h + i + j

150 m

175 mLA + LB + Ld + L1 + L3 + L4 + L5 + L6 + j

65 m L3 + L4 + L5 + L6 + j

25 m LA + LB + Ld, (LA + Lb, LA + LB + Lc)

85 m L1

10 m Ld, (La, Lb, Lc)

30 m a, b, c, d, e, f, g, h, i, j

50 m _

40 m ( _

30 m**)

_

5 m _

Outdoor unit

T-shape branching joint

LaLA LB

Lb Lc

Main piping

L1

1st branching section

DFollower unit 3

Connecting piping of outdoor unit

BFollower

unit 1

CFollower

unit 2

AHeader

unit

Main connecting piping between outdoor unitsLength corresponded to farthest piping between outdoor units LO 25 m

Branching piping L2

Connecting piping of indoor unit L7

b c d ea

g h i jf

L4 L5 L6

L3

Branching header

Indoor unit

Indoor unit

Equivalent length corresponded to farthest piping L 175 m

Equivalent length corresponded to farthest piping after 1st branching Li 65 m

Y-joint

Ex.2Ex.1

Ld

Follower unit 1

Follower unit 2

Headerunit

Follower unit 1

Follower unit 2

Headerunit

6

6 ForewordPiping requirements

1. Allowable length/height difference of refrigerant piping

* (D) is outdoor unit furthest from the 1st branch and ( j ) is the indoor unit furthest from the 1st branch.

** If the height difference (H2) between indoor units exceeds 3m, set below 30m.

*** If the maximum combined outdoor unit capacity is 46 HP or more, then the maximum equivalent length is restricted to 70m.

HeightdifferencebetweenoutdoorunitsH3 5m

HeightdifferencebetweenoutdoorunitsH1 50m

NOTE :In case of connecting method Ex. 2, a large amount ofrefrigerant and refrigerant oil may return to the head unit.Therefore, set the T-shape joint so that oil does not enter directly.

Max. No. of combined outdoor units

System restrictions

Max. capacity of combined outdoor units

Max. No. of connected indoor units

Max. capacity of combinedindoor units

Height differencebetween indoorunitsH2 30m

Combination of outdoor units : Header unit (1 unit) + Follower units (0 to 3 units).Header unit is the outdoor unit nearest to the connected indoor units.

Note 1)

Install the outdoor units in order of capacity.(Header unit Follower unit 1 Follower unit 2 Follower unit 3)

Note 2)

Refer to outdoor unit combination table.Note 3)

Piping to indoor units shall be perpendicular to piping to the header outdoor unit as <Ex.1>.Do not connect piping to indoor units in the same direction of Header outdoor unit as <Ex.2>.

Note 4)

Allowable length and height difference of refrigerant piping

Pipinglength

Heightdifference

Total extension of pipe (Liquid pipe, real length)

Farthest piping length L (*)Real length

Equivalent length

Equivalent length of farthest piping from 1st branching Li (*)

Equivalent length of farthest piping between outdoor units LO (*)

Max. equivalent length of main piping (***)

Max. equivalent length of outdoor unit connecting piping

Max. real length of indoor unit connecting piping

Height between indoorand outdoor units H1

Upper outdoor unit

Lower outdoor unit

Height between indoor units H2

Height between outdoor units H3

Allowable value Piping section

Page 33: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

30

3

1 1 1 1

22

45 5 5

4

4

4

4 4

5 5

5 5 5 5 5

2

66

6

Outdoorunit

Balance pipe

T-shape branching jointOutdoor unit

connectingpiping

Main connecting piping between outdoor units

Main piping

Branching pipingHeader branching pipe

1st branching section

Indoor unit connecting piping

Y-shape branching joint

Indoor unit connecting piping

Follower unit 2

Follower unit 3

Follower unit 1 Header unit

Indoor unit

Indoor unit

MMY-

MAP0501T8 MAP0501HT8 MAP0501HT7 O/ 15.9 O/ 9.5

MAP0601T8 MAP0601HT8 MAP0601HT7 O/ 19.1 O/ 9.5

MAP0801T8 MAP0801HT8 MAP0801HT7 O/ 22.2 O/ 12.7

MAP1001T8 MAP1001HT8 MAP1001HT7 O/ 22.2 O/ 12.7

MAP1201T8 MAP1201HT8 MAP1201HT7 O/ 28.6 O/ 12.7

14 to below 22 O/ 28.6 O/ 15.9

22 to below 26 O/ 34.9 O/ 15.9

26 to below 36 O/ 34.9 O/ 19.1

36 or more O/ 41.3 O/ 22.2

O/ 9.5

Below 6 O/ 15.9 O/ 9.5

6 to below 8 O/ 19.1 O/ 9.5

8 to below 12 O/ 22.2 O/ 12.7

12 to below 14 O/ 28.6 O/ 12.7

14 to below 22 O/ 28.6 O/ 15.9

22 to below 26 O/ 34.9 O/ 15.9

26 to below 36 O/ 34.9 O/ 19.1

36 to below 46 O/ 41.3 O/ 22.2

46 or more O/ 41.3 *5 O/ 22.2

2.8 or less O/ 12.7 O/ 9.5

2.8 to below 6.4 O/ 15.9 O/ 9.5

6.4 to below 12.2 O/ 22.2 O/ 12.7

12.2 to below 20.2 O/ 28.6 O/ 15.9

20.2 to below 25.2 O/ 34.9 O/ 15.9

25.2 to below 35.2 O/ 34.9 O/ 19.1

35.2 or more O/ 41.3 O/ 22.2

Real length 15m or less O/ 9.5 O/ 6.4007 type to012 type Real length exceeds 15m O/ 12.7 O/ 6.4

015 type to 018 type O/ 12.7 O/ 6.4

024 type to 056 type O/ 15.9 O/ 9.5

072 type to 096 type O/ 22.2 O/ 12.7

Below 6.4 RBM-BY53E

6.4 to below 14.2 RBM-BY103E

14.2 to below 25.2 RBM-BY203E*2

*6

25.2 or more RBM-BY303E

Below 14.2 RBM-HY1043E

14.2 to below 25.2 RBM-HY2043E

Below 14.2 RBM-HY1083E*3 14.2 to below 25.2 RBM-HY2083E

RBM-BT13E

OK OK 1/4'' 6.35 0.80

OK OK 3/8'' 9.52 0.80

OK OK 1/2'' 12.70 0.80

OK OK 5/8'' 15.88 1.00

NG*4 OK 3/4'' 19.05 1.00

NG*4 OK 7/8'' 22.20 1.00

NG*4 OK 1.1/8'' 28.58 1.00

NG*4 OK 1.3/8'' 34.92 1.10

NG*4 OK 1.5/8'' 41.28 1.25

6

*1 Code is determined according to the capacity rank.

*2 When using a Y-shape branching joint for the 1st branch, select according to capacity code of the outdoor unit.

*3 For 1 line after branching header indoor units with a maximum capacity code of 6.0 in total can be connected.

*4 If the pipe size is O/ 19.0 or more, use a suitable material as detailed in the installation manual.

*5 The maximum equivalent length of the main pipe should be 70m.

*6 When the first branch is a header with the outdoor total capacity codes of 12 to 26, apply the model RBM- HY2043E(4-branch) or RBM-HY2083E(8-branch) regardless of the total capacity codes of the down-stream indoor units.

2. Selection of refrigerant piping

1 Pipe size of outdoor unit (Table 1)

3 Size of main pipe (Table 3)

4 Pipe size between branching sections (Table 4)

5 Piping of indoor unit (Table 5)

6 Selection of branching section (Table 6)

7 Minimum wall thickness for R410A application (Table 7)

2 Connecting pipe size between outdoor units (Table 2)

Model name Gas side Liquid side

Total capacity code of outdoorunits at downstream side Gas side Liquid side Balance pipe

Total capacity code of all outdoor units *1 Gas side Liquid side

Total capacity code of indoor units atdownstream side *1 Gas side Liquid side

Determine thickness of the main pipe according to capacity of the outdoorunits.

If the total capacity code value of indoor units exceeds that of the outdoorunits, apply the capacity code of outdoor units.

Capacity rank Gas side Liquid side

Total capacity code of indoor unit *1 Model name

Y-shapebranching joint

Branchingheader

T-shapebranching joint(Forconnectingoutdoor unit)

For 4branching

For 8branching

1 set of 3 types of T-shape joint pipes asdescribed below:The required quantity is arranged andcombinedat the site. Balance pipe (Corresponded difference O/ 9.52) 1 Piping at liquid side (Corresponded difference O/ 9.5 to O/ 22.1) 1

Piping at gas side (Corresponded difference O/ 15.9 to O/ 41.3) 1

Half hard or hardSoft OD (Inch) OD (mm) Minimum wall thickness (mm)

Page 34: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

31

5HP 6HP 8HP 10HP 12HP

8.5kg

8.0kg

8.5kg

8.0kg

12.5kg

11.0kg

12.5kg

11.0kg

12.5kg

11.0kg

o/ 6.4 o/ 9.5 o/ 12.7 o/ 15.9 o/ 19.0 o/ 22.2

0.025kg 0.055kg 0.105kg 0.160kg 0.250kg 0.350kg

5

6

8

10

12

14

16

18

20

22

24

26

5

6

8

10

12

8 6

8 8

10 8

10 10

12 10

8 8 6

12 12

8 8 8

10 8 8

0.0

0.0

1.5

2.5

3.5

0.0

0.0

0.0

3.0

5.0

0.0

7.0

-4.0

-4.0

28

30

32

34

36

38

40

42

44

46

48

10 10 8

10 10 10

12 10 10

8 8 8 8

12 12 10

10 8 8 8

12 12 12

10 10 8 8

10 10 10 8

10 10 10 10

12 10 10 10

12 12 10 10

12 12 12 10

12 12 12 12

-2.0

0.0

1.0

-6.0

3.0

-6.0

4.0

-6.0

-6.0

-5.0

-4.0

-2.0

0.0

2.0

R410A

6

Foreword

3. Charging requirement with additional refrigerantAfter the system has been vacuumed, replace the vacuum pump with a refrigerant cylinder and charge thesystem with additional refrigerant.

Calculating the amount of additional refrigerant required

Refrigerant in the system when shipped from the factory

Refrigerant amountcharged in factory

Heat pump model

Cooling only model

When the system is charged with refrigerant at the factory, the amount of refrigerant needed for the pipes at thesite is not included. Therefore, calculate the additional amount needed and add the required amount to the system.

(Calculation)Additional refrigerant charge amount is calculated based on the size of liquid pipe at site and its real length.

Additional refrigerant charge amount at site =

Real length of liquid pipe X Additional refrigerant charge amountper liquid pipe 1m (Table 1)

+ Compensation by system HP (Table 2)

Example : Additional charge amount R (kg) = (L1 x 0.025kg/m) + (L2 x 0.055kg/m) + (L3 x 0.105kg/m) + (3.0kg)L1 : Real total length of liquid pipe 6.4 (m)L2 : Real total length of liquid pipe 9.5 (m)L3 : Real total length of liquid pipe 12.7 (m)

Pipe dia. at liquid side

Additional refrigerant amount/1m

Table 7-1

Table 7-2

Combinedhorse power

(HP)Outdoor combination

(HP)

Compensationby System HP

(kg)

Combinedhorse power

(HP)Outdoor combination

(HP)

Compensationby System HP

(kg)

Page 35: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

32

Page 36: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

33

Refrigerant cycle diagram

7

Page 37: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

34

Foreword

Page 38: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

35

7

7 ForewordRefrigerant cycle diagram

1. Inverter Unit (5, 6, 8, 10, 12HP)Model: MMY-MAP0501HT, MAP0601HT, MAP0801HT, MAP1001HT, MAP1201HT

Capillary tube

Capillarytube

Capillary tube

M

Propeller fan

Fan motor

Sensor(TO)

Sensor (TS1)

Sensor(TL)

Sensor(TE1) (Right side)

Air heat exchanger at outdoor side

(Left side)

Air heat exchanger at outdoor side

Solenoid valve(SV2)

Solenoid valve (SV5)

Solenoid valve(SV41)

Solenoid valve(SV3A)

Solenoid valve(SV3E)

Solenoid valve(SV3B)

Solenoid valve(SV3D)

Solenoid valve(SV3C)

4-Way valve

Check joint

Low-pressuresensor

Accumulator

Check joint

Check joint

High-pressure sensor

High-pressure switch

Oilseparator

Check valve

Check valve

Check valve

Check valve

Check valveC

ompr

esso

r 1

(Inv

erte

r)

Strainer

Strainer

Sensor(TK1)

Sensor(TK4)

Sensor(TK3)

Capillary tube

Capillary tube

Capillary tubeStrainer

Strainer

Strainer(PMV1)

Strainer

StrainerStrainer

Capillary tube

Capillary tube

Solenoid valve(SV42)

High-pressure switch

Check valve

Check valve C

ompr

esso

r 2

(Inv

erte

r)

Strainer

Sensor(TK2)

Sensor(TD2)

Sensor(TD1)

Liquidtank

Oil tank

Balance pipeservise valve

Liquid side

servise valve

Gas sideservise valve

Pulse motor valve (PMV)

(PMV1)

(8,10,12HP)

(5,6HP)

(PMV2)

Page 39: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

36

7

2. Explanation of Functional PartsFunctional part name Functional outline

Solenoid valve

4-way valve

1.SV3A

(Connector CN313: Blue) 1) Returns oil in the balance pipe to the compressor.

2.SV3B

3.SV3C

4.SV3D

5.SV3E

6.SV2

7.SV4(n)

8.SV5

PMV1,2

1. TD1 TD2

2. TS1

3. TE1

4. TK1, TK2, TK3, TK4

5. TL

6. TO

1.High pressure sensor

2. Low pressure sensor

Compressor caseheater

Accumulator caseheater

Pulse motor valve

Oil separator

Temp. sensor

Pressure sensor

Heater

Balance pipe

(Connector CN324: Red) 1) Collects oil in the oil tank during OFF time. 2) Supplies oil in the oil tank during ON time.

(Connector CN314: Black) 1) Pressurizes oil reserved in the oil tank during operation.

(Connector CN323: White) 1) Reserves oil in the oil separator during OFF time, and supplies oil during operation.

(Connector CN323: White) 1) Turns on during operation and balances oil between the compressors.

(Hot gas bypass) (Connector CN312: White) 1) Low pressure release function 2) High pressure release function 3) Gas balance during off status

(Start compensation valve of compressor) (Connector CN311: Blue) 1) For gas balance start 2) High pressure release function 3) Low pressure release function

(Connector CN310: White) (for Heating model only) 1) Preventive function for high-pressure rising in heating operation

(Connector CN317: Blue) 1) Cooling/heating exchange 2) Reverse defrost

(Connector CN300, 301: White) 1) Super heat control function in heating operation 2) Liquid line shut-down function while follower unit stops 3) Under-cool adjustment function in cooling operation

1) Prevention for rapid decreasing of oil (Decreases oil flowing to the cycle) 2) Reserve function of surplus oil

(TD1: Connector, CN502: White, TD2: Connector, CN503: Pink) 1) Protection of compressor discharge temp. Used for release

(Connector CN504: White) 1) Controls super heat in heating operation

(Connector CN505: Green) 1) Controls defrost in heating operation 2) Controls outdoor fan in heating operation

(Connector CN521: White) 1) Detects under cool in cooling operation

(Connector CN507: Yellow) 1) Detects outside temperature

(Connector CN501: Red) 1) Detects high pressure and controls compressor capacity 2) Detects high pressure in cooling operation, and controls the fan in low ambient cooling operation

(Connector CN500: White) 1) Detects low pressure in cooling operation and controls compressor capacity 2) Detects low pressure in heating operation, and controls the super heat

(Compressor 1 Connector CN316: White, Compressor 2 Connector CN315: Blue) 1) Prevents liquid accumulation to compressor

(Connector CN321: Red) 1) Prevents liquid accumulation to accumulator

1) Oil balancing in each outdoor unit

TK1 Connector CN514: Black, TK2 Connector CN515: Green, TK3 Connector CN516: Red, TK4 Connector CN523: Yellow 1) Judges oil level of the compressor

( )

Page 40: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

37

M

7

Foreword

3. Indoor Unit

(NOTE) MMU-AP0071YH to AP0121YH type air conditioners do not have a TC2 sensor.

Pulse Motor Valve

Temp. sensor

PMV

1. TA

2. TC1

3. TC2

4. TCJ

(Connector CN082 (6P): Blue)1)Controls super heat in cooling operation2)Controls under cool in heating operation3)Recovers refrigerant oil in cooling operation4)Recovers refrigerant oil in heating operation

(Connector CN104 (2P): Yellow)1)Detects indoor suction temperature

(Connector CN100 (3P): Brown)1)Controls PMV super heat in cooling operation

(Connector CN101 (2P): Black)1)Controls PMV under cool in heating operation

(Connector CN102 (2P): Red)1)Controls PMV super heat in cooling operation2) MMU-AP0071 to AP0121YH only Controls PMV under cool in heating operation

Functional part name Functional outline

Liquid side Gas side

Strainer Capillary tube

Pulse MotorValve (PMV)

Sensor(TC2)

Strainer Sensor(TCJ)

Sensor(TA)

Fan motor

Fan

Sensor(TC1)

Air heat exchangerat indoor side

Page 41: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

38

FM

TO

TS1

Liquidtank

4-Way valve

Accumulator

TK2

TK4

TK1

SV3E

SV41 SV42

SV3D

SV3A

TK3

SV3C

Oil tank

OS

TE1

SV5

SV3B

Ps sensor

SV2TL

PMV1 PMV2

Com

pres

sor

1

Com

pres

sor

2

TD1

HP HP

TD2

Pd sensor

FM

TO

TS1

Liquidtank

4-Way valve

Accumulator

TK2

TK4

TK1

SV3E

SV41 SV42

SV3D

SV3A

TK3

SV3C

Oil tank

OS

TE1

SV5

SV3B

Ps sensor

SV2TL

PMV1 PMV2

Com

pres

sor

1

Com

pres

sor

2

TD1

HP HP

TD2

Pd sensor

Strainer

TCJTC2 TC1

PMV

Strainer Strainer

TCJTC2 TC1

PMV

Strainer Strainer

TCJTC2 TC1

PMV

Strainer Strainer

TCJTC2 TC1

PMV

Strainer

Gas pipe

Gas pipe

Liquid pipe

Liquid pipe

Balance pipe

7

COMBINED REFRIGERANT PIPES SYSTEMATIC DRAWING1. Normal Operation (COOL Mode / DEFROST Mode)

Header unit(MMY-MAP1001H)

Follower unit(MMY-MAP1001H)

Indoor unit

NOTEAn outdoor unit which is connected with indoor/outdoor communication lines isreferred to as the ‘‘Header unit’’, and the other unit is called the ‘‘Follower unit’’.

(Example: 20HP system)

High-pressure gas or condensate liquid refrigerantEvaporative gas refrigerant (Low-pressure gas)

Page 42: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

39

FM

TO

TS1

Liquidtank

4-Way valve

Accumulator

TK2

TK4

TK1

SV3E

SV41 SV42

SV3D

SV3A

TK3

SV3C

Oil tank

OS

TE1

SV5

SV3B

Ps sensor

SV2TL

PMV1 PMV2

Com

pres

sor

1

Com

pres

sor

2

TD1

HP HP

TD2

Pd sensor

Strainer

TCJTC2 TC1

PMV

Strainer Strainer

TCJTC2 TC1

PMV

Strainer Strainer

TCJTC2 TC1

PMV

Strainer Strainer

TCJTC2 TC1

PMV

Strainer

Gas pipe

Gas pipe

Liquid pipe

Liquid pipe

Balance pipe

FM

TO

TS1

Liquidtank

4-Way valve

Accumulator

TK2

TK4

TK1

SV3E

SV41 SV42

SV3D

SV3A

TK3

SV3C

Oil tank

OS

TE1

SV5

SV3B

Ps sensor

SV2TL

PMV1 PMV2

Com

pres

sor

1

Com

pres

sor

2

TD1

HP HP

TD2

Pd sensor

7

2. Normal Operation (HEAT Mode)

Indoor unit

High-pressure gas or condensate liquid refrigerantEvaporative gas refrigerant (Low-pressure gas)

NOTEAn outdoor unit which is connected with indoor/outdoor communication lines isreferred to as the ‘‘Header unit’’, and the other unit is called the ‘‘Follower unit’’.

(Example: 20HP system)

Header unit(MMY-MAP1001H)

Follower unit(MMY-MAP1001H)

Page 43: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

40

FM

TO

TS1

Liquidtank

4-Way valve

Accumulator

TK2

TK4

TK1

SV3E

SV41 SV42

SV3D

SV3A

TK3

SV3C

Oil tank

OS

TE1

SV5

SV3B

Ps sensor

SV2TL

PMV1 PMV2

Com

pres

sor

1

Com

pres

sor

2

TD1

HP HP

TD2

Pd sensor

Strainer

TCJTC2 TC1

PMV

Strainer Strainer

TCJTC2 TC1

PMV

Strainer Strainer

TCJTC2 TC1

PMV

Strainer Strainer

TCJTC2 TC1

PMV

Strainer

Gas pipe

Gas pipe

Liquid pipe

Liquid pipe

Balance pipe

FM

TO

TS1

Liquidtank

4-Way valve

Accumulator

TK2

TK4

TK1

SV3E

SV41 SV42

SV3D

SV3A

TK3

SV3C

Oil tank

OS

TE1

SV5

SV3B

Ps sensor

SV2TL

PMV1 PMV2

Com

pres

sor

1

Com

pres

sor

2

TD1

HP HP

TD2

Pd sensor

*1

*3 *2

7

3. Backup Operation (Cooling Operation when Header Outdoor unit failure)

Header unit(MMY-MAP1001H)

Follower unit(MMY-MAP1001H)

Indoor unit

NOTEAn outdoor unit which is connected with indoor/outdoor communication lines isreferred to as the ‘‘Header unit’’, and the other unit is called the ‘‘Follower unit’’.

(Example: 20HP system)

High-pressure gas or condensate liquid refrigerantEvaporative gas refrigerant (Low-pressure gas)

FailureUnit set temporarilyto header unit duringemergent operation.

*1 When liquid leaks from PMV, packed valve at liquid side = Close fully*2 Gas pipe service valve = Close fully*3 Balance pipe packed valve = Open fully

Page 44: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

41

FM

TO

TS1

Liquidtank

4-Way valve

Accumulator

TK2

TK4

TK1

SV3E

SV41 SV42

SV3D

SV3A

TK3

SV3C

Oil tank

OS

TE1

SV5

SV3B

Ps sensor

SV2TL

PMV1 PMV2

Com

pres

sor

1

Com

pres

sor

2

TD1

HP HP

TD2

Pd sensor

Strainer

TCJTC2 TC1

PMV

Strainer Strainer

TCJTC2 TC1

PMV

Strainer Strainer

TCJTC2 TC1

PMV

Strainer Strainer

TCJTC2 TC1

PMV

Strainer

Gas pipe

Gas pipe

Liquid pipe

Liquid pipe

Balance pipe

FM

TO

TS1

Liquidtank

4-Way valve

Accumulator

TK2

TK4

TK1

SV3E

SV41 SV42

SV3D

SV3A

TK3

SV3C

Oil tank

OS

TE1

SV5

SV3B

Ps sensor

SV2TL

PMV1 PMV2

Com

pres

sor

1

Com

pres

sor

2

TD1

HP HP

TD2

Pd sensor

*1

*3 *2

7

4. Emergent Operation (Heating Operation when Header Outdoor unit failure)

Indoor unit

High-pressure gas or condensate liquid refrigerantEvaporative gas refrigerant (Low-pressure gas)

NOTEAn outdoor unit which is connected with indoor/outdoor communication lines isreferred to as the ‘‘Header unit’’, and the other unit is called the ‘‘Follower unit’’.

(Example: 20HP system)

Header unit(MMY-MAP1001H)

Follower unit(MMY-MAP1001H)

*1 When liquid leaks from PMV, packed valve at liquid side = Close fully*2 Gas pipe service valve = Close fully*3 Balance pipe packed valve = Open fully

FailureUnit set temporarilyto header unit duringemergent operation.

Page 45: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

42

FM

TO

TS1

Liquidtank

4-Way valve

Accumulator

TK2

TK4

TK1

SV3E

SV41 SV42

SV3D

SV3A

TK3

SV3C

Oil tank

OS

TE1

SV5

SV3B

Ps sensor

SV2TL

PMV1 PMV2

Com

pres

sor

1

Com

pres

sor

2

TD1

HP HP

TD2

Pd sensor

Strainer

TCJTC2 TC1

PMV

Strainer Strainer

TCJTC2 TC1

PMV

Strainer Strainer

TCJTC2 TC1

PMV

Strainer Strainer

TCJTC2 TC1

PMV

Strainer

Gas pipe

Gas pipe

Liquid pipe

Liquid pipe

Balance pipe

FM

TO

TS1

Liquidtank

4-Way valve

Accumulator

TK2

TK4

TK1

SV3E

SV41 SV42

SV3D

SV3A

TK3

SV3C

Oil tank

OS

TE1

SV5

SV3B

Ps sensor

SV2TL

PMV1 PMV2

Com

pres

sor

1

Com

pres

sor

2

TD1

HP HP

TD2

Pd sensor

*3*1*2

7

5. Recovery of Refrigerant in Failed Outdoor Unit (In Case of Failure of Follower Unit)

Header unit(MMY-MAP1001H)

Follower unit(MMY-MAP1001H)

Indoor unit

NOTEAn outdoor unit which is connected with indoor/outdoor communication lines isreferred to as ‘‘Header unit’’, and the other unit is called the ‘‘Follower unit’’.

(Example: 20HP system)

High-pressure gas or condensate liquid refrigerantEvaporative gas refrigerant (Low-pressure gas)

Failure

*1 Packed valve of balance pipe = Open fully*2 Packed valve at liquid side = Close fully*3 Service valve open fully at gas side Close fully 10 minutes after operation start

Page 46: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

43

Sensible capacity table

8

Page 47: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

44

Foreword

Page 48: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

45

14.0oCWB 16.0oCWB 18.0oCWB 19.0oCWB 20.0oCWB 22.0oCWB 24.0oCWB20oCDB 23oCDB 26oCDB 27oCDB 28oCDB 30oCDB 32oCDB

oCDB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC10.0 2.3 1.9 2.5 2.0 2.7 2.1 2.8 2.1 2.9 2.1 3.1 2.1 3.2 2.012.0 2.3 1.9 2.5 2.0 2.7 2.1 2.8 2.1 2.9 2.1 3.1 2.1 3.2 2.014.0 2.3 1.9 2.5 2.0 2.7 2.1 2.8 2.1 2.9 2.1 3.1 2.1 3.2 2.016.0 2.3 1.9 2.5 2.0 2.7 2.1 2.8 2.1 2.9 2.1 3.1 2.1 3.2 2.018.0 2.3 1.9 2.5 2.0 2.7 2.1 2.8 2.1 2.9 2.1 3.1 2.1 3.2 2.020.0 2.3 1.9 2.5 2.0 2.7 2.1 2.8 2.1 2.9 2.1 3.1 2.1 3.2 2.021.0 2.3 1.9 2.5 2.0 2.7 2.1 2.8 2.1 2.9 2.1 3.1 2.1 3.2 2.0

009 23.0 2.3 1.9 2.5 2.0 2.7 2.1 2.8 2.1 2.9 2.1 3.1 2.1 3.2 2.025.0 2.3 1.9 2.5 2.0 2.7 2.1 2.8 2.1 2.9 2.1 3.1 2.1 3.2 2.027.0 2.3 1.9 2.5 2.0 2.7 2.1 2.8 2.1 2.9 2.1 3.1 2.1 3.2 2.029.0 2.3 1.9 2.5 2.0 2.7 2.1 2.8 2.1 2.9 2.1 3.1 2.1 3.2 2.031.0 2.3 1.9 2.5 2.0 2.7 2.1 2.8 2.1 2.9 2.1 3.1 2.1 3.2 2.033.0 2.3 1.9 2.5 2.0 2.7 2.1 2.8 2.1 2.9 2.1 3.1 2.1 3.2 2.035.0 2.3 1.9 2.5 2.0 2.7 2.1 2.8 2.1 2.9 2.1 3.1 2.1 3.2 2.037.0 2.2 1.8 2.5 1.9 2.6 2.0 2.7 2.0 2.8 2.0 3.0 2.0 3.1 2.039.0 2.2 1.8 2.4 1.9 2.6 2.0 2.6 2.0 2.7 2.0 2.9 2.0 3.0 1.910.0 3.0 2.3 3.3 2.5 3.5 2.6 3.6 2.6 3.7 2.6 3.9 2.6 4.1 2.512.0 3.0 2.3 3.3 2.5 3.5 2.6 3.6 2.6 3.7 2.6 3.9 2.6 4.1 2.514.0 3.0 2.3 3.3 2.5 3.5 2.6 3.6 2.6 3.7 2.6 3.9 2.6 4.1 2.516.0 3.0 2.3 3.3 2.5 3.5 2.6 3.6 2.6 3.7 2.6 3.9 2.6 4.1 2.518.0 3.0 2.3 3.3 2.5 3.5 2.6 3.6 2.6 3.7 2.6 3.9 2.6 4.1 2.520.0 3.0 2.3 3.3 2.5 3.5 2.6 3.6 2.6 3.7 2.6 3.9 2.6 4.1 2.521.0 3.0 2.3 3.3 2.5 3.5 2.6 3.6 2.6 3.7 2.6 3.9 2.6 4.1 2.5

012 23.0 3.0 2.3 3.3 2.5 3.5 2.6 3.6 2.6 3.7 2.6 3.9 2.6 4.1 2.525.0 3.0 2.3 3.3 2.5 3.5 2.6 3.6 2.6 3.7 2.6 3.9 2.6 4.1 2.527.0 3.0 2.3 3.3 2.5 3.5 2.6 3.6 2.6 3.7 2.6 3.9 2.6 4.1 2.529.0 3.0 2.3 3.3 2.5 3.5 2.6 3.6 2.6 3.7 2.6 3.9 2.6 4.1 2.531.0 3.0 2.3 3.3 2.5 3.5 2.6 3.6 2.6 3.7 2.6 3.9 2.6 4.1 2.533.0 3.0 2.3 3.3 2.5 3.5 2.6 3.6 2.6 3.7 2.6 3.9 2.6 4.1 2.535.0 3.0 2.3 3.3 2.5 3.5 2.6 3.6 2.6 3.7 2.6 3.9 2.6 4.1 2.537.0 2.9 2.2 3.2 2.4 3.4 2.5 3.5 2.5 3.6 2.5 3.8 2.5 4.0 2.439.0 2.8 2.2 3.1 2.3 3.3 2.5 3.4 2.4 3.5 2.4 3.7 2.4 3.9 2.410.0 3.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.112.0 3.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.114.0 3.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.116.0 3.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.118.0 3.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.120.0 3.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.121.0 3.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.1

015 23.0 3.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.125.0 3.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.127.0 3.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.129.0 3.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.131.0 3.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.133.0 3.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.135.0 3.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.137.0 3.6 2.7 4.0 2.9 4.2 3.1 4.4 3.1 4.5 3.1 4.7 3.1 5.0 3.039.0 3.5 2.7 3.8 2.8 4.1 3.0 4.2 3.0 4.4 3.0 4.6 3.0 4.8 2.910.0 4.6 3.5 5.1 3.8 5.4 4.0 5.6 4.0 5.8 4.0 6.1 4.0 6.4 3.912.0 4.6 3.5 5.1 3.8 5.4 4.0 5.6 4.0 5.8 4.0 6.1 4.0 6.4 3.914.0 4.6 3.5 5.1 3.8 5.4 4.0 5.6 4.0 5.8 4.0 6.1 4.0 6.4 3.916.0 4.6 3.5 5.1 3.8 5.4 4.0 5.6 4.0 5.8 4.0 6.1 4.0 6.4 3.918.0 4.6 3.5 5.1 3.8 5.4 4.0 5.6 4.0 5.8 4.0 6.1 4.0 6.4 3.920.0 4.6 3.5 5.1 3.8 5.4 4.0 5.6 4.0 5.8 4.0 6.1 4.0 6.4 3.921.0 4.6 3.5 5.1 3.8 5.4 4.0 5.6 4.0 5.8 4.0 6.1 4.0 6.4 3.9

018 23.0 4.6 3.5 5.1 3.8 5.4 4.0 5.6 4.0 5.8 4.0 6.1 4.0 6.4 3.925.0 4.6 3.5 5.1 3.8 5.4 4.0 5.6 4.0 5.8 4.0 6.1 4.0 6.4 3.927.0 4.6 3.5 5.1 3.8 5.4 4.0 5.6 4.0 5.8 4.0 6.1 4.0 6.4 3.929.0 4.6 3.5 5.1 3.8 5.4 4.0 5.6 4.0 5.8 4.0 6.1 4.0 6.4 3.931.0 4.6 3.5 5.1 3.8 5.4 4.0 5.6 4.0 5.8 4.0 6.1 4.0 6.4 3.933.0 4.6 3.5 5.1 3.8 5.4 4.0 5.6 4.0 5.8 4.0 6.1 4.0 6.4 3.935.0 4.6 3.5 5.1 3.8 5.4 4.0 5.6 4.0 5.8 4.0 6.1 4.0 6.4 3.937.0 4.5 3.4 4.9 3.7 5.3 3.9 5.4 3.9 5.6 3.9 5.9 3.8 6.2 3.739.0 4.3 3.3 4.8 3.6 5.1 3.8 5.3 3.8 5.4 3.8 5.7 3.7 6.0 3.6

8

8 ForewordSensible capacity table4-way Discharge Cassette Type ( MMU-AP****H) TC : Total capacity [kW] SHC : Sensible capacity [kW]

unitsize

outdoorair temp.

indoor air temp.

Page 49: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

46

14.0oCWB 16.0oCWB 18.0oCWB 19.0oCWB 20.0oCWB 22.0oCWB 24.0oCWB20oCDB 23oCDB 26oCDB 27oCDB 28oCDB 30oCDB 32oCDB

oCDB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC10.0 5.8 4.3 6.4 4.6 6.9 4.9 7.1 4.9 7.3 4.9 7.7 4.9 8.1 4.712.0 5.8 4.3 6.4 4.6 6.9 4.9 7.1 4.9 7.3 4.9 7.7 4.9 8.1 4.714.0 5.8 4.3 6.4 4.6 6.9 4.9 7.1 4.9 7.3 4.9 7.7 4.9 8.1 4.716.0 5.8 4.3 6.4 4.6 6.9 4.9 7.1 4.9 7.3 4.9 7.7 4.9 8.1 4.718.0 5.8 4.3 6.4 4.6 6.9 4.9 7.1 4.9 7.3 4.9 7.7 4.9 8.1 4.720.0 5.8 4.3 6.4 4.6 6.9 4.9 7.1 4.9 7.3 4.9 7.7 4.9 8.1 4.721.0 5.8 4.3 6.4 4.6 6.9 4.9 7.1 4.9 7.3 4.9 7.7 4.9 8.1 4.7

024 23.0 5.8 4.3 6.4 4.6 6.9 4.9 7.1 4.9 7.3 4.9 7.7 4.9 8.1 4.725.0 5.8 4.3 6.4 4.6 6.9 4.9 7.1 4.9 7.3 4.9 7.7 4.9 8.1 4.727.0 5.8 4.3 6.4 4.6 6.9 4.9 7.1 4.9 7.3 4.9 7.7 4.9 8.1 4.729.0 5.8 4.3 6.4 4.6 6.9 4.9 7.1 4.9 7.3 4.9 7.7 4.9 8.1 4.731.0 5.8 4.3 6.4 4.6 6.9 4.9 7.1 4.9 7.3 4.9 7.7 4.9 8.1 4.733.0 5.8 4.3 6.4 4.6 6.9 4.9 7.1 4.9 7.3 4.9 7.7 4.9 8.1 4.735.0 5.8 4.3 6.4 4.6 6.9 4.9 7.1 4.9 7.3 4.9 7.7 4.9 8.1 4.737.0 5.6 4.2 6.2 4.5 6.7 4.8 6.9 4.7 7.1 4.7 7.5 4.7 7.8 4.639.0 5.5 4.1 6.1 4.4 6.5 4.6 6.7 4.6 6.9 4.6 7.3 4.6 7.6 4.510.0 6.6 4.9 7.3 5.2 7.8 5.5 8.0 5.5 8.2 5.5 8.7 5.4 9.1 5.312.0 6.6 4.9 7.3 5.2 7.8 5.5 8.0 5.5 8.2 5.5 8.7 5.4 9.1 5.314.0 6.6 4.9 7.3 5.2 7.8 5.5 8.0 5.5 8.2 5.5 8.7 5.4 9.1 5.316.0 6.6 4.9 7.3 5.2 7.8 5.5 8.0 5.5 8.2 5.5 8.7 5.4 9.1 5.318.0 6.6 4.9 7.3 5.2 7.8 5.5 8.0 5.5 8.2 5.5 8.7 5.4 9.1 5.320.0 6.6 4.9 7.3 5.2 7.8 5.5 8.0 5.5 8.2 5.5 8.7 5.4 9.1 5.321.0 6.6 4.9 7.3 5.2 7.8 5.5 8.0 5.5 8.2 5.5 8.7 5.4 9.1 5.3

027 23.0 6.6 4.9 7.3 5.2 7.8 5.5 8.0 5.5 8.2 5.5 8.7 5.4 9.1 5.325.0 6.6 4.9 7.3 5.2 7.8 5.5 8.0 5.5 8.2 5.5 8.7 5.4 9.1 5.327.0 6.6 4.9 7.3 5.2 7.8 5.5 8.0 5.5 8.2 5.5 8.7 5.4 9.1 5.329.0 6.6 4.9 7.3 5.2 7.8 5.5 8.0 5.5 8.2 5.5 8.7 5.4 9.1 5.331.0 6.6 4.9 7.3 5.2 7.8 5.5 8.0 5.5 8.2 5.5 8.7 5.4 9.1 5.333.0 6.6 4.9 7.3 5.2 7.8 5.5 8.0 5.5 8.2 5.5 8.7 5.4 9.1 5.335.0 6.6 4.9 7.3 5.2 7.8 5.5 8.0 5.5 8.2 5.5 8.7 5.4 9.1 5.337.0 6.4 4.7 7.0 5.0 7.5 5.3 7.7 5.3 8.0 5.3 8.4 5.3 8.8 5.239.0 6.2 4.6 6.8 4.9 7.3 5.2 7.5 5.2 7.8 5.2 8.2 5.1 8.6 5.010.0 7.4 5.5 8.2 5.9 8.7 6.2 9.0 6.2 9.3 6.2 9.8 6.1 10.3 6.012.0 7.4 5.5 8.2 5.9 8.7 6.2 9.0 6.2 9.3 6.2 9.8 6.1 10.3 6.014.0 7.4 5.5 8.2 5.9 8.7 6.2 9.0 6.2 9.3 6.2 9.8 6.1 10.3 6.016.0 7.4 5.5 8.2 5.9 8.7 6.2 9.0 6.2 9.3 6.2 9.8 6.1 10.3 6.018.0 7.4 5.5 8.2 5.9 8.7 6.2 9.0 6.2 9.3 6.2 9.8 6.1 10.3 6.020.0 7.4 5.5 8.2 5.9 8.7 6.2 9.0 6.2 9.3 6.2 9.8 6.1 10.3 6.021.0 7.4 5.5 8.2 5.9 8.7 6.2 9.0 6.2 9.3 6.2 9.8 6.1 10.3 6.0

030 23.0 7.4 5.5 8.2 5.9 8.7 6.2 9.0 6.2 9.3 6.2 9.8 6.1 10.3 6.025.0 7.4 5.5 8.2 5.9 8.7 6.2 9.0 6.2 9.3 6.2 9.8 6.1 10.3 6.027.0 7.4 5.5 8.2 5.9 8.7 6.2 9.0 6.2 9.3 6.2 9.8 6.1 10.3 6.029.0 7.4 5.5 8.2 5.9 8.7 6.2 9.0 6.2 9.3 6.2 9.8 6.1 10.3 6.031.0 7.4 5.5 8.2 5.9 8.7 6.2 9.0 6.2 9.3 6.2 9.8 6.1 10.3 6.033.0 7.4 5.5 8.2 5.9 8.7 6.2 9.0 6.2 9.3 6.2 9.8 6.1 10.3 6.035.0 7.4 5.5 8.2 5.9 8.7 6.2 9.0 6.2 9.3 6.2 9.8 6.1 10.3 6.037.0 7.2 5.3 7.9 5.7 8.5 6.0 8.7 6.0 9.0 6.0 9.5 5.9 9.9 5.839.0 7.0 5.2 7.7 5.5 8.2 5.9 8.5 5.8 8.7 5.8 9.2 5.8 9.7 5.610.0 9.2 6.8 10.2 7.3 10.9 7.7 11.2 7.7 11.5 7.7 12.2 7.6 12.8 7.512.0 9.2 6.8 10.2 7.3 10.9 7.7 11.2 7.7 11.5 7.7 12.2 7.6 12.8 7.514.0 9.2 6.8 10.2 7.3 10.9 7.7 11.2 7.7 11.5 7.7 12.2 7.6 12.8 7.516.0 9.2 6.8 10.2 7.3 10.9 7.7 11.2 7.7 11.5 7.7 12.2 7.6 12.8 7.518.0 9.2 6.8 10.2 7.3 10.9 7.7 11.2 7.7 11.5 7.7 12.2 7.6 12.8 7.520.0 9.2 6.8 10.2 7.3 10.9 7.7 11.2 7.7 11.5 7.7 12.2 7.6 12.8 7.521.0 9.2 6.8 10.2 7.3 10.9 7.7 11.2 7.7 11.5 7.7 12.2 7.6 12.8 7.5

036 23.0 9.2 6.8 10.2 7.3 10.9 7.7 11.2 7.7 11.5 7.7 12.2 7.6 12.8 7.525.0 9.2 6.8 10.2 7.3 10.9 7.7 11.2 7.7 11.5 7.7 12.2 7.6 12.8 7.527.0 9.2 6.8 10.2 7.3 10.9 7.7 11.2 7.7 11.5 7.7 12.2 7.6 12.8 7.529.0 9.2 6.8 10.2 7.3 10.9 7.7 11.2 7.7 11.5 7.7 12.2 7.6 12.8 7.531.0 9.2 6.8 10.2 7.3 10.9 7.7 11.2 7.7 11.5 7.7 12.2 7.6 12.8 7.533.0 9.2 6.8 10.2 7.3 10.9 7.7 11.2 7.7 11.5 7.7 12.2 7.6 12.8 7.535.0 9.2 6.8 10.2 7.3 10.9 7.7 11.2 7.7 11.5 7.7 12.2 7.6 12.8 7.537.0 8.9 6.6 9.8 7.0 10.5 7.5 10.8 7.5 11.2 7.5 11.8 7.4 12.4 7.239.0 8.7 6.4 9.6 6.8 10.2 7.3 10.5 7.2 10.9 7.2 11.5 7.2 12.0 7.0

8

4-way Discharge Cassette Type ( MMU-AP****H) TC : Total capacity [kW] SHC : Sensible capacity [kW]

unitsize

outdoorair temp.

indoor air temp.

Page 50: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

47

14.0oCWB 16.0oCWB 18.0oCWB 19.0oCWB 20.0oCWB 22.0oCWB 24.0oCWB20oCDB 23oCDB 26oCDB 27oCDB 28oCDB 30oCDB 32oCDB

oCDB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC10.0 11.5 8.7 12.7 9.3 13.6 9.8 14.0 9.8 14.4 9.8 15.3 9.7 16.0 9.512.0 11.5 8.7 12.7 9.3 13.6 9.8 14.0 9.8 14.4 9.8 15.3 9.7 16.0 9.514.0 11.5 8.7 12.7 9.3 13.6 9.8 14.0 9.8 14.4 9.8 15.3 9.7 16.0 9.516.0 11.5 8.7 12.7 9.3 13.6 9.8 14.0 9.8 14.4 9.8 15.3 9.7 16.0 9.518.0 11.5 8.7 12.7 9.3 13.6 9.8 14.0 9.8 14.4 9.8 15.3 9.7 16.0 9.520.0 11.5 8.7 12.7 9.3 13.6 9.8 14.0 9.8 14.4 9.8 15.3 9.7 16.0 9.521.0 11.5 8.7 12.7 9.3 13.6 9.8 14.0 9.8 14.4 9.8 15.3 9.7 16.0 9.5

048 23.0 11.5 8.7 12.7 9.3 13.6 9.8 14.0 9.8 14.4 9.8 15.3 9.7 16.0 9.525.0 11.5 8.7 12.7 9.3 13.6 9.8 14.0 9.8 14.4 9.8 15.3 9.7 16.0 9.527.0 11.5 8.7 12.7 9.3 13.6 9.8 14.0 9.8 14.4 9.8 15.3 9.7 16.0 9.529.0 11.5 8.7 12.7 9.3 13.6 9.8 14.0 9.8 14.4 9.8 15.3 9.7 16.0 9.531.0 11.5 8.7 12.7 9.3 13.6 9.8 14.0 9.8 14.4 9.8 15.3 9.7 16.0 9.533.0 11.5 8.7 12.7 9.3 13.6 9.8 14.0 9.8 14.4 9.8 15.3 9.7 16.0 9.535.0 11.5 8.7 12.7 9.3 13.6 9.8 14.0 9.8 14.4 9.8 15.3 9.7 16.0 9.537.0 11.1 8.4 12.3 9.0 13.1 9.5 13.6 9.5 14.0 9.5 14.8 9.4 15.4 9.239.0 10.8 8.2 12.0 8.7 12.8 9.2 13.2 9.2 13.6 9.2 14.4 9.1 15.0 8.910.0 13.1 9.8 14.5 10.4 15.5 11.0 16.0 11.0 16.5 11.0 17.4 10.9 18.2 10.612.0 13.1 9.8 14.5 10.4 15.5 11.0 16.0 11.0 16.5 11.0 17.4 10.9 18.2 10.614.0 13.1 9.8 14.5 10.4 15.5 11.0 16.0 11.0 16.5 11.0 17.4 10.9 18.2 10.616.0 13.1 9.8 14.5 10.4 15.5 11.0 16.0 11.0 16.5 11.0 17.4 10.9 18.2 10.618.0 13.1 9.8 14.5 10.4 15.5 11.0 16.0 11.0 16.5 11.0 17.4 10.9 18.2 10.620.0 13.1 9.8 14.5 10.4 15.5 11.0 16.0 11.0 16.5 11.0 17.4 10.9 18.2 10.621.0 13.1 9.8 14.5 10.4 15.5 11.0 16.0 11.0 16.5 11.0 17.4 10.9 18.2 10.6

056 23.0 13.1 9.8 14.5 10.4 15.5 11.0 16.0 11.0 16.5 11.0 17.4 10.9 18.2 10.625.0 13.1 9.8 14.5 10.4 15.5 11.0 16.0 11.0 16.5 11.0 17.4 10.9 18.2 10.627.0 13.1 9.8 14.5 10.4 15.5 11.0 16.0 11.0 16.5 11.0 17.4 10.9 18.2 10.629.0 13.1 9.8 14.5 10.4 15.5 11.0 16.0 11.0 16.5 11.0 17.4 10.9 18.2 10.631.0 13.1 9.8 14.5 10.4 15.5 11.0 16.0 11.0 16.5 11.0 17.4 10.9 18.2 10.633.0 13.1 9.8 14.5 10.4 15.5 11.0 16.0 11.0 16.5 11.0 17.4 10.9 18.2 10.635.0 13.1 9.8 14.5 10.4 15.5 11.0 16.0 11.0 16.5 11.0 17.4 10.9 18.2 10.637.0 12.7 9.4 14.1 10.1 15.0 10.7 15.5 10.6 16.0 10.6 16.9 10.5 17.7 10.339.0 12.4 9.2 13.7 9.8 14.6 10.4 15.1 10.4 15.5 10.4 16.4 10.3 17.2 10.0

8

Foreword

4-way Discharge Cassette Type ( MMU-AP****H) TC : Total capacity [kW] SHC : Sensible capacity [kW]

unitsize

outdoorair temp.

indoor air temp.

Page 51: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

48

14.0oCWB 16.0oCWB 18.0oCWB 19.0oCWB 20.0oCWB 22.0oCWB 24.0oCWB20oCDB 23oCDB 26oCDB 27oCDB 28oCDB 30oCDB 32oCDB

oCDB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC10.0 1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.612.0 1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.614.0 1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.616.0 1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.618.0 1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.620.0 1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.621.0 1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.6

007 23.0 1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.625.0 1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.627.0 1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.629.0 1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.631.0 1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.633.0 1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.635.0 1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.637.0 1.7 1.5 1.9 1.6 2.1 1.7 2.1 1.6 2.2 1.6 2.3 1.6 2.4 1.639.0 1.7 1.4 1.9 1.5 2.0 1.6 2.1 1.6 2.1 1.6 2.3 1.6 2.4 1.510.0 2.3 1.8 2.5 1.9 2.7 2.0 2.8 2.0 2.9 2.0 3.1 2.0 3.2 1.912.0 2.3 1.8 2.5 1.9 2.7 2.0 2.8 2.0 2.9 2.0 3.1 2.0 3.2 1.914.0 2.3 1.8 2.5 1.9 2.7 2.0 2.8 2.0 2.9 2.0 3.1 2.0 3.2 1.916.0 2.3 1.8 2.5 1.9 2.7 2.0 2.8 2.0 2.9 2.0 3.1 2.0 3.2 1.918.0 2.3 1.8 2.5 1.9 2.7 2.0 2.8 2.0 2.9 2.0 3.1 2.0 3.2 1.920.0 2.3 1.8 2.5 1.9 2.7 2.0 2.8 2.0 2.9 2.0 3.1 2.0 3.2 1.921.0 2.3 1.8 2.5 1.9 2.7 2.0 2.8 2.0 2.9 2.0 3.1 2.0 3.2 1.9

009 23.0 2.3 1.8 2.5 1.9 2.7 2.0 2.8 2.0 2.9 2.0 3.1 2.0 3.2 1.925.0 2.3 1.8 2.5 1.9 2.7 2.0 2.8 2.0 2.9 2.0 3.1 2.0 3.2 1.927.0 2.3 1.8 2.5 1.9 2.7 2.0 2.8 2.0 2.9 2.0 3.1 2.0 3.2 1.929.0 2.3 1.8 2.5 1.9 2.7 2.0 2.8 2.0 2.9 2.0 3.1 2.0 3.2 1.931.0 2.3 1.8 2.5 1.9 2.7 2.0 2.8 2.0 2.9 2.0 3.1 2.0 3.2 1.933.0 2.3 1.8 2.5 1.9 2.7 2.0 2.8 2.0 2.9 2.0 3.1 2.0 3.2 1.935.0 2.3 1.8 2.5 1.9 2.7 2.0 2.8 2.0 2.9 2.0 3.1 2.0 3.2 1.937.0 2.2 1.7 2.5 1.8 2.6 1.9 2.7 1.9 2.8 1.9 3.0 1.9 3.1 1.939.0 2.2 1.7 2.4 1.8 2.6 1.9 2.6 1.9 2.7 1.9 2.9 1.9 3.0 1.810.0 3.0 2.0 3.3 2.2 3.5 2.3 3.6 2.3 3.7 2.3 3.9 2.3 4.1 2.212.0 3.0 2.0 3.3 2.2 3.5 2.3 3.6 2.3 3.7 2.3 3.9 2.3 4.1 2.214.0 3.0 2.0 3.3 2.2 3.5 2.3 3.6 2.3 3.7 2.3 3.9 2.3 4.1 2.216.0 3.0 2.0 3.3 2.2 3.5 2.3 3.6 2.3 3.7 2.3 3.9 2.3 4.1 2.218.0 3.0 2.0 3.3 2.2 3.5 2.3 3.6 2.3 3.7 2.3 3.9 2.3 4.1 2.220.0 3.0 2.0 3.3 2.2 3.5 2.3 3.6 2.3 3.7 2.3 3.9 2.3 4.1 2.221.0 3.0 2.0 3.3 2.2 3.5 2.3 3.6 2.3 3.7 2.3 3.9 2.3 4.1 2.2

012 23.0 3.0 2.0 3.3 2.2 3.5 2.3 3.6 2.3 3.7 2.3 3.9 2.3 4.1 2.225.0 3.0 2.0 3.3 2.2 3.5 2.3 3.6 2.3 3.7 2.3 3.9 2.3 4.1 2.227.0 3.0 2.0 3.3 2.2 3.5 2.3 3.6 2.3 3.7 2.3 3.9 2.3 4.1 2.229.0 3.0 2.0 3.3 2.2 3.5 2.3 3.6 2.3 3.7 2.3 3.9 2.3 4.1 2.231.0 3.0 2.0 3.3 2.2 3.5 2.3 3.6 2.3 3.7 2.3 3.9 2.3 4.1 2.233.0 3.0 2.0 3.3 2.2 3.5 2.3 3.6 2.3 3.7 2.3 3.9 2.3 4.1 2.235.0 3.0 2.0 3.3 2.2 3.5 2.3 3.6 2.3 3.7 2.3 3.9 2.3 4.1 2.237.0 2.9 2.0 3.2 2.1 3.4 2.2 3.5 2.2 3.6 2.2 3.8 2.2 4.0 2.239.0 2.8 1.9 3.1 2.0 3.3 2.2 3.4 2.2 3.5 2.2 3.7 2.1 3.9 2.110.0 3.7 2.7 4.1 2.9 4.4 3.1 4.5 3.1 4.6 3.1 4.9 3.0 5.1 3.012.0 3.7 2.7 4.1 2.9 4.4 3.1 4.5 3.1 4.6 3.1 4.9 3.0 5.1 3.014.0 3.7 2.7 4.1 2.9 4.4 3.1 4.5 3.1 4.6 3.1 4.9 3.0 5.1 3.016.0 3.7 2.7 4.1 2.9 4.4 3.1 4.5 3.1 4.6 3.1 4.9 3.0 5.1 3.018.0 3.7 2.7 4.1 2.9 4.4 3.1 4.5 3.1 4.6 3.1 4.9 3.0 5.1 3.020.0 3.7 2.7 4.1 2.9 4.4 3.1 4.5 3.1 4.6 3.1 4.9 3.0 5.1 3.021.0 3.7 2.7 4.1 2.9 4.4 3.1 4.5 3.1 4.6 3.1 4.9 3.0 5.1 3.0

015 23.0 3.7 2.7 4.1 2.9 4.4 3.1 4.5 3.1 4.6 3.1 4.9 3.0 5.1 3.025.0 3.7 2.7 4.1 2.9 4.4 3.1 4.5 3.1 4.6 3.1 4.9 3.0 5.1 3.027.0 3.7 2.7 4.1 2.9 4.4 3.1 4.5 3.1 4.6 3.1 4.9 3.0 5.1 3.029.0 3.7 2.7 4.1 2.9 4.4 3.1 4.5 3.1 4.6 3.1 4.9 3.0 5.1 3.031.0 3.7 2.7 4.1 2.9 4.4 3.1 4.5 3.1 4.6 3.1 4.9 3.0 5.1 3.033.0 3.7 2.7 4.1 2.9 4.4 3.1 4.5 3.1 4.6 3.1 4.9 3.0 5.1 3.035.0 3.7 2.7 4.1 2.9 4.4 3.1 4.5 3.1 4.6 3.1 4.9 3.0 5.1 3.037.0 3.6 2.6 4.0 2.8 4.2 3.0 4.4 3.0 4.5 3.0 4.7 2.9 5.0 2.939.0 3.5 2.5 3.8 2.7 4.1 2.9 4.2 2.9 4.4 2.9 4.6 2.8 4.8 2.8

8

2-way Air Discharge Cassette Type ( MMU-AP****WH)TC : Total capacity [kW] SHC : Sensible capacity [kW]

unitsize

outdoorair temp.

indoor air temp.

Page 52: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

49

14.0oCWB 16.0oCWB 18.0oCWB 19.0oCWB 20.0oCWB 22.0oCWB 24.0oCWB20oCDB 23oCDB 26oCDB 27oCDB 28oCDB 30oCDB 32oCDB

oCDB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC10.0 4.6 3.4 5.1 3.6 5.4 3.8 5.6 3.8 5.8 3.8 6.1 3.8 6.4 3.712.0 4.6 3.4 5.1 3.6 5.4 3.8 5.6 3.8 5.8 3.8 6.1 3.8 6.4 3.714.0 4.6 3.4 5.1 3.6 5.4 3.8 5.6 3.8 5.8 3.8 6.1 3.8 6.4 3.716.0 4.6 3.4 5.1 3.6 5.4 3.8 5.6 3.8 5.8 3.8 6.1 3.8 6.4 3.718.0 4.6 3.4 5.1 3.6 5.4 3.8 5.6 3.8 5.8 3.8 6.1 3.8 6.4 3.720.0 4.6 3.4 5.1 3.6 5.4 3.8 5.6 3.8 5.8 3.8 6.1 3.8 6.4 3.721.0 4.6 3.4 5.1 3.6 5.4 3.8 5.6 3.8 5.8 3.8 6.1 3.8 6.4 3.7

018 23.0 4.6 3.4 5.1 3.6 5.4 3.8 5.6 3.8 5.8 3.8 6.1 3.8 6.4 3.725.0 4.6 3.4 5.1 3.6 5.4 3.8 5.6 3.8 5.8 3.8 6.1 3.8 6.4 3.727.0 4.6 3.4 5.1 3.6 5.4 3.8 5.6 3.8 5.8 3.8 6.1 3.8 6.4 3.729.0 4.6 3.4 5.1 3.6 5.4 3.8 5.6 3.8 5.8 3.8 6.1 3.8 6.4 3.731.0 4.6 3.4 5.1 3.6 5.4 3.8 5.6 3.8 5.8 3.8 6.1 3.8 6.4 3.733.0 4.6 3.4 5.1 3.6 5.4 3.8 5.6 3.8 5.8 3.8 6.1 3.8 6.4 3.735.0 4.6 3.4 5.1 3.6 5.4 3.8 5.6 3.8 5.8 3.8 6.1 3.8 6.4 3.737.0 4.5 3.3 4.9 3.5 5.3 3.7 5.4 3.7 5.6 3.7 5.9 3.6 6.2 3.639.0 4.3 3.2 4.8 3.4 5.1 3.6 5.3 3.6 5.4 3.6 5.7 3.5 6.0 3.510.0 5.8 4.3 6.4 4.5 6.9 4.8 7.1 4.8 7.3 4.8 7.7 4.8 8.1 4.612.0 5.8 4.3 6.4 4.5 6.9 4.8 7.1 4.8 7.3 4.8 7.7 4.8 8.1 4.614.0 5.8 4.3 6.4 4.5 6.9 4.8 7.1 4.8 7.3 4.8 7.7 4.8 8.1 4.616.0 5.8 4.3 6.4 4.5 6.9 4.8 7.1 4.8 7.3 4.8 7.7 4.8 8.1 4.618.0 5.8 4.3 6.4 4.5 6.9 4.8 7.1 4.8 7.3 4.8 7.7 4.8 8.1 4.620.0 5.8 4.3 6.4 4.5 6.9 4.8 7.1 4.8 7.3 4.8 7.7 4.8 8.1 4.621.0 5.8 4.3 6.4 4.5 6.9 4.8 7.1 4.8 7.3 4.8 7.7 4.8 8.1 4.6

024 23.0 5.8 4.3 6.4 4.5 6.9 4.8 7.1 4.8 7.3 4.8 7.7 4.8 8.1 4.625.0 5.8 4.3 6.4 4.5 6.9 4.8 7.1 4.8 7.3 4.8 7.7 4.8 8.1 4.627.0 5.8 4.3 6.4 4.5 6.9 4.8 7.1 4.8 7.3 4.8 7.7 4.8 8.1 4.629.0 5.8 4.3 6.4 4.5 6.9 4.8 7.1 4.8 7.3 4.8 7.7 4.8 8.1 4.631.0 5.8 4.3 6.4 4.5 6.9 4.8 7.1 4.8 7.3 4.8 7.7 4.8 8.1 4.633.0 5.8 4.3 6.4 4.5 6.9 4.8 7.1 4.8 7.3 4.8 7.7 4.8 8.1 4.635.0 5.8 4.3 6.4 4.5 6.9 4.8 7.1 4.8 7.3 4.8 7.7 4.8 8.1 4.637.0 5.6 4.1 6.2 4.4 6.7 4.7 6.9 4.6 7.1 4.6 7.5 4.6 7.8 4.539.0 5.5 4.0 6.1 4.3 6.5 4.5 6.7 4.5 6.9 4.5 7.3 4.5 7.6 4.410.0 6.6 4.9 7.3 5.2 7.8 5.5 8.0 5.5 8.2 5.5 8.7 5.4 9.1 5.312.0 6.6 4.9 7.3 5.2 7.8 5.5 8.0 5.5 8.2 5.5 8.7 5.4 9.1 5.314.0 6.6 4.9 7.3 5.2 7.8 5.5 8.0 5.5 8.2 5.5 8.7 5.4 9.1 5.316.0 6.6 4.9 7.3 5.2 7.8 5.5 8.0 5.5 8.2 5.5 8.7 5.4 9.1 5.318.0 6.6 4.9 7.3 5.2 7.8 5.5 8.0 5.5 8.2 5.5 8.7 5.4 9.1 5.320.0 6.6 4.9 7.3 5.2 7.8 5.5 8.0 5.5 8.2 5.5 8.7 5.4 9.1 5.321.0 6.6 4.9 7.3 5.2 7.8 5.5 8.0 5.5 8.2 5.5 8.7 5.4 9.1 5.3

027 23.0 6.6 4.9 7.3 5.2 7.8 5.5 8.0 5.5 8.2 5.5 8.7 5.4 9.1 5.325.0 6.6 4.9 7.3 5.2 7.8 5.5 8.0 5.5 8.2 5.5 8.7 5.4 9.1 5.327.0 6.6 4.9 7.3 5.2 7.8 5.5 8.0 5.5 8.2 5.5 8.7 5.4 9.1 5.329.0 6.6 4.9 7.3 5.2 7.8 5.5 8.0 5.5 8.2 5.5 8.7 5.4 9.1 5.331.0 6.6 4.9 7.3 5.2 7.8 5.5 8.0 5.5 8.2 5.5 8.7 5.4 9.1 5.333.0 6.6 4.9 7.3 5.2 7.8 5.5 8.0 5.5 8.2 5.5 8.7 5.4 9.1 5.335.0 6.6 4.9 7.3 5.2 7.8 5.5 8.0 5.5 8.2 5.5 8.7 5.4 9.1 5.337.0 6.4 4.7 7.0 5.0 7.5 5.3 7.7 5.3 8.0 5.3 8.4 5.3 8.8 5.239.0 6.2 4.6 6.8 4.9 7.3 5.2 7.5 5.2 7.8 5.2 8.2 5.1 8.6 5.010.0 7.4 5.3 8.2 5.7 8.7 6.0 9.0 6.0 9.3 6.0 9.8 5.9 10.3 5.812.0 7.4 5.3 8.2 5.7 8.7 6.0 9.0 6.0 9.3 6.0 9.8 5.9 10.3 5.814.0 7.4 5.3 8.2 5.7 8.7 6.0 9.0 6.0 9.3 6.0 9.8 5.9 10.3 5.816.0 7.4 5.3 8.2 5.7 8.7 6.0 9.0 6.0 9.3 6.0 9.8 5.9 10.3 5.818.0 7.4 5.3 8.2 5.7 8.7 6.0 9.0 6.0 9.3 6.0 9.8 5.9 10.3 5.820.0 7.4 5.3 8.2 5.7 8.7 6.0 9.0 6.0 9.3 6.0 9.8 5.9 10.3 5.821.0 7.4 5.3 8.2 5.7 8.7 6.0 9.0 6.0 9.3 6.0 9.8 5.9 10.3 5.8

030 23.0 7.4 5.3 8.2 5.7 8.7 6.0 9.0 6.0 9.3 6.0 9.8 5.9 10.3 5.825.0 7.4 5.3 8.2 5.7 8.7 6.0 9.0 6.0 9.3 6.0 9.8 5.9 10.3 5.827.0 7.4 5.3 8.2 5.7 8.7 6.0 9.0 6.0 9.3 6.0 9.8 5.9 10.3 5.829.0 7.4 5.3 8.2 5.7 8.7 6.0 9.0 6.0 9.3 6.0 9.8 5.9 10.3 5.831.0 7.4 5.3 8.2 5.7 8.7 6.0 9.0 6.0 9.3 6.0 9.8 5.9 10.3 5.833.0 7.4 5.3 8.2 5.7 8.7 6.0 9.0 6.0 9.3 6.0 9.8 5.9 10.3 5.835.0 7.4 5.3 8.2 5.7 8.7 6.0 9.0 6.0 9.3 6.0 9.8 5.9 10.3 5.837.0 7.2 5.1 7.9 5.5 8.5 5.8 8.7 5.8 9.0 5.8 9.5 5.8 9.9 5.639.0 7.0 5.0 7.7 5.3 8.2 5.7 8.5 5.6 8.7 5.6 9.2 5.6 9.7 5.5

8

2-way Air Discharge Cassette Type ( MMU-AP****WH)TC : Total capacity [kW] SHC : Sensible capacity [kW]indoor air temp.

unitsize

outdoorair temp.

Page 53: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

50

14.0oCWB 16.0oCWB 18.0oCWB 19.0oCWB 20.0oCWB 22.0oCWB 24.0oCWB20oCDB 23oCDB 26oCDB 27oCDB 28oCDB 30oCDB 32oCDB

oCDB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC10.0 11.5 8.4 12.7 9.0 13.6 9.5 14.0 9.5 14.4 9.5 15.3 9.4 16.0 9.212.0 11.5 8.4 12.7 9.0 13.6 9.5 14.0 9.5 14.4 9.5 15.3 9.4 16.0 9.214.0 11.5 8.4 12.7 9.0 13.6 9.5 14.0 9.5 14.4 9.5 15.3 9.4 16.0 9.216.0 11.5 8.4 12.7 9.0 13.6 9.5 14.0 9.5 14.4 9.5 15.3 9.4 16.0 9.218.0 11.5 8.4 12.7 9.0 13.6 9.5 14.0 9.5 14.4 9.5 15.3 9.4 16.0 9.220.0 11.5 8.4 12.7 9.0 13.6 9.5 14.0 9.5 14.4 9.5 15.3 9.4 16.0 9.221.0 11.5 8.4 12.7 9.0 13.6 9.5 14.0 9.5 14.4 9.5 15.3 9.4 16.0 9.2

048 23.0 11.5 8.4 12.7 9.0 13.6 9.5 14.0 9.5 14.4 9.5 15.3 9.4 16.0 9.225.0 11.5 8.4 12.7 9.0 13.6 9.5 14.0 9.5 14.4 9.5 15.3 9.4 16.0 9.227.0 11.5 8.4 12.7 9.0 13.6 9.5 14.0 9.5 14.4 9.5 15.3 9.4 16.0 9.229.0 11.5 8.4 12.7 9.0 13.6 9.5 14.0 9.5 14.4 9.5 15.3 9.4 16.0 9.231.0 11.5 8.4 12.7 9.0 13.6 9.5 14.0 9.5 14.4 9.5 15.3 9.4 16.0 9.233.0 11.5 8.4 12.7 9.0 13.6 9.5 14.0 9.5 14.4 9.5 15.3 9.4 16.0 9.235.0 11.5 8.4 12.7 9.0 13.6 9.5 14.0 9.5 14.4 9.5 15.3 9.4 16.0 9.237.0 11.1 8.2 12.3 8.7 13.1 9.2 13.6 9.2 14.0 9.2 14.8 9.1 15.4 8.939.0 10.8 7.9 12.0 8.4 12.8 9.0 13.2 8.9 13.6 8.9 14.4 8.9 15.0 8.7

8

2-way Air Discharge Cassette Type ( MMU-AP****WH)TC : Total capacity [kW] SHC : Sensible capacity [kW]

unitsize

outdoorair temp.

indoor air temp.

Page 54: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

51

14.0oCWB 16.0oCWB 18.0oCWB 19.0oCWB 20.0oCWB 22.0oCWB 24.0oCWB20oCDB 23oCDB 26oCDB 27oCDB 28oCDB 30oCDB 32oCDB

oCDB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC10.0 1.8 1.6 2.0 1.7 2.1 1.8 2.2 1.8 2.3 1.8 2.4 1.8 2.5 1.712.0 1.8 1.6 2.0 1.7 2.1 1.8 2.2 1.8 2.3 1.8 2.4 1.8 2.5 1.714.0 1.8 1.6 2.0 1.7 2.1 1.8 2.2 1.8 2.3 1.8 2.4 1.8 2.5 1.716.0 1.8 1.6 2.0 1.7 2.1 1.8 2.2 1.8 2.3 1.8 2.4 1.8 2.5 1.718.0 1.8 1.6 2.0 1.7 2.1 1.8 2.2 1.8 2.3 1.8 2.4 1.8 2.5 1.720.0 1.8 1.6 2.0 1.7 2.1 1.8 2.2 1.8 2.3 1.8 2.4 1.8 2.5 1.721.0 1.8 1.6 2.0 1.7 2.1 1.8 2.2 1.8 2.3 1.8 2.4 1.8 2.5 1.7

007 23.0 1.8 1.6 2.0 1.7 2.1 1.8 2.2 1.8 2.3 1.8 2.4 1.8 2.5 1.725.0 1.8 1.6 2.0 1.7 2.1 1.8 2.2 1.8 2.3 1.8 2.4 1.8 2.5 1.727.0 1.8 1.6 2.0 1.7 2.1 1.8 2.2 1.8 2.3 1.8 2.4 1.8 2.5 1.729.0 1.8 1.6 2.0 1.7 2.1 1.8 2.2 1.8 2.3 1.8 2.4 1.8 2.5 1.731.0 1.8 1.6 2.0 1.7 2.1 1.8 2.2 1.8 2.3 1.8 2.4 1.8 2.5 1.733.0 1.8 1.6 2.0 1.7 2.1 1.8 2.2 1.8 2.3 1.8 2.4 1.8 2.5 1.735.0 1.8 1.6 2.0 1.7 2.1 1.8 2.2 1.8 2.3 1.8 2.4 1.8 2.5 1.737.0 1.7 1.5 1.9 1.6 2.1 1.7 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.739.0 1.7 1.5 1.9 1.6 2.0 1.7 2.1 1.7 2.1 1.7 2.3 1.7 2.4 1.610.0 2.3 2.0 2.5 2.1 2.7 2.2 2.8 2.2 2.9 2.2 3.1 2.2 3.2 2.112.0 2.3 2.0 2.5 2.1 2.7 2.2 2.8 2.2 2.9 2.2 3.1 2.2 3.2 2.114.0 2.3 2.0 2.5 2.1 2.7 2.2 2.8 2.2 2.9 2.2 3.1 2.2 3.2 2.116.0 2.3 2.0 2.5 2.1 2.7 2.2 2.8 2.2 2.9 2.2 3.1 2.2 3.2 2.118.0 2.3 2.0 2.5 2.1 2.7 2.2 2.8 2.2 2.9 2.2 3.1 2.2 3.2 2.120.0 2.3 2.0 2.5 2.1 2.7 2.2 2.8 2.2 2.9 2.2 3.1 2.2 3.2 2.121.0 2.3 2.0 2.5 2.1 2.7 2.2 2.8 2.2 2.9 2.2 3.1 2.2 3.2 2.1

009 23.0 2.3 2.0 2.5 2.1 2.7 2.2 2.8 2.2 2.9 2.2 3.1 2.2 3.2 2.125.0 2.3 2.0 2.5 2.1 2.7 2.2 2.8 2.2 2.9 2.2 3.1 2.2 3.2 2.127.0 2.3 2.0 2.5 2.1 2.7 2.2 2.8 2.2 2.9 2.2 3.1 2.2 3.2 2.129.0 2.3 2.0 2.5 2.1 2.7 2.2 2.8 2.2 2.9 2.2 3.1 2.2 3.2 2.131.0 2.3 2.0 2.5 2.1 2.7 2.2 2.8 2.2 2.9 2.2 3.1 2.2 3.2 2.133.0 2.3 2.0 2.5 2.1 2.7 2.2 2.8 2.2 2.9 2.2 3.1 2.2 3.2 2.135.0 2.3 2.0 2.5 2.1 2.7 2.2 2.8 2.2 2.9 2.2 3.1 2.2 3.2 2.137.0 2.2 1.9 2.5 2.0 2.6 2.1 2.7 2.1 2.8 2.1 3.0 2.1 3.1 2.139.0 2.2 1.8 2.4 2.0 2.6 2.1 2.6 2.1 2.7 2.1 2.9 2.1 3.0 2.010.0 3.0 2.4 3.3 2.5 3.5 2.7 3.6 2.7 3.7 2.7 3.9 2.7 4.1 2.612.0 3.0 2.4 3.3 2.5 3.5 2.7 3.6 2.7 3.7 2.7 3.9 2.7 4.1 2.614.0 3.0 2.4 3.3 2.5 3.5 2.7 3.6 2.7 3.7 2.7 3.9 2.7 4.1 2.616.0 3.0 2.4 3.3 2.5 3.5 2.7 3.6 2.7 3.7 2.7 3.9 2.7 4.1 2.618.0 3.0 2.4 3.3 2.5 3.5 2.7 3.6 2.7 3.7 2.7 3.9 2.7 4.1 2.620.0 3.0 2.4 3.3 2.5 3.5 2.7 3.6 2.7 3.7 2.7 3.9 2.7 4.1 2.621.0 3.0 2.4 3.3 2.5 3.5 2.7 3.6 2.7 3.7 2.7 3.9 2.7 4.1 2.6

012 23.0 3.0 2.4 3.3 2.5 3.5 2.7 3.6 2.7 3.7 2.7 3.9 2.7 4.1 2.625.0 3.0 2.4 3.3 2.5 3.5 2.7 3.6 2.7 3.7 2.7 3.9 2.7 4.1 2.627.0 3.0 2.4 3.3 2.5 3.5 2.7 3.6 2.7 3.7 2.7 3.9 2.7 4.1 2.629.0 3.0 2.4 3.3 2.5 3.5 2.7 3.6 2.7 3.7 2.7 3.9 2.7 4.1 2.631.0 3.0 2.4 3.3 2.5 3.5 2.7 3.6 2.7 3.7 2.7 3.9 2.7 4.1 2.633.0 3.0 2.4 3.3 2.5 3.5 2.7 3.6 2.7 3.7 2.7 3.9 2.7 4.1 2.635.0 3.0 2.4 3.3 2.5 3.5 2.7 3.6 2.7 3.7 2.7 3.9 2.7 4.1 2.637.0 2.9 2.3 3.2 2.5 3.4 2.6 3.5 2.6 3.6 2.6 3.8 2.6 4.0 2.539.0 2.8 2.3 3.1 2.4 3.3 2.5 3.4 2.5 3.5 2.5 3.7 2.5 3.9 2.510.0 3.7 2.7 4.1 2.9 4.4 3.1 4.5 3.1 4.6 3.1 4.9 3.0 5.1 3.012.0 3.7 2.7 4.1 2.9 4.4 3.1 4.5 3.1 4.6 3.1 4.9 3.0 5.1 3.014.0 3.7 2.7 4.1 2.9 4.4 3.1 4.5 3.1 4.6 3.1 4.9 3.0 5.1 3.016.0 3.7 2.7 4.1 2.9 4.4 3.1 4.5 3.1 4.6 3.1 4.9 3.0 5.1 3.018.0 3.7 2.7 4.1 2.9 4.4 3.1 4.5 3.1 4.6 3.1 4.9 3.0 5.1 3.020.0 3.7 2.7 4.1 2.9 4.4 3.1 4.5 3.1 4.6 3.1 4.9 3.0 5.1 3.021.0 3.7 2.7 4.1 2.9 4.4 3.1 4.5 3.1 4.6 3.1 4.9 3.0 5.1 3.0

015 23.0 3.7 2.7 4.1 2.9 4.4 3.1 4.5 3.1 4.6 3.1 4.9 3.0 5.1 3.025.0 3.7 2.7 4.1 2.9 4.4 3.1 4.5 3.1 4.6 3.1 4.9 3.0 5.1 3.027.0 3.7 2.7 4.1 2.9 4.4 3.1 4.5 3.1 4.6 3.1 4.9 3.0 5.1 3.029.0 3.7 2.7 4.1 2.9 4.4 3.1 4.5 3.1 4.6 3.1 4.9 3.0 5.1 3.031.0 3.7 2.7 4.1 2.9 4.4 3.1 4.5 3.1 4.6 3.1 4.9 3.0 5.1 3.033.0 3.7 2.7 4.1 2.9 4.4 3.1 4.5 3.1 4.6 3.1 4.9 3.0 5.1 3.035.0 3.7 2.7 4.1 2.9 4.4 3.1 4.5 3.1 4.6 3.1 4.9 3.0 5.1 3.037.0 3.6 2.6 4.0 2.8 4.2 3.0 4.4 3.0 4.5 3.0 4.7 2.9 5.0 2.939.0 3.5 2.5 3.8 2.7 4.1 2.9 4.2 2.9 4.4 2.9 4.6 2.8 4.8 2.8

TC : Total capacity [kW] SHC : Sensible capacity [kW]indoor air temp.

unitsize

outdoorair temp.

1-way Air Discharge Cassette Type ( MMU-AP****YH [007 012] , -AP****SH [015 024] )

8

Page 55: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

52

8

TC : Total capacity [kW] SHC : Sensible capacity [kW]1-way Air Discharge Cassette Type ( MMU-AP****YH [007 012] , -AP****SH [015 024] )

14.0oCWB 16.0oCWB 18.0oCWB 19.0oCWB 20.0oCWB 22.0oCWB 24.0oCWB20oCDB 23oCDB 26oCDB 27oCDB 28oCDB 30oCDB 32oCDB

oCDB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC10.0 4.6 3.4 5.1 3.6 5.4 3.8 5.6 3.8 5.8 3.8 6.1 3.8 6.4 3.712.0 4.6 3.4 5.1 3.6 5.4 3.8 5.6 3.8 5.8 3.8 6.1 3.8 6.4 3.714.0 4.6 3.4 5.1 3.6 5.4 3.8 5.6 3.8 5.8 3.8 6.1 3.8 6.4 3.716.0 4.6 3.4 5.1 3.6 5.4 3.8 5.6 3.8 5.8 3.8 6.1 3.8 6.4 3.718.0 4.6 3.4 5.1 3.6 5.4 3.8 5.6 3.8 5.8 3.8 6.1 3.8 6.4 3.720.0 4.6 3.4 5.1 3.6 5.4 3.8 5.6 3.8 5.8 3.8 6.1 3.8 6.4 3.721.0 4.6 3.4 5.1 3.6 5.4 3.8 5.6 3.8 5.8 3.8 6.1 3.8 6.4 3.7

018 23.0 4.6 3.4 5.1 3.6 5.4 3.8 5.6 3.8 5.8 3.8 6.1 3.8 6.4 3.725.0 4.6 3.4 5.1 3.6 5.4 3.8 5.6 3.8 5.8 3.8 6.1 3.8 6.4 3.727.0 4.6 3.4 5.1 3.6 5.4 3.8 5.6 3.8 5.8 3.8 6.1 3.8 6.4 3.729.0 4.6 3.4 5.1 3.6 5.4 3.8 5.6 3.8 5.8 3.8 6.1 3.8 6.4 3.731.0 4.6 3.4 5.1 3.6 5.4 3.8 5.6 3.8 5.8 3.8 6.1 3.8 6.4 3.733.0 4.6 3.4 5.1 3.6 5.4 3.8 5.6 3.8 5.8 3.8 6.1 3.8 6.4 3.735.0 4.6 3.4 5.1 3.6 5.4 3.8 5.6 3.8 5.8 3.8 6.1 3.8 6.4 3.737.0 4.5 3.3 4.9 3.5 5.3 3.7 5.4 3.7 5.6 3.7 5.9 3.6 6.2 3.639.0 4.3 3.2 4.8 3.4 5.1 3.6 5.3 3.6 5.4 3.6 5.7 3.5 6.0 3.510.0 5.8 4.4 6.4 4.7 6.9 5.0 7.1 5.0 7.3 5.0 7.7 5.0 8.1 4.812.0 5.8 4.4 6.4 4.7 6.9 5.0 7.1 5.0 7.3 5.0 7.7 5.0 8.1 4.814.0 5.8 4.4 6.4 4.7 6.9 5.0 7.1 5.0 7.3 5.0 7.7 5.0 8.1 4.816.0 5.8 4.4 6.4 4.7 6.9 5.0 7.1 5.0 7.3 5.0 7.7 5.0 8.1 4.818.0 5.8 4.4 6.4 4.7 6.9 5.0 7.1 5.0 7.3 5.0 7.7 5.0 8.1 4.820.0 5.8 4.4 6.4 4.7 6.9 5.0 7.1 5.0 7.3 5.0 7.7 5.0 8.1 4.821.0 5.8 4.4 6.4 4.7 6.9 5.0 7.1 5.0 7.3 5.0 7.7 5.0 8.1 4.8

024 23.0 5.8 4.4 6.4 4.7 6.9 5.0 7.1 5.0 7.3 5.0 7.7 5.0 8.1 4.825.0 5.8 4.4 6.4 4.7 6.9 5.0 7.1 5.0 7.3 5.0 7.7 5.0 8.1 4.827.0 5.8 4.4 6.4 4.7 6.9 5.0 7.1 5.0 7.3 5.0 7.7 5.0 8.1 4.829.0 5.8 4.4 6.4 4.7 6.9 5.0 7.1 5.0 7.3 5.0 7.7 5.0 8.1 4.831.0 5.8 4.4 6.4 4.7 6.9 5.0 7.1 5.0 7.3 5.0 7.7 5.0 8.1 4.833.0 5.8 4.4 6.4 4.7 6.9 5.0 7.1 5.0 7.3 5.0 7.7 5.0 8.1 4.835.0 5.8 4.4 6.4 4.7 6.9 5.0 7.1 5.0 7.3 5.0 7.7 5.0 8.1 4.837.0 5.6 4.3 6.2 4.6 6.7 4.9 6.9 4.8 7.1 4.8 7.5 4.8 7.8 4.739.0 5.5 4.2 6.1 4.4 6.5 4.7 6.7 4.7 6.9 4.7 7.3 4.7 7.6 4.6

unitsize

outdoorair temp.

indoor air temp.

Page 56: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

53

8

Concealed Duct Standard Type ( MMD-AP****BH ) TC : Total capacity [kW] SHC : Sensible capacity [kW]

14.0oCWB 16.0oCWB 18.0oCWB 19.0oCWB 20.0oCWB 22.0oCWB 24.0oCWB20oCDB 23oCDB 26oCDB 27oCDB 28oCDB 30oCDB 32oCDB

oCDB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC10.0 1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.612.0 1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.614.0 1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.616.0 1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.618.0 1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.620.0 1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.621.0 1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.6

007 23.0 1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.625.0 1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.627.0 1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.629.0 1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.631.0 1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.633.0 1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.635.0 1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.637.0 1.7 1.5 1.9 1.6 2.1 1.7 2.1 1.6 2.2 1.6 2.3 1.6 2.4 1.639.0 1.7 1.4 1.9 1.5 2.0 1.6 2.1 1.6 2.1 1.6 2.3 1.6 2.4 1.510.0 2.3 1.9 2.5 2.0 2.7 2.1 2.8 2.1 2.9 2.1 3.1 2.1 3.2 2.012.0 2.3 1.9 2.5 2.0 2.7 2.1 2.8 2.1 2.9 2.1 3.1 2.1 3.2 2.014.0 2.3 1.9 2.5 2.0 2.7 2.1 2.8 2.1 2.9 2.1 3.1 2.1 3.2 2.016.0 2.3 1.9 2.5 2.0 2.7 2.1 2.8 2.1 2.9 2.1 3.1 2.1 3.2 2.018.0 2.3 1.9 2.5 2.0 2.7 2.1 2.8 2.1 2.9 2.1 3.1 2.1 3.2 2.020.0 2.3 1.9 2.5 2.0 2.7 2.1 2.8 2.1 2.9 2.1 3.1 2.1 3.2 2.021.0 2.3 1.9 2.5 2.0 2.7 2.1 2.8 2.1 2.9 2.1 3.1 2.1 3.2 2.0

009 23.0 2.3 1.9 2.5 2.0 2.7 2.1 2.8 2.1 2.9 2.1 3.1 2.1 3.2 2.025.0 2.3 1.9 2.5 2.0 2.7 2.1 2.8 2.1 2.9 2.1 3.1 2.1 3.2 2.027.0 2.3 1.9 2.5 2.0 2.7 2.1 2.8 2.1 2.9 2.1 3.1 2.1 3.2 2.029.0 2.3 1.9 2.5 2.0 2.7 2.1 2.8 2.1 2.9 2.1 3.1 2.1 3.2 2.031.0 2.3 1.9 2.5 2.0 2.7 2.1 2.8 2.1 2.9 2.1 3.1 2.1 3.2 2.033.0 2.3 1.9 2.5 2.0 2.7 2.1 2.8 2.1 2.9 2.1 3.1 2.1 3.2 2.035.0 2.3 1.9 2.5 2.0 2.7 2.1 2.8 2.1 2.9 2.1 3.1 2.1 3.2 2.037.0 2.2 1.8 2.5 1.9 2.6 2.0 2.7 2.0 2.8 2.0 3.0 2.0 3.1 2.039.0 2.2 1.8 2.4 1.9 2.6 2.0 2.6 2.0 2.7 2.0 2.9 2.0 3.0 1.910.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.412.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.414.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.416.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.418.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.420.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.421.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.4

012 23.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.425.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.427.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.429.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.431.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.433.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.435.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.437.0 2.9 2.1 3.2 2.3 3.4 2.4 3.5 2.4 3.6 2.4 3.8 2.4 4.0 2.339.0 2.8 2.1 3.1 2.2 3.3 2.4 3.4 2.4 3.5 2.4 3.7 2.3 3.9 2.310.0 3.7 2.7 4.1 2.8 4.4 3.0 4.5 3.0 4.6 3.0 4.9 3.0 5.1 2.912.0 3.7 2.7 4.1 2.8 4.4 3.0 4.5 3.0 4.6 3.0 4.9 3.0 5.1 2.914.0 3.7 2.7 4.1 2.8 4.4 3.0 4.5 3.0 4.6 3.0 4.9 3.0 5.1 2.916.0 3.7 2.7 4.1 2.8 4.4 3.0 4.5 3.0 4.6 3.0 4.9 3.0 5.1 2.918.0 3.7 2.7 4.1 2.8 4.4 3.0 4.5 3.0 4.6 3.0 4.9 3.0 5.1 2.920.0 3.7 2.7 4.1 2.8 4.4 3.0 4.5 3.0 4.6 3.0 4.9 3.0 5.1 2.921.0 3.7 2.7 4.1 2.8 4.4 3.0 4.5 3.0 4.6 3.0 4.9 3.0 5.1 2.9

015 23.0 3.7 2.7 4.1 2.8 4.4 3.0 4.5 3.0 4.6 3.0 4.9 3.0 5.1 2.925.0 3.7 2.7 4.1 2.8 4.4 3.0 4.5 3.0 4.6 3.0 4.9 3.0 5.1 2.927.0 3.7 2.7 4.1 2.8 4.4 3.0 4.5 3.0 4.6 3.0 4.9 3.0 5.1 2.929.0 3.7 2.7 4.1 2.8 4.4 3.0 4.5 3.0 4.6 3.0 4.9 3.0 5.1 2.931.0 3.7 2.7 4.1 2.8 4.4 3.0 4.5 3.0 4.6 3.0 4.9 3.0 5.1 2.933.0 3.7 2.7 4.1 2.8 4.4 3.0 4.5 3.0 4.6 3.0 4.9 3.0 5.1 2.935.0 3.7 2.7 4.1 2.8 4.4 3.0 4.5 3.0 4.6 3.0 4.9 3.0 5.1 2.937.0 3.6 2.6 4.0 2.7 4.2 2.9 4.4 2.9 4.5 2.9 4.7 2.9 5.0 2.839.0 3.5 2.5 3.8 2.7 4.1 2.8 4.2 2.8 4.4 2.8 4.6 2.8 4.8 2.7

unitsize

outdoorair temp.

indoor air temp.

Page 57: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

54

14.0oCWB 16.0oCWB 18.0oCWB 19.0oCWB 20.0oCWB 22.0oCWB 24.0oCWB20oCDB 23oCDB 26oCDB 27oCDB 28oCDB 30oCDB 32oCDB

oCDB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC10.0 4.6 3.3 5.1 3.5 5.4 3.7 5.6 3.7 5.8 3.7 6.1 3.7 6.4 3.612.0 4.6 3.3 5.1 3.5 5.4 3.7 5.6 3.7 5.8 3.7 6.1 3.7 6.4 3.614.0 4.6 3.3 5.1 3.5 5.4 3.7 5.6 3.7 5.8 3.7 6.1 3.7 6.4 3.616.0 4.6 3.3 5.1 3.5 5.4 3.7 5.6 3.7 5.8 3.7 6.1 3.7 6.4 3.618.0 4.6 3.3 5.1 3.5 5.4 3.7 5.6 3.7 5.8 3.7 6.1 3.7 6.4 3.620.0 4.6 3.3 5.1 3.5 5.4 3.7 5.6 3.7 5.8 3.7 6.1 3.7 6.4 3.621.0 4.6 3.3 5.1 3.5 5.4 3.7 5.6 3.7 5.8 3.7 6.1 3.7 6.4 3.6

018 23.0 4.6 3.3 5.1 3.5 5.4 3.7 5.6 3.7 5.8 3.7 6.1 3.7 6.4 3.625.0 4.6 3.3 5.1 3.5 5.4 3.7 5.6 3.7 5.8 3.7 6.1 3.7 6.4 3.627.0 4.6 3.3 5.1 3.5 5.4 3.7 5.6 3.7 5.8 3.7 6.1 3.7 6.4 3.629.0 4.6 3.3 5.1 3.5 5.4 3.7 5.6 3.7 5.8 3.7 6.1 3.7 6.4 3.631.0 4.6 3.3 5.1 3.5 5.4 3.7 5.6 3.7 5.8 3.7 6.1 3.7 6.4 3.633.0 4.6 3.3 5.1 3.5 5.4 3.7 5.6 3.7 5.8 3.7 6.1 3.7 6.4 3.635.0 4.6 3.3 5.1 3.5 5.4 3.7 5.6 3.7 5.8 3.7 6.1 3.7 6.4 3.637.0 4.5 3.2 4.9 3.4 5.3 3.6 5.4 3.6 5.6 3.6 5.9 3.5 6.2 3.539.0 4.3 3.1 4.8 3.3 5.1 3.5 5.3 3.5 5.4 3.5 5.7 3.4 6.0 3.410.0 5.8 4.4 6.4 4.7 6.9 5.0 7.1 5.0 7.3 5.0 7.7 5.0 8.1 4.812.0 5.8 4.4 6.4 4.7 6.9 5.0 7.1 5.0 7.3 5.0 7.7 5.0 8.1 4.814.0 5.8 4.4 6.4 4.7 6.9 5.0 7.1 5.0 7.3 5.0 7.7 5.0 8.1 4.816.0 5.8 4.4 6.4 4.7 6.9 5.0 7.1 5.0 7.3 5.0 7.7 5.0 8.1 4.818.0 5.8 4.4 6.4 4.7 6.9 5.0 7.1 5.0 7.3 5.0 7.7 5.0 8.1 4.820.0 5.8 4.4 6.4 4.7 6.9 5.0 7.1 5.0 7.3 5.0 7.7 5.0 8.1 4.821.0 5.8 4.4 6.4 4.7 6.9 5.0 7.1 5.0 7.3 5.0 7.7 5.0 8.1 4.8

024 23.0 5.8 4.4 6.4 4.7 6.9 5.0 7.1 5.0 7.3 5.0 7.7 5.0 8.1 4.825.0 5.8 4.4 6.4 4.7 6.9 5.0 7.1 5.0 7.3 5.0 7.7 5.0 8.1 4.827.0 5.8 4.4 6.4 4.7 6.9 5.0 7.1 5.0 7.3 5.0 7.7 5.0 8.1 4.829.0 5.8 4.4 6.4 4.7 6.9 5.0 7.1 5.0 7.3 5.0 7.7 5.0 8.1 4.831.0 5.8 4.4 6.4 4.7 6.9 5.0 7.1 5.0 7.3 5.0 7.7 5.0 8.1 4.833.0 5.8 4.4 6.4 4.7 6.9 5.0 7.1 5.0 7.3 5.0 7.7 5.0 8.1 4.835.0 5.8 4.4 6.4 4.7 6.9 5.0 7.1 5.0 7.3 5.0 7.7 5.0 8.1 4.837.0 5.6 4.3 6.2 4.6 6.7 4.9 6.9 4.8 7.1 4.8 7.5 4.8 7.8 4.739.0 5.5 4.2 6.1 4.4 6.5 4.7 6.7 4.7 6.9 4.7 7.3 4.7 7.6 4.610.0 6.6 5.0 7.3 5.3 7.8 5.6 8.0 5.6 8.2 5.6 8.7 5.5 9.1 5.412.0 6.6 5.0 7.3 5.3 7.8 5.6 8.0 5.6 8.2 5.6 8.7 5.5 9.1 5.414.0 6.6 5.0 7.3 5.3 7.8 5.6 8.0 5.6 8.2 5.6 8.7 5.5 9.1 5.416.0 6.6 5.0 7.3 5.3 7.8 5.6 8.0 5.6 8.2 5.6 8.7 5.5 9.1 5.418.0 6.6 5.0 7.3 5.3 7.8 5.6 8.0 5.6 8.2 5.6 8.7 5.5 9.1 5.420.0 6.6 5.0 7.3 5.3 7.8 5.6 8.0 5.6 8.2 5.6 8.7 5.5 9.1 5.421.0 6.6 5.0 7.3 5.3 7.8 5.6 8.0 5.6 8.2 5.6 8.7 5.5 9.1 5.4

027 23.0 6.6 5.0 7.3 5.3 7.8 5.6 8.0 5.6 8.2 5.6 8.7 5.5 9.1 5.425.0 6.6 5.0 7.3 5.3 7.8 5.6 8.0 5.6 8.2 5.6 8.7 5.5 9.1 5.427.0 6.6 5.0 7.3 5.3 7.8 5.6 8.0 5.6 8.2 5.6 8.7 5.5 9.1 5.429.0 6.6 5.0 7.3 5.3 7.8 5.6 8.0 5.6 8.2 5.6 8.7 5.5 9.1 5.431.0 6.6 5.0 7.3 5.3 7.8 5.6 8.0 5.6 8.2 5.6 8.7 5.5 9.1 5.433.0 6.6 5.0 7.3 5.3 7.8 5.6 8.0 5.6 8.2 5.6 8.7 5.5 9.1 5.435.0 6.6 5.0 7.3 5.3 7.8 5.6 8.0 5.6 8.2 5.6 8.7 5.5 9.1 5.437.0 6.4 4.8 7.0 5.1 7.5 5.4 7.7 5.4 8.0 5.4 8.4 5.4 8.8 5.239.0 6.2 4.7 6.8 5.0 7.3 5.3 7.5 5.3 7.8 5.3 8.2 5.2 8.6 5.110.0 7.4 5.5 8.2 5.9 8.7 6.2 9.0 6.2 9.3 6.2 9.8 6.1 10.3 6.012.0 7.4 5.5 8.2 5.9 8.7 6.2 9.0 6.2 9.3 6.2 9.8 6.1 10.3 6.014.0 7.4 5.5 8.2 5.9 8.7 6.2 9.0 6.2 9.3 6.2 9.8 6.1 10.3 6.016.0 7.4 5.5 8.2 5.9 8.7 6.2 9.0 6.2 9.3 6.2 9.8 6.1 10.3 6.018.0 7.4 5.5 8.2 5.9 8.7 6.2 9.0 6.2 9.3 6.2 9.8 6.1 10.3 6.020.0 7.4 5.5 8.2 5.9 8.7 6.2 9.0 6.2 9.3 6.2 9.8 6.1 10.3 6.021.0 7.4 5.5 8.2 5.9 8.7 6.2 9.0 6.2 9.3 6.2 9.8 6.1 10.3 6.0

030 23.0 7.4 5.5 8.2 5.9 8.7 6.2 9.0 6.2 9.3 6.2 9.8 6.1 10.3 6.025.0 7.4 5.5 8.2 5.9 8.7 6.2 9.0 6.2 9.3 6.2 9.8 6.1 10.3 6.027.0 7.4 5.5 8.2 5.9 8.7 6.2 9.0 6.2 9.3 6.2 9.8 6.1 10.3 6.029.0 7.4 5.5 8.2 5.9 8.7 6.2 9.0 6.2 9.3 6.2 9.8 6.1 10.3 6.031.0 7.4 5.5 8.2 5.9 8.7 6.2 9.0 6.2 9.3 6.2 9.8 6.1 10.3 6.033.0 7.4 5.5 8.2 5.9 8.7 6.2 9.0 6.2 9.3 6.2 9.8 6.1 10.3 6.035.0 7.4 5.5 8.2 5.9 8.7 6.2 9.0 6.2 9.3 6.2 9.8 6.1 10.3 6.037.0 7.2 5.3 7.9 5.7 8.5 6.0 8.7 6.0 9.0 6.0 9.5 5.9 9.9 5.839.0 7.0 5.2 7.7 5.5 8.2 5.9 8.5 5.8 8.7 5.8 9.2 5.8 9.7 5.6

8

Concealed Duct Standard Type ( MMD-AP***BH ) TC : Total capacity [kW] SHC : Sensible capacity [kW]

unitsize

outdoorair temp.

indoor air temp.

Page 58: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

55

14.0oCWB 16.0oCWB 18.0oCWB 19.0oCWB 20.0oCWB 22.0oCWB 24.0oCWB20oCDB 23oCDB 26oCDB 27oCDB 28oCDB 30oCDB 32oCDB

oCDB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC10.0 9.2 6.5 10.2 6.9 10.9 7.3 11.2 7.3 11.5 7.3 12.2 7.2 12.8 7.112.0 9.2 6.5 10.2 6.9 10.9 7.3 11.2 7.3 11.5 7.3 12.2 7.2 12.8 7.114.0 9.2 6.5 10.2 6.9 10.9 7.3 11.2 7.3 11.5 7.3 12.2 7.2 12.8 7.116.0 9.2 6.5 10.2 6.9 10.9 7.3 11.2 7.3 11.5 7.3 12.2 7.2 12.8 7.118.0 9.2 6.5 10.2 6.9 10.9 7.3 11.2 7.3 11.5 7.3 12.2 7.2 12.8 7.120.0 9.2 6.5 10.2 6.9 10.9 7.3 11.2 7.3 11.5 7.3 12.2 7.2 12.8 7.121.0 9.2 6.5 10.2 6.9 10.9 7.3 11.2 7.3 11.5 7.3 12.2 7.2 12.8 7.1

036 23.0 9.2 6.5 10.2 6.9 10.9 7.3 11.2 7.3 11.5 7.3 12.2 7.2 12.8 7.125.0 9.2 6.5 10.2 6.9 10.9 7.3 11.2 7.3 11.5 7.3 12.2 7.2 12.8 7.127.0 9.2 6.5 10.2 6.9 10.9 7.3 11.2 7.3 11.5 7.3 12.2 7.2 12.8 7.129.0 9.2 6.5 10.2 6.9 10.9 7.3 11.2 7.3 11.5 7.3 12.2 7.2 12.8 7.131.0 9.2 6.5 10.2 6.9 10.9 7.3 11.2 7.3 11.5 7.3 12.2 7.2 12.8 7.133.0 9.2 6.5 10.2 6.9 10.9 7.3 11.2 7.3 11.5 7.3 12.2 7.2 12.8 7.135.0 9.2 6.5 10.2 6.9 10.9 7.3 11.2 7.3 11.5 7.3 12.2 7.2 12.8 7.137.0 8.9 6.3 9.8 6.7 10.5 7.1 10.8 7.1 11.2 7.1 11.8 7.0 12.4 6.839.0 8.7 6.1 9.6 6.5 10.2 6.9 10.5 6.9 10.9 6.9 11.5 6.8 12.0 6.610.0 11.5 8.2 12.7 8.7 13.6 9.2 14.0 9.2 14.4 9.2 15.3 9.1 16.0 8.912.0 11.5 8.2 12.7 8.7 13.6 9.2 14.0 9.2 14.4 9.2 15.3 9.1 16.0 8.914.0 11.5 8.2 12.7 8.7 13.6 9.2 14.0 9.2 14.4 9.2 15.3 9.1 16.0 8.916.0 11.5 8.2 12.7 8.7 13.6 9.2 14.0 9.2 14.4 9.2 15.3 9.1 16.0 8.918.0 11.5 8.2 12.7 8.7 13.6 9.2 14.0 9.2 14.4 9.2 15.3 9.1 16.0 8.920.0 11.5 8.2 12.7 8.7 13.6 9.2 14.0 9.2 14.4 9.2 15.3 9.1 16.0 8.921.0 11.5 8.2 12.7 8.7 13.6 9.2 14.0 9.2 14.4 9.2 15.3 9.1 16.0 8.9

048 23.0 11.5 8.2 12.7 8.7 13.6 9.2 14.0 9.2 14.4 9.2 15.3 9.1 16.0 8.925.0 11.5 8.2 12.7 8.7 13.6 9.2 14.0 9.2 14.4 9.2 15.3 9.1 16.0 8.927.0 11.5 8.2 12.7 8.7 13.6 9.2 14.0 9.2 14.4 9.2 15.3 9.1 16.0 8.929.0 11.5 8.2 12.7 8.7 13.6 9.2 14.0 9.2 14.4 9.2 15.3 9.1 16.0 8.931.0 11.5 8.2 12.7 8.7 13.6 9.2 14.0 9.2 14.4 9.2 15.3 9.1 16.0 8.933.0 11.5 8.2 12.7 8.7 13.6 9.2 14.0 9.2 14.4 9.2 15.3 9.1 16.0 8.935.0 11.5 8.2 12.7 8.7 13.6 9.2 14.0 9.2 14.4 9.2 15.3 9.1 16.0 8.937.0 11.1 7.9 12.3 8.4 13.1 8.9 13.6 8.9 14.0 8.9 14.8 8.8 15.4 8.639.0 10.8 7.7 12.0 8.2 12.8 8.7 13.2 8.7 13.6 8.7 14.4 8.6 15.0 8.410.0 13.1 9.6 14.5 10.2 15.5 10.8 16.0 10.8 16.5 10.8 17.4 10.7 18.2 10.512.0 13.1 9.6 14.5 10.2 15.5 10.8 16.0 10.8 16.5 10.8 17.4 10.7 18.2 10.514.0 13.1 9.6 14.5 10.2 15.5 10.8 16.0 10.8 16.5 10.8 17.4 10.7 18.2 10.516.0 13.1 9.6 14.5 10.2 15.5 10.8 16.0 10.8 16.5 10.8 17.4 10.7 18.2 10.518.0 13.1 9.6 14.5 10.2 15.5 10.8 16.0 10.8 16.5 10.8 17.4 10.7 18.2 10.520.0 13.1 9.6 14.5 10.2 15.5 10.8 16.0 10.8 16.5 10.8 17.4 10.7 18.2 10.521.0 13.1 9.6 14.5 10.2 15.5 10.8 16.0 10.8 16.5 10.8 17.4 10.7 18.2 10.5

056 23.0 13.1 9.6 14.5 10.2 15.5 10.8 16.0 10.8 16.5 10.8 17.4 10.7 18.2 10.525.0 13.1 9.6 14.5 10.2 15.5 10.8 16.0 10.8 16.5 10.8 17.4 10.7 18.2 10.527.0 13.1 9.6 14.5 10.2 15.5 10.8 16.0 10.8 16.5 10.8 17.4 10.7 18.2 10.529.0 13.1 9.6 14.5 10.2 15.5 10.8 16.0 10.8 16.5 10.8 17.4 10.7 18.2 10.531.0 13.1 9.6 14.5 10.2 15.5 10.8 16.0 10.8 16.5 10.8 17.4 10.7 18.2 10.533.0 13.1 9.6 14.5 10.2 15.5 10.8 16.0 10.8 16.5 10.8 17.4 10.7 18.2 10.535.0 13.1 9.6 14.5 10.2 15.5 10.8 16.0 10.8 16.5 10.8 17.4 10.7 18.2 10.537.0 12.7 9.3 14.1 9.9 15.0 10.5 15.5 10.5 16.0 10.5 16.9 10.4 17.7 10.139.0 12.4 9.0 13.7 9.6 14.6 10.2 15.1 10.2 15.5 10.2 16.4 10.1 17.2 9.8

8

Concealed Duct Standard Type ( MMD-AP***BH ) TC : Total capacity [kW] SHC : Sensible capacity [kW]

unitsize

outdoorair temp.

indoor air temp.

Page 59: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

56

14.0oCWB 16.0oCWB 18.0oCWB 19.0oCWB 20.0oCWB 22.0oCWB 24.0oCWB20oCDB 23oCDB 26oCDB 27oCDB 28oCDB 30oCDB 32oCDB

oCDB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC10.0 4.6 3.6 5.1 3.8 5.4 4.0 5.6 4.0 5.8 4.0 6.1 4.0 6.4 3.912.0 4.6 3.6 5.1 3.8 5.4 4.0 5.6 4.0 5.8 4.0 6.1 4.0 6.4 3.914.0 4.6 3.6 5.1 3.8 5.4 4.0 5.6 4.0 5.8 4.0 6.1 4.0 6.4 3.916.0 4.6 3.6 5.1 3.8 5.4 4.0 5.6 4.0 5.8 4.0 6.1 4.0 6.4 3.918.0 4.6 3.6 5.1 3.8 5.4 4.0 5.6 4.0 5.8 4.0 6.1 4.0 6.4 3.920.0 4.6 3.6 5.1 3.8 5.4 4.0 5.6 4.0 5.8 4.0 6.1 4.0 6.4 3.921.0 4.6 3.6 5.1 3.8 5.4 4.0 5.6 4.0 5.8 4.0 6.1 4.0 6.4 3.9

018 23.0 4.6 3.6 5.1 3.8 5.4 4.0 5.6 4.0 5.8 4.0 6.1 4.0 6.4 3.925.0 4.6 3.6 5.1 3.8 5.4 4.0 5.6 4.0 5.8 4.0 6.1 4.0 6.4 3.927.0 4.6 3.6 5.1 3.8 5.4 4.0 5.6 4.0 5.8 4.0 6.1 4.0 6.4 3.929.0 4.6 3.6 5.1 3.8 5.4 4.0 5.6 4.0 5.8 4.0 6.1 4.0 6.4 3.931.0 4.6 3.6 5.1 3.8 5.4 4.0 5.6 4.0 5.8 4.0 6.1 4.0 6.4 3.933.0 4.6 3.6 5.1 3.8 5.4 4.0 5.6 4.0 5.8 4.0 6.1 4.0 6.4 3.935.0 4.6 3.6 5.1 3.8 5.4 4.0 5.6 4.0 5.8 4.0 6.1 4.0 6.4 3.937.0 4.5 3.5 4.9 3.7 5.3 3.9 5.4 3.9 5.6 3.9 5.9 3.9 6.2 3.839.0 4.3 3.4 4.8 3.6 5.1 3.8 5.3 3.8 5.4 3.8 5.7 3.8 6.0 3.710.0 5.8 4.4 6.4 4.7 6.9 5.0 7.1 5.0 7.3 5.0 7.7 5.0 8.1 4.812.0 5.8 4.4 6.4 4.7 6.9 5.0 7.1 5.0 7.3 5.0 7.7 5.0 8.1 4.814.0 5.8 4.4 6.4 4.7 6.9 5.0 7.1 5.0 7.3 5.0 7.7 5.0 8.1 4.816.0 5.8 4.4 6.4 4.7 6.9 5.0 7.1 5.0 7.3 5.0 7.7 5.0 8.1 4.818.0 5.8 4.4 6.4 4.7 6.9 5.0 7.1 5.0 7.3 5.0 7.7 5.0 8.1 4.820.0 5.8 4.4 6.4 4.7 6.9 5.0 7.1 5.0 7.3 5.0 7.7 5.0 8.1 4.821.0 5.8 4.4 6.4 4.7 6.9 5.0 7.1 5.0 7.3 5.0 7.7 5.0 8.1 4.8

024 23.0 5.8 4.4 6.4 4.7 6.9 5.0 7.1 5.0 7.3 5.0 7.7 5.0 8.1 4.825.0 5.8 4.4 6.4 4.7 6.9 5.0 7.1 5.0 7.3 5.0 7.7 5.0 8.1 4.827.0 5.8 4.4 6.4 4.7 6.9 5.0 7.1 5.0 7.3 5.0 7.7 5.0 8.1 4.829.0 5.8 4.4 6.4 4.7 6.9 5.0 7.1 5.0 7.3 5.0 7.7 5.0 8.1 4.831.0 5.8 4.4 6.4 4.7 6.9 5.0 7.1 5.0 7.3 5.0 7.7 5.0 8.1 4.833.0 5.8 4.4 6.4 4.7 6.9 5.0 7.1 5.0 7.3 5.0 7.7 5.0 8.1 4.835.0 5.8 4.4 6.4 4.7 6.9 5.0 7.1 5.0 7.3 5.0 7.7 5.0 8.1 4.837.0 5.6 4.3 6.2 4.6 6.7 4.9 6.9 4.8 7.1 4.8 7.5 4.8 7.8 4.739.0 5.5 4.2 6.1 4.4 6.5 4.7 6.7 4.7 6.9 4.7 7.3 4.7 7.6 4.610.0 6.6 4.8 7.3 5.1 7.8 5.4 8.0 5.4 8.2 5.4 8.7 5.3 9.1 5.212.0 6.6 4.8 7.3 5.1 7.8 5.4 8.0 5.4 8.2 5.4 8.7 5.3 9.1 5.214.0 6.6 4.8 7.3 5.1 7.8 5.4 8.0 5.4 8.2 5.4 8.7 5.3 9.1 5.216.0 6.6 4.8 7.3 5.1 7.8 5.4 8.0 5.4 8.2 5.4 8.7 5.3 9.1 5.218.0 6.6 4.8 7.3 5.1 7.8 5.4 8.0 5.4 8.2 5.4 8.7 5.3 9.1 5.220.0 6.6 4.8 7.3 5.1 7.8 5.4 8.0 5.4 8.2 5.4 8.7 5.3 9.1 5.221.0 6.6 4.8 7.3 5.1 7.8 5.4 8.0 5.4 8.2 5.4 8.7 5.3 9.1 5.2

027 23.0 6.6 4.8 7.3 5.1 7.8 5.4 8.0 5.4 8.2 5.4 8.7 5.3 9.1 5.225.0 6.6 4.8 7.3 5.1 7.8 5.4 8.0 5.4 8.2 5.4 8.7 5.3 9.1 5.227.0 6.6 4.8 7.3 5.1 7.8 5.4 8.0 5.4 8.2 5.4 8.7 5.3 9.1 5.229.0 6.6 4.8 7.3 5.1 7.8 5.4 8.0 5.4 8.2 5.4 8.7 5.3 9.1 5.231.0 6.6 4.8 7.3 5.1 7.8 5.4 8.0 5.4 8.2 5.4 8.7 5.3 9.1 5.233.0 6.6 4.8 7.3 5.1 7.8 5.4 8.0 5.4 8.2 5.4 8.7 5.3 9.1 5.235.0 6.6 4.8 7.3 5.1 7.8 5.4 8.0 5.4 8.2 5.4 8.7 5.3 9.1 5.237.0 6.4 4.6 7.0 4.9 7.5 5.2 7.7 5.2 8.0 5.2 8.4 5.2 8.8 5.139.0 6.2 4.5 6.8 4.8 7.3 5.1 7.5 5.1 7.8 5.1 8.2 5.0 8.6 4.910.0 9.2 6.9 10.2 7.4 10.9 7.8 11.2 7.8 11.5 7.8 12.2 7.7 12.8 7.512.0 9.2 6.9 10.2 7.4 10.9 7.8 11.2 7.8 11.5 7.8 12.2 7.7 12.8 7.514.0 9.2 6.9 10.2 7.4 10.9 7.8 11.2 7.8 11.5 7.8 12.2 7.7 12.8 7.516.0 9.2 6.9 10.2 7.4 10.9 7.8 11.2 7.8 11.5 7.8 12.2 7.7 12.8 7.518.0 9.2 6.9 10.2 7.4 10.9 7.8 11.2 7.8 11.5 7.8 12.2 7.7 12.8 7.520.0 9.2 6.9 10.2 7.4 10.9 7.8 11.2 7.8 11.5 7.8 12.2 7.7 12.8 7.521.0 9.2 6.9 10.2 7.4 10.9 7.8 11.2 7.8 11.5 7.8 12.2 7.7 12.8 7.5

036 23.0 9.2 6.9 10.2 7.4 10.9 7.8 11.2 7.8 11.5 7.8 12.2 7.7 12.8 7.525.0 9.2 6.9 10.2 7.4 10.9 7.8 11.2 7.8 11.5 7.8 12.2 7.7 12.8 7.527.0 9.2 6.9 10.2 7.4 10.9 7.8 11.2 7.8 11.5 7.8 12.2 7.7 12.8 7.529.0 9.2 6.9 10.2 7.4 10.9 7.8 11.2 7.8 11.5 7.8 12.2 7.7 12.8 7.531.0 9.2 6.9 10.2 7.4 10.9 7.8 11.2 7.8 11.5 7.8 12.2 7.7 12.8 7.533.0 9.2 6.9 10.2 7.4 10.9 7.8 11.2 7.8 11.5 7.8 12.2 7.7 12.8 7.535.0 9.2 6.9 10.2 7.4 10.9 7.8 11.2 7.8 11.5 7.8 12.2 7.7 12.8 7.537.0 8.9 6.7 9.8 7.1 10.5 7.6 10.8 7.6 11.2 7.5 11.8 7.5 12.4 7.339.0 8.7 6.5 9.6 6.9 10.2 7.4 10.5 7.3 10.9 7.3 11.5 7.3 12.0 7.1

8

indoor air temp.unitsize

outdoorair temp.

TC : Total capacity [kW] SHC : Sensible capacity [kW]Concealed Duct High Static Pressure Type ( MMD-AP****H )

Page 60: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

57

14.0oCWB 16.0oCWB 18.0oCWB 19.0oCWB 20.0oCWB 22.0oCWB 24.0oCWB20oCDB 23oCDB 26oCDB 27oCDB 28oCDB 30oCDB 32oCDB

oCDB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC10.0 11.5 8.4 12.7 9.0 13.6 9.5 14.0 9.5 14.4 9.5 15.3 9.4 16.0 9.212.0 11.5 8.4 12.7 9.0 13.6 9.5 14.0 9.5 14.4 9.5 15.3 9.4 16.0 9.214.0 11.5 8.4 12.7 9.0 13.6 9.5 14.0 9.5 14.4 9.5 15.3 9.4 16.0 9.216.0 11.5 8.4 12.7 9.0 13.6 9.5 14.0 9.5 14.4 9.5 15.3 9.4 16.0 9.218.0 11.5 8.4 12.7 9.0 13.6 9.5 14.0 9.5 14.4 9.5 15.3 9.4 16.0 9.220.0 11.5 8.4 12.7 9.0 13.6 9.5 14.0 9.5 14.4 9.5 15.3 9.4 16.0 9.221.0 11.5 8.4 12.7 9.0 13.6 9.5 14.0 9.5 14.4 9.5 15.3 9.4 16.0 9.2

048 23.0 11.5 8.4 12.7 9.0 13.6 9.5 14.0 9.5 14.4 9.5 15.3 9.4 16.0 9.225.0 11.5 8.4 12.7 9.0 13.6 9.5 14.0 9.5 14.4 9.5 15.3 9.4 16.0 9.227.0 11.5 8.4 12.7 9.0 13.6 9.5 14.0 9.5 14.4 9.5 15.3 9.4 16.0 9.229.0 11.5 8.4 12.7 9.0 13.6 9.5 14.0 9.5 14.4 9.5 15.3 9.4 16.0 9.231.0 11.5 8.4 12.7 9.0 13.6 9.5 14.0 9.5 14.4 9.5 15.3 9.4 16.0 9.233.0 11.5 8.4 12.7 9.0 13.6 9.5 14.0 9.5 14.4 9.5 15.3 9.4 16.0 9.235.0 11.5 8.4 12.7 9.0 13.6 9.5 14.0 9.5 14.4 9.5 15.3 9.4 16.0 9.237.0 11.1 8.2 12.3 8.7 13.1 9.2 13.6 9.2 14.0 9.2 14.8 9.1 15.4 8.939.0 10.8 7.9 12.0 8.4 12.8 9.0 13.2 8.9 13.6 8.9 14.4 8.9 15.0 8.710.0 18.4 13.2 20.3 14.1 21.7 14.9 22.4 14.9 23.1 14.9 24.4 14.8 25.5 14.412.0 18.4 13.2 20.3 14.1 21.7 14.9 22.4 14.9 23.1 14.9 24.4 14.8 25.5 14.414.0 18.4 13.2 20.3 14.1 21.7 14.9 22.4 14.9 23.1 14.9 24.4 14.8 25.5 14.416.0 18.4 13.2 20.3 14.1 21.7 14.9 22.4 14.9 23.1 14.9 24.4 14.8 25.5 14.418.0 18.4 13.2 20.3 14.1 21.7 14.9 22.4 14.9 23.1 14.9 24.4 14.8 25.5 14.420.0 18.4 13.2 20.3 14.1 21.7 14.9 22.4 14.9 23.1 14.9 24.4 14.8 25.5 14.421.0 18.4 13.2 20.3 14.1 21.7 14.9 22.4 14.9 23.1 14.9 24.4 14.8 25.5 14.4

072 23.0 18.4 13.2 20.3 14.1 21.7 14.9 22.4 14.9 23.1 14.9 24.4 14.8 25.5 14.425.0 18.4 13.2 20.3 14.1 21.7 14.9 22.4 14.9 23.1 14.9 24.4 14.8 25.5 14.427.0 18.4 13.2 20.3 14.1 21.7 14.9 22.4 14.9 23.1 14.9 24.4 14.8 25.5 14.429.0 18.4 13.2 20.3 14.1 21.7 14.9 22.4 14.9 23.1 14.9 24.4 14.8 25.5 14.431.0 18.4 13.2 20.3 14.1 21.7 14.9 22.4 14.9 23.1 14.9 24.4 14.8 25.5 14.433.0 18.4 13.2 20.3 14.1 21.7 14.9 22.4 14.9 23.1 14.9 24.4 14.8 25.5 14.435.0 18.4 13.2 20.3 14.1 21.7 14.9 22.4 14.9 23.1 14.9 24.4 14.8 25.5 14.437.0 17.8 12.8 19.7 13.6 21.0 14.5 21.7 14.4 22.3 14.4 23.6 14.3 24.7 14.039.0 17.3 12.4 19.1 13.2 20.4 14.1 21.1 14.0 21.7 14.0 23.0 13.9 24.0 13.610.0 23.0 16.2 25.4 17.3 27.2 18.4 28.0 18.3 28.8 18.3 30.5 18.1 31.9 17.712.0 23.0 16.2 25.4 17.3 27.2 18.4 28.0 18.3 28.8 18.3 30.5 18.1 31.9 17.714.0 23.0 16.2 25.4 17.3 27.2 18.4 28.0 18.3 28.8 18.3 30.5 18.1 31.9 17.716.0 23.0 16.2 25.4 17.3 27.2 18.4 28.0 18.3 28.8 18.3 30.5 18.1 31.9 17.718.0 23.0 16.2 25.4 17.3 27.2 18.4 28.0 18.3 28.8 18.3 30.5 18.1 31.9 17.720.0 23.0 16.2 25.4 17.3 27.2 18.4 28.0 18.3 28.8 18.3 30.5 18.1 31.9 17.721.0 23.0 16.2 25.4 17.3 27.2 18.4 28.0 18.3 28.8 18.3 30.5 18.1 31.9 17.7

096 23.0 23.0 16.2 25.4 17.3 27.2 18.4 28.0 18.3 28.8 18.3 30.5 18.1 31.9 17.725.0 23.0 16.2 25.4 17.3 27.2 18.4 28.0 18.3 28.8 18.3 30.5 18.1 31.9 17.727.0 23.0 16.2 25.4 17.3 27.2 18.4 28.0 18.3 28.8 18.3 30.5 18.1 31.9 17.729.0 23.0 16.2 25.4 17.3 27.2 18.4 28.0 18.3 28.8 18.3 30.5 18.1 31.9 17.731.0 23.0 16.2 25.4 17.3 27.2 18.4 28.0 18.3 28.8 18.3 30.5 18.1 31.9 17.733.0 23.0 16.2 25.4 17.3 27.2 18.4 28.0 18.3 28.8 18.3 30.5 18.1 31.9 17.735.0 23.0 16.2 25.4 17.3 27.2 18.4 28.0 18.3 28.8 18.3 30.5 18.1 31.9 17.737.0 22.3 15.7 24.6 16.7 26.3 17.8 18.3 17.7 27.9 17.7 29.5 17.6 30.9 17.139.0 21.6 15.3 23.9 16.3 25.6 17.3 26.3 17.2 27.1 17.2 28.7 17.1 30.0 16.7

8

TC : Total capacity [kW] SHC : Sensible capacity [kW]indoor air temp.

unitsize

outdoorair temp.

Concealed Duct High Static Pressure Type ( MMD-AP****H )

Page 61: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

58

14.0oCWB 16.0oCWB 18.0oCWB 19.0oCWB 20.0oCWB 22.0oCWB 24.0oCWB20oCDB 23oCDB 26oCDB 27oCDB 28oCDB 30oCDB 32oCDB

oCDB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC10.0 3.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.112.0 3.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.114.0 3.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.116.0 3.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.118.0 3.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.120.0 3.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.121.0 3.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.1

015 23.0 3.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.125.0 3.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.127.0 3.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.129.0 3.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.131.0 3.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.133.0 3.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.135.0 3.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.137.0 3.6 2.7 4.0 2.9 4.2 3.1 4.4 3.1 4.5 3.1 4.7 3.1 5.0 3.039.0 3.5 2.7 3.8 2.8 4.1 3.0 4.2 3.0 4.4 3.0 4.6 3.0 4.8 2.910.0 4.6 3.5 5.1 3.7 5.4 3.9 5.6 3.9 5.8 3.9 6.1 3.9 6.4 3.812.0 4.6 3.5 5.1 3.7 5.4 3.9 5.6 3.9 5.8 3.9 6.1 3.9 6.4 3.814.0 4.6 3.5 5.1 3.7 5.4 3.9 5.6 3.9 5.8 3.9 6.1 3.9 6.4 3.816.0 4.6 3.5 5.1 3.7 5.4 3.9 5.6 3.9 5.8 3.9 6.1 3.9 6.4 3.818.0 4.6 3.5 5.1 3.7 5.4 3.9 5.6 3.9 5.8 3.9 6.1 3.9 6.4 3.820.0 4.6 3.5 5.1 3.7 5.4 3.9 5.6 3.9 5.8 3.9 6.1 3.9 6.4 3.821.0 4.6 3.5 5.1 3.7 5.4 3.9 5.6 3.9 5.8 3.9 6.1 3.9 6.4 3.8

018 23.0 4.6 3.5 5.1 3.7 5.4 3.9 5.6 3.9 5.8 3.9 6.1 3.9 6.4 3.825.0 4.6 3.5 5.1 3.7 5.4 3.9 5.6 3.9 5.8 3.9 6.1 3.9 6.4 3.827.0 4.6 3.5 5.1 3.7 5.4 3.9 5.6 3.9 5.8 3.9 6.1 3.9 6.4 3.829.0 4.6 3.5 5.1 3.7 5.4 3.9 5.6 3.9 5.8 3.9 6.1 3.9 6.4 3.831.0 4.6 3.5 5.1 3.7 5.4 3.9 5.6 3.9 5.8 3.9 6.1 3.9 6.4 3.833.0 4.6 3.5 5.1 3.7 5.4 3.9 5.6 3.9 5.8 3.9 6.1 3.9 6.4 3.835.0 4.6 3.5 5.1 3.7 5.4 3.9 5.6 3.9 5.8 3.9 6.1 3.9 6.4 3.837.0 4.5 3.3 4.9 3.6 5.3 3.8 5.4 3.8 5.6 3.8 5.9 3.7 6.2 3.739.0 4.3 3.3 4.8 3.5 5.1 3.7 5.3 3.7 5.4 3.7 5.7 3.6 6.0 3.610.0 5.8 4.5 6.4 4.8 6.9 5.1 7.1 5.1 7.3 5.1 7.7 5.1 8.1 4.912.0 5.8 4.5 6.4 4.8 6.9 5.1 7.1 5.1 7.3 5.1 7.7 5.1 8.1 4.914.0 5.8 4.5 6.4 4.8 6.9 5.1 7.1 5.1 7.3 5.1 7.7 5.1 8.1 4.916.0 5.8 4.5 6.4 4.8 6.9 5.1 7.1 5.1 7.3 5.1 7.7 5.1 8.1 4.918.0 5.8 4.5 6.4 4.8 6.9 5.1 7.1 5.1 7.3 5.1 7.7 5.1 8.1 4.920.0 5.8 4.5 6.4 4.8 6.9 5.1 7.1 5.1 7.3 5.1 7.7 5.1 8.1 4.921.0 5.8 4.5 6.4 4.8 6.9 5.1 7.1 5.1 7.3 5.1 7.7 5.1 8.1 4.9

024 23.0 5.8 4.5 6.4 4.8 6.9 5.1 7.1 5.1 7.3 5.1 7.7 5.1 8.1 4.925.0 5.8 4.5 6.4 4.8 6.9 5.1 7.1 5.1 7.3 5.1 7.7 5.1 8.1 4.927.0 5.8 4.5 6.4 4.8 6.9 5.1 7.1 5.1 7.3 5.1 7.7 5.1 8.1 4.929.0 5.8 4.5 6.4 4.8 6.9 5.1 7.1 5.1 7.3 5.1 7.7 5.1 8.1 4.931.0 5.8 4.5 6.4 4.8 6.9 5.1 7.1 5.1 7.3 5.1 7.7 5.1 8.1 4.933.0 5.8 4.5 6.4 4.8 6.9 5.1 7.1 5.1 7.3 5.1 7.7 5.1 8.1 4.935.0 5.8 4.5 6.4 4.8 6.9 5.1 7.1 5.1 7.3 5.1 7.7 5.1 8.1 4.937.0 5.6 4.4 6.2 4.7 6.7 5.0 6.9 4.9 7.1 4.9 7.5 4.9 7.8 4.839.0 5.5 4.3 6.1 4.5 6.5 4.8 6.7 4.8 6.9 4.8 7.3 4.8 7.6 4.610.0 6.6 5.0 7.3 5.3 7.8 5.6 8.0 5.6 8.2 5.6 8.7 5.5 9.1 5.412.0 6.6 5.0 7.3 5.3 7.8 5.6 8.0 5.6 8.2 5.6 8.7 5.5 9.1 5.414.0 6.6 5.0 7.3 5.3 7.8 5.6 8.0 5.6 8.2 5.6 8.7 5.5 9.1 5.416.0 6.6 5.0 7.3 5.3 7.8 5.6 8.0 5.6 8.2 5.6 8.7 5.5 9.1 5.418.0 6.6 5.0 7.3 5.3 7.8 5.6 8.0 5.6 8.2 5.6 8.7 5.5 9.1 5.420.0 6.6 5.0 7.3 5.3 7.8 5.6 8.0 5.6 8.2 5.6 8.7 5.5 9.1 5.421.0 6.6 5.0 7.3 5.3 7.8 5.6 8.0 5.6 8.2 5.6 8.7 5.5 9.1 5.4

027 23.0 6.6 5.0 7.3 5.3 7.8 5.6 8.0 5.6 8.2 5.6 8.7 5.5 9.1 5.425.0 6.6 5.0 7.3 5.3 7.8 5.6 8.0 5.6 8.2 5.6 8.7 5.5 9.1 5.427.0 6.6 5.0 7.3 5.3 7.8 5.6 8.0 5.6 8.2 5.6 8.7 5.5 9.1 5.429.0 6.6 5.0 7.3 5.3 7.8 5.6 8.0 5.6 8.2 5.6 8.7 5.5 9.1 5.431.0 6.6 5.0 7.3 5.3 7.8 5.6 8.0 5.6 8.2 5.6 8.7 5.5 9.1 5.433.0 6.6 5.0 7.3 5.3 7.8 5.6 8.0 5.6 8.2 5.6 8.7 5.5 9.1 5.435.0 6.6 5.0 7.3 5.3 7.8 5.6 8.0 5.6 8.2 5.6 8.7 5.5 9.1 5.437.0 6.4 4.8 7.0 5.1 7.5 5.4 7.7 5.4 8.0 5.4 8.4 5.4 8.8 5.239.0 6.2 4.7 6.8 5.0 7.3 5.3 7.5 5.3 7.8 5.3 8.2 5.2 8.6 5.1

8

Under Ceiling Type ( MMC-AP****H ) TC : Total capacity [kW] SHC : Sensible capacity [kW]

unitsize

outdoorair temp.

indoor air temp.

Page 62: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

59

14.0oCWB 16.0oCWB 18.0oCWB 19.0oCWB 20.0oCWB 22.0oCWB 24.0oCWB20oCDB 23oCDB 26oCDB 27oCDB 28oCDB 30oCDB 32oCDB

oCDB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC10.0 9.2 6.7 10.2 7.2 10.9 7.6 11.2 7.6 11.5 7.6 12.2 7.5 12.8 7.412.0 9.2 6.7 10.2 7.2 10.9 7.6 11.2 7.6 11.5 7.6 12.2 7.5 12.8 7.414.0 9.2 6.7 10.2 7.2 10.9 7.6 11.2 7.6 11.5 7.6 12.2 7.5 12.8 7.416.0 9.2 6.7 10.2 7.2 10.9 7.6 11.2 7.6 11.5 7.6 12.2 7.5 12.8 7.418.0 9.2 6.7 10.2 7.2 10.9 7.6 11.2 7.6 11.5 7.6 12.2 7.5 12.8 7.420.0 9.2 6.7 10.2 7.2 10.9 7.6 11.2 7.6 11.5 7.6 12.2 7.5 12.8 7.421.0 9.2 6.7 10.2 7.2 10.9 7.6 11.2 7.6 11.5 7.6 12.2 7.5 12.8 7.4

036 23.0 9.2 6.7 10.2 7.2 10.9 7.6 11.2 7.6 11.5 7.6 12.2 7.5 12.8 7.425.0 9.2 6.7 10.2 7.2 10.9 7.6 11.2 7.6 11.5 7.6 12.2 7.5 12.8 7.427.0 9.2 6.7 10.2 7.2 10.9 7.6 11.2 7.6 11.5 7.6 12.2 7.5 12.8 7.429.0 9.2 6.7 10.2 7.2 10.9 7.6 11.2 7.6 11.5 7.6 12.2 7.5 12.8 7.431.0 9.2 6.7 10.2 7.2 10.9 7.6 11.2 7.6 11.5 7.6 12.2 7.5 12.8 7.433.0 9.2 6.7 10.2 7.2 10.9 7.6 11.2 7.6 11.5 7.6 12.2 7.5 12.8 7.435.0 9.2 6.7 10.2 7.2 10.9 7.6 11.2 7.6 11.5 7.6 12.2 7.5 12.8 7.437.0 8.9 6.5 9.8 6.9 10.5 7.4 10.8 7.4 11.2 7.4 11.8 7.3 12.4 7.139.0 8.7 6.3 9.6 6.8 10.2 7.2 10.5 7.2 10.9 7.2 11.5 7.1 12.0 6.910.0 11.5 8.7 12.7 9.3 13.6 9.8 14.0 9.8 14.4 9.8 15.3 9.7 16.0 9.512.0 11.5 8.7 12.7 9.3 13.6 9.8 14.0 9.8 14.4 9.8 15.3 9.7 16.0 9.514.0 11.5 8.7 12.7 9.3 13.6 9.8 14.0 9.8 14.4 9.8 15.3 9.7 16.0 9.516.0 11.5 8.7 12.7 9.3 13.6 9.8 14.0 9.8 14.4 9.8 15.3 9.7 16.0 9.518.0 11.5 8.7 12.7 9.3 13.6 9.8 14.0 9.8 14.4 9.8 15.3 9.7 16.0 9.520.0 11.5 8.7 12.7 9.3 13.6 9.8 14.0 9.8 14.4 9.8 15.3 9.7 16.0 9.521.0 11.5 8.7 12.7 9.3 13.6 9.8 14.0 9.8 14.4 9.8 15.3 9.7 16.0 9.5

048 23.0 11.5 8.7 12.7 9.3 13.6 9.8 14.0 9.8 14.4 9.8 15.3 9.7 16.0 9.525.0 11.5 8.7 12.7 9.3 13.6 9.8 14.0 9.8 14.4 9.8 15.3 9.7 16.0 9.527.0 11.5 8.7 12.7 9.3 13.6 9.8 14.0 9.8 14.4 9.8 15.3 9.7 16.0 9.529.0 11.5 8.7 12.7 9.3 13.6 9.8 14.0 9.8 14.4 9.8 15.3 9.7 16.0 9.531.0 11.5 8.7 12.7 9.3 13.6 9.8 14.0 9.8 14.4 9.8 15.3 9.7 16.0 9.533.0 11.5 8.7 12.7 9.3 13.6 9.8 14.0 9.8 14.4 9.8 15.3 9.7 16.0 9.535.0 11.5 8.7 12.7 9.3 13.6 9.8 14.0 9.8 14.4 9.8 15.3 9.7 16.0 9.537.0 11.1 8.4 12.3 9.0 13.1 9.5 13.6 9.5 14.0 9.5 14.8 9.4 15.4 9.239.0 10.8 8.2 12.0 8.7 12.8 9.2 13.2 9.2 13.6 9.2 14.4 9.1 15.0 8.9

8

Under Ceiling Type ( MMC-AP****H ) TC : Total capacity [kW] SHC : Sensible capacity [kW]

unitsize

outdoorair temp.

indoor air temp.

Page 63: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

60

14.0oCWB 16.0oCWB 18.0oCWB 19.0oCWB 20.0oCWB 22.0oCWB 24.0oCWB20oCDB 23oCDB 26oCDB 27oCDB 28oCDB 30oCDB 32oCDB

oCDB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC10.0 1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.612.0 1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.614.0 1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.616.0 1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.618.0 1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.620.0 1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.621.0 1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.6

007 23.0 1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.625.0 1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.627.0 1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.629.0 1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.631.0 1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.633.0 1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.635.0 1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.637.0 1.7 1.5 1.9 1.6 2.1 1.7 2.1 1.6 2.2 1.6 2.3 1.6 2.4 1.639.0 1.7 1.4 1.9 1.5 2.0 1.6 2.1 1.6 2.1 1.6 2.3 1.6 2.4 1.510.0 2.3 1.8 2.5 1.9 2.7 2.0 2.8 2.0 2.9 2.0 3.1 2.0 3.2 1.912.0 2.3 1.8 2.5 1.9 2.7 2.0 2.8 2.0 2.9 2.0 3.1 2.0 3.2 1.914.0 2.3 1.8 2.5 1.9 2.7 2.0 2.8 2.0 2.9 2.0 3.1 2.0 3.2 1.916.0 2.3 1.8 2.5 1.9 2.7 2.0 2.8 2.0 2.9 2.0 3.1 2.0 3.2 1.918.0 2.3 1.8 2.5 1.9 2.7 2.0 2.8 2.0 2.9 2.0 3.1 2.0 3.2 1.920.0 2.3 1.8 2.5 1.9 2.7 2.0 2.8 2.0 2.9 2.0 3.1 2.0 3.2 1.921.0 2.3 1.8 2.5 1.9 2.7 2.0 2.8 2.0 2.9 2.0 3.1 2.0 3.2 1.9

009 23.0 2.3 1.8 2.5 1.9 2.7 2.0 2.8 2.0 2.9 2.0 3.1 2.0 3.2 1.925.0 2.3 1.8 2.5 1.9 2.7 2.0 2.8 2.0 2.9 2.0 3.1 2.0 3.2 1.927.0 2.3 1.8 2.5 1.9 2.7 2.0 2.8 2.0 2.9 2.0 3.1 2.0 3.2 1.929.0 2.3 1.8 2.5 1.9 2.7 2.0 2.8 2.0 2.9 2.0 3.1 2.0 3.2 1.931.0 2.3 1.8 2.5 1.9 2.7 2.0 2.8 2.0 2.9 2.0 3.1 2.0 3.2 1.933.0 2.3 1.8 2.5 1.9 2.7 2.0 2.8 2.0 2.9 2.0 3.1 2.0 3.2 1.935.0 2.3 1.8 2.5 1.9 2.7 2.0 2.8 2.0 2.9 2.0 3.1 2.0 3.2 1.937.0 2.2 1.7 2.5 1.8 2.6 1.9 2.7 1.9 2.8 1.9 3.0 1.9 3.1 1.939.0 2.2 1.7 2.4 1.8 2.6 1.9 2.6 1.9 2.7 1.9 2.9 1.9 3.0 1.810.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.412.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.414.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.416.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.418.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.420.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.421.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.4

012 23.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.425.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.427.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.429.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.431.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.433.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.435.0 3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.437.0 2.9 2.1 3.2 2.3 3.4 2.4 3.5 2.4 3.6 2.4 3.8 2.4 4.0 2.339.0 2.8 2.1 3.1 2.2 3.3 2.4 3.4 2.4 3.5 2.4 3.7 2.3 3.9 2.310.0 3.7 2.6 4.1 2.7 4.4 2.9 4.5 2.9 4.6 2.9 4.9 2.9 5.1 2.812.0 3.7 2.6 4.1 2.7 4.4 2.9 4.5 2.9 4.6 2.9 4.9 2.9 5.1 2.814.0 3.7 2.6 4.1 2.7 4.4 2.9 4.5 2.9 4.6 2.9 4.9 2.9 5.1 2.816.0 3.7 2.6 4.1 2.7 4.4 2.9 4.5 2.9 4.6 2.9 4.9 2.9 5.1 2.818.0 3.7 2.6 4.1 2.7 4.4 2.9 4.5 2.9 4.6 2.9 4.9 2.9 5.1 2.820.0 3.7 2.6 4.1 2.7 4.4 2.9 4.5 2.9 4.6 2.9 4.9 2.9 5.1 2.821.0 3.7 2.6 4.1 2.7 4.4 2.9 4.5 2.9 4.6 2.9 4.9 2.9 5.1 2.8

015 23.0 3.7 2.6 4.1 2.7 4.4 2.9 4.5 2.9 4.6 2.9 4.9 2.9 5.1 2.825.0 3.7 2.6 4.1 2.7 4.4 2.9 4.5 2.9 4.6 2.9 4.9 2.9 5.1 2.827.0 3.7 2.6 4.1 2.7 4.4 2.9 4.5 2.9 4.6 2.9 4.9 2.9 5.1 2.829.0 3.7 2.6 4.1 2.7 4.4 2.9 4.5 2.9 4.6 2.9 4.9 2.9 5.1 2.831.0 3.7 2.6 4.1 2.7 4.4 2.9 4.5 2.9 4.6 2.9 4.9 2.9 5.1 2.833.0 3.7 2.6 4.1 2.7 4.4 2.9 4.5 2.9 4.6 2.9 4.9 2.9 5.1 2.835.0 3.7 2.6 4.1 2.7 4.4 2.9 4.5 2.9 4.6 2.9 4.9 2.9 5.1 2.837.0 3.6 2.5 4.0 2.6 4.2 2.8 4.4 2.8 4.5 2.8 4.7 2.8 5.0 2.739.0 3.5 2.4 3.8 2.6 4.1 2.7 4.2 2.7 4.4 2.7 4.6 2.7 4.8 2.6

8

High Wall Type ( MMK-AP****H ) TC : Total capacity [kW] SHC : Sensible capacity [kW]

unitsize

outdoorair temp.

indoor air temp.

Page 64: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

61

14.0oCWB 16.0oCWB 18.0oCWB 19.0oCWB 20.0oCWB 22.0oCWB 24.0oCWB20oCDB 23oCDB 26oCDB 27oCDB 28oCDB 30oCDB 32oCDB

oCDB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC10.0 4.6 3.2 5.1 3.4 5.4 3.6 5.6 3.6 5.8 3.6 6.1 3.6 6.4 3.512.0 4.6 3.2 5.1 3.4 5.4 3.6 5.6 3.6 5.8 3.6 6.1 3.6 6.4 3.514.0 4.6 3.2 5.1 3.4 5.4 3.6 5.6 3.6 5.8 3.6 6.1 3.6 6.4 3.516.0 4.6 3.2 5.1 3.4 5.4 3.6 5.6 3.6 5.8 3.6 6.1 3.6 6.4 3.518.0 4.6 3.2 5.1 3.4 5.4 3.6 5.6 3.6 5.8 3.6 6.1 3.6 6.4 3.520.0 4.6 3.2 5.1 3.4 5.4 3.6 5.6 3.6 5.8 3.6 6.1 3.6 6.4 3.521.0 4.6 3.2 5.1 3.4 5.4 3.6 5.6 3.6 5.8 3.6 6.1 3.6 6.4 3.5

018 23.0 4.6 3.2 5.1 3.4 5.4 3.6 5.6 3.6 5.8 3.6 6.1 3.6 6.4 3.525.0 4.6 3.2 5.1 3.4 5.4 3.6 5.6 3.6 5.8 3.6 6.1 3.6 6.4 3.527.0 4.6 3.2 5.1 3.4 5.4 3.6 5.6 3.6 5.8 3.6 6.1 3.6 6.4 3.529.0 4.6 3.2 5.1 3.4 5.4 3.6 5.6 3.6 5.8 3.6 6.1 3.6 6.4 3.531.0 4.6 3.2 5.1 3.4 5.4 3.6 5.6 3.6 5.8 3.6 6.1 3.6 6.4 3.533.0 4.6 3.2 5.1 3.4 5.4 3.6 5.6 3.6 5.8 3.6 6.1 3.6 6.4 3.535.0 4.6 3.2 5.1 3.4 5.4 3.6 5.6 3.6 5.8 3.6 6.1 3.6 6.4 3.537.0 4.5 3.1 4.9 3.3 5.3 3.5 5.4 3.5 5.6 3.5 5.9 3.5 6.2 3.439.0 4.3 3.0 4.8 3.2 5.1 3.4 5.3 3.4 5.4 3.4 5.7 3.4 6.0 3.310.0 5.8 4.2 6.4 4.4 6.9 4.7 7.1 4.7 7.3 4.7 7.7 4.7 8.1 4.512.0 5.8 4.2 6.4 4.4 6.9 4.7 7.1 4.7 7.3 4.7 7.7 4.7 8.1 4.514.0 5.8 4.2 6.4 4.4 6.9 4.7 7.1 4.7 7.3 4.7 7.7 4.7 8.1 4.516.0 5.8 4.2 6.4 4.4 6.9 4.7 7.1 4.7 7.3 4.7 7.7 4.7 8.1 4.518.0 5.8 4.2 6.4 4.4 6.9 4.7 7.1 4.7 7.3 4.7 7.7 4.7 8.1 4.520.0 5.8 4.2 6.4 4.4 6.9 4.7 7.1 4.7 7.3 4.7 7.7 4.7 8.1 4.521.0 5.8 4.2 6.4 4.4 6.9 4.7 7.1 4.7 7.3 4.7 7.7 4.7 8.1 4.5

024 23.0 5.8 4.2 6.4 4.4 6.9 4.7 7.1 4.7 7.3 4.7 7.7 4.7 8.1 4.525.0 5.8 4.2 6.4 4.4 6.9 4.7 7.1 4.7 7.3 4.7 7.7 4.7 8.1 4.527.0 5.8 4.2 6.4 4.4 6.9 4.7 7.1 4.7 7.3 4.7 7.7 4.7 8.1 4.529.0 5.8 4.2 6.4 4.4 6.9 4.7 7.1 4.7 7.3 4.7 7.7 4.7 8.1 4.531.0 5.8 4.2 6.4 4.4 6.9 4.7 7.1 4.7 7.3 4.7 7.7 4.7 8.1 4.533.0 5.8 4.2 6.4 4.4 6.9 4.7 7.1 4.7 7.3 4.7 7.7 4.7 8.1 4.535.0 5.8 4.2 6.4 4.4 6.9 4.7 7.1 4.7 7.3 4.7 7.7 4.7 8.1 4.537.0 5.6 4.0 6.2 4.3 6.7 4.6 6.9 4.5 7.1 4.5 7.5 4.5 7.8 4.439.0 5.5 3.9 6.1 4.2 6.5 4.4 6.7 4.4 6.9 4.4 7.3 4.4 7.6 4.3

8

High Wall Type ( MMK-AP****H ) TC : Total capacity [kW] SHC : Sensible capacity [kW]

unitsize

outdoorair temp.

indoor air temp.

Page 65: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

62

14.0oCWB 16.0oCWB 18.0oCWB 19.0oCWB 20.0oCWB 22.0oCWB 24.0oCWB20oCDB 23oCDB 26oCDB 27oCDB 28oCDB 30oCDB 32oCDB

oCDB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC10.0 1.8 1.2 2.0 1.3 2.1 1.4 2.2 1.4 2.3 1.4 2.4 1.4 2.5 1.412.0 1.8 1.2 2.0 1.3 2.1 1.4 2.2 1.4 2.3 1.4 2.4 1.4 2.5 1.414.0 1.8 1.2 2.0 1.3 2.1 1.4 2.2 1.4 2.3 1.4 2.4 1.4 2.5 1.416.0 1.8 1.2 2.0 1.3 2.1 1.4 2.2 1.4 2.3 1.4 2.4 1.4 2.5 1.418.0 1.8 1.2 2.0 1.3 2.1 1.4 2.2 1.4 2.3 1.4 2.4 1.4 2.5 1.420.0 1.8 1.2 2.0 1.3 2.1 1.4 2.2 1.4 2.3 1.4 2.4 1.4 2.5 1.421.0 1.8 1.2 2.0 1.3 2.1 1.4 2.2 1.4 2.3 1.4 2.4 1.4 2.5 1.4

007 23.0 1.8 1.2 2.0 1.3 2.1 1.4 2.2 1.4 2.3 1.4 2.4 1.4 2.5 1.425.0 1.8 1.2 2.0 1.3 2.1 1.4 2.2 1.4 2.3 1.4 2.4 1.4 2.5 1.427.0 1.8 1.2 2.0 1.3 2.1 1.4 2.2 1.4 2.3 1.4 2.4 1.4 2.5 1.429.0 1.8 1.2 2.0 1.3 2.1 1.4 2.2 1.4 2.3 1.4 2.4 1.4 2.5 1.431.0 1.8 1.2 2.0 1.3 2.1 1.4 2.2 1.4 2.3 1.4 2.4 1.4 2.5 1.433.0 1.8 1.2 2.0 1.3 2.1 1.4 2.2 1.4 2.3 1.4 2.4 1.4 2.5 1.435.0 1.8 1.2 2.0 1.3 2.1 1.4 2.2 1.4 2.3 1.4 2.4 1.4 2.5 1.437.0 1.7 1.2 1.9 1.3 2.1 1.4 2.1 1.4 2.2 1.4 2.3 1.3 2.4 1.339.0 1.7 1.2 1.9 1.2 2.0 1.3 2.1 1.3 2.1 1.3 2.3 1.3 2.4 1.310.0 2.3 1.4 2.5 1.5 2.7 1.6 2.8 1.6 2.9 1.6 3.1 1.6 3.2 1.512.0 2.3 1.4 2.5 1.5 2.7 1.6 2.8 1.6 2.9 1.6 3.1 1.6 3.2 1.514.0 2.3 1.4 2.5 1.5 2.7 1.6 2.8 1.6 2.9 1.6 3.1 1.6 3.2 1.516.0 2.3 1.4 2.5 1.5 2.7 1.6 2.8 1.6 2.9 1.6 3.1 1.6 3.2 1.518.0 2.3 1.4 2.5 1.5 2.7 1.6 2.8 1.6 2.9 1.6 3.1 1.6 3.2 1.520.0 2.3 1.4 2.5 1.5 2.7 1.6 2.8 1.6 2.9 1.6 3.1 1.6 3.2 1.521.0 2.3 1.4 2.5 1.5 2.7 1.6 2.8 1.6 2.9 1.6 3.1 1.6 3.2 1.5

009 23.0 2.3 1.4 2.5 1.5 2.7 1.6 2.8 1.6 2.9 1.6 3.1 1.6 3.2 1.525.0 2.3 1.4 2.5 1.5 2.7 1.6 2.8 1.6 2.9 1.6 3.1 1.6 3.2 1.527.0 2.3 1.4 2.5 1.5 2.7 1.6 2.8 1.6 2.9 1.6 3.1 1.6 3.2 1.529.0 2.3 1.4 2.5 1.5 2.7 1.6 2.8 1.6 2.9 1.6 3.1 1.6 3.2 1.531.0 2.3 1.4 2.5 1.5 2.7 1.6 2.8 1.6 2.9 1.6 3.1 1.6 3.2 1.533.0 2.3 1.4 2.5 1.5 2.7 1.6 2.8 1.6 2.9 1.6 3.1 1.6 3.2 1.535.0 2.3 1.4 2.5 1.5 2.7 1.6 2.8 1.6 2.9 1.6 3.1 1.6 3.2 1.537.0 2.2 1.4 2.5 1.5 2.6 1.6 2.7 1.5 2.8 1.5 3.0 1.5 3.1 1.539.0 2.2 1.3 2.4 1.4 2.6 1.5 2.6 1.5 2.7 1.5 2.9 1.5 3.0 1.510.0 3.0 2.0 3.3 2.1 3.5 2.2 3.6 2.2 3.7 2.2 3.9 2.2 4.1 2.112.0 3.0 2.0 3.3 2.1 3.5 2.2 3.6 2.2 3.7 2.2 3.9 2.2 4.1 2.114.0 3.0 2.0 3.3 2.1 3.5 2.2 3.6 2.2 3.7 2.2 3.9 2.2 4.1 2.116.0 3.0 2.0 3.3 2.1 3.5 2.2 3.6 2.2 3.7 2.2 3.9 2.2 4.1 2.118.0 3.0 2.0 3.3 2.1 3.5 2.2 3.6 2.2 3.7 2.2 3.9 2.2 4.1 2.120.0 3.0 2.0 3.3 2.1 3.5 2.2 3.6 2.2 3.7 2.2 3.9 2.2 4.1 2.121.0 3.0 2.0 3.3 2.1 3.5 2.2 3.6 2.2 3.7 2.2 3.9 2.2 4.1 2.1

012 23.0 3.0 2.0 3.3 2.1 3.5 2.2 3.6 2.2 3.7 2.2 3.9 2.2 4.1 2.125.0 3.0 2.0 3.3 2.1 3.5 2.2 3.6 2.2 3.7 2.2 3.9 2.2 4.1 2.127.0 3.0 2.0 3.3 2.1 3.5 2.2 3.6 2.2 3.7 2.2 3.9 2.2 4.1 2.129.0 3.0 2.0 3.3 2.1 3.5 2.2 3.6 2.2 3.7 2.2 3.9 2.2 4.1 2.131.0 3.0 2.0 3.3 2.1 3.5 2.2 3.6 2.2 3.7 2.2 3.9 2.2 4.1 2.133.0 3.0 2.0 3.3 2.1 3.5 2.2 3.6 2.2 3.7 2.2 3.9 2.2 4.1 2.135.0 3.0 2.0 3.3 2.1 3.5 2.2 3.6 2.2 3.7 2.2 3.9 2.2 4.1 2.137.0 2.9 1.9 3.2 2.0 3.4 2.1 3.5 2.1 3.6 2.1 3.8 2.1 4.0 2.139.0 2.8 1.8 3.1 2.0 3.3 2.1 3.4 2.1 3.5 2.1 3.7 2.1 3.9 2.010.0 3.5 2.3 3.8 2.5 4.1 2.6 4.4 2.7 4.3 2.6 4.6 2.6 4.8 2.612.0 3.5 2.3 3.8 2.5 4.1 2.6 4.4 2.7 4.3 2.6 4.6 2.6 4.8 2.614.0 3.5 2.3 3.8 2.5 4.1 2.6 4.4 2.7 4.3 2.6 4.6 2.6 4.8 2.616.0 3.5 2.3 3.8 2.5 4.1 2.6 4.4 2.7 4.3 2.6 4.6 2.6 4.8 2.618.0 3.5 2.3 3.8 2.5 4.1 2.6 4.4 2.7 4.3 2.6 4.6 2.6 4.8 2.620.0 3.5 2.3 3.8 2.5 4.1 2.6 4.4 2.7 4.3 2.6 4.6 2.6 4.8 2.621.0 3.5 2.3 3.8 2.5 4.1 2.6 4.4 2.7 4.3 2.6 4.6 2.6 4.8 2.6

015 23.0 3.5 2.3 3.8 2.5 4.1 2.6 4.4 2.7 4.3 2.6 4.6 2.6 4.8 2.625.0 3.5 2.3 3.8 2.5 4.1 2.6 4.4 2.7 4.3 2.6 4.6 2.6 4.8 2.627.0 3.5 2.3 3.8 2.5 4.1 2.6 4.4 2.7 4.3 2.6 4.6 2.6 4.8 2.629.0 3.5 2.3 3.8 2.5 4.1 2.6 4.4 2.7 4.3 2.6 4.6 2.6 4.8 2.631.0 3.5 2.3 3.8 2.5 4.1 2.6 4.4 2.7 4.3 2.6 4.6 2.6 4.8 2.633.0 3.5 2.3 3.8 2.5 4.1 2.6 4.4 2.7 4.3 2.6 4.6 2.6 4.8 2.635.0 3.6 2.4 4.0 2.6 4.2 2.7 4.5 2.8 4.5 2.7 4.7 2.7 5.0 2.637.0 3.5 2.3 3.8 2.5 4.1 2.6 4.4 2.7 4.3 2.6 4.6 2.6 4.8 2.639.0 3.4 2.3 3.7 2.4 4.0 2.6 4.2 2.6 4.2 2.6 4.5 2.5 4.7 2.5

8

Floor Standing Cabinet Type ( MML-AP****H ) TC : Total capacity [kW] SHC : Sensible capacity [kW]

unitsize

outdoorair temp.

indoor air temp.

Page 66: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

63

14.0oCWB 16.0oCWB 18.0oCWB 19.0oCWB 20.0oCWB 22.0oCWB 24.0oCWB20oCDB 23oCDB 26oCDB 27oCDB 28oCDB 30oCDB 32oCDB

oCDB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC10.0 4.6 3.1 5.1 3.3 5.4 3.5 5.6 3.5 5.8 3.5 6.1 3.5 6.4 3.412.0 4.6 3.1 5.1 3.3 5.4 3.5 5.6 3.5 5.8 3.5 6.1 3.5 6.4 3.414.0 4.6 3.1 5.1 3.3 5.4 3.5 5.6 3.5 5.8 3.5 6.1 3.5 6.4 3.416.0 4.6 3.1 5.1 3.3 5.4 3.5 5.6 3.5 5.8 3.5 6.1 3.5 6.4 3.418.0 4.6 3.1 5.1 3.3 5.4 3.5 5.6 3.5 5.8 3.5 6.1 3.5 6.4 3.420.0 4.6 3.1 5.1 3.3 5.4 3.5 5.6 3.5 5.8 3.5 6.1 3.5 6.4 3.421.0 4.6 3.1 5.1 3.3 5.4 3.5 5.6 3.5 5.8 3.5 6.1 3.5 6.4 3.4

018 23.0 4.6 3.1 5.1 3.3 5.4 3.5 5.6 3.5 5.8 3.5 6.1 3.5 6.4 3.425.0 4.6 3.1 5.1 3.3 5.4 3.5 5.6 3.5 5.8 3.5 6.1 3.5 6.4 3.427.0 4.6 3.1 5.1 3.3 5.4 3.5 5.6 3.5 5.8 3.5 6.1 3.5 6.4 3.429.0 4.6 3.1 5.1 3.3 5.4 3.5 5.6 3.5 5.8 3.5 6.1 3.5 6.4 3.431.0 4.6 3.1 5.1 3.3 5.4 3.5 5.6 3.5 5.8 3.5 6.1 3.5 6.4 3.433.0 4.6 3.1 5.1 3.3 5.4 3.5 5.6 3.5 5.8 3.5 6.1 3.5 6.4 3.435.0 4.6 3.1 5.1 3.3 5.4 3.5 5.6 3.5 5.8 3.5 6.1 3.5 6.4 3.437.0 4.5 3.0 4.9 3.2 5.3 3.4 5.4 3.4 5.6 3.4 5.9 3.4 6.2 3.339.0 4.3 2.9 4.8 3.1 5.1 3.3 5.3 3.3 5.4 3.3 5.7 3.3 6.0 3.210.0 5.8 4.0 6.4 4.2 6.9 4.5 7.1 4.5 7.3 4.5 7.7 4.5 8.1 4.412.0 5.8 4.0 6.4 4.2 6.9 4.5 7.1 4.5 7.3 4.5 7.7 4.5 8.1 4.414.0 5.8 4.0 6.4 4.2 6.9 4.5 7.1 4.5 7.3 4.5 7.7 4.5 8.1 4.416.0 5.8 4.0 6.4 4.2 6.9 4.5 7.1 4.5 7.3 4.5 7.7 4.5 8.1 4.418.0 5.8 4.0 6.4 4.2 6.9 4.5 7.1 4.5 7.3 4.5 7.7 4.5 8.1 4.420.0 5.8 4.0 6.4 4.2 6.9 4.5 7.1 4.5 7.3 4.5 7.7 4.5 8.1 4.421.0 5.8 4.0 6.4 4.2 6.9 4.5 7.1 4.5 7.3 4.5 7.7 4.5 8.1 4.4

024 23.0 5.8 4.0 6.4 4.2 6.9 4.5 7.1 4.5 7.3 4.5 7.7 4.5 8.1 4.425.0 5.8 4.0 6.4 4.2 6.9 4.5 7.1 4.5 7.3 4.5 7.7 4.5 8.1 4.427.0 5.8 4.0 6.4 4.2 6.9 4.5 7.1 4.5 7.3 4.5 7.7 4.5 8.1 4.429.0 5.8 4.0 6.4 4.2 6.9 4.5 7.1 4.5 7.3 4.5 7.7 4.5 8.1 4.431.0 5.8 4.0 6.4 4.2 6.9 4.5 7.1 4.5 7.3 4.5 7.7 4.5 8.1 4.433.0 5.8 4.0 6.4 4.2 6.9 4.5 7.1 4.5 7.3 4.5 7.7 4.5 8.1 4.435.0 5.8 4.0 6.4 4.2 6.9 4.5 7.1 4.5 7.3 4.5 7.7 4.5 8.1 4.437.0 5.6 3.9 6.2 4.1 6.7 4.4 6.9 4.4 7.1 4.4 7.5 4.3 7.8 4.239.0 5.5 3.8 6.1 4.0 6.5 4.2 6.7 4.2 6.9 4.2 7.3 4.2 7.6 4.1

8

Floor Standing Cabinet Type ( MML-AP****H ) TC : Total capacity [kW] SHC : Sensible capacity [kW]

unitsize

outdoorair temp.

indoor air temp.

Page 67: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

64

14.0oCWB 16.0oCWB 18.0oCWB 19.0oCWB 20.0oCWB 22.0oCWB 24.0oCWB20oCDB 23oCDB 26oCDB 27oCDB 28oCDB 30oCDB 32oCDB

oCDB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC10.0 1.8 1.2 2.0 1.3 2.1 1.4 2.2 1.4 2.3 1.4 2.4 1.4 2.5 1.412.0 1.8 1.2 2.0 1.3 2.1 1.4 2.2 1.4 2.3 1.4 2.4 1.4 2.5 1.414.0 1.8 1.2 2.0 1.3 2.1 1.4 2.2 1.4 2.3 1.4 2.4 1.4 2.5 1.416.0 1.8 1.2 2.0 1.3 2.1 1.4 2.2 1.4 2.3 1.4 2.4 1.4 2.5 1.418.0 1.8 1.2 2.0 1.3 2.1 1.4 2.2 1.4 2.3 1.4 2.4 1.4 2.5 1.420.0 1.8 1.2 2.0 1.3 2.1 1.4 2.2 1.4 2.3 1.4 2.4 1.4 2.5 1.421.0 1.8 1.2 2.0 1.3 2.1 1.4 2.2 1.4 2.3 1.4 2.4 1.4 2.5 1.4

007 23.0 1.8 1.2 2.0 1.3 2.1 1.4 2.2 1.4 2.3 1.4 2.4 1.4 2.5 1.425.0 1.8 1.2 2.0 1.3 2.1 1.4 2.2 1.4 2.3 1.4 2.4 1.4 2.5 1.427.0 1.8 1.2 2.0 1.3 2.1 1.4 2.2 1.4 2.3 1.4 2.4 1.4 2.5 1.429.0 1.8 1.2 2.0 1.3 2.1 1.4 2.2 1.4 2.3 1.4 2.4 1.4 2.5 1.431.0 1.8 1.2 2.0 1.3 2.1 1.4 2.2 1.4 2.3 1.4 2.4 1.4 2.5 1.433.0 1.8 1.2 2.0 1.3 2.1 1.4 2.2 1.4 2.3 1.4 2.4 1.4 2.5 1.435.0 1.8 1.2 2.0 1.3 2.1 1.4 2.2 1.4 2.3 1.4 2.4 1.4 2.5 1.437.0 1.7 1.2 1.9 1.3 2.1 1.4 2.1 1.4 2.2 1.4 2.3 1.3 2.4 1.339.0 1.7 1.2 1.9 1.2 2.0 1.3 2.1 1.3 2.1 1.3 2.3 1.3 2.4 1.310.0 2.3 1.4 2.5 1.5 2.7 1.6 2.8 1.6 2.9 1.6 3.1 1.6 3.2 1.512.0 2.3 1.4 2.5 1.5 2.7 1.6 2.8 1.6 2.9 1.6 3.1 1.6 3.2 1.514.0 2.3 1.4 2.5 1.5 2.7 1.6 2.8 1.6 2.9 1.6 3.1 1.6 3.2 1.516.0 2.3 1.4 2.5 1.5 2.7 1.6 2.8 1.6 2.9 1.6 3.1 1.6 3.2 1.518.0 2.3 1.4 2.5 1.5 2.7 1.6 2.8 1.6 2.9 1.6 3.1 1.6 3.2 1.520.0 2.3 1.4 2.5 1.5 2.7 1.6 2.8 1.6 2.9 1.6 3.1 1.6 3.2 1.521.0 2.3 1.4 2.5 1.5 2.7 1.6 2.8 1.6 2.9 1.6 3.1 1.6 3.2 1.5

009 23.0 2.3 1.4 2.5 1.5 2.7 1.6 2.8 1.6 2.9 1.6 3.1 1.6 3.2 1.525.0 2.3 1.4 2.5 1.5 2.7 1.6 2.8 1.6 2.9 1.6 3.1 1.6 3.2 1.527.0 2.3 1.4 2.5 1.5 2.7 1.6 2.8 1.6 2.9 1.6 3.1 1.6 3.2 1.529.0 2.3 1.4 2.5 1.5 2.7 1.6 2.8 1.6 2.9 1.6 3.1 1.6 3.2 1.531.0 2.3 1.4 2.5 1.5 2.7 1.6 2.8 1.6 2.9 1.6 3.1 1.6 3.2 1.533.0 2.3 1.4 2.5 1.5 2.7 1.6 2.8 1.6 2.9 1.6 3.1 1.6 3.2 1.535.0 2.3 1.4 2.5 1.5 2.7 1.6 2.8 1.6 2.9 1.6 3.1 1.6 3.2 1.537.0 2.2 1.4 2.5 1.5 2.6 1.6 2.7 1.5 2.8 1.5 3.0 1.5 3.1 1.539.0 2.2 1.3 2.4 1.4 2.6 1.5 2.6 1.5 2.7 1.5 2.9 1.5 3.0 1.510.0 3.0 2.0 3.3 2.1 3.5 2.2 3.6 2.2 3.7 2.2 3.9 2.2 4.1 2.112.0 3.0 2.0 3.3 2.1 3.5 2.2 3.6 2.2 3.7 2.2 3.9 2.2 4.1 2.114.0 3.0 2.0 3.3 2.1 3.5 2.2 3.6 2.2 3.7 2.2 3.9 2.2 4.1 2.116.0 3.0 2.0 3.3 2.1 3.5 2.2 3.6 2.2 3.7 2.2 3.9 2.2 4.1 2.118.0 3.0 2.0 3.3 2.1 3.5 2.2 3.6 2.2 3.7 2.2 3.9 2.2 4.1 2.120.0 3.0 2.0 3.3 2.1 3.5 2.2 3.6 2.2 3.7 2.2 3.9 2.2 4.1 2.121.0 3.0 2.0 3.3 2.1 3.5 2.2 3.6 2.2 3.7 2.2 3.9 2.2 4.1 2.1

012 23.0 3.0 2.0 3.3 2.1 3.5 2.2 3.6 2.2 3.7 2.2 3.9 2.2 4.1 2.125.0 3.0 2.0 3.3 2.1 3.5 2.2 3.6 2.2 3.7 2.2 3.9 2.2 4.1 2.127.0 3.0 2.0 3.3 2.1 3.5 2.2 3.6 2.2 3.7 2.2 3.9 2.2 4.1 2.129.0 3.0 2.0 3.3 2.1 3.5 2.2 3.6 2.2 3.7 2.2 3.9 2.2 4.1 2.131.0 3.0 2.0 3.3 2.1 3.5 2.2 3.6 2.2 3.7 2.2 3.9 2.2 4.1 2.133.0 3.0 2.0 3.3 2.1 3.5 2.2 3.6 2.2 3.7 2.2 3.9 2.2 4.1 2.135.0 3.0 2.0 3.3 2.1 3.5 2.2 3.6 2.2 3.7 2.2 3.9 2.2 4.1 2.137.0 2.9 1.9 3.2 2.0 3.4 2.1 3.5 2.1 3.6 2.1 3.8 2.1 4.0 2.139.0 2.8 1.8 3.1 2.0 3.3 2.1 3.4 2.1 3.5 2.1 3.7 2.1 3.9 2.010.0 3.7 2.5 4.1 2.7 4.4 2.8 4.5 2.8 4.6 2.8 4.9 2.8 5.1 2.712.0 3.7 2.5 4.1 2.7 4.4 2.8 4.5 2.8 4.6 2.8 4.9 2.8 5.1 2.714.0 3.7 2.5 4.1 2.7 4.4 2.8 4.5 2.8 4.6 2.8 4.9 2.8 5.1 2.716.0 3.7 2.5 4.1 2.7 4.4 2.8 4.5 2.8 4.6 2.8 4.9 2.8 5.1 2.718.0 3.7 2.5 4.1 2.7 4.4 2.8 4.5 2.8 4.6 2.8 4.9 2.8 5.1 2.720.0 3.7 2.5 4.1 2.7 4.4 2.8 4.5 2.8 4.6 2.8 4.9 2.8 5.1 2.721.0 3.7 2.5 4.1 2.7 4.4 2.8 4.5 2.8 4.6 2.8 4.9 2.8 5.1 2.7

015 23.0 3.7 2.5 4.1 2.7 4.4 2.8 4.5 2.8 4.6 2.8 4.9 2.8 5.1 2.725.0 3.7 2.5 4.1 2.7 4.4 2.8 4.5 2.8 4.6 2.8 4.9 2.8 5.1 2.727.0 3.7 2.5 4.1 2.7 4.4 2.8 4.5 2.8 4.6 2.8 4.9 2.8 5.1 2.729.0 3.7 2.5 4.1 2.7 4.4 2.8 4.5 2.8 4.6 2.8 4.9 2.8 5.1 2.731.0 3.7 2.5 4.1 2.7 4.4 2.8 4.5 2.8 4.6 2.8 4.9 2.8 5.1 2.733.0 3.7 2.5 4.1 2.7 4.4 2.8 4.5 2.8 4.6 2.8 4.9 2.8 5.1 2.735.0 3.7 2.5 4.1 2.7 4.4 2.8 4.5 2.8 4.6 2.8 4.9 2.8 5.1 2.737.0 3.6 2.4 4.0 2.6 4.2 2.7 4.4 2.7 4.5 2.7 4.7 2.7 5.0 2.639.0 3.5 2.3 3.8 2.5 4.1 2.7 4.2 2.6 4.4 2.6 4.6 2.6 4.8 2.6

8

Floor Standing Concealed Type ( MML-AP****BH ) TC : Total capacity [kW] SHC : Sensible capacity [kW]

unitsize

outdoorair temp.

indoor air temp.

Page 68: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

65

14.0oCWB 16.0oCWB 18.0oCWB 19.0oCWB 20.0oCWB 22.0oCWB 24.0oCWB20oCDB 23oCDB 26oCDB 27oCDB 28oCDB 30oCDB 32oCDB

oCDB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC10.0 4.6 3.1 5.1 3.3 5.4 3.5 5.6 3.5 5.8 3.5 6.1 3.5 6.4 3.412.0 4.6 3.1 5.1 3.3 5.4 3.5 5.6 3.5 5.8 3.5 6.1 3.5 6.4 3.414.0 4.6 3.1 5.1 3.3 5.4 3.5 5.6 3.5 5.8 3.5 6.1 3.5 6.4 3.416.0 4.6 3.1 5.1 3.3 5.4 3.5 5.6 3.5 5.8 3.5 6.1 3.5 6.4 3.418.0 4.6 3.1 5.1 3.3 5.4 3.5 5.6 3.5 5.8 3.5 6.1 3.5 6.4 3.420.0 4.6 3.1 5.1 3.3 5.4 3.5 5.6 3.5 5.8 3.5 6.1 3.5 6.4 3.421.0 4.6 3.1 5.1 3.3 5.4 3.5 5.6 3.5 5.8 3.5 6.1 3.5 6.4 3.4

018 23.0 4.6 3.1 5.1 3.3 5.4 3.5 5.6 3.5 5.8 3.5 6.1 3.5 6.4 3.425.0 4.6 3.1 5.1 3.3 5.4 3.5 5.6 3.5 5.8 3.5 6.1 3.5 6.4 3.427.0 4.6 3.1 5.1 3.3 5.4 3.5 5.6 3.5 5.8 3.5 6.1 3.5 6.4 3.429.0 4.6 3.1 5.1 3.3 5.4 3.5 5.6 3.5 5.8 3.5 6.1 3.5 6.4 3.431.0 4.6 3.1 5.1 3.3 5.4 3.5 5.6 3.5 5.8 3.5 6.1 3.5 6.4 3.433.0 4.6 3.1 5.1 3.3 5.4 3.5 5.6 3.5 5.8 3.5 6.1 3.5 6.4 3.435.0 4.6 3.1 5.1 3.3 5.4 3.5 5.6 3.5 5.8 3.5 6.1 3.5 6.4 3.437.0 4.5 3.0 4.9 3.2 5.3 3.4 5.4 3.4 5.6 3.4 5.9 3.4 6.2 3.339.0 4.3 2.9 4.8 3.1 5.1 3.3 5.3 3.3 5.4 3.3 5.7 3.3 6.0 3.210.0 5.8 4.0 6.4 4.2 6.9 4.5 7.1 4.5 7.3 4.5 7.7 4.5 8.1 4.412.0 5.8 4.0 6.4 4.2 6.9 4.5 7.1 4.5 7.3 4.5 7.7 4.5 8.1 4.414.0 5.8 4.0 6.4 4.2 6.9 4.5 7.1 4.5 7.3 4.5 7.7 4.5 8.1 4.416.0 5.8 4.0 6.4 4.2 6.9 4.5 7.1 4.5 7.3 4.5 7.7 4.5 8.1 4.418.0 5.8 4.0 6.4 4.2 6.9 4.5 7.1 4.5 7.3 4.5 7.7 4.5 8.1 4.420.0 5.8 4.0 6.4 4.2 6.9 4.5 7.1 4.5 7.3 4.5 7.7 4.5 8.1 4.421.0 5.8 4.0 6.4 4.2 6.9 4.5 7.1 4.5 7.3 4.5 7.7 4.5 8.1 4.4

024 23.0 5.8 4.0 6.4 4.2 6.9 4.5 7.1 4.5 7.3 4.5 7.7 4.5 8.1 4.425.0 5.8 4.0 6.4 4.2 6.9 4.5 7.1 4.5 7.3 4.5 7.7 4.5 8.1 4.427.0 5.8 4.0 6.4 4.2 6.9 4.5 7.1 4.5 7.3 4.5 7.7 4.5 8.1 4.429.0 5.8 4.0 6.4 4.2 6.9 4.5 7.1 4.5 7.3 4.5 7.7 4.5 8.1 4.431.0 5.8 4.0 6.4 4.2 6.9 4.5 7.1 4.5 7.3 4.5 7.7 4.5 8.1 4.433.0 5.8 4.0 6.4 4.2 6.9 4.5 7.1 4.5 7.3 4.5 7.7 4.5 8.1 4.435.0 5.8 4.0 6.4 4.2 6.9 4.5 7.1 4.5 7.3 4.5 7.7 4.5 8.1 4.437.0 5.6 3.9 6.2 4.1 6.7 4.4 6.9 4.4 7.1 4.4 7.5 4.3 7.8 4.239.0 5.5 3.8 6.1 4.0 6.5 4.2 6.7 4.2 6.9 4.2 7.3 4.2 7.6 4.1

8

Floor Standing Concealed Type ( MML-AP****BH ) TC : Total capacity [kW] SHC : Sensible capacity [kW]

unitsize

outdoorair temp.

indoor air temp.

Page 69: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

66

14.0oCWB 16.0oCWB 18.0oCWB 19.0oCWB 20.0oCWB 22.0oCWB 24.0oCWB20oCDB 23oCDB 26oCDB 27oCDB 28oCDB 30oCDB 32oCDB

oCDB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC10.0 3.7 3.0 4.1 3.2 4.4 3.4 4.5 3.4 4.6 3.4 4.9 3.4 5.1 3.312.0 3.7 3.0 4.1 3.2 4.4 3.4 4.5 3.4 4.6 3.4 4.9 3.4 5.1 3.314.0 3.7 3.0 4.1 3.2 4.4 3.4 4.5 3.4 4.6 3.4 4.9 3.4 5.1 3.316.0 3.7 3.0 4.1 3.2 4.4 3.4 4.5 3.4 4.6 3.4 4.9 3.4 5.1 3.318.0 3.7 3.0 4.1 3.2 4.4 3.4 4.5 3.4 4.6 3.4 4.9 3.4 5.1 3.320.0 3.7 3.0 4.1 3.2 4.4 3.4 4.5 3.4 4.6 3.4 4.9 3.4 5.1 3.321.0 3.7 3.0 4.1 3.2 4.4 3.4 4.5 3.4 4.6 3.4 4.9 3.4 5.1 3.3

015 23.0 3.7 3.0 4.1 3.2 4.4 3.4 4.5 3.4 4.6 3.4 4.9 3.4 5.1 3.325.0 3.7 3.0 4.1 3.2 4.4 3.4 4.5 3.4 4.6 3.4 4.9 3.4 5.1 3.327.0 3.7 3.0 4.1 3.2 4.4 3.4 4.5 3.4 4.6 3.4 4.9 3.4 5.1 3.329.0 3.7 3.0 4.1 3.2 4.4 3.4 4.5 3.4 4.6 3.4 4.9 3.4 5.1 3.331.0 3.7 3.0 4.1 3.2 4.4 3.4 4.5 3.4 4.6 3.4 4.9 3.4 5.1 3.333.0 3.7 3.0 4.1 3.2 4.4 3.4 4.5 3.4 4.6 3.4 4.9 3.4 5.1 3.335.0 3.7 3.0 4.1 3.2 4.4 3.4 4.5 3.4 4.6 3.4 4.9 3.4 5.1 3.337.0 3.6 2.9 4.0 3.1 4.2 3.3 4.4 3.3 4.5 3.3 4.7 3.3 5.0 3.239.0 3.5 2.8 3.8 3.0 4.1 3.2 4.2 3.2 4.4 3.2 4.6 3.2 4.8 3.110.0 4.6 3.6 5.1 3.9 5.4 4.1 5.6 4.1 5.8 4.1 6.1 4.1 6.4 4.012.0 4.6 3.6 5.1 3.9 5.4 4.1 5.6 4.1 5.8 4.1 6.1 4.1 6.4 4.014.0 4.6 3.6 5.1 3.9 5.4 4.1 5.6 4.1 5.8 4.1 6.1 4.1 6.4 4.016.0 4.6 3.6 5.1 3.9 5.4 4.1 5.6 4.1 5.8 4.1 6.1 4.1 6.4 4.018.0 4.6 3.6 5.1 3.9 5.4 4.1 5.6 4.1 5.8 4.1 6.1 4.1 6.4 4.020.0 4.6 3.6 5.1 3.9 5.4 4.1 5.6 4.1 5.8 4.1 6.1 4.1 6.4 4.021.0 4.6 3.6 5.1 3.9 5.4 4.1 5.6 4.1 5.8 4.1 6.1 4.1 6.4 4.0

018 23.0 4.6 3.6 5.1 3.9 5.4 4.1 5.6 4.1 5.8 4.1 6.1 4.1 6.4 4.025.0 4.6 3.6 5.1 3.9 5.4 4.1 5.6 4.1 5.8 4.1 6.1 4.1 6.4 4.027.0 4.6 3.6 5.1 3.9 5.4 4.1 5.6 4.1 5.8 4.1 6.1 4.1 6.4 4.029.0 4.6 3.6 5.1 3.9 5.4 4.1 5.6 4.1 5.8 4.1 6.1 4.1 6.4 4.031.0 4.6 3.6 5.1 3.9 5.4 4.1 5.6 4.1 5.8 4.1 6.1 4.1 6.4 4.033.0 4.6 3.6 5.1 3.9 5.4 4.1 5.6 4.1 5.8 4.1 6.1 4.1 6.4 4.035.0 4.6 3.6 5.1 3.9 5.4 4.1 5.6 4.1 5.8 4.1 6.1 4.1 6.4 4.037.0 4.5 3.5 4.9 3.7 5.3 4.0 5.4 4.0 5.6 4.0 5.9 3.9 6.2 3.839.0 4.3 3.4 4.8 3.6 5.1 3.9 5.3 3.9 5.4 3.9 5.7 3.8 6.0 3.710.0 5.8 4.7 6.4 5.0 6.9 5.3 7.1 5.3 7.3 5.3 7.7 5.3 8.1 5.112.0 5.8 4.7 6.4 5.0 6.9 5.3 7.1 5.3 7.3 5.3 7.7 5.3 8.1 5.114.0 5.8 4.7 6.4 5.0 6.9 5.3 7.1 5.3 7.3 5.3 7.7 5.3 8.1 5.116.0 5.8 4.7 6.4 5.0 6.9 5.3 7.1 5.3 7.3 5.3 7.7 5.3 8.1 5.118.0 5.8 4.7 6.4 5.0 6.9 5.3 7.1 5.3 7.3 5.3 7.7 5.3 8.1 5.120.0 5.8 4.7 6.4 5.0 6.9 5.3 7.1 5.3 7.3 5.3 7.7 5.3 8.1 5.121.0 5.8 4.7 6.4 5.0 6.9 5.3 7.1 5.3 7.3 5.3 7.7 5.3 8.1 5.1

024 23.0 5.8 4.7 6.4 5.0 6.9 5.3 7.1 5.3 7.3 5.3 7.7 5.3 8.1 5.125.0 5.8 4.7 6.4 5.0 6.9 5.3 7.1 5.3 7.3 5.3 7.7 5.3 8.1 5.127.0 5.8 4.7 6.4 5.0 6.9 5.3 7.1 5.3 7.3 5.3 7.7 5.3 8.1 5.129.0 5.8 4.7 6.4 5.0 6.9 5.3 7.1 5.3 7.3 5.3 7.7 5.3 8.1 5.131.0 5.8 4.7 6.4 5.0 6.9 5.3 7.1 5.3 7.3 5.3 7.7 5.3 8.1 5.133.0 5.8 4.7 6.4 5.0 6.9 5.3 7.1 5.3 7.3 5.3 7.7 5.3 8.1 5.135.0 5.8 4.7 6.4 5.0 6.9 5.3 7.1 5.3 7.3 5.3 7.7 5.3 8.1 5.137.0 5.6 4.5 6.2 4.8 6.7 5.1 6.9 5.1 7.1 5.1 7.5 5.1 7.8 5.039.0 5.5 4.4 6.1 4.7 6.5 5.0 6.7 5.0 6.9 5.0 7.3 4.9 7.6 4.810.0 6.6 5.2 7.3 5.6 7.8 5.9 8.0 5.9 8.2 5.9 8.7 5.8 9.1 5.712.0 6.6 5.2 7.3 5.6 7.8 5.9 8.0 5.9 8.2 5.9 8.7 5.8 9.1 5.714.0 6.6 5.2 7.3 5.6 7.8 5.9 8.0 5.9 8.2 5.9 8.7 5.8 9.1 5.716.0 6.6 5.2 7.3 5.6 7.8 5.9 8.0 5.9 8.2 5.9 8.7 5.8 9.1 5.718.0 6.6 5.2 7.3 5.6 7.8 5.9 8.0 5.9 8.2 5.9 8.7 5.8 9.1 5.720.0 6.6 5.2 7.3 5.6 7.8 5.9 8.0 5.9 8.2 5.9 8.7 5.8 9.1 5.721.0 6.6 5.2 7.3 5.6 7.8 5.9 8.0 5.9 8.2 5.9 8.7 5.8 9.1 5.7

027 23.0 6.6 5.2 7.3 5.6 7.8 5.9 8.0 5.9 8.2 5.9 8.7 5.8 9.1 5.725.0 6.6 5.2 7.3 5.6 7.8 5.9 8.0 5.9 8.2 5.9 8.7 5.8 9.1 5.727.0 6.6 5.2 7.3 5.6 7.8 5.9 8.0 5.9 8.2 5.9 8.7 5.8 9.1 5.729.0 6.6 5.2 7.3 5.6 7.8 5.9 8.0 5.9 8.2 5.9 8.7 5.8 9.1 5.731.0 6.6 5.2 7.3 5.6 7.8 5.9 8.0 5.9 8.2 5.9 8.7 5.8 9.1 5.733.0 6.6 5.2 7.3 5.6 7.8 5.9 8.0 5.9 8.2 5.9 8.7 5.8 9.1 5.735.0 6.6 5.2 7.3 5.6 7.8 5.9 8.0 5.9 8.2 5.9 8.7 5.8 9.1 5.737.0 6.4 5.1 7.0 5.4 7.5 5.7 7.7 5.7 8.0 5.7 8.4 5.7 8.8 5.539.0 6.2 4.9 6.8 5.2 7.3 5.6 7.5 5.6 7.8 5.6 8.2 5.5 8.6 5.4

8

Floor Standing Type ( MMF-AP****H ) TC : Total capacity [kW] SHC : Sensible capacity [kW]

unitsize

outdoorair temp.

indoor air temp.

Page 70: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

67

14.0 WB 16.0oCWB 18.0oCWB 19.0oCWB 20.0oCWB 22.0oCWB 24.0oCWB20 DB 23oCoC

oC

oCDB 26oCDB 27oCDB 28oCDB 30oCDB 32oCDB

DB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC10.0 9.2 7.1 10.2 7.6 10.9 8.0 11.2 8.0 11.5 8.0 12.2 7.9 12.8 7.712.0 9.2 7.1 10.2 7.6 10.9 8.0 11.2 8.0 11.5 8.0 12.2 7.9 12.8 7.714.0 9.2 7.1 10.2 7.6 10.9 8.0 11.2 8.0 11.5 8.0 12.2 7.9 12.8 7.716.0 9.2 7.1 10.2 7.6 10.9 8.0 11.2 8.0 11.5 8.0 12.2 7.9 12.8 7.718.0 9.2 7.1 10.2 7.6 10.9 8.0 11.2 8.0 11.5 8.0 12.2 7.9 12.8 7.720.0 9.2 7.1 10.2 7.6 10.9 8.0 11.2 8.0 11.5 8.0 12.2 7.9 12.8 7.721.0 9.2 7.1 10.2 7.6 10.9 8.0 11.2 8.0 11.5 8.0 12.2 7.9 12.8 7.7

036 23.0 9.2 7.1 10.2 7.6 10.9 8.0 11.2 8.0 11.5 8.0 12.2 7.9 12.8 7.725.0 9.2 7.1 10.2 7.6 10.9 8.0 11.2 8.0 11.5 8.0 12.2 7.9 12.8 7.727.0 9.2 7.1 10.2 7.6 10.9 8.0 11.2 8.0 11.5 8.0 12.2 7.9 12.8 7.729.0 9.2 7.1 10.2 7.6 10.9 8.0 11.2 8.0 11.5 8.0 12.2 7.9 12.8 7.731.0 9.2 7.1 10.2 7.6 10.9 8.0 11.2 8.0 11.5 8.0 12.2 7.9 12.8 7.733.0 9.2 7.1 10.2 7.6 10.9 8.0 11.2 8.0 11.5 8.0 12.2 7.9 12.8 7.735.0 9.2 7.1 10.2 7.6 10.9 8.0 11.2 8.0 11.5 8.0 12.2 7.9 12.8 7.737.0 8.9 6.9 9.8 7.3 10.5 7.8 10.8 7.7 11.2 7.7 11.8 7.7 12.4 7.539.0 8.7 6.7 9.6 7.1 10.2 7.6 10.5 7.5 10.9 7.5 11.5 7.5 12.0 7.310.0 11.5 8.8 12.7 9.3 13.6 9.9 14.0 9.9 14.4 9.9 15.3 9.8 16.0 9.612.0 11.5 8.8 12.7 9.3 13.6 9.9 14.0 9.9 14.4 9.9 15.3 9.8 16.0 9.614.0 11.5 8.8 12.7 9.3 13.6 9.9 14.0 9.9 14.4 9.9 15.3 9.8 16.0 9.616.0 11.5 8.8 12.7 9.3 13.6 9.9 14.0 9.9 14.4 9.9 15.3 9.8 16.0 9.618.0 11.5 8.8 12.7 9.3 13.6 9.9 14.0 9.9 14.4 9.9 15.3 9.8 16.0 9.620.0 11.5 8.8 12.7 9.3 13.6 9.9 14.0 9.9 14.4 9.9 15.3 9.8 16.0 9.621.0 11.5 8.8 12.7 9.3 13.6 9.9 14.0 9.9 14.4 9.9 15.3 9.8 16.0 9.6

048 23.0 11.5 8.8 12.7 9.3 13.6 9.9 14.0 9.9 14.4 9.9 15.3 9.8 16.0 9.625.0 11.5 8.8 12.7 9.3 13.6 9.9 14.0 9.9 14.4 9.9 15.3 9.8 16.0 9.627.0 11.5 8.8 12.7 9.3 13.6 9.9 14.0 9.9 14.4 9.9 15.3 9.8 16.0 9.629.0 11.5 8.8 12.7 9.3 13.6 9.9 14.0 9.9 14.4 9.9 15.3 9.8 16.0 9.631.0 11.5 8.8 12.7 9.3 13.6 9.9 14.0 9.9 14.4 9.9 15.3 9.8 16.0 9.633.0 11.5 8.8 12.7 9.3 13.6 9.9 14.0 9.9 14.4 9.9 15.3 9.8 16.0 9.635.0 11.5 8.8 12.7 9.3 13.6 9.9 14.0 9.9 14.4 9.9 15.3 9.8 16.0 9.637.0 11.1 8.5 12.3 9.0 13.1 9.6 13.6 9.6 14.0 9.6 14.8 9.5 15.4 9.339.0 10.8 8.3 12.0 8.8 12.8 9.3 13.2 9.3 13.6 9.3 14.4 9.2 15.0 9.010.0 13.1 10.1 14.5 10.8 15.5 11.4 16.0 11.4 16.5 11.4 17.4 11.3 18.2 11.012.0 13.1 10.1 14.5 10.8 15.5 11.4 16.0 11.4 16.5 11.4 17.4 11.3 18.2 11.014.0 13.1 10.1 14.5 10.8 15.5 11.4 16.0 11.4 16.5 11.4 17.4 11.3 18.2 11.016.0 13.1 10.1 14.5 10.8 15.5 11.4 16.0 11.4 16.5 11.4 17.4 11.3 18.2 11.018.0 13.1 10.1 14.5 10.8 15.5 11.4 16.0 11.4 16.5 11.4 17.4 11.3 18.2 11.020.0 13.1 10.1 14.5 10.8 15.5 11.4 16.0 11.4 16.5 11.4 17.4 11.3 18.2 11.021.0 13.1 10.1 14.5 10.8 15.5 11.4 16.0 11.4 16.5 11.4 17.4 11.3 18.2 11.0

056 23.0 13.1 10.1 14.5 10.8 15.5 11.4 16.0 11.4 16.5 11.4 17.4 11.3 18.2 11.025.0 13.1 10.1 14.5 10.8 15.5 11.4 16.0 11.4 16.5 11.4 17.4 11.3 18.2 11.027.0 13.1 10.1 14.5 10.8 15.5 11.4 16.0 11.4 16.5 11.4 17.4 11.3 18.2 11.029.0 13.1 10.1 14.5 10.8 15.5 11.4 16.0 11.4 16.5 11.4 17.4 11.3 18.2 11.031.0 13.1 10.1 14.5 10.8 15.5 11.4 16.0 11.4 16.5 11.4 17.4 11.3 18.2 11.033.0 13.1 10.1 14.5 10.8 15.5 11.4 16.0 11.4 16.5 11.4 17.4 11.3 18.2 11.035.0 13.1 10.1 14.5 10.8 15.5 11.4 16.0 11.4 16.5 11.4 17.4 11.3 18.2 11.037.0 12.7 9.8 14.1 10.4 15.0 11.1 15.5 11.0 16.0 11.0 16.9 10.9 17.7 10.739.0 12.4 9.5 13.7 10.1 14.6 10.8 15.1 10.7 15.5 10.7 16.4 10.6 17.2 10.4

8

Floor Standing Type ( MMF-AP****H ) TC : Total capacity [kW] SHC : Sensible capacity [kW]

unitsize

outdoorair temp.

indoor air temp.

Page 71: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

68

Page 72: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

69

Part load performance

9

Page 73: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

70

Foreword

Page 74: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

71

9

9 ForewordPart load performance

Part Load Performance

( oC

40oC

35oC

30oC

25oC

20oC

15oC

)

( oC )

15oC

11oC

7oC

1oC

-5oC

-10oC

100% 90% 80% 70% 60% 50% 40% 30%Capacity Capacity Capacity Capacity Capacity Capacity Capacity Capacity

(kW)

13.0 3.86 3.16 2.54 2.02 1.59 1.24 1.03 0.88

14.0 3.65 2.98 2.40 1.90 1.49 1.16 0.96 0.82

14.0 3.02 2.48 2.00 1.60 1.27 1.00 0.84 0.73

14.0 2.71 2.22 1.80 1.45 1.15 0.92 0.78 0.68

14.0 2.52 2.07 1.68 1.35 1.08 0.87 0.74 0.65

14.0 2.34 1.93 1.57 1.26 1.01 0.82 0.70 0.61

100% 90% 80% 70% 60% 50% 40% 30%Capacity Capacity Capacity Capacity Capacity Capacity Capacity Capacity

(kW)

16.0 3.35 2.80 2.32 1.90 1.53 1.23 0.99 0.80

16.0 3.61 3.01 2.48 2.01 1.61 1.28 1.01 0.81

16.0 3.84 3.19 2.62 2.12 1.69 1.32 1.03 0.81

14.9 3.90 3.24 2.65 2.14 1.69 1.32 1.02 0.80

12.8 3.63 3.02 2.47 1.99 1.58 1.24 0.96 0.75

10.9 3.26 2.72 2.23 1.81 1.44 1.14 0.89 0.71

Cooling

OutdoorUnit

Dry-Bulb

OutdoorUnit 100%

CoolingCapacity

Compressor + Oudoor Fan Power consumption (kW)

Indoor air temperature conditions : 27.0 dry-bulb / 19.0 wet bulb

OutdoorUnit

Dry-Bulb

OutdoorUnit 100%

HeatingCapacity

Compressor + Oudoor Fan Power consumption (kW)

Indoor air temperature conditions : 20.0 dry-bulb

Heating

MMY-MAP0501 (5HP, 14kW system)

Page 75: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

72

( oC

40oC

35oC

30oC

25oC

20oC

15oC

)

( oC)

15oC

11oC

7oC

1oC

-5oC

-10oC

100% 90% 80% 70% 60% 50% 40% 30%Capacity Capacity Capacity Capacity Capacity Capacity Capacity Capacity

(kW)

14.9 4.91 4.01 3.23 2.57 2.02 1.58 1.26 1.05

16.0 4.64 3.79 3.05 2.42 1.90 1.48 1.17 0.97

16.0 3.84 3.15 2.55 2.03 1.61 1.28 1.03 0.87

16.0 3.44 2.83 2.29 1.84 1.46 1.17 0.95 0.82

16.0 3.20 2.63 2.14 1.72 1.37 1.10 0.90 0.78

16.0 2.97 2.45 1.99 1.61 1.29 1.04 0.86 0.74

100% 90% 80% 70% 60% 50% 40% 30%Capacity Capacity Capacity Capacity Capacity Capacity Capacity Capacity

(kW)

18.0 3.97 3.33 2.76 2.25 1.82 1.46 1.17 0.96

18.0 4.28 3.57 2.94 2.39 1.92 1.52 1.20 0.96

18.0 4.56 3.79 3.11 2.52 2.00 1.57 1.23 0.97

16.7 4.64 3.85 3.15 2.54 2.01 1.57 1.22 0.95

14.4 4.31 3.58 2.93 2.37 1.88 1.47 1.14 0.89

12.2 3.87 3.23 2.65 2.15 1.71 1.35 1.06 0.84

9

Part Load Performance

Cooling

OutdoorUnit

Dry-Bulb

OutdoorUnit 100%

CoolingCapacity

Compressor + Oudoor Fan Power consumption (kW)

Indoor air temperature conditions : 27.0 dry-bulb / 19.0 wet bulb

Compressor + Oudoor Fan Power consumption (kW)

Indoor air temperature conditions : 20.0 dry-bulb

Heating

OutdoorUnit

Dry-Bulb

OutdoorUnit 100%

HeatingCapacity

MMY-MAP0601 (6HP, 16kW system)

Page 76: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

73

9

Foreword

Part Load Performance

( oC

40oC

35oC

30oC

25oC

20oC

15oC

)

( oC )

15oC

11oC

7oC

1oC

-5oC

-10oC

100% 90% 80% 70% 60% 50% 40% 30%Capacity Capacity Capacity Capacity Capacity Capacity Capacity Capacity

(kW)

20.8 6.00 4.91 3.95 3.14 2.47 1.93 1.54 1.28

22.4 5.67 4.63 3.73 2.96 2.32 1.81 1.43 1.19

22.4 4.69 3.85 3.11 2.49 1.97 1.56 1.26 1.07

22.4 4.20 3.45 2.80 2.25 1.79 1.43 1.16 1.00

22.4 3.91 3.21 2.61 2.10 1.68 1.35 1.10 0.95

22.4 3.63 2.99 2.44 1.96 1.57 1.27 1.05 0.91

100% 90% 80% 70% 60% 50% 40% 30%Capacity Capacity Capacity Capacity Capacity Capacity Capacity Capacity

(kW)

25.0 5.12 4.29 3.55 2.91 2.35 1.89 1.51 1.23

25.0 5.52 4.61 3.79 3.08 2.47 1.96 1.55 1.24

25.0 5.88 4.89 4.01 3.24 2.58 2.03 1.58 1.25

23.3 5.98 4.97 4.06 3.27 2.59 2.02 1.57 1.22

20.0 5.55 4.62 3.78 3.05 2.42 1.90 1.47 1.15

17.0 5.00 4.16 3.42 2.77 2.21 1.74 1.37 1.08

Cooling

OutdoorUnit

Dry-Bulb

OutdoorUnit 100%

CoolingCapacity

Compressor + Oudoor Fan Power consumption (kW)

Indoor air temperature conditions : 27.0 dry-bulb / 19.0 wet bulb

Compressor + Oudoor Fan Power consumption (kW)

Indoor air temperature conditions : 20.0 dry-bulb

Heating

OutdoorUnit

Dry-Bulb

OutdoorUnit 100%

HeatingCapacity

MMY-MAP0801 (8HP, 22.4kW system)

Page 77: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

74

( oC

40oC

35oC

30oC

25oC

20oC

15oC

)

( oC )

15oC

11oC

7oC

1oC

-5oC

-10oC

100% 90% 80% 70% 60% 50% 40% 30%Capacity Capacity Capacity Capacity Capacity Capacity Capacity Capacity

(kW)

26.0 8.13 6.65 5.35 4.25 3.34 2.62 2.08 1.73

28.0 7.68 6.27 5.05 4.00 3.14 2.45 1.94 1.61

28.0 6.36 5.21 4.22 3.37 2.67 2.11 1.71 1.45

28.0 5.69 4.68 3.79 3.04 2.42 1.93 1.58 1.35

28.0 5.29 4.35 3.54 2.84 2.27 1.82 1.50 1.29

28.0 4.92 4.05 3.30 2.66 2.13 1.72 1.42 1.23

100% 90% 80% 70% 60% 50% 40% 30%Capacity Capacity Capacity Capacity Capacity Capacity Capacity Capacity

(kW)

31.5 6.94 5.82 4.82 3.94 3.18 2.56 2.05 1.67

31.5 7.49 6.25 5.14 4.18 3.35 2.65 2.10 1.68

31.5 7.97 6.63 5.44 4.40 3.50 2.75 2.15 1.69

29.3 8.10 6.73 5.51 4.44 3.52 2.74 2.12 1.66

25.2 7.53 6.26 5.13 4.13 3.28 2.57 2.00 1.56

21.4 6.77 5.64 4.63 3.75 2.99 2.36 1.85 1.47

9

Part Load Performance

Cooling

OutdoorUnit

Dry-Bulb

OutdoorUnit 100%

CoolingCapacity

Compressor + Oudoor Fan Power consumption (kW)

Indoor air temperature conditions : 27.0 dry-bulb / 19.0 wet bulb

Compressor + Oudoor Fan Power consumption (kW)

Indoor air temperature conditions : 20.0 dry-bulb

Heating

OutdoorUnit

Dry-Bulb

OutdoorUnit 100%

HeatingCapacity

MMY-MAP1001 (10HP, 28kW system)

Page 78: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

75

( oC

40oC

35oC

30oC

25oC

20oC

15oC

)

( oC )

15oC

11oC

7oC

1oC

-5oC

-10oC

100% 90% 80% 70% 60% 50% 40% 30%Capacity Capacity Capacity Capacity Capacity Capacity Capacity Capacity

(kW)

31.2 12.61 9.39 7.47 5.82 4.44 3.32 2.48 1.92

33.5 11.92 8.87 7.05 5.49 4.18 3.12 2.33 1.79

33.5 9.87 7.33 5.85 4.57 3.51 2.65 2.01 1.58

33.5 8.84 6.56 5.24 4.11 3.17 2.41 1.85 1.47

33.5 8.22 6.10 4.88 3.83 2.96 2.26 1.74 1.40

33.5 7.64 5.66 4.54 3.57 2.76 2.12 1.64 1.33

100% 90% 80% 70% 60% 50% 40% 30%Capacity Capacity Capacity Capacity Capacity Capacity Capacity Capacity

(kW)

37.5 8.88 7.53 6.26 5.14 4.06 3.15 2.42 1.87

37.5 9.57 8.12 6.73 5.50 4.31 3.31 2.51 1.90

37.5 10.19 8.66 7.16 5.82 4.54 3.46 2.59 1.93

34.9 10.36 8.81 7.27 5.90 4.58 3.48 2.58 1.91

30.0 9.63 8.18 6.76 5.49 4.27 3.25 2.42 1.79

25.5 8.66 7.35 6.08 4.96 3.87 2.96 2.23 1.67

9

Part Load Performance

Cooling

OutdoorUnit

Dry-Bulb

OutdoorUnit 100%

CoolingCapacity

Compressor + Oudoor Fan Power consumption (kW)

Indoor air temperature conditions : 27.0 dry-bulb / 19.0 wet bulb

Compressor + Oudoor Fan Power consumption (kW)

Indoor air temperature conditions : 20.0 dry-bulb

Heating

MMY-MAP1201 (12HP, 33.5kW system)

OutdoorUnit

Dry-Bulb

OutdoorUnit 100%

HeatingCapacity

Page 79: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

76

( oC

40oC

35oC

30oC

25oC

20oC

15oC

)

( oC )

15oC

11oC

7oC

1oC

-5oC

-10oC

100% 90% 80% 70% 60% 50% 40% 30%Capacity Capacity Capacity Capacity Capacity Capacity Capacity Capacity

(kW)

41.9 12.91 10.01 8.11 6.48 5.13 4.06 3.27 2.76

45.0 12.20 9.46 7.66 6.11 4.83 3.82 3.07 2.58

45.0 10.10 7.90 6.43 5.17 4.14 3.32 2.72 2.34

45.0 9.04 7.11 5.80 4.69 3.78 3.05 2.53 2.20

45.0 8.41 6.63 5.42 4.40 3.55 2.89 2.41 2.10

45.0 7.82 6.19 5.07 4.13 3.35 2.73 2.29 2.02

100% 90% 80% 70% 60% 50% 40% 30%Capacity Capacity Capacity Capacity Capacity Capacity Capacity Capacity

(kW)

50.0 10.70 8.80 7.33 6.03 4.92 3.99 3.25 2.69

50.0 11.53 9.44 7.81 6.38 5.16 4.14 3.31 2.69

50.0 12.28 10.00 8.25 6.71 5.38 4.28 3.39 2.71

46.5 12.49 10.15 8.35 6.77 5.41 4.27 3.36 2.66

40.0 11.60 9.45 7.78 6.32 5.06 4.01 3.17 2.53

34.0 10.43 8.54 7.06 5.76 4.64 3.70 2.95 2.39

9

Part Load Performance

Cooling

OutdoorUnit

Dry-Bulb

OutdoorUnit 100%

CoolingCapacity

Compressor + Oudoor Fan Power consumption (kW)

Indoor air temperature conditions : 27.0 dry-bulb / 19.0 wet bulb

Compressor + Oudoor Fan Power consumption (kW)

Indoor air temperature conditions : 20.0 dry-bulb

Heating

MMY-AP1601 (16HP, 45kW system)

OutdoorUnit

Dry-Bulb

OutdoorUnit 100%

HeatingCapacity

Page 80: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

77

( oC

40oC

35oC

30oC

25oC

20oC

15oC

)

( oC )

15oC

11oC

7oC

1oC

-5oC

-10oC

100% 90% 80% 70% 60% 50% 40% 30%Capacity Capacity Capacity Capacity Capacity Capacity Capacity Capacity

(kW)

52.1 17.11 13.49 10.91 8.70 6.88 5.43 4.36 3.67

56.0 16.17 12.75 10.30 8.21 6.48 5.10 4.09 3.43

56.0 13.38 10.62 8.63 6.93 5.53 4.42 3.61 3.09

56.0 11.99 9.56 7.79 6.28 5.04 4.07 3.35 2.90

56.0 10.82 8.66 7.08 5.74 4.63 3.76 3.13 2.73

56.0 10.06 8.08 6.62 5.37 4.35 3.55 2.97 2.61

100% 90% 80% 70% 60% 50% 40% 30%Capacity Capacity Capacity Capacity Capacity Capacity Capacity Capacity

(kW)

63.0 14.34 11.86 9.85 8.10 6.59 5.33 4.32 3.56

63.0 15.46 12.71 10.51 8.57 6.91 5.53 4.41 3.57

63.0 16.46 13.48 11.10 9.01 7.22 5.72 4.51 3.60

58.6 16.74 13.68 11.24 9.09 7.25 5.71 4.47 3.53

50.4 15.55 12.74 10.47 8.49 6.79 5.36 4.21 3.35

42.8 13.98 11.50 9.49 7.72 6.21 4.94 3.93 3.16

9

Part Load Performance

Cooling

OutdoorUnit

Dry-Bulb

OutdoorUnit 100%

CoolingCapacity

Compressor + Oudoor Fan Power consumption (kW)

Indoor air temperature conditions : 27.0 dry-bulb / 19.0 wet bulb

Compressor + Oudoor Fan Power consumption (kW)

Indoor air temperature conditions : 20.0 dry-bulb

Heating

MMY-AP2001 (20HP, 56kW system)

OutdoorUnit

Dry-Bulb

OutdoorUnit 100%

HeatingCapacity

Page 81: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

78

( oC

40oC

35oC

30oC

25oC

20oC

15oC

)

( oC )

15oC

11oC

7oC

1oC

-5oC

-10oC

100% 90% 80% 70% 60% 50% 40% 30%Capacity Capacity Capacity Capacity Capacity Capacity Capacity Capacity

(kW)

67.9 21.47 16.76 13.56 10.83 8.57 6.78 5.45 4.60

73.0 20.29 15.84 12.81 10.22 8.07 6.37 5.11 4.29

73.0 16.79 13.21 10.74 8.64 6.90 5.53 4.52 3.88

73.0 15.04 11.88 9.70 7.83 6.30 5.09 4.20 3.65

73.0 13.98 11.08 9.06 7.34 5.93 4.81 4.00 3.49

73.0 13.00 10.34 8.47 6.88 5.58 4.55 3.81 3.34

100% 90% 80% 70% 60% 50% 40% 30%Capacity Capacity Capacity Capacity Capacity Capacity Capacity Capacity

(kW)

81.5 17.87 14.73 12.25 10.08 8.21 6.66 5.41 4.47

81.5 19.26 15.79 13.06 10.67 8.62 6.90 5.52 4.48

81.5 20.51 16.75 13.80 11.21 8.99 7.14 5.64 4.52

75.8 20.86 16.99 13.97 11.31 9.03 7.12 5.59 4.43

65.2 19.37 15.82 13.02 10.57 8.46 6.69 5.27 4.20

55.4 17.42 14.29 11.80 9.62 7.74 6.18 4.92 3.96

9

Part Load Performance

Cooling

OutdoorUnit

Dry-Bulb

OutdoorUnit 100%

CoolingCapacity

Compressor + Oudoor Fan Power consumption (kW)

Indoor air temperature conditions : 27.0 dry-bulb / 19.0 wet bulb

Compressor + Oudoor Fan Power consumption (kW)

Indoor air temperature conditions : 20.0 dry-bulb

Heating

MMY-AP2601 (26HP, 73kW system)

OutdoorUnit

Dry-Bulb

OutdoorUnit 100%

HeatingCapacity

Page 82: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

79

9

Part Load Performance

Cooling

OutdoorUnit

Dry-Bulb

OutdoorUnit 100%

CoolingCapacity

Compressor + Oudoor Fan Power consumption (kW)

Indoor air temperature conditions : 27.0 dry-bulb / 19.0 wet bulb

Compressor + Oudoor Fan Power consumption (kW)

Indoor air temperature conditions : 20.0 dry-bulb

Heating

MMY-AP3001 (30HP, 84kW system)

OutdoorUnit

Dry-Bulb

OutdoorUnit 100%

HeatingCapacity

( oC

40oC

35oC

30oC

25oC

20oC

15oC

)

( oC )

15oC

11oC

7oC

1oC

-5oC

-10oC

100% 90% 80% 70% 60% 50% 40% 30%Capacity Capacity Capacity Capacity Capacity Capacity Capacity Capacity

(kW)

78.1 25.67 20.24 16.36 13.06 10.32 8.15 6.54 5.50

84.0 24.26 19.12 15.45 12.31 9.72 7.65 6.13 5.14

84.0 20.08 15.94 12.95 10.40 8.30 6.64 5.42 4.64

84.0 17.98 14.33 11.68 9.43 7.57 6.10 5.03 4.35

84.0 16.72 13.36 10.91 8.83 7.12 5.77 4.79 4.17

84.0 15.55 12.46 10.20 8.27 6.69 5.45 4.55 3.99

100% 90% 80% 70% 60% 50% 40% 30%Capacity Capacity Capacity Capacity Capacity Capacity Capacity Capacity

(kW)

95.0 21.63 17.78 14.78 12.14 9.88 8.00 6.48 5.34

95.0 23.31 19.07 15.76 12.86 10.37 8.29 6.62 5.36

95.0 24.82 20.22 16.65 13.52 10.83 8.58 6.77 5.40

88.4 25.24 20.52 16.85 13.64 10.88 8.56 6.70 5.30

76.0 23.45 19.10 15.71 12.73 10.18 8.04 6.32 5.02

64.6 21.09 17.25 14.23 11.59 9.31 7.41 5.89 4.73

Page 83: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

80

( oC

40oC

35oC

30oC

25oC

20oC

15oC

)

( oC )

15oC

11oC

7oC

1oC

-5oC

-10oC

100% 90% 80% 70% 60% 50% 40% 30%Capacity Capacity Capacity Capacity Capacity Capacity Capacity Capacity

(kW)

89.3 35.00 25.73 20.59 16.18 12.51 9.56 7.35 5.87

96.0 33.08 24.32 19.45 15.28 11.79 9.00 6.90 5.48

96.0 27.38 20.18 16.21 12.81 9.98 7.72 6.03 4.91

96.0 24.52 18.10 14.58 11.56 9.06 7.06 5.57 4.59

96.0 22.80 16.85 13.59 10.80 8.49 6.65 5.28 4.38

96.0 21.20 15.68 12.67 10.10 7.96 6.26 5.00 4.18

100% 90% 80% 70% 60% 50% 40% 30%Capacity Capacity Capacity Capacity Capacity Capacity Capacity Capacity

(kW)

108.0 25.74 21.20 17.66 14.54 11.63 9.19 7.23 5.75

108.0 27.74 22.82 18.94 15.50 12.29 9.61 7.44 5.81

108.0 29.54 24.28 20.08 16.37 12.90 10.00 7.66 5.89

100.4 30.04 24.68 20.38 16.56 13.01 10.03 7.62 5.80

86.4 27.90 22.95 18.97 15.44 12.15 9.39 7.17 5.48

73.4 25.10 20.68 17.13 13.99 11.07 8.61 6.64 5.14

9

Part Load Performance

Cooling

OutdoorUnit

Dry-Bulb

OutdoorUnit 100%

CoolingCapacity

Compressor + Oudoor Fan Power consumption (kW)

Indoor air temperature conditions : 27.0 dry-bulb / 19.0 wet bulb

Compressor + Oudoor Fan Power consumption (kW)

Indoor air temperature conditions : 20.0 dry-bulb

Heating

MMY-AP3411 (34HP, 96kW system)

OutdoorUnit

Dry-Bulb

OutdoorUnit 100%

HeatingCapacity

Page 84: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

81

( oC

40oC

35oC

30oC

25oC

20oC

15oC

)

( oC )

15oC

11oC

7oC

1oC

-5oC

-10oC

100% 90% 80% 70% 60% 50% 40% 30%Capacity Capacity Capacity Capacity Capacity Capacity Capacity Capacity

(kW)

104.2 34.22 26.98 21.82 17.41 13.76 10.86 8.72 7.34

112.0 32.34 25.49 20.60 16.42 12.95 10.20 8.17 6.85

112.0 26.77 21.25 17.26 13.87 11.06 8.85 7.22 6.19

112.0 23.97 19.11 15.58 12.57 10.09 8.13 6.71 5.81

112.0 22.29 17.82 14.55 11.78 9.49 7.69 6.38 5.56

112.0 20.72 16.61 13.60 11.03 8.92 7.27 6.07 5.32

100% 90% 80% 70% 60% 50% 40% 30%Capacity Capacity Capacity Capacity Capacity Capacity Capacity Capacity

(kW)

126.5 28.80 23.71 19.70 16.19 13.18 10.66 8.64 7.12

126.5 31.04 25.42 21.01 17.15 13.83 11.05 8.83 7.15

126.5 33.05 26.96 22.20 18.02 14.44 11.44 9.03 7.20

117.6 33.61 27.36 22.47 18.19 14.50 11.42 8.94 7.06

101.2 31.22 25.47 20.95 16.98 13.57 10.72 8.43 6.69

86.0 28.08 23.00 18.98 15.45 12.42 9.89 7.85 6.31

9

Part Load Performance

Cooling

OutdoorUnit

Dry-Bulb

OutdoorUnit 100%

CoolingCapacity

Compressor + Oudoor Fan Power consumption (kW)

Indoor air temperature conditions : 27.0 dry-bulb / 19.0 wet bulb

Compressor + Oudoor Fan Power consumption (kW)

Indoor air temperature conditions : 20.0 dry-bulb

Heating

MMY-AP4001 (40HP, 112kW system)

OutdoorUnit

Dry-Bulb

OutdoorUnit 100%

HeatingCapacity

Page 85: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

82

9

Part Load Performance

Cooling

OutdoorUnit

Dry-Bulb

OutdoorUnit 100%

CoolingCapacity

Compressor + Oudoor Fan Power consumption (kW)

Indoor air temperature conditions : 27.0 dry-bulb / 19.0 wet bulb

Compressor + Oudoor Fan Power consumption (kW)

Indoor air temperature conditions : 20.0 dry-bulb

Heating

MMY-AP4801 (48HP, 135kW system)

OutdoorUnit

Dry-Bulb

OutdoorUnit 100%

HeatingCapacity

( oC

40oC

35oC

30oC

25oC

20oC

15oC

)

( oC )

15oC

11oC

7oC

1oC

-5oC

-10oC

100% 90% 80% 70% 60% 50% 40% 30%Capacity Capacity Capacity Capacity Capacity Capacity Capacity Capacity

(kW)

125.6 52.55 37.96 30.27 23.67 18.14 13.70 10.34 8.06

135.0 49.67 35.89 28.61 22.35 17.11 12.90 9.71 7.54

135.0 41.11 29.74 23.79 18.69 14.43 11.02 8.45 6.72

135.0 36.82 26.65 21.37 16.84 13.07 10.05 7.78 6.27

135.0 34.23 24.79 19.90 15.72 12.24 9.45 7.37 5.98

135.0 31.83 23.06 18.54 14.68 11.46 8.89 6.97 5.70

100% 90% 80% 70% 60% 50% 40% 30%Capacity Capacity Capacity Capacity Capacity Capacity Capacity Capacity

(kW)

150.0 36.42 30.54 25.48 20.98 16.66 13.05 10.14 7.93

150.0 39.26 32.93 27.37 22.42 17.67 13.68 10.47 8.04

150.0 41.80 35.07 29.06 23.72 18.59 14.28 10.81 8.17

139.5 42.50 35.68 29.51 24.04 18.76 14.34 10.77 8.06

120.0 39.49 33.17 27.46 22.39 17.51 13.42 10.12 7.61

102.0 35.51 29.85 24.77 20.26 15.92 12.29 9.36 7.13

Page 86: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

83

Wiring guideline

10

Page 87: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

84

Foreword

Page 88: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

85

MAP0501T8 MAP0501HT8 MAP0501HT7 3.5mm2 (A WG #12) Max. 26 m 20 AMAP0601T8 MAP0601HT8 MAP0601HT7 3.5mm2 (A WG #12) Max. 26 m 20 AMAP0801T8 MAP0801HT8 MAP0801HT7 3.5mm2 (A WG #10) Max. 20 m 30 AMAP1001T8 MAP1001HT8 MAP1001HT7 5.5mm2 (A WG #10) Max. 28 m 30 AMAP1201T8 MAP1201HT8 MAP1201HT7 5.5mm2 (A WG #10) Max. 27 m 30 A

MMY-AP T8, HT8

MMY-AP HT7

3phase, 380_415 V, 50Hz

3phase, 380 V, 60Hz

L1 L2 L3 N L1 L2 L3 N L1 L2 L3 N L1 L2 L3 N

10

10 ForewordWiring guideline

WIRING DESIGN1. General

(1) Perform wiring of the power supplies in conformance with the regulations of the local electrical authorities.(2) Use a 2 core shielded wire for control wiring on connecting indoor units, and connecting of indoor units to outdoor units. This is recommended to prevent possible noise issues.(3) Be sure to connect an earth leakage breaker to the power supply of the indoor units.(4) Supply a separate power supply to each outdoor unit ensuring use of an earth leakage breaker and isolator.(5) Never connect 220_240V power to the terminal block (U1, U2, U3, U4, U5, U6) (Fault will be caused.)(6) Locate wiring system for the control and refrigerant piping system in the same line.(7) Arrange the electrical cables so that they do not come in to contact with high-temperature parts of the pipework; otherwise insulation will melt and an accident may be caused.(8) Do not turn on the power supply of the indoor units until vacuuming of the refrigerant pipe has finished.

2. For outdoor unit power supply Select the power supply cabling and fuse of each outdoor unit from the following specifications: 5 core cable in conformance with Design 60245 IEC 66 Do not connect the outdoor units by crossing outside of them, but connect them via the terminal block (L1, L2, L3, N).

Outdoor power supply3-phase 380V_415, 50Hz

380V, 60Hz

3. Electrical wiring design

3-phase50Hz 380-415VorEarth leakage breakerhand switch

60Hz 380VEarth

Outdoorpower source

Indoorpower source

Single phase50Hz 220-240VorEarth leakage breakerPower switch

60Hz 220V

Isolator box

Model Outdoor power supply

Unit capacities and power supply wire sizes (Reference)

Power supply wiringWire size Field size

Determine the wire size for the indoor unit according to the number of connected indoor units downstream. Observe local regulations in reference to the wire size selection and installation.

ModelMMY-

Page 89: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

86

2.0m2 (AWG#14) Max. 20m 3.5m2 (AWG#12) Max. 50m 15A

2 cores

2 cores

Up to 500m Up to 1000m 1000 to 2000m

1.25mm2 2.0mm Shield wire2

0.5 to 2.0mm2 _ _ _

10

NOTE :The above connecting lengths stated in the table, indicate the length from the isolator to the outdoor unit. When thepower supply of the indoor units are connected in parallel, it is assumed that no more than a 2% voltage drop will occur.

If the connecting length is to exceed the stated lengths, select a suitable wire in accordance with the local wiring standards.

4. For Indoor unit power supply (Must be independent from the outdoor unit power supply.)

Item

Model

All models of indoor units

Power supply wiring

Wire size Field fuse

CAUTIONS(1) Keep the refrigerant piping system and the indoor-indoor/indoor-outdoor control wiring systems together.(2) When running power supplies and control wires parallel to each other, either run them through separate conduits or maintain a suitable distance between them. (Current capacity of power supplies: 10A or less for 300m, 50A or less for 500m)

5. Design of control wiring

Power supplySingle phase220-240V 50Hz220Hz ~ 60Hz Earth

[Central remote controller] (Option)TCB-SC642TLE (For Line 64) Communication wire for control

between outdoor units Communi-cation wire for control betweenoutdoor unit and indoor unit

Connection of shield wire must be connected(Connected to all connecting sections in each outdoor unit)Connection of shield wire must be connected(Connected to all connecting sections in each indoor unit)

Wiredremote controller

Wire specification, quantity, size of crossover wiring and remote controller wiring

Name QtySize

Specification

Crossover wiring(indoor-indoor / indoor-outdoor / outdoor-indoorcontrol wiring, central control wiring)Remote controller wiring

(1) The crossover wiring and central control wiring uses a 2-core non-polarity communication wire. Use 2-core shieldedwire to prevent possible noise issues. Connect the end of the shielded wires and earth(ground) at both the outdoorand indoor unit. Where the shielded wire is connected between a central controller and a outdoor unit, onlyearth(ground) at one end of the central control line.

(2) Use 2-core non-polarity wire for remote controller. (A, B terminals) Use 2-core non-polarity wire for wiring of group control. (A, B terminals)

(Open)

Page 90: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

87

10

Foreword

6. Control wiring Diagram

2-core, non-polarity

1.25 m2 : Up to 1000 m2.0 m2 : Up to 2000 m (*1)

2-core, non-polarity

1.25 m2 to 2.0 m2

Up to 100 m (L5)

2-core

0.5 m2 to 2.0 m2

U3 U4

U1 U2

U1U3

U2U4

U5 U6

U1 U2

A B

U3 U4

U1 U2 U5 U6

U1 U2

A B

U1 U2

A B

U1 U2

A B

U1 U2

A B

U3 U4

U1 U2 U5 U6

U3 U4

U1 U2 U5 U6

U3 U4

U1 U2 U5 U6

Headerunit

Followerunit

Followerunit

Followerunit

U3 U4

U1 U2 U5 U6

U1 U2

A B

U1 U2

A B

U1 U2

A B

U3 U4

U1 U2 U5 U6

L1 L5

L6L7

L4

L2 L3

Headerunit

Headerunit

Followerunit

Table-1

Table-2

Table-3

Table-1

1. All control wiring is 2-core non-polarity wire.2. Be sure to use shield wire for the following wiring to prevent noise issues. Outdoor-outdoor / indoor-indoor / outdoor-indoor control wiring, Central control wiring.

Central controldevice

Super modular multi system

Outdoor unit

Indoor unit

Remotecontroller

Remote controllerRemote controller

Table-1 Control wiring between indoor and outdoor units (L1, L2, L3), Central control wiring (L4)

Wiring

Type

SizeLength

Shield wire

Shield wire

Up to 500 m ( L6 + L7) Up 400m in case of wireless remote controller in group control. Up to 200m total length of control wiring between indoor units ( L6 )

Note (*1) : Total length of control wiring length for all refrigerant circuits ( L1 + L2 + L3 + L4 )

Table-2 Control wiring between outdoor units (L5)

Table-3 Remote controller wiring (L6, L7)

Wiring

Type

SizeLength

Wire

Size

Length

Page 91: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

88

10

50Hz

kW FLA MCA MOCPMMU-AP 0091 H 230-1-50 198 264 0.060 0.20 0.25 15MMU-AP 0121 H 230-1-50 198 264 0.060 0.20 0.25 15MMU-AP 0151 H 230-1-50 198 264 0.060 0.22 0.28 15MMU-AP 0181 H 230-1-50 198 264 0.060 0.24 0.30 15MMU-AP 0241 H 230-1-50 198 264 0.060 0.28 0.35 15MMU-AP 0271 H 230-1-50 198 264 0.060 0.28 0.35 15MMU-AP 0301 H 230-1-50 198 264 0.060 0.40 0.50 15MMU-AP 0361 H 230-1-50 198 264 0.090 0.68 0.85 15MMU-AP 0481 H 230-1-50 198 264 0.090 0.93 1.16 15MMU-AP 0561 H 230-1-50 198 264 0.090 0.95 1.19 15MMU-AP 0071 WH 230-1-50 198 264 0.053 0.36 0.45 15MMU-AP 0091 WH 230-1-50 198 264 0.053 0.36 0.45 15MMU-AP 0121 WH 230-1-50 198 264 0.053 0.36 0.45 15MMU-AP 0151 WH 230-1-50 198 264 0.039 0.37 0.46 15MMU-AP 0181 WH 230-1-50 198 264 0.039 0.37 0.46 15MMU-AP 0241 WH 230-1-50 198 264 0.053 0.53 0.66 15MMU-AP 0271 WH 230-1-50 198 264 0.053 0.53 0.66 15MMU-AP 0301 WH 230-1-50 198 264 0.053 0.54 0.68 15MMU-AP 0481 WH 220-1-50 198 242 0.092 1.33 1.67 15MMU-AP 0071 YH 230-1-50 198 264 0.022 0.28 0.35 15MMU-AP 0091 YH 230-1-50 198 264 0.022 0.28 0.35 15MMU-AP 0121 YH 230-1-50 198 264 0.022 0.28 0.35 15MMU-AP 0151 SH 230-1-50 198 264 0.034 0.55 0.69 15MMU-AP 0181 SH 230-1-50 198 264 0.034 0.55 0.69 15MMU-AP 0241 SH 230-1-50 198 264 0.034 0.63 0.79 15MMD-AP 0071 BH 230-1-50 198 264 0.120 0.33 0.41 15MMD-AP 0091 BH 230-1-50 198 264 0.120 0.33 0.41 15MMD-AP 0121 BH 230-1-50 198 264 0.120 0.39 0.49 15MMD-AP 0151 BH 230-1-50 198 264 0.120 0.39 0.49 15MMD-AP 0181 BH 230-1-50 198 264 0.120 0.50 0.62 15MMD-AP 0241 BH 230-1-50 198 264 0.120 0.60 0.75 15MMD-AP 0271 BH 230-1-50 198 264 0.120 0.60 0.75 15MMD-AP 0301 BH 230-1-50 198 264 0.120 0.70 0.88 15MMD-AP 0361 BH 230-1-50 198 264 0.120 0.96 1.20 15MMD-AP 0481 BH 230-1-50 198 264 0.120 1.13 1.41 15MMD-AP 0561 BH 230-1-50 198 264 0.120 1.13 1.41 15MMD-AP 0181 H 230-1-50 198 264 0.160 0.93 1.16 15MMD-AP 0241 H 230-1-50 198 264 0.160 1.55 1.94 15MMD-AP 0271 H 230-1-50 198 264 0.160 1.55 1.94 15MMD-AP 0361 H 230-1-50 198 264 0.260 1.87 2.34 15MMD-AP 0481 H 230-1-50 198 264 0.260 2.12 2.65 15MMD-AP 0721 H 230-1-50 198 264 0.370 x 3 6.04 7.55 15MMD-AP 0961 H 230-1-50 198 264 0.370 x 3 6.35 7.94 15MMC-AP 0151 H 230-1-50 198 264 0.030 0.33 0.41 15MMC-AP 0181 H 230-1-50 198 264 0.030 0.37 0.46 15MMC-AP 0241 H 230-1-50 198 264 0.040 0.48 0.60 15MMC-AP 0271 H 230-1-50 198 264 0.040 0.48 0.60 15MMC-AP 0361 H 230-1-50 198 264 0.080 0.90 1.13 15MMC-AP 0481 H 230-1-50 198 264 0.080 0.96 1.20 15MMK-AP 0071 H 230-1-50 198 264 0.030 0.35 0.44 15MMK-AP 0091 H 230-1-50 198 264 0.030 0.35 0.44 15MMK-AP 0121 H 230-1-50 198 264 0.030 0.35 0.44 15MMK-AP 0151 H 230-1-50 198 264 0.030 0.37 0.46 15MMK-AP 0181 H 230-1-50 198 264 0.030 0.37 0.46 15MMK-AP 0241 H 230-1-50 198 264 0.030 0.40 0.50 15MML-AP 0071 H 230-1-50 198 264 0.045 0.30 0.37 15MML-AP 0091 H 230-1-50 198 264 0.045 0.30 0.37 15MML-AP 0121 H 230-1-50 198 264 0.045 0.49 0.62 15MML-AP 0151 H 230-1-50 198 264 0.045 0.49 0.62 15MML-AP 0181 H 230-1-50 198 264 0.070 0.54 0.68 15MML-AP 0241 H 230-1-50 198 264 0.070 0.54 0.68 15MML-AP 0071 BH 230-1-50 198 264 0.019 0.29 0.36 15MML-AP 0091 BH 230-1-50 198 264 0.019 0.29 0.36 15MML-AP 0121 BH 230-1-50 198 264 0.019 0.29 0.36 15MML-AP 0151 BH 230-1-50 198 264 0.070 0.52 0.65 15MML-AP 0181 BH 230-1-50 198 264 0.070 0.52 0.65 15MML-AP 0241 BH 230-1-50 198 264 0.070 0.53 0.66 15MMF-AP 0151 H 230-1-50 198 264 0.037 0.77 0.96 15MMF-AP 0181 H 230-1-50 198 264 0.037 0.77 0.96 15MMF-AP 0241 H 230-1-50 198 264 0.063 1.01 1.27 15MMF-AP 0271 H 230-1-50 198 264 0.063 1.01 1.27 15MMF-AP 0361 H 230-1-50 198 264 0.110 1.48 1.85 15MMF-AP 0481 H 230-1-50 198 264 0.160 1.84 2.30 15MMF-AP 0561 H 230-1-50 198 264 0.160 1.84 2.30 15

Type Model Nominal Voltage(V-Ph-Hz)

Voltage Range Fan Motor Power Supply

4-Way AirDischargeCassette Type

2-Way AirDischargeCassette Type

1-Way AirDischargeCassette Type

Concealed Duct Type

Concealed DuctHigh StaticPressure Type

Under Ceiling Type

Hige Wall Type

Floor StandingCabinet Type

Floor StandingConcealed Type

Floor Standing Type

Min Max

Page 92: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

89

10

60Hz

Min Max kW FLA MCA MOCPMMU-AP 0091 H 220-1-60 198 242 0.060 0.21 0.26 15MMU-AP 0121 H 220-1-60 198 242 0.060 0.21 0.26 15MMU-AP 0151 H 220-1-60 198 242 0.060 0.23 0.29 15MMU-AP 0181 H 220-1-60 198 242 0.060 0.25 0.31 15MMU-AP 0241 H 220-1-60 198 242 0.060 0.29 0.37 15MMU-AP 0271 H 220-1-60 198 242 0.060 0.29 0.37 15MMU-AP 0301 H 220-1-60 198 242 0.060 0.42 0.52 15MMU-AP 0361 H 220-1-60 198 242 0.090 0.70 0.88 15MMU-AP 0481 H 220-1-60 198 242 0.090 0.98 1.22 15MMU-AP 0561 H 220-1-60 198 242 0.090 1.00 1.25 15MMU-AP 0071 WH 220-1-60 198 242 0.053 0.38 0.47 15MMU-AP 0091 WH 220-1-60 198 242 0.053 0.38 0.47 15MMU-AP 0121 WH 220-1-60 198 242 0.053 0.38 0.47 15MMU-AP 0151 WH 220-1-60 198 242 0.039 0.44 0.55 15MMU-AP 0181 WH 220-1-60 198 242 0.039 0.44 0.55 15MMU-AP 0241 WH 220-1-60 198 242 0.053 0.61 0.76 15MMU-AP 0271 WH 220-1-60 198 242 0.053 0.61 0.76 15MMU-AP 0301 WH 220-1-60 198 242 0.053 0.67 0.84 15MMU-AP 0071 YH 220-1-60 198 242 0.022 0.30 0.37 15MMU-AP 0091 YH 220-1-60 198 242 0.022 0.30 0.37 15MMU-AP 0121 YH 220-1-60 198 242 0.022 0.30 0.37 15MMU-AP 0151 SH 220-1-60 198 242 0.034 0.62 0.78 15MMU-AP 0181 SH 220-1-60 198 242 0.034 0.62 0.78 15MMU-AP 0241 SH 220-1-60 198 242 0.034 0.70 0.88 15MMD-AP 0071 BH 220-1-60 198 242 0.120 0.35 0.43 15MMD-AP 0091 BH 220-1-60 198 242 0.120 0.35 0.43 15MMD-AP 0121 BH 220-1-60 198 242 0.120 0.41 0.51 15MMD-AP 0151 BH 220-1-60 198 242 0.120 0.41 0.51 15MMD-AP 0181 BH 220-1-60 198 242 0.120 0.52 0.65 15MMD-AP 0241 BH 220-1-60 198 242 0.120 0.63 0.78 15MMD-AP 0271 BH 220-1-60 198 242 0.120 0.63 0.78 15MMD-AP 0301 BH 220-1-60 198 242 0.120 0.73 0.91 15MMD-AP 0361 BH 220-1-60 198 242 0.120 1.00 1.25 15MMD-AP 0481 BH 220-1-60 198 242 0.120 1.18 1.48 15MMD-AP 0561 BH 220-1-60 198 242 0.120 1.18 1.48 15MMD-AP 0181 H 220-1-60 198 242 0.160 1.06 1.32 15MMD-AP 0241 H 220-1-60 198 242 0.160 2.07 2.59 15MMD-AP 0271 H 220-1-60 198 242 0.160 2.07 2.59 15MMD-AP 0361 H 220-1-60 198 242 0.260 2.38 2.98 15MMD-AP 0481 H 220-1-60 198 242 0.260 2.60 3.25 15MMD-AP 0721 H 220-1-60 198 242 0.370 x 3 8.17 10.2 15MMD-AP 0961 H 220-1-60 198 242 0.370 x 3 8.53 10.7 15MMC-AP 0151 H 220-1-60 198 242 0.030 0.35 0.43 15MMC-AP 0181 H 220-1-60 198 242 0.030 0.39 0.48 15MMC-AP 0241 H 220-1-60 198 242 0.040 0.50 0.63 15MMC-AP 0271 H 220-1-60 198 242 0.040 0.50 0.63 15MMC-AP 0361 H 220-1-60 198 242 0.080 0.94 1.18 15MMC-AP 0481 H 220-1-60 198 242 0.080 1.00 1.25 15MMK-AP 0071 H 220-1-60 198 242 0.030 0.37 0.46 15MMK-AP 0091 H 220-1-60 198 242 0.030 0.37 0.46 15MMK-AP 0121 H 220-1-60 198 242 0.030 0.37 0.46 15MMK-AP 0151 H 220-1-60 198 242 0.030 0.39 0.48 15MMK-AP 0181 H 220-1-60 198 242 0.030 0.39 0.48 15MMK-AP 0241 H 220-1-60 198 242 0.030 0.40 0.50 15MML-AP 0071 H 220-1-60 198 242 0.045 0.29 0.36 15MML-AP 0091 H 220-1-60 198 242 0.045 0.29 0.36 15MML-AP 0121 H 220-1-60 198 242 0.045 0.51 0.63 15MML-AP 0151 H 220-1-60 198 242 0.045 0.51 0.63 15MML-AP 0181 H 220-1-60 198 242 0.070 0.61 0.76 15MML-AP 0241 H 220-1-60 198 242 0.070 0.61 0.76 15MML-AP 0071 BH 220-1-60 198 242 0.019 0.31 0.39 15MML-AP 0091 BH 220-1-60 198 242 0.019 0.31 0.39 15MML-AP 0121 BH 220-1-60 198 242 0.019 0.31 0.39 15MML-AP 0151 BH 220-1-60 198 242 0.070 0.53 0.66 15MML-AP 0181 BH 220-1-60 198 242 0.070 0.53 0.66 15MML-AP 0241 BH 220-1-60 198 242 0.070 0.59 0.73 15MMF-AP 0151 H 220-1-60 198 242 0.037 0.77 0.96 15MMF-AP 0181 H 220-1-60 198 242 0.037 0.77 0.96 15MMF-AP 0241 H 220-1-60 198 242 0.063 1.04 1.29 15MMF-AP 0271 H 220-1-60 198 242 0.063 1.04 1.29 15MMF-AP 0361 H 220-1-60 198 242 0.110 1.58 1.97 15MMF-AP 0481 H 220-1-60 198 242 0.160 2.01 2.52 15MMF-AP 0561 H 220-1-60 198 242 0.160 2.01 2.52 15

Type Model Nominal Voltage(V-Ph-Hz)

Voltage Range Fan Motor Power Supply

4-Way AirDischargeCassette Type

2-Way AirDischargeCassette Type

1-Way AirDischargeCassette Type

Concealed Duct Type

Concealed DuctHigh StaticPressure Type

Under Ceiling Type

Hige Wall Type

Floor StandingCabinet Type

Floor StandingConcealed Type

Floor Standing Type

Page 93: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

90

MA

P05

01H

T8

MA

P05

01T

840

0-3-

5034

245

74.

0 +

4.0

0.6

00.

816

.520

_

MA

P06

01H

T8

MA

P06

01T

840

0-3-

5034

245

74.

6 +

4.6

0.6

00.

816

.520

_

MA

P08

01H

T8

MA

P08

01T

840

0-3-

5034

245

75.

2 +

5.2

0.6

01.

020

.030

_

MA

P10

01H

T8

MA

P10

01T

840

0-3-

5034

245

76.

5 +

6.5

0.6

01.

122

.530

_

MA

P12

01H

T8

MA

P12

01T

840

0-3-

5034

245

79.

5 +

9.5

0.6

01.

124

.530

_

AP

1401

HT

8A

P14

01T

840

0-3-

5034

245

75.

2 +

5.2

_4.

6 +

4.6

__

__

_0.

6

21.

0 +

0.8

36.5

40_

AP

1601

HT

8A

P16

01T

840

0-3-

5034

245

75.

2 +

5.2

_5.

2 +

5.2

__

__

_0.

6

21.

0 +

1.0

40.0

50_

AP

1801

HT

8A

P18

01T

840

0-3-

5034

245

76.

5 +

6.5

_5.

2 +

5.2

__

__

_0.

6

21.

0 +

1.1

42.5

50_

AP

2001

HT

8A

P20

01T

840

0-3-

5034

245

76.

5 +

6.5

_6.

5 +

6.5

__

__

_0.

6

21.

1 +

1.1

45.0

60_

AP

2201

HT

8A

P22

01T

840

0-3-

5034

245

75.

2 +

5.2

_5.

2 +

5.2

_4.

6 +

4.6

__

_0.

6

31.

0 +

1.0

+ 0

.856

.570

_

AP

2211

HT

8A

P22

11T

840

0-3-

5034

245

79.

5 +

9.5

_6.

5 +

6.5

__

__

_0.

6

21.

1 +

1.1

47.0

60_

AP

2401

HT

8A

P24

01T

840

0-3-

5034

245

75.

2 +

5.2

_5.

2 +

5.2

_5.

2 +

5.2

__

_0.

6

31.

0 +

1.0

+ 1

.060

.070

_

AP

2411

HT

8A

P24

11T

840

0-3-

5034

245

79.

5 +

9.5

_9.

5 +

9.5

__

__

_0.

6

21.

1 +

1.1

49.0

60_

AP

2601

HT

8A

P26

01T

840

0-3-

5034

245

76.

5 +

6.5

_5.

2 +

5.2

_5.

2 +

5.2

__

_0.

6

31.

1 +

1.1

+ 1

.062

.570

_

AP

2801

HT

8A

P28

01T

840

0-3-

5034

245

76.

5 +

6.5

_6.

5 +

6.5

_5.

2 +

5.2

__

_0.

6

31.

1 +

1.1

+ 1

.065

.080

_

AP

3001

HT

8A

P30

01T

840

0-3-

5034

245

76.

5 +

6.5

_6.

5 +

6.5

_6.

5 +

6.5

__

_0.

6

31.

1 +

1.1

+ 1

.167

.580

_

AP

3201

HT

8A

P32

01T

840

0-3-

5034

245

75.

2 +

5.2

_5.

2 +

5.2

_5.

2 +

5.2

_5.

2 +

5.2

_0.

6

41.

0 +

1.0

+ 1

.0 +

1.0

80.0

90_

AP

3211

HT

8A

P32

11T

840

0-3-

5034

245

79.

5 +

9.5

_6.

5 +

6.5

_6.

5 +

6.5

__

_0.

6

31.

1 +

1.1

+ 1

.169

.580

_

AP

3401

HT

8A

P34

01T

840

0-3-

5034

245

76.

5 +

6.5

_5.

2 +

5.2

_5.

2 +

5.2

_5.

2 +

5.2

_0.

6

41.

1 +

1.0

+ 1

.0 +

1.0

82.5

100

_

AP

3411

HT

8A

P34

11T

840

0-3-

5034

245

79.

5 +

9.5

_9.

5 +

9.5

_6.

5 +

6.5

__

_0.

6

31.

1 +

1.1

+ 1

.171

.580

_

AP

3601

HT

8A

P36

01T

840

0-3-

5034

245

76.

5 +

6.5

_6.

5 +

6.5

_5.

2 +

5.2

_5.

2 +

5.2

_0.

6

41.

1 +

1.1

+ 1

.0 +

1.0

85.0

100

_

AP

3611

HT

8A

P36

11T

840

0-3-

5034

245

79.

5 +

9.5

_9.

5 +

9.5

_9.

5 +

9.5

__

_0.

6

31.

1 +

1.1

+ 1

.173

.590

_

AP

3801

HT

8A

P38

01T

840

0-3-

5034

245

76.

5 +

6.5

_6.

5 +

9.5

_6.

5 +

6.5

_5.

2 +

5.2

_0.

6

41.

1 +

1.1

+ 1

.1 +

1.0

87.5

100

_

AP

4001

HT

8A

P40

01T

840

0-3-

5034

245

76.

5 +

6.5

_6.

5 +

6.5

_6.

5 +

6.5

_6.

5 +

6.5

_0.

6

41.

1 +

1.1

+ 1

.1 +

1.1

90.0

100

_

AP

4201

HT

8A

P42

01T

840

0-3-

5034

245

79.

5 +

9.5

_6.

5 +

6.5

_6.

5 +

6.5

_6.

5 +

6.5

_0.

6

41.

1 +

1.1

+ 1

.1 +

1.1

92.0

110

_

AP

4401

HT

8A

P44

01T

840

0-3-

5034

245

79.

5 +

9.5

_9.

5 +

9.5

_6.

5 +

6.5

_6.

5 +

6.5

_0.

6

41.

1 +

1.1

+ 1

.1 +

1.1

94.0

110

_

AP

4601

HT

8A

P46

01T

840

0-3-

5034

245

79.

5 +

9.5

_9.

5 +

9.5

_9.

5 +

9.5

_6.

5 +

6.5

_0.

6

41.

1 +

1.1

+ 1

.1 +

1.1

96.0

110

_

AP

4801

HT

8A

P48

01T

840

0-3-

5034

245

79.

5 +

9.5

_9.

5 +

9.5

_9.

5 +

9.5

_9.

5 +

9.5

_0.

6

41.

1 +

1.1

+ 1

.1 +

1.1

98.0

110

_

50H

z

x x x x x x x x x x x x x x x x x x x x x x x10

S

ing

le o

utd

oo

r un

it

C

om

bin

atio

n o

f out

do

or

unit

Leg

end

Hea

t P

um

pM

od

elM

MY

-

Co

olin

gO

nly

mo

del

MM

Y-

No

min

alV

olt

age

(V-P

h-H

z)

Vo

ltag

eR

ang

eC

om

pre

sso

rF

an M

oto

rP

ow

er S

up

ply

Min

Ma

xR

LALR

AM

CA

MO

CP

ICF

Hea

t P

um

pM

od

elM

MY

-

Co

olin

gO

nly

mo

del

MM

Y-

No

min

alV

olt

age

(V-P

h-H

z)

Vo

ltag

eR

ang

eC

om

pre

sso

rF

an M

oto

rP

ow

er S

up

ply

MC

AM

OC

PIC

F

kW

FLA

kW

FLA

Min

Ma

xR

LALR

AR

LALR

AR

LALR

AR

LALR

AU

nit

No

.1U

nit

No

.2U

nit

No

.3U

nit

No

.4

MC

A

: M

inim

um C

ircui

t A

mp

sM

OC

P

:

Max

imum

Ove

rcur

rent

Pro

tect

ion

(Am

ps)

ICF

: Max

imum

Inst

anta

neou

s C

urre

nt F

low

Sta

rtR

LA

: R

ated

Loa

d A

mp

s

LRA

: Lo

cked

Rot

or A

mp

sFL

A

:

Full

Load

Am

ps

kW

: Fa

n M

otor

R

ated

Out

put

(kW

)

NO

TE

:R

LA is

bas

ed o

n th

e fo

llow

ing

cond

ition

s.In

doo

r te

mp

erat

ure

:

27o C

DB

/19o C

WB

Out

doo

r te

mp

erat

ure

: 35

o C D

B

Page 94: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

91

10

MA

P05

01H

T7

380-

3-60

342

418

4.2

+ 4

.20.

60

0.8

16.5

20_

MA

P06

01H

T7

380-

3-60

342

418

4.8

+ 4

.80.

60

0.8

16.5

20_

MA

P08

01H

T7

380-

3-60

342

418

5.4

+ 5

.40.

60

1.0

20.0

30_

MA

P10

01H

T7

380-

3-60

342

418

6.9

+ 6

.90.

60

1.1

22.5

30_

MA

P12

01H

T7

380-

3-60

342

418

10.0

+ 1

0.0

0.6

01.

124

.530

_

AP

1401

HT

738

0-3-

6034

241

85.

4 +

5.4

_4.

8 +

4.8

__

__

_0.

6

21.

0 +

0.8

36.5

40_

AP

1601

HT

738

0-3-

6034

241

85.

4 +

5.2

_5.

4 +

5.4

__

__

_0.

6

21.

0 +

1.0

40.0

50_

AP

1801

HT

738

0-3-

6034

241

86.

9 +

6.9

_5.

4 +

5.4

__

__

_0.

6

21.

0 +

1.1

42.5

50_

AP

2001

HT

738

0-3-

6034

241

86.

9 +

6.9

_6.

9 +

6.9

__

__

_0.

6

21.

1 +

1.1

45.0

60_

AP

2201

HT

738

0-3-

6034

241

85.

4 +

5.4

_5.

4 +

5.4

_4.

8 +

4.8

__

_0.

6

31.

0 +

1.0

+ 0

.856

.570

_

AP

2211

HT

738

0-3-

6034

241

810

.0 +

10

.0_

6.9

+ 6

.9_

__

__

0.6

2

1.1

+ 1

.147

.060

_

AP

2401

HT

738

0-3-

6034

241

85.

4 +

5.4

_5.

4 +

5.4

_5.

4 +

5.4

__

_0.

6

31.

0 +

1.0

+ 1

.060

.070

_

AP

2411

HT

738

0-3-

6034

241

810

.0 +

10

.0_

10.0

+ 1

0.0

__

__

_0.

6

21.

1 +

1.1

49.0

60_

AP

2601

HT

738

0-3-

6034

241

86.

9 +

6.9

_5.

4 +

5.4

_5.

4 +

5.4

__

_0.

6

31.

1 +

1.1

+ 1

.062

.570

_

AP

2801

HT

738

0-3-

6034

241

86.

9 +

6.9

_6.

9 +

6.9

_5.

4 +

5.4

__

_0.

6

31.

1 +

1.1

+ 1

.065

.080

_

AP

3001

HT

738

0-3-

6034

241

86.

9 +

6.9

_6.

9 +

6.9

_6.

9 +

6.9

__

_0.

6

31.

1 +

1.1

+ 1

.167

.580

_

AP

3201

HT

738

0-3-

6034

241

85.

4 +

5.4

_5.

4 +

5.4

_5.

4 +

5.4

_5.

4 +

5.4

_0.

6

41.

0 +

1.0

+ 1

.0 +

1.0

80.0

90_

AP

3211

HT

738

0-3-

6034

241

810

.0 +

10

.0_

6.9

+ 6

.9_

6.9

+ 6

.9_

__

0.6

3

1.1

+ 1

.1 +

1.1

69.5

80_

AP

3401

HT

738

0-3-

6034

241

86.

9 +

6.9

_5.

4 +

5.4

_5.

4 +

5.4

_5.

4 +

5.4

_0.

6

41.

1 +

1.0

+ 1

.0 +

1.0

82.5

100

_

AP

3411

HT

738

0-3-

6034

241

810

.0 +

10

.0_

10.0

+ 1

0.0

_6

.9 +

6.9

__

_0.

6

31.

1 +

1.1

+ 1

.171

.580

_

AP

3601

HT

738

0-3-

6034

241

86.

9 +

6.9

_6.

9 +

6.9

_5.

4 +

5.4

_5.

4 +

5.4

_0.

6

41.

1 +

1.1

+ 1

.0 +

1.0

85.0

100

_

AP

3611

HT

738

0-3-

6034

241

810

.0 +

10

.0_

10.0

+ 1

0.0

_10

.0 +

10

.0_

__

0.6

3

1.1

+ 1

.1 +

1.1

73.5

90_

AP

3801

HT

738

0-3-

6034

241

86.

9 +

6.9

_6.

9 +

9.9

_6.

9 +

6.9

_5.

4 +

5.4

_0.

6

41.

1 +

1.1

+ 1

.1 +

1.0

87.5

100

_

AP

4001

HT

738

0-3-

6034

241

86.

9 +

6.9

_6.

9 +

6.9

_6.

9 +

6.9

_6.

9 +

6.9

_0.

6

41.

1 +

1.1

+ 1

.1 +

1.1

90.0

100

_

AP

4201

HT

738

0-3-

6034

241

810

.0 +

10

.0_

6.9

+ 6

.9_

6.9

+ 6

.9_

6.9

+ 6

.9_

0.6

4

1.1

+ 1

.1 +

1.1

+ 1

.192

.011

0_

AP

4401

HT

738

0-3-

6034

241

810

.0 +

10

.0_

10.0

+ 1

0.0

_6

.9 +

6.9

_6.

9 +

6.9

_0.

6

41.

1 +

1.1

+ 1

.1 +

1.1

94.0

110

_

AP

4601

HT

738

0-3-

6034

241

810

.0 +

10

.0_

10.0

+ 1

0.0

_10

.0 +

10

.0_

6.9

+ 6

.9_

0.6

4

1.1

+ 1

.1 +

1.1

+ 1

.196

.011

0_

AP

4801

HT

738

0-3-

6034

241

810

.0 +

10

.0_

10.0

+ 1

0.0

_10

.0 +

10

.0_

10.0

+ 1

0.0

_0.6

4

1.1

+ 1

.1 +

1.1

+ 1

.198

.011

0_

60H

z

x x x x x x x x x x x x x x x x x x x x x x x

Leg

end

MC

A

: M

inim

um C

ircui

t A

mp

sM

OC

P

:

Max

imum

Ove

rcur

rent

Pro

tect

ion

(Am

ps)

ICF

: Max

imum

Inst

anta

neou

s C

urre

nt F

low

Sta

rtR

LA

: R

ated

Loa

d A

mp

s

LRA

: Lo

cked

Rot

or A

mp

sFL

A

:

Full

Load

Am

ps

kW

: Fa

n M

otor

R

ated

Out

put

(kW

)

NO

TE

:R

LA is

bas

ed o

n th

e fo

llow

ing

cond

ition

s.In

doo

r te

mp

erat

ure

:

27o C

DB

/19o C

WB

Out

doo

r te

mp

erat

ure

: 35

o C D

B

S

ing

le o

utd

oo

r un

it

C

om

bin

atio

n o

f out

do

or

unit

Hea

t P

um

pM

od

elM

MY

-

No

min

alV

olt

age

(V-P

h-H

z)

Vo

ltag

eR

ang

eC

om

pre

sso

rF

an M

oto

rP

ow

er S

up

ply

Min

Ma

xR

LALR

AM

CA

MO

CP

ICF

kW

FLA

Hea

t P

um

pM

od

elM

MY

-

No

min

alV

olt

age

(V-P

h-H

z)

Vo

ltag

eR

ang

eC

om

pre

sso

rF

an M

oto

rP

ow

er S

up

ply

MC

AM

OC

PIC

Fk

WFL

AM

inM

ax

RLA

LRA

RLA

LRA

RLA

LRA

RLA

LRA

Un

it N

o.1

Un

it N

o.2

Un

it N

o.3

Un

it N

o.4

Page 95: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

92

10

Page 96: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

93

Wiring diagram

11

Page 97: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

94

Foreword

Page 98: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

95

11

11 ForewordWiring diagram

1. Indoor Unit

60Hz 380V

1-1. 4-way Air Discharge Cassette TypeModel: MMU-AP0091H, AP0121H, AP0151H, AP0181H, AP0241H, MMU-AP0271H, AP0301H, AP0361H, AP0481H, AP0561H

CN

104

(YE

L)

CN

102

(RE

D)

CN

101

(BLK

)

12

34

51

23

45

12

34

51

23

45

12

34

51

23

45

12

34

56

12

34

51

23

45

12

34

56

64

31

25

64

31

25

31

32

1C

N34

(RE

D)

FS

CN

33(W

HI)

CN

82(B

LU)

54

32

15

43

21

CN

334

(BLU

)

DC

20V

CN

333

(WH

I)C

N68

(BLU

)

CN

304

(GR

Y)

CN

66(W

HI)

CN

44(B

LN)

CN

67(B

LK)

LM1

PM

V

1 21 2

TA

1 21 2

TC

J1 2

1 2T

C2

CN

100

(BR

N)

1 21 2

33

CN

80(G

RN

)P

NL

EX

CT

1 2

CN

73(R

ED

)1 2

Filt

er in

put

(Opt

ion)

(Fan

driv

e)

CN

70(W

HI)

CN

20(B

LU)

1 23

TC

1

12

34

51

23

45

LM2

12

34

5

CN

81(B

LK)

CN

60(W

HI)

CN

32(W

HI)

CN

61(Y

EL)

CN

50(W

HI)

CN

40(B

LU)

T10

12

34

51

21

23

45

61

23

45

12

3

CN

309

(YE

L)

12

31

23

12

12

CN

41(B

LU)

12

31

23

45

6

RY

302

RY

303

1 2 3 1 2 3

1 2 3

1 2 3

1 2

1 2 1 2

3

~+

Fus

eT

6.3A

250V

~

Fus

eT

3.15

A25

0V~

DC

15V

DC

12V

DC

7V

P30

1B

LK

RE

D

WH

I

WH

IR

ED

S(N)

R(L)

Pow

er s

uppl

yS

ingl

e ph

ase

220-

240V

50H

z

2

20V

60H

z

Indo

or u

nit

Ear

th s

crew

DM

FM

Pow

ersu

pply

circ

uit

Mot

or d

rive

circ

uit

Clo

sed

end

conn

ecto

r

CN

01(W

HI)

CN

02(B

LU)

Ada

ptor

for

wire

less

re

mot

e co

ntro

ller

CN

03(R

ED

)

Net

wor

k ad

apto

r (O

ptio

n)1

21

2 12

12

12

12

XY

33

22

11

Wire

d re

mot

e co

ntro

ller

12B

AU

2

12

CN

1(W

HI)

CN

001

(WH

I)

WH

IO

utdo

or u

nit

BLK

WH

IB

LKBLK

BLUBLU

BLK

BLK

TR

WH

I

U1

U2

U1

Net

wor

k ad

apto

r P.

C. b

oard

MC

C-1

401

Flo

w s

elec

tor

unit

eart

h sc

rew

Co

lor

iden

tifi

cati

on

RE

D :

RE

DW

HI

: W

HIT

EY

EL

: Y

ELL

OW

BLU

: B

LUE

BR

N :

BR

OW

N

BLK

: B

LAC

KG

RY

: G

RAY

PN

K :

PIN

KO

RN

: O

RA

NG

EG

RN

: G

RE

EN

Sym

bo

l

FM TA TC

1

TCJ

TC

2

LM1,

LM

2

DM FS

RY

302

PM

V

Par

ts n

ame

Fan

mot

or

Ind

oor

tem

p s

enso

r

Tem

p s

enso

r

Tem

p s

enso

r

Tem

p s

enso

r

Love

r m

otor

Dra

in p

ump

mot

or

Flo

at s

witc

h

Dra

in c

ontr

ol r

elay

Pul

se M

otor

Val

ve

Ind

oo

r co

ntr

ol P

.C.

bo

ard

MC

C-1

402

1.

in

dic

ates

the

ter

min

al b

lock

, the

lett

er in

sid

e

ind

icat

es t

he t

erm

inal

num

ber

.

2. A

dot

ted

line

and

bro

ken

line

ind

icat

e th

e w

iring

on

site

.

3.

in

dic

ates

the

con

trol

P.C

. boa

rd.

Page 99: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

96

CN

104

(YE

L)

CN

102

(RE

D)

CN

101

(BLK

)

54

32

15

43

21

98

76

98

76

FAN

CN

083 (

WH

I)

WH

I

RE

D

DP

(BLU

)C

N06

8

DM

CN

304

(GR

Y)

CN

066

(WH

I)

CN

067

(BLK

)

CN

044

(BR

W)

1 21 2

TA

1 21 2

TC

J1 2

1 2T

C2

CN

100

(BR

W)

1 21 2

33

CN

080

(GR

N)

PN

L

EX

CT

1 2

CN

073

(RE

D)

1 2

Filt

erC

N07

0(W

HI)

CN

081

(BLK

)

CN

060

(WH

I)

Opt

ion

CN

032

(WH

I)C

N07

5(W

HI)

CN

074

(WH

I)

TR

1 2 1 2 3 4 5

1 2

3

TC

1

12

34

56

CN

061

(YE

L)

Fan

driv

e1

23

45

61

23

45

61

23

12

31

23

12

12

12

31

23

12

31

23

45

6

12

34

56

12

34

56

12

34

56

12

34

56

CN

050

(WH

I)C

N04

1(B

LU)

CN

040

(BLU

)

CN

01(W

HI)

CN

02(B

LU)

Net

wor

k ad

apto

r (O

ptio

n)

12

12

34

5

12

12

33 2

11

CN

03(R

ED

)M

CC

-140

1

22

11

RY

004

1 2 3 1 2 1 2

RY

002

RY

006

RY

007

RY

005

12B

AY

XS(

N)R(

L)

U2

12

Rem

ote

cont

rolle

r

CN

1(W

HI)

Pow

er s

uppl

yS

ingl

e ph

ase

220-

240V

50H

z

2

20V

60H

z

Indo

or u

nit

Ear

th s

crew

Out

door

uni

tBLUBLU

BLK

BLK

U1

U2

U1

Flo

w s

elec

tor

unit

eart

h sc

rew

Pow

er s

uppl

yci

rcui

t

CN

01(W

HI)

CN

02(Y

EL)

Sub

P.C

. boa

rdM

CC

-152

0

LM(G

RN

)C

N03

3

LM

12

31

23

FS

(RE

D)

CN

030

PM

V(B

LU)

CN

082

FS

12

31

23

12

31

23

45

64

56

64

36

43

12

51

25

RY

001

TR

Fus

eT

5.0A

250V

~1 2 3

1 2 3

CN

039

(YE

L)

1 2 3

1 2 3

12

12

PM

V

1 21 2

3 43 4

5 65 6

77 9

FM

YEL

BLU

ORN

BLK

HM

LU

L

RC

RE

D

Clo

sed

end

conn

ecto

r

Line

Filt

er

P30

1(B

LK)

11

1-2. 2-way Air Discharge Cassette TypeModel: MMU-AP0071WH, AP0091WH, AP0121WH, AP0151WH, AP0181WH, MMU-AP0241WH, AP0271WH, AP0301WH, AP0481WH

1.

ind

icat

es t

he t

erm

inal

blo

ck, t

he le

tter

insi

de

ind

icat

es t

he t

erm

inal

num

ber

.

2. A

dot

ted

line

and

bro

ken

line

ind

icat

e th

e w

iring

on

site

.

3.

in

dic

ates

the

con

trol

P.C

. boa

rd.

Sym

bo

lFM R

C

LM TR TA

TC1,

TC2,

TCJ

RY

001

RY

002

RY

004

RY

005~

007

FS DM

PM

V

Par

ts n

ame

Fan

mot

or

Run

ning

cap

acito

r

Tran

sfor

mer

Louv

er m

otor

Ind

oor

tem

p s

enso

r

Tem

p s

enso

r

Louv

er c

ontr

ol r

elay

Dra

in c

ontr

ol r

elay

Hea

ter

cont

rol r

elay

Fan

mot

or c

ontr

ol r

elay

Flo

at s

witc

h

Dra

in p

ump

mot

or

Pul

se M

otor

Val

ve

Co

lor

ind

icat

ion

RED

: R

EDW

HI

: WH

ITE

YEL

: Y

ELLO

WB

LU :

BLU

EB

LK

: BLA

CK

GR

Y :

GR

AYP

NK

: P

INK

OR

N :

OR

AN

GE

BR

N :

BR

OW

NG

RN

: G

REE

NIn

do

or

con

tro

l P.C

. b

oar

d

Page 100: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

97

CN

104

(YE

L)

CN

102

(RE

D)

CN

101

(BLK

)

54

32

15

43

21

98

76

98

76

FAN

CN

083(

WH

I)

DP

(BLU

)C

N06

8

DM

CN

304

(GR

Y)

Hea

ter

CN

301

(BLK

)

CN

066

(WH

I)

WH

I

RE

D

BLU

BLU

BLU

CN

067

(BLK

)

1 21 2

TA

TC

J

1 21 2 1 2

CN

100

(BR

W)

1 21 2

33

CN

080

(GR

N)

PN

L

EX

CT

1 2

CN

073

(RE

D)

1 2

Filt

erC

N07

0(W

HI)

CN

081

(BLK

)

CN

060

(WH

I)

Opt

ion

CN

032

(WH

I)C

N07

5(W

HI)

CN

074

(WH

I)

TR

1 2 1 2 3 4 5

1 2

3

TC

1

12

34

56

CN

061

(YE

L)

Fan

driv

e

12

34

56

12

34

56

12

31

23

13

12

12

12

31

23

12

31

23

12

31

23

45

6

CN

050

(WH

I)C

N04

1(B

LU)

CN

040

(BLU

)

12

12

CN

044

(BR

W)

CN

01(W

HI)

CN

02(B

LU)

Net

wor

k ad

apto

r (O

ptio

n)

12

12

34

5

12

12

11

22

21

23 3

1

CN

03(R

ED

)

MC

C-1

401

RY

004

1 2 3 1 2

RY

002

RY

006

RY

007

RY

005

12B

AY

XS(

N)R(

L)U

2

12

Rem

ote

cont

rolle

r

CN

1(W

HI)

Pow

er s

uppl

yS

ingl

e ph

ase

220-

240V

50H

z

2

20V

60H

z

Indo

or u

nit

Ear

th s

crew

Out

door

unit

BLU

BLU

RED

WHI

BLK

BLK

U1

U2

U1

Pow

er s

uppl

yci

rcui

t

Net

wor

k ad

apto

r P.

C. b

oard

LM(G

RN

)C

N03

3

LM

12

31

23

FS

(RE

D)

CN

030

PM

V(B

LU)

CN

082

FS

12

31

23

12

31

23

45

64

56

64

36

43

12

51

25

RY

001

AI-

NE

T

cent

ral c

ontr

ol

term

inal

TR

Fus

eT

5.0A

1 2 3

1 2 3

CN

309

(YE

L)

AC IN

1 2 3

1 2 3

21

21

21

21

PM

V1 2

1 23 4

3 45 6

5 6

FM

YEL

BLU

ORN

BLK

RED

HM

LU

L

RC

Clo

sed

end

conn

ecto

r

12

34

56

12

34

56

12

34

56

12

34

56

CN

01(W

HI)

CN

02(Y

EL)

Sub

P.C

. boa

rdM

CC

-152

0Li

ne F

ilter

Flo

w s

elec

tor

unit

eart

h sc

rew

11

1-3. 1-way Air Discharge Cassette Type (Compact type)Model: MMU-AP0071YH, AP0091YH, AP0121YH

1.

ind

icat

es t

he t

erm

inal

blo

ck, t

he le

tter

insi

de

ind

icat

es t

he t

erm

inal

num

ber

.

2. A

dot

ted

line

and

bro

ken

line

ind

icat

e th

e w

iring

on

site

.

3.

in

dic

ates

the

con

trol

P.C

. boa

rd.

Sym

bo

lFM R

C

TR LM TA

TC1,

TCJ

RY

001

RY

002

RY

004

RY

005~

007

FS DM

PM

V

Par

ts n

ame

Fan

mot

or

Run

ning

cap

acito

r

Pow

er t

rans

form

er

Louv

er m

otor

Ind

oor

tem

p s

enso

r

Tem

p s

enso

r

Flap

mot

or c

ontr

ol r

elay

Dra

in p

ump

con

trol

rel

ay

Hea

ter

cont

rol r

elay

Fan

mot

or c

ontr

ol r

elay

Flo

at s

witc

h

Dra

in p

ump

mot

or

Pul

se M

otor

Val

ve

Co

lor

ind

icat

ion

RED

: R

EDW

HI

: WH

ITE

YEL

: Y

ELLO

WB

LU :

BLU

EB

LK

: BLA

CK

GR

Y :

GR

AYP

NK

: P

INK

OR

N :

OR

AN

GE

BR

N :

BR

OW

NG

RN

: G

REE

N

Ind

oo

r co

ntr

ol P

.C.

bo

ard

Page 101: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

98

53

17 7

9 95

31

RY

007

P30

1

RY

004

(GR

Y)

CN

304

(YE

L)C

N30

9

(BLK

)

BLK

CN

067

FU

SE

T5.

0A 2

50V

~

RY

006

RY

005

H

RE

DB

LKO

RN

BLU

YE

L

ML

UL

31

31

31

31

31

RC

FM

1 2 3

1 3

CN

104

(YE

L)

TA

2121

CN

102

(RE

D)

TC

J

2121

CN

101

(BLK

)

CN

100

(BR

W)

1 3

CN

080

(GR

N)

TC

2

PN

L

EX

CT

21

CN

073

(RE

D)

22 1

FIL

TE

RC

N07

0(W

HI)

CN

081

(BLK

)

21

2121

1122

1122

1122

112

XY2

32

113

112

331

23

45

12

34

56

12

12

34

56

12

34

56

12

34

56

21 43 5

21

TC

1

CN

066

(WH

I)

AC

IN

CN

044

(BR

W)

CN

040

(BLU

)

Out

door

uni

tR

emot

e C

ontr

olle

r

Pow

er s

uppl

ysi

ngle

pha

se22

0-24

0V 5

0Hz

220V

60H

z

Indo

or u

nit

eart

h sc

rew

Clo

sed-

end

conn

ecto

r

Line

Filt

er

CN

01(W

HI)

CN

03(R

ED

)

CN

02(B

LU)

CN

041

(BLU

)C

N05

0(W

HI)

CN

061

(YE

L)C

N03

2(W

HI)

FAN

DR

IVE

OP

TIO

N

CN

060

(WH

I)

EM

G

BLU

BLU

BLK

BLK

RC

TR

U1

U1

U2U

2A

B

Net

wo

rk A

dap

ter

(Op

tio

n)

MC

C-1

401

1122

CN

1

1133

CN

074

(WH

I)

CN

075

(WH

I)

Pow

er s

uppl

yci

rcui

t

TR

1133

CN

068

(BLU

)

FAN

CN

083

(WH

I)

RY

002

DM

DM

1133

CN

033

(GR

N)

RY

001

LM

CN

082

(BLU

)

PM

V

LM

1133

CN

030

(RE

D)

FS

FS

1122

12

34

56

12

34

56

12

34

56

12

34

56

PM

V31

321

654

654

R(L)

S(N)

12

34

56

12

34

56

12

34

56

12

34

56

CN

01(W

HI)

CN

02(Y

EL)

Sub

P.C

. boa

rdM

CC

-152

0

Flo

w s

elec

tor

unit

eart

h sc

rew

1.

Ind

icat

es t

he t

erm

inal

bol

ock,

the

lett

er in

sid

e in

dic

ates

the

ter

min

al n

umb

er.

2. A

do

tted

line

and

bro

ken

line

ind

icat

e

t

he w

iring

on

site

.

3.

in

dic

ates

the

con

trol

P.C

. boa

rd.

11

Model: MMU-AP0151SH, AP0181SH, AP0241SH

Co

lor

ind

icat

ion

RED

: R

EDW

HI

: WH

ITE

YEL

: Y

ELLO

WB

LU :

BLU

EB

LK

: BLA

CK

GR

Y :

GR

AYP

NK

: P

INK

OR

N :

OR

AN

GE

BR

N :

BR

OW

NG

RN

: G

REE

N

Co

ntr

ol P

.C. b

oar

dfo

r In

do

or

un

itM

CC

-140

3

Sym

bo

l

FM RC

TR LM TA TC1,

TC2,

TCJ

RY

001

RY

002

RY

005~

007

FS DM

PM

V

Par

ts n

ame

Fan

mot

or

Run

ning

cap

acito

r

Tran

sfor

mer

Love

r m

otor

Ind

oor

tem

p s

enso

r

Tem

p s

enso

r

Louv

er c

ontr

ol r

elay

Dra

in c

ontr

ol r

elay

Fan

mot

or c

ontr

ol r

elay

Flo

at s

witc

h

Dra

in p

ump

mot

or

Pul

se m

otor

val

ve

Page 102: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

99

11

1-4. Concealed Duct Standard TypeModel: MMD-AP0071BH, AP0091BH, AP0121BH, AP0151BH, AP0181BH, AP0241BH MMD-AP0271BH, AP0301BH, AP0361BH, AP0481BH, AP0561BH

CN

104

(YE

L)

CN

102

(RE

D)

CN

101

(BLK

)

12

34

51

23

45

61

23

45

6

64

31

25

64

31

25

31

32

1C

N34

(RE

D)

FS

CN

33(W

HI)

CN

82(B

LU)

DC

20V

CN

68(B

LU)

CN

304

(GR

Y)

CN

66(W

HI)

CN

44(B

RW

)

CN

67(B

LK)

Rea

ctor

PM

V

1 21 2

TA

1 21 2

TC

J1 2

1 2T

C2

CN

100

(BR

N)

1 21 2

33

CN

80(G

RN

)P

NL

EX

CT

1 2

CN

73(R

ED

)1 2

(Sig

nal o

utpu

t)(F

an d

rive)

CN

70(W

HI)

CN

20(B

LU)

1 23

TC

1

12

34

5

CN

81(B

LK)

CN

60(W

HI)

CN

32(W

HI)

CN

61(Y

EL)

CN

50(W

HI)

Ada

puto

r fo

r w

ired

rem

ote

cont

rolle

r

CN

309

(YE

L)C

N41

(BLU

)C

N40

(BLU

)

T10

12

34

51

21

23

45

61

23

45

12

31

23

12

31

23

12

12

12

3

13

12

2

45

6

12

12

RY

302

1 2 3 1 2 3

1 2 3

1 2 3

1 2

1 2 1 2

3

~+

Fus

eT

6.3A

250V

~

Fus

eT

3.15

A

250V

~D

C15

VD

C12

VD

C7V

P30

1B

LK

RE

D

WH

I

WH

IW

HI

RE

D

Wire

d re

mot

e co

ntro

ller

12B

A

S(N)

R(L)

U2

12

CN

1(W

HI)

CN

001

(WH

I)

Indo

or u

nit p

ower

sup

ply

Sin

gle

phas

e 22

0-24

0V 5

0Hz

220

V 6

0Hz

Indo

or u

nit

Ear

th s

crew

WH

I

Out

door

uni

t

BLK

WH

IB

LK

BLK

BLUBLU

BLK

BLK

TR

WH

I

U1

U2

U1

DM

Pow

ersu

pply

circ

uit

Mot

or d

rive

circ

uit

CN

01(W

HI)

CN

02(B

LU)

CN

03(R

ED

)

Net

wor

k ad

apto

r (O

ptio

n)1

21

2

12

12

XY

33

22

11

Net

wor

k ad

apto

r P.

C. b

oard

Clo

sed

end

conn

ecto

r

CN

333

(WH

I)

CN

334

(WH

I)1122

344

551

35

13

12

31

23

5

11

5 45 4

FM

Flo

w s

elec

tor

unit

eart

h sc

rew

Ind

oo

r co

ntr

ol P

.C.

bo

ard

Co

lor

iden

tifi

cati

on

RE

D :

RE

DW

HI

: W

HIT

EY

EL

: Y

ELL

OW

BLU

: B

LUE

BR

N :

BR

OW

N

BLK

: B

LAC

KG

RY

: G

RAY

PN

K :

PIN

KO

RN

: O

RA

NG

EG

RN

: G

RE

EN

Sym

bo

lFM TA

TC1,

TC2,

TCJ

DM FS

RY

302

PM

V

Par

ts n

ame

Fan

mot

or

Ind

oor

tem

p s

enso

r

Ind

oor

tem

p s

enso

r

Dra

in p

ump

mot

or

Flo

at s

witc

h

Dra

in p

ump

con

trol

rel

ay

Pul

se M

otor

Val

ve

1.

ind

icat

es t

he t

erm

inal

blo

ck, t

he le

tter

insi

de

ind

icat

es t

he t

erm

inal

num

ber

.

2. A

dot

ted

line

and

bro

ken

line

ind

icat

e th

e w

iring

on

site

.

3.

in

dic

ates

the

con

trol

P.C

. boa

rd.

Page 103: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

100

TC

1T

C2

CN

080

(GR

N)

CN

101

(BLK

)

CN

073

(RE

D)

CN

070

(WH

I)

42

54

32

19

87

69

87

6FA

NC

N08

3(W

HI)

DP

(BLU

)C

N06

8

DP

CN

304

(GR

Y)

CN

066

(WH

I)

CN

067

(BLK

)

(BLK

)P

NL

EX

CT

1 2 1 2

Filt

er

CN

082

(BLU

)

CN

060

(WH

I)

Opt

ion

CN

032

(WH

I)C

N07

5(W

HI)

CN

074

(WH

I)

TRT10

1 2 6 5 4 3 2 1

6 5 4 3 2 1

5 2 1 3 4 6

5 2 1 3 4 6

CN

081

(BLK

)

1 2 3 4 53

12

34

56

CN

061

(YE

L)

Fan

driv

e

12

34

56

12

34

56

12

31

23

13

12

12

12

12

31

23

12

31

23

45

6

CN

050

(WH

I)C

N04

1(B

LU)

CN

040

(BLU

)C

N04

4(B

RW

)

12

12

34

5

RY

004

P30

1

1 2 3 1 2

RY

002

RY

006

RY

007

RY

005

12B

A

S(N)

R(L)

U2

12

Rem

ote

cont

rolle

r

CN

1(W

HI)

Pow

er s

uppl

yS

ingl

e ph

ase

220-

240V

50H

z

2

20V

60H

z

Indo

or u

nit

Ear

th s

crew

Out

door

uni

tU1

U2

U1

Pow

ersu

pply

circ

uit

LM(G

RN

)C

N03

31

23

12

3C

N10

0(B

RN

)1

23

12

31

23

12

31

21

2

TC

J

CN

102

(RE

D)

12

12

TA

CN

104

(YE

L)F

SC

N03

0(R

ED

)

12

12

RY

001

TR

OC

EM

GR

C

Fus

eT

5.0A

T10

A,2

50V

~1 2 3

1 2 3

CN

309

(YE

L)

1 2 3

1 2 3

RE

DW

HI

HM

LU

L

PM

V

(Opt

ion)

CN

01(W

HI)

CN

02(B

LU)

WH

I

WHIREDGRY

WHIRED

BLU

ORN

BLK

BRN

GRY

YE

LRE

DRE

DR

ED

F

RE

D

WH

I

43F

1

6 4

CN

03(R

ED

)

MC

C-1

401

Net

wor

k ad

apto

r (O

ptio

n)

12

12

12

12

XY

33 2

11

43F

1

Spa

rkki

ller

87

43F

1

5 3

12

34

12

34

F1F2

F3F4

RC

FM

WH

I

BLK

BLU

OR

NB

RN

GR

YR

ED

49F

Clo

sed

end

conn

ecto

r

Clo

sed

end

conn

ecto

r

Wire

d fo

r M

MD

-AP

0481

onl

y(B

RN

Wire

)

Mot

or o

ver

heat

ing

prot

ectio

n sw

itch

12

34

56

12

34

56

12

34

56

12

34

56

CN

01(W

HI)

CN

02(Y

EL)

Sub

P.C

. boa

rdM

CC

-152

0F

low

sel

ecto

r un

it ea

rth

scre

w

11

1-5. Concealed Duct High Static Pressure TypeModel: MMD-AP0181H, AP0241H, AP0271H, AP0361H, AP0481H

Ind

oo

r co

ntr

ol P

.C.

bo

ard

Co

lor

ind

icat

ion

RED

: R

EDW

HI

: WH

ITE

YEL

: Y

ELLO

WB

LU :

BLU

EB

LK

: BLA

CK

GR

Y :

GR

AYP

NK

: P

INK

OR

N :

OR

AN

GE

BR

N :

BR

OW

NG

RN

: G

REE

N

Sym

bo

lFM R

C

TR TA

TC1,

TC2,

TCJ

RY

005~

007

RY

001

RY

002

PM

V

F

43F

1

DM FS

Par

ts n

ame

Fan

mot

or

Run

ning

cap

acito

r

Tran

sfor

mer

Ind

oor

tem

p s

enso

r

Tem

p s

enso

r

Fan

mot

or c

ontr

ol r

elay

Flap

mot

or c

ontr

ol r

elay

Dra

in c

ontr

ol r

elay

Pul

se M

otor

Val

ve

Fus

e

Fan

mot

or c

ontr

ol r

elay

Dra

in p

ump

mot

or

Flo

at s

witc

h

Sol

dse

para

tely

1.

ind

icat

es t

he t

erm

inal

blo

ck,

the

lett

er in

sid

e in

dic

ates

the

ter

min

al n

umb

er.

2.

A d

otte

d li

ne a

nd b

roke

n lin

e in

dic

ate

the

wiri

ng o

n si

te.

3.

i

ndic

ates

the

con

trol

P.C

. boa

rd.

4.

Whe

n in

stal

ling

a d

rain

pum

p, R

emo

ve C

N03

0 co

nnec

tor

and

co

nnec

t flo

at s

wit

ch.

5.

A p

art

is c

onne

cted

to

the

term

inal

blo

ck.

Whe

n a

chan

ge

is r

equi

red

due

to

the

outs

ide

stat

ic p

ress

ure

at

site

,

c

heck

the

ter

min

al N

o. a

nd le

ad c

olou

r of

the

fan

mot

or in

the

bel

ow d

iagr

am

a

nd t

hen

chan

ge t

he le

ad w

ire a

s in

dic

ated

by

the

arro

w m

ark

(

),

6.

Pay

att

entio

n w

hen

chan

gin

g s

tatic

pre

ssur

e b

ecau

se t

he o

utsi

de

stat

ic p

ress

ure

o

f H

tap

in 5

0 or

60H

z.

Page 104: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

101

CN

080

(GR

N)

PN

L

EX

CT

2 31 2 23 34 45 561 12

22

33

34

44

55

56

66

1

11

CN

073

(RE

D)

21

FIL

TE

RC

N07

0(W

HI)

CN

081

(BLK

)

CN

082

(BLU

)

21

112

33

CN

100

(BR

W)

1122

CN

101

(BLK

)C

N03

0(R

ED

)

TC

1T

C2

1122

CN

102

(RE

D)

TC

J

1122

CN

104

(YE

L)

TA

PM

V

1133

FS

53

17 7

9 95

31

RY

007

P30

1(B

LK)

RE

DR

ED

Spa

rk K

iller

WHI

WHI

RE

D

YE

L

BLK

WH

IG

RY

RE

D

BLU

OR

N

RY

004

(GR

Y)

CN

304

(YE

L)C

N30

9

FU

SE

T5.

0A 2

50V

~

RY

006

RY

005

HM

LU

L

31

31

31

31

31

6

8

7

21

1122

12

1122

112

XY2

32

113

112

331

23

45

12

34

56

12

12

34

56

12

34

56

12

34

56

CN

066

(WH

I)

CN

067

(BLK

)

AC

INR

ED

WH

I

CN

044

(BR

W)

EM

G

Rem

ote

Con

trol

ler

Pow

er s

uppl

ysi

ngle

pha

se22

0-24

0V 5

0Hz

220V

60H

z

Indo

or u

nit

eart

h sc

rew

Clo

sed-

end

conn

ecto

r

Clo

sed-

end

conn

ecto

r

Line

Filt

er

WH

I

RE

D

RE

D

WH

I

RED

WHI

WHI

CN

01(W

HI)

CN

03(R

ED

)

CN

02(B

LU)

CN

040

(BLU

)C

N04

1(B

LU)

CN

050

(WH

I)C

N06

1(Y

EL)

CN

032

(WH

I)

FAN

DR

IVE

OP

TIO

N

CN

060

(WH

I)

BLU

BLU

BLK

BLK

RC

CO

TR

U1

U2

AB

Net

wo

rk A

dap

ter

(Op

tio

n)

MC

C-1

401

1122

CN

1

1133

CN

074

(WH

I)

CN

075

(WH

I)

Pow

er s

uppl

yci

rcui

t

TR

DP

CN

068

(BLU

)

LMC

N03

3(G

RN

)

FAN

CN

083

(WH

I)

RY00

2

13

RY00

1

R(L)

S(N)

1133

DM

(Opt

ion)

43F2

43F1

49F

F1

T10

.0A

, 250

V~

T10

.0A

, 250

V~

T10

.0A

, 250

V~

RE

D

F2

RE

D

F3

RE

D

7 8

5 343

F1

7 8

5 343

F2

FAN

3

4P(R

ED

)

RCO

RW

RE

D

RE

D

OR

W

OR

W

YEL

YEL

WHIREDGRY

WHIREDGRY

BLU

ORN

12

34

12

34

FM3

F1

F2

F3

F4

6 443

F2

FAN

2

4P(B

LU)

RC

YEL

WHIREDGRY

WHIREDGRY

BLU

ORN

12

34

12

34

FM2

F1

F2

F3

F4

6 443

F1

FAN

1

4P(W

HI)

RC

YEL

WHIREDGRY

WHIREDGRY

BLU

ORN

12

34

12

34

FM1

F1

F2

F3

F4

5

Mot

or o

ver

heat

ing

prot

ectio

n sw

itch

Fan

mot

or in

side

wiri

ng d

iagr

am

U1

U2

Out

door

uni

t

12

34

56

12

34

56

12

34

56

12

34

56

CN

01(Y

EL)

CN

02(Y

EL)

Sub

P.C

. boa

rdM

CC

-152

0

S.K

S.K

11

Sym

bo

lFM R

C

TR TA

TC1,

TC2,

TC3

RY

005~

007

RY

001

RY

002

PM

V

F1~

3

43F1

,43F

2

DM FS

Par

ts n

ame

Fan

mot

or

Run

ning

cap

acito

r

Tran

sfor

mer

Ind

oor

tem

p s

enso

r

Tem

p s

enso

r

Fan

mot

or c

ontr

ol r

elay

Louv

er c

ontr

ol r

elay

Dra

in c

ontr

ol r

elay

Pul

se m

otor

val

ve

Fuse

for

fan

mot

or

Fan

mot

or c

ontr

ol r

elay

Dra

in p

ump

mot

or

Flo

at s

witc

hS

old

sep

arat

ely

Co

lor

ind

icat

ion

RED

: R

EDW

HI

: WH

ITE

YEL

: Y

ELLO

WB

LU :

BLU

EB

LK

: BLA

CK

GR

Y :

GR

AYP

NK

: P

INK

OR

N :

OR

AN

GE

BR

N :

BR

OW

NG

RN

: G

REE

N

1.

Ind

icat

es t

he t

erm

inal

bol

ock,

L

ette

r on

the

insi

de

ind

icat

es t

he t

erm

inal

num

ber

.2.

A d

otte

d li

ne a

nd b

roke

n lin

e in

dic

ate

t

he w

iring

on

site

.3.

ind

icat

e th

e co

ntro

l p.c

. boa

rd.

4. W

hen

fittin

g a

dra

in p

ump

rem

ove

CN

030

conn

ecto

r an

d c

onn

ect

float

sw

itch.

5. A

Pos

ition

is c

onne

cted

to

the

term

inal

blo

ck w

hen

ther

e is

a

chan

ge t

o st

atic

pre

ssur

e. c

hang

e th

e le

ad w

ire o

f ar

row

pos

ition

aft

er c

heck

ing

the

term

inal

num

ber

as

per

fig

ure

a

nd t

he le

ad w

ire's

che

ckin

g fa

n m

otor

.6.

Whe

n se

ttin

g to

the

hig

h ta

p, t

ake

care

as

the

stat

ic p

ress

ures

a

re d

iffer

ent

at50

Hz

and

60H

z.

Ter

min

alN

o.

Fan

mo

tor

wir

ing

Sta

tic

pre

ssur

eP

a (m

mA

g)

No

te

F1 F2 F3

YE

LB

LUO

RN

69(7

)13

7(14

)19

6(20

)S

ettin

g fr

om f

acto

ry

Con

trol

P.C

. boa

rdfo

r In

doo

r un

itM

CC

-140

3

Model: MMD-AP0721H, AP0961H

Co

ntro

l P.C

. bo

ard

for

Ind

oo

r un

itM

CC

-140

3

Page 105: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

102

CN

104

(YE

L)

CN

102

(RE

D)

CN

101

(BLK

)

12

34

51

23

45

12

34

51

1 1

2

2 2

33 3

4

4 4

5

5 5 6 6

6 6

12

34

51

23

45

13

12

3C

N34

(RE

D)

FS

CN

33(W

HI)

CN

82(B

LU)

54

15

43

21

CN

334

(WH

I)

DC

20V

CN

333

(WH

I)C

N68

(BLU

)

CN

304

(GR

Y)

CN

66(W

HI)

CN

67(B

LK)

1 21 2

TA

1 21 2

TC

J1 2

1 2T

C2

CN

80(G

RN

)P

NL

EX

CT

1 2

CN

73(R

ED

)1 2

FIL

TE

R

Opt

ion

GR

LFa

ndriv

e

CN

70(W

HI)

CN

20(B

LU)

1 23

12

34

51

23

45

LM

12

34

5

CN

60(W

HI)

CN

32(W

HI)

CN

61(Y

EL)

CN

50(W

HI)

Adp

ter

for

wire

less

rem

ote

cont

rolle

r

CN

309

(YE

L)

CN

41(B

LU)

T10

12

12

34

56

CN

81(B

LK)

12

34

51

23

45

12

31

23

12

3

CN

40(B

LU)

45

6

12

12

RY

302

1 2 3 1 2 3

1 2 3

1 2 3

1 2

1 21 2

1 21

33

1 2

3

RY

303

~+

Fus

eT

6.3A

250V

~

Fus

eT

3.15

A

DC

15V

DC

12V

DC

7V

P30

1B

LK

RE

D WH

I Clo

sed

end

term

inal

RED

WHI

Wire

d re

mot

e co

ntro

ller

Out

door

uni

t1

2BA

U2

U1

U2

U1

12

CN

1(W

HI)

CN

001

(WH

I)

Indo

or u

nit

Ear

th s

crew

WH

IB

LKB

LKW

HI

BLK

TR

BLU

WH

I

BLU BLK

BLK

DM

FM

Pow

ersu

pply

circ

uit

Mot

or d

rive

circ

uit

CN

01(W

HI)

CN

02(B

LU)

CN

03(R

ED

)

Net

wor

k ad

apto

r (O

ptio

n)1

21

2

12

12

XY

33

22

11

Net

wor

k ad

apto

r P.

C. b

oard

S(N)

R(L)

Pow

er s

uppl

ysi

ngle

pha

se20

0-24

0V 5

0Hz

200

V 6

0Hz

PM

V

Flo

w s

elec

tor

unit

eart

h sc

rew

CN

100

(BR

W)

1 21 2

33

TC

1

11

Co

lor

iden

tifi

cati

on

RE

D :

RE

DW

HI

: W

HIT

EY

EL

: Y

ELL

OW

BLU

: B

LUE

BR

N :

BR

OW

N

BLK

: B

LAC

KG

RY

: G

RAY

PN

K :

PIN

KO

RN

: O

RA

NG

EG

RN

: G

RE

EN

Sym

bo

lFM TA

TC1,

TC2,

TCJ

LM

RY

302

DM FS

Sol

dse

par

atel

y

Par

ts n

ame

Fan

mot

or

Ind

oor

tem

p s

enso

r

Tem

p s

enso

r

Louv

er m

otor

Dra

in c

ontr

ol r

elay

Dra

in p

ump

mot

or

Flo

at s

witc

h

1-6. Under Ceiling TypeModel: MMC-AP0151H, AP0181H, AP0241H, AP0271H, AP0361H, AP0481H

Ind

oo

r co

ntr

ol P

.C.

bo

ard

1.

ind

icat

es t

he t

erm

inal

blo

ck, t

he le

tter

insi

de

ind

icat

es t

he t

erm

inal

num

ber

.

2. A

dot

ted

line

and

bro

ken

line

ind

icat

e th

e w

iring

on

site

.

3.

in

dic

ates

the

con

trol

P.C

. boa

rd.

Page 106: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

103

CN

080

(GR

N)

EX

CT

2 31

CN

68(B

LU)

31

CN

304

(GR

Y)31

31

CN

67(B

LK)

CN

66(W

HI)31 21

31

CN

103

(GR

N)

21

CN

73(R

ED

)21

CN

70(W

HI)

21

112

31

23

45

3

CN

100

(BR

W)

CN

101

(BLK

)C

N34

(RE

D)

CN

33(W

HI)

12

34

5

CN

20(B

LU)

12

34

5

CN

81(B

LK)

12

34

56

CN

60(W

HI)

12

34

56

CN

61(Y

EL)

12

31

31

31

21

21

23

13

45

CN

50(W

HI)

CN

41(B

LU)

CN

40(B

LU)

GR

Y

BLU

BLU

BLK

BLK

BLK

WH

I

GR

Y

CN

309

(YE

L)O

ptio

n

12

CN

32(W

HI)

Fand

rive

CN

82(B

LU)

Mot

or d

rive

circ

uit

CN

333

(WH

I)C

N33

4(W

HI)

TC

1T

C2

CN

102

(RE

D)

TC

J

2121

2121

2121

CN

104

(YE

L)

TA

1133

12

34

56

111

23

45

6

12

34

56

12

34

56

223

4455

13

51

3

12

31

23

5

PM

V1

1

5 45 4

LM

P30

1B

LK

RY

302

FU

SE

T6.

3A 2

50V

~

RY

303

1122

1122

32

113

CN

01(W

HI)

CN

03(R

ED

)

CN

02(B

LU)

TR

1122

Net

wo

rk A

dap

ter

(Op

tio

n)

MC

C-1

401

U1

U2

U1

U2

AB

XY

CN

1(W

HI)

WH

IB

LK

Wire

d re

mot

eco

ntro

ller

Out

door

unit

1122

CN

001

(WH

I)

WH

IB

LK

Ada

pter

for

wire

less

rem

ote

cont

rolle

r

Pow

er s

uppl

ysi

ngle

pha

se22

0-24

0V 5

0Hz

220V

60H

z

Indo

or u

nit

Ear

th s

crew

Clo

sed-

end

conn

ecto

r

RE

D

WH

I

R(L)

S(N)

FM

FU

SE

T3.

15A

250

V~

Pow

ersu

pply

circ

uit

DC

20V

DC

15V

DC

12V

DC

7V

Flo

w s

elec

tor

unit

eart

h sc

rewR

ED

WH

I

11

1-7. High Wall TypeModel: MMK-AP0071H, AP0091H, AP0121H, AP0151H, AP0181H, AP0241H

1.

Ind

icat

es t

he t

erm

inal

bol

ock,

the

lett

er in

sid

e in

dic

ates

the

ter

min

al n

umb

er.

2. A

do

tted

line

and

bro

ken

line

ind

icat

e

t

he w

iring

on

site

.

3.

in

dic

ates

the

con

trol

P.C

. boa

rd.

Sym

bo

l

FM TA TC1,

TC2,

TCJ

PM

V

LM RY

303

Par

ts n

ame

Fan

mot

or

Ind

oor

tem

p s

enso

r

Tem

p s

enso

r

Pul

se m

otor

val

ve

Love

r m

otor

Louv

er c

ontr

ol r

elay

Co

ntr

ol P

.C.

bo

ard

for

Ind

oo

r u

nit

MC

C-1

402

Co

lor

ind

icat

ion

RED

: R

EDW

HI

: WH

ITE

YEL

: Y

ELLO

WB

LU :

BLU

EB

LK

: BLA

CK

GR

Y :

GR

AYP

NK

: P

INK

OR

N :

OR

AN

GE

BR

N :

BR

OW

NG

RN

: G

REE

N

Page 107: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

104

53

17 7

9 95

31

RY

007

P30

1(B

LK)

RY

004

(GR

Y)

CN

304

(YE

L)C

N30

9

FU

SE

T5.

0A 2

50V

~

RY

006

RY

005

H

RE

DB

LKO

RN

BLU

YE

L

ML

UL

31

31

31

31

31

31

RC

FM

CN

104

(YE

L)

TA

2121

CN

102

(RE

D)

TC

J

2121

CN

101

(BLK

)

CN

100

(BR

N)

1 3

CN

080

(GR

N)

TC

2

PN

L

EX

CT

21

CN

073

(RE

D)

22 1 32 4 51

FIL

TE

RC

N07

0(W

HI)

CN

081

(BLK

)

21

2121

1122

1122

112

XY2

32

113

112

331

23

45

12

34

56

12

12

34

56

12

34

56

12

34

56

12

34

56

12

34

56

12

34

56

12

34

56

21

TC

1

2121

CN

066

(WH

I)

CN

067

(BLK

)

AC

INR

ED

WH

I

CN

040

(BLU

)

Out

door

uni

tR

emot

e C

ontr

olle

r

Pow

er s

uppl

ysi

ngle

pha

se22

0-24

0V 5

0Hz

220V

60H

z

Indo

or u

nit

eart

h sc

rew

Clo

sed-

end

conn

ecto

r

Line

Filt

er

RE

D

WH

I

CN

01(W

HI)

CN

03(R

ED

)

CN

02(B

LU)

CN

041

(BLU

)C

N05

0(W

HI)

CN

061

(YE

L)

T10

CN

032

(WH

I)

FAN

DR

IVE

OP

TIO

N

CN

060

(WH

I)

BLU

BLU

BLK

BLK

RC

TR

U1

U1

U2U

2A

B

Net

wo

rk A

dap

ter

(Op

tio

n)

MC

C-1

401

1122

CN

1

1133

CN

074

(WH

I)

CN

075

(WH

I)

Pow

er s

uppl

yci

rcui

t

TR

13

CN

068

(BLU

)

FAN

CN

083

(WH

I)

RY

002

DP

13

CN

033

(GR

N)

RY

001LM

CN

082

(BLU

)

PM

V

112

33C

N03

0(R

ED

)

FS

12

34

56

12

34

56

12

34

56

12

34

56

PM

V32

32

654

654

R(L)

S(N)

CN

01(W

HI)

CN

02(Y

EL)

Sub

P.C

. boa

rdM

CC

-152

0F

low

sel

ecto

r un

it ea

rth

scre

w

11

1-8. Floor Standing Cabinet TypeModel: MML-AP0071H, AP0091H, AP0121H, AP0151H, AP0181H, AP0241H

Co

lor

ind

icat

ion

RED

: R

EDW

HI

: WH

ITE

YEL

: Y

ELLO

WB

LU :

BLU

EB

LK

: BLA

CK

GR

Y :

GR

AYP

NK

: P

INK

OR

N :

OR

AN

GE

BR

N :

BR

OW

NG

RN

: G

REE

N

Sym

bo

l

FM RC

TR TA TC1,

TC2,

TCJ

RY

001

RY

002

RY

004

RY

005~

007

PM

V

Par

ts n

ame

Fan

mot

or

Run

ning

cap

acito

r

Tran

sfor

mer

Ind

oor

tem

p s

enso

r

Tem

p s

enso

r

Louv

er c

ontr

ol r

elay

Dra

in c

ontr

ol r

elay

Hea

ter

cont

rol r

elay

Fan

mot

or c

ontr

ol r

elay

Pul

se m

otor

val

ve

Co

ntr

ol P

.C.

bo

ard

for

Ind

oo

r u

nit

MC

C-1

403

1.

in

dic

ates

the

ter

min

al b

lock

.

the

lett

er in

sid

e in

dic

ates

the

ter

min

al n

umb

er.

2. A

dot

ted

line

and

bro

ken

line

ind

icat

e

the

wiri

ng o

n si

te.

3.

Ind

icat

es t

he c

ontr

ol p

.c. b

oard

.

Page 108: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

105

GR

N

53

17 7

9 95

31

RY

007

R30

1(B

LK)

RY

004

(GR

Y)

CN

304

(YE

L)C

N30

9

(BLK

)C

N06

7

FU

SE

T5.

0A 2

50V

~

RY

006

RY

005

H

RE

DB

LKO

RN

BLU

YE

L

ML

UL

31

31

31

31

31

RC

WHI

1 3

1 3

CN

104

(YE

L)

TA

2121

CN

102

(RE

D)

TC

J

2121

CN

101

(BLK

)

CN

100

(BR

W)

1 3

CN

080

(GR

N)

TC

2

PN

L

EX

CT

21

CN

073

(RE

D)

22 1

FIL

TE

RC

N07

0(W

HI)

CN

081

(BLK

)

21

21

1122

1122

1122

22

32

11

11

3

112

331

23

45

12

34

56

12

12

34

56

12

34

56

12

34

56

12

34

56

12

34

56

12

34

56

12

34

56

21 43 5

2

2

1

TC

1

AC

IN

CN

044

(BR

W)

21C

N06

6(W

HI) C

N04

0(B

LU)

Out

door

uni

t Rem

ote

Con

trol

ler

Pow

er s

uppl

ysi

ngle

pha

se22

0-24

0V 5

0Hz

220V

60H

z

Indo

or u

nit

eart

h sc

rew

Clo

sed-

end

conn

ecto

r

CN

01(W

HI)

CN

03(R

ED

)

CN

02(B

LU)

CN

03(R

ED

)

CN

041

(BLU

)C

N05

0(W

HI)

CN

061

(YE

L)C

N03

2(W

HI)

FAN

DR

IVE

OP

TIO

N

CN

060

(WH

I)

EM

G

TR

RE

D

RED

WHI

WH

I

U1

U2

U1

U2

AB

XY

Net

wo

rk

adap

ter

(Op

tio

n)

MC

C-1

401

For

AP

0071

BH

,AP

0091

BH

,AP

0121

BH

1122

CN

1

1133

CN

074

(WH

I)

CN

075

(WH

I)

Pow

er s

uppl

yci

rcui

t

TR

1133

CN

068

(BLU

)

FAN

CN

083

(WH

I)

RY

002

1133

112

33C

N03

3(G

RN

)

RY

001

CN

082

(BLU

)C

N03

0(R

ED

)

PM

V1

23

45

61

23

45

6

12

34

56

12

34

56

PM

V

RE

D

4242

365

365

R(L)

S(N)

FM

GR

N

53

17 7

9 95

31

RE

DB

LKO

RN

BLU

YE

LFA

NC

N08

3(W

HI)

RE

DW

HI

231

231

654

654

RC

FM

CN

01(W

HI)

CN

02(Y

EL)

Sub

P.C

. boa

rdM

CC

-152

0

Flo

w s

elec

tor

unit

eart

h sc

rew

11

1-9. Floor Standing Concealed TypeModel: MML-AP0071BH, AP0091BH, AP0121BH, AP0151BH, AP0181BH, AP0241BH

Sym

bo

l

FM RC

TR TA TC1,

TC2,

TCJ

RY

001

RY

002

RY

004

RY

005~

007

PM

V

Par

ts n

ame

Fan

mot

or

Run

ning

cap

acito

r

Tran

sfor

mer

Ind

oor

tem

p s

enso

r

Tem

p s

enso

r

Louv

er c

ontr

ol r

elay

Dra

in c

ontr

ol r

elay

Hea

ter

cont

rol r

elay

Fan

mot

or c

ontr

ol r

elay

Pul

se m

otor

val

ve

Co

lor

ind

icat

ion

RED

: R

EDW

HI

: WH

ITE

YEL

: Y

ELLO

WB

LU :

BLU

EB

LK

: BLA

CK

GR

Y :

GR

AYP

NK

: P

INK

OR

N :

OR

AN

GE

BR

N :

BR

OW

NG

RN

: G

REE

N

Co

ntr

ol P

.C. b

oar

dfo

r u

nd

oo

r u

nit

MC

C-1

403

1.

in

dic

ates

the

ter

min

al b

lock

.

the

lett

er in

sid

e in

dic

ates

the

ter

min

al n

umb

er.

2. A

dot

ted

line

and

bro

ken

line

ind

icat

e

the

wiri

ng o

n si

te.

3.

Ind

icat

es t

he c

ontr

ol p

.c. b

oard

.

Page 109: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

106

.

53

17 7

9 95

31

RY

007

P30

1(B

LK)

RY

004

(GR

Y)

CN

304

(YE

L)C

N30

9

(BLK

)C

N06

7

FU

SE

T5.

0A 2

50V

~

RY

006

RY

005

H

RE

DB

LKO

RN

BLU

YE

L

ML

UL

31

31

31

31

31

RC

BR

W

FM

1 3

1 3

CN

104

(YE

L)

TA

2121

CN

102

(RE

D)

TC

J

2121

CN

101

(BLK

)

CN

100

(BR

W)

1 3

CN

080

(GR

N)

TC

2

PN

L

EX

CT

21

CN

073

(RE

D)

22 1

FIL

TE

RC

N07

0(W

HI)

CN

081

(BLK

)

21

2121

1122

1122

1122

112

XY2

32

113

112

331

23

45

12

34

56

12

12

34

56

12

34

56

12

34

56

21 43 5

21

TC

1

CN

066

(WH

I)

AC

IN

CN

044

(BR

W)

CN

040

(BLU

)

Out

door

uni

tR

emot

e C

ontr

olle

r

Pow

er s

uppl

ysi

ngle

pha

se22

0-24

0V 5

0Hz

220V

60H

z

Indo

or u

nit

eart

h sc

rew

Clo

sed-

end

conn

ecto

r

Line

Filt

er

CN

01(W

HI)

CN

03(R

ED

)

CN

02(B

LU)

CN

041

(BLU

)C

N05

0(W

HI)

CN

061

(YE

L)C

N03

2(W

HI)

FAN

DR

IVE

OP

TIO

N

CN

060

(WH

I)

EM

G

BLU

BLU

RED

WHI

BLK

BLK

RC

TR

U1

U1

U2U

2A

B

Net

wo

rk A

dap

ter

(Op

tio

n)

MC

C-1

401

1122

CN

1

1133

CN

074

(WH

I)

CN

075

(WH

I)

Pow

er s

uppl

yci

rcui

t

TR

13

CN

068

(BLU

)

FAN

CN

083

(WH

I)

RY

002

DP

1133

CN

033

(GR

N)

RY

001

LM

CN

082

(BLU

)

PM

V

LM

112

33C

N03

0(R

ED

)

FS

2211

12

34

56

12

34

56

12

34

56

12

34

56

PM

V

R(L)

S(N)

31

31

654

654

787

12

34

56

12

34

56

12

34

56

12

34

56

CN

01(W

HI)

CN

02(Y

EL)

Sub

P.C

. boa

rdM

CC

-152

0F

low

sel

ecto

r un

it ea

rth

scre

w

11

1-10. Floor Standing TypeModel: MMF-AP0151H, AP0181H, AP0241H, AP0271H, AP0361H, AP0481H, AP0561H

Co

lor

ind

icat

ion

RED

: R

EDW

HI

: WH

ITE

YEL

: Y

ELLO

WB

LU :

BLU

EB

LK

: BLA

CK

GR

Y :

GR

AYP

NK

: P

INK

OR

N :

OR

AN

GE

BR

N :

BR

OW

NG

RN

: G

REE

N

Sym

bo

l

FM RC

TR LM TA TC1,

TC2,

TCJ

RY

001

RY

002

RY

005~

007

PM

V

Par

ts n

ame

Fan

mot

or

Run

ning

cap

acito

r

Tran

sfor

mer

Love

r m

otor

Ind

oor

tem

p s

enso

r

Tem

p s

enso

r

Louv

er c

ontr

ol r

elay

Dra

in c

ontr

ol r

elay

Fan

mot

or c

ontr

ol r

elay

Pul

se m

otor

val

ve

1.

In

dic

ates

the

ter

min

al b

oloc

k, le

tter

.

the

lett

er in

sid

e in

dic

ates

the

ter

min

al n

umb

er.

2. A

do

tted

line

and

bro

ken

line

ind

icat

e

t

he w

iring

on

site

.

3.

Ind

icat

es t

he c

ontr

ol p

.c. b

oard

.

Co

ntro

l P.C

. bo

ard

for

Ind

oo

r un

itM

CC

-140

3

Page 110: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

107

1 12 2

1 12 2

3 3

CN

311(

BLU

)

CN

03(W

HI)

CN

300

(WH

I)C

N30

1(W

HI)

Exc

ept 5

HP,

6H

P

CN

500

(WH

I)C

N01

(BLU

)

BLUBLU

WHIWHI

7 5 3 1

7 5 3 1S

V41

BLU

BLU

CN

312(

WH

I)3 1

3 1S

V2

BLU

BLU

CN

324(

RE

D)

3 1

3 1S

V3A

BLU

BLU

CN

313(

YE

L)3 1

3 1S

V3B

BLU

BLU

CN

314(

BLK

)3 1

3 1S

V3C

BLU

BLU

BR

W

BR

W

CN

316(

WH

I)

Hea

ter

1

1 3

1 3

CN

315(

BLU

)

T H

eate

r 2

1 3

1 3

CN

310(

WH

I)4 3 2 1

2 1S

V51

BLU

BLU

SV

42

BLU

BLU

RY

503

CR

503

RY

502

CR

502

RY

506

CR

506

RY

507

CR

507

RY

508

CR

508

RY

509

CR

509

RY

516

CR

516

RY

517

L3

L1

CR

517

RY

504

CR

504

U1

U2

U3

U4

U5

U6

U1

U2

U5

U6

1 12 2

65

43

21

65

43

21

REDBRNBLUORNYELWHI

PM

V1

43

24

32

1

REDBLK WHI

65

43

21

65

43

21

REDBRNBLUORNYELWHI

PM

V2

Pre

ssur

eS

enso

rP

S

CN

501

(RE

D)

43

14

32

1

REDBLK

WHI

Pre

ssur

eS

enso

rP

D

CN

508

(RE

D)

43

21

43

21

Opt

ion

Boa

rd

CN

509

(BLK

)

43

21

43

21

Opt

ion

Boa

rd

CN

510

(WH

I)

43

21

43

21

Opt

ion

Boa

rd

CN

512

(BLU

)C

N30

6(W

HI)63

H1

43

21

43

21

13

13

Opt

ion

Boa

rd

CN

513

(BLU

)

43

21

45 5

32

1

Opt

ion

Boa

rd

CN

308

(BLU

)

63H

2

13

13

BLU

(BLK

)

BLU

(BLK

)C

N50

2(W

HI)

3 1

3 1

TD

1(Y

EL)

TD

2(R

ED

)

TS

1(G

RY

)

BLU

(BLK

)

BLU

(BLK

)

BLK

BLK

3 1

3 1

CN

504

(WH

I)

CN

503

(PN

K)

TK

1(B

LK)

BLU

(BLK

)

BLU

(BLK

)

3 1

3 1

CN

514

(BLK

)

TK

2(B

LU)

BLU

(BLK

)

BLU

(BLK

)

3 1

3 1

CN

515

(GR

N)

TK

3(B

LU)

BLU

(BLK

)

BLU

(BLK

)

3 1

3 1

CN

516

(RE

D)

TK4

(GR

N)

BLU

(BLK

)

BLU

(BLK

)

3 1

3 1

CN

523

(YE

L)

BLU

BLU

3 1

3 1

CN

100

(BLK

)

3 1

34

4 1

CN

511

(GR

N)

2 12 1

TE

1(B

LK)

BLK

BLK

CN

505

(GR

N)

2 12 1

TO (BLK

)

BLK

BLK

CN

507

(YE

L)2 1

2 1

TL

(WH

I)

BLK

BLK

CN

521

(WH

I)2 1

2

221

Opt

ion

boar

d

3 1

34

4 1

CN

600(

WH

I)

T6.

3AF

US

E

CN

325

(YE

L)

CN

400

(WH

I)

CN

305(

RE

D)

OR

N

BLK

BLK

OR

N

CN

307(

WH

I)

RY

521

RY

511

CN

401

WH

IR

ED

PNKREDBLUWHIBLK

CN

402

22

55

53

13

21

7 75

4 43

3 32 2

1

31

31

43

21

21

1 1

T6.

3AF

US

E

T6.

3AF

US

E

REDWHIBLKGRY

CN

317

(BLU

)C

N32

3(W

HI)

4 43 3

2 21 1 PNK

PNKPNKPNK

L1L2L3N

ORN

RED

BLU

ORN

BLK(PNK)

BLK(PNK)

Com

p1

Com

p2

12

12

4WV

1S

V 3ES

V 3D

RY

518

CN

321

(RE

D)

BRN12

12

Acc

umul

ator

heat

er

RY

510

CR

521

CR

511

CR

510

CR

518

ON

SW

30

SW

01

SW

06

43

1O

N2

SW

14

43

1O

N2

SW

13

1O

N

SW

08

43

1O

N2

SW

12

43

1O

N2

SW

11

43

1O

N2

SW

07

43

1O

N2

SW

06

43

1O

N2

SW

10

43

1O

N2

SW

09

SW

05S

W04

SW

32

SW

02S

W03

D60

3D

602

D60

1D

600

D60

4

SW

31

SW

30

CN

800

CN

802

Fla

sh654321 654 987321

(Srv

ice)

31

31

31

31

32

13

25

45

41

32

13

25

45

41

31C

N18

(RE

D)

CN

17(B

LK)

CN

06(W

HI)

CN

26(B

LU)

CN

11C

N10

CN

09

CN

25(W

HI)

W V U

BLK

PNKREDBLUWHIBLK

PNKREDBLUWHIBLK

BLU

YE

L

WH

IR

ED

YE

LB

LUC

N22

CN

23

CM

2C

N03

CN

02C

N01

CN

15C

N13

CN

07W

HI

CN

08W

HI

T S R

BLK

WH

IR

ED

Rea

ctor

31

31

31

31

34

53

41

21

25

34

53

41

21

2

3311

53

41

25

32

13

25

45

41

22

33

11

CN

18(R

ED

)C

N17

(BLK

)C

N06

(WH

I)C

N26

(BLU

)

CN

500

(WH

I)

CN

503

(WH

I)

CN

504

CN

505(

RE

D)

CN

506(

BLK

)C

N50

2(B

LU)

GR

Y

BLU

YE

L

RE

D

CN

501

(RE

D)

CN

11C

N10

CN

09

CN

25(W

HI)

YE

L BLU

W V U

CN

21

CN

01

CN

02

CN

03

RE

D

WH

I

BLK

GR

YC

N04

CN

23(B

LU)

CN

22(W

HI)

CN

17

CN

18

CN

19

CN

20

BLK

WH

IR

ED

YE

LB

LUC

N22

CN

23

CM

1C

N03

CN

02C

N01

CN

15

BLK

BLU

YELYEL

BLK

BLU

BLK

CN

13

CN

20W

HI

CN

21W

HI

T S R

BLK

WH

IR

ED

Rea

ctor

13

13

13

13

1 3 5

2 4 6

2 4 6

A1

A2

Mg-

SW

OC

R

RE

DR

ED

RE

DR

ED

RE

DW

HI

BLK

BLK

BLK

GR

YG

RY

GR

Y

PT

C T

hem

isto

r

5 4 3 2 1

5 4 3 2 1

3 1

3 1

5 3 1

5 3 1

3 1

3 1

5 4 3 2 1

5 4 3 2 1

CN

01(W

HI)

RED

WHI

BLK

WV

U

FM

Ð +

YEL

PNK

PNK

RED

RED

BLU

BLUWHIBLK

WHIBLKBLU

Indo

orun

itO

utdo

orun

it

Cen

tral

rem

ote

cont

rolle

r

Tran

sfor

mer

RE

D

WH

I

BLK

GR

Y

L1 L2 L3 N

Pow

er S

uppl

y 3p

hase

380-

415V

50H

z38

0 6

0Hz

Noi

se fi

lter

P.C

. boa

rdM

CC

-136

6

Fan

IPD

UM

CC

-896

Inte

rfac

eco

ntro

lP.

C. b

oard

(I/F

)M

CC

-142

9

Pow

er s

uppl

yte

rmin

al

Com

p. IP

DU

No.

1M

CC

-150

2MG

-S

W

OC

R

Com

p. IP

DU

No.

2M

CC

-150

2

Pow

er s

uppl

yfo

r fa

nM

CC

-143

9

U1

U2

U3

U4

U5

U6

L1L2

L3N

Con

nect

ing

term

inal

Par

ts la

you

tE

arth

scr

ew

U3

U4

U1

U2

BLK

WH

IB

LUBLU

RE

DP

NK

YE

L

11

Co

lor

ind

icat

ion

RED

: R

EDW

HI

: WH

ITE

YEL

: Y

ELLO

WB

LU :

BLU

EB

LK

: BLA

CK

GR

Y :

GR

AYP

NK

: P

INK

OR

N :

OR

AN

GE

BR

N :

BR

OW

NG

RN

: G

REE

N

2. Outdoor UnitModel: MMY-MAP0501HT , MAP0601HT , MAP0801HT , MAP1001HT , MAP1201HT

Sym

bo

lC

M1,

CM

2P

MV

1, P

MV

2SV

2, S

V41,

SV4

2, S

V51,

SV3

A, S

V3B,

SV3

C, S

V3D,

SV3

E4

WV

1C

OM

P1,

CO

MP

2T

S1

TD

1, T

D2

TE

1T

OTK

1, T

K2,

TK

3, T

K4

TL

HE

ATE

R1,

HE

ATE

R2,

AC

CU

ME

ATE

RFM P

SP

D63

H1,

63H

2M

G-S

WO

CR

Par

ts n

ame

Co

mp

ress

or

Pul

se m

oto

r va

lve

2-w

ay v

alve

co

il4-

way

val

ve c

oil

Co

mp

ress

or

case

the

rmo

.P

ipe

tem

p.

sens

or

(Inle

t)P

ipe

tem

p.

sens

or

(Out

let)

Hea

t ex

chan

ge

tem

p.

sens

or

Air

tem

p.

sens

or

Oil

tem

p.

sens

or

Liq

uid

tem

p.

sens

orC

ase

heat

er,

230V

, 26

WF

an m

oto

r (D

C)

Low

pre

ssur

e se

nso

rH

igh

pre

ssur

e se

nso

rH

igh

pre

ssur

e sw

itch

Mag

net

switc

hO

verc

urre

nt r

elay

1. T

he t

wo

-do

t ch

ain

line

ind

icat

es w

iring

at

the

loca

l site

, an

d t

he d

ashe

d li

ne in

dic

ates

acce

sso

ries

sold

sep

arat

ely

and

ser

vice

cab

les,

res

pec

tivel

y.

2.

,

, and

ind

icat

e th

e te

rmin

al b

lock

s an

d t

he n

umer

als

ind

icat

e th

e te

rmin

al n

umb

ers.

3.

in

dic

ates

P.C

. boa

rd.

*B

e su

re t

o fix

the

ele

ctric

par

ts c

over

sur

ely

with

tw

o sc

rew

s.

(Oth

erw

ise

wat

er e

nter

s in

to t

he b

ox r

esul

ting

in a

tro

uble

.)Po

wer

sup

ply

P.C

. bo

ard

for

FAN

MC

C-1

439

FA

N IP

DU

P.C

. Bo

ard

MC

C-8

96,

897

IPD

U P

.C. B

oar

d (1

)M

CC

-150

2

No

ise

filte

rP

.C. b

oar

dM

CC

-136

6

IPD

U B

oar

d (2

)M

CC

-150

2

Inte

rfac

e C

ont

rol P

.C. B

oar

dM

CC

-142

9

Page 111: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

108

Page 112: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

109

Controls

12

Page 113: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

110

Foreword

Page 114: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

111

I/F

12

12 ForewordControls

1:1 Outline of application Control

Net

wor

k ad

apte

rT

CB

-PC

NT

20E

Sup

er D

igita

l Inv

erte

rD

igita

l Inv

erte

r

``1:1

mod

el``

conn

ectio

n in

terf

ace

TCB

-PC

NT3

01TL

E2

AI-

NE

TWO

RK

AI-

NE

TC

entr

al c

ont

rol

dev

ices

Wire

less

rem

ote

cont

rolle

rS

impl

e re

mot

e co

ntro

ller

RB

C-A

S21

E2

Wire

d r

emot

e co

ntro

ller

RB

C-A

MT2

1ER

BC

-AM

T31E

Wee

kly

timer

RB

C-E

XW

21E

2

Sid

e re

mot

eco

ntro

ller

Mas

ter

rem

ote

cont

rolle

r

Wee

kly

timer

RB

C-E

XW

21E

2

Con

trol

rem

ote

cont

rolle

rTC

B-S

C64

2TLE

2

Air-

cond

ition

ing

Man

agem

ent

Sys

tem

on

site

Mas

ter

ON

/OFF

sig

nal

Bat

ch d

rive,

err

or o

utp

ut

1 B

AC

netTM

: A

NS

l/AS

HR

AE

135Ð

1995

, A

Dat

a C

omm

uniC

atio

n P

roto

col f

or B

uld

ing

Aut

omat

ion

and

Con

troI

Net

wor

ks.

2 L

oNW

oRK

S¨ ,

Res

iste

rd t

rad

emar

k of

Ech

elon

Cor

por

atio

n

Rem

ote

loca

tion

ON

/OFF

con

trol

boa

rdTC

B IP

CB

-4E

Ala

rm S

tatu

s ou

tput

ON

/OFF

Com

man

d

Ext

erna

l mas

ter

ON

/OFF

boa

rdTC

B-P

CD

MO

2E

Pow

er p

eak-

cut

cont

rol b

oard

TCB

-PC

DM

2E

LON

Gat

eway

LON

WO

RK

S

TCS

-Net

Inte

rfac

eB

MS

-IFL

SV

1EB

MS

-LS

V2E

Inte

llige

nt s

erve

r

Ene

rgy

met

er r

elay

Inte

rfac

eB

MS

-IFW

H3E

Loca

l sup

ply

Ene

rgy

mon

itorin

g

Touc

hsc

reen

cont

rolle

r

Mon

itorin

g R

emot

e co

ntro

l S

ched

ule

oper

atio

n E

rror

cod

e in

dic

atio

n A

larm

list

ind

icat

ion

Mon

thly

rep

ort

Ene

rgy

mon

itorin

g

dat

a et

c.

Operation status outputOperation control command

Power peak-cut control signal

Master ON/OFF signal

Sup

er M

odul

ar M

ulti

Out

doo

r U

nit

Page 115: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

112

(((

(((

( ( (( ( (

12

CAUTIONS

1. Applications for indoor remote controller

Basic function System diagram Model

1-1

1-2

1-3

1-4

Individual controlAir conditioner isindividually operatedat a distance.

GROUP control

One remote controller cancontrol a group of up to amaximum. 8 indoor units.Operating on the samesetting

Two remote controlAir conditioner iscontrolled by tworemote controllers intwo locations.

Control byweekly timer

Weekly scheduleoperation

Main remote controller

Possible up to Max.total length 500m Receiver unit

Wireless remote controller

Indoorunit

Remotecontroller

WirelessRemote

controller

Indoorunit

Max.8 indoor units

Indoorunit

Indoorunit

Indoorunit

Indoorunit

Remotecontroller

Possible up to Max.total length 500m

Wired system Wireless system

Indoorunit

Indoorunit

Remotecontroller

Remotecontroller

Wirelessremote

controller 1

Wirelessremote

controller2Master Side SideMaster

Possible up to Max.total length 500m

Wired & Wirelesscombination control(Either one of the twocontrollers can be set asside control.)

Indoorunit

Remotecontroller

Wirelessremote

controller

Indoorunit

Remotecontroller

Weeklytimer

Weekly timer function Setting of ON-OFF

3 times par day Timer operation time is displayed. Holiday period

Wired remote controller RBC-AMT21E RBC-AMT31E Simple wired remote

controller RBC-AS21E2 Wireless remote controller

kit TCB-AX21U(W)-E2 RBC-AX22CE2 TCB-AX21E2

Wired remote controller RBC-AMT21E RBC-AMT31E Simple wired remote

controller RBC-AS21E2

Wired remote controller RBC-AMT21E RBC-AMT31E Simple wired remote

controller RBC-AS21E2 Wireless remote controller

kit TCB-AX21U(W)-E2 RBC-AX22CE2 TCB-AX21E2

Wired remote controller RBC-AMT21E RBC-AMT31E

Weekly timer RBC-EXW21E2

+

Page 116: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

113

Outdoor unit

Indoor unitLine-3

U3, U4

U5, U6

U1, U2

Single phase 220/230/240V

Powersupply

Central remote controller

Outdoor unit

Outdoor unit

Indoor unit

Indoor unit

Indoor remote controller

Indoor remote controller

Indoor remote controller

Line-2

Line-1

U3, U4

U3, U4

Zone4

Zone3

Zone2

Zone1

U5, U6

U1, U2

Header unit

Header unit

U1, U2

Header unit

Outdoor unitU3, U4

U1, U2

Indoor remote controller

Indoor unit

Weekly timer

Central remote controller

Power supply

Single phase 220/230/240V

12

Foreword

2. Application controls for central remote controller

Basic function System diagram Model

2-1

2-2

Central manage-mentcontroller for 64units

Central remotecontroller

Weekly timer

+

Weekly operationschedulecan be set byconnecting a weeklytimer to the centralremote controller

Function of central remote controller

Individual control for up to 64 indoor units Individual control for max. 64 indoor units

divided in to 4 zones. (Up to 16 indoor units for each zone.) Up to 16 outdoor header units are connectable. 4 specific central control settings to restrict individual

operation by remote controller are selectable. Different settings for 1 to 4 zones. Usable with other central control devices

(Up to 10 central control devices in one control circuit) Two selectable control modes

Central controller mode/Remote controller mode Setting of simultaneous ON/OFF 3 times per day

of the week combined with weekly timer.

Central remote controller TCB-SC642TLE2

<Indoor remote controller> Wired remote controller

RBC-AMT21E RBC-AMT31E

Simple wired remote controller RBC-AS21E2

Indoor remote controller Wired remote controller

RBC-AMT21E RBC-AMT31E

Simple wired remote controller RBC-AS21E2

Weekly timer RBC-EXW21E2

Central remote controller TCB-SC642TLE2

+

or

Page 117: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

114

12Super MMS * 1

2-3

Basic function System diagram Model

2-4

Either one of thetwo controllerscan be set as

side control.without indoorremote controller

Central manage-ment control with‘‘1 : 1 model’’

Even when grouping operation is performedby connecting multiple indoor units to 1 line,the indoor remote controller is required.

Available

Available

* TOSHIBA Digital Inverter System and Super Digital Inverter System

Central remote controllerTCB-SC642TLE2

Indoor remote controllerWired remote controllerRBC-AMT21ERBC-AMT31E

Central remote controllerTCB-SC642TLE2TCB-CC163TLE2

‘‘1 : 1 model’’ connectioninterfaceTCB-PCNT30TLE2RAV-SM560KRT-E,SM800KRT-E are notcompatible to connect

Indoor remote controllerWired remote controllerRBC-AMT21ERBC-AMT31E

Simple wired remotecontrollerRBC-AS21E2

U3, U4Outdoor unit

U1, U2

Indoor unitPowersupply

Central remote controller

Single phase220/230/240V

Example of grouping operation

U3, U4Outdoor unit

U1, U2

(Group)Indoor remote controlleris required

Central remote controllerSingle phase220/230/240V

Powersupply

U3, U4Outdoor unit

U1, U2

(Group)Powersupply

Single phase220/230/240V

Central remote controller

Powersupply

Central remote controller

U3, U4

Headerunit

U1, U2 Indoor unit

Indoor remote controller

‘‘1:1 model’’connectioninterface

Page 118: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

115

12

TCB-

Super MMS

LN Interface

Remote controller

LON Center

LON WORKS

TCB-IFLN060

TCB-

* 1

`̀ 1:1 model`̀connection interface

TCB-

Super MMS

Local server

TCS-NetRelay Interface

Remote controller

BACnet center

TCB-

* 1

`̀ 1:1 model`̀connection interface

• • •

3. Application control for network

3-1-1

3-1-2

Basic function System diagram Model

LONWORKS

BACnet

*1 TOSHIBA Digital Inverter System and Super Digital Inverter System

The LONWORKS interface should be connectedbetween a building management computer and aSuper MMS air conditioning system.

Wired remote controllerRBC-AMT21ERBC-AMT31E

Simple wired remotecontrollerRBC-AS21E2

LN interfaceTCB-IFLN640TLE‘‘1 : 1 model’’ connectioninterfaceTCB-PCNT30TLE2RAV-SM560KRT-E,SM800KRT-E are notcompatible to connect

or

Indoor remote controller

BACnet local serverBMS-LSV2E

TCS-Net Relay InterfaceBMS-IFLSV1E

Wired remote controllerRBC-AMT21ERBC-AMT31E

Simple wired remotecontrollerRBC-AS21E2

‘‘1 : 1 model’’ connectioninterfaceTCB-PCNT30TLE2RAV-SM560KRT-E,SM800KRT-E are notcompatible to connect

Indoor remote controller

*1 TOSHIBA Digital Inverter System and Super Digital Inverter System

The local server should be connected to the BACnetnetwork, and the Super MMS air conditioningsystem through the interface.

Page 119: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

116

12

Touch screen controller system

System Diagram

Intelligent Server Software

Touch ScreenController

Intelligent ServerTCS-Net Relay Interface

Energy Meter Relay Interface

Digital I/O Relay Interface

Fire alarmDoor Key Entry ON/OFFError code output

Control Maximum 512 FCU

Ethernetconnection RS-485 Control wiring

Outdoor units

Indoor units

Remote controller

Control wiring

Control wiring

Maximum 4 Intelligent server

Maximum 8 Relay Interface

Maximum 4 Energy MonitoringRelay Interface

Maximum 4 Digital I/O Relay Interface

Maximum 8 Power Meter

Local supply1kWh/pulse or 10kWh/pulse50-1000 ms

Pulse SignalI/F

I/F

3-2-1

Dev

ices

Fun

ctio

n

Model Name Model Name SpecificationTouch Screen controller (English version)

Intelligent ServerIntelligent Server SoftwareTCS-Net Relay InterfaceEnergy Monitoring Relay InterfaceDigital I/O Relay Interface

(1) Monitoring air-conditioners

(2) Operating of air-conditioners

(3) Schedule operation

(4) Alarm list display

(5) Alarm record display

(6) Monthly report data extraction

(7) Energy monitoring data extraction

Max 64 FCU , without electrical bill calculationMax 512 FCU , without electrical bill calculationMax 64 FCU , with electrical bill calculationMax 512 FCU , with electrical bill calculationServer in between Touch Screen controller & RS-485Installed on Intelligent ServerI/F in between Intelligent server & Control wiringI/F for Power MeterI/F for I/O signal

BMS-TP0640ACEBMS-TP5120ACEBMS-TP0640PWEBMS-TP5120PWEBMS-LSV2EBMS-STCC01EBMS-IFLSV1EBMS-IFWH3EBMS-IFDD01EOperation status can be viewed according to a unit. Unit All building, All tenants, Each tenant, Each area, Each air-conditioning system Monitoring contents Operation and alarm status, Setting status for each air-conditioning system

Header / individual control can be performed according to a unit. Operating contents ON/OFF, Operation setting (operation mode, air volume, louver position, setting temp., restricted setting from remote location)

Air-conditioners are operated according to the set-up schedule / operation pattern.Schedule opretaion can be performed according to a unit. Operation pattern Weekly pattern, special day pattern (4 pattern), Non-operation days pattern

The present alarm contents are list-displayed. Display contents Alarm contents, Unit number, Generated timeThe alarm history records are displayed. Display contents Alarm contents, Unit number, Generated timeMonthly report data is wrtten to ‘‘Compact Flash’’. Monthly reports can be created according toa unit using the monthly report software. Monthly report contents The number of ON/OFF, Operating time, Results of energy monitoring

Power consumption data is written to ‘‘Compact Flash’’. Energy monitoring can be performedaccording to a unit using the energy monitoring software. Energy monitoring data Power consumption according to the power meter

Page 120: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

117

12

3-2-2

Basic function System diagram Model

Windows basedcentral controller(Now planning) Personal computer on site

server

Relay Interface

Remote controller‘‘1:1 model’’connection interface

Energy monitoring relay interface

Digital I/O relay interface

Super MMS * 1

*1 TOSHIBA Digital Inverter System and Super Digital Inverter System

Page 121: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

118

12

Display

Operation

Interface

RemoteController

Central RemoteControllerTCB-SC641E

PowerSupply AI Network

Indoor unit

Network Adapter

ON /OFF

COM

Application control of optional devices connectable to indoor units

Remote location ON/OFF control boxModelName

Appearance Features

TC

B-I

FCB

-4E

TCB

-PC

NT2

0E

Network adapterModelName

Appearance Features

Monitoring ON/OFF status (for indoor unit) Alarm status (system & indoor unit stop)ON/OFF command Air conditioner can be turned ON/OFF by external signals. The external ON/OFF signals will initiate

the signals shown below.

Application Function

Application

Wiring diagram of indoor P.C. board

Connection of cables

Indoor units of Super MMS system arecontrolled by AI-NETWORK centralremote controller.Connectable indoor units per group.

Install optional P.C. board in Electrical parts box of indoor unit.

Non-voltageON /OFF continious signal

Start and stop of the air conditioner is possibleby a external signal and indication ofoperation/alarm externally.

Page 122: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

119

12

adoptor

ON-OFFcontroldevices

‘‘1:1 model’’ connection interfaceModelName

Appearance Features

Link adapter for ‘‘1:1 model’’ intosuper modular muti network

1:1 model : Super digital inverter Digital inverter

Wiring diagram of indoor P.C. board

Connection of cables

Install optional P.C. board in Electrical parts box of indoor unit.

Central RemoteControllerTCB-SC642TLE2

Application

1:1 modelconnectioninterface

Indoor units

Super MMS control wiring

Digital InverterSuper Digital Inverter

Outdoor unit

TC

B-P

CN

T30

TLE

2

TCB-CC163TLE2

Page 123: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

120

12

Application controls by optional P.C. board of outdoor unit

Local Supply

ON

COM

TCB-PCDM2E

OFF

COM

SW1

SW2

ModelName

Appearance Function

TC

B-P

CD

M2E

Application

1 Power peak-cut Control

FeatureThe upper limit capacity of the outdoor unit isrestricted based on the power peak cut requestsignal from outside.

FunctionTwo types of control can be selected by settingSW07 on the interface P.C. board on theheader outdoor unit.

Size : 71 x 85

*Install this optional P.C. board in the inverter assembly of the header outdoor unit.

Standard funciton SW07-2 OFF

Input SW07-1SW01

ONOFF

SW02OFFON

ONUp to 60%

100%(Normal)

OFF0% (stop)

100%(Nomal)

Expansion function SW07-2 ON

Input SW07-1SW01OFFONOFFON

SW02OFFOFFONON

ON100%(Normal)

Up to 85%Up to 75%Up to 60%

OFF100%(Nomal)Up to 80%Up to 60%0%(stop)

Ensure terminal contacts are securely fixed.Do not turn on both SW1 and SW2 terminals simultaneously.

Page 124: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

121

Local Supply

SMC

COM

Cooling

TCB-PCMO2E

Local Supply

SMC

COM

Cooling

TCB-PCMO2E

Heating

SMH 12

ModelName Appearance Function

TC

B-P

CM

02E

Application

Size : 55.5 x 60

*Install this optional P.C. board in the inverter assembly of the header outdoor unit.

2 Snowfall fan controlFeatureOutdoor fan is operated by a snowfall signal from outside.

Function

SMC : Cooling mode select input (switch)Terminal Operation Input signal

OFF SMC

ON

ON

OFF

Snowfall fan control(Operates outdoor fan.)

Usual operation

This control is activated when a input signal increases or decreases.(The increasing or decreasing signal needs to be held for a minimumof 100m/sec in order to activate the control).

3 External master ON/OFF controlFeatureThe outdoor unit starts or stops the system.

Function

SMC : Input signal for startSMH : Input signal for stopTerminal Operation Input signal

SMC

OFF

Starts all indoor units.

SMH

ON

ON OFF

Stops all indoor units.

This control is activated when a input signal increases or decreases.(The increasing or decreasing signal needs to be held for a minimumof 100m/sec in order to activate the control).

Ensure terminal contacts are securely fixed.

Page 125: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

122

12

Local Supply

SMC

COM

Cooling

TCB-PCMO2E

Local Supply

SMC

COM

Cooling

TCB-PCMO1E

Heating

SMH

ModelName Appearance Function

TC

B-P

CM

02E

Application

Size : 55.5 x 60

4 Night operation (Sound reduction) control

FeatureSound level can be reduced by restricting the compressorand fan speeds.

Function

SMC : Cooling mode designated input switchTerminal Operation Input signal

SMC

ON

Usual operation ON OFF

OFF

Night operation control

This control is activated when a input signal increases or decreases.(The increasing or decreasing signal needs to held for a minimum of100m/sec in order to activate the control).

5 Operation mode selection controlFeatureThis control can restrict the selectable operation mode.

Function

SMC : Cooling mode designated input switchSMH : Heating mode designated input switch

SMC Selected operation modeSMHOnly cooling modepermitted

ON OFF

OFF ON Only heating modepermitted

Ensure terminal contacts are securely fixed.

*Install this optional P.C. board in the inverter assembly of the header outdoor unit.

Page 126: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

123

12

Remote controller

RBC-AMT31E

Wired remote controller

RBC-AMT21E

16120

4

2.7

120

120

62

8418

16

120

Page 127: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

124

12

RBC-AS21E / RBC-AS21E2

Simple wired remote controller

80 120

6070

13

16

Page 128: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

125

12

Wireless remote controller

RBC-AX22CE / RBC-AX22CE2

Wireless remote controller kit

TCB-AX21U (W)-E / TCB-AX21U (W)-E2

18658 19.5

61

186

177

32

58 19.5130

61

177

65

Page 129: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

126

12

TCB-AX21E / TCB-AX21E2

Wireless remote controller kit

RBC-EXW21E / RBC-EXW21E2

Weekly timer

13

83.5

83.5

70 4.4 x 5.4 long hole

4.4 x 9.4 long hole

58 19.5

61

177

16120

4

2.7

120

Page 130: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

127

12

TCB-SC642TLE / TCB-SC642TLE2

Remote sensor

Central remote controller

TCB-TC21LE / TCB-TC21LE2

127-1

11647

15

13

1601486 (6)

121

160

148

6(6

)

121

115

6921

12880

128

80

36

47

13

Z

Z view (back side)

80 120

6070

13

16

Page 131: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

128

12

TCB-CC163TLE2

ON-OFF controller

127-2

116

160

1486 (6)

122

160

148

6(6

)

12

1

11

5

6914

128

80

128 80

36 47

13

Unit: mm

Z

4-Ø5 diameter holes(for mounting)

Hole for electrical wiring

4-Ø5.5 diameter holes (for mounting)

Z-view (back side)

Page 132: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

129

12

BMS-IFLSV1E

TCS-Net relay interface

BMS-TP0640ACEBMS-TP5120ACEBMS-TP0640PWEBMS-TP5120PWE

Touch screen controller

127-3

70

25695

.75

91.7

575

75

316249

48

1624

299

.3

82.5 30255.5

3019

54495

200

22787822

22787822

66

63.6

146.

9

156

170

6- 5.5 mounting holes

Page 133: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

130

12

Intelligent server

Energy monitoring relay interface / Digital I/O relay interface

BMS-IFWH3EBMS-IFDDO1

BMS-LSV2E

128

370

198

39CAUTION

Do not rem

ove.

WARNINGDo not decompose.

7(2

.4)

63.6

715

6

170

144.

912

.55

12.5

5

146.

9

2222 7878

200

6 5.5 mounting hole(2.4) 63.6

Page 134: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

131

12

129

Dimension

TCB-PCDM2E

TCB-PCMO2E

TCB-PCIN2E

85 75

TerminalScrew M3 x 6

TerminalScrew M4 x 8

4-4ø hole

71

61

TerminalScrew M3 x 6

55.5

45.5

60 50

4-4ø hole

6979

6373

4- 4 hole

Terminal (Screw M3 )

Page 135: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

132

12

130

Page 136: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

131

Fan characteristics

13

Page 137: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

132

Foreword

13

Page 138: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

133

13 ForewordFan characteristics

200 400 600480

400 600 800650

300 500 700570

500 700 900780

0

20

40

60

80

100

120

140

0

20

40

60

80

100

120

140

0

20

40

60

80

100

120

140

0

20

40

60

80

100

120

140

13

A

MMD-AP0071BH, AP0091BH

Standard air volume:480m3/h

MMD-AP0121BH

Standard air volume:570m3/h

MMD-AP0151BH

Standard air volume:650m3/h

MMD-AP0181BH

Standard air volume:780m3/h

Ext

ern

al s

tati

c p

ress

ure

(P

a)

Ext

ern

al s

tati

c p

ress

ure

(P

a)

Ext

ern

al s

tati

c p

ress

ure

(P

a)

Ext

ern

al s

tati

c p

ress

ure

(P

a)

Air volume(m3/h) Air volume(m3/h)

Air volume(m3/h) Air volume(m3/h)

Air

volu

me

limit

(Min

)

Applic

atio

n lim

it

High-static pressure 2H tap

High static pressure 1H tap

Standard H tap

Low static pressure H tapStandard L tap

long life filter

Air

volu

me

limit

(Max

) Applicati

on lim

it

High-static pressure 2H tapHigh static pressure 1H tap

Standard H tapLow static pressure H tapStandard L tap

long life filter

Air

volu

me

limit

(Max

)

Application lim

it

High-static pressure 2H tap

High static pressure 1H tap

Standard H tap

Low static pressure H tap

Standard L tap

long life filter

Air

volu

me

limit

(Max

)

Applicatio

n limit

High-static pressure 2H tap

High static pressure 1H tap

Standard H tap

Low static pressure H tap

Standard L tap

long life filter

Air

volu

me

limit

(Max

)

Air

volu

me

limit

(Min

)

Air

volu

me

limit

(Min

)

Air

volu

me

limit

(Min

)

Page 139: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

134

800 1000 12001140

1200 20001620

900 1100 13001260

1400 1800 22001980

0

20

40

60

80

100

120

140

0

20

40

60

80

100

120

140

0

20

40

60

80

100

120

140

0

20

40

60

80

100

120

140

13

MMD-AP0241BH, AP0271BH

Standard air volume:1140m3/h

Ext

ern

al s

tati

c p

ress

ure

(P

a)

Air volume(m3/h)

Air

volu

me

limit

(Min

)

Application limit

High-static pressure 2H tap

High static pressure 1H tap

Standard H tap

Low static pressure H tap

Standard L tap

long life filter

Air

volu

me

limit

(Max

)

MMD-AP0301BH

Ext

ern

al s

tati

c p

ress

ure

(P

a)

MMD-AP0361BH

Ext

ern

al s

tati

c p

ress

ure

(P

a)

MMD-AP0481BH, AP0561BH

Ext

ern

al s

tati

c p

ress

ure

(P

a)

Standard air volume:1260m3/h

Standard air volume:1620m3/h Standard air volume:1980m3/h

Air

volu

me

limit

(Max

)

Air

volu

me

limit

(Max

)

Air

volu

me

limit

(Max

)

Air volume(m3/h)

long life filter

Air volume(m3/h)

long life filter

Air volume(m3/h)

long life filter

Application limit

High-static pressure 2H tap

High static pressure 1H tap

Standard H tap

Low static pressure H tap

Standard L tap

Application limit

High-static pressure 2H tap

High static pressure 1H tap

Standard H tap

Low static pressure H tap

Standard L tap

Application lim

itHigh-static pressure 2H tap

High static pressure 1H tap

Standard H tap

Low static pressure H tap

Standard L tap

Air

volu

me

limit

(Min

)

Air

volu

me

limit

(Min

)

Air

volu

me

limit

(Min

)

Page 140: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

135

Foreword

Concealed Duct High Static Pressure type

1.5

1.0

0.5

250

200

150

100

50

700 800 900 1000 11000

50Hz60Hz

2.0

1.5

1.0

300

250

200

150

50

100

1000 1100 1200 13001320

1400 1500 16000

50Hz60Hz

2.5

2.0

1.5

1.0

250

200

150

100

50

1400 1500 1600 1700 18000

2.0

2.5

3.0

1.5

0.5

250

200

150

50

100

1500 2000

2100

25000

Lo

50Hz60Hz

50Hz60Hz 13

MMD-AP0181H MMD-AP0241H, AP0271H

MMD-AP0361H MMD-AP0481H

Standard air volume: 900 m3/h

Fan

mot

or c

urre

nt (A

)

High static pressure tap

Medium static pressure tap

Low static pressure tap

Out

sid

e st

atic

pre

ssur

e (P

a)

Air

vo

lum

e lo

wer

lim

it

Air

volu

me

upp

er li

mit

High static pressure tapM

edium static pressure tap

Low static pressure tap

Air volume (m3/h)

Standard air volume: 1320 m3/h

Fan

mot

or c

urre

nt (A

)

High static pressure tapMedium static pressure tap

Low static pressure tap

Out

sid

e st

atic

pre

ssur

e (P

a)

Air

vo

lum

e lo

wer

lim

it

Air

volu

me

upp

er li

mitHigh static pressure tap

Medium

static pressure tap

Low static pressure tap

Air volume (m3/h)

Standard air volume: 2100 m3/h

Fan

mot

or c

urre

nt (A

)

High static pressure tap

Medium static pressure tap

Low static pressure tap

Out

sid

e st

atic

pre

ssur

e (P

a)

Air

vo

lum

e lo

wer

lim

it

Air

volu

me

upp

er li

mitHigh static pressure tap

Medium static pressure tapLow static pressure tap

Air volume (m3/h)

Fan

mot

or c

urre

nt (A

)

High static pressure tap

Medium static pressure tap

Low static pressure tap

Out

sid

e st

atic

pre

ssur

e (P

a)

Air

vo

lum

e lo

wer

lim

it

Air

volu

me

upp

er li

mit

High static pressure tapMedium static pressure tap

Low static pressure tap

Air volume (m3/h)

Standard air volume: 1600 m3/h

Page 141: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

136

4

4.5

5

5.5

6

6.5

7

7.5

8

3000 3400 3800 42002880 3200 3600 4000 43205

50

100

150

200

250

300

4

4.5

5

5.5

6

6.5

7

7.5

8

8.5

3360 3600 4000 4400 4800 50405

50

100

150

200

250

300

350

13

MMD-AP0721HStandard air volume : 3600m3/h

Cur

rent

of

fan

mot

or (A

)

High static pressure tap (60Hz)

Medium static pressure tap (60Hz)

Low static pressure tap

Low static pressure tap (60Hz)

High static pressure tap (50Hz)

Medium static pressure tap (50Hz)

High static pressure tap (60Hz)

Low static pressure tap (60Hz)

Medium static pressure tap (50Hz)Medium static pressure tap (60Hz)

Upper limit of air volumeAir volume (m3/h)Lower limit of air volume

Ext

erna

l sta

tic p

ress

ure

(Pa)

High static pressure tap (50Hz)

Low static pressure tap (50Hz)

MMD-AP0961HStandard air volume : 4200m3/h

Cur

rent

of

fan

mot

or (A

)

High static pressure tap (60Hz)

Low static pressure tap

Low static pressure tap (60Hz)

High static pressure tap (50Hz)

Medium static pressure tap (50Hz)

High static pressure tap (60Hz)

Low static pressure tap (60Hz)

Medium static pressure tap (50Hz)

Medium static pressure tap (60Hz)

Upper limit of air volumeAir volume (m3/h)Lower limit of air volume

Ext

erna

l sta

tic p

ress

ure

(Pa)

High static pressure tap (50Hz)

Low static pressure tap (50Hz)

Medium static pressure tap (60Hz)

Add a air volume damper to the supplied air duct, and adjust the air volume from 80% to 120% ofthe standard air volume.

REQUIREMENT

Page 142: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

137

2

0.3m/s

1

2

1

2.8m

0 1 2 3 4 5m

0.7m/s

0.5m/s

0.7m/s

0.5m/s

0.3m/s1

2

33.6m

0 1 2 3 4 5m

2

3

0.7m/s

0.7m/s

0.5m/s

0.5m/s

0.3m/s

0.3m/s

1

2

3

1

3.6m

3.6m

0 1 2 3 4 5m 0 1 2 3 4 5m

0 1 2 3 4 5m

2 0.7m/s

0.7m/s

0.5m/s

0.5m/s

0.3m/s

0.3m/s

1

2.8m

0 1 2 3 4 5m

0 1 2 3 4 5m

2

3 0.7m/s

0.5m/s

0.3m/s1

2

3

1

3.6m

3.6m

0 1 2 3 4 5m

2.7m

0.7m/s

0.5m/s

0.3m/s

13

AIR SPEED CHARACTERISTICS

B

4-way air discharge cassette type

MMU-AP0091H, AP0121H MMU-AP0151H

MMU-AP0181H MMU-AP0241H,AP0271H

MMU-AP0301H

MMU-A0361H

MMU-AP0561H

MMU-A0481H

Air Speed Distribution

Page 143: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

138

2

0

(m)

1 2

0

1

2

2.7

1.0

0.5

0.30.3

1 2 3 4

3m

2.7m

1

1.0

0.5

0.3 0.3

2

0

(m)

1 2 3m

2.7m

1

1.0

0.50.5

0.30.30.3

2

0

(m)

1 2 3m

2.7m

11.0

0.5

0.30.30.3

0

1

2

2.7

1.0

0.5

0.30.3

1 2 3 4

13

2-way air discharge cassette type

MMU-AP0071WH, AP0091WH, AP0121WH

Air Speed Distribution

Horizontal distance (m)

MMU-AP0151WH, AP0181WH

Horizontal distance (m)

MMU-AP0241WH, AP0271WH

Horizontal distance (m)

MMU-AP0301WH

Horizontal distance (m)

MMU-AP0481WH

Horizontal distance (m)

Cei

ling

heig

ht (m

)

Cei

ling

heig

ht (m

)

Cei

ling

heig

ht (m

)

Cei

ling

heig

ht (m

)

Cei

ling

heig

ht (m

)

Page 144: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

139

21.0

0.3 0.5 0.3

1

2.7m

0 1 2 3m

2

1

2.7m

0 1 2 3m

1m

1m 2m 3m 4m 1m 2m 3m 4m

1m 2m 3m 4m

2m

3m

1.0

0.50.3

0.3

0.3

0.5

1.0

0.3 0.5

1m

2m

3m

1m

2m

3m

0.3

0.5

1.0

0.3

0.3

0.5

1.0

0.3

2.7m

2

0 1 2 3m0.6

0.9

0.4 0.4

2.3

5.0

1

2.7m

2

0 1 2 3m

1.71.5

0.4

4.5

1

2.7m

2

0 1 2 3m0.3

0.5

0.20.2

2.5

4.0

1

2.7m

2

0 1 2 3m

1.5 1.10.3

3.00.3

1

13

1-way air discharge cassette type

Air Speed Distribution

MMU-AP0071YH, AP0091YH, AP0121YH

MMU-AP0151SH,AP0181SH MMU-AP0241SH

MMC-AP0181H,AP0481H MMC-AP0361H

MMC-AP015H,AP0241H,AP0271H

Under ceiling type

H (High wind, blowing downward)

L (Low wind, blowing downward)

L (Low wind, blowing horizontally)

H (High wind, blowing horizontally)

Page 145: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

140

0 1 2 3 4 5 6 7

1

2

3

4

5

0 1 2 3 4 5 6 7

1

2

3

4

5

0 1 2 3 4 5 6 7

1

2

3

4

5

0 1 2 3 4 5 6 7

1

2

3

0 1 2 3 4 5 6 7

1

2

3

0 1 2 3 4 5 6 7 8

1

2

3

4

High wind

Med. wind

Low wind

High wind

Med. windLow wind

High wind

Med. windLow wind

13

High wall type

Discharge Air Speed and Air Throw

Floor standing cabinet type

MML-AP0071H, AP0091H MML-AP0121H, AP0151H MML-AP0181H, AP0241H

MMK-AP0241H

MMK-AP0071H, AP0091H, AP0121H MMK-AP0151H, AP0181H

Horizontal discharge Initialspeed

Air

spee

d (m

/s)

High wind: 5.0m/sMed. wind: 4.4m/s

Horizontal throw (m)

Horizontal discharge Initialspeed

Air

spee

d (m

/s)

High wind: 5.0m/sMed. wind: 4.4m/s

Horizontal throw (m)

Horizontal discharge Initialspeed

Air

spee

d (m

/s)

High wind: 5.0m/sMed. wind: 4.4m/s

Horizontal throw (m)

Air

spee

d (m

/s)

Distance from discharge grille (m)

Air

spee

d (m

/s)

Distance from discharge grille (m)

Air

spee

d (m

/s)

Distance from discharge grille (m)

Page 146: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

141

1 2 3 4 5 6 7 8

2.7

2.0

1.0

1.5m/s 1.0m/s 0.7m/s0.5m/s

1 2 3 4 5 6 7 8

2.7

2.0

1.0

1.5m/s 1.0m/s

0.5m/s

1 2 3 4 5 6 7 8

2.7

2.0

(m)

(m)

(m)

(m)

(m)

(m)

(m)

(m)

1.0

2.0m/s1.0m/s1.5m/s

0.5m/s

1 2 3 4 5 6 7 8

2.7

2.0

1.0

1.5m/s1.5m/s1.5m/s1.0m/s

13

Floor standing type

Air Speed Distribution

MMF-AP0151H, AP0181H MMF-AP0241H, AP0271H

MMF-AP0361H MMF-AP0481H,AP0561H

Page 147: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

142

Page 148: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

143

Sound characteristics (NC CURVE)

14

Page 149: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

144

Foreword

Page 150: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

145

14 ForewordSound characteristics (NC CURVE)

14

Microphone

MMU-AP0091H, AP0121H

Sound level data (NC CURVE) Sound level values shown are based on a measurement in a non resound room.

Oct

ave

ban

d s

ou

nd

pre

ssu

re le

vel (

dB

)Octave band frequency(Hz)

Audibility limits ofcontinous white sound

Audibility limits ofcontinous white sound

Audibility limits ofcontinous white sound

Audibility limits ofcontinous white sound

Octave band frequency(Hz)Octave band frequency(Hz)

Octave band frequency(Hz)

Oct

ave

ban

d s

ou

nd

pre

ssu

re le

vel (

dB

)

Oct

ave

ban

d s

ou

nd

pre

ssu

re le

vel (

dB

)O

ctav

e b

and

so

un

d p

ress

ure

leve

l (d

B)

MMU-AP0181HMMU-AP0151H

MMU-AP0241H, AP0271H

Fan Tap

Sound pressurelevel(dB(A))

H

30

M

29

L

27

Fan Tap

Sound pressurelevel(dB(A))

H

32

M

29

L

28

Fan Tap

Sound pressurelevel(dB(A))

H

31

M

29

L

27

Fan Tap

Sound pressurelevel(dB(A))

H

34

M

31

L

28

Page 151: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

146

14

MMU-AP0301H

Sound level data (NC CURVE) Sound level values shown are based on a measurement in a non resound room.

Oct

ave

ban

d s

ou

nd

pre

ssu

re le

vel (

dB

)

Octave band frequency(Hz)

Fan Tap

Sound pressurelevel(dB(A))

H

37

M

33

L

30

Audibility limits ofcontinous white sound

MMU-AP0361H

Oct

ave

ban

d s

ou

nd

pre

ssu

re le

vel (

dB

)Octave band frequency(Hz)

Fan Tap

Sound pressurelevel(dB(A))

H

40

M

36

L

33

Audibility limits ofcontinous white sound

MMU-AP0481H MMU-AP0561HFan Tap

Sound pressurelevel(dB(A))

H

44

M

38

L

34

Fan Tap

Sound pressurelevel(dB(A))

H

45

M

48

L

34

Audibility limits ofcontinous white sound

Audibility limits ofcontinous white sound

Octave band frequency(Hz) Octave band frequency(Hz)

Oct

ave

ban

d s

ou

nd

pre

ssu

re le

vel (

dB

)

Oct

ave

ban

d s

ou

nd

pre

ssu

re le

vel (

dB

)

Page 152: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

147

Foreword

14

Microphone

Sound level data (NC CURVE) Sound level values shown are based on a measurement in a non resound room.

MMU-AP0071WH, AP0091WH, AP0121WH

Oct

ave

ban

d s

ound

pre

ssur

e le

vel (

dB

)

Octave band frequency (Hz)

standard sound pressure 0.0002 µbar

Audibility limitsof continouswhite level

Fan Tap

Sound pressurelevel(dB(A))

H

34

M

32

L

30

Fan Tap

Sound pressurelevel(dB(A))

H

38

M

35

L

33

Fan Tap

Sound pressurelevel(dB(A))

H

35

M

33

L

30

MMU-AP0151WH, AP0181WH MMU-AP0241WH, AP0271WH

Oct

ave

ban

d s

ound

pre

ssur

e le

vel (

dB

)

Oct

ave

ban

d s

ound

pre

ssur

e le

vel (

dB

)

Octave band frequency (Hz) Octave band frequency (Hz)

Audibility limitsof continouswhite level

Audibility limitsof continouswhite level

standard sound pressure 0.0002 µbar standard sound pressure 0.0002 µbar

Page 153: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

148

NC-70

NC-60

NC-50

NC-40

NC-30

NC-20

HM

L

10

20

30

40

50

60

70

80

90

63 125 250 500 1000 2000 4000 8000

NC-70

NC-60

NC-50

NC-40

NC-30

NC-20

HM

L

10

20

30

40

50

60

70

80

90

63 125 250 500 1000 2000 4000 8000

NC-20

NC-70

NC-60

NC-50

NC-40

NC-30

NC-70

NC-60

NC-50

NC-40

NC-30

NC-20

Microphone

14

MMU-AP0301WH

Sound level data (NC CURVE)

Oct

ave

ban

d

soun

d p

ress

ure

leve

l (d

B)

Fan Tap

Sound pressurelevel(dB(A))

H

40

M

37

L

34

Audibility limitsof continous white level

Octave band center frequency (Hz)

MMU-AP0481WH

MMU-AP0151SH, AP0181SH

MMU-AP0241SH

Fan Tap

Sound pressurelevel(dB(A))

H

45

M

42

L

39

Fan Tap

Sound pressurelevel(dB(A))

H

42

M

39

L

36

Fan Tap

Sound pressurelevel(dB(A))

H

43

M

41

L

37

Oct

ave

ban

d

soun

d p

ress

ure

leve

l (d

B)

Oct

ave

ban

d

soun

d p

ress

ure

leve

l (d

B)

Oct

ave

ban

d

soun

d p

ress

ure

leve

l (d

B)

Octave band center frequency (Hz)

Octave band frequency (Hz)

Octave band frequency (Hz)

Audibility limitsof continous white level

Audibility limitsof continous white level

Audibility limitsof continous white level

Page 154: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

149

HM

L

10

20

30

40

50

60

70

80

90

63 125 250 500 1000 2000 4000 8000

NC-70

NC-60

NC-50

NC-40

NC-30

NC-20

H

ML

10

20

30

40

50

60

70

80

90

63 125 250 500 1000 2000 4000 8000

NC-70

NC-60

NC-50

NC-40

NC-30

NC-20

H

ML

10

20

30

40

50

60

70

80

90

63 125 250 500 1000 2000 4000 8000

NC-70

NC-60

NC-50

NC-40

NC-30

NC-20

HM

L

10

20

30

40

50

60

70

80

90

63 125 250 500 1000 2000 4000 8000

NC-70

NC-60

NC-50

NC-40

NC-30

NC-20

Microphone

14

Sound level data (NC CURVE)

MMD-AP0071BH, AP0091BH

MMD-AP0151BHMMD-AP0121BH

MMD-AP0181BH

Oct

ave

ban

d s

oun

d p

ress

ure

leve

l(dB

)

Octave band center frequency (Hz)

Audibility limits ofwhite level

Oct

ave

ban

d s

oun

d p

ress

ure

leve

l(dB

)

Octave band center frequency (Hz)

Audibility limits ofwhite level

Oct

ave

ban

d s

oun

d p

ress

ure

leve

l(dB

)

Audibility limits ofwhite level

Octave band center frequency (Hz)

Audibility limits ofwhite level

Octave band center frequency (Hz)

Oct

ave

ban

d s

oun

d p

ress

ure

leve

l(dB

)

Fan TapSound pressure level

(dB(A))

H

30

M

28

L

26

Fan TapSound pressure level

(dB(A))

H

31

M

29

L

27

Fan TapSound pressure level

(dB(A))

H

31

M

29

L

27

Fan TapOverall level

dB(A)

H

32

M

30

L

28

Page 155: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

150

10

20

30

40

50

60

70

80

90

63 125 250 500 1000 2000 4000 8000

NC-70

NC-60

NC-50

NC-40

NC-30

NC-20

10

20

30

40

50

60

70

80

90

63 125 250 500 1000 2000 4000 8000

NC-70

NC-60

NC-50

NC-40

NC-30

NC-20

10

20

30

40

50

60

70

80

90

63 125 250 500 1000 2000 4000 8000

NC-70

NC-60

NC-50

NC-40

NC-30

NC-20

10

20

30

40

50

60

70

80

90

63 125 250 500 1000 2000 4000 8000

NC-70

NC-60

NC-50

NC-40

NC-30

NC-2014

MMD-AP0241BH, AP0271BH

Sound level data (NC CURVE)

Oct

ave

ban

d s

ound

pre

ssur

e le

vel(d

B)

Audibility limits ofwhite level

Octave band center frequency (Hz)

Fan TapSound pressure level

(dB(A))

H

33

M

31

L

29

MMD-AP0301BH

Fan TapSound pressure level

(dB(A))

H

34

M

32

L

29

MMD-AP0361BH

Fan TapSound pressure level

(dB(A))

H

36

M

34

L

32

MMD-AP0481BH, AP0561BH

Fan TapSound pressure level

(dB(A))

H

38

M

36

L

32

Oct

ave

ban

d s

ound

pre

ssur

e le

vel(d

B)

Oct

ave

ban

d s

ound

pre

ssur

e le

vel(d

B)

Oct

ave

ban

d s

ound

pre

ssur

e le

vel(d

B)

Octave band center frequency (Hz)

Octave band center frequency (Hz) Octave band center frequency (Hz)

Audibility limits ofwhite level

Audibility limits ofwhite level

Audibility limits ofwhite level

Page 156: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

151

Microphone

14

Sound level data (NC CURVE) Sound level values shown are based on a measurement in a non resound room.

MMD-AP0181H

Oct

ave

ban

d s

ound

pre

ssur

e le

vel (

dB

)

Octave band center frequency (Hz)

Audibility limitsof continouswhite level

196.0(external static pressure(Pa))

(standard sound pressure 0.0002 µbar) (standard sound pressure 0.0002 µbar)

(standard sound pressure 0.0002 µbar) (standard sound pressure 0.0002 µbar)

MMD-AP0241H, AP0271H

Audibility limitsof continouswhite level

Audibility limitsof continouswhite level

Audibility limitsof continouswhite level

Octave band center frequency (Hz)

Octave band center frequency (Hz) Octave band center frequency (Hz)

Oct

ave

ban

d s

ound

pre

ssur

e le

vel (

dB

)

Oct

ave

ban

d s

ound

pre

ssur

e le

vel (

dB

)

Oct

ave

ban

d s

ound

pre

ssur

e le

vel (

dB

)

196.0(external static pressure(Pa))

196.0(external static pressure(Pa)) 196.0(external static pressure(Pa))

Outside still pressure

Overall level(dB)

68.6 (Pa)

33

46

A

C

137.2 (Pa)

37

51

196.0 (Pa)

40

53

(dB)

Outside still pressure

Overall level(dB)

68.6 (Pa)

33

47

A

C

137.2 (Pa)

37

49

196.0 (Pa)

40

53

(dB)

Outside still pressure

Overall level(dB)

68.6 (Pa)

36

50.5

A

C

137.2 (Pa)

40

53

196.0 (Pa)

44

57

(dB)

Outside still pressure

Overall level(dB)

68.6 (Pa)

36

50

A

C

137.2 (Pa)

40

53

196.0 (Pa)

44

57

(dB)

Page 157: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

152

14

MMD-AP0361H

Oct

ave

ban

d s

ound

pre

ssur

e le

vel (

dB

)

Octave band center frequency (Hz)

Audibility limitsof continouswhite level

196.0(external static pressure(Pa))

(dB)

(standard sound pressure 0.0002 µbar) (standard sound pressure 0.0002 µbar)

Oct

ave

ban

d s

ound

pre

ssur

e le

vel (

dB

)Octave band center frequency (Hz)

Audibility limitsof continouswhite level

196.0(external static pressure(Pa))

(standard sound pressure 0.0002 µbar)

Oct

ave

ban

d s

ound

pre

ssur

e le

vel (

dB

)

Octave band center frequency (Hz)

Audibility limitsof continouswhite level

196.0(external static pressure(Pa))

(standard sound pressure 0.0002 µbar)

Oct

ave

ban

d s

ound

pre

ssur

e le

vel (

dB

)

Octave band center frequency (Hz)

Audibility limitsof continouswhite level

196.0(external static pressure(Pa))

Outside still pressure

Overall level(dB)

68.6 (Pa)

36

49.5

A

C

137.2 (Pa)

40

54

196.0 (Pa)

44

59

Outside still pressure

Overall level(dB)

68.6 (Pa)

36

49

A

C

137.2 (Pa)

40

53.5

196.0 (Pa)

44

57

(dB)

Outside still pressure

Overall level(dB)

68.6 (Pa)

36

47

A

C

137.2 (Pa)

40

51

196.0 (Pa)

44

54

(dB)

Outside still pressure

Overall level(dB)

68.6 (Pa)

36

47

A

C

137.2 (Pa)

40

51

196.0 (Pa)

44

54

(dB)

Page 158: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

153

14

Sound level data (NC CURVE) Sound level values shown are based on a measurement in a non resound room.

MMD-AP0721H

Oct

ave

ban

d s

ound

pre

ssur

e le

vel (

dB

)

Octave band center frequency (Hz)

Audibility limitsof continouswhite level

Outside still pressure

Overall level(dB)

69 (Pa)

48

54

A

(50Hz)

C

137 (Pa)

49

55

196 (Pa)

50.5

57

Outside still pressure

Overall level(dB)

69 (Pa)

48

55

A

(60Hz)

C

137 (Pa)

49

50

196 (Pa)

50.5

58

Outside still pressure

Overall level(dB)

69 (Pa)

49

56

A

(50Hz)

C

137 (Pa)

50

59

196 (Pa)

51.5

61

Outside still pressure

Overall level(dB)

69 (Pa)

49

57

A

(60Hz)

C

137 (Pa)

50

59

196 (Pa)

51.5

61

MMD-AP0961H

Oct

ave

ban

d s

ound

pre

ssur

e le

vel (

dB

)

Oct

ave

ban

d s

ound

pre

ssur

e le

vel (

dB

)

Oct

ave

ban

d s

ound

pre

ssur

e le

vel (

dB

)

Octave band center frequency (Hz)

Octave band center frequency (Hz) Octave band center frequency (Hz)

Audibility limitsof continouswhite level

Audibility limitsof continouswhite level

Audibility limitsof continouswhite level

Page 159: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

154

10

20

30

40

50

60

70

80

90

NC-70

NC-60

NC-50

NC-40

NC-30

NC-20

20~

75

75~

150

150~

300

300~

600

600~

1200

1200~

2400

2400~

4800

4800~

9600

HML

10

20

30

40

50

60

70

80

90

NC-70

NC-60

NC-50

NC-40

NC-30

NC-20

20~

75

75~

150

150~

300

300~

600

600~

1200

1200~

2400

2400~

4800

4800~

9600

HML

10

20

30

40

50

60

70

80

90

NC-70

NC-60

NC-50

NC-40

NC-30

NC-20

20~

75

75~

150

150~

300

300~

600

600~

1200

1200~

2400

2400~

4800

4800~

9600

HML

10

20

30

40

50

60

70

80

90

NC-70

NC-60

NC-50

NC-40

NC-30

NC-20

20~

75

75~

150

150~

300

300~

600

600~

1200

1200~

2400

2400~

4800

4800~

9600

HML

10

20

30

40

50

60

70

80

90

NC-70

NC-60

NC-50

NC-40

NC-30

NC-20

20~

75

75~

150

150~

300

300~

600

600~

1200

1200~

2400

2400~

4800

4800~

9600

HML

Microphone

14

Sound level data (NC CURVE) Sound level values shown are based on a measurement in a non resound room.

MMC-AP0151HFan Tap

Sound pressurelevel(dB(A))

H

35

M

32

L

30

Oct

ave

ban

d s

ou

nd

pre

ssu

re le

vel (

dB

)

Octave band frequency (Hz)

Audibility limits ofcontinous white sound

MMC-AP0181HFan Tap

Sound pressurelevel(dB(A))

H

36

M

33

L

30

MMC-AP0241H,AP0271HFan Tap

Sound pressurelevel(dB(A))

H

38

M

36

L

33

MMC-AP0361HFan Tap

Sound pressurelevel(dB(A))

H

41

M

38

L

35

MMC-AP0481HFan Tap

Sound pressurelevel(dB(A))

H

43

M

40

L

37

Oct

ave

ban

d s

ou

nd

pre

ssu

re le

vel (

dB

)

Oct

ave

ban

d s

ou

nd

pre

ssu

re le

vel (

dB

)O

ctav

e b

and

so

un

d p

ress

ure

leve

l (d

B)

Oct

ave

ban

d s

ou

nd

pre

ssu

re le

vel (

dB

)

Octave band frequency (Hz) Octave band frequency (Hz)

Octave band frequency (Hz) Octave band frequency (Hz)

Audibility limits ofcontinous white sound

Audibility limits ofcontinous white sound

Audibility limits ofcontinous white sound

Audibility limits ofcontinous white sound

Page 160: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

155

NC-70

NC-60

NC-50

NC-40

NC-30

NC-20

MM

L

10

20

30

40

50

60

70

80

90

60 125 250 500 1000 2000 4000 8000

NC-70

NC-60

NC-50

NC-40

NC-30

NC-20

H

M

L

10

20

30

40

50

60

70

80

90

63 125 250 500 1000 2000 4000 8000

NC-70

NC-60

NC-50

NC-40

NC-30

NC-20

HM

L

10

20

30

40

50

60

70

80

90

63 125 250 500 1000 2000 4000 8000

Microphone

14

Sound level data (NC CURVE)

MMK-AP0071H, AP0091H, AP0121H

Oct

ave

ban

d

soun

d p

ress

ure

leve

l (d

B)

Octave band frequency (Hz)

Audibility limitsof continouswhite level

MMK-AP0151H, AP0181H

Oct

ave

ban

d

soun

d p

ress

ure

leve

l (d

B)

Octave band frequency (Hz)

Audibility limitsof continouswhite level

MMK-AP0241H

Oct

ave

ban

d

soun

d p

ress

ure

leve

l (d

B)

Octave band frequency (Hz)

Audibility limitsof continouswhite level

Fan TapSound pressure

level(dB(A))

H

39

M

34

L

31

Fan TapSound pressure

level(dB(A))

H

42

M

38

L

35

Fan TapSound pressure

level(dB(A))

H

42

M

38

L

35

Page 161: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

156

Microphone

14

MML-AP0071BH, AP0091BH, AP0121BH

Oct

ave

ban

d

soun

d p

ress

ure

leve

l (d

B)

Octave band center frequency (Hz)

Audibility limitsof continous white level

(standard sound pressure 0.0002 µbar)

Oct

ave

ban

d

soun

d p

ress

ure

leve

l (d

B)

Octave band center frequency (Hz)

Audibility limitsof continous white level

(standard sound pressure 0.0002 µbar)

MML-AP0151BH, AP0181BH

Oct

ave

ban

d

soun

d p

ress

ure

leve

l (d

B)

Octave band center frequency (Hz)

Audibility limitsof continous white level

(standard sound pressure 0.0002 µbar)

Oct

ave

ban

d

soun

d p

ress

ure

leve

l (d

B) (standard sound pressure 0.0002 µbar)

Octave band center frequency (Hz)

Audibility limitsof continous white level

Fan Tap

Overall level(dB)

H

36.0

41.7

A

50Hz

C

M

34.0

40.2

L

32.0

37.9

Fan Tap

Overall level(dB)

H

36.0

41.6

A

60Hz

C

M

34.0

39.8

L

32.0

38.1

Fan Tap

Overall level(dB)

H

36.0

41.4

A

50Hz

C

M

34.0

40.0

L

32.0

38.8

Fan Tap

Overall level(dB)

H

36.0

41.4

A

60Hz

C

M

34.0

40.0

L

32.0

39.0

Sound level data (NC CURVE) Sound level values shown are based on a measurement in a non resound room.

Page 162: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

157

14

MML-AP0241BH

Oct

ave

ban

d

soun

d p

ress

ure

leve

l (d

B)

Octave band center frequency (Hz)

Audibility limitsof continous white level

(standard sound pressure 0.0002 µbar)

Fan Tap

Overall level(dB)

H

42.0

46.4

A

50Hz

C

M

37.0

41.0

L

33.0

37.7

Oct

ave

ban

d

soun

d p

ress

ure

leve

l (d

B)

Octave band center frequency (Hz)

Audibility limitsof continous white level

(standard sound pressure 0.0002 µbar)

Fan Tap

Overall level(dB)

H

42.0

46.6

A

60Hz

C

M

37.0

41.0

L

33.0

38.0

Page 163: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

158

NC-70

NC-60

NC-50

NC-40

NC-30

NC-20

10

20

30

40

50

60

70

80

90

20~75 75~150 150~300 300~600 600~1200 1200~2400 2400~4800 4800~10000

Cooling

Heating

NC-70

NC-60

NC-50

NC-40

NC-30

NC-20

10

20

30

40

50

60

70

80

90

20~75 75~150 150~300 300~600 600~1200 1200~2400 2400~4800 4800~10000

Cooling

Heating

NC-70

NC-60

NC-50

NC-40

NC-30

NC-20

10

20

30

40

50

60

70

80

90

20~75 75~150 150~300 300~600 600~1200 1200~2400 2400~4800 4800~10000

Cooling

Heating

NC-70

NC-60

NC-50

NC-40

NC-30

NC-2010

20

30

40

50

60

70

80

90

20~75 75~150 150~300 300~600 600~1200 1200~2400 2400~4800 4800~10000

Cooling

Heating

NC-70

NC-60

NC-50

NC-40

NC-30

NC-20

10

20

30

40

50

60

70

80

90

20~75 75~150 150~300 300~600 600~1200 1200~2400 2400~4800 4800~10000

Cooling

Heating

Microphone

14

Sound level data (NC CURVE) Sound level values shown are based on a measurement in a non resound room.

MMY-MAP0501HT8, MAP0501HT7, MAP0501T8

Oct

ave

ban

d s

ou

nd

pre

ssu

re le

vel(d

B)

Octave band frequency(Hz)

Audibility limits ofcontinous white sound

Sound pressure Level (dB(A)) 55

Sound pressure Level (dB(A)) 56 Sound pressure Level (dB(A)) 57

Sound pressure Level (dB(A)) 58 Sound pressure Level (dB(A)) 59

MMY-MAP0601HT8, MAP0601HT7, MAP0601T8 MMY-MAP0801HT8, MAP0801HT7, MAP0801T8

MMY-MAP1001HT8, MAP1001HT7, MAP1001T8 MMY-MAP1201HT8, MAP1201HT7, MAP1201T8

Oct

ave

ban

d s

ou

nd

pre

ssu

re le

vel(d

B)

Octave band frequency(Hz)

Oct

ave

ban

d s

ou

nd

pre

ssu

re le

vel(d

B)

Octave band frequency(Hz)

Oct

ave

ban

d s

ou

nd

pre

ssu

re le

vel(d

B)

Octave band frequency(Hz)

Oct

ave

ban

d s

ou

nd

pre

ssu

re le

vel(d

B)

Octave band frequency(Hz)

Audibility limits ofcontinous white sound

Audibility limits ofcontinous white sound

Audibility limits ofcontinous white sound

Audibility limits ofcontinous white sound

Page 164: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

159

14

NC-70

NC-60

NC-50

NC-40

NC-30

NC-20

10

20

30

40

50

60

70

80

90

20~75 75~150 150~300 300~600 600~1200 1200~2400 2400~4800 4800~10000

Cooling

Heating

NC-70

NC-60

NC-50

NC-40

NC-30

NC-20

10

20

30

40

50

60

70

80

90

20~75 75~150 150~300 300~600 600~1200 1200~2400 2400~4800 4800~10000

Cooling

Heating

NC-70

NC-60

NC-50

NC-40

NC-30

NC-2010

20

30

40

50

60

70

80

90

20~75 75~150 150~300 300~600 600~1200 1200~2400 2400~4800 4800~10000

Cooling

Heating

NC-70

NC-60

NC-50

NC-40

NC-30

NC-2010

20

30

40

50

60

70

80

90

20~75 75~150 150~300 300~600 600~1200 1200~2400 2400~4800 4800~10000

Cooling

Heating

NC-70

NC-60

NC-50

NC-40

NC-30

NC-2010

20

30

40

50

60

70

80

90

20~75 75~150 150~300 300~600 600~1200 1200~2400 2400~4800 4800~10000

Cooling

Heating

NC-70

NC-60

NC-50

NC-40

NC-30

NC-20

10

20

30

40

50

60

70

80

90

20~75 75~150 150~300 300~600 600~1200 1200~2400 2400~4800 4800~10000

Cooling

Heating

Sound level data (NC CURVE) Sound level values shown are based on a measurement in a non resound room.

MMY-AP1401HT8, AP1401HT7, AP1401T8

Oct

ave

ban

d s

ou

nd

pre

ssu

re le

vel(d

B)

Octave band frequency(Hz)

Audibility limits ofcontinous white sound

Sound pressure Level (dB(A)) 59.5

MMY-AP1601HT8, AP1601HT7, AP1601T8

Oct

ave

ban

d s

ou

nd

pre

ssu

re le

vel(d

B)

Octave band frequency(Hz)

Audibility limits ofcontinous white sound

Sound pressure Level (dB(A)) 60

MMY-AP1801HT8, AP1801HT7, MAP1801T8 MMY-AP2001HT8, AP2001HT7, AP2001T8

Sound pressure Level (dB(A)) 60.5 Sound pressure Level (dB(A)) 61

Oct

ave

ban

d s

ou

nd

pre

ssu

re le

vel(d

B)

Oct

ave

ban

d s

ou

nd

pre

ssu

re le

vel(d

B)

Octave band frequency(Hz) Octave band frequency(Hz)

Audibility limits ofcontinous white sound

Audibility limits ofcontinous white sound

Audibility limits ofcontinous white sound

Audibility limits ofcontinous white sound

MMY-AP2201HT8, AP2201HT7, AP2201T8 MMY-AP2211HT8, AP2211HT7, AP2211T8

Sound pressure Level (dB(A)) 61.5 Sound pressure Level (dB(A)) 61.5

Oct

ave

ban

d s

ou

nd

pre

ssu

re le

vel(d

B)

Octave band frequency(Hz)

Oct

ave

ban

d s

ou

nd

pre

ssu

re le

vel(d

B)

Octave band frequency(Hz)

Page 165: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

160

NC-70

NC-60

NC-50

NC-40

NC-30

NC-2010

20

30

40

50

60

70

80

90

20~75 75~150 150~300 300~600 600~1200 1200~2400 2400~4800 4800~10000

Cooling

Heating

NC-70

NC-60

NC-50

NC-40

NC-30

NC-2010

20

30

40

50

60

70

80

90

20~75 75~150 150~300 300~600 600~1200 1200~2400 2400~4800 4800~10000

Cooling

Heating

NC-70

NC-60

NC-50

NC-40

NC-30

NC-2010

20

30

40

50

60

70

80

90

20~75 75~150 150~300 300~600 600~1200 1200~2400 2400~4800 4800~10000

Cooling

Heating

NC-70

NC-60

NC-50

NC-40

NC-30

NC-2010

20

30

40

50

60

70

80

90

20~75 75~150 150~300 300~600 600~1200 1200~2400 2400~4800 4800~10000

Cooling

Heating

NC-70

NC-60

NC-50

NC-40

NC-30

NC-2010

20

30

40

50

60

70

80

90

20~75 75~150 150~300 300~600 600~1200 1200~2400 2400~4800 4800~10000

Cooling

Heating

14

Sound level data (NC CURVE) Sound level values shown are based on a measurement in a non resound room.

MMY-AP2401HT8, AP2401HT7, AP2401T8

Oct

ave

ban

d s

ou

nd

pre

ssu

re le

vel(d

B)

Octave band frequency(Hz)

Audibility limits ofcontinous white sound

Sound pressure Level (dB(A)) 62

MMY-AP2411HT8, AP2411HT7, AP2411T8

MMY-AP2601HT8, AP2601HT7, AP2601T8 MMY-AP2801HT8, AP2801HT7, AP2801T8

MMY-AP3001HT8, AP3001HT7, AP3001T8

Sound pressure Level (dB(A)) 62

Sound pressure Level (dB(A)) 62 Sound pressure Level (dB(A)) 62.5

Sound pressure Level (dB(A)) 63

Oct

ave

ban

d s

ou

nd

pre

ssu

re le

vel(d

B)

Oct

ave

ban

d s

ou

nd

pre

ssu

re le

vel(d

B)

Oct

ave

ban

d s

ou

nd

pre

ssu

re le

vel(d

B)

Oct

ave

ban

d s

ou

nd

pre

ssu

re le

vel(d

B)

Octave band frequency(Hz)

Octave band frequency(Hz) Octave band frequency(Hz)

Octave band frequency(Hz)

Audibility limits ofcontinous white sound

Audibility limits ofcontinous white sound

Audibility limits ofcontinous white sound

Audibility limits ofcontinous white sound

Page 166: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

161

NC-70

NC-60

NC-50

NC-40

NC-30

NC-20

10

20

30

40

50

60

70

80

90

20~75 75~150 150~300 300~600 600~1200 1200~2400 2400~4800 4800~10000

Cooling

Heating

NC-70

NC-60

NC-50

NC-40

NC-30

NC-2010

20

30

40

50

60

70

80

90

20~75 75~150 150~300 300~600 600~1200 1200~2400 2400~4800 4800~10000

Cooling

Heating

NC-70

NC-60

NC-50

NC-40

NC-30

NC-2010

20

30

40

50

60

70

80

90

20~75 75~150 150~300 300~600 600~1200 1200~2400 2400~4800 4800~10000

Cooling

Heating

NC-70

NC-60

NC-50

NC-40

NC-30

NC-2010

20

30

40

50

60

70

80

90

20~75 75~150 150~300 300~600 600~1200 1200~2400 2400~4800 4800~10000

Cooling

Heating

NC-70

NC-60

NC-50

NC-40

NC-30

NC-2010

20

30

40

50

60

70

80

90

20~75 75~150 150~300 300~600 600~1200 1200~2400 2400~4800 4800~10000

Cooling

Heating

NC-70

NC-60

NC-50

NC-40

NC-30

NC-2010

20

30

40

50

60

70

80

90

20~75 75~150 150~300 300~600 600~1200 1200~2400 2400~4800 4800~10000

Cooling

Heating

14

Sound level data (NC CURVE) Sound level values shown are based on a measurement in a non resound room.

MMY-AP3201HT8, AP3201HT7, AP3201T8

Oct

ave

ban

d s

ou

nd

pre

ssu

re le

vel(d

B)

Octave band frequency(Hz)

Audibility limits ofcontinous white sound

Sound pressure Level (dB(A)) 63

MMY-AP3211HT8, AP3211HT7, AP3211T8

MMY-AP3401HT8, AP3401HT7, AP3401T8 MMY-AP3411HT8, AP3411HT7, AP3411T8

MMY-AP3601HT8, AP3601HT7, AP3601T8 MMY-AP3611HT8, AP3611HT7, AP3611T8

Sound pressure Level (dB(A)) 63

Sound pressure Level (dB(A)) 63.5 Sound pressure Level (dB(A)) 63.5

Sound pressure Level (dB(A)) 63.5 Sound pressure Level (dB(A)) 64

Oct

ave

ban

d s

ou

nd

pre

ssu

re le

vel(d

B)

Oct

ave

ban

d s

ou

nd

pre

ssu

re le

vel(d

B)

Oct

ave

ban

d s

ou

nd

pre

ssu

re le

vel(d

B)

Oct

ave

ban

d s

ou

nd

pre

ssu

re le

vel(d

B)

Oct

ave

ban

d s

ou

nd

pre

ssu

re le

vel(d

B)

Octave band frequency(Hz)

Octave band frequency(Hz) Octave band frequency(Hz)

Octave band frequency(Hz) Octave band frequency(Hz)

Audibility limits ofcontinous white sound

Audibility limits ofcontinous white sound

Audibility limits ofcontinous white sound

Audibility limits ofcontinous white sound

Audibility limits ofcontinous white sound

Page 167: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

162

NC-70

NC-60

NC-50

NC-40

NC-30

NC-2010

20

30

40

50

60

70

80

90

20~75 75~150 150~300 300~600 600~1200 1200~2400 2400~4800 4800~10000

Cooling

Heating

NC-70

NC-60

NC-50

NC-40

NC-30

NC-2010

20

30

40

50

60

70

80

90

20~75 75~150 150~300 300~600 600~1200 1200~2400 2400~4800 4800~10000

Cooling

Heating

NC-70

NC-60

NC-50

NC-40

NC-30

NC-2010

20

30

40

50

60

70

80

90

20~75 75~150 150~300 300~600 600~1200 1200~2400 2400~4800 4800~10000

Cooling

Heating

NC-70

NC-60

NC-50

NC-40

NC-30

NC-2010

20

30

40

50

60

70

80

90

20~75 75~150 150~300 300~600 600~1200 1200~2400 2400~4800 4800~10000

Cooling

Heating

NC-70

NC-60

NC-50

NC-40

NC-30

NC-2010

20

30

40

50

60

70

80

90

20~75 75~150 150~300 300~600 600~1200 1200~2400 2400~4800 4800~10000

Cooling

Heating

NC-70

NC-60

NC-50

NC-40

NC-30

NC-2010

20

30

40

50

60

70

80

90

20~75 75~150 150~300 300~600 600~1200 1200~2400 2400~4800 4800~10000

Cooling

Heating

14

Sound level data (NC CURVE) Sound level values shown are based on a measurement in a non resound room.

MMY-AP3801HT8, AP3801HT7, AP3801T8

Oct

ave

ban

d s

ou

nd

pre

ssu

re le

vel(d

B)

Octave band frequency(Hz)

Audibility limits ofcontinous white sound

Sound pressure Level (dB(A)) 64

MMY-AP4001HT8, AP4001HT7, AP4001T8

Sound pressure Level (dB(A)) 64

MMY-AP4201HT8, AP4201HT7, AP4201T8

Sound pressure Level (dB(A)) 64.5

MMY-AP4401HT8, AP4401HT7, AP4401T8

Sound pressure Level (dB(A)) 64.5

MMY-AP4601HT8, AP4601HT7, AP4601T8

Sound pressure Level (dB(A)) 65

MMY-AP4801HT8, AP4801HT7, AP4801T8

Sound pressure Level (dB(A)) 65

Oct

ave

ban

d s

ou

nd

pre

ssu

re le

vel(d

B)

Octave band frequency(Hz)

Audibility limits ofcontinous white sound

Oct

ave

ban

d s

ou

nd

pre

ssu

re le

vel(d

B)

Octave band frequency(Hz)

Audibility limits ofcontinous white sound

Oct

ave

ban

d s

ou

nd

pre

ssu

re le

vel(d

B)

Octave band frequency(Hz)

Audibility limits ofcontinous white sound

Oct

ave

ban

d s

ou

nd

pre

ssu

re le

vel(d

B)

Octave band frequency(Hz)

Audibility limits ofcontinous white sound

Oct

ave

ban

d s

ou

nd

pre

ssu

re le

vel(d

B)

Octave band frequency(Hz)

Audibility limits ofcontinous white sound

Page 168: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

163

Dimensional drawing

15

Page 169: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

164

Foreword

Page 170: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

165

15 ForewordDimensional drawing

15

200

200

Check port( 450)

Check port( 450)

Electric parts box

Z35.o.

105

105

B97

16120

4 2.7

120

57188

64

57.525

360

415

381.6

840 840

30

1000 or more

1000

or

mor

e15

or

mor

e

15 o

r m

ore

1000 or more

250 70270

35 210

45 113

174

130

A

88

227480

346.

5

254.

5 950

pane

l ext

erna

l dim

ensi

on

790

hang

ing

bolt

pitc

h

723 hanging bolt pitch

950panel external dimension

Suction grille (Air suction port)

Air discharge port (4-way)

860 to 910ceiling open dimension

860

to 9

10ce

iling

ope

n di

men

sion

Hanging boltM10 or W3/8 local arrange

Bottom face of ceiling Bottom face of ceiling

For branch duct knockout square hole O/ 150 (2 positions at right side)

Refrigerant pipe connecting port(Gas)Refrigerant pipe connecting port(Liquid)

Drain discharge port

Indoor unit Bottom face of ceiling

Bottom face of ceiling

Knockout for flesh air intakeFor O/ 100

Sta

nd-u

p85

0 or

less

Sta

nd-u

p64

0 or

less

Indoor unit4-way Air Discharge Cassette Type

MMU-AP0091H to P0561H

Z view Drain-up standing-up size Space required for installation and servicing

(NOTE)As ABS is used for the drain dis-chargeport of the main unit, the vinyl chloridepaste cannot be used.Use the flexible hose (Band fix)included in the package.

ModelAP0091H to AP0301HAP0361H to AP0561H

A250319

B120183

mm

Wired remote controller RBC-AMT21E RBC-AMT31ESimple wired remote controller RBC-AS21E RBC-AS21E2Wireless remote controller kit TCB-AX21U(W)-E TCB-AX21U(W)-E2Weekly timer application RBC-AMT31E and RBC-EXW21E2

Page 171: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

166

15

Electric parts box

Z

53

60

30

95 35

265

1000

100

75 55

56

222 39

8

156

8

650

Center of main unit Center of panel

Unit external dimension830

Hanging bolt pitch880

Ceiling open dimension960

Panel external dimension1000

Han

ging

bol

tpi

tch

480

Uni

t ext

erna

ldi

men

sion

550

Cei

ling

open

dim

ensi

on 6

20P

anel

ext

erna

ldi

men

sion

650

Air discharge port(2-way)

Air discharge port(2-way)

1000 or more

Ceiling

1000or more

5mmor more

1000or moreObstruction

Hanging bolt4-M10 procured locally

Branch duct knockout hole(Also on opposite side)

Ceiling panel(Procured by locally) Bottom face of ceiling

O/ 200

508m

m o

r le

ss

160m

m o

r le

ss

100mmor less

Bottom face of ceiling

Indoor unit

Power supply connecting port

178

242

282

348

35

78 35

210 Knockout hole for taking-in air(Only at reverse side)

Refrigerant pipe connecting port(Gas side O/ 9.5)

Refrigerant pipe connecting port(Liquid side O/ 6.4)

Drain pipe connecting portInner O/ 32, Nominal O/ 25 for vinyl chloride pipe

Pour water port

O/ 150

2-way Air Discharge Cassette Type

MMU-AP0071WH, AP0091WH, AP0121WH

Z view

Space required for installation and servicing

Wired remote controller RBC-AMT21E RBC-AMT31ESimple wired remote controller RBC-AS21E RBC-AS21E2Wireless remote controller kit TCB-AX21E TCB-AX21E2Weekly timer application RBC-AMT31E and RBC-EXW21E2

Page 172: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

167

Foreword

15

Power supply connecting port

Branch duct knockout hole(Also on opposite side)

650

35 95

30

Z53

¯ 20060

295

222 39

8

156

8

178

242

282

348

35

75 55

56

100

78 35

210

Center of main unit

1000 or more

Center of panel

Electric parts box

Unit external dimension 1350

Hanging bolt pitch 1400

Ceiling open dimension 1480

Ceiling 1000or more

5mm

or

mor

e

Panel external dimension 1520

1000or more

Han

ging

bol

tpi

tch

480

Uni

t ext

erna

ldi

men

sion

550

Cei

ling

open

imen

sion

620

Pan

el e

xter

nal

dim

ensi

on 6

50

Air suction port(2-way)

Air discharge port(2-way)

Obstruction

Hanging bolt4-M10 procured locally

Ceiling panel(Procured locally)

Bottom face of ceiling

508m

m o

r le

ss

160m

m o

r le

ss

100mmor less

Bottom face of ceiling

Knockout hole for taking-in air(Only at reverse side)

Refrigerant pipe connecting port(Gas side O/ B)

Refrigerant pipe connecting port(Liquid side O/ A)

Drain pipe connecting portInner O/ 3̄2, Nominal O/ 25 for vinyl chloride pipe

Pour water port

¯ 150

MMU-AP0151WH, AP0181WH, AP0241WH, AP0271WH, AP0301WH

Z view

Space required for installation and servicing

ModelMMU-AP0151WH to AP0181WHMMU-AP0241WH to AP0301WH

AO/ 6.4O/ 9.5

BO/ 12.7O/ 15.9

Wired remote controller RBC-AMT21E RBC-AMT31ESimple wired remote controller RBC-AS21E RBC-AS21E2Wireless remote controller kit TCB-AX21E TCB-AX21E2Weekly timer application RBC-AMT31E and RBC-EXW21E2

Page 173: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

168

Air suction port(2-way)

Air discharge port(2-way)Electric parts box

95

Z

230 40

6 60

8

166 68

455 150

5 105

680

1898

16120

4 2.7

120

Center of main unit Center of panel

Unit external dimension 1650

Hanging bolt pitch 1700

Ceiling open dimension 1850

Panel external dimension 1898

5mm

or

mor

e

Han

ging

bol

tpi

tch

510

Uni

t ext

erna

ldi

men

sion

620

Cei

ling

open

dim

ensi

on 6

50P

anel

ext

erna

ldi

men

sion

680

1000 or more

Ceiling 1000or more

1000or moreObstruction

Hanging bolt4-M10 procured locally

Ceiling panel(Procured locally)

Branch duct knockout hole(Also on reverse side)

Bottom face of ceiling

¯20

0

¯20

0

516m

m o

r le

ss

160m

m o

r le

ss

Bottom face of ceiling

100mmor less

Power supply connecting port

186

250

290

356

15

75 55

56

100

86

15

Knockout hole for taking-in air(Only at reverse side)

210

Refrigerant pipe connecting port(Gas side O/ 15.9)

Refrigerant pipe connecting port(Liquid side O/ 9.5)

Drain pipe connecting port(VP25)

Pour water port

¯ 150

15

MMU-AP0481WH

Z view

Space required for installation and servicing

Wired remote controller RBC-AMT21E RBC-AMT31ESimple wired remote controller RBC-AS21E RBC-AS21E2Wireless remote controller kit TCB-AX21E TCB-AX21E2Weekly timer application RBC-AMT31E and RBC-EXW21E2

Page 174: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

169

16

4 2.7

120

120

Panel external dimension 1050

Ceiling open dimension 1010

Pan

el e

xter

nal

dim

ensi

on47

0

Cei

ling

open

dim

ensi

on43

020

20

Center of panelDrain pipe connecting port(VP25)

Power supply connecting port

Hanging bolt4-M10 procured locally

Supportmetal

Ceiling panelProcured by locally

Bottom face of ceilingAir discharge portDischarge louver

Refrigerant pipe connecting port(Gas side) 9.5

Refrigerant pipe connecting port(Liquid side) 6.4

Panel mounting hole5 positions

Air suction port

100 or more 100 or more 200 or more

Bor

mor

e

15

1-way Air Discharge Cassette Type

MMU-AP0071YH, AP0091YH, AP0121YH

Space required for installation and servicing

Model MMU-

AP0071YH, AP0091YH, AP0121YH

A

235

B

245

C

200

Dimensions

Wired remote controller RBC-AMT21E RBC-AMT31ESimple wired remote controller RBC-AS21E RBC-AS21E2Wireless remote controller kit TCB-AX21E TCB-AX21E2Weekly timer application RBC-AMT31E and RBC-EXW21E2

Page 175: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

170

16

4 2.7

180

150 knockout hole (For air intake)

96

30

530

655

20 30

20 3016

012

0

100

30

125DC65

50 E F 110

G

Panel external dimension ACeiling open dimension B

Center of panel

Cei

ling

open

dim

ensi

on 6

95P

anel

ext

erna

ldi

men

sion

755

Pitch 200 N10 10255

Z

Z

Knockout hole for discharge forward

8080 60

100

100 100H

130

198

10

A

Suction port

755

Air discharge port

Power supply connecting port

335440

Drain pipe connecting port(VP25)

Refrigerant pipe connecting port(Liquid side) I

Refrigerant pipe connecting port(Gas side) J

ObstacleCeiling

200

or m

ore

1000 or more

120

120

1000 or more

1000 or more

15

MMU-AP0151SH, AP0181SH, AP0241SH

Space required for installation and servicing

Dimensions

Model MMU-

AP0151SH, AP0181SH

AP0241SH

A

1220

1420

B

1160

1360

C

545

645

D

485

585

E

530

630

F

470

570

G

254

460

H

800

1000

I

6.4

9.5

J

12.7

15.9

N

4

5

Z view

Wired remote controller RBC-AMT21E RBC-AMT31ESimple wired remote controller RBC-AS21E RBC-AS21E2Wireless remote controller kit TCB-AX21E TCB-AX21E2Weekly timer application RBC-AMT31E and RBC-EXW21E2

Page 176: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

171

O/125 knockout hole(For air intake)

10-O/ 4 tapping screw O/ 160

100mm or less

Panel C, L

150

91

550m

m o

r les

s

271m

m o

r les

s

450mm

Air outlet

Check port B

450mmCheck port A

Air filter700mm for maintenance of air filter 700mm for

maintenance of air filter

Ceiling opening part

(150mm)

300m

m

O/ 26 power supply, remote controller wires drawing-out port

Ceiling opendimension D

E

Air Suction

B

C 142

70 to

270

240

Drain pipe connecting port(Inner O/ 32 vinyl chloride pipe VP25 connection)

Hanging bolt 4-M10 (Procured locally)

Refrigerant pipe connecting port(Gas side O/ F)

Refrigerant pipe connecting port(Liquid side O/ G)

Unit external dimension 800

Hanging bolt pitch 700

Hanging bolt pitch A 7.5

44

50 638498

41 59

25 40

49(Whe

n at

tach

ing

dire

ctly

)

Ceiling opening470

393

196

50 50 24313

1

41

21

5 AirDischarge

AirSuction

15

Concealed Duct Standard Type

MMD-AP0071BH, AP0091BH, AP0121BH, AP0151BH, AP0181BH, AP0241BH,AP0271BH, AP0301BH, AP0361BH, AP0481BH, AP0561BH

(Note)Two of f high efficiency filters available.Deodorant filter not available.

(Note)Be sure to create a check port at position A as indicatedin the following figure. This is for maintenance of the equipment.

Drain-up piping

Model MMD-

AP0071BH, AP0091BH, AP0121BH

AP0151BH, AP0181BH

AP0241BH, AP0271BH, AP0301BH

AP0361BH, AP0481BH, AP0561BH

A61676610661416

B55070010001350

C3505008001150

D60075010501400

E4706209201270

F9.512.715.915.9

G6.49.49.59.5

Wired remote controller RBC-AMT21E RBC-AMT31ESimple wired remote controller RBC-AS21E RBC-AS21E2Wireless remote controller kit TCB-AX21E TCB-AX21E2Weekly timer application RBC-AMT31E and RBC-EXW21E2

Page 177: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

172

624698

31

470

406

35

150

200

370

65Hole for hanging bolt(4-O/ 12 x 72)

Electric parts box

Electric parts box

Power supply/communicationpiping port (O/ 26)(Under electric parts box)

Refrigerant pipe connecting port(Gas side O/ B)

Refrigerant pipe connecting port(Gas side O/ A)

710

(Han

ging

bol

t mou

ntin

g pi

tch

800)

1380

100

1260

(Han

ging

bol

t mou

ntin

g pi

tch)

1288(Hanging bolt mounting pitch)

1328

1250

45

190 250 250 250

250 250 250 250 190

250

Power supply/communicationpiping port (O/ 26)(Under electric parts box)

Refrigerant pipe connecting port(Liquid side O/ A)

Refrigerant pipe connecting port(Liquid side O/ 12.7)

Screw hole for duct mounting (6-M6)

Air suction port

Screw hole for duct mounting (10-M6)

Screw hole for duct mounting (10-M6)

Drain pipe connecting port (VP25)

Drain pipe connecting port (VP25)

Z view Z view

Z view

Air discharge port

Suction port

Discharge port

Screw hole for duct mounting (4-M6)

Screw hole for duct mounting (6-M6)

Hole for hanging bolt(4-O/ 12 x 72)

Long hole for hanging bolt(4-O/ 12 92)

Electric parts box

Refrigerant pipe connecting port(Gas side O/ 15.9)

Refrigerant pipe connecting port(Liquid side O/ 9.5)

Screw hole for duct mounting (8-M6) Air suction port

Drain pipe connectingport (VP25)

Air discharge portScrew hole for duct mounting (8-M6)

16

4 2.7

120

120

500

mm

or

mor

e60

0 m

mor

mor

e

Check port 600

Service space

Service space

Air discharge port

15

Concealed Duct High Static Pressure Type

MMD-AP0181H, AP0241H, AP0271H, AP0361H, AP0481H, AP0721H, AP0961H

MMD-AP0181H to AP0361H MMD-AP0481H

Model MMD- AP0181H AP0241H, AP0271H, AP0361H, AP0481H

A6.49.5

B12.715.9

MMD-AP0721H, AP0961H

AP0181H to AP0271H type AP0361H type

*1 Service space requirement for MMD-AP0721H and AP0961H aredifferent from those in the above figure. For details make enquiries

to your dealer.

Space required for installation and servicing *1

Model MMD-

AP0721H

AP0961H

Gas pipe O/ A

O/ 22.2

O/ 22.2

Wired remote controller RBC-AMT21E RBC-AMT31ESimple wired remote controller RBC-AS21E RBC-AS21E2Wireless remote controller kit TCB-AX21E TCB-AX21E2Weekly timer application RBC-AMT31E and RBC-EXW21E2

Page 178: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

173

Remote controller piping taking-in port (Knockout hole)

Upper piping drawing-out port (Knockout)

Power supply cable taking-in port (Knockout)

Left drain size

B (Hanging position)

500

or m

ore

Refrigerant pipe (Liquid side O/ D)

Refrigerant pipe (Gas side O/ C)

Drain pipe connecting port

Piping drawing-out port (Knockout port)

Drain port VP20 (Inner diam. O/ 26, hose supplied)

Wireless sensor mounting section(Optional)

250 or more250 or more

(Han

ging

pos

ition

)

320

170

70

16

4 2.7

120

120

Piping hole on the wall (O/ 100 hole)

Drain left piping drawing-out port (Knockout)

Air taking-in port (Duct sold separately) (Knockout hole O/ 92)

Remote controller cable taking-in port

Power supply taking-in port (Knockout hole)

Remote controller cable taking-in port (Knockout)

(Front side to be positioned horizontally.)

Hanging bolt

Ceiling surface

With

in 5

0

Unit

A

15

Under Ceiling Type

MMC-AP0151H, AP0181H, AP0241H, AP0271H, AP0361H, AP0481H

Space required for installation and servicing

Model MMC-

AP0151H, AP0181H

AP0241H to AP0271H

AP0361H, AP0481H

A

910

1180

1595

B

855

1125

1540

C

12.7

15.9

15.9

D

6.4

9.5

9.5

Wired remote controller RBC-AMT21E RBC-AMT31ESimple wired remote controller RBC-AS21E RBC-AS21E2Wireless remote controller kit RBC-AX22CE RBC-AX22CE2Weekly timer application RBC-AMT31E and RBC-EXW21E2

Page 179: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

174

9.5

690 (Installation plate)

Upper end of installation plate

Discharge port(Air direction upward/downward/leftward/rightward are adjustable.)

Air suction port

Gas pipe 440Liquid pipe 540Drain pipe 560

Long hole for wooden screw15-6 x 30

Hole for anchor bolt10-10 x 20 long hole

16

4 2.7

120

120

Piping port from left/right sides(Knockout)

(Including installation plate)210

Including installation plate (Accessory)

Earth screw (M4)(Inside of electric parts box)

Refrigerant pipe connecting portGas side O/ 9.5

Refrigerant pipe connecting portLiquid side O/ 6.4

Drain pipe connecting port

300 or more 300 or more

30 o

r m

ore

At shipment(When drawing pipe from left)

15

High Wall Type

MMK-AP0071H, AP0091H, AP0121H

Position of holes on the installation plate.

Space required for service

Wired remote controller RBC-AMT21E RBC-AMT31ESimple wired remote controller RBC-AS21E RBC-AS21E2Wireless remote controller kit TCB-AX21E TCB-AX21E2Weekly timer application RBC-AMT31E and RBC-EXW21E2

Page 180: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

175

690 (Installation plate)182.5 182.5

Upper end of installation plate

Gas pipe 440Liquid pipe 540Drain pipe 560

At shipment(When drawing pipe from left)

hole for wooden screw15-6 x 30

Hole for anchor bolt10-10 x 20 long hole

Piping port from left/right sides(Knockout)

(Including installation plate)210

Including installation plate (Accessory)

Earth screw (M4)(Inside of electric parts box)

Refrigerant pipe connecting portGas side O/ 12.7

Refrigerant pipe connecting portLiquid side O/ 6.4

Drain pipe connecting port

300 or more 300 or more

30 o

r m

ore

Air discharge port(Air direction upward/downward/leftward/rightward is adjustable.)

Air suction port

15

MMK-AP0151H, AP0181H

Position of holes on the installation plate

Space required for service

Wired remote controller RBC-AMT21E RBC-AMT31ESimple wired remote controller RBC-AS21E RBC-AS21E2Wireless remote controller kit TCB-AX21E TCB-AX21E2Weekly timer application RBC-AMT31E and RBC-EXW21E2

Page 181: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

176

1090 (Installation plate)170 170

Upper end of installation plate

Air discharge port (Air direction upward/downward/leftward/rightward are adjustable.)

Air suction port

Gas pipe 440Liquid pipe 540Drain pipe 560

At shipment(When drawing pipe from left)

hole for wooden screw21-6 x 30 Hole for anchor bolt

16-10 x 20 long hole

Piping port from left/right sides(Knockout)

(Including installation plate)210

Including installation plate (Accessory)

Earth screw (M4)(Inside of electric parts box)

Refrigerant pipe connecting portGas side O/ 15.9

Refrigerant pipe connecting portLiquid side O/ 9.5

Drain pipe connecting port

300 or more 300 or more

30 o

r m

ore

15

MMK-AP0241H

Position of holes on the installation plate

Space required for serviceWired remote controller RBC-AMT21E RBC-AMT31ESimple wired remote controller RBC-AS21E RBC-AS21E2Wireless remote controller kit TCB-AX21E TCB-AX21E2Weekly timer application RBC-AMT31E and RBC-EXW21E2

Page 182: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

177

130

Fixing hole (Floor)(2-O/ 10)

Lower refrigerant piping port(50 x 100 knockout hole)

Operation switch section (Sold separately)

Fixing hole (Floor)(Two off knockout holes O/ 10-O/ 20)

Air suction port

100left side( )

Power supply cord hole(O/ 26 knockout on both sides)

Earth screw (M6)

Refrigerant pipe port(O/ 130 knockout hole)

Refrigerant pipe port(50 x 100 knockout hole)

Hole fixing wall(2-10 x 24 long hole)

1000

or

mor

e

Drain pipe connecting port (O/ 20)

Refrigerant pipe connecting port(Liquid side O/ B)

Refrigerant pipe connecting port(Gas side O/ A)

Wall

Wall(Front side)

(Front side)

500or more 30

0or

mor

e

Air discharge port

15

Floor Standing Cabinet Type

MML-AP0071H, AP0091H, AP0121H, AP0151H, AP0181H, AP0241H

Positionaldrawing of piping

Model MMC-

AP0071H, AP0091H, AP0121H

AP0151H, AP0181H

AP0241H

A

O/ 9.5

O/ 12.7

O/ 15.9

B

O/ 6.4

O/ 6.4

O/ 9.5

Dimensions

Space required for serviceFigure shows piping at the left side

Wired remote controller RBC-AMT21E RBC-AMT31ESimple wired remote controller RBC-AS21E RBC-AS21E2Wireless remote controller kit TCB-AX21E TCB-AX21E2Weekly timer application RBC-AMT31E and RBC-EXW21E2

Page 183: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

178

(Service space)

150or more

(Service space)

150or more

Fixing hole (Floor) (Discharge port size in flange)

Ceiling board section

(Air discharge port size in flange)

No. Name

G-O/ 4.7 hole(Front side and rear side each)

4-O/ 15 hole(For mounting rear side)

Expansionvalve box

2-O/ 4.7 hole (Left/right side each)

2-12 x 18 holeFixing hole (floor)

16

4 2.7

120

120

15

Floor Standing Concealed Type

MML-AP0071BH, AP0091BH, AP0121BH, AP0151BH, AP0181BH, AP0241BH

Model MML-

AP0071BH, AP0091BH, AP0121BH

AP0151BH, AP0181BH

AP0241BH

A

610

910

B

580

880

C

550

850

D

4

7

E

6.4

9.5

F

9.5

12.7

15.9

G

5

8

DimensionsPipe connecting port at liquid side (O/ E)

Pipe connecting port at gas side (O/ F)

Drain pipe connecting port (20A)

Air filter

Electric parts box(Earth terminal is on the inside)

Wired remote controller RBC-AMT21E RBC-AMT31ESimple wired remote controller RBC-AS21E RBC-AS21E2Weekly timer application RBC-AMT31E and RBC-EXW21E2

Page 184: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

179

Installation plate

Installation plate

Suction port

Drainhose

Refrigerant piping hole (Back side)(O/ 130 Knockout)

Refrigerant piping hole (Bottom side)(50 x 120 Knockout)

Earth screw (M4)

Dischargeport 80

30 x 3 30 x 3600

Wall

Wall

Wall

Wall

Wall

Floor

Wall

Incase of installing distance is 50mm from wall( )

Lower refrigerant piping port(50 x 120 Knockout hole)

Controlpart

Controlcover

Refrigerant piping port (Both side)(O/ 80 Knockout)

a b

In c

ase

1770

a

In c

ase

1773

b

( )4- lower hole For M8 Screw bolt or M8 Anchor bolt

( )2- lower hole For M8 Screw bolt or M8 Anchor bolt

Front

Fro

nt

Mor

e th

an10

00

Mor

e th

an20

0

Morethan500

Refrigerant piping joint (Gas side A)

Refrigerant piping joint (Liquid side B)

50 x 120 (Square)(For under surface piping)O/ 130 Knockout

(For backside piping)

15

Floor Standing Type

MMF-AP0151H, AP0181H, AP0241H, AP0271H

Dimensions

Model

MMF-AP0151H, AP0181H

MMF-AP0241H, AP0271H

A

O/ 12.7

O/ 15.7

B

O/ 6.4

O/ 9.5

Details of hole for back side piping Details of hole for lower side piping

Refrigerant piping position

Space required for service(In case of right side piping )

Wired remote controller RBC-AMT21E RBC-AMT31ESimple wired remote controller RBC-AS21E RBC-AS21E2Wireless remote controller kit TCB-AX21E TCB-AX21E2Weekly timer application RBC-AMT31E and RBC-EXW21E2

Page 185: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

180

Installation plate

Dischargeport 80

30 x 3 30 x 3600

Wall

Wall

Incase of installing distance is 50mm from wall( )

Lower refrigerant piping port(50 x 120 Knockout)

Controlpart

Controlcover

Installation plate

Suction portDtain hose

Drain hose

Refrigerant piping hole (Back side)(O/ 130 Knockout)

Refrigerant piping hole (Bottom side)(50 x 120 Knockout)

Earth screw (M4)

Refrigerant piping port (Both side)(O/ 80 Knockout)

Wall

Wall

Wall

Wall

Front

Fro

nt

Mor

e th

an10

00

Mor

e th

an 2

00

Morethan500

Refrigerant piping joint (Gas side O/ 19)

Refrigerant piping joint (Liquid side O/ 9.5)

Gas side

Liquidside

( )4- lower hole For M8 Screw bolt or M8 Anchor bolt

( )2- lower hole For M8 Screw bolt or M8 Anchor bolt

50 x 120 (Square)(For under surface piping)

O/ 130 Knockout(For backside piping)

Floor

a b

In c

ase

1770

a

In c

ase

1773

b

15

MMF-AP0361H, AP0481H, AP0561H

Details of hole for lower side piping

Space required for service(In case of right side piping )

Details of hole for back side piping

Refrigerant piping positionWired remote controller RBC-AMT21E RBC-AMT31ESimple wired remote controller RBC-AS21E RBC-AS21E2Wireless remote controller kit TCB-AX21E TCB-AX21E2Weekly timer application RBC-AMT31E and RBC-EXW21E2

Page 186: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

181

500

700

88 24

114

0 136

64

52

20

55

125

173

165

1640

1800

67

88115

225

230

155 21

5

88

135

80

80

630

610

100

100

C *1

C

700anchor bolt pitch

755

anch

or b

olt p

itch

700anchor bolt pitch

99075

5an

chor

bol

t pitc

h

790

(incl

udin

g st

eady

leg)

750

4-15 x 20 (Long hole)

2-60 x 150 square hole (Hole for handling goods)

Balance pipe connecting port O/ 9.5

Refrigerant pipe connecting port (Liquid side) B

Refrigerant pipe connecting port (Gas side) A

Earth-attaching section of bottom plate

Foundation

Foundation

Front side (For work and service)

Front sideFront side

Front sideFront side

Front side

10 or more

500

or m

ore

(Not

e 3)

(100

0 or

mor

e)60

0 or

mor

e

500

or m

ore

500

or m

ore

(Not

e 3)

(100

0 or

mor

e)60

0 or

mor

e

600

or m

ore

500

or m

ore

800

or le

ss

10 or more

1010 or more

500

or m

ore

500

or m

ore 17

50or

mor

e

Knockout hole for power piping (O/ 48)

Knockout for control piping (O/ 27)

Balance pipe connecting port

Refrigerant pipe connecting port (Liquid side)

Refrigerant pipe connecting port (Gas side)

Square hole 15

Outdoor module

MMY-MAP0501T8, MAP0601T8, MAP0801T8, MAP1001T8, MAP1201T8MMY-MAP0501HT8, MAP0601HT8, MAP0801HT8, MAP1001HT8, MAP1201HT8MMY-MAP0501HT7, MAP0601HT7, MAP0801HT7, MAP1001HT7, MAP1201HT7

(NOTES)1. If there is an obstacle above the outdoor unit, ensure there is a minimum space of 2000mm or more above the unit.2. Any obstacle around the perimeter of the outdoor unit must be kept 800mm or less.3. Draw out the locally supplied piping at the front of the outdoor unit horizontally, keep a minimum of 500mm or more. between the outdoor unit and traversing pipe If the pipework is to be installed in this method.

*1 Cutting position of L-shape pipe when pipe at gas side is connected (Recommended pipe connecting position)

Details of front pipe/cabling holes Details of hole for piping at lower side (Plane view)

Space required for service

MMY-MAP0501T8MMY-MAP0501T8

MMY-MAP0501HT8MMY-MAP0601HT8MMY-MAP0601HT7MMY-MAP0601HT7

Applied model

MMY-MAP0501T8, MAP0501HT8, MAP0501HT7

MMY-MAP0601T8, MAP0601HT8, MAP0601HT7

MMY-MAP0801T8, MAP0801HT8, MAP0801HT7

MMY-MAP1001T8, MAP1001HT8, MAP1001HT7

MMY-MAP1201T8, MAP1201HT8, MAP1201HT7

A

O/ 15.9

O/ 19.1

O/ 22.2

O/ 22.2

O/ 28.6

B

O/ 9.5

O/ 9.5

O/ 12.7

O/ 12.7

O/ 12.7

C

280

280

(205)

(205)

(205)

Page 187: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

182

2000

700

164018

00

88

165

20 or more990 990

700anchor bolt pitch

(310)700anchor bolt pitch

755

anch

or b

olt p

itch

790

(incl

udin

g st

eady

leg)

750

8-15 x 20 (Long hole)

1 2

Front sideFront side

Front sideFront side

Front sideFront side

Front sideFront side

Front side Front side

500

or m

ore

500

or m

ore

(Not

e 3)

(Not

e 4)

(Not

e 4)

(100

0 or

mor

e)60

0 or

mor

e

500

or m

ore

(Not

e 3)

(Not

e 4)

(100

0 or

mor

e)60

0 or

mor

e60

0or

mor

e50

0or

mor

e

500m

m o

r m

ore

500m

mor

mor

e

1750

mm

or

mor

e

10mm or more

2020mm or more

20mm or more10mm

or more

800

or le

ss

800

or le

ss

Front side (For work and service)

(Not

e 4)

15

Two units connectedMMY-AP1401T8, AP1601T8, AP1801T8, AP2001T8, AP2211T8, AP2411T8MMY-AP1401HT8, AP1601HT8, AP1801HT8, AP2001HT8, AP2211HT8, AP2411HT8MMY-AP1401HT7, AP1601HT7, AP1801HT7, AP2001HT7, AP2211HT7, AP2411HT7

(NOTES)1. If there is an obstacle above the outdoor unit, ensure there is a minimum space of 2000mm or more above the unit.2. Any obstacle around the perimeter of the outdoor unit must be kept 800mm or less.3. Draw out the locally supplied piping at the front of the outdoor unit horizontally, keep a minimum of 500mm or more. between the outdoor unit and traversing pipe If the pipework is to be installed in this method.4. Arrange each of the outdoor units in order of their capacity. (Header >_ Follower)

Combination unit

MMY-AP1401T8, AP1401HT8, AP1401HT7

MMY-AP1601T8, AP1601HT8, AP1601HT7

MMY-AP1801T8, AP1801HT8, AP1801HT7

MMY-AP2001T8, AP2001HT8, AP2001HT7

MMY-AP2211T8, AP2211HT8, AP2211HT7

MMY-AP2411T8, AP2411HT8, AP2411HT7

Combination outdoor unit

Header

MMY-MAP0801T8, MAP0801HT8, MAP0801HT7

MMY-MAP0801T8, MAP0801HT8, MAP0801HT7

MMY-MAP1001T8, MAP1001HT8, MAP1001HT7

MMY-MAP1001T8, MAP1001HT8, MAP1001HT7

MMY-MAP1201T8, MAP1201HT8, MAP1201HT7

MMY-MAP1201T8, MAP1201HT8, MAP1201HT7

Follower

MMY-MAP0601T8, MAP0601HT8, MAP0601HT7

MMY-MAP0801T8, MAP0801HT8, MAP0801HT7

MMY-MAP0801T8, MAP0801HT8, MAP0801HT7

MMY-MAP1001T8, MAP1001HT8, MAP1001HT7

MMY-MAP1001T8, MAP1001HT8, MAP1001HT7

MMY-MAP1201T8, MAP1201HT8, MAP1201HT7

Space required for service

Page 188: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

183

3010

700

164018

00

88

165

20 or more99020 or more990 990

700anchor bolt pitch

(310)700anchor bolt pitch

(310)700anchor bolt pitch

755

anch

or b

olt p

itch

790

(incl

udin

g st

eady

leg)

750

12-15 x 20 (Long hole)

321

Front sideFront side

Front sideFront side

Front sideFront side

Front sideFront side

Front sideFront side

Front sideFront side

Front side Front side Front side

(Fro

nt s

ide)

500

or m

ore

500

or m

ore

(Not

e 3)

(Not

e 4)

(Not

e 4)

(100

0 or

mor

e)60

0 or

mor

e

500

or m

ore

600

or m

ore

500

or m

ore

(Not

e 3)

(100

0 or

mor

e)60

0 or

mor

e

800

or le

ss

800

or le

ss

(Rea

r si

de)

500m

m o

r m

ore

500m

mor

mor

e

1750

mm

or

mor

e

10mm or more 20mm or more 20mm or more

3030mm or more

10mmor more

Front side (For work and service)

(Not

e 4)

(Not

e 4)

15

Three units connectedMMY-AP2201T8, AP2401T8, AP2601T8, AP2801T8, AP3001T8, AP3211T8, AP3411T8, AP3611T8MMY-AP2201HT8, AP2401HT8, AP2601HT8, AP2801HT8, AP3001HT8, AP3211HT8, AP3411HT8, AP3611HT8MMY-AP2201HT7, AP2401HT7, AP2601HT7, AP2801HT7, AP3001HT7, AP3211HT7, AP3411HT7, AP3611HT7

(NOTES)1. If there is an obstacle above the outdoor unit, ensure there is a minimum space of 2000mm or more

above the unit.2. Any obstacle around the perimeter of the outdoor unit

must be kept 800mm or less.3. Draw out the locally supplied piping at the front of the

outdoor unit horizontally, keep a minimum of 500mm ormore. between the outdoor unit and traversing pipe If thepipework is to be installed in this method.

4. Arrange each of the outdoor units in order of their capacity. (Header >_ Follower 2 >_ Follower 3 )

Combination unit

MMY-AP2201T8, HT8, HT7

MMY-AP2401T8, HT8, HT7

MMY-AP2601T8, HT8, HT7

MMY-AP2801T8, HT8, HT7

MMY-AP3001T8, HT8, HT7

MMY-AP3221T8, HT8, HT7

MMY-AP3411T8, HT8, HT7

MMY-AP3611T8, HT8, HT7

Combination outdoor unit

Header

MMY-MAP0801T8, HT8, HT7

MMY-MAP0801T8, HT8, HT7

MMY-MAP1001T8, HT8, HT7

MMY-MAP1001T8, HT8, HT7

MMY-MAP1001T8, HT8, HT7

MMY-MAP1201T8, HT8, HT7

MMY-MAP1201T8, HT8, HT7

MMY-MAP1201T8, HT8, HT7

Follower

MMY-MAP0801T8, HT8, HT7

MMY-MAP0801T8, HT8, HT7

MMY-MAP0801T8, HT8, HT7

MMY-MAP1001T8, HT8, HT7

MMY-MAP1001T8, HT8, HT7

MMY-MAP1001T8, HT8, HT7

MMY-MAP1201T8, HT8, HT7

MMY-MAP1201T8, HT8, HT7

Follower

MMY-MAP0601T8, HT8, HT7

MMY-MAP0801T8, HT8, HT7

MMY-MAP0801T8, HT8, HT7

MMY-MAP0801T8, HT8, HT7

MMY-MAP1001T8, HT8, HT7

MMY-MAP1001T8, HT8, HT7

MMY-MAP1001T8, HT8, HT7

MMY-MAP1201T8, HT8, HT7

Space required for service

Page 189: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

184

4020

700

164018

00

8816

5

700anchor bolt pitch

20 or more990 990 990 99020 or more 20 or more

700anchor bolt pitch

700anchor bolt pitch

(310) (310) (310)700anchor bolt pitch

755

anch

or b

olt p

itch

790

(incl

udin

g st

eady

leg)

750

16-15 x 20 (Long hole)

1 2 3 4

Front sideFront side

Front sideFront side

Front sideFront side

Front sideFront side

Front sideFront side

Front sideFront side

Front sideFront side

Front sideFront side

Front sideFront side Front side Front side

600

or m

ore

500

or m

ore

500

or m

ore

500

or m

ore

(Not

e 3)

(Not

e 4)

(Not

e 4)

(Not

e 4)

(100

0 or

mor

e)60

0 or

mor

e

500

or m

ore

(Not

e 3)

(100

0 or

mor

e)60

0 or

mor

e

800

or le

ss

800

or le

ss

500m

mor

mor

e50

0mm

or m

ore

1750

mm

or

mor

e

10mm or more 20mm or more 20mm or more 20mm or more

4040mm or more

10mmor more

Front side (For work and service)

(Not

e 4)

15

Space required for service

Four units connectedMMY-AP3201T8, AP3401T8, AP3601T8, AP3801T8, AP4001T8, AP4201T8, AP4401T8, AP4601T8, AP4801T8MMY-AP3201HT8, AP3401HT8, AP3601HT8, AP3801HT8, AP4001HT8, AP4201HT8, AP4401HT8, AP4601HT8, AP4801HT8MMY-AP3201HT7, AP3401HT7, AP3601HT7, AP3801HT7, AP4001HT7, AP4201HT7, AP4401HT7, AP4601HT7, AP4801HT7

Combination unit

MMY-AP3201T8, HT8, HT7MMY-AP3401T8, HT8, HT7MMY-AP3601T8, HT8, HT7MMY-AP3801T8, HT8, HT7MMY-AP4001T8, HT8, HT7MMY-AP4201T8, HT8, HT7MMY-AP4401T8, HT8, HT7MMY-AP4601T8, HT8, HT7MMY-AP4801T8, HT8, HT7

Combination outdoor unitHeader

MMY-MAP0801T8, HT8, HT7MMY-MAP1001T8, HT8, HT7MMY-MAP1001T8, HT8, HT7MMY-MAP1001T8, HT8, HT7MMY-MAP1001T8, HT8, HT7MMY-MAP1201T8, HT8, HT7MMY-MAP1201T8, HT8, HT7MMY-MAP1201T8, HT8, HT7MMY-MAP1201T8, HT8, HT7

FollowerMMY-MAP0801T8, HT8, HT7MMY-MAP0801T8, HT8, HT7MMY-MAP1001T8, HT8, HT7MMY-MAP1001T8, HT8, HT7MMY-MAP1001T8, HT8, HT7MMY-MAP1001T8, HT8, HT7MMY-MAP1201T8, HT8, HT7MMY-MAP1201T8, HT8, HT7MMY-MAP1201T8, HT8, HT7

FollowerMMY-MAP0801T8, HT8, HT7MMY-MAP0801T8, HT8, HT7MMY-MAP0801T8, HT8, HT7MMY-MAP1001T8, HT8, HT7MMY-MAP1001T8, HT8, HT7MMY-MAP1001T8, HT8, HT7MMY-MAP1001T8, HT8, HT7MMY-MAP1201T8, HT8, HT7MMY-MAP1201T8, HT8, HT7

FollowerMMY-MAP0801T8, HT8, HT7MMY-MAP0801T8, HT8, HT7MMY-MAP0801T8, HT8, HT7MMY-MAP0801T8, HT8, HT7MMY-MAP1001T8, HT8, HT7MMY-MAP1001T8, HT8, HT7MMY-MAP1001T8, HT8, HT7MMY-MAP1001T8, HT8, HT7MMY-MAP1201T8, HT8, HT7

(NOTES)1. If there is an obstacle above the

outdoor unit, ensure there is aminimum space of 2000mm ormore above the unit.

2. Any obstacle around theperimeter of the outdoor unitmust be kept 800mm or less.

3. Draw out the locally suppliedpiping at the front of theoutdoor unit horizontally, keep aminimum of 500mm or more.between the outdoor unit andtraversing pipe If the pipeworkis to be installed in this method.

4. Arrange each outdoor unit inorder of its capacity.

Header >_ Follower 2 >>_ Follower 3 >>_ Follower 4( )

Page 190: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

185

O/ 38.1

14O /

38.1

39

O / 38

.1

14 1478

O/ 22.2

10O /

22.2

26

O / 22

.2

10 1052

O/ 9.5

7O /

9.5

13

7 732

O / 9.

5

B 80 x n

Insulator

Insulator

50A

C

B 80 x n BA

74.5

61

61 x 1,

14 x 2, 18 x 1, 85 x 2, 86 x 1

6 x 4, 9 x 4, 14 x 1, 18 x 1, 70 x 1

1 x 4, 6 x 1, 9 x 1

6 x 8, 9 x 8, 14 x 1, 18 x 1, 70 x 1

1 x 8, 6 x 1, 9 x 1

6 x 2, 9 x 2, 27 x 1, 59 x 1

1 x 2

6 x 7, 9 x 7, 27 x 1, 59 x 1

1 x 7

Accessory soket Q,tyA B C O/ D O/ E n

71 x 2,62 x 1, 73 x 2, 74 x 1,

15

Branch headerRBM-HY1043E, HY1083E, HY2043E, HY2083E

Gas side

Liquid side

Gas side

T-shape branch jointRBM-BT13E

Balance pipeLiquid side

Model

RBM-HY1043E

RBM-HY1083E

RBM-HY2043E

RBM-HY2083E

Gas side

Liquid side

Gas side

Liquid side

Gas side

Liquid side

Gas side

Liquid side

380

360

700

680

385.5

360

705.5

680

90

60

90

60

95.5

60

95.5

60

83.6_

83.6_

89.3_

89.3_

22.2

15.9

22.2

15.9

31.8

15.9

31.8

15.9

15.9

9.5

15.9

9.5

15.9

9.5

15.9

9.5

3

3

7

7

3

3

7

7

Accessory soket Q,ty

Gas side

Liquid side

Branch header/Branch joint

Page 191: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

186

O / C

AO /

B

O / D

O / D

B

O / D

O / C

A

O / D

O / C

A

Insulator

Insulator

Insulator

Insulator

O / D

O / D

B

O / C

A

O / D

O / D

B

5 x 2, 54 x 2, 9 x 1, 51 x 1

1 x 2, 5 x 1

7 x 1, 10 x 1, 13 x 2, 18 x 1, 52 x 2, 70 x 1, 89 x 1

2 x 1, 5 x 2, 6 x 1, 9 x 1, 54 x 1

16 x 1, 20 x 1, 27 x 1, 43 x 2, 48 x 1, 49 x 1, 58 x 1, 59 x 1

3 x 1, 6 x 1, 9 x 2

61 x 3, 62 x 2, 71 x 2, 73 x 1, 74 x 1, 75 x 1, 76 x 1, 77 x 1

4 x 1, 7 x 1, 10 x 1, 13 x 2, 14 x 1, 18 x 1, 52 x 1

15

Y-shape branch jointRBM-BY53E, BY103E

Gas side Liquid side

Gas side Liquid side

RBM-BY203E, BY303E

Model

Gas side

Liquid side

250

200

350

250

350

250

400

350

RBM-BY53E

RBM-BY203E

RBM-BY303E

Gas side

Liquid side

Gas side

Liquid side

Gas side

Liquid side

80

70

80

80

80

80

110

80

15.9

12.7

22.2

15.9

31.8

15.9

38.1

22.2

12.7

9.5

19.1

12.7

28.6

15.9

38.1

19.1

RBM-BY103E

Accessory soket Q,ty

Page 192: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

187

O/ B

A

O/ 15.9Outer dia

O/ B

A

O/ 12.7Outer dia

O/ 6.4

O/ 9.5Outer dia

24

O/ BA

O/ 19.1Outer dia

O/ B

A

O/ 22.2Outer dia

O/ B

A

O/ 28.6Outer dia

O/ B

A

O/ 31.8Outer dia

O/ B

A

O/ 38.1Outer dia

1 2 5 54

3 6 9 51 4 7 10 13 52 89

16 20 43 48 49 5814 18 70 85 86

27 59 61 62 73 74 75 76 77

15

Accessory socket

A O/ B55

66

66

66

66

64

62

62

34.9

41.3

28.6

22.2

19.1

15.9

12.7

9.5

61

62

71

73

74

75

76

77

A O/ B50

52

50

54

52

62

15.9

19.1

22.2

9.5

12.7

34.9

16

20

43

48

49

58

A O/ B39

39

36

33

43

53

6.4

9.5

12.7

15.9

22.2

28.6

4

7

10

13

52

89

A O/ B40

40

54

41

44

15.9

19.1

28.6

12.7

9.5

14

18

70

85

86

A O/ B35

32

28

38

6.4

9.5

12.7

19.1

3

6

9

51

A O/ B29

26

31

6.4

9.5

15.9

2

5

54

A O/ B49

59

28.6

34.9

27

59

Page 193: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

188

Page 194: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

189

Specifications

16

Page 195: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

190

Foreword

Page 196: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

191

16 Foreword

16

Specifications

TECHNICAL SPECIFICATIONSIndoor unit (50Hz specification)

50Hz

Model name

Cooling/Heating capacity (Note 1)

Power supply

Running current

Power consumption

Starting current

Electricalcharacteristics

Appearance

Main unit

CeilingPanel

Model

Panel colour

Height

Width

Depth

Height

Width

Depth

Main unit

Ceilingpanel

Outerdimension

Total weightMain unit

Ceiling panel

Heat exchanger

Soundproof/Heat-insulatingmaterial

Fan unit

Fan

Standard air flow High(Mid./Low)

Motor

Air filter

Controller

Connectingpipe

Gas side

Liquid side

Drain port

Sound pressure level(Note 2)(High/Mid./Low)

MMU-

(kW)

(A)

(kW)

(A)

(mm)

(mm)

(mm)

(mm)

(mm)

(mm)

(kg)

(kg)

(m3/h)

(mm)

(mm)

(Nominal dia. mm)

(dB(A))

AP0091H

2.8/3.2

AP0121H

3.6/4.0

AP0151H

4.5/5.0

AP0181H

5.6/6.3

AP0241H

7.1/8.0

AP0271H

8.0/9.0

AP0301H

9.0/10.0

AP0361H

11.2/12.5

AP0481H

14.0/16.0

AP0561H

16.0/18.0

1 phase 50Hz 230V (220 - 240V) (Separate power supply for indoor units is required.)

0.17

0.020

0.30

0.19

0.022

0.33

0.21

0.026

0.36

0.24

0.032

0.42

0.35

0.048

0.59

0.59

0.070

0.87

0.81

0.110

1.23

0.83

0.112

1.26

Heat-insulating material attached Zinc hot dipping steel plate

RBC-U21PG (W) -E

Moon white (Munsell/2.5GY 9.0/0.5)

256 319

840

840

35

950

950

2220 23 28

4.5

Finned tube

Non-flammable insulation

Turbo fan

800(730/680)

930(830/790)

1,050(920/800)

1,200(920/820)

1,320(1,110/850)

1,680(1,300/1,070)

2,040(1,430/1,130)

2,090(1,520/1,230)

60 90

Standard filter (Long life filter)

Remote controller

O/ 9.5 O/ 12.7

O/ 6.4

O/ 15.9

O/ 9.5

25 (Polyvinyl chloride tube)

30/29/27 31/29/27 32/29/28 34/31/28 37/33/30 40/36/33 44/38/34 45/40/34

4-way Air Discharge Cassette Type

(W)

Note 1 : The cooling capacities and electrical characteristics are measured under the conditions specified by JIS B 8615 based on thereference piping. The reference piping consists of 5 m of main piping and 2.5 m of branch piping connected with 0 meter height.

Note 2 : The sound levels are measured in an anechoic chamber in accordance with JIS B8616. Normally, the values measured inthe actual operating environment become larger than the indicated values due to the effects of external sound.

Note : Rated conditions Cooling : Indoor air temperature 27OC DB/19OC WB, Outdoor air temperature 35OC DBHeating : Indoor air temperature 20OC DB, Outdoor air temperature 7OC DB/6OC WB

Page 197: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

192

16

50Hz

Model name

Cooling/Heating capacity

Power supply

Electricalcharacteristics

Appearance

Power factor

Outerdimension

Total weight

Heat exchanger

Soundproof/Heat-insulating material

Fan unit

Fan

Standard air flow(High/Mid./Low)

Motor

Air filter

Connectingpipe

Gas side

Liquid side

Drain port (Nominal dia. mm)

Sound pressure level(Note 2)(High/Mid./Low)

MMU-

Running current

Powerconsumption

Starting current

Main unit

Ceilingpanel

Model

Panel colour

Mainunit

Ceilingpanel

Height

Width

Depth

Height

Width

Depth

Controller

Main unit

Ceiling panel

(kW)

(A)

(kW)

(%)

(A)

(mm)

(mm)

(mm)

(mm)

(mm)

(mm)

(kg)

(kg)

(m3/h)

(W)

(mm)

(mm)

(dB(A))

AP0071WH AP0091WH AP0121WH AP0151WH

2.2/2.5 2.8/3.2 3.6/4.0 4.5/5.0 5.6/6.3

AP0181WH

7.1/8.0

AP0241WH

8.0/9.0

AP0271WH

9.0/10.0

AP0301WH

14.0/16.0

AP0481WHChina only

1 phase 50Hz 230V (220 - 240V) (Separate power supply for indoor units is required.)1 phase

50Hz 220V

0.31

0.070

0.32

0.072

0.46

0.105

0.47

0.106

1.16

0.250

97

0.47 0.60

99 98 98

0.89 0.98 1.33

RBC-UW136PG

Heat-insulating material attached Zinc hot dipping steel plate

RBC-UW266PGRBC-

UW466PG

Light ivory (Munsell 10Y 9/0.5)

398 406

830 1,350 1,650

550 620

8

1,000 1,520 1,898

650 680

33 44 48 52

8 11 18

Finned tube

Non-flammable insulation

Centrifugal fan

570/510/450 780/700/600 1140/960/720 1260/1140/960 1920/1500/1050

53 39 53 92

Standard filter (Long life filter)

Remote controller

O/ 9.5 O/ 12.7 O/ 15.9

O/ 6.4 O/ 9.5

25 (Polyvinyl chloride tube)

34/32/30 35/33/30 38/35/33 40/37/34 45/42/39

2-way Air Discharge Cassette Type

Note 1 : The cooling capacities and electrical characteristics are measured under the conditions specified by JIS B 8615 based on thereference piping. The reference piping consists of 5 m of main piping and 2.5 m of branch piping connected with 0 meter height.

Note 2 : The sound levels are measured in an anechoic chamber in accordance with JIS B8616. Normally, the values measured inthe actual operating environment become larger than the indicated values due to the effects of external sound.

Note : Rated conditions Cooling : Indoor air temperature 27OC DB/19OC WB, Outdoor air temperature 35OC DBHeating : Indoor air temperature 20OC DB, Outdoor air temperature 7OC DB/6OC WB

Page 198: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

193

Foreword

16

50Hz

Model name

Cooling/Heating capacity (Note 1)

Electricalcharacteristics(Note 2)

Power supply

Power factor

Running current

Power consumption

Starting current

Appearance

Outerdimension

Main unit

Ceilingpanel

Main unit

Ceilingpanel

Model

Height

Width

Depth

Panel colour

Height

Width

Depth

Total weightMain unit

Ceiling panel

Heat exchanger

Soundproof/Heat-insulating material

Fanunit

Fan

Standard air flow (High/Mid./Low)

Motor

Controller

Room thermostat

Air filter

Connectingpipe

Gas side

Liquid side

Drain port

Sound pressure level(Note 2)(High/Mid./Low)

MMU-

(kW)

(A)

(kW)

(%)

(A)

(mm)

(mm)

(mm)

(mm)

(mm)

(mm)

(kg)

(kg)

(m3h)

(W)

(mm)

(mm)

(Nominal dia. mm)

(dB(A))

AP0071YH

2.2/2.5

AP0091YH

2.8/3.2

AP0121YH

3.6/4.0

AP0151SH

4.5/5.0

AP0181SH

5.6/6.3

AP0241SH

7.1/8.0

1 phase 50Hz 230V (220 - 240V) (Separate power supply for indoor units is required.)

0.24

0.053

95

0.6

0.48 0.55

0.103 0.115

93 91

0.8 1.1

Heat-insulating material attached Zinc hot dipping steel plate

RBC-UY135PG RBC-US165PG RBC-US265PG

W : Silky shade (1Y8.5/0.5)

235

850

400

18

1,050

470

22

3.5

198

1,000 1,200

655

1,220 1,420

10

755

27 31

8 9

Finned tube

Non-flammable insulation

Centrifugal fan

540/480/420

22

780/720/660 1,200/1,140/1,020

34

Remote controller

Attached

Standard filter (Long life filter)

O/ 12.7 O/ 15.9

O/ 6.4 O/ 9.5

25 (Polyvinyl chloride tube)

42/39/34 42/39/35 43/41/37

O/ 9.5

1-way Air Discharge Cassette Type

Note 1 : The cooling capacities and electrical characteristics are measured under the conditions specified by JIS B 8615 based on thereference piping. The reference piping consists of 5 m of main piping and 2.5 m of branch piping connected with 0 meter height.

Note 2 : The sound levels are measured in an anechoic chamber in accordance with JIS B8616. Normally, the values measured inthe actual operating environment become larger than the indicated values due to the effects of external sound.

Note : Rated conditions Cooling : Indoor air temperature 27OC DB/19OC WB, Outdoor air temperature 35OC DBHeating : Indoor air temperature 20OC DB, Outdoor air temperature 7OC DB/6OC WB

Page 199: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

194

16

50Hz

Concealed Duct Type

Model name

Power supply

MMD-

(kW)Cooling/Heating capacity (Note 1)

Running current

Power consumption

Starting current

(A)

(kW)

(A)

Electricalcharacteristics

Appearance Main unit

Height

Width

Depth

Height

Width

Depth

Main unit

Suctionceilingpanel

Outerdimension

Total weight

Main unit

Ceiling panel

Heat exchanger

Soundproof/Heat-insulating material

Fan unit

Fan

Standard air flow High(Mid./Low)

Motor

External static pressure(factory setting)

External static pressure

Air filter

Controller

Connectingpipe

Gas side

Liquid side

Drain port (Nominal dia. mm)

Sound pressure level(Note 2)(High/Mid./Low)

(mm)

(mm)

(mm)

(mm)

(mm)

(mm)

(kg)

(kg)

(m3/h)

(W)

(Pa)

(Pa)

(mm)

(mm)

(dB(A))

AP0071BH

2.2/2.5

AP0091BH

2.8/3.2

AP0121BH

3.6/4.0

AP0151BH

4.5/5.0

AP0181BH

5.6/6.3

AP0241BH

7.1/8.0

AP0271BH

8.0/9.0

AP0301BH

9.0/10.0

AP0361BH

11.2/12.5

AP0481BH

14.0/16.0

AP0561BH

16.0/18.0

1 phase 50Hz 230V (220 - 240V) (Separate power supply for indoor units is required.)

0.29

0.033

0.5

0.34

0.039

0.59

0.43

0.050

0.75

0.52

0.060

0.90

0.61

0.071

1.05

0.83

0.107

1.44

0.98

0.128

1.70

Zinc hot dipping steel plate

320

550 700 1,000 1,350

800

9

630 780 1,080 1,430

28 32 43 55

3.5 4 6 7

500

Finned tube

Non-flammable insulation

Centrifugal fan

480(420/340)

570(490/400)

650(540/480)

780(660/540)

1,140(990/870)

1,260(1080/870)

1,620(1410/1200)

1,980(1710/1490)

120

50 (4 mmAq)

110 (10 mmAq)

Standard filter (Long life filter)

O/ 9.5 O/ 12.7 O/ 15.9

O/ 6.4 O/ 9.5

25 (Polyvinyl chloride tube)

30/28/26 31/29/27 33/31/29 36/34/3232/30/28 34/32/29 36/34/32

Remote controller

Note 1 : The cooling capacities and electrical characteristics are measured under the conditions specified by JIS B 8615 based on thereference piping. The reference piping consists of 5 m of main piping and 2.5 m of branch piping connected with 0 meter height.

Note 2 : The sound levels are measured in an anechoic chamber in accordance with JIS B8616. Normally, the values measured inthe actual operating environment become larger than the indicated values due to the effects of external sound.

Note : Rated conditions Cooling : Indoor air temperature 27OC DB/19OC WB, Outdoor air temperature 35OC DBHeating : Indoor air temperature 20OC DB, Outdoor air temperature 7OC DB/6OC WB

Page 200: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

195

16

50Hz

Concealed Duct High Static Pressure TypeModel name MMD-

Cooling/Heating capacity (Note 1)

Power supply

Running current

Power consumption

Power factor

Starting current

Electricalcharacteristics

Appearance

Outerdimension

Height x Width x Depth

Total weight

Heat exchanger

Soundproof/Heat-insulating material

Fanunit

Fan

Standard air flow

Motor

External static pressure

External static pressure(Factory setting)

Air flow limitLower limit/Upper limit

Air filter

Controller

Connectingpipe

Gas side

Liquid side

Drain port (Nominal dia. mm)

Sound pressure level(Note 2)(High/Mid./Low)

(kW)

(A)

(kW)

(%)

(A)

(mm)

(kg)

(m3/h)

(W)

(Pa)

(Pa)

(m3/h)

(mm)

(mm)

(dB(A))

AP0181H

5.6/6.3

AP0241H

7.1/8.0

AP0271H

8.0/9.0

AP0361H

11.2/12.5

AP0481H

14.0/16.0

AP0721H

22.4/25.0

AP0961H

28.0/31.5

1 phase 50Hz 230V (220 - 240V) (Separate power supply for indoor units is required.)

0.81 1.35 1.63 1.84 5.25 5.52

0.184 0.299 0.368 0.414 1.200 1.260

99 96 98 98 99 99

1.3 3.5 4.1 4.8 13.6 14.8

Zinc hot dipping steel plate

380 x 850 x 660 380 x 1,200 x 660 470 x 1,380 x 1,250

50 52 56 67 150

Finned tube

Non-flammable insulation

Centrifugal fan

900 1,320 1,600 2,100 3,600 4,200

160 260 370 x 3

137

68.6-137-196

720/1,080 1,060/1,580 1,280/1,920 1,680/2,520 2,880/4,320 3,360/5,040

Option or field supply

Remote controller

O/ 12.7 O/ 15.9 O/ 22.2

O/ 6.4 O/ 9.5 O/ 12.7

25 (One side of male screw)

37 40 49 50

Note 1 : The cooling capacities and electrical characteristics are measured under the conditions specified by JIS B 8615 based on thereference piping. The reference piping consists of 5 m of main piping and 2.5 m of branch piping connected with 0 meter height.

Note 2 : The sound levels are measured in an anechoic chamber in accordance with JIS B8616. Normally, the values measured inthe actual operating environment become larger than the indicated values due to the effects of external sound.

Note : Rated conditions Cooling : Indoor air temperature 27OC DB/19OC WB, Outdoor air temperature 35OC DBHeating : Indoor air temperature 20OC DB, Outdoor air temperature 7OC DB/6OC WB

Page 201: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

196

16

50Hz

Under Ceiling Type

Model name MMC-

(kW)Cooling/Heating capacity (Note 1)

AP0151H

4.5/5.0

Power supply

Running current

Power consumption

Starting current

Electricalcharacteris-tics

Appearance

Outerdimension Height x Width x Depth

Total weight

Heat exchanger

Soundproof/Heat-insulating

material Fan

Motor

Standard air flow(High/Mid./Low)Fan unit

Controller

Room thermostat

Air filter

Gas side

Liquid side

Drain port

Connectingpipe

Sound pressure level(Note 2)(High/Mid./Low)

(kW)

(A)

(A)

(mm)

(kg)

(m3/h)

(W)

(mm)

(mm)

(Nominal dia. mm)

(dB(A))

AP0181H

5.6/6.3

AP0241H

7.1/8.0

AP0271H

8.0/9.0

AP0361H

11.2/12.5

AP0481H

14.0/16.0

1 phase 50Hz 230V (220 - 240V) (Separate power supply for indoor units is required.)

0.29

0.033

0.43

0.32 0.42 0.78 0.84

0.038 0.050 0.091 0.110

0.48 0.62 1.17 1.25

White (Munsell 10Y 9.3/0.4)

210 x 910 x 680 210 x 1,180 x 680 210 x 1,595 x 680

22 26 34

Finned tube

Non-flammable insulation

Centrifugal fan

720/600/540 780/660/540 1,110/900/840 1,650/1,380/1,2001,800/1,560/1,320

30 40 80

Remote controller

Attached

Standard filter (Long life filter)

O/ 12.7 O/ 15.9

O/ 6.4 O/ 9.5

20 (Polyvinyl chloride tube)

35/32/30 36/33/30 38/36/33 41/38/35 43/40/37

Note 1 : The cooling capacities and electrical characteristics are measured under the conditions specified by JIS B 8615 based on thereference piping. The reference piping consists of 5 m of main piping and 2.5 m of branch piping connected with 0 meter height.

Note 2 : The sound levels are measured in an anechoic chamber in accordance with JIS B8616. Normally, the values measured inthe actual operating environment become larger than the indicated values due to the effects of external sound.

Note : Rated conditions Cooling : Indoor air temperature 27OC DB/19OC WB, Outdoor air temperature 35OC DBHeating : Indoor air temperature 20OC DB, Outdoor air temperature 7OC DB/6OC WB

Page 202: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

197

16

50Hz

High Wall Type

Model name MMK-

(kW)Cooling/Heating capacity (Note 1)

AP0071H

2.2/2.5

Power supply

Running current

Power consumption

Starting current

Electricalcharacteristics

Appearance

Suction grille and side panel

Discharge grille

Bottom surface

Outerdimension

Height x Width x Depth

Total weight

Heat exchanger

Soundproof/Heat-insulating material

Fanunit

Fan

Standard air flow (High/Mid./Low)

Motor outlet

Air filter

Controller

Connecting

pipe

Gas side

Liquid side

Drain port

Sound pressure level(Note 2)(High/Mid./Low)

(A)

(kW)

(A)

(mm)

(kg)

(m3/h)

(W)

(mm)

(mm)

(Nominal dia. mm)

(dB(A))

AP0091H

2.8/3.2

AP0121H

3.6/4.0

AP0151H

4.5/5.0

AP0181H

5.6/6.3

AP0241H

7.1/8.0

1 phase 50Hz 230V (220 - 240V) (Separate power supply for indoor units is required.)

0.30 0.32 0.35

0.035 0.037 0.040

0.36 0.42 0.47

Silky mist (Munsell 1Y 8.9/0.5)

City gray (Munsell N6.5)

Silky mist (Munsell 1Y 8.9/0.5)

368 x 895 x 210 368 x 1,055 x 210 368 x 1,430 x 210

18 19 25

Finned tube

Non-flammable insulation

Cross-flow fan

600/540/480 780/660/600 1,200/1,020/900

30

Standard filter (Simple filter)

Remote controller

O/ 9.5 O/ 12.7 O/ 15.9

O/ 6.4 O/ 9.5

20 (Polyvinyl chloride tube)

39/34/31 42/38/35 42/38/35

Note 1 : The cooling capacities and electrical characteristics are measured under the conditions specified by JIS B 8615 based on thereference piping. The reference piping consists of 5 m of main piping and 2.5 m of branch piping connected with 0 meter height.

Note 2 : The sound levels are measured in an anechoic chamber in accordance with JIS B8616. Normally, the values measured inthe actual operating environment become larger than the indicated values due to the effects of external sound.

Note : Rated conditions Cooling : Indoor air temperature 27OC DB/19OC WB, Outdoor air temperature 35OC DBHeating : Indoor air temperature 20OC DB, Outdoor air temperature 7OC DB/6OC WB

Page 203: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

198

16

50Hz

Model name MML-

(kW)Cooling/Heating capacity (Note 1)

AP0071H

2.2/2.5

Power supply

Floor Standing Cabinet Type

Running current

Power consumption

Power factor

Starting current

Electricalcharacteristics

Appearance

Total weight

Outerdimension Height x Width x Depth

Heat exchanger

Soundproof/Heat-insulating material

Fan unit

Fan

Standard air flow(High/Mid./Low)

Motor outlet

Air filter

Controller

Gas side

Liquid side

Drain port

Connectingpipe

Sound pressure level(Note 2)(High/Mid./Low)

(A)

(kW)

(%)

(A)

(mm)

(kg)

(m3/h)

(W)

(mm)

(mm)

(Nominal dia. mm)

(dB(A))

AP0091H

2.8/3.2

AP0121H

3.6/4.0

AP0151H

4.5/5.0

AP0181H

5.6/6.3

AP0241H

7.1/8.0

1 phase 50Hz 230V (220 - 240V) (Separate power supply for indoor units is required.)

0.26 0.43 0.47

0.056 0.092 0.102

94 93 94

0.60 0.80 1.10

Silky shade (1Y8.5/0.5)

630 x 950 x 230

37 40 40

Finned tube

Non-flammable insulation

Centrifugal fan

480/420/360 900/780/650 1,080/930/780

45 70

Standard filter (Simple filter)

Remote controller

O/ 9.5 O/ 12.7 O/ 15.9

O/ 6.4 O/ 9.5

20 (Polyvinyl chloride tube)

39/37/35 45/41/38 49/44/39

Note 1 : The cooling capacities and electrical characteristics are measured under the conditions specified by JIS B 8615 based on thereference piping. The reference piping consists of 5 m of main piping and 2.5 m of branch piping connected with 0 meter height.

Note 2 : The sound levels are measured in an anechoic chamber in accordance with JIS B8616. Normally, the values measured inthe actual operating environment become larger than the indicated values due to the effects of external sound.

Note : Rated conditions Cooling : Indoor air temperature 27OC DB/19OC WB, Outdoor air temperature 35OC DBHeating : Indoor air temperature 20OC DB, Outdoor air temperature 7OC DB/6OC WB

Page 204: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

199

16

50Hz

Floor Standing Concealed TypeModel name MML-

(kW)Cooling/Heating capacity (Note 1)

AP0071BH

2.2/2.5

Power supply

Electricalcharacteristics

Running current

Power consumption

Power factor

Starting current

Appearance

Outerdimension

Height x Width xDepth

Total weight

Heat exchanger

Soundproof/Heat-insulating material

Fan

Standard air flow(High/Mid./Low)

Motor

Static pressure range

Fan unit

Air filter

Controller

Connectingpipe

Gas side

Liquid side

Drain port

Sound pressure level(Note 2)(High/Mid./Low)

(A)

(kW)

(%)

(A)

(mm)

(kg)

(m3/h)

(W)

(kPa)

(mm)

(mm)

(Nominal dia. mm)

(dB(A))

AP0091BH

2.8/3.2

AP0121BH

3.6/4.0

AP0151BH

4.5/5.0

AP0181BH

5.6/6.3

AP0241BH

7.1/8.0

1 phase 50Hz 230V (220 - 240V) (Separate power supply for indoor units is required.)

0.25 0.45 0.46

0.056 0.090 0.095

97 87 90

0.60 0.80 1.00

Zinc hot dipping steel plate

600 x 745 x 220 600 x 1,045 x 220

21 29

Finned tube

Non-flammable insulation

Centrifugal fan

460/400/300 740/600/490 950/790/640

19 70

0

Standard filter (Simple filter)

Remote controller

O/ 9.5 O/ 12.7 O/ 15.9

O/ 6.4 O/ 9.5

20 (One side of male screw)

36 (34/32) 42 (37/33)

Note 1 : The cooling capacities and electrical characteristics are measured under the conditions specified by JIS B 8615 based on thereference piping. The reference piping consists of 5 m of main piping and 2.5 m of branch piping connected with 0 meter height.

Note 2 : The sound levels are measured in an anechoic chamber in accordance with JIS B8616. Normally, the values measured inthe actual operating environment become larger than the indicated values due to the effects of external sound.

Note : Rated conditions Cooling : Indoor air temperature 27OC DB/19OC WB, Outdoor air temperature 35OC DBHeating : Indoor air temperature 20OC DB, Outdoor air temperature 7OC DB/6OC WB

Page 205: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

200

16

50Hz

Model name MMF-

(kW)Cooling/Heating capacity (Note 1)

AP0151H

4.5/5.0

Power supply

Floor Standing Type

Electricalcharacteristics

Running current

Power consumption

Power factor

Starting current

Appearance

Outerdimension

Height x Width xDepth

Total weight

Heat exchanger

Soundproof/Heat-insulating material

Fan unit

Fan

Motor

Standard air flow(High/Mid./Low)

Air filter

Controller

Gas side

Liquid side

Drain port

Connectingpipe

Sound pressure level(Note 2)(High/Mid./Low)

(A)

(kW)

(%)

(A)

(mm)

(kg)

(m3/h)

(W)

(mm)

(mm)

(Nominal dia. mm)

(dB(A))

AP0181H

5.6/6.3

AP0241H

7.1/8.0

AP0271H

8.0/9.0

AP0361H

11.2/12.5

AP0481H

14.0/16.0

AP0561H

16.0/18.0

1 phase 50Hz 230V (220 - 240V) (Separate power supply for indoor units is required.)

0.67 0.88 1.29 1.60

0.150 0.190 0.280 0.350

97 9594

0.90 1.10 1.70 2.10

W : Silky shade (1Y 8.5/0.5)

1750 x 600 x 210 1750 x 600 x 390

48 6549

Finned tube

Non-flammable insulation

Centrifugal fan

900/780/660 1,200/1,020/840 1,920/1,680/1,380 2,160/1,860/1,560

37 63 11 16

Standard filter (Simple filter)

Remote controller

O/ 12.7 O/ 15.9

O/ 6.4 O/ 9.5

20 (One side of male screw)

46/43/38 49/45/40 51/48/44 54/50/46

Note 1 : The cooling capacities and electrical characteristics are measured under the conditions specified by JIS B 8615 based on thereference piping. The reference piping consists of 5 m of main piping and 2.5 m of branch piping connected with 0 meter height.

Note 2 : The sound levels are measured in an anechoic chamber in accordance with JIS B8616. Normally, the values measured inthe actual operating environment become larger than the indicated values due to the effects of external sound.

Note : Rated conditions Cooling : Indoor air temperature 27OC DB/19OC WB, Outdoor air temperature 35OC DBHeating : Indoor air temperature 20OC DB, Outdoor air temperature 7OC DB/6OC WB

Page 206: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

201

16

60Hz

Model name MMU-

(kW)Cooling/Heating capacity (Note 1)

AP0091H

2.8/3.2

Power supply

4-way Air Discharge Cassette Type

Electricalcharacteristics

Indoor unit (60Hz specifications)

Running current

Power consumption

Starting current

Main unit

CeilingPanel

Model

Panel colour

Height

Width

Depth

Height

Width

Depth

Main unit

Ceilingpanel

Outerdimension

Total weightMain unit

Ceiling panel

Heat exchanger

Soundproof/Heat-insulatingmaterial

Fan

Motor

Fan unit Standard air flow High(Mid./Low)

Air filter

Controller

Gas side

Liquid side

Drain port

Connectingpipe

Sound pressure level(Note 2)(High/Mid./Low)

(A)

(kW)

(A)

(mm)

(mm)

(mm)

(mm)

(mm)

(mm)

(kg)

(kg)

(m3/h)

(W)

(mm)

(mm)

(Nominal dia. mm)

(dB(A))

AP0121H

3.6/4.0

AP0151H

4.5/5.0

AP0181H

5.6/6.3

AP0241H

7.1/8.0

AP0271H

8.0/9.0

AP0301H

9.0/10.0

AP0361H

11.2/12.5

AP0481H

14.0/16.0

AP0561H

16.0/18.0

1 phase 60Hz 220V (Separate power supply for indoor units is required.)

0.18 0.20 0.22 0.26 0.37 0.61 0.85 0.87

0.020 0.022 0.026 0.032 0.048 0.070 0.110 0.112

0.30 0.33 0.36 0.42 0.59 0.87 1.23 1.26

Heat-insulating material attached Zinc hot dipping steel plate

RBC-U21PG (W) -E

Moon white (Munsell/2.5GY 9.0/0.5)

256 319

840

840

35

950

950

20 22 23 28

4.5

Finned tube

Non-flammable insulation

Turbo fan

800(730/680)

930(830/790)

1,050(920/800)

1,200(920/820)

1,320(1,110/850)

1,680(1,300/1,070)

2,040(1,430/1,130)

2,090(1,520/1,230)

60 90

Standard filter (Long life filter)

O/ 9.5 O/ 12.7 O/ 15.9

O/ 6.4 O/ 9.5

25 (Polyvinyl chloride tube)

30/29/27 31/29/27 32/29/28 34/31/28 37/33/30 40/36/33 44/38/34 45/40/34

Appearance

Remote controller

Note 1 : The cooling capacities and electrical characteristics are measured under the conditions specified by JIS B 8615 based on thereference piping. The reference piping consists of 5 m of main piping and 2.5 m of branch piping connected with 0 meter height.

Note 2 : The sound levels are measured in an anechoic chamber in accordance with JIS B8616. Normally, the values measured inthe actual operating environment become larger than the indicated values due to the effects of external sound.

Note : Rated conditions Cooling : Indoor air temperature 27OC DB/19OC WB, Outdoor air temperature 35OC DBHeating : Indoor air temperature 20OC DB, Outdoor air temperature 7OC DB/6OC WB

Page 207: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

202

16

60Hz

Model name MMU-

(kW)Cooling/Heating capacity

AP0071WH

2.2/2.5

Power supply

2-way Air Discharge Cassette Type

Electricalcharacteris-tics

Running current

Powerconsumption

Power factor

Starting current

Main unit

Model

Panel colour

AppearanceCeilingpanel

Height

Width

Depth

Height

Width

Depth

Mainunit

Ceilingpanel

Outerdimension

Main unit

Ceiling panelTotal weight

Heat exchanger

Soundproof/Heat-insulating material

Fan unit

Fan

Motor

Standard air flow(High/Mid./Low)

Air filter

Controller

Gas side

Liquid side

Drain port

Connectingpipe

Sound pressure level(Note 2)(High/Mid./Low)

(A)

(kW)

(%)

(A)

(mm)

(mm)

(mm)

(mm)

(mm)

(mm)

(kg)

(kg)

(W)

(m3/h)

(mm)

(mm)

(Nominal dia.mm)

(dB(A))

AP0091WH

2.8/3.2

AP0121WH

3.6/4.0

AP0151WH

4.5/5.0

AP0181WH

5.6/6.3

AP0241WH

7.1/8.0

AP0271WH

8.0/9.0

AP0301WH

9.0/10.0

1 phase 60Hz 220V (Separate power supply for indoor units is required.)

0.33 0.38 0.53 0.58

0.070 0.076 0.115 0.123

97 90 99 96

0.46 0.59 0.87 0.96

Heat-insulating material attached Zinc hot dipping steel plate

RBC-UW136PG RBC-UW266PG

Light ivory (Munsell 10Y 9/0.5)

398

830 1.350

550

8

1,000 1,520

650

33 44 48

8 11

Finned tube

Non-flammable insulation

Centrifugal fan

570/510/450 780/700/600 1,140/960/720 1,260/1,140/960

53 39 53

Remote controller

Standard filter (Long life filter)

25 (Polyvinyl chloride tube)

O/ 9.5 O/ 12.7 O/ 15.9

O/ 6.4 O/ 9.5

34/32/30 35/33/30 38/35/33 40/37/34

Note 1 : The cooling capacities and electrical characteristics are measured under the conditions specified by JIS B 8615 based on thereference piping. The reference piping consists of 5 m of main piping and 2.5 m of branch piping connected with 0 meter height.

Note 2 : The sound levels are measured in an anechoic chamber in accordance with JIS B8616. Normally, the values measured inthe actual operating environment become larger than the indicated values due to the effects of external sound.

Note : Rated conditions Cooling : Indoor air temperature 27OC DB/19OC WB, Outdoor air temperature 35OC DBHeating : Indoor air temperature 20OC DB, Outdoor air temperature 7OC DB/6OC WB

Page 208: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

203

16

60Hz

Model name MMU-

(kW)Cooling/Heating capacity (Note 1)

AP0071YH

2.2/2.5

Power supply

1-way Air Discharge Cassette Type

Electricalcharacteristics(Note 2)

Running current (A)

Power consumption

Power factor

Starting current

Main unit

Model

Panel colour

Height

Width

Depth

Height

Width

Depth

AppearanceCeilingpanel

Main unit

Ceilingpanel

Outerdimension

Main unit

Ceiling panelTotal weight

Heat exchanger

Soundproof/Heat-insulating material

Fanunit

Fan

Standard air flow (High/Mid./Low)

Motor

Controller

Room thermostat

Air filter

Gas side

Liquid side

Drain port

Connectingpipe

Sound pressure level(Note 2)(High/Mid./Low)

(kW)

(%)

(A)

(mm)

(mm)

(mm)

(mm)

(mm)

(mm)

(kg)

(kg)

(m3/h)

(mm)

(mm)

(Nominal dia. mm)

(dB(A))

AP0091YH

2.8/3.2

AP0121YH

3.6/4.0

AP0151SH

4.5/5.0

AP0181SH

5.6/6.3

AP0241SH

7.1/8.0

1 phase 60Hz 220V (Separate power supply for indoor units is required.)

0.26 0.54 0.61

0.056 0.115 0.130

98 97 97

0.60 0.80 1.10

Heat-insulating material attached Zinc hot dipping steel plate

W : Silky shade (1Y8.5/0.5)

RBC-UY135PG RBC-US165PG RBC-US265PG

235 198

850 1,000 1,200

400 655

18 10

1,050 1,220 1,420

470 755

22 27 31

3.5 8 9

Finned tube

Non-flammable insulation

Centrifugal fan

540/480/420 780/720/660 1,200/1,140/1,020

22 34

Remote controller

Attached

Standard filter (Long life filter)

O/ 9.5 O/ 12.7 O/ 15.9

O/ 6.4 O/ 9.5

42/39/34 42/39/35 43/41/37

25 (Polyvinyl chloride tube)

(W)

Note 1 : The cooling capacities and electrical characteristics are measured under the conditions specified by JIS B 8615 based on thereference piping. The reference piping consists of 5 m of main piping and 2.5 m of branch piping connected with 0 meter height.

Note 2 : The sound levels are measured in an anechoic chamber in accordance with JIS B8616. Normally, the values measured inthe actual operating environment become larger than the indicated values due to the effects of external sound.

Note : Rated conditions Cooling : Indoor air temperature 27OC DB/19OC WB, Outdoor air temperature 35OC DBHeating : Indoor air temperature 20OC DB, Outdoor air temperature 7OC DB/6OC WB

Page 209: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

204

16

60Hz

Model name MMD-

(kW)Cooling/Heating capacity (Note 1)

AP0071BH

2.2/2.5

Power supply

Concealed Duct Type

Electricalcharacteristics

Running current (A)

Power consumption

Starting current

Main unitAppearance

Outerdimension

Main unit

Height

Width

Depth

Height

Width

Depth

Suctionceilingpanel

Main unit

Total weightCeiling panel

Heat exchanger

Soundproof/Heat-insulating material

Fan

Motor

External static pressure

Fan unit

Standard air flow High(Mid./Low)

External static pressure(factory setting)

Air filter

Controller

Connectingpipe

Gas side

Liquid side

Drain port

Sound pressure level(Note 2)(High/Mid./Low)

(kW)

(A)

(mm)

(mm)

(mm)

(mm)

(mm)

(mm)

(kg)

(kg)

(m3/h)

(W)

(Pa)

(pa)

(mm)

(mm)

(Nominal dia. mm)

(dB(A))

AP0091BH

2.8/3.2

AP0121BH

3.6/4.0

AP0151BH

4.5/5.0

AP0181BH

5.6/6.3

AP0241BH

7.1/8.0

AP0271BH

8.0/9.0

AP0301BH

9.0/10.0

AP0361BH

11.2/12.5

AP0481BH

14.0/16.0

AP0561BH

16.0/18.0

1 phase 60Hz 220V (Separate power supply for indoor units is required.)

0.30 0.35 0.45 0.55 0.64 0.87 1.03

0.033 0.039 0.050 0.060 0.071 0.107 0.128

0.5 0.59 0.75 0.90 1.05 1.44 1.70

Zinc hot dipping steel plate

320

550 700 1,000 1,350

800

9

630 780 1,080 1,430

500

28 32 43 55

3.5 4 6 7

Finned tube

Non-flammable insulation

Centrifugal fan

480(420/340)

570(490/400)

650(540/480)

780(660/540)

1,140(990/870)

1,260(1,080/870)

1,620(1,410/1,200)

1,980(1,710/1,490)

120

50 (4 mmAq)

110 (10 mmAq)

Remote controller

Standard filter (Long life filter)

O/ 9.5 O/ 12.7 O/ 15.9

O/ 6.4 O/ 9.5

25 (Polyvinyl chloride tube)

30/28/26 31/29/27 31/29/27 32/30/28 33/31/29 34/32/29 36/34/32 38/36/32

Note 1 : The cooling capacities and electrical characteristics are measured under the conditions specified by JIS B 8615 based on thereference piping. The reference piping consists of 5 m of main piping and 2.5 m of branch piping connected with 0 meter height.

Note 2 : The sound levels are measured in an anechoic chamber in accordance with JIS B8616. Normally, the values measured inthe actual operating environment become larger than the indicated values due to the effects of external sound.

Note : Rated conditions Cooling : Indoor air temperature 27OC DB/19OC WB, Outdoor air temperature 35OC DBHeating : Indoor air temperature 20OC DB, Outdoor air temperature 7OC DB/6OC WB

Page 210: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

205

16

60Hz

Model name

Cooling/Heating capacity (Note 1)

AP0181H

5.6/6.3

Power supply

Concealed Duct High Static Pressure Type

Electricalcharacteris-tics

Running current (A)

Power consumption

Power factor

Starting current

Appearance

Height x Width x DepthOuterdimension

Total weight

Heat exchanger

Soundproof/Heat-insulating material

Fan

Standard air flow

Motor

External static pressure

External static pressure(Factory setting)

Air flow limitLower limit/Upper limit

Fanunit

Air filter

Controller

Gas side

Liquid side

Drain port

Connectingpipe

MMD-

(kW)

(kW)

(%)

(A)

(mm)

(kg)

(m3/h)

(W)

(Pa)

(Pa)

(m3/h)

(mm)

(mm)

(Nominal dia. mm)

(dB(A))Sound pressure level(Note 2)(High/Mid./Low)

AP0241H

7.1/8.0

AP0271H

8.0/9.0

AP0361H

11.2/12.5

AP0481H

14.0/16.0

AP0721H

22.4/25.0

AP0961H

28.0/31.5

1 phase 60Hz 220V (Separate power supply for indoor units is required.)

0.92 1.80 2.07 2.26 7.10 7.42

0.198 0.385 0.450 0.490 1.540 1.610

98 97 99 99

1.30 3.40 3.90 4.35 13.00 13.60

Zinc hot dipping steel plate

380 x 850 x 660 380 x 1,200 x 660 470 x 1,380 x 1,250

50 67 15052 56

Finned tube

Non-flammable insulation

Centrifugal fan

900 2,100 3,6001,320 1,600

370 x 3160 260

4,200

137

68.6-137-196

720/1,080 1,680/2,520 2,880/4,3201,060/1,580 1,280/1,920 3,360/5,040

Option or field supply

Remote controller

O/ 12.7 O/ 22.2O/ 15.9

O/ 6.4 O/ 12.7O/ 9.5

25 (One side of male screw)

37 4940 50

Note 1 : The cooling capacities and electrical characteristics are measured under the conditions specified by JIS B 8615 based on thereference piping. The reference piping consists of 5 m of main piping and 2.5 m of branch piping connected with 0 meter height.

Note 2 : The sound levels are measured in an anechoic chamber in accordance with JIS B8616. Normally, the values measured inthe actual operating environment become larger than the indicated values due to the effects of external sound.

Note : Rated conditions Cooling : Indoor air temperature 27OC DB/19OC WB, Outdoor air temperature 35OC DBHeating : Indoor air temperature 20OC DB, Outdoor air temperature 7OC DB/6OC WB

Page 211: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

206

16

60Hz

Model name MMC-

(kW)

AP0151H

4.5/5.0

Power supply

Under Ceiling Type

Electricalcharacteris-tics

Running current (A)

Power consumption

Starting current

Appearance

Height x Width x DepthOuterdimension

Total weight

Heat exchanger

Soundproof/Heat-insulating material

Standard air flow(High/Mid./Low)

Fan

Motor

Fan unit

Controller

Room thermostat

Air filter

Gas side

Liquid side

Drain port

Connectingpipe

Sound pressure level(Note 2)(High/Mid./Low)

(kW)

(A)

(mm)

(kg)

(m3/h)

(W)

(mm)

(mm)

(Nominal dia. mm)

(db(A))

AP0181H

5.6/6.3

AP0241H

7.1/8.0

AP0271H

8.0/9.0

AP0361H

11.2/12.5

AP0481H

14.0/16.0

1 phase 60Hz 220V (Separate power supply for indoor units is required.)

0.30 0.34 0.44 0.82 0.87

0.033 0.038 0.050 0.091 0.110

0.43 0.48 0.62 1.17 1.25

White (Munsell 10Y 9.3/0.4)

210 x 910 x 680 210 x 1,180 x 680 210 x 1,595 x 680

22 26 34

Finned tube

Non-flammable insulation

Centrifugal fan

720/600/540 1,110/900/840 1,650/1,380/1,2001,800/1,560/1,320780/660/540

30 40 80

Remote controller

Attached

Standard filter (Long life filter)

O/ 12.7 O/ 15.9

O/ 6.4 O/ 9.5

20 (Polyvinyl chloride tube)

35/32/30 38/36/33 41/38/35 43/40/3736/33/30

Note 1 : The cooling capacities and electrical characteristics are measured under the conditions specified by JIS B 8615 based on thereference piping. The reference piping consists of 5 m of main piping and 2.5 m of branch piping connected with 0 meter height.

Note 2 : The sound levels are measured in an anechoic chamber in accordance with JIS B8616. Normally, the values measured inthe actual operating environment become larger than the indicated values due to the effects of external sound.

Note : Rated conditions Cooling : Indoor air temperature 27OC DB/19OC WB, Outdoor air temperature 35OC DBHeating : Indoor air temperature 20OC DB, Outdoor air temperature 7OC DB/6OC WB

Cooling/Heating capacity (Note 1)

Page 212: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

207

16

60Hz

Model name

Cooling/Heating capacity (Note 1)

AP0071H

2.2/2.5

Power supply

High Wall Type

Electricalcharacteris-tics

Running current (A)

Power consumption

Starting current

Suction grille and side panel

Discharge grille

Bottom surface

Appearance

Outerdimension Height x Width x Depth

Total weight

Heat exchanger

Soundproof/Heat-insulating material

Fanunit

Fan

Standard air flow (High/Mid./Low)

Motor outlet

Air filter

Controller

Connecting

pipe

Gas side

Liquid side

Drain port

Sound pressure level(Note 2)(High/Mid./Low)

MMK-

(kW)

(kW)

(A)

(mm)

(kg)

(W)

(m3/h)

(mm)

(mm)

(Nominal dia. mm)

(dB(A))

AP0091H

2.8/3.2

AP0121H

3.6/4.0

AP0151H

4.5/5.0

AP0181H

5.6/6.3

AP0241H

7.1/8.0

1 phase 60Hz 220V (Separate power supply for indoor units is required.)

0.32 0.34 0.35

0.035 0.037 0.040

0.46 0.48 0.60

Silky mist (Munsell 1Y 8.9/0.5)

City gray (Munsell N6.5)

Silky mist (Munsell 1Y 8.9/0.5)

368 x 895 x 210 368 x 1,055 x 210 368 x 1,430 x 210

18 19 25

Finned tube

Non-flammable insulation

Cross-flow fan

600/540/480 780/660/600 1,200/1,020/900

30

Remote controller

Standard filter (Simple filter)

O/ 9.5 O/ 12.7 O/ 15.9

O/ 6.4 O/ 9.5

20 (Polyvinyl chloride tube)

39/34/31 42/38/35 42/38/35

Note 1 : The cooling capacities and electrical characteristics are measured under the conditions specified by JIS B 8615 based on thereference piping. The reference piping consists of 5 m of main piping and 2.5 m of branch piping connected with 0 meter height.

Note 2 : The sound levels are measured in an anechoic chamber in accordance with JIS B8616. Normally, the values measured inthe actual operating environment become larger than the indicated values due to the effects of external sound.

Note : Rated conditions Cooling : Indoor air temperature 27OC DB/19OC WB, Outdoor air temperature 35OC DBHeating : Indoor air temperature 20OC DB, Outdoor air temperature 7OC DB/6OC WB

Page 213: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

208

16

60Hz

Model name MML-

(kW)Cooling/Heating capacity (Note 1)

AP0071H

2.2/2.5

Power supply

Floor Standing Cabinet Type

Electricalcharacteris-tics

Running current (A)

Power consumption

Power factor

Starting current

Appearance

Outerdimension

Height x Width x Depth

Total weight

Heat exchanger

Soundproof/Heat-insulating material

Connectingpipe

Fan

Motor outlet

Fan unit

Air filter

Controller

Gas side

Liquid side

Drain port

Sound pressure level(Note 2)(High/Mid./Low)

(kW)

(%)

(A)

(mm)

(kg)

(m3/h)

(W)

(mm)

(mm)

(Nominal dia. mm)

(dB(A))

Standard air flow(High/Mid./Low)

AP0091H

2.8/3.2

AP0121H

3.6/4.0

AP0151H

4.5/5.0

AP0181H

5.6/6.3

AP0241H

7.1/8.0

1 phase 60Hz 220V (Separate power supply for indoor units is required.)

0.25 0.44 0.53

0.053 0.092 0.113

96 95 97

0.60 0.80 1.10

Silky shade (1Y8.5/0.5)

630 x 950 x 230

37 40

Finned tube

Non-flammable insulation

Centrifugal fan

480/420/360 900/780/650 1,080/930/780

45 70

Remote controller

Standard filter (Simple filter)

O/ 9.5 O/ 12.7 O/ 15.9

O/ 6.4 O/ 9.5

20 (Polyvinyl chloride tube)

39/37/35 45/41/38 49/44/39

Note 1 : The cooling capacities and electrical characteristics are measured under the conditions specified by JIS B 8615 based on thereference piping. The reference piping consists of 5 m of main piping and 2.5 m of branch piping connected with 0 meter height.

Note 2 : The sound levels are measured in an anechoic chamber in accordance with JIS B8616. Normally, the values measured inthe actual operating environment become larger than the indicated values due to the effects of external sound.

Note : Rated conditions Cooling : Indoor air temperature 27OC DB/19OC WB, Outdoor air temperature 35OC DBHeating : Indoor air temperature 20OC DB, Outdoor air temperature 7OC DB/6OC WB

Page 214: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

209

16

60Hz

Model name MML-

(kW)Cooling/Heating capacity (Note 1)

AP0071BH

2.2/2.5

Power supply

Floor Standing Concealed Type

Electricalcharacteristics

Running current (A)

(kW)Power consumption

Power factor

Starting current

Appearance

Outerdimension

Height x Width xDepth

Total weight

Heat exchanger

Soundproof/Heat-insulating material

Fan

Standard air flow(High/Mid./Low)

Motor

Static pressure range

Fan unit

Air filter

Controller

Gas side

Liquid side

Drain port

Connectingpipe

Sound pressure level(Note 2)(High/Mid./Low)

(%)

(A)

(mm)

(kg)

(m3/h)

(W)

(kPa)

(mm)

(Nominal dia. mm)

(dB(A))

AP0091BH

2.8/3.2

AP0121BH

3.6/4.0

AP0151BH

4.5/5.0

AP0181BH

5.6/6.3

AP0241BH

7.1/8.0

1 phase 60Hz 220V (Separate power supply for indoor units is required.)

0.27 0.46 0.51

0.058 0.096 0.110

98 95 98

0.60 0.80 1.00

600 x 745 x 220 600 x 1,045 x 220

460/400/300 740/600/490

Zinc hot dipping steel plate

Finned tube

Non-flammable insulation

Centrifugal fan

950/790/640

19 70

0

Standard filter (Simple filter)

O/ 9.5 O/ 12.7 O/ 15.9

O/ 6.4 O/ 9.5

20 (One side of male screw)

36/34/32 42/37/33

(mm)

21 29

Remote controller

Note 1 : The cooling capacities and electrical characteristics are measured under the conditions specified by JIS B 8615 based on thereference piping. The reference piping consists of 5 m of main piping and 2.5 m of branch piping connected with 0 meter height.

Note 2 : The sound levels are measured in an anechoic chamber in accordance with JIS B8616. Normally, the values measured inthe actual operating environment become larger than the indicated values due to the effects of external sound.

Note : Rated conditions Cooling : Indoor air temperature 27OC DB/19OC WB, Outdoor air temperature 35OC DBHeating : Indoor air temperature 20OC DB, Outdoor air temperature 7OC DB/6OC WB

Page 215: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

210

16

60Hz

Model name MMF-

(kW)Cooling/Heating capacity (Note 1)

AP0151H

4.5/5.0

Power supply

Floor Standing Type

Electricalcharacteris-tics

Running current (A)

Power consumption

Power factor

Starting current

(kW)

(%)

(A)

1 phase 60Hz 220V (Separate power supply for indoor units is required.)

Appearance

Outerdimension

Height x Width xDepth

Total weight

Heat exchanger

Soundproof/Heat-insulating material

Fan

Motor

Standard air flow(High/Mid./Low)Fan unit

Air filter

Controller

Gas side

Liquid side

Drain port

Connectingpipe

Sound pressure level(Note 2)(High/Mid./Low)

(mm)

(kg)

(m3/h)

(W)

(mm)

(mm)

(Nominal dia. mm)

(dB(A))

AP0181H

5.6/6.3

AP0241H

7.1/8.0

AP0271H

8.0/9.0

AP0361H

11.2/12.5

AP0481H

14.0/16.0

AP0561H

16.0/18.0

0.67 0.90 1.37 1.75

0.146 0.195 0.295 0.380

99 9998

0.90 1.10 1.18 2.30

W : Silky Shade (1Y 8.5/0.5)

1,750 x 600 x 210 1,750 x 600 x 390

48 6549

Finned tube

Non-flammable insulation

Centrifugal fan

900/780/660 1,200/1,020/840 1,680/1,920/1,380 2,160/1,860/1,560

37 63 110 160

Remote controller

Standard filter (Simple filter)

O/ 12.7 O/ 15.9

O/ 6.4 O/ 9.5

20 (One side of male screw)

46/43/38 49/45/40 51/48/44 54/50/46

Note 1 : The cooling capacities and electrical characteristics are measured under the conditions specified by JIS B 8615 based on thereference piping. The reference piping consists of 5 m of main piping and 2.5 m of branch piping connected with 0 meter height.

Note 2 : The sound levels are measured in an anechoic chamber in accordance with JIS B8616. Normally, the values measured inthe actual operating environment become larger than the indicated values due to the effects of external sound.

Note : Rated conditions Cooling : Indoor air temperature 27OC DB/19OC WB, Outdoor air temperature 35OC DBHeating : Indoor air temperature 20OC DB, Outdoor air temperature 7OC DB/6OC WB

Page 216: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

211

16

Outdoor unit (50Hz)

50Hz

Equivalent HP

Model nameCooling Only

Heat Pump

Outdoor unit type

Cooling capacity (*1)

Standard heating capacity (*1)

Power supply (* 2)

Cooling

Heating

Electricalcharacteris-tics(*1)

Running current

Power consumption

Power factor

EER (Energy Efficiency Ratio)

Starting current

Running current

Power consumption

Power factor

EER (Energy Efficiency Ratio)

Starting currentExternal dimension

Total weightCooling Only

Heat Pump

Colour

Type

Motor output

Fan

Motor output

Air volume

Compressor

Fan unit

Heat exchanger

Refrigerant R410A(Charged refrigerant amount) (*3)

Cooling Only

Heat Pump

High-pressure switch

Protective devices

Gas side

Liquid side

Balance pipe

Gas side

Liquid side

Balance pipe

Connectingport dia

Connectingmethod

Refrigerantpipingspecifica-tions(*4)

Max. equivalent length

Max. real length

Max. total pipe length (Real length)

Max. height difference

Control wiring

Central remote controller

Max. No. of connected indoor units

Sound pressure level

MMY-

MMY-

(kW)

(kW)

(A)

(kW)

(%)(kW/kW)

(A)

(A)

(kW)

(%)

(kW/kW)

(mm)

(kg)

(kg)

(A)

(kW)

(kW)

(m3/h)

(kg)

(kg)

(MPa)

(mm)

(mm)

(mm)

(m)

(m)

(m)

(m)

(dB(A))

Equivalent to5HP

MAP0501T8

MAP0501HT8Inverter unit

14.0

16.0

3 phase 50Hz 400V (380 - 415V)

5.85

3.65

6.09

3.84

91

Height 1,800 x Width 990 x Depth 750

227

228

1.1 x 2

Silky shade (Munsell 1Y8.5/0.5)

Hermetic type

Propeller fan

0.60

9,000

Finned tube

8.0

8.5OFF : 2.90 ON : 3.73

(*5)

O/ 15.9

O/ 9.5O/ 9.5

Flare

Flare

Flare

175150 (If the total bend length exceeds 150m, use the max equivalent length as the standard.)

300Outdoor unit is higher than indoor unit : 50

Outdoor unit is lower than indoor unit : 40 (*6)

Shield wire 1.25mm2 x 2 cores. up to 2000m

When connecting to outdoor unit : (Shield wire) 1.25mm2 x 2 cores. up to 1000m(Shield wire) 2.0mm2 x 2 cores. up to 2000m

8

55

10

56

13

57

16

58

20

59

Equivalent to6HP

MAP0601T8

MAP0601HT8

Equivalent to8HP

MAP0801T8

MAP0801HT8

Equivalent to10HP

MAP1001T8

MAP1001HT8

Equivalent to12HP

MAP1201T8

MAP1201HT8

16.0

18.0

22.4

25.0

28.0

31.5

33.5

37.5

90

3.84

1.0

4.17

1.0

7.28

4.64

7.08

4.56

93

92

3.45

1.0

3.95

1.0

8.62

5.67

8.93

5.88

95

95

3.95

1.0

4.25

1.0

11.55

7.68

11.98

7.97

96

96

3.65

1.0

3.95

1.0

18.30

11.92

15.65

10.19

94

94

2.81

1.0

3.68

1.0

256

258

1.4 x 2 2.3 x 2 3.1 x 2 4.2 x 2

9,000 9,900 10,500

11

12.5

O/ 19.1 O/ 22.2 O/ 28.6

O/ 12.7

Brazing

*1 : Rated conditions Cooling : Indoor air temperature 27OC DB/19OC WB, Outdoor air temperature 35OC DBHeating : Indoor air temperature 20OC DB, Outdoor air temperature 7OC DB/6OC WB

The standard piping means that main pipe length is 5 m, branching pipe length 2.5 m of branch piping connected with a 0 meter height.

*2 : The source voltage must not fluctuate more than +-10%.

*3 : The amount does not consider extra piping lengths. Refrigerant must be added on site in accordance with the actual piping length.

*4 : The maximum total piping length indicates the sum of one-way piping lengths on the liquid side or gas side.System safety protection*5 : Discharge temp. sensor, Suction temp. sensor, Compressor case thermostat, High-pressure Switch, Over-current sensor,

High-pressure Sensor, Low pressure sensor, Over-current relay.

*6 : 30m when the height difference between indoor units exceeds 3m.

Page 217: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

212

16

50Hz

Outdoor unit (Combination) (50Hz)

Equivalent HP

Set Model name Cooling OnlyHeat Pump

Outdoor unit type

Cooling

Heating

Electricalcharacteristics(*1)

Running current

External dimension

Total weight

MMY-MMY-

Equivalent to 14HP

Outdoor unit modelCooling OnlyHeat Pump

Rated cooling capacity (*1)

EER(Energy Efficiency Ratio)

Standard heating capacity (*1)Power supply (*2)

Power consumption

Power factor

Starting currentRunning current

Power consumptionPower factor

Starting current

Cooling OnlyHeat Pump

Colour

CompressorTypeMotor outputFanMotor outputAir volume

Fan unit

Heat exchanger

Refrigerant R410ACharged amount (*3)

Cooling OnlyHeat Pump

High-pressure switchProtective devices

Refrigerantpipe spec.(* 4)

Connectingport dia.

Connectingmethod

Gas sideLiquid sideBalance sideGas side

Liquid sideBalance side

Max. equivalent length

Max. real lengthMax. total pipe length(Real length)

Max. height difference

Control wiring

Central remote controller

Max. No. of connected indoor unitsSound pressure level

MMY-MMY-

(kW)(kW)

(A)(kW)

(%)(kW/kW)

(A)(A)

(kW)(%)

EER(Energy Efficiency Ratio)

(A)

(kg)(kg)

(kW)

(kW)(m3/h)

(kg)(kg)

(MPa)

(m)(m)(m)

(m)

(m)

(m)

(m)

(dB(A))

AP1401T8Equivalent to 16HP

AP1601T8Equivalent to 18HP

AP1801T8Equivalent to 20HP

AP2001T8

InverterAP1401HT8 AP1601HT8 AP1801HT8 AP2001HT8

MAP0801T8MAP0801HT8

MAP0601T8MAP0601HT8

MAP0801T8MAP0801HT8

MAP0801T8MAP0801HT8

MAP1001T8MAP1001HT8

MAP0801T8MAP0801HT8

MAP1001T8MAP1001HT8

MAP1001T8MAP1001HT8

38.443.0

4550.0

50.456.5

56.063.0

3 phase 50Hz 400V (380 - 415V)17.0811.12

94

18.5412.20

95

21.2914.16

96

24.3116.17

96

3.45 3.69 3.56 3.46

1.0 1.0 1.0 1.0

16.83 18.65 21.61 24.7510.96 12.28 14.37 16.46

94 95 96 96

3.92 4.07 3.93 3.83

1.0 1.0 1.0 1.0Height 1,800 x Width 990 x Depth 750

256258

227228

256258

256258

256258

256258

256258

256258

Silky shade (Munsell 1Y8.5/0.5)Hermetic type

2.3 x 2 1.4 x 2 3.1 x 2 2.3 x 22.3 x 2 3.1 x 2Propeller fan

0.69,900 9,000 10,500 9,9009,900 10,500

Finned tube

11.0 8.0 11.0 11.0 11.0 11.0 11.0 11.012.5 8.5 12.5 12.5 12.5 12.5 12.5 12.5

OFF : 2.90 ON : 3.73(*5)

O/ 22.2 O/ 19.1O/ 12.7 O/ 9.5

O/ 22.2O/ 12.7

O/ 9.5Brazing

Flare

Flare

175

150 (If the total bend length exceeds 150m, use the max equivalent length as the standard.)

300

Outdoor unit is higher than indoor unit : 50Outdoor unit is lower than indoor unit : 40 (*6)Shield wire 1.25mm2 x 2 cores. up to 2000m

When connecting to outdoor unit : (Shield wire) 1.25mm2 x 2 cores. up to 1000m, and (Shield wire) 2.0mm2 x 2 cores. up to 2000m

2359.5

2760

3060.5

3361

(mm)

(kW/kW)

*1 : Rated conditions Cooling : Indoor air temperature 27OC DB/19OC WB, Outdoor air temperature 35OC DBHeating : Indoor air temperature 20OC DB, Outdoor air temperature 7OC DB/6OC WB

The standard piping means that main pipe length is 5 m, branching pipe length 2.5 m of branch piping connected with a 0 meter height.

*2 : The source voltage must not fluctuate more than +-10%.

*3 : The amount does not consider extra piping lengths. Refrigerant must be added on site in accordance with the actual piping length.

*4 : The maximum total piping length indicates the sum of one-way piping lengths on the liquid side or gas side.System safety protection*5 : Discharge temp. sensor, Suction temp. sensor, Compressor case thermostat, High-pressure Switch, Over-current sensor,

High-pressure Sensor, Low pressure sensor, Over-current relay.

*6 : 30m when the height difference between indoor units exceeds 3m.

Page 218: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

213

16

50Hz

Equivalent HP

Set Model nameCooling Only

Outdoor unit type

MMY-Equivalent to 22HP

AP2201T8Heat Pump

Cooling OnlyHeat Pump

Rated cooling capacity (*1)Standard heating capacity (*1)Power supply (*2)

Electricalcharacteristics(*1)

Cooling

Heating

Running currentPower consumptionPower factorEER(Energy Efficiency Ratio)Starting currentRunning currentPower consumptionPower factor

Starting current

EER(Energy Efficiency Ratio)

External dimension

Total weightCooling OnlyHeat Pump

Colour

CompressorTypeMotor outputFan

Motor outputAir volume

Fan unit

Heat exchanger

Refrigerant R410ACharged amount (*3)

Cooling OnlyHeat Pump

High-pressure switchProtective devices

Connectingport dia.

Connectingmethod

Gas sideLiquid sideBalance sideGas sideLiquid sideBalance side

Max. equivalent length

Max. real length

Max. height difference

Max. total pipe length(Real length)

Control wiring

Central remote controller

Max. No. of connected indoor units

Sound pressure level

(kW)

MMY-

MMY-MMY-

(kW)

(A)(kW)(%)

(kW/kW)

(A)(A)

(kW)(%)

(kW/kW)

(A)(mm)

(kg)

(kg)

(kW)

(kW)(m3/h)

(kg)(kg)

(MPa)

(mm)(mm)(mm)

(m)(m)

(m)

(m)

(dB(A))

AP2211T8AP2201HT8 AP2211HT8

InverterMAP0801T8

MAP0801HT8MAP0801T8

MAP0801HT8MAP0601T8

MAP0601HT8MAP1201T8

MAP1201HT8MAP1001T8

MAP1001HT861.569.0

3 phase 50Hz 400V (380 - 415V)26.42 31.0117.39 20.41

95

3.54 3.01

1.0 1.026.36 28.3817.35 18.68

95

3.98 3.69

1.0 1.0Height 1,800 x Width 990 x Depth 750

256 256 227 256 256258 258 228 258 258

Silky shade (Munsell 1Y8.5/0.5)Hermetic type

2.3 x 2 1.4 x 2 4.2 x 2 3.1 x 2Propeller fan

0.69,900 9,000 10,500

Finned tube11.0 11.0 8.0 11.0 11.0

12.5 12.5 8.5 12.5 12.5OFF : 2.90 ON : 3.73

(*5)O/ 22.2 O/ 19.1 O/ 28.6 O/ 22.2O/ 12.7 O/ 9.5 O/ 12.7

O/ 9.5Brazing

FlareFlare175

150 (If the total bend length exceeds 150m, use the max equivalent length as the standard.)

300

Outdoor unit is higher than indoor unit : 50Outdoor unit is lower than indoor unit : 40 (*6)Shield wire 1.25mm2 x 2 cores. up to 2000m

3761.5

When connecting to outdoor unit : (Shield wire) 1.25mm2 x 2 cores. up to 1000m, and (Shield wire) 2.0mm2 x 2 cores. up to 2000m

Refrigerantpipe spec.(*4)

Outdoor unit model

*1 : Rated conditions Cooling : Indoor air temperature 27OC DB/19OC WB, Outdoor air temperature 35OC DBHeating : Indoor air temperature 20OC DB, Outdoor air temperature 7OC DB/6OC WB

The standard piping means that main pipe length is 5 m, branching pipe length 2.5 m of branch piping connected with a 0 meter height.

*2 : The source voltage must not fluctuate more than +-10%.

*3 : The amount does not consider extra piping lengths. Refrigerant must be added on site in accordance with the actual piping length.

*4 : The maximum total piping length indicates the sum of one-way piping lengths on the liquid side or gas side.System safety protection*5 : Discharge temp. sensor, Suction temp. sensor, Compressor case thermostat, High-pressure Switch, Over-current sensor,

High-pressure Sensor, Low pressure sensor, Over-current relay.

*6 : 30m when the height difference between indoor units exceeds 3m.

Page 219: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

214

16

50Hz

Equivalent to 24HP

AP2401T8

Equivalent HP

Set Model name Cooling OnlyHeat Pump

Outdoor unit type

Cooling

Heating

Electricalcharacteristics(*1)

Running current

External dimension

Total weight

MMY-MMY-

Outdoor unit modelCooling OnlyHeat Pump

Rated cooling capacity (*1)

EER(Energy Efficiency Ratio)

Standard heating capacity (*1)Power supply (*2)

Power consumptionPower factor

Starting currentRunning currentPower consumptionPower factor

Starting current

Cooling OnlyHeat Pump

Colour

Compressor TypeMotor outputFanMotor outputAir volume

Fan unit

Heat exchanger

Refrigerant R410ACharged amount (*3)

Cooling OnlyHeat Pump

High-pressure switchProtective devices

Refrigerantpipe spec.(* 4)

Connectingport dia.

Connectingmethod

Gas sideLiquid sideBalance sideGas side

Liquid sideBalance side

Max. equivalent length

Max. real lengthMax. total pipe length(Real length)

Max. height difference

Control wiring

Central remote controller

Max. No. of connected indoor unitsSound pressure level

MMY-MMY-

(kW)(kW)

(A)

(kW)(%)

(kW/kW)

(A)(A)

(kW)(%)

EER(Energy Efficiency Ratio)

(A)

(kg)(kg)

(kW)

(kW)

(m3/h)

(kg)(kg)

(MPa)

(mm)(mm)

(mm)

(m)

(m)

(m)

(m)

(dB(A))

(mm)

(kW/kW)

AP2411T8AP2401HT8 AP2411HT8

InverterMAP0801T8 MAP0801T8 MAP0801T8 MAP1201T8 MAP1201T8

MAP0801HT8 MAP0801HT8 MAP0801HT8 MAP1201HT8 MAP1201HT868.076.5

3 phase 50Hz 400V (380 - 415V)27.73 38.02

18.44 25.0296 95

3.69 2.72

1.0 1.027.96 32.0618.79 21.32

97 96

4.07 3.59

1.0 1.0Height 1,800 x Width 990 x Depth 750

256 256 256 256 256258 258 258 258 258

Silky shade (Munsell 1Y8.5/0.5)Hermetic type

2.3 x 2 4.2 x 2

9,900 10,500

Propeller fan0.6

Finned tube11.0 11.0 11.0 11.0 11.012.5 12.5 12.5 12.5 12.5

OFF : 2.90 ON : 3.73(*5)

O/ 22.2 O/ 28.6O/ 12.7O/ 9.5

BrazingFlareFlare175

150 (If the total bend length exceeds 150m, use the max equivalent length as the standard.)

300

Outdoor unit is higher than indoor unit : 50Outdoor unit is lower than indoor unit : 40 (*6)Shield wire 1.25mm2 x 2 cores. up to 2000m

When connecting to outdoor unit : (Shield wire) 1.25mm2 x 2 cores. up to 1000m, and (Shield wire) 2.0mm2 x 2 cores. up to 2000m

4062

*1 : Rated conditions Cooling : Indoor air temperature 27OC DB/19OC WB, Outdoor air temperature 35OC DBHeating : Indoor air temperature 20OC DB, Outdoor air temperature 7OC DB/6OC WB

The standard piping means that main pipe length is 5 m, branching pipe length 2.5 m of branch piping connected with a 0 meter height.

*2 : The source voltage must not fluctuate more than +-10%.

*3 : The amount does not consider extra piping lengths. Refrigerant must be added on site in accordance with the actual piping length.

*4 : The maximum total piping length indicates the sum of one-way piping lengths on the liquid side or gas side.System safety protection*5 : Discharge temp. sensor, Suction temp. sensor, Compressor case thermostat, High-pressure Switch, Over-current sensor,

High-pressure Sensor, Low pressure sensor, Over-current relay.

*6 : 30m when the height difference between indoor units exceeds 3m.

Page 220: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

215

16

50Hz

Equivalent HP

Set Model nameCooling OnlyHeat Pump

Outdoor unit type

Cooling

Heating

Electricalcharacteristics(*1)

Running current

External dimension

Total weight

MMY-MMY-

Outdoor unit modelCooling OnlyHeat Pump

Rated cooling capacity (*1)

EER(Energy Efficiency Ratio)

Standard heating capacity (*1)Power supply (*2)

Power consumptionPower factor

Starting currentRunning currentPower consumptionPower factor

Starting current

Cooling OnlyHeat Pump

Colour

CompressorTypeMotor output

FanMotor outputAir volume

Fan unit

Heat exchanger

Refrigerant R410ACharged amount (*3)

Cooling OnlyHeat Pump

High-pressure switchProtective devices

Refrigerantpipe spec.(*4)

Connectingport dia.

Connectingmethod

Gas sideLiquid sideBalance sideGas sideLiquid sideBalance side

Max. equivalent length

Max. real lengthMax. total pipe length(Real length)

Max. height difference

Control wiring

Central remote controller

Max. No. of connected indoor unitsSound pressure level

MMY-MMY-

(kW)(kW)

(A)(kW)(%)

(kW/kW)

(A)(A)

(kW)(%)

EER(Energy Efficiency Ratio)

(A)

(kg)(kg)

(kW)

(kW)

(m3/h)

(kg)(kg)

(MPa)

(mm)(mm)

(mm)

(m)

(m)

(m)

(m)

(dB(A))

(mm)

(kW/kW)

Equivalent to 26HP

AP2601T8

Equivalent to 28HP

AP2801T8

Equivalent to 30HP

AP3001T8AP2601HT8 AP2801HT8 AP3001HT8

InverterMAP1001T8 MAP0801T8 MAP0801T8 MAP1001T8 MAP1001T8 MAP0801T8 MAP1001T8 MAP1001T8 MAP1001T8MAP1001HT8 MAP0801HT8 MAP0801HT8 MAP1001HT8 MAP1001HT8 MAP0801HT8 MAP1001HT8 MAP1001HT8 MAP1001HT8

3 phase 50Hz 400V (380 - 415V)

73 78.5 84.081.5 88.0 95.0

30.51 33.48 36.4820.29 22.27 24.26

96

3.60 3.52 3.46

1.0 1.0 1.031.16 33.98 36.9320.51 22.60 24.82

95 96 97

3.97 3.89 3.83

1.0 1.0 1.0Height 1,800 x Width 990 x Depth 750

256 256 256 256 256 256 256 256 256258 258 258 258 258 258 258 258 258

Silky shade (Munsell 1Y8.5/0.5)Hermetic type

2.3 x 2 3.1 x 2 2.3 x 2 3.1 x 2Propeller fan

0.610,500 9,900 10,500 9,900 10,500

Finned tube11.0 11.0 11.0 11.0 11.0 11.0 11.0 11.0 11.012.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5

OFF : 2.90 ON : 3.73(*5)

O/ 22.2O/ 12.7O/ 9.5

BrazingFlareFlare

175

150 (If the total bend length exceeds 150m, use the max equivalent length as the standard.)

300

Outdoor unit is higher than indoor unit : 50Outdoor unit is lower than indoor unit : 40 (*6)Shield wire 1.25mm2 x 2 cores. up to 2000m

When connecting to outdoor unit : (Shield wire) 1.25mm2 x 2 cores. up to 1000m, and (Shield wire) 2.0mm2 x 2 cores. up to 2000m

4362

4762.5

4863

*1 : Rated conditions Cooling : Indoor air temperature 27OC DB/19OC WB, Outdoor air temperature 35OC DBHeating : Indoor air temperature 20OC DB, Outdoor air temperature 7OC DB/6OC WB

The standard piping means that main pipe length is 5 m, branching pipe length 2.5 m of branch piping connected with a 0 meter height.

*2 : The source voltage must not fluctuate more than +-10%.

*3 : The amount does not consider extra piping lengths. Refrigerant must be added on site in accordance with the actual piping length.

*4 : The maximum total piping length indicates the sum of one-way piping lengths on the liquid side or gas side.System safety protection*5 : Discharge temp. sensor, Suction temp. sensor, Compressor case thermostat, High-pressure Switch, Over-current sensor,

High-pressure Sensor, Low pressure sensor, Over-current relay.

*6 : 30m when the height difference between indoor units exceeds 3m.

Page 221: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

216

16

50Hz

Equivalent HP

Set Model nameCooling OnlyHeat Pump

Outdoor unit type

Cooling

Heating

Electricalcharacteristics(*1)

Running current

External dimension

Total weight

MMY-MMY-

Outdoor unit modelCooling OnlyHeat Pump

Rated cooling capacity (*1)

EER(Energy Efficiency Ratio)

Standard heating capacity (*1)Power supply (*2)

Power consumptionPower factor

Starting currentRunning currentPower consumption

Power factor

Starting current

Cooling OnlyHeat Pump

Colour

CompressorTypeMotor output

FanMotor outputAir volume

Fan unit

Heat exchanger

Refrigerant R410ACharged amount (*3)

Cooling OnlyHeat Pump

High-pressure switchProtective devices

Refrigerantpipe spec.(* 4)

Connectingport dia.

Connectingmethod

Gas sideLiquid sideBalance side

Gas sideLiquid sideBalance side

Max. equivalent length

Max. real lengthMax. total pipe length(Real length)

Max. height difference

Control wiring

Central remote controller

Max. No. of connected indoor unitsSound pressure level

MMY-MMY-

(kW)(kW)

(A)(kW)(%)

(kW/kW)

(A)(A)

(kW)(%)

EER(Energy Efficiency Ratio)

(A)

(kg)(kg)

(kW)

(kW)(m3/h)

(kg)(kg)

(MPa)

(mm)(mm)(mm)

(m)

(m)

(m)

(m)

(dB(A))

(mm)

(kW/kW)

Equivalent to 32HP

AP3201T8 AP3211T8AP3201HT8 AP3211HT8

InverterMAP0801T8MAP0801HT8

MAP0801T8MAP0801HT8

MAP0801T8MAP0801HT8

MAP0801T8MAP0801HT8

MAP1201T8MAP1201HT8

MAP1001T8MAP1001HT8

MAP1001T8MAP1001HT8

90.0100.0

3 phase 50Hz 400V (380 - 415V)37.09 43.0824.41 28.65

95 96

3.69 3.14

1.0 1.037.32 40.6924.56 26.78

95 95

4.07 3.73

1.0 1.0Height 1,800 x Width 990 x Depth 750

256258

256258

256258

256258

256258

256258

256258

Silky shade (Munsell 1Y8.5/0.5)Hermetic type

2.3 x 2 4.2 x 2 3.1 x 2Propeller fan

0.6

9,900 10,500Finned tube

11.012.5

11.012.5

11.012.5

11.012.5

11.012.5

11.012.5

11.012.5

OFF : 2.90 ON : 3.73(*5)

O/ 22.2 O/ 28.6 O/ 22.2O/ 12.7O/ 9.5

BrazingFlareFlare

175

150 (If the total bend length exceeds 150m, use the max equivalent length as the standard.)

300

Outdoor unit is higher than indoor unit : 50Outdoor unit is lower than indoor unit : 40 (*6)Shield wire 1.25mm2 x 2 cores. up to 2000m

When connecting to outdoor unit : (Shield wire) 1.25mm2 x 2 cores. up to 1000m, and (Shield wire) 2.0mm2 x 2 cores. up to 2000m

4863

*1 : Rated conditions Cooling : Indoor air temperature 27OC DB/19OC WB, Outdoor air temperature 35OC DBHeating : Indoor air temperature 20OC DB, Outdoor air temperature 7OC DB/6OC WB

The standard piping means that main pipe length is 5 m, branching pipe length 2.5 m of branch piping connected with a 0 meter height.

*2 : The source voltage must not fluctuate more than +-10%.

*3 : The amount does not consider extra piping lengths. Refrigerant must be added on site in accordance with the actual piping length.

*4 : The maximum total piping length indicates the sum of one-way piping lengths on the liquid side or gas side.System safety protection*5 : Discharge temp. sensor, Suction temp. sensor, Compressor case thermostat, High-pressure Switch, Over-current sensor,

High-pressure Sensor, Low pressure sensor, Over-current relay.

*6 : 30m when the height difference between indoor units exceeds 3m.

Page 222: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

217

16

50Hz

Equivalent HP

Set Model name Cooling OnlyHeat Pump

Outdoor unit type

Cooling

Heating

Electricalcharacteristics(*1)

Running current

External dimension

Total weight

MMY-MMY-

Outdoor unit modelCooling OnlyHeat Pump

Rated cooling capacity (*1)

EER(Energy Efficiency Ratio)

Standard heating capacity (*1)Power supply (*2)

Power consumptionPower factor

Starting currentRunning currentPower consumptionPower factor

Starting current

Cooling OnlyHeat Pump

Colour

CompressorTypeMotor outputFanMotor outputAir volume

Fan unit

Heat exchangerRefrigerant R410ACharged amount (*3)

Cooling OnlyHeat Pump

High-pressure switchProtective devices

Refrigerantpipe spec.(*4)

Connectingport dia.

Connectingmethod

Gas sideLiquid sideBalance sideGas sideLiquid sideBalance side

Max. equivalent length

Max. real lengthMax. total pipe length(Real length)

Max. height difference

Control wiring

Central remote controller

Max. No. of connected indoor unitsSound pressure level

MMY-MMY-

(kW)(kW)

(A)(kW)(%)

(kW/kW)

(A)(A)

(kW)(%)

EER(Energy Efficiency Ratio)

(A)

(kg)(kg)

(kW)

(kW)(m3/h)

(kg)(kg)

(MPa)

(mm)(mm)(mm)

(m)

(m)

(m)

(m)

(dB(A))

(mm)

(kW/kW)

Equivalent to 34HPAP3401T8 AP3411T8

AP3401HT8 AP3411HT8Inverter

MAP1001T8MAP1001HT8

MAP0801T8MAP0801HT8

MAP0801T8MAP0801HT8

MAP0801T8MAP0801HT8

MAP1201T8MAP1201HT8

MAP1201T8MAP1201HT8

MAP1001T8MAP1001HT8

96.0108.0

3 phase 50Hz 400V (380 - 415V)39.89 50.2626.53 33.08

96 95

3.62 2.90

1.0 1.040.22 44.4227.03 29.54

97 96

4.00 3.66

1.0 1.0Height 1,800 x Width 990 x Depth 750

256258

256258

256258

256258

256258

256258

256258

11.012.5

11.012.5

11.012.5

11.012.5

11.012.5

11.012.5

11.012.5

Silky shade (Munsell 1Y8.5/0.5)Hermetic type

3.1 x 2 2.3 x 2 4.2 x 2 3.1 x 2

10,500 9,900 10,500

Propeller fan

0.6

Finned tube

OFF : 2.90 ON : 3.73(*5)

O/ 22.2 O/ 28.6 O/ 22.2

O/ 12.7O/ 9.5

BrazingFlareFlare175

150 (If the total bend length exceeds 150m, use the max equivalent length as the standard.)

300

Outdoor unit is higher than indoor unit : 50Outdoor unit is lower than indoor unit : 40 (*6)Shield wire 1.25mm2 x 2 cores. up to 2000m

When connecting to outdoor unit : (Shield wire) 1.25mm2 x 2 cores. up to 1000m, and (Shield wire) 2.0mm2 x 2 cores. up to 2000m

4863.5 63.5

*1 : Rated conditions Cooling : Indoor air temperature 27OC DB/19OC WB, Outdoor air temperature 35OC DBHeating : Indoor air temperature 20OC DB, Outdoor air temperature 7OC DB/6OC WB

The standard piping means that main pipe length is 5 m, branching pipe length 2.5 m of branch piping connected with a 0 meter height.

*2 : The source voltage must not fluctuate more than +-10%.

*3 : The amount does not consider extra piping lengths. Refrigerant must be added on site in accordance with the actual piping length.

*4 : The maximum total piping length indicates the sum of one-way piping lengths on the liquid side or gas side.System safety protection*5 : Discharge temp. sensor, Suction temp. sensor, Compressor case thermostat, High-pressure Switch, Over-current sensor,

High-pressure Sensor, Low pressure sensor, Over-current relay.

*6 : 30m when the height difference between indoor units exceeds 3m.

Page 223: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

218

16

50Hz

Equivalent HP

Set Model nameCooling OnlyHeat Pump

Outdoor unit type

Cooling

Heating

Electricalcharacteristics(*1)

Running current

External dimension

Total weight

MMY-MMY-

Outdoor unit modelCooling OnlyHeat Pump

Rated cooling capacity (*1)

EER(Energy Efficiency Ratio)

Standard heating capacity (*1)Power supply (*2)

Power consumptionPower factor

Starting currentRunning currentPower consumptionPower factor

Starting current

Cooling OnlyHeat Pump

Colour

CompressorTypeMotor outputFanMotor outputAir volume

Fan unit

Heat exchanger

Refrigerant R410ACharged amount (*3)

Cooling OnlyHeat Pump

High-pressure switchProtective devices

Refrigerantpipe spec.(*4)

Connectingport dia.

Connectingmethod

Gas sideLiquid sideBalance sideGas sideLiquid sideBalance side

Max. equivalent length

Max. real lengthMax. total pipe length(Real length)

Max. height difference

Control wiring

Central remote controller

Max. No. of connected indoor unitsSound pressure level

MMY-MMY-

(kW)(kW)

(A)(kW)(%)

(kW/kW)

(A)(A)

(kW)(%)

EER(Energy Efficiency Ratio)

(A)

(kg)(kg)

(kW)

(kW)(m3/h)

(kg)(kg)

(MPa)

(mm)(mm)(mm)

(m)

(m)

(m)

(m)

(dB(A))

(mm)

(kW/kW)

Equivalent to 36HPAP3601T8 AP3611T8

AP3601HT8 AP3611HT8Inverter

MAP1001T8MAP1001HT8

MAP1001T8MAP1001HT8

MAP0801T8MAP0801HT8

MAP0801T8MAP0801HT8

MAP1201T8MAP1201HT8

MAP1201T8MAP1201HT8

MAP1201T8MAP1201HT8

101.0113.0

3 phase 50Hz 400V (380 - 415V)42.67 57.0628.38 37.16

96 94

3.56 2.72

1.0 1.043.21 48.3628.74 31.49

96 94

3.93 3.59

1.0 1.0Height 1,800 x Width 990 x Depth 750

256258

256258

256258

256258

256258

256258

256258

Silky shade (Munsell 1Y8.5/0.5)Hermetic type

3.1 x 2 4.2 x 2Propeller fan

0.610,500 10,500

Finned tube

11.012.5

11.012.5

11.012.5

11.012.5

11.012.5

11.012.5

11.012.5

OFF : 2.90 ON : 3.73(*5)

O/ 22.2 O/ 28.6O/ 12.7O/ 9.5

BrazingFlareFlare

175

150 (If the total bend length exceeds 150m, use the max equivalent length as the standard.)

300

Outdoor unit is higher than indoor unit : 50Outdoor unit is lower than indoor unit : 40 (*6)Shield wire 1.25mm2 x 2 cores. up to 2000m

When connecting to outdoor unit : (Shield wire) 1.25mm2 x 2 cores. up to 1000m, and (Shield wire) 2.0mm2 x 2 cores. up to 2000m

4863.5

2.3 x 2

9,900

64

*1 : Rated conditions Cooling : Indoor air temperature 27OC DB/19OC WB, Outdoor air temperature 35OC DBHeating : Indoor air temperature 20OC DB, Outdoor air temperature 7OC DB/6OC WB

The standard piping means that main pipe length is 5 m, branching pipe length 2.5 m of branch piping connected with a 0 meter height.

*2 : The source voltage must not fluctuate more than +-10%.

*3 : The amount does not consider extra piping lengths. Refrigerant must be added on site in accordance with the actual piping length.

*4 : The maximum total piping length indicates the sum of one-way piping lengths on the liquid side or gas side.System safety protection*5 : Discharge temp. sensor, Suction temp. sensor, Compressor case thermostat, High-pressure Switch, Over-current sensor,

High-pressure Sensor, Low pressure sensor, Over-current relay.

*6 : 30m when the height difference between indoor units exceeds 3m.

Page 224: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

219

16

50Hz

Equivalent HP

Set Model nameCooling OnlyHeat Pump

Outdoor unit type

Cooling

Heating

Electricalcharacteristics(*1)

Running current

External dimension

Total weight

MMY-MMY-

Outdoor unit modelCooling OnlyHeat Pump

Rated cooling capacity (*1)

EER(Energy Efficiency Ratio)

Standard heating capacity (*1)Power supply (*2)

Power consumptionPower factor

Starting currentRunning currentPower consumptionPower factor

Starting current

Cooling OnlyHeat Pump

Colour

CompressorTypeMotor outputFanMotor outputAir volume

Fan unit

Heat exchanger

Refrigerant R410ACharged amount (*3)

Cooling OnlyHeat Pump

High-pressure switch

Protective devices

Refrigerantpipe spec.(*4)

Connectingport dia.

Connectingmethod

Gas sideLiquid side

Balance sideGas sideLiquid sideBalance side

Max. equivalent length

Max. real lengthMax. total pipe length(Real length)

Max. height difference

Control wiring

Central remote controller

Max. No. of connected indoor unitsSound pressure level

MMY-MMY-

(kW)(kW)

(A)(kW)(%)

(kW/kW)

(A)(A)

(kW)(%)

EER(Energy Efficiency Ratio)

(A)

(kg)(kg)

(kW)

(kW)(m3/h)

(kg)(kg)

(MPa)

(mm)

(mm)(mm)

(m)

(m)

(m)

(m)

(dB(A))

(mm)

(kW/kW)

Equivalent to 38HP

AP3801T8 AP4001T8AP3801HT8 AP4001HT8

InverterMAP1001T8MAP1001HT8

106.5

3 phase 50Hz 400V (380 - 415V)45.65

3.88

Height 1,800 x Width 990 x Depth 750256

Silky shade (Munsell 1Y8.5/0.5)Hermetic type

3.1 x 2Propeller fan

0.610,500

Finned tube

11.0

OFF : 2.90 ON : 3.73(*5)

O/ 22.2O/ 12.7

O/ 9.5Brazing

FlareFlare

175

150 (If the total bend length exceeds 150m, use the max equivalent length as the standard.)

300

Outdoor unit is higher than indoor unit : 50Outdoor unit is lower than indoor unit : 40 (*6)Shield wire 1.25mm2 x 2 cores. up to 2000m

When connecting to outdoor unit : (Shield wire) 1.25mm2 x 2 cores. up to 1000m, and (Shield wire) 2.0mm2 x 2 cores. up to 2000m

4864

Equivalent to 40HP

MAP1001T8MAP1001HT8

MAP1001T8MAP1001HT8

MAP0801T8MAP0801HT8

MAP1001T8MAP1001HT8

MAP1001T8MAP1001HT8

MAP1001T8MAP1001HT8

MAP1001T8MAP1001HT8

119.5112.0126.5

48.6330.36 32.34

96

3.51 3.46

1.0 1.0

46.36 49.6930.83 33.05

96

1.0 1.0

258256258

256258

256258

256258

256258

256258

256258

2.3 x 2 3.1 x 2

9,900 10,500

12.511.012.5

11.012.5

11.012.5

11.012.5

11.012.5

11.012.5

11.012.5

3.83

*1 : Rated conditions Cooling : Indoor air temperature 27OC DB/19OC WB, Outdoor air temperature 35OC DBHeating : Indoor air temperature 20OC DB, Outdoor air temperature 7OC DB/6OC WB

The standard piping means that main pipe length is 5 m, branching pipe length 2.5 m of branch piping connected with a 0 meter height.

*2 : The source voltage must not fluctuate more than +-10%.

*3 : The amount does not consider extra piping lengths. Refrigerant must be added on site in accordance with the actual piping length.

*4 : The maximum total piping length indicates the sum of one-way piping lengths on the liquid side or gas side.System safety protection*5 : Discharge temp. sensor, Suction temp. sensor, Compressor case thermostat, High-pressure Switch, Over-current sensor,

High-pressure Sensor, Low pressure sensor, Over-current relay.

*6 : 30m when the height difference between indoor units exceeds 3m.

Page 225: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

220

16

50Hz

Equivalent HP

Set Model nameCooling OnlyHeat Pump

Outdoor unit type

Cooling

Heating

Electricalcharacteristics(*1)

Running current

External dimension

Total weight

MMY-MMY-

Outdoor unit modelCooling OnlyHeat Pump

Rated cooling capacity (*1)

EER(Energy Efficiency Ratio)

Standard heating capacity (*1)Power supply (*2)

Power consumptionPower factor

Starting currentRunning currentPower consumptionPower factor

Starting current

Cooling OnlyHeat Pump

Colour

CompressorTypeMotor outputFanMotor outputAir volume

Fan unit

Heat exchanger

Refrigerant R410ACharged amount (*3)

Cooling OnlyHeat Pump

High-pressure switchProtective devices

Refrigerantpipe spec.(*4)

Connectingport dia.

Connectingmethod

Gas side

Liquid sideBalance sideGas sideLiquid sideBalance side

Max. equivalent length

Max. real lengthMax. total pipe length(Real length)

Max. height difference

Control wiring

Central remote controller

Max. No. of connected indoor unitsSound pressure level

MMY-MMY-

(kW)(kW)

(A)

(kW)(%)

(kW/kW)

(A)(A)

(kW)(%)

EER(Energy Efficiency Ratio)

(A)

(kg)(kg)

(kW)

(kW)(m3/h)

(kg)(kg)

(MPa)

(mm)(mm)(mm)

(m)

(m)

(m)

(m)

(dB(A))

(mm)

(kW/kW)

Equivalent to 42HPAP4201T8 AP4401T8

AP4201HT8 AP4401HT8Inverter

MAP1201T8MAP1201HT8

118.0

3 phase 50Hz 400V (380 - 415V)55.24

36.7496

3.21

1.05.39

35.1495

3.76

1.0Height 1,800 x Width 990 x Depth 750

256

Silky shade (Munsell 1Y8.5/0.5)Hermetic type

4.2 x 2

Propeller fan0.6

10,500Finned tube

11.0

OFF : 2.90 ON : 3.73(*5)

O/ 28.6O/ 12.7O/ 9.5

BrazingFlareFlare175

150 (If the total bend length exceeds 150m, use the max equivalent length as the standard.)

300

Outdoor unit is higher than indoor unit : 50Outdoor unit is lower than indoor unit : 40 (*6)Shield wire 1.25mm2 x 2 cores. up to 2000m

When connecting to outdoor unit : (Shield wire) 1.25mm2 x 2 cores. up to 1000m, and (Shield wire) 2.0mm2 x 2 cores. up to 2000m

48

Equivalent to 44HP

MAP1001T8MAP1001HT8

MAP1001T8MAP1001HT8

MAP1001T8MAP1001HT8

MAP1201T8MAP1201HT8

MAP1201T8MAP1201HT8

MAP1001T8MAP1001HT8

MAP1001T8MAP1001HT8

123.5132.0 138.5

258256258

256258

256258

256258

256258

256258

256258

3.1 x 2 4.2 x 2 3.1 x 2

12.511.012.5

11.012.5

11.012.5

11.012.5

11.012.5

11.012.5

11.012.5

O/ 22.2 O/ 28.6 O/ 22.2

64.5

62.28

40.9995

3.01

1.056.7637.36

3.69

1.0

*1 : Rated conditions Cooling : Indoor air temperature 27OC DB/19OC WB, Outdoor air temperature 35OC DBHeating : Indoor air temperature 20OC DB, Outdoor air temperature 7OC DB/6OC WB

The standard piping means that main pipe length is 5 m, branching pipe length 2.5 m of branch piping connected with a 0 meter height.

*2 : The source voltage must not fluctuate more than +-10%.

*3 : The amount does not consider extra piping lengths. Refrigerant must be added on site in accordance with the actual piping length.

*4 : The maximum total piping length indicates the sum of one-way piping lengths on the liquid side or gas side.System safety protection*5 : Discharge temp. sensor, Suction temp. sensor, Compressor case thermostat, High-pressure Switch, Over-current sensor,

High-pressure Sensor, Low pressure sensor, Over-current relay.

*6 : 30m when the height difference between indoor units exceeds 3m.

Page 226: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

221

16

50Hz

Equivalent HP

Set Model nameCooling OnlyHeat Pump

Outdoor unit type

Cooling

Heating

Electricalcharacteristics(*1)

Running current

External dimension

Total weight

MMY-MMY-

Outdoor unit modelCooling OnlyHeat Pump

Rated cooling capacity (*1)

EER(Energy Efficiency Ratio)

Standard heating capacity (*1)Power supply (*2)

Power consumptionPower factor

Starting currentRunning currentPower consumptionPower factor

Starting current

Cooling OnlyHeat Pump

Colour

CompressorTypeMotor outputFanMotor outputAir volume

Fan unit

Heat exchanger

Refrigerant R410ACharged amount (*3)

Cooling OnlyHeat Pump

High-pressure switchProtective devices

Refrigerantpipe spec.(*4)

Connectingport dia.

Connectingmethod

Gas sideLiquid sideBalance sideGas sideLiquid sideBalance side

Max. equivalent length

Max. real length

Max. total pipe length(Real length)

Max. height difference

Control wiring

Central remote controller

Max. No. of connected indoor units

Sound pressure level

MMY-MMY-

(kW)(kW)

(A)(kW)(%)

(kW/kW)

(A)(A)

(kW)(%)

EER(Energy Efficiency Ratio)

(A)

(kg)(kg)

(kW)

(kW)(m3/h)

(kg)(kg)

(MPa)

(mm)

(mm)(mm)

(m)

(m)

(m)

(m)

(dB(A))

(mm)

(kW/kW)

Equivalent to 46HPAP4601T8 AP4801T8

AP4601HT8 AP4801HT8Inverter

MAP1201T8MAP1201HT8

130.0

3 phase 50Hz 400V (380 - 415V)69.27

3.64

Height 1,800 x Width 990 x Depth 750256

Silky shade (Munsell 1Y8.5/0.5)

Hermetic type4.2 x 2

Propeller fan0.6

10,500Finned tube

11.0

OFF : 2.90 ON : 3.73(*5)

O/ 28.6O/ 12.7O/ 9.5

Brazing

FlareFlare

160

135 (If the total bend length exceeds 135m, use the max equivalent length as the standard.)

300

Outdoor unit is higher than indoor unit : 50Outdoor unit is lower than indoor unit : 40 (*6)Shield wire 1.25mm2 x 2 cores. up to 2000m

When connecting to outdoor unit : (Shield wire) 1.25mm2 x 2 cores. up to 1000m, and (Shield wire) 2.0mm2 x 2 cores. up to 2000m

4865

Equivalent to 48HP

MAP1201T8MAP1201HT8

MAP1201T8MAP1201HT8

MAP1001T8MAP1001HT8

MAP1201T8MAP1201HT8

MAP1201T8MAP1201HT8

MAP1201T8MAP1201HT8

MAP1201T8MAP1201HT8

145.0135.0150.0

75.4745.59 49.67

95

2.85 2.72

1.0 1.060.55 64.1939.85 41.80

1.0 1.0

258256258

256258

256258

256258

256258

256258

256258

3.1 x 2 4.2 x 2

12.511.012.5

11.012.5

11.012.5

11.012.5

11.012.5

11.012.5

11.012.5

3.59

95 94

O/ 22.2 O/ 28.6

*1 : Rated conditions Cooling : Indoor air temperature 27OC DB/19OC WB, Outdoor air temperature 35OC DBHeating : Indoor air temperature 20OC DB, Outdoor air temperature 7OC DB/6OC WB

The standard piping means that main pipe length is 5 m, branching pipe length 2.5 m of branch piping connected with a 0 meter height.

*2 : The source voltage must not fluctuate more than +-10%.

*3 : The amount does not consider extra piping lengths. Refrigerant must be added on site in accordance with the actual piping length.

*4 : The maximum total piping length indicates the sum of one-way piping lengths on the liquid side or gas side.System safety protection*5 : Discharge temp. sensor, Suction temp. sensor, Compressor case thermostat, High-pressure Switch, Over-current sensor,

High-pressure Sensor, Low pressure sensor, Over-current relay.

*6 : 30m when the height difference between indoor units exceeds 3m.

Page 227: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

222

16

60Hz

Outdoor unit (60Hz)

Equivalent HP

Model name Heat Pump

Outdoor unit type

Cooling capacity (*1)

Standard heating capacity (*1)

Power supply (* 2)

Cooling

Heating

Electricalcharacteris-tics(*1)

Running current

Power consumption

Power factor

EER (Energy Efficiency Ratio)

Starting current

Running current

Power consumption

Power factor

EER (Energy Efficiency Ratio)

Starting current

External dimension

Total weight

Colour

Type

Motor output

Fan

Motor output

Air volume

Compressor

Fan unit

Heat exchanger

Refrigerant R410A(Charged refrigerant amount) (* 3)

High-pressure switch

Protective devices

Gas side

Liquid side

Balance pipe

Gas side

Liquid side

Balance pipe

Connectingport dia

Connectingmethod

Refrigerantpipingspecifica-tions(*4)

Max. equivalent length

Max. real length

Max. total pipe length (Real length)

Max. height difference

Control wiring

Central remote controller

Max. No. of connected indoor units

Sound pressure level

MMY-

(kW)

(kW)

(A)

(kW)

(%)

(kW/kW)

(A)

(A)

(kW)

(%)

(kW/kW)

(mm)

(kg)

(A)

(kW)

(kW)

(m3/h)

(kg)

(MPa)

(mm)

(mm)

(mm)

(m)

(m)

(m)

(m)

(dB(A))

Equivalent to5HP

MAP0501HT7

Inverter unit

14.0

16.0

3 phase 60Hz 380V

6.16

3.65

6.41

3.84

91

Height 1,800 x Width 990 x Depth 750

228

1.1 x 2

Hermetic type

Propeller fan

0.60

Finned tube

R410A (8.5)

OFF : 2.90 ON : 3.73

(*5)

O/ 15.9

O/ 9.5

O/ 9.5

Flare

Flare

Flare

175

150 (If the total bend length exceeds 150m, use the max equivalent length as the standard.)

300

Outdoor unit is higher than indoor unit : 50

Outdoor unit is lower than indoor unit : 40 (*6)

Shield wire 1.25mm2 x 2 cores. up to 2000m

When connecting to outdoor unit : (Shield wire) 1.25mm2 x 2 cores. up to 1000m, and (Shield wire) 2.0mm2 x 2 cores. up to 2000m

8

55

10

56

13

57

16

58

20

59

Equivalent to6HP

Equivalent to8HP

Equivalent to10HP

Equivalent to12HP

16.0

18.0

22.4

25.0

28.0

31.5

33.5

37.5

90

3.84

1.0

4.17

1.0

7.66

4.64

7.45

4.56

93

92

3.45

1.0

3.95

1.0

9.07

5.67

9.40

5.88

95

95

3.95

1.0

4.25

1.0

12.16

7.68

12.61

7.97

96

96

3.65

1.0

3.95

1.0

19.27

11.92

16.47

10.19

94

94

2.81

1.0

3.68

1.0

1.4 x 2 2.3 x 2 3.1 x 2 4.2 x 2

9,000 9,900 10,500

O/ 19.1 O/ 22.2 O/ 28.6

O/ 12.7

Brazing

MAP0601HT7 MAP0801HT7 MAP1001HT7 MAP1201HT7

258

Silky shade (Munsell 1Y8.5/0.5)

R410A (12.5)

*1 : Rated conditions Cooling : Indoor air temperature 27OC DB/19OC WB, Outdoor air temperature 35OC DBHeating : Indoor air temperature 20OC DB, Outdoor air temperature 7OC DB/6OC WB

The standard piping means that main pipe length is 5 m, branching pipe length 2.5 m of branch piping connected with a 0 meter height.

*2 : The source voltage must not fluctuate more than +-10%.

*3 : The amount does not consider extra piping lengths. Refrigerant must be added on site in accordance with the actual piping length.

*4 : The maximum total piping length indicates the sum of one-way piping lengths on the liquid side or gas side.System safety protection*5 : Discharge temp. sensor, Suction temp. sensor, Compressor case thermostat, High-pressure Switch, Over-current sensor,

High-pressure Sensor, Low pressure sensor, Over-current relay.

*6 : 30m when the height difference between indoor units exceeds 3m.

Page 228: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

223

Running current

16

60Hz

Outdoor unit (Combination) (60Hz)

Equivalent HP

Set Model name

Outdoor unit type

Heat Pump

Heat Pump

Electricalcharacteristics(*1)

Cooling

Heating

Power consumptionPower factor

EER(Energy Efficiency Ratio)

Starting currentRunning current

Power consumption

Power factor

Starting current

EER(Energy Efficiency Ratio)

External dimension

Total weightColour

CompressorTypeMotor output

Fan

Motor outputAir volume

Fan unit

Heat exchanger

Refrigerant R410A Charged amount (*3)

High-pressure switch

Protective devices

Connectingport dia.

Connectingmethod

Gas side

Liquid side

Balance side

Gas side

Max. equivalent length

Max. real length

Max. height difference

Max. total pipe length(Real length)

Control wiring

Central remote controller

Max. No. of connected indoor units

(kW)

MMY-

MMY-

(A)

(kW)

(%)

(kW/kW)

(A)(A)

(kW)

(%)(kW/kW)

(A)

(mm)

(kg)

(kW)

(kW)(m3/h)

(kg)

(MPa)

(mm)

(mm)

(mm)

Refrigerantpipe spec.(*4)

Liquid sideBalance side

(m)

(m)

(m)

Sound pressure level (dB(A))

Equivalent to 14HP

AP1401HT7

(m)

Equivalent to 16HP

AP1601HT7

Equivalent to 18HP

AP1801HT7

Equivalent to 20HP

AP2001HT7Inverter

MAP0801HT7 MAP0601HT7 MAP0801HT7 MAP0801HT7 MAP1001HT7 MAP0801HT7 MAP1001HT7 MAP1001HT738.4 45 50.4 56.0

43.0 50.0 56.5 63.0

17.97 19.51 22.41 25.5911.12 12.20 14.16 16.17

94 95 96 96

3.45 3.69 3.56 3.46

1.0 1.0 1.0 1.0

17.72 19.64 22.74 26.05

10.96 12.28 14.37 16.46

94 95 96 96

3.92 4.07 3.93 3.83

1.0 1.0 1.0 1.0

3 phase 60Hz 380V

Height 1,800 x Width 990 x Depth 750

258 228 258 258 258 258 258 258

2.3 x 2 1.4 x 2 2.3 x 2 3.1 x 2 2.3 x 2 3.1 x 2

9,900 9,000 9,900 10,500 9,900 10,5000

12.5 8.5 12.5

O/ 22.2 O/ 19.1 O/ 22.2

O/ 12.7 O/ 9.5 O/ 12.7

Silky shade (Munsell 1Y8.5/0.5)

Hermetic type

Propeller fan

0.6

Finned tube

OFF : 2.90 ON : 3.73

(*5)

O/ 9.5Brazing

FlareFlare

175

150 (If the total bend length exceeds 150m, use the max equivalent length as the standard.)

300

Outdoor unit is higher than indoor unit : 50

Outdoor unit is lower than indoor unit : 40 (*6)

When connecting to outdoor unit : (Shield wire) 1.25mm2 x 2 cores. up to 1000m, and (Shield wire) 2.0mm2 x 2 cores. up to 2000m

23

59.5

27

60

30

60.5

33

61

Shield wire 1.25mm2 x 2 cores. up to 2000m

Outdoor unit type

Rated cooling capacity (*1)

Standard heating capacity (*1)

Power supply (*2)

(kW)

*1 : Rated conditions Cooling : Indoor air temperature 27OC DB/19OC WB, Outdoor air temperature 35OC DBHeating : Indoor air temperature 20OC DB, Outdoor air temperature 7OC DB/6OC WB

The standard piping means that main pipe length is 5 m, branching pipe length 2.5 m of branch piping connected with a 0 meter height.

*2 : The source voltage must not fluctuate more than +-10%.

*3 : The amount does not consider extra piping lengths. Refrigerant must be added on site in accordance with the actual piping length.

*4 : The maximum total piping length indicates the sum of one-way piping lengths on the liquid side or gas side.System safety protection*5 : Discharge temp. sensor, Suction temp. sensor, Compressor case thermostat, High-pressure Switch, Over-current sensor,

High-pressure Sensor, Low pressure sensor, Over-current relay.

*6 : 30m when the height difference between indoor units exceeds 3m.

Page 229: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

224

16

60Hz

Equivalent HP

Set Model name

Outdoor unit type

Heat Pump

Heat Pump

Rated cooling capacity (*1)Standard heating capacity (*1)

Power supply (*2)

Electricalcharacteristics(*1)

Cooling

Heating

Running currentPower consumption

Power factor

EER(Energy Efficiency Ratio)

Starting current

Running current

Power consumption

Power factor

Starting current

EER(Energy Efficiency Ratio)

External dimension

Total weightColour

CompressorType

Motor outputFan

Motor outputAir volume

Fan unit

Heat exchanger

Refrigerant R410A Charged amount (* 3)

High-pressure switch

Protective devices

Connectingport dia.

Connectingmethod

Gas side

Liquid sideBalance side

Gas side

Max. equivalent length

Max. real length

Max. height difference

Max. total pipe length(Real length)

Control wiring

Central remote controller

Max. No. of connected indoor units

(kW)

MMY-

MMY-

(kW)

(A)

(kW)

(%)(kW/kW)

(A)

(A)

(kW)(%)

(kW/kW)

(A)(mm)

(kg)

(kW)

(kW)(m3/h)

(kg)

(MPa)

(mm)

(mm)(mm)

Refrigerantpipe spec.(*4)

Outdoor unit model

Liquid side

Balance side

(m)

(m)

(m)

Sound pressure level (dB(A))

Equivalent to 22HP

AP2201HT7

(m)

Inverter

MAP0801HT7

61.5

27.81

3 phase 60Hz 380V

Height 1,800 x Width 990 x Depth 750

258

2.3 x 2

Silky shade (Munsell 1Y8.5/0.5)

Hermetic type

Propeller fan

0.6

Finned tube

OFF : 2.90 ON : 3.73(*5)

O/ 9.5

BrazingFlare

Flare

175

150 (If the total bend length exceeds 150m, use the max equivalent length as the standard.)

300

Outdoor unit is higher than indoor unit : 50

Outdoor unit is lower than indoor unit : 40 (*6)

When connecting to outdoor unit : (Shield wire) 1.25mm2 x 2 cores. up to 1000m, and (Shield wire) 2.0mm2 x 2 cores. up to 2000m

37

Shield wire 1.25mm2 x 2 cores. up to 2000m

AP2211HT7

MAP0801HT7 MAP0601HT7 MAP1201HT7 MAP1001HT7

69.0

17.3995

3.54

1.0

27.75

17.35

95

3.98

1.0

32.64

20.41

3.01

1.0

29.88

18.68

3.69

1.0

258 228 258 258

1.4 x 2 4.2 x 2 3.1 x 2

9,900 9,000 10,500

12.5 8.5 12.5

O/ 22.2 O/ 19.1 O/ 28.6 O/ 22.2

O/ 12.7 O/ 9.5 O/ 12.7

61.5

*1 : Rated conditions Cooling : Indoor air temperature 27OC DB/19OC WB, Outdoor air temperature 35OC DBHeating : Indoor air temperature 20OC DB, Outdoor air temperature 7OC DB/6OC WB

The standard piping means that main pipe length is 5 m, branching pipe length 2.5 m of branch piping connected with a 0 meter height.

*2 : The source voltage must not fluctuate more than +-10%.

*3 : The amount does not consider extra piping lengths. Refrigerant must be added on site in accordance with the actual piping length.

*4 : The maximum total piping length indicates the sum of one-way piping lengths on the liquid side or gas side.System safety protection*5 : Discharge temp. sensor, Suction temp. sensor, Compressor case thermostat, High-pressure Switch, Over-current sensor,

High-pressure Sensor, Low pressure sensor, Over-current relay.

*6 : 30m when the height difference between indoor units exceeds 3m.

Page 230: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

225

16

60Hz

Equivalent HP

Set Model name

Outdoor unit type

Heat Pump

Heat Pump

Rated cooling capacity (*1)

Standard heating capacity (*1)Power supply (*2)

Electricalcharacteristics(*1)

Cooling

Heating

Running current

Power consumption

Power factor

EER(Energy Efficiency Ratio)Starting current

Running current

Power consumption

Power factor

Starting current

EER(Energy Efficiency Ratio)

External dimension

Total weightColour

CompressorTypeMotor output

Fan

Motor output

Air volume

Fan unit

Heat exchanger

Refrigerant R410A Charged amount (* 3)

High-pressure switch

Protective devices

Connectingport dia.

Connectingmethod

Gas sideLiquid side

Balance side

Gas side

Max. equivalent length

Max. real length

Max. height difference

Max. total pipe length(Real length)

Control wiring

Central remote controller

Max. No. of connected indoor units

(kW)

MMY-

MMY-

(kW)

(A)

(kW)

(%)(kW/kW)

(A)

(A)(kW)

(%)

(kW/kW)

(A)

(mm)

(kg)

(kW)

(kW)(m3/h)

(kg)

(MPa)

(mm)(mm)

(mm)

Refrigerantpipe spec.(*4)

Outdoor unit model

Liquid side

Balance side(m)

(m)

(m)

Sound pressure level (dB(A))

Equivalent to 24HP

AP2401HT7

(m)

Inverter

MAP0801HT768.0

29.193 phase 60Hz 380V

Height 1,800 x Width 990 x Depth 750

258

2.3 x 2

Silky shade (Munsell 1Y8.5/0.5)

Hermetic type

Propeller fan

0.6

Finned tube

OFF : 2.90 ON : 3.73(*5)

O/ 9.5

BrazingFlare

Flare

175

150 (If the total bend length exceeds 150m, use the max equivalent length as the standard.)

300

Outdoor unit is higher than indoor unit : 50

Outdoor unit is lower than indoor unit : 40 (*6)

When connecting to outdoor unit : (Shield wire) 1.25mm2 x 2 cores. up to 1000m, and (Shield wire) 2.0mm2 x 2 cores. up to 2000m

40

Shield wire 1.25mm2 x 2 cores. up to 2000m

AP2411HT7

MAP0801HT7 MAP0801HT7 MAP1201HT7 MAP1201HT7

76.5

18.44

96

3.69

1.0

29.43

18.7997

4.07

1.0

258 258 258 258

4.2 x 2

9,900 10,500

12.5

O/ 22.2 O/ 28.6

O/ 12.7

62

40.02

25.02

95

2.72

1.0

33.74

21.3296

3.59

1.0

*1 : Rated conditions Cooling : Indoor air temperature 27OC DB/19OC WB, Outdoor air temperature 35OC DB Heating : Indoor air temperature 20OC DB, Outdoor air temperature 7OC DB/6OC WB The standard piping means that main pipe length is 5 m, branching pipe length 2.5 m of branch piping connected with a 0 meter height.

*2 : The source voltage must not fluctuate more than +-10%.

*3 : The amount does not consider extra piping lengths. Refrigerant must be added on site in accordance with the actual piping length.

*4 : The maximum total piping length indicates the sum of one-way piping lengths on the liquid side or gas side.System safety protection*5 : Discharge temp. sensor, Suction temp. sensor, Compressor case thermostat, High-pressure Switch, Over-current sensor, High-pressure Sensor, Low pressure sensor, Over-current relay.

*6 : 30m when the height difference between indoor units exceeds 3m.

Page 231: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

226

16

60Hz

Equivalent HP

Set Model name

Outdoor unit type

Heat Pump

Heat Pump

Rated cooling capacity (*1)

Standard heating capacity (*1)Power supply (*2)

Electricalcharacteristics(*1)

Cooling

Heating

Running currentPower consumption

Power factor

EER(Energy Efficiency Ratio)

Starting current

Running currentPower consumption

Power factor

Starting current

EER(Energy Efficiency Ratio)

External dimension

Total weight

Colour

CompressorType

Motor output

FanMotor output

Air volumeFan unit

Heat exchanger

Refrigerant R410A Charged amount (* 3)

High-pressure switchProtective devices

Connectingport dia.

Connectingmethod

Gas sideLiquid side

Balance side

Gas side

Max. equivalent length

Max. real length

Max. height difference

Max. total pipe length(Real length)

Control wiring

Central remote controller

Max. No. of connected indoor units

(kW)

MMY-

MMY-

(kW)

(A)(kW)

(%)

(kW/kW)

(A)

(A)(kW)

(%)

(kW/kW)

(A)

(mm)

(kg)

(kW)

(kW)

(m3/h)

(kg)

(MPa)

(mm)

(mm)

(mm)

Refrigerantpipe spec.(*4)

Outdoor unit model

Liquid side

Balance side

(m)

(m)

(m)

Sound pressure level (dB(A))

Equivalent to 26HP

AP2601HT7

(m)

Inverter

MAP1001HT773

32.11

3 phase 60Hz 380V

Height 1,800 x Width 990 x Depth 750

258

2.3 x 2

Silky shade (Munsell 1Y8.5/0.5)Hermetic type

Propeller fan0.6

Finned tube

OFF : 2.90 ON : 3.73(*5)

O/ 22.2

Brazing

Flare

Flare175

150 (If the total bend length exceeds 150m, use the max equivalent length as the standard.)

300

Outdoor unit is higher than indoor unit : 50

Outdoor unit is lower than indoor unit : 40 (*6)

When connecting to outdoor unit : (Shield wire) 1.25mm2 x 2 cores. up to 1000m, and (Shield wire) 2.0mm2 x 2 cores. up to 2000m

43

Shield wire 1.25mm2 x 2 cores. up to 2000m

81.5

96

3.60

1.0

32.80

3.97

1.0

10,500

12.5

Equivalent to 28HP Equivalent to 30HP

AP2801HT7 AP3001HT7

MAP0801HT7 MAP0801HT7 MAP1001HT7 MAP1001HT7 MAP0801HT7 MAP1001HT7 MAP1001HT7 MAP1001HT778.5 84.0

88.0 95.0

35.25 38.4022.27 24.2620.29

3.52 3.46

1.0 1.0

35.77 38.8820.51 22.60 24.82

95 96 97

3.89 3.83

1.0 1.0

258 258 258 258 258 258 258 258

3.1 x 2 2.3 x 2 3.1 x 2

9,900 10,500 9,900 10,500

O/ 12.7

O/ 9.5

47 4862 62.5 63

*1 : Rated conditions Cooling : Indoor air temperature 27OC DB/19OC WB, Outdoor air temperature 35OC DBHeating : Indoor air temperature 20OC DB, Outdoor air temperature 7OC DB/6OC WB

The standard piping means that main pipe length is 5 m, branching pipe length 2.5 m of branch piping connected with a 0 meter height.

*2 : The source voltage must not fluctuate more than +-10%.

*3 : The amount does not consider extra piping lengths. Refrigerant must be added on site in accordance with the actual piping length.

*4 : The maximum total piping length indicates the sum of one-way piping lengths on the liquid side or gas side.System safety protection*5 : Discharge temp. sensor, Suction temp. sensor, Compressor case thermostat, High-pressure Switch, Over-current sensor,

High-pressure Sensor, Low pressure sensor, Over-current relay.

*6 : 30m when the height difference between indoor units exceeds 3m.

Page 232: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

227

16

60Hz

Equivalent HP

Set Model nameOutdoor unit type

Heat Pump

Heat Pump

Rated cooling capacity (*1)

Standard heating capacity (*1)Power supply (*2)

Electricalcharacteristics(*1)

Cooling

Heating

Running currentPower consumption

Power factor

EER(Energy Efficiency Ratio)

Starting current

Running currentPower consumption

Power factor

Starting current

EER(Energy Efficiency Ratio)

External dimension

Total weight

Colour

CompressorType

Motor output

FanMotor output

Air volume

Fan unit

Heat exchanger

Refrigerant R410A Charged amount (* 3)

High-pressure switch

Protective devices

Connectingport dia.

Connectingmethod

Gas side

Liquid side

Balance side

Gas side

Max. equivalent length

Max. real length

Max. height difference

Max. total pipe length(Real length)

Control wiring

Central remote controller

Max. No. of connected indoor units

(kW)

MMY-

MMY-

(kW)

(A)(kW)

(%)

(kW/kW)

(A)

(A)(kW)

(%)

(kW/kW)

(A)(mm)

(kg)

(kW)

(kW)

(m3/h)

(kg)

(MPa)

(mm)

(mm)

(mm)

Refrigerantpipe spec.(*4)

Outdoor unit model

Liquid side

Balance side

(m)

(m)

(m)

Sound pressure level (dB(A))

Equivalent to 32HP

AP3201HT7

(m)

Inverter

MAP0801HT7

90.0

39.04

3 phase 60Hz 380V

Height 1,800 x Width 990 x Depth 750

258

2.3 x 2

Silky shade (Munsell 1Y8.5/0.5)Hermetic type

Propeller fan

0.6

Finned tube

OFF : 2.90 ON : 3.73

(*5)

O/ 9.5

Brazing

Flare

Flare

175

150 (If the total bend length exceeds 150m, use the max equivalent length as the standard.)

300

Outdoor unit is higher than indoor unit : 50

Outdoor unit is lower than indoor unit : 40 (*6)

When connecting to outdoor unit : MVVS (Shield wire) 1.25mm2 x 2 cores. up to 1000m, andMVVS (Shield wire) 2.0mm2 x 2 cores. up to 2000m

48

Shield wire 1.25mm2 x 2 cores. up to 2000m

100.0

24.41

95

3.69

1.0

39.2824.56

95

4.07

1.0

9,900

12.5

O/ 22.2

O/ 12.7

63

AP3211HT7

MAP0801HT7 MAP0801HT7 MAP0801HT7 MAP1201HT7 MAP1001HT7 MAP1001HT7

45.34

28.65

96

3.14

1.0

42.8326.78

95

3.73

1.0

258 258 258 258 258 258

4.2 x 2 3.1 x 2

10,500

O/ 28.6 O/ 22.2

*1 : Rated conditions Cooling : Indoor air temperature 27OC DB/19OC WB, Outdoor air temperature 35OC DBHeating : Indoor air temperature 20OC DB, Outdoor air temperature 7OC DB/6OC WB

The standard piping means that main pipe length is 5 m, branching pipe length 2.5 m of branch piping connected with a 0 meter height.

*2 : The source voltage must not fluctuate more than +-10%.

*3 : The amount does not consider extra piping lengths. Refrigerant must be added on site in accordance with the actual piping length.

*4 : The maximum total piping length indicates the sum of one-way piping lengths on the liquid side or gas side.System safety protection*5 : Discharge temp. sensor, Suction temp. sensor, Compressor case thermostat, High-pressure Switch, Over-current sensor,

High-pressure Sensor, Low pressure sensor, Over-current relay.

*6 : 30m when the height difference between indoor units exceeds 3m.

Page 233: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

228

16

60Hz

Equivalent HP

Set Model nameOutdoor unit type

Heat Pump

Heat Pump

Rated cooling capacity (*1)

Standard heating capacity (*1)Power supply (* 2)

Electricalcharacteristics(*1)

Cooling

Heating

Running current

Power consumption

Power factor

EER(Energy Efficiency Ratio)

Starting current

Running current

Power consumptionPower factor

Starting current

EER(Energy Efficiency Ratio)

External dimension

Total weight

Colour

CompressorType

Motor output

Fan

Motor outputAir volume

Fan unit

Heat exchangerRefrigerant R410A Charged amount (*3)

High-pressure switch

Protective devices

Connectingport dia.

Connectingmethod

Gas side

Liquid side

Balance sideGas side

Max. equivalent length

Max. real length

Max. height difference

Max. total pipe length(Real length)

Control wiring

Central remote controller

Max. No. of connected indoor units

(kW)

MMY-

MMY-

(kW)

(A)(kW)

(%)

(kW/kW)

(A)(A)

(kW)(%)

(kW/kW)

(A)

(mm)(kg)

(kW)

(kW)(m3/h)

(kg)

(MPa)

(mm)

(mm)

(mm)

Refrigerantpipe spec.(*4)

Outdoor unit model

Liquid side

Balance side

(m)

(m)

(m)

Sound pressure level (dB(A))

Equivalent to 34HP

AP3401HT7

(m)

Inverter

MAP1001HT796.0

41.99

3 phase 60Hz 380V

Height 1,800 x Width 990 x Depth 750

258

3.1 x 2

Silky shade (Munsell 1Y8.5/0.5)

Hermetic type

Propeller fan

0.6

Finned tube

OFF : 2.90 ON : 3.73

(*5)

O/ 9.5

Brazing

Flare

Flare

175

150 (If the total bend length exceeds 150m, use the max equivalent length as the standard.)

300

Outdoor unit is higher than indoor unit : 50

Outdoor unit is lower than indoor unit : 40 (*6)

When connecting to outdoor unit : (Shield wire) 1.25mm2 x 2 cores. up to 1000m, and (Shield wire) 2.0mm2 x 2 cores. up to 2000m

48

Shield wire 1.25mm2 x 2 cores. up to 2000m

108.0

26.53

96

3.62

1.0

42.34

27.03

97

4.00

1.0

10,500

12.5

O/ 22.2

O/ 12.7

63.5

AP3411HT7

MAP0801HT7 MAP0801HT7 MAP0801HT7 MAP1201HT7 MAP1201HT7 MAP1001HT7

52.91

33.0895

2.90

1.0

46.75

29.5496

3.66

1.0

258 258 258 258 258 258

4.2 x 2 3.1 x 2

10,500

O/ 28.6

2.3 x 2

O/ 22.2

63.5

9,900 9,900

*1 : Rated conditions Cooling : Indoor air temperature 27OC DB/19OC WB, Outdoor air temperature 35OC DBHeating : Indoor air temperature 20OC DB, Outdoor air temperature 7OC DB/6OC WB

The standard piping means that main pipe length is 5 m, branching pipe length 2.5 m of branch piping connected with a 0 meter height.

*2 : The source voltage must not fluctuate more than +-10%.

*3 : The amount does not consider extra piping lengths. Refrigerant must be added on site in accordance with the actual piping length.

*4 : The maximum total piping length indicates the sum of one-way piping lengths on the liquid side or gas side.System safety protection*5 : Discharge temp. sensor, Suction temp. sensor, Compressor case thermostat, High-pressure Switch, Over-current sensor,

High-pressure Sensor, Low pressure sensor, Over-current relay.

*6 : 30m when the height difference between indoor units exceeds 3m.

Page 234: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

229

16

60Hz

Equivalent HP

Set Model name

Outdoor unit type

Heat Pump

Heat Pump

Rated cooling capacity (*1)

Standard heating capacity (*1)Power supply (*2)

Electricalcharacteristics(*1)

Cooling

Heating

Running currentPower consumption

Power factor

EER(Energy Efficiency Ratio)

Starting current

Running currentPower consumption

Power factor

Starting current

EER(Energy Efficiency Ratio)

External dimension

Total weight

Colour

CompressorType

Motor output

FanMotor output

Air volume

Fan unit

Heat exchanger

Refrigerant R410A Charged amount (* 3)

High-pressure switchProtective devices

Connectingport dia.

Connectingmethod

Gas side

Liquid side

Balance side

Gas side

Max. equivalent length

Max. real length

Max. height difference

Max. total pipe length(Real length)

Control wiring

Central remote controller

Max. No. of connected indoor units

(kW)

MMY-

MMY-

(kW)

(A)(kW)

(%)

(kW/kW)

(A)

(A)(kW)

(%)

(kW/kW)

(A)(mm)

(kg)

(kW)

(kW)

(m3/h)

(kg)

(MPa)

(mm)

(mm)

(mm)

Refrigerantpipe spec.(*4)

Outdoor unit model

Liquid side

Balance side

(m)

(m)

(m)

Sound pressure level (dB(A))

Equivalent to 36HP

AP3601HT7

(m)

Inverter

MAP1001HT7101.0

44.92

3 phase 60Hz 380V

Height 1,800 x Width 990 x Depth 750

258

3.1 x 2

Silky shade (Munsell 1Y8.5/0.5)

Hermetic type

Propeller fan

0.6

Finned tube

OFF : 2.90 ON : 3.73

(*5)

O/ 9.5

Brazing

Flare

Flare

175

150 (If the total bend length exceeds 150m, use the max equivalent length as the standard.)

300

Outdoor unit is higher than indoor unit : 50

Outdoor unit is lower than indoor unit : 40 (*6)

When connecting to outdoor unit : (Shield wire) 1.25mm2 x 2 cores. up to 1000m, and (Shield wire) 2.0mm2 x 2 cores. up to 2000m

48

Shield wire 1.25mm2 x 2 cores. up to 2000m

113.0

28.38

96

3.56

1.0

45.4928.74

96

3.93

1.0

10,500

12.5

O/ 22.2

O/ 12.7

63.5

AP3611HT7

MAP1001HT7 MAP0801HT7 MAP0801HT7 MAP1201HT7 MAP1201HT7 MAP1201HT7

60.06

37.16

94

2.72

1.0

50.9031.49

94

3.59

1.0

258 258 258 258 258 258

10,500

O/ 28.6

64

9,900

4.2 x 22.3 x 2

*1 : Rated conditions Cooling : Indoor air temperature 27OC DB/19OC WB, Outdoor air temperature 35OC DBHeating : Indoor air temperature 20OC DB, Outdoor air temperature 7OC DB/6OC WB

The standard piping means that main pipe length is 5 m, branching pipe length 2.5 m of branch piping connected with a 0 meter height.

*2 : The source voltage must not fluctuate more than +-10%.

*3 : The amount does not consider extra piping lengths. Refrigerant must be added on site in accordance with the actual piping length.

*4 : The maximum total piping length indicates the sum of one-way piping lengths on the liquid side or gas side.System safety protection*5 : Discharge temp. sensor, Suction temp. sensor, Compressor case thermostat, High-pressure Switch, Over-current sensor,

High-pressure Sensor, Low pressure sensor, Over-current relay.

*6 : 30m when the height difference between indoor units exceeds 3m.

Page 235: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

230

16

60Hz

Equivalent HP

Set Model nameOutdoor unit type

Heat Pump

Heat Pump

Rated cooling capacity (*1)

Standard heating capacity (*1)

Power supply (*2)

Electricalcharacteristics(*1)

Cooling

Heating

Running currentPower consumption

Power factor

EER(Energy Efficiency Ratio)

Starting current

Running currentPower consumption

Power factor

Starting current

EER(Energy Efficiency Ratio)

External dimension

Total weight

Colour

CompressorType

Motor outputFan

Motor output

Air volume

Fan unit

Heat exchanger

Refrigerant R410A Charged amount (*3)

High-pressure switchProtective devices

Connectingport dia.

Connectingmethod

Gas side

Liquid side

Balance sideGas side

Max. equivalent length

Max. real length

Max. height difference

Max. total pipe length(Real length)

Control wiring

Central remote controller

Max. No. of connected indoor units

(kW)

MMY-

MMY-(kW)

(A)(kW)

(%)

(kW/kW)

(A)

(A)(kW)

(%)

(kW/kW)

(A)(mm)

(kg)

(kW)

(kW)

(m3/h)

(kg)

(MPa)

(mm)

(mm)(mm)

Refrigerantpipe spec.(*4)

Outdoor unit model

Liquid side

Balance side

(m)

(m)

(m)

Sound pressure level (dB(A))

Equivalent to 38HP

AP3801HT7

(m)

Inverter

MAP1001HT7106.5

48.05

3 phase 60Hz 380V

Height 1,800 x Width 990 x Depth 750

258

3.1 x 2

Silky shade (Munsell 1Y8.5/0.5)Hermetic type

Propeller fan

0.6

Finned tube

OFF : 2.90 ON : 3.73(*5)

O/ 9.5

Brazing

Flare

Flare

175

150 (If the total bend length exceeds 150m, use the max equivalent length as the standard.)

300

Outdoor unit is higher than indoor unit : 50Outdoor unit is lower than indoor unit : 40 (*6)

When connecting to outdoor unit : (Shield wire) 1.25mm2 x 2 cores. up to 1000m, and (Shield wire) 2.0mm2 x 2 cores. up to 2000m

48

Shield wire 1.25mm2 x 2 cores. up to 2000m

119.5

30.3696

3.51

1.0

48.79

30.8396

3.88

1.0

10,500

12.5

O/ 22.2

O/ 12.7

64

Equivalent to 40HP

AP4001HT7

MAP1001HT7 MAP1001HT7 MAP0801HT7 MAP1001HT7 MAP1001HT7 MAP1001HT7 MAP1001HT7112.0

126.5

51.18

32.34

3.46

1.0

52.31

33.05

3.83

1.0

258 258 258 258 258 258 258

2.3 x 2 3.1 x 2

9,900 10,500

*1 : Rated conditions Cooling : Indoor air temperature 27OC DB/19OC WB, Outdoor air temperature 35OC DBHeating : Indoor air temperature 20OC DB, Outdoor air temperature 7OC DB/6OC WB

The standard piping means that main pipe length is 5 m, branching pipe length 2.5 m of branch piping connected with a 0 meter height.

*2 : The source voltage must not fluctuate more than +-10%.

*3 : The amount does not consider extra piping lengths. Refrigerant must be added on site in accordance with the actual piping length.

*4 : The maximum total piping length indicates the sum of one-way piping lengths on the liquid side or gas side.System safety protection*5 : Discharge temp. sensor, Suction temp. sensor, Compressor case thermostat, High-pressure Switch, Over-current sensor,

High-pressure Sensor, Low pressure sensor, Over-current relay.

*6 : 30m when the height difference between indoor units exceeds 3m.

Page 236: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

231

16

60Hz

Equivalent HPSet Model name

Outdoor unit typeHeat Pump

Heat Pump

Rated cooling capacity (*1)

Standard heating capacity (*1)

Power supply (*2)

Electricalcharacteristics(*1)

Cooling

Heating

Running currentPower consumption

Power factor

EER(Energy Efficiency Ratio)

Starting current

Running current

Power consumption

Power factor

Starting current

EER(Energy Efficiency Ratio)

External dimension

Total weightColour

CompressorType

Motor output

Fan

Motor output

Air volume

Fan unit

Heat exchanger

Refrigerant R410A Charged amount (*3)High-pressure switch

Protective devices

Connectingport dia.

Connectingmethod

Gas side

Liquid sideBalance side

Gas side

Max. equivalent length

Max. real length

Max. height difference

Max. total pipe length(Real length)

Control wiring

Central remote controller

Max. No. of connected indoor units

(kW)

MMY-

MMY-(kW)

(A)(kW)

(%)

(kW/kW)

(A)

(A)(kW)(%)

(kW/kW)

(A)

(mm)

(kg)

(kW)

(kW)

(m3/h)

(kg)

(MPa)

(mm)

(mm)(mm)

Refrigerantpipe spec.(*4)

Outdoor unit model

Liquid side

Balance side

(m)

(m)

(m)

Sound pressure level (dB(A))

Equivalent to 42HP

AP4201HT7

(m)

Inverter

MAP1201HT7

118.0

58.15

3 phase 60Hz 380V

Height 1,800 x Width 990 x Depth 750

258

4.2 x 2

Silky shade (Munsell 1Y8.5/0.5)

Hermetic type

Propeller fan

0.6

Finned tube

OFF : 2.90 ON : 3.73

(*5)

O/ 9.5

BrazingFlare

Flare

175

150 (If the total bend length exceeds 150m, use the max equivalent length as the standard.)

300

Outdoor unit is higher than indoor unit : 50Outdoor unit is lower than indoor unit : 40 (*6)

When connecting to outdoor unit : (Shield wire) 1.25mm2 x 2 cores. up to 1000m, and (Shield wire) 2.0mm2 x 2 cores. up to 2000m

48

Shield wire 1.25mm2 x 2 cores. up to 2000m

132.0

36.74

96

3.21

1.0

56.2035.14

95

3.76

1.0

10,500

12.5

O/ 28.6

O/ 12.7

64.5

Equivalent to 44HP

AP4401HT7

MAP1001HT7 MAP1001HT7 MAP1001HT7 MAP1201HT7 MAP1201HT7 MAP1001HT7 MAP1001HT7

258 258 258 258 258 258 258

3.1 x 2 4.2 x 2 3.1 x 2

O/ 22.2 O/ 28.6 O/ 22.2

123.5

138.0

60.56

40.99

95

3.01

1.0

59.75

37.36

3.69

1.0

*1 : Rated conditions Cooling : Indoor air temperature 27OC DB/19OC WB, Outdoor air temperature 35OC DBHeating : Indoor air temperature 20OC DB, Outdoor air temperature 7OC DB/6OC WB

The standard piping means that main pipe length is 5 m, branching pipe length 2.5 m of branch piping connected with a 0 meter height.

*2 : The source voltage must not fluctuate more than +-10%.

*3 : The amount does not consider extra piping lengths. Refrigerant must be added on site in accordance with the actual piping length.

*4 : The maximum total piping length indicates the sum of one-way piping lengths on the liquid side or gas side.System safety protection*5 : Discharge temp. sensor, Suction temp. sensor, Compressor case thermostat, High-pressure Switch, Over-current sensor,

High-pressure Sensor, Low pressure sensor, Over-current relay.

*6 : 30m when the height difference between indoor units exceeds 3m.

Page 237: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

232

16

60Hz

Equivalent HP

Set Model name

Outdoor unit type

Heat Pump

Heat Pump

Rated cooling capacity (*1)

Standard heating capacity (*1)Power supply (*2)

Electricalcharacteristics(*1)

Cooling

Heating

Running currentPower consumption

Power factor

EER(Energy Efficiency Ratio)

Starting current

Running current

Power consumptionPower factor

Starting current

EER(Energy Efficiency Ratio)

External dimension

Total weight

Colour

CompressorType

Motor output

Fan

Motor output

Air volume

Fan unit

Heat exchanger

Refrigerant R410A Charged amount (*3)

High-pressure switchProtective devices

Connectingport dia.

Connectingmethod

Gas side

Liquid sideBalance side

Gas side

Max. equivalent length

Max. real length

Max. height difference

Max. total pipe length(Real length)

Control wiring

Central remote controller

Max. No. of connected indoor units

(kW)

MMY-

MMY-(kW)

(A)(kW)

(%)

(kW/kW)

(A)

(A)

(kW)

(%)(kW/kW)

(A)(mm)

(kg)

(kW)

(kW)

(m3/h)

(kg)

(MPa)

(mm)

(mm)(mm)

Refrigerantpipe spec.(*4)

Outdoor unit model

Liquid sideBalance side

(m)

(m)

(m)

Sound pressure level (dB(A))

Equivalent to 46HP

AP4601HT7

(m)

Inverter

MAP1201HT7130.0

72.92

3 phase 60Hz 380V

Height 1,800 x Width 990 x Depth 750

258

4.2 x 2

Silky shade (Munsell 1Y8.5/0.5)Hermetic type

Propeller fan

0.6

Finned tube

OFF : 2.90 ON : 3.73(*5)

O/ 9.5

Brazing

FlareFlare

160

135 (If the total bend length exceeds 135m, use the max equivalent length as the standard.)

300

Outdoor unit is higher than indoor unit : 50Outdoor unit is lower than indoor unit : 40 (*6)

When connecting to outdoor unit : (Shield wire) 1.25mm2 x 2 cores. up to 1000m, and (Shield wire) 2.0mm2 x 2 cores. up to 2000m

48

Shield wire 1.25mm2 x 2 cores. up to 2000m

145

45.59

95

2.85

1.0

63.7339.85

95

3.64

1.0

10,500

12.5

O/ 28.6

O/ 12.7

65

Equivalent to 48HP

AP4801HT7

MAP1201HT7 MAP1201HT7 MAP1001HT7 MAP1201HT7 MAP1201HT7 MAP1201HT7 MAP1201HT7

258 258 258 258 258 258 258

135.0

150.0

79.44

49.67

2.72

67.56

41.80

3.59

1.0

1.0

94

3.1 x 2 4.2 x 2

O/ 22.2 O/ 28.6

*1 : Rated conditions Cooling : Indoor air temperature 27OC DB/19OC WB, Outdoor air temperature 35OC DBHeating : Indoor air temperature 20OC DB, Outdoor air temperature 7OC DB/6OC WB

The standard piping means that main pipe length is 5 m, branching pipe length 2.5 m of branch piping connected with a 0 meter height.

*2 : The source voltage must not fluctuate more than +-10%.

*3 : The amount does not consider extra piping lengths. Refrigerant must be added on site in accordance with the actual piping length.

*4 : The maximum total piping length indicates the sum of one-way piping lengths on the liquid side or gas side.System safety protection*5 : Discharge temp. sensor, Suction temp. sensor, Compressor case thermostat, High-pressure Switch, Over-current sensor,

High-pressure Sensor, Low pressure sensor, Over-current relay.

*6 : 30m when the height difference between indoor units exceeds 3m.

Page 238: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

High Wall Type( 2 Series )

Engineering Data

Indoor UnitMMK-AP0072HMMK-AP0092HMMK-AP0122H

1. Equipments

2. Technical Specifications

3. Dimensional Drawing

4. Wiring Diagram

5. Refrigerant Cycle Diagram

6. Sensible Capacity Table

7. Fan characteristics

8. Sound Characteristics (NC curve)

9. Wireless Remote controller

Oct. 05’

A-1

Page 239: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

A-2

Page 240: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

1

1. Equipment

1-1. Line upType

High Wall type(2 series)

Appearance Model Name

MMK-AP0072H

MMK-AP0092H

MMK-AP0122H

Capacityrank

007 type

009 type

012 type

Capacitycode

0.8

1.0

1.25

CoolingCapacity (kW)

2.2

2.8

3.6

HeatingCapacity (kW)

2.5

3.2

4.0

Name Modelname

Appearance

1-2. Remote controller (Packed with the indoor unit)

Application Function

Start / StopChanging modeTemperature settingAir flow changing (5 step)ClockTimer function- ON/OFF timer (10 min. step)- Daily timerHigh power modeECO mode (Sleep timer with ECO-logic)One-touch pre-set memoryOne-touch Auto (*1)

Wire

less

rem

ote

cont

rolle

r

WH

-H2U

E

1-3. Wiring Design

Model

MMK-AP0072H

MMK-AP0092H

MMK-AP0122H

Nominal Voltage

(V-Ph-Hz)

230-1-50

230-1-50

230-1-50

Min

198

198

198

Max

264

264

264

kW

0.03

0.03

0.03

FLA

0.20

0.21

0.22

MCA

0.24

0.26

0.27

MOCP

15

15

15

Voltage Fan Motor Power Supply

Legend MCA : Minimum Circuit Amps FLA : Full Load AmpsMOCP : Maximum Overcurrent Protection (Amps) kW : Fan Motor Rated Output (kW)

1-4. AccessoriesAccessory parts name

Wired remote controller

Simple remote controller

Wireless remote controller kit

Central remote controller

Weekly timer

Model

RBC-AMT31E

RBC-AS21E2

TCB-AX21E2

TCB-SC642TLE2

RBC-EXW21E2

Remarks

with separated receiver unit

Max. 64 group / unit

Use with RBC-AMT31E

50Hz

(Note.1) Super MMS can not accept “AUTO” mode, Super HRM can accept “AUTO” mode.

A-3

Page 241: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

2

2. Technical Specifications

High Wall type (2 Series)

Model name MMK-

Cooling / Heating capacity (Note 1) (kW)

Electrical

Characteristics

Appearance

Outerdimension

Total weight (kg)

Heat exchanger

Soundproof/Heat-insulating material

Fan unit

Air filter

Controller (Note 3)

Connectingpipe

Sound level (Note 2) (High / Mid / Low) (dB(A))

Power Supply

Running current (A)

Power consumption (kW)

Starting current (A)

Suction grille and side panel

Discharge grille

Bottom surface

Height x Width x Depth (mm)

Fan

Standard air flow (High/Mid/Low)(m3/h)

Motor

Gas side (mm)

Liquid side (mm)

Drain port (Outer dia.)

AP0072H AP0092H AP0122H

2.2 / 2.5 2.8 / 3.2 3.6 / 4.0

1 phase 50Hz 230V (220-240V)(Power exclusive for indoor is required.)

0.17 0.18 0.19

0.017 0.018 0.019

0.22 0.23 0.24

Moon white

Moon white

Moon white

275 x 790 x 208

11

Finned tube

Non-flammable insulation

Cross-flow fan

480 / 420 /360 510 / 450 / 360 540 / 450 / 360

30

Standard filter attached (Simple filter)

Wireless remote controller(WH-H2UE, Packed with indoor unit)

9.5

6.4

16 (Polyvinyl chloride tube)

35-32-29 36-33-29 37-33-29

Note 1 : The cooling capacities and electrical characteristics are measured under theconditions specified by JIS B 8615 based on the reference piping. The referencepiping consists of 5 m of main piping and 2.5 m of branch piping connected with 0meter height.

Note 2 : The sound level are measured in an anechoic chamber in accordance with JISB8616.Normally, the values measured in the actual operating environment become largerthan the indicated values due to the effects of external sound.

Note 3 : Wireless remote controller is packed with indoor unit.Wired remote controller (RBC-AMT31E,RBC-AS21E2) can be also connected.

Note 4 : Rated conditions Cooling : Indoor air temperature 27 C DB/19 C WB,Outdoor air temperature 35 C DB

Heating : Indoor air temperature 20C DB,Outdoor air temperature 7C DB/6C WB

50Hz

A-4

Page 242: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

3

3. Dimensional Drawing

Model : MMK-AP0072H, AP0092H, AP0122H

Note : All dimensions are in mm.

208

790

6

48

208

60

275

275

790

Air inlet port

Air outlet port

208

48

275

6 Knockout

321

275

790

Tab for insulation plate

Refrigerant pipe connecting port Gas side O9.5

Refrigerant pipe connecting port Liquid side O6.4

Drain pipe

60 54.5

208

6054.5

48

790

48

Knockout60

(Installation space)

100mm or more

170mm or more*300mm or more170mm or more

*(For attached Flow Selector unit when used in heat recovery model)

Wired remote controller RBC-AMT21E RBC-AMT31ESimple wired remote controller RBC-AS21E RBC-AS21E2Wireless remote controller kit RBC-AX22CE RBC-AX22CE2

A-5

Page 243: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

4

4. Wiring Diagram

Model : MMK-AP0072H, AP0092H, AP0122H

A-6

Page 244: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

5

5. Refrigerant Cycle Diagram

Model : MMK-AP0072H, AP0092H, AP0122H

Air heat exchangerat indoor side

Sensor(TC2)

Fan

Fan motor

Sensor(TCJ)

Sensor(TC1)

Strainer

Pulse MotorValve (PMV)

Liquid side Gas side

Capillary tube

Sensor(TA)

Functional part name

Pulse MotorValve(PMV)

Temp. sensor

PMV

1.TA

2.TC1

3.TC2

4.TCJ

Functional outline

(Connector CN082 (6P): Blue)1) Controls super heat in cooling operation2) Controls under cool in heating operation3) Recovers refrigerant oil in cooling operation4) Recovers refrigerant oil in heating operation

(Connector CN104 (2P): Yellow)1) Detects indoor suction temperature

(Connector CN100 (3P): Brown)1) Controls PMV super heat in cooling operation

(Connector CN101 (2P): Black1) Controls PMV under cool in heating operation

(Connector CN102 (2P): Red)1) Controls PMV super heat in cooling operation

A-7

Page 245: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

6

6. Sensible Capacity TableHigh Wall Type ( MMK-AP****2H ) 2 series

unitsize

007

009

012

outdoor

air temp.

CDB

10.0

12.0

14.0

16.0

18.0

20.0

21.0

23.0

25.0

27.0

29.0

31.0

33.0

35.0

37.0

39.0

10.0

12.0

14.0

16.0

18.0

20.0

21.0

23.0

25.0

27.0

29.0

31.0

33.0

35.0

37.0

39.0

10.0

12.0

14.0

16.0

18.0

20.0

21.0

23.0

25.0

27.0

29.0

31.0

33.0

35.0

37.0

39.0

Indoor Air Temp.

14.0CWB 16.0CWB 18.0CWB 19.0CWB 20.0CWB 22.0CWB 24.0CWB

20CDB 23CDB 26CDB 27CDB 28CDB 30CDB 32CDB

TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC

1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.6

1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.6

1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.6

1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.6

1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.6

1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.6

1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.6

1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.6

1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.6

1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.6

1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.6

1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.6

1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.6

1.8 1.5 2.0 1.6 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.7 2.5 1.6

1.7 1.5 1.9 1.6 2.1 1.7 2.1 1.6 2.2 1.6 2.3 1.6 2.4 1.6

1.7 1.4 1.9 1.5 2.0 1.6 2.1 1.6 2.1 1.6 2.3 1.6 2.4 1.5

2.3 1.8 2.5 1.9 2.7 2.0 2.8 2.0 2.9 2.0 3.1 2.0 3.2 1.9

2.3 1.8 2.5 1.9 2.7 2.0 2.8 2.0 2.9 2.0 3.1 2.0 3.2 1.9

2.3 1.8 2.5 1.9 2.7 2.0 2.8 2.0 2.9 2.0 3.1 2.0 3.2 1.9

2.3 1.8 2.5 1.9 2.7 2.0 2.8 2.0 2.9 2.0 3.1 2.0 3.2 1.9

2.3 1.8 2.5 1.9 2.7 2.0 2.8 2.0 2.9 2.0 3.1 2.0 3.2 1.9

2.3 1.8 2.5 1.9 2.7 2.0 2.8 2.0 2.9 2.0 3.1 2.0 3.2 1.9

2.3 1.8 2.5 1.9 2.7 2.0 2.8 2.0 2.9 2.0 3.1 2.0 3.2 1.9

2.3 1.8 2.5 1.9 2.7 2.0 2.8 2.0 2.9 2.0 3.1 2.0 3.2 1.9

2.3 1.8 2.5 1.9 2.7 2.0 2.8 2.0 2.9 2.0 3.1 2.0 3.2 1.9

2.3 1.8 2.5 1.9 2.7 2.0 2.8 2.0 2.9 2.0 3.1 2.0 3.2 1.9

2.3 1.8 2.5 1.9 2.7 2.0 2.8 2.0 2.9 2.0 3.1 2.0 3.2 1.9

2.3 1.8 2.5 1.9 2.7 2.0 2.8 2.0 2.9 2.0 3.1 2.0 3.2 1.9

2.3 1.8 2.5 1.9 2.7 2.0 2.8 2.0 2.9 2.0 3.1 2.0 3.2 1.9

2.3 1.8 2.5 1.9 2.7 2.0 2.8 2.0 2.9 2.0 3.1 2.0 3.2 1.9

2.2 1.7 2.5 1.8 2.6 1.9 2.7 1.9 2.8 1.9 3.0 1.9 3.1 1.9

2.2 1.7 2.4 1.8 2.6 1.9 2.6 1.9 2.7 1.9 2.9 1.9 3.0 1.8

3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.4

3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.4

3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.4

3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.4

3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.4

3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.4

3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.4

3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.4

3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.4

3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.4

3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.4

3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.4

3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.4

3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.4

2.9 2.1 3.2 2.3 3.4 2.4 3.5 2.4 3.6 2.4 3.8 2.4 4.0 2.3

2.8 2.1 3.1 2.2 3.3 2.4 3.4 2.4 3.5 2.4 3.7 2.3 3.9 2.3

TC: Total capacity [kW] SHC: Sensible capacity [kW]

A-8

Page 246: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

7

7. Fan Characteristics

Discharge Air Speed and Air Throw

High Wall Type (2 series)

Model : MMK-AP0072H, AP0092H, AP0122H

Horizontal discharge Initial speed High wind : 4.5m/sMed wind : 3.7m/sLow wind : 3.2m/s

0

1

2

3

4

5

Horizontal throw (m)

Air

spee

d (

m/s

)

HighMidLow

0 1 2 3 4 5 6 7

A-9

Page 247: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

8

8. Sound Characteristics (NC curve)High Wall Type (2 series)

Model : MMK-AP0072H, AP0092H, AP0122H

Microphone

1m

1m

MMK-AP0072H Fan tap H M L

Sound pressure level (dB(A)) 35 32 29

10

20

30

40

50

60

70

80

90

20-75 75-150 150-300 300-600 600-1200 1200-2400 2400-4800 4800-10000

Octave band frequency (Hz)

Oct

ave

band

sou

nd p

ress

ure

leve

l (dB

)

NC-70

NC-60

NC-50

NC-40

NC-30

NC-20Audibility limits of

continuous white level

A-10

Page 248: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

9

MMK-AP0092H Fan tap H M L

Sound pressure level (dB(A)) 36 33 29

MMK-AP0122H Fan tap H M L

Sound pressure level (dB(A)) 35 33 29

10

20

30

40

50

60

70

80

90

20-75 75-150 150-300 300-600 600-1200 1200-2400 2400-4800 4800-10000

Octave band frequency (Hz)

Oct

ave

band

sou

nd p

ress

ure

leve

l (dB

)

NC-70

NC-60

NC-50

NC-40

NC-30

NC-20Audibility limits ofcontinuous white level

10

20

30

40

50

60

70

80

90

20-75 75-150 150-300 300-600 600-1200 1200-2400 2400-4800 4800-10000

Octave band frequency (Hz)

Oct

ave

band

sou

nd p

ress

ure

leve

l (dB

)

NC-70

NC-60

NC-50

NC-40

NC-30

NC-20Audibility limits of

continuous white level

A-11

Page 249: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

10

9. Wireless Remote controller

External View

Function

Start/Stop

Setting

temp.

Fahrenheit display

Air Volume Control

Flap

Swing

Operation select

One-touch Auto

Preset mode

Clock

ON/OFF timer

ECONO mode

Daily timer

Timer cancel

High Power mode

Filter reset

Reset

Sensor button

High wall (1 series)

TCB-AX21E (Sold Separately)

Contents

OK

17~27 °C

18~30 °C

18~30 °C

16~26 °C

OK

3-Speed, Auto

OK

Auto, Heat, Dry,Cool, Fan

-

-

-

OFF timer, ON timer,Repeat timer, 30minutes interval,max. 72 hours,

-

-

OK

-

OK

OK

OK

Button

Start/Stop

-

Swing/Frap

-

-

-

SET

-

-

CL

-

Filter reset

Reset

SENSOR

High Wall (2 series)

WH-H2UE

Contents

OK

17~30 °C

17~30 °C

17~30 °C

17~30 °C

-

5-Speed, Auto

OK

OK

Auto,Cool,Dry,Heat, Fan

One-touch Auto

OK

OK

Clock displaysystem,10 minutes interval,max. 24 hours,

OK

OK

OK

OK

OK

OK

-

Button

START/STOP

-

FAN

FIX

SWING

MODE

AUTO

MEMO /PRESET

CLOCK

ON/OFF/SET

ECO

ON/OFF/SET

Hi-POWER

FILTER

RESET

-

Remarks

No Fahrenheit display function

5-step control

No switch setting forcooling only

One-touch auto ( Auto mode,Setting temperature :22 °C,Air volume : Auto, Flapposition : Auto, Swing : Off)

Memorizing of setting contentsfor preset mode freely.

Available for ON / OFFworking together

Sleep timer with ECO logic

Setting both ON and OFFtimer simultaneously anddaily

-

Automatic controls for quickcooling and heating

-

-

No remote controller sensor

AUTO

COOL

DRY

HEAT

(Note)1. Automatic operation mode can not be accepted by heat pump system. If transmission is sent as auto mode, operation lamp and

timer lamp of the indoor unit will light up with a beep as notification. In this case, change the other operation mode. (Heat recovery system can accept automatic operation by using this wireless remote controller.)2. Group control using the wired remote controller (WH-H2UE) is not available. If it is incorrect action or display disagreement

may occur.3. A wired remote controller is required for the group control. (sold separately.)4. When the wired remote controller is connected to this high wall unit, two remote control with the wireless remote controller

(WH-H2UE) can be used. In this case, last-push priority control is performed.5. When the unit is controlled in a group through a wired control, ECO-Timer and Hi-POWER operation will not function.

TCB-AX21E2(sold Separately)

A-12

Page 250: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

1-way (2 series)Air Discharge Cassette Type

Engineering Data

Oct. 05’

Contents

1. Specifications

2. Dimensions

3. Electrical current characteristics

4. Sensible capacity table

5. Wiring diagrams

6. Air speed characteristics

7. Sound characteristics (NC Curve)

8. Fresh air intake (Design guide)

9. Barycentric position

Indoor UnitMMU-AP0152SHMMU-AP0182SHMMU-AP0242SH

A-13

Page 251: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

A-14

Page 252: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

1

1. Specification1-way (2 series) Air Discharge Cassette Type

Model name MMU-

Cooling/Heating capacity (kW)

Electrical

characteristics

Appearance

Dimension

Total weight

Heat exchanger

Soundproof / Heat-insulating material

Fan

Standard air flow

Motor (W)

Air filter

Controller

Connecting pipe

Sound pressure level

Power supply

Running current (A)

Power consumption (kW)

Starting current (A)

Main unit

Ceiling panel

Panel color

Main unit

Ceiling panel

Height (mm)

Width (mm)

Depth (mm)

Height (mm)

Width (mm)

Depth (mm)

Main unit (kg)

Ceiling panel (kg)

High (m3/h)

(Mid./Low) (m3/h)

Gas pipe (mm)

Liquid pipe (mm)

Drain pipe (Nominal dia.mm)

High/Mid./Low (dB(A))

AP0152SH AP0182SH AP0242SH

4.5/5.0 5.6/6.3 7.1/8.0

1 phase 50Hz 230V (220-240V)

0.34 0.37 0.62

0.042 0.046 0.075

0.51 0.54 0.80

Heat-insulating material attached Zinc hot dipping steel plate

RBC-US21PGE

Moon white (Munsel 2.5GY9.0/0.5)

200

1000

710

20

1230

800

21 22

5.5

Finned tube

Polyethylene foam + Expanded polystyrene

Centrifugal fan (Sirocco fan)

750 780 1140

690/630 720/660 960/810

30

Standard filter attached (Long life filter)

Remote controller

12.7 15.9

6.4 9.5

25 (Polyvinyl chloride tube : External dia.32 Internal dia.25)

37/35/32 38/36/34 45/41/37

50Hz

A-15

Page 253: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

2

1. Specification1-way (2 series) Air Discharge Cassette Type

60Hz

AP0152SH AP0182SH AP0242SH

4.5/5.0 5.6/6.3 7.1/8.0

1 phase 60Hz 220V

0.35 0.39 0.62

0.041 0.045 0.073

0.53 0.54 0.80

Heat-insulating material attached Zinc hot dipping steel plate

RBC-US21PGE

Moon white (Munsel 2.5GY9.0/0.5)

200

1000

710

20

1230

800

21 22

5.5

Finned tube

Polyethylene foam + Expanded polystyrene

Centrifugal fan (Sirocco fan)

750 780 1140

690/630 720/660 960/810

30

Standard filter attached (Long life filter)

Remote controller

12.7 15.9

6.4 9.5

25 (Polyvinyl chloride tube : External dia.32 Internal dia.25)

37/35/32 38/36/34 45/41/37

Model name MMU-

Cooling/Heating capacity (kW)

Electrical

characteristics

Appearance

Dimension

Total weight

Heat exchanger

Soundproof / Heat-insulating material

Fan

Standard air flow

Motor (W)

Air filter

Controller

Connecting pipe

Sound pressure level

Power supply

Running current (A)

Power consumption (kW)

Starting current (A)

Main unit

Ceiling panel

Panel color

Main unit

Ceiling panel

Height (mm)

Width (mm)

Depth (mm)

Height (mm)

Width (mm)

Depth (mm)

Main unit (kg)

Ceiling panel (kg)

High (m3/h)

(Mid./Low) (m3/h)

Gas pipe (mm)

Liquid pipe (mm)

Drain pipe (Nominal dia.mm)

High/Mid./Low (dB(A))

A-16

Page 254: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

3

2. Dimensions1-way (2 series) Air Discharge Cassette Type (MMU-AP***SH)

Cable inlet (Knockout hole)

Drain pipe connecting port(Be sure to connect the attached flexible hose.)

248

20 94

154

5620

20

7673

.4

135

220

233

122

200

20

2.7

120

93

475

Han

ging

bol

t pitc

h

760

Cei

ling

open

ing

size

710

Uni

t ext

erna

l siz

e

800

Pan

el e

xter

nal s

ize

1060 Hanging bolt pitch

Refrigerant pipe connecting port Gas side B

Refrigerant pipe connecting port Liquid side A

Hanging bolt M10 or W3/8 (Local supply)

1190 Ceiling opening size

1230 Panel external size

1000 Unit external size

Lower surface of ceiling Ceiling panel (Sold separately) For front air discharge unit (Sold separately) knockout hole

100 43

6080

216

72

Cable inlet

252

C/L

C/L

20

706

4

12016

112Fresh air inlet (Ø92 knockout hole)

Ø112 (4-tapping screw under-hole)

Model name MMU-

AP015, AP018 type

AP024 type

A B

Ø6.4 Ø12.7

Ø9.5 Ø15.9Wired remote controller RBC-AMT21E RBC-AMT31ESimple wired remote controller RBC-AS21E RBC-AS21E2Wireless remote controller kit TCB-AX21E TCB-AX21E2Weekly timer application RBC-AMT31E and RBC-EXW21E2

A-17

Page 255: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

4

3. Electrical current characteristics1-way (2 series) Air Discharge Cassette Type

Model

MMU-AP0152SH

MMU-AP0182SH

MMU-AP0242SH

MMU-AP0152SH

MMU-AP0182SH

MMU-AP0242SH

MMU-AP0152SH

MMU-AP0182SH

MMU-AP0242SH

Nominal Voltage

(V-Ph-Hz)

230-1-50

230-1-50

230-1-50

220-1-60

220-1-60

220-1-60

230-1-50

230-1-50

230-1-50

Type

S-MMS (50Hz)

S-MMS (60Hz)

S-HRM

Voltage Range

Min Max

198 264

198 264

198 264

198 264

198 264

198 264

198 264

198 264

198 264

Fan Motor

kW FLA

0.030 0.40

0.030 0.42

0.030 0.71

0.030 0.40

0.030 0.45

0.030 0.75

0.030 0.40

0.030 0.42

0.030 0.71

Power Supply

MCA MOCP

0.49 15

0.53 15

0.88 15

0.50 15

0.57 15

0.94 15

0.49 15

0.53 15

0.88 15

A-18

Page 256: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

5

4. Sensible capacity table1-way (2 series) Air Discharge Cassette Type (MMU-AP***SH)

TC : Total capacity [kW] SHC : Sensible capacity [kW]

Indoor air temp.14.0CWB 16.0CWB 18.0CWB 19.0CWB 20.0CWB 22.0CWB 24.0CWB20CDB 23CDB 26CDB 27CDB 28CDB 30CDB 32CDB

TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC

3.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.13.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.13.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.13.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.13.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.13.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.13.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.13.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.13.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.13.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.13.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.13.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.13.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.13.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.13.6 2.7 4.0 2.9 4.2 3.1 4.4 3.1 4.5 3.1 4.7 3.1 5.0 3.03.5 2.7 3.8 2.8 4.1 3.0 4.2 3.0 4.4 3.0 4.6 3.0 4.8 2.9

4.6 3.5 5.1 3.7 5.4 3.9 5.6 3.9 5.8 3.9 6.1 3.9 6.4 3.84.6 3.5 5.1 3.7 5.4 3.9 5.6 3.9 5.8 3.9 6.1 3.9 6.4 3.84.6 3.5 5.1 3.7 5.4 3.9 5.6 3.9 5.8 3.9 6.1 3.9 6.4 3.84.6 3.5 5.1 3.7 5.4 3.9 5.6 3.9 5.8 3.9 6.1 3.9 6.4 3.84.6 3.5 5.1 3.7 5.4 3.9 5.6 3.9 5.8 3.9 6.1 3.9 6.4 3.84.6 3.5 5.1 3.7 5.4 3.9 5.6 3.9 5.8 3.9 6.1 3.9 6.4 3.84.6 3.5 5.1 3.7 5.4 3.9 5.6 3.9 5.8 3.9 6.1 3.9 6.4 3.84.6 3.5 5.1 3.7 5.4 3.9 5.6 3.9 5.8 3.9 6.1 3.9 6.4 3.84.6 3.5 5.1 3.7 5.4 3.9 5.6 3.9 5.8 3.9 6.1 3.9 6.4 3.84.6 3.5 5.1 3.7 5.4 3.9 5.6 3.9 5.8 3.9 6.1 3.9 6.4 3.84.6 3.5 5.1 3.7 5.4 3.9 5.6 3.9 5.8 3.9 6.1 3.9 6.4 3.84.6 3.5 5.1 3.7 5.4 3.9 5.6 3.9 5.8 3.9 6.1 3.9 6.4 3.84.6 3.5 5.1 3.7 5.4 3.9 5.6 3.9 5.8 3.9 6.1 3.9 6.4 3.84.6 3.5 5.1 3.7 5.4 3.9 5.6 3.9 5.8 3.9 6.1 3.9 6.4 3.84.5 3.3 4.9 3.6 5.3 3.8 5.4 3.8 5.6 3.8 5.9 3.7 6.2 3.74.3 3.3 4.8 3.5 5.1 3.7 5.3 3.7 5.4 3.7 5.7 3.6 6.0 3.6

5.8 4.4 6.4 4.7 6.9 5.0 7.1 5.0 7.3 5.0 7.7 5.0 8.1 4.85.8 4.4 6.4 4.7 6.9 5.0 7.1 5.0 7.3 5.0 7.7 5.0 8.1 4.85.8 4.4 6.4 4.7 6.9 5.0 7.1 5.0 7.3 5.0 7.7 5.0 8.1 4.85.8 4.4 6.4 4.7 6.9 5.0 7.1 5.0 7.3 5.0 7.7 5.0 8.1 4.85.8 4.4 6.4 4.7 6.9 5.0 7.1 5.0 7.3 5.0 7.7 5.0 8.1 4.85.8 4.4 6.4 4.7 6.9 5.0 7.1 5.0 7.3 5.0 7.7 5.0 8.1 4.85.8 4.4 6.4 4.7 6.9 5.0 7.1 5.0 7.3 5.0 7.7 5.0 8.1 4.85.8 4.4 6.4 4.7 6.9 5.0 7.1 5.0 7.3 5.0 7.7 5.0 8.1 4.85.8 4.4 6.4 4.7 6.9 5.0 7.1 5.0 7.3 5.0 7.7 5.0 8.1 4.85.8 4.4 6.4 4.7 6.9 5.0 7.1 5.0 7.3 5.0 7.7 5.0 8.1 4.85.8 4.4 6.4 4.7 6.9 5.0 7.1 5.0 7.3 5.0 7.7 5.0 8.1 4.85.8 4.4 6.4 4.7 6.9 5.0 7.1 5.0 7.3 5.0 7.7 5.0 8.1 4.85.8 4.4 6.4 4.7 6.9 5.0 7.1 5.0 7.3 5.0 7.7 5.0 8.1 4.85.8 4.4 6.4 4.7 6.9 5.0 7.1 5.0 7.3 5.0 7.7 5.0 8.1 4.85.6 4.3 6.2 4.6 6.7 4.9 6.9 4.8 7.1 4.8 7.5 4.8 7.8 4.75.5 4.2 6.1 4.4 6.5 4.7 6.7 4.7 6.9 4.7 7.3 4.7 7.6 4.6

Unitsize

015

018

024

Outdoorair temp.

CDB

10.012.014.016.018.020.021.023.025.027.029.031.033.035.037.039.0

10.012.014.016.018.020.021.023.025.027.029.031.033.035.037.039.0

10.012.014.016.018.020.021.023.025.027.029.031.033.035.037.039.0

A-19

Page 257: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

6

5. Wiring diagrams1-way (2 series) Air Discharge Cassette Type (MMU-AP***SH)

on s

ide

A-20

Page 258: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

7

Heating mode

MMU-AP0152SH, AP0182SH

MMU-AP0242SH

6. Air speed characteristics1-way (2 series) Air Discharge Cassette Type

1.0

0.50.5

0.3 0.3

Main unit3.5m

3m

2m

1m

1m 2m 3m 4m

Main unit

1.0

0.50.5

0.3

0.3

3.5m

3m

2m

1m

1m 2m 3m 4m

A-21

Page 259: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

8

7. Sound Characteristics (NC Curve)1-way (2 series) Air Discharge Cassette Type

MMU-AP0152SH MMU-AP0242SH

MMU-AP0182SH

10

20

30

40

50

60

70

80

90

63 125 250 500 1000 2000 4000 8000

Octave band center frequency (Hz)

Oct

ave

band

sou

nd p

ress

ure

leve

l (dB

)

L

H M

NC-60

NC-50

NC-40

NC-20

NC-70

NC-30

Approximate threshold ofhearing for continuous noise

10

20

30

40

50

60

70

80

90

63 125 250 500 1000 2000 4000 8000

Octave band center frequency (Hz)

Oct

ave

band

sou

nd p

ress

ure

leve

l (dB

)

M

L

H

NC-60

NC-50

NC-40

NC-20

NC-70

NC-30

Approximate threshold ofhearing for continuous noise

10

20

30

40

50

60

70

80

90

63 125 250 500 1000 2000 4000 8000

Octave band center frequency (Hz)

Oct

ave

band

sou

nd p

ress

ure

leve

l (dB

)

L

H M

NC-60

NC-50

NC-40

NC-20

NC-70

NC-30

Approximate threshold ofhearing for continuous noise

Center1.5m

Microphone

Fan tapSound pressure

level (dB(A))

H M L

37 35 32

Fan tapSound pressure

level (dB(A))

H M L

45 41 37

Fan tapSound pressure

level (dB(A))

H M L

38 36 34

A-22

Page 260: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

9

8. Fresh air intake (Design guide)1-way (2 series) Air Discharge Cassette Type

CautionThe fresh air shall be conditioned by a heat reclaim ventilator or similar.Ensure the fresh air volume is determined so that mixed suction air and fresh air can maintain theoperating temperature.*1.Recommended conditioned air temperature is 12 °C to 30 °C.

However, Make a fresh air volume within 20% of standard.

Install a filter within the fresh air duct.(Fresh air does not pass through the filter of Indoor unit.)

Insulate the fresh air duct.Electrically connect the fan of the Heat exchanger unit and the Indoor unit to a single isolator.

Inter - lock circuitConnect the driving relay of the duct fan(DC 12V) between 1 and 6 on the indoor P.C. board.(Rated current of the relay for duct fan should be up to 75mA.)After installation, carry out a trial operation to check that the duct fan of the indoor unit start/stopsimultaneously.(Carry out the trial operation following the installation manual of the indoor unit.)

0

10

20

30

40

50

60

70

80

0 50 100 150 200 250

Fresh Air Volume (m3/h)

Sta

tic P

ress

ure

(Pa)

MMU-AP0242SH

MMU-AP0152SH,MMU-AP182SH

Flange Option :TCB-FF101URE

Duct fanmotor Fresh Air VolumeIndoor unit

Model name MMU- AP0152SH AP0182SH AP0242SHStandard air flow (m3/h) 750 780 1140

A-23

Page 261: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

10

9. Units center of gravity1-way (2 series) Air Discharge Cassette Type

Model name X (mm) Y (mm) Z (mm)Weight (kg)

Main unit Ceiling panel

MMU-AP0152SH

MMU-AP0182SH

MMU-AP0242SH

370 475 8020 5.5

21 5.5

A-24

Page 262: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

Slim Duct Type

Engineering Data

Oct. 05’

Contents

1. Specifications2. Electrical current characteristics3. Dimensions4. Sensible capacity table5. Wiring diagrams6. Fan characteristics7. Sound characteristics (NC Curve)8. Fresh air intake (Design guide)

Indoor UnitMMD-AP0071SPHMMD-AP0091SPHMMD-AP0121SPHMMD-AP0151SPHMMD-AP0181SPH

MMD-AP0071SPH (SH)-CMMD-AP0091SPH (SH)-CMMD-AP0121SPH (SH)-CMMD-AP0151SPH (SH)-CMMD-AP0181SPH (SH)-C

MMD-AP0071SPH-KMMD-AP0091SPH-KMMD-AP0121SPH-KMMD-AP0151SPH-KMMD-AP0181SPH-K

A-25

Page 263: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

A-26

Page 264: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

1

1. Specification

Model name MMD-

Cooling/Heating capacity (kW)

Electrical

characteristics

Appearance

Dimension

Total weight (kg)

Heat exchanger

Soundproof / Heat-insulating material

Fan

Standard air

flow

Motor (W)

External static pressure (Pa)

Controller

Air filter

Connecting

pipe

Sound pressure level

High/Mid./Low

Sound power level (dB(A))

Gas pipe (mm)

Liquid pipe (mm)

Drain pipe (Nominal dia.mm)

Under air inlet (dB(A))

Back air inlet (dB(A))

High (m3/h)

(Mid./Low) (m3/h)

Air filter pressure loss (Pa)

Power supply

Running current (A)

Power consumption (kW)

Starting current (A)

Height (mm)

Width (mm)

Depth (mm)

AP0071SPH AP0091SPH AP0121SPH AP0151SPH AP0181SPH

2.2/2.5 2.8/3.2 3.6/4.0 4.5/5.0 5.6/6.3

1 phase 50Hz 230V (220-240V)

0.29 0.29 0.31 0.32 0.39

0.039 0.039 0.043 0.045 0.054

0.51 0.51 0.54 0.56 0.68

Zinc hot dipping steel plate

210

845

645

22 22 22 23 23

Finned tube

Polyethylene foam + Polyurethane foam

Centrifugal fan (Sirocco fan)

540 600 690 780

470/400 520/450 600/520 680/580

60

6 (Factory setting) 5 (Factory setting) 4 (Factory setting)

-16-31-46 4steps -15-30-45 4steps -14-29-44 4steps

4 5 6

Remote controller

Standard filter supplied (Long life filter)

9.5 12.7

6.4

25 (Polyvinyl chloride tube : External dia.32 Internal dia.25)

36/33/30 38/35/32 39/36/33 40/38/36

28/26/24 29/27/25 32/30/28 33/3129

51 53 54 55

* This sound pressure level is measured on the condition of Factory setting external static pressure.* This sound pressure level are measured in an anechoic chamber in accordance with JIS B8616.

50Hz

A-27

Page 265: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

2

1. Specification60Hz

AP0071SPH AP0091SPH AP0121SPH AP0151SPH AP0181SPH

2.2/2.5 2.8/3.2 3.6/4.0 4.5/5.0 5.6/6.3

1 phase 60Hz 220V

0.27 0.27 0.30 0.31 0.37

0.037 0.037 0.041 0.043 0.052

0.47 0.47 0.53 0.54 0.65

Zinc hot dipping steel plate

210

845

645

22 22 22 23 23

Finned tube

Polyethylene foam + Polyurethane foam

Centrifugal fan (Sirocco fan)

540 600 690 780

470/400 520/450 600/520 680/580

60

6 (Factory setting) 5 (Factory setting) 4 (Factory setting)

-16-31-46 4steps -15-30-45 4steps -14-29-44 4steps

4 5 6

Remote controller

Standard filter supplied (Long life filter)

9.5 12.7

6.4

25 (Polyvinyl chloride tube : External dia.32 Internal dia.25)

36/33/30 38/35/32 39/36/33 40/38/36

28/26/24 29/27/25 32/30/28 33/31/29

51 53 54 55

Model name MMD-

Cooling/Heating capacity (kW)

Electrical

characteristics

Appearance

Dimension

Total weight (kg)

Heat exchanger

Soundproof / Heat-insulating material

Fan

Standard air

flow

Motor (W)

External static pressure (Pa)

Controller

Air filter

Connecting

pipe

Sound pressure level

High/Mid./Low

Sound power level (dB(A))

Gas pipe (mm)

Liquid pipe (mm)

Drain pipe (Nominal dia.mm)

Under air inlet (dB(A))

Back air inlet (dB(A))

High (m3/h)

(Mid./Low) (m3/h)

Air filter pressure loss (Pa)

Power supply

Running current (A)

Power consumption (kW)

Starting current (A)

Height (mm)

Width (mm)

Depth (mm)

* This sound pressure level is measured on the condition of Factory setting external static pressure.* This sound pressure level are measured in an anechoic chamber in accordance with JIS B8616.

A-28

Page 266: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

3

1. Specification

China Model

AP0071SPH-C AP0091SPH-C AP0121SPH-C AP0151SPH-C AP0181SPH-C

2.2/2.5 2.8/3.2 3.6/4.0 4.5/5.0 5.6/6.3

1 phase 50Hz 220V

0.29 0.29 0.31 0.32 0.39

0.039 0.039 0.043 0.045 0.054

0.51 0.51 0.54 0.56 0.68

Zinc hot dipping steel plate

210

845

645

22 22 22 23 23

Finned tube

Polyethylene foam + Polyurethane foam

Centrifugal fan (Sirocco fan)

540 600 690 780

470/400 520/450 600/520 680/580

60

10(factory setting)-20-35-50 4steps

Remote controller

Field supply

9.5 12.7

6.4

25 (Polyvinyl chloride tube : External dia.32 Internal dia.25)

36/33/30 38/35/32 39/36/33 40/38/36

28/26/24 29/27/25 32/30/28 33/31/29

Model name MMD-

Cooling/Heating capacity (kW)

Electrical

characteristics

Appearance

Dimension

Total weight (kg)

Heat exchanger

Soundproof / Heat-insulating material

Fan

Standard air

flow

Motor (W)

External static pressure (Pa)

Controller

Air filter

Connecting

pipe

Sound pressure level

High/Mid./Low

Gas pipe (mm)

Liquid pipe (mm)

Drain pipe (Nominal dia.mm)

Under air inlet (dB(A))

Back air inlet (dB(A))

High (m3/h)

(Mid./Low) (m3/h)

Power supply

Running current (A)

Power consumption (kW)

Starting current (A)

Height (mm)

Width (mm)

Depth (mm)

* This sound pressure level is measured on the condition of Factory setting external static pressure.* This sound pressure level are measured in an anechoic chamber in accordance with JIS B8616.

A-29

Page 267: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

4

1. Specification

China Model

AP0071SH-C P0091SH-C AP0121SH-C AP0151SH-C AP0181SH-C

2.2/2.5 2.8/3.2 3.6/4.0 4.5/5.0 5.6/6.3

1 phase 50Hz 220V

0.26 0.26 0.27 0.28 0.35

0.027 0.027 0.031 0.033 0.042

0.46 0.46 0.47 0.49 0.61

Zinc hot dipping steel plate

210

845

645

22 22 22 23 23

Finned tube

Polyethylene foam + Polyurethane foam

Centrifugal fan (Sirocco fan)

540 600 690 780

470/400 520/450 600/520 680/580

60

10(factory setting)-20-35-50 4steps

Remote controller

Field supply

9.5 12.7

6.4

20 (Polyvinyl chloride tube : External dia.26 Internal dia.20)

36/33/30 38/35/32 39/36/33 40/38/36

28/26/24 29/27/25 32/30/28 33/31/29

Model name MMD-

Cooling/Heating capacity (kW)

Electrical

characteristics

Appearance

Dimension

Total weight (kg)

Heat exchanger

Soundproof / Heat-insulating material

Fan

Standard air

flow

Motor (W)

External static pressure (Pa)

Controller

Air filter

Connecting

pipe

Sound pressure level

High/Mid./Low

Gas pipe (mm)

Liquid pipe (mm)

Drain pipe (Nominal dia.mm)

Under air inlet (dB(A))

Back air inlet (dB(A))

High (m3/h)

(Mid./Low) (m3/h)

Power supply

Running current (A)

Power consumption (kW)

Starting current (A)

Height (mm)

Width (mm)

Depth (mm)

A-30

Page 268: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

5

1. Specification

60Hz

AP0071SPH-K AP0091SPH-K AP0121SPH-K AP0151SPH-K AP0181SPH-K

2.2/2.5 2.8/3.2 3.6/4.0 4.5/5.0 5.6/6.3

1 phase 60Hz 220V

0.27 0.27 0.30 0.31 0.37

0.037 0.037 0.041 0.043 0.052

0.47 0.47 0.53 0.54 0.65

Zinc hot dipping steel plate

210

845

645

22 22 22 23 23

Finned tube

Polyethylene foam + Polyurethane foam

Centrifugal fan (Sirocco fan)

540 600 690 780

470/400 520/450 600/520 680/580

60

6 (Factory setting) 5 (Factory setting) 4 (Factory setting)

-16-31-46 4steps -15-30-45 4steps -14-29-44 4steps

4 5 6

Remote controller

Standard filter supplied (Long life filter)

9.5 12.7

6.4

25 (Polyvinyl chloride tube : External dia.32 Internal dia.25)

36/33/30 38/35/32 39/36/33 40/38/36

28/26/24 29/27/25 32/30/28 33/31/29

Model name MMD-

Cooling/Heating capacity (kW)

Electrical

characteristics

Appearance

Dimension

Total weight (kg)

Heat exchanger

Soundproof / Heat-insulating material

Fan

Standard air

flow

Motor (W)

External static pressure (Pa)

Controller

Air filter

Connecting

pipe

Sound pressure level

High/Mid./Low

Gas pipe (mm)

Liquid pipe (mm)

Drain pipe (Nominal dia.mm)

Under air inlet (dB(A))

Back air inlet (dB(A))

High (m3/h)

(Mid./Low) (m3/h)

Air filter pressure loss (Pa)

Power supply

Running current (A)

Power consumption (kW)

Starting current (A)

Height (mm)

Width (mm)

Depth (mm)

* This sound pressure level is measured on the condition of Factory setting external static pressure.* This sound pressure level are measured in an anechoic chamber in accordance with JIS B8616.

A-31

Page 269: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

6

2. Electrical current characteristics

Nominal Voltage

(V-Ph-Hz)

230-1-50

230-1-50

230-1-50

230-1-50

230-1-50

220-1-60

220-1-60

220-1-60

220-1-60

220-1-60

230-1-50

230-1-50

230-1-50

230-1-50

230-1-50

Type

S-MMS (50Hz)

S-MMS (60Hz)

S-HRM

Voltage Range

Min Max

198 264

198 264

198 264

198 264

198 264

198 264

198 264

198 264

198 264

198 264

198 264

198 264

198 264

198 264

198 264

Fan Motor

kW FLA

0.060 0.35

0.060 0.35

0.060 0.37

0.060 0.38

0.060 0.47

0.060 0.32

0.060 0.32

0.060 0.36

0.060 0.37

0.060 0.44

0.060 0.35

0.060 0.35

0.060 0.37

0.060 0.38

0.060 0.47

Power Supply

MCA MOCP

0.44 15

0.44 15

0.47 15

0.48 15

0.59 15

0.41 15

0.41 15

0.45 15

0.47 15

0.56 15

0.44 15

0.44 15

0.47 15

0.48 15

0.59 15

MMD-AP0071SPH

MMD-AP0091SPH

MMD-AP0121SPH

MMD-AP0151SPH

MMD-AP0181SPH

MMD-AP0071SPH

MMD-AP0091SPH

MMD-AP0121SPH

MMD-AP0151SPH

MMD-AP0181SPH

MMD-AP0071SPH

MMD-AP0091SPH

MMD-AP0121SPH

MMD-AP0151SPH

MMD-AP0181SPH

Model

A-32

Page 270: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

7

805

805

825

n=24 M5 (Ø4.2 mounting hole)

n=22 M5 (Ø4.2 mounting hole)

10012.5

100 100 100 100 100 10012.5

45.3

10026

6.5

12.5

170

100

41.5 8.2

or le

ss28

6.8

12.5

44.3

100

44.3

188.

6

100

825

100 100 100 100 100 100 100 100

845

80580

Fresh air inlet(Knock-out hole)

59 910

168

(insi

de)

2120

19

67

210

5751

164

567

359

40

372

422

502

4-Ø

4

Ø92 80 16

812

021 803 (inside) Refrigerant piping2121

Air filter 103

31

33163

Hanger plate

Drain-up port

3. DimensionsMMD-AP0071SPH(-K), AP0091SPH(-K), AP0121SPH(-K), AP0151SPH(-K), AP0181SPH(-K)

Air inlet connecting flange (Field supply)

Rearside

Underside

Wired remote controller RBC-AMT21E RBC-AMT31ESimple wired remote controller RBC-AS21E RBC-AS21E2Wireless remote controller kit TCB-AX21E TCB-AX21E2Weekly timer application RBC-AMT31E and RBC-EXW21E2

A-33

Page 271: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

8

3. DimensionsInstallation space

5 or more

210

100 or more 250 or more

235 or moreAir outlet

5 or more

210

50 or more

235 or m

2500 or more

Floor surface

Air inletCeiling

5 or more

210

300 or more

235 or more

2500 or more

Air intlet

Floor surface

Ceiling

Service space

(length:mm)

50 50 645945 Air filter

Service door (Ceiling opening)

645945

Service door (Ceiling opening)

Air filter

745

945

645

745

Air outlet

(length:mm)

Under air inlet Rear air inlet

A-34

Page 272: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

9

845

80580

Fresh air inlet(Knock-out hole)

59 910

168

(insi

de)

2120

19

67

210

5751

164

5

67

359

40

372

422

502

4-Ø

4

Ø92 80 16

8

146

120

21 21 803 (inside)Refrigerant piping

21Natural drain port 103

31

33163

Hanger plate

Drain-up port(SPH model only)

3. DimensionsMMD-AP007SPH-C, AP0091SPH-C, AP0121SPH-C, AP0151SPH-C, AP0181SPH-C,MMD-AP0071SH-C, AP0091SH-C, AP0121SH-C, AP0151SH-C, AP0181SH-C

Air inlet connecting flange (Field supply)

805

805

825

n=24 M5 (Ø4.2 mounting hole)

n=22 M5 (Ø4.2 mounting hole)

10012.5

100 100 100 100 100 10012.5

45.3

10026

6.5

12.5

170

100

41.5 8.2

or le

ss28

6.8

12.5

44.3

100

44.3

188.

6

100

825

100 100 100 100 100 100 100 100

Rearside

Underside

Wired remote controller RBC-AMT21E RBC-AMT31ESimple wired remote controller RBC-AS21E RBC-AS21E2Wireless remote controller kit TCB-AX21E TCB-AX21E2Weekly timer application RBC-AMT31E and RBC-EXW21E2

A-35

Page 273: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

10

3. DimensionsInstallation space(length:mm)

5 or more

100 or more 250 or more

210 235 or moreAir outlet

MMD-AP0071SPH-C, MMD-AP0091SPH-C, MMD-AP0121SPH-C, MMD-AP0151SPH-C, MMD-AP0181SPH-C

MMD-AP0071SH-C, MMD-AP0091SH-C, MMD-AP0121SH-C, MMD-AP0151SH-C, MMD-AP0181SH-C

Drain piping

5 or more

100 or more 250 or more

210 235 or moreAir outlet

Drain piping left side

Drain pipng right sideDrain piping

5 or more

250 or more 200 or more

(Refrigerant piping space)

210 235 or moreAir outlet

MMD-AP0071SPH-C, MMD-AP0091SPH-C, MMD-AP0121SPH-C, MMD-AP0151SPH-C, MMD-AP0181SPH-CMMD-AP0071SH-C, MMD-AP0091SH-C, MMD-AP0121SH-C, MMD-AP0151SH-C, MMD-AP0181SH-C

5 or more

50 or more

210 235 or more

2500 or more

Floor surface

Air inletCeiling

5 or more

210

300 or more

235 or more

2500 or more

Air intlet

Floor surface

Ceiling

Under air inlet

Rear air inlet

A-36

Page 274: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

11

3. DimensionsService space(length:mm)

50 50

945 645

Service door (Ceiling opening)

945

645

Air outlet

MMD-AP0071SPH-C, MMD-AP0091SPH-C, MMD-AP0121SPH-C, MMD-AP0151SPH-C, MMD-AP0181SPH-C

MMD-AP0071SH-C, MMD-AP0091SH-C, MMD-AP0121SH-C, MMD-AP0151SH-C, MMD-AP0181SH-CDrain piping

50 100

995 645

Service door (Ceiling opening)

995

645

Air outlet

Drain piping left side

Drain pipng right sideDrain piping

100 50

645

Service door (Ceiling opening)

995

995

645

Air outlet

A-37

Page 275: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

12

4. Sensible capacity tableSlim Duct Type ( MMD-AP***SPH )

TC : Total capacity [kW] SHC : Sensible capacity [kW]

Unitsize

007

009

012

Outdoorair temp.

CDB

10.012.014.016.018.020.021.023.025.027.029.031.033.035.037.039.0

10.012.014.016.018.020.021.023.025.027.029.031.033.035.037.039.0

10.012.014.016.018.020.021.023.025.027.029.031.033.035.037.039.0

Indoor air temp.14.0CWB 16.0CWB 18.0CWB 19.0CWB 20.0CWB 22.0CWB 24.0CWB20CDB 23CDB 26CDB 27CDB 28CDB 30CDB 32CDB

TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC

1.8 1.6 2.0 1.7 2.1 1.8 2.2 1.8 2.3 1.8 2.4 1.8 2.5 1.71.8 1.6 2.0 1.7 2.1 1.8 2.2 1.8 2.3 1.8 2.4 1.8 2.5 1.71.8 1.6 2.0 1.7 2.1 1.8 2.2 1.8 2.3 1.8 2.4 1.8 2.5 1.71.8 1.6 2.0 1.7 2.1 1.8 2.2 1.8 2.3 1.8 2.4 1.8 2.5 1.71.8 1.6 2.0 1.7 2.1 1.8 2.2 1.8 2.3 1.8 2.4 1.8 2.5 1.71.8 1.6 2.0 1.7 2.1 1.8 2.2 1.8 2.3 1.8 2.4 1.8 2.5 1.71.8 1.6 2.0 1.7 2.1 1.8 2.2 1.8 2.3 1.8 2.4 1.8 2.5 1.71.8 1.6 2.0 1.7 2.1 1.8 2.2 1.8 2.3 1.8 2.4 1.8 2.5 1.71.8 1.6 2.0 1.7 2.1 1.8 2.2 1.8 2.3 1.8 2.4 1.8 2.5 1.71.8 1.6 2.0 1.7 2.1 1.8 2.2 1.8 2.3 1.8 2.4 1.8 2.5 1.71.8 1.6 2.0 1.7 2.1 1.8 2.2 1.8 2.3 1.8 2.4 1.8 2.5 1.71.8 1.6 2.0 1.7 2.1 1.8 2.2 1.8 2.3 1.8 2.4 1.8 2.5 1.71.8 1.6 2.0 1.7 2.1 1.8 2.2 1.8 2.3 1.8 2.4 1.8 2.5 1.71.8 1.6 2.0 1.7 2.1 1.8 2.2 1.8 2.3 1.8 2.4 1.8 2.5 1.71.7 1.5 1.9 1.6 2.1 1.7 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.71.7 1.5 1.9 1.6 2.0 1.7 2.1 1.7 2.1 1.7 2.3 1.7 2.4 1.6

2.3 1.9 2.5 2.0 2.7 2.1 2.8 2.1 2.9 2.1 3.1 2.1 3.2 2.02.3 1.9 2.5 2.0 2.7 2.1 2.8 2.1 2.9 2.1 3.1 2.1 3.2 2.02.3 1.9 2.5 2.0 2.7 2.1 2.8 2.1 2.9 2.1 3.1 2.1 3.2 2.02.3 1.9 2.5 2.0 2.7 2.1 2.8 2.1 2.9 2.1 3.1 2.1 3.2 2.02.3 1.9 2.5 2.0 2.7 2.1 2.8 2.1 2.9 2.1 3.1 2.1 3.2 2.02.3 1.9 2.5 2.0 2.7 2.1 2.8 2.1 2.9 2.1 3.1 2.1 3.2 2.02.3 1.9 2.5 2.0 2.7 2.1 2.8 2.1 2.9 2.1 3.1 2.1 3.2 2.02.3 1.9 2.5 2.0 2.7 2.1 2.8 2.1 2.9 2.1 3.1 2.1 3.2 2.02.3 1.9 2.5 2.0 2.7 2.1 2.8 2.1 2.9 2.1 3.1 2.1 3.2 2.02.3 1.9 2.5 2.0 2.7 2.1 2.8 2.1 2.9 2.1 3.1 2.1 3.2 2.02.3 1.9 2.5 2.0 2.7 2.1 2.8 2.1 2.9 2.1 3.1 2.1 3.2 2.02.3 1.9 2.5 2.0 2.7 2.1 2.8 2.1 2.9 2.1 3.1 2.1 3.2 2.02.3 1.9 2.5 2.0 2.7 2.1 2.8 2.1 2.9 2.1 3.1 2.1 3.2 2.02.3 1.9 2.5 2.0 2.7 2.1 2.8 2.1 2.9 2.1 3.1 2.1 3.2 2.02.2 1.8 2.5 1.9 2.6 2.0 2.7 2.0 2.8 2.0 3.0 2.0 3.1 2.02.2 1.8 2.4 1.9 2.6 2.0 2.6 2.0 2.7 2.0 2.9 2.0 3.0 1.9

3.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.43.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.43.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.43.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.43.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.43.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.43.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.43.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.43.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.43.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.43.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.43.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.43.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.43.0 2.2 3.3 2.4 3.5 2.5 3.6 2.5 3.7 2.5 3.9 2.5 4.1 2.42.9 2.1 3.2 2.3 3.4 2.4 3.5 2.4 3.6 2.4 3.8 2.4 4.0 2.32.8 2.1 3.1 2.2 3.3 2.4 3.4 2.4 3.5 2.4 3.7 2.3 3.9 2.3

A-38

Page 276: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

13

4. Sensible capacity tableSlim Duct Type ( MMD-AP***SPH )

TC : Total capacity [kW] SHC : Sensible capacity [kW]

Unitsize

015

018

Outdoorair temp.

CDB

10.012.014.016.018.020.021.023.025.027.029.031.033.035.037.039.0

10.012.014.016.018.020.021.023.025.027.029.031.033.035.037.039.0

Indoor air temp.14.0CWB 16.0CWB 18.0CWB 19.0CWB 20.0CWB 22.0CWB 24.0CWB20CDB 23CDB 26CDB 27CDB 28CDB 30CDB 32CDB

TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC

3.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.13.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.13.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.13.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.13.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.13.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.13.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.13.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.13.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.13.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.13.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.13.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.13.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.13.7 2.8 4.1 3.0 4.4 3.2 4.5 3.2 4.6 3.2 4.9 3.2 5.1 3.13.6 2.7 4.0 2.9 4.2 3.1 4.4 3.1 4.5 3.1 4.7 3.1 5.0 3.03.5 2.7 3.8 2.8 4.1 3.0 4.2 3.0 4.4 3.0 4.6 3.0 4.8 2.9

4.6 3.5 5.1 3.7 5.4 3.9 5.6 3.9 5.8 3.9 6.1 3.9 6.4 3.84.6 3.5 5.1 3.7 5.4 3.9 5.6 3.9 5.8 3.9 6.1 3.9 6.4 3.84.6 3.5 5.1 3.7 5.4 3.9 5.6 3.9 5.8 3.9 6.1 3.9 6.4 3.84.6 3.5 5.1 3.7 5.4 3.9 5.6 3.9 5.8 3.9 6.1 3.9 6.4 3.84.6 3.5 5.1 3.7 5.4 3.9 5.6 3.9 5.8 3.9 6.1 3.9 6.4 3.84.6 3.5 5.1 3.7 5.4 3.9 5.6 3.9 5.8 3.9 6.1 3.9 6.4 3.84.6 3.5 5.1 3.7 5.4 3.9 5.6 3.9 5.8 3.9 6.1 3.9 6.4 3.84.6 3.5 5.1 3.7 5.4 3.9 5.6 3.9 5.8 3.9 6.1 3.9 6.4 3.84.6 3.5 5.1 3.7 5.4 3.9 5.6 3.9 5.8 3.9 6.1 3.9 6.4 3.84.6 3.5 5.1 3.7 5.4 3.9 5.6 3.9 5.8 3.9 6.1 3.9 6.4 3.84.6 3.5 5.1 3.7 5.4 3.9 5.6 3.9 5.8 3.9 6.1 3.9 6.4 3.84.6 3.5 5.1 3.7 5.4 3.9 5.6 3.9 5.8 3.9 6.1 3.9 6.4 3.84.6 3.5 5.1 3.7 5.4 3.9 5.6 3.9 5.8 3.9 6.1 3.9 6.4 3.84.6 3.5 5.1 3.7 5.4 3.9 5.6 3.9 5.8 3.9 6.1 3.9 6.4 3.84.5 3.3 4.9 3.6 5.3 3.8 5.4 3.8 5.6 3.8 5.9 3.7 6.2 3.74.3 3.3 4.8 3.5 5.1 3.7 5.3 3.7 5.4 3.7 5.7 3.6 6.0 3.6

A-39

Page 277: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

14

5. Wiring diagramsMMD-AP0071SPH(SH), AP0091SPH(SH), AP0121SPH(SH), AP0151SPH(SH), AP0181SPH(SH)

A-40

Page 278: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

15

6. Fan characteristicsMMD-AP0071SPHMMD-AP0091SPH

0

10

20

30

40

50

60

300 400 500 600 700

Air Volume (m3/h)

Ext

erna

l sta

tic p

ress

ure

(Pa)

High (50Pa)

High (35Pa)

High (20Pa)

High (10Pa)

Low (50Pa)

Low (35Pa)

Low (20Pa)

Lower limit of externalstatic pressure (50Pa)

Lower limit of externalstatic pressure (35Pa)

Lower limit of externalstatic pressure (20Pa)

Upper limit ofexternal static

pressure(35Pa)

Upper limit of externalstatic pressure(50Pa)

Upper limit ofexternal static

pressure(20Pa)

Upper limit ofexternal static

pressure(10Pa)

Standard air volume : 540m3/h

Low (10Pa)

MMD-AP0121SPH

0

10

20

30

40

50

60

300 400 500 600 700

Air Volume (m3/h)

Ext

erna

l sta

tic p

ress

ure

(Pa)

High (50Pa)

High (35Pa)

High (20Pa)

High (10Pa)

Low (50Pa)

Low (35Pa)

Low (20Pa)

Low (10Pa)

Lower limit of externalstatic pressure (50Pa)

Lower limit of externalstatic pressure (35Pa)

Lower limit of externalstatic pressure (20Pa)

Upper limit of externalstatic pressure(50Pa)

Upper limit ofexternal static

pressure(20Pa)

Upper limit ofexternal static

pressure(35Pa)

Upper limit ofexternal static

pressure(10Pa)

Standard air volume : 600m3/h

MMD-AP0151SPH

0

10

20

30

40

50

60

400 500 600 700 800

High (50Pa)

High (35Pa)

High (20Pa)

High (10Pa)

Low (50Pa)

Low (35Pa)

Low (20Pa)

Low (10Pa)

Lower limit of externalstatic pressure (50Pa)

Lower limit of externalstatic pressure (35Pa)

Lower limit of externalstatic pressure (20Pa)

Upper limit of externalstatic pressure(50Pa)

Upper limit ofexternal static

pressure(20Pa)

Upper limit ofexternal static

pressure(35Pa)

Upper limit ofexternal static

pressure(10Pa)

Air Volume (m3/h)

Ext

erna

l sta

tic p

ress

ure

(Pa)

Standard air volume : 690m3/h

MMD-AP0181SPH

0

10

20

30

40

50

60

400 500 600 700 800 900

High (50Pa)

High (35Pa)

High (20Pa)

Low (50Pa)

Low (35Pa)

Low (20Pa)

Low (10Pa)

Lower limit ofexternal staticpressure (50Pa)

Lower limit ofexternal staticpressure (35Pa)

Lower limit ofexternal staticpressure (20Pa)

Upper limit of externalstatic pressure(50Pa)

Upper limit ofexternal static

pressure(20Pa)

Upper limit ofexternal static

pressure(35Pa)

Upper limit ofexternal static

pressure(10Pa)

High (10Pa)

Standard air volume : 780m3/h

Air Volume (m3/h)

Ext

erna

l sta

tic p

ress

ure

(Pa)

A-41

Page 279: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

16

6. Fan characteristics(Filter attached)

MMD-AP0071SPHMMD-AP0091SPH

MMD-AP0121SPH

0

10

20

30

40

50

60

300 400 500 600 700

High (50Pa)

High (20Pa)

High (10Pa)

Low (50Pa)

Low (35Pa)

Low (20Pa)

Lower limit of externastatic pressure (50Pa)

Lower limit of externalstatic pressure (35Pa)

Lower limit of externstatic pressure (20Pa)

Upper limit of externalstatic pressure(50Pa)

Upper limit ofexternal static

pressure(20Pa)

Upper limit of external static

pressure(35Pa)

Upper limit ofexternal static

pressure(10Pa)Standard filterpressure loss

Air Volume (m3/h)

Ext

erna

l sta

tic p

ress

ure

(Pa)

Standard air volume : 540m3/h

Low (10Pa)0

10

20

30

40

50

60

300 400 500 600 700

High (50Pa)

High (35Pa)

High (20Pa)

High (10Pa)

Low (50Pa)

Low (35Pa)

Low (20Pa)

Low (10Pa)

Lower limit of externalstatic pressure (50Pa)

Lower limit of externalstatic pressure (35Pa)

Lower limit of externalstatic pressure (20Pa)

Upper limit of externalstatic pressure(50Pa)

Upper limit oexternal static

pressure(20Pa)

Upper limit oexternal static

pressure(35Pa)

Upper limit oexternal static

pressure(10Pa)Standard filterpressure loss

Air Volume (m3/h)

Ext

erna

l sta

tic p

ress

ure

(Pa)

Standard air volume : 600m3/h

MMD-AP0151SPH MMD-AP0181SPH

0

10

20

30

40

50

60

400 500 600 700 800

High (50Pa)

High (35Pa)

High (10Pa)

Low (50Pa)

Low (35Pa)

Low (20Pa)

Low (10Pa)

Lower limit of externalstatic pressure (35Pa)

Lower limit of externastatic pressure (20Pa)

Upper limit of externalstatic pressure(50Pa)

Upper limit ofexternal static

pressure(20Pa)

Upper limit of externalstatic pressure(35Pa)

Upper limit ofexternal static

pressure(10Pa)

Standard filterpressure loss

High (20Pa)

Lower limit of externalstatic pressure (50Pa)

Standard air volume : 690m3/h

Air Volume (m3/h)

Ext

erna

l sta

tic p

ress

ure

(Pa)

0

10

20

30

40

50

60

400 500 600 700 800 900

High (50Pa)

High (35Pa)

High (20Pa)

High (10Pa)

Low (50Pa)

Low (35Pa)

Low (20Pa)

Low (10Pa)

Lower limit ofexternal staticpressure (50Pa)

Lower limit ofexternal staticpressure (35Pa)

Upper limit of externalstatic pressure(50Pa)

Upper limit of externalstatic pressure(20Pa)

Upper limit of externalstatic pressure(35Pa)

Upper limit ofexternal static

pressure(10Pa)

Lower limit ofexternal staticpressure (20Pa)

Standard filterpressure loss

Air Volume (m3/h)

Ext

erna

l sta

tic p

ress

ure

(Pa)

Standard air volume : 780m3/h

A-42

Page 280: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

17

6. Fan characteristicsCHINA model (Filter attached)

MMD-AP0071SPH-C, SH-CMMD-AP0091SPH-C, SH-C

MMD-AP0121SPH-C, SH-C

0

10

20

30

40

50

60

300 400 500 600 700

High (50Pa)

High (35Pa)

High (20Pa)

High (10Pa)

Low (50Pa)

Low (35Pa)

Low (20Pa)

Lower limit of externalstatic pressure (50Pa)

Lower limit of externalstatic pressure (35Pa)

Lower limit of externalstatic pressure (20Pa)

Upper limit ofexternal static

pressure(35Pa)

Upper limit of externalstatic pressure(50Pa)

Upper limit ofexternal static

pressure(35Pa)

Upper limit ofexternal static

pressure(10Pa)

Air Volume (m3/h)

Ext

erna

l sta

tic p

ress

ure

(Pa)

Standard air volume : 540m3/h

Low (10Pa)

Upper limit ofexternal static

pressure(20Pa)

0

10

20

30

40

50

60

300 400 500 600 700

High (50Pa)

High (35Pa)

High (20Pa)

High (10Pa)

Low (50Pa)

Low (35Pa)

Low (20Pa)

Low (10Pa)

Upper limit of externalstatic pressure(50Pa)

Upper limit ofexternal static

pressure(20Pa)

Upper limit ofexternal static

pressure(35Pa)

Upper limit of externalstatic pressure(10Pa)

Air Volume (m3/h)

Ext

erna

l sta

tic p

ress

ure

(Pa)

Standard air volume : 600m3/h

Lower limit of externalstatic pressure (50Pa)

Lower limit of externalstatic pressure (35Pa)

Lower limit of externalstatic pressure (20Pa)

MMD-AP0151SPH-C, SH-C MMD-AP0181SPH-C, SH-C

0

10

20

30

40

50

60

400 500 600 700 800

High (50Pa)

High (35Pa)

High (20Pa)

High (10Pa)

Low (50Pa)

Low (35Pa)

Low (20Pa)

Low (10Pa)

Upper limit of externalstatic pressure(50Pa)

Upper limit ofexternal static

pressure(20Pa)

Upper limit of externalstatic pressure(35Pa)

Upper limit of external static

pressure(10Pa)

Air Volume (m3/h)

Ext

erna

l sta

tic p

ress

ure

(Pa)

Standard air volume : 690m3/h

Lower limit of externalstatic pressure (50Pa)

Lower limit of externstatic pressure (35Pa)

Lower limit of externalstatic pressure (20Pa)

0

10

20

30

40

50

60

400 500 600 700 800 900

High (50Pa)

High (35Pa)

High (20Pa)

High (10Pa)

Low (50Pa)

Low (35Pa)

Low (20Pa)

Low (10Pa)

Lower limit of externstatic pressure (35Pa)

Upper limit of externalstatic pressure(50Pa)

Upper limit of externalstatic pressure(20Pa)

Upper limit of externalstatic pressure(35Pa)

Upper limit of externalstatic pressure(10Pa)

Air Volume (m3/h)

Ext

erna

l sta

tic p

ress

ure

(Pa)

Standard air volume : 780m3/h

Lower limit ofexternal staticpressure (50Pa)

Lower limit of extestatic pressure (20Pa)

A-43

Page 281: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

18

7. Sound Characteristics (NC Curve)MMD-AP0071SPH/SH ,MMD-AP0091SPH/SH

Air outlet Air inlet

2m 1m

Duct Duct

Center1.5m

Microphone

Measuring location

Rear air intake

External static pressure 10Pa External static pressure 20Pa

10

20

30

40

50

60

70

63 125 250 500 1000 2000 4000 8000

L

HM

NC-50

NC-40

NC-30

NC-20

Octave band center frequency (Hz)

Oct

ave

band

sou

nd p

ress

ure

leve

l (dB

)

hearing for continuous noiseApproximate threshold of

10

20

30

40

50

60

70

63 125 250 500 1000 2000 4000 8000

L

HM

NC-50

NC-40

NC-30

NC-20

Octave band center frequency (Hz)

Oct

ave

band

sou

nd p

ress

ure

leve

l (dB

)

hearing for continuous noiseApproximate threshold of

External static pressure 35Pa External static pressure 50Pa

10

20

30

40

50

60

70

63 125 250 500 1000 2000 4000 8000

NC-50

NC-40

NC-30

NC-20L

H

M

Octave band center frequency (Hz)

Oct

ave

band

sou

nd p

ress

ure

leve

l (dB

)

hearing for continuous noiseApproximate threshold of

10

20

30

40

50

60

70

63 125 250 500 1000 2000 4000 8000

L

HM

NC-50

NC-40

NC-30

NC-20

Octave band center frequency (Hz)

Oct

ave

band

sou

nd p

ress

ure

leve

l (dB

)

hearing for continuous noiseApproximate threshold of

Fan tapSound pressure

level (dB(A))

H M L

28 26 24

Fan tapSound pressure

level (dB(A))

H M L

29 27 25

Fan tapSound pressure

level (dB(A))

H M L

30 28 26

Fan tapSound pressure

level (dB(A))

H M L

32 29 27

A-44

Page 282: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

19

7. Sound Characteristics (NC Curve)MMD-AP0121SPH/SH

Measuring location

Rear air intakeAir outlet Air inlet

2m 1m

Duct Duct

Center1.5m

Microphone

10

20

30

40

50

60

70

63 125 250 500 1000 2000 4000 8000

L

H

M

NC-50

NC-40

NC-30

NC-20

Octave band center frequency (Hz)

Oct

ave

band

sou

nd p

ress

ure

leve

l (dB

)

hearing for continuous noiseApproximate threshold of

10

20

30

40

50

60

70

63 125 250 500 1000 2000 4000 8000

Octave band center frequency (Hz)

Oct

ave

band

sou

nd p

ress

ure

leve

l (dB

)

L

H

M

NC-50

NC-40

NC-30

NC-20

hearing for continuous noiseApproximate threshold of

10

20

30

40

50

60

70

63 125 250 500 1000 2000 4000 8000

Octave band center frequency (Hz)

Oct

ave

band

sou

nd p

ress

ure

leve

l (dB

)

NC-50

NC-40

NC-30

NC-20

L

H

M

hearing for continuous noiseApproximate threshold of

10

20

30

40

50

60

70

63 125 250 500 1000 2000 4000 8000

Octave band center frequency (Hz)

Oct

ave

band

sou

nd p

ress

ure

leve

l (dB

)

L

H

M

NC-50

NC-40

NC-30

NC-20

hearing for continuous noiseApproximate threshold of

External static pressure 10Pa External static pressure 20Pa

External static pressure 35Pa External static pressure 50Pa

Fan tapSound pressure

level (dB(A))

H M L

29 27 25

Fan tapSound pressure

level (dB(A))

H M L

30 28 26

Fan tapSound pressure

level (dB(A))

H M L

31 29 27

Fan tapSound pressure

level (dB(A))

H M L

32 30 28

A-45

Page 283: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

20

10

20

30

40

50

60

70

63 125 250 500 1000 2000 4000 8000

Octave band center frequency (Hz)

Oct

ave

band

sou

nd p

ress

ur le

vel (

dB)

NC-50

NC-40

NC-30

NC-20

L

H

M

Approximate threshold ofhearing for continuous noise

10

20

30

40

50

60

70

63 125 250 500 1000 2000 4000 8000

Octave band center frequency (Hz)

Oct

ave

band

sou

nd p

ress

ure

leve

l (dB

)

L

H

M

NC-50

NC-40

NC-30

NC-20

Approximate threshold ofhearing for continuous noise

7. Sound Characteristics (NC Curve)

Measuring location

Rear air intakeAir outlet Air inlet

2m 1m

Duct Duct

Center1.5m

Microphone

L

10

20

30

40

50

60

70

63 125 250 500 1000 2000 4000 8000

Octave band center frequency (Hz)

Oct

ave

band

sou

nd p

ress

ure

leve

l (dB

)

H

M

NC-50

NC-40

NC-30

NC-20

Approximate threshold ofhearing for continuous noise

10

20

30

40

50

60

70

63 125 250 500 1000 2000 4000 8000

Octave band center frequency (Hz)

Oct

ave

band

sou

nd p

ress

ure

leve

l (dB

)

L

H

M

NC-50

NC-40

NC-30

NC-20

Approximate threshold ofhearing for continuous noise

MMD-AP0151SPH/SH

External static pressure 10Pa External static pressure 20Pa

External static pressure 35Pa External static pressure 50Pa

Fan tapSound pressure

level (dB(A))

H M L

32 30 28

Fan tapSound pressure

level (dB(A))

H M L

33 31 29

Fan tapSound pressure

level (dB(A))

H M L

34 32 30

Fan tapSound pressure

level (dB(A))

H M L

35 33 31

A-46

Page 284: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

21

10

20

30

40

50

60

70

63 125 250 500 1000 2000 4000 8000

Octave band center frequency (Hz)

Oct

ave

band

sou

nd p

ress

ure

leve

l (dB

)

Approximate threshold ofhearing for continuous noise

L

H

M

NC-50

NC-40

NC-30

NC-20

7. Sound Characteristics (NC Curve)MMD-AP0181SPH/SH

Measuring location

Rear air intake

Air outlet Air inlet

2m 1m

Duct Duct

Center1.5m

Microphone

10

20

30

40

50

60

70

63 125 250 500 1000 2000 4000 8000

Octave band center frequency (Hz)

Oct

ave

band

sou

nd p

ress

ure

leve

l (dB

)

L

H

M

NC-50

NC-40

NC-30

NC-20Approximate threshold ofhearing for continuous noise

10

20

30

40

50

60

70

63 125 250 500 1000 2000 4000 8000

Octave band center frequency (Hz)

Oct

ave

band

sou

nd p

ress

ure

leve

l (dB

)

L

HM

NC-50

NC-40

NC-30

NC-20

hearing for continuous noiseApproximate threshold of

10

20

30

40

50

60

70

63 125 250 500 1000 2000 4000 8000

Octave band center fequency (Hz)

Oct

ave

band

sou

nd p

ress

ure

leve

l (dB

)

NC-50

NC-40

NC-30

NC-20

Approximate threshold ofhearing for continuous noise

L

H

M

External static pressure 10Pa External static pressure 20Pa

External static pressure 35Pa External static pressure 50Pa

Fan tapSound pressure

level (dB(A))

H M L

33 31 29

Fan tapSound pressure

level (dB(A))

H M L

34 32 30

Fan tapSound pressure

level (dB(A))

H M L

35 33 31

Fan tapSound pressure

level (dB(A))

H M L

36 34 32

A-47

Page 285: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

22

10

20

30

40

50

60

70

63 125 250 500 1000 2000 4000 8000

Octave band center frequency (Hz)

Oct

ave

band

sou

nd p

ress

ure

leve

l (dB

)

L

H

M

NC-50

NC-40

NC-30

NC-20

hearing for continuous noiseApproximate threshold of

7. Sound Characteristics (NC Curve)

Measuring location

Under air intake

10

20

30

40

50

60

70

63 125 250 500 1000 2000 4000 8000

Octave band center frequency (Hz)

Oct

ave

band

sou

nd p

ress

ure

leve

l (dB

)

L

H

M

NC-50

NC-40

NC-30

NC-20

hearing for continuous noiseApproximate threshold of

10

20

30

40

50

60

70

63 125 250 500 1000 2000 4000 8000

Octave band center frequency (Hz)

Oct

ave

band

sou

ne p

ress

ure

leve

l (dB

)

NC-50

NC-40

NC-30

NC-20

L

H

M

hearing for continuous noiseApproximate threshold of

10

20

30

40

50

60

70

63 125 250 500 1000 2000 4000 8000

Octave band center frequency (Hz)

Oct

ave

band

sou

nd p

ress

ure

leve

l (dB

)

L

HM

NC-50

NC-40

NC-30

NC-20

hearing for continuous noiseApproximate threshold of

MMD-AP0071SPH/SH ,MMD-AP0091SPH/SH

Air outlet

Air inlet

2m

Center1.5m

Duct

Microphone

External static pressure 10Pa External static pressure 20Pa

External static pressure 35Pa External static pressure 50Pa

Fan tapSound pressure

level (dB(A))

H M L

36 33 30

Fan tapSound pressure

level (dB(A))

H M L

37 34 31

Fan tapSound pressure

level (dB(A))

H M L

39 36 33

Fan tapSound pressure

level (dB(A))

H M L

41 38 35

A-48

Page 286: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

23

7. Sound Characteristics (NC Curve)MMD-AP0121SPH/SH

Measuring location

Under air intake

Air outlet

Air inlet

2m

Center1.5m

Duct

Microphone

10

20

30

40

50

60

70

63 125 250 500 1000 2000 4000 8000

Octave band center frequency (Hz)

Oct

ave

band

sou

nd p

ress

ure

leve

l (dB

)

L

H

M

NC-50

NC-40

NC-30

NC-20

hearing for continuous noiseApproximate threshold of

10

20

30

40

50

60

70

63 125 250 500 1000 2000 4000 8000

Octave band center frequency (Hz)

Oct

ave

band

sou

nd p

ress

ure

leve

l (dB

)

L

H

M

NC-50

NC-40

NC-30

NC-20

hearing for continuous noiseApproximate threshold of

10

20

30

40

50

60

70

63 125 250 500 1000 2000 4000 8000

Octave band center frequency (Hz)

Oct

ave

band

sou

nd p

ress

ure

leve

l (dB

)

NC-50

NC-40

NC-30

NC-20

L

H

M

hearing for continuous noiseApproximate threshold of

10

20

30

40

50

60

70

63 125 250 500 1000 2000 4000 8000

Octave band center frequency (Hz)

Oct

ave

band

sou

nd p

ress

ure

frequ

ency

(dB

)

L

H

M

NC-50

NC-40

NC-30

NC-20

hearing for continuous noiseApproximate threshold of

External static pressure 10Pa External static pressure 20Pa

External static pressure 35Pa External static pressure 50Pa

Fan tapSound pressure

level (dB(A))

H M L

38 35 32

Fan tapSound pressure

level (dB(A))

H M L

39 36 33

Fan tapSound pressure

level (dB(A))

H M L

41 38 35

Fan tapSound pressure

level (dB(A))

H M L

43 40 37

A-49

Page 287: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

24

10

20

30

40

50

60

70

63 125 250 500 1000 2000 4000 8000

Octave band center frequency (Hz)

Oct

ave

band

sou

nd fr

eque

ncy

leve

l (dB

)

L

H

M

NC-50

NC-40

NC-30

NC-20

hearing for continuous noiseApproximate threshold of

7. Sound Characteristics (NC Curve)MMD-AP0151SPH/SH

Measuring location

Under air intake

Air outlet

Air inlet

2m

Center1.5m

Duct

Microphone

10

20

30

40

50

60

70

63 125 250 500 1000 2000 4000 8000

Octave band center frequency (Hz)

Oct

ave

band

sou

nd p

ress

ure

leve

l (dB

)

L

H

M

NC-50

NC-40

NC-30

NC-20

hearing for continuous noiseApproximate threshold of

10

20

30

40

50

60

70

63 125 250 500 1000 2000 4000 8000

L

H

M

NC-50

NC-40

NC-30

NC-20

hearing for continuous noiseApproximate threshold of

Octave band center frequency (Hz)

Oct

ave

band

sou

nd fr

eque

ncy

leve

l (dB

)

10

20

30

40

50

60

70

63 125 250 500 1000 2000 4000 8000

Octave band center frequency (Hz)

Oct

ave

band

sou

nd p

ress

ure

leve

l (dB

)

NC-50

NC-40

NC-30

NC-20

L

H

M

hearing for continuous noiseApproximate threshold of

External static pressure 10Pa External static pressure 20Pa

External static pressure 35Pa External static pressure 50Pa

Fan tapSound pressure

level (dB(A))

H M L

39 36 33

Fan tapSound pressure

level (dB(A))

H M L

40 37 34

Fan tapSound pressure

level (dB(A))

H M L

41 38 35

Fan tapSound pressure

level (dB(A))

H M L

43 40 37

A-50

Page 288: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

25

10

20

30

40

50

60

70

63 125 250 500 1000 2000 4000 8000

Octave band center frequency (Hz)

Oct

ave

band

sou

nd p

ress

ure

leve

l (dB

)

L

H

M

NC-50

NC-40

NC-30

NC-20

hearing for continuous noiseApproximate threshold of

7. Sound Characteristics (NC Curve)MMD-AP0181SPH/SH

Measuring location

Under air intake

Air outlet

Air inlet

2m

Center1.5m

Duct

Microphone

10

20

30

40

50

60

70

63 125 250 500 1000 2000 4000 8000

Octave band center frequency (Hz)

Oct

ave

band

sou

nd p

ress

ure

leve

l (dB

)

L

H

M

NC-50

NC-40

NC-30

NC-20

hearing for continuous noiseApproximate threshold of

10

20

30

40

50

60

70

63 125 250 500 1000 2000 4000 8000

Octave band center frequency (Hz)

Oct

ave

band

sou

nd p

ress

ure

leve

l (dB

)

L

H

M

NC-50

NC-40

NC-30

NC-20

hearing for continuous noiseApproximate threshold of

10

20

30

40

50

60

70

63 125 250 500 1000 2000 4000 8000

Octave band center frequency (Hz)

Oct

ave

band

sou

nd p

ress

ure

leve

l (dB

)

NC-50

NC-40

NC-30

NC-20

L

H

M

hearing for continuous noiseApproximate threshold of

External static pressure 10Pa External static pressure 20Pa

External static pressure 35Pa External static pressure 50Pa

Fan tapSound pressure

level (dB(A))

H M L

40 38 36

Fan tapSound pressure

level (dB(A))

H M L

42 40 37

Fan tapSound pressure

level (dB(A))

H M L

43 41 38

Fan tapSound pressure

level (dB(A))

H M L

44 42 39

A-51

Page 289: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

26

8. Fresh air intake (Design guide)

Slim Duct Type MMD-AP0071SPH, AP0091SPH, AP0121SPHMMD-AP0071SPH-C, AP0091SPH-C, AP0121SPH-CMMD-AP0071SH-C, AP0091SH-C, AP0121SH-C

CautionThe fresh air shall be conditioned by heat reclaim ventilator or similar.Ensure the fresh air volume is determined so that mixed suction air and fresh air maintain theoperating temperature.*1.Recommended conditioned air temperature is 12 °C to 30 °C.

However, Make a fresh air volume within 20% of standard.

Install a air filter within the fresh air duct.( Fresh air does not pass through the filter of Indoor unit.)

Insulate the fresh air duct.Electrically connect the fan of the Heat exchanger unit and the Indoor unit to a single isolator.

-10

0

10

20

30

0 20 40 60 80 100 120 140

Fresh Air Volume (m3/h)

Sta

tic P

ress

ure

(Pa)

Duct fanmotor Fresh Air Volume

Flange Option :TCB-FF101URE

Indoor unit

Inter - lock circuitConnect the driving relay of the duct fan (DC 12V) between 1 and 6 on the indoor P.C. board.(Rated current of the relay for duct fan should be up to 75mA.)After installation, carry out a trial operation to check that the duct fan of the indoor unit start/stopsimultaneously.(Carry out the trial operation following the installation manual of the indoor unit.)

Model name MMD- AP0071SPH AP0091SPH AP0121SPHAP0071SPH-C AP0091SPH-C AP0121SPH-CAP0071SH-C AP0091SH-C AP0121SH-C

Standard air flow (m3/h) 540 540 600

A-52

Page 290: Super-MMS Engineering Data Book Engineering... · Indoor units with different capacities and configurations can be combined up to a maximum of 135% of the outdoor units capacity

27

8. Fresh air intake (Design guide)

Slim Duct Type MMD-AP0151SPH, AP0181SPHMMD-AP0151SPH-C, AP0181SPH-CMMD-AP0151SH-C, AP0181SH-C

CautionThe fresh air shall be conditioned by heat reclaim ventilator or similar.Ensure the fresh air volume is determined so that mixed suction air and fresh air maintain theoperating temperature.*1.Recommended conditioned air temperature is 12 °C to 30 °C.

However, Make a fresh air volume within 20% of standard.

Install a air filter within the fresh air duct.( Fresh air does not pass through the filter of Indoor unit.)

Insulate the fresh air duct.Electrically connect the fan of the Heat exchanger unit and the Indoor unit to a single isolator.

-10

0

10

20

30

40

50

60

0 20 40 60 80 100 120 140 160 180

Fresh Air Volume (m3/h)

Sta

tic P

ress

ure

(Pa) AP0151

AP0181

Duct fanmotor Fresh Air Volume

Flange Option :TCB-FF101URE

Indoor unit

Inter - lock circuitConnect the driving relay of the duct fan (DC 12V) between 1 and 6 on the indoor P.C. board.(Rated current of the relay for duct fan should be up to 75mA.)After installation, carry out a trial operation to check that the duct fan of the indoor unit start/stopsimultaneously.(Carry out the trial operation following the installation manual of the indoor unit.)

Model name MMD- AP0151SPH AP0181SPHAP0151SPH-C AP0181SPH-CAP0151SH-C AP0181SH-C

Standard air flow (m3/h) 690 780

A-53