PERFORMANCE SUMMARY • UMA # 38
Untitled • SOTANO OFICINAS MANTO
Tuesday, January 21, 2003 Page 1 of 159 Version 3.70 - Released 5/13/2002 - VA01
CS² Air Handler
Model # AHD2 FS 040 V M Insulation (entire unit) 2.00#Quantity 1 Wall thickness 2" (5.08 cm)Environment Indoor Sealed panels Positive pressure only
Notes
- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which isbased on ARI Standard-430.- See individual coil ratings for ARI certification information.- ETL listed & UL 1995 Approved.
A. Section 16C Combination filter/mixing box section
Inlet location(s) Top and back Access panels OneTop dampers Standard Panel hand LeftBack dampers Standard Liners SolidFilter media 2" Pleated 35% eff. Pressure drop (in w.g.) 0.10
B. Section 18 Internal face & bypass short coil section
Coil size Small Liners SolidDrain pan Standard Pressure drop (in w.g.) 0.61Maximum bypass air flow (ft³/min) 2,191
Refer to attached pages for coil performance.
C. Shipping split
D. Section 3 Vertical draw-thru fan section
Fan type Forward curved (alternate) Total static @ Actual (in w.g.) 1.71Internal isolation Spring Brake power @ Actual (HP) 1.53Arrangement #3 Rotations per minute 1,553Motor type High Eff. TEFC Altitude (ft) 0Motor voltage 460V/3/60 Coldest dry bulb temp (°F) 54.0Motor power (HP) 2.00 Coil size LargeMotor hand Left Drain pan StandardDrive 150% HP Adjustable Access panels OneAir flow (ft³/min) 2,280 Panel hand LeftExternal static @ Actual (in w.g.) 1.00 Liners SolidInternal static @ Actual (in w.g.) 0.71
PERFORMANCE SUMMARY • UMA # 38
Untitled • SOTANO OFICINAS MANTO
Tuesday, January 21, 2003 Page 2 of 159 Version 3.70 - Released 5/13/2002 - VA01
Air Handler Coils
Coil Tag Model # Qty Location Footnotes
CoilTotal capacity (MBH)Sensible capacity (MBH)Air PropertiesAir flow (ft³/min)Altitude (ft)Face velocity (ft/min)Air pressure drop (in w.g.)Entering air DB / WB (°F)Leaving air DB / WB (°F)Air properties measured atFluid PropertiesFluidFluid flow rate (gal/min)Fluid velocity (ft/s)Entering fluid temp. (°F)Leaving fluid temp. (°F)Fluid pressure drop (ft w.g.)ConstructionType / tubes in faceFinned height (in)Finned length (in)Face area (ft²)Rows / fin spacing (fins/in)Number of feedsCasing constructionSupply connections (qty@in)Return connections (qty@in)Connection type
#1 5 W H 6 C - 14T x 44 LH Q 1 Section B - Coil A
A. Certified in accordance with the ARIForced-Circulation Air-Cooling and Air-HeatingCoils Certification Program, which is based onARI Standard-410.
B. Fin material - 0.008 Polycoat
A,B
#1102.665.3
2,2800
3340.47
77.2 / 65.850.6 / 50.4
Actual
Water17.02.6
44.056.15.7
5 / 1422.344.06.8
6 / 127
Air handler1@1 1/21@1 1/2
MPT
FAN CURVE • UMA # 38
Untitled • SOTANO OFICINAS MANTO
Tuesday, January 21, 2003 Page 3 of 159 Version 3.70 - Released 5/13/2002 - VA01
Supply Fan Specification
Air handler model AHD2 FS 040 V M Air flow (ft³/min) 2,280Fan type Forward curved (alternate/9-9) Static pressure @ Altitude (in w.g.) 1.71Style Draw-thru Rotations per minute 1,553Inlet vanes No Brake power @ Altitude (HP) 1.53Altitude (ft) 0 Coldest dry bulb (°F) 54.0
Fan Curve
Air flow (ft³/min)
Stat
ic p
ress
ure
@ A
ltitu
de (i
n w
.g.)
Brak
e po
wer
@ A
ltitu
de (H
P)
1,600 2,000 2,400 2,800 3,200 3,600 4,000 4,400
2.00
3.60
1.75
3.20
1.50
2.80
1.25
2.40
1.00
2.00
0.75
1.60
0.50
1.20
0.25
0.80
DRAWING • UMA # 38
Untitled • SOTANO OFICINAS MANTO
Tuesday, January 21, 2003 Page 4 of 159 Version 3.70 - Released 5/13/2002 - VA01
Side
vie
w -
AH
D2
FS 0
40 V
M
Ente
ring
air v
iew
Leav
ing
air v
iew
This
dra
win
g is
not
to s
cale
; it i
s to
be
used
for d
imen
sion
al p
urpo
ses
only
.20.0 in
15.0 in
1.0
in15
.0 in
65.0
in/7
75 lb
Con
tact
fact
ory
for f
an d
imen
sion
als.
37.5
in/1
,057
lb
38.5 in
78.0 in
54.0
in3.
0 in
3.0
in
60.0
in60
.0 in
PERFORMANCE SUMMARY • UMA # 37
Untitled • SOTANO COMEDOR
Tuesday, January 21, 2003 Page 5 of 159 Version 3.70 - Released 5/13/2002 - VA01
CS² Air Handler
Model # AHD2 FS 040 V M Insulation (entire unit) 2.00#Quantity 1 Wall thickness 2" (5.08 cm)Environment Indoor Sealed panels Positive pressure only
Notes
- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which isbased on ARI Standard-430.- See individual coil ratings for ARI certification information.- ETL listed & UL 1995 Approved.
A. Section 16C Combination filter/mixing box section
Inlet location(s) Top and back Access panels OneTop dampers Standard Panel hand LeftBack dampers Standard Liners SolidFilter media 2" Pleated 35% eff. Pressure drop (in w.g.) 0.11
B. Section 18 Internal face & bypass short coil section
Coil size Small Liners SolidDrain pan Standard Pressure drop (in w.g.) 0.89Maximum bypass air flow (ft³/min) 2,191
Refer to attached pages for coil performance.
C. Shipping split
D. Section 3 Vertical draw-thru fan section
Fan type Forward curved (alternate) Total static @ Actual (in w.g.) 2.00Internal isolation Spring Brake power @ Actual (HP) 2.01Arrangement #3 Rotations per minute 1,688Motor type High Eff. TEFC Altitude (ft) 0Motor voltage 460V/3/60 Coldest dry bulb temp (°F) 54.0Motor power (HP) 3.00 Coil size LargeMotor hand Left Drain pan StandardDrive 150% HP Adjustable Access panels OneAir flow (ft³/min) 2,520 Panel hand LeftExternal static @ Actual (in w.g.) 1.00 Liners SolidInternal static @ Actual (in w.g.) 1.00
PERFORMANCE SUMMARY • UMA # 37
Untitled • SOTANO COMEDOR
Tuesday, January 21, 2003 Page 6 of 159 Version 3.70 - Released 5/13/2002 - VA01
Air Handler Coils
Coil Tag Model # Qty Location Footnotes
CoilTotal capacity (MBH)Sensible capacity (MBH)Air PropertiesAir flow (ft³/min)Altitude (ft)Face velocity (ft/min)Air pressure drop (in w.g.)Entering air DB / WB (°F)Leaving air DB / WB (°F)Air properties measured atFluid PropertiesFluidFluid flow rate (gal/min)Fluid velocity (ft/s)Entering fluid temp. (°F)Leaving fluid temp. (°F)Fluid pressure drop (ft w.g.)ConstructionType / tubes in faceFinned height (in)Finned length (in)Face area (ft²)Rows / fin spacing (fins/in)Number of feedsCasing constructionSupply connections (qty@in)Return connections (qty@in)Connection type
#1 5 W P 8 C - 14T x 44 LH 1 Section B - Coil A
A. Certified in accordance with the ARIForced-Circulation Air-Cooling and Air-HeatingCoils Certification Program, which is based onARI Standard-410.
A
#1184.291.4
2,5200
3700.71
82.3 / 72.048.4 / 48.3
Actual
Water35.54.3
44.054.413.6
5 / 1422.344.06.8
8 / 129
Air handler1@1 1/21@1 1/2
MPT
FAN CURVE • UMA # 37
Untitled • SOTANO COMEDOR
Tuesday, January 21, 2003 Page 7 of 159 Version 3.70 - Released 5/13/2002 - VA01
Supply Fan Specification
Air handler model AHD2 FS 040 V M Air flow (ft³/min) 2,520Fan type Forward curved (alternate/9-9) Static pressure @ Altitude (in w.g.) 2.00Style Draw-thru Rotations per minute 1,688Inlet vanes No Brake power @ Altitude (HP) 2.01Altitude (ft) 0 Coldest dry bulb (°F) 54.0
Fan Curve
Air flow (ft³/min)
Stat
ic p
ress
ure
@ A
ltitu
de (i
n w
.g.)
Brak
e po
wer
@ A
ltitu
de (H
P)
1,600 2,000 2,400 2,800 3,200 3,600 4,000 4,400
2.25
4.00
2.00
3.60
1.75
3.20
1.50
2.80
1.25
2.40
1.00
2.00
0.75
1.60
0.50
1.20
DRAWING • UMA # 37
Untitled • SOTANO COMEDOR
Tuesday, January 21, 2003 Page 8 of 159 Version 3.70 - Released 5/13/2002 - VA01
Side
vie
w -
AH
D2
FS 0
40 V
M
Ente
ring
air v
iew
Leav
ing
air v
iew
This
dra
win
g is
not
to s
cale
; it i
s to
be
used
for d
imen
sion
al p
urpo
ses
only
.20.0 in
15.0 in
1.0
in15
.0 in
65.0
in/8
45 lb
Con
tact
fact
ory
for f
an d
imen
sion
als.
37.5
in/1
,084
lb
38.5 in
78.0 in
54.0
in3.
0 in
3.0
in
60.0
in60
.0 in
PERFORMANCE SUMMARY • UMA # 36
Untitled • SOTANO OFICINAS DIETISTA
Tuesday, January 21, 2003 Page 9 of 159 Version 3.70 - Released 5/13/2002 - VA01
CS² Air Handler
Model # AHD2 FS 048 V M Insulation (entire unit) 2.00#Quantity 1 Wall thickness 2" (5.08 cm)Environment Indoor Sealed panels Positive pressure only
Notes
- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which isbased on ARI Standard-430.- See individual coil ratings for ARI certification information.- ETL listed & UL 1995 Approved.
A. Section 16C Combination filter/mixing box section
Inlet location(s) Top and back Access panels OneTop dampers Standard Panel hand LeftBack dampers Standard Liners SolidFilter media 2" Pleated 35% eff. Pressure drop (in w.g.) 0.15
B. Section 18 Internal face & bypass short coil section
Coil size Small Liners SolidDrain pan Standard Pressure drop (in w.g.) 1.12Maximum bypass air flow (ft³/min) 2,689
Refer to attached pages for coil performance.
C. Shipping split
D. Section 3 Vertical draw-thru fan section
Fan type Forward curved (standard) Total static @ Actual (in w.g.) 2.27Internal isolation Spring Brake power @ Actual (HP) 3.15Arrangement #3 Rotations per minute 1,259Motor type High Eff. TEFC Altitude (ft) 0Motor voltage 460V/3/60 Coldest dry bulb temp (°F) 54.0Motor power (HP) 5.00 Coil size LargeMotor hand Left Drain pan StandardDrive 150% HP Adjustable Access panels OneAir flow (ft³/min) 4,040 Panel hand LeftExternal static @ Actual (in w.g.) 1.00 Liners SolidInternal static @ Actual (in w.g.) 1.27
PERFORMANCE SUMMARY • UMA # 36
Untitled • SOTANO OFICINAS DIETISTA
Tuesday, January 21, 2003 Page 10 of 159 Version 3.70 - Released 5/13/2002 - VA01
Air Handler Coils
Coil Tag Model # Qty Location Footnotes
CoilTotal capacity (MBH)Sensible capacity (MBH)Air PropertiesAir flow (ft³/min)Altitude (ft)Face velocity (ft/min)Air pressure drop (in w.g.)Entering air DB / WB (°F)Leaving air DB / WB (°F)Air properties measured atFluid PropertiesFluidFluid flow rate (gal/min)Fluid velocity (ft/s)Entering fluid temp. (°F)Leaving fluid temp. (°F)Fluid pressure drop (ft w.g.)ConstructionType / tubes in faceFinned height (in)Finned length (in)Face area (ft²)Rows / fin spacing (fins/in)Number of feedsCasing constructionSupply connections (qty@in)Return connections (qty@in)Connection type
#1 5 W P 6 C - 14T x 54 LH Q 1 Section B - Coil A
A. Certified in accordance with the ARIForced-Circulation Air-Cooling and Air-HeatingCoils Certification Program, which is based onARI Standard-410.
B. Fin material - 0.008 Polycoat
A,B
#1149.3105.5
4,0400
4830.82
76.4 / 64.752.2 / 52.2
Actual
Water26.12.8
44.055.55.1
5 / 1422.354.08.4
6 / 1210
Air handler1@1 1/21@1 1/2
MPT
FAN CURVE • UMA # 36
Untitled • SOTANO OFICINAS DIETISTA
Tuesday, January 21, 2003 Page 11 of 159 Version 3.70 - Released 5/13/2002 - VA01
Supply Fan Specification
Air handler model AHD2 FS 048 V M Air flow (ft³/min) 4,040Fan type Forward curved (standard/12-12) Static pressure @ Altitude (in w.g.) 2.27Style Draw-thru Rotations per minute 1,259Inlet vanes No Brake power @ Altitude (HP) 3.15Altitude (ft) 0 Coldest dry bulb (°F) 54.0
Fan Curve
Air flow (ft³/min)
Stat
ic p
ress
ure
@ A
ltitu
de (i
n w
.g.)
Brak
e po
wer
@ A
ltitu
de (H
P)
2,400 3,200 4,000 4,800 5,600 6,400 7,200 8,000
2.40
7.20
2.20
6.40
2.00
5.60
1.80
4.80
1.60
4.00
1.40
3.20
1.20
2.40
1.00
1.60
DRAWING • UMA # 36
Untitled • SOTANO OFICINAS DIETISTA
Tuesday, January 21, 2003 Page 12 of 159 Version 3.70 - Released 5/13/2002 - VA01
Side
vie
w -
AH
D2
FS 0
48 V
M
Ente
ring
air v
iew
Leav
ing
air v
iew
This
dra
win
g is
not
to s
cale
; it i
s to
be
used
for d
imen
sion
al p
urpo
ses
only
.20.0 in
15.0 in
1.0
in15
.0 in
65.0
in/8
71 lb
12.4
in13
.6 in
37.5
in/1
,204
lb
38.5 in
80.0 in
64.0
in3.
0 in
3.0
in
70.0
in
26.6
in15
.8 in
70.0
in
PERFORMANCE SUMMARY • UMA # 35
Untitled • P.BAJA AUTOPSIA
Tuesday, January 21, 2003 Page 13 of 159 Version 3.70 - Released 5/13/2002 - VA01
CS² Air Handler
Model # AHD2 FS 080 V M Insulation (entire unit) 2.00#Quantity 1 Wall thickness 2" (5.08 cm)Environment Indoor Sealed panels Positive pressure only
Notes
- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which isbased on ARI Standard-430.- See individual coil ratings for ARI certification information.- ETL listed & UL 1995 Approved.
A. Section 16C Combination filter/mixing box section
Inlet location(s) Top and back Access panels OneTop dampers Standard Panel hand LeftBack dampers Standard Liners SolidFilter media 2" Pleated 35% eff. Pressure drop (in w.g.) 0.14
B. Section 18 Internal face & bypass short coil section
Coil size Small Liners SolidDrain pan Standard Pressure drop (in w.g.) 0.98Maximum bypass air flow (ft³/min) 5,146
Refer to attached pages for coil performance.
C. Shipping split
D. Section 3 Vertical draw-thru fan section
Fan type Forward curved (standard) Total static @ Actual (in w.g.) 2.12Internal isolation Spring (standard) Brake power @ Actual (HP) 4.34Arrangement #3 Rotations per minute 1,014Motor type High Eff. TEFC Altitude (ft) 0Motor voltage 460V/3/60 Coldest dry bulb temp (°F) 54.0Motor power (HP) 5.00 Coil size LargeMotor hand Left Drain pan StandardDrive 150% HP Adjustable Access panels OneAir flow (ft³/min) 5,979 Panel hand LeftExternal static @ Actual (in w.g.) 1.00 Liners SolidInternal static @ Actual (in w.g.) 1.12
PERFORMANCE SUMMARY • UMA # 35
Untitled • P.BAJA AUTOPSIA
Tuesday, January 21, 2003 Page 14 of 159 Version 3.70 - Released 5/13/2002 - VA01
Air Handler Coils
Coil Tag Model # Qty Location Footnotes
CoilTotal capacity (MBH)Sensible capacity (MBH)Air PropertiesAir flow (ft³/min)Altitude (ft)Face velocity (ft/min)Air pressure drop (in w.g.)Entering air DB / WB (°F)Leaving air DB / WB (°F)Air properties measured atFluid PropertiesFluidFluid flow rate (gal/min)Fluid velocity (ft/s)Entering fluid temp. (°F)Leaving fluid temp. (°F)Fluid pressure drop (ft w.g.)ConstructionType / tubes in faceFinned height (in)Finned length (in)Face area (ft²)Rows / fin spacing (fins/in)Number of feedsCasing constructionSupply connections (qty@in)Return connections (qty@in)Connection type
#1 5 W P 5 C - 18T x 62 LH 1 Section B - Coil A
A. Certified in accordance with the ARIForced-Circulation Air-Cooling and Air-HeatingCoils Certification Program, which is based onARI Standard-410.
A
#1231.8152.9
5,9790
4840.68
77.4 / 66.053.7 / 52.9
Actual
Water45.43.3
44.054.25.5
5 / 1828.762.012.4
5 / 1215
Air handler1@1 1/21@1 1/2
MPT
FAN CURVE • UMA # 35
Untitled • P.BAJA AUTOPSIA
Tuesday, January 21, 2003 Page 15 of 159 Version 3.70 - Released 5/13/2002 - VA01
Supply Fan Specification
Air handler model AHD2 FS 080 V M Air flow (ft³/min) 5,979Fan type Forward curved (standard/15-15) Static pressure @ Altitude (in w.g.) 2.12Style Draw-thru Rotations per minute 1,014Inlet vanes No Brake power @ Altitude (HP) 4.34Altitude (ft) 0 Coldest dry bulb (°F) 54.0
Fan Curve
Air flow (ft³/min)
Stat
ic p
ress
ure
@ A
ltitu
de (i
n w
.g.)
Brak
e po
wer
@ A
ltitu
de (H
P)
4,000 4,800 5,600 6,400 7,200 8,000 8,800 9,600
2.50
10.8
0
2.25
9.60
2.00
8.40
1.75
7.20
1.50
6.00
1.25
4.80
1.00
3.60
0.75
2.40
DRAWING • UMA # 35
Untitled • P.BAJA AUTOPSIA
Tuesday, January 21, 2003 Page 16 of 159 Version 3.70 - Released 5/13/2002 - VA01
Side
vie
w -
AH
D2
FS 0
80 V
M
Ente
ring
air v
iew
Leav
ing
air v
iew
This
dra
win
g is
not
to s
cale
; it i
s to
be
used
for d
imen
sion
al p
urpo
ses
only
.26.5 in
21.0 in
2.0
in21
.0 in
69.0
in/1
,190
lb
51.0 in15.8
in16
.0 in
43.5
in/1
,834
lb
51.0 in
90.5 in
72.0
in3.
0 in
3.0
in
78.0
in
37.0
in18
.8 in
78.0
in
PERFORMANCE SUMMARY • UMA # 34
Untitled • P.BAJA CIRCULA Y ESPERA
Tuesday, January 21, 2003 Page 17 of 159 Version 3.70 - Released 5/13/2002 - VA01
CS² Air Handler
Model # AHD2 FS 180 V M Insulation (entire unit) 2.00#Quantity 1 Wall thickness 2" (5.08 cm)Environment Indoor Sealed panels Positive pressure only
Notes
- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which isbased on ARI Standard-430.- See individual coil ratings for ARI certification information.- ETL listed & UL 1995 Approved.
A. Section 10F2 Flat filter section
Filter depth 2" (5.08 cm) Panel hand LeftFilter media Pleated 35% eff. Liners SolidAccess panels One Pressure drop (in w.g.) 0.13
B. Shipping split
C. Section 18 Internal face & bypass short coil section
Coil size Small Liners SolidDrain pan Standard Pressure drop (in w.g.) 0.87Maximum bypass air flow (ft³/min) 11,422
Refer to attached pages for coil performance.
D. Shipping split
E. Section 3 Vertical draw-thru fan section
Fan type Forward curved (standard) Total static @ Actual (in w.g.) 1.99Internal isolation Spring (standard) Brake power @ Actual (HP) 7.91Arrangement #3 Rotations per minute 659Motor type High Eff. TEFC Altitude (ft) 0Motor voltage 460V/3/60 Coldest dry bulb temp (°F) 54.0Motor power (HP) 10.00 Coil size LargeMotor hand Left Drain pan StandardDrive Fixed Access panels OneAir flow (ft³/min) 11,820 Panel hand LeftExternal static @ Actual (in w.g.) 1.00 Liners SolidInternal static @ Actual (in w.g.) 0.99
PERFORMANCE SUMMARY • UMA # 34
Untitled • P.BAJA CIRCULA Y ESPERA
Tuesday, January 21, 2003 Page 18 of 159 Version 3.70 - Released 5/13/2002 - VA01
Air Handler Coils
Coil Tag Model # Qty Location Footnotes
CoilTotal capacity (MBH)Sensible capacity (MBH)Air PropertiesAir flow (ft³/min)Altitude (ft)Face velocity (ft/min)Air pressure drop (in w.g.)Entering air DB / WB (°F)Leaving air DB / WB (°F)Air properties measured atFluid PropertiesFluidFluid flow rate (gal/min)Fluid velocity (ft/s)Entering fluid temp. (°F)Leaving fluid temp. (°F)Fluid pressure drop (ft w.g.)ConstructionType / tubes in faceFinned height (in)Finned length (in)Face area (ft²)Rows / fin spacing (fins/in)Number of feedsCasing constructionSupply connections (qty@in)Return connections (qty@in)Connection type
#1 5 W F 6 C - 30T x 86 LH 1 Section C - Coil A
A. Certified in accordance with the ARIForced-Circulation Air-Cooling and Air-HeatingCoils Certification Program, which is based onARI Standard-410.
A
#1650.1373.2
11,8200
4140.65
80.2 / 68.950.8 / 50.8
Actual
Water120.0
4.344.054.811.4
5 / 3047.886.028.6
6 / 1230
Air handler1@2 1@2 MPT
FAN CURVE • UMA # 34
Untitled • P.BAJA CIRCULA Y ESPERA
Tuesday, January 21, 2003 Page 19 of 159 Version 3.70 - Released 5/13/2002 - VA01
Supply Fan Specification
Air handler model AHD2 FS 180 V M Air flow (ft³/min) 11,820Fan type Forward curved (standard/22-22) Static pressure @ Altitude (in w.g.) 1.99Style Draw-thru Rotations per minute 659Inlet vanes No Brake power @ Altitude (HP) 7.91Altitude (ft) 0 Coldest dry bulb (°F) 54.0
Fan Curve
Air flow (ft³/min)
Stat
ic p
ress
ure
@ A
ltitu
de (i
n w
.g.)
Brak
e po
wer
@ A
ltitu
de (H
P)
8,000 10,000 12,000 14,000 16,000 18,000 20,000 22,000
2.25
20.0
0
2.00
18.0
0
1.75
16.0
0
1.50
14.0
0
1.25
12.0
0
1.00
10.0
0
0.75
8.00
0.50
6.00
DRAWING • UMA # 34
Untitled • P.BAJA CIRCULA Y ESPERA
Tuesday, January 21, 2003 Page 20 of 159 Version 3.70 - Released 5/13/2002 - VA01
Side
vie
w -
AH
D2
FS 1
80 V
M
Ente
ring
air v
iew
Leav
ing
air v
iew
This
dra
win
g is
not
to s
cale
; it i
s to
be
used
for d
imen
sion
al p
urpo
ses
only
.
10.0
in/6
13 lb
32.0
in/1
,546
lb74.0 in17
.8 in
27.4
in
61.8
in/4
,026
lb
74.0 in
146.5 in
104.
0 in
45.4
in27
.4 in
104.
0 in
PERFORMANCE SUMMARY • UMA # 33
Untitled • P.BAJA LABORATORIO
Tuesday, January 21, 2003 Page 21 of 159 Version 3.70 - Released 5/13/2002 - VA01
CS² Air Handler
Model # AHD2 FS 100 V M Insulation (entire unit) 2.00#Quantity 1 Wall thickness 2" (5.08 cm)Environment Indoor Sealed panels Positive pressure only
Notes
- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which isbased on ARI Standard-430.- See individual coil ratings for ARI certification information.- ETL listed & UL 1995 Approved.
A. Section 16C Combination filter/mixing box section
Inlet location(s) Top and back Access panels OneTop dampers Standard Panel hand LeftBack dampers Standard Liners SolidFilter media 2" Pleated 35% eff. Pressure drop (in w.g.) 0.14
B. Section 18 Internal face & bypass short coil section
Coil size Small Liners SolidDrain pan Standard Pressure drop (in w.g.) 0.97Maximum bypass air flow (ft³/min) 6,176
Refer to attached pages for coil performance.
C. Shipping split
D. Section 3 Vertical draw-thru fan section
Fan type Forward curved (standard) Total static @ Actual (in w.g.) 2.11Internal isolation Spring (standard) Brake power @ Actual (HP) 5.27Arrangement #3 Rotations per minute 864Motor type High Eff. TEFC Altitude (ft) 0Motor voltage 460V/3/60 Coldest dry bulb temp (°F) 54.0Motor power (HP) 7.50 Coil size LargeMotor hand Left Drain pan StandardDrive 150% HP Adjustable Access panels OneAir flow (ft³/min) 7,259 Panel hand LeftExternal static @ Actual (in w.g.) 1.00 Liners SolidInternal static @ Actual (in w.g.) 1.11
PERFORMANCE SUMMARY • UMA # 33
Untitled • P.BAJA LABORATORIO
Tuesday, January 21, 2003 Page 22 of 159 Version 3.70 - Released 5/13/2002 - VA01
Air Handler Coils
Coil Tag Model # Qty Location Footnotes
CoilTotal capacity (MBH)Sensible capacity (MBH)Air PropertiesAir flow (ft³/min)Altitude (ft)Face velocity (ft/min)Air pressure drop (in w.g.)Entering air DB / WB (°F)Leaving air DB / WB (°F)Air properties measured atFluid PropertiesFluidFluid flow rate (gal/min)Fluid velocity (ft/s)Entering fluid temp. (°F)Leaving fluid temp. (°F)Fluid pressure drop (ft w.g.)ConstructionType / tubes in faceFinned height (in)Finned length (in)Face area (ft²)Rows / fin spacing (fins/in)Number of feedsCasing constructionSupply connections (qty@in)Return connections (qty@in)Connection type
#1 5 W P 5 C - 22T x 62 LH Q 1 Section B - Coil A
A. Certified in accordance with the ARIForced-Circulation Air-Cooling and Air-HeatingCoils Certification Program, which is based onARI Standard-410.
B. Fin material - 0.008 Polycoat
A,B
#1288.0189.9
7,2590
4810.67
77.8 / 66.553.5 / 53.4
Actual
Water54.33.3
44.054.65.5
5 / 2235.162.015.1
5 / 1218
Air handler1@1 1/21@1 1/2
MPT
FAN CURVE • UMA # 33
Untitled • P.BAJA LABORATORIO
Tuesday, January 21, 2003 Page 23 of 159 Version 3.70 - Released 5/13/2002 - VA01
Supply Fan Specification
Air handler model AHD2 FS 100 V M Air flow (ft³/min) 7,259Fan type Forward curved (standard/18-18) Static pressure @ Altitude (in w.g.) 2.11Style Draw-thru Rotations per minute 864Inlet vanes No Brake power @ Altitude (HP) 5.27Altitude (ft) 0 Coldest dry bulb (°F) 54.0
Fan Curve
Air flow (ft³/min)
Stat
ic p
ress
ure
@ A
ltitu
de (i
n w
.g.)
Brak
e po
wer
@ A
ltitu
de (H
P)
4,500 6,000 7,500 9,000 10,500 12,000 13,500 15,000
2.40
13.5
0
2.20
12.0
0
2.00
10.5
0
1.80
9.00
1.60
7.50
1.40
6.00
1.20
4.50
1.00
3.00
DRAWING • UMA # 33
Untitled • P.BAJA LABORATORIO
Tuesday, January 21, 2003 Page 24 of 159 Version 3.70 - Released 5/13/2002 - VA01
Side
vie
w -
AH
D2
FS 1
00 V
M
Ente
ring
air v
iew
Leav
ing
air v
iew
This
dra
win
g is
not
to s
cale
; it i
s to
be
used
for d
imen
sion
al p
urpo
ses
only
.28.0 in
26.5 in
2.0
in26
.5 in
73.0
in/1
,334
lb
58.0 in16.4
in19
.0 in
51.0
in/2
,420
lb
58.0 in
114.5 in
72.0
in3.
0 in
3.0
in
78.0
in
36.0
in22
.0 in
78.0
in
PERFORMANCE SUMMARY • UMA # 32
Untitled • P.BAJA DIAGNOSTICO
Tuesday, January 21, 2003 Page 25 of 159 Version 3.70 - Released 5/13/2002 - VA01
CS² Air Handler
Model # AHD2 FS 080 V M Insulation (entire unit) 2.00#Quantity 1 Wall thickness 2" (5.08 cm)Environment Indoor Sealed panels Positive pressure only
Notes
- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which isbased on ARI Standard-430.- See individual coil ratings for ARI certification information.- ETL listed & UL 1995 Approved.
A. Section 16C Combination filter/mixing box section
Inlet location(s) Top and back Access panels OneTop dampers Standard Panel hand LeftBack dampers Standard Liners SolidFilter media 2" Throw away Pressure drop (in w.g.) 0.11
B. Section 18 Internal face & bypass short coil section
Coil size Small Liners SolidDrain pan Standard Pressure drop (in w.g.) 0.90Maximum bypass air flow (ft³/min) 5,146
Refer to attached pages for coil performance.
C. Shipping split
D. Section 3 Vertical draw-thru fan section
Fan type Forward curved (standard) Total static @ Actual (in w.g.) 2.01Internal isolation Spring (standard) Brake power @ Actual (HP) 3.82Arrangement #3 Rotations per minute 982Motor type High Eff. TEFC Altitude (ft) 0Motor voltage 460V/3/60 Coldest dry bulb temp (°F) 54.0Motor power (HP) 5.00 Coil size LargeMotor hand Left Drain pan StandardDrive 150% HP Adjustable Access panels OneAir flow (ft³/min) 5,660 Panel hand LeftExternal static @ Actual (in w.g.) 1.00 Liners SolidInternal static @ Actual (in w.g.) 1.01
PERFORMANCE SUMMARY • UMA # 32
Untitled • P.BAJA DIAGNOSTICO
Tuesday, January 21, 2003 Page 26 of 159 Version 3.70 - Released 5/13/2002 - VA01
Air Handler Coils
Coil Tag Model # Qty Location Footnotes
CoilTotal capacity (MBH)Sensible capacity (MBH)Air PropertiesAir flow (ft³/min)Altitude (ft)Face velocity (ft/min)Air pressure drop (in w.g.)Entering air DB / WB (°F)Leaving air DB / WB (°F)Air properties measured atFluid PropertiesFluidFluid flow rate (gal/min)Fluid velocity (ft/s)Entering fluid temp. (°F)Leaving fluid temp. (°F)Fluid pressure drop (ft w.g.)ConstructionType / tubes in faceFinned height (in)Finned length (in)Face area (ft²)Rows / fin spacing (fins/in)Number of feedsCasing constructionSupply connections (qty@in)Return connections (qty@in)Connection type
#1 5 W H 5 C - 18T x 62 LH 1 Section B - Coil A
A. Certified in accordance with the ARIForced-Circulation Air-Cooling and Air-HeatingCoils Certification Program, which is based onARI Standard-410.
A
#1208.4147.6
5,6600
4580.63
76.0 / 64.251.9 / 51.4
Actual
Water38.14.6
44.054.916.1
5 / 1828.762.012.4
5 / 129
Air handler1@1 1/21@1 1/2
MPT
FAN CURVE • UMA # 32
Untitled • P.BAJA DIAGNOSTICO
Tuesday, January 21, 2003 Page 27 of 159 Version 3.70 - Released 5/13/2002 - VA01
Supply Fan Specification
Air handler model AHD2 FS 080 V M Air flow (ft³/min) 5,660Fan type Forward curved (standard/15-15) Static pressure @ Altitude (in w.g.) 2.01Style Draw-thru Rotations per minute 982Inlet vanes No Brake power @ Altitude (HP) 3.82Altitude (ft) 0 Coldest dry bulb (°F) 54.0
Fan Curve
Air flow (ft³/min)
Stat
ic p
ress
ure
@ A
ltitu
de (i
n w
.g.)
Brak
e po
wer
@ A
ltitu
de (H
P)
4,000 4,800 5,600 6,400 7,200 8,000 8,800 9,600
2.20
9.00
2.00
8.00
1.80
7.00
1.60
6.00
1.40
5.00
1.20
4.00
1.00
3.00
0.80
2.00
DRAWING • UMA # 32
Untitled • P.BAJA DIAGNOSTICO
Tuesday, January 21, 2003 Page 28 of 159 Version 3.70 - Released 5/13/2002 - VA01
Side
vie
w -
AH
D2
FS 0
80 V
M
Ente
ring
air v
iew
Leav
ing
air v
iew
This
dra
win
g is
not
to s
cale
; it i
s to
be
used
for d
imen
sion
al p
urpo
ses
only
.26.5 in
21.0 in
2.0
in21
.0 in
69.0
in/1
,190
lb
51.0 in15.8
in16
.0 in
43.5
in/1
,834
lb
51.0 in
90.5 in
72.0
in3.
0 in
3.0
in
78.0
in
37.0
in18
.8 in
78.0
in
PERFORMANCE SUMMARY • UMA # 31
Untitled • P.BAJA URGENCIA
Tuesday, January 21, 2003 Page 29 of 159 Version 3.70 - Released 5/13/2002 - VA01
CS² Air Handler
Model # AHD2 FS 240 V M Insulation (entire unit) 2.00#Quantity 1 Wall thickness 2" (5.08 cm)Environment Indoor Sealed panels Positive pressure only
Notes
- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which isbased on ARI Standard-430.- See individual coil ratings for ARI certification information.- ETL listed & UL 1995 Approved.
A. Section 16C Combination filter/mixing box section
Inlet location(s) Top and back Access panels OneTop dampers Standard Panel hand LeftBack dampers Standard Liners SolidFilter media 2" Pleated 35% eff. Pressure drop (in w.g.) 0.11
B. Shipping split
C. Section 18 Internal face & bypass short coil section
Coil size Small Liners SolidDrain pan Standard Pressure drop (in w.g.) 0.73Maximum bypass air flow (ft³/min) 14,078
Refer to attached pages for coil performance.
D. Shipping split
E. Section 3 Vertical draw-thru fan section
Fan type Forward curved (standard) Total static @ Actual (in w.g.) 1.94Internal isolation Spring (standard) Brake power @ Actual (HP) 8.79Arrangement #3 Rotations per minute 553Motor type High Eff. TEFC Altitude (ft) 0Motor voltage 460V/3/60 Coldest dry bulb temp (°F) 54.0Motor power (HP) 15.00 Coil size LargeMotor hand Left Drain pan StandardDrive 150% HP Adjustable Access panels OneAir flow (ft³/min) 14,849 Panel hand LeftExternal static @ Actual (in w.g.) 1.10 Liners SolidInternal static @ Actual (in w.g.) 0.84
PERFORMANCE SUMMARY • UMA # 31
Untitled • P.BAJA URGENCIA
Tuesday, January 21, 2003 Page 30 of 159 Version 3.70 - Released 5/13/2002 - VA01
Air Handler Coils
Coil Tag Model # Qty Location Footnotes
CoilTotal capacity (MBH)Sensible capacity (MBH)Air PropertiesAir flow (ft³/min)Altitude (ft)Face velocity (ft/min)Air pressure drop (in w.g.)Entering air DB / WB (°F)Leaving air DB / WB (°F)Air properties measured atFluid PropertiesFluidFluid flow rate (gal/min)Fluid velocity (ft/s)Entering fluid temp. (°F)Leaving fluid temp. (°F)Fluid pressure drop (ft w.g.)ConstructionType / tubes in faceFinned height (in)Finned length (in)Face area (ft²)Rows / fin spacing (fins/in)Number of feedsCasing constructionSupply connections (qty@in)Return connections (qty@in)Connection type
#1 5 W F 6 C - 34T x 106 LH 1 Section C - Coil A
A. Certified in accordance with the ARIForced-Circulation Air-Cooling and Air-HeatingCoils Certification Program, which is based onARI Standard-410.
A
#1757.9448.4
14,8490
3720.55
78.6 / 67.550.5 / 50.5
Actual
Water126.3
4.044.056.011.6
5 / 3454.2
106.039.9
6 / 1234
Air handler1@2 1@2 MPT
FAN CURVE • UMA # 31
Untitled • P.BAJA URGENCIA
Tuesday, January 21, 2003 Page 31 of 159 Version 3.70 - Released 5/13/2002 - VA01
Supply Fan Specification
Air handler model AHD2 FS 240 V M Air flow (ft³/min) 14,849Fan type Forward curved (standard/25-25) Static pressure @ Altitude (in w.g.) 1.94Style Draw-thru Rotations per minute 553Inlet vanes No Brake power @ Altitude (HP) 8.79Altitude (ft) 0 Coldest dry bulb (°F) 54.0
Fan Curve
Air flow (ft³/min)
Stat
ic p
ress
ure
@ A
ltitu
de (i
n w
.g.)
Brak
e po
wer
@ A
ltitu
de (H
P)
12,500 15,000 17,500 20,000 22,500 25,000 27,500 30,000
2.20
25.0
0
2.00
22.5
0
1.80
20.0
0
1.60
17.5
0
1.40
15.0
0
1.20
12.5
0
1.00
10.0
0
0.80
7.50
DRAWING • UMA # 31
Untitled • P.BAJA URGENCIA
Tuesday, January 21, 2003 Page 32 of 159 Version 3.70 - Released 5/13/2002 - VA01
Side
vie
w -
AH
D2
FS 2
40 V
M
Ente
ring
air v
iew
Leav
ing
air v
iew
This
dra
win
g is
not
to s
cale
; it i
s to
be
used
for d
imen
sion
al p
urpo
ses
only
.
40.0 in
38.0 in
2.0
in38
.0 in
49.0
in/1
,103
lb34
.0 in
/1,9
73 lb
82.5 in18.4
in31
.3 in
70.0
in/4
,845
lb
82.5 in
162.5 in
116.
0 in
3.0
in3.
0 in
122.
0 in
45.4
in31
.3 in
122.
0 in
PERFORMANCE SUMMARY • UMA # 30
Untitled • P.BAJA QQUIROFANO 1-4
Tuesday, January 21, 2003 Page 33 of 159 Version 3.70 - Released 5/13/2002 - VA01
CS² Air Handler
Model # AHD2 FS 064 H M Insulation (entire unit) 2.00#Quantity 1 Wall thickness 2" (5.08 cm)Environment Indoor Sealed panels Positive pressure only
Notes
- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which isbased on ARI Standard-430.- See individual coil ratings for ARI certification information.- ETL listed & UL 1995 Approved.
A. Section 16C Combination filter/mixing box section
Inlet location(s) Top and back Access panels OneTop dampers Standard Panel hand LeftBack dampers Standard Liners SolidFilter media 2" Pleated 35% eff. Pressure drop (in w.g.) 0.17
B. Section 13 Cartridge/bag
Filter depth 12" (30.48 cm) Panel hand LeftFilter media Supplied by other Liners SolidAccess panels One
C. Section 7 Short cooling coil section
Coil size Large Liners SolidDrain pan Standard Pressure drop (in w.g.) 0.68
Refer to attached pages for coil performance.
D. Section 2 Horizontal blow-thru fan section
Fan type Forward curved (standard) Internal static @ Actual (in w.g.) 1.03Internal isolation Spring (standard) Total static @ Actual (in w.g.) 3.53Arrangement #3 Brake power @ Actual (HP) 6.88Motor type High Eff. TEFC Rotations per minute 1,288Motor voltage 460V/3/60 Altitude (ft) 0Motor power (HP) 10.00 Coldest dry bulb temp (°F) 54.0Motor hand Left Access panels OneDrive Fixed Panel hand LeftAir flow (ft³/min) 5,900 Liners SolidExternal static @ Actual (in w.g.) 2.50
E. Shipping split
PERFORMANCE SUMMARY • UMA # 30
Untitled • P.BAJA QQUIROFANO 1-4
Tuesday, January 21, 2003 Page 34 of 159 Version 3.70 - Released 5/13/2002 - VA01
F. Section 27 Diffuser section
Liners Solid Pressure drop (in w.g.) 0.19
G. Section 13 Cartridge/bag
Filter depth 12" (30.48 cm) Panel hand LeftFilter media Supplied by other Liners SolidAccess panels One
PERFORMANCE SUMMARY • UMA # 30
Untitled • P.BAJA QQUIROFANO 1-4
Tuesday, January 21, 2003 Page 35 of 159 Version 3.70 - Released 5/13/2002 - VA01
Air Handler Coils
Coil Tag Model # Qty Location Footnotes
CoilTotal capacity (MBH)Sensible capacity (MBH)Air PropertiesAir flow (ft³/min)Altitude (ft)Face velocity (ft/min)Air pressure drop (in w.g.)Entering air DB / WB (°F)Leaving air DB / WB (°F)Air properties measured atFluid PropertiesFluidFluid flow rate (gal/min)Fluid velocity (ft/s)Entering fluid temp. (°F)Leaving fluid temp. (°F)Fluid pressure drop (ft w.g.)ConstructionType / tubes in faceFinned height (in)Finned length (in)Face area (ft²)Rows / fin spacing (fins/in)Number of feedsCasing constructionSupply connections (qty@in)Return connections (qty@in)Connection type
#1 5 W P 8 A - 21T x 60 LH 1 Section C - Coil A
A. Certified in accordance with the ARIForced-Circulation Air-Cooling and Air-HeatingCoils Certification Program, which is based onARI Standard-410.
A
#1239.2158.6
5,9000
4230.68
74.8 / 64.050.0 / 50.0
Actual
Water47.63.7
44.054.112.8
5 / 2133.560.013.98 / 8
14Air handler
1@1 1/21@1 1/2
MPT
FAN CURVE • UMA # 30
Untitled • P.BAJA QQUIROFANO 1-4
Tuesday, January 21, 2003 Page 36 of 159 Version 3.70 - Released 5/13/2002 - VA01
Supply Fan Specification
Air handler model AHD2 FS 064 H M Air flow (ft³/min) 5,900Fan type Forward curved (standard/15-11) Static pressure @ Altitude (in w.g.) 3.53Style Blow-thru Rotations per minute 1,288Inlet vanes No Brake power @ Altitude (HP) 6.87Altitude (ft) 0 Coldest dry bulb (°F) 54.0
Fan Curve
Air flow (ft³/min)
Stat
ic p
ress
ure
@ A
ltitu
de (i
n w
.g.)
Brak
e po
wer
@ A
ltitu
de (H
P)
4,000 5,000 6,000 7,000 8,000 9,000 10,000 11,000
4.00
18.0
0
3.60
16.0
0
3.20
14.0
0
2.80
12.0
0
2.40
10.0
0
2.00
8.00
1.60
6.00
1.20
4.00
DRAWING • UMA # 30
Untitled • P.BAJA QQUIROFANO 1-4
Tuesday, January 21, 2003 Page 37 of 159 Version 3.70 - Released 5/13/2002 - VA01
Side
vie
w -
AH
D2
FS 0
64 H
M
Ente
ring
air v
iew
Leav
ing
air v
iew
This
dra
win
g is
not
to s
cale
; it i
s to
be
used
for d
imen
sion
al p
urpo
ses
only
.
20.5 in21.0 in
2.0
in21
.0 in
134.
5 in
/2,3
57 lb
52.0
in/5
63 lb
45.0 in
45.0 in
70.0
in3.
0 in
3.0
in
76.0
in76
.0 in
PERFORMANCE SUMMARY • UMA # 29
Untitled • P.BAJA RECOBRO
Tuesday, January 21, 2003 Page 38 of 159 Version 3.70 - Released 5/13/2002 - VA01
CS² Air Handler
Model # AHD2 FS 150 V M Insulation (entire unit) 2.00#Quantity 1 Wall thickness 2" (5.08 cm)Environment Indoor Sealed panels Positive pressure only
Notes
- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which isbased on ARI Standard-430.- See individual coil ratings for ARI certification information.- ETL listed & UL 1995 Approved.
A. Section 16C Combination filter/mixing box section
Inlet location(s) Top and back Access panels OneTop dampers Standard Panel hand LeftBack dampers Standard Liners SolidFilter media 2" Pleated 35% eff. Pressure drop (in w.g.) 0.13
B. Section 18 Internal face & bypass short coil section
Coil size Small Liners SolidDrain pan Standard Pressure drop (in w.g.) 0.81Maximum bypass air flow (ft³/min) 10,094
Refer to attached pages for coil performance.
C. Shipping split
D. Section 3 Vertical draw-thru fan section
Fan type Forward curved (standard) Total static @ Actual (in w.g.) 2.94Internal isolation Spring (standard) Brake power @ Actual (HP) 9.08Arrangement #3 Rotations per minute 785Motor type High Eff. TEFC Altitude (ft) 0Motor voltage 460V/3/60 Coldest dry bulb temp (°F) 54.0Motor power (HP) 10.00 Coil size LargeMotor hand Left Drain pan StandardDrive 150% HP Adjustable Access panels OneAir flow (ft³/min) 10,170 Panel hand LeftExternal static @ Actual (in w.g.) 2.00 Liners SolidInternal static @ Actual (in w.g.) 0.94
PERFORMANCE SUMMARY • UMA # 29
Untitled • P.BAJA RECOBRO
Tuesday, January 21, 2003 Page 39 of 159 Version 3.70 - Released 5/13/2002 - VA01
Air Handler Coils
Coil Tag Model # Qty Location Footnotes
CoilTotal capacity (MBH)Sensible capacity (MBH)Air PropertiesAir flow (ft³/min)Altitude (ft)Face velocity (ft/min)Air pressure drop (in w.g.)Entering air DB / WB (°F)Leaving air DB / WB (°F)Air properties measured atFluid PropertiesFluidFluid flow rate (gal/min)Fluid velocity (ft/s)Entering fluid temp. (°F)Leaving fluid temp. (°F)Fluid pressure drop (ft w.g.)ConstructionType / tubes in faceFinned height (in)Finned length (in)Face area (ft²)Rows / fin spacing (fins/in)Number of feedsCasing constructionSupply connections (qty@in)Return connections (qty@in)Connection type
#1 5 W P 5 C - 28T x 76 LH 1 Section B - Coil A
A. Certified in accordance with the ARIForced-Circulation Air-Cooling and Air-HeatingCoils Certification Program, which is based onARI Standard-410.
A
#1396.9267.9
10,1700
4320.57
77.1 / 65.652.7 / 52.6
Actual
Water72.03.4
44.055.06.7
5 / 2844.676.023.6
5 / 1223
Air handler1@1 1/21@1 1/2
MPT
FAN CURVE • UMA # 29
Untitled • P.BAJA RECOBRO
Tuesday, January 21, 2003 Page 40 of 159 Version 3.70 - Released 5/13/2002 - VA01
Supply Fan Specification
Air handler model AHD2 FS 150 V M Air flow (ft³/min) 10,170Fan type Forward curved (standard/22-15) Static pressure @ Altitude (in w.g.) 2.94Style Draw-thru Rotations per minute 785Inlet vanes No Brake power @ Altitude (HP) 9.08Altitude (ft) 0 Coldest dry bulb (°F) 54.0
Fan Curve
Air flow (ft³/min)
Stat
ic p
ress
ure
@ A
ltitu
de (i
n w
.g.)
Brak
e po
wer
@ A
ltitu
de (H
P)
9,000 10,500 12,000 13,500 15,000 16,500 18,000 19,500
3.00
25.0
0
2.70
22.5
0
2.40
20.0
0
2.10
17.5
0
1.80
15.0
0
1.50
12.5
0
1.20
10.0
0
0.90
7.50
DRAWING • UMA # 29
Untitled • P.BAJA RECOBRO
Tuesday, January 21, 2003 Page 41 of 159 Version 3.70 - Released 5/13/2002 - VA01
Side
vie
w -
AH
D2
FS 1
50 V
M
Ente
ring
air v
iew
Leav
ing
air v
iew
This
dra
win
g is
not
to s
cale
; it i
s to
be
used
for d
imen
sion
al p
urpo
ses
only
.42.0 in
26.5 in
2.0
in26
.5 in
77.0
in/1
,967
lb
72.0 in16.5
in27
.4 in
56.0
in/3
,162
lb
72.0 in
142.5 in
88.0
in3.
0 in
3.0
in
94.0
in
39.0
in20
.4 in
94.0
in
PERFORMANCE SUMMARY • UMA # 28
Untitled • P.BAJA QUIROFANO ORTOP.
Tuesday, January 21, 2003 Page 42 of 159 Version 3.70 - Released 5/13/2002 - VA01
CS² Air Handler
Model # AHD2 FS 040 H M Insulation (entire unit) 2.00#Quantity 1 Wall thickness 2" (5.08 cm)Environment Indoor Sealed panels Positive pressure only
Notes
- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which isbased on ARI Standard-430.- See individual coil ratings for ARI certification information.- ETL listed & UL 1995 Approved.
A. Section 16C Combination filter/mixing box section
Inlet location(s) Top and back Access panels OneTop dampers Standard Panel hand LeftBack dampers Standard Liners SolidFilter media 2" Pleated 35% eff. Pressure drop (in w.g.) 0.24
B. Section 13 Cartridge/bag
Filter depth 12" (30.48 cm) Panel hand LeftFilter media Supplied by other Liners SolidAccess panels One
C. Section 7 Short cooling coil section
Coil size Large Liners SolidDrain pan Standard Pressure drop (in w.g.) 1.15
Refer to attached pages for coil performance.
D. Section 2 Horizontal blow-thru fan section
Fan type Forward curved (standard) Internal static @ Actual (in w.g.) 1.64Internal isolation Spring Total static @ Actual (in w.g.) 4.14Arrangement #3 Brake power @ Actual (HP) 5.16Motor type High Eff. TEFC Rotations per minute 1,664Motor voltage 460V/3/60 Altitude (ft) 0Motor power (HP) 10.00 Coldest dry bulb temp (°F) 54.0Motor hand Left Access panels OneDrive Fixed Panel hand LeftAir flow (ft³/min) 4,120 Liners SolidExternal static @ Actual (in w.g.) 2.50
E. Shipping split
PERFORMANCE SUMMARY • UMA # 28
Untitled • P.BAJA QUIROFANO ORTOP.
Tuesday, January 21, 2003 Page 43 of 159 Version 3.70 - Released 5/13/2002 - VA01
F. Section 27 Diffuser section
Liners Solid Pressure drop (in w.g.) 0.26
G. Section 13 Cartridge/bag
Filter depth 12" (30.48 cm) Panel hand LeftFilter media Supplied by other Liners SolidAccess panels One
PERFORMANCE SUMMARY • UMA # 28
Untitled • P.BAJA QUIROFANO ORTOP.
Tuesday, January 21, 2003 Page 44 of 159 Version 3.70 - Released 5/13/2002 - VA01
Air Handler Coils
Coil Tag Model # Qty Location Footnotes
CoilTotal capacity (MBH)Sensible capacity (MBH)Air PropertiesAir flow (ft³/min)Altitude (ft)Face velocity (ft/min)Air pressure drop (in w.g.)Entering air DB / WB (°F)Leaving air DB / WB (°F)Air properties measured atFluid PropertiesFluidFluid flow rate (gal/min)Fluid velocity (ft/s)Entering fluid temp. (°F)Leaving fluid temp. (°F)Fluid pressure drop (ft w.g.)ConstructionType / tubes in faceFinned height (in)Finned length (in)Face area (ft²)Rows / fin spacing (fins/in)Number of feedsCasing constructionSupply connections (qty@in)Return connections (qty@in)Connection type
#1 5 W H 8 C - 17T x 44 LH 1 Section C - Coil A
A. Certified in accordance with the ARIForced-Circulation Air-Cooling and Air-HeatingCoils Certification Program, which is based onARI Standard-410.
A
#1173.4114.3
4,1200
4981.15
74.5 / 63.848.9 / 48.8
Actual
Water32.64.4
44.054.619.0
5 / 1727.144.08.3
8 / 128
Air handler1@1 1/21@1 1/2
MPT
FAN CURVE • UMA # 28
Untitled • P.BAJA QUIROFANO ORTOP.
Tuesday, January 21, 2003 Page 45 of 159 Version 3.70 - Released 5/13/2002 - VA01
Supply Fan Specification
Air handler model AHD2 FS 040 H M Air flow (ft³/min) 4,120Fan type Forward curved (standard/12-12) Static pressure @ Altitude (in w.g.) 4.14Style Blow-thru Rotations per minute 1,664Inlet vanes No Brake power @ Altitude (HP) 5.16Altitude (ft) 0 Coldest dry bulb (°F) 54.0
Fan Curve
Air flow (ft³/min)
Stat
ic p
ress
ure
@ A
ltitu
de (i
n w
.g.)
Brak
e po
wer
@ A
ltitu
de (H
P)
3,200 4,000 4,800 5,600 6,400 7,200 8,000 8,800
4.50
15.0
0
4.20
13.5
0
3.90
12.0
0
3.60
10.5
0
3.30
9.00
3.00
7.50
2.70
6.00
2.40
4.50
DRAWING • UMA # 28
Untitled • P.BAJA QUIROFANO ORTOP.
Tuesday, January 21, 2003 Page 46 of 159 Version 3.70 - Released 5/13/2002 - VA01
Side
vie
w -
AH
D2
FS 0
40 H
M
Ente
ring
air v
iew
Leav
ing
air v
iew
This
dra
win
g is
not
to s
cale
; it i
s to
be
used
for d
imen
sion
al p
urpo
ses
only
.
23.5 in15.0 in
1.0
in15
.0 in
124.
5 in
/1,9
60 lb
52.0
in/4
79 lb
42.0 in
42.0 in
54.0
in3.
0 in
3.0
in
60.0
in60
.0 in
PERFORMANCE SUMMARY • UMA # 27
Untitled • P.BAJA QUIROF. 5
Tuesday, January 21, 2003 Page 47 of 159 Version 3.70 - Released 5/13/2002 - VA01
CS² Air Handler
Model # AHD2 FS 048 H M Insulation (entire unit) 2.00#Quantity 1 Wall thickness 2" (5.08 cm)Environment Indoor Sealed panels Positive pressure only
Notes
- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which isbased on ARI Standard-430.- See individual coil ratings for ARI certification information.- ETL listed & UL 1995 Approved.
A. Section 16C Combination filter/mixing box section
Inlet location(s) Top and back Access panels OneTop dampers Standard Panel hand LeftBack dampers Standard Liners SolidFilter media 2" Pleated 35% eff. Pressure drop (in w.g.) 0.18
B. Section 13 Cartridge/bag
Filter depth 12" (30.48 cm) Panel hand LeftFilter media Supplied by other Liners SolidAccess panels One
C. Section 7 Short cooling coil section
Coil size Large Liners SolidDrain pan Standard Pressure drop (in w.g.) 0.86
Refer to attached pages for coil performance.
D. Section 2 Horizontal blow-thru fan section
Fan type Forward curved (standard) Internal static @ Actual (in w.g.) 1.25Internal isolation Spring Total static @ Actual (in w.g.) 3.75Arrangement #3 Brake power @ Actual (HP) 5.46Motor type High Eff. TEFC Rotations per minute 1,595Motor voltage 460V/3/60 Altitude (ft) 0Motor power (HP) 10.00 Coldest dry bulb temp (°F) 54.0Motor hand Left Access panels OneDrive 150% HP Adjustable Panel hand LeftAir flow (ft³/min) 4,550 Liners SolidExternal static @ Actual (in w.g.) 2.50
E. Shipping split
PERFORMANCE SUMMARY • UMA # 27
Untitled • P.BAJA QUIROF. 5
Tuesday, January 21, 2003 Page 48 of 159 Version 3.70 - Released 5/13/2002 - VA01
F. Section 27 Diffuser section
Liners Solid Pressure drop (in w.g.) 0.21
G. Section 13 Cartridge/bag
Filter depth 12" (30.48 cm) Panel hand LeftFilter media Supplied by other Liners SolidAccess panels One
PERFORMANCE SUMMARY • UMA # 27
Untitled • P.BAJA QUIROF. 5
Tuesday, January 21, 2003 Page 49 of 159 Version 3.70 - Released 5/13/2002 - VA01
Air Handler Coils
Coil Tag Model # Qty Location Footnotes
CoilTotal capacity (MBH)Sensible capacity (MBH)Air PropertiesAir flow (ft³/min)Altitude (ft)Face velocity (ft/min)Air pressure drop (in w.g.)Entering air DB / WB (°F)Leaving air DB / WB (°F)Air properties measured atFluid PropertiesFluidFluid flow rate (gal/min)Fluid velocity (ft/s)Entering fluid temp. (°F)Leaving fluid temp. (°F)Fluid pressure drop (ft w.g.)ConstructionType / tubes in faceFinned height (in)Finned length (in)Face area (ft²)Rows / fin spacing (fins/in)Number of feedsCasing constructionSupply connections (qty@in)Return connections (qty@in)Connection type
#1 5 W P 8 B - 17T x 54 LH 1 Section C - Coil A
A. Certified in accordance with the ARIForced-Circulation Air-Cooling and Air-HeatingCoils Certification Program, which is based onARI Standard-410.
A
#1203.2128.9
4,5500
4480.86
75.5 / 64.949.3 / 49.3
Actual
Water39.63.9
44.054.313.2
5 / 1727.154.010.2
8 / 1011
Air handler1@1 1/21@1 1/2
MPT
FAN CURVE • UMA # 27
Untitled • P.BAJA QUIROF. 5
Tuesday, January 21, 2003 Page 50 of 159 Version 3.70 - Released 5/13/2002 - VA01
Supply Fan Specification
Air handler model AHD2 FS 048 H M Air flow (ft³/min) 4,550Fan type Forward curved (standard/12-12) Static pressure @ Altitude (in w.g.) 3.75Style Blow-thru Rotations per minute 1,595Inlet vanes No Brake power @ Altitude (HP) 5.46Altitude (ft) 0 Coldest dry bulb (°F) 54.0
Fan Curve
Air flow (ft³/min)
Stat
ic p
ress
ure
@ A
ltitu
de (i
n w
.g.)
Brak
e po
wer
@ A
ltitu
de (H
P)
3,200 4,000 4,800 5,600 6,400 7,200 8,000 8,800
4.00
18.0
0
3.60
16.0
0
3.20
14.0
0
2.80
12.0
0
2.40
10.0
0
2.00
8.00
1.60
6.00
1.20
4.00
DRAWING • UMA # 27
Untitled • P.BAJA QUIROF. 5
Tuesday, January 21, 2003 Page 51 of 159 Version 3.70 - Released 5/13/2002 - VA01
Side
vie
w -
AH
D2
FS 0
48 H
M
Ente
ring
air v
iew
Leav
ing
air v
iew
This
dra
win
g is
not
to s
cale
; it i
s to
be
used
for d
imen
sion
al p
urpo
ses
only
.
25.5 in15.0 in
1.0
in15
.0 in
124.
5 in
/2,0
74 lb
52.0
in/5
34 lb
44.0 in
44.0 in
64.0
in3.
0 in
3.0
in
70.0
in70
.0 in
PERFORMANCE SUMMARY • UMA # 26
Untitled • P.BAJA ESTERILIZACION
Tuesday, January 21, 2003 Page 52 of 159 Version 3.70 - Released 5/13/2002 - VA01
CS² Air Handler
Model # AHD2 FS 040 V M Insulation (entire unit) 2.00#Quantity 1 Wall thickness 2" (5.08 cm)Environment Indoor Sealed panels Positive pressure only
Notes
- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which isbased on ARI Standard-430.- See individual coil ratings for ARI certification information.- ETL listed & UL 1995 Approved.
A. Section 16C Combination filter/mixing box section
Inlet location(s) Top and back Access panels OneTop dampers Standard Panel hand LeftBack dampers Standard Liners SolidFilter media 2" Pleated 35% eff. Pressure drop (in w.g.) 0.14
B. Section 18 Internal face & bypass short coil section
Coil size Small Liners SolidDrain pan Standard Pressure drop (in w.g.) 0.84Maximum bypass air flow (ft³/min) 2,191
Refer to attached pages for coil performance.
C. Shipping split
D. Section 3 Vertical draw-thru fan section
Fan type Forward curved (standard) Total static @ Actual (in w.g.) 1.98Internal isolation Spring Brake power @ Actual (HP) 1.83Arrangement #3 Rotations per minute 1,153Motor type High Eff. TEFC Altitude (ft) 0Motor voltage 460V/3/60 Coldest dry bulb temp (°F) 54.0Motor power (HP) 3.00 Coil size LargeMotor hand Left Drain pan StandardDrive 150% HP Adjustable Access panels OneAir flow (ft³/min) 3,000 Panel hand LeftExternal static @ Actual (in w.g.) 1.00 Liners SolidInternal static @ Actual (in w.g.) 0.98
PERFORMANCE SUMMARY • UMA # 26
Untitled • P.BAJA ESTERILIZACION
Tuesday, January 21, 2003 Page 53 of 159 Version 3.70 - Released 5/13/2002 - VA01
Air Handler Coils
Coil Tag Model # Qty Location Footnotes
CoilTotal capacity (MBH)Sensible capacity (MBH)Air PropertiesAir flow (ft³/min)Altitude (ft)Face velocity (ft/min)Air pressure drop (in w.g.)Entering air DB / WB (°F)Leaving air DB / WB (°F)Air properties measured atFluid PropertiesFluidFluid flow rate (gal/min)Fluid velocity (ft/s)Entering fluid temp. (°F)Leaving fluid temp. (°F)Fluid pressure drop (ft w.g.)ConstructionType / tubes in faceFinned height (in)Finned length (in)Face area (ft²)Rows / fin spacing (fins/in)Number of feedsCasing constructionSupply connections (qty@in)Return connections (qty@in)Connection type
#1 5 W H 5 C - 14T x 44 LH 1 Section B - Coil A
A. Certified in accordance with the ARIForced-Circulation Air-Cooling and Air-HeatingCoils Certification Program, which is based onARI Standard-410.
A
#1128.782.5
3,0000
4400.59
77.7 / 66.452.2 / 52.1
Actual
Water25.74.0
44.054.010.0
5 / 1422.344.06.8
5 / 127
Air handler1@1 1/21@1 1/2
MPT
FAN CURVE • UMA # 26
Untitled • P.BAJA ESTERILIZACION
Tuesday, January 21, 2003 Page 54 of 159 Version 3.70 - Released 5/13/2002 - VA01
Supply Fan Specification
Air handler model AHD2 FS 040 V M Air flow (ft³/min) 3,000Fan type Forward curved (standard/12-12) Static pressure @ Altitude (in w.g.) 1.98Style Draw-thru Rotations per minute 1,153Inlet vanes No Brake power @ Altitude (HP) 1.83Altitude (ft) 0 Coldest dry bulb (°F) 54.0
Fan Curve
Air flow (ft³/min)
Stat
ic p
ress
ure
@ A
ltitu
de (i
n w
.g.)
Brak
e po
wer
@ A
ltitu
de (H
P)
2,500 3,000 3,500 4,000 4,500 5,000 5,500 6,000
2.10
5.00
1.95
4.50
1.80
4.00
1.65
3.50
1.50
3.00
1.35
2.50
1.20
2.00
1.05
1.50
DRAWING • UMA # 26
Untitled • P.BAJA ESTERILIZACION
Tuesday, January 21, 2003 Page 55 of 159 Version 3.70 - Released 5/13/2002 - VA01
Side
vie
w -
AH
D2
FS 0
40 V
M
Ente
ring
air v
iew
Leav
ing
air v
iew
This
dra
win
g is
not
to s
cale
; it i
s to
be
used
for d
imen
sion
al p
urpo
ses
only
.20.0 in
15.0 in
1.0
in15
.0 in
65.0
in/7
40 lb
12.4
in13
.6 in
37.5
in/1
,084
lb
38.5 in
78.0 in
54.0
in3.
0 in
3.0
in
60.0
in
25.6
in15
.8 in
60.0
in
PERFORMANCE SUMMARY • UMA # 25
Untitled • P.BAJA LABOR EXPULSION
Tuesday, January 21, 2003 Page 56 of 159 Version 3.70 - Released 5/13/2002 - VA01
CS² Air Handler
Model # AHD2 AF 120 V M Insulation (entire unit) 2.00#Quantity 1 Wall thickness 2" (5.08 cm)Environment Indoor Sealed panels Positive pressure only
Notes
- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which isbased on ARI Standard-430.- See individual coil ratings for ARI certification information.- ETL listed & UL 1995 Approved.
A. Section 16C Combination filter/mixing box section
Inlet location(s) Top and back Access panels OneTop dampers Standard Panel hand LeftBack dampers Standard Liners SolidFilter media 2" Pleated 35% eff. Pressure drop (in w.g.) 0.13
B. Section 13 Cartridge/bag
Filter depth 12" (30.48 cm) Panel hand LeftFilter media Supplied by other Liners SolidAccess panels One
C. Shipping split
D. Section 18 Internal face & bypass short coil section
Coil size Small Liners SolidDrain pan Standard Pressure drop (in w.g.) 0.96Maximum bypass air flow (ft³/min) 7,570
Refer to attached pages for coil performance.
E. Shipping split
PERFORMANCE SUMMARY • UMA # 25
Untitled • P.BAJA LABOR EXPULSION
Tuesday, January 21, 2003 Page 57 of 159 Version 3.70 - Released 5/13/2002 - VA01
F. Section 3 Vertical draw-thru fan section
Fan type Airfoil (standard) Total static @ Actual (in w.g.) 3.59Internal isolation Spring (standard) Brake power @ Actual (HP) 7.54Arrangement #3 Rotations per minute 1,894Motor type High Eff. TEFC Altitude (ft) 0Motor voltage 460V/3/60 Coldest dry bulb temp (°F) 54.0Motor power (HP) 10.00 Coil size LargeMotor hand Left Drain pan StandardDrive 150% HP Adjustable Access panels OneAir flow (ft³/min) 8,590 Panel hand LeftExternal static @ Actual (in w.g.) 2.50 Liners SolidInternal static @ Actual (in w.g.) 1.09
PERFORMANCE SUMMARY • UMA # 25
Untitled • P.BAJA LABOR EXPULSION
Tuesday, January 21, 2003 Page 58 of 159 Version 3.70 - Released 5/13/2002 - VA01
Air Handler Coils
Coil Tag Model # Qty Location Footnotes
CoilTotal capacity (MBH)Sensible capacity (MBH)Air PropertiesAir flow (ft³/min)Altitude (ft)Face velocity (ft/min)Air pressure drop (in w.g.)Entering air DB / WB (°F)Leaving air DB / WB (°F)Air properties measured atFluid PropertiesFluidFluid flow rate (gal/min)Fluid velocity (ft/s)Entering fluid temp. (°F)Leaving fluid temp. (°F)Fluid pressure drop (ft w.g.)ConstructionType / tubes in faceFinned height (in)Finned length (in)Face area (ft²)Rows / fin spacing (fins/in)Number of feedsCasing constructionSupply connections (qty@in)Return connections (qty@in)Connection type
#1 5 W P 6 B - 22T x 76 LH 1 Section D - Coil A
A. Certified in accordance with the ARIForced-Circulation Air-Cooling and Air-HeatingCoils Certification Program, which is based onARI Standard-410.
A
#1331.2225.0
8,5900
4640.68
76.7 / 65.252.4 / 52.3
Actual
Water58.43.9
44.055.411.6
5 / 2235.176.018.5
6 / 1016
Air handler1@1 1/21@1 1/2
MPT
FAN CURVE • UMA # 25
Untitled • P.BAJA LABOR EXPULSION
Tuesday, January 21, 2003 Page 59 of 159 Version 3.70 - Released 5/13/2002 - VA01
Supply Fan Specification
Air handler model AHD2 AF 120 V M Air flow (ft³/min) 8,590Fan type Airfoil (standard/201) Static pressure @ Altitude (in w.g.) 3.59Style Draw-thru Rotations per minute 1,894Inlet vanes No Brake power @ Altitude (HP) 7.54Altitude (ft) 0 Coldest dry bulb (°F) 54.0
Fan Curve
Air flow (ft³/min)
Stat
ic p
ress
ure
@ A
ltitu
de (i
n w
.g.)
Brak
e po
wer
@ A
ltitu
de (H
P)
6,400 7,200 8,000 8,800 9,600 10,400 11,200 12,000
5.00
7.80
4.50
7.65
4.00
7.50
3.50
7.35
3.00
7.20
2.50
7.05
2.00
6.90
1.50
6.75
DRAWING • UMA # 25
Untitled • P.BAJA LABOR EXPULSION
Tuesday, January 21, 2003 Page 60 of 159 Version 3.70 - Released 5/13/2002 - VA01
Side
vie
w -
AH
D2
AF
120
V M
Ente
ring
air v
iew
Leav
ing
air v
iew
This
dra
win
g is
not
to s
cale
; it i
s to
be
used
for d
imen
sion
al p
urpo
ses
only
.
28.0 in
26.5 in
2.0
in26
.5 in
73.0
in/1
,048
lb32
.0 in
/951
lb
58.0 in22.9
in22
.3 in
51.0
in/3
,079
lb
58.0 in
114.5 in
88.0
in3.
0 in
3.0
in
94.0
in
42.0
in27
.0 in
94.0
in
PERFORMANCE SUMMARY • UMA # 24
Untitled • P.BAJA SEMI. INTENS.
Tuesday, January 21, 2003 Page 61 of 159 Version 3.70 - Released 5/13/2002 - VA01
CS² Air Handler
Model # AHD2 FS 040 H M Insulation (entire unit) 2.00#Quantity 1 Wall thickness 2" (5.08 cm)Environment Indoor Sealed panels Positive pressure only
Notes
- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which isbased on ARI Standard-430.- See individual coil ratings for ARI certification information.- ETL listed & UL 1995 Approved.
A. Section 16C Combination filter/mixing box section
Inlet location(s) Top and back Access panels OneTop dampers Standard Panel hand LeftBack dampers Standard Liners SolidFilter media 2" Pleated 35% eff. Pressure drop (in w.g.) 0.14
B. Section 13 Cartridge/bag
Filter depth 12" (30.48 cm) Panel hand LeftFilter media Supplied by other Liners SolidAccess panels One
C. Section 20 External face & bypass section
Liners Solid Pressure drop (in w.g.) 0.17
D. Section 7 Short cooling coil section
Coil size Large Liners SolidDrain pan Standard Pressure drop (in w.g.) 0.45
Refer to attached pages for coil performance.
E. Shipping split
PERFORMANCE SUMMARY • UMA # 24
Untitled • P.BAJA SEMI. INTENS.
Tuesday, January 21, 2003 Page 62 of 159 Version 3.70 - Released 5/13/2002 - VA01
F. Section 2 Horizontal blow-thru fan section
Fan type Forward curved (alternate) Internal static @ Actual (in w.g.) 0.91Internal isolation Spring Total static @ Actual (in w.g.) 3.41Arrangement #3 Brake power @ Actual (HP) 3.93Motor type High Eff. TEFC Rotations per minute 2,170Motor voltage 460V/3/60 Altitude (ft) 0Motor power (HP) 5.00 Coldest dry bulb temp (°F) 54.0Motor hand Left Access panels OneDrive 150% HP Adjustable Panel hand LeftAir flow (ft³/min) 3,050 Liners SolidExternal static @ Actual (in w.g.) 2.50
G. Section 27 Diffuser section
Liners Solid Pressure drop (in w.g.) 0.14
H. Section 13 Cartridge/bag
Filter depth 12" (30.48 cm) Panel hand LeftFilter media Supplied by other Liners SolidAccess panels One
PERFORMANCE SUMMARY • UMA # 24
Untitled • P.BAJA SEMI. INTENS.
Tuesday, January 21, 2003 Page 63 of 159 Version 3.70 - Released 5/13/2002 - VA01
Air Handler Coils
Coil Tag Model # Qty Location Footnotes
CoilTotal capacity (MBH)Sensible capacity (MBH)Air PropertiesAir flow (ft³/min)Altitude (ft)Face velocity (ft/min)Air pressure drop (in w.g.)Entering air DB / WB (°F)Leaving air DB / WB (°F)Air properties measured atFluid PropertiesFluidFluid flow rate (gal/min)Fluid velocity (ft/s)Entering fluid temp. (°F)Leaving fluid temp. (°F)Fluid pressure drop (ft w.g.)ConstructionType / tubes in faceFinned height (in)Finned length (in)Face area (ft²)Rows / fin spacing (fins/in)Number of feedsCasing constructionSupply connections (qty@in)Return connections (qty@in)Connection type
#1 5 W H 5 C - 17T x 44 LH 1 Section D - Coil A
A. Certified in accordance with the ARIForced-Circulation Air-Cooling and Air-HeatingCoils Certification Program, which is based onARI Standard-410.
A
#1113.679.8
3,0500
3680.45
76.7 / 64.852.5 / 52.2
Actual
Water20.22.7
44.055.35.2
5 / 1727.144.08.3
5 / 128
Air handler1@1 1/21@1 1/2
MPT
FAN CURVE • UMA # 24
Untitled • P.BAJA SEMI. INTENS.
Tuesday, January 21, 2003 Page 64 of 159 Version 3.70 - Released 5/13/2002 - VA01
Supply Fan Specification
Air handler model AHD2 FS 040 H M Air flow (ft³/min) 3,050Fan type Forward curved (alternate/9-9) Static pressure @ Altitude (in w.g.) 3.41Style Blow-thru Rotations per minute 2,170Inlet vanes No Brake power @ Altitude (HP) 3.93Altitude (ft) 0 Coldest dry bulb (°F) 54.0
Fan Curve
Air flow (ft³/min)
Stat
ic p
ress
ure
@ A
ltitu
de (i
n w
.g.)
Brak
e po
wer
@ A
ltitu
de (H
P)
2,000 2,500 3,000 3,500 4,000 4,500 5,000 5,500
4.00
9.00
3.50
8.00
3.00
7.00
2.50
6.00
2.00
5.00
1.50
4.00
1.00
3.00
0.50
2.00
DRAWING • UMA # 24
Untitled • P.BAJA SEMI. INTENS.
Tuesday, January 21, 2003 Page 65 of 159 Version 3.70 - Released 5/13/2002 - VA01
Side
vie
w -
AH
D2
FS 0
40 H
M
Ente
ring
air v
iew
Leav
ing
air v
iew
This
dra
win
g is
not
to s
cale
; it i
s to
be
used
for d
imen
sion
al p
urpo
ses
only
.
23.5 in
15.0 in
1.0
in15
.0 in
107.
0 in
/1,1
35 lb
89.5
in/1
,194
lb
42.0 in
42.0 in
54.0
in3.
0 in
3.0
in
60.0
in60
.0 in
PERFORMANCE SUMMARY • UMA # 23
Untitled • P.BAJA QUEMADOS
Tuesday, January 21, 2003 Page 66 of 159 Version 3.70 - Released 5/13/2002 - VA01
CS² Air Handler
Model # AHD2 FS 022 H M Insulation (entire unit) 2.00#Quantity 1 Wall thickness 2" (5.08 cm)Environment Indoor Sealed panels Positive pressure only
Notes
- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which isbased on ARI Standard-430.- See individual coil ratings for ARI certification information.- ETL listed & UL 1995 Approved.
A. Section 16C Combination filter/mixing box section
Inlet location(s) Top and back Access panels OneTop dampers Standard Panel hand LeftBack dampers Standard Liners SolidFilter media 2" Pleated 35% eff. Pressure drop (in w.g.) 0.14
B. Section 13 Cartridge/bag
Filter depth 12" (30.48 cm) Panel hand LeftFilter media Supplied by other Liners SolidAccess panels One
C. Section 20 External face & bypass section
Liners Solid Pressure drop (in w.g.) 0.20
D. Section 7 Short cooling coil section
Coil size Large Liners SolidDrain pan Standard Pressure drop (in w.g.) 0.51
Refer to attached pages for coil performance.
E. Section 2 Horizontal blow-thru fan section
Fan type Forward curved (alternate) Internal static @ Actual (in w.g.) 1.02Internal isolation Spring Total static @ Actual (in w.g.) 3.52Arrangement #3 Brake power @ Actual (HP) 2.32Motor type High Eff. TEFC Rotations per minute 2,110Motor voltage 460V/3/60 Altitude (ft) 0Motor power (HP) 3.00 Coldest dry bulb temp (°F) 54.0Motor hand Left Access panels OneDrive 150% HP Adjustable Panel hand LeftAir flow (ft³/min) 1,830 Liners SolidExternal static @ Actual (in w.g.) 2.50
PERFORMANCE SUMMARY • UMA # 23
Untitled • P.BAJA QUEMADOS
Tuesday, January 21, 2003 Page 67 of 159 Version 3.70 - Released 5/13/2002 - VA01
F. Shipping split
G. Section 27 Diffuser section
Liners Solid Pressure drop (in w.g.) 0.16
H. Section 13 Cartridge/bag
Filter depth 12" (30.48 cm) Panel hand LeftFilter media Supplied by other Liners SolidAccess panels One
PERFORMANCE SUMMARY • UMA # 23
Untitled • P.BAJA QUEMADOS
Tuesday, January 21, 2003 Page 68 of 159 Version 3.70 - Released 5/13/2002 - VA01
Air Handler Coils
Coil Tag Model # Qty Location Footnotes
CoilTotal capacity (MBH)Sensible capacity (MBH)Air PropertiesAir flow (ft³/min)Altitude (ft)Face velocity (ft/min)Air pressure drop (in w.g.)Entering air DB / WB (°F)Leaving air DB / WB (°F)Air properties measured atFluid PropertiesFluidFluid flow rate (gal/min)Fluid velocity (ft/s)Entering fluid temp. (°F)Leaving fluid temp. (°F)Fluid pressure drop (ft w.g.)ConstructionType / tubes in faceFinned height (in)Finned length (in)Face area (ft²)Rows / fin spacing (fins/in)Number of feedsCasing constructionSupply connections (qty@in)Return connections (qty@in)Connection type
#1 5 W H 5 C - 13T x 32 LH 1 Section D - Coil A
A. Certified in accordance with the ARIForced-Circulation Air-Cooling and Air-HeatingCoils Certification Program, which is based onARI Standard-410.
A
#159.445.7
1,8300
3970.51
76.4 / 64.053.3 / 53.0
Actual
Water11.12.0
44.054.72.5
5 / 1320.732.04.6
5 / 126
Air handler1@1 1/21@1 1/2
MPT
FAN CURVE • UMA # 23
Untitled • P.BAJA QUEMADOS
Tuesday, January 21, 2003 Page 69 of 159 Version 3.70 - Released 5/13/2002 - VA01
Supply Fan Specification
Air handler model AHD2 FS 022 H M Air flow (ft³/min) 1,830Fan type Forward curved (alternate/9-6) Static pressure @ Altitude (in w.g.) 3.52Style Blow-thru Rotations per minute 2,110Inlet vanes No Brake power @ Altitude (HP) 2.32Altitude (ft) 0 Coldest dry bulb (°F) 54.0
Fan Curve
Air flow (ft³/min)
Stat
ic p
ress
ure
@ A
ltitu
de (i
n w
.g.)
Brak
e po
wer
@ A
ltitu
de (H
P)
1,500 1,800 2,100 2,400 2,700 3,000 3,300 3,600
4.00
6.00
3.60
5.40
3.20
4.80
2.80
4.20
2.40
3.60
2.00
3.00
1.60
2.40
1.20
1.80
DRAWING • UMA # 23
Untitled • P.BAJA QUEMADOS
Tuesday, January 21, 2003 Page 70 of 159 Version 3.70 - Released 5/13/2002 - VA01
Side
vie
w -
AH
D2
FS 0
22 H
M
Ente
ring
air v
iew
Leav
ing
air v
iew
This
dra
win
g is
not
to s
cale
; it i
s to
be
used
for d
imen
sion
al p
urpo
ses
only
.
15.5 in
15.0 in
1.0
in15
.0 in
128.
0 in
/1,2
75 lb
46.0
in/3
43 lb
34.0 in
34.0 in
42.0
in3.
0 in
3.0
in
48.0
in48
.0 in
PERFORMANCE SUMMARY • UMA # 22
Untitled • P.BAJA INTENS.
Tuesday, January 21, 2003 Page 71 of 159 Version 3.70 - Released 5/13/2002 - VA01
CS² Air Handler
Model # AHD2 FS 048 H M Insulation (entire unit) 2.00#Quantity 1 Wall thickness 2" (5.08 cm)Environment Indoor Sealed panels Positive pressure only
Notes
- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which isbased on ARI Standard-430.- See individual coil ratings for ARI certification information.- ETL listed & UL 1995 Approved.
A. Section 16C Combination filter/mixing box section
Inlet location(s) Top and back Access panels OneTop dampers Standard Panel hand LeftBack dampers Standard Liners SolidFilter media 2" Pleated 35% eff. Pressure drop (in w.g.) 0.21
B. Section 13 Cartridge/bag
Filter depth 12" (30.48 cm) Panel hand LeftFilter media Supplied by other Liners SolidAccess panels One
C. Section 20 External face & bypass section
Liners Solid Pressure drop (in w.g.) 0.31
D. Section 7 Short cooling coil section
Coil size Large Liners SolidDrain pan Standard Pressure drop (in w.g.) 0.70
Refer to attached pages for coil performance.
E. Shipping split
PERFORMANCE SUMMARY • UMA # 22
Untitled • P.BAJA INTENS.
Tuesday, January 21, 2003 Page 72 of 159 Version 3.70 - Released 5/13/2002 - VA01
F. Section 2 Horizontal blow-thru fan section
Fan type Forward curved (standard) Internal static @ Actual (in w.g.) 1.47Internal isolation Spring Total static @ Actual (in w.g.) 3.97Arrangement #3 Brake power @ Actual (HP) 6.54Motor type High Eff. TEFC Rotations per minute 1,650Motor voltage 460V/3/60 Altitude (ft) 0Motor power (HP) 10.00 Coldest dry bulb temp (°F) 54.0Motor hand Left Access panels OneDrive 150% HP Adjustable Panel hand LeftAir flow (ft³/min) 4,991 Liners SolidExternal static @ Actual (in w.g.) 2.50
G. Section 27 Diffuser section
Liners Solid Pressure drop (in w.g.) 0.25
H. Section 13 Cartridge/bag
Filter depth 12" (30.48 cm) Panel hand LeftFilter media Supplied by other Liners SolidAccess panels One
PERFORMANCE SUMMARY • UMA # 22
Untitled • P.BAJA INTENS.
Tuesday, January 21, 2003 Page 73 of 159 Version 3.70 - Released 5/13/2002 - VA01
Air Handler Coils
Coil Tag Model # Qty Location Footnotes
CoilTotal capacity (MBH)Sensible capacity (MBH)Air PropertiesAir flow (ft³/min)Altitude (ft)Face velocity (ft/min)Air pressure drop (in w.g.)Entering air DB / WB (°F)Leaving air DB / WB (°F)Air properties measured atFluid PropertiesFluidFluid flow rate (gal/min)Fluid velocity (ft/s)Entering fluid temp. (°F)Leaving fluid temp. (°F)Fluid pressure drop (ft w.g.)ConstructionType / tubes in faceFinned height (in)Finned length (in)Face area (ft²)Rows / fin spacing (fins/in)Number of feedsCasing constructionSupply connections (qty@in)Return connections (qty@in)Connection type
#1 5 W H 5 C - 17T x 54 LH 1 Section D - Coil A
A. Certified in accordance with the ARIForced-Circulation Air-Cooling and Air-HeatingCoils Certification Program, which is based onARI Standard-410.
A
#1195.8130.6
4,9910
4910.70
77.3 / 65.953.0 / 52.9
Actual
Water35.94.9
44.054.916.3
5 / 1727.154.010.2
5 / 128
Air handler1@1 1/21@1 1/2
MPT
FAN CURVE • UMA # 22
Untitled • P.BAJA INTENS.
Tuesday, January 21, 2003 Page 74 of 159 Version 3.70 - Released 5/13/2002 - VA01
Supply Fan Specification
Air handler model AHD2 FS 048 H M Air flow (ft³/min) 4,991Fan type Forward curved (standard/12-12) Static pressure @ Altitude (in w.g.) 3.97Style Blow-thru Rotations per minute 1,650Inlet vanes No Brake power @ Altitude (HP) 6.54Altitude (ft) 0 Coldest dry bulb (°F) 54.0
Fan Curve
Air flow (ft³/min)
Stat
ic p
ress
ure
@ A
ltitu
de (i
n w
.g.)
Brak
e po
wer
@ A
ltitu
de (H
P)
3,000 4,000 5,000 6,000 7,000 8,000 9,000 10,000
4.40
18.0
0
4.00
16.0
0
3.60
14.0
0
3.20
12.0
0
2.80
10.0
0
2.40
8.00
2.00
6.00
1.60
4.00
DRAWING • UMA # 22
Untitled • P.BAJA INTENS.
Tuesday, January 21, 2003 Page 75 of 159 Version 3.70 - Released 5/13/2002 - VA01
Side
vie
w -
AH
D2
FS 0
48 H
M
Ente
ring
air v
iew
Leav
ing
air v
iew
This
dra
win
g is
not
to s
cale
; it i
s to
be
used
for d
imen
sion
al p
urpo
ses
only
.
25.5 in
15.0 in
1.0
in15
.0 in
107.
0 in
/1,2
65 lb
89.5
in/1
,345
lb
44.0 in
44.0 in
64.0
in3.
0 in
3.0
in
70.0
in70
.0 in
PERFORMANCE SUMMARY • UMA # 21
Untitled • P.BAJA MED.FIS. Y REHAB.
Tuesday, January 21, 2003 Page 76 of 159 Version 3.70 - Released 5/13/2002 - VA01
CS² Air Handler
Model # AHD2 FS 040 V M Insulation (entire unit) 2.00#Quantity 1 Wall thickness 2" (5.08 cm)Environment Indoor Sealed panels Positive pressure only
Notes
- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which isbased on ARI Standard-430.- See individual coil ratings for ARI certification information.- ETL listed & UL 1995 Approved.
A. Section 16C Combination filter/mixing box section
Inlet location(s) Top and back Access panels OneTop dampers Standard Panel hand LeftBack dampers Standard Liners SolidFilter media 2" Pleated 35% eff. Pressure drop (in w.g.) 0.16
B. Section 18 Internal face & bypass short coil section
Coil size Small Liners SolidDrain pan Standard Pressure drop (in w.g.) 1.05Maximum bypass air flow (ft³/min) 2,191
Refer to attached pages for coil performance.
C. Shipping split
D. Section 3 Vertical draw-thru fan section
Fan type Forward curved (standard) Total static @ Actual (in w.g.) 2.21Internal isolation Spring Brake power @ Actual (HP) 2.33Arrangement #3 Rotations per minute 1,223Motor type High Eff. TEFC Altitude (ft) 0Motor voltage 460V/3/60 Coldest dry bulb temp (°F) 54.0Motor power (HP) 3.00 Coil size LargeMotor hand Left Drain pan StandardDrive 150% HP Adjustable Access panels OneAir flow (ft³/min) 3,350 Panel hand LeftExternal static @ Actual (in w.g.) 1.00 Liners SolidInternal static @ Actual (in w.g.) 1.22
PERFORMANCE SUMMARY • UMA # 21
Untitled • P.BAJA MED.FIS. Y REHAB.
Tuesday, January 21, 2003 Page 77 of 159 Version 3.70 - Released 5/13/2002 - VA01
Air Handler Coils
Coil Tag Model # Qty Location Footnotes
CoilTotal capacity (MBH)Sensible capacity (MBH)Air PropertiesAir flow (ft³/min)Altitude (ft)Face velocity (ft/min)Air pressure drop (in w.g.)Entering air DB / WB (°F)Leaving air DB / WB (°F)Air properties measured atFluid PropertiesFluidFluid flow rate (gal/min)Fluid velocity (ft/s)Entering fluid temp. (°F)Leaving fluid temp. (°F)Fluid pressure drop (ft w.g.)ConstructionType / tubes in faceFinned height (in)Finned length (in)Face area (ft²)Rows / fin spacing (fins/in)Number of feedsCasing constructionSupply connections (qty@in)Return connections (qty@in)Connection type
#1 5 W H 6 B - 14T x 44 LH 1 Section B - Coil A
A. Certified in accordance with the ARIForced-Circulation Air-Cooling and Air-HeatingCoils Certification Program, which is based onARI Standard-410.
A
#1134.689.1
3,3500
4910.74
76.8 / 65.552.2 / 51.9
Actual
Water26.64.1
44.054.112.7
5 / 1422.344.06.8
6 / 107
Air handler1@1 1/21@1 1/2
MPT
FAN CURVE • UMA # 21
Untitled • P.BAJA MED.FIS. Y REHAB.
Tuesday, January 21, 2003 Page 78 of 159 Version 3.70 - Released 5/13/2002 - VA01
Supply Fan Specification
Air handler model AHD2 FS 040 V M Air flow (ft³/min) 3,350Fan type Forward curved (standard/12-12) Static pressure @ Altitude (in w.g.) 2.21Style Draw-thru Rotations per minute 1,223Inlet vanes No Brake power @ Altitude (HP) 2.33Altitude (ft) 0 Coldest dry bulb (°F) 54.0
Fan Curve
Air flow (ft³/min)
Stat
ic p
ress
ure
@ A
ltitu
de (i
n w
.g.)
Brak
e po
wer
@ A
ltitu
de (H
P)
2,400 3,000 3,600 4,200 4,800 5,400 6,000 6,600
2.25
6.00
2.10
5.40
1.95
4.80
1.80
4.20
1.65
3.60
1.50
3.00
1.35
2.40
1.20
1.80
DRAWING • UMA # 21
Untitled • P.BAJA MED.FIS. Y REHAB.
Tuesday, January 21, 2003 Page 79 of 159 Version 3.70 - Released 5/13/2002 - VA01
Side
vie
w -
AH
D2
FS 0
40 V
M
Ente
ring
air v
iew
Leav
ing
air v
iew
This
dra
win
g is
not
to s
cale
; it i
s to
be
used
for d
imen
sion
al p
urpo
ses
only
.20.0 in
15.0 in
1.0
in15
.0 in
65.0
in/7
61 lb
12.4
in13
.6 in
37.5
in/1
,084
lb
38.5 in
78.0 in
54.0
in3.
0 in
3.0
in
60.0
in
25.6
in15
.8 in
60.0
in
PERFORMANCE SUMMARY • UMA # 20
Untitled • P.BAJA ADMIN.
Tuesday, January 21, 2003 Page 80 of 159 Version 3.70 - Released 5/13/2002 - VA01
CS² Air Handler
Model # AHD2 FS 150 H M Insulation (entire unit) 2.00#Quantity 1 Wall thickness 2" (5.08 cm)Environment Indoor Sealed panels Positive pressure only
Notes
- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which isbased on ARI Standard-430.- See individual coil ratings for ARI certification information.- ETL listed & UL 1995 Approved.
A. Section 16C Combination filter/mixing box section
Inlet location(s) Top and back Access panels OneTop dampers Standard Panel hand LeftBack dampers Standard Liners SolidFilter media 2" Pleated 35% eff. Pressure drop (in w.g.) 0.16
B. Section 20 External face & bypass section
Liners Solid Pressure drop (in w.g.) 0.19
C. Section 7 Short cooling coil section
Coil size Large Liners SolidDrain pan Standard Pressure drop (in w.g.) 0.49
Refer to attached pages for coil performance.
D. Shipping split
E. Section 1 Horizontal draw-thru fan section
Fan type Forward curved (standard) Internal static @ Actual (in w.g.) 0.84Internal isolation Spring (standard) Total static @ Actual (in w.g.) 1.84Arrangement #3 Brake power @ Actual (HP) 8.60Motor type High Eff. TEFC Rotations per minute 677Motor voltage 460V/3/60 Altitude (ft) 0Motor power (HP) 10.00 Coldest dry bulb temp (°F) 54.0Motor hand Left Access panels OneDrive 150% HP Adjustable Panel hand LeftAir flow (ft³/min) 11,780 Liners SolidExternal static @ Actual (in w.g.) 1.00
PERFORMANCE SUMMARY • UMA # 20
Untitled • P.BAJA ADMIN.
Tuesday, January 21, 2003 Page 81 of 159 Version 3.70 - Released 5/13/2002 - VA01
Air Handler Coils
Coil Tag Model # Qty Location Footnotes
CoilTotal capacity (MBH)Sensible capacity (MBH)Air PropertiesAir flow (ft³/min)Altitude (ft)Face velocity (ft/min)Air pressure drop (in w.g.)Entering air DB / WB (°F)Leaving air DB / WB (°F)Air properties measured atFluid PropertiesFluidFluid flow rate (gal/min)Fluid velocity (ft/s)Entering fluid temp. (°F)Leaving fluid temp. (°F)Fluid pressure drop (ft w.g.)ConstructionType / tubes in faceFinned height (in)Finned length (in)Face area (ft²)Rows / fin spacing (fins/in)Number of feedsCasing constructionSupply connections (qty@in)Return connections (qty@in)Connection type
#1 5 W Q 5 C - 36T x 76 LH 1 Section C - Coil A
A. Certified in accordance with the ARIForced-Circulation Air-Cooling and Air-HeatingCoils Certification Program, which is based onARI Standard-410.
A
#1517.7319.5
11,7800
3890.49
78.7 / 67.453.5 / 52.9
Actual
Water102.2
2.544.054.12.6
5 / 3657.476.030.3
5 / 1245
Air handler1@2 1/21@2 1/2
MPT
FAN CURVE • UMA # 20
Untitled • P.BAJA ADMIN.
Tuesday, January 21, 2003 Page 82 of 159 Version 3.70 - Released 5/13/2002 - VA01
Supply Fan Specification
Air handler model AHD2 FS 150 H M Air flow (ft³/min) 11,780Fan type Forward curved (standard/22-15) Static pressure @ Altitude (in w.g.) 1.84Style Draw-thru Rotations per minute 677Inlet vanes No Brake power @ Altitude (HP) 8.61Altitude (ft) 0 Coldest dry bulb (°F) 54.0
Fan Curve
Air flow (ft³/min)
Stat
ic p
ress
ure
@ A
ltitu
de (i
n w
.g.)
Brak
e po
wer
@ A
ltitu
de (H
P)
7,500 9,000 10,500 12,000 13,500 15,000 16,500 18,000
2.25
15.0
0
2.00
13.5
0
1.75
12.0
0
1.50
10.5
0
1.25
9.00
1.00
7.50
0.75
6.00
0.50
4.50
DRAWING • UMA # 20
Untitled • P.BAJA ADMIN.
Tuesday, January 21, 2003 Page 83 of 159 Version 3.70 - Released 5/13/2002 - VA01
Side
vie
w -
AH
D2
FS 1
50 H
M
Ente
ring
air v
iew
Leav
ing
air v
iew
This
dra
win
g is
not
to s
cale
; it i
s to
be
used
for d
imen
sion
al p
urpo
ses
only
.
42.0 in26.5 in
2.0
in26
.5 in
101.
0 in
/2,3
42 lb
12.8 in27.4 in
56.0
in/2
,130
lb
72.0 in
72.0 in
88.0
in3.
0 in
3.0
in
94.0
in
39.0
in20
.4 in
94.0
in
PERFORMANCE SUMMARY • UMA # 19
Untitled • P.BAJA FARMACIA
Tuesday, January 21, 2003 Page 84 of 159 Version 3.70 - Released 5/13/2002 - VA01
CS² Air Handler
Model # AHD2 FS 040 V M Insulation (entire unit) 2.00#Quantity 1 Wall thickness 2" (5.08 cm)Environment Indoor Sealed panels Positive pressure only
Notes
- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which isbased on ARI Standard-430.- See individual coil ratings for ARI certification information.- ETL listed & UL 1995 Approved.
A. Section 16C Combination filter/mixing box section
Inlet location(s) Top and back Access panels OneTop dampers Standard Panel hand LeftBack dampers Standard Liners SolidFilter media 2" Pleated 35% eff. Pressure drop (in w.g.) 0.13
B. Section 18 Internal face & bypass short coil section
Coil size Small Liners SolidDrain pan Standard Pressure drop (in w.g.) 0.76Maximum bypass air flow (ft³/min) 2,191
Refer to attached pages for coil performance.
C. Shipping split
D. Section 3 Vertical draw-thru fan section
Fan type Forward curved (standard) Total static @ Actual (in w.g.) 1.88Internal isolation Spring Brake power @ Actual (HP) 1.62Arrangement #3 Rotations per minute 1,124Motor type High Eff. TEFC Altitude (ft) 0Motor voltage 460V/3/60 Coldest dry bulb temp (°F) 54.0Motor power (HP) 2.00 Coil size LargeMotor hand Left Drain pan StandardDrive 150% HP Adjustable Access panels OneAir flow (ft³/min) 2,824 Panel hand LeftExternal static @ Actual (in w.g.) 1.00 Liners SolidInternal static @ Actual (in w.g.) 0.88
PERFORMANCE SUMMARY • UMA # 19
Untitled • P.BAJA FARMACIA
Tuesday, January 21, 2003 Page 85 of 159 Version 3.70 - Released 5/13/2002 - VA01
Air Handler Coils
Coil Tag Model # Qty Location Footnotes
CoilTotal capacity (MBH)Sensible capacity (MBH)Air PropertiesAir flow (ft³/min)Altitude (ft)Face velocity (ft/min)Air pressure drop (in w.g.)Entering air DB / WB (°F)Leaving air DB / WB (°F)Air properties measured atFluid PropertiesFluidFluid flow rate (gal/min)Fluid velocity (ft/s)Entering fluid temp. (°F)Leaving fluid temp. (°F)Fluid pressure drop (ft w.g.)ConstructionType / tubes in faceFinned height (in)Finned length (in)Face area (ft²)Rows / fin spacing (fins/in)Number of feedsCasing constructionSupply connections (qty@in)Return connections (qty@in)Connection type
#1 5 W H 5 C - 14T x 44 LH 1 Section B - Coil A
A. Certified in accordance with the ARIForced-Circulation Air-Cooling and Air-HeatingCoils Certification Program, which is based onARI Standard-410.
A
#1188.390.9
2,8240
4140.53
83.1 / 73.352.9 / 52.8
Actual
Water36.45.6
44.054.418.6
5 / 1422.344.06.8
5 / 127
Air handler1@1 1/21@1 1/2
MPT
FAN CURVE • UMA # 19
Untitled • P.BAJA FARMACIA
Tuesday, January 21, 2003 Page 86 of 159 Version 3.70 - Released 5/13/2002 - VA01
Supply Fan Specification
Air handler model AHD2 FS 040 V M Air flow (ft³/min) 2,824Fan type Forward curved (standard/12-12) Static pressure @ Altitude (in w.g.) 1.88Style Draw-thru Rotations per minute 1,124Inlet vanes No Brake power @ Altitude (HP) 1.62Altitude (ft) 0 Coldest dry bulb (°F) 54.0
Fan Curve
Air flow (ft³/min)
Stat
ic p
ress
ure
@ A
ltitu
de (i
n w
.g.)
Brak
e po
wer
@ A
ltitu
de (H
P)
2,500 3,000 3,500 4,000 4,500 5,000 5,500 6,000
2.10
4.50
1.95
4.00
1.80
3.50
1.65
3.00
1.50
2.50
1.35
2.00
1.20
1.50
1.05
1.00
DRAWING • UMA # 19
Untitled • P.BAJA FARMACIA
Tuesday, January 21, 2003 Page 87 of 159 Version 3.70 - Released 5/13/2002 - VA01
Side
vie
w -
AH
D2
FS 0
40 V
M
Ente
ring
air v
iew
Leav
ing
air v
iew
This
dra
win
g is
not
to s
cale
; it i
s to
be
used
for d
imen
sion
al p
urpo
ses
only
.20.0 in
15.0 in
1.0
in15
.0 in
65.0
in/7
40 lb
12.4
in13
.6 in
37.5
in/1
,057
lb
38.5 in
78.0 in
54.0
in3.
0 in
3.0
in
60.0
in
25.6
in15
.8 in
60.0
in
PERFORMANCE SUMMARY • UMA # 18
Untitled • P.BAJA CONSULTA
Tuesday, January 21, 2003 Page 88 of 159 Version 3.70 - Released 5/13/2002 - VA01
CS² Air Handler
Model # AHD2 FS 240 V M Insulation (entire unit) 2.00#Quantity 1 Wall thickness 2" (5.08 cm)Environment Indoor Sealed panels Positive pressure only
Notes
- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which isbased on ARI Standard-430.- See individual coil ratings for ARI certification information.- ETL listed & UL 1995 Approved.
A. Section 16C Combination filter/mixing box section
Inlet location(s) Top and back Access panels OneTop dampers Standard Panel hand LeftBack dampers Standard Liners SolidFilter media 2" Pleated 35% eff. Pressure drop (in w.g.) 0.12
B. Shipping split
C. Section 18 Internal face & bypass short coil section
Coil size Small Liners SolidDrain pan Standard Pressure drop (in w.g.) 0.68Maximum bypass air flow (ft³/min) 14,078
Refer to attached pages for coil performance.
D. Shipping split
E. Section 3 Vertical draw-thru fan section
Fan type Forward curved (standard) Total static @ Actual (in w.g.) 1.80Internal isolation Spring (standard) Brake power @ Actual (HP) 8.80Arrangement #3 Rotations per minute 537Motor type High Eff. TEFC Altitude (ft) 0Motor voltage 460V/3/60 Coldest dry bulb temp (°F) 54.0Motor power (HP) 10.00 Coil size LargeMotor hand Left Drain pan StandardDrive 150% HP Adjustable Access panels OneAir flow (ft³/min) 15,507 Panel hand LeftExternal static @ Actual (in w.g.) 1.00 Liners SolidInternal static @ Actual (in w.g.) 0.80
PERFORMANCE SUMMARY • UMA # 18
Untitled • P.BAJA CONSULTA
Tuesday, January 21, 2003 Page 89 of 159 Version 3.70 - Released 5/13/2002 - VA01
Air Handler Coils
Coil Tag Model # Qty Location Footnotes
CoilTotal capacity (MBH)Sensible capacity (MBH)Air PropertiesAir flow (ft³/min)Altitude (ft)Face velocity (ft/min)Air pressure drop (in w.g.)Entering air DB / WB (°F)Leaving air DB / WB (°F)Air properties measured atFluid PropertiesFluidFluid flow rate (gal/min)Fluid velocity (ft/s)Entering fluid temp. (°F)Leaving fluid temp. (°F)Fluid pressure drop (ft w.g.)ConstructionType / tubes in faceFinned height (in)Finned length (in)Face area (ft²)Rows / fin spacing (fins/in)Number of feedsCasing constructionSupply connections (qty@in)Return connections (qty@in)Connection type
#1 5 W Q 5 C - 34T x 106 LH 1 Section C - Coil A
A. Certified in accordance with the ARIForced-Circulation Air-Cooling and Air-HeatingCoils Certification Program, which is based onARI Standard-410.
A
#1749.2455.1
15,5070
3890.49
79.6 / 68.152.3 / 52.2
Actual
Water140.6
3.644.054.76.6
5 / 3454.2
106.039.9
5 / 1242
Air handler1@2 1/21@2 1/2
MPT
FAN CURVE • UMA # 18
Untitled • P.BAJA CONSULTA
Tuesday, January 21, 2003 Page 90 of 159 Version 3.70 - Released 5/13/2002 - VA01
Supply Fan Specification
Air handler model AHD2 FS 240 V M Air flow (ft³/min) 15,507Fan type Forward curved (standard/25-25) Static pressure @ Altitude (in w.g.) 1.80Style Draw-thru Rotations per minute 537Inlet vanes No Brake power @ Altitude (HP) 8.80Altitude (ft) 0 Coldest dry bulb (°F) 54.0
Fan Curve
Air flow (ft³/min)
Stat
ic p
ress
ure
@ A
ltitu
de (i
n w
.g.)
Brak
e po
wer
@ A
ltitu
de (H
P)
12,500 15,000 17,500 20,000 22,500 25,000 27,500 30,000
2.00
22.5
0
1.80
20.0
0
1.60
17.5
0
1.40
15.0
0
1.20
12.5
0
1.00
10.0
0
0.80
7.50
0.60
5.00
DRAWING • UMA # 18
Untitled • P.BAJA CONSULTA
Tuesday, January 21, 2003 Page 91 of 159 Version 3.70 - Released 5/13/2002 - VA01
Side
vie
w -
AH
D2
FS 2
40 V
M
Ente
ring
air v
iew
Leav
ing
air v
iew
This
dra
win
g is
not
to s
cale
; it i
s to
be
used
for d
imen
sion
al p
urpo
ses
only
.
40.0 in
38.0 in
2.0
in38
.0 in
49.0
in/1
,103
lb34
.0 in
/1,7
97 lb
82.5 in18.4
in31
.3 in
70.0
in/4
,785
lb
82.5 in
162.5 in
116.
0 in
3.0
in3.
0 in
122.
0 in
45.4
in31
.3 in
122.
0 in
PERFORMANCE SUMMARY • UMA # 17
Untitled • E.P.3-ESTE
Tuesday, January 21, 2003 Page 92 of 159 Version 3.70 - Released 5/13/2002 - VA01
CS² Air Handler
Model # AHD2 FS 120 V M Insulation (entire unit) 2.00#Quantity 1 Wall thickness 2" (5.08 cm)Environment Indoor Sealed panels Positive pressure only
Notes
- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which isbased on ARI Standard-430.- See individual coil ratings for ARI certification information.- ETL listed & UL 1995 Approved.
A. Section 10F2 Flat filter section
Filter depth 2" (5.08 cm) Panel hand LeftFilter media Pleated 35% eff. Liners SolidAccess panels One Pressure drop (in w.g.) 0.13
B. Section 18 Internal face & bypass short coil section
Coil size Small Liners SolidDrain pan Standard Pressure drop (in w.g.) 0.90Maximum bypass air flow (ft³/min) 7,570
Refer to attached pages for coil performance.
C. Shipping split
D. Section 3 Vertical draw-thru fan section
Fan type Forward curved (standard) Total static @ Actual (in w.g.) 1.53Internal isolation Spring (standard) Brake power @ Actual (HP) 3.80Arrangement #3 Rotations per minute 636Motor type High Eff. TEFC Altitude (ft) 0Motor voltage 460V/3/60 Coldest dry bulb temp (°F) 54.0Motor power (HP) 5.00 Coil size LargeMotor hand Left Drain pan StandardDrive 150% HP Adjustable Access panels OneAir flow (ft³/min) 7,860 Panel hand LeftExternal static @ Actual (in w.g.) 0.50 Liners SolidInternal static @ Actual (in w.g.) 1.03
PERFORMANCE SUMMARY • UMA # 17
Untitled • E.P.3-ESTE
Tuesday, January 21, 2003 Page 93 of 159 Version 3.70 - Released 5/13/2002 - VA01
Air Handler Coils
Coil Tag Model # Qty Location Footnotes
CoilTotal capacity (MBH)Sensible capacity (MBH)Air PropertiesAir flow (ft³/min)Altitude (ft)Face velocity (ft/min)Air pressure drop (in w.g.)Entering air DB / WB (°F)Leaving air DB / WB (°F)Air properties measured atFluid PropertiesFluidFluid flow rate (gal/min)Fluid velocity (ft/s)Entering fluid temp. (°F)Leaving fluid temp. (°F)Fluid pressure drop (ft w.g.)ConstructionType / tubes in faceFinned height (in)Finned length (in)Face area (ft²)Rows / fin spacing (fins/in)Number of feedsCasing constructionSupply connections (qty@in)Return connections (qty@in)Connection type
#1 5 W F 6 C - 22T x 76 LH Q 1 Section B - Coil A
A. Certified in accordance with the ARIForced-Circulation Air-Cooling and Air-HeatingCoils Certification Program, which is based onARI Standard-410.
B. Fin material - 0.008 Polycoat
A,B
#1394.8238.0
7,8600
4250.67
79.4 / 67.951.2 / 51.2
Actual
Water71.33.5
44.055.17.2
5 / 2235.176.018.5
6 / 1222
Air handler1@2 1@2 MPT
FAN CURVE • UMA # 17
Untitled • E.P.3-ESTE
Tuesday, January 21, 2003 Page 94 of 159 Version 3.70 - Released 5/13/2002 - VA01
Supply Fan Specification
Air handler model AHD2 FS 120 V M Air flow (ft³/min) 7,860Fan type Forward curved (standard/20-18) Static pressure @ Altitude (in w.g.) 1.53Style Draw-thru Rotations per minute 636Inlet vanes No Brake power @ Altitude (HP) 3.80Altitude (ft) 0 Coldest dry bulb (°F) 54.0
Fan Curve
Air flow (ft³/min)
Stat
ic p
ress
ure
@ A
ltitu
de (i
n w
.g.)
Brak
e po
wer
@ A
ltitu
de (H
P)
6,000 7,200 8,400 9,600 10,800 12,000 13,200 14,400
1.80
10.0
0
1.65
9.00
1.50
8.00
1.35
7.00
1.20
6.00
1.05
5.00
0.90
4.00
0.75
3.00
DRAWING • UMA # 17
Untitled • E.P.3-ESTE
Tuesday, January 21, 2003 Page 95 of 159 Version 3.70 - Released 5/13/2002 - VA01
Side
vie
w -
AH
D2
FS 1
20 V
M
Ente
ring
air v
iew
Leav
ing
air v
iew
This
dra
win
g is
not
to s
cale
; it i
s to
be
used
for d
imen
sion
al p
urpo
ses
only
.
42.0
in/1
,458
lb
58.0 in17.5
in24
.9 in
51.0
in/2
,789
lb
58.0 in
114.5 in
94.0
in
39.6
in22
.9 in
94.0
in
PERFORMANCE SUMMARY • UMA # 16
Untitled • E.P.3-OESTE
Tuesday, January 21, 2003 Page 96 of 159 Version 3.70 - Released 5/13/2002 - VA01
CS² Air Handler
Model # AHD2 FS 100 H M Insulation (entire unit) 2.00#Quantity 1 Wall thickness 2" (5.08 cm)Environment Indoor Sealed panels Positive pressure only
Notes
- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which isbased on ARI Standard-430.- See individual coil ratings for ARI certification information.- ETL listed & UL 1995 Approved.
A. Section 13 Cartridge/bag
Filter depth 12" (30.48 cm) Panel hand LeftFilter media Supplied by other Liners SolidPre-filter media 2" Pleated 35% eff. Pressure drop (in w.g.) 0.18Access panels One
B. Section 20 External face & bypass section
Liners Solid Pressure drop (in w.g.) 0.23
C. Section 7 Short cooling coil section
Coil size Large Liners SolidDrain pan Standard Pressure drop (in w.g.) 0.42
Refer to attached pages for coil performance.
D. Section 1 Horizontal draw-thru fan section
Fan type Forward curved (standard) Internal static @ Actual (in w.g.) 0.83Internal isolation Spring (standard) Total static @ Actual (in w.g.) 1.83Arrangement #3 Brake power @ Actual (HP) 5.65Motor type High Eff. TEFC Rotations per minute 825Motor voltage 460V/3/60 Altitude (ft) 0Motor power (HP) 7.50 Coldest dry bulb temp (°F) 54.0Motor hand Left Access panels OneDrive Fixed Panel hand LeftAir flow (ft³/min) 8,070 Liners SolidExternal static @ Actual (in w.g.) 1.00
PERFORMANCE SUMMARY • UMA # 16
Untitled • E.P.3-OESTE
Tuesday, January 21, 2003 Page 97 of 159 Version 3.70 - Released 5/13/2002 - VA01
Air Handler Coils
Coil Tag Model # Qty Location Footnotes
CoilTotal capacity (MBH)Sensible capacity (MBH)Air PropertiesAir flow (ft³/min)Altitude (ft)Face velocity (ft/min)Air pressure drop (in w.g.)Entering air DB / WB (°F)Leaving air DB / WB (°F)Air properties measured atFluid PropertiesFluidFluid flow rate (gal/min)Fluid velocity (ft/s)Entering fluid temp. (°F)Leaving fluid temp. (°F)Fluid pressure drop (ft w.g.)ConstructionType / tubes in faceFinned height (in)Finned length (in)Face area (ft²)Rows / fin spacing (fins/in)Number of feedsCasing constructionSupply connections (qty@in)Return connections (qty@in)Connection type
#1 5 W H 4 C - 28T x 62 LH 1 Section C - Coil A
A. Certified in accordance with the ARIForced-Circulation Air-Cooling and Air-HeatingCoils Certification Program, which is based onARI Standard-410.
A
#1354.2215.0
8,0700
4200.42
78.6 / 67.653.8 / 53.4
Actual
Water70.85.5
44.054.017.9
5 / 2844.662.019.2
4 / 1214
Air handler1@1 1/21@1 1/2
MPT
FAN CURVE • UMA # 16
Untitled • E.P.3-OESTE
Tuesday, January 21, 2003 Page 98 of 159 Version 3.70 - Released 5/13/2002 - VA01
Supply Fan Specification
Air handler model AHD2 FS 100 H M Air flow (ft³/min) 8,070Fan type Forward curved (standard/18-18) Static pressure @ Altitude (in w.g.) 1.83Style Draw-thru Rotations per minute 825Inlet vanes No Brake power @ Altitude (HP) 5.65Altitude (ft) 0 Coldest dry bulb (°F) 54.0
Fan Curve
Air flow (ft³/min)
Stat
ic p
ress
ure
@ A
ltitu
de (i
n w
.g.)
Brak
e po
wer
@ A
ltitu
de (H
P)
4,800 6,000 7,200 8,400 9,600 10,800 12,000 13,200
2.40
13.5
0
2.20
12.0
0
2.00
10.5
0
1.80
9.00
1.60
7.50
1.40
6.00
1.20
4.50
1.00
3.00
DRAWING • UMA # 16
Untitled • E.P.3-OESTE
Tuesday, January 21, 2003 Page 99 of 159 Version 3.70 - Released 5/13/2002 - VA01
Side
vie
w -
AH
D2
FS 1
00 H
M
Ente
ring
air v
iew
Leav
ing
air v
iew
This
dra
win
g is
not
to s
cale
; it i
s to
be
used
for d
imen
sion
al p
urpo
ses
only
.
8.6 in19.0 in
133.
0 in
/2,9
31 lb
58.0 in
58.0 in
78.0
in
36.0
in22
.0 in
78.0
in
PERFORMANCE SUMMARY • UMA # 15
Untitled • E.P.2-AUDIT.
Tuesday, January 21, 2003 Page 100 of 159 Version 3.70 - Released 5/13/2002 - VA01
CS² Air Handler
Model # AHD2 FS 100 V M Insulation (entire unit) 2.00#Quantity 1 Wall thickness 2" (5.08 cm)Environment Indoor Sealed panels Positive pressure only
Notes
- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which isbased on ARI Standard-430.- See individual coil ratings for ARI certification information.- ETL listed & UL 1995 Approved.
A. Section 10F2 Flat filter section
Filter depth 2" (5.08 cm) Panel hand LeftFilter media Pleated 35% eff. Liners SolidAccess panels One Pressure drop (in w.g.) 0.18
B. Shipping split
C. Section 3 Vertical draw-thru fan section
Fan type Forward curved (standard) Total static @ Actual (in w.g.) 1.28Internal isolation Spring (standard) Brake power @ Actual (HP) 4.66Arrangement #3 Rotations per minute 719Motor type High Eff. TEFC Altitude (ft) 0Motor voltage 460V/3/60 Coldest dry bulb temp (°F) 54.0Motor power (HP) 5.00 Coil size LargeMotor hand Left Drain pan StandardDrive Fixed Access panels OneAir flow (ft³/min) 8,175 Panel hand LeftExternal static @ Actual (in w.g.) 0.50 Liners SolidInternal static @ Actual (in w.g.) 0.78 Pressure drop (in w.g.) 0.60
Refer to attached pages for coil performance.
PERFORMANCE SUMMARY • UMA # 15
Untitled • E.P.2-AUDIT.
Tuesday, January 21, 2003 Page 101 of 159 Version 3.70 - Released 5/13/2002 - VA01
Air Handler Coils
Coil Tag Model # Qty Location Footnotes
CoilTotal capacity (MBH)Sensible capacity (MBH)Air PropertiesAir flow (ft³/min)Altitude (ft)Face velocity (ft/min)Air pressure drop (in w.g.)Entering air DB / WB (°F)Leaving air DB / WB (°F)Air properties measured atFluid PropertiesFluidFluid flow rate (gal/min)Fluid velocity (ft/s)Entering fluid temp. (°F)Leaving fluid temp. (°F)Fluid pressure drop (ft w.g.)ConstructionType / tubes in faceFinned height (in)Finned length (in)Face area (ft²)Rows / fin spacing (fins/in)Number of feedsCasing constructionSupply connections (qty@in)Return connections (qty@in)Connection type
#1 5 W P 6 B - 28T x 62 LH 1 Section C - Coil A
A. Certified in accordance with the ARIForced-Circulation Air-Cooling and Air-HeatingCoils Certification Program, which is based onARI Standard-410.
A
#1389.9234.4
8,1750
4250.60
78.6 / 67.652.0 / 51.8
Actual
Water76.03.9
44.054.39.9
5 / 2844.662.019.2
6 / 1021
Air handler1@1 1/21@1 1/2
MPT
FAN CURVE • UMA # 15
Untitled • E.P.2-AUDIT.
Tuesday, January 21, 2003 Page 102 of 159 Version 3.70 - Released 5/13/2002 - VA01
Supply Fan Specification
Air handler model AHD2 FS 100 V M Air flow (ft³/min) 8,175Fan type Forward curved (standard/18-18) Static pressure @ Altitude (in w.g.) 1.28Style Draw-thru Rotations per minute 719Inlet vanes No Brake power @ Altitude (HP) 4.66Altitude (ft) 0 Coldest dry bulb (°F) 54.0
Fan Curve
Air flow (ft³/min)
Stat
ic p
ress
ure
@ A
ltitu
de (i
n w
.g.)
Brak
e po
wer
@ A
ltitu
de (H
P)
3,600 4,800 6,000 7,200 8,400 9,600 10,800 12,000
1.56
9.00
1.44
8.00
1.32
7.00
1.20
6.00
1.08
5.00
0.96
4.00
0.84
3.00
0.72
2.00
DRAWING • UMA # 15
Untitled • E.P.2-AUDIT.
Tuesday, January 21, 2003 Page 103 of 159 Version 3.70 - Released 5/13/2002 - VA01
Side
vie
w -
AH
D2
FS 1
00 V
M
Ente
ring
air v
iew
Leav
ing
air v
iew
This
dra
win
g is
not
to s
cale
; it i
s to
be
used
for d
imen
sion
al p
urpo
ses
only
.
10.0
in/4
41 lb
58.0 in16.4
in19
.0 in
51.0
in/2
,915
lb
58.0 in
114.5 in
78.0
in
36.0
in22
.0 in
78.0
in
PERFORMANCE SUMMARY • UMA # 14
Untitled • E.P.2-ESTE
Tuesday, January 21, 2003 Page 104 of 159 Version 3.70 - Released 5/13/2002 - VA01
CS² Air Handler
Model # AHD2 FS 120 V M Insulation (entire unit) 2.00#Quantity 1 Wall thickness 2" (5.08 cm)Environment Indoor Sealed panels Positive pressure only
Notes
- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which isbased on ARI Standard-430.- See individual coil ratings for ARI certification information.- ETL listed & UL 1995 Approved.
A. Section 10F2 Flat filter section
Filter depth 2" (5.08 cm) Panel hand LeftFilter media Pleated 35% eff. Liners SolidAccess panels One Pressure drop (in w.g.) 0.13
B. Section 18 Internal face & bypass short coil section
Coil size Small Liners SolidDrain pan Standard Pressure drop (in w.g.) 0.84Maximum bypass air flow (ft³/min) 7,570
Refer to attached pages for coil performance.
C. Shipping split
D. Section 3 Vertical draw-thru fan section
Fan type Forward curved (standard) Total static @ Actual (in w.g.) 1.48Internal isolation Spring (standard) Brake power @ Actual (HP) 3.79Arrangement #3 Rotations per minute 626Motor type High Eff. TEFC Altitude (ft) 0Motor voltage 460V/3/60 Coldest dry bulb temp (°F) 54.0Motor power (HP) 5.00 Coil size LargeMotor hand Left Drain pan StandardDrive 150% HP Adjustable Access panels OneAir flow (ft³/min) 7,975 Panel hand LeftExternal static @ Actual (in w.g.) 0.50 Liners SolidInternal static @ Actual (in w.g.) 0.98
PERFORMANCE SUMMARY • UMA # 14
Untitled • E.P.2-ESTE
Tuesday, January 21, 2003 Page 105 of 159 Version 3.70 - Released 5/13/2002 - VA01
Air Handler Coils
Coil Tag Model # Qty Location Footnotes
CoilTotal capacity (MBH)Sensible capacity (MBH)Air PropertiesAir flow (ft³/min)Altitude (ft)Face velocity (ft/min)Air pressure drop (in w.g.)Entering air DB / WB (°F)Leaving air DB / WB (°F)Air properties measured atFluid PropertiesFluidFluid flow rate (gal/min)Fluid velocity (ft/s)Entering fluid temp. (°F)Leaving fluid temp. (°F)Fluid pressure drop (ft w.g.)ConstructionType / tubes in faceFinned height (in)Finned length (in)Face area (ft²)Rows / fin spacing (fins/in)Number of feedsCasing constructionSupply connections (qty@in)Return connections (qty@in)Connection type
#1 5 W P 6 B - 22T x 76 LH 1 Section B - Coil A
A. Certified in accordance with the ARIForced-Circulation Air-Cooling and Air-HeatingCoils Certification Program, which is based onARI Standard-410.
A
#1381.4232.6
7,9750
4310.61
79.2 / 67.752.1 / 51.9
Actual
Water70.44.8
44.054.816.1
5 / 2235.176.018.5
6 / 1016
Air handler1@1 1/21@1 1/2
MPT
FAN CURVE • UMA # 14
Untitled • E.P.2-ESTE
Tuesday, January 21, 2003 Page 106 of 159 Version 3.70 - Released 5/13/2002 - VA01
Supply Fan Specification
Air handler model AHD2 FS 120 V M Air flow (ft³/min) 7,975Fan type Forward curved (standard/20-18) Static pressure @ Altitude (in w.g.) 1.48Style Draw-thru Rotations per minute 626Inlet vanes No Brake power @ Altitude (HP) 3.79Altitude (ft) 0 Coldest dry bulb (°F) 54.0
Fan Curve
Air flow (ft³/min)
Stat
ic p
ress
ure
@ A
ltitu
de (i
n w
.g.)
Brak
e po
wer
@ A
ltitu
de (H
P)
6,000 7,200 8,400 9,600 10,800 12,000 13,200 14,400
1.56
9.00
1.44
8.00
1.32
7.00
1.20
6.00
1.08
5.00
0.96
4.00
0.84
3.00
0.72
2.00
DRAWING • UMA # 14
Untitled • E.P.2-ESTE
Tuesday, January 21, 2003 Page 107 of 159 Version 3.70 - Released 5/13/2002 - VA01
Side
vie
w -
AH
D2
FS 1
20 V
M
Ente
ring
air v
iew
Leav
ing
air v
iew
This
dra
win
g is
not
to s
cale
; it i
s to
be
used
for d
imen
sion
al p
urpo
ses
only
.
42.0
in/1
,425
lb
58.0 in17.5
in24
.9 in
51.0
in/2
,789
lb
58.0 in
114.5 in
94.0
in
39.6
in22
.9 in
94.0
in
PERFORMANCE SUMMARY • UMA # 13
Untitled • E.P.2-OESTE
Tuesday, January 21, 2003 Page 108 of 159 Version 3.70 - Released 5/13/2002 - VA01
CS² Air Handler
Model # AHD2 FS 120 V M Insulation (entire unit) 2.00#Quantity 1 Wall thickness 2" (5.08 cm)Environment Indoor Sealed panels Positive pressure only
Notes
- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which isbased on ARI Standard-430.- See individual coil ratings for ARI certification information.- ETL listed & UL 1995 Approved.
A. Section 10F2 Flat filter section
Filter depth 2" (5.08 cm) Panel hand LeftFilter media Pleated 35% eff. Liners SolidAccess panels One Pressure drop (in w.g.) 0.16
B. Section 18 Internal face & bypass short coil section
Coil size Small Liners SolidDrain pan Standard Pressure drop (in w.g.) 1.05Maximum bypass air flow (ft³/min) 7,570
Refer to attached pages for coil performance.
C. Shipping split
D. Section 3 Vertical draw-thru fan section
Fan type Forward curved (standard) Total static @ Actual (in w.g.) 1.72Internal isolation Spring (standard) Brake power @ Actual (HP) 5.20Arrangement #3 Rotations per minute 681Motor type High Eff. TEFC Altitude (ft) 0Motor voltage 460V/3/60 Coldest dry bulb temp (°F) 54.0Motor power (HP) 7.50 Coil size LargeMotor hand Left Drain pan StandardDrive 150% HP Adjustable Access panels OneAir flow (ft³/min) 9,100 Panel hand LeftExternal static @ Actual (in w.g.) 0.50 Liners SolidInternal static @ Actual (in w.g.) 1.22
PERFORMANCE SUMMARY • UMA # 13
Untitled • E.P.2-OESTE
Tuesday, January 21, 2003 Page 109 of 159 Version 3.70 - Released 5/13/2002 - VA01
Air Handler Coils
Coil Tag Model # Qty Location Footnotes
CoilTotal capacity (MBH)Sensible capacity (MBH)Air PropertiesAir flow (ft³/min)Altitude (ft)Face velocity (ft/min)Air pressure drop (in w.g.)Entering air DB / WB (°F)Leaving air DB / WB (°F)Air properties measured atFluid PropertiesFluidFluid flow rate (gal/min)Fluid velocity (ft/s)Entering fluid temp. (°F)Leaving fluid temp. (°F)Fluid pressure drop (ft w.g.)ConstructionType / tubes in faceFinned height (in)Finned length (in)Face area (ft²)Rows / fin spacing (fins/in)Number of feedsCasing constructionSupply connections (qty@in)Return connections (qty@in)Connection type
#1 5 W P 6 B - 22T x 76 LH 1 Section B - Coil A
A. Certified in accordance with the ARIForced-Circulation Air-Cooling and Air-HeatingCoils Certification Program, which is based onARI Standard-410.
A
#1333.2232.5
9,1000
4920.74
76.3 / 64.752.7 / 52.4
Actual
Water59.34.0
44.055.311.9
5 / 2235.176.018.5
6 / 1016
Air handler1@1 1/21@1 1/2
MPT
FAN CURVE • UMA # 13
Untitled • E.P.2-OESTE
Tuesday, January 21, 2003 Page 110 of 159 Version 3.70 - Released 5/13/2002 - VA01
Supply Fan Specification
Air handler model AHD2 FS 120 V M Air flow (ft³/min) 9,100Fan type Forward curved (standard/20-18) Static pressure @ Altitude (in w.g.) 1.72Style Draw-thru Rotations per minute 681Inlet vanes No Brake power @ Altitude (HP) 5.20Altitude (ft) 0 Coldest dry bulb (°F) 54.0
Fan Curve
Air flow (ft³/min)
Stat
ic p
ress
ure
@ A
ltitu
de (i
n w
.g.)
Brak
e po
wer
@ A
ltitu
de (H
P)
6,000 7,500 9,000 10,500 12,000 13,500 15,000 16,500
1.80
12.0
0
1.65
10.8
0
1.50
9.60
1.35
8.40
1.20
7.20
1.05
6.00
0.90
4.80
0.75
3.60
DRAWING • UMA # 13
Untitled • E.P.2-OESTE
Tuesday, January 21, 2003 Page 111 of 159 Version 3.70 - Released 5/13/2002 - VA01
Side
vie
w -
AH
D2
FS 1
20 V
M
Ente
ring
air v
iew
Leav
ing
air v
iew
This
dra
win
g is
not
to s
cale
; it i
s to
be
used
for d
imen
sion
al p
urpo
ses
only
.
42.0
in/1
,425
lb
58.0 in17.5
in24
.9 in
51.0
in/2
,856
lb
58.0 in
114.5 in
94.0
in
39.6
in22
.9 in
94.0
in
PERFORMANCE SUMMARY • UMA # 12
Untitled • PISO 6-ESTE(FUTURO)
Tuesday, January 21, 2003 Page 112 of 159 Version 3.70 - Released 5/13/2002 - VA01
CS² Air Handler
Model # AHD2 FS 150 V M Insulation (entire unit) 2.00#Quantity 1 Wall thickness 2" (5.08 cm)Environment Indoor Sealed panels Positive pressure only
Notes
- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which isbased on ARI Standard-430.- See individual coil ratings for ARI certification information.- ETL listed & UL 1995 Approved.
A. Section 10F2 Flat filter section
Filter depth 2" (5.08 cm) Panel hand LeftFilter media Pleated 35% eff. Liners SolidAccess panels One Pressure drop (in w.g.) 0.12
B. Section 18 Internal face & bypass short coil section
Coil size Small Liners SolidDrain pan Standard Pressure drop (in w.g.) 0.84Maximum bypass air flow (ft³/min) 10,094
Refer to attached pages for coil performance.
C. Shipping split
D. Section 3 Vertical draw-thru fan section
Fan type Forward curved (standard) Total static @ Actual (in w.g.) 1.47Internal isolation Spring (standard) Brake power @ Actual (HP) 5.09Arrangement #3 Rotations per minute 586Motor type High Eff. TEFC Altitude (ft) 0Motor voltage 460V/3/60 Coldest dry bulb temp (°F) 54.0Motor power (HP) 7.50 Coil size LargeMotor hand Left Drain pan StandardDrive 150% HP Adjustable Access panels OneAir flow (ft³/min) 9,560 Panel hand LeftExternal static @ Actual (in w.g.) 0.50 Liners SolidInternal static @ Actual (in w.g.) 0.97
PERFORMANCE SUMMARY • UMA # 12
Untitled • PISO 6-ESTE(FUTURO)
Tuesday, January 21, 2003 Page 113 of 159 Version 3.70 - Released 5/13/2002 - VA01
Air Handler Coils
Coil Tag Model # Qty Location Footnotes
CoilTotal capacity (MBH)Sensible capacity (MBH)Air PropertiesAir flow (ft³/min)Altitude (ft)Face velocity (ft/min)Air pressure drop (in w.g.)Entering air DB / WB (°F)Leaving air DB / WB (°F)Air properties measured atFluid PropertiesFluidFluid flow rate (gal/min)Fluid velocity (ft/s)Entering fluid temp. (°F)Leaving fluid temp. (°F)Fluid pressure drop (ft w.g.)ConstructionType / tubes in faceFinned height (in)Finned length (in)Face area (ft²)Rows / fin spacing (fins/in)Number of feedsCasing constructionSupply connections (qty@in)Return connections (qty@in)Connection type
#1 5 W P 6 C - 28T x 76 LH 1 Section B - Coil A
A. Certified in accordance with the ARIForced-Circulation Air-Cooling and Air-HeatingCoils Certification Program, which is based onARI Standard-410.
A
#1377.2262.1
9,5600
4060.63
76.2 / 64.550.8 / 50.8
Actual
Water61.33.2
44.056.37.8
5 / 2844.676.023.6
6 / 1221
Air handler1@1 1/21@1 1/2
MPT
FAN CURVE • UMA # 12
Untitled • PISO 6-ESTE(FUTURO)
Tuesday, January 21, 2003 Page 114 of 159 Version 3.70 - Released 5/13/2002 - VA01
Supply Fan Specification
Air handler model AHD2 FS 150 V M Air flow (ft³/min) 9,560Fan type Forward curved (standard/22-15) Static pressure @ Altitude (in w.g.) 1.47Style Draw-thru Rotations per minute 586Inlet vanes No Brake power @ Altitude (HP) 5.09Altitude (ft) 0 Coldest dry bulb (°F) 54.0
Fan Curve
Air flow (ft³/min)
Stat
ic p
ress
ure
@ A
ltitu
de (i
n w
.g.)
Brak
e po
wer
@ A
ltitu
de (H
P)
6,000 7,200 8,400 9,600 10,800 12,000 13,200 14,400
1.80
10.0
0
1.60
9.00
1.40
8.00
1.20
7.00
1.00
6.00
0.80
5.00
0.60
4.00
0.40
3.00
DRAWING • UMA # 12
Untitled • PISO 6-ESTE(FUTURO)
Tuesday, January 21, 2003 Page 115 of 159 Version 3.70 - Released 5/13/2002 - VA01
Side
vie
w -
AH
D2
FS 1
50 V
M
Ente
ring
air v
iew
Leav
ing
air v
iew
This
dra
win
g is
not
to s
cale
; it i
s to
be
used
for d
imen
sion
al p
urpo
ses
only
.
42.0
in/1
,849
lb
72.0 in16.5
in27
.4 in
56.0
in/3
,141
lb
72.0 in
142.5 in
94.0
in
39.0
in20
.4 in
94.0
in
PERFORMANCE SUMMARY • UMA # 11
Untitled • PISO 6-OESTE ( FUTURO )
Tuesday, January 21, 2003 Page 116 of 159 Version 3.70 - Released 5/13/2002 - VA01
CS² Air Handler
Model # AHD2 FS 150 V M Insulation (entire unit) 2.00#Quantity 1 Wall thickness 2" (5.08 cm)Environment Indoor Sealed panels Positive pressure only
Notes
- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which isbased on ARI Standard-430.- See individual coil ratings for ARI certification information.- ETL listed & UL 1995 Approved.
A. Section 10F2 Flat filter section
Filter depth 2" (5.08 cm) Panel hand LeftFilter media Pleated 35% eff. Liners SolidAccess panels One Pressure drop (in w.g.) 0.13
B. Section 18 Internal face & bypass short coil section
Coil size Small Liners SolidDrain pan Standard Pressure drop (in w.g.) 0.81Maximum bypass air flow (ft³/min) 10,094
Refer to attached pages for coil performance.
C. Shipping split
D. Section 3 Vertical draw-thru fan section
Fan type Forward curved (standard) Total static @ Actual (in w.g.) 1.45Internal isolation Spring (standard) Brake power @ Actual (HP) 5.68Arrangement #3 Rotations per minute 594Motor type High Eff. TEFC Altitude (ft) 0Motor voltage 460V/3/60 Coldest dry bulb temp (°F) 54.0Motor power (HP) 7.50 Coil size LargeMotor hand Left Drain pan StandardDrive 150% HP Adjustable Access panels OneAir flow (ft³/min) 10,160 Panel hand LeftExternal static @ Actual (in w.g.) 0.50 Liners SolidInternal static @ Actual (in w.g.) 0.95
PERFORMANCE SUMMARY • UMA # 11
Untitled • PISO 6-OESTE ( FUTURO )
Tuesday, January 21, 2003 Page 117 of 159 Version 3.70 - Released 5/13/2002 - VA01
Air Handler Coils
Coil Tag Model # Qty Location Footnotes
CoilTotal capacity (MBH)Sensible capacity (MBH)Air PropertiesAir flow (ft³/min)Altitude (ft)Face velocity (ft/min)Air pressure drop (in w.g.)Entering air DB / WB (°F)Leaving air DB / WB (°F)Air properties measured atFluid PropertiesFluidFluid flow rate (gal/min)Fluid velocity (ft/s)Entering fluid temp. (°F)Leaving fluid temp. (°F)Fluid pressure drop (ft w.g.)ConstructionType / tubes in faceFinned height (in)Finned length (in)Face area (ft²)Rows / fin spacing (fins/in)Number of feedsCasing constructionSupply connections (qty@in)Return connections (qty@in)Connection type
#1 5 W P 5 C - 28T x 76 LH 1 Section B - Coil A
A. Certified in accordance with the ARIForced-Circulation Air-Cooling and Air-HeatingCoils Certification Program, which is based onARI Standard-410.
A
#1347.8256.2
10,1600
4310.58
75.9 / 64.152.6 / 52.5
Actual
Water61.42.9
44.055.35.1
5 / 2844.676.023.6
5 / 1223
Air handler1@1 1/21@1 1/2
MPT
FAN CURVE • UMA # 11
Untitled • PISO 6-OESTE ( FUTURO )
Tuesday, January 21, 2003 Page 118 of 159 Version 3.70 - Released 5/13/2002 - VA01
Supply Fan Specification
Air handler model AHD2 FS 150 V M Air flow (ft³/min) 10,160Fan type Forward curved (standard/22-15) Static pressure @ Altitude (in w.g.) 1.45Style Draw-thru Rotations per minute 594Inlet vanes No Brake power @ Altitude (HP) 5.68Altitude (ft) 0 Coldest dry bulb (°F) 54.0
Fan Curve
Air flow (ft³/min)
Stat
ic p
ress
ure
@ A
ltitu
de (i
n w
.g.)
Brak
e po
wer
@ A
ltitu
de (H
P)
6,000 7,200 8,400 9,600 10,800 12,000 13,200 14,400
1.80
10.0
0
1.60
9.00
1.40
8.00
1.20
7.00
1.00
6.00
0.80
5.00
0.60
4.00
0.40
3.00
DRAWING • UMA # 11
Untitled • PISO 6-OESTE ( FUTURO )
Tuesday, January 21, 2003 Page 119 of 159 Version 3.70 - Released 5/13/2002 - VA01
Side
vie
w -
AH
D2
FS 1
50 V
M
Ente
ring
air v
iew
Leav
ing
air v
iew
This
dra
win
g is
not
to s
cale
; it i
s to
be
used
for d
imen
sion
al p
urpo
ses
only
.
42.0
in/1
,746
lb
72.0 in16.5
in27
.4 in
56.0
in/3
,141
lb
72.0 in
142.5 in
94.0
in
39.0
in20
.4 in
94.0
in
PERFORMANCE SUMMARY • UMA # 10
Untitled • PISO 5-ESTE
Tuesday, January 21, 2003 Page 120 of 159 Version 3.70 - Released 5/13/2002 - VA01
CS² Air Handler
Model # AHD2 FS 120 V M Insulation (entire unit) 2.00#Quantity 1 Wall thickness 2" (5.08 cm)Environment Indoor Sealed panels Positive pressure only
Notes
- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which isbased on ARI Standard-430.- See individual coil ratings for ARI certification information.- ETL listed & UL 1995 Approved.
A. Section 10F2 Flat filter section
Filter depth 2" (5.08 cm) Panel hand LeftFilter media Pleated 35% eff. Liners SolidAccess panels One Pressure drop (in w.g.) 0.17
B. Section 18 Internal face & bypass short coil section
Coil size Small Liners SolidDrain pan Standard Pressure drop (in w.g.) 1.08Maximum bypass air flow (ft³/min) 7,570
Refer to attached pages for coil performance.
C. Shipping split
D. Section 3 Vertical draw-thru fan section
Fan type Forward curved (standard) Total static @ Actual (in w.g.) 1.75Internal isolation Spring (standard) Brake power @ Actual (HP) 5.41Arrangement #3 Rotations per minute 688Motor type High Eff. TEFC Altitude (ft) 0Motor voltage 460V/3/60 Coldest dry bulb temp (°F) 54.0Motor power (HP) 7.50 Coil size LargeMotor hand Left Drain pan StandardDrive 150% HP Adjustable Access panels OneAir flow (ft³/min) 9,250 Panel hand LeftExternal static @ Actual (in w.g.) 0.50 Liners SolidInternal static @ Actual (in w.g.) 1.25
PERFORMANCE SUMMARY • UMA # 10
Untitled • PISO 5-ESTE
Tuesday, January 21, 2003 Page 121 of 159 Version 3.70 - Released 5/13/2002 - VA01
Air Handler Coils
Coil Tag Model # Qty Location Footnotes
CoilTotal capacity (MBH)Sensible capacity (MBH)Air PropertiesAir flow (ft³/min)Altitude (ft)Face velocity (ft/min)Air pressure drop (in w.g.)Entering air DB / WB (°F)Leaving air DB / WB (°F)Air properties measured atFluid PropertiesFluidFluid flow rate (gal/min)Fluid velocity (ft/s)Entering fluid temp. (°F)Leaving fluid temp. (°F)Fluid pressure drop (ft w.g.)ConstructionType / tubes in faceFinned height (in)Finned length (in)Face area (ft²)Rows / fin spacing (fins/in)Number of feedsCasing constructionSupply connections (qty@in)Return connections (qty@in)Connection type
#1 5 W P 6 B - 22T x 76 LH 1 Section B - Coil A
A. Certified in accordance with the ARIForced-Circulation Air-Cooling and Air-HeatingCoils Certification Program, which is based onARI Standard-410.
A
#1342.1239.1
9,2500
5000.76
76.7 / 64.852.8 / 52.5
Actual
Water61.74.2
44.055.112.8
5 / 2235.176.018.5
6 / 1016
Air handler1@1 1/21@1 1/2
MPT
FAN CURVE • UMA # 10
Untitled • PISO 5-ESTE
Tuesday, January 21, 2003 Page 122 of 159 Version 3.70 - Released 5/13/2002 - VA01
Supply Fan Specification
Air handler model AHD2 FS 120 V M Air flow (ft³/min) 9,250Fan type Forward curved (standard/20-18) Static pressure @ Altitude (in w.g.) 1.75Style Draw-thru Rotations per minute 688Inlet vanes No Brake power @ Altitude (HP) 5.42Altitude (ft) 0 Coldest dry bulb (°F) 54.0
Fan Curve
Air flow (ft³/min)
Stat
ic p
ress
ure
@ A
ltitu
de (i
n w
.g.)
Brak
e po
wer
@ A
ltitu
de (H
P)
7,200 8,400 9,600 10,800 12,000 13,200 14,400 15,600
1.95
12.0
0
1.80
10.8
0
1.65
9.60
1.50
8.40
1.35
7.20
1.20
6.00
1.05
4.80
0.90
3.60
DRAWING • UMA # 10
Untitled • PISO 5-ESTE
Tuesday, January 21, 2003 Page 123 of 159 Version 3.70 - Released 5/13/2002 - VA01
Side
vie
w -
AH
D2
FS 1
20 V
M
Ente
ring
air v
iew
Leav
ing
air v
iew
This
dra
win
g is
not
to s
cale
; it i
s to
be
used
for d
imen
sion
al p
urpo
ses
only
.
42.0
in/1
,425
lb
58.0 in17.5
in24
.9 in
51.0
in/2
,856
lb
58.0 in
114.5 in
94.0
in
39.6
in22
.9 in
94.0
in
PERFORMANCE SUMMARY • UMA # 9
Untitled • PISO 5-OESTE
Tuesday, January 21, 2003 Page 124 of 159 Version 3.70 - Released 5/13/2002 - VA01
CS² Air Handler
Model # AHD2 FS 120 V M Insulation (entire unit) 2.00#Quantity 1 Wall thickness 2" (5.08 cm)Environment Indoor Sealed panels Positive pressure only
Notes
- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which isbased on ARI Standard-430.- See individual coil ratings for ARI certification information.- ETL listed & UL 1995 Approved.
A. Section 10F2 Flat filter section
Filter depth 2" (5.08 cm) Panel hand LeftFilter media Pleated 35% eff. Liners SolidAccess panels One Pressure drop (in w.g.) 0.16
B. Section 18 Internal face & bypass short coil section
Coil size Small Liners SolidDrain pan Standard Pressure drop (in w.g.) 1.16Maximum bypass air flow (ft³/min) 7,570
Refer to attached pages for coil performance.
C. Shipping split
D. Section 3 Vertical draw-thru fan section
Fan type Forward curved (standard) Total static @ Actual (in w.g.) 1.82Internal isolation Spring (standard) Brake power @ Actual (HP) 5.45Arrangement #3 Rotations per minute 699Motor type High Eff. TEFC Altitude (ft) 0Motor voltage 460V/3/60 Coldest dry bulb temp (°F) 54.0Motor power (HP) 7.50 Coil size LargeMotor hand Left Drain pan StandardDrive 150% HP Adjustable Access panels OneAir flow (ft³/min) 9,130 Panel hand LeftExternal static @ Actual (in w.g.) 0.50 Liners SolidInternal static @ Actual (in w.g.) 1.32
PERFORMANCE SUMMARY • UMA # 9
Untitled • PISO 5-OESTE
Tuesday, January 21, 2003 Page 125 of 159 Version 3.70 - Released 5/13/2002 - VA01
Air Handler Coils
Coil Tag Model # Qty Location Footnotes
CoilTotal capacity (MBH)Sensible capacity (MBH)Air PropertiesAir flow (ft³/min)Altitude (ft)Face velocity (ft/min)Air pressure drop (in w.g.)Entering air DB / WB (°F)Leaving air DB / WB (°F)Air properties measured atFluid PropertiesFluidFluid flow rate (gal/min)Fluid velocity (ft/s)Entering fluid temp. (°F)Leaving fluid temp. (°F)Fluid pressure drop (ft w.g.)ConstructionType / tubes in faceFinned height (in)Finned length (in)Face area (ft²)Rows / fin spacing (fins/in)Number of feedsCasing constructionSupply connections (qty@in)Return connections (qty@in)Connection type
#1 5 W P 6 C - 22T x 76 LH 1 Section B - Coil A
A. Certified in accordance with the ARIForced-Circulation Air-Cooling and Air-HeatingCoils Certification Program, which is based onARI Standard-410.
A
#1347.9243.8
9,1300
4930.85
76.3 / 64.651.6 / 51.6
Actual
Water58.64.0
44.055.911.6
5 / 2235.176.018.5
6 / 1216
Air handler1@1 1/21@1 1/2
MPT
FAN CURVE • UMA # 9
Untitled • PISO 5-OESTE
Tuesday, January 21, 2003 Page 126 of 159 Version 3.70 - Released 5/13/2002 - VA01
Supply Fan Specification
Air handler model AHD2 FS 120 V M Air flow (ft³/min) 9,130Fan type Forward curved (standard/20-18) Static pressure @ Altitude (in w.g.) 1.82Style Draw-thru Rotations per minute 699Inlet vanes No Brake power @ Altitude (HP) 5.45Altitude (ft) 0 Coldest dry bulb (°F) 54.0
Fan Curve
Air flow (ft³/min)
Stat
ic p
ress
ure
@ A
ltitu
de (i
n w
.g.)
Brak
e po
wer
@ A
ltitu
de (H
P)
7,200 8,400 9,600 10,800 12,000 13,200 14,400 15,600
1.95
13.5
0
1.80
12.0
0
1.65
10.5
0
1.50
9.00
1.35
7.50
1.20
6.00
1.05
4.50
0.90
3.00
DRAWING • UMA # 9
Untitled • PISO 5-OESTE
Tuesday, January 21, 2003 Page 127 of 159 Version 3.70 - Released 5/13/2002 - VA01
Side
vie
w -
AH
D2
FS 1
20 V
M
Ente
ring
air v
iew
Leav
ing
air v
iew
This
dra
win
g is
not
to s
cale
; it i
s to
be
used
for d
imen
sion
al p
urpo
ses
only
.
42.0
in/1
,458
lb
58.0 in17.5
in24
.9 in
51.0
in/2
,856
lb
58.0 in
114.5 in
94.0
in
39.6
in22
.9 in
94.0
in
PERFORMANCE SUMMARY • UMA # 8
Untitled • PISO 4-OESTE
Tuesday, January 21, 2003 Page 128 of 159 Version 3.70 - Released 5/13/2002 - VA01
CS² Air Handler
Model # AHD2 FS 150 V M Insulation (entire unit) 2.00#Quantity 1 Wall thickness 2" (5.08 cm)Environment Indoor Sealed panels Positive pressure only
Notes
- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which isbased on ARI Standard-430.- See individual coil ratings for ARI certification information.- ETL listed & UL 1995 Approved.
A. Section 10F2 Flat filter section
Filter depth 2" (5.08 cm) Panel hand LeftFilter media Pleated 35% eff. Liners SolidAccess panels One Pressure drop (in w.g.) 0.15
B. Section 18 Internal face & bypass short coil section
Coil size Small Liners SolidDrain pan Standard Pressure drop (in w.g.) 0.94Maximum bypass air flow (ft³/min) 10,094
Refer to attached pages for coil performance.
C. Shipping split
D. Section 3 Vertical draw-thru fan section
Fan type Forward curved (standard) Total static @ Actual (in w.g.) 1.59Internal isolation Spring (standard) Brake power @ Actual (HP) 7.07Arrangement #3 Rotations per minute 632Motor type High Eff. TEFC Altitude (ft) 0Motor voltage 460V/3/60 Coldest dry bulb temp (°F) 54.0Motor power (HP) 7.50 Coil size LargeMotor hand Left Drain pan StandardDrive 150% HP Adjustable Access panels OneAir flow (ft³/min) 11,080 Panel hand LeftExternal static @ Actual (in w.g.) 0.50 Liners SolidInternal static @ Actual (in w.g.) 1.09
PERFORMANCE SUMMARY • UMA # 8
Untitled • PISO 4-OESTE
Tuesday, January 21, 2003 Page 129 of 159 Version 3.70 - Released 5/13/2002 - VA01
Air Handler Coils
Coil Tag Model # Qty Location Footnotes
CoilTotal capacity (MBH)Sensible capacity (MBH)Air PropertiesAir flow (ft³/min)Altitude (ft)Face velocity (ft/min)Air pressure drop (in w.g.)Entering air DB / WB (°F)Leaving air DB / WB (°F)Air properties measured atFluid PropertiesFluidFluid flow rate (gal/min)Fluid velocity (ft/s)Entering fluid temp. (°F)Leaving fluid temp. (°F)Fluid pressure drop (ft w.g.)ConstructionType / tubes in faceFinned height (in)Finned length (in)Face area (ft²)Rows / fin spacing (fins/in)Number of feedsCasing constructionSupply connections (qty@in)Return connections (qty@in)Connection type
#1 5 W P 5 C - 28T x 76 LH 1 Section B - Coil A
A. Certified in accordance with the ARIForced-Circulation Air-Cooling and Air-HeatingCoils Certification Program, which is based onARI Standard-410.
A
#1406.6287.7
11,0800
4700.65
76.9 / 65.052.8 / 52.7
Actual
Water75.23.5
44.054.87.3
5 / 2844.676.023.6
5 / 1223
Air handler1@1 1/21@1 1/2
MPT
FAN CURVE • UMA # 8
Untitled • PISO 4-OESTE
Tuesday, January 21, 2003 Page 130 of 159 Version 3.70 - Released 5/13/2002 - VA01
Supply Fan Specification
Air handler model AHD2 FS 150 V M Air flow (ft³/min) 11,080Fan type Forward curved (standard/22-15) Static pressure @ Altitude (in w.g.) 1.59Style Draw-thru Rotations per minute 632Inlet vanes No Brake power @ Altitude (HP) 7.07Altitude (ft) 0 Coldest dry bulb (°F) 54.0
Fan Curve
Air flow (ft³/min)
Stat
ic p
ress
ure
@ A
ltitu
de (i
n w
.g.)
Brak
e po
wer
@ A
ltitu
de (H
P)
7,200 8,400 9,600 10,800 12,000 13,200 14,400 15,600
2.00
12.0
0
1.80
10.8
0
1.60
9.60
1.40
8.40
1.20
7.20
1.00
6.00
0.80
4.80
0.60
3.60
DRAWING • UMA # 8
Untitled • PISO 4-OESTE
Tuesday, January 21, 2003 Page 131 of 159 Version 3.70 - Released 5/13/2002 - VA01
Side
vie
w -
AH
D2
FS 1
50 V
M
Ente
ring
air v
iew
Leav
ing
air v
iew
This
dra
win
g is
not
to s
cale
; it i
s to
be
used
for d
imen
sion
al p
urpo
ses
only
.
42.0
in/1
,746
lb
72.0 in16.5
in27
.4 in
56.0
in/3
,141
lb
72.0 in
142.5 in
94.0
in
39.0
in20
.4 in
94.0
in
PERFORMANCE SUMMARY • UMA # 7
Untitled • PISO 4-OESTE
Tuesday, January 21, 2003 Page 132 of 159 Version 3.70 - Released 5/13/2002 - VA01
CS² Air Handler
Model # AHD2 FS 080 H M Insulation (entire unit) 2.00#Quantity 1 Wall thickness 2" (5.08 cm)Environment Indoor Sealed panels Positive pressure only
Notes
- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which isbased on ARI Standard-430.- See individual coil ratings for ARI certification information.- ETL listed & UL 1995 Approved.
A. Section 13 Cartridge/bag
Filter depth 12" (30.48 cm) Panel hand LeftFilter media Supplied by other Liners SolidPre-filter media 2" Pleated 35% eff. Pressure drop (in w.g.) 0.24Access panels One
B. Section 20 External face & bypass section
Liners Solid Pressure drop (in w.g.) 0.30
C. Section 7 Short cooling coil section
Coil size Large Liners SolidDrain pan Standard Pressure drop (in w.g.) 0.96
Refer to attached pages for coil performance.
D. Section 1 Horizontal draw-thru fan section
Fan type Forward curved (standard) Internal static @ Actual (in w.g.) 1.50Internal isolation Spring (standard) Total static @ Actual (in w.g.) 2.50Arrangement #3 Brake power @ Actual (HP) 7.47Motor type High Eff. TEFC Rotations per minute 1,134Motor voltage 460V/3/60 Altitude (ft) 0Motor power (HP) 7.50 Coldest dry bulb temp (°F) 54.0Motor hand Left Access panels OneDrive 150% HP Adjustable Panel hand LeftAir flow (ft³/min) 7,680 Liners SolidExternal static @ Actual (in w.g.) 1.00
PERFORMANCE SUMMARY • UMA # 7
Untitled • PISO 4-OESTE
Tuesday, January 21, 2003 Page 133 of 159 Version 3.70 - Released 5/13/2002 - VA01
Air Handler Coils
Coil Tag Model # Qty Location Footnotes
CoilTotal capacity (MBH)Sensible capacity (MBH)Air PropertiesAir flow (ft³/min)Altitude (ft)Face velocity (ft/min)Air pressure drop (in w.g.)Entering air DB / WB (°F)Leaving air DB / WB (°F)Air properties measured atFluid PropertiesFluidFluid flow rate (gal/min)Fluid velocity (ft/s)Entering fluid temp. (°F)Leaving fluid temp. (°F)Fluid pressure drop (ft w.g.)ConstructionType / tubes in faceFinned height (in)Finned length (in)Face area (ft²)Rows / fin spacing (fins/in)Number of feedsCasing constructionSupply connections (qty@in)Return connections (qty@in)Connection type
#1 5 W F 8 B - 23T x 62 LH 1 Section C - Coil A
A. Certified in accordance with the ARIForced-Circulation Air-Cooling and Air-HeatingCoils Certification Program, which is based onARI Standard-410.
A
#1616.7281.6
7,6800
4870.96
85.8 / 75.751.3 / 51.3
Actual
Water112.9
5.344.054.917.0
5 / 2336.762.015.8
8 / 1023
Air handler1@2 1@2 MPT
FAN CURVE • UMA # 7
Untitled • PISO 4-OESTE
Tuesday, January 21, 2003 Page 134 of 159 Version 3.70 - Released 5/13/2002 - VA01
Supply Fan Specification
Air handler model AHD2 FS 080 H M Air flow (ft³/min) 7,680Fan type Forward curved (standard/15-15) Static pressure @ Altitude (in w.g.) 2.50Style Draw-thru Rotations per minute 1,134Inlet vanes No Brake power @ Altitude (HP) 7.47Altitude (ft) 0 Coldest dry bulb (°F) 54.0
Fan Curve
Air flow (ft³/min)
Stat
ic p
ress
ure
@ A
ltitu
de (i
n w
.g.)
Brak
e po
wer
@ A
ltitu
de (H
P)
4,000 5,000 6,000 7,000 8,000 9,000 10,000 11,000
3.00
13.5
0
2.70
12.0
0
2.40
10.5
0
2.10
9.00
1.80
7.50
1.50
6.00
1.20
4.50
0.90
3.00
DRAWING • UMA # 7
Untitled • PISO 4-OESTE
Tuesday, January 21, 2003 Page 135 of 159 Version 3.70 - Released 5/13/2002 - VA01
Side
vie
w -
AH
D2
FS 0
80 H
M
Ente
ring
air v
iew
Leav
ing
air v
iew
This
dra
win
g is
not
to s
cale
; it i
s to
be
used
for d
imen
sion
al p
urpo
ses
only
.
5.2 in16.0 in
123.
5 in
/2,7
05 lb
51.0 in
51.0 in
78.0
in
37.0
in18
.8 in
78.0
in
PERFORMANCE SUMMARY • UMA # 6
Untitled • PISO 3-ESTE
Tuesday, January 21, 2003 Page 136 of 159 Version 3.70 - Released 5/13/2002 - VA01
CS² Air Handler
Model # AHD2 FS 150 V M Insulation (entire unit) 2.00#Quantity 1 Wall thickness 2" (5.08 cm)Environment Indoor Sealed panels Positive pressure only
Notes
- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which isbased on ARI Standard-430.- See individual coil ratings for ARI certification information.- ETL listed & UL 1995 Approved.
A. Section 10F2 Flat filter section
Filter depth 2" (5.08 cm) Panel hand LeftFilter media Pleated 35% eff. Liners SolidAccess panels One Pressure drop (in w.g.) 0.12
B. Section 18 Internal face & bypass short coil section
Coil size Small Liners SolidDrain pan Standard Pressure drop (in w.g.) 0.87Maximum bypass air flow (ft³/min) 10,094
Refer to attached pages for coil performance.
C. Shipping split
D. Section 3 Vertical draw-thru fan section
Fan type Forward curved (standard) Total static @ Actual (in w.g.) 1.49Internal isolation Spring (standard) Brake power @ Actual (HP) 5.31Arrangement #3 Rotations per minute 592Motor type High Eff. TEFC Altitude (ft) 0Motor voltage 460V/3/60 Coldest dry bulb temp (°F) 54.0Motor power (HP) 7.50 Coil size LargeMotor hand Left Drain pan StandardDrive 150% HP Adjustable Access panels OneAir flow (ft³/min) 9,730 Panel hand LeftExternal static @ Actual (in w.g.) 0.50 Liners SolidInternal static @ Actual (in w.g.) 0.99
PERFORMANCE SUMMARY • UMA # 6
Untitled • PISO 3-ESTE
Tuesday, January 21, 2003 Page 137 of 159 Version 3.70 - Released 5/13/2002 - VA01
Air Handler Coils
Coil Tag Model # Qty Location Footnotes
CoilTotal capacity (MBH)Sensible capacity (MBH)Air PropertiesAir flow (ft³/min)Altitude (ft)Face velocity (ft/min)Air pressure drop (in w.g.)Entering air DB / WB (°F)Leaving air DB / WB (°F)Air properties measured atFluid PropertiesFluidFluid flow rate (gal/min)Fluid velocity (ft/s)Entering fluid temp. (°F)Leaving fluid temp. (°F)Fluid pressure drop (ft w.g.)ConstructionType / tubes in faceFinned height (in)Finned length (in)Face area (ft²)Rows / fin spacing (fins/in)Number of feedsCasing constructionSupply connections (qty@in)Return connections (qty@in)Connection type
#1 5 W F 6 C - 28T x 76 LH 1 Section B - Coil A
A. Certified in accordance with the ARIForced-Circulation Air-Cooling and Air-HeatingCoils Certification Program, which is based onARI Standard-410.
A
#1463.5288.3
9,7300
4130.65
78.8 / 67.251.3 / 51.3
Actual
Water82.93.2
44.055.26.1
5 / 2844.676.023.6
6 / 1228
Air handler1@2 1@2 MPT
FAN CURVE • UMA # 6
Untitled • PISO 3-ESTE
Tuesday, January 21, 2003 Page 138 of 159 Version 3.70 - Released 5/13/2002 - VA01
Supply Fan Specification
Air handler model AHD2 FS 150 V M Air flow (ft³/min) 9,730Fan type Forward curved (standard/22-15) Static pressure @ Altitude (in w.g.) 1.49Style Draw-thru Rotations per minute 592Inlet vanes No Brake power @ Altitude (HP) 5.31Altitude (ft) 0 Coldest dry bulb (°F) 54.0
Fan Curve
Air flow (ft³/min)
Stat
ic p
ress
ure
@ A
ltitu
de (i
n w
.g.)
Brak
e po
wer
@ A
ltitu
de (H
P)
6,000 7,200 8,400 9,600 10,800 12,000 13,200 14,400
1.80
10.0
0
1.60
9.00
1.40
8.00
1.20
7.00
1.00
6.00
0.80
5.00
0.60
4.00
0.40
3.00
DRAWING • UMA # 6
Untitled • PISO 3-ESTE
Tuesday, January 21, 2003 Page 139 of 159 Version 3.70 - Released 5/13/2002 - VA01
Side
vie
w -
AH
D2
FS 1
50 V
M
Ente
ring
air v
iew
Leav
ing
air v
iew
This
dra
win
g is
not
to s
cale
; it i
s to
be
used
for d
imen
sion
al p
urpo
ses
only
.
42.0
in/1
,849
lb
72.0 in16.5
in27
.4 in
56.0
in/3
,141
lb
72.0 in
142.5 in
94.0
in
39.0
in20
.4 in
94.0
in
PERFORMANCE SUMMARY • UMA # 5
Untitled • PISO 3-OESTE
Tuesday, January 21, 2003 Page 140 of 159 Version 3.70 - Released 5/13/2002 - VA01
CS² Air Handler
Model # AHD2 FS 120 V M Insulation (entire unit) 2.00#Quantity 1 Wall thickness 2" (5.08 cm)Environment Indoor Sealed panels Positive pressure only
Notes
- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which isbased on ARI Standard-430.- See individual coil ratings for ARI certification information.- ETL listed & UL 1995 Approved.
A. Section 10F2 Flat filter section
Filter depth 2" (5.08 cm) Panel hand LeftFilter media Pleated 35% eff. Liners SolidAccess panels One Pressure drop (in w.g.) 0.15
B. Section 18 Internal face & bypass short coil section
Coil size Small Liners SolidDrain pan Standard Pressure drop (in w.g.) 0.97Maximum bypass air flow (ft³/min) 7,570
Refer to attached pages for coil performance.
C. Shipping split
D. Section 3 Vertical draw-thru fan section
Fan type Forward curved (standard) Total static @ Actual (in w.g.) 1.62Internal isolation Spring (standard) Brake power @ Actual (HP) 4.64Arrangement #3 Rotations per minute 660Motor type High Eff. TEFC Altitude (ft) 0Motor voltage 460V/3/60 Coldest dry bulb temp (°F) 54.0Motor power (HP) 5.00 Coil size LargeMotor hand Left Drain pan StandardDrive 150% HP Adjustable Access panels OneAir flow (ft³/min) 8,680 Panel hand LeftExternal static @ Actual (in w.g.) 0.50 Liners SolidInternal static @ Actual (in w.g.) 1.12
PERFORMANCE SUMMARY • UMA # 5
Untitled • PISO 3-OESTE
Tuesday, January 21, 2003 Page 141 of 159 Version 3.70 - Released 5/13/2002 - VA01
Air Handler Coils
Coil Tag Model # Qty Location Footnotes
CoilTotal capacity (MBH)Sensible capacity (MBH)Air PropertiesAir flow (ft³/min)Altitude (ft)Face velocity (ft/min)Air pressure drop (in w.g.)Entering air DB / WB (°F)Leaving air DB / WB (°F)Air properties measured atFluid PropertiesFluidFluid flow rate (gal/min)Fluid velocity (ft/s)Entering fluid temp. (°F)Leaving fluid temp. (°F)Fluid pressure drop (ft w.g.)ConstructionType / tubes in faceFinned height (in)Finned length (in)Face area (ft²)Rows / fin spacing (fins/in)Number of feedsCasing constructionSupply connections (qty@in)Return connections (qty@in)Connection type
#1 5 W P 6 B - 22T x 76 LH 1 Section B - Coil A
A. Certified in accordance with the ARIForced-Circulation Air-Cooling and Air-HeatingCoils Certification Program, which is based onARI Standard-410.
A
#1336.1228.2
8,6800
4690.69
76.8 / 65.252.5 / 52.3
Actual
Water60.24.1
44.055.212.2
5 / 2235.176.018.5
6 / 1016
Air handler1@1 1/21@1 1/2
MPT
FAN CURVE • UMA # 5
Untitled • PISO 3-OESTE
Tuesday, January 21, 2003 Page 142 of 159 Version 3.70 - Released 5/13/2002 - VA01
Supply Fan Specification
Air handler model AHD2 FS 120 V M Air flow (ft³/min) 8,680Fan type Forward curved (standard/20-18) Static pressure @ Altitude (in w.g.) 1.62Style Draw-thru Rotations per minute 660Inlet vanes No Brake power @ Altitude (HP) 4.64Altitude (ft) 0 Coldest dry bulb (°F) 54.0
Fan Curve
Air flow (ft³/min)
Stat
ic p
ress
ure
@ A
ltitu
de (i
n w
.g.)
Brak
e po
wer
@ A
ltitu
de (H
P)
6,000 7,500 9,000 10,500 12,000 13,500 15,000 16,500
1.80
10.8
0
1.65
9.60
1.50
8.40
1.35
7.20
1.20
6.00
1.05
4.80
0.90
3.60
0.75
2.40
DRAWING • UMA # 5
Untitled • PISO 3-OESTE
Tuesday, January 21, 2003 Page 143 of 159 Version 3.70 - Released 5/13/2002 - VA01
Side
vie
w -
AH
D2
FS 1
20 V
M
Ente
ring
air v
iew
Leav
ing
air v
iew
This
dra
win
g is
not
to s
cale
; it i
s to
be
used
for d
imen
sion
al p
urpo
ses
only
.
42.0
in/1
,425
lb
58.0 in17.5
in24
.9 in
51.0
in/2
,789
lb
58.0 in
114.5 in
94.0
in
39.6
in22
.9 in
94.0
in
PERFORMANCE SUMMARY • UMA # 4
Untitled • PISO 2-ESTE
Tuesday, January 21, 2003 Page 144 of 159 Version 3.70 - Released 5/13/2002 - VA01
CS² Air Handler
Model # AHD2 FS 100 H M Insulation (entire unit) 2.00#Quantity 1 Wall thickness 2" (5.08 cm)Environment Indoor Sealed panels Positive pressure only
Notes
- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which isbased on ARI Standard-430.- See individual coil ratings for ARI certification information.- ETL listed & UL 1995 Approved.
A. Section 10F2 Flat filter section
Filter depth 2" (5.08 cm) Panel hand LeftFilter media Pleated 35% eff. Liners SolidAccess panels One Pressure drop (in w.g.) 0.22
B. Section 20 External face & bypass section
Liners Solid Pressure drop (in w.g.) 0.28
C. Section 7 Short cooling coil section
Coil size Large Liners SolidDrain pan Standard Pressure drop (in w.g.) 0.59
Refer to attached pages for coil performance.
D. Section 1 Horizontal draw-thru fan section
Fan type Forward curved (standard) Internal static @ Actual (in w.g.) 1.09Internal isolation Spring (standard) Total static @ Actual (in w.g.) 1.59Arrangement #3 Brake power @ Actual (HP) 6.42Motor type High Eff. TEFC Rotations per minute 812Motor voltage 460V/3/60 Altitude (ft) 0Motor power (HP) 7.50 Coldest dry bulb temp (°F) 70.0Motor hand Left Access panels OneDrive 150% HP Adjustable Panel hand LeftAir flow (ft³/min) 9,155 Liners SolidExternal static @ Actual (in w.g.) 0.50
PERFORMANCE SUMMARY • UMA # 4
Untitled • PISO 2-ESTE
Tuesday, January 21, 2003 Page 145 of 159 Version 3.70 - Released 5/13/2002 - VA01
Air Handler Coils
Coil Tag Model # Qty Location Footnotes
CoilTotal capacity (MBH)Sensible capacity (MBH)Air PropertiesAir flow (ft³/min)Altitude (ft)Face velocity (ft/min)Air pressure drop (in w.g.)Entering air DB / WB (°F)Leaving air DB / WB (°F)Air properties measured atFluid PropertiesFluidFluid flow rate (gal/min)Fluid velocity (ft/s)Entering fluid temp. (°F)Leaving fluid temp. (°F)Fluid pressure drop (ft w.g.)ConstructionType / tubes in faceFinned height (in)Finned length (in)Face area (ft²)Rows / fin spacing (fins/in)Number of feedsCasing constructionSupply connections (qty@in)Return connections (qty@in)Connection type
#1 5 W H 5 B - 28T x 62 LH 1 Section C - Coil A
A. Certified in accordance with the ARIForced-Circulation Air-Cooling and Air-HeatingCoils Certification Program, which is based onARI Standard-410.
A
#1325.2232.1
9,1550
4760.59
76.8 / 64.853.3 / 52.8
Actual
Water61.34.7
44.054.617.1
5 / 2844.662.019.2
5 / 1014
Air handler1@1 1/21@1 1/2
MPT
FAN CURVE • UMA # 4
Untitled • PISO 2-ESTE
Tuesday, January 21, 2003 Page 146 of 159 Version 3.70 - Released 5/13/2002 - VA01
Supply Fan Specification
Air handler model AHD2 FS 100 H M Air flow (ft³/min) 9,155Fan type Forward curved (standard/18-18) Static pressure @ Altitude (in w.g.) 1.59Style Draw-thru Rotations per minute 812Inlet vanes No Brake power @ Altitude (HP) 6.42Altitude (ft) 0 Coldest dry bulb (°F) 70.0
Fan Curve
Air flow (ft³/min)
Stat
ic p
ress
ure
@ A
ltitu
de (i
n w
.g.)
Brak
e po
wer
@ A
ltitu
de (H
P)
4,800 6,000 7,200 8,400 9,600 10,800 12,000 13,200
1.95
10.8
0
1.80
9.60
1.65
8.40
1.50
7.20
1.35
6.00
1.20
4.80
1.05
3.60
0.90
2.40
DRAWING • UMA # 4
Untitled • PISO 2-ESTE
Tuesday, January 21, 2003 Page 147 of 159 Version 3.70 - Released 5/13/2002 - VA01
Side
vie
w -
AH
D2
FS 1
00 H
M
Ente
ring
air v
iew
Leav
ing
air v
iew
This
dra
win
g is
not
to s
cale
; it i
s to
be
used
for d
imen
sion
al p
urpo
ses
only
.
8.6 in19.0 in
113.
0 in
/2,9
93 lb
58.0 in
58.0 in
78.0
in
36.0
in22
.0 in
78.0
in
PERFORMANCE SUMMARY • UMA # 3
Untitled • PISO 2-OESTE
Tuesday, January 21, 2003 Page 148 of 159 Version 3.70 - Released 5/13/2002 - VA01
CS² Air Handler
Model # AHD2 FS 120 V M Insulation (entire unit) 2.00#Quantity 1 Wall thickness 2" (5.08 cm)Environment Indoor Sealed panels Positive pressure only
Notes
- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which isbased on ARI Standard-430.- See individual coil ratings for ARI certification information.- ETL listed & UL 1995 Approved.
A. Section 10F2 Flat filter section
Filter depth 2" (5.08 cm) Panel hand LeftFilter media Pleated 35% eff. Liners SolidAccess panels One Pressure drop (in w.g.) 0.14
B. Section 18 Internal face & bypass short coil section
Coil size Small Liners SolidDrain pan Standard Pressure drop (in w.g.) 0.93Maximum bypass air flow (ft³/min) 7,570
Refer to attached pages for coil performance.
C. Shipping split
D. Section 3 Vertical draw-thru fan section
Fan type Forward curved (standard) Total static @ Actual (in w.g.) 1.57Internal isolation Spring (standard) Brake power @ Actual (HP) 4.32Arrangement #3 Rotations per minute 648Motor type High Eff. TEFC Altitude (ft) 0Motor voltage 460V/3/60 Coldest dry bulb temp (°F) 54.0Motor power (HP) 5.00 Coil size LargeMotor hand Left Drain pan StandardDrive 150% HP Adjustable Access panels OneAir flow (ft³/min) 8,430 Panel hand LeftExternal static @ Actual (in w.g.) 0.50 Liners SolidInternal static @ Actual (in w.g.) 1.07
PERFORMANCE SUMMARY • UMA # 3
Untitled • PISO 2-OESTE
Tuesday, January 21, 2003 Page 149 of 159 Version 3.70 - Released 5/13/2002 - VA01
Air Handler Coils
Coil Tag Model # Qty Location Footnotes
CoilTotal capacity (MBH)Sensible capacity (MBH)Air PropertiesAir flow (ft³/min)Altitude (ft)Face velocity (ft/min)Air pressure drop (in w.g.)Entering air DB / WB (°F)Leaving air DB / WB (°F)Air properties measured atFluid PropertiesFluidFluid flow rate (gal/min)Fluid velocity (ft/s)Entering fluid temp. (°F)Leaving fluid temp. (°F)Fluid pressure drop (ft w.g.)ConstructionType / tubes in faceFinned height (in)Finned length (in)Face area (ft²)Rows / fin spacing (fins/in)Number of feedsCasing constructionSupply connections (qty@in)Return connections (qty@in)Connection type
#1 5 W P 6 B - 22T x 76 LH 1 Section B - Coil A
A. Certified in accordance with the ARIForced-Circulation Air-Cooling and Air-HeatingCoils Certification Program, which is based onARI Standard-410.
A
#1360.1231.3
8,4300
4560.66
77.7 / 66.452.2 / 52.1
Actual
Water65.04.4
44.055.114.0
5 / 2235.176.018.5
6 / 1016
Air handler1@1 1/21@1 1/2
MPT
FAN CURVE • UMA # 3
Untitled • PISO 2-OESTE
Tuesday, January 21, 2003 Page 150 of 159 Version 3.70 - Released 5/13/2002 - VA01
Supply Fan Specification
Air handler model AHD2 FS 120 V M Air flow (ft³/min) 8,430Fan type Forward curved (standard/20-18) Static pressure @ Altitude (in w.g.) 1.57Style Draw-thru Rotations per minute 648Inlet vanes No Brake power @ Altitude (HP) 4.32Altitude (ft) 0 Coldest dry bulb (°F) 54.0
Fan Curve
Air flow (ft³/min)
Stat
ic p
ress
ure
@ A
ltitu
de (i
n w
.g.)
Brak
e po
wer
@ A
ltitu
de (H
P)
6,000 7,200 8,400 9,600 10,800 12,000 13,200 14,400
1.80
10.0
0
1.65
9.00
1.50
8.00
1.35
7.00
1.20
6.00
1.05
5.00
0.90
4.00
0.75
3.00
DRAWING • UMA # 3
Untitled • PISO 2-OESTE
Tuesday, January 21, 2003 Page 151 of 159 Version 3.70 - Released 5/13/2002 - VA01
Side
vie
w -
AH
D2
FS 1
20 V
M
Ente
ring
air v
iew
Leav
ing
air v
iew
This
dra
win
g is
not
to s
cale
; it i
s to
be
used
for d
imen
sion
al p
urpo
ses
only
.
42.0
in/1
,425
lb
58.0 in17.5
in24
.9 in
51.0
in/2
,789
lb
58.0 in
114.5 in
94.0
in
39.6
in22
.9 in
94.0
in
PERFORMANCE SUMMARY • UMA # 2
Untitled • PISO 1- ESTE
Tuesday, January 21, 2003 Page 152 of 159 Version 3.70 - Released 5/13/2002 - VA01
CS² Air Handler
Model # AHD2 FS 150 V M Insulation (entire unit) 2.00#Quantity 1 Wall thickness 2" (5.08 cm)Environment Indoor Sealed panels Positive pressure only
Notes
- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which isbased on ARI Standard-430.- See individual coil ratings for ARI certification information.- ETL listed & UL 1995 Approved.
A. Section 10F2 Flat filter section
Filter depth 2" (5.08 cm) Panel hand LeftFilter media Pleated 35% eff. Liners SolidAccess panels One Pressure drop (in w.g.) 0.12
B. Section 18 Internal face & bypass short coil section
Coil size Small Liners SolidDrain pan Standard Pressure drop (in w.g.) 0.82Maximum bypass air flow (ft³/min) 10,094
Refer to attached pages for coil performance.
C. Shipping split
D. Section 3 Vertical draw-thru fan section
Fan type Forward curved (standard) Total static @ Actual (in w.g.) 1.44Internal isolation Spring (standard) Brake power @ Actual (HP) 4.91Arrangement #3 Rotations per minute 580Motor type High Eff. TEFC Altitude (ft) 0Motor voltage 460V/3/60 Coldest dry bulb temp (°F) 54.0Motor power (HP) 5.00 Coil size LargeMotor hand Left Drain pan StandardDrive 150% HP Adjustable Access panels OneAir flow (ft³/min) 9,420 Panel hand LeftExternal static @ Actual (in w.g.) 0.50 Liners SolidInternal static @ Actual (in w.g.) 0.94
PERFORMANCE SUMMARY • UMA # 2
Untitled • PISO 1- ESTE
Tuesday, January 21, 2003 Page 153 of 159 Version 3.70 - Released 5/13/2002 - VA01
Air Handler Coils
Coil Tag Model # Qty Location Footnotes
CoilTotal capacity (MBH)Sensible capacity (MBH)Air PropertiesAir flow (ft³/min)Altitude (ft)Face velocity (ft/min)Air pressure drop (in w.g.)Entering air DB / WB (°F)Leaving air DB / WB (°F)Air properties measured atFluid PropertiesFluidFluid flow rate (gal/min)Fluid velocity (ft/s)Entering fluid temp. (°F)Leaving fluid temp. (°F)Fluid pressure drop (ft w.g.)ConstructionType / tubes in faceFinned height (in)Finned length (in)Face area (ft²)Rows / fin spacing (fins/in)Number of feedsCasing constructionSupply connections (qty@in)Return connections (qty@in)Connection type
#1 5 W P 6 C - 28T x 76 LH 1 Section B - Coil A
A. Certified in accordance with the ARIForced-Circulation Air-Cooling and Air-HeatingCoils Certification Program, which is based onARI Standard-410.
A
#1390.3263.9
9,4200
4000.62
76.9 / 65.050.9 / 50.9
Actual
Water64.23.3
44.056.28.5
5 / 2844.676.023.6
6 / 1221
Air handler1@1 1/21@1 1/2
MPT
FAN CURVE • UMA # 2
Untitled • PISO 1- ESTE
Tuesday, January 21, 2003 Page 154 of 159 Version 3.70 - Released 5/13/2002 - VA01
Supply Fan Specification
Air handler model AHD2 FS 150 V M Air flow (ft³/min) 9,420Fan type Forward curved (standard/22-15) Static pressure @ Altitude (in w.g.) 1.44Style Draw-thru Rotations per minute 580Inlet vanes No Brake power @ Altitude (HP) 4.91Altitude (ft) 0 Coldest dry bulb (°F) 54.0
Fan Curve
Air flow (ft³/min)
Stat
ic p
ress
ure
@ A
ltitu
de (i
n w
.g.)
Brak
e po
wer
@ A
ltitu
de (H
P)
6,000 7,200 8,400 9,600 10,800 12,000 13,200 14,400
1.80
10.0
0
1.60
9.00
1.40
8.00
1.20
7.00
1.00
6.00
0.80
5.00
0.60
4.00
0.40
3.00
DRAWING • UMA # 2
Untitled • PISO 1- ESTE
Tuesday, January 21, 2003 Page 155 of 159 Version 3.70 - Released 5/13/2002 - VA01
Side
vie
w -
AH
D2
FS 1
50 V
M
Ente
ring
air v
iew
Leav
ing
air v
iew
This
dra
win
g is
not
to s
cale
; it i
s to
be
used
for d
imen
sion
al p
urpo
ses
only
.
42.0
in/1
,849
lb
72.0 in16.5
in27
.4 in
56.0
in/3
,074
lb
72.0 in
142.5 in
94.0
in
39.0
in20
.4 in
94.0
in
PERFORMANCE SUMMARY • UMA # 1
Untitled • PISO 1-OESTE
Tuesday, January 21, 2003 Page 156 of 159 Version 3.70 - Released 5/13/2002 - VA01
CS² Air Handler
Model # AHD2 FS 150 V M Insulation (entire unit) 2.00#Quantity 1 Wall thickness 2" (5.08 cm)Environment Indoor Sealed panels Positive pressure only
Notes
- Certified in accordance with the ARI Central-Station Air-Handling Units Certification Program, which isbased on ARI Standard-430.- See individual coil ratings for ARI certification information.- ETL listed & UL 1995 Approved.
A. Section 10F2 Flat filter section
Filter depth 2" (5.08 cm) Panel hand LeftFilter media Pleated 35% eff. Liners SolidAccess panels One Pressure drop (in w.g.) 0.12
B. Section 18 Internal face & bypass short coil section
Coil size Small Liners SolidDrain pan Standard Pressure drop (in w.g.) 0.66Maximum bypass air flow (ft³/min) 10,094
Refer to attached pages for coil performance.
C. Shipping split
D. Section 3 Vertical draw-thru fan section
Fan type Forward curved (standard) Total static @ Actual (in w.g.) 1.28Internal isolation Spring (standard) Brake power @ Actual (HP) 4.60Arrangement #3 Rotations per minute 557Motor type High Eff. TEFC Altitude (ft) 0Motor voltage 460V/3/60 Coldest dry bulb temp (°F) 54.0Motor power (HP) 5.00 Coil size LargeMotor hand Left Drain pan StandardDrive 150% HP Adjustable Access panels OneAir flow (ft³/min) 9,430 Panel hand LeftExternal static @ Actual (in w.g.) 0.50 Liners SolidInternal static @ Actual (in w.g.) 0.78
PERFORMANCE SUMMARY • UMA # 1
Untitled • PISO 1-OESTE
Tuesday, January 21, 2003 Page 157 of 159 Version 3.70 - Released 5/13/2002 - VA01
Air Handler Coils
Coil Tag Model # Qty Location Footnotes
CoilTotal capacity (MBH)Sensible capacity (MBH)Air PropertiesAir flow (ft³/min)Altitude (ft)Face velocity (ft/min)Air pressure drop (in w.g.)Entering air DB / WB (°F)Leaving air DB / WB (°F)Air properties measured atFluid PropertiesFluidFluid flow rate (gal/min)Fluid velocity (ft/s)Entering fluid temp. (°F)Leaving fluid temp. (°F)Fluid pressure drop (ft w.g.)ConstructionType / tubes in faceFinned height (in)Finned length (in)Face area (ft²)Rows / fin spacing (fins/in)Number of feedsCasing constructionSupply connections (qty@in)Return connections (qty@in)Connection type
#1 5 W P 5 B - 28T x 76 LH 1 Section B - Coil A
A. Certified in accordance with the ARIForced-Circulation Air-Cooling and Air-HeatingCoils Certification Program, which is based onARI Standard-410.
A
#1319.8233.4
9,4300
4000.45
76.1 / 64.353.2 / 52.7
Actual
Water60.02.8
44.054.74.9
5 / 2844.676.023.6
5 / 1023
Air handler1@1 1/21@1 1/2
MPT
FAN CURVE • UMA # 1
Untitled • PISO 1-OESTE
Tuesday, January 21, 2003 Page 158 of 159 Version 3.70 - Released 5/13/2002 - VA01
Supply Fan Specification
Air handler model AHD2 FS 150 V M Air flow (ft³/min) 9,430Fan type Forward curved (standard/22-15) Static pressure @ Altitude (in w.g.) 1.28Style Draw-thru Rotations per minute 557Inlet vanes No Brake power @ Altitude (HP) 4.60Altitude (ft) 0 Coldest dry bulb (°F) 54.0
Fan Curve
Air flow (ft³/min)
Stat
ic p
ress
ure
@ A
ltitu
de (i
n w
.g.)
Brak
e po
wer
@ A
ltitu
de (H
P)
6,000 7,200 8,400 9,600 10,800 12,000 13,200 14,400
1.50
8.00
1.35
7.20
1.20
6.40
1.05
5.60
0.90
4.80
0.75
4.00
0.60
3.20
0.45
2.40
DRAWING • UMA # 1
Untitled • PISO 1-OESTE
Tuesday, January 21, 2003 Page 159 of 159 Version 3.70 - Released 5/13/2002 - VA01
Side
vie
w -
AH
D2
FS 1
50 V
M
Ente
ring
air v
iew
Leav
ing
air v
iew
This
dra
win
g is
not
to s
cale
; it i
s to
be
used
for d
imen
sion
al p
urpo
ses
only
.
42.0
in/1
,713
lb
72.0 in16.5
in27
.4 in
56.0
in/3
,074
lb
72.0 in
142.5 in
94.0
in
39.0
in20
.4 in
94.0
in