STUDOR STUDOR ® AUSTRALIA Presents Active Venting System Design Active Venting System Design Utilizing STUDOR Air Admittance Utilizing STUDOR Air Admittance Valves and Valves and Positive Air Pressure Attenuators Positive Air Pressure Attenuators (As per AS/NZS3500.2.2003 Amendment 1 November 2005) (As per AS/NZS3500.2.2003 Amendment 1 November 2005)

STUDOR® AUSTRALIA Presents Active Venting System Design Utilizing STUDOR Air Admittance Valves and Positive Air Pressure Attenuators (As per AS/NZS3500.2.2003

Embed Size (px)

Citation preview

Page 1: STUDOR® AUSTRALIA Presents Active Venting System Design Utilizing STUDOR Air Admittance Valves and Positive Air Pressure Attenuators (As per AS/NZS3500.2.2003

STUDORSTUDOR®®

AUSTRALIA Presents

Active Venting System DesignActive Venting System Design

Utilizing STUDOR Air Admittance Valves Utilizing STUDOR Air Admittance Valves and and

Positive Air Pressure AttenuatorsPositive Air Pressure Attenuators

(As per AS/NZS3500.2.2003 Amendment 1 November 2005)(As per AS/NZS3500.2.2003 Amendment 1 November 2005)

Page 2: STUDOR® AUSTRALIA Presents Active Venting System Design Utilizing STUDOR Air Admittance Valves and Positive Air Pressure Attenuators (As per AS/NZS3500.2.2003

Preface:

• This presentation is intended to provide the participants with the most current information available at time of publication and draws on Australian National Standards AN/NZS3500.2.2003.

• This presentation is at best, a guide, and it is always the installers/designers responsibility to confirm the local regulations, variations, updates and options that apply in their state and/or area.

Page 3: STUDOR® AUSTRALIA Presents Active Venting System Design Utilizing STUDOR Air Admittance Valves and Positive Air Pressure Attenuators (As per AS/NZS3500.2.2003

This Presentation:

should at its completion, :

1. Inform the participant of the options now available for single fixture, group, stack and relief venting.

2. Enable the participant to draw a plumbing system showing the correct use of Air Admittance Valves and Positive Air Pressure Attenuators.

The Assessment:

will be via a hand-drawn sketch sheet at the end of the presentation.

Page 4: STUDOR® AUSTRALIA Presents Active Venting System Design Utilizing STUDOR Air Admittance Valves and Positive Air Pressure Attenuators (As per AS/NZS3500.2.2003

Introduction

• It is assumed that the participants in this course have completed the first and second modules of this course or have at least practical experience or knowledge of the installation and application of Air Admittance Valves.

• In this module we will learn their applications as to system design.

Page 5: STUDOR® AUSTRALIA Presents Active Venting System Design Utilizing STUDOR Air Admittance Valves and Positive Air Pressure Attenuators (As per AS/NZS3500.2.2003

The Valves

MINI-VENT™ MAXI-VENT™

•Both Valves have a lifetime warranty•Both conform to AN/NZS4936 Australian Manufacturing Standard

Airflow of 7.5 litres/second at -250 PaCapacity:

*60 Fixture units for Group Venting*6 Fixture units for Stack Venting

Airflow of 32 litres/second at -250 PaCapacity:

*1000 Fixture units for Group Venting*140 Fixture units for Stack Venting

Page 6: STUDOR® AUSTRALIA Presents Active Venting System Design Utilizing STUDOR Air Admittance Valves and Positive Air Pressure Attenuators (As per AS/NZS3500.2.2003

Important Note*. Always ensure when installing or specifying any AAV that it is an Australian/New Zealand Standards approved product and has both approval and airflow capacity (l/s) clearly marked on the body of the valve or packaging.

On the top of the Mini-Vent and Maxi-Vent are the relevant Australian Standards Marking

Page 7: STUDOR® AUSTRALIA Presents Active Venting System Design Utilizing STUDOR Air Admittance Valves and Positive Air Pressure Attenuators (As per AS/NZS3500.2.2003

STUDOR AAV’s

• Are guaranteed for the life of the plumbing system to which they are attached!

• Every Mini-Vent and Maxi-Vent has been tested twice before dispatch from the factory!

Page 8: STUDOR® AUSTRALIA Presents Active Venting System Design Utilizing STUDOR Air Admittance Valves and Positive Air Pressure Attenuators (As per AS/NZS3500.2.2003

The STUDOR Mini-Vent & Maxi-Vent

POLYSTYRENE PACKAGING TOP FOR INSULATION

OUTER SLEEVE

POLYSTYRENE PACKAGINGBOTTOM

MINI/MAXI-VENT

ADAPTER

•Both AAV’s share a common form of packaging

Page 9: STUDOR® AUSTRALIA Presents Active Venting System Design Utilizing STUDOR Air Admittance Valves and Positive Air Pressure Attenuators (As per AS/NZS3500.2.2003

Installation

The Mini-Vent as supplied can be installed on 3 different sizes of PVC DWV pipes:

* 40mm: to suit basins, small sinks and baths in Australia

* 50mm: to suit sinks, laundry tubs etc * 32mm: Older plumbing systems in

Australia (and basins etc in NewZealand)

*The Mini-Vent can be installed up 1000mm (1 metre) below the rim/flood level of the

highest fixture of the group it is venting

Page 10: STUDOR® AUSTRALIA Presents Active Venting System Design Utilizing STUDOR Air Admittance Valves and Positive Air Pressure Attenuators (As per AS/NZS3500.2.2003

Installation

• Note: The capacity of the Mini-Vent is not

limited by the pipe size it is connected to but the total number of fixture units it is venting.

i.e.: a Mini-Vent can be installed (via reducers etc.) on a 80mm (or above) DWV Waste Pipe if the total number of fixture units doesn’t exceed 60 F.U.

Page 11: STUDOR® AUSTRALIA Presents Active Venting System Design Utilizing STUDOR Air Admittance Valves and Positive Air Pressure Attenuators (As per AS/NZS3500.2.2003

Installation

The Maxi-Vent as supplied can be installed on 2 different sizes of PVC DWV pipes:

* 80mm * 100mm

*When used as a group vent the Maxi-Vent can also be installed up to 1000mm (1 metre) below the rim/flood level of thehighestfixture in the group it is venting

Page 12: STUDOR® AUSTRALIA Presents Active Venting System Design Utilizing STUDOR Air Admittance Valves and Positive Air Pressure Attenuators (As per AS/NZS3500.2.2003

Group VentingThis plumbing ventilation test rig, the biggest in the world, was built by students and staff at Gymea TAFE in Sydney, to prove AAVs were equal to or better than ‘Open Air Venting’ for groups of fixtures

This entire rig was vented by just 2 Mini-Vents

Page 13: STUDOR® AUSTRALIA Presents Active Venting System Design Utilizing STUDOR Air Admittance Valves and Positive Air Pressure Attenuators (As per AS/NZS3500.2.2003

•Clause 6.9 AIR ADMITTANCE VALVES•6.9.1 Air admittance valves•Air admittance valves complying with AS/NZS 4936 may be used in sanitary plumbing systems for *trap vents, group vents and stack vents and to ventilate branch drains*. They shall not be used for the upstream venting of a main drain.•NOTE: Branches connected into a positive pressure area, such as near boundary traps in multi storey buildings, may need additional venting.•6.9.2 Requirements for use•The following apply:•(a) Air admittance valves shall be used only on *systems that have at least one open upstream vent off the main drain. The upstream vent shall be sized in accordance with Table 3.5 and shall be not less than DN 50.•(b) Where more than one building on an allotment drains to the sewerage system, the sanitary drainage system of each building shall have one open upstream vent connected to its sanitary drain•(c) Air admittance valves shall have a determined airflow capacity not less than that in Table 6.6Table 6.6 when used as a trap vent, group vent or branch drain upstream vent, and Table 6.7Table 6.7 when used as a stack vent•.(d) An air admittance valve shall not be used as a stack vent where the stack extends through 10 or more floor levels.•(e) Where a sanitary plumbing system has a relief vent fitted to the stack, the relief vent shall be extended separately to atmosphere as an open vent.•(f) In Australia, air admittance valves that form an integral part of a fixture trap shall only be used as a trap vent

AN/NZS 3500.2.2003

Page 14: STUDOR® AUSTRALIA Presents Active Venting System Design Utilizing STUDOR Air Admittance Valves and Positive Air Pressure Attenuators (As per AS/NZS3500.2.2003

Group Venting (Installation)

Here we see two options;*1. Coming off the 100 x 50 vented Pan bend, (probably the last fixture in the group)*2. Coming off a 100 x 50 Junction on the common discharge pipe

1 2

Page 15: STUDOR® AUSTRALIA Presents Active Venting System Design Utilizing STUDOR Air Admittance Valves and Positive Air Pressure Attenuators (As per AS/NZS3500.2.2003

Group Venting

Note the connection of the AAV within the cupboard rather than extending the pipe through to the ceiling space.

Page 16: STUDOR® AUSTRALIA Presents Active Venting System Design Utilizing STUDOR Air Admittance Valves and Positive Air Pressure Attenuators (As per AS/NZS3500.2.2003

GroupVenting Diagram

* Refer to Australian National Standards

AS/NZS 3500.2.2003

*Please note: Although group vents have been deleted, the relief vent is still required on the stack to maintain air flow and equalize pressures within the stack• The relief vent should also be extended to atmosphere when the stack is vented with a Maxi-Vent. (although in Aust. states with a Performance Code option, Studor advises that this is deleted)

•Clause 7.5.3 and 7.5.7.5.3(b)

Clause 7.5.3.•Clause 7.5.7.5. 2

Clause 7.5.7.5.2 (b)

•Clause 7.5.7.2(a)

* Common Discharge pipes

•Alternative Position

•Relief Vent to atmosphere

Fully Vented Modified

Page 17: STUDOR® AUSTRALIA Presents Active Venting System Design Utilizing STUDOR Air Admittance Valves and Positive Air Pressure Attenuators (As per AS/NZS3500.2.2003

• So , knowing that we have to use the Table 6.6 to correctly size our AAV, we now add up the number of fixture units in our group and check the table.

• Let’s assume we have 6 W.C.’s (Pan/Cistern combinations)

• i.e. 1 x W.C.= 4 Fixture Units

• 4F.U.X 6 = 24 Fixture Units

Group Venting

Page 18: STUDOR® AUSTRALIA Presents Active Venting System Design Utilizing STUDOR Air Admittance Valves and Positive Air Pressure Attenuators (As per AS/NZS3500.2.2003

Table 6.6Minimum Determined Airflow Capacity of Air Admittance Valves When used as a Trap or Group Vent

Fixture Unit loading of discharge pipe

6810121824303642485460

Min. Airflow capacity of AAV’s(litres per second)122.42.73.33.84.24.65.05.35.76.0

The maximum capacity:

STUDOR® Mini-Vent™ 7.50 l/s (or 60 FU)

STUDOR® Maxi-Vent™ 32.01 l/s (or 1000 FU)

Page 19: STUDOR® AUSTRALIA Presents Active Venting System Design Utilizing STUDOR Air Admittance Valves and Positive Air Pressure Attenuators (As per AS/NZS3500.2.2003

• The same rule also applies to Stack Venting.• Lets assume 6 x W.C.’s on one common

discharge pipe and 6 washbasins on the opposite one and we have the same on 2 floors of a multi storey building.

• 6 x 4 F.U.(24FU)

+ 6 x 1 F.U.(Washbasins)(6FU) = 30 FU

X 2 Floors

= 60FU

Let’s check the next table………..

Stack Venting

Page 20: STUDOR® AUSTRALIA Presents Active Venting System Design Utilizing STUDOR Air Admittance Valves and Positive Air Pressure Attenuators (As per AS/NZS3500.2.2003

TABLE 6.7MINIMUM DETERMINED AIRFLOW CAPACITY OF AIRADMITTANCE VALVES VENTING DISCHARGE STACKS

Fixture unit loading of discharge Minimum determined air flow stack capacity of AAV, Litres per second

1 3 2 4 4 6 6 7 10 9 12 10 15 11 20 13 25 15 30 16 40 18 60 23 80 26 100 29 200 41 300 51 400 58 500 65 600 72

1000 92

Page 21: STUDOR® AUSTRALIA Presents Active Venting System Design Utilizing STUDOR Air Admittance Valves and Positive Air Pressure Attenuators (As per AS/NZS3500.2.2003

Adapter allows push-fit over 80mm DWV pipe

STUDOR Maxi-VentWith adapter

Removal of adapter enables solvent welding to 80mm DWV

Push-fit into 100mm DWVpipe with adapter

Stack Venting

Page 22: STUDOR® AUSTRALIA Presents Active Venting System Design Utilizing STUDOR Air Admittance Valves and Positive Air Pressure Attenuators (As per AS/NZS3500.2.2003

When a Maxi-Vent is installed in a roof space, always allow at least 150mm above any insulation

Stack Venting

•No need to penetrate the roof!

Page 23: STUDOR® AUSTRALIA Presents Active Venting System Design Utilizing STUDOR Air Admittance Valves and Positive Air Pressure Attenuators (As per AS/NZS3500.2.2003

Stack Venting•When installing the Mini-Vent or Maxi-Vent in areas that might be subject to temperatures below 0 ْ or above 60 ْ , use the top half of the foam packaging for thermal protection ْ

•For additional physical protection, where the Maxi-Vent is installed externally, an aluminum cap is available as an cover over the foam packaging.

Page 24: STUDOR® AUSTRALIA Presents Active Venting System Design Utilizing STUDOR Air Admittance Valves and Positive Air Pressure Attenuators (As per AS/NZS3500.2.2003

The Maxi-Vent™

The Mini-Vent™

Traditionally Vented

plumbing system

A stack and group vented

plumbing system using Studor AAV’s

Note the saving of unnecessary vent piping/fire collars etc and

no roof penetration

required

*Although not shown here, each plumbing system/building/house etc must have at least one open vent to atmosphere. In some cases this may need to be the main stack, so a Maxi-vent might not be used.Mini-Vents would still be used however for venting single fixtures and bathroom groups

Page 25: STUDOR® AUSTRALIA Presents Active Venting System Design Utilizing STUDOR Air Admittance Valves and Positive Air Pressure Attenuators (As per AS/NZS3500.2.2003

Relief Venting

• The relief vent in any multi-storey plumbing system is used to equalize air pressure within the stack.

• It is usually a pipe of lesser or equal diameter running parallel to the wet stack pipe that it is venting

• Until recently this was the only option available and approved for application to AS/NZS3500, Aust & N.Z.

Page 26: STUDOR® AUSTRALIA Presents Active Venting System Design Utilizing STUDOR Air Admittance Valves and Positive Air Pressure Attenuators (As per AS/NZS3500.2.2003

Relief Venting

Now Designers have the option of designing a approved plumbing system without relief venting.The Studor P.A.P.A (Positive Air Pressure Attenuator) can be installed at the base of the stack and at various floor intervals, depending on the height of the building ,without the need for a continuous parallel vent pipe.

Designed to utilize standard DWV fittings wherever possible, the PAPA is simply connected directly to the stack either horizontally or vertically to provide protection against positive pressures within the stack.

Page 27: STUDOR® AUSTRALIA Presents Active Venting System Design Utilizing STUDOR Air Admittance Valves and Positive Air Pressure Attenuators (As per AS/NZS3500.2.2003

Relief Venting cont:

The P.A.P.A. can also be installed with a Maxi-Vent to provide additional protection against negative pressure

As well as in series as per this 40 storey apartment block in Hong Kong

Page 28: STUDOR® AUSTRALIA Presents Active Venting System Design Utilizing STUDOR Air Admittance Valves and Positive Air Pressure Attenuators (As per AS/NZS3500.2.2003

AN/NZS3500.2.2003 Amendment 1

6.10 PRESSURE ATTENUATORS6.10.1 GeneralPressure attenuators may be used in sanitary plumbing systems as an alternative to relief venting.Attenuators are used to counter the tendency for the loss of trap water seals resulting from positive pressure pulses in discharge stacks. Positive pressure pulses or transients arise from disruptions to airflow produced at changes of direction or restriction to the airflow path.

The size of the pressure attenuator is independent of stack size and fixture unit loading.Although the application of pressure is not limited by building height, this Standard covers installation of pressure attenuators in sanitary plumbing stacks up to 50 floor levels only.6.10.2 Installation of pressure attenuatorsPressure attenuators shall be...(a) connected to stacks by means of 45° or sweep junctions;(b) positioned above the point of connection in either a vertical or horizontal orientation;and(c) adequately supported with allowance for thermal movement.Connections to the stack other than these immediately above the base of the stack or offset, shall be above the branch discharge pipe at that floor level.

Page 29: STUDOR® AUSTRALIA Presents Active Venting System Design Utilizing STUDOR Air Admittance Valves and Positive Air Pressure Attenuators (As per AS/NZS3500.2.2003

6.10.3 Location

Relief Venting (cont)

•Pressure attenuators shall be accessible and installed in accordance with Table 6.8.

•Where there is no stack offset, the connection for the lowest device shall be between the prohibited connection zone at the base of the stack and the first branch connected to the stack

•Where there is a stack offset, the connection for the lowest device above the offset shall be between the prohibited connection zone above the graded offset within the stack and the first branch connected to the stack above that offset

Where the stack extends through more than 25 floors, two pressure attenuators, arranged in series shall be used at the base of the stack.

Page 30: STUDOR® AUSTRALIA Presents Active Venting System Design Utilizing STUDOR Air Admittance Valves and Positive Air Pressure Attenuators (As per AS/NZS3500.2.2003

TABLE 6.8LOCATION OF PRESSURE ATTENUATORS

Number of floor levels served by the Stack above the base or

offset

Location

3 to 8 floors One at the base of the stack

9 to 15 floors One at the base of the stack plus one at mid level of the stack

16 to 25 floors One at the base plus one at intervals not exceeding 5 floors

26 to 50 floors Two at the base of the stack plus one not exceeding 3 floors up to level 25 and at intervals not exceeding 5 floors above level 25

Note: Where the height of the discharge stack above the base or offset is less than 5 floor levels Clause 7.5.3.1 may apply

Relief Venting (cont.)

Page 31: STUDOR® AUSTRALIA Presents Active Venting System Design Utilizing STUDOR Air Admittance Valves and Positive Air Pressure Attenuators (As per AS/NZS3500.2.2003

Note: if the P.A.P.A is to be installed with a Maxi-Vent in its top, it is not be installed Horizontally.

Relief Venting (cont.)

However if a P.A.P.A is installed complete with a Maxi-Vent this gives the Designer added flexibility in his design as well as additional protection against pressure variations within the stack. The Maxi-Vent will open immediately under negative pressure, allowing air into the stack at the point of need instead of the traditional method of waiting for the air to circulate through the relief vent pipe.

Page 32: STUDOR® AUSTRALIA Presents Active Venting System Design Utilizing STUDOR Air Admittance Valves and Positive Air Pressure Attenuators (As per AS/NZS3500.2.2003

Relief Venting (cont)

7.5.3.1 GeneralIf one or more floors separate the floor levels of the highest and lowest branch pipe connected to the stack, a relief vent shall be installed in accordance with Clauses 7.5.3.2 to 7.5.3.5, or pressure attenuators may be installed as specified in Clause 6.10.

Page 33: STUDOR® AUSTRALIA Presents Active Venting System Design Utilizing STUDOR Air Admittance Valves and Positive Air Pressure Attenuators (As per AS/NZS3500.2.2003

Relief Venting (cont)

Page 34: STUDOR® AUSTRALIA Presents Active Venting System Design Utilizing STUDOR Air Admittance Valves and Positive Air Pressure Attenuators (As per AS/NZS3500.2.2003

•Clause 7.5.3 and 7.5.7.5.3(b)

Clause 7.5.3. •Clause 7.5.7.5. 2

Clause 7.5.7.5.2 (b)

•Clause 7.5.7.2(a)

•Relief Vent to atmosphere

Relief Venting (cont)

Note the P.A.P.A installed in place of the relief vent.This now streamlines the system to simply the pipe that transports the waste.

This system is Single Stack Modified

Page 35: STUDOR® AUSTRALIA Presents Active Venting System Design Utilizing STUDOR Air Admittance Valves and Positive Air Pressure Attenuators (As per AS/NZS3500.2.2003

The Studor System

Note: This diagram for demonstrative purposes only.

Page 36: STUDOR® AUSTRALIA Presents Active Venting System Design Utilizing STUDOR Air Admittance Valves and Positive Air Pressure Attenuators (As per AS/NZS3500.2.2003

Summary• So now we have learned that plumbing systems

can be completely vented with only one open vent to atmosphere and the only pipes required are those carrying the waste.

• Please clarify any points with your instructor on which you are unsure

• Your Instructor will now hand out a design sheet for you to complete.

GOOD LUCK!

Page 37: STUDOR® AUSTRALIA Presents Active Venting System Design Utilizing STUDOR Air Admittance Valves and Positive Air Pressure Attenuators (As per AS/NZS3500.2.2003

Acknowledgements

STUDOR Australia would like to thank:- the Teaching and Stores Staff under the guidance of Raymond Jones,

Senior Head Teacher of Plumbing,TAFE NSW Southern Sydney Institute, Sutherland College (Gymea Campus)

for their support and contribution to this entire course.

- All TAFE teachers nationally

STUDOR would also like to acknowledge the continued support offered by Plumbers Supplies Co-operative who provided the materials for this project