Upload
prasanth-nair
View
233
Download
2
Embed Size (px)
Citation preview
8/10/2019 Structural Analysis Report of RCC Building
1/45
ABBREVIATIONS
A - Area
bf - Effective width of flange
D - Overall depth of beam or slab or diameter of column;
dimension of a rectangular column in the direction under
consideration
Df - Thickness of flange
DL - Dead load
d - Effective depth of beam or slab
d - Depth of compression reinforcement from the highly
compressed face
EC - Modulus of elasticity of concrete
EL - Earthquake load
Es - Modulus of elasticity of steel
fck - characteristic cube compressive strength of concrete
fy - Characteristic strength of steel
Ief - Effective moment of inertia
K - Stiffness of member
k - Constant or coefficient or factor
Ld - Development length
LL - Live load or imposed load
Lw - Horizontal distance between centers of lateral restraint
l - Length of a column or beam between adequate lateral
restraints or the unsupported length of a columnlef - Effective span of beam or slab or effective length of
column
lex - Effective length about x-x axis
ley - Effective length about y-y axis
ln - Clear span, face-to-face of supports
lx - Length of shorter side of slab
ly - Length of longer side of slab
8/10/2019 Structural Analysis Report of RCC Building
2/45
ll - Span in the direction in which moments are determined,
centre to centre of supports
l2 - Span transverse to I,, centre to centre of supports
l2 - l2 for the shorter of the continuous spans
M - Bending moment
m - Modular ratio
P - Axial load on a compression member
q0 - Calculated maximum bearing pressure of soil
r - Radius
s - Spacing of stirrups or standard deviation
T - Torsional moment
V - Shear force
W - Total load
X - Depth of neutral axis
Z - Modulus of section
z - Lever arm
f - Partial safety factor for load
m - Partial safety factor for material
m - Percentage reduction in moment
- Creep strain of concrete
cbc - Permissible stress in concrete in bending compression
cc - Permissible stress in concrete in direct compression
sc - Permissible stress in steel in compression
st - Permissible stress in steel in tension
sv - Permissible tensile stress in shear reinforcement
c - Shear stress in concrete
c,max - Maximum shear stress in concrete with shear
reinforcement
v - Nominal shear stress
- Diameter of bar
8/10/2019 Structural Analysis Report of RCC Building
3/45
INTRODUCTION
Public Hospitals are to be established as per government requirement and
community expectations. According to the present time, public hospital sector handles
the majority of acute care separations and accounts for most regional and remote
hospitals while private hospitals are concentrated in metropolitan areas, and are more
likely to treat patients of higher socio economic advantage. Public hospitals treat
medical cases originated in an area including emergency cases where as in private
sector, cases are selective and opted. These services are separate, not overlapping
between public and private sector.
Public Hospitals are completely and entirely run on the Government funding and
money. Everything from the construction, to the salary of Doctors/Staff, to the medical
equipments, medicines each and every single thing is being taken care of by local
Government. A public hospital is considered to be a preferable option for the not- so-
rich lot of people who despite acute illness cant afford heavy fees of private hospitals.
Although it is very ironical to see that a hospital governed by the Government (who has
obliviously more funds than a group of people or one person alone), does not offer that
level of service which can be counted on in most of the times.
The building is designed for Basement+ Lower Ground + Ground +4 floors.
OPDS, Registration Facilities are planned in Ground floor. Basements are used for
occupying various services like Medical Gases, Laundry, Electrical room, Generator etc.
Operation theatres, Wards, Labour Rooms, pediatrics wards and Nursing Station areplanned in Other Floors. So it is planned to construct Basement+ Lower Ground+ Ground
floors (3 floors) for accommodating the important facilities which is inevitable for the
functioning of M&C Hospital. A Ramp is provided for connecting all the floors. The other
facilities as per the initial planning can construct as future expansion for which the
column and foundations are designed for.
The building foundation was first proposed with column isolated footings based on the
submitted soil report of nearest building. The Sbc recommended by soil expert was
150kN/m2 1.5m from GL. The Building is proposed with two basements, so the founding
level will be 4m below from existing GL, the N value at this level is good and hence the
calculation of Sbc at this level yields as 200kN/m2. The design of foundation was done
adopting a sbc of 200kN/m2
and the DPR was submitted to Executive Engineer. On
scrutiny of the same, he doubted bout the adoption of Sbc and the joint site visit with
Exe. Engineer, Asst. Exe. Engineer and the Consultant decided to do a soil investigation
at the proposed plot. The Geotechnical investigation is carried out by the Consultant
itself and the results were co ordinate from Mar Athanasius College of Engineering.
8/10/2019 Structural Analysis Report of RCC Building
4/45
STRUCTURAL SYSTEM
The whole structure is analyzed as closed column beam frame in ETABS analysis
software and the design of various structural elements done manually.
Load transfer path is slab-beam-column-footing to soil.
Design parameters
Design loads
Dead loads
The dead loads are in accordance with IS 875 Part 1 (1987).
For the calculation of dead load acting over beams at various levels the unit
weight of the building materials are taken according to that given in IS 875 Part -I-Dead
weight of building materials. For calculating the live load acting over various floor levels
IS 875 Part II is referred. All the loads are given according to the data given in the floor
plans and cross sections given. The self weight of the structure is taken by the software
itself.
The unit weight of hollow brick masonry is taken as =20 kN/m3
The unit weight of concrete is taken as =25 kN/m3
Weight of brick wall = 0.20 x 3.3x 20 = 13.20kN/m
Wt of floor finish = 1.0 kN/m2
Self Wt of floor slab (12cm Thick) = 3 kN/m2
Load considered for water tank = 15 kN/m2
Live loads
The live loads are in accordance with IS 875 Part 2 (1987).
type Live load (kN/m2)
Wards, Nursing
stations2
Operating rooms, X
rays, Scan, store 3
8/10/2019 Structural Analysis Report of RCC Building
5/45
Stair cases,
Balconies, Corridors,4
OPDs, Offices, 2.5
Laboratories,
laundries, Kitchen3
Earthquake Loads as per IS: 1893 (part 1): 2002
Dynamic forces on multi-storied are best computed through a detailed vibration analysis.
Detailed dynamic analysis or modal analysis or pseudo static analysis should be carried
out depending on the importance of problem. BIS Code 1893 (Part 1): 2002 recommends
that [Ref: Cl: 7:8:1]
Dynamic analysis shall be performed to obtain the design seismic force, and its
distribution to different levels along the height of the building and to the various lateral
load-resisting elements for the following buildings:
a) Regular buildings those greater than 40m in height in Zone IV
and Zone V, and those greater than 90m in height in Zone II and
Zone III.b) Irregular buildingall framed buildings higher than 12m in Zones
IV and Zone V, and those greater than 40m in height in Zone II and
III.
Since the height of the residential complex is 44.35m and its located in Zone III, static
method of analysis was performed to find the seismic load and its distribution.
Static method:
The base shear or total design lateral force along any principal direction shall be
determined by the following expression:
VB= AhW
where,
VB = The design base shear
Ah = Design horizontal acceleration spectrum value using the fundamental natural
period T
8/10/2019 Structural Analysis Report of RCC Building
6/45
W= Seismic weight of the building.
The design horizontal seismic coefficientgR2
SIZ ah A
Where,
Z = Zone factor given in table 2, for the Maximum Considered Earthquake (MCE)
and service life of structure in a zone. The factor 2 in the denominator of Z is
used so as to reduce the MCE zone factor to the factor for Design Basis
Earthquake (DBE)
I = Importance factor, depending upon the functional use of structures,
characterized by hazardous consequences of failure, post-earthquake
functional needs, historical value or economic importance (Table 6 IS 1893
(Part 1):2002
R = Response reduction factor, depending on the perceived seismic damage
performance of the structure, characterized by ductile or brittle deformations.
However, the ratio (I/R) shall not be greater than 1.0. The values for
buildings are given in Table 7 of IS 1893 (Part 1): 2002.
g
Sa Average response acceleration coefficient.
Distribution of Design Force
The design base shear VB was distributed along the height of the buildings
as per the following expressions.
ni
i
ii
iii
hW
hWVBQ
1
2
2
Where,
iQ = Design lateral force at floori
iW = Seismic weight of floori
ih = Height of floori measured from base.
8/10/2019 Structural Analysis Report of RCC Building
7/45
n = Number of storeys in the building is the number of levels at which the
masses are located.
Seismic weight, W
The seismic weight of each floor is its full dead load plus appropriate
amount of imposed loads while computing the seismic weight of each floor, the weight of
columns and walls in any storey shall be equally distributed to the floors above and below
the storey. The seismic weight of the whole building is the sum of the seismic weights of
all the floors. Any weight supported in between storey shall be distributed to the floors
above and below in inverse proportion to its distance from the floors.
Imposed uniformly distributed floor
loads kN/m
Percentage of imposed load
%
Upto and including 3.0 25
Above 3.0 50
Table-Percentage of imposed load to be considered in seismic weight calculation
Determination of Design Base Shear for Seismic Analysis:
As per IS 1893 (Part 1):2002
Fundamental natural period, Ta(Clause 7.6.2) = 0.09h/d
h = height of building exclude basement floor = 20.30 m
d- base dimension at plinth level in respective direction=36.6
= 0.50sec
For 0.1
8/10/2019 Structural Analysis Report of RCC Building
8/45
4.3.6. Calculation of design seismic pressure
Calculation of design seismic pressure
The above parameters are defined in the ETABS software and software itself will
calculate the seismic loads and create the load cases and load combinations. The software
automatically has done the distribution of seismic force.
8/10/2019 Structural Analysis Report of RCC Building
9/45
STRUCTURAL MATERIALS
Concrete and Reinforcement
Concrete: M25 for Foundations, M30 for Columns, M25 for Beams, Slabs, Stairs,
and all other components
Steel reinforcement:
Fe500 TMT grade pertaining to IS: 1786 1985
Cover:
From durability requirement, environmental exposure condition is assumed as
8/10/2019 Structural Analysis Report of RCC Building
10/45
The nominal cover to outermost reinforcement shall be as follows for two hour
fire rating.
Columns 40mm
Beams 25mm
Slab 20mm
Stair 25mm
Foundations 50mm
MODELLING AND ANALYSIS METHODOLOGY
BRIEF:
The building is modelled as 3D structure and is analysed as SMRF (Special
Moment Resisting Frames).
The FEM based structural software (ETABS Nonlinear v9.7.2) is used for modeling and
analysis of the building.
MODELLING
The basic approach for using the program is very straight forward. The user
establishes grid lines, defines material and structural properties, places structural
objects relative to the grid lines using point, line and area object tool. All the types of
loads that the structure is subjected can be defined and assigned to the appropriate
structural components. The analysis can be performed and the results are generated in
graphical or tabular form that can be printed to a printer or to a file for use in other
programs. The following topics describe some of the important areas in the modeling.
Defining Material Properties
In the property data area, name of the material, mass per unit volume, weight
per unit volume, modulus of elasticity, Poissons ratio should be specified for each type
of material defined. The mass per unit volume is used in the calculation of self-mass of
the structure. The weight per unit volume is used in calculating the self-weight of the
structure.
8/10/2019 Structural Analysis Report of RCC Building
11/45
Defining Frame Sections
Frame sections like beams, columns and are defined under this. The sizes of
beams and columns are fixed here and their reinforcement requirements and concrete
covers defined. Hinges were introduced (i.e. end moments were released) near the
connecting where ever required.
Defining Slab Sections
For defining the type of slab section in ETABS, there are three options available
based on its behavior, namely shell type, membrane type and plate type. Shell type
behavior means, both in-plane membrane stiffness and out-of-plane plate bending
stiffness can be provided for the section. Membrane type behavior mean, only in-plane
membrane stiffness is provided for the section. Plate-type behavior means that only out-
of-plane bending stiffness is provided for the section. In the present analysis, slabs are
given membrane type behavior to provide in plane stiffness and shear walls are defined
as shell elements. Shell elements should be divided in to finer mesh so that proper
connectivity is achieved, as our focus is mainly on the global behavior of the in filled
frame structure.
Dead load, live load, roof live load, are defined under the static load case option
of the define menu. Various load combinations can also be defined in the load
combinations option of the define menu.
Member Property Specifications and Support Condition
The dimensions of different members were fixed based on the trial design. The column
dimensions provided for the modeling is as prescribed by the Architect. If necessary it
will revised during the design stage. The beams are provided in such a way that torsion is
released since compatibility torsion alone comes in them. The member properties
assigned are as given below.
Slab
Thickness of the slab = 120mm
8/10/2019 Structural Analysis Report of RCC Building
12/45
Beams
The dimensions of the beams are as shown below
Beam Breadth, B Depth, D
Fixed Beams 200mm 500mm
Fixed beam 250mm 600mm
Fixed beam 200mm 450mm
Column:
The column dimensions are as follows:
Ground floor: 250mm X 500mm, 300mm X 500mm, 400mm X 400mm, 500mmX 500mm,
(steel as per details)
Staircase:
The staircase is provided as an equivalent slab. The thicknesses of the slab used for
staircase is 175mm
Support condition
Then support conditions were given to the structure. The support condition given was
pinned.
LOAD COMBINATION
The following are the load combinations as IS: 456-2000
1) 1.5 D.L + 1.5 LL
2) 1.5 DL + 1.5 SLX
3) 1.5 DL - 1.5 SLX
4) 1.5 DL + 1.5 SLY
5) 1.5 DL - 1.5 SLX
8/10/2019 Structural Analysis Report of RCC Building
13/45
6) 0.9 DL + 1.5 SLX
7) 0.9 DL - 1.5 SLX
8) 0.9 DL + 1.5 SLY
9) 0.9 DL - 1.5 SLY
10) 1.2 DL + 1.2LL + 1.2 SLX
11)1.2 DL + 1.2LL - 1.2 SLX
12) 1.2 DL + 1.2LL + 1.2 SLY
13)1.2 DL + 1.2LL - 1.2 SLY
Column Layout
8/10/2019 Structural Analysis Report of RCC Building
14/45
Completed Model
8/10/2019 Structural Analysis Report of RCC Building
15/45
Completed Extruded Model
8/10/2019 Structural Analysis Report of RCC Building
16/45
Completed Extruded Model of Ramp
8/10/2019 Structural Analysis Report of RCC Building
17/45
DESIGN OF ELEMENTS
Analysis Results
Axial Force on Columns
8/10/2019 Structural Analysis Report of RCC Building
18/45
Bending Moment Diagram of Beams
Shear Force Diagram of Beams
8/10/2019 Structural Analysis Report of RCC Building
19/45
Design Methodology:
All structural concrete elements will be designed according to the Limit State
Method as specified in IS: 456 - 2000 for reinforced concrete elements and detailing will
be as per standards.
Design of foundation:
The building foundation was first proposed with column isolated footings based
on the submitted soil report of nearest building. The Sbc recommended by soil expert
was 150kN/m2
1.5m from GL. The Building is proposed with two basements, so the
founding level will be 4m below from existing GL, the N value at this level is good and
hence the calculation of Sbc at this level yields as 200kN/m
2
. The design of foundationwas done adopting a sbc of 200kN/m
2and the DPR was submitted to Executive
Engineer. On scrutiny of the same, he doubted bout the adoption of Sbc and the joint
site visit with Exe. Engineer, Asst. Exe. Engineer and the Consultant decided to do a soil
investigation at the proposed plot. The Geotechnical investigation is carried out by the
Consultant itself and the results were co ordinate from Mar Athanasius College of
Engineering.
Soil Profile
The boreholes, numbered 1,2.3 and 4 were terminated at 29.40
m,29.90m,26.00m and 27.70m respectively. Hard rock was encountered in all the
boreholes. Lateritic clayey silt were found in all the bore holes. Very fine sandy silt, very
fine silty sand and Lateritic clay with sand were found in some of the boreholes ,Hard
rock was fund in all the boreholes,. The N value is found tobe varying from 7 to greater
than 100.
DATA AND DISCUSSION
The bore hole details are given in the attached bore log. The report on the
analysis of the recovered representative samples collected from the boreholes is
attached. Based on visual identification and the laboratory test results using
representative samples, the soil profile at the bore hole location is drawn and are also
presented in borehole logs. For the lateritic clay found in all the bore holes, sand content
3% to9%, silt content varies between 42% and 73% and clay content was between 18%
8/10/2019 Structural Analysis Report of RCC Building
20/45
between 0.30 kg/cm2 and 0.60 kg/cm2. The N value for these strata was fond to be
between 8 and 21. For the lateritic clayey silt found in all the bore holes, sand content
2% to 15% silt content varies between 72% and 87% and clay content was between 3%
ad 27%. The cohesion was between 0.25 kg/cm2 and 0.70 kg/cm2. The N value for these
strata was found to be between 7 and 45. The very fine sandy silt found in bore holes 1,3
and 4 sand content varies between 15 % to 42% and silt content varies between 55%
and 85%. The N value for these strata was found to be between 23 and greater than 100.
The very fine silty sand found in bore holes 1 and 2 sand content varies between 58% to
68% and silt content varies between 32% and 42%. The N value was found to be greater
than 100. The Lateritic clay with sand found in bore holes 2,3 and 4, sand content varies
between 0% to 21%, silt content varies between 36% and 55% and clay content between
35% and 45%. The N value for these strata was fond to be between 7 and 18. From the
test results for the stratum having N value more than 10 the safe bearing capacity can be
taken as 6.3T/sq.m and for layers having N value 20, it may be taken as 17.2T/sq.m.
RECOMMENDATIONS
The soil at the site mainly consists of Lateritic clay and Lateritic clayey silt. Very
fine sandy silt. Very fine silty sand and Lateritic clay with sand were found in some of the
boreholes. Hard rock was found at all the bore holes. The N value is found to be varying
from 7 to greater than 100.
For the stratum having N value more than 10, the safe bearing capacity can be
taken as 6.3T/sq.m and for layers having N value 20, it may be taken as 17.2T/sq.m.
Depending on the number of floors, the foundation shall be decided. It is suggested to
provide pile foundation which extends to hard rock. Open foundation shall be adopted.
If the load on foundation is not high. She recommendations made in this report are
based on the results of field tests as well as tests done on the samples recovered from
the bore holes. It is presumed that the soil below the maximum depth of exploration at
the site does not vary much or rather improves from that observed at the maximum
depth
Based on this report, the foundation system adopted is Pile Foundation. Since
the capacity is not provided by the Soil Expert, the Consultant Engineer calculated both
geotechnical and Structural Capacity of various dia piles
8/10/2019 Structural Analysis Report of RCC Building
21/45
Geotechnical Capacity of Piles
450mmDia
500mm dia
8/10/2019 Structural Analysis Report of RCC Building
22/45
550mm dia
Pile Capacity
Sl No Pile Diameter(mm) Pile Capcity(kN)
1 450 970
2 500 1100
3 550 1300
Design of Pile
450mm Dia Pile
As per IS: 2911
Fixity depth = 8d = 8 x 0.45 = 3.6m
Total No of Pile =134 No.s
Base Shaer( Result from Etabs)= 4354kN
Horizontal Force =32.73kN
Moment due to horizontal force = 117.8kNm
8/10/2019 Structural Analysis Report of RCC Building
23/45
Factored Moment Mu =176kN-m
For 450mm dia pile; P =970kN
Pu =1445kN
2Df
P
ck
u
= (1445x1000)/ (25x4502)
=0.284
3
6
345025
10176
Df
M
ck
u
=0.077
Providing 40 mm clear cover and assuming 20 mm dia bar
d' =50
D
d1
= 0.106
062.ck
f
P, p = 1.55
pmin= 0.8
Area of longitudinal steel 22403mmAs
This is to be provided up to fixity depth 8d = 3.6m
Hence provide 12 nos of Y16mm dia bars as longitudinal reinforcement
Provide circular links of 8 mm dia at 200 mm c/c spacing.
Provide minimum longitudinal reinforcement as per IS 2911 Part I/ section 2
Minimum area of longitudinal steel = 0.4% of total c/s area
=635 mm2
Hence provide 6 nos of Y16mm dia bars as longitudinal reinforcement
Provide circular links of 8 mm dia at 150 mm c/c spacing.
Provide circular spacers of 12mm dia at 3000mm c/c
8/10/2019 Structural Analysis Report of RCC Building
24/45
500mm Dia Pile
As per IS: 2911
Fixity depth = 8d = 8 x 0.5 = 4.0 m
Total No of Pile =134 No.s
Base Shaer( Result from Etabs)= 4354kN
Horizontal Force =32.73kN
Moment due to horizontal force = 130.8kNm
Factored Moment Mu =196.38kN-m
For 450mm dia pile; P =1100kN
Pu =1650kN
2Df
P
ck
u
= (1650x1000)/ (25x5002)
=0.264
3
6
3
50025
10196
Df
M
ck
u
=0.062
Providing 40 mm clear cover and assuming 20 mm dia bar
d' =50
D
d1
= 0.10
041.ckf
P, p = 1.01
pmin= 0.8
Area of longitudinal steel 21982mmAs
This is to be provided up to fixity depth 8d = 4m
Hence provide 10 nos of Y16mm dia bars as longitudinal reinforcement
Provide circular links of 8 mm dia at 200 mm c/c spacing.
8/10/2019 Structural Analysis Report of RCC Building
25/45
Provide minimum longitudinal reinforcement as per IS 2911 Part I/ section 2
Minimum area of longitudinal steel = 0.4% of total c/s area
=785 mm2
Hence provide 5 nos of Y16mm dia bars as longitudinal reinforcement
Provide circular links of 8 mm dia at 150 mm c/c spacing.
Provide circular spacers of 12mm dia at 3000mm c/c
Design of Pile Cap
Two pile group
Material Constants
Concrete,fck = 25 N/mm
Steel, fy = 500 N/mm
Each pile should be connected using pile cap with a minimum of 100mm edge distance to either
sides of the pile. This pile cap is designed as simply supported beam.
As per IS 2911 spacing between two pile is 2.5 x dia of pile
Length of pile cap = 2.5 x 500 + 2 x 250 + 2 x 150
=2050 mm=2050mm
Depth of pile cap = development length of column bar + cover
As per SP-16 Table 65
For 20 mm diameter bars
Ldc = 777 mm
Assume a 100 mm projection of pile in to the cap concrete
Depth of pile cap = 777 + 100
= 877 mm
Provide an overall depth, D = 1000mm
Breadth of pile cap = diameter of pile + 150 mm overhang
= 500 + 2 x 150
= 800mm
Size of pile cap 2.05 x 0.8 x 1.0 m
8/10/2019 Structural Analysis Report of RCC Building
26/45
Effective depth, d = 900 mm
b =800 mm
Factored axial load on pile Pu = 1650 kN
Bending moment at face of column = 1100 x 0.625
= 656.25 kN-m
Ultimate moment,Mu = 1030 kN-m
Mu / (bd2) = 1.69
% of tension steel, pt = 0.428
Area of tension reinforcement,Ast = 3425mm
Provide reinforcement of Y25mm dia bars 7 Nos
Area of steel provided = 3430 mm
8/10/2019 Structural Analysis Report of RCC Building
27/45
Hence Maximum shear force on pile cap = 1100kN
Ultimate shear,Vu = 1650 kN
Nominal shear stress, v = 2.4 N/mm
100As/ (bd) = 0.48
Deign shear strength, c = 0.49 N/mm
ie, v > c so shear reinforcement are needed
Assume 12mm dia 6 legged stirrups
Vus =Vu - c bd = 1372 kN
Diameter of bar = 12 mm
Area of shear reinforcement effective in shear,Asv = 678.58 mm
Provide Y12 mm dia 6 legged stirrups
Spacing of shear reinforcement,Sv = 0.87 x d xfyx Asv
Vus
8/10/2019 Structural Analysis Report of RCC Building
28/45
Design of columns:
Columns are designed by taking the forces and moments from the FEM software.
The sizes of columns are kept constant at all the stories. The design of column is done
considering the axial compression, biaxial bending moment including slenderness effect.
Excel spread sheets are used for designing of columns as per standards. The Columns are
designed for GF+4 floors.
Axial force diagram of typical Column
8/10/2019 Structural Analysis Report of RCC Building
29/45
8/10/2019 Structural Analysis Report of RCC Building
30/45
ETABS 2013 13.1.3 License #*192TZNDF9YDF4PW
Final Model with Pile.EDB Page 1 of 2 7/16/2014
ETABS 2013 Concrete Frame Design
IS 456:2000 Column Section Design
Column Element Details Type: Ductile Frame (Summary)
Level Element Section ID Combo ID Station Loc Length (mm) LLRF
GF C83 C300X500 DCON7 0 3900 0.594
Section Properties
b (mm) h (mm) dc (mm) Cover (Torsion) (mm)
300 500 50 23.6
Material Properties
E c (MPa) f ck (MPa) Lt.Wt Factor (Unitless) f y (MPa) f ys (MPa)
27386.13 30 1 500 500
Design Code Parameters
C S
1.5 1.15
Axial Force and Biaxial Moment Design For P u , M u2 , M u3
Design P ukN
Design M u2kN-m
Design M u3kN-m
Minimum M 2kN-m
Minimum M 3kN-m
Rebar Area
mm
Rebar %
%
2092.8237 -45.7945 142.2591 41.8565 48.693 3152 2.1
Axial Force and Biaxial Moment Factors
K Factor
Unitless
Length
mm
Initial Moment
kN-m
Additional Moment
kN-m
Minimum Moment
kN-m
Major Bend(M3) 0.831928 3300 57.2852 0 48.693
Minor Bend(M2) 0.704905 3300 -18.3178 0 41.8565
8/10/2019 Structural Analysis Report of RCC Building
31/45
ETABS 2013 13.1.3 License #*192TZNDF9YDF4PW
Final Model with Pile.EDB Page 2 of 2 7/16/2014
Shear Design for V u2 , V u3
Shear V ukN
Shear V ckN
Shear V skN
Shear V pkN
Rebar A sv/s
mm/m
Major, Vu2 64.3742 140.4314 54 87.6777 332.53
Minor, V u3 63.1923 133.5314 50 63.1923 554.22
Joint Shear Check/Design
Joint Shear
Force
kN
Shear
V TopkN
Shear
V u,TotkN
Shear
V ckN
Joint
Area
cm
Shear
Ratio
Unitless
Major Shear, V u2 N/A N/A N/A N/A N/A N/A
Minor Shear, V u3 N/A N/A N/A N/A N/A N/A
(1.1) Beam/Column Capacity Ratio
Major Ratio Minor Ratio
N/A N/A
Additional Moment Reduction Factor k (IS 39.7.1.1)
A gcm
A sccm
P uzkN
P bkN
P ukN
k
Unitless
1500 31.5 3207.0354 989.5549 2092.8237 0.502467
Additional Moment (IS 39.7.1)
Consider
M a
Length
Factor
Section
Depth (mm)
KL/Depth
Ratio
KL/Depth
Limit
KL/Depth
Exceeded
M aMoment (kN-m)
Major Bending (M 3 ) No 0.8462 0.5 5.4907 12 No 0
Minor Bending (M 2 ) No 0.8462 0.3 7.754 12 No 0
Notes:
N/A: Not Applicable
N/C: Not Calculated
N/N: Not Needed
8/10/2019 Structural Analysis Report of RCC Building
32/45
Design of beams
The RC beams and slabs are designed using Excel spreadsheet using the analysis
results from FEM software. The top as well as bottom reinforcement shall consist of at
least two bars throughout the member length.
Bending Moment diagram of typical continuous beam
Shear Force diagram of typical continuous beam
8/10/2019 Structural Analysis Report of RCC Building
33/45
Design for area of steel and shear for singly reinforced beam by limit state design method
Calculation of Ast req for beams
Ref IS 456-2000 Cl G-1.1b & G-1.1c For sections without compression reinforcement
fy fck b D Cc Cg of bar d Mulim pt lim
N/mm2 N/mm2 mm mm mm mm mm kN.m %
500 25 200 500 25 8 467 145.03 0.94
Mu support Ast req. spt ptreq.spt Mu span Ast span ptreq.span
kNm mm2 % kNm mm % d req mm d prov mm Result
135 802.93 0.86 55 288.73 0.31 450.56 467 okay
Reinforcement details provided at support and span of beam
Nos. dia Ast support pt support Result Nos. dia Ast span pt span
mm mm % mm mm %
2 16 2 16
2 16 2 16
Check for shear in beams (limit state design method)Ref IS 456-2000 Cl 40.1, Cl 40.2.3, Table 19, Table 20 & Cl 40.2.1
fck Vu pt v c c max
prov. Cl 40.1 Table 19 Table 20
N/mm2 kN % N/mm2 N/mm2 N/mm2
25 110 0.86 1.18 0.61 3.1
Design for shear reinforcement (vertical stirrups)
Ref IS 456-2000 Cl 40.4a
Vu cb d Vus Vus/d fy assuming no. stirrup Vus/d prov.
req req stirrup dia of stirrup sp assumed kN/cm
kN kN kN kN/cm N/mm2
mm legs mm Cl 40.4 a
110 56.97 53.03 1.14 415 8 2 100 3.630
Check for minimum and maximum spacing of stirrup
Min stirrup Max stirrup stirrup Result
spacing mm spacing mm sp prov.
Cl 26.5.1.6 Cl 26.5.1.5 mm
546.64 300 100 Hence ok
Side face reinforcement
Ref IS 456-2000 Cl 26.5.1.3
b D side face spc b/w
of reinf. bars not to
web req. / face no. dia of Ast prov. exceedmm mm Cl 26.5.1.3 per face bar mm Cl 26.5.1.3
200 500 not req 2 12 226.19 200 mm
Check for span to depth ratio
Ref IS 456-2000 Cl 23.2.1
Type of fy span d pt req. pt prov. pc MFt MFc
beam N/mm2 mm mm % % %
Cont.Beam 500 5250 467 0.31 0.86 0 1.924 1
l/d l/d Result
prov Cl 23.2.1 Cl 23.2.1
11.24 50.02 Okay
okay 804.25 0.86
tau_v tau_c,design for shear
8/10/2019 Structural Analysis Report of RCC Building
34/45
Design of slab
Design of slab
Material Constants:
Concrete,fck= 25 N/mm
Steel, fy = 500 N/mm
Loads:
Using 120 mm thick slab
Dead Load on Slab = 0.12 x 25 = 3 kN/m
Live Load on Slab = 3kN/m
Finishes = 1.5 kN/m
Partition load = 2.5 kN/m
Total = 10.0 kN/m
Boundary Conditions one long edge discontinuous
Assume a clear cover of 20 mm & 8 mm dia bars
Eff: depth along shorter direction dx = 96 mm
Eff: depth along longer direction dy = 88 mm
Effective span as per IS 456: 2000 clause 22.2.b
lyeff= 3.2+0.088 = 3.288 m
lxeff= 3.9+0.096 = 3.996 m
lyeff/lxeff =1.22, Hence design as Two Way Slab.
8/10/2019 Structural Analysis Report of RCC Building
35/45
1 Design for area of steel and shear for two way slab by limit state design method
Slab Geometry
Lx Ly Ly/Lx
m m
3.2 3.9 1.219
8/10/2019 Structural Analysis Report of RCC Building
36/45
Calculation of Ast req for slab spanning Ly
Ref IS 456-2000 Cl G-1.1b & G-1.1c
- Muy cont. Ast min pt req.cont. + Muy span Ast min pt req.span
kNm mm2 % kNm mm %
4.26 144.00 0.16 3.23 144.00 0.16
Reinforcement details provided at support and span of slab spanning Ly
dia prov. spacing Ast cont. pt cont. Result dia prov. spacing Ast span pt span
mm mm mm % mm mm mm %
8 150 8 150
0 250 0 250
Check for shear in solid slabs for limit state design method
Ref IS 456-2000 Cl 40.1, Cl 40.2.3, Table 19, Table 20 & Cl 40.2.1.1
fck Vu b D clear cg d
N/mm kN mm of slab mm cover mm of bar mm mm
25 21.6 1000 120 20 4 96
pt v k c c max
Cl 40.1 Cl 40.2.1.1 Table 20
% N/mm N/mm N/mm
0.35 0.23 0.55 3.1
Check for span to depth ratio
Ref IS 456-2000 Cl 23.2.1
Type of fy span d pt req. pt prov. pc MFt MFcbeam N/mm
2 mm mm % % %
Cont.slab 500 3200 96 0.15 0.35 0 2.936 1
l/d l/d Result
prov Cl 23.2.1 Cl 23.2.1
33.33 76.34 Okay
Result
tau_v < k tau_c, Ok
tau_v
8/10/2019 Structural Analysis Report of RCC Building
37/45
DESIGN OF DOG LEGGED STAIRCASE
Data
Internal Dimensions
Length = 4.76 m
Width = 2.6 m
Floor Height = 3.9 m
Fck = 25 N/mm
Fy = 500 N/mm
Riser = 160 mm
Tread = 280 mm
Landing width = 1200 mm
Effective Span = 4.8 m
Height of each flight = 1.95 m
No. of risers in each flight 12.1875 Nos
No. of Tread in each flight 11.1875 Nos
Design
d = 152 mm Required
D = 175 mm
d = 154 mm
Loads
= .
DL on horizontal area = 5.04 kN/m
DL of steps = 2 kN/m
LL = 5 kN/m
FF = 1.5 kN/m
Total load = 13.54 kN/m
Factored load = 20.3 (of one flight)
BM and SF
Mu = 58 kN-m
Vu = 49 kN
d from BM consideration 146 mm
k = 2.466
pt = 0.652 %
Ast = 1005 mm
Main Reinforcement
Dia = 12 mm
Spacing = 112 mm
Distr ibut ion Steel
Ast = 185 mm
Dia of bar = 8 mm
Spacing = 270 mm
Development Length
8/10/2019 Structural Analysis Report of RCC Building
38/45
Floor Beam
4760
mm
DOWN UP
1200 mm
Mid Landing Beam
2600
mm
Ld = 590 mm
300
mm
Y8 @ 270 mm C/C (Distribution Reinforceme
Y12@112 mm C/C
(Main Reinforcement)
175 mm
175 mm
DETAILING
8/10/2019 Structural Analysis Report of RCC Building
39/45
ETABS 2013 13.1.3 License #*192TZNDF9YDF4PW
Final Model with Pile.EDB Page 1 of 2 7/16/2014
ETABS 2013 Shear Wall Design
IS 456:2000 Pier Design
Pier Details
Story ID Pier ID Centroid X (mm) Centroid Y (mm) Length (mm) Thickness (mm) LLRF
TF P4 8115.5 10950.9 4556.7 250 0.426
Material Properties
E c (MPa) f ck (MPa) Lt.Wt Factor (Unitless) f y (MPa) f ys (MPa)
25000 25 1 500 500
Design Code Parameters
S C IP MAX IP MIN P MAX
1.15 1.5 0.02 0.0025 0.8
Pier Leg Location, Length and Thickness
StationLocation
ID Left X 1mm
Left Y 1mm
Right X 2mm
Right Y 2mm
Lengthmm
Thicknessmm
Top Leg 1 7650 11130 9700 11130 2050 250
Top Leg 2 9700 11130 9700 11886.7 756.7 250
Top Leg 3 5900 10500 7650 10500 1750 250
Bottom Leg 1 7650 11130 9700 11130 2050 250
Bottom Leg 2 9700 11130 9700 11886.7 756.7 250
Bottom Leg 3 5900 10500 7650 10500 1750 250
Flexural Design for P u, M u2 and M u3
Station
Location
Required
Rebar Area (mm)
Required
Reinf Ratio
Current
Reinf Ratio
Flexural
Combo
P ukN
M u2kN-m
M u3kN-m
Pier A gmm
Top 2848 0.0025 0.0037 DWAL14 784.892 139.749 275.88 1139166
Bottom 5457 0.0048 0.0037 DWAL12 635.1675 -660.8535 -3663.8173 1139166
Shear Design
Station
Location
ID Rebar
mm/m
Shear Combo P ukN
M ukN-m
V ukN
V ckN
V c + V skN
Top Leg 1 OS DWAL12 430.2772 1013.9719 -1311.7222 130.8789 500.7702
Top Leg 2 1018.78 DWAL7 297.3436 -172.3923 272.992 50.4431 272.992
Top Leg 3 OS DWAL11 493.7266 -892.7358 1127.576 115.2453 431.0062
Bottom Leg 1 OS DWAL12 72.6428 -1121.5661 -1314.807 147.0513 516.9426
Bottom Leg 2 861.61 DWAL9 167.9797 189.7462 238.6595 50.4431 238.6595
Bottom Leg 3 OS DWAL12 878.7701 -880.6772 -1092.6488 153.1835 468.9444
Number of legs where shear force exceeds max allowed (top, bottom) = 2, 2
8/10/2019 Structural Analysis Report of RCC Building
40/45
DETAILING
All the structural elements were detailed according to IS 456:2000 and SP34.
Detailed drawings were prepared in AutoCAD 2007. Detailing of all the structural
elements were done based on SP 34 and IS 13920
8/10/2019 Structural Analysis Report of RCC Building
41/45
COLUMN DETAILS
Special confining reinforcement as per is 13920:1993
Special confining reinforcement shall be provided over a length lo from each joint face,
towards midspan, and on either side of any section, where flexural yielding may occur
under the effect of earthquake forces
The length lo shall not be less than
(a) Larger lateral dimension of the member at
Section where yielding occurs,
(b) 1/6 of Clear span of the member, and
(c) 450 mm.
The spacing of hoops used as special confining reinforcement shall not exceed 1/4 of
minimum member dimension but need not be less than 75 mm nor more than 100 mm.
8/10/2019 Structural Analysis Report of RCC Building
42/45
BEAM DETAILING
Different things which are to be detailed in Beam Detailing is shown below vide sp 34,
page 108
SLAB DETAILING
Different things which are to be detailed in Slab Detailing is shown below vide sp 34,
page 127
8/10/2019 Structural Analysis Report of RCC Building
43/45
Design of Retaining Wall
Height of Earth Filling =3.6m
Thickness of Wall Assumed =200mm
Unit weight of Soil = 17kN/m3
Surcharge Pressure = 5kN/m2
Co efficient of Active Earth Pressure =0.33
Earth pressure (Kah) =25kN/m2taperded to top to a Value 0 kN/m2
Analysis
The building is having two basements so the retaining wall is inevitable at basement 1and 2. An
internal retaining wall is proposed to separate basement2 and basement 1. The retaining wall is
supported on grade beams, building columns and slabs at top. Hence it is acting as a retaining
slab supported on four sides which effectively reducing the design complications. Another
retaining wall is proposed to retain the external earth forming the road. This retaining wall is
supported on beams at bottom, vertically restrained columns. The top of retaining wall is fixed to
lateral beams connecting vertical columns. This retaining wall is supported on columns
supported on cantilevered grade beams. The analysis is done with building frame in Etabs
software, the results were extracted to design the same.
8/10/2019 Structural Analysis Report of RCC Building
44/45
Moments in Plate
Maximum Vertical Moment Mx = 50kNm
Moments in Plate
Maximum Horizontal Moment Mx = 30kNm
8/10/2019 Structural Analysis Report of RCC Building
45/45
Depth of Section
Effective Depth dreq =Mu/ (0.138fckb)
d= 147.5mm,
Provided d =175mm with an overall depth of 200mm. hence okay.
Design for Vertical Moment
Mx = 50 kNm
Factored Moment = 75kNm
Mu/(bd2) = 2.45and
Pt =0.648
Hence provide reinforcement as T 12 @ 100mm C/C as Vertical.
Design for Horizontal Moment
Mx =30 kNm
Factored Moment = 45kNm
Mu/(bd2) = 1.50and
Pt =0.648
Hence provide reinforcement as T 12 @ 150mm C/C as Vertical.
Design for Shear
Vu =45 kN
Factored Shear Force Vu= 67.5kN
Nominal shear stress,v = Vu/bd
= 0.385
From IS 456,
Design shear stressc = 0.60
v