Structural Analysis Report of RCC Building

Embed Size (px)

Citation preview

  • 8/10/2019 Structural Analysis Report of RCC Building

    1/45

    ABBREVIATIONS

    A - Area

    bf - Effective width of flange

    D - Overall depth of beam or slab or diameter of column;

    dimension of a rectangular column in the direction under

    consideration

    Df - Thickness of flange

    DL - Dead load

    d - Effective depth of beam or slab

    d - Depth of compression reinforcement from the highly

    compressed face

    EC - Modulus of elasticity of concrete

    EL - Earthquake load

    Es - Modulus of elasticity of steel

    fck - characteristic cube compressive strength of concrete

    fy - Characteristic strength of steel

    Ief - Effective moment of inertia

    K - Stiffness of member

    k - Constant or coefficient or factor

    Ld - Development length

    LL - Live load or imposed load

    Lw - Horizontal distance between centers of lateral restraint

    l - Length of a column or beam between adequate lateral

    restraints or the unsupported length of a columnlef - Effective span of beam or slab or effective length of

    column

    lex - Effective length about x-x axis

    ley - Effective length about y-y axis

    ln - Clear span, face-to-face of supports

    lx - Length of shorter side of slab

    ly - Length of longer side of slab

  • 8/10/2019 Structural Analysis Report of RCC Building

    2/45

    ll - Span in the direction in which moments are determined,

    centre to centre of supports

    l2 - Span transverse to I,, centre to centre of supports

    l2 - l2 for the shorter of the continuous spans

    M - Bending moment

    m - Modular ratio

    P - Axial load on a compression member

    q0 - Calculated maximum bearing pressure of soil

    r - Radius

    s - Spacing of stirrups or standard deviation

    T - Torsional moment

    V - Shear force

    W - Total load

    X - Depth of neutral axis

    Z - Modulus of section

    z - Lever arm

    f - Partial safety factor for load

    m - Partial safety factor for material

    m - Percentage reduction in moment

    - Creep strain of concrete

    cbc - Permissible stress in concrete in bending compression

    cc - Permissible stress in concrete in direct compression

    sc - Permissible stress in steel in compression

    st - Permissible stress in steel in tension

    sv - Permissible tensile stress in shear reinforcement

    c - Shear stress in concrete

    c,max - Maximum shear stress in concrete with shear

    reinforcement

    v - Nominal shear stress

    - Diameter of bar

  • 8/10/2019 Structural Analysis Report of RCC Building

    3/45

    INTRODUCTION

    Public Hospitals are to be established as per government requirement and

    community expectations. According to the present time, public hospital sector handles

    the majority of acute care separations and accounts for most regional and remote

    hospitals while private hospitals are concentrated in metropolitan areas, and are more

    likely to treat patients of higher socio economic advantage. Public hospitals treat

    medical cases originated in an area including emergency cases where as in private

    sector, cases are selective and opted. These services are separate, not overlapping

    between public and private sector.

    Public Hospitals are completely and entirely run on the Government funding and

    money. Everything from the construction, to the salary of Doctors/Staff, to the medical

    equipments, medicines each and every single thing is being taken care of by local

    Government. A public hospital is considered to be a preferable option for the not- so-

    rich lot of people who despite acute illness cant afford heavy fees of private hospitals.

    Although it is very ironical to see that a hospital governed by the Government (who has

    obliviously more funds than a group of people or one person alone), does not offer that

    level of service which can be counted on in most of the times.

    The building is designed for Basement+ Lower Ground + Ground +4 floors.

    OPDS, Registration Facilities are planned in Ground floor. Basements are used for

    occupying various services like Medical Gases, Laundry, Electrical room, Generator etc.

    Operation theatres, Wards, Labour Rooms, pediatrics wards and Nursing Station areplanned in Other Floors. So it is planned to construct Basement+ Lower Ground+ Ground

    floors (3 floors) for accommodating the important facilities which is inevitable for the

    functioning of M&C Hospital. A Ramp is provided for connecting all the floors. The other

    facilities as per the initial planning can construct as future expansion for which the

    column and foundations are designed for.

    The building foundation was first proposed with column isolated footings based on the

    submitted soil report of nearest building. The Sbc recommended by soil expert was

    150kN/m2 1.5m from GL. The Building is proposed with two basements, so the founding

    level will be 4m below from existing GL, the N value at this level is good and hence the

    calculation of Sbc at this level yields as 200kN/m2. The design of foundation was done

    adopting a sbc of 200kN/m2

    and the DPR was submitted to Executive Engineer. On

    scrutiny of the same, he doubted bout the adoption of Sbc and the joint site visit with

    Exe. Engineer, Asst. Exe. Engineer and the Consultant decided to do a soil investigation

    at the proposed plot. The Geotechnical investigation is carried out by the Consultant

    itself and the results were co ordinate from Mar Athanasius College of Engineering.

  • 8/10/2019 Structural Analysis Report of RCC Building

    4/45

    STRUCTURAL SYSTEM

    The whole structure is analyzed as closed column beam frame in ETABS analysis

    software and the design of various structural elements done manually.

    Load transfer path is slab-beam-column-footing to soil.

    Design parameters

    Design loads

    Dead loads

    The dead loads are in accordance with IS 875 Part 1 (1987).

    For the calculation of dead load acting over beams at various levels the unit

    weight of the building materials are taken according to that given in IS 875 Part -I-Dead

    weight of building materials. For calculating the live load acting over various floor levels

    IS 875 Part II is referred. All the loads are given according to the data given in the floor

    plans and cross sections given. The self weight of the structure is taken by the software

    itself.

    The unit weight of hollow brick masonry is taken as =20 kN/m3

    The unit weight of concrete is taken as =25 kN/m3

    Weight of brick wall = 0.20 x 3.3x 20 = 13.20kN/m

    Wt of floor finish = 1.0 kN/m2

    Self Wt of floor slab (12cm Thick) = 3 kN/m2

    Load considered for water tank = 15 kN/m2

    Live loads

    The live loads are in accordance with IS 875 Part 2 (1987).

    type Live load (kN/m2)

    Wards, Nursing

    stations2

    Operating rooms, X

    rays, Scan, store 3

  • 8/10/2019 Structural Analysis Report of RCC Building

    5/45

    Stair cases,

    Balconies, Corridors,4

    OPDs, Offices, 2.5

    Laboratories,

    laundries, Kitchen3

    Earthquake Loads as per IS: 1893 (part 1): 2002

    Dynamic forces on multi-storied are best computed through a detailed vibration analysis.

    Detailed dynamic analysis or modal analysis or pseudo static analysis should be carried

    out depending on the importance of problem. BIS Code 1893 (Part 1): 2002 recommends

    that [Ref: Cl: 7:8:1]

    Dynamic analysis shall be performed to obtain the design seismic force, and its

    distribution to different levels along the height of the building and to the various lateral

    load-resisting elements for the following buildings:

    a) Regular buildings those greater than 40m in height in Zone IV

    and Zone V, and those greater than 90m in height in Zone II and

    Zone III.b) Irregular buildingall framed buildings higher than 12m in Zones

    IV and Zone V, and those greater than 40m in height in Zone II and

    III.

    Since the height of the residential complex is 44.35m and its located in Zone III, static

    method of analysis was performed to find the seismic load and its distribution.

    Static method:

    The base shear or total design lateral force along any principal direction shall be

    determined by the following expression:

    VB= AhW

    where,

    VB = The design base shear

    Ah = Design horizontal acceleration spectrum value using the fundamental natural

    period T

  • 8/10/2019 Structural Analysis Report of RCC Building

    6/45

    W= Seismic weight of the building.

    The design horizontal seismic coefficientgR2

    SIZ ah A

    Where,

    Z = Zone factor given in table 2, for the Maximum Considered Earthquake (MCE)

    and service life of structure in a zone. The factor 2 in the denominator of Z is

    used so as to reduce the MCE zone factor to the factor for Design Basis

    Earthquake (DBE)

    I = Importance factor, depending upon the functional use of structures,

    characterized by hazardous consequences of failure, post-earthquake

    functional needs, historical value or economic importance (Table 6 IS 1893

    (Part 1):2002

    R = Response reduction factor, depending on the perceived seismic damage

    performance of the structure, characterized by ductile or brittle deformations.

    However, the ratio (I/R) shall not be greater than 1.0. The values for

    buildings are given in Table 7 of IS 1893 (Part 1): 2002.

    g

    Sa Average response acceleration coefficient.

    Distribution of Design Force

    The design base shear VB was distributed along the height of the buildings

    as per the following expressions.

    ni

    i

    ii

    iii

    hW

    hWVBQ

    1

    2

    2

    Where,

    iQ = Design lateral force at floori

    iW = Seismic weight of floori

    ih = Height of floori measured from base.

  • 8/10/2019 Structural Analysis Report of RCC Building

    7/45

    n = Number of storeys in the building is the number of levels at which the

    masses are located.

    Seismic weight, W

    The seismic weight of each floor is its full dead load plus appropriate

    amount of imposed loads while computing the seismic weight of each floor, the weight of

    columns and walls in any storey shall be equally distributed to the floors above and below

    the storey. The seismic weight of the whole building is the sum of the seismic weights of

    all the floors. Any weight supported in between storey shall be distributed to the floors

    above and below in inverse proportion to its distance from the floors.

    Imposed uniformly distributed floor

    loads kN/m

    Percentage of imposed load

    %

    Upto and including 3.0 25

    Above 3.0 50

    Table-Percentage of imposed load to be considered in seismic weight calculation

    Determination of Design Base Shear for Seismic Analysis:

    As per IS 1893 (Part 1):2002

    Fundamental natural period, Ta(Clause 7.6.2) = 0.09h/d

    h = height of building exclude basement floor = 20.30 m

    d- base dimension at plinth level in respective direction=36.6

    = 0.50sec

    For 0.1

  • 8/10/2019 Structural Analysis Report of RCC Building

    8/45

    4.3.6. Calculation of design seismic pressure

    Calculation of design seismic pressure

    The above parameters are defined in the ETABS software and software itself will

    calculate the seismic loads and create the load cases and load combinations. The software

    automatically has done the distribution of seismic force.

  • 8/10/2019 Structural Analysis Report of RCC Building

    9/45

    STRUCTURAL MATERIALS

    Concrete and Reinforcement

    Concrete: M25 for Foundations, M30 for Columns, M25 for Beams, Slabs, Stairs,

    and all other components

    Steel reinforcement:

    Fe500 TMT grade pertaining to IS: 1786 1985

    Cover:

    From durability requirement, environmental exposure condition is assumed as

  • 8/10/2019 Structural Analysis Report of RCC Building

    10/45

    The nominal cover to outermost reinforcement shall be as follows for two hour

    fire rating.

    Columns 40mm

    Beams 25mm

    Slab 20mm

    Stair 25mm

    Foundations 50mm

    MODELLING AND ANALYSIS METHODOLOGY

    BRIEF:

    The building is modelled as 3D structure and is analysed as SMRF (Special

    Moment Resisting Frames).

    The FEM based structural software (ETABS Nonlinear v9.7.2) is used for modeling and

    analysis of the building.

    MODELLING

    The basic approach for using the program is very straight forward. The user

    establishes grid lines, defines material and structural properties, places structural

    objects relative to the grid lines using point, line and area object tool. All the types of

    loads that the structure is subjected can be defined and assigned to the appropriate

    structural components. The analysis can be performed and the results are generated in

    graphical or tabular form that can be printed to a printer or to a file for use in other

    programs. The following topics describe some of the important areas in the modeling.

    Defining Material Properties

    In the property data area, name of the material, mass per unit volume, weight

    per unit volume, modulus of elasticity, Poissons ratio should be specified for each type

    of material defined. The mass per unit volume is used in the calculation of self-mass of

    the structure. The weight per unit volume is used in calculating the self-weight of the

    structure.

  • 8/10/2019 Structural Analysis Report of RCC Building

    11/45

    Defining Frame Sections

    Frame sections like beams, columns and are defined under this. The sizes of

    beams and columns are fixed here and their reinforcement requirements and concrete

    covers defined. Hinges were introduced (i.e. end moments were released) near the

    connecting where ever required.

    Defining Slab Sections

    For defining the type of slab section in ETABS, there are three options available

    based on its behavior, namely shell type, membrane type and plate type. Shell type

    behavior means, both in-plane membrane stiffness and out-of-plane plate bending

    stiffness can be provided for the section. Membrane type behavior mean, only in-plane

    membrane stiffness is provided for the section. Plate-type behavior means that only out-

    of-plane bending stiffness is provided for the section. In the present analysis, slabs are

    given membrane type behavior to provide in plane stiffness and shear walls are defined

    as shell elements. Shell elements should be divided in to finer mesh so that proper

    connectivity is achieved, as our focus is mainly on the global behavior of the in filled

    frame structure.

    Dead load, live load, roof live load, are defined under the static load case option

    of the define menu. Various load combinations can also be defined in the load

    combinations option of the define menu.

    Member Property Specifications and Support Condition

    The dimensions of different members were fixed based on the trial design. The column

    dimensions provided for the modeling is as prescribed by the Architect. If necessary it

    will revised during the design stage. The beams are provided in such a way that torsion is

    released since compatibility torsion alone comes in them. The member properties

    assigned are as given below.

    Slab

    Thickness of the slab = 120mm

  • 8/10/2019 Structural Analysis Report of RCC Building

    12/45

    Beams

    The dimensions of the beams are as shown below

    Beam Breadth, B Depth, D

    Fixed Beams 200mm 500mm

    Fixed beam 250mm 600mm

    Fixed beam 200mm 450mm

    Column:

    The column dimensions are as follows:

    Ground floor: 250mm X 500mm, 300mm X 500mm, 400mm X 400mm, 500mmX 500mm,

    (steel as per details)

    Staircase:

    The staircase is provided as an equivalent slab. The thicknesses of the slab used for

    staircase is 175mm

    Support condition

    Then support conditions were given to the structure. The support condition given was

    pinned.

    LOAD COMBINATION

    The following are the load combinations as IS: 456-2000

    1) 1.5 D.L + 1.5 LL

    2) 1.5 DL + 1.5 SLX

    3) 1.5 DL - 1.5 SLX

    4) 1.5 DL + 1.5 SLY

    5) 1.5 DL - 1.5 SLX

  • 8/10/2019 Structural Analysis Report of RCC Building

    13/45

    6) 0.9 DL + 1.5 SLX

    7) 0.9 DL - 1.5 SLX

    8) 0.9 DL + 1.5 SLY

    9) 0.9 DL - 1.5 SLY

    10) 1.2 DL + 1.2LL + 1.2 SLX

    11)1.2 DL + 1.2LL - 1.2 SLX

    12) 1.2 DL + 1.2LL + 1.2 SLY

    13)1.2 DL + 1.2LL - 1.2 SLY

    Column Layout

  • 8/10/2019 Structural Analysis Report of RCC Building

    14/45

    Completed Model

  • 8/10/2019 Structural Analysis Report of RCC Building

    15/45

    Completed Extruded Model

  • 8/10/2019 Structural Analysis Report of RCC Building

    16/45

    Completed Extruded Model of Ramp

  • 8/10/2019 Structural Analysis Report of RCC Building

    17/45

    DESIGN OF ELEMENTS

    Analysis Results

    Axial Force on Columns

  • 8/10/2019 Structural Analysis Report of RCC Building

    18/45

    Bending Moment Diagram of Beams

    Shear Force Diagram of Beams

  • 8/10/2019 Structural Analysis Report of RCC Building

    19/45

    Design Methodology:

    All structural concrete elements will be designed according to the Limit State

    Method as specified in IS: 456 - 2000 for reinforced concrete elements and detailing will

    be as per standards.

    Design of foundation:

    The building foundation was first proposed with column isolated footings based

    on the submitted soil report of nearest building. The Sbc recommended by soil expert

    was 150kN/m2

    1.5m from GL. The Building is proposed with two basements, so the

    founding level will be 4m below from existing GL, the N value at this level is good and

    hence the calculation of Sbc at this level yields as 200kN/m

    2

    . The design of foundationwas done adopting a sbc of 200kN/m

    2and the DPR was submitted to Executive

    Engineer. On scrutiny of the same, he doubted bout the adoption of Sbc and the joint

    site visit with Exe. Engineer, Asst. Exe. Engineer and the Consultant decided to do a soil

    investigation at the proposed plot. The Geotechnical investigation is carried out by the

    Consultant itself and the results were co ordinate from Mar Athanasius College of

    Engineering.

    Soil Profile

    The boreholes, numbered 1,2.3 and 4 were terminated at 29.40

    m,29.90m,26.00m and 27.70m respectively. Hard rock was encountered in all the

    boreholes. Lateritic clayey silt were found in all the bore holes. Very fine sandy silt, very

    fine silty sand and Lateritic clay with sand were found in some of the boreholes ,Hard

    rock was fund in all the boreholes,. The N value is found tobe varying from 7 to greater

    than 100.

    DATA AND DISCUSSION

    The bore hole details are given in the attached bore log. The report on the

    analysis of the recovered representative samples collected from the boreholes is

    attached. Based on visual identification and the laboratory test results using

    representative samples, the soil profile at the bore hole location is drawn and are also

    presented in borehole logs. For the lateritic clay found in all the bore holes, sand content

    3% to9%, silt content varies between 42% and 73% and clay content was between 18%

  • 8/10/2019 Structural Analysis Report of RCC Building

    20/45

    between 0.30 kg/cm2 and 0.60 kg/cm2. The N value for these strata was fond to be

    between 8 and 21. For the lateritic clayey silt found in all the bore holes, sand content

    2% to 15% silt content varies between 72% and 87% and clay content was between 3%

    ad 27%. The cohesion was between 0.25 kg/cm2 and 0.70 kg/cm2. The N value for these

    strata was found to be between 7 and 45. The very fine sandy silt found in bore holes 1,3

    and 4 sand content varies between 15 % to 42% and silt content varies between 55%

    and 85%. The N value for these strata was found to be between 23 and greater than 100.

    The very fine silty sand found in bore holes 1 and 2 sand content varies between 58% to

    68% and silt content varies between 32% and 42%. The N value was found to be greater

    than 100. The Lateritic clay with sand found in bore holes 2,3 and 4, sand content varies

    between 0% to 21%, silt content varies between 36% and 55% and clay content between

    35% and 45%. The N value for these strata was fond to be between 7 and 18. From the

    test results for the stratum having N value more than 10 the safe bearing capacity can be

    taken as 6.3T/sq.m and for layers having N value 20, it may be taken as 17.2T/sq.m.

    RECOMMENDATIONS

    The soil at the site mainly consists of Lateritic clay and Lateritic clayey silt. Very

    fine sandy silt. Very fine silty sand and Lateritic clay with sand were found in some of the

    boreholes. Hard rock was found at all the bore holes. The N value is found to be varying

    from 7 to greater than 100.

    For the stratum having N value more than 10, the safe bearing capacity can be

    taken as 6.3T/sq.m and for layers having N value 20, it may be taken as 17.2T/sq.m.

    Depending on the number of floors, the foundation shall be decided. It is suggested to

    provide pile foundation which extends to hard rock. Open foundation shall be adopted.

    If the load on foundation is not high. She recommendations made in this report are

    based on the results of field tests as well as tests done on the samples recovered from

    the bore holes. It is presumed that the soil below the maximum depth of exploration at

    the site does not vary much or rather improves from that observed at the maximum

    depth

    Based on this report, the foundation system adopted is Pile Foundation. Since

    the capacity is not provided by the Soil Expert, the Consultant Engineer calculated both

    geotechnical and Structural Capacity of various dia piles

  • 8/10/2019 Structural Analysis Report of RCC Building

    21/45

    Geotechnical Capacity of Piles

    450mmDia

    500mm dia

  • 8/10/2019 Structural Analysis Report of RCC Building

    22/45

    550mm dia

    Pile Capacity

    Sl No Pile Diameter(mm) Pile Capcity(kN)

    1 450 970

    2 500 1100

    3 550 1300

    Design of Pile

    450mm Dia Pile

    As per IS: 2911

    Fixity depth = 8d = 8 x 0.45 = 3.6m

    Total No of Pile =134 No.s

    Base Shaer( Result from Etabs)= 4354kN

    Horizontal Force =32.73kN

    Moment due to horizontal force = 117.8kNm

  • 8/10/2019 Structural Analysis Report of RCC Building

    23/45

    Factored Moment Mu =176kN-m

    For 450mm dia pile; P =970kN

    Pu =1445kN

    2Df

    P

    ck

    u

    = (1445x1000)/ (25x4502)

    =0.284

    3

    6

    345025

    10176

    Df

    M

    ck

    u

    =0.077

    Providing 40 mm clear cover and assuming 20 mm dia bar

    d' =50

    D

    d1

    = 0.106

    062.ck

    f

    P, p = 1.55

    pmin= 0.8

    Area of longitudinal steel 22403mmAs

    This is to be provided up to fixity depth 8d = 3.6m

    Hence provide 12 nos of Y16mm dia bars as longitudinal reinforcement

    Provide circular links of 8 mm dia at 200 mm c/c spacing.

    Provide minimum longitudinal reinforcement as per IS 2911 Part I/ section 2

    Minimum area of longitudinal steel = 0.4% of total c/s area

    =635 mm2

    Hence provide 6 nos of Y16mm dia bars as longitudinal reinforcement

    Provide circular links of 8 mm dia at 150 mm c/c spacing.

    Provide circular spacers of 12mm dia at 3000mm c/c

  • 8/10/2019 Structural Analysis Report of RCC Building

    24/45

    500mm Dia Pile

    As per IS: 2911

    Fixity depth = 8d = 8 x 0.5 = 4.0 m

    Total No of Pile =134 No.s

    Base Shaer( Result from Etabs)= 4354kN

    Horizontal Force =32.73kN

    Moment due to horizontal force = 130.8kNm

    Factored Moment Mu =196.38kN-m

    For 450mm dia pile; P =1100kN

    Pu =1650kN

    2Df

    P

    ck

    u

    = (1650x1000)/ (25x5002)

    =0.264

    3

    6

    3

    50025

    10196

    Df

    M

    ck

    u

    =0.062

    Providing 40 mm clear cover and assuming 20 mm dia bar

    d' =50

    D

    d1

    = 0.10

    041.ckf

    P, p = 1.01

    pmin= 0.8

    Area of longitudinal steel 21982mmAs

    This is to be provided up to fixity depth 8d = 4m

    Hence provide 10 nos of Y16mm dia bars as longitudinal reinforcement

    Provide circular links of 8 mm dia at 200 mm c/c spacing.

  • 8/10/2019 Structural Analysis Report of RCC Building

    25/45

    Provide minimum longitudinal reinforcement as per IS 2911 Part I/ section 2

    Minimum area of longitudinal steel = 0.4% of total c/s area

    =785 mm2

    Hence provide 5 nos of Y16mm dia bars as longitudinal reinforcement

    Provide circular links of 8 mm dia at 150 mm c/c spacing.

    Provide circular spacers of 12mm dia at 3000mm c/c

    Design of Pile Cap

    Two pile group

    Material Constants

    Concrete,fck = 25 N/mm

    Steel, fy = 500 N/mm

    Each pile should be connected using pile cap with a minimum of 100mm edge distance to either

    sides of the pile. This pile cap is designed as simply supported beam.

    As per IS 2911 spacing between two pile is 2.5 x dia of pile

    Length of pile cap = 2.5 x 500 + 2 x 250 + 2 x 150

    =2050 mm=2050mm

    Depth of pile cap = development length of column bar + cover

    As per SP-16 Table 65

    For 20 mm diameter bars

    Ldc = 777 mm

    Assume a 100 mm projection of pile in to the cap concrete

    Depth of pile cap = 777 + 100

    = 877 mm

    Provide an overall depth, D = 1000mm

    Breadth of pile cap = diameter of pile + 150 mm overhang

    = 500 + 2 x 150

    = 800mm

    Size of pile cap 2.05 x 0.8 x 1.0 m

  • 8/10/2019 Structural Analysis Report of RCC Building

    26/45

    Effective depth, d = 900 mm

    b =800 mm

    Factored axial load on pile Pu = 1650 kN

    Bending moment at face of column = 1100 x 0.625

    = 656.25 kN-m

    Ultimate moment,Mu = 1030 kN-m

    Mu / (bd2) = 1.69

    % of tension steel, pt = 0.428

    Area of tension reinforcement,Ast = 3425mm

    Provide reinforcement of Y25mm dia bars 7 Nos

    Area of steel provided = 3430 mm

  • 8/10/2019 Structural Analysis Report of RCC Building

    27/45

    Hence Maximum shear force on pile cap = 1100kN

    Ultimate shear,Vu = 1650 kN

    Nominal shear stress, v = 2.4 N/mm

    100As/ (bd) = 0.48

    Deign shear strength, c = 0.49 N/mm

    ie, v > c so shear reinforcement are needed

    Assume 12mm dia 6 legged stirrups

    Vus =Vu - c bd = 1372 kN

    Diameter of bar = 12 mm

    Area of shear reinforcement effective in shear,Asv = 678.58 mm

    Provide Y12 mm dia 6 legged stirrups

    Spacing of shear reinforcement,Sv = 0.87 x d xfyx Asv

    Vus

  • 8/10/2019 Structural Analysis Report of RCC Building

    28/45

    Design of columns:

    Columns are designed by taking the forces and moments from the FEM software.

    The sizes of columns are kept constant at all the stories. The design of column is done

    considering the axial compression, biaxial bending moment including slenderness effect.

    Excel spread sheets are used for designing of columns as per standards. The Columns are

    designed for GF+4 floors.

    Axial force diagram of typical Column

  • 8/10/2019 Structural Analysis Report of RCC Building

    29/45

  • 8/10/2019 Structural Analysis Report of RCC Building

    30/45

    ETABS 2013 13.1.3 License #*192TZNDF9YDF4PW

    Final Model with Pile.EDB Page 1 of 2 7/16/2014

    ETABS 2013 Concrete Frame Design

    IS 456:2000 Column Section Design

    Column Element Details Type: Ductile Frame (Summary)

    Level Element Section ID Combo ID Station Loc Length (mm) LLRF

    GF C83 C300X500 DCON7 0 3900 0.594

    Section Properties

    b (mm) h (mm) dc (mm) Cover (Torsion) (mm)

    300 500 50 23.6

    Material Properties

    E c (MPa) f ck (MPa) Lt.Wt Factor (Unitless) f y (MPa) f ys (MPa)

    27386.13 30 1 500 500

    Design Code Parameters

    C S

    1.5 1.15

    Axial Force and Biaxial Moment Design For P u , M u2 , M u3

    Design P ukN

    Design M u2kN-m

    Design M u3kN-m

    Minimum M 2kN-m

    Minimum M 3kN-m

    Rebar Area

    mm

    Rebar %

    %

    2092.8237 -45.7945 142.2591 41.8565 48.693 3152 2.1

    Axial Force and Biaxial Moment Factors

    K Factor

    Unitless

    Length

    mm

    Initial Moment

    kN-m

    Additional Moment

    kN-m

    Minimum Moment

    kN-m

    Major Bend(M3) 0.831928 3300 57.2852 0 48.693

    Minor Bend(M2) 0.704905 3300 -18.3178 0 41.8565

  • 8/10/2019 Structural Analysis Report of RCC Building

    31/45

    ETABS 2013 13.1.3 License #*192TZNDF9YDF4PW

    Final Model with Pile.EDB Page 2 of 2 7/16/2014

    Shear Design for V u2 , V u3

    Shear V ukN

    Shear V ckN

    Shear V skN

    Shear V pkN

    Rebar A sv/s

    mm/m

    Major, Vu2 64.3742 140.4314 54 87.6777 332.53

    Minor, V u3 63.1923 133.5314 50 63.1923 554.22

    Joint Shear Check/Design

    Joint Shear

    Force

    kN

    Shear

    V TopkN

    Shear

    V u,TotkN

    Shear

    V ckN

    Joint

    Area

    cm

    Shear

    Ratio

    Unitless

    Major Shear, V u2 N/A N/A N/A N/A N/A N/A

    Minor Shear, V u3 N/A N/A N/A N/A N/A N/A

    (1.1) Beam/Column Capacity Ratio

    Major Ratio Minor Ratio

    N/A N/A

    Additional Moment Reduction Factor k (IS 39.7.1.1)

    A gcm

    A sccm

    P uzkN

    P bkN

    P ukN

    k

    Unitless

    1500 31.5 3207.0354 989.5549 2092.8237 0.502467

    Additional Moment (IS 39.7.1)

    Consider

    M a

    Length

    Factor

    Section

    Depth (mm)

    KL/Depth

    Ratio

    KL/Depth

    Limit

    KL/Depth

    Exceeded

    M aMoment (kN-m)

    Major Bending (M 3 ) No 0.8462 0.5 5.4907 12 No 0

    Minor Bending (M 2 ) No 0.8462 0.3 7.754 12 No 0

    Notes:

    N/A: Not Applicable

    N/C: Not Calculated

    N/N: Not Needed

  • 8/10/2019 Structural Analysis Report of RCC Building

    32/45

    Design of beams

    The RC beams and slabs are designed using Excel spreadsheet using the analysis

    results from FEM software. The top as well as bottom reinforcement shall consist of at

    least two bars throughout the member length.

    Bending Moment diagram of typical continuous beam

    Shear Force diagram of typical continuous beam

  • 8/10/2019 Structural Analysis Report of RCC Building

    33/45

    Design for area of steel and shear for singly reinforced beam by limit state design method

    Calculation of Ast req for beams

    Ref IS 456-2000 Cl G-1.1b & G-1.1c For sections without compression reinforcement

    fy fck b D Cc Cg of bar d Mulim pt lim

    N/mm2 N/mm2 mm mm mm mm mm kN.m %

    500 25 200 500 25 8 467 145.03 0.94

    Mu support Ast req. spt ptreq.spt Mu span Ast span ptreq.span

    kNm mm2 % kNm mm % d req mm d prov mm Result

    135 802.93 0.86 55 288.73 0.31 450.56 467 okay

    Reinforcement details provided at support and span of beam

    Nos. dia Ast support pt support Result Nos. dia Ast span pt span

    mm mm % mm mm %

    2 16 2 16

    2 16 2 16

    Check for shear in beams (limit state design method)Ref IS 456-2000 Cl 40.1, Cl 40.2.3, Table 19, Table 20 & Cl 40.2.1

    fck Vu pt v c c max

    prov. Cl 40.1 Table 19 Table 20

    N/mm2 kN % N/mm2 N/mm2 N/mm2

    25 110 0.86 1.18 0.61 3.1

    Design for shear reinforcement (vertical stirrups)

    Ref IS 456-2000 Cl 40.4a

    Vu cb d Vus Vus/d fy assuming no. stirrup Vus/d prov.

    req req stirrup dia of stirrup sp assumed kN/cm

    kN kN kN kN/cm N/mm2

    mm legs mm Cl 40.4 a

    110 56.97 53.03 1.14 415 8 2 100 3.630

    Check for minimum and maximum spacing of stirrup

    Min stirrup Max stirrup stirrup Result

    spacing mm spacing mm sp prov.

    Cl 26.5.1.6 Cl 26.5.1.5 mm

    546.64 300 100 Hence ok

    Side face reinforcement

    Ref IS 456-2000 Cl 26.5.1.3

    b D side face spc b/w

    of reinf. bars not to

    web req. / face no. dia of Ast prov. exceedmm mm Cl 26.5.1.3 per face bar mm Cl 26.5.1.3

    200 500 not req 2 12 226.19 200 mm

    Check for span to depth ratio

    Ref IS 456-2000 Cl 23.2.1

    Type of fy span d pt req. pt prov. pc MFt MFc

    beam N/mm2 mm mm % % %

    Cont.Beam 500 5250 467 0.31 0.86 0 1.924 1

    l/d l/d Result

    prov Cl 23.2.1 Cl 23.2.1

    11.24 50.02 Okay

    okay 804.25 0.86

    tau_v tau_c,design for shear

  • 8/10/2019 Structural Analysis Report of RCC Building

    34/45

    Design of slab

    Design of slab

    Material Constants:

    Concrete,fck= 25 N/mm

    Steel, fy = 500 N/mm

    Loads:

    Using 120 mm thick slab

    Dead Load on Slab = 0.12 x 25 = 3 kN/m

    Live Load on Slab = 3kN/m

    Finishes = 1.5 kN/m

    Partition load = 2.5 kN/m

    Total = 10.0 kN/m

    Boundary Conditions one long edge discontinuous

    Assume a clear cover of 20 mm & 8 mm dia bars

    Eff: depth along shorter direction dx = 96 mm

    Eff: depth along longer direction dy = 88 mm

    Effective span as per IS 456: 2000 clause 22.2.b

    lyeff= 3.2+0.088 = 3.288 m

    lxeff= 3.9+0.096 = 3.996 m

    lyeff/lxeff =1.22, Hence design as Two Way Slab.

  • 8/10/2019 Structural Analysis Report of RCC Building

    35/45

    1 Design for area of steel and shear for two way slab by limit state design method

    Slab Geometry

    Lx Ly Ly/Lx

    m m

    3.2 3.9 1.219

  • 8/10/2019 Structural Analysis Report of RCC Building

    36/45

    Calculation of Ast req for slab spanning Ly

    Ref IS 456-2000 Cl G-1.1b & G-1.1c

    - Muy cont. Ast min pt req.cont. + Muy span Ast min pt req.span

    kNm mm2 % kNm mm %

    4.26 144.00 0.16 3.23 144.00 0.16

    Reinforcement details provided at support and span of slab spanning Ly

    dia prov. spacing Ast cont. pt cont. Result dia prov. spacing Ast span pt span

    mm mm mm % mm mm mm %

    8 150 8 150

    0 250 0 250

    Check for shear in solid slabs for limit state design method

    Ref IS 456-2000 Cl 40.1, Cl 40.2.3, Table 19, Table 20 & Cl 40.2.1.1

    fck Vu b D clear cg d

    N/mm kN mm of slab mm cover mm of bar mm mm

    25 21.6 1000 120 20 4 96

    pt v k c c max

    Cl 40.1 Cl 40.2.1.1 Table 20

    % N/mm N/mm N/mm

    0.35 0.23 0.55 3.1

    Check for span to depth ratio

    Ref IS 456-2000 Cl 23.2.1

    Type of fy span d pt req. pt prov. pc MFt MFcbeam N/mm

    2 mm mm % % %

    Cont.slab 500 3200 96 0.15 0.35 0 2.936 1

    l/d l/d Result

    prov Cl 23.2.1 Cl 23.2.1

    33.33 76.34 Okay

    Result

    tau_v < k tau_c, Ok

    tau_v

  • 8/10/2019 Structural Analysis Report of RCC Building

    37/45

    DESIGN OF DOG LEGGED STAIRCASE

    Data

    Internal Dimensions

    Length = 4.76 m

    Width = 2.6 m

    Floor Height = 3.9 m

    Fck = 25 N/mm

    Fy = 500 N/mm

    Riser = 160 mm

    Tread = 280 mm

    Landing width = 1200 mm

    Effective Span = 4.8 m

    Height of each flight = 1.95 m

    No. of risers in each flight 12.1875 Nos

    No. of Tread in each flight 11.1875 Nos

    Design

    d = 152 mm Required

    D = 175 mm

    d = 154 mm

    Loads

    = .

    DL on horizontal area = 5.04 kN/m

    DL of steps = 2 kN/m

    LL = 5 kN/m

    FF = 1.5 kN/m

    Total load = 13.54 kN/m

    Factored load = 20.3 (of one flight)

    BM and SF

    Mu = 58 kN-m

    Vu = 49 kN

    d from BM consideration 146 mm

    k = 2.466

    pt = 0.652 %

    Ast = 1005 mm

    Main Reinforcement

    Dia = 12 mm

    Spacing = 112 mm

    Distr ibut ion Steel

    Ast = 185 mm

    Dia of bar = 8 mm

    Spacing = 270 mm

    Development Length

  • 8/10/2019 Structural Analysis Report of RCC Building

    38/45

    Floor Beam

    4760

    mm

    DOWN UP

    1200 mm

    Mid Landing Beam

    2600

    mm

    Ld = 590 mm

    300

    mm

    Y8 @ 270 mm C/C (Distribution Reinforceme

    Y12@112 mm C/C

    (Main Reinforcement)

    175 mm

    175 mm

    DETAILING

  • 8/10/2019 Structural Analysis Report of RCC Building

    39/45

    ETABS 2013 13.1.3 License #*192TZNDF9YDF4PW

    Final Model with Pile.EDB Page 1 of 2 7/16/2014

    ETABS 2013 Shear Wall Design

    IS 456:2000 Pier Design

    Pier Details

    Story ID Pier ID Centroid X (mm) Centroid Y (mm) Length (mm) Thickness (mm) LLRF

    TF P4 8115.5 10950.9 4556.7 250 0.426

    Material Properties

    E c (MPa) f ck (MPa) Lt.Wt Factor (Unitless) f y (MPa) f ys (MPa)

    25000 25 1 500 500

    Design Code Parameters

    S C IP MAX IP MIN P MAX

    1.15 1.5 0.02 0.0025 0.8

    Pier Leg Location, Length and Thickness

    StationLocation

    ID Left X 1mm

    Left Y 1mm

    Right X 2mm

    Right Y 2mm

    Lengthmm

    Thicknessmm

    Top Leg 1 7650 11130 9700 11130 2050 250

    Top Leg 2 9700 11130 9700 11886.7 756.7 250

    Top Leg 3 5900 10500 7650 10500 1750 250

    Bottom Leg 1 7650 11130 9700 11130 2050 250

    Bottom Leg 2 9700 11130 9700 11886.7 756.7 250

    Bottom Leg 3 5900 10500 7650 10500 1750 250

    Flexural Design for P u, M u2 and M u3

    Station

    Location

    Required

    Rebar Area (mm)

    Required

    Reinf Ratio

    Current

    Reinf Ratio

    Flexural

    Combo

    P ukN

    M u2kN-m

    M u3kN-m

    Pier A gmm

    Top 2848 0.0025 0.0037 DWAL14 784.892 139.749 275.88 1139166

    Bottom 5457 0.0048 0.0037 DWAL12 635.1675 -660.8535 -3663.8173 1139166

    Shear Design

    Station

    Location

    ID Rebar

    mm/m

    Shear Combo P ukN

    M ukN-m

    V ukN

    V ckN

    V c + V skN

    Top Leg 1 OS DWAL12 430.2772 1013.9719 -1311.7222 130.8789 500.7702

    Top Leg 2 1018.78 DWAL7 297.3436 -172.3923 272.992 50.4431 272.992

    Top Leg 3 OS DWAL11 493.7266 -892.7358 1127.576 115.2453 431.0062

    Bottom Leg 1 OS DWAL12 72.6428 -1121.5661 -1314.807 147.0513 516.9426

    Bottom Leg 2 861.61 DWAL9 167.9797 189.7462 238.6595 50.4431 238.6595

    Bottom Leg 3 OS DWAL12 878.7701 -880.6772 -1092.6488 153.1835 468.9444

    Number of legs where shear force exceeds max allowed (top, bottom) = 2, 2

  • 8/10/2019 Structural Analysis Report of RCC Building

    40/45

    DETAILING

    All the structural elements were detailed according to IS 456:2000 and SP34.

    Detailed drawings were prepared in AutoCAD 2007. Detailing of all the structural

    elements were done based on SP 34 and IS 13920

  • 8/10/2019 Structural Analysis Report of RCC Building

    41/45

    COLUMN DETAILS

    Special confining reinforcement as per is 13920:1993

    Special confining reinforcement shall be provided over a length lo from each joint face,

    towards midspan, and on either side of any section, where flexural yielding may occur

    under the effect of earthquake forces

    The length lo shall not be less than

    (a) Larger lateral dimension of the member at

    Section where yielding occurs,

    (b) 1/6 of Clear span of the member, and

    (c) 450 mm.

    The spacing of hoops used as special confining reinforcement shall not exceed 1/4 of

    minimum member dimension but need not be less than 75 mm nor more than 100 mm.

  • 8/10/2019 Structural Analysis Report of RCC Building

    42/45

    BEAM DETAILING

    Different things which are to be detailed in Beam Detailing is shown below vide sp 34,

    page 108

    SLAB DETAILING

    Different things which are to be detailed in Slab Detailing is shown below vide sp 34,

    page 127

  • 8/10/2019 Structural Analysis Report of RCC Building

    43/45

    Design of Retaining Wall

    Height of Earth Filling =3.6m

    Thickness of Wall Assumed =200mm

    Unit weight of Soil = 17kN/m3

    Surcharge Pressure = 5kN/m2

    Co efficient of Active Earth Pressure =0.33

    Earth pressure (Kah) =25kN/m2taperded to top to a Value 0 kN/m2

    Analysis

    The building is having two basements so the retaining wall is inevitable at basement 1and 2. An

    internal retaining wall is proposed to separate basement2 and basement 1. The retaining wall is

    supported on grade beams, building columns and slabs at top. Hence it is acting as a retaining

    slab supported on four sides which effectively reducing the design complications. Another

    retaining wall is proposed to retain the external earth forming the road. This retaining wall is

    supported on beams at bottom, vertically restrained columns. The top of retaining wall is fixed to

    lateral beams connecting vertical columns. This retaining wall is supported on columns

    supported on cantilevered grade beams. The analysis is done with building frame in Etabs

    software, the results were extracted to design the same.

  • 8/10/2019 Structural Analysis Report of RCC Building

    44/45

    Moments in Plate

    Maximum Vertical Moment Mx = 50kNm

    Moments in Plate

    Maximum Horizontal Moment Mx = 30kNm

  • 8/10/2019 Structural Analysis Report of RCC Building

    45/45

    Depth of Section

    Effective Depth dreq =Mu/ (0.138fckb)

    d= 147.5mm,

    Provided d =175mm with an overall depth of 200mm. hence okay.

    Design for Vertical Moment

    Mx = 50 kNm

    Factored Moment = 75kNm

    Mu/(bd2) = 2.45and

    Pt =0.648

    Hence provide reinforcement as T 12 @ 100mm C/C as Vertical.

    Design for Horizontal Moment

    Mx =30 kNm

    Factored Moment = 45kNm

    Mu/(bd2) = 1.50and

    Pt =0.648

    Hence provide reinforcement as T 12 @ 150mm C/C as Vertical.

    Design for Shear

    Vu =45 kN

    Factored Shear Force Vu= 67.5kN

    Nominal shear stress,v = Vu/bd

    = 0.385

    From IS 456,

    Design shear stressc = 0.60

    v