28
Section 9‐1 SECTION 9 DECORATIVE STREET LIGHTING STANDARDS 9.1 Street Lighting Decorative street lighting is required on all public and private streets, public and private parking lots and along all shared use paths. Any variation from this requirement must have approval of the Public Works Director. Street lights shall be installed concurrently with underground utilities. Street lighting will be decorative in character, unless otherwise approved by the City Council. All decorative street lights must be compliant with the City's Outdoor Lighting Standards (Section 11-3-25 of the Whitefish City Code). Applicable lighting standard details 47a thru 47m must be included with lighting plans. Lighting plans shall include features such as, but not limited to, service assembly, photo control, layout of poles, conduits and pull boxes, conduit and wire sizes, fuses, etc. 9.1.1 Residential – Streets, Parking Lots & Shared Use Paths Use the following, or approved equal, street light poles and luminaries on residential streets, parking lots and shared use paths: Vendor: Mountain States Lighting (MSL) Luminaire: HADCO #C2316-50-HPS-J-240V Lamp: 50 Watt High Pressure Sodium (HPS) Pole: MSL #14EFA-5-TT/3x3-16.5WF(Name)-LEG-J(Green) Base: MSL #WF-16.5” Wx48” H-500-HDEB-J(Green) Break Away: See SD-47h Height: 17’-8” = Pole 14’-0” + Luminaire 3’-8” Pole Foundation: 18” Sonotube, 3’-8” Deep (See SD-47f) Qty. 4 - ¾” x 18” Ell Bolts 10” (+) Pattern, 3-½” Bolt Projection Isometric Footprint: See Cut Sheets for Isometric Footprint Exhibit Standard Drawing: See SD-47a 9.1.2 Commercial – Downtown Streets & Parking Lots Use the following, or approved equal, street light poles and luminaries on downtown streets and commercial parking lots: Vendor: Mountain States Lighting (MSL) Luminaire: HADCO #C2316-100-HPS-J-240V Lamp: 100 Watt High Pressure Sodium (HPS) Single Arm Pole: MSL #22TFS-SA/17’/2’x2.375”/SCR-22” MAD(Madison)-C2316AF1XT-(1) BA-J(Green) Double Arm Pole: MSL #22TFS-DBLSA/17’/2’x2.375”/SCR-22” MAD(Madison)-C2316AF1XT-(2) BA-J(Green) Base: MSL#MAD(Madison)-22”Wx38”H-HDEB-J(Green) Break Away: None

Street Lighting Standards Update - cityofwhitefish.org Lighting...9.1.5 Bollard – Share Use Paths ... Pull boxes shall be installed flush with finished grade. ... Simple wire size

Embed Size (px)

Citation preview

Page 1: Street Lighting Standards Update - cityofwhitefish.org Lighting...9.1.5 Bollard – Share Use Paths ... Pull boxes shall be installed flush with finished grade. ... Simple wire size

Section 9‐1 

SECTION 9 DECORATIVE STREET LIGHTING STANDARDS

9.1 Street Lighting  

Decorative street lighting is required on all public and private streets, public and private parking lots and along all shared use paths. Any variation from this requirement must have approval of the Public Works Director. Street lights shall be installed concurrently with underground utilities. Street lighting will be decorative in character, unless otherwise approved by the City Council. All decorative street lights must be compliant with the City's Outdoor Lighting Standards (Section 11-3-25 of the Whitefish City Code). Applicable lighting standard details 47a thru 47m must be included with lighting plans. Lighting plans shall include features such as, but not limited to, service assembly, photo control, layout of poles, conduits and pull boxes, conduit and wire sizes, fuses, etc.

 

9.1.1 Residential – Streets, Parking Lots & Shared Use Paths

Use the following, or approved equal, street light poles and luminaries on residential streets, parking lots and shared use paths: Vendor: Mountain States Lighting (MSL) Luminaire: HADCO #C2316-50-HPS-J-240V Lamp: 50 Watt High Pressure Sodium (HPS) Pole: MSL #14EFA-5-TT/3x3-16.5WF(Name)-LEG-J(Green) Base: MSL #WF-16.5” Wx48” H-500-HDEB-J(Green) Break Away: See SD-47h Height: 17’-8” = Pole 14’-0” + Luminaire 3’-8” Pole Foundation: 18” Sonotube, 3’-8” Deep (See SD-47f) Qty. 4 - ¾” x 18” Ell Bolts 10” (+) Pattern, 3-½” Bolt Projection Isometric Footprint: See Cut Sheets for Isometric Footprint Exhibit Standard Drawing: See SD-47a

9.1.2 Commercial – Downtown Streets & Parking Lots

Use the following, or approved equal, street light poles and luminaries on downtown streets and commercial parking lots: Vendor: Mountain States Lighting (MSL) Luminaire: HADCO #C2316-100-HPS-J-240V Lamp: 100 Watt High Pressure Sodium (HPS) Single Arm Pole: MSL #22TFS-SA/17’/2’x2.375”/SCR-22” MAD(Madison)-C2316AF1XT-(1) BA-J(Green) Double Arm Pole: MSL #22TFS-DBLSA/17’/2’x2.375”/SCR-22” MAD(Madison)-C2316AF1XT-(2) BA-J(Green) Base: MSL#MAD(Madison)-22”Wx38”H-HDEB-J(Green) Break Away: None

Page 2: Street Lighting Standards Update - cityofwhitefish.org Lighting...9.1.5 Bollard – Share Use Paths ... Pull boxes shall be installed flush with finished grade. ... Simple wire size

Section 9‐2 

Height: Pole 22’-0” Luminaire Height: 3’-8” Mounted on Arm at 17’-0” Pole Foundation: 28” Sonotube, 5’-0” Deep Qty. 4 - 1” x 36” Ell Bolts 12” (+) Pattern, 3-½” Bolt Projection Plant Hanger: Qty. 1 at 15’-0” Irrigation Ready: Yes Isometric Footprint: Contact Mountain States Lighting Standard Drawing: See SD-47b

9.1.3 Commercial – MDT (HWY 93) Downtown

Use the following, or approved equal, street light poles and luminaries on MDT (HWY 93) downtown streets: Vendor: Mountain States Lighting (MSL) Luminaire: HADCO #C2316-100-HPS-J-240V, or HADCO #C2316-150-HPS-J-240V Lamp: 100 Watt High Pressure Sodium (HPS), or 150 Watt High Pressure Sodium (HPS), Single Arm Pole: MSL #25TFS-SA/17’/2’x2.375”/SCR-22” Base: MSL#MAD(Madison)-23.5”Wx44”H-HDEB-HADCO-

J(Green) Break Away: None Height: Pole 25’-0” Luminaire Height: 3’-8” Mounted on Arm at 17’-0” Pole Foundation: 48” Diameter, 15’-0” Deep Qty. 4 - 1” x 36” Ell Bolts 12” (+) Pattern, 3-½” Bolt Projection Plant Hanger: Qty. 1 at 13’-0” Irrigation Ready: Yes Isometric Footprint: Contact Mountain States Lighting Standard Drawing: See SD-47c

9.1.4 Commercial – MDT (HWY 93) West District

Use the following, or approved equal, street light poles and luminaries on MDT (HWY 93) West District streets: Vendor: Mountain States Lighting (MSL) Luminaire: HADCO #C0855E-250-HPS-J-(Green) Lamp: 250 Watt High Pressure Sodium (HPS) Single Arm Pole: MSL #_(Call for Model Number) Base: MSL#MAD(Madison)-23.5”Wx44”H-HDEB-HADCO-

J(Green) Break Away: None

Page 3: Street Lighting Standards Update - cityofwhitefish.org Lighting...9.1.5 Bollard – Share Use Paths ... Pull boxes shall be installed flush with finished grade. ... Simple wire size

Section 9‐3 

Height: Pole 25’-0” Luminaire Height: 3’-8” Mounted on Arm at 25’-0” Pole Foundation: 24” Sonotube, 7’-6” Deep Qty. 4 - 1” x 36” Ell Bolts 12” (+) Pattern, 3-½” Bolt Projection Plant Hanger: Qty. 2 at Bottom and Top Flag Holder: Qty. 1 Irrigation Ready: Yes Isometric Footprint: Contact Mountain States Lighting Standard Drawing: See SD-47d

9.1.5 Bollard – Share Use Paths

As an alternate to 9.1.1, the following, or approved equal, bollard lights may be used on share use paths:

Vendor: Cyclone Lighting Fixture Types: Army Helmet Hood (two options)

Option One: #CBM1154C-LAP-3-25W-4K-240-BB3-NONE-DK-GRN-TX

Option Two: #CBM1105C-LAP-3-25W-4K-240-BB3-NONE-DK-GRN-TX

Luminaire: LAP, Pond Acrylic, 75% Diffusing Optic: LED Type 3, Full Cut-Off Standards, Dark Sky Friendly Foundation: 18” Sonotube, 3’-8” Deep (See SD-47f) Qty. 4 - ¾” x 18” Ell Bolts 3-½” (+) Pattern, 3-½” Bolt Projection Base Skirt: Hagerstown Decorative Base Skirt Source: 240 Volt, 4K High Power LED, 4000K Finish: Dark Green Textured Powder Coat Isometric Footprint: Contact Cyclone Lighting Standard Drawing: See SD-47e

9.2 Pull Boxes

Pull boxes shall be installed flush with finished grade. To promote drainage and stability, all pull boxes shall receive a 6-inch deep foundation section of clean 3/8” minus aggregate chips extending 3-inches past the base of the box (See SD-47i). Pull boxes shall be placed at all locations where conduit layouts would result in 45-degree angles, except for street light base and service assembly pad sweeps. Pull boxes shall be installed at the ends of all conduit runs.

Use the following, or approved equal, pull boxes:

- Brooks 38PB (superimposed, bolt down, 3/8” diamond plate steel cover) - Old Castle 1324-12(Model #13244180, steel cover)

Page 4: Street Lighting Standards Update - cityofwhitefish.org Lighting...9.1.5 Bollard – Share Use Paths ... Pull boxes shall be installed flush with finished grade. ... Simple wire size

Section 9‐4 

9.3 Conduits, Wiring and Fuses

All conduits shall be Schedule 40 PVC. Minimum conduit size is 1 ¼”. Minimum conduit bury depth is 1’-8”. Conduit runs from power source to service assembly shall be 3” (See SD-47m). All conduit work shall be inspected by a licensed electrician prior to burial. When present, conduits shall be placed 6” behind curbs (See SD-47j). Conduits shall be sealed from dirt, debris and rodents (dux seal, perma seal, etc.) when entering and existing light bases and pull boxes. Pull box splices shall be made watertight.

Wire & Conduit Sizing & Specifications

Notes:

1) Keep linear footage of 1 ¼” conduit to 2,000’ maximum with #8 & #6 wire sizes. (measuring along main conduit run)

2) For conduit runs over 2,000’, use 2” conduit. 3) For conduit runs with #4 wire size, use 2” conduit. 4) For conduit runs with more than 1 circuit, use 2” conduit.

5) Simple wire size formula, CM(wire size) = 1.3 x L(linear footage) x F (number of fixtures)

6) Copper Wire

Size

#8 16,510 CM Maximum Circular Mills #6 26,240 CM

#4 41,740 CM 7) Sizing Chart Fixture Qnty. Max. Linear Footage Min. Wire Size Min Conduit Size 1 2,000 #8 1 ¼” 2 2,000 #8 1 ¼” 3 2,000 #8 1 ¼” 4 2,000 #8 1 ¼” 5 2,000 #8 1 ¼” 6 1,500 #8 1 ¼” 7 1,000 #6 1 ¼” 7 1,500 #6 1 ¼” 8 1,500 #6 1 ¼” 8 2,000 #6 1 ¼” 9 1,500 #6 1 ¼” 9 2,000 #6 1 ¼” 10 1,500 #6 1 ¼” 10 2,000 #6 1 ¼” 11 1,500 #6 1 ¼” 11 2,000 #6 1 ¼” 12 1,500 #6 1 ¼” 12 2,000 #4 2” 12 2,500 #4 2”

8) Wire installed in conduit runs shall not be smaller than #8 THHN copper stranded conductor.

9) Wire installed in poles from base to luminaire shall be #10 THHN copper stranded conductor.

10) Notes 1 thru 9 are minimum standards. (larger size wire and conduits are always acceptable).

11) 12 fixtures maximum per circuit.

Page 5: Street Lighting Standards Update - cityofwhitefish.org Lighting...9.1.5 Bollard – Share Use Paths ... Pull boxes shall be installed flush with finished grade. ... Simple wire size

Section 9‐5 

Each luminaire shall have two (2) watertight break away fuse holders with dual element midget fuses.

Fusing Specifications The following are acceptable fuse holders and fuses for decorative street lights. Equals

accepted on approval only.

In Line Break Away Weatherproof Fuse Holders No. Manufacturer Single Pole Terminal Two Pole

1FH Homac SLK – M SLK -6 SLK - 2

Screw Crimp Crimp

SLT – M SLT – 6 SLT - 2

2FH Bussmann (Copper)

HEB – JW- RLC – J HEB – JW – RYC HEB – AW – RLC – J HEB – AW – RYC

Screw Screw Crimp Crimp

HEY – JW- RLC – J HEY – JW – RYC HEY – AW – RLC – J HEY – AW – RYC

3FH Ferraz -

Shawmut FEB – 81 – 81 – BA FEB – 11 – 11 - BA

Screw Screw

FEX – 91 – 91 – BA FEX – 11 – 11 - BA

4FH SEC

Connector Company

SEC 1791 - SF Screw SEC 1791 - SDF

Midget Fuse, 1-1/2” x 13/32”, Dual Element No. Manufacturer Fuse

1F Bussmann FNM – 3 / 5

2F Ferraz - Shawmut TRM – 3 / 5

3F Little Fuse FLM – 3 / 5

9.4 Pole Spacing, Offset & Installation

Poles shall be installed plumb and level. Anchor bolts and nuts shall be corrosion resistant and installed with an anti-seize compound on threads. Decorative lights shall be spaced 150 to 180 feet along residential streets. The light location should alternate from side to side of street. Lights shall be placed a minimum of 3 feet from back of curb.

9.5 Service Assemblies

Service assemblies shall be 100 Amp, 120/240 Volt, 1 Phase. Service assemblies shall be bolted to a mounting base (Milbank CP-16DMNT-CALT, or approved equal) that is bolted

Page 6: Street Lighting Standards Update - cityofwhitefish.org Lighting...9.1.5 Bollard – Share Use Paths ... Pull boxes shall be installed flush with finished grade. ... Simple wire size

Section 9‐6 

bolt anchors fixed in a reinforced concrete pad (See SD-47l). Anchor bolts and nuts shall be corrosion resistant and installed with an anti-seize compound on threads. Use the following, or approved equal, service assembly commercial pedestals:

- Milbank CP3B11115A22 Commercial Pedestal - Cooper “B Line” Commercial Pedestal

All service assemblies shall be controlled by a photo control (See SD-47k). Photo control device shall be Tork #2107, or approved equal.

9.6 Inspections

Call for electrical conduit rough-in inspection before covering conduits. Call for electrical final inspection and compete working test before project sign-off. Project will not be complete until work test is finalized.

Inspection Contact Number: 406-253-6183 or 406-863-2460

9.7 Product Sheets & Isometric Footprint Exhibit

Product sheets for preapproved products can be obtained by contacting the Public Works Department (406-863-2460). Included are pull boxes, commercial pedestals, mounting base and photo control product sheets. Type 3 Residential Street Light Isometric Footprint Exhibit can also be provided by the Public Work Department upon request.

Page 7: Street Lighting Standards Update - cityofwhitefish.org Lighting...9.1.5 Bollard – Share Use Paths ... Pull boxes shall be installed flush with finished grade. ... Simple wire size

Section 9‐7 

SECTION 9

STANDARD DRAWINGS

SD-47a Residential Street Light SD-47b Commercial Street Light SD-47c MDT Downtown Street Light SD-47d MDT West District Street Light SD-47e Bollard Shared Use Path Light SD-47f Residential Pole and Bollard Foundation SD-47g Commercial Pole Foundation SD-47h Break Away Attachment SD-47i Pull Box Installation SD-47j Typical Street Lighting Conduit SD-47k Street Light Electrical Service and Wiring Diagram SD-47l Street Light Electrical Service Base SD-47m Utility Power Service Conduit Riser

Page 8: Street Lighting Standards Update - cityofwhitefish.org Lighting...9.1.5 Bollard – Share Use Paths ... Pull boxes shall be installed flush with finished grade. ... Simple wire size

LUMINAIRE DETAIL

BASE DETAIL

AutoCAD SHX Text
CONSTRUCTION STANDARDS CITY OF WHITEFISH
AutoCAD SHX Text
LUMINAIRE AND POLE DETAIL (RESIDENTIAL-CITY STREET, PARKING LOT AND SHARED USE PATH)
AutoCAD SHX Text
SD-47a
AutoCAD SHX Text
PROVIDE FUSE HOLDERS AND FUSES IN HAND HOLE AS SPECIFIED BY THE CITY OF WHITEFISH DECORATIVE STREET LIGHTS STANDARD.
AutoCAD SHX Text
COLOR: "J" GREEN
AutoCAD SHX Text
LUMINAIRE: HADCO #C2316-50-HPS-J-240V POLE: MSL #14EFA-5-TT/3x3-16.5WF(NAME)-LEG-J (GREEN) BASE: MSL #WF-16.5"Wx48"H-5OD-HDEB-J (GREEN)
AutoCAD SHX Text
POLE
AutoCAD SHX Text
LUMINAIRE
AutoCAD SHX Text
BASE
AutoCAD SHX Text
3/8-16x " LONG 12" LONG GRADE 8 BOLTS
AutoCAD SHX Text
OPEN LEG DESIGN STUMP FOR EASE OF WIRING. GROUND LUG BOLT (NOT PAINTED/BARE)
AutoCAD SHX Text
RESIDENTIAL POLE & BOLLARD FOUNDATION
AutoCAD SHX Text
BASE BY MOUNTAIN STATES LIGHTING HIGH DENSITY ELASTOMER DECORATIVE BASE, DENSITY OF 71 lbs PER CUBIC FOOT. ELASTOMER ( " MIN THICKNESS). 12" MIN THICKNESS). "WELCOME TO WHITEFISH" CAST INTO BASE AND PAINTED PER CITY REQUIREMENTS.
AutoCAD SHX Text
NUT
AutoCAD SHX Text
NUT
AutoCAD SHX Text
FLAT WASHERS
AutoCAD SHX Text
BREAK AWAY ATTACHMENT
Page 9: Street Lighting Standards Update - cityofwhitefish.org Lighting...9.1.5 Bollard – Share Use Paths ... Pull boxes shall be installed flush with finished grade. ... Simple wire size

NOTES:

LUMINAIRE DETAIL

BASE DETAIL

AutoCAD SHX Text
CONSTRUCTION STANDARDS CITY OF WHITEFISH
AutoCAD SHX Text
LUMINAIRE AND POLE DETAIL (COMMERCIAL-CITY STREET AND PARKING LOT)
AutoCAD SHX Text
SD-47b
AutoCAD SHX Text
PLANT HANGER ARM COMES OUT OF SHEET ON DOUBLE LIGHT POLE, NOT SHOWN FOR CLARITY.
AutoCAD SHX Text
PROVIDE FUSE HOLDERS AND FUSES IN HAND HOLE AS SPECIFIED BY THE CITY OF WHITEFISH DECORATIVE STREET LIGHTS STANDARD.
AutoCAD SHX Text
1
AutoCAD SHX Text
WELCOME
AutoCAD SHX Text
WHITEFISH
AutoCAD SHX Text
TO
AutoCAD SHX Text
NUT
AutoCAD SHX Text
NUT
AutoCAD SHX Text
FLAT WASHERS
AutoCAD SHX Text
COMMERCIAL POLE FOUNDATION
AutoCAD SHX Text
"WELCOME TO WHITEFISH" CAST INTO BASE AND PAINTED PER CITY REQUIREMENTS. HAND HOLE LOCATED BEHIND BASE.
AutoCAD SHX Text
POLE SHAFT: TAPERED FLUTED STEEL MINIMUM 20 EPA @ 80 MPH, 1.3 GF
AutoCAD SHX Text
BASE
AutoCAD SHX Text
GFI DUPLEX RECEPTACLE 6" ABOVE DECORATIVE BASE WITH WEATHERPROOF AND LOCKABLE COVER
AutoCAD SHX Text
HIGH DENSITY ELASTOMER DECORATIVE BASE, DENSITY OF 71 LBS/CF, PAINTED (SPECIFIED COLOR) WITH A MODIFIED URETHANE BED LINER COATING. (STAYS FLEXIBLE OVER TIME WITH MAXIMUM ADHESION) BASE TO BE AN AVERAGE OF 1" THICK.
AutoCAD SHX Text
COLOR: "J" GREEN
AutoCAD SHX Text
LUMINAIRE: HADCO #C2316-100-HPS-J-240V SINGLE ARM POLE: MSL #22TFS-SA/17'/2'x2.375"/SCR-22" MSL #22TFS-SA/17'/2'x2.375"/SCR-22" MAD(Madison)-C2316AF1XT-(1)BA-J (GREEN) DOUBLE ARM POLE: MSL #22TFS-DBLSA/17'/2'x2.375"/SCR-22" MSL #22TFS-DBLSA/17'/2'x2.375"/SCR-22" MAD(Madison)-C2316AF1XT-(2)BA-J (GREEN) BASE: MSL #MAD(Madison)-22"Wx38"H-HDEB-J
AutoCAD SHX Text
HAND HOLE ACCESS HATCH (BEHIND POLE)
AutoCAD SHX Text
GFI DUPLEX RECEPTACLE AT 21' WITH WEATHERPROOF COVER
AutoCAD SHX Text
FOUR EYE HOOKS AT 90° FOR MOUNTING DECORATIONS
AutoCAD SHX Text
LUMINAIRE (SINGLE ARM)
AutoCAD SHX Text
HAND HOLE FOR IRRIGATION ACCESS
AutoCAD SHX Text
PLANT HANGER ARM
AutoCAD SHX Text
34" ELECTRICAL COUPLING WITH " THREADED ADAPTER 34" THREADED ADAPTER (TYP)
AutoCAD SHX Text
1
AutoCAD SHX Text
LUMINAIRE BOTH SIDES (DOUBLE ARM)
Page 10: Street Lighting Standards Update - cityofwhitefish.org Lighting...9.1.5 Bollard – Share Use Paths ... Pull boxes shall be installed flush with finished grade. ... Simple wire size

SINGLE FIXTURE DECORATIVE LUMINAIRE POLE, DBL PLANT HANGER ARM, IRRIGATION HOLE

DECORATIVE LUMINAIRE POLE FOUNDATION

AA

NOTES:

SECTION A-A

AutoCAD SHX Text
CONSTRUCTION STANDARDS CITY OF WHITEFISH
AutoCAD SHX Text
LUMINAIRE AND POLE DETAIL (COMMERCIAL - MDT HWY 93 - DOWNTOWN)
AutoCAD SHX Text
SD-47c
AutoCAD SHX Text
WELCOME TO WHITEFISH
AutoCAD SHX Text
FINISH: HADCO "J" GREEN LOGO ON BASE TIPPED IN GOLD
AutoCAD SHX Text
HAND HOLE ACCESS HATCH (OPPOSITE LUMINAIRE)
AutoCAD SHX Text
GFI DUPLEX RECEPTACLE AT 24' WITH WEATHERPROOF COVER
AutoCAD SHX Text
FOUR EYE HOOKS AT 90° FOR MOUNTING DECORATIONS (PROVIDED WITH BACKLASH DAMPENING SPRING)
AutoCAD SHX Text
TOP CAP WITH LONG SETSCREWS
AutoCAD SHX Text
HADCO 150 HPS FIXTURE PART# C2316G-150HPS. OR HADCO 100 HPS FIXTURE PART# C2316A-100HPS.
AutoCAD SHX Text
ORIENT LUMINAIRE ON TRAFFIC SIDE OF POLE (90° TO CURB)
AutoCAD SHX Text
POLE SHAFT: TAPERED FLUTED STEEL MINIMUM 13.2 EPA @ 90 MPH, 1.3 GF POLE BY MOUNTAIN STATES LIGHTING
AutoCAD SHX Text
4" OF EXPOSED STRAIGHT PIPE SECTION TO INCREASE THE STRENGTH OF THE POLE TO ACCOMMODATE LOADING
AutoCAD SHX Text
GFI DUPLEX RECEPTACLE 6" ABOVE DECORATIVE BASE WITH WEATHERPROOF AND LOCKABLE COVER
AutoCAD SHX Text
HAND HOLE LOCATED BEHIND MADISON BASE PART# EXT MAD-23.5"W x 44"H-HDEB-HADCO "J" GREEN HIGH DENSITY ELASTOMER DECORATIVE BASE, DENSITY OF 71 LBS/CF BASE TO BE AN AVERAGE OF 1" THICK.
AutoCAD SHX Text
** CITY NAME/LOGO ON BASE - TIPPED IN GOLD COLOR **
AutoCAD SHX Text
90° VIEW OF POLE SECTION(SHOWING PLANT HANGERS, TWO AT 180°)
AutoCAD SHX Text
HAND HOLE FOR IRRIGATION OPENING WITH 1 " COUPLING HOLE 12" COUPLING HOLE FOR IRRIGATION TUBE MOUNTED 6" BELOW PLANT HANGER ARM
AutoCAD SHX Text
FIXED DOUBLE 1" DIA, 18" LONG PLANT HANGER ARM (TWO ARMS AT 180°) PLANT HANGERS ARE 90° TO LUMINAIRE(ONE ROD GOING THROUGH THE POLE WITH A JAM NUT ONE EITHER SIDE TO SECURE AND CENTER ARM)
AutoCAD SHX Text
POLE TO HAVE 12" BOLT CIRCLE TO ACCOMMODATE 1"x36" BOLTS WITH A 4" BOLT PROJECTION
AutoCAD SHX Text
1. ALL CONCRETE SHALL BE CLASS "DD" PER ALL CONCRETE SHALL BE CLASS "DD" PER MDT STANDARDS SPECIFICATIONS FOR ROAD AND BRIDGE CONSTRUCTION AND HAVE A MINIMUM COMPRESSIVE STRENGTH OF F'C=3,000 PSI AT 28 DAYS, NORMAL WEIGHT.
AutoCAD SHX Text
4'-0" DIA
AutoCAD SHX Text
CONCRETE DRILLED SHAFT W/ 6-#6 VERTS ARRANGED EVENLY W/ #4 TIES
AutoCAD SHX Text
COPPER GROUNDING STRIP BETWEEN ANCHOR BOLT, CONDUIT AND NO. 6 AWG BARE GROUND WIRE OR PIGTAIL EXTENSION
AutoCAD SHX Text
SIDEWALK
AutoCAD SHX Text
LIGHT POLE
AutoCAD SHX Text
NO. 6 AWG BARE GROUND WIRE OR PIGTAIL EXTENSION
AutoCAD SHX Text
GROUNDING LUG
AutoCAD SHX Text
PROTRUDE CONDUIT FROM FOUNDATION AT LEAST 2" BUT NO MORE THAN 3"
AutoCAD SHX Text
PLATE AND ANCHORS
AutoCAD SHX Text
#4 TIES @ 10"OC W/ 3-#4 TIES AT TOP
AutoCAD SHX Text
1 " CONDUIT WITH 12" CONDUIT WITH WIRE AS SHOWN IN WIRING DIAGRAM
Page 11: Street Lighting Standards Update - cityofwhitefish.org Lighting...9.1.5 Bollard – Share Use Paths ... Pull boxes shall be installed flush with finished grade. ... Simple wire size
AutoCAD SHX Text
CONSTRUCTION STANDARDS CITY OF WHITEFISH
AutoCAD SHX Text
LUMINAIRE AND POLE DETAIL (COMMERCIAL - MDT HWY 93 - WEST DISTRICT)
AutoCAD SHX Text
SD-47d
AutoCAD SHX Text
GROUNDING LUG
AutoCAD SHX Text
NO. 6 AWG BARE GROUND WIRE
AutoCAD SHX Text
OR PIGTAIL EXTENSION
AutoCAD SHX Text
COPPER GROUNDING STRAP BETWEEN
AutoCAD SHX Text
ANCHOR BOLT, CONDUIT & NO. 6 AWG
AutoCAD SHX Text
BARE GROUND WIRE OR PIGTAIL
AutoCAD SHX Text
EXTENSION.
AutoCAD SHX Text
SCALE: NONE
AutoCAD SHX Text
DECORATIVE LUMINAIRE POLE TYPE 2 FOUNDATION
AutoCAD SHX Text
(8 TYPICAL)
AutoCAD SHX Text
ANCHOR BOLT CIRCLE
AutoCAD SHX Text
USE GRADE 400 REINFORCING STEEL
AutoCAD SHX Text
#6 REBAR (7'-1" LONG)
AutoCAD SHX Text
P
AutoCAD SHX Text
A
AutoCAD SHX Text
L
AutoCAD SHX Text
N
AutoCAD SHX Text
I
AutoCAD SHX Text
6
AutoCAD SHX Text
ANCHOR BOLT
AutoCAD SHX Text
(4 TYPICAL)
AutoCAD SHX Text
SECTION A-A
AutoCAD SHX Text
PROTRUDE CONDUIT FROM FOUNDATION
AutoCAD SHX Text
AT LEAST 2" BUT NOT MORE 3"
AutoCAD SHX Text
24"
AutoCAD SHX Text
24"
AutoCAD SHX Text
2"
AutoCAD SHX Text
3"
AutoCAD SHX Text
3"
AutoCAD SHX Text
7'-6"
AutoCAD SHX Text
A
AutoCAD SHX Text
A
AutoCAD SHX Text
1
AutoCAD SHX Text
SNAP LATCH: TOOL-LESS
AutoCAD SHX Text
STAINLESS STEEL, ALLOWS
AutoCAD SHX Text
ACCESS TO BOTH TOOL-LESS
AutoCAD SHX Text
BALLAST & TOOL-LESS RELAMPING
AutoCAD SHX Text
HOUSING:
AutoCAD SHX Text
DIE-CAST ALUMINUM #360 ALLOY
AutoCAD SHX Text
BALLAST; FACTORY PREWIRED & TESTED
AutoCAD SHX Text
PORCELAIN MOGUL BASE SOCKET
AutoCAD SHX Text
REFLECTOR: CLEAR
AutoCAD SHX Text
ANODIZED HYDROFORMED
AutoCAD SHX Text
ALUMINUM, OPTIC CHAMBER
AutoCAD SHX Text
IP66 RATED (TYPE 3 OPTICS)
AutoCAD SHX Text
FLAT GLASS LENSE
AutoCAD SHX Text
ALUMINUM BRIM/GLARE SHIELD
AutoCAD SHX Text
POLYURETHANE FINIAL
AutoCAD SHX Text
HANG STRAIGHT PLUMBIZER
AutoCAD SHX Text
WITH PHOTOCELL RECEPTACLE
AutoCAD SHX Text
MINIMUM 16 EPA @ 145 KPH, 1.3 GF
AutoCAD SHX Text
SHAFT: TAPERED FLUTED STEEL OR ALUMINUM
AutoCAD SHX Text
BANNER ARMS-LOWER & UPPER
AutoCAD SHX Text
VERIFY LENGTH - BANNER BY OTHERS
AutoCAD SHX Text
FLAGHOLDER ACCESSORY
AutoCAD SHX Text
POLE & FLAG BY OTHERS
AutoCAD SHX Text
AS NEEDED
AutoCAD SHX Text
GROUT
AutoCAD SHX Text
38"
AutoCAD SHX Text
NO SCALE
AutoCAD SHX Text
CAST ALUMINUM #356HM ALLOY
AutoCAD SHX Text
WELDED TO HOUSING
AutoCAD SHX Text
NECK:
AutoCAD SHX Text
22"
AutoCAD SHX Text
POLE: 25 FT
AutoCAD SHX Text
DECORATIVE LUMINAIRE POLE - TYPE 2
AutoCAD SHX Text
120V GFCI RECEPTACLE
AutoCAD SHX Text
250 WATT HPS
AutoCAD SHX Text
1" MIN. THICKNESS
AutoCAD SHX Text
DECORATIVE HIGH DENSITY ELASTOMER,
AutoCAD SHX Text
FOURTEEN #4 REBAR HOOPS EVENLY SPACED
AutoCAD SHX Text
#4 REBAR HOOPS
AutoCAD SHX Text
BASE:
AutoCAD SHX Text
2 " CLEARANCE12" CLEARANCE
Page 12: Street Lighting Standards Update - cityofwhitefish.org Lighting...9.1.5 Bollard – Share Use Paths ... Pull boxes shall be installed flush with finished grade. ... Simple wire size
AutoCAD SHX Text
CONSTRUCTION STANDARDS CITY OF WHITEFISH
AutoCAD SHX Text
LUMINAIRE AND BOLLARD DETAIL (SHARED USE PATH)
AutoCAD SHX Text
SD-47e
AutoCAD SHX Text
FIXTURE TYPE (OPTION ONE): CYCLONE LIGHTING : CYCLONE LIGHTING #CBM1154C-LAP-3-25W-4K-240-BB3-NONE- DK-GRN-TX FIXTURE TYPE (OPTION TWO): CYCLONE LIGHTING : CYCLONE LIGHTING #CBM1105C-LAP-3-25W-4K-240-BB3-NONE- DK-GRN-TX LUMINAIRE: LAP, POND ACRYLIC, 75% DIFFUSING : LAP, POND ACRYLIC, 75% DIFFUSING OPTIC: LED TYPE 3 : LED TYPE 3 SOURCE: 240 VOLT, 4K HIGH POWER LED, 4000K : 240 VOLT, 4K HIGH POWER LED, 4000K FINISH: DARK GREEN TEXTURED POWDER COAT: DARK GREEN TEXTURED POWDER COAT
AutoCAD SHX Text
RESIDENTIAL POLE & BOLLARD FOUNDATION
Page 13: Street Lighting Standards Update - cityofwhitefish.org Lighting...9.1.5 Bollard – Share Use Paths ... Pull boxes shall be installed flush with finished grade. ... Simple wire size

NOTES:

ANCHOR BOLT TEMPLATE

ST

RE

ET

SID

EW

AL

K

ANCHOR BOLT TEMPLATE

AutoCAD SHX Text
CONSTRUCTION STANDARDS CITY OF WHITEFISH
AutoCAD SHX Text
RESIDENTIAL POLE & BOLLARD FOUNDATION (RESIDENTIAL-CITY STREET, PARKING LOT AND SHARED USE PATH)
AutoCAD SHX Text
SD-47f
AutoCAD SHX Text
FOUR (4) #5 BARS EVENLY SPACED
AutoCAD SHX Text
#6 BARE COPPER GROUND WIRE ATTACHED TO REBAR WITH `JONES' TYPE CLAMP OR BY OTHER APPROVED MEANS. LEAVE 36" AVAILABLE FOR BONDING IN POLE.
AutoCAD SHX Text
FOUR (4) ANCHOR BOLTS "x18" BOLTS 34"x18" BOLTS WITH 4" HOOK
AutoCAD SHX Text
SPECIFIED CONDUIT IN CONCRETE
AutoCAD SHX Text
#3 TIES @ 12" OC
AutoCAD SHX Text
MATCH FINISHED SURFACE
AutoCAD SHX Text
TOP OF FOUNDATION TO
AutoCAD SHX Text
BURY CONDUIT 18" MIN
AutoCAD SHX Text
LUMINAIRE POLE OR BOLLARD
AutoCAD SHX Text
1. GROUND LIGHT POLE BASES PER MANUFACTURER'S RECOMMENDATIONS. GROUND LIGHT POLE BASES PER MANUFACTURER'S RECOMMENDATIONS. 2. SET ANCHOR BOLTS WITH OR 3 " OF THREADS EXPOSED. SET ANCHOR BOLTS WITH OR 3 " OF THREADS EXPOSED. 12" OF THREADS EXPOSED. 3. LIGHT POLE FOUNDATION SHALL BE BACKFILLED USING SUITABLE ON-SITE LIGHT POLE FOUNDATION SHALL BE BACKFILLED USING SUITABLE ON-SITE MATERIAL. BACKFILL TO BE COMPACTED TO 95% OF ASTM D-698. 4. ALL LIGHT POLE FOUNDATIONS SHALL BE CAST IN PLACE. PRECAST LIGHT ALL LIGHT POLE FOUNDATIONS SHALL BE CAST IN PLACE. PRECAST LIGHT POLE FOUNDATION SHALL NOT BE USED. 5. TOP OF FOUNDATION SHALL BE PLUMB SO THAT BASE SITS FLAT ON FOUNDATION.TOP OF FOUNDATION SHALL BE PLUMB SO THAT BASE SITS FLAT ON FOUNDATION.
AutoCAD SHX Text
(POLE)
AutoCAD SHX Text
(TYP)
AutoCAD SHX Text
EDGE OF BOLLARD BASE
AutoCAD SHX Text
(BOLLARD)
AutoCAD SHX Text
EDGE OF FOUNDATION
AutoCAD SHX Text
3 " BOLT HOLE 12" BOLT HOLECENTERLINE
AutoCAD SHX Text
EDGE OF FOUNDATION
AutoCAD SHX Text
EDGE OF POLE BASE
AutoCAD SHX Text
10" BOLT HOLECENTERLINE
AutoCAD SHX Text
(TYP)
AutoCAD SHX Text
BOLT HOLE (TYP OF 4)
AutoCAD SHX Text
BOLT HOLE (TYP OF 4)
Page 14: Street Lighting Standards Update - cityofwhitefish.org Lighting...9.1.5 Bollard – Share Use Paths ... Pull boxes shall be installed flush with finished grade. ... Simple wire size

NOTES:

ANCHOR BOLT TEMPLATE

ST

RE

ET

SID

EW

AL

K

AutoCAD SHX Text
CONSTRUCTION STANDARDS CITY OF WHITEFISH
AutoCAD SHX Text
COMMERCIAL POLE FOUNDATION (COMMERCIAL-CITY STREET AND PARKING LOT)
AutoCAD SHX Text
SD-47g
AutoCAD SHX Text
1. GROUND LIGHT POLE BASES PER MANUFACTURER'S RECOMMENDATIONS. GROUND LIGHT POLE BASES PER MANUFACTURER'S RECOMMENDATIONS. 2. SET ANCHOR BOLTS WITH 3 " OF THREADS EXPOSED. SET ANCHOR BOLTS WITH 3 " OF THREADS EXPOSED. 12" OF THREADS EXPOSED. 3. LIGHT POLE FOUNDATION SHALL BE BACKFILLED USING SUITABLE ON-SITE LIGHT POLE FOUNDATION SHALL BE BACKFILLED USING SUITABLE ON-SITE MATERIAL. BACKFILL TO BE COMPACTED TO 95% OF ASTM D-698. 4. ALL LIGHT POLE FOUNDATIONS SHALL BE CAST IN PLACE. PRECAST LIGHT ALL LIGHT POLE FOUNDATIONS SHALL BE CAST IN PLACE. PRECAST LIGHT POLE FOUNDATION SHALL NOT BE USED. 5. TOP OF FOUNDATION SHALL BE PLUMB SO THAT BASE SITS FLAT ON FOUNDATION. TOP OF FOUNDATION SHALL BE PLUMB SO THAT BASE SITS FLAT ON FOUNDATION. 6. IRRIGATION CONDUITS SHALL BE PROVIDED. (NOT SHOWN FOR CLARITY)IRRIGATION CONDUITS SHALL BE PROVIDED. (NOT SHOWN FOR CLARITY)
AutoCAD SHX Text
FOUR (4) #5 BARS EVENLY SPACED
AutoCAD SHX Text
#6 BARE COPPER GROUND WIRE ATTACHED TO REBAR WITH `JONES' TYPE CLAMP OR BY OTHER APPROVED MEANS. LEAVE 36" AVAILABLE FOR BONDING IN POLE.
AutoCAD SHX Text
FOUR (4) ANCHOR BOLTS 1"x36" BOLTS WITH 3" HOOK
AutoCAD SHX Text
SPECIFIED CONDUIT IN CONCRETE
AutoCAD SHX Text
#3 TIES @ 12" OC
AutoCAD SHX Text
MATCH FINISHED SURFACE
AutoCAD SHX Text
TOP OF FOUNDATION TO
AutoCAD SHX Text
BURY CONDUIT 18" MIN
AutoCAD SHX Text
LUMINAIRE POLE
AutoCAD SHX Text
DRYPACK
AutoCAD SHX Text
12" BOLT HOLECENTERLINE
AutoCAD SHX Text
(TYP)
AutoCAD SHX Text
EDGE OF FOUNDATION
AutoCAD SHX Text
EDGE OF POLE BASE
AutoCAD SHX Text
BOLT HOLE (TYP OF 4)
Page 15: Street Lighting Standards Update - cityofwhitefish.org Lighting...9.1.5 Bollard – Share Use Paths ... Pull boxes shall be installed flush with finished grade. ... Simple wire size
AutoCAD SHX Text
CONSTRUCTION STANDARDS CITY OF WHITEFISH
AutoCAD SHX Text
SD-47h
AutoCAD SHX Text
LUMINAIRE POLE (RESIDENTIAL)
AutoCAD SHX Text
BREAK AWAY ATTACHMENT (RESIDENTIAL POLE)
AutoCAD SHX Text
RESIDENTIAL POLE & BOLLARD FOUNDATION
AutoCAD SHX Text
ANCHOR BOLTS (TYP)
AutoCAD SHX Text
SQUARE WASHERS FOR TOP AND BOTTOM SLIP PLATES 2"(W)x3"(L) (TYP OF 8)
AutoCAD SHX Text
UPPER POLE ANCHOR PLATE SLOTS ON A 9" BOLT PATTERN (BOLTS TO LOWER PLATE)
AutoCAD SHX Text
SPACING PLATE (WELDED TO BOTTOM PLATE)
AutoCAD SHX Text
LOWER ANCHOR PLATE (BOLTS TO ANCHOR BOLTS)
AutoCAD SHX Text
7 " DIAMETER78" DIAMETER
AutoCAD SHX Text
5 " DIAMETER78" DIAMETER
AutoCAD SHX Text
10" BOLT CIRCLE (ANCHOR BOLTS)
AutoCAD SHX Text
(4) " DIA HOLES78" DIA HOLES
AutoCAD SHX Text
1" RADIUS
Page 16: Street Lighting Standards Update - cityofwhitefish.org Lighting...9.1.5 Bollard – Share Use Paths ... Pull boxes shall be installed flush with finished grade. ... Simple wire size
AutoCAD SHX Text
CONSTRUCTION STANDARDS CITY OF WHITEFISH
AutoCAD SHX Text
PULL BOX INSTALLATION
AutoCAD SHX Text
SD-47i
AutoCAD SHX Text
CONDUIT IN PLACE AS REQUIRED
AutoCAD SHX Text
BACKFILL TOP 6" WITH EXCAVATED MATERIAL AND TAMP SECURE
AutoCAD SHX Text
CLEAN STONE ( " MINUS)12" MINUS)
AutoCAD SHX Text
PULL BOX
Page 17: Street Lighting Standards Update - cityofwhitefish.org Lighting...9.1.5 Bollard – Share Use Paths ... Pull boxes shall be installed flush with finished grade. ... Simple wire size

NOTES:

AutoCAD SHX Text
CONSTRUCTION STANDARDS CITY OF WHITEFISH
AutoCAD SHX Text
SD-47j
AutoCAD SHX Text
1. COORDINATE TRENCHING TO SHARE TRENCHES COORDINATE TRENCHING TO SHARE TRENCHES WITH OTHER UTILITIES WHEN FEASIBLE
AutoCAD SHX Text
COMPACTED BACKFILL
AutoCAD SHX Text
CONDUIT
AutoCAD SHX Text
SAND OR CLEAN SOIL
AutoCAD SHX Text
RESURFACE TO MATCH EXISTING OR PROPOSED AS SPECIFIED
AutoCAD SHX Text
WARNING TAPE
AutoCAD SHX Text
FINISHED GRADE
AutoCAD SHX Text
(SEE ELECTRICAL PLANS FOR CONDUIT SIZES)
AutoCAD SHX Text
FROM FINISHED GRADE
AutoCAD SHX Text
TOP BACK OF CURB
AutoCAD SHX Text
UNDER DRAIN
AutoCAD SHX Text
CONDUIT
AutoCAD SHX Text
TYPICAL STREET LIGHTING CONDUIT (BEDDING AND BACKFILL)
AutoCAD SHX Text
FROM FINISHED GRADE
AutoCAD SHX Text
FINISHED GRADE
Page 18: Street Lighting Standards Update - cityofwhitefish.org Lighting...9.1.5 Bollard – Share Use Paths ... Pull boxes shall be installed flush with finished grade. ... Simple wire size

100

100

15

20

20

L1 L2

CR

H

O

A

N

N

WIRE DIAGRAM

STREET LIGHT ELECTRICAL SERVICE

AutoCAD SHX Text
CONSTRUCTION STANDARDS CITY OF WHITEFISH
AutoCAD SHX Text
STREET LIGHT ELECTRICAL SERVICE AND WIRE DIAGRAM
AutoCAD SHX Text
SD-47k
AutoCAD SHX Text
UTILITY POWER
AutoCAD SHX Text
METER
AutoCAD SHX Text
TORK #2107 PHOTO CONTROL
AutoCAD SHX Text
LIGHTING CONTACTOR
AutoCAD SHX Text
LIGHTING LOAD
AutoCAD SHX Text
AUTO/OFF/TEST SELECTOR SWITCH
AutoCAD SHX Text
HINGED DOOR
AutoCAD SHX Text
L.B. CONDULET - 90° TURN( ")34")
AutoCAD SHX Text
30" OF "HEAVY WALL CONDUIT" ( ")34")
AutoCAD SHX Text
"C" CONDULET - CONNECTION BOX ( ")34")
AutoCAD SHX Text
PHOTO EYE - TORK #2107
Page 19: Street Lighting Standards Update - cityofwhitefish.org Lighting...9.1.5 Bollard – Share Use Paths ... Pull boxes shall be installed flush with finished grade. ... Simple wire size

LINE SIDE (F.E.C.)

LOAD SIDE (CITY)

STREET SIDE

NOTES:

AutoCAD SHX Text
CONSTRUCTION STANDARDS CITY OF WHITEFISH
AutoCAD SHX Text
STREET LIGHT ELECTRICAL SERVICE BASE
AutoCAD SHX Text
SD-47l
AutoCAD SHX Text
(4) "x8" GALVANIZED STEEL 12"x8" GALVANIZED STEEL BENT ANCHOR BOLTS
AutoCAD SHX Text
3" LINE CONDUIT
AutoCAD SHX Text
#8 GROUND ROD
AutoCAD SHX Text
MOUNTING BASE
AutoCAD SHX Text
HORIZONTAL #4 REBAR (TYP OF 4)
AutoCAD SHX Text
VERTICAL #4 REBAR (TYP OF 8)
AutoCAD SHX Text
12"x8" GALVANIZED STEEL BENT ANCHOR BOLTS (TYP)
AutoCAD SHX Text
#8 GROUND ROD
AutoCAD SHX Text
HORIZONTAL #4 REBAR (TYP)
AutoCAD SHX Text
HORIZONTAL #4 REBAR (TYP)
AutoCAD SHX Text
VERTICAL #4 REBAR (TYP)
AutoCAD SHX Text
(2) 2" LOAD CONDUITS
AutoCAD SHX Text
CONCRETE PAD (3'x3'x2')
AutoCAD SHX Text
CONCRETE PAD (3'x3'x2')
AutoCAD SHX Text
1. (2) 8' COPPER CLAD GROUND RODS. INSTALL 6' APART. (2) 8' COPPER CLAD GROUND RODS. INSTALL 6' APART. #6 AWG GROUND WIRE WITH 6' FREE CONDUCTOR FOR CONNECTION TO SERVICE.
AutoCAD SHX Text
FINISH GRADE
AutoCAD SHX Text
#6 WIRE
AutoCAD SHX Text
#8 GROUND ROD
Page 20: Street Lighting Standards Update - cityofwhitefish.org Lighting...9.1.5 Bollard – Share Use Paths ... Pull boxes shall be installed flush with finished grade. ... Simple wire size

NOTES:

AutoCAD SHX Text
CONSTRUCTION STANDARDS CITY OF WHITEFISH
AutoCAD SHX Text
UTILITY POWER SERVICE CONDUIT RISER
AutoCAD SHX Text
SD-47m
AutoCAD SHX Text
1.3" PVC RISER AT F.E.C. POLE STUB UP SEPARATION 6" TO CENTERLINE.3" PVC RISER AT F.E.C. POLE STUB UP SEPARATION 6" TO CENTERLINE.
AutoCAD SHX Text
3" PVC CONDUIT
AutoCAD SHX Text
FINISH GRADE
AutoCAD SHX Text
F.E.C. POLE
Page 21: Street Lighting Standards Update - cityofwhitefish.org Lighting...9.1.5 Bollard – Share Use Paths ... Pull boxes shall be installed flush with finished grade. ... Simple wire size
Page 22: Street Lighting Standards Update - cityofwhitefish.org Lighting...9.1.5 Bollard – Share Use Paths ... Pull boxes shall be installed flush with finished grade. ... Simple wire size
Page 23: Street Lighting Standards Update - cityofwhitefish.org Lighting...9.1.5 Bollard – Share Use Paths ... Pull boxes shall be installed flush with finished grade. ... Simple wire size

19Customer Service Department at 800-735-5566 All Plastic and

H-Series Productswww.oldcastleprecast.com/enclosuresolutions

1324RA

TING

Part# Description 1 Description 2 Color Depth Item Weight Pallet Qty List Price Line Item Discount

DesignLoad

T22

T22

2215

T15

Extension - 1324

13242600 Body, PC1324-18,FW PC132418FW Gray 18 71 15 $131.94 OC03 1500013242020 Body, PC1324-12,SW PC132412SW Gray 12 50 20 $113.01 OC03 2250013242023 Body, PC1324-18,SW PC132418SW Gray 18 52 15 $130.38 OC03 2250013242038 Body, PC1324-24,SW PC132424SW Gray 24 89 10 $179.12 OC03 22500

13243001 Ext, PC 1324-9 PC13249X Gray 9 50 16 $157.07 OC03 22500

13241600 Unit, PC1324-12, T15 - Blank PC132412-T15 Gray 12 90 20 $248.09 OC03 1500013241603 Unit, PC1324-12, T15 -"Electric" PC132412-T15 Gray 12 90 20 $248.09 OC03 1500013241605 Unit, PC1324-12, T15 -"Street Lighting" PC132412-T15 Gray 12 90 20 $248.09 OC03 1500013241606 Unit, PC1324-12, T15 -"Tra c Signal" PC132412-T15 Gray 12 90 20 $248.09 OC03 1500013241610 Unit, PC1324-18, T15 - Blank PC132418-T15 Gray 18 109 15 $265.25 OC03 1500013241611 Unit, PC1324-18, T15 - Blank, FW PC132418-T15 Gray 18 116 15 $265.25 OC03 1500013241616 Unit, PC1324-18, T15 -"Electric" PC132418-T15 Gray 18 109 15 $265.25 OC03 1500013241617 Unit, PC1324-18, T15 -"Electric", FW PC132418-T15 Gray 18 116 15 $265.25 OC03 1500013241620 Unit, PC1324-18, T15 -"Street Lighting" PC132418-T15 Gray 18 109 15 $265.25 OC03 1500013241621 Unit, PC1324-18, T15 -"Street Lighting", FW PC132418-T15 Gray 18 116 15 $265.25 OC03 1500013241622 Unit, PC1324-18, T15 -"Tra c Signal" PC132418-T15 Gray 18 109 15 $265.25 OC03 1500013241623 Unit, PC1324-18, T15 -"Tra c Signal", FW PC132418-T15 Gray 18 116 15 $265.25 OC03 1500013241635 Unit, PC1324-24, T15 - Blank PC132424-T15 Gray 24 127 10 $313.42 OC03 1500013241638 Unit, PC1324-24, T15 -"Electric" PC132424-T15 Gray 24 127 10 $313.42 OC03 1500013241640 Unit, PC1324-24, T15 -"Street Lighting" PC132424-T15 Gray 24 127 10 $313.42 OC03 1500013241641 Unit, PC1324-24, T15 -"Tra c Signal" PC132424-T15 Gray 24 127 10 $313.42 OC03 1500013241021 Unit, PC1324-12, T22 - "Electric" PC132412-T22 Gray 12 99 20 $292.57 OC03 2250013241023 Unit, PC1324-12, T22 - Blank PC132412-T22 Gray 12 99 20 $292.57 OC03 2250013241124 Unit, PC1324-12, T22 - "Tra c Signal" PC132412-T22 Gray 12 99 20 $292.57 OC03 2250013241265 Unit, PC1324-12, T22 - "Street Lighting" PC132412-T22 Gray 12 99 20 $292.57 OC03 2250013241027 Unit, PC1324-18, T22 - "Electric" PC132418-T22 Gray 18 118 15 $309.73 OC03 2250013241029 Unit, PC1324-18, T22 - Blank PC132418-T22 Gray 18 118 15 $309.73 OC03 2250013241630 Unit, PC1324-18, T22 - "Street Lighting" PC132418-T22 Gray 18 118 15 $309.73 OC03 2250013241632 Unit, PC1324-18, T22 - "Tra c Signal" PC132418-T22 Gray 18 118 15 $309.73 OC03 2250013241164 Unit, PC1324-24, T22 - Blank PC132424-T22 Gray 24 140 10 $357.90 OC03 2250013241262 Unit, PC1324-24, T22 - "Electric" PC132424-T22 Gray 24 140 10 $357.90 OC03 2250013241271 Unit, PC1324-24, T22 - "Street Lighting" PC132424-T22 Gray 24 140 10 $357.90 OC03 2250013241644 Unit, PC1324-24, T22 - "Tra c Signal" PC132424-T22 Gray 24 140 10 $357.90 OC03 22500

T22

T15

13244603 Lid, PC1324-T, T15 - Blank PC1324T-T15 Gray - 38 30 $119.90 OC03 1500013244607 Lid, PC1324-T, T15 -"Electric" PC1324T-T15 Gray - 38 30 $119.90 OC03 1500013244609 Lid, PC1324-T, T15 -"Ground" PC1324T-T15 Gray - 38 30 $119.90 OC03 1500013244610 Lid, PC1324-T, T15 -"Street Lighting" PC1324T-T15 Gray - 38 30 $119.90 OC03 1500013244612 Lid, PC1324-T, T15 -"Tra c Signal" PC1324T-T15 Gray - 38 30 $119.90 OC03 1500013244012 Lid, PC1324-T, T22 - "Electric" PC1324T-T22 Gray - 51 30 $163.84 OC03 2250013244014 Lid, PC1324-T , T22 - Blank PC1324T-T22 Gray - 51 30 $163.84 OC03 2250013244173 Lid, PC1324-T, T22 - "Tra c Signal" PC1324T-T22 Gray - 51 30 $163.84 OC03 2250013244178 Lid, PC1324-T, T22 - "Street Lighting" PC1324T-T22 Gray - 51 30 $163.84 OC03 2250013244613 Lid, PC1324-T, T22 - "Ground" PC1324T-T22 Gray - 51 30 $163.84 OC03 22500

Unit - 1324 (Units come standard with Body-Open Bottom, Lid and SS Hex Bolt Floating Nut Hardware)

Lid - 1324

Body - 1324

H-SER

IES

Tier 15*

H-Series - 1324 Rectangular & Flared Wall (FW)Polymer Concrete

Straight Wall

Flared Wall

Medium DutyNon-deliberate Traffic

Medium DutyNon-deliberate Traffic

Heavy DutyNon-deliberate Traffic

Tier 15 & 22*

*P roduc ts a re ra ted by the lowest component rating. A tier 15 cover with a tier 22 body is rated tier 15. A tier 22 cover with a tier 22 body is rated tier 22.

See Accesso r ies Sec t i on in the Back of th is Manual for Opt ions, Hardware, Special ty Markings and Other Accessories

Page 24: Street Lighting Standards Update - cityofwhitefish.org Lighting...9.1.5 Bollard – Share Use Paths ... Pull boxes shall be installed flush with finished grade. ... Simple wire size

41Customer Service Department at 800-735-5566 All Plastic and

H-Series Productswww.oldcastleprecast.com/enclosuresolutions

AC

CESSO

RIES

80002006 1x HBlt+ Wsh+ Rcfnt+ Clip 3/8"x2.5SSTCapt1220/1419 XX-50 1015, 1220, 1419 $5.02 OC09 -80002008 1x HBlt+Wsh+ Rcfnt+Spring 3/8"-16 x 2.5 Capt 0910 Only 0910 $5.35 OC09 -80002025 2x Hexbolt + 2x Wash SST 3/8" 16 x 2" 1324, 1730 $10.31 OC09 -80002007 1x LgPnta+ Wsh+ Rcfnt+Clip 3/8" x 2.5 SST Cap 1220/1419 1015, 1220, 1419 $9.06 OC09 -

MS02200 Hook Wrench, Penta Hook Wrench - $158.61 OC09 -3005065 Hook, Universal Lifting, 36" Hook - $56.38 OC09 -

80002005 Hex Bolt + Washer SST Hex 3/8" 16 x 2-1/2" 1324, 1730 $3.68 OC09 -80002025 2x Hexbolt + 2x Wash SST Hex 3/8" 16 x 2" 1324, 1730 $10.31 OC09 -80002052 2x Hexbolt + 2x Washer SST Hex 1/2" 13 x 1-1/4" 1118, 1212 $3.92 OC09 -80002033 2x Hexbolt + 2x Washer SST Hex 1/2" 13 x 2-1/2" 1118, 1324, 1730 $8.63 OC08 -80002029 2x Hexbolt + 2x Washer SST Hex 1/2" 13 x 3-1/2" 2436, 3048, 3060 $17.63 OC09 -80002026 2x LgPnta + 2x Washer SST Penta 3/8" 16 x 2" 1324, 1730 $15.73 OC09 -80002054 2x LgPnta + 2x Washer SST Penta 1/2" 13 x 1-1/4" 1118, 1212 $6.78 OC09 -80002034 2x LgPnta + 2x Washer SST Penta 1/2" 13 x 2-1/2" 1118, 1324, 1730 $10.41 OC09 -80002030 2x LgPnta + 2x Washer SST Penta 1/2" 13 x 3-1/2" 2436, 3048, 3060 $21.71 OC09 -

- Dividers - - Call Cust. Service - -

80002052 2x Hexbolt + 2x Washer SST Hex 1/2" 13 x 1-1/4" 1212 $3.92 OC09 -80002033 2x Hexbolt + 2x Washer SST Hex 1/2" 13 x 2-1/2" 1118, 1324, 1730 $8.63 OC08 -80002029 2x Hexbolt + 2x Washer SST Hex 1/2" 13 x 3-1/2" 2436, 3048, 3636 $17.63 OC09 -80002054 2x LgPnta + 2x Washer SST Penta 1/2" 13 x 1-1/4" 1212 $6.78 OC09 -80002034 2x LgPnta + 2x Washer SST Penta 1/2" 13 x 2-1/2" 1118, 1324, 1730 $10.41 OC09 -80002030 2x LgPnta + 2x Washer SST Penta 1/2" 13 x 3-1/2" 2436, 3048, 3660 $21.71 OC09 -

34358265 Terminators-3" - - $3.68 OC10 -34358270 Terminators-4" - - $5.11 OC10 -34358280 Terminators-5" - - $9.63 OC10 -34358290 Terminators-6" - - $14.99 OC10 -34358160 Trench, Pulling Eye/B. Oeil 3/8-16SS - - $35.60 OC10 -34358170 Trench, J Hook/Crochet en J, Zinc - - $3.87 OC10 -34358256 Hook cov. HB/Crochet couv. BH - - $32.26 OC10 -34358260 Terminators-2" - - $3.36 OC10 -34358450 Cable Rack Hook 7-1/2" #10A36 - - $9.01 OC10 -- Dividers - - Call Cust Service - -

Hardware & Accessories

Carson Hardware

Enclosure Tools

H-Series Hardware

H-Series Accessories

Synertech Hardware

Synertech Accessories

RATIN

G

Part# Description 1 Description 2 For Use With: ListPrice

Line Item Discount

DesignLoad

31900100 Sealant, Surebond SB-12 10.2oz Cartridge 10 Lid Coverage - - - - $14.73 OC09 -

31901000 Marking Plate-Blank 4"x8" - - - - $7.86 OC10 -31901010 Marking Plate-Electric 4"x8" - - - - $7.86 OC10 -31901030 Marking Plate-Traf c Signal 4"x8" - - - - $7.86 OC10 -31901040 Marking Plate-Street Lighting 4"x8" - - - - $7.86 OC10 -31901050 Marking Plate-High Voltage 4"x8" - - - - $7.86 OC10 -31901070 Marking Plate-Lighting 4"x8" - - - - $7.86 OC10 -31901090 Marking Plate-Special 4"x8" - - - - $7.86 OC10 -

H-Series & Synertech Marking Plates

Marking Plate

Marking Plate Adhesive

RATIN

G

Part# Description 1 Description 2 Color/Item Depth Item

WeightPalletQty

ListPrice

Line Item Discount

DesignLoad

11184054 1118 Steel T Cover Gal Blank PC Box 1118 $163.14 OC01 -13244180 1324 Steel T Cover Gal Blank PC Box 1324 $385.38 OC01 -17304186 1730 Steel T Cover Gal Blank PC Box 1730 $388.00 OC01 -24364011 2436 Steel T Cover Gal Blank PC Box 2436 $677.69 OC01 -30484019 3048 Steel T Cover Gal Blank PC Box 3048 $790.00 OC01 -30604013 3060 Steel T Cover Blank 2 Piece Over | Under 3060 $902.20 OC01 -

H-Series Steel Lids

Steel Lids

RATIN

G

Part# Description 1 Description 2 For Use With: ListPrice

Line Item Discount

DesignLoad

For solid bottom, dividers, and other H-Series options contact customer service.

Page 25: Street Lighting Standards Update - cityofwhitefish.org Lighting...9.1.5 Bollard – Share Use Paths ... Pull boxes shall be installed flush with finished grade. ... Simple wire size

Milbank Manufacturing | 4801 Deramus Ave., Kansas City, MO 64120 | 877.483.5314 | milbankworks.com

7

Utility requirements for this equipment may vary. Always consult the serving utility for their requirements prior to ordering or installing this equipment. This product must be installed by a licensed electrician. Installation of this equipment may require local electrical inspector approval.

COMMERCIAL

PEDESTALS

Commercial PedestalsCP3B “ML” Main Load Center Series

The Milbank Main Load Center Commercial Pedestals are designed to handle the vast majority of all requirements in a standard, stocked configuration.

• No waiting or extra charge• Units feature a load center with a plug-on, back-fed main

breaker• Load center has 16 positions for the 100 amp pedestals and

24 circuits for the 200 amp pedestals• Both sizes include sub-feed lugs to allow feeding an external

panel If your application requires turning loads on based on “dusk-to-dawn” requirements, be sure to see the Milbank Switched Load Center Commercial Pedestal products on the next page.

*Note: Chart shows standard, stocked items. Other options and features are available. Contact factory for options details and availability.

Stocked Pedestals*Optional Fifth Terminal Kit

Main CB Load Center Circuits

Meter Socket TypeAmps Spaces

CP3B11115A22 105J 100 1,2 16 Ring type with test / bypass blocksCP3B12119A22 105J 200 1,2,3 4 24 Ring type with test / bypass blocksCP3B51115A22 K3865 100 1,2 16 Ringless socket with lever bypassCP3B52119A22 K3865 200 1,2,3,4 24 Ringless socket with lever bypass

Typical Applications

Remote site service for multiple loads.

Features

These units include everything required for remote site service:• Type 3R construction• Expandable: load centers allow for future expansion without

costly modifications• All units feature 200 amp meter socket with optional field-

installable fifth terminal kit available• Optional mounting base can be embedded in concrete for

fast, easy installation• Separate sealable and lockable utility termination section• Separate sealable and lockable metering section with the

option of either a ring-type socket with test/bypass blocks (conforms to EUSERC 308) or a heavy duty ringless socket with lever bypass

• A separate sealable and lockable customer section with a load center for “always on” loads that includes:

• Main circuit breaker• 20 (200 or 125 amp models) or 14 (100 amp models)

blank breaker spaces• A circuit directory to document configuration

CP3B11115A22(see drawing on pg. 17)

Page 26: Street Lighting Standards Update - cityofwhitefish.org Lighting...9.1.5 Bollard – Share Use Paths ... Pull boxes shall be installed flush with finished grade. ... Simple wire size

Com

mercial

Meter Pedestals

Data subject to change without notice. Consult local utility for area acceptance. All dimensions are in inches.

Commercial Meter Pedestals - Pad Mounted

Meter Mounting Equipment111

Utility Meter & Test

Block Section

Front Side Back

Customer

Distribution Section

(Padlock Provision) Utility

Termination Section

(Padlock & Sealing

Provisions)

Catalog Amp Jaws Service Bypass Voltage Distribution Type Mounting DimensionsNumber Rating Type Main Breaker Branches Pad Width Depth Height

CMP4111MC-1 100 4 1Ø,3W TB 240 100A,2P 12 Plug-In MB1515 15” 171/2” 54”CMP4111MCH-1 100 4 1Ø,3W TB 480 100A,2P 14 Bolt-On MB2015 20” 171/2” 54”CMP4121MC-1 200 4 1Ø,3W TB 240 200A,2P 12 Plug-In MB2015 20” 171/2” 54”CMP4121MCH-1 200 4 1Ø,3W TB 480 200A,2P 18 Bolt-On MB1515 15” 171/2” 54”CMP4411MC-1 100 7 3Ø,4W TB 240 100A,3P 12 Plug-In MB1515 15” 171/2” 54”CMP4411MCH-1 100 7 3Ø,4W TB 480 100A,3P 12 Bolt-On MB2015 20” 171/2” 54”CMP4421MC-1 200 7 3Ø,4W TB 240 200A,3P 12 Plug-In MB1515 15” 171/2” 54”CMP4421MCH-1 200 7 3Ø,4W TB 480 200A,3P 18 Bolt-On MB2015 20” 171/2” 54”

Application• Utility meter, main disconnect and distribution panel• Receive ANSI C12.10 watthour meters

Construction• Ring type• NEMA Type 3R• ANSI 61 gray E-coat finish• Separate sealable utility termination and meter compartments• Padlockable disconnect and distribution section• Underground feed

Standards• UL Listed• ANSI C12.7• EUSERC #308

Accessories• 5th jaw kit - 50365 (single phase)• Filler plate kit - 25139• Class T fusible pullouts• Controls, see page 109

CMP4111MC-1

Page 27: Street Lighting Standards Update - cityofwhitefish.org Lighting...9.1.5 Bollard – Share Use Paths ... Pull boxes shall be installed flush with finished grade. ... Simple wire size

Utility requirements may vary. Always consult the serving utility for their requirements prior to ordering or installing this equipment. This product must always be installed by a licensed electrician. Installation of this equipment may require local electrical inspector approval.

milbankworks.com

CP-16PDMNT-CALTCOM MTR PED ACCESSORIES784572164857

CCatalog Number:IItem Description:UUPC Code:

Page 28: Street Lighting Standards Update - cityofwhitefish.org Lighting...9.1.5 Bollard – Share Use Paths ... Pull boxes shall be installed flush with finished grade. ... Simple wire size

TORK

PH

OTO

CO

NTR

OLS

435

FEATURES

APPLICATIONS

SPECIFICATIONS

2100 SERIESSPECIFICATION GRADE1/2" CONDUIT MOUNTINGDIE CAST ZINCPHOTOCONTROL

Parking lot lightingBuilding perimeter lightingOutdoor signage

CAT.NO.

UPCCODE

VOLTAGE(VAC) 50-60Hz

RATINGLED

TUNGSTEN BALLAST

2101 60012 120 2000W 1800VA 600VA*

2104 60013 208-277 2000W 1800VA 600VA*

2107 60031 120/277 2000W 1800VA 600VA*

73866 62020 Mounting Bracket - - -

SENSOR: Conformal coated cadmium sulphide photocell resists effects of moisture and airborne contaminants. Photocell responds to the light spectrum near to that of a human eye.

OPERATION: Delay of up to two minutes to prevent false switching due to light from passing vehicles, lightning, etc.

STANDARDS: Meets ANSI/UL773A.

HOUSING: Heavy Duty die cast zinc housing and base. Gasketed for maximum weather protection.

ENERGY SAVINGS: Works with screw base CFLs.

ON/OFF: Turn ON is 1 to 5fc, Turn OFF is 3 to 15fc, without the slide in position. ON/OFF adjustment is easily made by moving a slide cover. No tools required.

TIME DELAY: ON and OFF.

CELL: Cadmium sulphide, epoxy conformal coated 1" diameter.

CONTACTS: Remain closed between dusk and dawn. (The unit fails in the ON position).

LEAD WIRES: Three color coded, minimum 6” wire leads, #16AWG, rated for 105 °C.

POWER CONSUMPTION: Averages under 1 watt.

TEMPERATURE RANGE: -40 °F to +140 °F (-40 °C to +60 °C).

FAIL MODE: ON.

WARRANTY: 5 years.

*LED rating for UL only.

BO

PBOO

2107 Only