173
Drawing Description Drawing No. Drawing Register ST 001 - 005 Introduction Series 000 StoTherm Insulated Facade System Introduction ST 006 StoTherm Insulated Facade System Reinforcing Mesh Application ST 007 StoTherm Insulated Facade System Panel Information ST 008 Panel Layout Series 100 StoTherm Insulated Facade System SS 106 StoTherm StoArmat Render System ST 100 StoTherm Insulated Facade System SS 105 StoTherm StoMiral Render System ST 101 StoTherm Insulated Facade System EPS sheet and Fixing Layout Typical Elevation ST 102 StoTherm Insulated Facade System StoTherm Panel Layout ST 103 Foundation Series 200 StoTherm Insulated Facade System Foundation Slab-on-Ground ST 200 StoTherm Insulated Facade System Insulated Slab-on-Ground ST 201 StoTherm Insulated Facade System Rebated Slab-on-Ground - Render Finish ST 202 StoTherm Insulated Facade System Ribraft Floor System/Edge Detail ST 203 StoTherm Insulated Facade System Conc.Block Foundation Edge Detail ST 204 StoTherm Insulated Facade System EPS Block Foundation Detail ST 205 StoTherm Insulated Facade System Solid Conc. Foundation Edge Detail ST 206 StoTherm Insulated Facade System Conc. Continuous Perimeter Foundation Wall ST 207 StoTherm Insulated Facade System Maxraft Floor System/Edge Detail ST 208 StoTherm Insulated Facade System Timber Pile/Subfloor Ventilation (parallel wall) ST 209 StoTherm Insulated Facade System Timber Pile/Subfloor Ventilation (right angled wall) ST 210 StoTherm Insulated Facade System Timber Subfloor With Jackstuds ST 211 StoTherm Insulated Facade System Masonry Conc. Block in Ground Wall ST 212 StoTherm Insulated Facade System Concrete Block Interstorey Drained Junction ST 213 Walls Series 300 StoTherm Insulated Facade System StoTherm Panel Layout ST 300 StoTherm Insulated Facade System Panel Fixing Vertical ST 301 StoTherm Insulated Facade System Panel Fixing Horizontal ST 302 StoTherm Insulated Facade System External Corner ST 303 StoTherm Insulated Facade System Internal Corner ST 304 StoTherm Insulated Facade System Vertical Control Joint ST 305 StoTherm Insulated Facade System Horizontal Inter Storey ST 306 StoTherm Insulated Facade System Horizontal Inter Storey Control Joint ST 307 StoTherm Insulated Facade System Drained Junction at Third Storey ST 308 StoTherm Insulated Facade System Boxed Beam ST 309 StoTherm Insulated Facade System Post Detail ST 310 THESE DETAILS ARE ISSUED AS A GUIDE USING STANDARD BUILDING PRACTICES BASED ON THE NZBC. VARIOUS BUILDING COMPONENTS ARE DETAILED AND IT IS THE RESPONSIBILITY OF EACH TRADE INVOLVED TO ENSURE THAT THEIR PARTICULAR ELEMENTS ARE INSTALLED CORRECTLY. NOTE: REFER TO INDIVIDUAL MANUFACTURES FOR CURRENT DETAILS AND SPECIFICATIONS - SEE www.sto.co.nz FOR CURRENT DETAILS. STO DRAWING REGISTER PAGE 1 OF 6 The information contained on this page is based on our experience and research at the date of issue. The detail is for use by Registered Architects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right to alter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insure they have and use the current Sto details and specifications on site. STOTHERM SYSTEM STOTHERM INSULATED FACADE SYSTEM DRAWING REGISTER ST 001 2017

STOTHERM INSULATED FACADE SYSTEM DRAWING …...StoTherm Insulated Facade System Vertical Junction Schist or StoneVeneer/StoTherm ST 847 StoTherm Insulated Facade System Horiz.Junction

  • Upload
    others

  • View
    10

  • Download
    0

Embed Size (px)

Citation preview

  • Drawing Description Drawing No.

    Drawing Register ST 001 - 005Introduction Series 000StoTherm Insulated Facade System Introduction ST 006StoTherm Insulated Facade System Reinforcing Mesh Application ST 007StoTherm Insulated Facade System Panel Information ST 008

    Panel Layout Series 100StoTherm Insulated Facade System SS 106 StoTherm StoArmat Render System ST 100StoTherm Insulated Facade System SS 105 StoTherm StoMiral Render System ST 101StoTherm Insulated Facade System EPS sheet and Fixing Layout Typical Elevation ST 102StoTherm Insulated Facade System StoTherm Panel Layout ST 103

    Foundation Series 200StoTherm Insulated Facade System Foundation Slab-on-Ground ST 200StoTherm Insulated Facade System Insulated Slab-on-Ground ST 201StoTherm Insulated Facade System Rebated Slab-on-Ground - Render Finish ST 202StoTherm Insulated Facade System Ribraft Floor System/Edge Detail ST 203StoTherm Insulated Facade System Conc.Block Foundation Edge Detail ST 204StoTherm Insulated Facade System EPS Block Foundation Detail ST 205StoTherm Insulated Facade System Solid Conc. Foundation Edge Detail ST 206StoTherm Insulated Facade System Conc. Continuous Perimeter Foundation Wall ST 207StoTherm Insulated Facade System Maxraft Floor System/Edge Detail ST 208 StoTherm Insulated Facade System Timber Pile/Subfloor Ventilation (parallel wall) ST 209StoTherm Insulated Facade System Timber Pile/Subfloor Ventilation (right angled wall) ST 210StoTherm Insulated Facade System Timber Subfloor With Jackstuds ST 211StoTherm Insulated Facade System Masonry Conc. Block in Ground Wall ST 212StoTherm Insulated Facade System Concrete Block Interstorey Drained Junction ST 213

    Walls Series 300StoTherm Insulated Facade System StoTherm Panel Layout ST 300StoTherm Insulated Facade System Panel Fixing Vertical ST 301 StoTherm Insulated Facade System Panel Fixing Horizontal ST 302StoTherm Insulated Facade System External Corner ST 303StoTherm Insulated Facade System Internal Corner ST 304StoTherm Insulated Facade System Vertical Control Joint ST 305StoTherm Insulated Facade System Horizontal Inter Storey ST 306StoTherm Insulated Facade System Horizontal Inter Storey Control Joint ST 307StoTherm Insulated Facade System Drained Junction at Third Storey ST 308StoTherm Insulated Facade System Boxed Beam ST 309StoTherm Insulated Facade System Post Detail ST 310

    THESE DETAILS ARE ISSUED AS A GUIDE USING STANDARD BUILDING PRACTICES BASED ON THE NZBC.VARIOUS BUILDING COMPONENTS ARE DETAILED AND IT IS THE RESPONSIBILITY OF EACH TRADE INVOLVED TOENSURE THAT THEIR PARTICULAR ELEMENTS ARE INSTALLED CORRECTLY. NOTE: REFER TO INDIVIDUALMANUFACTURES FOR CURRENT DETAILS AND SPECIFICATIONS - SEE www.sto.co.nz FOR CURRENT DETAILS.

    STO DRAWING REGISTER

    PAGE 1 OF 6

    The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.

    STOTHERMSYSTEM

    STOTHERM INSULATED FACADE SYSTEM

    DRAWING REGISTER

    ST 001

    2017

  • Drawing Description Drawing No.

    Wall Penetrations & Fittings Series 350StoTherm Insulated Facade System Pipe Penetration Detail ST 350StoTherm Insulated Facade System Light Fitting/Fixing Detail ST 351StoTherm Insulated Facade System Tap Fitting/Fixing Detail ST 352StoTherm Insulated Facade System Handrail Bracket/Fixing Detail ST 353StoTherm Insulated Facade System Meterbox - Isometric ST 354StoTherm Insulated Facade System Meterbox - Cross Section ST 355StoTherm Insulated Facade System Downpipe Saddle Fixing & Wiring Details ST 356StoTherm Insulated Facade System Fan Vent Detail ST 357StoTherm Insulated Facade System Inter-Storey Junction with Poly Profile ST 358StoTherm Insulated Facade System Joint at Third Storey with Poly profile ST 359

    Joinery Series 400StoTherm Insulated Facade System Alu.Joinery - Head Detail - Stick on Jamb ST 400StoTherm Insulated Facade System Alu.Joinery - Head Detail - Cavity Jamb ST 401StoTherm Insulated Facade System Alu.Joinery - Sill Detail - Sto uPVC Stick on Sill ST 402StoTherm Insulated Facade System Alu.Joinery - Jamb Detail - Sto uPVC Cavity Jamb ST 403StoTherm Insulated Facade System Alu.Joinery - Jamb Detail - Sto uPVC Stick on Jamb ST 404StoTherm Insulated Facade System Int.Cnr Alu.Window/Door Joinery - Jamb Detail ST 405StoTherm Insulated Facade System Entry Door Threshold Detail ST 406StoTherm Insulated Facade System Entry Door/Deck Threshold Detail ST 407StoTherm Insulated Facade System Bifold Door/Threshold Detail ST 408StoTherm Insulated Facade System Level Entry Threshold Detail ST 409StoTherm Insulated Facade System Garage Door - Timber Head Detail ST 410StoTherm Insulated Facade System Garage Door - Timber Jamb Detail ST 411StoTherm Insulated Facade System Garage Door - Rendered Head Detail ST 412StoTherm Insulated Facade System Garage Door - Rendered Jamb Detail ST 413StoTherm Insulated Facade System Sto uPVC Head and Jamb Flashing Isometric ST 414

    Parapets, Balustrades, Decks Series 500StoTherm Insulated Facade System Parapet/Metal Flashing Detail ST 500StoTherm Insulated Facade System Rendered Parapet/Balustrade Detail ST 501StoTherm Insulated Facade System Parapet and/or Encl.Balustrade Wall Junction - Plan View ST 502StoTherm Insulated Facade System Flexible Flashing Install - Isometric ST 503StoTherm Insulated Facade System Metal Saddle Flashing & Cap Install - Isometric ST 504StoTherm Insulated Facade System StoFlexyl Meshed Saddle Flashing Install - Isometric ST 505StoTherm Insulated Facade System StoFlexyl Meshed Waterproofing Cap - Isometric ST 506StoTherm Insulated Facade System Balustrade/Encl.Deck Detail ST 507StoTherm Insulated Facade System Enclosed Deck Detail ST 508StoTherm Insulated Facade System Cantilevered Slatted Deck ST 509StoTherm Insulated Facade System Non Cantilevered Slatted Deck ST 510StoTherm Insulated Facade System Timber Beam/Pergola Detail ST 511StoTherm Insulated Facade System Parallel Deck Joist Bracket ST 512StoTherm Insulated Facade System RWH/Scupper Opening ST 513

    STO DRAWING REGISTER

    THESE DETAILS ARE ISSUED AS A GUIDE USING STANDARD BUILDING PRACTICES BASED ON THE NZBC.VARIOUS BUILDING COMPONENTS ARE DETAILED AND IT IS THE RESPONSIBILITY OF EACH TRADE INVOLVED TOENSURE THAT THEIR PARTICULAR ELEMENTS ARE INSTALLED CORRECTLY. NOTE: REFER TO INDIVIDUALMANUFACTURES FOR CURRENT DETAILS AND SPECIFICATIONS - SEE www.sto.co.nz FOR CURRENT DETAILS.

    PAGE 2 OF 6

    The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.

    STOTHERMSYSTEM

    STOTHERM INSULATED FACADE SYSTEM

    DRAWING REGISTER

    ST 002

    2017

  • Drawing Description Drawing No.

    Soffit Series 600StoTherm Insulated Facade System Flat Soffit/Wall Junction Timber Fascia ST 600 StoTherm Insulated Facade System Raking Soffit/Wall Junction Timber Fascia ST 601StoTherm Insulated Facade System Face Fixed Timber Fascia ST 602StoTherm Insulated Facade System Reverse Raking Soffit to wall with Flashing ST 603 StoTherm Insulated Facade System Raking Soffit - Sto uPVC Control Joint ST 604 StoTherm Insulated Facade System Soffit to Cladding Detail ST 605StoTherm Insulated Facade System Gutter/Wall Apron Flashing Junction ST 606 StoTherm Insulated Facade System Soffit at Window/Door Head ST 607StoTherm Insulated Facade System Metal Fascia Face Fixed Membrane Roof ST 608StoTherm Insulated Facade System Metal Fascia Barge Detail ST 609StoTherm Insulated Facade System Metal Fascia Face Fixed Barge Detail ST 610StoTherm Insulated Facade System Flat Soffit/Wall Junction Metal Fascia ST 611StoTherm Insulated Facade System Raking Soffit/Wall Junction Metal Fascia ST 612StoTherm Insulated Facade System Face Fixed Metal Fascia ST 613

    Roof Series 700StoTherm Insulated Facade System Apron Flashing ST 700StoTherm Insulated Facade System Parallel Apron Flashing ST 701StoTherm Insulated Facade System Inter-storey Transverse (Apron) Roof/Stopend ST 702 StoTherm Insulated Facade System Inter-storey Deck or Roof/Stopend Flashing ST 703StoTherm Insulated Facade System Inter-storey Roof Stop End Flashing - Plan View ST 704StoTherm Insulated Facade System Roof Penetration/Gutter (Masonry Tile) ST 705StoTherm Insulated Facade System Roof Parallel/Hidden Gutter ST 706StoTherm Insulated Facade System Face Fixed Fascia/Barge ST 707StoTherm Insulated Facade System Face Fixed Fascia/Membrane Roof ST 708StoTherm Insulated Facade System Roof/Wall Ridge ST 709StoTherm Insulated Facade System Framed Chimney ST 710

    Dissimilar Material

    Weatherboard Series 800StoTherm Insulated Facade System Ext.Corner Weatherboard/StoTherm - Opt 1 ST 800StoTherm Insulated Facade System Ext.Corner Weatherboard/StoTherm - Opt 2 ST 801StoTherm Insulated Facade System Ext.Corner Direct Fixed Weatherboards/StoTherm ST 802StoTherm Insulated Facade System Int.Corner Weatherboard/StoTherm - Opt 1 ST 803StoTherm Insulated Facade System Int.Corner Weatherboard/StoTherm - Opt 2 ST 804StoTherm Insulated Facade System Int.Corner Weatherboard/StoTherm - Direct Fix ST 805StoTherm Insulated Facade System Vertical Joint Weatherboard/StoTherm - Opt 1 ST 806StoTherm Insulated Facade System Vertical Joint Weatherboard/StoTherm - Opt 2 ST 807StoTherm Insulated Facade System Horizontal Junction Weatherboard/StoTherm ST 808StoTherm Insulated Facade System Gable End Weatherboard/StoTherm ST 809StoTherm Insulated Facade System Internal Corner Direct Fixed EIFS to StoTherm ST 810.1

    STO DRAWING REGISTER

    THESE DETAILS ARE ISSUED AS A GUIDE USING STANDARD BUILDING PRACTICES BASED ON THE NZBC.VARIOUS BUILDING COMPONENTS ARE DETAILED AND IT IS THE RESPONSIBILITY OF EACH TRADE INVOLVED TOENSURE THAT THEIR PARTICULAR ELEMENTS ARE INSTALLED CORRECTLY. NOTE: REFER TO INDIVIDUALMANUFACTURES FOR CURRENT DETAILS AND SPECIFICATIONS - SEE www.sto.co.nz FOR CURRENT DETAILS.

    PAGE 3 OF 6

    The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.

    STOTHERMSYSTEM

    STOTHERM INSULATED FACADE SYSTEM

    DRAWING REGISTER

    ST 003

    2017

  • Drawing Description Drawing No.

    Continuation Dissimilar Material

    Brick Series 810StoTherm Insulated Facade System External Corner Brick Veneer/StoTherm ST 810StoTherm Insulated Facade System Internal Corner Brick Veneer/StoTherm - Opt 1 ST 811StoTherm Insulated Facade System Internal Corner Brick Veneer/StoTherm - Opt 2 ST 812StoTherm Insulated Facade System Vertical Junction Brick Veneer/StoTherm ST 813StoTherm Insulated Facade System Horizontal Junction Brick Veneer/StoTherm ST 814

    Fibre Cement Sheet Series 820StoTherm Insulated Facade System External Corner FC Sheet/ StoTherm ST 820StoTherm Insulated Facade System Internal Corner FC Sheet/ StoTherm - Opt 1 ST 821StoTherm Insulated Facade System Internal Corner FC Sheet/ StoTherm - Opt 2 ST 822StoTherm Insulated Facade System FC Sheet - Framed Sub Floor Cladding ST 823StoTherm Insulated Facade System FC Sheet Gable End ST 824

    Concrete Block Series 830StoTherm Insulated Facade System External Corner Concrete Block/StoTherm ST 830StoTherm Insulated Facade System Internal Corner Concrete Block/StoTherm ST 831StoTherm Insulated Facade System Vertical Joint Concrete Block/StoTherm ST 832StoTherm Insulated Facade System Horizontal Junction Concrete Block/StoTherm ST 833

    Manufactured Stone - Schist & Natural Stone Series 840StoTherm Insulated Facade System Ext.Cnr Manuf.Stone/StoTherm - Opt 1 ST 840StoTherm Insulated Facade System Ext.Cnr Manuf.Stone/StoTherm - Opt 2 ST 841StoTherm Insulated Facade System Ext.Cnr Schist or Stone Veneer/StoTherm ST 842StoTherm Insulated Facade System Boxed Ext.Cnr Stone Veneer/StoTherm ST 843StoTherm Insulated Facade System Internal Cnr. Manuf.Stone/StoTherm ST 844StoTherm Insulated Facade System Internal Cnr. Schist or Stone Veneer/StoTherm ST 845StoTherm Insulated Facade System Vertical Junction Manuf.Stone/StoTherm ST 846StoTherm Insulated Facade System Vertical Junction Schist or StoneVeneer/StoTherm ST 847StoTherm Insulated Facade System Horiz.Junction Manuf.Stone/StoTherm ST 848StoTherm Insulated Facade System Horiz.Junction Schist or StoneVeneer/StoTherm ST 849

    Profile Metal Series 850StoTherm Insulated Facade System Ext.Cnr Horiz.Profiled Metal/StoTherm ST 850StoTherm Insulated Facade System Int.Cnr Horiz.Profiled Metal/StoTherm ST 851StoTherm Insulated Facade System Vertical Junction Horiz.Profiled Metal/StoTherm ST 852StoTherm Insulated Facade System Horizontal Junction Horiz.Profiled Metal/StoTherm ST 853StoTherm Insulated Facade System External Corner Vertical Profiled Metal/StoTherm ST 854StoTherm Insulated Facade System Internal Corner Vertical Profiled Metal/StoTherm ST 855StoTherm Insulated Facade System Horiz.Junction Vertical Profiled Metal/StoTherm ST 856

    STO DRAWING REGISTER

    THESE DETAILS ARE ISSUED AS A GUIDE USING STANDARD BUILDING PRACTICES BASED ON THE NZBC.VARIOUS BUILDING COMPONENTS ARE DETAILED AND IT IS THE RESPONSIBILITY OF EACH TRADE INVOLVED TOENSURE THAT THEIR PARTICULAR ELEMENTS ARE INSTALLED CORRECTLY. NOTE: REFER TO INDIVIDUALMANUFACTURES FOR CURRENT DETAILS AND SPECIFICATIONS - SEE www.sto.co.nz FOR CURRENT DETAILS.

    PAGE 4 OF 6

    The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.

    STOTHERMSYSTEM

    STOTHERM INSULATED FACADE SYSTEM

    DRAWING REGISTER

    ST 004

    2017

  • Drawing Description Drawing No.

    Continuation Dissimilar Material

    StoTherm Panel EIFS Series 860StoTherm Insulated Facade System Ext.Cnr StoPoren/StoTherm ST 860StoTherm Insulated Facade System Int.Cnr StoPoren/StoTherm ST 861StoTherm Insulated Facade System Vertical Joint 50mm StoPoren/StoTherm ST 862StoTherm Insulated Facade System Vertical Joint 80mm StoPoren/StoTherm ST 863StoTherm Insulated Facade System Inter-Storey Junction StoPoren/StoTherm ST 864StoTherm Insulated Facade System Inter-Storey Third Storey Drained Inter-storey Junction ST 865

    DISSIMILAR JOINERY Series 870TIMBER JOINERYStoTherm Insulated Facade System Timber Window Joinery - Head Detail ST 870StoTherm Insulated Facade System Timber Window Joinery - Sill Detail ST 871StoTherm Insulated Facade System Timber Window Joinery - Jamb Detail ST 872StoTherm Insulated Facade System Timber Door Joinery - Timber Floor/Threshold Detail ST 873StoTherm Insulated Facade System Timber Door Joinery - Concrete Floor/Threshold Detail ST 874NK PVCu JOINERYStoTherm Insulated Facade System NK PVCu - Head Detail ST 875StoTherm Insulated Facade System NK PVCu - Sill Detail ST 876StoTherm Insulated Facade System NK PVCu - Jamb Detail ST 877FLASHMAN JOINERY FLASHING SYSTEMStoTherm Insulated Facade System Flashman Head Flashing ST 878StoTherm Insulated Facade System Flashman Sill Flashing ST 879StoTherm Insulated Facade System Flashman Jamb Flashing ST 880HOMERIT PVC JOINERYStoTherm Insulated Facade System Homerit PVC Joinery - Head Detail ST 881StoTherm Insulated Facade System Homerit PVC Joinery - Sill Detail ST 882StoTherm Insulated Facade System Homerit PVC Joinery - Jamb Detail ST 883

    Rusticated Weatherboard Series 890StoTherm Insulated Facade System Ext.Corner Rusticated Weatherboard/StTherm - Opt 1 ST 890StoTherm Insulated Facade System Ext.Corner Rusticated Weatherboard/StoTherm - Opt 2 ST 891StoTherm Insulated Facade System Ext.Corner Direct Fixed Rusticated Weatherboards/StoTherm ST 892StoTherm Insulated Facade System Int.Corner Rusticated Weatherboard/StoTherm - Opt 1 ST 893StoTherm Insulated Facade System Int.Corner Rusticated Weatherboard/StoTherm - Opt 2 ST 894StoTherm Insulated Facade System Int.Corner Direct Fixed Rusticated Weatherboard/StoTherm ST 895StoTherm Insulated Facade System Vertical Joint Rusticated Weatherboard/StoTherm - Opt 1 ST 896StoTherm Insulated Facade System Vertical Joint Rusticated Weatherboard/StoTherm - Opt 2 ST 897StoTherm Insulated Facade System Horizontal Junction Rusticated Weatherboard/StoTherm ST 898StoTherm Insulated Facade System Gable End Rusticated Weatherboard/StoTherm ST 899

    STO DRAWING REGISTER

    THESE DETAILS ARE ISSUED AS A GUIDE USING STANDARD BUILDING PRACTICES BASED ON THE NZBC.VARIOUS BUILDING COMPONENTS ARE DETAILED AND IT IS THE RESPONSIBILITY OF EACH TRADE INVOLVED TOENSURE THAT THEIR PARTICULAR ELEMENTS ARE INSTALLED CORRECTLY. NOTE: REFER TO INDIVIDUALMANUFACTURES FOR CURRENT DETAILS AND SPECIFICATIONS - SEE www.sto.co.nz FOR CURRENT DETAILS.

    PAGE 5 OF 6

    The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.

    STOTHERMSYSTEM

    STOTHERM INSULATED FACADE SYSTEM

    DRAWING REGISTER

    ST 005

    2017

  • STOTHERM INSULATED FACADE SYSTEM

    SS105 STOTHERM STOMIRAL RENDER SYSTEM BRANZ APPRAISAL CERTIFICATE NO. 478INCORPORATING:1. STOLEVELL NOVO, STOLEVELL UNI or MULTISCREED 25kg BAG EUROPEAN FIBRE

    REINFORCED CEMENT BASED RENDER USED WITH EUROPEAN MESH AS A REINFORCINGBASECOAT RENDER.

    2. STOPLEX W SEALER - 10lt CONTAINER EUROPEANACYLIC/SILANE PRIMER TO SEAL MINERALSURFACES

    3. STOLIT K COLOURED - 25kg PAIL EUROPEAN FIBRE REINFORCED NON CEMENT COLOUREDFINISHING RENDER AVAILABLE IN 1.0/1.5/2.0/3.0mm SIZED TEXTURE IN A PAIL

    4. STOCOLOR : MAXICRYL MATT FACADE PAINT 15lt PAIL: LASTIC SATIN FACADE PAINT 15lt PAIL: LOTUSAN MINERAL RESIN PAINT 15lt PAIL

    SS106 STOTHERM STOARMAT RENDER SYSTEM BRANZ APPRAISAL CERTIFICATE NO. 478INCORPORATING:1. STOLEVELL NOVO, STOLEVELL UNI or MULTISCREED 25kg BAG BASECOAT RENDER TO

    STRAIGHTEN AND PROVIDE A SOLID THICKER BASECOAT2. STOARMAT CLASSIC RENDER 23kg PAIL EUROPEAN FIBRE REINFORCED NON CEMENT BASED

    CRACKED RESISTANT RENDER USED WITH EUROPEAN MESH AS A REINFORCEMENT RENDER3. STOLIT K or MP COLOURED RENDER 25kg PAIL EUROPEAN FIBRE REINFORCED NON CEMENT

    COLOURED FINISHING RENDER AVAILABLE IN 1.0/1.5/2.0/3.0mm SIZED TEXTURE AND MP or MPNATURAL SPONGE FINISHED RENDER

    4. STOCOLOR : MAXICRYL MATT FACADE PAINT 15lt PAIL: LASTIC SATIN FACADE PAINT 15lt PAIL: LOTUSAN MINERAL RESIN PAINT 15lt PAIL

    The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.

    STOTHERMSYSTEM

    STOTHERM INSULATED FACADE SYSTEM

    INTRODUCTION

    ST 006

    2017

  • ALU.WINDOW JOINERY

    STO COATINGSTOLIT COLOUREDFINISHING RENDER

    6mm SEALANT GAPBETWEEN JOINERY AND

    uPVC FLASHING

    NOTE:1. PROPRIETARY ALUMINUM HEAD FLASHING AND

    STO uPVC SILL & JAMB FLASHINGS AREREQUIRED

    2. MS SEALANT APPLIED TO JAMBS & WINDOWSILL TO CLADDING JUNCTION

    STO ARMAT MESHEDRENDER

    STOTHERM PANEL

    NOTE: STO uPVCFLASHING NOT SHOWNFOR CLARITY AREMESHED IN STOARMAT

    MESH WRAPPEDAROUND REVEALSAND ONTO STO uPVCFLASHINGS

    MESH 50mm MIN. INEACH DIRECTION TOREINFORCE MESH SEAMAT INSIDE CORNER

    DIAGONALREINFORCEMENT/BUTTERFLY USING STOMESH - 200X100mm OVERWALL MESHSTOLEVELL NOVO, STO

    LEVELL UNI orMULTISCREED

    BASECOAT

    The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.

    STOTHERMSYSTEM

    STOTHERM INSULATED FACADE SYSTEM

    REINFORCING MESH APPLICATION

    ST 007

    2017

  • SCALE 1:20

    STOTHERM PANELS

    H GRADE WHITE SELF EXTINGUISHINGPOLYSTYRENE MANUFACTURED TO COMPLYWITH AS1366.3

    SIZES - STANDARD PANEL 2700 x 1200mm

    THICKNESS AND R VALUE NZS4214 REQUIRES A45% REDUCTION OF R VALUE ON A CAVITY

    cavity + 50mm - RV 0.76cavity + 60mm - RV 0.91cavity + 80mm - RV 1.22cavity + 100mm - RV 1.52

    STOTHERM+ PANELS

    GREY GRAPHITE INFUSED SELF EXTINGUISHINGPOLYSTYRENE COMPLYING WITH AS1366

    SIZES - STANDARD PANEL 2700 x 1200mm

    cavity + 40mm - RV 0.72cavity + 60mm - RV 1.06cavity + 80mm - RV 1.41

    1200

    2700

    The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.

    STOTHERMSYSTEM

    STOTHERM INSULATED FACADE SYSTEM

    PANEL INFORMATION

    ST 008

    2017

  • SCALE 1:20

    TIMBER FRAMINGTO NZS 3604

    STOTHERM ARMAT CLASSICRENDER SYSTEM - SS106

    STO uPVC ADJUSTABLE FOOTTRAY - incl.base/extension/base

    WALL UNDERLAY MEETINGREQUIREMENTS E2/AS1

    CONCRETE FOUNDATION AS PER NZS3604 ORSPECIFIC ENGINEERING REQUIREMENTS

    FINISHING RENDER: STOLIT K &MP RANGE

    INSULATION:SELF-EXTINGUISHINGPOLYSTYRENE SHEET

    SELECTED COATING:STOCOLOR: MAXICRYL MATT FACADE PAINT: LASTIC SATIN PAINT: LOTUSAN MINERAL RESIN

    BASECOAT: STOLEVELL NOVO,STOLEVELL UNI or MULTISCREED 4-5mm

    STOTHERM 20mm VH CAVITYBATTENS

    REINFORCEMENT: STOARMAT

    PLUS STO MESH

    The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.

    STOTHERMSYSTEM

    STOTHERM INSULATED FACADE SYSTEM

    SS106 STOTHERM STOARMAT RENDER SYSTEM

    ST 100

    2017

  • SCALE 1:20

    TIMBER FRAMINGTO NZS 3604

    STOTHERM STOMIRALRENDER SYSTEM - SS105

    STO uPVC ADJUSTABLE FOOTTRAY - incl.base/extension/base

    WALL UNDERLAY MEETINGREQUIREMENTS E2/AS1

    CONCRETE FOUNDATION AS PER NZS3604 ORSPECIFIC ENGINEERING REQUIREMENTS

    FINISHING RENDER: STOLIT K &MP RANGE

    SELECTED STOTHERM PANEL

    COATING/STOCOLOR: MAXICRYL MATT FACADE PAINT: LASTIC SATIN PAINT: LOTUSAN MINERAL RESIN PAINT

    BASECOAT: STOLEVELL NOVO,STOLEVELL UNI or MULTISCREEDPLUS: STO EUROPEAN MESHSEALED WITH STOPLEX WPRIMER

    STOTHERM 20mm VH CAVITYBATTENS

    The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.

    STOTHERMSYSTEM

    STOTHERM INSULATED FACADE SYSTEM

    SS105 STOTHERM STOMIRAL RENDER SYSTEM

    ST 101

    2017

  • N.T.S

    300600

    DOORWINDOW

    NOTE: SHEET JOINTS AROUNDOPENINGS ARE GLUED or FOAMFUSED FOR STABILITY

    STOTHERM 20mm VH FIXEDOVER FRAME & BUILDING

    UNDERLAY

    REFER TO WIND ZONES FORREQUIRED HORIZONTAL

    SPACERS 100mm LONG - MUSTBE SET TO A FALL 5° MIN.

    NOTE: CAVITY SYSTEM IS A VENTED DRAINAGE SYSTEM.FIX STO uPVC FOOT TRAY BEFORE BATTENS.

    FIXINGS IN WIND ZONES

    LOW, MEDIUM & HIGHStuds 300mm fixing ctrs top & bottom plates and dwangs. Onefixing between studs

    VERY HIGHStuds, plates and dwangs 200mm fixing ctrsEXTRA HIGHStuds, plates and dwangs 150mm fixing ctrs

    WHERE STUD SPACINGS ARE GREATER THAN 450mmCTRS FIX ADDITIONAL INTERMEDIATE BATTEN TOPREVENT INSULATION ENCROACHING INTO CAVITY SPACE

    2nd LEVEL

    300

    A A A A

    A A

    A

    NO INTER-STOREY JOINTREQUIRED AT 2nd LEVEL

    VERTICAL CONTROL JOINTS REQUIREDFOR WALLS OVER 20 METERS

    The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.

    STOTHERMSYSTEM

    STOTHERM INSULATED FACADE SYSTEM

    EPS SHEET & FIXING LAYOUT - TYPICAL (Elevation)

    ST 102

    2017

  • N.T.S

    SHEET LAYOUT - LINE UPSHEETS WITH OPENINGS.FLUSH FILL ANY JOINTGAPS WITH STO FOAMTAKING CARE NOT TOFILL CAVITY

    STOARMAT CLASSICMESHED HEAD, SILL& JAMB FLASHINGS

    100x200mm MIN. DIAGONALBUTTERFLY REINFORCEMENT

    STO uPVC PREMESHEDCORNER ANGLE

    SELECTED EPSSHEETS -2700x1200mm

    NOTE: USE FULL SHEETS WHERE POSSIBLE ALL CUT SHEETS SHALLBE CAREFULLY MADE TO ACHIEVE A GOOD FIT. ALL SHEET JOINTSSHOULD BE FLUSHED FILLED WITH STO ADHESIVE FOAM - TAKINGCARE NOT TO FILL CAVITY

    200

    STO MESH JOINTSOVERLAPPED 75mm MIN.STO LEVELL UNI/MESHMULTI SCREED ORSTOARMAT CLASSICMESH COAT

    H GRADE EPS SHEETS NORMALLY - 2700 x 1200mm

    NOTE: USE FULL SHEETS WHERE POSSIBLEALL SHEET EDGES MUST BE SUPPORTED BY A FRAMING MEMBERALL SHEETS CUTS SHALL BE MADE CAREFULLY TO ACHIEVE A TIGHT BUTT FIT.

    ANY GAPS IN THE EPS SHEET MUST BE FILLED WITH STO FOAM ON HORIZONTAL JOINTS CARE MUST BE TAKEN TO AVOID FOAM FILLING THE CAVITY

    The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.

    STOTHERMSYSTEM

    STOTHERM INSULATED FACADE SYSTEM

    STOTHERM PANEL LAYOUT

    ST 103

    2017

  • STO uPVC VENTEDADJUSTABLE FOOT TRAY

    SCALE 1:5

    6mm OVERHANGRECOMMENDED TOAVOID VARIANCES INFOUNDATION

    TIMBER FRAMINGTO NZS 3604

    DPC

    INTERIOR LINING

    225m

    m M

    IN.

    TO U

    NP

    AV

    ED

    GR

    OU

    ND

    LE

    VE

    L

    50m

    mcl

    ad.

    150m

    m M

    IN.

    TO P

    AV

    ED

    GL

    WALL UNDERLAY

    STOTHERM RENDER SYSTEM

    CAVITY SPACERS TO SUITFIXINGS

    AS PER NZS 3604

    STOTHERM PANELFIXING

    6

    STO RENDER SYSTEMON FOUNDATION

    CONCRETE SLAB/REINFORCINGAS PER NZS 3604 OR ENGINEERSPECIFIC DESIGN - NOT SHOWN

    FOR CLARITY

    DPM

    INSULATIONAS PER NZBC

    H1/AS1

    100m

    m M

    IN.

    Sto

    Pla

    ster

    50m

    mFl

    exyl

    STOTHERM 20mm VHCAVITY BATTENS

    STOTHERM PANEL

    The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.

    STOTHERMSYSTEM

    STOTHERM INSULATED FACADE SYSTEM

    FOUNDATION SLAB-ON-GROUND

    ST 200

    2017

  • SCALE 1:5

    5mm MIN GAP

    STO uPVC VENTED BASE CAP

    6mm OVERHANGRECOMMENDED TO AVOIDVARIANCES IN FOUNDATION

    TIMBER FRAMINGTO NZS 3604

    DPC

    225m

    m M

    IN.

    TO U

    NP

    AV

    ED

    GR

    OU

    ND

    LE

    VE

    L

    150m

    m M

    IN.

    TO P

    AV

    ED

    GL

    WALL UNDERLAY

    STOTHERM 20mm VH CAVITYBATTENS

    STOTHERM RENDER SYSTEM

    STOTHERM PANEL FIXING

    CAVITY SPACERS TO SUIT FIXINGS

    AS PER NZS 3604

    5

    STOTHERM PANEL

    STO FLEXYL WATERPROOFINGTO REBATE

    INSULATED FOUNDATION WITHSTOTHERM RENDER SYSTEM ONSTOFLEXYL WATERPROOFING

    CONCRETE SLAB/REINFORCINGAS PER NZS 3604 OR ENGINEERSPECIFIC DESIGN - NOT SHOWN

    FOR CLARITY

    DPM

    INSULATION ASPER NZBC -

    Clause H1

    100m

    m M

    IN.

    Sto

    Ren

    der

    50m

    mC

    lad.

    The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.

    STOTHERMSYSTEM

    STOTHERM INSULATED FACADE SYSTEM

    INSULATED SLAB-ON-GROUND

    ST 201

    2017

  • SCALE 1:5

    TIMBER FRAMINGTO NZS 3604

    DPC

    STO RENDER SYSTEM

    INTERNAL LINING

    DPM

    AS PER NZS 3604

    75mmrebate

    BUILDING UNDERLAY

    20mm DRAINED CAVITY

    STOTHERM PANEL

    STO FLEXYL OR LIQUID DPM ONREBATE

    STO uPVC CONTROL JOINT ORFINISHING EDGE AT JUNCTIONTO FOUNDATION

    WEATHER PROTECTED VENTSTO ACHIEVE MIN. VENTILATIONOF 1000mm²/LINEAL METERPOSITIONED HARD ON REBATE1

    0

    INSULATION TO EXTERIORWALLS

    CONCRETE SLAB/REINFORCINGAS PER NZS 3604 OR ENGINEERSPECIFIC DESIGN - NOT SHOWN

    FOR CLARITY

    STOTHERM PANELFIXING

    INSULATION ASNZBC H1/AS1

    100m

    m M

    IN.

    Sto

    Ren

    der

    50m

    mfle

    xyl

    50m

    mC

    lad.

    100m

    mto

    pav

    ing

    STOTHERM RENDERSYSTEM

    STO uPVC END CAP

    The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.

    STOTHERMSYSTEM

    STOTHERM INSULATED FACADE SYSTEM

    REBATED SLAB-ON-GROUND - RENDERED FINISH

    ST 202

    2017

  • SCALE 1:5

    50m

    mcl

    addi

    ng15

    0mm

    to p

    avin

    g

    225m

    m u

    npav

    ed G

    L

    DPC

    GL

    WALL UNDERLAY

    STOTHERM PANELFIXING

    STOTHERM PANEL

    STO uPVC VENTEDBASE CAP

    STOTHERM 20mm VHCAVITY BATTENSSTOTHERM RENDERSYSTEM

    CAVITY SPACERS TOSUIT FIXINGS

    RIBRAFT POLYSTYRENE PODINSTALLATION IN ACCORDANCE TO FIRTHRIBRAFT CONSTRUCTION DETAILS

    8522

    0

    CONCRETE SLAB/REINFORCINGAS PER NZS 3604, SPECIFIC

    DESIGN OR ENGINEER (SED)Reinforcing not shown for clarity

    300

    The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.

    STOTHERMSYSTEM

    STOTHERM INSULATED FACADE SYSTEM

    RIBRAFT FLOOR SYSTEM / EDGE DETAIL

    ST 203

    2017

  • 225m

    m u

    npav

    ed G

    L

    SCALE 1:5

    CONCRETE FOOTING ASPER NZS 3604 OR ENGINEER

    SPECIFIC DESIGN

    CONCRETE SLAB/REINFORCINGAS PER NZS 3604 OR ENGINEER

    SPECIFIC DESIGN

    DPC

    NOTE:SHELL OF BLOCK CAN SUPPORT

    BOTTOM PLATE WHEN SLAB ISTIED TO FOUNDATION

    50m

    mcl

    addi

    ng15

    0mm

    to p

    aved

    GLINSULATION AS PERNZBC - Clause H1

    DPM

    STO uPVC VENTEDBASE CAP

    WALL UNDERLAY

    STOTHERM 20mm VHCAVITY BATTENS

    STOTHERM RENDERSYSTEM

    STOTHERM PANELFIXING

    STOTHERM PANEL

    CAVITY SPACERS TOSUIT FIXINGS

    The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.

    STOTHERMSYSTEM

    STOTHERM INSULATED FACADE SYSTEM

    CONC.BLOCK FOUNDATION EDGE DETAIL

    ST 204

    2017

  • SCALE 1:5

    CONCRETE FOOTING ASPER NZS 3604 OR ENGINEER

    SPECIFIC DESIGN

    DPM REQUIRED ONFOUNDATION FOR POORLYDRAINED SITES OTHERWISETERMINATE AT BOTTOMEXTERNAL CORNER OFFOUNDATION

    CONCRETE SLAB/REINFORCINGAS PER NZS 3604 OR ENGINEER

    SPECIFIC DESIGN

    DPC

    NOTE:INSTALL STOFLEXYL UNDER DPM AT TRANSITION IF REQUIRED FOR POORLYDRAINED SITES.

    STO uPVC VENTED BASECAP - 5mm MIN.GAP

    WALL UNDERLAY

    STOTHERM 20mm VHCAVITY BATTENS

    STOTHERM RENDERSYSTEM

    STOTHERM PANELFIXING

    STOTHERM PANEL

    CAVITY SPACERS TOSUIT FIXINGS

    DPM

    INSULATION AS PERNZBC - Clause H1

    STOFLEXYL WATERPROOFINGTO REBATE, CONTINUE TO50mm PAST STO RENDERTERMINATION POINT

    100m

    mS

    to R

    ende

    r50

    mm

    Flex

    yl50

    mm

    clad

    ding

    150m

    mTO

    PA

    VE

    D G

    L22

    5mm

    TO U

    NP

    AV

    ED

    GR

    OU

    ND

    LE

    VE

    L

    The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.

    STOTHERMSYSTEM

    STOTHERM INSULATED FACADE SYSTEM

    EPS BLOCK FOUNDATION DETAIL

    ST 205

    2017

  • SCALE 1:5

    50m

    mcl

    addi

    ng15

    0mm

    to p

    aved

    225m

    m u

    npav

    ed G

    L

    INSULATION AS PERNZBC - Clause H1

    DPM

    DPC10mm INSULATION

    IF REQUIRED

    GL

    CONCRETE SLAB/REINFORCINGAS PER NZS 3604 OR SPECIFIC

    ENGINEER DESIGN (SED)

    Var

    ies

    refe

    r to

    NZS

    3604

    or S

    ED

    WALL UNDERLAY

    STOTHERM PANEL FIXING

    STOTHERM PANEL

    STO uPVC VENTEDBASE CAP

    STOTHERM 20mm VHCAVITY BATTENSSTOTHERM RENDERSYSTEM

    CAVITY SPACERS TOSUIT FIXINGS

    The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.

    STOTHERMSYSTEM

    STOTHERM INSULATED FACADE SYSTEM

    SOLID CONC.FOUNDATION EDGE DETAIL

    ST 206

    2017

  • SCALE 1:5

    TIMBER FRAMING/STUCTURETO NZS 3604

    DPCSTO uPVC VENTEDADJUSTABLE FOOT TRAY

    SELECTEDFLOORING

    50

    NOTE:1. CONTINUOUS PERIMETER FOUNDATION

    WALL WITH VENTILATION OPENINGS2. CLEARANCE BETWEEN CLADDING AND

    ADJACENT GROUND - REFER NZS3604SED - Specific Engineer Design

    100mm DRAPE TO DBL SIDEDPERFORATED FOIL INSUL.R = 0.9

    - REFER NZBC - Clause H1

    as p

    er N

    ZS36

    04or

    SE

    D

    as p

    er N

    ZS36

    04or

    SE

    D

    CGL

    FGL

    as per NZS3604

    MA

    X.H

    EIG

    HT

    - NZS

    3604

    6.1

    1.2

    MIN

    .HE

    IGH

    T 6.

    11.2

    WALL UNDERLAY

    STOTHERM 20mm VH CAVITYBATTENS

    STOTHERM RENDER SYSTEM

    STOTHERM PANELFIXING

    STOTHERM PANEL

    The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.

    STOTHERMSYSTEM

    STOTHERM INSULATED FACADE SYSTEM

    CONC.CONTINOUS PERIMETER FOUND.WALL

    ST 207

    2017

  • DPC

    WALL UNDERLAY

    STOTHERM PANEL FIXING

    STOTHERM PANEL

    STO uPVC VENTED BASE CAP

    20mm DRAINED CAVITY

    STOTHERM RENDERSYSTEM

    CAVITY SPACERS TO SUITFIXINGS

    1. CONCRETE SLAB/REINFORCING AS PER NZS 3604, SPECIFIC DESIGN ORENGINEER (SED)

    Reinforcing not shown for clarity2. WHERE INSULATION OS BELOW GROUND, APPLY TWO (2) COATS OF

    STOFLEXYL TO MAXRAFT INSULATION BEFORE COMMENCING3. 150mm MIN. CLEARANCE FROM SLAB LEVEL TO EXTERIOR PAVING,

    225mm MIN. CLEARANCE FROM SLAB LEVEL TO UNPAVED GROUND TOE2/AS1

    4. AS REQUIRED, SECURE THE DPM TO THE MAXRAFT EDGE INSULATIONUSING AN EIFS FLASHING TAPE 50mm ON MAXRAFT AND 100MM ONTOUNDERSLAB DPM

    SOLID COMPACTION 800mmMIN.PAST EDGE OFFOUNDATION

    100

    100

    50

    250 50

    10450

    STOMULTI SCREED MESHEDBASECOAT FINISHED IN1.0mm FLOAT or STOLIT KFINISHING RENDER,PAINTED IN STOCOLORMAXICRYL

    SCALE 1:10

    DPM REFER NOTE 4

    The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.

    STOTHERMSYSTEM

    STOTHERM INSULATED FACADE SYSTEM

    MAXRAFT FLOOR SYSTEM / EDGE DETAIL

    ST 208

    2017

  • MIN. H1.2 TREATEDFLOOR JOISTS

    2020

    50

    100mm DRAPE TODOUBLE-SIDED PERFORATED

    FOIL INSULATION R = 0.9 -REFER NZBC - Clause H1

    2/NAIL LAMINATED FLOOR JOISTSUNDER LOAD BEARING WALLS

    STO uPVC VENTEDADJUSTABLE FOOT TRAY

    WALL UNDERLAY

    STOTHERM 20mm VH CAVITYBATTENS

    STOPOREN RENDER SYSTEM

    STOTHERM PANELFIXING

    STOTHERM PANEL

    H4 TREATED BASEBOARDSWITH 20mm CONTINUOUS SUBFLOOR VENTILATION GAPBETWEEN

    H3.2 TREATED BEARER, H5TREATED PILE - REFER NZS 3604

    FOR TIMBER & PILE SETOUT

    STOTHERM PANELFIXING

    NOTE:FOR CLEARANCE BETWEENCLADDING AND ADJACENT GROUND- REFER NZS3604

    SCALE 1:5

    STOTHERM RENDERSYSTEM

    The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.

    STOTHERMSYSTEM

    STOTHERM INSULATED FACADE SYSTEM

    TIMBER PILE/SUBFLOOR VENTILATION (Parallel Wall)

    ST 209

    2017

  • 50

    100mm DRAPE TODOUBLE-SIDED PERFORATED

    FOIL INSULATION R = 0.9 -REFER NZBC - Clause H1

    MIN. H1.2 TREATEDFLOOR JOISTSTRIMMER JOIST

    2020

    H4 TREATED BASEBOARDSWITH 20mm CONTINUOUS SUBFLOOR VENTILATION GAPBETWEEN

    SELECTED FLOORING

    TIMBER FRAMINGTO NZS 3604

    WALL UNDERLAY

    STOTHERM 20mm VH CAVITYBATTENS

    STOTHERM RENDER SYSTEM

    STOTHERM PANELFIXING

    STOTHERM PANEL

    STO uPVC VENTEDADJUSTABLE FOOT TRAY

    H5 TREATED PILE - REFERNZS 3604 FOR TIMBER & PILE

    SET OUT

    SCALE 1:5

    STOTHERM PANELFIXING

    NOTE:FOR CLEARANCE BETWEENCLADDING AND ADJACENTGROUND - REFER NZS3604

    The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.

    STOTHERMSYSTEM

    STOTHERM INSULATED FACADE SYSTEM

    TIMBER PILE/SUBFLOOR VENTILATION (Right Angled Wall)

    ST 210

    2017

  • SCALE 1:5

    OVERHANG TRIMMER JOISTTO ALLOW CLADDING TO LAPSUBFLOOR CLADDING

    100mm DRAPE TODOUBLE-SIDED PERFORATED

    FOIL INSULATION R = 0.9 -REFER NZBC - Clause H1

    JACK FRAMING IN AS PERNZS3604 6.10.2

    DPC

    WALL UNDERLAY

    STOTHERM 20mm VH CAVITYBATTENS

    STOTHERM RENDER SYSTEM

    STOTHERM PANEL

    STO uPVC VENTEDADJUSTABLE FOOT TRAY

    PROVIDE SHEET BRACINGMATERIAL and VENTILATION AS PERNZS 3604

    STOTHERM PANELFIXING

    STOTHERM PANELFIXING

    NOTE:FOR CLEARANCE BETWEENCLADDING AND ADJACENTGROUND - REFER NZS3604

    The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.

    STOTHERMSYSTEM

    STOTHERM INSULATED FACADE SYSTEM

    TIMBER SUBFLOOR WITH JACK STUDS

    ST 211

    2017

  • SCALE 1:10

    STO FLEXYL MESHED WATERPROOFINGFROM 150mm ABOVE GROUND ANDDOWN OVER COMPRESSION BAR

    SLAB-ON-GROUND FLOOR & CONC.MASONRY WALLS AS PER NZS4210/4229/4230 & AND ENGINEERS DRAWINGS

    ALLOW ADEQUATE TIME FOR BLOCK TO DRY/STABALISE BEFOREPLASTERING NORMALLY FROM 4-8 WEEKS IN AVERAGE DRYINGCONDITIONS.

    STOARMAT RENDER SYSTEM

    TIMBER FRAMINGTO NZS 3604

    50m

    mDPC

    SELECTEDINTERIOR LINING

    CONCRETE FLOOR SLAB,FOOTING & WALL TO SPECIFIC

    DESIGN

    SELECTED INTERIORRENDER/FINISH

    FILTER FABRIC

    SLOTTED DRAIN LAIDTO A FALL

    WALL UNDERLAY

    NOMINAL 20x45mm H3.1 TIMBERCAVITY BATTENSSTOTHERM PANEL FIXING

    STOTHERM PANELSTOTHERM RENDER SYSTEM

    STO uPVC VENTEDADJUSTABLE FOOT TRAY

    NOTE:FOR CLEARANCE BETWEENCLADDING AND ADJACENTGROUND - REFER NZS3604:2011

    TANKING SEALANT

    COMPRESSION BAR MECHANICALLYFIXED TO CONC.BLOCK. TRANSITIONAPPROX 100mm BELOW GROUND

    GRANDULAR FILL RECOMMENDED

    SELECTED BITUMOUS PEEL &STICK TANKING MEMBRANE WITHPROTECTION MATERIAL

    INSULATE BLOCKWORK IFNEEDED

    The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.

    STOTHERMSYSTEM

    STOTHERM INSULATED FACADE SYSTEM

    MASONRY CONC.BLOCK IN-GROUND WALL

    ST 212

    2017

  • SCALE 1:2

    STOFLEXYL WATERPROOFING TOCONCRETE REBATE SURFACES ANDRENDER INTO REBATE

    STOARMAT RENDER SYSTEM

    TIMBER FRAMINGTO NZS 3604

    DPC

    NOTE:CUT SLOPE AT 15° OR CUTREBATE AND PLASTER 15°SLOPE IN.

    WALL UNDERLAY

    STOTHERM 20mm VH CAVITYBATTENS

    STOTHERM RENDER SYSTEM

    STOTHERM PANEL FIXING

    STOTHERM PANEL

    STO uPVC VENTED BASECAP

    50m

    m

    REINFORCED CONCRETE BLOCKWALLS IN ACCORDANCE WITH NZS4230, 4229, 4218 & 4210

    The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.

    STOTHERMSYSTEM

    STOTHERM INSULATED FACADE SYSTEM

    CONCRETE BLOCK INTER-STOREY DRAINED JUNCTION

    ST 213

    2017

  • NOTE: USE FULL PANELS WHERE POSSIBLE.ALL PANEL CUTS SHALL BE CAREFULLY MADE TO ACHIEVE A TIGHT BUTT FIT.ALL PANEL JOINTS MUST BE FLUSH FILLED WITH STO FOAM TAKING CARE NOT TO FILL THE CAVITY.MECHANICALLY FIX ALL PANELS WITH STOTHERM FIXINGS AT MAXIMUM 300mm CENTRES.PANELS TO BE SUPPORTED BY MINIMUM TWO STUDS OR BLOCKING.VERTICAL CONTROL JOINTS ARE REQUIRED ON WALLS OVER 20 METRES LONG, SEE STO DETAILS.HORIZONTAL CONTROL JOINTS AT INTERSTOREY JUNCTION IF UNSEASONED JOISTS USED. HORIZONTAL DRAINED JUNCTION REQUIRED AT THIRD STOREY OR 7 METERS INCLUDING GABLES.

    N.T.S

    600

    Panel thicknessPanel thickness

    STAGGERCORNERS

    TO SPANMINIMUM OFTWO STUDS

    FILL IN JOINERY SILLAND HEAD PANELSAFTER JAMB PANELSFITTED

    AVOID NARROWPANEL WIDTHS

    GENERALLY BUTT JOINPANELS ON STUDS

    Equal 1200Equal

    2700

    H GRADE EPS SHEETS NORMALLY - 2700 x 1200mm

    NOTE: USE FULL SHEETS WHERE POSSIBLEALL SHEET EDGES MUST BE SUPPORTED BY A FRAMING MEMBERALL SHEETS CUTS SHALL BE MADE CAREFULLY TO ACHIEVE A TIGHT BUTT FIT.

    ANY GAPS IN THE EPS SHEET MUST BE FILLED WITH STO FOAM ON HORIZONTAL JOINTS CARE MUST BE TAKEN TO AVOID FOAM FILLING THE CAVITY

    The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.

    STOTHERMSYSTEM

    STOTHERM INSULATED FACADE SYSTEM

    STOTHERM PANEL LAYOUT

    ST 300

    2017

  • SCALE: 1:2

    TIMBER FRAMING TO NZS3604 REQUIREMENTS

    WALL UNDERLAY/RAB ASSPECIFIED - ENSUREUNDERLAY RUNSCONTINUOUS OVER JOINT

    STOTHERM PANEL

    STOTHERM 20mm VHCAVITY BATTENS

    STOTHERM RENDERSYSTEM

    STOTHERM PANEL FIXING

    FLUSH FILL WITH ADHESIVEFOAM TAKING CARE NOT TOFILL CAVITY

    The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.

    STOTHERMSYSTEM

    STOTHERM INSULATED FACADE SYSTEM

    STOTHERM PANEL FIXING VERTICAL

    ST 301

    2017

  • SCALE: 1:2

    TIMBER FRAMING TO NZS3604 REQUIREMENTS

    WALL UNDERLAY/RAB ASSPECIFIED

    STOTHERM PANEL

    STOTHERM RENDERSYSTEM

    STOTHERM PANEL FIXING

    FLUSH FILL WITH ADHESIVEFOAM TAKING CARE NOT TOFILL CAVITY

    BLOCKING/DWANGS

    The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.

    STOTHERMSYSTEM

    STOTHERM INSULATED FACADE SYSTEM

    STOTHERM PANEL FIXING HORIZONTAL

    ST 302

    2017

  • SCALE 1:2

    TIMBER FRAMINGTO NZS 3604

    WALL UNDERLAY/RABCONTINUOUS AROUNDCORNERS

    STO PREMESHEDCORNER ANGLE

    STOTHERM 20mm VHCAVITY BATTENS

    STOTHERM RENDERSYSTEM

    STOTHERM PANELFIXING

    STOTHERM PANEL

    FLUSH FILL WITHADHESIVE FOAMTAKING CARE NOT TOFILL CAVITY

    The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.

    STOTHERMSYSTEM

    STOTHERM INSULATED FACADE SYSTEM

    EXTERNAL CORNER

    ST 303

    2017

  • SCALE: 1:2

    WALL UNDERLAY/RAB CONTINUOUSAROUND CORNERS

    INTERNAL CORNERS AREDOUBLE LAPPED MESHED

    STOTHERM 20mm VHCAVITY BATTENS

    STOTHERM RENDERSYSTEM

    STOTHERM PANELFIXING

    STOTHERM PANEL

    FLUSH FILL WITH ADHESIVEFOAM TAKING CARE NOT TOFILL CAVITY

    The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.

    STO THERMSYSTEM

    STOTHERM INSULATED FACADE SYSTEM

    INTERNAL CORNER

    ST 304

    2017

  • SCALE: 1:2

    TIMBER FRAMINGTO NZS 3604

    WALL UNDERLAY/RABCONTINUOUS

    10mm GAP IN PANEL

    NOTE:ENSURE STOTHERM PANELS ARE SUPPORTED BY A MIN. OF 2/STUDS. VERTICALCONTROL JOINTS ARE REQUIRED AT 20 LINEAL METRES MAX. OR AT ENGINEEREDFRAMING EXPANSION JOINTS and at DISSIMILAR MATERIAL JUNCTIONS. SET STOCONTROL JOINT AND REMOVE TAB CAREFULLY AS SOON AS THE JOINT IS SET TOAVOID CRACKS

    IN MESHCOAT, INSTALL STO uPVCCONTROL JOINT WITH MS SEALANT

    STOTHERM 20mm VHCAVITY BATTENS

    STOTHERM RENDERSYSTEM

    STOTHERM PANELFIXING

    STOTHERM PANEL

    The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.

    STOTHERMSYSTEM

    STOTHERM INSULATED FACADE SYSTEM

    VERTICAL CONTROL JOINT

    ST 305

    2017

  • SCALE: 1:2

    DRY or SEASONED TIMBERFRAMING TO NZS 3604 OR

    PROPRIETARY FLOORJOISTS

    STOTHERM 20mm VHCAVITY BATTENS

    STOTHERM RENDERSYSTEM

    WALL UNDERLAY/RAB -ENSURE UNDERLAY RUNSCONTINUOUS OVER JOINT

    STOTHERM PANEL

    STOTHERM 20mm VHCAVITY BATTENS

    STOTHERM RENDERSYSTEM

    NOTE: INTERSTOREY CONTROL JOINT NOT REQUIRED ON SEASONED TIMBER OR PROPRIETARY FLOOR JOISTS, CONTINUOUS CAVITY CONSTRUCTION IS LIMITEDTO TWO STORIES OR 7 METRES BEFORE A DRAINED CAVITY JUNCTION IS REQUIRED

    NOTE: SEASONED (dry) TIMBER OR PROPRIETARY FLOOR JOIST DETAIL

    STOTHERM PANEL FIXING

    STOTHERM PANEL FIXING

    The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.

    STOTHERMSYSTEM

    STOTHERM INSULATED FACADE SYSTEM

    HORIZONTAL INTER-STOREY (on dry or proprietary joists)

    ST 306

    2017

  • SCALE: 1:2

    A

    A: INTERSTOREYPANEL JOINT CENTRED

    1/3 WAY DOWN FROMTOP OF THE JOIST.

    IN MESH COAT INSTALL STOuPVC 12mm CONTROL JOINTWITH MS SEALANT

    15

    10m

    m G

    AP

    STOTHERM PANEL

    STOTHERM 20mm VH CAVITYBATTENS

    15mm GAP BETWEENCAVITY BATTENS

    STOTHERM RENDERSYSTEM

    WALL UNDERLAY/RAB - ENSUREUNDERLAY RUNS CONTINUOUSOVER JOINT

    STOTHERM PANEL

    STOTHERM 20mm VH CAVITYBATTENS

    STOTHERM RENDER SYSTEM

    NOTE: INTERSTOREY CONTROL JOINT NOT REQUIRED ON SEASONED TIMBER OR PROPRIETARY FLOOR JOISTS. CAVITY CONSTRUCTION LIMITED TO TWO STORIES OR 7 METERS, BEFORE A DRAINED INTERSTOREY JUNCTION IS REQUIRED

    NOTE: UNSEASONED TIMBER FLOOR JOIST DETAIL.

    STOTHERM PANEL FIXING

    STOTHERM PANEL FIXING

    UNSEASONED TIMBERFLOOR FRAMING TO NZS

    3604

    The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.

    STOTHERMSYSTEM

    STOTHERM INSULATED FACADE SYSTEM

    HORIZONTAL INTER-STOREY CONTROL JOINT

    ST 307

    2017

  • STO THERM 20mm VH CAVITYBATTEN

    FLASHING TAPE OVER

    STO uPVC VENTEDBASE CAP

    ALLOW TO RENDER BEHINDTHEN SEAL WITH MS SEALANTor STO SEAL TAPE

    1. AS REQUIRED TO LIMITCONTINUOUS CAVITYCONSTRUCTION TO TWOSTOREYS OR MAX. 7METERS. FLASHING BACKAND FRONT COVER TO BEA MINIMUM 35mmEXCLUDING DRIP EDGES.

    2. IN EXTRA HIGH WIND ZONEINCREASE FLASHINGCOVER TO 60mm MIN. ANDUSE A RIGID AIR BARRIER.

    SCALE: 1:2

    MIN

    .CO

    VE

    R T

    O B

    OTT

    OM

    OF

    CLA

    DD

    ING

    MIN

    .CO

    VE

    R35

    mm

    STOTHERM RENDER SYSTEM

    STOTHERM PANEL

    WALL UNDERLAY/RAB - ENSUREUNDERLAY RUNS CONTINUOUSOVER JOINT

    WALL UNDERLAY/RAB - ENSUREUNDERLAY RUNS CONTINUOUSOVER JOINT

    5

    35m

    m

    STOTHERM FIXING

    STOTHERM PANEL FIXING

    DRY OR SEASONED TIMBER ORPROPRIETARY FLOOR JOISTS

    100mm HORIZONTAL CAVITYBATTEN SET TO A FALL OF 5O

    100mm HORIZONTAL CAVITYBATTEN SET TO A FALL OF 5O

    STO uPVC 6mm FINISHING EDGE

    STO uPVC END CAP

    STOTHERM RENDER SYSTEM

    IF NON-HEMMED FLASHINGUSED, INCREASE UPSTANDHEIGHT BY 25mm.

    The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.

    STOTHERMSYSTEM

    STOTHERM INSULATED FACADE SYSTEM

    DRAINED JUNCTION AT THIRD STOREY

    ST 308

    2017

  • SCALE 1:2

    MIN. 35mm HIGHBACK FLASHING

    6mm FIBRE CEMENT SOFFIT.STOARMAT RENDER FC SOFFIT& uPVC STO CLIP ON TRAYS

    STOTHERM 20mmVH CAVITY BATTEN

    WALL UNDERLAY

    FLASHING TAPEONTO WALLUNDERLAY

    5mm GAP 5mm GAP

    STO uPVC VENTEDBASE CAP

    STOTHERMRENDERSYSTEM

    STOTHERM PANEL

    STOTHERM PANELFIXING

    MIN. 35mm HIGH BACK FLASHING

    The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.

    STOTHERMSYSTEM

    STOTHERM INSULATED FACADE SYSTEM

    BOXED BEAM

    ST 309

    2017

  • STOTHERM PANEL

    1025

    POST ANCHOR BRACKET

    STOTHERM RENDERSYSTEM

    STOTHERM 20mm VHCAVITY BATTEN

    STOTHERMPANEL FIXING

    SCALE 1:5

    STO PREMESHED CORNER

    STOTHERM RENDER SYSTEM

    STOTHERM PANEL FIXING

    H3.2 TIMBER POST

    STOTHERM 20mm VHCAVITY BATTENS

    25mm HIGH CONCRETEPLINTH

    10mm GAP BETWEEN PANELAND CONCRETE - SLOPECONCRETE OUT

    STO uPVC VENTEDBASE CAP

    FLUSH FILL WITH ADHESIVEFOAM TAKING CARE NOT TOFILL CAVITY

    The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.

    STOTHERMSYSTEM

    STOTHERM INSULATED FACADE SYSTEM

    POST DETAIL

    ST 310

    2017

  • 100mm min.

    SCALE 1:5

    FLASHING TAPE

    STAR CUT

    CUT LINES TO SUITPIPE DIAMETER

    8/10mm SEALANT BEAD ON PEF RODBETWEEN PIPE AND RENDER

    PIPE OR OTHER PENETRATIONSLOPED DOWNWARDS MIN 5O

    NOTE: INSTALL FLASHING TAPE WITH 100mm CLEARANCE AROUND PIPE ONTO WALLUNDERLAY AND WRAP 25mm AROUND PIPE.

    WHERE MIN 75mm BLOCKING SUPPORTS THE WALL UNDERLAY AROUND THEPENETRATION THE FLASHING TAPE CAN BE OMITTED BUT A FACE FIXEDEXTERIOR FLANGE WITH SEALANT IS REQUIRED AS PER E2AS1 FIG.68

    TIMBERFRAMING TO

    NZS3604

    STOTHERM PANEL

    STOTHERM RENDER SYSTEM

    STOTHERM 20mm VH CAVITYBATTEN

    WALL UNDERLAY/RAB

    Bottom

    ADDITIONAL FLASHING TAPEWRAPPED OVER STAR CUT AROUNDPIPE

    The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.

    STOTHERMSYSTEM

    STOTHERM INSULATED FACADE SYSTEM

    PIPE PENETRATION DETAIL

    ST 350

    2017

  • SCALE 1:2

    50 x 3mm EPDM WASHER GASKETSREQUIRED AROUND FIXINGS AND PLATETO PROVIDE WATERTIGHTNESS

    TIMBER PACKER SLOPED AT 5°50mm min CLEARANCE FROM

    CAVITY BATTENS

    TIMBER BLOCKING BETWEENSTUDS AS REQUIRED

    ALL WIRING SHOULD BEENCLOSED IN CONDUIT

    STOTHERM PANELSTOTHERM RENDER SYSTEM

    STOTHERM 20mm VH CAVITYBATTEN

    WALL UNDERLAY/RAB

    ADHESIVE GLUE AROUNDPERIMETER OF STO QUADERBLOCKING TO STOTHERM PANEL

    SLOPE CONDUIT

    NOTE: STO QUADER BLOCK IS A HIGH DENSITY NON COMPRESIBLE EPS POLY BLOCKWITH 4x28mm PLYWOOD INSERTS. FACING FRAMING SIZE 645x145x60/FOUR SECTIONSPER BLOCK, USE A FIXING PLATE TO AVOID POINT LOADS

    The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.

    STOTHERMSYSTEM

    STOTHERM INSULATED FACADE SYSTEM

    LIGHT FITTING/FIXING DETAIL

    ST 351

    2017

  • SCALE 1:2

    PROVIDE TIMBERBLOCKING AT TAP

    FLASHING TAPE100mm ONTO UNDERLAY

    25mm ONTO TAP CONNECTION

    TAP FITTING ON EPDMRUBBER WASHER

    WALL UNDERLAY

    STOTHERM 20mm VHCAVITY BATTENS

    STOTHERM PLASTERSYSTEM

    STOTHERM PANEL

    ADHESIVE GLUE AROUNDPERIMETER OF STO QUADERBLOCKING TO STOTHERM PANEL

    STO QUADERBLOCK FIXING

    NOTE: STO QUADER BLOCK IS A HIGH DENSITY NON COMPRESIBLE EPS POLY BLOCKWITH 4x28mm PLYWOOD INSERTS. FACING FRAMING SIZE 645x145x60/FOUR SECTIONSPER BLOCK, USE A FIXING PLATE TO AVOID POINT LOADS

    MS SEALANTAROUND PIPE

    The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.

    STOTHERMSYSTEM

    STOTHERM INSULATED FACADE SYSTEM

    TAP FITTING/FIXING DETAIL

    ST 352

    2017

  • SCALE 1:2

    SELECTED HANDRAIL

    TIMBER PACKER AT FIXINGSPOINTS - SLOPED AT 5

    DEGREES min. 50mmCLEARANCE FROM CAVITY

    BATTENS

    50 x 3 mm EPDM WASHER GASKETSREQUIRED AROUND FIXINGSBETWEEN PLATE AND RENDER TOPROVIDE WATERTIGHTNESSTIMBER BLOCKING

    BETWEEN STUDS ASREQUIRED

    100mm MAX.NZBC D1 clause 1.5.2

    INSTALL HANDRAIL PLATESOVER STO RENDER SYSTEMUSING METAL BUSHES TO TAKELOAD IF REQUIRED

    WALL UNDERLAY

    STOTHERM 20mm VHCAVITY BATTENS

    STOTHERM RENDERSYSTEM

    STOTHERM PANEL

    NOTE: STO QUADER BLOCK IS A HIGH DENSITY NON COMPRESIBLE EPS POLY BLOCKWITH 4x28mm PLYWOOD INSERTS. FACING FRAMING SIZE 645x645x145x60/FOURSECTIONS PER BLOCK, USE A FIXING PLATE TO AVOID POINT LOADS

    ADHESIVE GLUE AROUNDPERIMETER OF STO QUADERBLOCKING TO STOTHERM PANEL

    STO QUADER BLOCK FIXING

    The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.

    STOTHERMSYSTEM

    STOTHERM INSULATED FACADE SYSTEM

    HANDRAIL BRACKET/FIXING DETAIL

    ST 353

    2017

  • STO JOINT SEAL TAPEOR PEF RODMS SEALANT

    POLY WEDGE OR BATTENFULL WIDTH OF METER BOX

    AT min. 10° SLOPE WITHFLASHING TAPE OVER.

    EXTEND WEDGE 100mmPAST SIDE OF METER BOX

    LEAVE min. 50mm GAP IN CAVITYBATTEN FOR DRAINAGE

    STO JOINT SEALTAPE OR PEF RODAPPLY 6mm BEAD OF MS SEALANTOVER STO JOINT SEAL TAPE TOTOP, SIDES AND BOTTOM

    STOTHERM 20mm VH CAVITYBATTENS TO BE 8mm FROM

    SIDES OF METERBOX

    STOTHERMPANEL

    SCALE 1:10

    FLEXIBLE FLASHING TAPE 50mmOUT OVER THE METERBOX

    PERIMETER ALL AROUND AND100mm ONTO UNDERLAY

    STOTHERM uPVC END CAP

    STOTHERM uPVC END CAP

    The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.

    STOTHERMSYSTEM

    STOTHERM INSULATED FACADE SYSTEM

    METERBOX - ISOMETRIC

    ST 354

    2017

  • SCALE 1:2

    WEDGE OR BATTEN SLOPEDAT 10° MIN.EXTENDING INTOCAVITY

    METERBOX

    88

    INTERNAL LINING

    TIMBER FRAMINGTO NZS3604

    INTERNAL LINING

    TIMBER FRAMINGTO NZS3604

    MS SEALANT OVER STO JOINT SEALTAPE TO PERIMETER OF METERBOX

    STOTHERM RENDERSYSTEM

    STOTHERM 20mm VH CAVITYBATTEN WITH 50mm GAP FROMHORIZONTAL SLOPED BATTENAT BOTTOM JUNCTION

    8mm AIRSEAL ONPEF ROD BY

    BUILDER

    8mm AIRSEAL ONPEF ROD BY

    BUILDER

    FLASHING TAPE OVER SLOPEDPOLY WEDGE OR BATTEN ONTOWALL UNDERLAY

    STO uPVC END CAP

    METERBOX FLASHING TAPED 50mmONTO BOX AND 100mm ONTO WALL

    UNDERLAY ALL ROUND

    STO 6mm PRE MESHEDFINISHING EDGE

    The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.

    STOTHERMSYSTEM

    STOTHERM INSULATED FACADE SYSTEM

    METERBOX - CROSS SECTION

    ST 355

    2017

  • SCALE 1:2

    uPVC OR OTHERDOWNPIPE -SIZE REFERNZBC E1 Table 5

    STOTHERM 20mm VH CAVITYBATTENS

    DOWNPIPE/CLIP -SADDLE @ 1.2MCTRS MAX.FIXEDINTO STO SPIRALFIXING

    MS SEALANT ALL AROUND

    CABLE/WIRING

    PVC CONDUIT SLEEVE INSTALLEDAT 5 DEGREES DOWNWARDSLOPE

    1. DOWNPIPE/CLIP - SADDLE DETAIL

    2. WIRING PENETRATION DETAILNOTE: ENSURE THE NUMBER OF PENETRATIONS THROUGH THESYSTEM IS KEPT TO A MINIMUM. THE WEATHER SEALING OF ALLWIRING, ETC AS SHOWN, IS THE RESPONSIBILITY OF THE APPLICABLETRADE

    STOTHERM RENDER SYSTEM

    STOTHERM 20mm VHCAVITY BATTENS

    TIMBER FRAMINGTO NZS3604

    STOTHERM PANEL

    STOTHERM RENDER SYSTEM

    STO SPIRAL FIXING

    The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.

    STOTHERMSYSTEM

    STOTHERM INSULATED FACADE SYSTEM

    DOWNPIPE SADDLE FIXING & WIRING DETAILS

    ST 356

    2017

  • SCALE 1:2

    EXTRACTION PIPE SLOPEDOWNWARDS AT MINIMUM 5°

    FAN

    CO

    VE

    R

    TIMBER BLOCKING ASREQUIRED

    NOTE:LEAVE 40mm DRAINAGE GAP IN SEALANT AT BOTTOM OF FAN COVER.INSTALL FLASHING TAPE 100mm AROUND PIPE ONTO WALL UNDERLAY AND WRAP25mm ROUND PIPE.FOR FLEXIBLE PIPES, TAPE PIPE TO FAN COVER, APPLY STO JOINT SEAL, TAPEAROUND TAPE BEFORE PLACING IN HOLE. ALWAYS FINISH RENDER BEFOREINSTALLING FAN COVER

    TIMBER FRAMING ASPER NZS 3604

    STOTHERM 20mm VHCAVITY BATTENS

    STOTHERM PANEL

    STOTHERM RENDER SYSTEM

    TIMBER BLOCKING ASREQUIRED

    FLEXIBLE FLASHINGTAPE

    MS SEALANT TO HEAD &SIDES

    MS SEALANT/PEF RODAT PIPE JUNCTION (STOSEAL TAPE ON FLEXIBLEPIPES)

    STO uPVC 6mmFINISHING EDGE

    STO uPVC END CAP

    LEAVE 40mm GAP INSEALANT FOR EXIT OFMOISTURE

    The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.

    STOTHERMSYSTEM

    STOTHERM INSULATED FACADE SYSTEM

    FAN VENT DETAIL

    ST 357

    2017

  • PREMESHEDARCHITECTURAL PROFILEOVER INTERSTOREY JOINTFIXED OVER MESH COAT

    STOTHERM RENDERSYSTEM

    SCALE 1:2

    A: INTERSTOREYPANEL JOINT

    CENTRED 1/3 WAYDOWN FROM TOP

    OF JOIST

    NOTE:1. VERTICAL CAVITY BATTENS AREINSTALLED WITH A 15mm GAP ATINTER-STOREY JOINT2. INSTALL STO uPVC 12mm CONTROLJOINT3. ONLY SUITABLE FOR 2 STOREY - REFERDRAWING SHEET ST 359 FOR THIRDSTOREY4. ENSURE THERE ARE NO FIXINGS INTOFLOOR JOIST

    A15

    WALL UNDERLAY - ENSUREUNDERLAY RUNSCONTINUOUS OVER JOINT

    STOTHERM PANEL

    min.10°FALL

    STOTHERMN RENDERSYSTEM

    5mm GAP

    STOTHERM 20mm VHCAVITY BATTEN

    10°

    DRY OR SEASONEDTIMBER OR

    PROPRIETARY FLOORJOISTS

    The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.

    STOTHERMSYSTEM

    STOTHERM INSULATED FACADE SYSTEM

    INTER-STOREY JUNCTION WITH POLY PROFILE

    ST 358

    2017

  • STOTHERM RENDERSYSTEM

    SCALE 1:2

    WALL UNDERLAY -ENSURE UNDERLAY RUNSCONTINUOUS OVER JOINT

    STOTHERM RENDERSYSTEM

    1. AS REQUIRED TO LIMITCONTINUOUS CAVITYCONSTRUCTION TO TWOSTOREYS or 7 METERS.FLASHING BACK ANDFRONT COVER TO BE AMINIMUM 35mmEXCLUDING DRIP EDGES

    2. IN EXTRA HIGH WINDZONES INCREASEFLASHING COVER TO60mm AND USE A RIGIDUNDERLAY

    35m

    m M

    IN.

    35m

    m M

    IN.

    CO

    VE

    R F

    RO

    MB

    OTT

    OM

    OF

    PA

    NE

    LC

    OV

    ER

    STOTHERM 20mm VHDRAINED CAVITYSTOTHERM PANEL

    INTER-STOREYFLASHING15°MIN.SLOPEAND 5mmMIN.GAP

    ADDITIONAL WALLUNDERLAY DRESSED

    OVER FLASHING5

    STO VENTEDBASE CAP

    ATTACH WITH EPSSUITABLE ADHESIVE -TOPSIDE ONLY

    STOTHERM RENDERMESHED BASECOATBEHIND PROFILE

    PREMESHEDARCHITECTURALPROFILE

    min.10°FALL

    10°

    DRY OR SEASONEDTIMBER OR PROPRIETARY

    FLOOR JOISTS

    The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.

    STOTHERMSYSTEM

    STOTHERM INSULATED FACADE SYSTEM

    JOINT AT THIRD STOREY WITH POLY PROFILE

    ST 359

    2017

  • 1. FLASHING TAPE SYSTEM TO BE INSTALLED AROUND JOINERYOPENINGS AS PER E2/AS1 DETAILS

    2. STO UPVC CAVITY VENTED HEAD FLASHING CAN BE USEDWHERE A RENDERED HEAD IS DETAILED - REFER DWG PP 401

    3. IN EXTRA HIGH WIND ZONES INCREASE FLASHING COVER TO60mm MIN.AND USE A RIGID UNDERLAY

    4. 10mm MINIMUM HEAD FLASHING OR PROPRIETARY STOP ENDSREQUIRED

    SCALE 1:2

    TIMBER LINTEL ASPER NZS 3604

    STOTHERM RENDERSYSTEM

    STOTHERM 20mm VHCAVITY BATTEN

    WALL UNDERLAY

    FLASHING TAPE ONTOWALL UNDERLAY

    STOTHERM PANEL

    ALUMINIUM WINDOWHEAD FLASHING WITH 15°SLOPE AND 10mm COVERAT WINDOW HEAD

    MIN. 5mm GAP REQUIRED

    SEALANT REQUIRED FORVERY HIGH AND EXTRAHIGH WIND ZONES

    35m

    m M

    IN.

    50m

    m

    ALUMINIUM WINDOWJOINERY

    INTERIOR LINING

    AIRSEAL ON PEFROD GAP

    7.5-8mm APPROX

    5

    STO uPVC VENTEDBASE CAP

    STOTHERM PANEL FIXING

    HEAD FLASHING WITH 10mmSTOPENDS POSITIONED10mm PAST WINDOW JAMBS

    STO STICK ON JAMBFLASHING. FINISH AT HEADFLASHING WITH PUNCHEDRENDER LEG CONTINUING30mm ABOVE

    10 s

    tope

    nd

    The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.

    STOTHERMSYSTEM

    STOTHERM INSULATED FACADE SYSTEM

    ALU.JOINERY - HEAD DETAIL - STICK ON JAMB

    ST 400

    2017

  • SCALE 1:2

    TIMBER LINTEL ASPER NZS 3604

    STOTHERM RENDERSYSTEM

    STOTHERM 20mm VHCAVITY BATTEN

    WALL UNDERLAY

    FLASHING TAPE ONTOWALL UNDERLAY

    STOTHERM PANEL

    ALUMINIUM WINDOWHEAD FLASHING WITH 15°SLOPE AND 10mm COVERAT WINDOW HEAD

    MIN. 5mm GAP REQUIRED

    SEALANT REQUIRED FORVERY HIGH AND EXTRAHIGH WIND ZONES

    35m

    m M

    IN.

    50m

    m

    ALUMINIUM WINDOWJOINERY

    INTERIOR LINING

    AIRSEAL ON PEFROD GAP

    7.5-8mm APPROX

    1. FLASHING TAPE SYSTEM TO BE INSTALLEDAROUND JOINERY OPENINGS AS PER E2/AS1DETAILS.

    2. THE ALUMINUM WINDOW HEAD FLASHING BUTTSINTO THE STO CAVITY JAMB TO PROVIDESTOPEND AFTER REMOVING THE JAMB TAB ANDFITTING TO JOINERY BEFORE FITTING WINDOWHEAD FLASHING TIGHT AND MS SEALANT THEJUNCTIONS - SEE DETAIL PP402

    3. IN EXTRA HIGH WIND ZONES INCREASE FLASHINGCOVER TO 60mm MIN. AND USE A RIGID UNDERLAY

    STO uPVC MESHEDDRIP EDGE

    STOTHERM PANELFIXING

    5

    STO uPVC VENTEDHEAD FLASHING

    STO CAVITY JAMBFLASHING 30mm ABOVEHEAD FLASHING FLASHINGTO FORM STOPENDS

    The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.

    STOTHERMSYSTEM

    STOTHERM INSULATED FACADE SYSTEM

    ALU.JOINERY - HEAD DETAIL - CAVITY JAMB

    ST 401

    2017

  • SCALE 1:2

    NOTE: OPENINGS OVER 600mm REQUIRE JOINERY SUPPORT BAR USE STO uPVC ADHESIVE SILL AND JAMB FLASHING WITH WANZ JOINERY SUPPORT BAR

    JOINERY SUPPORT MUST BE CUT 15mm SHORT OF JOINERY JAMBS TO ALLOW FOR STO uPVC FLASHINGS1. SEALANT IS APPLIED TO THE SILL AND JAMB FLASHINGS2. WINDOW HEADS ARE LEFT OPEN3. FLEXIBLE FLASHING TAPE SYSTEM TO BE INSTALLED AROUND JOINERY OPENINGS AS PER E2/AS1 DETAILS

    WARNING: SOME BRANDS OF ALUMINIUM JOINERY HAVE DRAINAGE VENTS IN THE BOTTOM EDGE OF THE SILL FLANGE. ENSURE DRAINAGE VENTS REMAIN CLEAR.

    JOINERY SUPPORT BARREQUIRE FOR OPENINGSOVER 600mm

    PROPRIETARY ALUM.WINDOW JOINERY

    MS SEALANT

    STOTHERM RENDERSYSTEM

    STOTHERM PANEL

    TIMBER FRAMINGTO NZS 3604

    AIRSEAL ON PEF ROD GAP7.5-8mm APPROX.

    WALL UNDERLAY RETURNEDINTO OPENINGS & FLASHINGTAPE CONTINUOUS ALONGSILL MIN 100mm UP JAMBS &50mm ONTO FACE OF WALLUNDERLAY

    STOTHERM PANEL FIXING

    STOTHERM 20mm VHCAVITY BATTEN

    STO uPVC ADHESIVE SILLAND JAMB FLASHING.ADHESIVE FIX TO PANELAT min.15° SLOPE

    STO PRE-MESHEDADJUSTABLE CORNER

    The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.

    STOTHERMSYSTEM

    STOTHERM INSULATED FACADE SYSTEM

    ALUMINIUM JOINERY - SILL DETAIL - STICK ON SILL

    ST 402

    2017

  • SCALE 1:2

    23 -

    25m

    m G

    AP

    10mm

    20m

    m C

    AV

    ITY

    BA

    TTE

    N+/

    - 3-5

    mm

    TO

    ALL

    OW

    FOR

    FLA

    SH

    ING

    TA

    PE

    SA

    T JO

    INE

    RY

    ALUMINIUM WINDOWJOINERY

    MS SEALANT TO JAMBS

    6

    FLASHING TAPE(100mm UP JAMBS)

    H1.2 PACKER TOSUPPORT JOINERY

    AIRSEAL ON PEF ROD GAP7.5-8mm APPROX.

    LINE OF HEAD FLASHINGBUTT INTO JAMBS TOFORM STOPENDS

    WALL UNDERLAY RETURNED INTORECESS WITH FLASHING TAPE

    SYSTEM. FLASHING TAPE RETURNEDmin 100mm UP JAMBS AS PER E2/AS1

    STOTHERM RENDER SYSTEM

    STOTHERM PANEL

    STOTHERM PANEL FIXING

    STOTHERM 20mm VHCAVITY BATTEN

    STO uPVC CAVITY JAMBAND SILL FLASHING

    STO PRE-MESHED ANGLE

    The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.

    STOTHERMSYSTEM

    STOTHERM INSULATED FACADE SYSTEM

    ALU.JOINERY - JAMB DETAIL - STO uPVC CAVITY JAMB

    ST 403

    2017

  • NOTE: INSTALL STOTHERM JOINERY FLASHINGS DURING STOTHERM PANEL CONSTRUCTION

    SCALE 1:2

    23 -

    25m

    m G

    AP

    10mm20

    mm

    CA

    VIT

    Y B

    ATT

    EN

    +/- 3

    -5m

    m T

    O A

    LLO

    WFO

    R F

    LAS

    HIN

    G T

    AP

    ES

    AT

    JOIN

    ER

    Y

    ALUMINIUMWINDOW JOINERY

    MS SEALANT TO JAMBS

    6

    FLASHING TAPE(100mm UP JAMBS)

    H1.2 PACKER TOSUPPORT JOINERY

    AIRSEAL ON PEF ROD GAP7.5-8mm APPROX.

    LINE OF HEAD FLASHING10mm OVER WITH STOPEND

    WALL UNDERLAY RETURNED INTORECESS WITH FLASHING TAPE

    SYSTEM. FLASHING TAPE RETURNEDmin 100mm UP JAMBS AS PER E2/AS1

    STOTHERM RENDER SYSTEM

    STOTHERM PANEL

    STOTHERM PANEL FIXING

    STOTHERM 20mm VHCAVITY BATTEN

    STO uPVC ADHESIVE SILL ANDJAMB FLASHING

    STO PRE-MESHEDANGLE

    The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.

    STOTHERMSYSTEM

    STOTHERM INSULATED FACADE SYSTEM

    ALU.JOINERY - JAMB DETAIL - STO uPVC STICK ON JAMB

    ST 404

    2017

  • MS SEALANT TO JAMBS

    SCALE 1:2

    TIMBER FRAMINGTO NZS 3604

    20

    FLASHING TAPE(100mm UP JAMBS)

    H1.2 PACKER TOSUPPORT JOINERY

    AIRSEAL ON PEF ROD GAP7.5-8mm APPROX.

    LINE OF HEAD FLASHINGOVER WITH STOPEND

    STO UPVC CAVITY JAMBAND SILL FLASHINGSTOTHERM PANEL FIXING

    STOTHERM 20mm VHCAVITY BATTEN

    STOTHERM PANEL

    STOTHERM RENDERSYSTEM

    The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.

    STOTHERMSYSTEM

    STOTHERM INSULATED FACADE SYSTEM

    INT.CNR ALU.WINDOW/DOOR JOINERY - JAMB DETAIL

    ST 405

    2017

  • SCALE 1:5

    SILL SUPPORT BAR

    LINE OF CLADDINGBEYONDALUMINIUM DOORJOINERY

    FLASHING TAPE TAPE OVER SILL ANDMIN. 100mm UP FRAME FINISH AT

    BOTTOM EDGE OF SILL SUPPORT BAR

    UNDER DOORTRIM BY BUILDER

    REFER TO E2/AS1 FIG. 17 A,B,C & D INCLUDING SECTION 9.1.10 .GROUND LEVELS 150mm MIN.FROM TOP OF FINISHED FLOOR COVERING TOPAVED GROUND

    100

    SELECTED FLOORFINISH

    FLASHING TAPE

    CONTINUOUSAIR SEAL

    The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.

    STOTHERMSYSTEM

    STOTHERM INSULATED FACADE SYSTEM

    ENTRY DOOR THRESHOLD DETAIL

    ST 406

    2017

  • SCALE 1:5

    LINE OF STOTHERM PANEL CLADDINGBEYOND - SHOWN DASHED

    SELECTED ALU.DOOR JOINERYINSTALLED TO MANUFACTURERSRECOMMENDATIONS

    REFER TO E2/AS1 FIG. 17 A,B,C & D INCLUDING SECTION 9.1.10MIN.THRESHOLD 100mm FROM FLOOR TO FINISHED DECK

    NOTE: ADJUST 35mm TO ALLOW FOR SELECTED TILES AS REQUIRED, UNDERDOOR TRIM BY BUILDER

    100

    35 m

    in to

    fini

    shed

    surfa

    ce

    SELECTED FLOORING WANZ SUPPORT BAR COMPLETE WITHVENTILATION/DRAINAGE HOLESINSTALLED TO MANUFACTURERSRECOMMENDATIONS

    SELECTED MEMBRANE FINISH OVER H3 "C"FACED PLYWOOD LAID TO 1:40MIN.FALL.GLUE & SCREW TO TIMBER JOISTS, ALLEDGES SUPPORTED ON TIMBER

    TIMBER STRUCTUREAS PER NZS3604

    20mm MIN.ANGLE FILLET

    TURN-UP FLASHINGTAPE 100mm MIN. AT

    TRIMMER STUDS

    MEMBRANE REINFORCING STRIP

    CONTINUOUSAIR SEAL

    The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on site.

    STOTHERMSYSTEM

    STOTHERM INSULATED FACADE SYSTEM

    ENTRY DOOR/DECK THRESHOLD DETAIL

    ST 407

    2017

  • SCALE 1:5

    WANZ SUPPORT BAR COMPLETE WITHVENTILATION/DRAINAGE HOLES,INSTALLED TO MANUFACTURERSRECOMENDATIONS

    SELECTED ALU. BIFOLD DOOR JOINERYINSTALLED TO MANUFACTURERSRECOMMENDATIONS

    FLASHING TAPE TAPE OVER SILL ANDMIN. 100mm UP FRAME FINISH AT

    BOTTOM EDGE OF SILL SUPPORT BAR

    100

    8

    REFER TO E2/AS1 FIG. 17 A,B,C & D INCLUDING SECTION 9.1.10 .150mm MIN. FROM TOP OF FFL COVERING TO PAVED GROUND

    LINE OF STOTHERM CLADDINGSYSTEM BEYOND

    The information contained on this page is based on our experience and research at the date of issue. The detail is for use by RegisteredArchitects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right toalter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insurethey have and use the current Sto details and specifications on