Installation, Operation and Maintenance Manual IOMM Starter Group: Chiller Part Number: 331375501 Effective: Sept. 2005 Supercedes: New Starters for Centrifugal Chillers Low Voltage, Solid State and Wye-Delta Medium/High Voltage, Solid State and Across-the-Line

Starters for Centrifugal Chillers - Daikin Applied · IOMM Starter 5 Interrupting capacity: The maximum fault current that a circuit breaker or fused disconnect can successfully interrupt

  • Upload
    others

  • View
    4

  • Download
    0

Embed Size (px)

Citation preview

  • Installation, Operation and Maintenance Manual IOMM Starter

    Group: Chiller

    Part Number: 331375501

    Effective: Sept. 2005

    Supercedes: New

    Starters for Centrifugal Chillers Low Voltage, Solid State and Wye-Delta Medium/High Voltage, Solid State and Across-the-Line

  • 2 IOMM Starter

    Table of Contents

    General....................................................................................................................3 Variable Frequency Drives ............................................................................................................4 Basic Electrical Terms...................................................................................................................4

    Installation..............................................................................................................5 Mounting Arrangements................................................................................................................5 Receiving and Setting....................................................................................................................6 Location and Mounting .................................................................................................................6

    Power Wiring .........................................................................................................8 Connection Sizes.........................................................................................................................10

    Control Wiring .....................................................................................................13 Low Voltage Starters...................................................................................................................14 Medium/high Voltage Starters .....................................................................................................15

    Startup ..................................................................................................................18 Low Voltage Solid State (LVSS) .................................................................................................18 Low Voltage Wye-Delta (LVYD .................................................................................................21 Medium/High Voltage, Solid State ..............................................................................................24

    Operation, Low Voltage Starters, 200 – 600 Volts.............................................27 Introduction.................................................................................................................................27 Viewing Data...............................................................................................................................27 Changing Parameters...................................................................................................................32 Fault Code Troubleshooting Chart ..............................................................................................40 General Troubleshooting Chart ...................................................................................................48

    Operation, Medium/High Voltage Starters, 2300V – 7.2KV............................52 Introduction.................................................................................................................................52 Viewing Data...............................................................................................................................52 Changing Parameters...................................................................................................................53 Quick Start ..................................................................................................................................55 Troubleshooting ..........................................................................................................................57 Fault/Log Codes ..........................................................................................................................59 LED Diagnostics .........................................................................................................................62

    Maintenance .........................................................................................................63 Index of Figures & Tables ...................................................................................65

    "McQuay" is a registered trademark of McQuay International ©2005 McQuay International

    "Illustrations and data cover McQuay International products at the time of publication and we reserve the right to make changes in design and construction at anytime without notice".

  • IOMM Starter 3

    General

    These starters are completely automatic and require no operator intervention (other than clearing and resetting faults) to perform their function of providing a controlled connection of the compressor motor to the power supply. The Wye-Delta and solid-state starters have many similar software characteristics and are discussed together in their operating section. However, some parameters and data are different. Where this occurs, separate tables and figures are provided. The low voltage (200-600 volts) starters are characterized by their control software, known as “D3 Control”. Certain electrical operating data for these low voltage starters is transmitted to the chiller and can be viewed on the operator touch screen if the “Full Metering Option” has been ordered. See page 27 for details. Medium and high voltage (2300-7200 volts) starters share common software known as “Micro II Control”, not to be confused with the McQuay MicroTech II™ chiller control system.

    Figure 1, Wye-Delta Starter

    LED Display

    Incoming Lugs

    Surge Capacitor

    Terminal Strip

    D3 Controller

    Control Transformer and Fuses

    Contactors

    Transition Resistors

  • 4 IOMM Starter

    Figure 2, Solid State Starter, Wall Mounted

    Variable Frequency Drives While known and specified for their ability to control compressor motor speed for efficiency enhancement, VFDs also perform starting and motor protection functions. They are only available for 3/60/460-480 service.

    VFDs are available only from McQuay and when purchased as part of the original chiller purchase. Installation and operation are covered in McQuay manual IOMM VFD.

    Basic Electrical Terms Locked rotor amps (LRA): The amount of current that a specific motor will draw at start-up, when full voltage is applied across the line. The LRA may be 6 to 8 times FLA, or possibly higher in some cases.

    Inrush current: The amount of current that a specific motor and starter combination will draw during start-up. Normal inrush current will be substantially less than LRA for all starter types, except for across-the-line starters.

    Full load amps (FLA): The maximum amps the motor is designed for.

    Rated load amps (RLA): Actual amperage that the motor draws for a specific application. Centrifugal compressor motors operate at a RLA significantly below their maximum full load amps. RLA is used to determine electrical component sizing such as wire size and disconnect switches.

    Starting torque: Minimum torque required to begin the motor’s rotation. Bypass contactor: Contactors that bypass auto-transformers, reactors, or SCRs, and allow full power to reach the motor directly.

    Terminal Strip

    Disconnect Switch

    Primary Control Circuit Fuses

    Control Transformer

    SCRs (Behind)

    D3 Controller

    Bypass Contactor

    LED Display

  • IOMM Starter 5

    Interrupting capacity: The maximum fault current that a circuit breaker or fused disconnect can successfully interrupt. As the rating increases, the construction becomes heavier duty. For disconnect switches with fuses, the rating is based on 0 to 600 volts. For circuit breakers, the voltage and amperage relationship is considered with interrupting capacity decreasing as voltage increases. Withstand rating: There is a period of time that the short circuit current passes to the shorted circuit before the protection device can open. This time can be as long as 0.020 seconds (one cycle). The withstand rating of a starter is the maximum short circuit current that it can pass safely without emitting sparks or debris. Phase amps: The current draw inside the delta connection of a wye-delta motor winding. It is equal to 0.577 x RLA of the motor for a specific load. Open transition: A reduced voltage starter characteristic occurring when the motor is temporarily disconnected from power at the time the starter changes from the starting mode to the final running mode. A second smaller inrush spike will occur. McQuay does not recommend use of this type of starter. Closed transition: A reduced voltage starter characteristic when the motor is NOT temporarily disconnected from the line during the transition from starting mode to operating mode. The electrical load is transferred to resistors during the transition phase and the second inrush spike is suppressed.

    Installation Mounting Arrangements Low voltage starters can be factory-mounted with power and control wiring factory-installed or they can be free-standing, requiring field mounting remote from the unit and field-wiring of power and control wiring. Because of dimension restrictions for shipping, some “factory-mounted” starters for large chillers are shipped separate from the unit. Mounting supports are on the unit and preassembled cable kits are provided. Mounting and wiring on site are the customer’s responsibility and can be subcontracted to McQuay Factory Service if desired. Medium voltage starters and some size low voltage starters on WSC 100 through 126 are only available for free-standing applications. Low voltage starters can be supplied in several different mounting arrangements depending on the chiller size and starter type. See Table 1 for available arrangements. • Factory-Mounted (optional): The starter is mounted on the chiller unit with the back of

    the starter against the motor terminal box and wired directly to the motor. This arrangement is only available on WSC/WDC 063, 079, or 087 units (cover photograph). On models WSC/WDC 048/050, the starter is factory-mounted on the front of the chiller unit and connected to the motor with conduit and cable.

    • Free-standing (standard): Floor-mounted, separate from the chiller unit, and field wired to the compressor motor. This is available on all units and is the only starter arrangement available for WDC/WCC 100 and 126 dual compressor units.

    • Brackets and cable (optional): Starters for WSC 100 and 126 single compressor units may be shipped separately from the chiller unit and furnished with mounting brackets and interconnecting cables for field mounting and connection by others. This option must be clearly specified when chillers are ordered since brackets are welded onto the evaporator during its construction.

  • 6 IOMM Starter

    Table 1, Starter/VFD Mounting Arrangements Size Factory- Mounted

    Free-Standing

    Brackets & Cables

    WSC/WDC 050 X X WSC/WDC 063 X X WSC/WDC 079 X X WSC/WDC 087 X X WSC 100 - 126 X X WDC 100 - 126 X WCC 100 - 126 X

    Receiving and Setting Since factory-mounted starters are mounted and wired at the factory, this section will only apply to free-standing units.

    The unit should be inspected immediately after receipt for possible damage.

    All McQuay centrifugal starters are shipped FOB factory and all claims for handling and shipping damage are the responsibility of the consignee.

    Extreme care must be used when rigging the starter to prevent damage. See the certified dimension drawings included in the job submittal for the center of gravity of the unit. Consult the local McQuay sales office for assistance if the drawings are not available.

    The starter can be lifted by fastening the rigging hooks to the four lifting eyes located on the top of the unit.

    Location and Mounting Clearance The starter must be mounted on a level concrete or steel base and must be located to provide adequate service. Local codes or the National Electric Code (NEC) can require more clearance in and around electrical components and must be checked.

    Mounting Make sure that the floor or structural support is adequate to support the full weight of the unit.

    Standard NEMA 1 and NEMA 12 starters must be installed indoors in an area that is not exposed to direct water spray. Do not install in areas where the ambient temperature falls below 32°F (0°C) or exceeds 104°F (40°C) enclosed, or 122°F (50°C) open unless this was noted at the time of order placement and special precautions were taken to protect against these abnormal temperatures.

    Heatsink temperatures can run as high as 158°F (70°C) during normal operation. Do not mount the starter in contact with any material that cannot accept this heat. The starter must be mounted with the heat sink fins oriented vertically in an area that will not experience excessive shock or vibration.

    Ventilation Requirements Provisions should be provided in the starter enclosure to ensure that the temperature inside the enclosure never rises above 122°F (50°C) or the starter could be damaged or the life of the starter could be reduced. As a general rule of thumb the following ventilation guidelines should be followed. These values are for starters with bypass. Bypassed starters generally do not require ventilation.

  • IOMM Starter 7

    Safety Precautions Electrical codes require that all equipment (starter, motor, operator station, etc.) be properly grounded. An incoming disconnect must be locked open before wiring or servicing the starter, motor, or other related equipment. The equipment must only be serviced by qualified personnel fully familiar with the equipment.

    The opening of the branch circuit protective device may be an indication that a fault current has been interrupted. To reduce the risk of electrical shock, current carrying parts and other components of the starter should be inspected and replaced if damaged.

    Equipment is at line voltage when AC power is connected. Pressing the Stop push-button on the chiller control panel does not remove AC mains potential. All phases must be disconnected before it is safe to work on machinery or touch motor terminals and control equipment parts.

    Power Factor Capacitors, Surge Capacitors and Lightning Arrestors These devices MUST NOT be used with solid state starters. The SCR’s in the starter will be damaged by the di/dt levels created.

    On wye-delta starters, they are connected between the starter and the motor.

  • 8 IOMM Starter

    Power Wiring

    Power wiring between the starter and the compressor motor terminals is field supplied and installed on units with remote-mounted, free-standing starters. See the field wiring diagram on page 16.

    Wiring, fuse and wire size must be in accordance with the National Electric Code (NEC). Standard NEMA motor starters require modification to meet McQuay specifications. Refer to McQuay Specification R35999901.

    CAUTION

    Important: Voltage unbalance not to exceed 2% with a resultant current unbalance of 6 to 10 times the voltage unbalance per NEMA MG-1, 1998

    Standard. This is an important restriction that must be adhered to.

    WARNING

    Qualified and licensed electricians must perform wiring. Shock hazard exists.

    Refer to Figure 5 on page 16 for power wiring connections.

    Power wiring to compressors must be in proper phase sequence. Motor rotation is set up for clockwise rotation facing the lead end with phase sequence of 1-2-3. Care must be taken that the proper phase sequence is carried through the starter to compressor. With the phase sequence of 1-2-3 and L1 connected to T1 and T6, L2 connected to T2 and T4, and L3 connected to T3 and T5, rotation is proper. See diagram in terminal box cover.

    The McQuay start-up technician will check the phase sequence. Note: Do not make final connections to motor terminals until wiring has been checked and approved by a McQuay technician.

    CAUTION

    Connections to terminals must be made with copper lugs and copper wire.

    Under no circumstances should a compressor be brought up to speed unless proper sequence and rotation have been established. Serious damage can result if the compressor starts in the wrong direction. Such damage is not covered by product warranty.

  • IOMM Starter 9

    Motor Terminal Insulation It is the installing contractor's responsibility to insulate the compressor motor terminals when the unit voltage is 600 volts or greater, or in high humidity locations that could cause condensation on the motor terminals that are at about 50°F (10°C). The required material is shipped in as a kit (775123601) placed in the motor terminal box on all medium and high voltage units. It can be ordered for high humidity applications.

    This is to be done after the McQuay start-up technician has checked for proper phase sequence and motor rotation.

    Following this verification by the McQuay technician, the contractor should apply the following items.

    Materials required for 600+volts or high humidity: 1. Loctite® brand safety solvent (12 oz. package available as McQuay part number

    350A263H72) 2. 3M™ Co. Scotchfil brand electrical insulation putty (available in a 60-inch roll as

    McQuay part number 350A263H81) 3. 3M Co. Scotchkote™ brand electrical coating (available in a 15 oz. can with brush as

    McQuay Part Number 350A263H16) 4. Vinyl plastic electrical tape The above items are also available at most electrical supply outlets.

    Application procedure: 1. Disconnect and lock out the power source to the compressor motor. 2. Using the safety solvent, clean the motor terminals, motor barrel adjacent to the

    terminals, lead lugs, and electrical cables within the terminal 4OX to remove all dirt, grime, moisture and oil.

    3. Wrap the terminal with Scotchfil putty, filling in all irregularities. The final result should be smooth and cylindrical.

    4. Doing one terminal at a time, brush the Scotchkote coating on the motor barrel to a distance of up to 1/2 in. around the terminal and on the wrapped terminal, the rubber insulation next to the terminal, and the lug and cable for approximately 10 in. Wrap additional Scotchfil insulation over the Scotchkote coating.

    5. Tape the entire wrapped length with electrical tape to form a protective jacket. 6. Finally, brush on one more coat of Scotchkote coating to provide an extra moisture

    barrier. General Wiring Practice Wire groups

    Signal wiring refers to wires connected to the control terminals that are low voltage, below 15V.

    • Shielded wire is required to prevent electrical noise interference from causing improper operation or nuisance trips.

    • Signal wire should be rated for at least 300V. • Keep signal wire as far away as possible from control and power wiring.

    Control wiring is wiring connected to the control terminal strip that carry 24V to 220V. • Use only UL or CSA recognized wire. • Use copper wire rated for 60/75°C. • Power wiring to the motor must have the maximum possible separation from all other

    wiring. Do not run control wiring in the same conduit; this separation reduces the possibility of coupling electrical noise between circuits. Minimum spacing between metallic conduits containing different wiring groups should be three inches (76 mm).

    • Minimum spacing between different wiring groups should be six inches (152 mm).

  • 10 IOMM Starter

    • Wire runs outside of an enclosure should be run in metallic conduit or have shielding/armor with equivalent attenuation.

    • Different wire groups should cross at 90 degrees whenever power and control wiring cross.

    • Different wire groups should be run in separate conduits. • Adhere to local electrical codes. • The National Electrical Code and Canadian Electrical Code requires that an approved

    circuit disconnecting device be installed in series with the incoming AC supply in a location readily accessible to personnel installing or servicing this equipment. If a disconnect switch is not supplied with the starter, one must be installed.

    • Supply and motor wiring will usually enter and leave the enclosure from the top. Wire connections can be determined to best suit specific installations. Wire runs should be properly braced to handle both starting and fault currents. Size power cable per local electrical codes. Long lengths of cable to the motor of over 150 feet must be de-rated.

    BEFORE APPLYING MAIN POWER The starter has been fully tested before leaving the factory to help a rapid and problem-free start-up. Before applying power to the starter, consult the start-up checklist below.

    1. Inspect starter and remove any foreign matter. 2. Inspect the starter for any shipping damage. 3. Ensure that all electrical connections are as per the system schematics supplied with

    the starter and/or connection diagrams. 4. Ensure that all connections are properly tightened. 5. Test L to T resistance of each phase and ensure that it is greater than 50 kohms.

    Reverse leads and test again. 6. Check that the gate to cathode resistance of each SCR is between 8 and 50 ohms. 7. Check the resistance of all power and motor leads to ground to ensure that there is no

    foreign matter present or damage to the insulation which can short one or more of the phases to ground.

    8. Apply 120 Vac control voltage to the starter.

    Connection Sizes Low Voltage Solid State

    Table 2, Solid State Connection Sizes, Power Block Starter

    Model No. (Note 1)

    Incoming Connection to Power Block

    Outgoing Connection Size

    (Note 2) RVSS14 2/C #6-300 0.5 RVSS17 2/C #6-300 0.5 RVSS20 2/C #6-300 0.5 RVSS27 2/C #6-300 0.5 RVSS34 2/C #6-300 0.5 RVSS41 2/C #6-300 0.5 RVSS47 2/C #6-350 0.5 RVSS57 4/C 1/0 - 750 0.5 RVSS67 4/C 1/0 - 750 0.5 RVSS82 4/C 1/0 - 750 0.5 RVSS96 4/C 1/0 - 750 0.5 RVSS2K 4/C 1/0 - 750 0.5 RVSS4K 4/C 1/0 - 750 0.5

    NOTES: 1. Data is the same for unit-mounted

    starters, RVST14, etc. 2. Outgoing are NEMA 1 hole pattern.3. Outgoing connections are factory-

    connected to the motor on factory-mounted starters.

    4. When connecting to a starter with the standard power block, the incoming connection size is determined by the starter size as listed in the above table.

  • IOMM Starter 11

    Table 3, Solid State, Connection Sizes, Disconnect & Circuit Breaker 50/60 HZ Max RLA

    Incoming Size Disc. Switch

    Incoming Size Circuit Breaker

    74 #6- 350 #6- 350 93 #6- 350 #6- 350

    148 #6- 350 #6- 350 163 #6- 350 #6- 350 185 2/C 3/0 - 500 2/C 3/0 - 500 296 2/C 3/0 - 500 2/C 3/0 - 500 444 3/C 1/0 - 500 3/C 1/0 - 500 593 4/C 250 - 500 4/C 250 - 500 889 5/C 300 - 600 5/C 300 - 600

    1185 5/C 300 - 600 5/C 300 - 600 1481 5/C 300 - 600 5/C 300 - 600

    NOTES:

    1. For field wiring free-standing starters, the outgoing connection size is determined by the starter size as listed under the “Outgoing Connection Size” column in Table 2. Outgoing connections are factory-connected to the motor on factory-mounted starters.

    2. When wiring to a starter (either factory-mounted or free-standing) with an optional disconnect switch or circuit breaker, the incoming connection size is determined by the device size as shown in the above table. For standard power block, the incoming connections are as shown in Table 2.

    Low Voltage Wye-Delta

    Table 4, Wye-Delta Connection Sizes, Standard Power Block Starter

    Model No (Note 1).

    Incoming Connection Size,

    Power Block

    Outgoing Connection Size

    (Note 2) D3WD11 2/C #6 - 300 0.31 D3WD12 2/C #6 - 300 0.31 D3WD14 2/C #6 - 300 0.31 D3WD15 2/C #6 - 300 0.31 D3WD25 2/C #6 - 300 0.31 D3WD31 2/C #6 - 300 0.38 D3WD34 2/C #6 - 300 0.38 D3WD43 2/C #6 - 300 0.44 D3WD62 2/C #6 - 350 0.44 D3WD65 2/C #6 - 350 0.44 D3WD86 4/C 1/0 - 750 0.63 D3WD1K 4/C 1/0 - 750 0.63 D3WD2K 4/C 1/0 - 750 0.63

    NOTES: 1. Data is the same for unit-mounted starters, D3WT11, etc. 2. Outgoing connection is NEMA 1 hole pattern, diameter in inches as shown. 3. Outgoing connections are factory-connected to the motor on factory-mounted starters. 4. When connecting to a power block, the connection size is determined by the starter size.

  • 12 IOMM Starter

    Table 5, Wye-Delta Connection Size, Disconnects & Circuit Breakers 50/60 HZ Max RLA

    Incoming Size Disc. Switch

    Incoming Size Circuit Breaker

    74 #6- 350 #6- 350 93 #6- 350 #6- 350

    148 #6- 350 #6- 350 163 #6- 350 #6- 350 185 2/C 3/0 - 500 2/C 3/0 - 500 296 2/C 3/0 - 500 2/C 3/0 - 500 444 3/C 1/0 - 500 3/C 1/0 - 500 593 4/C 250 - 500 4/C 250 - 500 889 5/C 300 - 600 5/C 300 - 600

    1185 5/C 300 - 600 5/C 300 - 600 1481 5/C 300 - 600 5/C 300 - 600

    NOTES: 1. For field wiring free-standing starters, the outgoing connection size is determined by

    the starter size as listed under the “Outgoing Connection Size” column in Table 2. Outgoing lugs are factory-connected to the motor on factory-mounted starters.

    2. When wiring to a starter (either factory-mounted or free-standing) with an optional disconnect switch or circuit breaker, the incoming lug size is determined by the device size as shown in the above table. For standard power block, the incoming connections are as shown in Table 2.

    Medium Voltage, Solid State, Across-the-Line Incoming and outgoing connections are crimp-type connectors, standard bus tabs are NEMA 2.

    Compressor Motor Connections Power wiring connections at the motor are “spark plug” type terminals with threaded copper bar, sized per the following table.

    Type/Size Comp. Size Terminal Size

    Low Voltage to 275 A, to 575 V CE 050 0.375-16 UNC-2A, 0.94 in. long

    Low Voltage to 750 A, to 575V CE 063-126 0.635-11 UNC-2A, 1.88 in. long

    Med. Voltage to 275 A, to 4160 V CE 063-126 0.375-16 UNC-2A, 0.97 in. long

    Hi Voltage to 275 A, to 7200 V CE 063-126 0.375-16 UNC-2A, 1.00 in. long

  • IOMM Starter 13

    Control Wiring

    Control wiring is required between the starter and the unit for three purposes:

    1. Transmit start and stop commands from the unit to the starter.

    2. Transmit electrical information concerning motor operation from the starter to the unit control system.

    3. Supply control power from the starter transformer to the unit control panels.

    General Practice Signal wiring refers to wires connected to the control terminals that are low voltage, below 15V.

    • Shielded wire is required to prevent electrical noise interference from causing improper operation or nuisance trips.

    • Signal wire should be rated for at least 300V. • Keep signal wire as far away as possible from control and power wiring.

    Control wiring refers to wires connected to the control terminal strip that carry 24V to 220V.

    • Use only UL or CSA recognized wire. • Use copper wire rated for 60/75°C.

    Control Power Wiring Control power wiring for starters covered in this manual is shown on Figure 5 on page 16. Low voltage starters may have additional control wiring as shown on Figure 4 if the optional full metering package is ordered with the unit.

    The control circuit on the McQuay centrifugal packaged chiller is designed for 115-volts. Control power can be supplied from three different sources:

    • If the unit is supplied with a factory-mounted starter, the control circuit power supply is factory-wired from a transformer located in the starter.

    • A free-standing starter furnished by McQuay, or by the customer to McQuay specifications, will have a control transformer in it and requires field wiring to terminals in the compressor terminal box.

    • Power can be supplied from a separate circuit and fused at 20 amps inductive load. The control circuit disconnect switch must be tagged to prevent current interruption. Other than for service work, the switch is to remain on at all times in order to keep oil heaters operative and prevent refrigerant from diluting in oil.

    DANGER If a separate control power source is used, the following must be done to avoid

    severe personal injury or death from electrical shock: Place a notice on the unit that multiple power sources

    are connected to the unit. Place a notice on the main and control power disconnects that

    another source of power to the unit exists.

  • 14 IOMM Starter

    Separate Power Source

    Chiller control power usually comes from a control transformer located in the starter and factory or field wired to the chiller control panel. In the event a separate transformer supplies control voltage, it must be rated at 3 KVA, with an inrush rating of 12 KVA minimum at 80% power factor and 95% secondary voltage. For control wire sizing, refer to NEC. Articles 215 and 310. In the absence of complete information to permit calculations, the voltage drop should be physically measured.

    Table 6, Control Power Line Sizing Maximum Length, ft (m) Wire Size (AWG) Maximum Length, ft (m) Wire Size (AWG)

    0 (0) to 50 (15.2) 12 120 (36.6) to 200 (61.0) 6 50 (15.2) to 75 (22.9) 10 200 (61.0) to 275 (83.8) 4 75 (22.9) to 120 (36.6) 8 275 (83.8) to 350 (106.7) 3

    Notes: 1. Maximum length is the distance a conductor will traverse between the control power

    source and the unit control panel. 2. Panel terminal connectors will accommodate up to number 10 AWG wire. Larger

    conductors will require an intermediate junction box. The Unit On/Off switch located in the Unit Control Panel should be turned to the "Off" position any time compressor operation is not desired.

    Low Voltage Starters Control wiring for low voltage starters is per the wiring diagram on page 16. If the optional

    “Full Metering Display” has been ordered, the following section will apply.

    Wiring for Optional Remote D3 Display Figure 3, Starter Panel Remote mounted low voltage wye-delta and solid state starters require field wiring to activate the optional full metering display on the chiller’s operator interface panel. The wiring is from the D3 board in the starter to the compressor controller and to the bias block; both located in the compressor control panel. See Figure 4, Field Wiring for Optional D3 .

    The location of the connections in the starter are shown to the right.

    Wiring Connection on Starter for Optional Display

  • IOMM Starter 15

    Figure 4, Field Wiring for Optional D3 Communication

    NOTES. 1. See Figure 3 for Starter connection location. 2. The compressor controller serial card location is in the lower-center of the compressor

    controller, under the operating buttons. 3. The bias block is located on the rail, just to the left of the compressor controller. 4. Note that the connections are (-) to (-), (+) to (+), and SCOM to GND, with a shield

    connection on the starter terminal board.

    Medium/high Voltage Starters Control wiring for medium and high voltage solid state and across-the-line starters is per the wiring diagram on page 16.

  • 16 IOMM Starter

    Figure 5, Control and Power Field Wiring

    80

    CP2

    CP1

    H

    O

    A

    C4

    H

    A

    O

    C3

    H

    A

    O

    79

    78

    77

    74

    73

    54

    CF

    86

    EF

    86C

    25

    1

    2

    11

    11

    12

    22

    1

    2

    6

    11

    12

    22

    NOTE 2

    NOTE 2

    (115V) (24V)

    25

    55

    70

    H

    A

    O

    H

    A

    O

    HO

    A C

    H

    O

    A C

    H

    O

    A C

    C2

    C1 T3-S

    PE

    L1

    L2CP2

    CP1

    24

    23(5A)

    24(5)

    23

    3

    4

    3

    4

    76

    75

    PE

    85

    86

    81

    84

    A82(NO)

    83(NC)

    POWER

    EP2

    EP1

    L1 L2 L3

    GND

    T4 T5 T6T1 T2 T3

    T4 T5 T6T1 T2 T3

    T1 T2 T3

    T3T1 T2

    U V W

    T4 T3 T5T1 T6 T2

    T1 T2 T3

    T4 T3 T5T1 T6 T2

    GND

    LESSTHAN30VOR24VAC

    53

    71

    71

    52

    1-10 VDC

    1-10 VDC

    MICROTECH CONTROLBOX TERMINALS

    * COOLINGTOWER

    FOURTHSTAGE

    STARTER

    * COOLINGTOWER

    THIRDSTAGE

    STARTER

    * COOLINGTOWER

    SECONDHSTAGE

    STARTER

    * COOLINGTOWER

    FIRSTSTAGE

    STARTER

    COOLING TOWERBYPASS VALVE

    COOLING TOWER VFD

    ALARM RELAY(NOTE 4)

    MICROTECHCOMPRESSOR CONTROL

    BOX TERMINALSCTB1

    -LOAD-

    COMPRESSORMOTOR

    STARTER(NOTE 1)

    115 VAC

    STARTER LOAD SIDE TERMINBALSVFD

    STARTER LOAD SIDE TERMINBALSWYE-DELTA

    STARTER LOAD SIDE TERMINBALSSOLID STATE

    STARTER LOAD SIDE TERMINBALSMEDIUM AND HIGH VOLTAGE

    COMPRESSOR TERMINALS

    COMPRESSOR TERMINALS

    COMPRESSOR TERMINALS

    COMPRESSOR TERMINALS

    NOTE 12

    - FOR DC VOLTAGE AND 4-20 MA CONNECTIONS (SEE NOTE 3)

    - FOR DETAILS OF CONTROL REFER TO UNIT CONTROL SCHEMATIC 330342101

    - COMPRESSOR CONTROL SCHEMATIC 330342201

    - LEGEND: 330343001

    * FIELD SUPPLIED ITEM

    * NOTE 7

    * NOTE 10

    * NOTE 10

    * NOTE 10

    * NOTE 10

    330387901-0A

    COMMON

    NEUTRAL

    POWER

    See notes on the following page.

  • IOMM Starter 17

    NOTES for Wiring Diagram

    1. Compressor motor starters are either factory-mounted and wired, or shipped separate for field-mounting and wiring. If provided by others, starters must comply with McQuay specification 359AB99. All line and load side power conductors must be copper.

    2. If starters are freestanding, then field control wiring between the starter and the control panel is required. Minimum wire size for 115 Vac is 12 GA for a maximum length of 50 feet. If greater than 50 feet, refer to McQuay for recommended wire size minimum. Wire size for 24 Vac is 18 GA. All wiring to be installed as NEC Class 1 wiring system and must be made with copper wire and copper lugs only. All 24 Vac wiring must be run in separate conduit from 115 Vac wiring.

    3. Main power wiring between starter and motor terminal is factory-installed when chillers are supplied with unit-mounted starters.

    4. For wye-delta, and solid state starters connected to six (6) terminal motors (low voltage), the conductors between the starter and motor carry phase current and wire size selection is based on 58 percent of the motor rated load amperes (RLA). Wiring of free-standing starters must be in accordance with the NEC and connection to the compressor motor terminals shall be made with copper wire and copper lugs only. Main power wiring between the starter and motor terminals is factory-installed when chillers are supplied with unit-mounted starters.

    5. The “Full Metering” option will require some field wiring when free-standing starters are used, as shown in Figure 4 on page 15.

  • 18 IOMM Starter

    Startup

    General The startup of McQuay centrifugal chillers, including the starters, is performed by McQuay authorized and trained technicians. They review the starter connections, phase sequence, and settings prior to starting the chiller.

    Setting a freestanding starter and power and control wiring from it to the chiller is the responsibility of the owner/contractor. See the installation and power and control wiring sections of this manual before commencing installation.

    In the rare instances where a starter is being replaced after the chiller has been in service, McQuay service is not automatically involved but can be contracted to supervise the starter installation.

    For general information, brief startup instructions are included on the following pages.

    Low Voltage Solid State (LVSS) LED Display

    • Located on the starter control board • View parameters, messages and faults. • Shows software revision on power up.

    Programming • Press PARAM to enter the menu and

    then UP or DOWN to reach the desired parameter.

    • Press ENTER to show the present value of the parameter.

    • Press UP or DOWN to change the parameter value.

    • Press ENTER to store the new value or PARAM to abandon the change.

    Quick Meters • Press DOWN to display the motor thermal overload content. • Press UP to display the incoming line phase order. • Press ENTER to display the status meter.

    Fault Log· • Select P32 and press ENTER. The most recent fault will be displayed as “xFyy”

    where x will be 1 to indicate the most recent fault is being displayed and yy is the fault code.

    • Press DOWN to view older faults. Up to 9 faults may be stored in the log.

    Resetting a Fault· • Press RESET to reset from a fault.Resetting Parameters· • Press and hold PARAM and ENTER on power up to reset parameters to default

    values.

  • IOMM Starter 19

    Emergency Thermal Reset· • Press RESET and DOWN to perform an emergency thermal reset.

    Messages (LVSS) No Line Ready Accelerating Up to Speed Run – Done with ramp but not yet

    Up to Speed. Decelerating Overload Alarm – The motor

    overload level is between 90% and 100%.

    Overload Fault – The motor overload level has reached 100%.

    Overload Lockout – A start is not allowed until the motor overload level cools below 60%.

    Control Power Lockout – A start is not allowed because the control power is too low.

    xxx xxx = overload content. Press DOWN to toggle.

    xx xx = Alarm code. If the condition persists, a fault will occur.

    xx xx = Fault code. Press RESET to clear.

    Instantaneous Overcurrent – Press RESET to clear.

    Default – Flashes when parameter defaults are loaded.

    Default Meter Display (P13) (LVSS) 0: Status 1: Ave RMS Current 2: L1 RMS Current 3: L2 RMS Current 4: L3 RMS Current 5: Current Imbalance % 6: Ground Fault Current

    7: Ave L-L Voltage RMS 8: L1-L2 Voltage RMS 9: L2-L3 Voltage RMS 10: L3-L1 Voltage RMS 11: Overload % 12: PF 13: KW

    14: KVA 15: KWh 16: MWh 17: Phase Rotation 18: Line Frequency 19: Analog Input

    Analog Output Function (P28) (LVSS) 0: OFF (no output) 1: Ave Current (0 – 200% RLA) 2: Ave Current (0 – 800% RLA) 3: Ave Voltage (0 – 750VAC) 4: Thermal Overload% 5: KW (0 - 10KW)

    6: KW (0 – 100KW) 7: KW (0 – 1MW) 8: KW (0 – 10MW) 9: Analog Input 10: Output Voltage (% of FV) 11: Calibrate (full 100% output)

    CT Burden Switch Settings (P1 and P23) (LVSS) FLA in Amps Setting

    864:1 CTs 2640:1 CTs 5760:1 CTs 8000:1 CTs SW1 SW2 24 to 42 73 to128 160 to 280 223 to 390 Off Off 42 to 50 128 to 151 280 to 330 390 to 465 Off On

    50 to 108 151 to 330 330 to 720 465 to 1000 On Off 108 to 190 330 to 590 720 to 1280 1000 to 1800 On On

    Parameters (LVSS)

    DESCRIPTION Values DEFAULT SET TO: P1 Motor FLA 1 to 9999 Amps 10 P2 Motor RLA 1 to 9999 Amps 10 P3 Motor Service Factor 1.00 to 1.99 1.08 P4 Motor Overload Class OFF, 1 to 40 10 P5 Initial Motor Current 50 to 400 %FLA 250 P6 Maximum Motor Current 100 to 800 %FLA 300 P7 Ramp Time 0 to 300 seconds 10 P8 UTS Time 1 to 900 seconds 15

    P9 Stop Mode CoS: Coast dcL: Voltage Decel CoS

    P10 Decel Begin Level 100 to 0 %Volts 40 Continued on next page.

  • 20 IOMM Starter

    DESCRIPTION Values DEFAULT SET TO: P11 Decel End Level 50 to 0 %Volts 20 P12 Decel Time 1 to 180 seconds 15 P13 Default Meter Display 0 to 19 1 P14 Overcurrent Trip Level OFF, 50 to 800 %RLA OFF

    P15 Overcurrent Trip Delay Time 0.1 to 90.0 seconds 2.0

    P16 Rated RMS Voltage

    100, 110, 120, 200, 208, 220, 230, 240, 350, 380, 400, 415, 440, 460, 480,

    575, 600, 660, 1000 Volts

    480

    P17 Over Voltage Trip Level OFF, 1 to 40 % rated Volts 10 P18 Under Voltage Trip Level OFF, 1 to 40 % rated Volts 10

    P19 Over/Under Voltage Delay Time 0.1 to 90.0 seconds 1.0

    P20 Current Imbalance Trip Level 5 to 40 % 10

    P21 Controlled Fault Stop OFF, On OFF P22 Auto Fault Reset Time OFF, 1 to 120 seconds 60

    P23 CT Ratio 72, 96, 144, 288, 864, 2640, 2880, 5760, 8000 2640

    P24 Control Source TEr: Terminal NEt: Network tEr

    P25 Modbus Address 1 to 247 1 P26 Modbus Baud Rate 1.2, 2.4, 4.8, 9.6, 19.2 Kbps 19.2 P27 Modbus Timeout OFF, 1 to 120 seconds 3 P28 Analog Output Function 0 to 11 1 P29 Analog Output Span 1 to 125 % 100 P30 Analog Output Offset 0 to 99 % 0 P31 Passcode 0 to 9999 – P32 Fault Log xFyy –

    Fault/Alarm Codes (LVSS)

    Description Controlled Stop Auto Reset

    00 No fault - - 01 UTS Time Limit Expired Y Y 02 Motor Thermal Overload Trip Y N 10 Phase Rotation Error, not ABC N Y 12 Low Line Frequency N Y 13 High Line Frequency N Y 15 Input power not three phase N Y 21 Low Line L1-L2 Voltage Y Y 22 Low Line L2-L3 Voltage Y Y 23 Low Line L3-L1 Voltage Y Y 24 High Line L1-L2 Voltage Y Y 25 High Line L2-L3 Voltage Y Y 26 High Line L3-L1 Voltage Y Y 27 Phase Loss N Y 28 No Line Voltage N Y 30 I.O.C. (Instantaneous Overcurrent) N N 31 Overcurrent Y N 37 Current Imbalance Y Y 38 Ground Fault Y N 39 No Current at Run N Y 40 Shorted / Open SCR N N 41 Current While Stopped N N 47 Stack Protection Fault N Y 48 Bypass Contactor Fault (on STOP input) Y N 50 Control Power Low N Y 51 Current Sensor Offset Error - N 52 Burden Switch Error N N

  • IOMM Starter 21

    Description Controlled Stop Auto Reset

    60 Thermistor Trip (on DIN#1) N N 61 Stack OT Switch Trip (on DIN#2) N N 71 Analog Input Trip Y Y 82 Modbus Timeout Y Y 94 CPU Error – Software Fault N N 95 CPU Error – Parameter Storage Fault N N 96 CPU Error – Illegal Instruction Trap N N 97 CPU Error – Software Watchdog Fault N N 98 CPU Error – Spurious Interrupt N N 99 CPU Error – Program Storage Fault N N

    • If a fault occurs that has a Y in the “Controlled Stop” column, and P21 (Controlled Fault Stop) is set to On, and P9 (Stop Mode) is set to dcL, then the starter will perform a voltage decel to stop. Otherwise it will coast to stop.

    • If a fault occurs that has a Y in the “Auto Reset” column, and P22 (Auto Fault Reset Time) is set to some value other than OFF, then the fault will automatically be cleared after the time specified by P22.

    Low Voltage Wye-Delta (LVYD

    Operation • LED Display

    • View parameters, messages and faults.

    • Shows software revision on power up.

    Programming· • Press PARAM to enter the menu and then UP

    or DOWN to reach the desired parameter.

    • Press ENTER to show the present value of the parameter.

    • Press UP or DOWN to change the parameter value.

    • Press ENTER to store the new value or PARAM to abandon the change.

    Quick Meters· • Press DOWN to display the motor thermal overload content.

    • Press UP to display the incoming line phase order.

    • Press ENTER to display the status meter.

    Fault Log • Select P24 and press ENTER. The most recent fault will be displayed as “xFyy” where x

    will be 1 to indicate the most recent fault is being displayed and yy is the fault code.

    • Press DOWN to view older faults. Up to 9 faults may be stored in the log.

  • 22 IOMM Starter

    Resetting a Fault • Press RESET to reset from a fault.

    Resetting Parameters • Press and hold PARAM and ENTER on power up to reset parameters to default values.

    Emergency Thermal Reset • Press RESET and DOWN to perform an emergency thermal reset.

    Messages (LVYD) No Line Ready Running in wye mode. Running in delta mode. Overload Alarm – The motor

    overload level is between 90% and 100%.

    Overload Fault – The motor overload level has reached 100%.

    Overload Lockout – A start is not allowed until the motor overload level cools below 60%.

    Control Power Lockout – A start is not allowed because the control power is too low.

    xxx xxx = overload content. Press DOWN to toggle.

    xx xx = Alarm code. If the condition persists, a fault will occur.

    xx xx = Fault code. Press RESET to clear.

    Instantaneous Overcurrent – Press RESET to clear.

    Default – Flashes when parameter defaults are loaded.

    Default Meter Display (P5) (LVYD) 0: Status 1: Ave RMS Current 2: L1 RMS Current 3: L2 RMS Current 4: L3 RMS Current 5: Current Imbalance % 6: Ground Fault Current

    7: Ave L-L Voltage RMS 8: L1-L2 Voltage RMS 9: L2-L3 Voltage RMS 10: L3-L1 Voltage RMS 11: Overload % 12: PF 13: KW

    14: KVA 15: KWh 16: MWh 17: Phase Rotation 18: Line Frequency 19: Analog Input

    Analog Output Function (P20) (LVYD) 0: OFF (no output) 1: Ave Current (0 – 200% RLA) 2: Ave Current (0 – 800% RLA) 3: Ave Voltage (0 – 750VAC) 4: Thermal Overload% 5: KW (0 - 10KW)

    6: KW (0 – 100KW) 7: KW (0 – 1MW) 8: KW (0 – 10MW) 9: Analog Input 10: Reserved 11: Calibrate (full 100% output)

    CT Burden Switch Settings (P1 and P15) (LVYD) RLA in Amps Setting

    864:1 CTs 2640:1 CTs 5760:1 CTs 8000:1 CTs SW1 SW2 24 to 42 73 to 128 160 to 280 223 to 390 Off Off 42 to 50 128 to 151 280 to 330 390 to 465 Off On

    50 to 108 151 to 330 330 to 720 465 to 1000 On Off 108 to 190 330 to 590 720 to 1280 1000 to 1800 On On

    Parameters (LVYD) DESCRIPTION Values DEFAULT

    P1 Motor RLA 1 to 9999 Amps 1 P2 Motor Service Factor 1.00 to 1.99 1.08 P3 Motor Overload Class OFF, 1 to 40 10 P4 Transition Time 1 to 30 seconds 10 P5 Default Meter Display 0 to 19 0

    Continued on next page.

  • IOMM Starter 23

    DESCRIPTION Values DEFAULT

    P6 Sequence Complete Delay Time 0.1 to 5.0 seconds 2.0

    P7 Overcurrent Trip Level OFF, 50 to 800 %RLA OFF

    P8 Overcurrent Trip Delay Time 0.1 to 90.0 seconds 2.0

    P9 Rated RMS Voltage

    100, 110, 120, 200, 208, 220, 230, 240, 350, 380, 400, 415, 440, 460, 480,

    575, 600, 660, 1000 Volts

    480

    P10 Over Voltage Trip Level OFF, 1 to 40 % rated Volts 10 P11 Under Voltage Trip Level OFF, 1 to 40 % rated Volts 15

    P12 Over/Under Voltage Delay Time 0.1 to 90.0 seconds 1.0

    P13 Current Imbalance Trip Level 5 to 40 % 20

    P14 Auto Fault Reset Time OFF, 1 to 120 seconds 60

    P15 CT Ratio 72, 96, 144, 288, 864, 2640, 2880, 5760, 8000 2640

    P16 Control Source TEr: Terminal NEt: Network tEr

    P17 Modbus Address 1 to 247 2 P18 Modbus Baud Rate 1.2, 2.4, 4.8, 9.6, 19.2 Kbps 19.2 P19 Modbus Timeout OFF, 1 to 120 seconds 3 P20 Analog Output Function 0 to 11 1 P21 Analog Output Span 1 to 125 % 100 P22 Analog Output Offset 0 to 99 % 0 P23 Passcode 0 to 9999 – P24 Fault Log xFyy –

    Fault/Alarm Codes (LVYD)

    Description Auto Reset 00 No fault - 02 Motor Thermal Overload Trip N 10 Phase Rotation Error, not ABC Y 12 Low Line Frequency Y 13 High Line Frequency Y 15 Input power not three phase Y 21 Low Line L1-L2 Voltage Y 22 Low Line L2-L3 Voltage Y 23 Low Line L3-L1 Voltage Y 24 High Line L1-L2 Voltage Y 25 High Line L2-L3 Voltage Y 26 High Line L3-L1 Voltage Y 27 Phase Loss Y 28 No Line Voltage Y 30 I.O.C. (Instantaneous Overcurrent) N 31 Overcurrent N 37 Current Imbalance Y 38 Ground Fault N 39 No Current at Run Y 40 Open Line or Motor Lead N 41 Current While Stopped N 48 2M Feedback Fault (on DIN#2) N 50 Control Power Low Y 51 Current Sensor Offset Error N

  • 24 IOMM Starter

    Description Auto Reset 52 Burden Switch Error N 60 Thermistor Trip (on DIN#1) N 71 Analog Input Trip Y 82 Modbus Timeout Y 94 CPU Error – Software Fault N 95 CPU Error – Parameter Storage Fault N 96 CPU Error – Illegal Instruction Trap N 97 CPU Error – Software Watchdog Fault N 98 CPU Error – Spurious Interrupt N 99 CPU Error – Program Storage Fault N

    If a fault occurs that has a Y in the “Auto Reset” column, and P14 (Auto Fault Reset Time) is set to some value other than OFF, then the fault will automatically be cleared after the time specified by P14.

    Medium/High Voltage, Solid State Quick Start

    Motor FLA

    Parameter Description The motor FLA parameter must be set to the full load amps of the motor connected to the starter for the starter to function correctly. NOTE: The starter uses the entered motor FLA for every current based calculation. If the motor FLA is not entered correctly, the current ramp profile and many of the starter’s advanced protection features will not function properly.

    Parameter Values The motor FLA parameter is adjustable from 1 to 1200 amps in 1-amp increments.

    Parameter Default The default value for the motor FLA is 1 amp.

    Serv. Fact (Service Factor)

    Description The service factor parameter should be set to the service factor of the motor. The service factor is used for the overload calculations. The service factor is factory set, will be checked by the start-up technician and should not require further adjustment. If the service factor of the motor is not known, then the service factor should be set to 1.08.

    Values The service factor can be set from 1.00 to 1.99, in 0.01 increments. NOTE: The NEC (National Electrical Code) does not allow the service factor to be set above 1.40. Check with other local electrical codes for their requirements.

    Default The default value for the service factor is 1.08.

  • IOMM Starter 25

    Start Mode Description The Start Mode parameter allows for an optimal start of the motor based on the application. For a description of the possible Start Mode parameters, refer to page 31 in the Operations chapter. Values

    The Start Mode Parameter can be set to Curr, TT, or Tach. Default

    The default value for the Start Mode is Curr.

    Stop Mode Description The Stop Mode parameter allows for the most suitable stop of the motor based on the application. For a description of the possible Stop Mode parameters, refer to page 31 in the Operations chapter of the starter manual.

    Values The Stop Mode can be set to Coas, VDCL, or TT.

    Default The default value for the Stop Mode is Coas.

    Int. Curr. (initial current) Description The initial current parameter is set as a percentage of the motor FLA parameter setting. The initial current parameter sets the current that will initially reach the motor when a start is commanded.

    If the motor does not rotate within a few seconds after a start command, the initial current should be increased. If the motor takes off too quickly after a start command, the initial current should be decreased.

    The initial current must be set to a value that is lower than the maximum current parameter setting.

    A typical setting for the initial current parameter is from 50% to 175%.

    Values The initial current is adjustable from 50% to 400% in 1% intervals. Default The default value for the initial current is 100%.

    Max. Curr. (maximum current) Description The maximum current parameter is set as a percentage of the motor FLA parameter setting. The maximum current parameter performs two functions. It sets the current for the end of the ramp profile and sets the maximum current that is allowed to reach the motor while the motor is being started.

    If the ramp time expires before the motor has reached full speed, the starter will hold the current at the maximum current level until the stall time expires, the motor reaches full speed, or the overload trips.

    Typically, the maximum current is set to 600% unless the power system or load dictates the setting of a lower maximum current.

    Values The maximum current is adjustable from 100% to 600% in 1% intervals.

  • 26 IOMM Starter

    Default The default value for the maximum current is 600%.

    Ramp Time Description The ramp time sets the amount of time that it takes for the starter to linearly increase the current from the initial current level to the maximum current level. A typical ramp time setting is from 15 to 30 seconds.

    Settings The ramp time is adjustable from 0 to 120 seconds in 1 second intervals. Default The default value for the ramp time is 15 seconds.

    Overload Default

    The default value for the overload parameter is 10.

    Phase Order Description The line phasing parameter sets the phase sensitivity of the starter. This can be used to protect the motor from a possible change in the incoming phase sequence. If the incoming phase sequence does not match the set phase rotation, the starter will display phs err while stopped and will fault if a start is attempted.

    Values The line phasing can be set to:

    • INS - will run with either phase sequence • ABC - will only run with ABC phase sequence • CBA - will only run with CBA phase sequence

    Default The default value for the phase sensitivity parameter is ABC.

  • IOMM Starter 27

    Operation, Low Voltage Starters, 200 – 600 Volts Introduction This section contains information on low voltage, Wye-Delta and solid-state starters as manufactured by Benshaw Inc. for McQuay centrifugal Chillers. They are known collectively as “D3” starters, which is their software designation. These low voltage starters have similar software (designated D3) and are grouped together in this manual. Model numbers are as follows: D3WD11 to D3WD2K Wye-Delta, Free-standing D3WT11 to D3WT65 Wye-Delta, Factory (Terminal) Mounted RVSS14 to RVSS4K Solid State, Free-standing RVST14 to RVST82 Solid State, Factory (Terminal) Mounted

    Viewing Data The information in this section applies to low voltage, solid start and wye-delta starters, with the exceptions noted at the end of the section beginning on page 36.

    Starter information is available on the starter-mounted LED as explained beginning on page 30. If the optional “Full Meter Display” (available only on low voltage starters) is ordered with the unit, power information will also be available on the chiller’s operator interface touchscreen, as explained below.

    Figure 6, Optional Starter View Screen

    The ability to view the starter’s power characteristics and to set starter setpoints on the operator interface screen is an optional extra available at the time of purchase. If the optional “Full Meter Display” is supplied on the unit, the “POWER” button (or “STARTER” in some software versions) will be visible on the upper left side of the VIEW screen as shown above. Pressing this button will open the screen shown in Figure 7 in the blank area to the right of the screen shown above.

  • 28 IOMM Starter

    Figure 7, Expanded Starter View Screen The screen shown to the right will be superimposed on the right side of the VIEW screen shown in Figure 6 when the optional “Full Meter Display” is included with the unit.

    If the “Full Meter Display” package is not ordered, only the Percent Unit RLA amps will appear on the Home screen. This Starter/Power screen will remain visible until another display button; such as STATE, I/O, etc, is selected.

    The option will also provide a starter setpoint screen as in Figure 8. Without this option, the setpoints are made on the starter keypad.

  • IOMM Starter 29

    Figure 8, Optional Starter Setpoint Screen

    Table 7, Starter Setpoints

    Description No. Default Range Pass- word Comments

    Ground Fault Current Trip 8 1 % 1 to 100% RLA M

    Sets the value for ground current above which the compressor will be shut down

    Ground Fault Enable 7 OFF On or OFF M Turns the ground fault option on or off

    Maximum Current Unbalance 6 10% 5% to 40% T

    Sets the value for current unbalance above which the compressor will be shut down

    Starter Ramp Time 5 15 sec. 0 to 30 seconds T Sets the time the starter ramps up the motor current

    Maximum Starter Current 4 600%

    100% to 800% of FLA (SP1) T

    Sets the maximum current when the compressor starts

    Initial Starter Current 3 100% 50% to 400% of FLA (SP1) T Sets the initial current when the compressor starts

    Rated load Amps 2 1 A Factory set at

    design conditions

    T Value that gives the 100% RLA value and used for motor protection

    Full Load Amps 1 1 A Factory set to

    motor max current rating

    T Value used to compute SP3 and SP4

    1. The setpoints shown above are for solid state starters. Other types of starters will have slightly different setpoints. Units without the starter display option will have their setpoints set in the starter itself.

    2. Do not change these setpoints after McQuay startup.

    3. Do not remove the D3 control wiring. If accidentally disconnected, contact McQuay service.

  • 30 IOMM Starter

    Standard Starter Keypad and Display When the optional full metering display is not ordered, the LED display located in the starter provides information on starter operation and programming. The 4-digit, 7-segment display shows starter meter outputs and programming data. Special symbols provide further information about the starter operation (see the following section).

    Figure 9, Starter-mounted LED

    The LED display and keypad is used to:

    1. Perform operations 2. View and set parameters (setpoints) 3. View operating messages 4. View faults and alarms

    Special Messages Displayed The keypad’s display may show the following special information under certain conditions.

    Table 8, LED Special Characters Displayed

    PARAM DOWN UP ENTER

    RESET

    LED Display

    Operating Keys

    Reset Key

    No Line Ready Accelerating or Kicking Up to Speed Run – Done with Accel ramp but not yet Up to

    Speed. Decelerating Motor Overload Alarm – The motor overload level is

    between 90% and 100%. Overload Fault – The motor overload level has

    reached 100%. Overload Lockout – A start is not allowed until the

    motor overload level cools below 60%.

    Phase order meter showing ABC Phase order meter showing CBA Phase order meter showing Single Phase

    xxx xxx = overload content. xx xx = Parameter code. xx xx = Alarm code. If the condition persists,

    a fault will occur. xx xx = Fault code.

    Instantaneous Overcurrent Default – Flashes when parameter defaults

    are loaded. Energy Saver

    In reflash mode

  • IOMM Starter 31

    Display Operation Display

    • View parameters, messages and faults. • Shows software revision on power up.

    ramming • Press PARAM to enter the menu and

    then UP or DOWN to reach the desired parameter.

    • Press ENTER to show the present value of the parameter.

    • Press UP or DOWN to change the parameter value.

    • Press ENTER to store the new value or PARAM to abandon the change.

    k Meters • Press DOWN to display the motor

    thermal overload content. • Press UP to display the incoming line

    phase order. • Press ENTER to display the status

    meter.

    Log • Press PARAM, Select P24 and press

    ENTER. The most recent fault will be displayed as “xFyy” where x will be 1 to indicate the most recent fault is being displayed and yy is the fault code.

    • Press DOWN to view older faults. Up to 9 faults may be stored in the log.

    tting a Fault • First correct the cause of the fault.

    Then press RESET to reset from a fault.

    tting Parameters • Press and hold PARAM and ENTER on

    power up to reset parameters to default values.

    rgency Thermal Reset • Press RESET and DOWN to perform an

    emergency thermal reset.

  • 32 IOMM Starter

    Changing Parameters Viewing Parameter Values Parameter view mode can be entered by:

    1. At the default meter display, press the PARAM key to enter parameter mode. “P 1” will be displayed to indicate Parameter 1.

    2. Use the UP and DOWN keys to scroll through the available parameters. 3. Pressing the UP key from “P 1” will advance to parameter “P 2”. 4. Pressing the DOWN key from “P 1” will wrap around to the highest parameter. 5. The value of the parameter can be viewed by pressing the ENTER key. 6. To view another parameter without changing/saving the parameter, press the PARAM key

    to return to the parameter number display. To return to the default meter display either:

    1. Press the PARAM key while in the parameter number display mode. 2. Wait 60 seconds and the display will return to the default meter display.

    Changing Parameter Values Parameter change mode can be entered by:

    1. At the default meter display, press the PARAM key to enter parameter mode. 2. Use the UP and DOWN keys to scroll through the available parameters. 3. The value of the parameter can be viewed by pressing the ENTER key. 4. When viewing the parameter value, the parameter can be changed by using the UP and

    DOWN keys. 5. To store the new value, press the ENTER key. When the ENTER key is pressed the

    value will be saved and the display will go back to parameter # “P_”. To exit parameter change mode without saving the new parameter value either:

    1. Press the PARAM key to return to the parameter number display. 2. Wait 60 seconds and the display will return to the default meter display. The starter setpoint parameters are factory set and subsequently reviewed during commissioning by the McQuay startup technician. They should not be changed unless authorized by McQuay. The programming procedure is explained above and the following table shows the range of values and defaults.

    Table 9, Setpoints, Wye-Delta Starter Description Values Default

    P1 Motor RLA 1 to 9999 Amps 1 P2 Motor Service Factor 1.00 to 1.99 1.08 P3 Motor Overload Class OFF, 1 to 40 10 P4 Transition Time 1 to 30 seconds 10 P5 Default Meter Display 0 to 19 0 P6 Sequence Complete Delay Time 0.1 to 5.0 seconds 2.0 P7 Overcurrent Trip Level OFF, 50 to 800 %RLA OFF

    Continued on next page.

  • IOMM Starter 33

    Description Values Default P8 Overcurrent Trip Delay Time 0.1 to 90.0 seconds 2.0

    P9 Rated RMS Voltage 208, 220, 230, 240, 380, 415, 440, 460, 480, 575 Volts 480

    P10 Over Voltage Trip Level OFF, 1 to 40 % rated Volts 10 P11 Under Voltage Trip Level OFF, 1 to 40 % rated Volts 15 P12 Over/Under Voltage Delay Time 0.1 to 90.0 seconds 1.0 P13 Current Imbalance Trip Level 5 to 40 % 20 P14 Auto Fault Reset Time OFF, 1 to 120 seconds 60

    P15 CT Ratio 72, 96, 144, 288, 864, 2640, 2880, 5760, 8000 2640

    P16 Control Source TEr: = Terminal, NEt: = Network TEr

    P17 Modbus Address 1 to 247 2 P18 Modbus Baud Rate 1.2, 2.4, 4.8, 9.6, 19.2 Kbps 19.2 P19 Modbus Timeout OFF, 1 to 120 seconds 3 P20 Analog Output Function 0 to 11 1 P21 Analog Output Span 1 to 125 % 100 P22 Analog Output Offset 0 to 99 % 0 P23 Passcode (See Note) 0 to 9999 Disabled P24 Fault Log xFyy –

    Table 10, Setpoints, Solid State Starter Description Values Default

    P1 Motor FLA 1 to 9999 Amps 10 P2 Motor RLA 1 to 9999 Amps 10 P3 Motor Service Factor 1.00 to 1.99 1.08 P4 Motor Overload Class OFF, 1 to 40 10 P5 Initial Motor Current 50 to 400 %FLA 100 P6 Maximum Motor Current 100 to 800 %FLA 600 P7 Ramp Time 0 to 300 seconds 15 P8 UTS Time (Up To Speed) 1 to 900 seconds 30

    P9 Stop Mode CoS: Coast dcL: Voltage Decel CoS

    P10 Decel Begin Level 100 to 0 %Volts 40 P11 Decel End Level 50 to 0 %Volts 20 P12 Decel Time 1 to 180 seconds 15 P13 Default Meter Display 0 to 19 0 P14 Overcurrent Trip Level OFF, 50 to 800 %RLA OFF P15 Overcurrent Trip Delay Time 0.1 to 90.0 seconds 2.0

    P16 Rated RMS Voltage 208, 220, 230, 240, 380, 415, 440, 460, 480, 575 Volts 480

    P17 Over Voltage Trip Level OFF, 1 to 40 % rated Volts 10 P18 Under Voltage Trip Level OFF, 1 to 40 % rated Volts 15 P19 Over/Under Voltage Delay Time 0.1 to 90.0 seconds 1.0 P20 Current Imbalance Trip Level 5 to 40 % 35 P21 Controlled Fault Stop OFF, On OFF P22 Auto Fault Reset Time OFF, 1 to 120 seconds 60

    P23 CT Ratio 72, 96, 144, 288, 864, 2640, 2880, 5760, 8000 2640

    P24 Control Source Ter: Terminal, Net: Network tEr

    P25 Modbus Address 1 to 247 2 Continued on next page.

  • 34 IOMM Starter

    Description Values Default P26 Modbus Baud Rate 1.2, 2.4, 4.8, 9.6, 19.2 Kbps 19.2 P27 Modbus Timeout OFF, 1 to 120 seconds 3 P28 Analog Output Function 0 to 11 1 P29 Analog Output Span 1 to 125 % 100 P30 Analog Output Offset 0 to 99 % 0 P31 Passcode (See Note) 0 to 9999 Disabled P32 Fault Log xFyy –

    NOTE: Passcode is a numerical password that can be entered in P31. The factory default is to disable the password requirement. It is recommended that a Passcode not be entered.

    Messages Setpoint P5 for Wye-Delta or P13 for solid state can be set to establish what message is shown on the LED. Selecting meter display “0” (which is the default) will display the active status message as shown in Table 11 or Table 12, except if there is a fault (requiring a message) or some other information has been requested. Alternatively, parameter P5 or P13 can be set to select a message (1 to 19 as shown in Table 13).

    Table 11, Status Messages, Wye-Delta Starter No Line Ready Running in wye mode. Running in delta mode. Overload Alarm – The motor overload

    level is between 90% and 100%. Overload Fault – The motor overload

    level has reached 100%. Overload Lockout – A start is not

    allowed until the motor overload level cools below 100%.

    Control Power Lockout – A start is not allowed because the control power is too low.

    xxx xxx = overload content. Press DOWN to toggle.

    xx xx = Alarm code. If the condition persists, a fault will occur.

    xx xx = Fault code. Press RESET to clear. Instantaneous Overcurrent – Press

    RESET to clear. Default – Flashes when parameter

    defaults are loaded.

    Table 12, Status Messages, Solid State Starter No Line Ready Accelerating Up to Speed Run – Done with ramp but not yet Up

    to Speed. Decelerating Overload Alarm – The motor overload

    level is between 90% and 100%. Overload Fault – The motor overload

    level has reached 100%. Overload Lockout – A start is not

    allowed until the motor overload level cools below 100%.

    Control Power Lockout – A start is not allowed because the control power is too low.

    xxx xxx = overload content. Press DOWN to toggle.

    xx xx = Alarm code. If the condition persists, a fault will occur.

    xx xx = Fault code. Press RESET to clear.

    Instantaneous Overcurrent – Press RESET to clear.

    Default – Flashes when parameter defaults are loaded.

  • IOMM Starter 35

    Table 13, Default Meter Display 0: Status Message 1: Ave RMS Current 2: L1 RMS Current 3: L2 RMS Current 4: L3 RMS Current 5: Current Imbalance % 6: Ground Fault Current

    7: Ave L-L Voltage RMS 8: L1-L2 Voltage RMS 9: L2-L3 Voltage RMS 10: L3-L1 Voltage RMS 11: Overload % 12: Power Factor 13: KW

    14: KVA 15: KWh 16: MWh 17: Phase Rotation 18: Line Frequency 19: Analog Input

    Display Output for the Standard Keypad The display will output different information depending on the operation of the starter. See Table 8, LED Special Characters Displayed.

    Power Up The software version will be displayed as a series of blinking digits once power has been applied to the D3 control. If the parameters were being reset on power up, “dFLt” will be flashed on the display for three seconds, then the software version will be displayed.

    Stopped When the starter is not in the run mode, the display will show the status condition of the starter, such as “rdY” (ready), “L OL” (Overload Lockout), “noL” (No Line).

    Running When running, the display will show the user selected meter function. The following meters can be selected using the “Meter” display parameter P13.

    Status Avg. Voltage (RMS) KVA

    Avg. RMS current L1-L2 Voltage (RMS) KWh

    Phase 1 RMS current L2-L3 Voltage (RMS) MWh

    Phase 2 RMS current L3-L1 Voltage (RMS) Phase Rotation

    Phase 3 RMS current Overload % Line Frequency

    Current Imbalance % Power Factor

    GF Current (% FLA) KW

    Alarm Condition When an alarm condition exists, the display alternates between displaying the selected meter and the alarm code. The alarm code is displayed as “A XX”, where XX is the alarm code. • When a thermal overload alarm condition exists, “A OL” will be displayed. • When a no line alarm condition exists, “noL” will be displayed. When the starter is stopped, the selected meter is not displayed.

    Lockout Condition When a lockout condition exists, the display shows the lockout code. The lockout code is displayed as “L XX: where XX is the lockout code. Following are the defined lockout conditions and their codes: • When a motor thermal overload lockout condition exists, “L OL” will be displayed. • When a power stack thermal overload lockout condition exists, “L Ot” will be displayed. • When a low control power lockout condition exists, “L CP” will be displayed. When there are multiple lockout codes, each will be displayed at 2 second intervals.

  • 36 IOMM Starter

    Faulted Condition When a fault condition exists, the display shows the fault code Fxx. The exceptions to this are as follows: • When the fault is thermal overload trip, “F OL” will be displayed. • When the fault is Instantaneous over current, ioc will be displayed.

    Quick Meters Although any meter may be viewed by changing the meter parameter, there are 3 “Quick Meters” that are always available with a single key press. When the starter is in the normal display mode, the display may be toggled between the information currently displayed and the following quick meters. Status Meter Toggle between the programmed meter display and the starter operational

    status display (rdY, run, utS, dcL, etc) by pressing the ENTER key.

    Overload Meter Toggle between the programmed meter display and the overload content by pressing the DOWN key. The overload will be displayed as “oXXX” where XXX is the overload content. For example if the overload content is 76 percent, it will be displayed as “o 76”.

    Phase Order Meter Toggle between the programmed meter display and the phase order by pressing the UP key. The phase order will be displayed as “AbC” or “CbA”. The phase order must be AbC to operate.

    Restoring Factory Parameter Settings To restore ALL parameters to the factory default settings, press and hold the PARAM and ENTER pushbutton switch on power up. The display will blink “dFLt”. Parameters unique to the motor starter applications will need to be set again to appropriate values before motor operation

    Resetting a Fault To reset from a fault condition, press RESET.

    Emergency Thermal Reset To perform an emergency thermal reset, press RESET and DOWN. This will set the motor thermal overload content to 0.

    Wye Delta When the D3 control is provided for Wye-Delta – there is Wye-Delta specific software and the D3 control is configured to operate an electromechanical closed transition Wye-Delta (Star-Delta) starter. When equipped with Wye-Delta software, all D3 motor and starter protective functions, except bad SCR detection and power stack overload, are available to provide full motor and starter protection. There is an additional specific parameter for Transition Time. This sets the time when the Wye to Delta transition occurs during starting.

    A closed transition starter uses resistors that are inserted during the transition so that the motor is never completely disconnected from the input line.

    The presence of these resistors in a closed transition starter smoothes the transition from Wye to Delta operation mode. A typical closed transition Wye-Delta starter schematic is shown in Figure 10, Wye Delta Motor Connection to the D3 Control.

  • IOMM Starter 37

    Figure 10, Wye Delta Motor Connection to the D3 Control

    M echanicalInterlock

    T1

    T2

    T3 T6

    T5

    T4

    Resistor

    Resistor

    Resistor

    1M

    L1 L2 L3

    2M2S

    1S

    1S

    2S

    1M

    2M

    2S

    Control Power

    2M

    1S

    1M 1S

    Run

    MX

    UTS

    M X

    2M M X

    Input Com m on

    To TB3, C1+ (W hite W ire)

    To TB3, C2+ (W hite W ire)

    To TB3, C3+ (W hite W ire)

    To TB3, C1- (B lack W ire)

    To TB3, C 2- (B lack W ire)

    To TB3, C 3- (B lack W ire)

    Current Feedbacks to M X

    Lin

    e V

    olta

    ge

    &

    Fre

    que

    nc

    y to

    MX

    To

    TB

    4 (

    SC

    R 1

    ) K

    1

    To

    TB

    6 (

    SC

    R 2

    ) K

    2

    To

    TB

    8 (

    SC

    R 3

    ) K

    3

    2M Confirm

    The closed transition resistors generally are sized to be in the circuit for a short period of time. To protect the resistors from over heating, one input should be programmed as a Bypass/2M contact feedback input and the Bypass/2M confirm parameter must be set.

    For the Wye-Delta starter mode to operate properly, one output relay needs to be programmed to the RUN output function and another output relay needs to be programmed to the UTS output function. (Refer to parameters I/0 04-06, P42-44 for more information).

    Wye-Delta Operation When the D3 control Starter Type parameter (FUN 07, P64) is set to Wye-Delta, the D3 control is configured to operate an electromechanical Wye-Delta (Star-Delta) starter. When in Wye-Delta mode, all D3 motor and starter protective functions except bad SCR detection and power stack overload, are available to provide full motor and starter protection.

    The D3 control utilizes an intelligent Wye to Delta transition algorithm. If during starting the measured motor current drops below 85% of FLA and more than 25% of the UTS / Transition Time (QST 09, P9) has elapsed then a Wye to Delta transition will occur. The intelligent transition algorithm prevents unnecessarily prolonged motor starts thereby

  • 38 IOMM Starter

    reducing motor heating. If a Wye to Delta transition has not already occurred, a transition will always occur when the complete UTS / Transition Time (QST 09, P9) expires.

    The D3 control can operate two configurations of Wye-Delta starters, open transition and closed transition. An open transition starter momentarily disconnects the motor from the input line during the transition from Wye to Delta operating mode. A closed transition starter uses resistors that are inserted during the transition so that the motor is never completely disconnected from the input line. The presence of these resistors in a closed transition starter smoothes the transition from Wye to Delta operating mode. A typical closed transition Wye-Delta starter schematic is shown in Figure 10.

    For the Wye-Delta starter mode to operate properly, one output relay needs to be programmed to the RUN output function and another output relay needs to be programmed to the UTS output function. (Refer to parameters I/0 04-06, P42-44 for more information.)

    Based on the typical closed transition schematic shown in Figure 10, Wye Delta Motor Connection to the D3 Control, when a start command is given the starter will enter the Wye starting mode by energizing the relay programmed as RUN.

    The transition to Wye (Starting) mode occurs as follows:

    1. Start command is given to the starter.

    2. The RUN relay is energized which energizes the 1S contactor.

    3. When the 1S contactor pulls in, the 1M contactor is energized.

    The D3 starter will remain in the Wye mode until either:

    1. The start command is removed.

    2. The Transition Time (QST 09, P9) expires

    or

    The measured motor current is less than 85% of FLA and at least 25% of the Transition Time (QST 09, P9) has elapsed.

    3. A fault occurs.

    When the Transition Time (QST 09, P9) expires, the starter will change from Wye starting mode to the Delta or normal running mode by energizing the relay programmed as UTS. In Delta mode, the RUN and UTS relays are both energized and the motor is connected in the normal running Delta configuration.

    The transition to Delta (Run) mode occurs as follows:

    1. The Transition Time (QST 09, P9) expires

    or

    The measured motor current is less than 85% of FLA and at least 25% of the Transition Time (QST 09, P9) has elapsed.

    2. The UTS relay is energized which energizes the 2S contactor.

    3. When the 2S contactor pulls in, resistors are inserted in the circuit and the 1S contactor is DE-energized.

    4. When the 1S contactor drops out the 2M contactor is energized.

    5. When the 2M contactor is pulled in, feedback can be sent to the D3 control board to confirm that the transition sequence to Delta is complete.

  • IOMM Starter 39

    The starter will remain in the Delta or running mode until the start command is removed or a fault occurs.

    Usually the D3 intelligent Wye to Delta transition algorithm provides an optimal transition point that minimizes the transient current and torque surges that can occur. However sometimes, based on the motor and loading, the Wye to Delta transition will occur only after the Transition Time has expired. In order to reduce the current surge that can take place during the transition from Wye to Delta mode, the Transition Time parameter (QST 09, P9) should be adjusted so that the transition occurs as close to full speed as possible within the constraints of the load. If the transition time is set too short, a large current and torque surge may occur during the transition. If the transition time is set too long, the motor may not have sufficient torque to continue accelerating when in Wye mode and may stop accelerating at a low speed until the transition to Delta mode occurs. If this occurs, the start is unnecessarily prolonged and motor heating is increased.

    A typical closed transition Wye-Delta starting current profile is shown in Figure 11.

    Figure 11, Wye Delta Profile

    100%

    200%

    300%

    400%

    500%

    600%

    0% 100%% speed

    Wye-Delta Closed Transition Current Profile

    % Full Load Motor

    Current

    Transition from Wye to Delta mode

    A digital input (I/O 01-03, P39-41) can be programmed as a 2M contactor feedback input. This input provides verification that the 2M contactor has fully closed preventing operation when the transition resistors are still connected in the motor circuit. The use of this feedback is recommended to prevent the overheating of the transition resistors if the 2M contactor does not close properly. The 2M confirmation trip time can be adjusted by modifying the Bypass / 2M Confirm parameter (I/O 16, P54).

    Note: When in Wye-Delta mode, the acceleration ramp, kick, and deceleration settings have no effect on motor operation and the SCR gate outputs are disabled.

  • 40 IOMM Starter

    Fault Code Troubleshooting Chart The following is a list of possible fault messages that can be generated by the D3 starter control.

    Code Description Detailed Description of Fault / Possible Solutions

    Motor did not achieve full speed before the UTS timer (QST 09, P9) expired.

    Check motor for jammed or overloaded condition.

    Verify that the combined kick time (CFN11, P14) and acceleration ramp time (QST 08, P8) is shorter than the UTS timer setting.

    Evaluate acceleration ramp settings. The acceleration ramp settings may be too low to permit the motor to start and achieve full speed. If so, revise acceleration ramp settings to provide more motor torque during starting.

    F01 UTS Time Limit Expired

    Evaluate UTS timer setting and, if acceptable, increase UTS timer setting (QST 09, P9).

    The D3 motor thermal overload protection has tripped.

    Check motor for mechanical failure, jammed, or overloaded condition.

    Verify the motor thermal overload parameter settings (QST 03, P3 and PFN 12-16, P35-38) and motor service factor setting (QST 02, P2).

    Verify that the motor FLA (QST 01, P1), CT ratio (FUN 03, P68), and burden switch settings are correct.

    If motor OL trip occurs during starting, review acceleration ramp profile settings.

    Verify that there is not an input line power quality problem or excessive line distortion present.

    Verify that PF caps, if installed, are ahead of CT’s.

    F02 (F OL)

    Motor Thermal Overload Trip

    Reset overload when content falls below 15%.

    Input phase rotation is not ABC and Input Phase Sensitivity parameter (FUN 04, P67) is set to ABC only.

    Verify correct phase rotation of input power. Correct wiring if necessary. F10

    Phase Rotation Error, not ABC

    Verify correct setting of Input Phase Sensitivity parameter (FUN 04, P67).

    Input phase rotation is not CBA and Input Phase Sensitivity parameter (FUN 04, P67) is set to CBA only.

    Verify correct phase rotation of input power. Correct wiring if necessary. F11

    Phase Rotation Error, not CBA

    Verify correct setting of Input Phase Sensitivity parameter (FUN 04, P67).

    Line frequency below 23 Hz was detected.

    Verify input line frequency.

    If operating on a generator, check generator speed governor for malfunctions.

    Check input supply for open fuses or open connections

    F12 Low Line Frequency

    Line power quality problem / excessive line distortion.

  • IOMM Starter 41

    Code Description Detailed Description of Fault / Possible Solutions

    Line frequency above 72 Hz was detected.

    Verify input line frequency.

    If operating on a generator, check generator speed governor for malfunctions. F13

    High Line Frequency

    Line power quality problem / excessive line distortion.

    Three-phase power has been detected when the starter is expecting single-phase power.

    Verify that input power is single phase.

    Verify that single-phase power is connected to the L1 and L2 inputs. Correct wiring if necessary.

    F14 Input power not single phase

    Verify that the SCR gate wires are properly connected to the D3 control board.

    Single-phase power has been detected when the starter is expecting three-phase power.

    Verify that input power is three phase. Correct wiring if necessary.

    Verify that the SCR gate wires are properly connected to the D3 control board. F15

    Input power not three phase

    On medium voltage systems, verify wiring of the voltage feedback measurement circuit.

    Low voltage below the Undervoltage Trip Level parameter setting (PFN 08, P31) was detected for longer than the Over/Under Voltage Trip delay time (PFN 09, P32).

    Verify that the actual input voltage level is correct.

    Verify that the Rated Voltage parameter (FUN 05, P66) is set correctly.

    Check input supply for open fuses or open connections.

    F21 Low Line L1-L2

    On medium voltage systems, verify wiring of the voltage measurement circuit.

    Low voltage below the Undervoltage Trip Level parameter setting (PFN 08, P31) was detected for longer than the Over/Under Voltage Trip delay time (PFN 09, P32).

    Verify that the actual input voltage level is correct.

    Verify that the Rated Voltage parameter (FUN 05, P66) is set correctly.

    Check input supply for open fuses or open connections.

    F22 Low Line L2-L3

    On medium voltage systems, verify wiring of the voltage feedback measurement circuit.

    Low voltage below the Undervoltage Trip Level parameter setting (PFN 08, P31) was detected for longer than the Over/Under Voltage Trip delay time (PFN 09, P32).

    Verify that the actual input voltage level is correct.

    Verify that the Rated Voltage parameter (FUN 05, P66) is set correctly.

    Check input supply for open fuses or open connections.

    F23 Low Line L3-L1

    On medium voltage systems, verify wiring of the voltage feedback measurement circuit.

  • 42 IOMM Starter

    Code Description Detailed Description of Fault / Possible Solutions

    High voltage above the Over voltage Trip Level parameter setting (PFN 07, P30) was detected for longer than the Over/Under Voltage Trip delay time (PFN 09, P32).

    Verify that the actual input voltage level is correct. F24

    High Line L1-L2

    Verify that the Rated Voltage parameter (FUN 05, P66) is set correctly.

    Line power quality problems/ excessive line distortions.

    High voltage above the Over voltage Trip Level parameter setting (PFN 07, P30) was detected for longer than the Over/Under Voltage Trip delay time (PFN 09, P32).

    Verify that the actual input voltage level is correct. F25

    High Line L2-L3

    Verify that the Rated Voltage parameter (FUN 05, P66) is set correctly.

    Line power quality problems/ excessive line distortions.

    High voltage above the Over voltage Trip Level parameter setting (PFN 07, P30) was detected for longer than the Over/Under Voltage Trip delay time (PFN 09, P32).

    Verify that the actual input voltage level is correct. F26

    High Line L3-L1

    Verify that the Rated Voltage parameter (FUN 05, P66) is set correctly.

    Line power quality problems/ excessive line distortions.

    The D3 control has detected the loss of one or more input or output phases when the starter was running. Can also be caused by line power dropouts.

    Check input supply for open fuses.

    Check power supply wiring for open or intermittent connections.

    Check motor wiring for open or intermittent connections.

    On medium voltage systems, verify wiring of the voltage feedback measurement circuit.

    F27 Phase Loss

    Check Gate and Cathode connections to D3 board

    No input voltage was detected for longer than the Inline Configuration time delay parameter setting (I/O 15, P53) when a start command was given to the starter.

    If an inline contactor is being used, verify that the setting of the Inline Configuration time delay parameter (I/O 15, P53) allows enough time for the inline contactor to completely close before the No Line fault occurs.

    Check input supply for open disconnects, open fuses, open circuit breakers, or disconnected wiring.

    Verify that the SCR gate wires are properly connected to the D3 control board.

    F28 No Line

    On medium voltage systems, verify wiring of the voltage feedback measurement circuit.

  • IOMM Starter 43

    Fault Code

    Description Detailed Description of Fault / Possible Solutions

    During operation, the D3 controller detected a very high level of current in one or more phases.

    Check motor wiring for short circuits or ground faults.

    Check motor for short circuits or ground faults.

    Check if power factor or surge capacitors are installed on the motor side of the starter.

    F30

    I.O.C.

    (Instantaneous Overcurrent Current)

    Verify that the motor FLA (QST 01, P1), CT ratio (FUN 03, P68), and burden sw