Upload
truonghanh
View
274
Download
4
Embed Size (px)
Citation preview
Honeywell Process Solutions
SmartLine Pressure Transmitters
ST 700 User’s Manual
34-ST-25-44
Revision 9.0
September 2017
Page ii ST 700 SmartLine Pressure Transmitters User’s Manual Revision 9.0
Copyrights, Notices and Trademarks
© Copyright 2017 by Honeywell, Inc.
Revision 9.0, September 2017
While the information in this document is presented in good faith and believed to be
accurate, Honeywell disclaims any implied warranties of merchantability and fitness for a
particular purpose and makes no express warranties except as may be stated in the written
agreement with and for its customers. In no event is Honeywell liable to anyone for any
indirect, special, or consequential damages. The information and specifications in this
document are subject to change without notice.
Honeywell, TDC 3000, SFC, Smartline, PlantScape, Experion PKS, and TotalPlant are
registered trademarks of Honeywell International Inc. Other brand or product names are
trademarks of their respective owners.
Honeywell Process Solutions 1250 W Sam Houston Pkwy S
Houston, TX 77042
Revision 9.0 ST 700 SmartLine Pressure Transmitters User’s Manual Page iii
About This Manual
This manual is a detailed how to reference for installing, piping, wiring, configuring, starting up,
operating, maintaining, calibrating, and servicing Honeywell’s family of ST 700 SmartLine
Pressure Transmitters, Standard and Basic models.
Users who have a Honeywell ST 700 SmartLine Pressure Transmitter configured for HART
protocol or Honeywell’s Digitally Enhanced (DE) are referred to the ST 700 Series HART/DE
Option User’s Manual, Document # 34-ST-25-47.
Users who have a Honeywell ST 700 SmartLine Pressure Transmitter configured for Fieldbus
operation are referred to the ST 700 Series Fieldbus Option User’s Manual, Document # 34-ST-
25-48.
The configuration of your Transmitter depends on the mode of operation and the options selected
for it with respect to operating controls, displays and mechanical installation. This manual
provides detailed procedures to assist first-time users, and it further includes keystroke
summaries, where appropriate, as quick reference or refreshers for experienced personnel.
To digitally integrate a Transmitter with one of the following systems:
For the Experion PKS, you will need to supplement the information in this document with the
data and procedures in the Experion Knowledge Builder.
For Honeywell’s TotalPlant Solutions (TPS), you will need to supplement the information in
this document with the data in the PM/APM SmartLine Transmitter Integration Manual,
which is supplied with the TDC 3000 book set. (TPS is the evolution of the TDC 3000).
Release Information
ST 700 SmartLine Pressure Transmitter User Manual, Document # 34-ST-25-44,
Revision 1, February, 2013
Revision 2, May, 2013 – Updates to Parts list, Explosionproof Seal class, Fail Safe and Comms
Module procedures.
Revision 3, July 2013 – Control Drawing updated to Rev.D
Revision 4, December 2013 – STG73P Flush Mount
Revision 5, December 2014 – MID and MARINE Approvals added
Revision 6, March 2016 – Standard Display added
Revision 7, May 2016 – Approval updates and EU cert.
Revision 8, December 2016 – Basic models added.
Revision 9, September 2017 – Display enhancements to the Simple Display, Parts list updates
Page iv ST 700 SmartLine Pressure Transmitters User’s Manual Revision 9.0
References
The following list identifies publications that may contain information relevant to the information in
this document.
SmartLine Pressure Transmitter ST 800/ST700 Standard Quick Start Guide, Document
# 34-ST-25-36
SmartLine Pressure Transmitter ST 700 Basic Quick Start Guide, Document # 34-ST-25-57
ST 800 & ST 700 Pressure Transmitter with HART Safety Manual, # 34-ST-25-37
ST 700 SmartLine Pressure Transmitter HART/DE Option User’s Manual, Document
# 34-ST-25-47
ST 700 FF Transmitter with FOUNDATION Fieldbus Option Installation & Device Reference Guide,
Document # 34-ST-25-48
MC Tookit User Manual, for 400 or later, Document # 34-ST-25-20
PM/APM Smartline Transmitter Integration Manual, Document # PM 12-410
ST 800 & ST 700 Series Pressure, Analog, HART and DE Communications form, Honeywell drawing
50049892
Smart Field Communicator Model STS 103 Operating Guide, Document # 34-ST-11-14
Patent Notice
The Honeywell ST 700 SmartLine Pressure Transmitter family is covered by one or more of the
following U. S. Patents: 5,485,753; 5,811,690; 6,041,659; 6,055,633; 7,786,878; 8,073,098; and other
patents pending.
Support and Contact Information
For Europe, Asia Pacific, North and South America contact details, refer to the back page of this
manual or the appropriate Honeywell Solution Support web site:
Honeywell Corporate www.honeywellprocess.com
Honeywell Process Solutions www.honeywellprocess.com/pressue-transmitters/
Training Classes http://www.honeywellprocess.com/en-US/training
Telephone and Email Contacts
Area Organization Phone Number
United States and
Canada Honeywell Inc.
1-800-343-0228 Customer Service
1-800-423-9883 Global Technical Support
Global Email
Support
Honeywell Process
Solutions [email protected]
Revision 9.0 ST 700 SmartLine Pressure Transmitters User’s Manual Page v
Symbol Descriptions and Definitions
The symbols identified and defined in the following table may appear in this document.
Symbol Definition
ATTENTION: Identifies information that requires special consideration.
TIP: Identifies advice or hints for the user, often in terms of performing a task.
CAUTION Indicates a situation which, if not avoided, may result in equipment or work (data) on the system being damaged or lost, or may result in the inability to properly operate the process.
CAUTION: Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices.
CAUTION symbol on the equipment refers the user to the product manual for additional information. The symbol appears next to required information in the manual.
WARNING: Indicates a potentially hazardous situation, which, if not avoided, could result in serious injury or death.
WARNING symbol on the equipment refers the user to the product manual for additional information. The symbol appears next to required information in the manual.
WARNING, Risk of electrical shock: Potential shock hazard where HAZARDOUS LIVE voltages greater than 30 Vrms, 42.4 Vpeak, or 60 VDC may be accessible.
ESD HAZARD: Danger of an electro-static discharge to which equipment may be sensitive. Observe precautions for handling electrostatic sensitive devices.
Protective Earth (PE) terminal: Provided for connection of the protective earth (green or green/yellow) supply system conductor.
Functional earth terminal: Used for non-safety purposes such as noise immunity improvement. Note: This connection shall be bonded to Protective Earth at the source of supply in accordance with national local electrical code requirements.
Earth Ground: Functional earth connection. Note: This connection shall be bonded to Protective Earth at the source of supply in accordance with national and local electrical code requirements.
Chassis Ground: Identifies a connection to the chassis or frame of the equipment shall be bonded to Protective Earth at the source of supply in accordance with national and local electrical code requirements.
continued
Page vi ST 700 SmartLine Pressure Transmitters User’s Manual Revision 9.0
Symbol Description
The Factory Mutual®: Approval mark means the equipment has been rigorously tested and certified to be reliable.
The Canadian Standards mark means the equipment has been tested and meets applicable standards for safety and/or performance.
The Ex mark means the equipment complies with the requirements of the European standards that are harmonised with the 94/9/EC Directive (ATEX Directive, named after the French "ATmosphere EXplosible").
Revision 9.0 ST 700 SmartLine Pressure Transmitters User’s Manual Page vii
Contents Copyrights, Notices and Trademarks ..................................................................................................... ii 1. ST 700 Transmitter Series .............................................................................................................. 1
1.1 Overview ................................................................................................................................ 1 2. Introduction to the ST 700 Standard Transmitter ........................................................................... 3
2.1 Features and Options .............................................................................................................. 3 2.1.1 Physical Characteristics .................................................................................................. 4 2.1.2 Functional Characteristics .............................................................................................. 5
2.2 ST 700 Standard Transmitter Nameplate ............................................................................... 5 2.3 Safety Certification Information ............................................................................................. 6 2.4 Transmitter Adjustments ........................................................................................................ 6 2.5 Display Options –Standard Display ....................................................................................... 6 2.6 Optional Integrated Two-Button Assembly (Standard Display) ............................................ 7
3. Application Design for the ST 700 Standard Transmitter ............................................................. 8 3.1 Overview ................................................................................................................................ 8 3.2 Accuracy ................................................................................................................................. 8
3.2.1 Diagnostic Messages ...................................................................................................... 8 3.3 Safety ...................................................................................................................................... 9
3.3.1 Safety Integrity Level (SIL) ........................................................................................... 9 4. Installation and Startupfor the ST 700 Standard Transmitter ....................................................... 10
4.1 Installation Site Evaluation ................................................................................................... 10 4.2 Honeywell MC Toolkit......................................................................................................... 10 4.3 Display Installation Precautions ........................................................................................... 10 4.4 Mounting ST 700 Standard Transmitters ............................................................................. 11
4.4.1 Summary....................................................................................................................... 11 4.4.2 Flush mounting - ST 700 Standard Transmitter ........................................................... 12 4.4.3 Mounting Dimensions .................................................................................................. 12 4.4.4 Bracket Mounting Procedure ........................................................................................ 13 4.4.5 Mounting Transmitters with Small Absolute or Differential Pressure Spans .............. 15 4.4.6 Flange Mounting .......................................................................................................... 16 4.4.7 Remote Diaphragm Seal Mounting Information .......................................................... 17
4.5 Piping the ST 700 Standard Transmitter .............................................................................. 18 4.5.1 Piping Arrangements .................................................................................................... 18 4.5.2 Transmitter Location .................................................................................................... 19 4.5.3 General Piping Guidelines ............................................................................................ 19 4.5.4 Procedure to Install Flange Adapters ............................................................................ 19
4.6 Wiring the ST 700 Standard Transmitter ............................................................................. 20 4.6.1 Overview ...................................................................................................................... 20 4.6.2 Digital System Integration Information ........................................................................ 22 4.6.3 Wiring Variations ......................................................................................................... 22 4.6.4 Wiring Procedure .......................................................................................................... 22 4.6.5 Lightning Protection ..................................................................................................... 23 4.6.6 Supply Voltage Limiting Requirements ....................................................................... 23 4.6.7 Process Sealing ............................................................................................................. 23 4.6.8 Explosion-Proof Conduit Seal ...................................................................................... 23
4.7 Startup – ST 700 Standard Transmitter ................................................................................ 24 4.7.1 Overview ...................................................................................................................... 24 4.7.2 Startup Tasks ................................................................................................................ 24 4.7.3 Output Check Procedures ............................................................................................. 24 4.7.4 Constant Current Source Mode Procedure ................................................................... 25
Page viii ST 700 SmartLine Pressure Transmitters User’s Manual Revision 9.0
5. Operation_ST 700 Standard Transmitter ..................................................................................... 26 5.1 Overview .............................................................................................................................. 26 5.2 Three-Button Operation ....................................................................................................... 26
5.2.1 The Basic Display Menu .............................................................................................. 27 5.2.2 Data Entry .................................................................................................................... 31 5.2.3 Editing a Numeric value .............................................................................................. 31 5.2.4 Selecting a new setting from a list of choices .............................................................. 31
5.3 Two-Button Operation ......................................................................................................... 32 5.3.1 The Standard Display Menu ........................................................................................ 32 5.3.2 Standard Display Abbreviations: ................................................................................. 36 5.3.3 Data Entry .................................................................................................................... 37 5.3.4 Editing a Numeric value .............................................................................................. 37 5.3.5 Selecting a new setting from a list of choices .............................................................. 37
5.4 Basic and Standard Display Operations ............................................................................... 38 5.4.1 Editing a Numeric value .............................................................................................. 38 5.4.2 Selecting a new setting from a list of choices .............................................................. 38
5.5 Three Button Operation with no Display Installed .............................................................. 39 5.5.1 Zero Adjustment .......................................................................................................... 39 5.5.2 Span Adjustment .......................................................................................................... 39
5.6 Changing the Default Failsafe Direction.............................................................................. 40 5.6.1 DE and Analog Differences ......................................................................................... 40 5.6.2 Procedure to Establish Failsafe Operation ................................................................... 40
5.7 Monitoring the Basic and Standard Displays for the ST 700 Standard Transmitter ........... 43 5.7.1 Basic Display_ST 700 Standard Transmitter - ............................................................. 43 5.7.2 Standard Display_ST 700 Standard Transmitter - ....................................................... 43
6. Maintenance_ST 700 Standard Transmitter................................................................................. 45 6.1 Overview .............................................................................................................................. 45 6.2 Preventive Maintenance Practices and Schedules ................................................................ 45 6.3 Inspecting and Cleaning Barrier Diaphragms ...................................................................... 45 6.4 Replacing the Communication Module ............................................................................... 48 6.5 Replacing the Meter Body ................................................................................................... 50
7. Calibration for the ST 700 Standard Transmitter ......................................................................... 54 7.1 Recommendations for Transmitter Calibration .................................................................... 54 7.2 Calibration Procedures ......................................................................................................... 54
8. Troubleshooting on the ST 700 Standard Transmitter ................................................................. 55 8.1 Overview .............................................................................................................................. 55 8.2 Critical Diagnostics Screens ................................................................................................ 55
8.2.1 Fault Conditions and Recommended Corrective Actions – Basic Display .................. 55 8.2.2 Fault Conditions and Recommended Corrective Actions – Standard Display ........... 56
9. Parts List_ST 700 Standard Transmitter ...................................................................................... 57 9.1 Overview .............................................................................................................................. 57
10. Introduction_ST 700 Basic Transmitter ................................................................................... 73 10.1 Overview .............................................................................................................................. 73 10.2 Features and Options ............................................................................................................ 73
10.2.1 Physical Characteristics ............................................................................................... 74 10.2.2 Functional Characteristics ............................................................................................ 75
10.3 ST 700 Transmitter Nameplate ............................................................................................ 75 10.4 Safety Certification Information .......................................................................................... 76 10.5 Transmitter Adjustments ...................................................................................................... 76 10.6 Display Options –Standard Display ..................................................................................... 76 10.7 Optional Integrated two-Button Assembly (Standard Display) ........................................... 77
Revision 9.0 ST 700 SmartLine Pressure Transmitters User’s Manual Page ix
11. Application Design_ST 700 Basic Transmitter ........................................................................ 78 11.1 Overview .............................................................................................................................. 78 11.2 Accuracy ............................................................................................................................... 78
11.2.1 Diagnostic Messages .................................................................................................... 78 11.3 Safety .................................................................................................................................... 78
11.3.1 Safety Integrity Level (SIL) ......................................................................................... 78 12. Installation and Startup_ST 700 Basic Transmitter .................................................................. 79
12.1 Installation Site Evaluation ................................................................................................... 79 12.2 Honeywell MC Toolkit......................................................................................................... 79 12.3 Display Installation Precautions ........................................................................................... 79 12.4 Mounting_ST 700 Basic Transmitter ................................................................................... 80
12.4.1 Summary....................................................................................................................... 80 12.5 Flush mounting_ST 700 Basic Transmitter .......................................................................... 81
12.5.1 Mounting Dimensions, ST 700 Basic Transmitter ....................................................... 81 12.5.2 Bracket Mounting Procedure for ST 700 Basic Transmitter, ....................................... 82 12.5.3 Mounting Transmitters with Small Absolute or Differential Pressure Spans .............. 84 12.5.4 Flange Mounting_ST 700 Basic Transmitter ............................................................... 85 12.5.5 Remote Diaphragm Seal Mounting Information_ST 700 Basic Transmitter, .............. 86
12.6 Piping the ST 700 Basic Transmitter .................................................................................... 87 12.6.1 Piping Arrangements .................................................................................................... 87 12.6.2 Suggestions for Transmitter Location .......................................................................... 88 12.6.3 General Piping Guidelines ............................................................................................ 88 12.6.4 Procedure to Install Flange Adapters ............................................................................ 88
12.7 Wiring an ST 700 Basic Transmitter .................................................................................... 89 12.7.1 Overview ...................................................................................................................... 89 12.7.2 Digital System Integration Information ........................................................................ 91 12.7.3 Wiring Variations ......................................................................................................... 91 12.7.4 Wiring Procedure .......................................................................................................... 91 12.7.5 Lightning Protection ..................................................................................................... 92 12.7.6 Supply Voltage Limiting Requirements ....................................................................... 92 12.7.7 Process Sealing ............................................................................................................. 92 12.7.8 Explosion-Proof Conduit Seal ...................................................................................... 92
12.8 Startup .................................................................................................................................. 93 12.8.1 Overview ...................................................................................................................... 93 12.8.2 Startup Tasks ................................................................................................................ 93 12.8.3 Output Check Procedures ............................................................................................. 93 12.8.4 Constant Current Source Mode Procedure ................................................................... 94
13. Operation_ST 700 Basic Transmitter ....................................................................................... 95 13.1 Overview .............................................................................................................................. 95 13.2 External Two-Button Operation ........................................................................................... 95
13.2.1 The Standard Display Menu ......................................................................................... 96 13.2.2 Standard Display Abbreviations: ................................................................................ 100 13.2.3 Data Entry ................................................................................................................... 101 13.2.4 Editing a Numeric value ............................................................................................. 101 13.2.5 Selecting a new setting from a list of choices ............................................................ 101
13.3 Two Button Operation with no Display Installed ............................................................... 102 13.3.1 Zero Adjustment ......................................................................................................... 102 13.3.2 Span Adjustment ........................................................................................................ 102 13.3.3 Zero Correction .......................................................................................................... 102
13.4 Changing the Default Failsafe Direction ............................................................................ 103 13.4.1 Procedure to Establish Failsafe Operation .................................................................. 103
Page x ST 700 SmartLine Pressure Transmitters User’s Manual Revision 9.0
13.5 Monitoring the Standard Displays ..................................................................................... 105 13.5.1 Standard Display ........................................................................................................ 105
14. Maintenance_ST 700 Basic Transmitter ................................................................................ 106 14.1 Overview ............................................................................................................................ 106 14.2 Preventive Maintenance Practices and Schedules .............................................................. 106 14.3 Inspecting and Cleaning Barrier Diaphragms .................................................................... 106 14.4 Replacing the Communication Module ............................................................................. 109 14.5 Replacing the Meter Body ................................................................................................. 111
15. Calibration_ST 700 Basic Transmitter .................................................................................. 115 15.1 Recommendations for Transmitter Calibration .................................................................. 115 15.2 Calibration Procedures ....................................................................................................... 115
16. Troubleshooting_ST 700 Basic Transmitter .......................................................................... 116 16.1 Overview ............................................................................................................................ 116 16.2 Critical Diagnostics Screens .............................................................................................. 116
16.2.1 Fault Conditions and Recommended Corrective Actions – Standard Display ......... 116 17. Parts List_ST 700 Basic Transmitter ..................................................................................... 117
17.1 Overview ............................................................................................................................ 117 Appendix A - PRODUCT CERTIFICATIONS for the ST 700 Standard and Basic Transmitter 132 Glossary ......................................................................................................................................... 148 INDEX ........................................................................................................................................... 149
Revision 9.0 ST 700 SmartLine Pressure Transmitters User’s Manual Page xi
List of Figures Figure 1 – ST 700 Standard Transmitter Major Assemblies .................................................................. 4 Figure 2 – ST 700 Standard Transmitter Electronics Housing Components .......................................... 4 Figure 3 –ST 700 Standard Transmitter - Typical Name Plate .............................................................. 5 Figure 4 – ST 700 Standard Transmitter - Typical Bracket and Flange Mounted Installations ........... 11 Figure 5 - ST 700 Standard Transmitter - Typical Flush Mounted Installation ................................... 12 Figure 6 – ST 700 Standard Transmitter - Angle Mounting Bracket Secured to a Horizontal or
Vertical Pipe ......................................................................................................................................... 13 Figure 7 – ST 700 Standard Transmitter - Inline Model Mounted to an Optional Bracket .................. 14 Figure 8 – ST 700 Standard Transmitter - Rotating the Electronics Housing ...................................... 14 Figure 9 – ST 700 Standard Transmitter - Using a Spirit Balance to Level a Transmitter .................. 15 Figure 10 – ST 700 Standard Transmitter - Tank-Flange Mounted Transmitter.................................. 16 Figure 11 – ST 700 Standard Transmitter - Representative Remote Diaphragm Seal Transmitter
Installation ............................................................................................................................................ 17 Figure 12 – ST 700 Standard Transmitter - Typical 3-Valve Manifold with Blow-Down Piping ....... 18 Figure 13 – ST 700 Standard Transmitter - Flange Adapter Removal and Replacement .................... 20 Figure 14 – ST 700 Standard Transmitter - Operating Ranges ............................................................ 21 Figure 15 – ST 700 Standard Transmitter - 3-Screw Terminal Board and Grounding Screw ............. 21 Figure 16 – ST 700 Standard Transmitter - Current Loop Test Connections ...................................... 25 Figure 17 – ST 700 Standard Transmitter - Three-Button Option ....................................................... 26 Figure 18 – ST 700 Standard Transmitter - Two-Button Option ......................................................... 32 Figure 19 – ST 700 Standard Transmitter - Locating the Failsafe and Write Protect Jumpers ............ 41 Figure 20 – ST 700 Standard Transmitter - Basic Display with Process Variable Format .................. 43 Figure 21 – ST 700 Standard Transmitter - Standard Display with Process Variable Format ............. 44 Figure 22 – ST 700 Standard Transmitter - DP Transmitter Head Disassembly ................................. 46 Figure 23 – ST 700 Standard Transmitter - Head Bolt Tightening Sequence ...................................... 47 Figure 24 – ST 700 Standard Transmitter - PWA Replacement .......................................................... 48 Figure 25 – ST 700 Standard Transmitter - Disassembly for Meter Body Replacement ..................... 50 Figure 26 – ST 700 Standard Transmitter - Hardware Location to Remove the Meter Assembly ...... 51 Figure 27 – ST 700 Standard Transmitter - Meter Body Reassembly ................................................. 52 Figure 28 – ST 700 Standard Transmitter - Head Bolt Tightening Sequence ...................................... 52 Figure 29 – ST 700 Standard Transmitter - Angle and Flat Bracket Parts ........................................... 58 Figure 30 – ST 700 Standard Transmitter - Electronic Housing, Display End .................................... 60 Figure 31 – ST 700 Standard Transmitter - Electronic Housing, Terminal Block End ....................... 61 Figure 32 – ST 700 Standard Transmitter - Major Assemblies ............................................................ 62 Figure 33 - ST 700 Standard Transmitter - ST 700 Models STD720, 730, 770 .................................. 65 Figure 34 – ST 700 Standard Transmitter - STG730, 740, 770 and STA722, 740 Transmitter Body . 68 Figure 35 – ST 700 Standard Transmitter - Inline Gauge and Inline Atmospheric Meter Body Bodies
.............................................................................................................................................................. 69 Figure 36 – ST 700 Standard Transmitter - Extended Flange Design .................................................. 70 Figure 37 - ST 700 Standard Transmitter - Flush Flange Design......................................................... 70 Figure 38 - ST 700 Standard Transmitter - Pseudo Flange Design ...................................................... 71 Figure 39 – ST 700 Standard Transmitter - Remote Seal Diaphragm .................................................. 71 Figure 40 - ST 700 Standard Transmitter - Flush Mount Meter Body. ................................................ 72 Figure 41 – ST 700 Basic Transmitter - Major Assemblies ................................................................. 74 Figure 42 – ST 700 Basic transmitter Electronics Housing Components ............................................ 74 Figure 43 – ST 700 Basic Transmitter - Name Plate ............................................................................ 75 Figure 44 – ST 700 Basic Transmitter - Typical Bracket Mounted and Flange Mounted Installations
.............................................................................................................................................................. 80 Figure 45 - ST 700 Basic Transmitter - Typical Flush Mounted Transmitter Installation ................... 81
Page xii ST 700 SmartLine Pressure Transmitters User’s Manual Revision 9.0
Figure 46 – ST 700 Basic Transmitter - Angle Mounting Bracket Secured to a Horizontal or Vertical
Pipe ...................................................................................................................................................... 82 Figure 47 – ST 700 Basic Transmitter - Inline Model Mounted to an Optional Bracket .................... 83 Figure 48 – ST 700 Basic Transmitter - Rotating the Electronics Housing ......................................... 83 Figure 49 – ST 700 Basic Transmitter, using a Spirit Balance to Level a Transmitter ....................... 84 Figure 50 – ST 700 Basic Transmitter, Tank-Flange Mounted Transmitter ........................................ 85 Figure 51 – ST 700 Basic Transmitter - Representative Remote Diaphragm Seal Transmitter
Installation............................................................................................................................................ 86 Figure 52– ST 700 Basic Transmitter - Typical 3-Valve Manifold with Blow-Down Piping ............. 87 Figure 53 – ST 700 Basic Transmitter - Flange Adapter Removal and Replacement ......................... 89 Figure 54 – ST 700 Basic Transmitter - Operating Ranges ................................................................. 89 Figure 55 – ST 700 Basic Transmitter - 3-Screw Terminal Board and Grounding Screw .................. 90 Figure 56 – ST 700 Basic Transmitter - Current Loop Test Connections ........................................... 94 Figure 57 – ST 700 Basic Transmitter - Two-Button Option .............................................................. 95 Figure 58 – ST 700 Basic Transmitter - Two-Button Option .............................................................. 96 Figure 59 – ST 700 Basic Transmitter - Locating the Failsafe and Write Protect Jumpers ............... 103 Figure 60 – ST 700 Basic Transmitter - Standard Display with Process Variable Format ................ 105 Figure 61 – ST 700 Basic Transmitter - DP Transmitter Head Disassembly .................................... 107 Figure 62 – ST 700 Basic Transmitter - Head Bolt Tightening Sequence ......................................... 108 Figure 63 – ST 700 Basic Transmitter - PWA Replacement ............................................................. 109 Figure 64 – ST 700 Basic Transmitter - Disassembly for Meter Body Replacement ........................ 111 Figure 65 – ST 700 Basic Transmitter - Hardware Location to Remove the Meter Assembly ......... 112 Figure 66 – ST 700 Basic Transmitter - Meter Body Reassembly .................................................... 113 Figure 67 – ST 700 Basic Transmitter - Head Bolt Tightening Sequence ......................................... 113 Figure 68 – ST 700 Basic Transmitter - Angle and Flat Bracket Parts (refer to Table 43) ............... 118 Figure 69 – ST 700 Basic Transmitter - Electronic Housing, Display End ....................................... 120 Figure 70 – ST 700 Basic Transmitter - Electronic Housing, Terminal Block End .......................... 121 Figure 71 – ST 700 Basic Transmitter - Major Assemblies............................................................... 122 Figure 72 - ST 700 Basic Transmitter Models STD725, 735, 775 – refer to Table 45 ...................... 125 Figure 73 – ST 700 Basic Transmitter - STG735, 745, 775 and STA725, 745 Transmitter Body .... 127 Figure 74 – ST 700 Basic Transmitter - Inline Gauge and Inline Atmospheric Meter Body Bodies 128 Figure 75 – ST 700 Basic Transmitter - Extended Flange Design .................................................... 129 Figure 76 - ST 700 Basic Transmitter - Flush Flange Design ........................................................... 129 Figure 77 - ST 700 Basic Transmitter - Pseudo Flange Design ......................................................... 130 Figure 78 – ST 700 Basic Transmitter - Remote Seal Diaphragm .................................................... 130 Figure 79 - ST 700 Basic Transmitter - Series 700 Flush Mount Meter Body. ................................. 131
Revision 9.0 ST 700 SmartLine Pressure Transmitters User’s Manual Page xiii
List of Tables Table 1 – ST 700 Standard andf Basic model types ...................................................................................... 2 Table 2 – Features and Options_ST 700 Standard transmitter ....................................................................... 3 Table 3 – Available Display Characteristics .................................................................................................. 6 Table 4 – ST 700 Standard transmitter - Basic Display Diagnostics Messages ............................................. 9 Table 5 - ST 700 Standard Transmitter - Mounting Bracket procedure....................................................... 13 Table 6 – ST 700 Standard Transmitter - Flange Mounting Guidelines ...................................................... 17 Table 7 – ST 700 Standard Transmitter - Remote Diaphragm Mounting Details ........................................ 17 Table 8 – ST 700 Standard Transmitter - Suggested Connection Locations ............................................... 19 Table 9 – Three-Button Option Functions ................................................................................................... 27 Table 10 – The Basic Display Menus .......................................................................................................... 28 Table 11 – Three-Button Data Entry ............................................................................................................ 31 Table 12 – ST 700 Standard Transmitter: Standard Display Menus ............................................................ 33 Table 13 – ST 700 Standard Transmitter - Extended Display Menu ........................................................... 35 Table 14 – The Standard Display abbreviations .......................................................................................... 36 Table 15 –Two-Button Data Entry ............................................................................................................... 37 Table 16 – ST 700 Standard Transmitter - Hart and DE Failsafe and Write Protect Jumpers ..................... 41 Table 17 – ST 700 Standard Transmitter - Fieldbus Simulation and Write Protect Jumpers ...................... 42 Table 18 – Head Bolt Torque Values ........................................................................................................... 47 Table 19 – ST 700 Standard Transmitter - Fault Conditions and Recommended Corrective Actions. ....... 55 Table 20 – ST 700 Standard Transmitter - Fault Conditions and Recommended Corrective Actions. ....... 56 Table 21 – ST 700 Standard Transmitter - Summary List of Recommended Spare Parts ........................... 57 Table 22 – ST 700 Standard Transmitter - Angle and Flat Bracket Parts .................................................... 59 Table 23 – ST 700 Standard Transmitter Major Assemblies ....................................................................... 60 Table 24 – ST 700 Standard Transmitter Models STD720, 730 & 770 ...................................................... 63 Table 25 – ST 700 Standard Transmitter - Parts for STG730, 740, 770 and STD720, 730, 770 and
STA722, 740 Transmitter Body ................................................................................................................... 66 Table 26 - ST 700 Standard Transmitter - Inline Gauge and Inline Atmospheric Meter Body Parts .......... 69 Table 27 – ST 700 Standard Transmitter - Flange-Mounted Meter Body Parts – STF724, 732 ................. 70 Table 28 – ST 700 Standard Transmitter - Flush Mount Meter Body Parts ................................................ 72 Table 29 – ST 700 Basic Transmitter - Features and Options ..................................................................... 73 Table 30 – ST 700 Basic Transmitter - Available Display Characteristics .................................................. 76 Table 31 - ST 700 Basic Transmitter - Mounting Bracket procedure .......................................................... 82 Table 32 – ST 700 Basic Transmitter, Flange Mounting Guidelines ........................................................... 86 Table 33 – ST 700 Basic Transmitter - Remote Diaphragm Mounting Details ........................................... 86 Table 34 – ST 700 Basic Transmitter - Suggested Connection Locations ................................................... 88 Table 35 – ST 700 Basic Transmitter: Standard Display Menus ................................................................. 97 Table 36 – ST 700 Basic Transmitter - Extended Display Menu ................................................................ 99 Table 37 – ST 700 Basic Transmitter - The Standard Display abbreviations ............................................ 100 Table 38 – ST 700 Basic Transmitter - Two-Button Data Entry ............................................................... 101 Table 39 – ST 700 Basic Transmitter - HART Failsafe and Write Protect Jumpers ................................. 104 Table 40 – Head Bolt Torque Values ......................................................................................................... 108 Table 41 – ST 700 Basic Transmitter - Fault Conditions and Recommended Corrective Actions. ........... 116 Table 42 – ST 700 Basic Transmitter - Summary List of Recommended Spare Parts .............................. 117 Table 43 – ST 700 Basic Transmitter - Angle and Flat Bracket Parts ....................................................... 119 Table 44 – ST 700 Basic Transmitter - Major Assemblies ........................................................................ 120 Table 45 – ST 700 Basic Transmitter Models STD720, 725, 730, 735, 770, 775 & STG774 .................. 123 Table 46 – ST 700 Basic Transmitter - Parts for STG725, 735, 745, 775, 745 Transmitter Body ............ 126 Table 47 - ST 700 Basic Transmitter - Inline Gauge and Inline Atmospheric Meter Body Parts .............. 128 Table 48 – ST 700 Basic Transmitter - Flange-Mounted Meter Body Parts .............................................. 129 Table 49 – ST 700 Basic Transmitter - Flush Mount Meter Body Parts .................................................... 131
Page xiv ST 700 SmartLine Pressure Transmitters User’s Manual Revision 9.0
Revision 8.0 ST 700 SmartLine Pressure Transmitters User’s Manual Page 1
1. ST 700 Transmitter Series
1.1 Overview SmartLine Pressure Transmitter ST 700 family conists of a series of ST 700 Standard Transmitter
models and a series of ST 700 Basic Transmitter models.
The entire manual is broadly classified in two sections.
The first half of this manual, Sections 2 through 9, are for ST 700 Standard Transmitter model series
and the second half, Sections 10 through 17, are applicable only to ST 700 Basic Transmitter model
series.
Which type of transmitter do I have?
To determine which version you have:
Look at the nameplate on top of the unit shown in Figure 3. Refer to the Model number
If you have a ST 700 Standard Transmitter use Sections 2 through 9.
If you have a ST 700 Basic Transmitter go straight to Sections 10 through 17.
Appendix A - PRODUCT CERTIFICATIONS is applicable for both ST 700 Standard and Basic
Transmitters.
Table 1 below to identify which type of Transmitter you have; Standard or Basic.
The Standard transmitter will have a three button assembly (see Figure 17), the basic Transmitter with
have two button assembly (see Figure 18)
3-button Standard ST 700 Transmitter 2-button Basic ST 700 Transmitter
Page 2 ST 700 SmartLine Pressure Transmitters User’s Manual Revision 9.0
Table 1 – ST 700 Standard andf Basic model types
Transmitter Configuration
Smart Line Pressure ST700
Standard Models Basic Models
Dual head DP STD720/730/770 STD725/735/775
Dual head GP STG730/740/770 STG735/745/775
Inline GP STG73L/74L/77L/78L/79L STG73S/74S/77S/78S/79S
Inline flush GP STG73P STG73SP
Dual head AP STA722/740 STA725/745
Inline AP STA72L/74L/77L STA72S/74S/77S
Flush flanged level STF724/732 STF725/735
Pseudo flanged level STF72F/73F STF72P/73P
Remote seal DP/GP STR73D/74G STR735D/745G
Revision 9.0 ST 700 SmartLine Pressure Transmitters User’s Manual Page 3
,
2. Introduction to the ST 700 Standard Transmitter This section is an introduction to the physical and functional characteristics Honeywell’s family of
the ST 700 Standard Transmitters.
2.1 Features and Options The ST 700 Standard Transmitter is available in a variety of models for measuring Differential
Pressure (DP), Gauge Pressure (GP), and Absolute Pressure (AP). Table 2 lists the protocols, human
interface (HMI), materials, approvals, and mounting bracket options.
Table 2 – Features and Options_ST 700 Standard transmitter
Feature/Option Standard/Available Options
Communication Protocols HART version 7, Digitally Enhanced (DE), Fieldbus
Human-Machine Interface (HMI) Options (Basic Display/Standard Display)
Basic Digital Display:
Three-button programming (optional)
Basic display language: English only
Standard Display (HART only):
Two integral buttons programming (optional)
Standard display language: English only
Two-mode operations: PV display and Menu Navigation
Calibration Single
Approvals for details go to page 132 FM, CSA, ATEX, IECEx, SAEx, INMETRO, NEPSI, GOST and MARINE
Mounting Brackets Angle/flat carbon steel/304 and 316 stainless steel, Marine 304 stainless steel, 316 Stainless Steel
Integration Tools Experion
The three-button option is available for the Basic Display.
The two-button option is available for the Standard Display.
Also, for the Basic Display, the three button reed switch is used only for span & zero correction and not for the Display navigation.
Page 4 ST 700 SmartLine Pressure Transmitters User’s Manual Revision 9.0
2.1.1 Physical Characteristics
As shown in Figure 1, the ST 700 Standard is packaged in two major assemblies: the Electronics
Housing and the Meter Body. The elements in the Electronic Housing respond to setup commands
and execute the software and protocol for the different pressure measurement types. Figure 2 shows
the assemblies in the Electronics Housing with available options.
The Meter Body provides connection to a process system. Several physical interface configurations
are available, as determined by the mounting and mechanical connections, all of which are described
in the Installation section of this manual.
Figure 1 – ST 700 Standard Transmitter Major Assemblies
Figure 2 – ST 700 Standard Transmitter Electronics Housing Components
Revision 9.0 ST 700 SmartLine Pressure Transmitters User’s Manual Page 5
2.1.2 Functional Characteristics
The ST 700 Standard Transmitter measures process pressure and provides a proportional analog
4 to 20mA output to the measured process variable (PV). Available output communication protocols
include Honeywell Digitally Enhanced (DE), HART, and FOUNDATIONTM Fieldbus.
The Standard display is only available on HART transmitters.
An optional 3-button assembly is available to set up and make adjustments to the Transmitter. In
addition, a Honeywell Multi-Communication (MC) Toolkit (not supplied with the Transmitter) can
facilitate setup and adjustment procedures. Certain adjustments can be made through an Experion
Station or a Universal Station if the Transmitter is digitally integrated with Honeywell’s Experion or
TPS/TDC 3000 control system.
The Standard Display Menu is implemented as one long single-level menu and will “wrap around”
when it reaches the start or end of the menu. The Standard Display uses an optional two-button
assembly to set up and make adjustments to the Transmitter.
2.2 ST 700 Standard Transmitter Nameplate The Transmitter nameplate mounted on the bottom of the electronics housing (see Figure 1) lists its
model number, physical configuration, electronics options, accessories, certifications, and
manufacturing specialties. Figure 3 is an example of a typical Gauge Pressure (GP) or Atmospheric
Pressure (AP) Transmitter name plate. The model number format consists of a Key Number with
several table selections. The Differential Pressure (DP), Absolute Pressure (AP), and Gauge Pressure
(GP) name plates are essentially the same. The DP model provides one additional entry (7 vs. 6) in
the Meter Body Selections (Table I) to accommodate the static pressure rating.
Figure 3 –ST 700 Standard Transmitter - Typical Name Plate
You can readily identify the series and basic Transmitter type from the third and fourth digits in the
key number. The letter in the third digit represents one of these basic transmitter types:
A = Absolute Pressure D = Differential Pressure F = Flange Mounted
G = Gauge Pressure R = Remote Seals
For a complete selection breakdown, refer to the appropriate Specification and Model Selection
Guide provided as a separate document.
Page 6 ST 700 SmartLine Pressure Transmitters User’s Manual Revision 9.0
2.3 Safety Certification Information An “approvals” name plate is located on the bottom of the Electronics Assembly; see Figure 1for
exact location. The approvals name plate contains information and service marks that disclose the
Transmitter compliance information.
Refer to Section Appendix A in this document for safety certification requirements and details.
2.4 Transmitter Adjustments Zero and Span adjustments are possible in ST 700 Standard Transmitter with the optional 3 button
and two-button assemblies.
You can also use the Honeywell MC Toolkit or other third-party hand-held configurator to make
adjustments to the ST 700 Standard Transmitter. Alternately, certain adjustments can be made
through the Experion or Universal Station, if the Transmitter is digitally integrated with a Honeywell
Experion or TPS system.
2.5 Display Options –Standard Display
Table 3 – Available Display Characteristics
Basic Display Suitable for basic process needs
360o rotation in 90o Increments
2 lines, 16 characters
Standard units of measurement: Pa, KPa, MPa, KGcm2, TORR, ATM, inH2O, mH2O, bar, mbar, inHg, FTH2O, mmH2O, MMHG, & PSI
Diagnostic messaging
Square root output indications
Standard Display 360o rotation in 90o Increments
2 lines, 8 characters
Standard units of measurement: Pa, KPa, MPa, KGcm2, TORR, ATM, inH2O, mH2O, bar, mbar, inHg, FTH2O, mmH2O, MMHG, Flow Units (DP models only) ,PSI , cmH2O and mH2O
Diagnostic messaging
Revision 9.0 ST 700 SmartLine Pressure Transmitters User’s Manual Page 7
2.6 Optional Integrated Two-Button Assembly (Standard Display) The Standard Display does not support all the transmitter configuration parameters and has limited
features.
The optional Integrated two-Button Assembly for the Standard Display provides the following
features and capabilities:
Menu and enter key functionality.
With the menu-driven display:
o Comprehensive on-screen menu for navigation.
o Transmitter configuration: enter LRV, enter URV and Loop Test.
o Transmitter calibration
o Display configuration (contrast only)
o Set zero and span parameters.
If you are using the optional external two-button assembly with the Standard
Display then you can perform all the above operations without removing external
glass cap using the external buttons
Lower range value (LRV): A display parameter (Standard display), which allows users to enter the measuring value for which the analog output will be scaled to 4mA.
Upper range value (URV): A display parameter (Standard display), which allows users to enter the measuring value for which the analog output will be scaled to 20mA.
Page 8 ST 700 SmartLine Pressure Transmitters User’s Manual Revision 9.0
3. Application Design for the ST 700 Standard Transmitter
3.1 Overview This section discusses the considerations involved with deploying a Honeywell ST 700 Standard
Transmitter in a process system. The following areas are covered:
Safety
Input and output data
Reliability
Environmental limits
Installation considerations
Operation and maintenance\
Repair and replacement
3.2 Accuracy The ST 700 Standard Transmitter measures the gauge, differential, or absolute pressure of a process
and reports the measurement to a receiving device.
3.2.1 Diagnostic Messages
Transmitter standard diagnostics are reported in the two basic categories listed in Table 4. Problems
detected as critical diagnostics drive the analog output to the programmed burnout level. Problems
detected as non-critical diagnostics may affect performance without driving the analog output to the
programmed burnout level. Informational messages (not listed in Table 4) report various Transmitter
status or setting conditions. The messages listed in Table 4 are specific to the Transmitter, exclusive
of those associated with HART and DE protocols. HART and DE diagnostic messages are listed and
described in the ST 700 SmartLine Pressure Transmitter HART/DE Option User Manual, Document
# 34-ST-25-47.
The Standard Display is only available on HART transmitters
The Standard Display only displays critical diagnostics (Meter Body Fault, Electronics Module Fault and Meter Body Communication Fault). Non-critical diagnostics are not displayed.
Revision 9.0 ST 700 SmartLine Pressure Transmitters User’s Manual Page 9
Table 4 – ST 700 Standard transmitter - Basic Display Diagnostics Messages
Critical Diagnostics (Failure Conditions)
Non-Critical Diagnostics (Warning Conditions)
Sensor Comm Timeout
Meter Body Critical Failure
Electronic Module Diag Failure
Config Data Corrupt
Meter Body NVM Corrupt
Electronic Module DAC Failure
No DAC Compensation
No Factory Calibration
PV Out of Range
Fixed Current Mode
Sensor Over Temperature
Meter Body Excess Correct
Local Display
Low Supply Voltage
No DAC Calibration
Tamper Alarm
Meter Body Unreliable Comm
Loop Current Noise
AO Out of Range
URV Set Error – Span Config
Button
LRV Set Error – Span Config
Button
3.3 Safety
3.3.1 Safety Integrity Level (SIL)
The ST 700 Standard transmitter has met manufacturer design process requirements of Safety Integrity
Level (SIL) 3. These are intended to achieve sufficient integrity against systematic errors of design by
the manufacturer.
A Safety Instrumented Function (SIF) designed with this product must not be used at a SIL level higher
than the statement, without “prior use” justification by the end user or diverse technology redundancy in
the design.
Refer to the Honeywell SmartLine Safety Manual, Document # 34-ST-25-37, for additional information.
Page 10 ST 700 SmartLine Pressure Transmitters User’s Manual Revision 9.0
4. Installation and Startupfor the ST 700 Standard Transmitter
4.1 Installation Site Evaluation Evaluate the site selected for the ST 700 Standard Transmitter installation with respect to the process
system design specifications and Honeywell’s published performance characteristics for your
particular model. Some parameters that you may want to include in your site evaluation are:
Environmental Conditions:
o Ambient Temperature
o Relative Humidity
Potential Noise Sources:
o Radio Frequency Interference (RFI)
o Electromagnetic Interference (EMI)
Vibration Sources
o Pumps
o Motorized System Devices (e.g., pumps)
o Valve Cavitation
Process Parameters
o Temperature
o Maximum Pressure Rating
4.2 Honeywell MC Toolkit In preparation for post-installation processes, refer to the MC Tookit User Manual, Document
# 34-ST-25-20, for battery conditioning and device operation and maintenance information.
4.3 Display Installation Precautions Temperature extremes can affect display quality. The display can become unreadable at temperature
extremes; however, this is only a temporary condition. The display will again be readable when
temperatures return to within operable limits.
The display update rate may become slower at cold temperature extremes, but as with readability,
normal updating resumes when temperatures are within limits for full operability.
The ST 700 Standard Transmitter should not be operated without the endcap covers on. Covers can be removed temporarily for configuration with buttons or during maintenance/wiring.
The static voltage must be discharged before removing the cover.
Revision 9.0 ST 700 SmartLine Pressure Transmitters User’s Manual Page 11
4.4 Mounting ST 700 Standard Transmitters
4.4.1 Summary
The ST 700 Standard transmitter models, except flush mounts and those with integral flanges, can be
attached to a two-inch (50 millimeters) vertical or horizontal pipe using Honeywell’s optional angle
or flat mounting bracket; alternately you can use your own bracket. Flush-mount models are attached
directly to a process pipe or tank by a one-inch weld nipple. Models with integral flanges are
supported by the flange connection.
Figure 4 shows a typical bracket-mounted and flange-mounted transmitter installations.
Figure 4 – ST 700 Standard Transmitter - Typical Bracket and Flange Mounted Installations
Page 12 ST 700 SmartLine Pressure Transmitters User’s Manual Revision 9.0
4.4.2 Flush mounting - ST 700 Standard Transmitter
To mount a flush mounted model, cut a hole for a 1” standard pipe in the tank or pipe where the
transmitter is to be mounted. Weld the 1” mounting sleeve to the wall of the tank or to the hole cut on
the pipe. Insert the meter body of the transmitter into the mounting sleeve and secure with the locking
bolt. Tighten the bolt to a torque of 6,4 Nm +/- 0,30 Nm (4.7 ft-lbs +/- 0.2 ft.-lbs.). Figure 5 shows a
typical installation for a transmitter with a flush mount on a pipe.
Once the transmitter is mounted, the electronics housing can be rotated to the desired
position. See Figure 8 for details.
ATTENTION: On insulated tanks, remove enough insulation to accommodate the mounting
sleeve.
Figure 5 - ST 700 Standard Transmitter - Typical Flush Mounted Installation
4.4.3 Mounting Dimensions
Refer to Honeywell drawing number 50049930 (Dual Head), 50049931 (In-Line), 50049932 (Flange
Mount) 50049933 (Extended Flange), 50049934 (Remote Seal) and 50049936 (Flush Mount Pressure
Transmitter) for detailed dimensions. Abbreviated overall dimensions are also shown on the
Specification Sheets for the transmitter models. This section assumes that the mounting dimensions
have already been taken into account and the mounting area can accommodate the Transmitter.
Revision 9.0 ST 700 SmartLine Pressure Transmitters User’s Manual Page 13
4.4.4 Bracket Mounting Procedure
If you are using an optional bracket, start with Step 1. For an existing bracket, start with Step 2.
1. Refer to Figure 6. Position the bracket on a 2-inch (50.8mm nominal diameter, 2.38”
(60.4mm) actual OD) for a horizontal or vertical pipe, and install a “U” bolt around the pipe
and through the holes in the bracket. Secure the bracket with the nuts and lock washers
provided.
Figure 6 – ST 700 Standard Transmitter - Angle Mounting Bracket Secured to a Horizontal or
Vertical Pipe
2. Align the appropriate mounting holes in the Transmitter with the holes in the bracket. Use the
bolts and washers provided to secure the Transmitter to the bracket; see the following
variations.
Table 5 - ST 700 Standard Transmitter - Mounting Bracket procedure
Transmitter Type Use Hardware
DP with double-ended process heads and/or remote seals
Alternate mounting holes in the ends of the heads
ST 700 Standard transmitter models only. In-line GP: STG7x0 and STG7xL AP models: STA7xL and STA72x, STA740
The smaller “U” bolt provided to attach the meter body to the bracket. See the following example.
Dual-head GP and AP Mounting holes in the end of the process head.
Example: Inline model mounted to an optional angle bracket. See Figure 7.
Horizontal Pipe
MountingBracket
Nuts andLockwashersNuts and
Lockwashers
U-Bolt
U-Bolt
MountingBracket
Vertical Pipe
Page 14 ST 700 SmartLine Pressure Transmitters User’s Manual Revision 9.0
Figure 7 – ST 700 Standard Transmitter - Inline Model Mounted to an Optional Bracket
3. Loosen the set screw on the outside neck of the Transmitter one (1) full turn.
4. Rotate the Electronics housing a maximum of 180o left or right from the center to the position
you require, and tighten the set screw using a 4mm metric socket head wrench. See the
following example and Figure 8.
Example: Rotating the Electronics Housing
Figure 8 – ST 700 Standard Transmitter - Rotating the Electronics Housing
The mounting position of AP models STA722 and STA72L becomes critical as the Transmitter spans become smaller. A maximum zero shift of 2.5mmHg for these models can result from a mounting position that is rotated 90o from the vertical. A typical zero-shift of 0.12mmHg or 0.20 inH2O can occur for a five (5)-degree rotation from
the vertical.
Revision 9.0 ST 700 SmartLine Pressure Transmitters User’s Manual Page 15
4.4.5 Mounting Transmitters with Small Absolute or Differential Pressure Spans
To minimize positional effects on calibration (zero shift), take the appropriate mounting precautions for the respective Transmitter model. Ensure that the Transmitter is vertical when mounting models STA722 and STA72L. You do this by leveling the Transmitter side-to-side and front-to-back. Figure 9 shows how to level a Transmitter using a spirit level.
Figure 9 – ST 700 Standard Transmitter - Using a Spirit Balance to Level a Transmitter
Page 16 ST 700 SmartLine Pressure Transmitters User’s Manual Revision 9.0
4.4.6 Flange Mounting
Figure 10 shows a typical tank-flange mount installation, with the Transmitter flange mounted to the
pipe on the wall of the tank.
On insulated tanks, remove enough insulaiton to accommodate the flange extension.
When flange-mounting to a tank, note the following:
The End User is responsible for providing a flange gasket and mounting hardware suitable for
the Transmitter service conditions.
To avoid degrading performance in flush-mounted flanged Transmitters, exercise care to
ensure that the internal diameter of the flange gasket does not obstruct the sensing diaphragm.
To prevent performance degradation in extended-mount flanged Transmitters, ensure that
sufficient clearance exists in front of the sensing diaphragm body.
Figure 10 – ST 700 Standard Transmitter - Tank-Flange Mounted Transmitter
Revision 9.0 ST 700 SmartLine Pressure Transmitters User’s Manual Page 17
4.4.7 Remote Diaphragm Seal Mounting Information
The combination of tank vacuum and high pressure capillary head effect should not exceed nine (9) psi (300mmHg) absolute. For insulated tanks, be sure to remove enough insulation to accommodate the flange extension. The end user is responsible for supplying a flange gasket and mounting hardware suitable for the service condition of the Transmitter.
Mount the Transmitter flanges within the limits in Table 6 for the fill fluid in the capillary tubes, with a tank at one (1) atmosphere.
Table 6 – ST 700 Standard Transmitter - Flange Mounting Guidelines
Fill Fluid Mount the Flange…
Silicone 200 Oil <22 feet (6.7 meters) below the Transmitter
Chlorotrifluorethylene (CTFE) <11 feet (3.4 meters) below the Transmitter
Refer to Figure 11 for a representative remote diaphragm seal installation. Mount the Transmitter at a
remote distance determined by the length of the capillary tubing.
Figure 11 – ST 700 Standard Transmitter - Representative Remote Diaphragm Seal Transmitter
Installation
Depending on Transmitter model, connect the remote seal to the tank according to Table 7.
Table 7 – ST 700 Standard Transmitter - Remote Diaphragm Mounting Details
Transmitter Model
Connect the Remote Seal on ….
Variable Head Fixed or Constant Head
STR73D Transmitter High Pressure (HP) Side to tank wall lower flange mounting.
Transmitter Low Pressure (LP) side to tank wall upper flange.
Page 18 ST 700 SmartLine Pressure Transmitters User’s Manual Revision 9.0
4.5 Piping the ST 700 Standard Transmitter
4.5.1 Piping Arrangements
Piping arrangements vary depending upon process measurement requirements and the Transmitter
model. For example, a differential pressure transmitter comes with double-ended process heads with
¼-inch NPT connections, which can be modified to accept ½-inch NPT through optional flange
adapters. Gauge pressure transmitters are available with various connections for direct mounting to a
process pipe.
A ½-inch, schedule 80, steel pipe is commonly used for Transmitter integration into a process system.
Many piping arrangements use a three-valve manifold to connect the process piping to the
Transmitter. A manifold makes it easy to install and remove or re-zero a Transmitter without
interrupting the process. A manifold also accommodates the installation of blow-down valves to clear
debris from pressure lines. Figure 12 represents a typical piping arrangement using a three-valve
manifold and blow-down lines for a differential pressure transmitter being used to measure flow.
Figure 12 – ST 700 Standard Transmitter - Typical 3-Valve Manifold with Blow-Down Piping
Blow-Down
Valve3-Valve
Manifold
To Upstream TapTo Downstream Tap
To Low Pressure
Side of Transmitter
To High Pressure
Side of Transmitter
Blow-Down
Valve
Blow-Down
Piping
To WasteTo Waste
Blow-Down
Piping
21010
Revision 9.0 ST 700 SmartLine Pressure Transmitters User’s Manual Page 19
4.5.2 Transmitter Location
The following are suggested connections based on what is being processed by the system.
Table 8 – ST 700 Standard Transmitter - Suggested Connection Locations
Process Suggested Location Description
Gases Above the gas line. The condensate drains away from the Transmitter.
Liquids Below but near the elevation of the process connection.
This minimizes that static head effect of the condensate.
Level with or above the process connection.
This requires a siphon to protect theTransmitter from process steam. The siphon retains water as a fill fluid.
1. For liquid or steam, the piping should slope a minimum of 25.4mm (1 inch) per 305mm (1 foot).
2. Slope the piping down toward the Transmitter if it is below the process connection to allow
the bubbles to rise back into the piping through the liquid.
3. If the transmitter is located above the process connection, the piping should rise vertically
above the Transmitter. In this case, slope down toward the flow line with a vent valve at the
high point.
4. For gas measurement, use a condensate leg and drain at the low point (freeze protection may
be required here).
ATTENTION Care must be taken when installing transmitters on hot processes. The operating temperature limits for the device (as outlined in Table 5) must not be exceeded. Impulse piping may be used to reduce the temperature of the process that comes
into contact with the transmitter meter body. As a general rule there is a 56C drop (100F) in the temperature of the process for every foot of ½ inch uninsulated piping.
4.5.3 General Piping Guidelines
When measuring fluids that contain suspended solids, install permanent valves at regular
intervals to blow-down piping.
Blow-down all lines on new installations with compressed air or steam, and flush them with
process fluids (where possible) before connecting these lines to the Transmitter Meter body.
Verify that the valves in the blow-down lines are closed tightly after the initial blow-down
procedure and each maintenance procedure thereafter.
4.5.4 Procedure to Install Flange Adapters
The following procedure provides the steps for removing and replacing an optional flange adapter on
the process head. Refer to Figure 13.
This procedure does not require that the Meter body be removed from the Electronics Housing. If flange adapters are being replaced with parts from other kits (for example, process heads), follow the procedures for the kits and incorporate the following procedure.
The threaded hole in each Flange Adapter is offset from center. To ensure proper orientation for re-assembly, note the orientation of the offset relative to each Process Head before removing the adapter.
Page 20 ST 700 SmartLine Pressure Transmitters User’s Manual Revision 9.0
Figure 13 – ST 700 Standard Transmitter - Flange Adapter Removal and Replacement
Refer to the instructions included with the kit for removal and replacement procedures.
4.6 Wiring the ST 700 Standard Transmitter
4.6.1 Overview
The transmitter is designed to operate in a two-wire power/current loop with loop resistance and
power supply voltage within the operating range shown in
Figure 14.
Revision 9.0 ST 700 SmartLine Pressure Transmitters User’s Manual Page 21
Figure 14 – ST 700 Standard Transmitter - Operating Ranges
Loop wiring is connected to the Transmitter by simply attaching the positive (+) and negative (–) loop
wires to the positive (+) and negative (–) terminals on the Transmitter terminal block in the
Electronics Housing shown in Figure 15.
Figure 15 – ST 700 Standard Transmitter - 3-Screw Terminal Board and Grounding Screw
As shown in Figure 15, each Transmitter has an internal terminal to connect it to earth ground.
Optionally, a ground terminal can be added to the outside of the Electronics Housing. While it is not
necessary to ground the Transmitter for proper operation, doing so tends to minimize the possible
effects of noise on the output signal and affords protection against lightning and static discharge. An
optional lightning terminal block can be installed in place of the non-lightning terminal block for
Transmitters that will be installed in an area that is highly susceptible to lightning strikes.
Wiring must comply with local codes, regulations and ordinances. Grounding may be required to meet various approval body certification, for example CE conformity. Refer to Appendix A of this document for details.
Note: The right hand terminal is for loop test and is not applicable for the Fieldbus option.
The Transmitter is designed to operate in a two-wire power/current loop with loop resistance and
power supply voltage within the operating range; see
Figure 14. With optional lightning protection and/or a remote meter, the voltage drop for these
options must be added to the basic 10.8-volt supply requirements to determine the required
Transmitter voltage (VXMTR) and maximum loop resistance (RLOOP MAX). Additional consideration is
required when selecting intrinsic safety barriers to ensure that they will supply at least minimum
Page 22 ST 700 SmartLine Pressure Transmitters User’s Manual Revision 9.0
Transmitter voltage (VXMTR MIN), including the required 250 ohms of resistance (typically within the
barriers) needed for digital communications.
Transmitter loop parameters are as follows:
RLOOP MAX = maximum loop resistance (barriers plus wiring) that will allow proper Transmitter
operation and is calculated as RLOOP MAX = (VSUPPLY MIN – VXMTR MIN) 21.8mA.
In this calculation:
VXMTR MIN = 10.8V + VLP + VSM
VLP = 1.1V, lightning protection option, LP VSM = 2.3V, remote meter
Note that VSM should only be considered if a remote meter will be connected to the transmitter.
The positive and negative loop wires are connected to the positive (+) and negative (–) terminals on
the terminal block in the Transmitter Electronics Housing.
Barriers can be installed per Honeywell’s instructions for Transmitters to be used in intrinsically safe
applications.
4.6.2 Digital System Integration Information
Transmitters that are to be digitally integrated to Honeywell’s Total Plant Solution (TPS) system will
be connected to the Pressure Transmitter Interface Module in the Process Manager, Advanced
Process Manager or High Performance Process Manager through a Field Termination Assembly.
Details about the TPS system connections are given in the PM/APM SmartLine Transmitter
Integration Manual, PM12-410, which is part of the TDC 3000X system bookset.
If you are digitally integrating a Transmitter in an Allen Bradley Programmable Logic Controller
(PLC) process system, the same Field Terminal Assembly (FTA) and wiring procedures used with
Honeywell’s TPS system are also used with the Allen-Bradley 1771 and 1746 platforms.
4.6.3 Wiring Variations
The above procedures are used to connect power to a Transmitter. For loop wiring and external
wiring, detailed drawings are provided for Transmitter installation in non-intrinsically safe areas and
for intrinsically safe loops in hazardous area locations.
If you are using the Transmitter with Honeywell’s TPS system, see PM/APM Smartline Transmitter
Integration Manual, PM12-410, which is part of the TDC 3000X system bookset.
4.6.4 Wiring Procedure
1. See Figure 15, above, for parts locations. Loosen the end cap lock using a 1.5mm Allen wrench.
2. Remove the end cap cover from the terminal block end of the Electronics Housing.
3. Feed loop power leads through one end of the conduit entrances on either side of the
Electronics Housing. The Transmitter accepts up to 16AWG wire.
4. Plug the unused conduit entrance with the appropriate plug for the environment.
5. Connect the positive loop power lead to the positive (+) terminal and the negative loop power
lead to the negative (-) terminal. Note that the Transmitter is not polarity-sensitive.
6. Replace the end cap, and secure it in place.
Revision 9.0 ST 700 SmartLine Pressure Transmitters User’s Manual Page 23
4.6.5 Lightning Protection
If your Transmitter includes the optional lightning protection, connect a wire from the Earth Ground
Clamp (see Figure 15) to Earth Ground to make the protection effective. Use a size 8 AWG or
(8.37mm2) bare or green covered wire for this connection.
4.6.6 Supply Voltage Limiting Requirements
If your Transmitter complies with the ATEX 4 directive for self-declared approval per 94/9EC, the
power supply has to include a voltage-limiting device. Voltage must be limited such that it does not
exceed 42V DC. Consult the process design system documentation for specifics.
4.6.7 Process Sealing
The ST 700 SmartLine Pressure Transmitter is CSA-certified as a Dual Seal device in accordance
with ANSI/ISA–12.27.01–2003, “Requirements for Process Sealing Between Electrical Systems and
Flammable, or Combustible Process Fluids.”
4.6.8 Explosion-Proof Conduit Seal
When installed as explosion proof in a Division 1 Hazardous Location, keep covers tight while the Transmitter is energized. Disconnect power to the Transmitter in the non-hazardous area prior to removing end caps for service.
When installed as non-incendive equipment in a Division 2 hazardous location, disconnect power to the Transmitter in the non-hazardous area, or determine that the location is non-hazardous before disconnecting or connecting the Transmitter wires.
Transmitters installed as explosion proof in Class I, Division 1, Group A Hazardous (classified)
locations in accordance with ANSI/NFPA 70, the US National Electrical Code, with 1/2 inch conduit
do not require an explosion-proof seal for installation. If 3/4 inch conduit is used, a LISTED
explosion-proof seal to be installed in the conduit, within 18 inches (457.2mm) of the Transmitter.
Page 24 ST 700 SmartLine Pressure Transmitters User’s Manual Revision 9.0
4.7 Startup – ST 700 Standard Transmitter
4.7.1 Overview
This section identifies typical start up tasks associated with several generic pressure measurement
applications. It also includes the procedure for running an optional analog output check.
4.7.2 Startup Tasks
After completing the installation and configuration tasks for a Transmitter, you are ready to start up the
process loop. Startup usually includes:
Checking zero input
Reading inputs and outputs
Applying process pressure to the transmitter.
You can also run an optional output check to wring out an analog loop and check out individual
Process Variable (PV) outputs in Digitally Enhanced (DE) mode before startup.
The actual steps in a startup procedure vary based on the type of Transmitter and the measurement
application. In general, the procedures in this section are based on using Honeywell MC Toolkit to
check the Transmitter input and output under static process conditions, and make adjustments as
required initiating full operation with the running process. Note that similar checks can be made using
the optional three-button assembly, where the Transmitter is equipped. Operation with the three-
button assembly is discussed in the Operation section.
When the Standard Display is connected, the two-button assembly for the Standard Display is
present. The buttons will function 1 second after powering up.
4.7.3 Output Check Procedures
The Output Check comprises the following procedures:
The Loop Test procedure checks for continuity and the condition of components in the output
current loop.
The Trim DAC Current procedure calibrates the output of the Digital-to-Analog converter for
minimum (0%) and maximum (100%) values of 4mA and 20mA, respectively. This
procedure is used for Transmitters operating online in analog mode to ensure proper
operation with associated circuit components (for example, wiring, power supply, control
equipment). Precision test equipment (an ammeter or a voltmeter in parallel with precision
resistor) is required for the Trim DAC Current procedure.
The Apply Values procedure uses actual Process Variable (PV) input levels for calibrating
the range of a Transmitter. To measure a liquid level for example, a sight-glass can be used to
determine the minimum (0%) and maximum (100%) level in a vessel. The PV is carefully
adjusted to stable minimum and maximum levels, and the LRV and URV are then set by
commands from the MC Toolkit.
The Transmitter does not measure the given PV input or update the PV output while it operates in the Output mode.
Revision 9.0 ST 700 SmartLine Pressure Transmitters User’s Manual Page 25
4.7.4 Constant Current Source Mode Procedure
Figure 16 – ST 700 Standard Transmitter - Current Loop Test Connections
1. Refer to Figure 16 for test connections. Verify the integrity of electrical components in the output
current loop.
2. Establish communication with the Transmitter. For these procedures, the values of components in
the current loop are not critical if they support reliable communication between the Transmitter
and the Toolkit.
3. On the Toolkit, display the Output Calibration box.
4. In the Output Calibration box, select the Loop Test button; the LOOP TEST box will be
displayed.
5. Select the desired constant-level Output: 0%, 100%, or Other (any between 0% - 100%).
6. Select the Set button. A box will be displayed asking Are you sure you want to place the
transmitter in output mode?
With the Transmitter in Analog mode, you can observe the output on an externally-connected meter or on a local meter. In DE mode, you can observe the output on the local meter or on the Toolkit Monitor display.
7. Select the Yes button. Observe the output current at the percentage you selected in Step 5.
8. To view the monitor display, navigate back from the LOOP TEST display, and select the
MONITOR display. A Confirm popup will be displayed.
9. Select Yes to continue. This concludes the Startup procedure.
Page 26 ST 700 SmartLine Pressure Transmitters User’s Manual Revision 9.0
5. Operation_ST 700 Standard Transmitter
5.1 Overview This section provides the information and processes involved for both Digitally Enhanced (DE) and
HART operation using the three-button Basic and two-button Standard options for the ST 700
Standard transmitter.
5.2 Three-Button Operation The ST 700 Standrad transmitter has optional three-button interface that provides a user interface and
operation capability without opening the transmitter. Figure 17 shows the location of the three-button
option and the labels for each button.
Figure 17 – ST 700 Standard Transmitter - Three-Button Option
Revision 9.0 ST 700 SmartLine Pressure Transmitters User’s Manual Page 27
Table 9 – Three-Button Option Functions
Physical Button
Basic Display Action
Left
Increment Previous Menu Item
Scroll to previous menu item in an active list.
Scroll through alphanumeric list to desired character (ex. for entering Tag names or numeric values)
Center
Decrement Next Menu Item
Scroll to next menu item in an active list.
Scroll through alphanumeric list to desired character (ex. for entering Tag names or numeric values)
Right
Select displayed menu item for activation or editing
Call up the Main Menu. Select an item for data entry. Confirm a data entry operation
Activate the service associated with a selected menu item.
5.2.1 The Basic Display Menu
The Basic Display Menu is implemented as one long single-level menu and will “wrap around” when
it reaches the start or end of the menu. Operation is as follows:
Press the button to call up the Menu.
1. Select <Exit Menu> and press to exit the Menu.
2. Use the and buttons to scroll through the list of menu items.
3. Press the button to select an item for data entry or activation. When an item is selected for
data entry or activation, the cursor will jump to the lower line of the LCD to allow editing of
the value. No action is taken against a menu item until the user presses the button.
4. If you want to abort a data entry operation, simply refrain from pushing any buttons for 10
seconds; the data entry operation will time out and the original value of the selected item will
be preserved.
Page 28 ST 700 SmartLine Pressure Transmitters User’s Manual Revision 9.0
Table 10 – The Basic Display Menus
LCD Contrast »»»»»
Adjust the LCD contrast level. Range from » (1) to »»»»»»»»» (9) Default: »»»»»»»(7)
Press to enter menu selection
and to select level.
to enter
Press to enter menu selection
and to select from
list to enter
PV Display
Pressure Pressure Units Select Process Variable (PV) to be shown on the display from list.
Percent Output %
Loop Output mA
PV Decimal
None Select the PV decimal resolution to be shown on selected screen from list.
X.X
X.XX
X.XXX
Pressure Units
atm, bar ftH2O @ 68ºF gf/cm2 inH2O @ 39ºF inH2O @ 60ºF inH2O @ 68ºF inHg @ 0ºC kgf/cm2, kPa mbar, mmH2O @ 4ºC, mmH2O @ 68ºF, mmHg @ 0ºC, MPa, Pa, psi Torr, mHg @ 0ºC
Choose appropriate engineering units from list
Zero Correct Do Correct Executing this selection corrects the Zero based on the input pressure
Press to enter menu selection
Press to initiate action
LRV Correct Do Correct Executing this selection corrects the LRV based on the input pressure
URV Correct Do Correct Executing this selection corrects the LRV based on the input pressure
Reset Corrects Do Correct Executing this selection Resets the Zero, LRV, and URV Corrects back to Factory values
DAC Zero Trim Note: Loop must be removed from Automatic Control
DAC Zero Trim
This selection allows the loop zero output 4mA value to be trimmed.
Note: You must connect a current meter to the transmitter to monitor the loop output.
Press to enter menu selection
and to select number.
to enter and shift to the next digit to the right
DAC Span Trim Note: Loop must be removed from Automatic Control
DAC Span Trim
This selection allows the loop span output 20mA value to be trimmed. Note: You must connect a current meter to the transmitter to monitor the loop output.
Revision 9.0 ST 700 SmartLine Pressure Transmitters User’s Manual Page 29
Loop Test Note: Loop must be removed from Automatic Control
Loop Test 12.000
This selection allows the user to force the DAC output to any value between 3.8 and 20.8 mA. Note: This selection will put the DAC into Fixed Output Mode, as indicated by the flashing output value. Navigation away from this menu item will return the loop to Normal (Automatic) Mode.
LRV URV
#. ## #. ##
The limits are: 2X the Lower Range Limit (LRL) of the Meter body and 2X the Upper Range Limit (URL) of the Meter body
Press to enter menu selection
and to select number.
to enter and shift to the next digit to the right
Damping #. ##
Selection applies digital filtering to suppress noise effects on the PV. The limits for this value are 0.0 to 32.0 seconds
NAMUR Enabled Disabled
Disabling sets the loop output and burnout levels to the Honeywell levels
Press to enter menu selection
and to select from list
to enter
Filter Perf
Fast SOR Standard SOR
Fast Speed of Response Standard Speed of Response
Transfer Function (only available for DP Transmitters)
Linear The loop output of the transmitter is a linear representation of the differential pressure
Press to enter menu selection
and to select Alphanumeric
to enter and shift to next character to the right.
Square Root
The loop output of the transmitter represents %Flow as defined by the DP Square Root flow equation.
Flow Cutoff
Single Breakpt
Allows the user to specify a single breakpoint as the low flow cutoff point. This item is only available when the Transfer Function is set to Square Root.
Dual Slope
Uses a dual slope formula to determine the low flow cutoff point. This item is only available when the Transfer Function is set to Square Root.
Page 30 ST 700 SmartLine Pressure Transmitters User’s Manual Revision 9.0
Flow Breakpoint ##. #% Enter the low flow cutoff point when Single Breakpt is selected. Range: 0 to 25.0 %Flow.
Tag ID Enter Tag ID name up to 8 characters long. = any Alphanumeric value
Press to enter menu selection
and to select Alphanumeric
to enter and shift to next character to the right.
Device ID Unique for each device Read Only
PV Units Units of transmitted PV
Install Date DD MM YYYY
This selection allows the user to enter the date a transmitter is installed. The Install Date is entered in sequence of Day, Month, and Year, followed by the new date and the prompt Write Date to confirm the entry. CAUTION: The Install Date can only be written once in the life of the Transmitter. You cannot erase or overwrite the Install Date once it has been written.
Press to enter menu selection
and to select number
to enter and shift to next digit to the right. Read Only after entered
Firmware Display Electronics Meterbody
Menu item shows the current Firmware versions of the Display, Electronics Module and the Meter body
Read Only Parameter
Protocol HART Menu item shows the
communications protocol DE
Model Key
Identifies the type and range of the transmitter
Read Only Parameter
<Exit Menu>
Revision 9.0 ST 700 SmartLine Pressure Transmitters User’s Manual Page 31
5.2.2 Data Entry
Data entry is performed from left to right. Select a character / digit by pressing or buttons, and
then press to advance to the next character position to the right. Select the cross-hatch character ▒
to terminate the entry or if the final character is already a space character, just press << again.
All numeric entries are clamped at the low or high limit if needed. You can determine the low and
high limit for a parameter by selecting either the H or L character while the cursor is positioned over
the left-most digit and press button. The Display will show the selected limit.
Table 11 – Three-Button Data Entry
Screen Symbol
Numeric data entry Text entry
H Display the high limit for this parameter. This symbol only appears in the left-most position of the data entry field.
Not Available
L Display the low limit for this parameter. This symbol only appears in the left-most position of the data entry field.
Not Available
<< Terminate the numeric entry Terminate the text entry
0 thru 9, Minus, Decimal
These characters are used to enter numeric values. The minus sign only appears in the left-most digit.
These characters can be used to enter the Tag ID
5.2.3 Editing a Numeric value
Editing of a numeric value is a digit-by-digit process, starting with the left-most digit.
1. Press to begin the edit process.
2. The Basic Display will show the current value of the item on the lower line, left justified. The
3. Press the or buttons to select the desired digit, and then press to advance to the next
digit to the right.
4. After the last digit has been entered, press one more time to write the new value to the
transmitter.
5.2.4 Selecting a new setting from a list of choices
Use the procedure described below to select a new setting for parameters that present a list of choices
(e.g., PV Display, Pressure Units, etc.).
1. Press to begin the edit process.
a. The Basic Display will show the current setting of the item on the lower line, left
justified.
2. Press the or buttons to scroll through the list of choices.
Press to make your selection. The new selection will be stored in the transmitter and will be
displayed on the lower line, right justified.
Page 32 ST 700 SmartLine Pressure Transmitters User’s Manual Revision 9.0
5.3 Two-Button Operation The ST 700 Standrad transmitter has an optional two-button interface that provides a user interface
and operation capability without opening the transmitter. Figure 18 shows the location of the two-
button option and the labels for the buttons.
Figure 18 – ST 700 Standard Transmitter - Two-Button Option
5.3.1 The Standard Display Menu
The Standard Display Menu is implemented as one long single-level menu, after entering into Menu
mode, and will “wrap around” when it reaches the end of the menu. To enter Menu mode select in
PV display mode. Operation is as follows:
1. Select <Exit Menu> and press to exit the Menu.
2. Use the buttons to scroll through the list of menu items.
3. Press the button to select an item in Menu mode for data entry or activation. When an item
is selected for data entry or activation, the cursor will jump to the lower line of the LCD to
allow editing of the value. No action is taken against a menu item until the user presses the
button.
4. If you want to abort a data entry operation, simply refrain from pushing any buttons for more
than 10 seconds; the data entry operation will time out and the original value of the selected
item will be preserved.
5. If you want to abort a menu operation, simply refrain from pushing any buttons for more than
60 seconds; the menu operation will time out and the exit from menu & it will show PV
value.
The menu is divided into Standard Menu and Extended menu which can be enabled and disabled
by Extended Menu Enable/Disable operation.
Note: The abort option is not available for Loop test parameter. The timeout for the DAC trim
operation is more to enable user to calculate the loop current value to enter.
Revision 9.0 ST 700 SmartLine Pressure Transmitters User’s Manual Page 33
Table 12 – ST 700 Standard Transmitter: Standard Display Menus
PV Display [1SEL PV]
Pressure (PRESURE) Pressure Units
Select Process Variable (PV) to be shown on the display from list.
Press to enter Menu Mode
Press to enter menu selection
Press to initiate action Press
Menu to Exit to Menu
Percent Output (% OUT) %
Loop Output (LOOPOUT) mA
Flow (FLOW) Note: Before seleting PV type as Flow, please ensure the LRV/URV values in (pressure unit) are as per application. For PV type Flow the pressure unit will not be visible.
Flow unit
Pressure Units [2UNITS] (Visible for all PV except Flow)
atm, bar ftH2O @ 68ºF gf/cm2 inH2O @ 39ºF inH2O @ 60ºF inH2O @ 68ºF inHg @ 0ºC kgf/cm2, kPa mbar, mmH2O @ 4ºC, mmH2O @ 68ºF, mmHg @ 0ºC, MPa, Pa, psi Torr, mH2O @ 4ºC cmH2O @ 4ºC mHg @ 0ºC
Choose appropriate engineering units from list
Flow Units [3FLUNIT]
Cubic
meter/hour[m3/hr] Kg/hour
[Kg/hr]
Metric Ton/Hour [MT/hr]
Liter per second [L/sec]
Liters/hour [L/hr]
Standard Cubic feet per
hour[SCFH]
Cubic feet per hour[CFH]
Gallons/hour[gal/hr]
Barrel/hours [bbl/hr]
Imperial
Gallons/hours[Igal/hr]
Percentage[%]
Choose appropriate engineering units from list
Page 34 ST 700 SmartLine Pressure Transmitters User’s Manual Revision 9.0
Scaling Low [4SCLLOW ] Scaling High [5SCLHIG ]
#. ## #. ##
The limits are: -999999 to 999999
Press to enter Menu Mode
Press to enter menu selection
Menu to select number.
to enter and shift to the next digit to the right After complete value is Entered Press
Menu to Exit to Menu
Enter LRV [6ENTLRV] Enter URV [7ENTURV]
#. ## #. ##
The limits are: 2X the Lower Range Limit (LRL) of the Meter body and 2X the Upper Range Limit (URL) of the Meter body. The LRV/URV value will be available in Pressure Units (Standard Display pressure unit)
Zero Correct [8SETZRO]
Zero Correct Executing this selection performing for Zero Correct operation
Press to enter Menu Mode
Press to enter menu selection
Press to initiate action Press
Menu to Exit to Menu
Revision 9.0 ST 700 SmartLine Pressure Transmitters User’s Manual Page 35
Table 13 – ST 700 Standard Transmitter - Extended Display Menu
DAC Zero Trim [9ZEROTR] Note: Loop must be removed from Automatic Control
DAC Zero Trim
This selection allows the loop zero output 4mA value to be trimmed.
Note: You must connect a current meter to the transmitter to monitor the loop output.
Press to enter Menu Mode
Press to enter menu selection
Menu to select number.
to enter and shift to the next digit to the right After complete value is Entered Press
Menu to Exit to Menu
DAC Span Trim [10SPANTR] Note: Loop must be removed from Automatic Control
DAC Span Trim
This selection allows the loop span output 20mA value to be trimmed. Note: You must connect a current meter to the transmitter to monitor the loop output.
Loop Test [11LPTEST] Note: Loop must be removed from Automatic Control
Loop Test 12.000
This selection allows the user to force the DAC output to any value between 3.8 and 20.8 mA. Note: This selection will put the DAC into Fixed Output Mode, as indicated by the flashing output value. Navigation away from this menu item will return the loop to Normal (Automatic) Mode.
Set LRV [12SETLRV]
Set LRV Executing this selection performing for Zero operation.
Press to enter Menu Mode
Press to enter menu selection
Press to initiate action
Set URV [13SETURV]
Set URV Executing this selection for Span operation
Contrast [14CNTRST ]
»»»»»
Adjust the LCD contrast level. Range from » (1) to »»»»»»»»» (7) Default: »»»»»»»(7)
Enable Extended Menu [EXDMNU ]
Enable/Disable Enable the extended Menu.The default is disabled
Press toto Enter the Menu Mode
Press to enter Menu selection Menu to Enable or disable the Extended Menu
to Enter Press
Menu to Exit to Menu
Exit Menu
Page 36 ST 700 SmartLine Pressure Transmitters User’s Manual Revision 9.0
5.3.2 Standard Display Abbreviations:
Table 14 – The Standard Display abbreviations
Abbreviation Meaning OOR Out of Range
PRSPAN Push reduce span
Wrng Mo Wrong Mode
Illegal Illegal Value
Wrt Err NVM write error
Too Hi Value/Parameter Too High
Too Lo Value/Parameter Too Low
LRV Hi LRV too High
LRV Lo LRV too Low
LargeSP Span too large
SmallSP Span too small
Locked Device is locked
Multidr Device in multidrop mode
Wrt Prt Device in write protect mode
NotSprt Not supported
Hi LMT Value is greater than high Limit value
Low LMT Value is less than low Limit value
Revision 9.0 ST 700 SmartLine Pressure Transmitters User’s Manual Page 37
5.3.3 Data Entry
Data entry is performed from left to right. Select a character / digit by pressing buttons, and then
press to advance to the next character position to the right. Select the cross-hatch character ▒ to
terminate the entry or if the final character is already a space character, just press << again.
All numeric entries are clamped at the low or high limit if needed. You can determine the low and
high limit for a parameter by selecting either the H or L character while the cursor is positioned over
the left-most digit and press button. The Display will show the selected limit.
For numeric entry sign is required to be entered only for negative numbers. For positive number,
select space and move ahead.
Table 15 –Two-Button Data Entry
Screen Symbol
Numeric data entry
H Display the high limit for this parameter. This symbol only appears in the left-most position of the data entry field.
L Display the low limit for this parameter. This symbol only appears in the left-most position of the data entry field.
<< Terminate the numeric entry
0 thru 9, Minus, Decimal
These characters are used to enter numeric values. The minus sign only appears in the left-most digit.
5.3.4 Editing a Numeric value
Editing a numeric value is a digit-by-digit process, starting with the left-most digit.
1. Press to begin the edit process.
2. The Standard Display will show the current value of the item on the lower line, left justified.
3. Press the buttons to select the desired digit, and then press to advance to the next digit to
the right.
4. After the last digit has been entered, press one more time to write the new value to the
transmitter.
5.3.5 Selecting a new setting from a list of choices
Use the procedure described below to select a new setting for parameters that present a list of choices
(e.g. PV Display, Pressure Units, and so forth.).
1. Press to begin the edit process.
a. The Standard Display will show the current setting of the item on the lower line
2. Press the buttons to scroll through the list of choices.
3. Press to make your selection. The new selection will be stored in the transmitter and will
be displayed on the lower line
Page 38 ST 700 SmartLine Pressure Transmitters User’s Manual Revision 9.0
5.4 Basic and Standard Display Operations
5.4.1 Editing a Numeric value
Editing of a numeric value is a digit-by-digit process, starting with the left-most digit.
1. Press to begin the edit process:
The Basic and Standard Display will display the current value of the item on the lower
line, left justified.
Basic Display: Press the or buttons to select the relevant digit, and then press to
advance to the next digit to the right.
Standard Display: Press the button to select the relevant digit, and then press (both
button simultaneously) to advance to the next digit on the right.
2. Basic and Simply Displays: After the last digit has been entered, press one more time to
write the new value to the transmitter.
5.4.2 Selecting a new setting from a list of choices
Use the procedure described below to select a new setting for parameters that present a list of choices
(e.g. PV Display, Pressure Units, etc.).
1. Press to begin the edit process.
a. The Basic Display will show the current setting of the item on the lower line, left
justified.
2. Press the or buttons to scroll through the list of choices.
Press to make your selection. The new selection will be stored in the transmitter and will
be displayed on the lower line, right justified.
Revision 9.0 ST 700 SmartLine Pressure Transmitters User’s Manual Page 39
5.5 Three Button Operation with no Display Installed When there is no Display installed, the buttons can be used to perform a Zero or Span adjustment of
the ST 700 Standard Transmitter. Caution should be taken to insure these adjustments are only made
when the correct input pressures are applied.
5.5.1 Zero Adjustment
This adjustment is the same as performing a Set LRV using the Display.
1. Connect a current meter or voltmeter as shown in Figure 16 to monitor the PV output of the
Transmitter.
2. Using an accurate pressure source, apply pressure equivalent to the Transmitter LRV.
3. Press the Down (↓ ) and Zero ( ) buttons together to set the Zero.
4. Verify that the output is now 4 mA.
5.5.2 Span Adjustment
This adjustment is the same as performing a Set URV using the Display.
1. Connect a current meter or voltmeter as shown in Figure 16 to monitor the PV output of the
Transmitter.
2. Using an accurate pressure source, apply pressure equivalent to the desired Upper Range
Value of the transmitter.
3. Press the Down (↓) and Span ( ) buttons together to set the span.
4. Verify that the PV output is now 20mA.
You can also use the MCT 202 Toolkit to make any adjustments to an ST 700 SmartLine Pressure Transmitter. Alternately, certain adjustments are possible through an Experion Station or Universal Station, if the ST 700 is digitally integrated with either of these stations.
Page 40 ST 700 SmartLine Pressure Transmitters User’s Manual Revision 9.0
5.6 Changing the Default Failsafe Direction Transmitters are shipped with a default failsafe direction of upscale. This means that the Transmitter
output will set the current output to upscale failsafe (maximum output) upon detection of a critical
status. You can change the direction from upscale failsafe to downscale failsafe (minimum output) by
moving the top jumper located in the Electronics module.
5.6.1 DE and Analog Differences
Failsafe operation is different between DE and analog operation:
Analog operation – Upscale failsafe drives the Transmitter output to 21.8mA. Downscale
failsafe drives the Transmitter output to 3.8mA.
DE operation – Upscale failsafe causes the Transmitter to generate a + infinity digital
signal. Downscale failsafe causes the Transmitter to generate a – infinity digital signal.
The Transmitter electronics module interprets either signal as not-a-number and initiates its own
configured failsafe action for the control system.
5.6.2 Procedure to Establish Failsafe Operation
The failsafe direction display accessible via the Toolkit shows only the state of the jumper as it correlates to analog Transmitter operation. Failsafe action for the DE control system may be configured to operate in a manner different from analog, as indicated by the state of the Transmitter jumper.
The integrated circuits in the Transmitter PWA are vunerable to damage by stray static discharges when removed from the Electronics Housing. Minimize the possibility of static discharge damage when handling the PWA as follows:
Do not touch terminals, connectors, component leads, or circuits when handling the PWA.
When removing or installing the PWA, handle it by its edges or bracket section only. If you need to touch the PWA circuits, be sure you are grounded by staying in contact with a grounded surface or by wearing a grounded wrist strap.
When the PWA is removed from the Transmitter, put it in an electrically conductive bag, or wrap it in aluminum foil to protect it.
The following procedure outlines the steps for positioning the write protect and failsafe jumpers on
the electronics module. See Figure 19 for the locations of the failsafe and write protect jumpers.
Revision 9.0 ST 700 SmartLine Pressure Transmitters User’s Manual Page 41
Figure 19 – ST 700 Standard Transmitter - Locating the Failsafe and Write Protect Jumpers
Table 16 – ST 700 Standard Transmitter - Hart and DE Failsafe and Write Protect Jumpers
Jumper Arrangements
Description
Failsafe = UP (High)
Write Protect = OFF (Not Protected)
Failsafe = DOWN (Low)
Write Protect = OFF (Not Protected)
Failsafe = UP (High)
Write Protect = ON (Protected)
Failsafe = Down (Low)
Write Protect = On (Protected)
Page 42 ST 700 SmartLine Pressure Transmitters User’s Manual Revision 9.0
Table 17 – ST 700 Standard Transmitter - Fieldbus Simulation and Write Protect Jumpers
Image Description
Fieldbus Simulation Mode = OFF
Write Protect = OFF (Not Protected)
Fieldbus Simulation Mode = OFF
Write Protect = ON (Protected)
Fieldbus SIM Mode = ON
Write Protect = OFF (Not Protected)
1. Turn OFF Transmitter power (Power removal is only required in accordance with area safety
approvals. Power removal is only required in Class 1 Div 1 Explosionproof and Class 1 Div
2 environments).
2. Loosen the end cap lock, and unscrew the end cap from the electronics side of the Transmitter
housing.
3. If equipped with a Display module, carefully depress the two tabs on the sides of the Display
Module, and pull it off.
4. If necessary, unplug the interface connector from the Communication module. Do not discard
the connector.
5. Set the Failsafe Jumper (top jumper) to the desired position (UP or DOWN). See Table 16
and Table 17 for jumper positioning.
6. If applicable, re-install the Display module as follows:
Orient the display as desired.
Install the Interface Connector in the Display module such that it will mate
with the socket for the display in the Communication module.
Carefully line up the display, and snap it into place. Verify that the two tabs
on the sides of the display latch.
Note: Installing a Display Module into a powered transmitter may cause a temporary upset to
the loop output value.
Orient the Display for proper viewing through the end cap window. You can rotate the meter mounting orientation in 90o increments.
7. Restore transmitter power if removed.
Revision 9.0 ST 700 SmartLine Pressure Transmitters User’s Manual Page 43
5.7 Monitoring the Basic and Standard Displays for the ST 700 Standard Transmitter
This section describes the information shown on the operator screens of the Basic and Standard
Displays.
5.7.1 Basic Display_ST 700 Standard Transmitter -
Figure 20 illustrates the Basic Display format with Process Variable (PV).
The PV value is user-configurable. This field has 7 characters. The maximum allowable
numeric value is 9999999 or -999999. If fractional decimals are configured, the fractional
positions will be dropped, as required. If the PV value exceeds the above limits, it is divided
by 1000 and “K” is appended to the result, allowing a maximum value with multiplier of
999999K or -99999K.
Process Variable Tag is user-configurable from a HART Host. This field has 14 characters.
Engineering Units, this field is user-configurable. This field has 8 characters.
Figure 20 – ST 700 Standard Transmitter - Basic Display with Process Variable Format
5.7.2 Standard Display_ST 700 Standard Transmitter -
The PV value is user-configurable. This field has 6 characters. The maximum allowable
numeric value is 999999 or -999999.
o If fractional decimals are configured, the fractional positions will be dropped, as
required.
o If the PV value exceeds the above limits, it is divided by 1000 and “K” is appended
to the result, allowing a maximum value with multiplier of 99999K or -99999K.
Page 44 ST 700 SmartLine Pressure Transmitters User’s Manual Revision 9.0
Special Symbol (Square root)
PV Value
Display Unit
Special Symbol (Write Protect)
Figure 21 – ST 700 Standard Transmitter - Standard Display with Process Variable Format
PV Value
Unit
Revision 9.0 ST 700 SmartLine Pressure Transmitters User’s Manual Page 45
6. Maintenance_ST 700 Standard Transmitter
6.1 Overview This section provides information about preventive maintenance and replacing damaged parts. The
topics covered in this section are:
Preventive maintenance of the meter body barrier diaphragms and process piping to the
Transmitter.
Replacement of damaged parts such as the Transmitter Printed Wiring Assembly (PWA) and
meter body
6.2 Preventive Maintenance Practices and Schedules The ST 700 Transmitter does not require any specific maintenance at regularly scheduled intervals.
However, it is recommended that you perform these typical inspection and maintenance routines on a
schedule that is dictated by the characteristics of the process medium and if blow-down facilities or
purge systems are being used.
Check piping for leaks.
Clear piping of sediment or other foreign matter.
Clean the Transmitter process heads, including the barrier diaphragms.
6.3 Inspecting and Cleaning Barrier Diaphragms Depending on the characteristics of the process medium, sediment or other foreign particles may
collect in the process head cavity/chamber and cause faulty measurement. In addition, the barrier
diaphragm(s) in the Transmitter meter body may become coated with residue from the process
medium. The latter is also true for external diaphragms on flange-mount and remote seal type
Transmitters.
In many cases, you can readily remove the process head(s) from the Transmitter meter body to clean
the process head cavity and inspect the barrier diaphragm(s). For flange-mount and remote seal
diaphragms, you may only need to run a purge line in the tank to rinse off the face of the
diaphragm(s).
The following procedure comprises the general steps for inspecting and cleaning barrier diaphragms.
You may have to modify these steps to meet your particular process or transmitter model
requirements. Figure 22 shows an exploded view of a Differential Pressure (DP) Transmitter meter
body for reference. For disassembly/reassembly purposes, Gauge Pressure (GP) and Absolute
Pressure (AP) Transmitters are similar.
It is recommended that you remove the Transmitter from service and move it to a clean area before disassembling it.
Page 46 ST 700 SmartLine Pressure Transmitters User’s Manual Revision 9.0
Figure 22 – ST 700 Standard Transmitter - DP Transmitter Head Disassembly
1. Close all valves to isolate the Transmitter from the process.
2. Open the vent in the process head to drain fluid from the Transmitter meter body, as
necessary.
3. Remove the Transmitter from the process.
4. Loosen the nuts in the sequence shown in Figure 23.
5. Remove the nuts from the bolts that hold the process head(s) to the meter body.
6. Remove the process heads and bolts.
7. Remove the gasket/ O-ring, and clean the interior of the process head using a soft bristle
brush and an approved solvent.
8. Inspect the barrier diaphragm for signs of deterioration, corrosion, and distortion.
9. If the diaphragm is distorted contact Honeywell for assistance.
10. Install a new gasket/O-ring in each process head.
11. Coat threads on the process head bolts with a suitable anti-seize compound, such as
“Neverseize,” or equivalent.
12. Using a torque wrench, gradually tighten the nuts in the sequence shown in Figure 23.
Tighten head bolts in stages of 1/3-full torque, 2/3-full torque, and full torque. Refer to the
values in Table 18 for torque requirements versus Transmitter type and model.
Revision 9.0 ST 700 SmartLine Pressure Transmitters User’s Manual Page 47
Figure 23 – ST 700 Standard Transmitter - Head Bolt Tightening Sequence
Table 18 – Head Bolt Torque Values
Page 48 ST 700 SmartLine Pressure Transmitters User’s Manual Revision 9.0
6.4 Replacing the Communication Module The Communication module includes a connector to the sensor ribbon cable and a connector to the
optional Display module. This section includes the procedure to replace the Communication module.
The transmitter does not have to be removed from service to replace the Comm Module
Please take appropriate steps to avoid ESD damage when handling the Communication and Display Module assemblies
Refer to Figure 24 for parts locations.
Figure 24 – ST 700 Standard Transmitter - PWA Replacement
1. Turn OFF Transmitter power (Power removal is only required in accordance with area safety
approvals. Power removal is only required in Class 1 Div 1 Explosion-proof and Class 1 Div
2 environments).
When removing the Communications Module with power applied, the loop will go to
0V. Likewise, installing a Communications Module into a transmitter with power
applied will cause the loop output value to go to 12ma for several seconds then the
loop output value will go to the configured value based on the PV input.
Installing a Display Module into a powered transmitter may cause a temporary upset
to the loop output value.
2. Loosen the end cap lock, and unscrew the end cap from the electronics side of the Transmitter
housing.
3. If equipped with a Display module, carefully depress the two tabs on the sides of the Display
Module, and pull it off.
4. If necessary, unplug the interface connector from the Communication module. Do not
discard the connector.
5. Loosen the two retaining screws, and carefully pull the Communication module from the
Electronics compartment.
Revision 9.0 ST 700 SmartLine Pressure Transmitters User’s Manual Page 49
6. Carefully align and connect the Sensor Ribbon Cable to the connector “J4” at the bottom of
the Communication module. When installing the Communication module in the next step, be
careful not to pinch the Sensor Ribbon Cable.
7. Carefully, insert the Communication module into the Electronics compartment. Ensure that
the Sensor Ribbon Cable is not pinched.
8. Tighten the two Communication module retaining screws.
9. Refer to the SmartLine User's Manual to change the FAILSAFE, READ/WRITE, and SIM-
OFF/SIM-ON (Fieldbus Only) configuration settings.
10. If applicable, re-install the Display module as follows:
a. Orient the display as desired.
b. Install the Interface Connector in the Display module such that it will mate with the
socket for the display in the Communication module.
c. Carefully line up the display, and snap it into place. Verify that the two tabs on the
sides of the display latch.
Orient the Display for proper viewing through the end cap window. You can rotate the meter mounting orientation in 90 o increments.
11. Apply Parker Super O-ring Lubricant or equivalent to the end cap O-ring before installing the
end cap. Reinstall the End Cap and tighten the End Cap locking screw.
12. Installing Optional External Configuration Button Assembly.
a. Loosen (Do Not Remove) both top nameplate screws and pivot nameplate 90°.
b. Align the protrusion on the button assembly with the matching opening in the
housing and snap the button assembly into the housing.
c. Rotate the nameplate back to the original position, and tighten the nameplate screws.
(Steps 13 - 16 required for Field Upgrades Only)
13. Loosen the End Cap locking screw and unscrew the End Cap from the Field Wiring side of
the transmitter housing.
14. Select the proper Communication/External Configuration upgrade kit label from the label
strip provided and adhere to the inside of the Field Wiring compartment End Cap.
15. Apply Parker Super O-ring Lubricant or equivalent to the end cap o-ring before installing the
end cap. Reinstall the End Cap and tighten the end cap locking screw.
16. Install external upgrade label (e.g. DEVICE MODIFIED…..) provided on outside of housing
as shown in Figure 24.
Page 50 ST 700 SmartLine Pressure Transmitters User’s Manual Revision 9.0
17. Restore power if removed.
18. Check the settings of the Transmitter Setup and Display Setup parameters to make sure that
the transmitter is configured correctly for your application. See the HART/DE User's Manual
(ST 800 #34-ST-25-38, ST 700 #34-ST-25-44) for details on HART and DE transmitters.
Refer to manual #34-ST-25-39 for additional information about Fieldbus transmitters.
19. If applicable, verify External Button Configuration operation. The transmitter is now
available for use.
6.5 Replacing the Meter Body You can replace the complete meter body, including the process heads, or the meter body only on
certain Differential Pressure (DP), Gauge Pressure (GP), and Atmospheric Pressure (AP) Transmitters
by using the existing process head(s). Use the following procedure for meter body-only replacement.
1. Save or record device configuration data.
2. Turn off Transmitter power.
3. Remove the Transmitter from service, and move it to a clean area before disassembling it.
4. Refer to Figure 25. Loosen the End Cap Lock, and unscrew the End Cap from the electronics
side of the Transmitter housing.
Figure 25 – ST 700 Standard Transmitter - Disassembly for Meter Body Replacement
Please take appropriate steps to avoid ESD damage when handling the Communication and Display Module assemblies
5. If a display is present, press the two snaps along the side, and remove it from the
communication module assembly.
Note: Do not discard or misplace the Display/Communication connector, it will be required
to reassemble the Display Module
6. Loosen the two retaining screws, and remove the Communications Module assembly, and
remove the Communication Module assembly from the electronics housing.
Revision 9.0 ST 700 SmartLine Pressure Transmitters User’s Manual Page 51
7. Disconnect the Sensor Cable from the Communications Board.
8. Refer to Figure 26. Use a 2mm hex wrench to completely loosen the set screw on the outside
of the housing to permit rotating the meter body.
Figure 26 – ST 700 Standard Transmitter - Hardware Location to Remove the Meter Assembly
9. Carefully turn the complete meter body counterclockwise to unscrew it from the electronics
housing.
10. Remove the nuts from bolts that hold the process head(s) to the Meter Body.
11. Remove process heads and bolts.
12. Remove the gaskets or O-rings from the process heads.
13. Clean the interior of the process head(s) with a soft bristle brush and suitable solvent.
CAUTION: To prevent damage to the diaphragm in the Meter Body, use extreme care when handling or placing the Meter Body on any surface. Carefully assemble gaskets or O-rings to the meter body. If installing O-rings, lubricate with water or leave dry.
14. Coat threads on process head bolts with anti-seize compound such as “Neverseize” or
equivalent.
15. Refer to Figure 27. Apply Dow Corning #33 silicone grease to the meter body adapter O-ring
and carefully assemble the O-ring to the meter body. Assemble the process head(s) and bolts
to the new meter body. For now, make the bolts only finger-tight.
Page 52 ST 700 SmartLine Pressure Transmitters User’s Manual Revision 9.0
Figure 27 – ST 700 Standard Transmitter - Meter Body Reassembly
16. Use a torque wrench to gradually tighten nuts to torque rating in sequence shown in Figure 28.
Tighten head bolts in stages of 1/3 full torque, 2/3 full torque, and then full torque.
Figure 28 – ST 700 Standard Transmitter - Head Bolt Tightening Sequence
17. Feed the ribbon cable on the new meter body through the neck of the housing.
CAUTION: To prevent damage to the ribbon cable, use care when assembling the Meter Body to the electronics housing.
18. Screw the new meter body into the housing until the bottom of the Meter Body adapter is
flush with the neck of the electronics housing.
19. Tighten the outside set screw to be sure it is fully seated in the slot in the header.
Revision 9.0 ST 700 SmartLine Pressure Transmitters User’s Manual Page 53
20. Loosen the set screw ½- turn.
21. Rotate the housing to the desired position (Max. 180o in either direction), and tighten the set
screw.
22. Carefully align and connect the Sensor Ribbon Cable to connector “J4” at the bottom of the
Communication module board. When installing the Communication module in the next step,
be careful not to pinch the Sensor Ribbon Cable.
23. Carefully, insert the Communication module into the Electronics compartment. Ensure that
the Sensor Ribbon Cable is not pinched.
24. Tighten the two Communication module retaining screws.
25. If applicable, re-install the Display module as follows:
a. Orient the display as desired.
b. Install the Interface Connector in the Display module such that it will mate with
the socket for the display in the Communication module.
c. Carefully line up the display, and snap it into place. Verify that the two tabs on
the sides of the display latch.
Orient the Display for proper viewing through the end cap window. You can rotate the meter mounting orientation in 90 o increments.
26. Connect the bracket to the Transmitter housing.
27. Recalibrate the Transmitter per section 7 Calibration, of this document.
28. Return the Transmitter to service, and turn ON power
29. Verify the Transmitter configuration data. Restore the saved database if necessary.
30. Lubricate the end-cap O-ring with Parker Super O-ring silicone lubricant or equivalent before
replacing the end caps.
Page 54 ST 700 SmartLine Pressure Transmitters User’s Manual Revision 9.0
7. Calibration for the ST 700 Standard Transmitter
7.1 Recommendations for Transmitter Calibration The ST 700 Standard Transmitter does not require periodic calibration to maintain accuracy.
Typically, calibration of a process-connected Transmitter will degrade, rather than augment the
capability of a smart Transmitter. For this reason, it is recommended that a Transmitter be removed
from service before calibration. Moreover, calibration will be accomplished in a controlled,
laboratory-type environment, using certified precision equipment.
7.2 Calibration Procedures For a Transmitter operating in analog mode, you must calibrate its output signal measurement range
using any compatible hand-held communicator or a local display.
One calibration option is to use the Honeywell Smart Field Communicator (SFC). Refer to the Smart
Field Communicator Operating Guide, Document # 34-ST-11-14 for calibration procedures.
Calibration information and procedures for a Transmitter operating in the HART/DE mode are
provided in the ST 700 Series HART/DE Option User’s Manual, Document # 34-25-25-47.
Revision 9.0 ST 700 SmartLine Pressure Transmitters User’s Manual Page 55
8. Troubleshooting on the ST 700 Standard Transmitter
8.1 Overview Troubleshooting involves responding to error messages, primarily displayed by the MC Toolkit. Error
messages that may occur on the Transmitter’s local display are fairly self-explanatory and intuitive.
However, this section covers the diagnostic messages that indicate critical conditions. Other than the
critical conditions, additional detail is not provided. If you require assistance, contact your distributor
or Honeywell Technical Support. All other messages are covered by the MC Toolkit Users’ Manual.
8.2 Critical Diagnostics Screens The Basic Display will display the message CRITCAL FAULT on the top line of the LCD and the
appropriate diagnostic text on the lower line.
A description of the diagnostic conditions is given in Table 19 and Table 20 along with suggested
actions for resolving the problem.
8.2.1 Fault Conditions and Recommended Corrective Actions – Basic Display
Table 19 – ST 700 Standard Transmitter - Fault Conditions and Recommended Corrective Actions.
Condtion Analysis Recommended Corrective
Action
Fault. A critical failure has been detected in the Meter body
Use a HART, DE, or FF communicator to read the detailed status information from the transmitter. Refer to the appropriate communicator manual to get more information about the possible causes of the failure.
Cycle power to the Transmitter. If the problem continues to occur, replace the Meter body.
Electronics Module Fault. A critical failure has been detected on the HART, DE, or FF Electronics Module.
Use a HART, DE, or FF communicator to read the detailed status information from the transmitter. Refer to the appropriate communicator manual for more information about the possible failure causes.
Cycle power to the transmitter. If the problem continues to occur replace the Electronics Module.
Meter body Comm fault. Communications between the Meter body and the Electronics Module has failed.
This could be the result of a failure on either of these modules or the cable that connects them. Use a HART, DE, or FF communicator to read the detailed status information from the transmitter. Refer to the appropriate communicator manual to get more information about the possible causes of the failure.
Check the ribbon cable that connects the Meter body to the Electronics Module. Make sure that the cable is securely plugged into the Electronics Module. Make sure that all pins are plugged into the connector (e.g., make sure that the connector is not offset in a way that leaves some pins unconnected). Cycle power to the transmitter. If the problem continues to occur replace the Electronics Module. If
Page 56 ST 700 SmartLine Pressure Transmitters User’s Manual Revision 9.0
Condtion Analysis Recommended Corrective
Action
this does not fix the problem, replace the Meter body.
8.2.2 Fault Conditions and Recommended Corrective Actions – Standard Display
The Standard Display will display the message FAULT on the top line of the LCD and the
appropriate diagnostic text on the lower line.
Table 20 – ST 700 Standard Transmitter - Fault Conditions and Recommended Corrective
Actions.
Condtion Analysis Recommended Corrective
Action
Mbd Com (Meter body Comm fault)
Communications between the Meter body and the Electronics Module has failed.
Check the ribbon cable that connects the Meter body to the Electronics Module. Ensure that the cable is securely plugged into the Electronics Module. Ensure that all pins are plugged into the connector (e.g. ensure that the connector is not offset in a way that leaves some pins unconnected). Cycle power to the transmitter. If the problem continues to occur replace the Electronics Module. If this does not fix the problem, replace the Meter body.
Comm El (Communication Board fault)
A critical failure has been detected on the HART Electronics Module.
Cycle power to the transmitter. If the problem continues to occur replace the Electronics Module.
Mtrbody (Sensor Board Fault)
A critical failure has been detected in the Meter body
Cycle power to the transmitter. If the problem continues to occur replace the Electronics Module.
Revision 9.0 ST 700 SmartLine Pressure Transmitters User’s Manual Page 57
9. Parts List_ST 700 Standard Transmitter
9.1 Overview Individually saleable parts for the various Transmitter models are listed in this section. Some parts are
illustrated for identification. Parts are identified and listed in the corresponding tables as follows:
Individually saleable parts are indicated in each figure by key number callout.
Parts that are supplied in kits are indicated in each illustration by key number callout with the
letter K prefix.
Table 21 is a list of recommended spare parts.
Table 21 – ST 700 Standard Transmitter - Summary List of Recommended Spare Parts
Part Number Description Figure
No. Key No.
1-10 Units
10-100 Units
100-1000 Units Electronics Housing Assembly
50049849-501 50049849-502 50049849-503 50049849-504 50049849-509 50049849-510
HART Electronics Module Without REED Sensor PWA HART Electronics Module With REED Sensor PWA DE Electronics Module Without REED Sensor PWA DE Electronics Module With REED Sensor PWA Fieldbus Electronics Module Without REED Sensor PWA for ST700 Fieldbus Electronics Module With REED Sensor PWA for ST700
Figure 30 5 1 1-2 2-4
51452865-501 51452865-502 51452865-503 51462865-504
Meter Body Seal kit (includes O-rings) Glass Filled PTFE VITON 100% PTFE GRAPHITE
Figure 33 K1 1 1-2 2-4
50075472-531 50075472-532 50075472-533 50075472-534
HART/DE Terminal Block Assy Without Lightning Protection HART/DE Terminal Block Assy With Lightning Protection FieldBus Terminal Block Assy Without Lightning Protection FieldBus Terminal Block Assy With Lightning Protection
Figure 31 3 1 1-2 2-4
Page 58 ST 700 SmartLine Pressure Transmitters User’s Manual Revision 9.0
Process head gasket kit
Figure No.
Key No.
1-10 Units
10-100 Units
100-1000 Units
51452868-501 51452868-502 51452868-507
Gasket only, Process Head (12 PTFE packs) Gasket only, Process Head (6 Viton Head O’Rings) Gasket only, Process Head Graphite Gasket (replacement only for existing graphite gasket)
Figure 33 Ka
12
12-24
24-48
6 6-12 12-24
6 6-12 12-24
Meter Body
Specify complete model number from nameplate
DP Models GP/AP HEAD Models LGP/LAP Models Flush Mount Models Flange Mount Models
Figure 32
1 1-2 2-4
Figure 29 – ST 700 Standard Transmitter - Angle and Flat Bracket Parts
Revision 9.0 ST 700 SmartLine Pressure Transmitters User’s Manual Page 59
Table 22 – ST 700 Standard Transmitter - Angle and Flat Bracket Parts
(Refer to Figure 29)
Key No.
Part Number Description Quantity Per Unit
1 30752770-603 SS 304 Angle Bracket Mounting kit for all models except In- line and Flush mount transmitters
1
2 30752770-604 SS 304 Angle Bracket Mounting kit for all In-Line and Flush mount transmitters
1
3 30752770-803 Marine Approved Angle Bracket for all models except In-line and Flush mount transmitters
1
4 30752770-804 Marine Approved Angle Bracket for all In-line and Flush mount transmitters
1
5 51196557-505 SS 304 Flat Bracket Mounting kit for all models except In-line and Flush mount transmitters
1
6 51196557-506 SS 304 Flat Bracket Mounting kit for all In-line transmitters and Flush mount transmitters
1
7 30752770-603 SS 316 Angle Bracket Mounting kit for all In-line transmitters except In-Line and Flush mount transmitters
1
8 30752770-604 SS 316 Angle Bracket Mounting kit for all In-Line and Flush mount transmitters
1
9 51196557-508 SS 316 Flat Bracket Mounting kit for all In-line transmitters except In-Line and Flush mount transmitters
1
10 51196557-509 SS 316 Flat Bracket Mounting kit for all In-Line and Flush mount transmitters
1
Page 60 ST 700 SmartLine Pressure Transmitters User’s Manual Revision 9.0
Figure 30 – ST 700 Standard Transmitter - Electronic Housing, Display End
Table 23 – ST 700 Standard Transmitter Major Assemblies
(Refer to Figure 31 and Figure 32)
Key No.
Part Number Description Quantity Per Unit
1 50049858-501 50049858-521
End Cap (Aluminum) End Cap (Stainless Steel)
1
2 50049832-501 50049832-521
End Cap, Display (Aluminium) with window End Cap, Display (Stainless Steel) with window
1
3
50075472-531 50075472-532 50075472-533 50075472-534
Terminal Assy HART/DE without Lightning protection Terminal Assy HART/DE with Lightning protection Terminal Assy FF/PB without Lightning protection Terminal Assy FF/PB with Lightning protection
1
4 50049911-501 50126003-501
Basic Display Standard Display
1
5 50049849-501 50049849-502 50049849-503 50049849-504 50049849-509 50049849-510
HART Electronics Module Assembly (PWA) without Reed sensor HART Electronics Module Assembly (PWA) with Reed sensor DE Electronics Module Assembly (PWA) without Reed sensor DE Electronics Module Assembly (PWA) with Reed sensor FF Electronics Module Assembly (PWA) without Reed sensor FF Electronics Module Assembly (PWA) with Reed sensor
1
6 50049915-501 50131077-501
External Zero, Span & Config Buttons (3- button Assembly) External Zero, Span & Config Buttons (2- button Assembly)
1
K1 30757503-005 Electronics housing seals kit (includes O-rings) 2
Revision 9.0 ST 700 SmartLine Pressure Transmitters User’s Manual Page 61
Figure 31 – ST 700 Standard Transmitter - Electronic Housing, Terminal Block End
Page 62 ST 700 SmartLine Pressure Transmitters User’s Manual Revision 9.0
Figure 32 – ST 700 Standard Transmitter - Major Assemblies
Revision 9.0 ST 700 SmartLine Pressure Transmitters User’s Manual Page 63
Table 24 – ST 700 Standard Transmitter Models STD720, 730 & 770
(Refer to Figure 33) Key No.
Part Number Description Qty/Kit
Meter Body Gasket Kits
51452865-501 51452865-502 51452865-503 51452865-504
Glass Filled PTFE VITON 100% PTFE GRAPHITE
Each Meter Body Gasket Kit includes:
K6 Gasket, Process Head 6
Ka Gasket, Flange Adapter 6
K7 O-Ring, Meter Body to Electronics Housing 3
K7 Process Head Gasket Kits
K6 K6 K6
51452868-501 51452868-502 51452868-507
Gasket, Process Head (6 Gaskets/ 1 Kit) Gasket, Flange Adapter (6 Gaskets/ 1 Kit) O-Ring, Meter Body to Electronics Housing (3 Gaskets/ 1 Kit)
12 6 6
Flange Adapter Gasket Kits
Ka Ka Ka
51452868-504 51452868-505 51452868-508
Gasket only, Flange Adapter, 6 PTFE Adapter Gaskets Gasket only, Flange Adapter, 6 VITON Adapter O-Rings Gasket only, Flange Adapter Graphite Gasket (use only as replacement of existing graphite gasket)
6 6 6
½-inch NPT Flange Adapter Kits
51452867-110 51452867-210 51452867-310 51452867-410 51452867-150 51452867-350 51452867-130 51452867-330
Flange Adapter Kit, with: SS Flange Adapters and with carbon steel bolts SS Flange Adapters and with A286 SS (NACE) bolts SS Flange Adapters and with 316 SS (non-NACE) bolts SS Flange Adapters and with B7M alloy steel bolts Monel Flange Adapters and with carbon steel bolts Monel Flange Adapters and with 316 SS (non-NACE) bolts Hastelloy C Flange Adapters and with carbon steel bolts Hastelloy C Flange Adapters and with 316 SS (non-NACE) bolts
Each ½-inch NPT Flange Adapter Kit includes:
Ka Gasket, Flange Adapter 2
Kb ½-inch NPT Flange Adapter 2
Kc Bolt, hex head, 7/16-20 UNF, 1.50 inches long 4
Page 64 ST 700 SmartLine Pressure Transmitters User’s Manual Revision 9.0
Bolt And Nut Kit
51452866-501 Carbon steel bolt and Nut Kit
51452866-502 Stainless Steel Bolt and Nut Kit with NACE Certificate
51452866-503 Stainless Steel Bolt and Nut Kit without NACE Certificate
51452866-504 B7M Bolt and Nut Kit
51452866-505 All Stainless Steel NACE Bolt and Nut Kit
51452866-506 Monel Bolt and Nut Kit
51452866-507 Super Duplex Bolt and Nut Kit
51452866-508 Stainless Steel NACE 6K Bolt and Nut Kit
Each Bolt and Nut Kit Includes:
K8 Head Bolt 4
K4 Head Nut 4
Kc Adapter Bolt 4
Revision 9.0 ST 700 SmartLine Pressure Transmitters User’s Manual Page 65
Figure 33 - ST 700 Standard Transmitter - ST 700 Models STD720, 730, 770
(Refer to Table 24 )
Page 66 ST 700 SmartLine Pressure Transmitters User’s Manual Revision 9.0
Table 25 – ST 700 Standard Transmitter - Parts for STG730, 740, 770 and STD720, 730, 770 and STA722, 740 Transmitter Body
(Refer to
Figure 34)
Key No.
Part Number Description Qty/Unit
Process Head Assembly Kits with PTFE Gaskets
51452864-010 51452864-012 51452864-020 51452864-022 51452864-030 51452864-032 51452864-040 51452864-042 51452864-050 51452864-052
Carbon steel head (zinc plated) without side vent/drain Carbon steel head (zinc plated) with side vent/drain Stainless steel head without side vent/drain Stainless steel head with side vent/drain Hastelloy C head without side vent/drain Hastelloy C head with side vent/drain Monel head without side vent/drain Monel head with side vent/drain Carbon steel head (nickel plated) without side vent/drain Carbon steel head (nickel plated) with side vent/drain
Process Head Assembly Kits with VITON Gaskets
51452864-110 51452864-112 51452864-120 51452864-122 51452864-130 51452864-132 51452864-140 51452864-142 51452864-150 51452864-152
Carbon steel head (zinc plated) without side vent/drain Carbon steel head (zinc plated) with side vent/drain Stainless steel head without side vent/drain Stainless steel head with side vent/drain Hastelloy C head without side vent/drain Hastelloy C head with side vent/drain Monel head without side vent/drain Monel head with side vent/drain Carbon steel head (nickel plated) without side vent/drain Carbon steel head (nickel plated) with side vent/drain
Each process head assembly kit includes:
K1 Pipe Plug (See notes 1 & 2) 1
K2 Vent Plug (See note 1) 1
K3 Vent Bushing (See note 1.) 1
K5 Process Head 1
K6 Gasket (PTFE), Process Head 1
Ka Gasket (PTFE), Flange Adapter 1
Notes
Note 1: This item is made of the same material as the Process Heads, except for Kits with carbon steel Process Heads, which include stainless steel Pipe Plug, Vent Plug, and Vent Bushing. Note 2: The Kit for Process Heads without side vent/drain does not include Pipe Plugs (K1).
Reference Head
K9 51452951-502 316 SS Blind Reference Head 1
Revision 9.0 ST 700 SmartLine Pressure Transmitters User’s Manual Page 67
Bolt And Nut Kit
51452866-501 Carbon steel bolt and Nut Kit
51452866-502 Stainless Steel Bolt and Nut Kit with NACE Certificate
51452866-503 Stainless Steel Bolt and Nut Kit without NACE Certificate
51452866-504 B7M Bolt and Nut Kit
51452866-505 All Stainless Steel NACE Bolt and Nut Kit
51452866-506 Monel Bolt and Nut Kit
51452866-507 Super Duplex Bolt and Nut Kit
51452866-508 Stainless Steel NACE 6K Bolt and Nut Kit
Each Bolt and Nut Kit Includes:
K8 Head Bolt 4
K4 Head Nut 4
Kc Adapter Bolt 4
Page 68 ST 700 SmartLine Pressure Transmitters User’s Manual Revision 9.0
Figure 34 – ST 700 Standard Transmitter - STG730, 740, 770 and STA722, 740 Transmitter Body
Revision 9.0 ST 700 SmartLine Pressure Transmitters User’s Manual Page 69
Table 26 - ST 700 Standard Transmitter - Inline Gauge and Inline Atmospheric Meter Body Parts
(See Figure 35) Key No.
Part Number Description Qty/Unit
Specify complete model number from nameplate
ST Series replacement meter body (LAP/LGP model)
1
Figure 35 – ST 700 Standard Transmitter - Inline Gauge and Inline Atmospheric Meter Body Bodies
Page 70 ST 700 SmartLine Pressure Transmitters User’s Manual Revision 9.0
Table 27 – ST 700 Standard Transmitter - Flange-Mounted Meter Body Parts – STF724, 732
(Refer to Figure 36 and Figure 37)
Key No.
Part Number Description Qty/Unit
1 Specify complete model number from nameplate
ST Series 700 replacement meter body 1
Figure 36 – ST 700 Standard Transmitter - Extended Flange Design
Figure 37 - ST 700 Standard Transmitter - Flush Flange Design
Revision 9.0 ST 700 SmartLine Pressure Transmitters User’s Manual Page 71
Figure 38 - ST 700 Standard Transmitter - Pseudo Flange Design
Figure 39 – ST 700 Standard Transmitter - Remote Seal Diaphragm
Page 72 ST 700 SmartLine Pressure Transmitters User’s Manual Revision 9.0
Figure 40 - ST 700 Standard Transmitter - Flush Mount Meter Body.
Table 28 – ST 700 Standard Transmitter - Flush Mount Meter Body Parts
(Refer to Figure 40)
Key No.
Part Number Description Qty/Unit
1
Specify complete model number from nameplate
Replacement meter body (Flush Mount model)
1 30756445-508 Gasket Kit (0-rings)
51204496-501 316L SS Mounting Sleeve Kit
51204497-501 Calibration Sleeve Kit
Refer to Appendix A for Product Certifications and Approvals for the ST 700 Standard and Basic
Transmitter.
Revision 9.0 ST 700 SmartLine Pressure Transmitters User’s Manual Page 73
10. Introduction_ST 700 Basic Transmitter
10.1 Overview This section is an introduction to the physical and functional characteristics Honeywell’s family of
the ST 700 Basic SmartLine Pressure Transmitters.
If you are not sure which type of ST 700 you have, Standrad or Basic, please refer to Section 1 of this
manual
If you have a ST 700 Standard Transmitter use Sections 2 through 9.
If you have a ST 700 Basic Transmitter go straight to Section 10 through 17.
10.2 Features and Options The ST 700 Basic transmitter is available in a variety of models for measuring Differential Pressure
(DP), Gauge Pressure (GP), and Absolute Pressure (AP). Table 29 lists the protocols, human interface
(HMI), materials, approvals, and mounting bracket options for the ST 700.
Table 29 – ST 700 Basic Transmitter - Features and Options
Feature/Option Basic/Available Options
Communication Protocols HART version 7
Human-Machine Interface (HMI) Options (Standard Display/External Two buttons)
Standard Display (HART only):
Two-button programming (optional)
Standard display language: English only
Two-mode operations: PV display and Menu Navigation
Calibration Single
Approvals See section 0 for details.
FM, CSA, ATEX, IECEx, SAEx, INMETRO, NEPSI, GOST
Mounting Brackets Angle/flat carbon steel/304 and 316 stainless steel,
Integration Tools Experion
The 2-button option is available for the Standard Display.
The External 2-buttons option is available in this model.This is used for navigation of standard display or for setting zero, span and zero correct where standard display is not connected.
Page 74 ST 700 SmartLine Pressure Transmitters User’s Manual Revision 9.0
10.2.1 Physical Characteristics
As shown in Figure 41 the ST 700 Basic transmitter is packaged in two major assemblies: the
Electronics Housing and the Meter Body. The elements in the Electronic Housing respond to setup
commands and execute the software and protocol for the different pressure measurement types.
Figure 42 shows the assemblies in the Electronics Housing with available options.
The Meter Body provides connection to a process system. Several physical interface configurations
are available, as determined by the mounting and mechanical connections, all of which are described
in the Installation section of this manual.
Figure 41 – ST 700 Basic Transmitter - Major Assemblies
Figure 42 – ST 700 Basic transmitter Electronics Housing Components
Revision 9.0 ST 700 SmartLine Pressure Transmitters User’s Manual Page 75
10.2.2 Functional Characteristics
The Transmitter measures process pressure and provides a proportional analog
4 to 20mA output to the measured process variable (PV). Available output communication protocols
include HART.
The Standard display is only available on HART transmitters.
An optional external 2-button assembly is available to set up and make adjustments to the Transmitter.
In addition, a Honeywell Multi-Communication (MC) Toolkit (not supplied with the Transmitter) can
facilitate setup and adjustment procedures. Certain adjustments can be made through an Experion
Station if the Transmitter is digitally integrated with Honeywell’s Experion.
The Standard Display Menu is implemented as one long single-level menu and will “wrap around”
when it reaches the start or end of the menu. The Standard Display uses an optional 2-button
assembly to set up and make adjustments to the Transmitter.
10.3 ST 700 Transmitter Nameplate The Transmitter nameplate mounted on the bottom of the electronics housing (see Figure 42) lists its
model number, physical configuration, electronics options, accessories, certifications, and
manufacturing specialties. Figure 43 is an example of a typical Gauge Pressure (GP) or Atmospheric
Pressure (AP) Transmitter name plate. The model number format consists of a Key Number with
several table selections. The Differential Pressure (DP), Absolute Pressure (AP), and Gauge Pressure
(GP) name plates are essentially the same. The DP model provides one additional entry (7 vs. 6) in
the Meter Body Selections (Table I) to accommodate the static pressure rating.
Figure 43 – ST 700 Basic Transmitter - Name Plate
You can readily identify the series and basic Transmitter type from the third and fourth digits in the
key number. The letter in the third digit represents one of these basic transmitter types:
A = Absolute Pressure D = Differential Pressure F = Flange Mounted
G = Gauge Pressure R = Remote Seals
For a complete selection breakdown, refer to the appropriate Specification and Model Selection
Guide provided as a separate document.
Page 76 ST 700 SmartLine Pressure Transmitters User’s Manual Revision 9.0
10.4 Safety Certification Information An “approvals” name plate is located on the bottom of the Electronics Assembly; see Figure 42 exact
location. The approvals name plate contains information and service marks that disclose the
Transmitter compliance information.
See section 0 of this document for safety certification requirements and details.
10.5 Transmitter Adjustments Zero and Span adjustments are possible in ST 700 Basic Transmitter with the optional external 2-
button and integrated two-button assemblies. See Figure 42 for the external 2-button assembly.
You can also use the Honeywell MC Toolkit or other third-party hand-held configurator to make
adjustments to the ST 700 Basic Transmitter. Alternately, certain adjustments can be made through
the Experion or Universal Station, if the Transmitter is digitally integrated with a Honeywell
Experion or TPS system.
10.6 Display Options –Standard Display
Table 30 – ST 700 Basic Transmitter - Available Display Characteristics
Standard Display 360o rotation in 90o Increments
2 lines, 8 characters
Standard units of measurement: Pa, KPa, MPa, KGcm2, TORR, ATM, inH2O, mH2O, bar, mbar, inHg, FTH2O, mmH2O, MMHG, Flow Units (DP models only) ,PSI , cmH2O and mH2O
Diagnostic messaging
Revision 9.0 ST 700 SmartLine Pressure Transmitters User’s Manual Page 77
10.7 Optional Integrated two-Button Assembly (Standard Display) The Standard Display does not support all the transmitter configuration parameters and has limited
features. The optional Integrated Two-Button Assembly for the Standard Display provides the
following features and capabilities:
Menu and enter key functionality.
With the menu-driven display:
o Comprehensive on-screen menu for navigation.
o Transmitter configuration: enter LRV, enter URV and Loop Test.
o Transmitter calibration
o Display configuration (contrast only)
o Set zero and span parameters.
If you are using the optional external 2-button assembly with the Standard Display then you can perform all the above operations without removing external glass cap using the external buttons
Lower range value (LRV): A display parameter (Standard display), which allows users to enter the measuring value for which the analog output will be scaled to 4mA.
Upper range value (URV): A display parameter (Standard display), which allows users to enter the measuring value for which the analog output will be scaled to 20mA.
Page 78 ST 700 SmartLine Pressure Transmitters User’s Manual Revision 9.0
11. Application Design_ST 700 Basic Transmitter
11.1 Overview This section discusses the considerations involved with deploying a Honeywell ST 700 Basic
Transmitter in a process system. The following areas are covered:
Safety
Input and output data
Reliability
Environmental limits
Installation considerations
Operation and maintenance
Repair and replacement
11.2 Accuracy The ST 700 Basic Transmitter measures the gauge, differential, or absolute pressure of a process and
reports the measurement to a receiving device.
11.2.1 Diagnostic Messages
Transmitter standard diagnostics are reported in the two basic categories listed in Table 4. Problems
detected as critical diagnostics drive the analog output to the programmed burnout level. Problems
detected as non-critical diagnostics may affect performance without driving the analog output to the
programmed burnout level. Informational messages (not listed in Table 4 report various Transmitter
status or setting conditions.
The Standard Display is only available on HART transmitters
The Standard Display only displays critical diagnostics (Meter Body Fault, Electronics Module Fault and Meter Body Communication Fault). Non-critical diagnostics are not displayed.
11.3 Safety
11.3.1 Safety Integrity Level (SIL)
The ST 700 Basic Transmitter has met manufacturer design process requirements of Safety Integrity
Level (SIL) 3. These are intended to achieve sufficient integrity against systematic errors of design by
the manufacturer.
A Safety Instrumented Function (SIF) designed with this product must not be used at a SIL level higher
than the statement, without “prior use” justification by the end user or diverse technology redundancy in
the design.
Refer to the Honeywell SmartLine Safety Manual, Document # 34-ST-25-37, for additional information.
Revision 9.0 ST 700 SmartLine Pressure Transmitters User’s Manual Page 79
12. Installation and Startup_ST 700 Basic Transmitter
12.1 Installation Site Evaluation Evaluate the site selected for the ST 700 Basic Transmitter installation with respect to the process
system design specifications and Honeywell’s published performance characteristics for your
particular model. Some parameters that you may want to include in your site evaluation are:
Environmental Conditions:
o Ambient Temperature
o Relative Humidity
Potential Noise Sources:
o Radio Frequency Interference (RFI)
o Electromagnetic Interference (EMI)
Vibration Sources
o Pumps
o Motorized System Devices (e.g., pumps)
o Valve Cavitation
Process Parameters
o Temperature
o Maximum Pressure Rating
12.2 Honeywell MC Toolkit In preparation for post-installation processes, refer to the MC Tookit User Manual, Document
# 34-ST-25-20, for battery conditioning and device operation and maintenance information.
12.3 Display Installation Precautions Temperature extremes can affect display quality. The display can become unreadable at temperature
extremes; however, this is only a temporary condition. The display will again be readable when
temperatures return to within operable limits.
The display update rate may become slower at cold temperature extremes, but as with readability,
normal updating resumes when temperatures are within limits for full operability.
The Transmitter should not be operated without the endcap covers on. Covers can be removed temporarily for configuration with buttons or during maintenance/wiring.
The static voltage must be discharged before removing the cover.
Page 80 ST 700 SmartLine Pressure Transmitters User’s Manual Revision 9.0
12.4 Mounting_ST 700 Basic Transmitter
12.4.1 Summary
ST 700 Basic Transmitter models, except flush mounts and those with integral flanges, can be
attached to a two-inch (50 millimeters) vertical or horizontal pipe using Honeywell’s optional angle
or flat mounting bracket; alternately you can use your own bracket. Flush-mount models are attached
directly to a process pipe or tank by a one-inch weld nipple. Models with integral flanges are
supported by the flange connection.
Figure 44 shows a typical bracket-mounted and flange-mounted transmitter installations.
Figure 44 – ST 700 Basic Transmitter - Typical Bracket Mounted and Flange Mounted Installations
Revision 9.0 ST 700 SmartLine Pressure Transmitters User’s Manual Page 81
12.5 Flush mounting_ST 700 Basic Transmitter To mount a flush mounted model, cut a hole for a 1” standard pipe in the tank or pipe where the
transmitter is to be mounted. Weld the 1” mounting sleeve to the wall of the tank or to the hole cut on
the pipe. Insert the meter body of the transmitter into the mounting sleeve and secure with the locking
bolt. Tighten the bolt to a torque of 6,4 Nm +/- 0,30 Nm (4.7 ft-lbs +/- 0.2 ft.-lbs.). Figure 45 shows a
typical installation for a transmitter with a flush mount on a pipe.
Once the transmitter is mounted, the electronics housing can be rotated to the desired
position. See Figure 48 for details.
ATTENTION: On insulated tanks, remove enough insulation to accommodate the mounting
sleeve.
Figure 45 - ST 700 Basic Transmitter - Typical Flush Mounted Transmitter Installation
12.5.1 Mounting Dimensions, ST 700 Basic Transmitter
Refer to Honeywell drawing number 50049930 (Dual Head), 50049931 (In-Line), 50049932 (Flange
Mount) 50049933 (Extended Flange), 50049934 (Remote Seal) and 50049936 (Flush Mount Pressure
Transmitter) for detailed dimensions. Abbreviated overall dimensions are also shown on the
Specification Sheets for the transmitter models. This section assumes that the mounting dimensions
have already been taken into account and the mounting area can accommodate the Transmitter.
Page 82 ST 700 SmartLine Pressure Transmitters User’s Manual Revision 9.0
12.5.2 Bracket Mounting Procedure for ST 700 Basic Transmitter,
If you are using an optional bracket, start with Step 1. For an existing bracket, start with Step 2.
5. Refer to Figure 46 for position of the bracket on a 2-inch (50.8mm) nominal, 2.38-inch
(60.4mm) actual, horizontal or vertical pipe, and install a “U” bolt around the pipe and
through the holes in the bracket. Secure the bracket with the nuts and lock washers provided.
Figure 46 – ST 700 Basic Transmitter - Angle Mounting Bracket Secured to a Horizontal or
Vertical Pipe
6. Align the appropriate mounting holes in the Transmitter with the holes in the bracket. Use the
bolts and washers provided to secure the Transmitter to the bracket; see the following
variations.
Table 31 - ST 700 Basic Transmitter - Mounting Bracket procedure
Transmitter Type Use Hardware
DP with double-ended process heads and/or remote seals
Alternate mounting holes in the ends of the heads
In-line GP and AP models (STG7xS and STA7xS)
The smaller “U” bolt provided to attach the meter body to the bracket. See the following example.
Dual-head GP and AP Mounting holes in the end of the process head.
Example: Inline model mounted to an optional angle bracket. See Figure 47.
Revision 9.0 ST 700 SmartLine Pressure Transmitters User’s Manual Page 83
Figure 47 – ST 700 Basic Transmitter - Inline Model Mounted to an Optional Bracket
7. Loosen the set screw on the outside neck of the Transmitter one (1) full turn.
8. Rotate the Electronics housing a maximum of 180o left or right from the center to the position
you require, and tighten the set screw using a 4mm metric socket head wrench. See the
following example and Figure 48.
Example: Rotating the Electronics Housing
Figure 48 – ST 700 Basic Transmitter - Rotating the Electronics Housing
The mounting position of AP models STA725, STA745, STA72S, STA74S and STA77S becomes critical as the Transmitter spans become smaller. A maximum zero shift of 2.5mmHg for these models can result from a mounting position that is rotated 90o from the vertical. A typical zero-shift of 0.12mmHg or 0.20 inH2O can occur for a five (5)-degree rotation from
the vertical.
Page 84 ST 700 SmartLine Pressure Transmitters User’s Manual Revision 9.0
12.5.3 Mounting Transmitters with Small Absolute or Differential Pressure Spans
To minimize positional effects on calibration (zero shift), take the appropriate mounting precautions for the respective Transmitter model. Ensure that the Transmitter is vertical when
mounting models STA725, STA745, STA72S, STA74S and STA77S . You do this by leveling the Transmitter side-to-side and front-to-back.
Figure 49 shows how to level a Transmitter using a spirit level.
Figure 49 – ST 700 Basic Transmitter, using a Spirit Balance to Level a Transmitter
Revision 9.0 ST 700 SmartLine Pressure Transmitters User’s Manual Page 85
12.5.4 Flange Mounting_ST 700 Basic Transmitter
Figure 50 shows a typical tank-flange mount installation, with the Transmitter flange mounted to the
pipe on the wall of the tank.
On insulated tanks, remove enough insulaiton to accommodate the flange extension.
When flange-mounting to a tank, note the following:
The End User is responsible for providing a flange gasket and mounting hardware suitable for
the Transmitter service conditions.
To avoid degrading performance in flush-mounted flanged Transmitters, exercise care to
ensure that the internal diameter of the flange gasket does not obstruct the sensing diaphragm.
To prevent performance degradation in extended-mount flanged Transmitters, ensure that
sufficient clearance exists in front of the sensing diaphragm body.
Figure 50 – ST 700 Basic Transmitter, Tank-Flange Mounted Transmitter
Page 86 ST 700 SmartLine Pressure Transmitters User’s Manual Revision 9.0
12.5.5 Remote Diaphragm Seal Mounting Information_ST 700 Basic Transmitter,
The combination of tank vacuum and high pressure capillary head effect should not exceed nine (9) psi (300mmHg) absolute. For insulated tanks, be sure to remove enough insulation to accommodate the flange extension. The end user is responsible for supplying a flange gasket and mounting hardware suitable for the service condition of the Transmitter.
Mount the Transmitter flanges within the limits in Table 32Table 6 for the fill fluid in the capillary tubes, with a tank at one (1) atmosphere.
Table 32 – ST 700 Basic Transmitter, Flange Mounting Guidelines
Fill Fluid Mount the Flange…
Silicone 200 Oil <22 feet (6.7 meters) below the Transmitter
Chlorotrifluorethylene (CTFE) <11 feet (3.4 meters) below the Transmitter
Refer to Figure 51 for a representative remote diaphragm seal installation. Mount the Transmitter at a
remote distance determined by the length of the capillary tubing.
Figure 51 – ST 700 Basic Transmitter - Representative Remote Diaphragm Seal Transmitter
Installation
Depending on Transmitter model, connect the remote seal to the tank according to Table 33
Table 33 – ST 700 Basic Transmitter - Remote Diaphragm Mounting Details
Transmitter Model
Connect the Remote Seal on ….
Variable Head Fixed or Constant Head
STR735D Transmitter High Pressure (HP) Side to tank wall lower flange mounting.
Transmitter Low Pressure (LP) side to tank wall upper flange.
Revision 9.0 ST 700 SmartLine Pressure Transmitters User’s Manual Page 87
12.6 Piping the ST 700 Basic Transmitter
12.6.1 Piping Arrangements
Piping arrangements vary depending upon process measurement requirements and the Transmitter
model. For example, a differential pressure transmitter comes with double-ended process heads with
¼-inch NPT connections, which can be modified to accept ½-inch NPT through optional flange
adapters. Gauge pressure transmitters are available with various connections for direct mounting to a
process pipe.
A ½-inch, schedule 80, steel pipe is commonly used for Transmitter integration into a process system.
Many piping arrangements use a three-valve manifold to connect the process piping to the
Transmitter. A manifold makes it easy to install and remove or re-zero a Transmitter without
interrupting the process. A manifold also accommodates the installation of blow-down valves to clear
debris from pressure lines. Figure 52 represents a typical piping arrangement using a three-valve
manifold and blow-down lines for a differential pressure transmitter being used to measure flow.
Figure 52– ST 700 Basic Transmitter - Typical 3-Valve Manifold with Blow-Down Piping
Blow-Down
Valve3-Valve
Manifold
To Upstream TapTo Downstream Tap
To Low Pressure
Side of Transmitter
To High Pressure
Side of Transmitter
Blow-Down
Valve
Blow-Down
Piping
To WasteTo Waste
Blow-Down
Piping
21010
Page 88 ST 700 SmartLine Pressure Transmitters User’s Manual Revision 9.0
12.6.2 Suggestions for Transmitter Location
The following are suggested connections based on what is being processed by the system.
Table 34 – ST 700 Basic Transmitter - Suggested Connection Locations
Process Suggested Location Description
Gases Above the gas line. The condensate drains away from the Transmitter.
Liquids Below but near the elevation of the process connection.
This minimizes that static head effect of the condensate.
Level with or above the process connection.
This requires a siphon to protect theTransmitter from process steam. The siphon retains water as a fill fluid.
5. For liquid or steam, the piping should slope a minimum of 25.4mm (1 inch) per 305mm (1 foot).
6. Slope the piping down toward the Transmitter if it is below the process connection to allow
the bubbles to rise back into the piping through the liquid.
7. If the transmitter is located above the process connection, the piping should rise vertically
above the Transmitter. In this case, slope down toward the flow line with a vent valve at the
high point.
8. For gas measurement, use a condensate leg and drain at the low point (freeze protection may
be required here).
ATTENTION Care must be taken when installing transmitters on hot processes. The operating temperature limits for the device (as outlined in Table 5) must not be exceeded. Impulse piping may be used to reduce the temperature of the process that comes
into contact with the transmitter meter body. As a general rule there is a 56C drop (100F) in the temperature of the process for every foot of ½ inch uninsulated piping.
12.6.3 General Piping Guidelines
When measuring fluids that contain suspended solids, install permanent valves at regular
intervals to blow-down piping.
Blow-down all lines on new installations with compressed air or steam, and flush them with
process fluids (where possible) before connecting these lines to the Transmitter Meter body.
Verify that the valves in the blow-down lines are closed tightly after the initial blow-down
procedure and each maintenance procedure thereafter.
12.6.4 Procedure to Install Flange Adapters
The following procedure provides the steps for removing and replacing an optional flange adapter on
the process head. Refer to Figure 53.
This procedure does not require that the Meter body be removed from the Electronics Housing. If flange adapters are being replaced with parts from other kits (for example, process heads), follow the procedures for the kits and incorporate the following procedure.
The threaded hole in each Flange Adapter is offset from center. To ensure proper orientation for re-assembly, note the orientation of the offset relative to each Process Head before removing the adapter.
Revision 9.0 ST 700 SmartLine Pressure Transmitters User’s Manual Page 89
Figure 53 – ST 700 Basic Transmitter - Flange Adapter Removal and Replacement
Refer to the instructions included with the kit for removal and replacement procedures.
12.7 Wiring an ST 700 Basic Transmitter
12.7.1 Overview
The ST 700 basic transmitter is designed to operate in a two-wire power/current loop with loop
resistance and power supply voltage within the operating range shown in Figure 54
Figure 54 – ST 700 Basic Transmitter - Operating Ranges
Page 90 ST 700 SmartLine Pressure Transmitters User’s Manual Revision 9.0
Loop wiring is connected to the Transmitter by simply attaching the positive (+) and negative (–) loop
wires to the positive (+) and negative (–) terminals on the Transmitter terminal block in the
Electronics Housing shown in Figure 55
Figure 55 – ST 700 Basic Transmitter - 3-Screw Terminal Board and Grounding Screw
As shown in Figure 55 each Transmitter has an internal terminal to connect it to earth ground.
Optionally, a ground terminal can be added to the outside of the Electronics Housing. While it is not
necessary to ground the Transmitter for proper operation, doing so tends to minimize the possible
effects of noise on the output signal and affords protection against lightning and static discharge. An
optional lightning terminal block can be installed in place of the non-lightning terminal block for
Transmitters that will be installed in an area that is highly susceptible to lightning strikes.
Wiring must comply with local codes, regulations and ordinances. Grounding may be required to meet various approval body certification, for example CE conformity. Refer to Appendix A of this document for details.
The Transmitter is designed to operate in a two-wire power/current loop with loop resistance and
power supply voltage within the operating range; see Figure 54. With optional devices such as
remote meter, the voltage drop for these options must be added to the basic 10.8-volt supply
requirements to determine the required Transmitter voltage (VXMTR) and maximum loop resistance
(RLOOP MAX). Additional consideration is required when selecting intrinsic safety barriers to ensure that
they will supply at least minimum Transmitter voltage (VXMTR MIN), including the required 250 ohms
of resistance (typically within the barriers) needed for digital communications.
Revision 9.0 ST 700 SmartLine Pressure Transmitters User’s Manual Page 91
Transmitter loop parameters are as follows:
RLOOP MAX = maximum loop resistance (barriers plus wiring) that will allow proper Transmitter
operation and is calculated as RLOOP MAX = (VSUPPLY MIN – VXMTR MIN) 21.8mA.
In this calculation:
VXMTR MIN = 10.8V + VLP + VSM
VLP = 0V for Honeywell supplied lightning protection option, LP VSM = 2.3V, remote meter
Note that VSM should only be considered if a remote meter will be connected to the transmitter.
The positive and negative loop wires are connected to the positive (+) and negative (–) terminals on
the terminal block in the Transmitter Electronics Housing.
Barriers can be installed per Honeywell’s instructions for Transmitters to be used in intrinsically safe
applications.
12.7.2 Digital System Integration Information
Transmitters that are to be digitally integrated to Honeywell’s Total Plant Solution (TPS) system will
be connected to the Pressure Transmitter Interface Module in the Process Manager, Advanced
Process Manager or High Performance Process Manager through a Field Termination Assembly.
Details about the TPS system connections are given in the PM/APM SmartLine Transmitter
Integration Manual, PM12-410, which is part of the TDC 3000X system bookset.
If you are digitally integrating a Transmitter in an Allen Bradley Programmable Logic Controller
(PLC) process system, the same Field Terminal Assembly (FTA) and wiring procedures used with
Honeywell’s TPS system are also used with the Allen-Bradley 1771 and 1746 platforms.
12.7.3 Wiring Variations
The above procedures are used to connect power to a Transmitter. For loop wiring and external
wiring, detailed drawings are provided for Transmitter installation in non-intrinsically safe areas and
for intrinsically safe loops in hazardous area locations.
If you are using the Transmitter with Honeywell’s TPS system, see PM/APM Smartline Transmitter
Integration Manual, PM12-410, which is part of the TDC 3000X system bookset.
12.7.4 Wiring Procedure
7. See Figure 55 above, for parts locations. Loosen the end cap lock using a 1.5mm Allen wrench.
8. Remove the end cap cover from the terminal block end of the Electronics Housing.
9. Feed loop power leads through one end of the conduit entrances on either side of the
Electronics Housing. The Transmitter accepts up to 16AWG wire.
10. Plug the unused conduit entrance with the appropriate plug for the environment.
11. Connect the positive loop power lead to the positive (+) terminal and the negative loop power
lead to the negative (-) terminal. Note that the Transmitter is not polarity-sensitive.
12. Replace the end cap, and secure it in place.
Page 92 ST 700 SmartLine Pressure Transmitters User’s Manual Revision 9.0
12.7.5 Lightning Protection
If your Transmitter includes the optional lightning protection, connect a wire from the Earth Ground
Clamp (see Figure 15) to Earth Ground to make the protection effective. Use a size 8 AWG or
(8.37mm2) bare or green covered wire for this connection.
12.7.6 Supply Voltage Limiting Requirements
If your Transmitter complies with the ATEX 4 directive for self-declared approval per 94/9EC, the
power supply has to include a voltage-limiting device. Voltage must be limited such that it does not
exceed 42V DC. Consult the process design system documentation for specifics.
12.7.7 Process Sealing
The ST 700 SmartLine Pressure Transmitter is CSA-certified as a Dual Seal device in accordance
with ANSI/ISA–12.27.01–2003, “Requirements for Process Sealing Between Electrical Systems and
Flammable, or Combustible Process Fluids.”
12.7.8 Explosion-Proof Conduit Seal
When installed as explosion proof in a Division 1 Hazardous Location, keep covers tight while the Transmitter is energized. Disconnect power to the Transmitter in the non-hazardous area prior to removing end caps for service.
When installed as non-incendive equipment in a Division 2 hazardous location, disconnect power to the Transmitter in the non-hazardous area, or determine that the location is non-hazardous before disconnecting or connecting the Transmitter wires.
Transmitters installed as explosion proof in Class I, Division 1, Group A Hazardous (classified)
locations in accordance with ANSI/NFPA 70, the US National Electrical Code, with 1/2 inch conduit
do not require an explosion-proof seal for installation. If 3/4 inch conduit is used, a LISTED
explosion-proof seal to be installed in the conduit, within 18 inches (457.2mm) of the Transmitter.
Revision 9.0 ST 700 SmartLine Pressure Transmitters User’s Manual Page 93
12.8 Startup
12.8.1 Overview
This section identifies typical start up tasks associated with several generic pressure measurement
applications. It also includes the procedure for running an optional analog output check.
12.8.2 Startup Tasks
After completing the installation and configuration tasks for a Transmitter, you are ready to start up the
process loop. Startup usually includes:
Checking zero input
Reading inputs and outputs
Applying process pressure to the transmitter.
The actual steps in a startup procedure vary based on the type of Transmitter and the measurement
application. In general, the procedures in this section are based on using Honeywell MC Toolkit to
check the Transmitter input and output under static process conditions, and make adjustments as
required initiating full operation with the running process. Note that similar checks can be made using
the optional external 2-button assembly, where the Transmitter is equipped. Operation with the 2-
button assembly is discussed in the Operation section.
When the Standard Display is connected, the two-button assembly for the Standard Display is
present. The buttons will function 1 second after powering up.
12.8.3 Output Check Procedures
The Output Check comprises the following procedures:
The Loop Test procedure checks for continuity and the condition of components in the output
current loop.
The Trim DAC Current procedure calibrates the output of the Digital-to-Analog converter for
minimum (0%) and maximum (100%) values of 4mA and 20mA, respectively. This
procedure is used for Transmitters operating online in analog mode to ensure proper
operation with associated circuit components (for example, wiring, power supply, control
equipment). Precision test equipment (an ammeter or a voltmeter in parallel with precision
resistor) is required for the Trim DAC Current procedure.
The Apply Values procedure uses actual Process Variable (PV) input levels for calibrating
the range of a Transmitter. To measure a liquid level for example, a sight-glass can be used to
determine the minimum (0%) and maximum (100%) level in a vessel. The PV is carefully
adjusted to stable minimum and maximum levels, and the LRV and URV are then set by
commands from the MC Toolkit.
The Transmitter does not measure the given PV input or update the PV output while it operates in the Output mode.
Page 94 ST 700 SmartLine Pressure Transmitters User’s Manual Revision 9.0
12.8.4 Constant Current Source Mode Procedure
Figure 56 – ST 700 Basic Transmitter - Current Loop Test Connections
10. Refer to Figure 56 for test connections. Verify the integrity of electrical components in the output
current loop.
11. Establish communication with the Transmitter. For these procedures, the values of components in
the current loop are not critical if they support reliable communication between the Transmitter
and the Toolkit.
12. On the Toolkit, display the Output Calibration box.
13. In the Output Calibration box, select the Loop Test button; the LOOP TEST box will be
displayed.
14. Select the desired constant-level Output: 0%, 100%, or Other (any between 0% - 100%).
15. Select the Set button. A box will be displayed asking Are you sure you want to place the
transmitter in output mode?
With the Transmitter in Analog mode, you can observe the output on an externally-connected meter or on a local meter. In DE mode, you can observe the output on the local meter or on the Toolkit Monitor display.
16. Select the Yes button. Observe the output current at the percentage you selected in Step 5.
17. To view the monitor display, navigate back from the LOOP TEST display, and select the
MONITOR display. A Confirm popup will be displayed.
18. Select Yes to continue. This concludes the Startup procedure.
Revision 9.0 ST 700 SmartLine Pressure Transmitters User’s Manual Page 95
13. Operation_ST 700 Basic Transmitter
13.1 Overview This section provides the information and processes involved for operation of ST 700 Basic
Transmitter using the external two-button options.
13.2 External Two-Button Operation The ST 700 Basic Transmitter optional external two-button interface provides a user interface and
operation capability without opening the transmitter. Figure 57 shows the location of the two-button
option and the labels for each button. See Table 38 for button operation.
Figure 57 – ST 700 Basic Transmitter - Two-Button Option
Page 96 ST 700 SmartLine Pressure Transmitters User’s Manual Revision 9.0
Figure 58 – ST 700 Basic Transmitter - Two-Button Option
13.2.1 The Standard Display Menu
The Standard Display Menu is implemented as one long single-level menu, after entering into Menu
mode, and will “wrap around” when it reaches the end of the menu. To enter Menu mode select in
PV display mode. Operation is as follows:
6. Select <Exit Menu> and press to exit the Menu.
7. Use the buttons to scroll through the list of menu items.
8. Press the button to select an item in Menu mode for data entry or activation. When an item
is selected for data entry or activation, the cursor will jump to the lower line of the LCD to
allow editing of the value. No action is taken against a menu item until the user presses the
button.
9. If you want to abort a data entry operation, simply refrain from pushing any buttons for more
than 10 seconds; the data entry operation will time out and the original value of the selected
item will be preserved.
10. If you want to abort a menu operation, simply refrain from pushing any buttons for more than
60 seconds; the menu operation will time out and the exit from menu & it will show PV
value.
The menu is divided into Standard Menu and Extended menu which can be enabled and disabled
by Extended Menu Enable/Disable operation.
Note: The abort option is not available for Loop test parameter. The timeout for the DAC trim
operation is more to enable user to calculate the loop current value to enter.
Revision 9.0 ST 700 SmartLine Pressure Transmitters User’s Manual Page 97
Table 35 – ST 700 Basic Transmitter: Standard Display Menus
PV Display [1SEL PV]
Pressure (PRESURE) Pressure Units
Select Process Variable (PV) to be shown on the display from list.
Press to enter Menu Mode
Press to enter menu selection
Press to initiate action Press
Menu to Exit to Menu
Percent Output (% OUT) %
Loop Output (LOOPOUT) mA
Flow (FLOW) Note: Before seleting PV type as Flow, please ensure the LRV/URV values in (pressure unit) are as per application. For PV type Flow the pressure unit will not be visible.
Flow unit
Pressure Units [2UNITS] (Visible for all PV except Flow)
atm, bar ftH2O @ 68ºF gf/cm2 inH2O @ 39ºF inH2O @ 60ºF inH2O @ 68ºF inHg @ 0ºC kgf/cm2, kPa mbar, mmH2O @ 4ºC, mmH2O @ 68ºF, mmHg @ 0ºC, MPa, Pa, psi Torr, mH2O @ 4ºC cmH2O @ 4ºC mHg @ 0ºC
Choose appropriate engineering units from list
Flow Units [3FLUNIT]
Cubic
meter/hour[m3/hr] Kg/hour
[Kg/hr]
Metric Ton/Hour [MT/hr]
Liter per second [L/sec]
Liters/hour [L/hr]
Standard Cubic feet per
hour[SCFH]
Cubic feet per hour[CFH]
Gallons/hour[gal/hr]
Barrel/hours [bbl/hr]
Imperial
Gallons/hours[Igal/hr]
Percentage[%]
Choose appropriate engineering units from list
Page 98 ST 700 SmartLine Pressure Transmitters User’s Manual Revision 9.0
Scaling Low [4SCLLOW ] Scaling High [5SCLHIG ]
#. ## #. ##
The limits are: -999999 to 999999
Press to enter Menu Mode
Press to enter menu selection
Menu to select number.
to enter and shift to the next digit to the right After complete value is Entered Press
Menu to Exit to Menu
Enter LRV [6ENTLRV] Enter URV [7ENTURV]
#. ## #. ##
The limits are: 2X the Lower Range Limit (LRL) of the Meter body and 2X the Upper Range Limit (URL) of the Meter body. The LRV/URV value will be available in Pressure Units (Standard Display pressure unit)
Zero Correct [8SETZRO]
Zero Correct Executing this selection performing for Zero Correct operation
Press to enter Menu Mode
Press to enter menu selection
Press to initiate action Press
Menu to Exit to Menu
Revision 9.0 ST 700 SmartLine Pressure Transmitters User’s Manual Page 99
Table 36 – ST 700 Basic Transmitter - Extended Display Menu
DAC Zero Trim [9ZEROTR] Note: Loop must be removed from Automatic Control
DAC Zero Trim
This selection allows the loop zero output 4mA value to be trimmed.
Note: You must connect a current meter to the transmitter to monitor the loop output.
Press to enter Menu Mode
Press to enter menu selection
Menu to select number.
to enter and shift to the next digit to the right After complete value is Entered Press
Menu to Exit to Menu
DAC Span Trim [10SPANTR] Note: Loop must be removed from Automatic Control
DAC Span Trim
This selection allows the loop span output 20mA value to be trimmed. Note: You must connect a current meter to the transmitter to monitor the loop output.
Loop Test [11LPTEST] Note: Loop must be removed from Automatic Control
Loop Test 12.000
This selection allows the user to force the DAC output to any value between 3.8 and 20.8 mA. Note: This selection will put the DAC into Fixed Output Mode, as indicated by the flashing output value. Navigation away from this menu item will return the loop to Normal (Automatic) Mode.
Set LRV [12SETLRV]
Set LRV Executing this selection performing for Zero operation.
Press to enter Menu Mode
Press to enter menu selection
Press to initiate action
Set URV [13SETURV]
Set URV Executing this selection for Span operation
Contrast [14CNTRST ]
»»»»»
Adjust the LCD contrast level. Range from » (1) to »»»»»»»»» (7) Default: »»»»»»»(7)
Enable Extended Menu [EXDMNU ]
Enable/Disable Enable the extended Menu.The default is disabled
Press toto Enter the Menu Mode
Press to enter Menu selection Menu to Enable or disable the Extended Menu
to Enter Press
Menu to Exit to Menu
Exit Menu
Page 100 ST 700 SmartLine Pressure Transmitters User’s Manual Revision 9.0
13.2.2 Standard Display Abbreviations:
Table 37 – ST 700 Basic Transmitter - The Standard Display abbreviations
Abbreviation Meaning OOR Out of Range
PRSPAN Push reduce span
Wrng Mo Wrong Mode
Illegal Illegal Value
Wrt Err NVM write error
Too Hi Value/Parameter Too High
Too Lo Value/Parameter Too Low
LRV Hi LRV too High
LRV Lo LRV too Low
LargeSP Span too large
SmallSP Span too small
Locked Device is locked
Multidr Device in multidrop mode
Wrt Prt Device in write protect mode
NotSprt Not supported
Hi LMT Value is greater than high Limit value
Low LMT Value is less than low Limit value
Revision 9.0 ST 700 SmartLine Pressure Transmitters User’s Manual Page 101
13.2.3 Data Entry
Data entry is performed from left to right. Select a character / digit by pressing buttons, and then
press to advance to the next character position to the right. Select the cross-hatch character ▒ to
terminate the entry or if the final character is already a space character, just press << again.
All numeric entries are clamped at the low or high limit if needed. You can determine the low and
high limit for a parameter by selecting either the H or L character while the cursor is positioned over
the left-most digit and press button. The Display will show the selected limit.
For numeric entry sign is required to be entered only for negative numbers. For positive number,
select space and move ahead.
Table 38 – ST 700 Basic Transmitter - Two-Button Data Entry
Screen Symbol
Numeric data entry
H Display the high limit for this parameter. This symbol only appears in the left-most position of the data entry field.
L Display the low limit for this parameter. This symbol only appears in the left-most position of the data entry field.
<< Terminate the numeric entry
0 thru 9, Minus, Decimal
These characters are used to enter numeric values. The minus sign only appears in the left-most digit.
13.2.4 Editing a Numeric value
Editing a numeric value is a digit-by-digit process, starting with the left-most digit.
1. Press to begin the edit process.
2. The Standard Display will show the current value of the item on the lower line, left justified.
3. Press the buttons to select the desired digit, and then press to advance to the next digit to
the right.
4. After the last digit has been entered, press one more time to write the new value to the
transmitter.
13.2.5 Selecting a new setting from a list of choices
Use the procedure described below to select a new setting for parameters that present a list of choices
(e.g. PV Display, Pressure Units, and so forth.).
1. Press to begin the edit process.
a. The Standard Display will show the current setting of the item on the lower line
2. Press the buttons to scroll through the list of choices.
3. Press to make your selection. The new selection will be stored in the transmitter and will
be displayed on the lower line
Page 102 ST 700 SmartLine Pressure Transmitters User’s Manual Revision 9.0
13.3 Two Button Operation with no Display Installed When there is no Display installed, the buttons can be used to perform a Zero or Span adjustment and
zero correction of the ST 700 Basic Transmitter. Caution should be taken to insure these adjustments
are only made when the correct input pressures are applied.
13.3.1 Zero Adjustment
This adjustment is the same as performing a Set LRV using the Display.
1. Connect a current meter or voltmeter as shown in Figure 56 to monitor the PV output of the
Transmitter.
2. Using an accurate pressure source, apply pressure equivalent to the Transmitter LRV.
3. Press the Zero ( ) button for more than 2 seconds to set the Zero.
4. Verify that the output is now 4 mA.
Note: Pressing the zero button for more than 5 seconds will ignore the button press.
13.3.2 Span Adjustment
This adjustment is the same as performing a Set URV using the Display.
1. Connect a current meter or voltmeter as shown in Figure 56 to monitor the PV output of the
Transmitter.
2. Using an accurate pressure source, apply pressure equivalent to the desired Upper Range
Value of the transmitter.
3. Press the Span ( ) button for more than 2 secondsr to set the span.
4. Verify that the PV output is now 20mA.
Note: Pressing the zero button for more than 5 seconds will ignore the button press.
13.3.3 Zero Correction
This adjustment is the same as performing a Zero correct using the Display.
1. Connect a current meter or voltmeter as shown in Figure 56 to monitor the PV output of the
Transmitter.
2. Using an accurate pressure source, apply pressure equivalent to the zero Value of the
transmitter.
3. Press the Zero ( ) and Span ( ) buttons together for more than 5 sec to set the span.
4. Verify that the PV is set to 0 value.
Note: Pressing the SPAN button for more than 10 seconds will ignore the button press
You can also use the MCT Toolkit to make any adjustments to an ST 700 SmartLine Pressure Transmitter. Alternately, certain adjustments are possible through an Experion Station , if the ST 700 is digitally integrated with either of these stations.
Revision 9.0 ST 700 SmartLine Pressure Transmitters User’s Manual Page 103
13.4 Changing the Default Failsafe Direction ST 700 Basic Transmitters are shipped with a default failsafe direction of upscale. This means that the
Transmitter output will set the current output to upscale failsafe (maximum output) upon detection of
a critical status. You can change the direction from upscale failsafe to downscale failsafe (minimum
output) by moving the top jumper located in the Electronics module.
13.4.1 Procedure to Establish Failsafe Operation
The failsafe direction display accessible via the Toolkit shows only the state of the jumper as it correlates to analog Transmitter operation.
The integrated circuits in the Transmitter PWA are vunerable to damage by stray static discharges when removed from the Electronics Housing. Minimize the possibility of static discharge damage when handling the PWA as follows:
Do not touch terminals, connectors, component leads, or circuits when handling the PWA.
When removing or installing the PWA, handle it by its edges or bracket section only. If you need to touch the PWA circuits, be sure you are grounded by staying in contact with a grounded surface or by wearing a grounded wrist strap.
When the PWA is removed from the Transmitter, put it in an electrically conductive bag, or wrap it in aluminum foil to protect it.
The following procedure outlines the steps for positioning the write protect and failsafe jumpers on
the electronics module. See Figure 59 for the locations of the failsafe and write protect jumpers.
Figure 59 – ST 700 Basic Transmitter - Locating the Failsafe and Write Protect Jumpers
Page 104 ST 700 SmartLine Pressure Transmitters User’s Manual Revision 9.0
Table 39 – ST 700 Basic Transmitter - HART Failsafe and Write Protect Jumpers
Jumper Arrangements
Description
Failsafe = UP (High)
Write Protect = OFF (Not Protected)
Failsafe = DOWN (Low)
Write Protect = OFF (Not Protected)
Failsafe = UP (High)
Write Protect = ON (Protected)
Failsafe = Down (Low)
Write Protect = On (Protected)
1. Turn OFF Transmitter power (Power removal is only required in accordance with area safety
approvals. Power removal is only required in Class 1 Div 1 Explosionproof and Class 1 Div
2 environments).
2. Loosen the end cap lock, and unscrew the end cap from the electronics side of the Transmitter
housing.
3. If equipped with a Display module, carefully depress the two tabs on the sides of the Display
Module, and pull it off.
4. If necessary, unplug the interface connector from the Communication module. Do not discard
the connector.
5. Set the Failsafe Jumper (top jumper) to the desired position (UP or DOWN). See Figure 59?
and Table 39 for jumper positioning.
6. If applicable, re-install the Display module as follows:
Orient the display as desired.
Install the Interface Connector in the Display module such that it will mate
with the socket for the display in the Communication module.
Carefully line up the display, and snap it into place. Verify that the two tabs
on the sides of the display latch.
Note: Installing a Display Module into a powered transmitter may cause a temporary upset to
the loop output value.
Orient the Display for proper viewing through the end cap window. You can rotate the meter mounting orientation in 90o increments.
7. Restore transmitter power if removed.
Revision 9.0 ST 700 SmartLine Pressure Transmitters User’s Manual Page 105
13.5 Monitoring the Standard Displays This section describes the information shown on the operator screens of the Standard Display.
13.5.1 Standard Display
The PV value is user-configurable. This field has 6 characters. The maximum allowable
numeric value is 999999 or -999999.
o If fractional decimals are configured, the fractional positions will be dropped, as
required.
o If the PV value exceeds the above limits, it is divided by 1000 and “K” is appended
to the result, allowing a maximum value with multiplier of 99999K or -99999K.
Special Symbol (Square root)
PV Value
Display Unit
Special Symbol (Write Protect)
Figure 60 – ST 700 Basic Transmitter - Standard Display with Process Variable Format
PV Value
Unit
Page 106 ST 700 SmartLine Pressure Transmitters User’s Manual Revision 9.0
14. Maintenance_ST 700 Basic Transmitter
14.1 Overview This section provides information about preventive maintenance and replacing damaged parts. The
topics covered in this section are:
Preventive maintenance of the meter body barrier diaphragms and process piping to the
Transmitter.
Replacement of damaged parts such as the Transmitter Printed Wiring Assembly (PWA) and
meter body
14.2 Preventive Maintenance Practices and Schedules The ST 700 Basic Transmitter does not require any specific maintenance at regularly scheduled
intervals. However, it is recommended that you perform these typical inspection and maintenance
routines on a schedule that is dictated by the characteristics of the process medium and if blow-down
facilities or purge systems are being used.
Check piping for leaks.
Clear piping of sediment or other foreign matter.
Clean the Transmitter process heads, including the barrier diaphragms.
14.3 Inspecting and Cleaning Barrier Diaphragms Depending on the characteristics of the process medium, sediment or other foreign particles may
collect in the process head cavity/chamber and cause faulty measurement. In addition, the barrier
diaphragm(s) in the Transmitter meter body may become coated with residue from the process
medium. The latter is also true for external diaphragms on flange-mount and remote seal type
Transmitters.
In many cases, you can readily remove the process head(s) from the Transmitter meter body to clean
the process head cavity and inspect the barrier diaphragm(s). For flange-mount and remote seal
diaphragms, you may only need to run a purge line in the tank to rinse off the face of the
diaphragm(s).
The following procedure comprises the general steps for inspecting and cleaning barrier diaphragms.
You may have to modify these steps to meet your particular process or transmitter model
requirements. Figure 61 shows an exploded view of a Differential Pressure (DP) Transmitter meter
body for reference. For disassembly/reassembly purposes, Gauge Pressure (GP) and Absolute
Pressure (AP) Transmitters are similar.
It is recommended that you remove the Transmitter from service and move it to a clean area before disassembling it.
Revision 9.0 ST 700 SmartLine Pressure Transmitters User’s Manual Page 107
Figure 61 – ST 700 Basic Transmitter - DP Transmitter Head Disassembly
13. Close all valves to isolate the Transmitter from the process.
14. Open the vent in the process head to drain fluid from the Transmitter meter body, as
necessary.
15. Remove the Transmitter from the process.
16. Loosen the nuts in the sequence shown in Figure 62
17. Remove the nuts from the bolts that hold the process head(s) to the meter body.
18. Remove the process heads and bolts.
19. Remove the gasket/ O-ring, and clean the interior of the process head using a soft bristle
brush and an approved solvent.
20. Inspect the barrier diaphragm for signs of deterioration, corrosion, and distortion.
21. If the diaphragm is distorted contact Honeywell for assistance.
22. Install a new gasket/O-ring in each process head.
23. Coat threads on the process head bolts with a suitable anti-seize compound, such as
“Neverseize,” or equivalent.
24. Using a torque wrench, gradually tighten the nuts in the sequence shown in Figure 62
25. Tighten head bolts in stages of 1/3-full torque, 2/3-full torque, and full torque. See Table 40
or torque requirements versus Transmitter type and model.
Page 108 ST 700 SmartLine Pressure Transmitters User’s Manual Revision 9.0
Figure 62 – ST 700 Basic Transmitter - Head Bolt Tightening Sequence
Table 40 – Head Bolt Torque Values
Bolting Type 50049713XXXX all transmitters except draft range (XXX5)
50049713XXX5 Draft Range Transmitter only
Super Duplex Bolting Option Bolt 514452557-006 Nut 51452559-006
48,8 N-M +/- 2,4 N-M (36.0 Lb-Ft +/- 1.8 Lb-Ft)
20,3 N-M (16.0 Lb-Ft +/- 0.8 Lb-Ft)
316 Stainless Steel Bolting Option Bolt 51452557-003 Nut 51452559-004 56,9 N-M +/- 2,8 N-M
(42.0 Lb-Ft +/- 2.1 Lb-Ft) Grade 660 NACE Bolts/NACE 304 Nuts Option Bolt 51452557-002 Nut 51452559-002
Grade 660 NACE Bolting Option Bolt 51452557-002 Nut 51452559-008 67,8 N-M +/- 3,4 N-M
(50.0 Lb-Ft +/- 2.5 Lb-Ft) Carbon Steel Bolting Option Bolt 51452557-001 Nut 51452559-001
Revision 9.0 ST 700 SmartLine Pressure Transmitters User’s Manual Page 109
14.4 Replacing the Communication Module The Communication module includes a connector to the sensor ribbon cable and a connector to the
optional Display module. This section includes the procedure to replace the Communication module.
The transmitter does not have to be removed from service to replace the Comm Module
Please take appropriate steps to avoid ESD damage when handling the Communication and Display Module assemblies
Refer to Figure 63 for parts locations.
Figure 63 – ST 700 Basic Transmitter - PWA Replacement
1. Turn OFF Transmitter power (Power removal is only required in accordance with area
safety approvals. Power removal is only required in Class 1 Div 1 Explosion-proof and
Class 1 Div 2 environments).
When removing the Communications Module with power applied, the loop will go
to 0V. Likewise, installing a Communications Module into a transmitter with power
applied will cause the loop output value to go to 12ma for several seconds then the
loop output value will go to the configured value based on the PV input.
Installing a Display Module into a powered transmitter may cause a temporary upset
to the loop output value.
2. Loosen the end cap lock, and unscrew the end cap from the electronics side of the
Transmitter housing.
3. If equipped with a Display module, carefully depress the two tabs on the sides of the
Display Module, and pull it off.
Page 110 ST 700 SmartLine Pressure Transmitters User’s Manual Revision 9.0
4. If necessary, unplug the interface connector from the Communication module. Do not
discard the connector.
5. Loosen the two retaining screws, and carefully pull the Communication module from the
Electronics compartment.
6. Carefully align and connect the Sensor Ribbon Cable to the connector “J4” at the bottom of
the Communication module. When installing the Communication module in the next step, be
careful not to pinch the Sensor Ribbon Cable.
7. Carefully, insert the Communication module into the Electronics compartment. Ensure that
the Sensor Ribbon Cable is not pinched.
8. Tighten the two Communication module retaining screws.
9. Refer to the SmartLine User's Manual to change the FAILSAFE, READ/WRITE
configuration settings.
10. If applicable, re-install the Display module as follows:
d. Orient the display as desired.
e. Install the Interface Connector in the Display module such that it will mate with the
socket for the display in the Communication module.
f. Carefully line up the display, and snap it into place. Verify that the two tabs on the
sides of the display latch.
Orient the Display for proper viewing through the end cap window. You can rotate the meter mounting orientation in 90 o increments.
11. Apply Parker Super O-ring Lubricant or equivalent to the end cap O-ring before installing the
end cap. Reinstall the End Cap and tighten the End Cap locking screw.
12. Installing Optional External Configuration Button Assembly.
d. Loosen (Do Not Remove) both top nameplate screws and pivot nameplate 90°.
e. Align the protrusion on the button assembly with the matching opening in the
housing and snap the button assembly into the housing.
f. Rotate the nameplate back to the original position, and tighten the nameplate screws.
Revision 9.0 ST 700 SmartLine Pressure Transmitters User’s Manual Page 111
14.5 Replacing the Meter Body You can replace the complete meter body, including the process heads, or the meter body only on
certain Differential Pressure (DP), Gauge Pressure (GP), and Atmospheric Pressure (AP) Transmitters
by using the existing process head(s). Use the following procedure for meter body-only replacement.
1. Save or record device configuration data.
2. Turn off Transmitter power.
3. Remove the Transmitter from service, and move it to a clean area before disassembling it.
4. Refer to Figure 64. Loosen the End Cap Lock, and unscrew the End Cap from the electronics
side of the Transmitter housing.
Figure 64 – ST 700 Basic Transmitter - Disassembly for Meter Body Replacement
Please take appropriate steps to avoid ESD damage when handling the Communication and Display Module assemblies
5. If a display is present, press the two snaps along the side, and remove it from the
communication module assembly.
Note: Do not discard or misplace the Display/Communication connector, it will be required
to reassemble the Display Module
6. Loosen the two retaining screws, and remove the Communications Module assembly, and
remove the Communication Module assembly from the electronics housing.
7. Disconnect the Sensor Cable from the Communications Board.
8. Refer to Figure 66. Use a 2mm hex wrench to completely loosen the set screw on the outside
of the housing to permit rotating the meter body.
Page 112 ST 700 SmartLine Pressure Transmitters User’s Manual Revision 9.0
Figure 65 – ST 700 Basic Transmitter - Hardware Location to Remove the Meter Assembly
9. Carefully turn the complete meter body counterclockwise to unscrew it from the electronics
housing.
10. Remove the nuts from bolts that hold the process head(s) to the Meter Body.
11. Remove process heads and bolts.
12. Remove the gaskets or O-rings from the process heads.
13. Clean the interior of the process head(s) with a soft bristle brush and suitable solvent.
CAUTION: To prevent damage to the diaphragm in the Meter Body, use extreme care when handling or placing the Meter Body on any surface. Carefully assemble gaskets or O-rings to the meter body. If installing O-rings, lubricate with water or leave dry.
14. Coat threads on process head bolts with anti-seize compound such as “Neverseize” or
equivalent.
15. Refer to Figure 66. Apply Dow Corning #33 silicone grease to the meter body adapter O-ring
and carefully assemble the O-ring to the meter body. Assemble the process head(s) and bolts
to the new meter body. For now, make the bolts only finger-tight.
Revision 9.0 ST 700 SmartLine Pressure Transmitters User’s Manual Page 113
Figure 66 – ST 700 Basic Transmitter - Meter Body Reassembly
16. Use a torque wrench to gradually tighten nuts to torque rating in sequence shown in Figure 67.
Tighten head bolts in stages of 1/3 full torque, 2/3 full torque, and then full torque as per Table
40.
Figure 67 – ST 700 Basic Transmitter - Head Bolt Tightening Sequence
17. Feed the ribbon cable on the new meter body through the neck of the housing.
CAUTION: To prevent damage to the ribbon cable, use care when assembling the Meter Body to the electronics housing.
18. Screw the new meter body into the housing until the bottom of the Meter Body adapter is
flush with the neck of the electronics housing.
Page 114 ST 700 SmartLine Pressure Transmitters User’s Manual Revision 9.0
19. Tighten the outside set screw to be sure it is fully seated in the slot in the header.
20. Loosen the set screw ½- turn.
21. Rotate the housing to the desired position (Max. 180o in either direction), and tighten the set
screw.
22. Carefully align and connect the Sensor Ribbon Cable to connector “J4” at the bottom of the
Communication module board. When installing the Communication module in the next step,
be careful not to pinch the Sensor Ribbon Cable.
23. Carefully, insert the Communication module into the Electronics compartment. Ensure that
the Sensor Ribbon Cable is not pinched.
24. Tighten the two Communication module retaining screws.
25. If applicable, re-install the Display module as follows:
d. Orient the display as desired.
e. Install the Interface Connector in the Display module such that it will mate with
the socket for the display in the Communication module.
f. Carefully line up the display, and snap it into place. Verify that the two tabs on
the sides of the display latch.
Orient the Display for proper viewing through the end cap window. You can rotate the meter mounting orientation in 90 o increments.
26. Connect the bracket to the Transmitter housing.
27. Recalibrate the Transmitter per section Calibration_ST 700 Basic Transmitter, of this
document.
28. Return the Transmitter to service, and turn ON power
29. Verify the Transmitter configuration data. Restore the saved database if necessary.
30. Lubricate the end-cap O-ring with Parker Super O-ring silicone lubricant or equivalent before
replacing the end caps.
Revision 9.0 ST 700 SmartLine Pressure Transmitters User’s Manual Page 115
15. Calibration_ST 700 Basic Transmitter
15.1 Recommendations for Transmitter Calibration The ST 700 Basic Transmitter does not require periodic calibration to maintain accuracy. Typically,
calibration of a process-connected Transmitter will degrade, rather than augment the capability of a
smart Transmitter. For this reason, it is recommended that a Transmitter be removed from service
before calibration. Moreover, calibration will be accomplished in a controlled, laboratory-type
environment, using certified precision equipment.
15.2 Calibration Procedures For a transmitter operating in analog mode, you must calibrate its output signal measurement range
using any compatible hand-held communicator or a local display.
One calibration option is to use the Honeywell Smart Field Communicator (SFC). Refer to the Smart
Field Communicator Operating Guide, Document # 34-ST-11-14 for calibration procedures.
Calibration information and procedures for a Transmitter operating in the HART/DE mode are
provided in the ST 700 Series HART/DE Option User’s Manual, Document # 34-25-25-47.
Page 116 ST 700 SmartLine Pressure Transmitters User’s Manual Revision 9.0
16. Troubleshooting_ST 700 Basic Transmitter
16.1 Overview Troubleshooting involves responding to error messages, primarily displayed by the MC Toolkit. Error
messages that may occur on the Transmitter’s local display are fairly self-explanatory and intuitive.
However, this section covers the diagnostic messages that indicate critical conditions. Other than the
critical conditions, additional detail is not provided. If you require assistance, contact your distributor
or Honeywell Technical Support. All other messages are covered by the MC Toolkit Users’ Manual.
16.2 Critical Diagnostics Screens The Standard Display will display the fault message on the top line of the LCD .
16.2.1 Fault Conditions and Recommended Corrective Actions – Standard Display
The Standard Display will display the message FAULT on the top line of the LCD and the
appropriate diagnostic text on the lower line.
Table 41 – ST 700 Basic Transmitter - Fault Conditions and Recommended Corrective Actions.
Condtion Analysis Recommended Corrective
Action
Mbd Com (Meter body Comm fault)
Communications between the Meter body and the Electronics Module has failed.
Check the ribbon cable that connects the Meter body to the Electronics Module. Ensure that the cable is securely plugged into the Electronics Module. Ensure that all pins are plugged into the connector (e.g. ensure that the connector is not offset in a way that leaves some pins unconnected). Cycle power to the transmitter. If the problem continues to occur replace the Electronics Module. If this does not fix the problem, replace the Meter body.
Comm El (Communication Board fault)
A critical failure has been detected on the HART Electronics Module.
Cycle power to the transmitter. If the problem continues to occur replace the Electronics Module.
Mtrbody (Sensor Board Fault)
A critical failure has been detected in the Meter body
Cycle power to the transmitter. If the problem continues to occur replace the Electronics Module.
Revision 9.0 ST 700 SmartLine Pressure Transmitters User’s Manual Page 117
17. Parts List_ST 700 Basic Transmitter
17.1 Overview Individually saleable parts for the various Transmitter models are listed in this section. Some parts are
illustrated for identification. Parts are identified and listed in the corresponding tables as follows:
Individually saleable parts are indicated in each figure by key number callout.
Parts that are supplied in kits are indicated in each illustration by key number callout with the
letter K prefix.
Table 42 is a list of recommended spare parts.
Table 42 – ST 700 Basic Transmitter - Summary List of Recommended Spare Parts
Part Number Description Figure
No. Key No.
1-10 Units
10-100 Units
100-1000 Units Electronics Assembly
50129828-501 50129828-502
HART Comm Assembly without external 2 button support HART Comm Assembly with external 2 button support
Figure 69 5 1 1-2 2-4
51452865-501 51452865-502 51452865-503 51462865-504
Meter Body Seal kit (includes O-rings) Glass Filled PTFE VITON 100% PTFE GRAPHITE
Figure 72 K1 1 1-2 2-4
50129832-501 50129832-502
HART Terminal Block Assy Without Lightning Protection HART Terminal Block Assy With Lightning Protection
Figure 70 3 1 1-2 2-4
Page 118 ST 700 SmartLine Pressure Transmitters User’s Manual Revision 9.0
Process head gasket kit
Figure No.
Key No.
1-10 Units
10-100 Units
100-1000 Units
51452868-501 51452868-502 51452868-507
Gasket only, Process Head (12 PTFE packs) Gasket only, Process Head (6 Viton Head O’Rings) Gasket only, Process Head Graphite Gasket (replacement only for existing graphite gasket)
Figure 72 Ka
12
12-24
24-48
6 6-12 12-24
6 6-12 12-24
Meter Body
Specify complete model number from nameplate
DP Models GP/AP HEAD Models LGP/LAP Models Flush Mount Models Flange Mount Models
Figure 71
1 1-2 2-4
Figure 68 – ST 700 Basic Transmitter - Angle and Flat Bracket Parts (refer to Table 43)
Revision 9.0 ST 700 SmartLine Pressure Transmitters User’s Manual Page 119
Table 43 – ST 700 Basic Transmitter - Angle and Flat Bracket Parts
(Refer to
Figure 68)
Key No.
Part Number Description Quantity Per Unit
1 50132311-511 Carbon Steel Angle Bracket for all models except In-line and Flush mount transmitters (CHINA MARKET ONLY)
1
2 50132311-521 Carbon Steel Angle Bracket for all In-line and Flush mount transmitters (CHINA MARKET ONLY)
1
3 51196557-501 Carbon Steel Flat Bracket Mounting kit for all models except In-line and Flush mount transmitters
1
4 51196557-502 Carbon Steel Flat Bracket Mounting kit for all In-line transmitters and Flush mount transmitters
1
5 30752770-603 SS 304 Angle Bracket Mounting kit for all models except In- line and Flush mount transmitters
1
6 30752770-604 SS 304 Angle Bracket Mounting kit for all In-Line and Flush mount transmitters
1
7 51196557-505 SS 304 Flat Bracket Mounting kit for all models except In-line and Flush mount transmitters
1
8 51196557-506 SS 304 Flat Bracket Mounting kit for all In-line transmitters and Flush mount transmitters
1
9 50132311-513 SS 316 Angle Bracket Mounting kit for all In-line transmitters and Flush mount transmitters (CHINA MARKET ONLY)
1
10 50132311-523 SS 316 Angle Bracket Mounting kit for all models except In-line and Flush mount transmitters (CHINA MARKET ONLY)
1
11 51196557-508 SS 316 Flat Bracket Mounting kit for all In-line transmitters except In-Line and Flush mount transmitters
1
12 51196557-509 SS 316 Flat Bracket Mounting kit for all In-Line and Flush mount transmitters
1
1 50132311-511 Carbon Steel Angle Bracket for all models except In-line and Flush mount transmitters (CHINA MARKET ONLY)
1
2 50132311-521 Carbon Steel Angle Bracket for all In-line and Flush mount transmitters (CHINA MARKET ONLY)
1
Page 120 ST 700 SmartLine Pressure Transmitters User’s Manual Revision 9.0
Figure 69 – ST 700 Basic Transmitter - Electronic Housing, Display End
Table 44 – ST 700 Basic Transmitter - Major Assemblies
(Refer to Figure 69, Figure 70 and Figure 72)
Key No.
Part Number Description Quantity Per Unit
1 50049858-501 50049858-521
End Cap (Aluminum) End Cap (Stainless Steel)
1
2 50049832-501 50049832-521
End Cap, Display (Aluminium) with window End Cap, Display (Stainless Steel) with window
1
3 50129832-501 50129832-502
Terminal Assy HART without Lightning protection Terminal Assy HART with Lightning protection
1
4 50049911-501 50126003-501
Basic Display Standard Display
1
5 50129828-501 50129828-502
HART Electronics Module Assembly (PWA) without MR sensor HART Electronics Module Assembly (PWA) with MR sensor
1
6 50131077-501 External Zero, Span & Config Buttons (2- button Assembly) 1
K1 30757503-005 Electronics housing seals kit (includes O-rings) 2
Revision 9.0 ST 700 SmartLine Pressure Transmitters User’s Manual Page 121
Figure 70 – ST 700 Basic Transmitter - Electronic Housing, Terminal Block End
Page 122 ST 700 SmartLine Pressure Transmitters User’s Manual Revision 9.0
Figure 71 – ST 700 Basic Transmitter - Major Assemblies
Revision 9.0 ST 700 SmartLine Pressure Transmitters User’s Manual Page 123
Table 45 – ST 700 Basic Transmitter STG735, 745, 775, STD 725, 735, 775 & STA725 & 745, Transmitter Body. (Refer to Figure 72)
Key No.
Part Number Description Qty/Kit
Meter Body Gasket Kits
51452865-501 51452865-502 51452865-503 51452865-504
Glass Filled PTFE VITON 100% PTFE GRAPHITE
Each Meter Body Gasket Kit includes:
K6 Gasket, Process Head (6 Gaskets/ 1 Kit) 6
Ka Gasket, Flange Adapter (6 Gaskets/ 1 Kit) 6
K7 O-Ring, Meter Body to Electronics Housing (3 Gaskets/ 1 Kit) 3
K7 Process Head Gasket Kits
K6 K6 K6
51452868-501 51452868-502 51452868-507
Gasket only, Process Head (12 PTFE Gaskets/pack) Gasket only, Process Head (6 Viton Head O-Rings) Gasket only, Process Head Graphite Gasket (use only as replacement of existing graphite gasket)
12 6 6
Flange Adapter Gasket Kits
Ka Ka Ka
51452868-504 51452868-505 51452868-508
Gasket only, Flange Adapter, 6 PTFE Adapter Gaskets Gasket only, Flange Adapter, 6 VITON Adapter O-Rings Gasket only, Flange Adapter Graphite Gasket (use only as replacement of existing graphite gasket)
6 6 6
½-inch NPT Flange Adapter Kits
51452867-110 51452867-210 51452867-310 51452867-410 51452867-150 51452867-350 51452867-130 51452867-330
Flange Adapter Kit, with: SS Flange Adapters and with carbon steel bolts SS Flange Adapters and with A286 SS (NACE) bolts SS Flange Adapters and with 316 SS (non-NACE) bolts SS Flange Adapters and with B7M alloy steel bolts Monel Flange Adapters and with carbon steel bolts Monel Flange Adapters and with 316 SS (non-NACE) bolts Hastelloy C Flange Adapters and with carbon steel bolts Hastelloy C Flange Adapters and with 316 SS (non-NACE) bolts
Each ½-inch NPT Flange Adapter Kit includes:
Ka Gasket, Flange Adapter 2
Kb ½-inch NPT Flange Adapter 2
Kc Bolt, hex head, 7/16-20 UNF, 1.50 inches long 4
Page 124 ST 700 SmartLine Pressure Transmitters User’s Manual Revision 9.0
Bolt And Nut Kit
51452866-501 Carbon steel bolt and Nut Kit
51452866-502 Stainless Steel Bolt and Nut Kit with NACE Certificate
51452866-503 Stainless Steel Bolt and Nut Kit without NACE Certificate
51452866-504 B7M Bolt and Nut Kit
51452866-505 All Stainless Steel NACE Bolt and Nut Kit
51452866-506 Monel Bolt and Nut Kit
51452866-507 Super Duplex Bolt and Nut Kit
51452866-508 Stainless Steel NACE 6K Bolt and Nut Kit
Each Bolt and Nut Kit Includes:
K8 Head Bolt 4
K4 Head Nut 4
Kc Adapter Bolt 4
Revision 9.0 ST 700 SmartLine Pressure Transmitters User’s Manual Page 125
Figure 72 - ST 700 Basic Transmitter Models STD725, 735, 775 – refer to Table 45
Page 126 ST 700 SmartLine Pressure Transmitters User’s Manual Revision 9.0
Table 46 – ST 700 Basic Transmitter - Parts for STG725, 735, 745, 775, 745 Transmitter Body
(Refer to Figure 73)
Key No.
Part Number Description Qty/Unit
Process Head Assembly Kits with PTFE Gaskets
51452864-010 51452864-012 51452864-020 51452864-022 51452864-030 51452864-032
Carbon steel head (zinc plated) without side vent/drain Carbon steel head (zinc plated) with side vent/drain Stainless steel head without side vent/drain Stainless steel head with side vent/drain Hastelloy C head without side vent/drain Hastelloy C head with side vent/drain
Process Head Assembly Kits with Viton® or Fluorocarbon Elastomer Gaskets
51452864-110 51452864-112 51452864-120 51452864-122 51452864-130 51452864-132
Carbon steel head (zinc plated) without side vent/drain Carbon steel head (zinc plated) with side vent/drain Stainless steel head without side vent/drain Stainless steel head with side vent/drain Hastelloy C head without side vent/drain Hastelloy C head with side vent/drain
Each process head assembly kit includes:
K1 Pipe Plug (See notes 1 & 2) 1
K2 Vent Plug (See note 1) 1
K3 Vent Bushing (See note 1.) 1
K5 Process Head 1
K6 Gasket (PTFE), Process Head 1
Ka Gasket (PTFE), Flange Adapter 1
Notes
Note 1: This item is made of the same material as the Process Heads, except for Kits with carbon steel Process Heads, which include stainless steel Pipe Plug, Vent Plug, and Vent Bushing. Note 2: The Kit for Process Heads without side vent/drain does not include Pipe Plugs (K1).
Reference Head
K9 51452951-502 316 SS Blind Reference Head 1
Revision 9.0 ST 700 SmartLine Pressure Transmitters User’s Manual Page 127
Figure 73 – ST 700 Basic Transmitter - STG735, 745, 775 and STA725, 745 Transmitter Body
Page 128 ST 700 SmartLine Pressure Transmitters User’s Manual Revision 9.0
Table 47 - ST 700 Basic Transmitter - Inline Gauge and Inline Atmospheric Meter Body Parts
(Figure 74) Key No.
Part Number Description Qty/Unit
Specify complete model number from nameplate
ST Series replacement meter body (LAP/LGP model) 1
Figure 74 – ST 700 Basic Transmitter - Inline Gauge and Inline Atmospheric Meter Body Bodies
Revision 9.0 ST 700 SmartLine Pressure Transmitters User’s Manual Page 129
Table 48 – ST 700 Basic Transmitter - Flange-Mounted Meter Body Parts
(Refer to Figure 75 and Figure 76)
Key No.
Part Number Description Qty/Unit
1 Specify complete model number from nameplate
ST Series 700 replacement meter body 1
Figure 75 – ST 700 Basic Transmitter - Extended Flange Design
Figure 76 - ST 700 Basic Transmitter - Flush Flange Design
Page 130 ST 700 SmartLine Pressure Transmitters User’s Manual Revision 9.0
Figure 77 - ST 700 Basic Transmitter - Pseudo Flange Design
Figure 78 – ST 700 Basic Transmitter - Remote Seal Diaphragm
Revision 9.0 ST 700 SmartLine Pressure Transmitters User’s Manual Page 131
Figure 79 - ST 700 Basic Transmitter - Series 700 Flush Mount Meter Body.
Table 49 – ST 700 Basic Transmitter - Flush Mount Meter Body Parts
(Refer to Figure 79)
Key No.
Part Number Description Qty/Unit
1
Specify complete model number from nameplate
Replacement meter body (Flush Mount model)
1 30756445-508 Gasket Kit (0-rings)
51204496-501 316L SS Mounting Sleeve Kit
51204497-501 Calibration Sleeve Kit
Page 132 ST 700 SmartLine Pressure Transmitters User’s Manual Revision 9.0
Appendix A - PRODUCT CERTIFICATIONS
for the ST 700 Standard and Basic Transmitter
A.1 Safety Instrumented Systems (SIS) Installations For Safety Certified Installations, please refer to the ST 800 and ST 700 Safety Manual 34-ST-25-37
for installation procedure and system requirements.
SIL 2/3
Certification
IEC 61508 SIL 2 for non-redundant use and SIL 3 for redundant use under the following standards: IEC61508-1: 2010; IEC 61508-2: 2010; IEC61508-3: 2010.
A.2 European Directive Information (CE Mark)
Revision 9.0 ST 700 SmartLine Pressure Transmitters User’s Manual Page 133
Page 134 ST 700 SmartLine Pressure Transmitters User’s Manual Revision 9.0
Revision 9.0 ST 700 SmartLine Pressure Transmitters User’s Manual Page 135
Page 136 ST 700 SmartLine Pressure Transmitters User’s Manual Revision 9.0
Revision 9.0 ST 700 SmartLine Pressure Transmitters User’s Manual Page 137
Page 138 ST 700 SmartLine Pressure Transmitters User’s Manual Revision 9.0
A3. Hazardous Locations Certifications
MSG CODE
AGENCY TYPE OF PROTECTION COMM OPTION
Electrical Parameters
Ambient Temperature
A FM-USA
Explosion proof: Class I, Division 1, Groups A, B, C, D Dust Ignition Proof: Class II, III, Division 1, Groups E, F, G Class I, Zone 0/1, AEx db IIC Ga/Gb Class II, Zone 21, AEx tb IIIC T 95oC Db
DE/HART /FF
Note 1 T5: -50 ºC to 85ºC T6: -50 ºC to 65ºC
Intrinsically Safe: Class I, II, III, Division 1, Groups A, B, C, D, E, F, G Class I Zone 0 AEx ia IIC Ga FISCO Field Device (Only for FF Option) Ex ia IIC Ga
DE/HART /FF
Note 2 T4: -50oC to 70oC
Non-Incendive Class I, Division 2, Groups A, B, C, D Class I Zone 2 AEx nA IIC Gc Class I Zone 2 AEx ic IIC Gc
DE/HART /FF
Note 1 T4: -50oC to 85oC
Enclosure: Type 4X/ IP66/ IP67 ALL ALL ALL
Standards: FM 3600:2011; ANSI/ ISA 60079-0: 2009
FM 3615:2006; ANSI/ ISA 60079-1 : 2009
FM 3616 : 2011 ; ANSI/ ISA 60079-31 : 2009
FM 3610:2010; ANSI/ ISA 60079-11 : 2011
FM 3810 : 2005 ; ANSI/ ISA 60079-26 : 2008
FM 3611:2004; ANSI/ ISA 60079-15 : 2009 ; FM 3810 : 2005 ;
NEMA 250 : 2003 ; ANSI/ IEC 60529 : 2004
B CSA-Canada
Explosion proof: Class I, Division 1, Groups A, B, C, D Dust Ignition Proof: Class II, III, Division 1, Groups E, F, G Zone 0/1, Ex db IIC Ga/Gb Ex tb IIIC T 95oC Db
DE/HART /FF
Note 1 T5: -50 ºC to 85ºC T6: -50 ºC to 65ºC
Intrinsically Safe:
Class I, II, III, Division 1, Groups A, B, C, D, E, F, G; Ex ia IIC Ga
FISCO Field Device (Only for FF Option) Ex ia IIC Ga
DE/HART /FF
Note 2 T4: -50oC to 70oC
Non-Incendive
Class I, Division 2, Groups A, B, C, D Ex nA IIC Gc Ex ic IIC Gc
DE/HART /FF
Note 1 T4: -50oC to 85oC
Enclosure: Type 4X/ IP66/ IP67 ALL ALL ALL
Revision 9.0 ST 700 SmartLine Pressure Transmitters User’s Manual Page 139
MSG CODE
AGENCY TYPE OF PROTECTION COMM OPTION
Electrical Parameters
Ambient Temperature
Standards: ANSI/ ISA 60079-0: 2009 ; CAN/ CSA-C22.2 No. 0-M91:2006; CAN/ CSAE60079-0:2002; ANSI/ UL 913 : 2010 ; ANSI/ ISA 60079-11 : 2009; CAN/ CSA-C22.2 No.157-92: 1992; CAN/CSA-E 60079-11: 2002; ANSI/ ISA 60079-26 : 2008; ANSI/ ISA 12.12.01 : 2007 ; ANSI/ ISA 60079-15 : 2009 ; C22.2 No. 213-M1987; CAN/CSA-E60079-15: 2002; ANSI/ UL 50 : 2007 ; ANSI/ IEC 60529 : 2004
C ATEX
Flameproof: FM12ATEX0029X II 1/2 G Ex d IIC Ga/Gb II 2 D Ex tb IIIC T 95oC Db
DE/HART /FF
Note 1 T5: -50 ºC to 85ºC T6: -50 ºC to 65ºC
Standards: EN 60079-0: 2012+A11: 2013 EN 60079-1 : 2014 EN 60079-31 : 2014 EN 60079-26 : 2015 EN 60529 : 2000 + A1
Intrinsically Safe: Sira12ATEX2233X II 1 G Ex ia IIC Ga FISCO Field Device (Only for FF Option) Ex ia IIC
DE/HART /FF
Note 2 T4: -50oC to 70oC
Non Sparking: Sira12ATEX4234X II 3 G Ex nA IIC Gc II 3 G Ex ic IIC Gc
DE/HART /FF
Note 1 T4: -50oC to 85oC
Standards: EN 60079-0: 2012+A11: 2013 EN 60079-11 : 2012 EN 60079-15 : 2010 IEC 60529 : 2009 with Corr 3
Enclosure: IP66/ IP67 ALL ALL ALL
D
IECEx
Intrinsically Safe: SIRA 12.0100 Ex ia IIC Ga FISCO Field Device (Only for FF Option) Ex ia IIC Ga
DE/HART
/FF
Note 2
T4: -50oC to 70oC
Non Sparking: SIRA 12.0100 Ex nA IIC Gc Ex ic IIC Gc
DE/HART /FF
Note 1 T4: -50oC to 85oC
Standards: IEC 60079-0: 2011 IEC 60079-11 : 2011 IEC 60079-15 : 2011 IEC 60529 : 2009 with Corr 3
Flameproof: Ex d IIC Ga/Gb Ex tb IIIC Db T 95oC
DE/HART /FF
Note 1 T5: -50 ºC to 85ºC T6: -50 ºC to 65ºC
Standards: IEC 60079-0: 2011 IEC 60079-1 : 2007 IEC 60079-31 : 2008 IEC 60079-26 : 2006 IEC 60529 : 2009 with Corr 3
Enclosure: IP66/ IP67 ALL ALL ALL
E SAEx (South Africa)
Intrinsically Safe: Ex ia IIC Ga FISCO Field Device (Only for FF Option) Ex ia IIC Ga
DE/HART /FF
Note 2 T4: -50oC to 70oC
Non Sparking: Ex nA IIC Gc
DE/HART /FF
Note 1 T4: -50oC to 85oC
Flameproof: Ex d IIC Ga/Gb Ex tb IIIC T 95oC Db
DE/HART /FF
Note 1 T4: -50oC to 85oC
Enclosure: IP66/ IP67 ALL ALL ALL
Page 140 ST 700 SmartLine Pressure Transmitters User’s Manual Revision 9.0
MSG CODE
AGENCY TYPE OF PROTECTION COMM OPTION
Electrical Parameters
Ambient Temperature
F INMETRO
Intrinsically Safe: Ex ia IIC Ga FISCO Field Device (Only for FF Option) Ex ia IIC Ga
DE/HART /FF
Note 2 T4: -50oC to 70oC
Non Sparking: Ex nA IIC Gc
DE/HART /FF
Note 1 T4: -50oC to 85oC
Flameproof: Ex d IIC Ga/Gb Ex tb IIIC T 95oC Db
DE/HART /FF
Note 1 T4: -50oC to 85oC
Enclosure: IP66/ IP67 ALL ALL ALL
G NEPSI (CHINA)
Intrinsically Safe:
Ex ia IIC Ga
FISCO Field Device (Only for FF Option) Ex ia IIC Gc
DE/HART /FF
Note 2 T4: -50oC to 70oC
Non Sparking:
Ex nA IIC Ga DE/HART
/FF Note 1 T4: -50oC to 85oC
Flameproof: 1 Ex d IIC Ga/Gb Ex tb IIIC Db T 95oC Db
All Note 1 T4: -50 ºC to 85ºC
Enclosure: IP66/ IP67 ALL ALL ALL
------- GOST
Intrinsically Safe: 0 Ex ia IIC Ga FISCO Field Device (Only for FF Option) Ex ia IIC
DE/ HART/ FF
Note 2 T4: -50 ºC to 70ºC
Enclosure : IP 66/67 All All
Notes
1. Operating Parameters:
DE/HART Foundation Fieldbus
Voltage= 11 to 42 V Voltages = 9 to 23 V
Current= 4-20 mA Normal (3.8 – 23 mA Faults) Current = 25 mA
2. Intrinsically Safe Entity Parameters
For details see Control Drawing on page 142.
3. Marking ATEX Directive
General:
The following information is provided as part of the labeling of the transmitter: • Name and Address of the manufacturer • Notified Body identification: DEKRA Quality B.V., Arnhem, the Netherlands • For complete model number, see the Model Selection Guide for the particular model of pressure
transmitter. • The serial number of the transmitter is located on the Meter Body data-plate. The first two digits of the
serial number identify the year (02) and the second two digits identify the week of the year (23); for example, 0223xxxxxxxx indicates that the product was manufactured in 2002, in the 23 rd week.
Revision 9.0 ST 700 SmartLine Pressure Transmitters User’s Manual Page 141
Apparatus Marked with Multiple Types of Protection
The user must determine the type of protection required for installation the equipment. The user shall then check the box [ ] adjacent to the type of protection used on the equipment certification nameplate. Once a type of protection has been checked on the nameplate, the equipment shall not then be reinstalled using any of the other certification types.
4. WARNINGS and Cautions: Intrinsically Safe and Non-Incendive Equipment: WARNING: SUBSTITUTION OF COMPONENTS MAY IMPAIR SUITABILITY FOR USE IN HAZARDOUS
LOCATIONS. Explosion-Proof/ Flameproof: WARNING: DO NOT OPEN WHEN AN EXPLOSIVE ATMOSPHERE MAY BE PRESENT
Non-Incendive Equipment: WARNING: DO NOT OPEN WHEN AN EXPLOSIVE ATMOSPHERE MAYBE PRESENT WARNING: FOR CONNECTION IN AMBIENTS ABOVE 60oC USE WIRE RATED 105oC
5. Conditions of Use for Ex Equipment, “Hazardous Location Equipment” or “Schedule of Limitations”: Painted surface of the ST800 may store electrostatic charge and become a source of ignition in applications with a low relative humidity less than approximately30% relative humidity where the painted surface is relatively free of surface contamination such as dirt, dust or oil. Cleaning of the painted surface should only be done with a damp cloth.
Flame-proof Installations: The Transmitter can installed in the boundary wall between an area of EPL
Ga/ Class I Zone 0/ Category 1 and the less hazardous area, EPL Gb/ Class I Zone 1/ Category 2. In this configuration, the process connection is installed in EPL Ga/ Class I Zone 0/ Category 1, while the transmitter housing is located in EPL Gb/ Class I Zone 1/ Category 2. The applicable temperature class, ambient temperature range and maximum process temperature of the equipment is as follows; T5 for -50°C < Ta < 85°C T6 for -50°C < Ta < 65°C Maximum process temperature = 125°C Consult the manufacturer for dimensional information on the flameproof joints for repair. The Transmitter can be installed in the boundary wall between an area of Category 1 and the less hazardous area, Category 2. In this configuration, the process connection is installed in Category 1 while the transmitter housing is installed in Category 2.
Intrinsically Safe: Must be installed per drawing 50049892
Division 2: This equipment is suitable for use in a Class I, Division 2, Groups A, B, C, D; T4 or Non-
Hazardous Locations Only. The enclosure is manufactured from low copper aluminum alloy. In rare cases, ignition sources due to impact and friction sparks could occur. This shall be considered during Installation, particularly if equipment is installed a Zone 0 location. If a charge-generating mechanism is present, the exposed metallic part on the enclosure is capable of storing a level of electrostatic that could become incendive for IIC gases. Therefore, the user/ installer shall implement precautions to prevent the buildup of electrostatic charge, e.g. earthing the metallic part. This is particularly important if equipment is installed a Zone 0 location.
Page 142 ST 700 SmartLine Pressure Transmitters User’s Manual Revision 9.0
A4. Control Drawing
Revision 9.0 ST 700 SmartLine Pressure Transmitters User’s Manual Page 143
Page 144 ST 700 SmartLine Pressure Transmitters User’s Manual Revision 9.0
Revision 9.0 ST 700 SmartLine Pressure Transmitters User’s Manual Page 145
Page 146 ST 700 SmartLine Pressure Transmitters User’s Manual Revision 9.0
Revision 9.0 ST 700 SmartLine Pressure Transmitters User’s Manual Page 147
A5. Marine Approvals
American Bureau of Shipping (ABS)
Certificate Number: 14-HS1265317
ABS Rules: Rules for Conditions of Classification, Part 1 - 2014 Steel Vessel Rules 1-1-4/7.7, 1-1-A3, 1-1-A4 which Covers the following: Steel Vessels 4-6-2/5.15, 4-8-3/13, 4-8-4/27.5.1, 4-9-8/13; Offshore Support Vessels 4-8-3/13, 4-8-4/29.5.1, 4-9-8/13; High Speed Craft 4-6-3/9.1.1(a), 4-7-9/15.1; Rules for Conditions of Classification, Part 1 - 2014 Offshore Units and Structures 1-1-4/9.7, 1-1-A2, 1-1-A3
Bureau Veritas (BV)
Certificate Number: 39542/A0 BV
Requirements: Bureau Veritas Rules for the Classification of Steel Ships
EC Code: 41S
Det Norske Veritas (DNV)
Certificate Number: A-13982 Application/ Location Classes: Temperature D Humidity: B Vibration: A EMC: B Enclosure: C For salt spray exposure; enclosure of 316 SST or 2-part epoxy protection with 316 SST bolts to be applied.
Korean Register of Shipping (KR)
Appl. No: DLN-T0044-14
Lloyd's Register (LR)
Certificate Number: 14/60017
Application: For use in environmental categories ENV1, ENV2, ENV3 adn ENV5 as defined by Lloyd’s Register Test specification No. 1, 2013
Page 148 ST 700 SmartLine Pressure Transmitters User’s Manual Revision 9.0
Glossary
AP Absolute Pressure
AWG American Wire Gauge
DE Digital Enhanced Communications Mode
DP Differential Pressure
d1 Inside diameter of pipe
d2 Orifice plate bore diameter at flowing temperature
do Inside diameter of orifice
EMI Electromagnetic Interference
FTA Field Termination Assembly
GP Gauge Pressure
HP High Pressure (also, High Pressure side of a Differential Pressure Transmitter)
Hz Hertz
inH2O Inches of Water
LGP In-Line Gauge Pressure
LP Low Pressure (also, Low Pressure side of a Differential Pressure Transmitter)
LRL Lower Range Limit
LRV Lower Range Value
mAdc Milliamperes Direct Current
mmHg Millimeters of Mercury
mV Millivolts
Nm Newton.meters
NPT National Pipe Thread
NVM Non-Volatile Memory
Pa Measured static pressure in PV4 algorithm
Pc Absolute critical pressure of the gas
Pd Static pressure at downstream point
Pdp Measured differential pressure in Pascals in PV4 algorithm
Pf Absolute pressure of flowing gas
Pr Reduced pressure
Pu Static pressure at upstream point
PM Process Manger
PSI Pounds per Square Inch
PSIA Pounds per Square Inch Absolute
PV Process Variable
PWA Printed Wiring Assembly
RFI Radio Frequency Interference
RTD Resistance Temperature Detector
SFC Smart Field Communicator
STIM Pressure Transmitter Interface Module
STIMV IOP Pressure Transmitter Interface Multivariable Input/Output Processor
T/C Thermocouple
URL Upper Range Limit
URV Upper Range Value
US Universal Station
Vac Volts Alternating Current
Vdc Volts Direct Current
Revision 9.0 ST 700 SmartLine Pressure Transmitters User’s Manual Page 149
INDEX
A
About This Manual ......................................................... iii Accuracy
ST 700 Basic Transmitter .......................................... 79 ST 700 Standard Display ............................................. 8
Application Design ST 700 Basic Transmitter .......................................... 79 ST 700 Standard Transmitter ..................................... 8
B
Basic and Standard Display Operations ST 700 Standard Transmitter ................................... 38
Basic Display Menus........................................ 28, 36, 101
C
Calibration ST 700 Basic Transmitter ........................................ 116 ST 700 Standard Transmitter ................................... 54
Changing the Default Failsafe ST 700 Basic Transmitter ........................................ 104 ST 700 Standard Transmitter ................................... 40
Copyrights, Notices and Trademarks .............................. ii
D
Data Entry ST 700 Basic Transmitter ........................................ 102 ST 700 Standard Transmitter ................................... 31
Diagnostic Messages ST 700 Basic Transmitter .......................................... 79 ST 700 Standard Display ............................................. 8
Display Installation Precautions ST 700 Basic Transmitter .......................................... 80 ST 700 Standard Display ........................................... 10
Display Options ST 700 Basic Transmitter .......................................... 77 ST 700 Standard Transmitter ..................................... 6
E
Explosion-Proof Seal ST 700 Basic Transmitter .......................................... 93 ST 700 Standard Transmitter ................................... 23
F
Features and Options ST 700 Basic Transmitter .......................................... 74 ST 700 Standard Transmitter ..................................... 3
G
Glossary ...................................................................... 149
H
Honeywell MC Toolkit ST 700 Basic Transmitter ......................................... 80 ST 700 Standard Display .......................................... 10
I
Installation and Startup ST 700 Basic Transmitter ......................................... 80 ST 700 Standard Transmitter ................................... 10
Introduction ST 700 Basic Transmitter ......................................... 74 ST 700 Standard Transmitter ..................................... 3
L
Location ST 700 Basic Transmitter ......................................... 89 ST 700 Standard Transmitter ................................... 19
M
Maintenance ST 700 Basic Transmitter ....................................... 107 ST 700 Standard Transmitter ................................... 45
Mounting ST 700 Basic Transmitter ......................................... 81 ST 700 Standard Transmitter ................................... 11
N
Nameplate ST 700 Basic Transmitter ......................................... 76 ST 700 Standard Transmitter ..................................... 5
O
Operation ST 700 Basic Transmitter ......................................... 96 ST 700 Standard Transmitter ................................... 26
Page 150 ST 700 SmartLine Pressure Transmitters User’s Manual Revision 9.0
P
Parts List ST 700 Basic Transmitter ........................................ 118 ST 700 Standard Transmitter ................................... 57
Patent Notice ................................................................. iv Piping
ST 700 Basic Transmitter .......................................... 88 ST 700 Standard Transmitter ................................... 18
Product Certifications ST 700 Basic Transmitter .................................... 1, 133
R
References ..................................................................... iv Release Information....................................................... iii Replacing the Communication Module
ST 700 Basic Transmitter ........................................ 110 ST 700 Standard Transmitter ................................... 48
Replacing the Meter Body Module ST 700 Basic Transmitter ........................................ 112 ST 700 Standard Transmitter ................................... 50
S
Safety Certification ST 700 Basic Transmitter .......................................... 77 ST 700 Standard Transmitter ..................................... 6
Safety_SIL ST 700 Basic Transmitter ...................................... 9, 79
Site Evaluation ST 700 Basic Transmitter .......................................... 80 ST 700 Standard Display ........................................... 10
ST 700 Basic Transmitter Application Design ................................................... 79 Calibration .............................................................. 116 Installation and Startup ........................................... 80 Introduction ............................................................. 74 Maintenance .......................................................... 107 Operation ................................................................. 96 Parts List ................................................................. 118 Product Certifications ........................................ 1, 133 Troubleshooting ..................................................... 117
ST 700 Standard Transmitter Application Design ..................................................... 8 Calibration ................................................................ 54 Installation and Startup ........................................... 10 Introduction ............................................................... 3 Maintenance ............................................................ 45 Operation ................................................................. 26 Parts List ................................................................... 57 Troubleshooting ....................................................... 55
ST 700 Transmitter Series............................................... 1 Standard Display Abbreviations
ST 700 Basic Transmitter ....................................... 101 ST 700 Standard Transmitter ................................... 36
Startup ST 700 Basic Transmitter ......................................... 94 ST 700 Standard Transmitter ................................... 24
Support and Contact Information .................................. iv Symbol Descriptions and Definitions.............................. v
T
Telephone and Email Contacts ....................................... iv Three Button Operation no Display
ST 700 Basic Transmitter ....................................... 103 ST 700 Standard Transmitter ................................... 39
Three-Button Operation ST 700 Standard Transmitter ................................... 26
Transmitter Adjustments ST 700 Basic Transmitter ......................................... 77 ST 700 Standard Transmitter ..................................... 6
Troubleshooting ST 700 Basic Transmitter ....................................... 117 ST 700 Standard Transmitter ................................... 55
Two-Button Assembly ST 700 Standard Transmitter ..................................... 7
Two-Button Operation ST 700 Standard Transmitter ................................... 32
Two-Button Operation ST 700 Basic Transmitter ......................................... 96
W
Wiring ST 700 Basic Transmitter ......................................... 90 ST 700 Standard Transmitter ................................... 20
Revision 9.0 ST 700 SmartLine Pressure Transmitters User’s Manual Page 151
Sales and Service
For application assistance, current specifications, pricing, or name of the nearest Authorized Distributor, contact one of the offices below.
ASIA PACIFIC Honeywell Process Solutions,
(TAC) [email protected]
Australia Honeywell Limited Phone: +(61) 7-3846 1255 FAX: +(61) 7-3840 6481 Toll Free 1300-36-39-36 Toll Free Fax: 1300-36-04-70 China – PRC - Shanghai Honeywell China Inc. Phone: (86-21) 5257-4568 Fax: (86-21) 6237-2826
Singapore Honeywell Pte Ltd. Phone: +(65) 6580 3278 Fax: +(65) 6445-3033 South Korea Honeywell Korea Co Ltd Phone: +(822) 799 6114 Fax: +(822) 792 9015
EMEA Honeywell Process Solutions,
Phone: + 80012026455 or +44 (0)1344 656000
Email: (Sales)
or
(TAC)
AMERICAS Honeywell Process Solutions,
Phone: (TAC) 1-800-423-9883 or 215/641-3610
(Sales) 1-800-343-0228
Email: (Sales)
or
(TAC)
Specifications are subject to change without notice.
For more information To learn more about SmartLine Transmitters, visit www.honeywellprocess.com Or contact your Honeywell Account Manager
Process Solutions Honeywell
1250 W Sam Houston Pkwy S Houston, TX 77042
Honeywell Control Systems Ltd Honeywell House, Skimped Hill Lane Bracknell, England, RG12 1EB
34-ST-25-44 Rev.9.0 September 2017
2017 Honeywell International Inc.
Shanghai City Centre, 100 Jungi Road Shanghai, China 20061 www.honeywellprocess.com