SUB-SURFACE
INVESTIGATION
REPORT
PROPOSED
33/11kV SUB-STATION ODGI
(RGGVY PACKAGE: SAR-A)
Sun- Tech N A B L A C C R E D I T E D T E S T H O U S E
I S O 1 7 0 2 5 : 2 0 0 5 & I S O 9 0 0 1 : 2 0 0 8
T-1523
PDF processed with CutePDF evaluation edition www.CutePDF.comPDF processed with CutePDF evaluation edition www.CutePDF.comPDF processed with CutePDF evaluation edition www.CutePDF.comPDF processed with CutePDF evaluation edition www.CutePDF.comPDF processed with CutePDF evaluation edition www.CutePDF.com
Sun-Tech
2
SUB-SURFACE INVESTIGATION REPORT
PROPOSED 33/11KV SUB-STATION LOCATION:
ODGI/ SARGUJA/ CHHATISGARH
Job Code: S530910
SUBMITTED TO:
OWNER: CHHATISGARH STATE POWER DISTRIBUTION COMPANY LTD.
CONSULTANT: POWER GRID CORPOARTION OF INDIA LTD.
CONTRACTOR: JYOTI STRUCTURES LTD.
INVESTIGATIONS DONE BY:
Sun-Tech HI-230, HARMU HOUSING COLONY, RANCHI-12, JHARKHAND
TEL: 0651-2242954, 6003411,FAX: 0651-2243889
E-MAIL: [email protected]. VISIT US AT: www.suntech.co.in
This document is the property of Sun-Tech, Hi-230, Harmu Housing Colony, Ranchi-12 .
Any unauthorised employment or reproduction, in full or part is forbidden.
Sun-Tech, Hi-230, Harmu Housing Colony, Ranchi-12, Jharkhand, India , 2010
THE LABORATORY TESTS WERE CONDUCTED AT OUR LABORATORY NABL ACCREDITED (ISO 17025:2005) AND ISO
9001:2008 CERTIFIED AT HI-230, HARMU HOUSING COLONY, RANCHI-12, JHARKHAND.
Sun-Tech
Sub-Surface Investigation Report CODE:S530910
33/11kV SUB-STATION AT ODGI, SARGUJA, UNDER RGGVY PACKAGE# SAR-A ii
Table Of Contents__________________
1.0 INTRODUCTION 1.1 Project Description 1.2 Purposes of Study 2.0 FIELD INVESTIGATIONS
2.1 Soil Borings 2.2 Rock Drilling 2.3 Groundwater
3.0 LABORATORY TESTS 4.0 GENERAL SITE CONDITIONS
4.1 Site Stratigraphy 4.2 Lithology 4.3 Underground water 4.4 Seismicity
5.0 FOUNDATION ANALYSIS AND RECOMMENDATIONS 5.1 General 5.2 Foundation Type and Depth 5.3 Shallow Foundations 6.0 GENERAL COMMENTS 7.0 REFERENCES
Sun-Tech
Sub-Surface Investigation Report CODE:S530910
33/11kV SUB-STATION AT ODGI, SARGUJA, UNDER RGGVY PACKAGE# SAR-A iii
1. INTRODUCTION 1.1. Project Description
M/s. Jyoti Structures Ltd. Valecha Chamber’s, 5-6th Floor, New Link Road,
Oshiwara, Andheri (W) has undertaken construction of a new Sub-Station of
33/11 kV at Odgi, Sarguja in Chhatisgarh State under Rural Electrification works
in Sarguja District under RGGVY package# SAR-A for the Chhatisgarh State
Power Distribution Company Limited. M/s. Power Grid Corporation of India Ltd.
are the Consultants of the Project.
The proposed Sub-Station will have Office buildings and foundations for various
electric equipments.
The current study is a detailed investigation for comprehensive assessment of
the site conditions, and inputs for foundation design of the various structures of
Sub-Station.
A layout plan showing the location of various boreholes is illustrated in the
annexure. This report presents the results of the investigation and our
recommendations based on the available geotechnical data.
1.2. Purposes of Study
The overall purpose of these investigations is to investigate the transmission
route and to develop geotechnical recommendation for foundation design and
construction. To accomplish these purposes, the study was conducted in the
following phases:
(a) Drilling Three nos. boreholes through soil and up to refusal to determine site
Stratigraphy and to collect disturbed and undisturbed soil samples for laboratory
testing;
(b) Conducting Dynamic Cone Penetration test at three locations.
(c) Testing selected soil samples in the laboratory to determine pertinent index and
engineering properties; and
(d) Analyzing all field and laboratory data to develop foundation design and
construction recommendations.
Sun-Tech
Sub-Surface Investigation Report CODE:S530910
33/11kV SUB-STATION AT ODGI, SARGUJA, UNDER RGGVY PACKAGE# SAR-A iv
2. FILED INVESTIGATION
2.1. Soil Borings
The boreholes were progressed using a hand operated auger to the Specified depth or
refusal, whichever is encountered earlier. The diameter of the borehole was 150 mm. Where
caving of the borehole occurred, casing was used to keep the borehole stable. The work was in
general accordance IS: 1892-1979.
Standard Penetration Test (SPT) was conducted in the borehole at 1.5 m interval by
connecting a split spoon sampler to ‘A’ rods and driving it by 45 cm. The tests were conducted
in accordance with IS: 2131-1981.
The numbers of blows for each 15 cm of penetration were recorded. The blows required
to penetrate the initial 15 cm of the split spoon for seating the sampler is ignored due to the
possible presence of loose materials or cuttings from the drilling operation. The cumulative
number of blows required to penetrate the balance 30 cm of the 45 cm sampling interval is
termed the SPT value of the ‘N’ value.
The ‘N’ values are presented on the profiles for each borehole. Refusal to further boring
penetration was considered when the ‘N’ values exceed 50 or when practical refusal to further
penetration by shell and auger was encountered.
Where the ‘N’ value exceeds 50, the penetration of split spoon sampler (after initial
seating) is recorded together with the number of blows given of the sampler. Where the seating
blow count exceeds 50, the ‘N’ value is recorded as “Ref” on the soil profile.
SPT ‘N’ values are correlated with relative density of non-cohesive stratum and with consistency of cohesive stratum:
CORRELATION FOR
CLAY/PLASTIC SILT
CORRELATION FOR SAND/NON-PLASTIC
SILT Consistency Penetration Value
(blows) Relative Density Penetration
Value (blows) Very Soft 0-2 Very Loose 0-4
Soft 3-4 Loose 5-10
Medium Stiff 5-8 Medium 11-30 Stiff 9-16 Dense 31-50
Very stiff 17-32 Very Dense >50 Hard >32
Sun-Tech
Sub-Surface Investigation Report CODE:S530910
33/11kV SUB-STATION AT ODGI, SARGUJA, UNDER RGGVY PACKAGE# SAR-A v
Disturbed Sampling (Soil) in boreholes
Disturbed soil collected in the SPT sampler was preserved in polythene covers and
transported to the laboratory. One more polythene cover was provided to prevent the
loss of moisture during the transit period.
Undisturbed Sampling (Soil) in Boreholes
Undisturbed samples are collected using 100mm diameter and 450mm long MS tubes
provided with sampler head with ball check arrangement. Undisturbed soil samples
are usually collected in soft to stiff clayey soil strata. Collection of undisturbed samples
in refusal strata is practically not possible. All samples were transported to our laboratory
at Ranchi for examination and testing.
2.2. Groundwater
Groundwater level was measured in the boreholes 24 hours after drilling and
sampling was completed. No water table was found in the bore holes.
Sun-Tech
Sub-Surface Investigation Report CODE:S530910
33/11kV SUB-STATION AT ODGI, SARGUJA, UNDER RGGVY PACKAGE# SAR-A vi
3. LABORATORY TESTS
The laboratory testing has been carried out in our laboratory at Ranchi. The
quality procedures in our laboratory conform to ISO/IEC-17025-2005 and ISO
9001:2008.
The laboratory testing programme was aimed at verifying the field classifications
and developing parameters for engineering analysis. All testing was performed in
accordance with the current applicable IS specifications. The following tests were
conducted on selected soil and water samples recovered from the borehole:
On Soil :
Laboratory Test IS : Code Referred
Natural moisture content IS : 2720 (Part-2)-1973
Grain size analysis IS : 2720 (Part-4)-1985
Liquid & Plastic limit IS : 2720 (Part-5)-1985
Specify Gravity IS : 2720 (Part-3)-1980
Unconsolidated Undrained Triaxial shear test IS : 2720 (Part-11)-1983
Consolidated Drained Direct Shear Test IS : 2720 (Part-13)-1986
Unconfined Compression Test IS : 2720 (Part-10)-1991
Determination of pH value IS : 2720 (Part-26)-1987
Determination of Sulphate content IS : 2720 (Part-27)-1977
Chemical
Analysis of
soil* Determination Chloride content IS : 3025 (Part-32)-1988
Determination of pH value IS : 3025 (Part-11)-1996
Determination of total soluble
sulphate
IS : 3025 (Part-24)-1998 Chemical
Analysis of
water* Determination of Chloride content IS : 3025 (Part-32)-1993
All test results are presented in the illustration section of this report.
Sun-Tech
Sub-Surface Investigation Report CODE:S530910
33/11kV SUB-STATION AT ODGI, SARGUJA, UNDER RGGVY PACKAGE# SAR-A vii
4.0 GENERAL SITE CONDITIONS
4.1 Site Stratigraphy
The boreholes are evenly spaced. The plot is about 1.50m above the
existing road level. The soil strata in the plot are uniform. In general, an
overburden of stiff to very stiff high to medium plastic silty sandy gravelly clay
is found up to 3.00-5.00m depth over dense completely weathered rocks.
The Bore logs in the annexure present the detailed Stratigraphy, cross sections and nature of soil at the borehole locations
4.2 SEISMICITY:
The area falls under Zone-III as classified by Bureau of Indian Standards,
indicating moderately active zone.
4.3 LIQUEFACTION:
Liquefaction is the sudden loss of shear strength of the loose fine-grained
sands due to earthquake-induced vibration under saturated conditions.
Subsurface consists of silty gravelly sand with high standard penetration
resistance, followed by dense rock, hence site may be classified as
“Liquefaction unlikely” in earthquake event.
4.4 GROUNDWATER:
Groundwater was encountered in the boreholes at 1.00m depth.
Sun-Tech
Sub-Surface Investigation Report CODE:S530910
33/11kV SUB-STATION AT ODGI, SARGUJA, UNDER RGGVY PACKAGE# SAR-A viii
5.0 FOUNDATION ANALYSIS AND RECOMMENDATIONS
5.1 General
A suitable foundation for any structure should have an adequate factor of safety
against exceeding the bearing capacity of the supporting soils. Also the vertical
movements due to compression of the soils should be within tolerable limits for
the structure. We consider that foundation designed in accordance with the
recommendations given herein will satisfy these criteria.
5.2 Foundation Type and Depth
All depths given in this report are with reference to the existing
ground surface at the time of our investigation. In case any substantial cutting /
filling operation is to be carried out, the recommendations given in this report
should be reviewed. It should be ensured that all foundations are placed on the
natural soils/ rock and not on fill.
5.3 Shallow Foundations
Bearing capacity analysis for open foundations bearing on soils at site has been
done in accordance with IS: 6403-1981 based on laboratory and field tests.
Settlement analysis has been performed in accordance with
IS: 8009 Part-1-1976. The N values from the Standard Penetration tests
conducted are indicated in the respective Bore-Logs. From The Average of N
values over the significant depth below the foundation, the safe bearing pressure
has been evaluated as per IS 8009 (Part-1) 1976 considering the soil is
predominantly sandy.
Sun-Tech
Sub-Surface Investigation Report CODE:S530910
33/11kV SUB-STATION AT ODGI, SARGUJA, UNDER RGGVY PACKAGE# SAR-A ix
RECOMMENDED ALLOWABLE BEARING PRESSURE :
Allowable Bearing
Pressure, ton /m2 for a
settlement of
Likely foundation bearing material
Embedment Depth, m
Width (m) / Type of
foundation
25mm
40mm
Recommended Net
Allowable Bearing
Pressure, ton /m2
1.00/ Open 10.00 16.00 10.00
2.00/ Open 8.00 13.00 8.00
3.00/ Open 8.00 13.00 8.00
4.00/ Open 9.00 14.00 9.00
5.00/ Open 8.50 13.50 8.50
Sandy gravelly clay 1.00
6.00/ Open 8.50 13.50 8.50
1.00/ Open 15.00 24.00 24.00
2.00/ Open 12.50 20.00 20.00
3.00/ Open 12.00 20.00 20.00
4.00/ Open 11.50 18.00 18.00
5.00/ Open 11.00 17.50 17.50
Sandy gravelly clay 1.50
6.00/ Open 10.50 17.00 17.00
1.00/ Open 16.00 25.50 25.50
2.00/ Open 13.00 21.00 21.00
3.00/ Open 12.50 20.00 20.00
4.00/ Open 11.50 19.00 19.00
5.00/ Open 11.00 18.00 18.00
Sandy gravelly clay 2.00
6.00/ Open 11.00 17.00 17.00
1.00/ Open 21.00 34.00 34.00
2.00/ Open 17.00 27.00 27.00
3.00/ Open 15.00 24.00 24.00
4.00/ Open 14.00 22.00 22.00
5.00/ Open 13.00 21.00 21.00
Sandy gravelly clay 3.00
6.00/ Open 13.00 20.00 20.00
Sun-Tech
Sub-Surface Investigation Report CODE:S530910
33/11kV SUB-STATION AT ODGI, SARGUJA, UNDER RGGVY PACKAGE# SAR-A x
Notes: ⇒ It has been found that the water table will rise to founding level from EGL in the peak rainy
season.
⇒ A maximum settlement of 40mm is expected.
⇒ The depth of embedment of foundation has been given from the existing ground level any cutting or filling at that point should be adequately taken care of.
5.4 Excavation Scheme
The temporary excavation is expected to be through the Silty clay / completely weathered Rock.
Description of Strata Recommended Side slopes Excavation Method
silty gravelly clay 1V:2H Conventional Excavators
Highly Weathered rocks 2-3V:1H Drilling / Blasting or needle
breaker
6.0 GENERAL COMMENTS:
The choice of the value for design is a matter of engineering judgment and field assessment of
soil and rock character. After review of the net bearing pressure computed from different
methods, the final value has been selected based on our engineering judgment based on soil and
rock encountered in the limited number of boreholes as reported herein. If any significant
departure from the reported data is noticed during actual construction, the Geotechnical
consultants may be referred for advice.
For Sun-Tech, Ranchi
(Pranay Kumar) Geotechnical Consultant
Sun-Tech
Sub-Surface Investigation Report CODE:S530910
33/11kV SUB-STATION AT ODGI, SARGUJA, UNDER RGGVY PACKAGE# SAR-A xi
7.References: 1. IS:2720 (part), Grain size Analysis
2. IS:2720(Part XIV), Determination of Density Index
3. IS:2720(Part V), Determination of Liquid & Plastic Limits
4. IS:1498-1970: Classification & identification of soils
5. IS 2720 (Part XV), Determination of Consolidation Properties.
6. IS:2720( Part XI)1975, Triaxial Test (UUT)
7. IS 2720 (Part X) 1973, unconfined compressive strength.
8. IS:1892-1962, site investigation
9. IS 2131-1981, Method for SPT.
10. IS: 2132-1981, Thin walled tube sampling of soils.
11. IS: 1904-1978, Structural Safety of Building Foundations
12. IS:6403-1981, Determination of Bearing Capacity of Foundations
13. IS:8009(Part-1)-1976, Calculation of Settlement of foundations.
14. Arora ,K.R. Soil Mechanics & Foundation Engg.
15. Murthy. VNS, Principles of soil mech. & foundation Engg.
16. Punamia, B.C. Soil Mechanics & foundation Engg.
17. Nayak, M.V., Foundation Design Manual.
18. Brahma, S.P. Soil Mechanics
19. Singh, Alam Modern Geotechnical Engineering
20. IS:2950 (Part-I)-1981 Code of Practice for Raft Foundations
*******************************END OF REPORT****************************
Sun-Tech
Sub-Surface Investigation Report CODE:S530910
33/11kV SUB-STATION AT ODGI, SARGUJA, UNDER RGGVY PACKAGE# SAR-A xii
Annexures `
BOREHOLE LOCATION PLAN
SOIL PROFILE
BORE LOG DATA SHEET
VARIATION OF SPT VALUES WITH DEPTH
DCPT RESULTS
SAMPLE CALCULATIONS
LABORATORY TEST RESULTS
GRAIN SIZE CURVE
TRIAXIAL TEST
Borehole No. : 1 Ground R.L. : 100.000 m
Termination : 5.00 m from EGL
S530910
33/11 kV NEW SUBSTATION AT ODGI
Job No. :
Fig No. :
Sun-Tech
RanchiN Value Curve
Variation of 'N' value with Depth
9
100
32
42
0
1
2
3
4
5
6
0 10 20 30 40 50 60 70 80 90 100
Field 'N' value
De
pth
fr
om
E
.G.L
. (m
)
Borehole No. : 2 Ground R.L. : 100.000 m
Termination : 3.00 m from EGL
S530910
2
33/11 kV NEW SUBSTATION AT ODGI
Job No. :
Fig No. :
Sun-Tech
RanchiN Value Curve
Variation of 'N' value with Depth
15
100
0
1
2
3
4
5
6
0 10 20 30 40 50 60 70 80 90 100
Field 'N' value
De
pth
fr
om
E
.G.L
. (m
)
Borehole No. : 3 Ground R.L. : 100.000 m
Termination : 4.00 m from EGL
S530910
3
33/11 kV NEW SUBSTATION AT ODGI
Job No. :
Fig No. :
Sun-Tech
RanchiN Value Curve
Variation of 'N' value with Depth
18
25
100
0
1
2
3
4
5
6
0 10 20 30 40 50 60 70 80 90 100
Field 'N' value
De
pth
fr
om
E
.G.L
. (m
)
Borehole No. : 1/DCPT Ground R.L. : 100.000 m
Termination : 3.10 m from EGL
S530910
4
33/11 kV NEW SUBSTATION AT ODGI
Job No. :
Fig No. :
Sun-Tech
RanchiDCPT Value Curve
Variation of DCPT value with Depth
10
27
78
79
100
9
9
0
1
2
3
4
5
6
0 10 20 30 40 50 60 70 80 90 100
Field 'N' value
De
pth
fr
om
E
.G.L
. (m
)
Borehole No. : 2/DCPT Ground R.L. : 100.000 m
Termination : 3.10 m from EGL
S530910
5
33/11 kV NEW SUBSTATION AT ODGI
Job No. :
Fig No. :
Sun-Tech
RanchiDCPT Value Curve
Variation of DCPT value with Depth
9
15
17
47
100
11
18
0
1
2
3
4
5
6
0 10 20 30 40 50 60 70 80 90 100
Field 'N' value
De
pth
fr
om
E
.G.L
. (m
)
Borehole No. : 3/DCPT Ground R.L. : 100.000 m
Termination : 2.20 m from EGL
S530910
6
33/11 kV NEW SUBSTATION AT ODGI
Job No. :
Fig No. :
Sun-Tech
RanchiDCPT Value Curve
Variation of DCPT value with Depth
12
100
15
35
0
1
2
3
4
5
6
0 10 20 30 40 50 60 70 80 90 100
Field 'N' value
De
pth
fr
om
E
.G.L
. (m
)
Sun-TechRanchi
U/P 2702 1.00 6.34 51.28 39.38 3.00 52.3 13.7 38.6 - SC 13.60 2.08 2.76 UUT 0.23 24 7 0.004 0.004 - -
P 2103 3.50 7.26 50.20 39.74 2.80 50.3 14.19 36.11 - SC 12.80 2.10 2.64 UUT 0.2 24.5 - - - - -
P 2105 4.50 0.30 61.36 35.54 2.80 40.6 17.65 22.95 - SC 11.85 1.99 2.61 - - - - - - - -
P 2717 4.90 0.00 53.20 37.80 9.00 36.8 17.74 19.06 - SC 12.06 2.02 2.64 - - - - - - - -
U/P 2713 1.50 1.88 58.44 23.68 16.00 43.1 14.5 28.6 - SC 14.31 1.99 2.56 UUT 0.36 20.5 6.5 0.005 0.004 - -
P 2715 3.00 1.32 58.90 39.78 0.00 33.7 15.68 18.02 - SM 13.00 2.04 2.71 UUT 0.01 32 - - - - -
U/P 2707 1.50 0.00 54.34 38.66 7.00 40.8 18.73 22.07 - SC 15.30 2.10 2.74 UUT 0.27 23 7 0.006 0.004 - -
p 2109 3.00 6.50 54.12 35.38 4.00 34.5 17.6 16.9 - SC 11.70 2.03 2.64 - - - - - - - -
p 2109 4.00 0.00 55.64 24.36 20.00 35.6 18.62 16.98 - SC 12.80 2.00 2.71 - - - - - - - -
3. Specific Gravity IS:2720 Part-3-1980 4. Direct Shear Test IS:2720-Part-13 1986 5. Triaxial Test IS:2720 Part-12 1981 6. Consolidation test IS: 2720 Part-15 -1986
7. pH of Soil IS:2720- Part-41 1976 8. Free Swell Index IS: 2720 part-40 1977
Sampling Process: Samples from Bore holes P- SPT Sample, D- Disturbed/ Wash Sample C- Rock Core Sample
BH-1
BH-3
Notes: CONSOLIDATION TEST NOT CONDUCTED DUE TO SANDY NATURE OF SOIL
Abrreviation used : UUT : Triaxial Unconsolidated Undrained, TCU : Triaxial Consolidated Undrained, TCD : Triaxial Consolidated Drained, DS : Direct Shear,
UC : Unconfined Compression, ( R ) : Remoulded sample, U : Undisturbed sample, D : Disturbed sample, P : SPT sample NP: Non Plastic
Notes: Test Methods Referred to: 1. Grain Size Distribution IS:2720 Part-4-1985 2. Liquid, Plastic & Shrinkage Limit IS:2720 Part-5-1985
Co-e
ff. O
f C
om
pre
ssio
n
(Cc)
BH-2
pH
Ch
lori
de (
%)
Su
lfate
(%
)
Init
ial V
oid
rati
o (
eo)
Shear Strength test Chemical TestConsolidation
Test
Gra
vel %
San
d %
Silt
%
Cla
y %
Type o
f te
st
Coh
esio
n (
Kg/cm
2)
An
gle
of
inte
rnal
Fri
cti
on
(D
egre
e)
Cla
ssif
icati
on
(IS
:14
98
-19
70
)
Natu
ral M
ois
ture
Con
ten
t %
Bu
lk D
en
sit
y (
gm
/cc)
Specif
ic G
ravit
y
Pla
sti
cit
y I
ndex
Sh
rin
kage L
imit
%
OWNER: CHHATISGARH STATE POWER DISTRIBUTION COMPANY LTD.
CONSULTANT: POWER GRID CORPORATION OF INDIA LTD.
CONTRACTOR: JYOTI STRUCTURES LTD.
PROJECT: 33/11 kV NEW SUBSTATION AT ODGI, UNDER RGVY
PCAKAGE-SAR-A Proj. Code. :530910
BH
No.
Sam
ple
Type
Sam
ple
Nu
mber
Depth
(m
)
Grain Size Distribution
Liq
uid
Lim
it %
Pla
sti
c L
imit
%
LABORATORY TEST RESULTS ON SOIL SAMPLES Page 1 of 1
Checked/ approved
PARTICLE SIZE DISTRIBUTION CURVE
Job No. : S530910Page 7
Particle Size Distribution CurvesSun-Tech
0
10
20
30
40
50
60
70
80
90
100
0.001 0.01 0.1 1 10
Particle Size, D (mm)
% F
ine
r th
an
D
BH No. - 1 Depth :1.00m BH No. - 1 Depth : 3.50m BH No. - 2 Depth 1.50m
0
10
20
30
40
50
60
70
80
90
100
0.001 0.01 0.1 1 10
Particle Size, D (mm)
% F
ine
r th
an
D
BH No. - 2 , Depth :3.00m
PARTICLE SIZE DISTRIBUTION CURVE
Job No. : S530910Page 8
Particle Size Distribution CurvesSun-Tech
0
10
20
30
40
50
60
70
80
90
100
0.001 0.01 0.1 1 10
Particle Size, D (mm)
% F
ine
r th
an
D
BH No. - 3 Depth :1.50m BH No. - 3 Depth : 3.00m BH No. - 3 Depth 4.00m
0
10
20
30
40
50
60
70
80
90
100
0.001 0.01 0.1 1 10
Particle Size, D (mm)
% F
ine
r th
an
D
BH No. - 2 , Depth :3.00m
CALCULATION OF ALLOWABLE BEARING PRESSURE BASED ON SPT 'N' VALUES Calculation Sheet
Project: PROPOSED 33/11 kV substation at ODIGA
Location: ODIGA
Customert: JSL
S530910 BH- 1/2/3
Type of Foundation: OPEN/ RAFT
Allowable Settlement: 50 mm
Position of Water Table: AT FOOTING LEVEL
IS:8009(Part-1)-1976
Depth of Width of SPT Design
Foundation Foundation Value
D (m) B (m) N
1.20 1.00 32.00 1.20
1.00 2.00 16.00 1.10
1.00 3.00 17.00 1.07
1.00 4.00 20.00 1.05
1.00 5.00 20.00 1.04
1.00 6.00 20.00 1.03
1.50 1.00 20.00 1.20
1.50 2.00 22.00 1.15
1.50 3.00 24.00 1.10
1.50 4.00 24.00 1.08
1.50 5.00 24.00 1.06
1.50 6.00 24.00 1.05
2.00 1.00 21.00 1.20
2.00 2.00 22.00 1.20
2.00 3.00 24.00 1.13
2.00 4.00 24.00 1.10
2.00 5.00 24.00 1.08
2.00 6.00 24.00 1.07
3.00 1.00 27.00 1.20
3.00 2.00 27.00 1.20
3.00 3.00 27.00 1.20
3.00 4.00 27.00 1.15
3.00 5.00 27.00 1.12
3.00 6.00 27.00 1.10
PROJECT CODE:
Water table correction W' Depth factor df
ALLOWABLE BEARING PRESSURE ton/m2
(qna)
Max. expected settelement
25mm 40mm
The Calculation for Allowable Bearing Pressure is based on
Teng’s Equation :
For a settlement of 25mm of foundation
qna= 3.5(N-3){(B+0.3)2/(4B
2)}df.W’
ref IS:8009-1976 Part-1
0.50
25.73
8.27
41.17
13.24
0.50
13.91
13.56
0.50
0.50
7.91
9.02
12.65
14.44
0.50
0.50
8.69
8.47
0.50 15.08 24.13
0.50 12.64 20.23
0.50 12.23 19.57
0.50 11.41 18.26
0.50 10.94 17.51
0.50 10.64 17.02
0.50 15.97 25.55
0.50 13.19 21.11
0.50 12.60 20.16
0.50 11.68 18.69
0.50 11.15 17.84
0.50 10.80 17.29
0.50 21.29 34.07
0.50 16.66 26.66
0.50 15.25 24.39
0.50 13.95 22.33
0.50 13.21 21.14
0.50 12.73 20.37
Sun-Tech
Ranchi Checked/ Approved
Sun-Tech
Ranchi
Calculation- Sheet
1
2
3
4
5 α
6 2
7 1
1 g/cc
2 %
3 g/cc
4
5
6 degree 20.5 Nc
7 kg/cm2
0.36 Nq
8 W' 0.5 Nγ
Assuming B: (m) 2.00 sc 1.30 dc
L: (m) 2.00 sq 1.20 dq
sγ0.80 dγ
ton/m2
FACTOR OF SAFETY: 3.00
Ultimate net bearing capacity qd: 93.04 ton/m2
qd= cNc. sc .dc.ic + γγγγd(Nq-1).sq.dq.iq + 1/2.B.γγγγ.Ng.sγγγγ.dγγγγ.iγγγγ.W’
Net Bearing Capacity 31.01
The effect of depth factor has not been considered ref. cl. 5.1.2.2 of IS 6403-1981
Effect of water Table 5.39
Void ratio 0.47
Angle of Internal Friction 14.83
Cohesion 6.4
As the soil is cohesionless the analysis for the bearing capacity will have to in pursuant to the Table-3 of IS:6403-1981based on void ratio.
The Void ratio of soil sample 0.47
The condition of soil is dense The bearing capacity will have to be calculated by General Shear Failure Values. Table: 3 of
IS:6403-1981
1.00
GENERAL SHEAR FAILURE
Width of foundation 1.00
Length of foundation 1.00
Specific Gravity 2.56
LABORATORY
Bulk Density of soil 1.99
Natural moisture Content 14.31
Dry Density 1.74
CALCULATION OF BEARING CAPACITY
(IS:6403-1981)
General data: FIELD
Project 33/11 kV SUB-STATION AT ODIGI AT AMBIKAPUR
Location BH-2
Depth of foundation m 1.5
Inclination of Load to vertical in drgrees 0
ISOLATED
-
Structure
RL
RL of Ground water level -
Sun-Tech
Ranchi
Calculation- Sheet
1
2
3
4
5 α
6 2
7 1
1 g/cc
2 %
3 g/cc
4
5
6 degree 20.5 Nc
7 kg/cm2
0.36 Nq
8 W' 0.5 Nγ
Assuming B: (m) 2.00 sc 1.30 dc
L: (m) 2.00 sq 1.20 dq
sγ0.80 dγ
ton/m2
FACTOR OF SAFETY: 3.00
CALCULATION OF BEARING CAPACITY
(IS:6403-1981)
General data: FIELD
Project 33/11 kV SUB-STATION AT ODIGI AT AMBIKAPUR
Location BH-2
Structure ISOLATED
RL -
Inclination of Load to vertical in drgrees 0
Depth of foundation m 2
RL of Ground water level -
LABORATORY
Bulk Density of soil 1.99
Natural moisture Content 14.31
Dry Density 1.74
Specific Gravity 2.56
Void ratio 0.47
Angle of Internal Friction 14.83
Cohesion 6.4
Effect of water Table 5.39
As the soil is cohesionless the analysis for the bearing capacity will have to in pursuant to the Table-3 of IS:6403-1981based on void ratio.
The Void ratio of soil sample 0.47
The condition of soil is dense The bearing capacity will have to be calculated by General Shear Failure Values. Table: 3 of
IS:6403-1981
GENERAL SHEAR FAILURE
Width of foundation 1.00
Length of foundation 1.001.00
Ultimate net bearing capacity qd: 99.49 ton/m2
qd= cNc. sc .dc.ic + γγγγd(Nq-1).sq.dq.iq + 1/2.B.γγγγ.Ng.sγγγγ.dγγγγ.iγγγγ.W’
Net Bearing Capacity 33.16
The effect of depth factor has not been considered ref. cl. 5.1.2.2 of IS 6403-1981
Calculation Sheet
25mm 40mm
2.00 0.36 20.50 1.99 31.01 22.00 12.64 20.23
2.00 0.36 20.50 1.99 33.16 22.00 13.19 21.11
WIDTH OF
FOUNDATION
(m)
SHEAR PARAMETERS
c kg/cm2 φφφφ degree γγγγ g/cc
RECOMMENDED ALLOWABLE BEARING PRESSURE- ODIGI SUB-STATION
1.50 20.00
2.00 21.00
Av. SPT N
value over
significant
depth
NET SAFE
BEARING
CAPACITY
ton/m2
NET BEARING
PRESSURE ton/m2 for
settlement of
RECOMMENDED
ALLOWABLE BEARING
PRESSURE ton/m2
DEPTH OF FOUNDATION
(m)
Sun-Tech
Ranchi Checked/ Approved
Sun-Tech
Sun-Tech