Khatib & Alami (CEC) November 2014 1 of 7
DETAILS OF CONNECTED LOAD/MAX. DEMAND
RATING-AMPS PVC/ CABLE SIZE CONNECTED LOAD - kW PROPOSED TYPE & NO. OF
CIRCUIT/ SP / FAULT XLPE ECC kWh METERS
FEEDER TP DUTY SIZE- LV/HV REMARKS
DB No. F/S / ACB MCCB kA SWA/ 2/4 X 2/3/4C IC, R - PH Y - PH B - PH TOTAL 1 - PH 3 - PH 3 - PH CT
ISO A PVC kW kW kW kW (1) (2) (3) (4)
INCOMER TP 400 50 XLPE/SWA 4C x 300 1C x 150 39.20 39.20 39.20 117.60
OUTGOING:FP - 2.1.1 TP 80 35 MDPE/SWA 4C x 240 1C x 120 39.20 39.20 39.20 117.60 1
Spare TP 0 25 0.00 0.00 0.00 0.00
Spare TP 0 25 0.00 0.00 0.00 0.00
Spare TP 0 25 0.00 0.00 0.00 0.00
TOTAL CONNECTED LOAD PER PHASE 39.20 39.20 39.20 117.60 1
162.55 DIVERSITY = 1.38 TOTAL CONNECTED LOAD (3PH): 117.60 kW
CONSULTANT : Khatib & Alami TEL:06 - 5722444 FAX: 06 - 5722224
Type of Meter (Rating of Incomer): (1) Upto 60 A (2) Upto 100 A (3) 125-160 A (4) LV CT ..…........ / …..........A HV CT ................ / ............ A
(1 Phase) (3 Phase)
.
PROJECT: Infrastructure Works for Dubai Parks (Phase 1) AREA: Saih Shuaib
PLANNED COMPLETION DATE: 2015 OWNER : Meraas Estates LLC PLOT NO.: 513-105
TOTAL SUMMARY SHEET: FP-2.1 CONSULTANT : KHATIB & ALAMI (CEC) LOCATION OF MDB: Beside PS-2
IC mm2 mm2 mm2
MAX DEMAND 3PH:
Khatib & Alami (CEC) November 2014 2 of 7
DETAILS OF CONNECTED LOAD/MAX. DEMAND
RATING-AMPS PVC/ CABLE SIZE CONNECTED LOAD - kW PROPOSED TYPE & NO. OF
CIRCUIT/ SP / FAULT XLPE ECC kWh METERS
FEEDER TP DUTY SIZE- LV/HV REMARKS
DB No. F/S / ACB MCCB kA SWA/ 2/4 X 2/3/4C IC, R - PH Y - PH B - PH TOTAL 1 - PH 3 - PH 3 - PH CT
ISO A PVC kW kW kW kW (1) (2) (3) (4)
INCOMER TP 80 35 XLPE/SWA 4C x 240 1C x 120 28.20 28.20 28.20 117.60 1
OUTGOING:Street Lighting FP1 TP 63 25 MDPE/SWA 4C x 150 1C x 95 10.33 10.33 10.33 31.00
Street Lighting FP2 TP 63 25 MDPE/SWA 4C x 150 1C x 95 9.75 9.75 9.75 29.25
Street Lighting FP3 TP 63 25 MDPE/SWA 4C x 70 1C x 35 8.12 8.12 8.12 24.35
spare TP 63 25 11.00 11.00 11.00 33.00
TOTAL CONNECTED LOAD PER PHASE 39.20 39.20 39.20 117.60
117.60 DIVERSITY = 1.00 TOTAL CONNECTED LOAD (3PH): 117.60 kW
CONSULTANT : Khatib & Alami TEL:06 - 5722444 FAX: 06 - 5722224
Type of Meter (Rating of Incomer): (1) Upto 60 A (2) Upto 100 A (3) 125-160 A (4) LV CT ..…........ / …..........A HV CT ................ / ............ A
(1 Phase) (3 Phase)
.
PROJECT: Infrastructure Works for Dubai Parks (Phase 1) AREA: Saih Shuaib
PLANNED COMPLETION DATE: 2015 OWNER : Meraas Estates LLC PLOT NO.: 513-105
TOTAL SUMMARY SHEET: FP-2.1.1 CONSULTANT : KHATIB & ALAMI (CEC) LOCATION OF MDB: Beside PS-2
IC mm2 mm2 mm2
MAX DEMAND 3PH:
Khatib & Alami (CEC) November 2014 3 of 7
DETAILS OF CONNECTED LOAD/MAX. DEMAND
RATING-AMPS PVC/ CABLE SIZE CONNECTED LOAD - kW PROPOSED TYPE & NO. OF
CIRCUIT/ SP / FAULT XLPE ECC kWh METERS
FEEDER TP DUTY SIZE- LV/HV REMARKS
DB No. F/S / ACB MCCB kA SWA/ 2/4 X 2/3/4C IC, R - PH Y - PH B - PH TOTAL 1 - PH 3 - PH 3 - PH CT
ISO A PVC kW kW kW kW (1) (2) (3) (4)
INCOMER TP 400 50 XLPE/SWA 4C x 300 1C x 150 41.03 41.03 41.03 123.10
OUTGOING:FP - 3.1.1 TP 100 35 MDPE/SWA 4C x 240 1C x 120 41.03 41.03 41.03 123.10 1
GSM Tower TP 0 25 0.00 0.00 0.00 0.00
Spare TP 0 25 0.00 0.00 0.00 0.00
Spare TP 0 25 0.00 0.00 0.00 0.00
TOTAL CONNECTED LOAD PER PHASE 41.03 41.03 41.03 123.10 1
183.00 DIVERSITY = 1.49 TOTAL CONNECTED LOAD (3PH): 123.10 kW
CONSULTANT : Khatib & Alami TEL:06 - 5722444 FAX: 06 - 5722224
Type of Meter (Rating of Incomer): (1) Upto 60 A (2) Upto 100 A (3) 125-160 A (4) LV CT ..…........ / …..........A HV CT ................ / ............ A
(1 Phase) (3 Phase)
.
PROJECT: Infrastructure Works for Dubai Parks (Phase 1) AREA: Saih Shuaib
PLANNED COMPLETION DATE: 2015 OWNER : Meraas Estates LLC PLOT NO.: 513-105
TOTAL SUMMARY SHEET: FP-3.1 CONSULTANT : KHATIB & ALAMI (CEC) LOCATION OF MDB: Beside PS-3
IC mm2 mm2 mm2
MAX DEMAND 3PH:
Khatib & Alami (CEC) November 2014 4 of 7
DETAILS OF CONNECTED LOAD/MAX. DEMAND
RATING-AMPS PVC/ CABLE SIZE CONNECTED LOAD - kW PROPOSED TYPE & NO. OF
CIRCUIT/ SP / FAULT XLPE ECC kWh METERS
FEEDER TP DUTY SIZE- LV/HV REMARKS
DB No. F/S / ACB MCCB kA SWA/ 2/4 X 2/3/4C IC, R - PH Y - PH B - PH TOTAL 1 - PH 3 - PH 3 - PH CT
ISO A PVC kW kW kW kW (1) (2) (3) (4)
INCOMER TP 100 35 XLPE/SWA 4C x 240 1C x 120 19.03 19.03 19.03 123.10 1
OUTGOING:Street Lighting FP4 TP 63 25 MDPE/SWA 4C x 150 1C x 95 7.97 7.97 7.97 23.90
Street Lighting FP5 TP 63 25 MDPE/SWA 4C x 120 1C x 70 11.07 11.07 11.07 33.20
spare TP 63 25 11.00 11.00 11.00 33.00
spare TP 63 25 11.00 11.00 11.00 33.00
TOTAL CONNECTED LOAD PER PHASE 41.03 41.03 41.03 123.10
183.00 DIVERSITY = 1.49 TOTAL CONNECTED LOAD (3PH): 123.10 kW
CONSULTANT : Khatib & Alami TEL:06 - 5722444 FAX: 06 - 5722224
Type of Meter (Rating of Incomer): (1) Upto 60 A (2) Upto 100 A (3) 125-160 A (4) LV CT ..…........ / …..........A HV CT ................ / ............ A
(1 Phase) (3 Phase)
.
PROJECT: Infrastructure Works for Dubai Parks (Phase 1) AREA: Saih Shuaib
PLANNED COMPLETION DATE: 2015 OWNER : Meraas Estates LLC PLOT NO.: 513-105
TOTAL SUMMARY SHEET: FP-3.1.1 CONSULTANT : KHATIB & ALAMI (CEC) LOCATION OF MDB: Beside PS-3
IC mm2 mm2 mm2
MAX DEMAND 3PH:
Khatib & Alami (CEC) November 2014 5 of 7
DETAILS OF CONNECTED LOAD/MAX. DEMAND
RATING-AMPS PVC/ CABLE SIZE CONNECTED LOAD - kW PROPOSED TYPE & NO. OF
CIRCUIT/ SP / FAULT XLPE ECC kWh METERS
FEEDER TP DUTY SIZE- LV/HV REMARKS
DB No. F/S / ACB MCCB kA SWA/ 2/4 X 2/3/4C IC, R - PH Y - PH B - PH TOTAL 1 - PH 3 - PH 3 - PH CT
ISO A PVC kW kW kW kW (1) (2) (3) (4)
INCOMER TP 400 50 XLPE/SWA 4C x 300 1C x 150 49.12 49.12 49.12 147.35
OUTGOING:FP - 4.1.1 TP 100 35 MDPE/SWA 4C x 240 1C x 120 49.12 49.12 49.12 147.35 1
Spare TP 0 25 0.00 0.00 0.00
Spare TP 0 25 0.00 0.00 0.00
Spare TP 0 25 0.00 0.00 0.00
TOTAL CONNECTED LOAD PER PHASE 49.12 49.12 49.12 147.35 1
177.30 DIVERSITY = 1.20 TOTAL CONNECTED LOAD (3PH): 147.35 kW
CONSULTANT : Khatib & Alami TEL:06 - 5722444 FAX: 06 - 5722224
Type of Meter (Rating of Incomer): (1) Upto 60 A (2) Upto 100 A (3) 125-160 A (4) LV CT ..…........ / …..........A HV CT ................ / ............ A
(1 Phase) (3 Phase)
.
PROJECT: Infrastructure Works for Dubai Parks (Phase 1) AREA: Saih Shuaib
PLANNED COMPLETION DATE: 2015 OWNER : Meraas Estates LLC PLOT NO.: 513-105
TOTAL SUMMARY SHEET: FP-4.1 CONSULTANT : KHATIB & ALAMI (CEC) LOCATION OF MDB: Beside PS-4
IC mm2 mm2 mm2
MAX DEMAND 3PH:
Khatib & Alami (CEC) November 2014 6 of 7
DETAILS OF CONNECTED LOAD/MAX. DEMAND
RATING-AMPS PVC/ CABLE SIZE CONNECTED LOAD - kW PROPOSED TYPE & NO. OF
CIRCUIT/ SP / FAULT XLPE ECC kWh METERS
FEEDER TP DUTY SIZE- LV/HV REMARKS
DB No. F/S / ACB MCCB kA SWA/ 2/4 X 2/3/4C IC, R - PH Y - PH B - PH TOTAL 1 - PH 3 - PH 3 - PH CT
ISO A PVC kW kW kW kW (1) (2) (3) (4)
INCOMER TP 100 50 XLPE/SWA 4C x 240 1C x 120 27.38 27.38 27.38 147.35 1
OUTGOING:Street Lighting FP6 TP 63 25 MDPE/SWA 4C x 120 1C x 70 8.02 8.02 8.02 24.05
Street Lighting FP7 TP 63 25 MDPE/SWA 4C x 120 1C x 70 9.12 9.12 9.12 27.35
Street Lighting FP8 TP 63 25 MDPE/SWA 4C x 120 1C x 70 10.25 10.25 10.25 30.75
Street Lighting FP10 TP 63 25 MDPE/SWA 4C x 185 1C x 95 10.73 10.73 10.73 32.20
SPARE TP 63 25 11.00 11.00 11.00 33.00
TOTAL CONNECTED LOAD PER PHASE 49.12 49.12 49.12 147.35
177.30 DIVERSITY = 1.20 TOTAL CONNECTED LOAD (3PH): 147.35 kW
CONSULTANT : Khatib & Alami TEL:06 - 5722444 FAX: 06 - 5722224
Type of Meter (Rating of Incomer): (1) Upto 60 A (2) Upto 100 A (3) 125-160 A (4) LV CT ..…........ / …..........A HV CT ................ / ............ A
(1 Phase) (3 Phase)
.
PROJECT: Infrastructure Works for Dubai Parks (Phase 1) AREA: Saih Shuaib
PLANNED COMPLETION DATE: 2015 OWNER : Meraas Estates LLC PLOT NO.: 513-105
TOTAL SUMMARY SHEET: FP-4.1.1 CONSULTANT : KHATIB & ALAMI (CEC) LOCATION OF MDB: Beside PS-4
IC mm2 mm2 mm2
MAX DEMAND 3PH:
Khatib & Alami (CEC) November 2014 7 of 7
DETAILS OF CONNECTED LOAD/MAX. DEMAND
RATING-AMPS PVC/ CABLE SIZE CONNECTED LOAD - kW PROPOSED TYPE & NO. OF
CIRCUIT/ SP / FAULT XLPE ECC kWh METERS
FEEDER TP DUTY SIZE- LV/HV REMARKS
DB No. F/S / ACB MCCB kA SWA/ 2/4 X 2/3/4C IC, R - PH Y - PH B - PH TOTAL 1 - PH 3 - PH 3 - PH CT
ISO A PVC kW kW kW kW (1) (2) (3) (4)
INCOMER TP 400 50 XLPE/SWA 4C x 300 1C x 150 11.47 11.47 11.47 34.40
OUTGOING:Street Lighting FP09 TP 63 25 XLPE/SWA 4C X 120 1C x 95 11.47 11.47 11.47 34.40 1
LIFTING STATION-1(SMDB-LS-1) TP 0 25 0.00 0.00 0.00 0
GSM Tower TP 0 25 0.00 0.00 0.00 0
GSM Tower TP 0 25 0.00 0.00 0.00 0
TOTAL CONNECTED LOAD PER PHASE 11.47 11.47 11.47 34.40
176.50 DIVERSITY = 5.13 TOTAL CONNECTED LOAD (3PH): 34.40 kW
CONSULTANT : Khatib & Alami TEL:06 - 5722444 FAX: 06 - 5722224
Type of Meter (Rating of Incomer): (1) Upto 60 A (2) Upto 100 A (3) 125-160 A (4) LV CT ..…........ / …..........A HV CT ................ / ............ A
(1 Phase) (3 Phase)
.
PROJECT: Infrastructure Works for Dubai Parks (Phase 1) AREA: Saih Shuaib
PLANNED COMPLETION DATE: 2015 OWNER : Meraas Estates LLC PLOT NO.: 513-105
TOTAL SUMMARY SHEET: FP-5.1 CONSULTANT : KHATIB & ALAMI (CEC) LOCATION OF MDB: Beside PS-5
IC mm2 mm2 mm2
MAX DEMAND 3PH: