SPS FIRE SAFETY PROJECTL S 2

2018-08-29 edms#1840655 D. del Alamo

Page 2: SPS FIRE SAFETY PROJECT€¦ · FIRE SPRINKLER PROTECTION SYSTEM 2018-08-29 edms#1840655 D. del Alamo Sprinkler StationSprinkler Station The definitive size of the sprinkler stations

FIRE SPRINKLER PROTECTION SYSTEM

2018-08-29 D. del Alamoedms#1840655

Sprinkler StationSprinkler Station

22

00

2225

96

0ST1029101_01

2510

Source CV

30

54

Page 3: SPS FIRE SAFETY PROJECT€¦ · FIRE SPRINKLER PROTECTION SYSTEM 2018-08-29 edms#1840655 D. del Alamo Sprinkler StationSprinkler Station The definitive size of the sprinkler stations

FIRE SPRINKLER PROTECTION SYSTEM

2018-08-29 D. del Alamoedms#1840655

Sprinkler StationSprinkler Station

The definitive size of the sprinkler stations are: - Height 3054mm - Length 1967mm (2225mm with fence). In some cases, depending the BA, the space required for the water source

pipe increases the length required to 2510mm.- Width 920mm (960mm with fence and support). ARCECLIMA foresees a support width of 111mm.- Any changes of the size above the accepted volumes will create a non-conformity.- ARCECLIMA will prepare the final requirements document and will send them to SMB to calculate the support,

preparing themselves a proposal beforehand.- ARCECLIMA will not model the CV part of the connecting pipe to the flange of the sprinkler station, which should

be modelled inside the fenced space.- CERN Integration Section will model the pipes connecting to the shaft.

Page 4: SPS FIRE SAFETY PROJECT€¦ · FIRE SPRINKLER PROTECTION SYSTEM 2018-08-29 edms#1840655 D. del Alamo Sprinkler StationSprinkler Station The definitive size of the sprinkler stations

FIRE DETECTION & PROTECTION SYSTEM

2018-08-29 D. del Alamoedms#1840655

23

00

1800

60

0

800

CIECIE

Page 5: SPS FIRE SAFETY PROJECT€¦ · FIRE SPRINKLER PROTECTION SYSTEM 2018-08-29 edms#1840655 D. del Alamo Sprinkler StationSprinkler Station The definitive size of the sprinkler stations

FIRE DETECTION & PROTECTION SYSTEM

2018-08-29 D. del Alamoedms#1840655

750

CIECIE

2 support UPN100 beams havebeen included in the model for theinstallation of the racks on top ofthe structure of the BAs floor.

Page 6: SPS FIRE SAFETY PROJECT€¦ · FIRE SPRINKLER PROTECTION SYSTEM 2018-08-29 edms#1840655 D. del Alamo Sprinkler StationSprinkler Station The definitive size of the sprinkler stations

FIRE DETECTION & PROTECTION SYSTEM

2018-08-29 D. del Alamoedms#1840655

20

00

1000

30

0

ASDASD

60

0

19

00

10

0

Page 7: SPS FIRE SAFETY PROJECT€¦ · FIRE SPRINKLER PROTECTION SYSTEM 2018-08-29 edms#1840655 D. del Alamo Sprinkler StationSprinkler Station The definitive size of the sprinkler stations

FIRE DETECTION & PROTECTION SYSTEM

2018-08-29 D. del Alamoedms#1840655

20

00

2000

30

0

ASDASD

10

0

Page 8: SPS FIRE SAFETY PROJECT€¦ · FIRE SPRINKLER PROTECTION SYSTEM 2018-08-29 edms#1840655 D. del Alamo Sprinkler StationSprinkler Station The definitive size of the sprinkler stations

FIRE DETECTION & PROTECTION SYSTEM

2018-08-29 D. del Alamoedms#1840655

20

00

5200

70

0

LASDLASD

40

023

00

1300

In BA2 the LASD has one moremodule

Page 9: SPS FIRE SAFETY PROJECT€¦ · FIRE SPRINKLER PROTECTION SYSTEM 2018-08-29 edms#1840655 D. del Alamo Sprinkler StationSprinkler Station The definitive size of the sprinkler stations

FIRE DETECTION & PROTECTION SYSTEM

2018-08-29 D. del Alamoedms#1840655

All of the support structures concerning the componentsof the FSP are for Civil Engineering to design. The modelsshown are integration simplified proposal to estimate thedimensions of the elements

Page 10: SPS FIRE SAFETY PROJECT€¦ · FIRE SPRINKLER PROTECTION SYSTEM 2018-08-29 edms#1840655 D. del Alamo Sprinkler StationSprinkler Station The definitive size of the sprinkler stations

SPS FIRE SAFETY PROJECT

2018-08-29 edms#1840655 D. del Alamo

BA1

ST0985021_02

FIXED

Page 11: SPS FIRE SAFETY PROJECT€¦ · FIRE SPRINKLER PROTECTION SYSTEM 2018-08-29 edms#1840655 D. del Alamo Sprinkler StationSprinkler Station The definitive size of the sprinkler stations

FIRE SPRINKLER PROTECTION SYSTEM

2018-08-29 D. del Alamoedms#1840655

BA1

FIXED

Page 12: SPS FIRE SAFETY PROJECT€¦ · FIRE SPRINKLER PROTECTION SYSTEM 2018-08-29 edms#1840655 D. del Alamo Sprinkler StationSprinkler Station The definitive size of the sprinkler stations

FIRE SPRINKLER PROTECTION SYSTEM

2018-08-29 D. del Alamoedms#1840655

BA1

FIXED

Page 13: SPS FIRE SAFETY PROJECT€¦ · FIRE SPRINKLER PROTECTION SYSTEM 2018-08-29 edms#1840655 D. del Alamo Sprinkler StationSprinkler Station The definitive size of the sprinkler stations

FIRE SPRINKLER PROTECTION SYSTEM

2018-08-29 D. del Alamoedms#1840655

BA1

FIXED

Allowable Load 15kN/m2

Page 14: SPS FIRE SAFETY PROJECT€¦ · FIRE SPRINKLER PROTECTION SYSTEM 2018-08-29 edms#1840655 D. del Alamo Sprinkler StationSprinkler Station The definitive size of the sprinkler stations

FIRE DETECTION & PROTECTION SYSTEM

2018-08-29 D. del Alamoedms#1840655

BA1

ONGOING

Page 15: SPS FIRE SAFETY PROJECT€¦ · FIRE SPRINKLER PROTECTION SYSTEM 2018-08-29 edms#1840655 D. del Alamo Sprinkler StationSprinkler Station The definitive size of the sprinkler stations

FIRE DETECTION & PROTECTION SYSTEM

2018-08-29 D. del Alamoedms#1840655

BA1

ONGOING

Page 16: SPS FIRE SAFETY PROJECT€¦ · FIRE SPRINKLER PROTECTION SYSTEM 2018-08-29 edms#1840655 D. del Alamo Sprinkler StationSprinkler Station The definitive size of the sprinkler stations

SPS FIRE SAFETY PROJECT

2018-08-29 edms#1840655 D. del Alamo

BA2

ST0985065_02

FIXED

Page 17: SPS FIRE SAFETY PROJECT€¦ · FIRE SPRINKLER PROTECTION SYSTEM 2018-08-29 edms#1840655 D. del Alamo Sprinkler StationSprinkler Station The definitive size of the sprinkler stations

FIRE SPRINKLER PROTECTION SYSTEM

2018-08-29 D. del Alamoedms#1840655

BA2

FIXED

Page 18: SPS FIRE SAFETY PROJECT€¦ · FIRE SPRINKLER PROTECTION SYSTEM 2018-08-29 edms#1840655 D. del Alamo Sprinkler StationSprinkler Station The definitive size of the sprinkler stations

FIRE SPRINKLER PROTECTION SYSTEM

2018-08-29 D. del Alamoedms#1840655

BA2

Removal of racks:• RA 5729 / BE-CO• RA 5730 / BE-BI• RA 5733 / TE-EPC• RA 5734 / TE-EPC• RA 5735 / TE-EPC

Move rack RA 5731 / TE-EPC900 to the right

RA

57

31

/ T

E-EP

C

FIXED

Page 19: SPS FIRE SAFETY PROJECT€¦ · FIRE SPRINKLER PROTECTION SYSTEM 2018-08-29 edms#1840655 D. del Alamo Sprinkler StationSprinkler Station The definitive size of the sprinkler stations

FIRE SPRINKLER PROTECTION SYSTEM

2018-08-29 D. del Alamoedms#1840655

BA2

FIXED

Page 20: SPS FIRE SAFETY PROJECT€¦ · FIRE SPRINKLER PROTECTION SYSTEM 2018-08-29 edms#1840655 D. del Alamo Sprinkler StationSprinkler Station The definitive size of the sprinkler stations

FIRE SPRINKLER PROTECTION SYSTEM

2018-08-29 D. del Alamoedms#1840655

BA2

FIXED

Allowable Load 3kN/m2

Page 21: SPS FIRE SAFETY PROJECT€¦ · FIRE SPRINKLER PROTECTION SYSTEM 2018-08-29 edms#1840655 D. del Alamo Sprinkler StationSprinkler Station The definitive size of the sprinkler stations

FIRE DETECTION & PROTECTION SYSTEM

2018-08-29 D. del Alamoedms#1840655

BA2

FIXED

Page 22: SPS FIRE SAFETY PROJECT€¦ · FIRE SPRINKLER PROTECTION SYSTEM 2018-08-29 edms#1840655 D. del Alamo Sprinkler StationSprinkler Station The definitive size of the sprinkler stations

FIRE DETECTION & PROTECTION SYSTEM

2018-08-29 D. del Alamoedms#1840655

BA2

FIXED

Page 23: SPS FIRE SAFETY PROJECT€¦ · FIRE SPRINKLER PROTECTION SYSTEM 2018-08-29 edms#1840655 D. del Alamo Sprinkler StationSprinkler Station The definitive size of the sprinkler stations

FIRE DETECTION & PROTECTION SYSTEM

2018-08-29 D. del Alamoedms#1840655

BA2

FIXED

70

0

Allowable Load 10kN/m2

Page 24: SPS FIRE SAFETY PROJECT€¦ · FIRE SPRINKLER PROTECTION SYSTEM 2018-08-29 edms#1840655 D. del Alamo Sprinkler StationSprinkler Station The definitive size of the sprinkler stations

SPS FIRE SAFETY PROJECT

2018-08-29 edms#1840655 D. del Alamo

BA3

ST0985121_02

FIXED

Page 25: SPS FIRE SAFETY PROJECT€¦ · FIRE SPRINKLER PROTECTION SYSTEM 2018-08-29 edms#1840655 D. del Alamo Sprinkler StationSprinkler Station The definitive size of the sprinkler stations

FIRE SPRINKLER PROTECTION SYSTEM

2018-08-29 D. del Alamoedms#1840655

BA3

FIXED

Page 26: SPS FIRE SAFETY PROJECT€¦ · FIRE SPRINKLER PROTECTION SYSTEM 2018-08-29 edms#1840655 D. del Alamo Sprinkler StationSprinkler Station The definitive size of the sprinkler stations

FIRE SPRINKLER PROTECTION SYSTEM

2018-08-29 D. del Alamoedms#1840655

BA3

FIXED

Page 27: SPS FIRE SAFETY PROJECT€¦ · FIRE SPRINKLER PROTECTION SYSTEM 2018-08-29 edms#1840655 D. del Alamo Sprinkler StationSprinkler Station The definitive size of the sprinkler stations

FIRE SPRINKLER PROTECTION SYSTEM

2018-08-29 D. del Alamoedms#1840655

BA3

FIXED

Allowable Load 25kN/m2

Page 28: SPS FIRE SAFETY PROJECT€¦ · FIRE SPRINKLER PROTECTION SYSTEM 2018-08-29 edms#1840655 D. del Alamo Sprinkler StationSprinkler Station The definitive size of the sprinkler stations

FIRE SPRINKLER PROTECTION SYSTEM

2018-08-29 D. del Alamoedms#1840655

BA3

FIXED

Page 29: SPS FIRE SAFETY PROJECT€¦ · FIRE SPRINKLER PROTECTION SYSTEM 2018-08-29 edms#1840655 D. del Alamo Sprinkler StationSprinkler Station The definitive size of the sprinkler stations

FIRE DETECTION & PROTECTION SYSTEM

2018-08-29 D. del Alamoedms#1840655

BA3

FIXED

Page 30: SPS FIRE SAFETY PROJECT€¦ · FIRE SPRINKLER PROTECTION SYSTEM 2018-08-29 edms#1840655 D. del Alamo Sprinkler StationSprinkler Station The definitive size of the sprinkler stations

FIRE DETECTION & PROTECTION SYSTEM

2018-08-29 D. del Alamoedms#1840655

BA3

Direct passage to the shaft

FIXED

Page 31: SPS FIRE SAFETY PROJECT€¦ · FIRE SPRINKLER PROTECTION SYSTEM 2018-08-29 edms#1840655 D. del Alamo Sprinkler StationSprinkler Station The definitive size of the sprinkler stations

FIRE DETECTION & PROTECTION SYSTEM

2018-08-29 D. del Alamoedms#1840655

BA3

FIXED

Allowable Load 5kN/m2

Page 32: SPS FIRE SAFETY PROJECT€¦ · FIRE SPRINKLER PROTECTION SYSTEM 2018-08-29 edms#1840655 D. del Alamo Sprinkler StationSprinkler Station The definitive size of the sprinkler stations

SPS FIRE SAFETY PROJECT

2018-08-29 edms#1840655 D. del Alamo

BA4

ST0985159_02

FIXED

Page 33: SPS FIRE SAFETY PROJECT€¦ · FIRE SPRINKLER PROTECTION SYSTEM 2018-08-29 edms#1840655 D. del Alamo Sprinkler StationSprinkler Station The definitive size of the sprinkler stations

FIRE SPRINKLER PROTECTION SYSTEM

2018-08-29 D. del Alamoedms#1840655

BA4

FIXED

Page 34: SPS FIRE SAFETY PROJECT€¦ · FIRE SPRINKLER PROTECTION SYSTEM 2018-08-29 edms#1840655 D. del Alamo Sprinkler StationSprinkler Station The definitive size of the sprinkler stations

FIRE SPRINKLER PROTECTION SYSTEM

2018-08-29 D. del Alamoedms#1840655

BA4

FIXED

Page 35: SPS FIRE SAFETY PROJECT€¦ · FIRE SPRINKLER PROTECTION SYSTEM 2018-08-29 edms#1840655 D. del Alamo Sprinkler StationSprinkler Station The definitive size of the sprinkler stations

FIRE SPRINKLER PROTECTION SYSTEM

2018-08-29 D. del Alamoedms#1840655

BA4

890mm

FIXED

Allowable Load 25kN/m2

Page 36: SPS FIRE SAFETY PROJECT€¦ · FIRE SPRINKLER PROTECTION SYSTEM 2018-08-29 edms#1840655 D. del Alamo Sprinkler StationSprinkler Station The definitive size of the sprinkler stations

FIRE DETECTION & PROTECTION SYSTEM

2018-08-29 D. del Alamoedms#1840655

BA4

FIXED

Page 37: SPS FIRE SAFETY PROJECT€¦ · FIRE SPRINKLER PROTECTION SYSTEM 2018-08-29 edms#1840655 D. del Alamo Sprinkler StationSprinkler Station The definitive size of the sprinkler stations

FIRE DETECTION & PROTECTION SYSTEM

2018-08-29 D. del Alamoedms#1840655

BA4

FIXED

Page 38: SPS FIRE SAFETY PROJECT€¦ · FIRE SPRINKLER PROTECTION SYSTEM 2018-08-29 edms#1840655 D. del Alamo Sprinkler StationSprinkler Station The definitive size of the sprinkler stations

FIRE DETECTION & PROTECTION SYSTEM

2018-08-29 D. del Alamoedms#1840655

BA4

FIXED

Allowable Load 0,4kN/m2

Page 39: SPS FIRE SAFETY PROJECT€¦ · FIRE SPRINKLER PROTECTION SYSTEM 2018-08-29 edms#1840655 D. del Alamo Sprinkler StationSprinkler Station The definitive size of the sprinkler stations

SPS FIRE SAFETY PROJECT

2018-08-29 edms#1840655 D. del Alamo

BA5

ST0985175_02

FIXED

Page 40: SPS FIRE SAFETY PROJECT€¦ · FIRE SPRINKLER PROTECTION SYSTEM 2018-08-29 edms#1840655 D. del Alamo Sprinkler StationSprinkler Station The definitive size of the sprinkler stations

FIRE SPRINKLER PROTECTION SYSTEM

2018-08-29 D. del Alamoedms#1840655

BA5

FIXED

Page 41: SPS FIRE SAFETY PROJECT€¦ · FIRE SPRINKLER PROTECTION SYSTEM 2018-08-29 edms#1840655 D. del Alamo Sprinkler StationSprinkler Station The definitive size of the sprinkler stations

FIRE SPRINKLER PROTECTION SYSTEM

2018-08-29 D. del Alamoedms#1840655

BA5

Installation on concrete block

FIXED

Page 42: SPS FIRE SAFETY PROJECT€¦ · FIRE SPRINKLER PROTECTION SYSTEM 2018-08-29 edms#1840655 D. del Alamo Sprinkler StationSprinkler Station The definitive size of the sprinkler stations

FIRE SPRINKLER PROTECTION SYSTEM

2018-08-29 D. del Alamoedms#1840655

BA5

Installation on concrete block

FIXED

Allowable Load 25kN/m2?

Page 43: SPS FIRE SAFETY PROJECT€¦ · FIRE SPRINKLER PROTECTION SYSTEM 2018-08-29 edms#1840655 D. del Alamo Sprinkler StationSprinkler Station The definitive size of the sprinkler stations

FIRE DETECTION & PROTECTION SYSTEM

2018-08-29 D. del Alamoedms#1840655

BA5

FIXED

Page 44: SPS FIRE SAFETY PROJECT€¦ · FIRE SPRINKLER PROTECTION SYSTEM 2018-08-29 edms#1840655 D. del Alamo Sprinkler StationSprinkler Station The definitive size of the sprinkler stations

FIRE DETECTION & PROTECTION SYSTEM

2018-08-29 D. del Alamoedms#1840655

BA5

FIXED

Page 45: SPS FIRE SAFETY PROJECT€¦ · FIRE SPRINKLER PROTECTION SYSTEM 2018-08-29 edms#1840655 D. del Alamo Sprinkler StationSprinkler Station The definitive size of the sprinkler stations

FIRE DETECTION & PROTECTION SYSTEM

2018-08-29 D. del Alamoedms#1840655

BA5

FIXED

Page 46: SPS FIRE SAFETY PROJECT€¦ · FIRE SPRINKLER PROTECTION SYSTEM 2018-08-29 edms#1840655 D. del Alamo Sprinkler StationSprinkler Station The definitive size of the sprinkler stations

FIRE DETECTION & PROTECTION SYSTEM

2018-08-29 D. del Alamoedms#1840655

BA5

43

00

mm

5200mm

1320mm

Access

FIXED

Page 47: SPS FIRE SAFETY PROJECT€¦ · FIRE SPRINKLER PROTECTION SYSTEM 2018-08-29 edms#1840655 D. del Alamo Sprinkler StationSprinkler Station The definitive size of the sprinkler stations

SPS FIRE SAFETY PROJECT

2018-08-29 edms#1840655 D. del Alamo

BA6

ST0985279_02

FIXED

Page 48: SPS FIRE SAFETY PROJECT€¦ · FIRE SPRINKLER PROTECTION SYSTEM 2018-08-29 edms#1840655 D. del Alamo Sprinkler StationSprinkler Station The definitive size of the sprinkler stations

FIRE SPRINKLER PROTECTION SYSTEM

2018-08-29 D. del Alamoedms#1840655

BA6

FIXED

Page 49: SPS FIRE SAFETY PROJECT€¦ · FIRE SPRINKLER PROTECTION SYSTEM 2018-08-29 edms#1840655 D. del Alamo Sprinkler StationSprinkler Station The definitive size of the sprinkler stations

FIRE SPRINKLER PROTECTION SYSTEM

2018-08-29 D. del Alamoedms#1840655

BA6

FIXED

Allowable Load 0,4kN/m2

Page 50: SPS FIRE SAFETY PROJECT€¦ · FIRE SPRINKLER PROTECTION SYSTEM 2018-08-29 edms#1840655 D. del Alamo Sprinkler StationSprinkler Station The definitive size of the sprinkler stations

FIRE DETECTION & PROTECTION SYSTEM

2018-08-29 D. del Alamoedms#1840655

BA6

FIXED

Page 51: SPS FIRE SAFETY PROJECT€¦ · FIRE SPRINKLER PROTECTION SYSTEM 2018-08-29 edms#1840655 D. del Alamo Sprinkler StationSprinkler Station The definitive size of the sprinkler stations

FIRE DETECTION & PROTECTION SYSTEM

2018-08-29 D. del Alamoedms#1840655

BA6

FIXED

Page 52: SPS FIRE SAFETY PROJECT€¦ · FIRE SPRINKLER PROTECTION SYSTEM 2018-08-29 edms#1840655 D. del Alamo Sprinkler StationSprinkler Station The definitive size of the sprinkler stations

FIRE DETECTION & PROTECTION SYSTEM

2018-08-29 D. del Alamoedms#1840655

BA6

FIXED

Allowable Load 10kN/m2

Page 53: SPS FIRE SAFETY PROJECT€¦ · FIRE SPRINKLER PROTECTION SYSTEM 2018-08-29 edms#1840655 D. del Alamo Sprinkler StationSprinkler Station The definitive size of the sprinkler stations

SPS FIRE SAFETY PROJECTL S 2

2018-08-29 edms#1840655 D. del Alamo