    NFPA 13 – Chapter 21

    Alternative Sprinkler System Designs

    for Chapters 12 -20

    1

    http://www.google.com/url?sa=i&rct=j&q=NFPA+13&source=images&cd=&cad=rja&docid=L5LMmf8bYad8tM&tbnid=1fpJXjxu_stfAM:&ved=0CAUQjRw&url=http://www.brownbookshop.com/products/NFPA-13:-Standard-for-the-Installation-of-Sprinkler-Systems-2013-Edition.html&ei=Ba-LUcKrMuji4APmyoCYCA&bvm=bv.46226182,d.dmg&psig=AFQjCNGdHrVnzx3Z2fCkEn2zRUckLA8g7A&ust=1368195199133546http://www.google.com/url?sa=i&rct=j&q=NFPA+13&source=images&cd=&cad=rja&docid=L5LMmf8bYad8tM&tbnid=1fpJXjxu_stfAM:&ved=0CAUQjRw&url=http://www.brownbookshop.com/products/NFPA-13:-Standard-for-the-Installation-of-Sprinkler-Systems-2013-Edition.html&ei=Ba-LUcKrMuji4APmyoCYCA&bvm=bv.46226182,d.dmg&psig=AFQjCNGdHrVnzx3Z2fCkEn2zRUckLA8g7A&ust=1368195199133546http://www.google.com/url?sa=i&rct=j&q=NFPA+13&source=images&cd=&cad=rja&docid=L5LMmf8bYad8tM&tbnid=1fpJXjxu_stfAM:&ved=0CAUQjRw&url=http://www.brownbookshop.com/products/NFPA-13:-Standard-for-the-Installation-of-Sprinkler-Systems-2013-Edition.html&ei=Ba-LUcKrMuji4APmyoCYCA&bvm=bv.46226182,d.dmg&psig=AFQjCNGdHrVnzx3Z2fCkEn2zRUckLA8g7A&ust=1368195199133546

  • 8/17/2019 Sprinkler Design Presentation

    2/25

    Why Chapter 21??

    • Add a New Chapter

    Performance-Based Discharge Criteria

    2

  • 8/17/2019 Sprinkler Design Presentation

    3/25

    Chapter 21

    • General

    • Palletized, Solid-Piled, Bin Box, Shelf or

    Back-to-Back Shelf Storage of Class I-IV and

    Plastic Commodities

    • Open-Frame Rack Storage of Class I-IV and

    Plastic Commodities

    • Hose Stream Allowance and Water Supply

    Duration

    • Minimum Obstruction Criteria

    3

  • 8/17/2019 Sprinkler Design Presentation

    4/25

    Baseline

    • Three Categories of Sprinklers

     – Control Mode Density/Area (CMDA)

     – Control Mode Specific Application (CMSA)

     – Early Suppression Fast Response (ESFR)

    • Minimum Hydraulic Design Criteria

     – Density/Area

     –ESFR

    • Hose Stream Demand

    4

  • 8/17/2019 Sprinkler Design Presentation

    5/25

    The Challenge

    • General Rules of Chapters 12-20

    • Storage Variables

     –

    Arrangement – Commodity Classification

     – Commodity Mixtures

     – Configurations

    5

  • 8/17/2019 Sprinkler Design Presentation

    6/25

    Chapter 21

    • Method for full-scale fire testing

     – Specific Storage Arrangements

     – Specific Maximum Ceiling Heights

    • Resulting in

     – Specific Design Requirements based on performance

     – Minimum safety factors

    6

  • 8/17/2019 Sprinkler Design Presentation

    7/25

    Intent

    • Guidance for planning research for Technical

    Committee review and acceptance.

    7

  • 8/17/2019 Sprinkler Design Presentation

    8/25

    Alternative Approach

    • Specific Data

    • Specific Storage Arrangement

    • Particular Commodity

    • More Flexibility in Design

    8

  • 8/17/2019 Sprinkler Design Presentation

    9/25

    General Requirements

    • 21.1.1 Sprinklers intended to protect storage

    fire risks shall be permitted to be installed

    using water supply design criteria that are

    different from the design criteria specified for

    the sprinklers described in Chapters 12through 20 when specifically listed for such

    use within the limitations described in this

    chapter.

    9

  • 8/17/2019 Sprinkler Design Presentation

    10/25

    General Requirements

    • Chapters 12 through 20 apply unless modified

    • In-rack protection requirements of Chapters

    12 through 20 apply when storage racks are

    equipped with solid shelves and in-rack

    sprinklers are required per the applicable

    chapter.

    10

  • 8/17/2019 Sprinkler Design Presentation

    11/25

    General Requirements

    • Requirements of the applicable chapter apply

    when ceiling-only protection options are not

    available in this chapter.

    • Design criteria cannot be used to permit a

    reduction in the water supply requirements

    for in-rack sprinkler protection.

    11

  • 8/17/2019 Sprinkler Design Presentation

    12/25

    Large Scale Fire Tests

    • Challenging test scenarios

    • Range of variables associated with the

    intended

    • Evaluate the ability of the sprinkler to protect

    representative storage fire risks

    • Based on the manufacturer’s installation and

    design parameter instructions and referenced

    in the listing.

    12

  • 8/17/2019 Sprinkler Design Presentation

    13/25

    Typical Considerations

    • Highest Commodity Classification

    • Storage Arrangement Type• Maximum Storage Height

    • Sprinkler Spacing

    Sprinkler Temperature Rating• Ceiling Height

    • Clearance to Ceiling

    • Sprinkler Distance Below Ceiling

    • Minimum Operating Pressure• Aisle Width

    • Ignition Location

    13

  • 8/17/2019 Sprinkler Design Presentation

    14/25

    Installation & Design Parameters

    (1) Commodity or commodities to be protected

    (2) Storage arrangements allowed

    (3) Installation guidelines including obstruction

    and ceiling construction limitations

    (4) Maximum ceiling and storage heights with

    associated minimum operating pressures and

    number of sprinklers required to be included in

    the hydraulic calculation

    (5) Hose stream allowance and duration

    14

  • 8/17/2019 Sprinkler Design Presentation

    15/25

    Number of Sprinklers

    • Twelve sprinklers for standard coverage

    sprinklers

    • Eight sprinklers for extended-coverage

    sprinklers based on a spacing of 12ft×12ft

    (3.7m×3.7m)

    • Six sprinklers for extended-coverage sprinklers

    based on a spacing of 14ft×14ft (4.3m×4.3m)

    15

  • 8/17/2019 Sprinkler Design Presentation

    16/25

    Minimum Area of Operation

    • Based on the proposed sprinkler spacing,

    Not be less than 768 ft2

     (71m2

    ).

    16

  • 8/17/2019 Sprinkler Design Presentation

    17/25

    21.2

    17

  • 8/17/2019 Sprinkler Design Presentation

    18/25

    21.2

    18

  • 8/17/2019 Sprinkler Design Presentation

    19/25

    21.3

    19

  • 8/17/2019 Sprinkler Design Presentation

    20/25

    21.3

    20

  • 8/17/2019 Sprinkler Design Presentation

    21/25

    Hose Stream Allowance & Duration

    21

    Sprinkler Type  Sprinkler

    Spacing Type 

    Number of

    Sprinklers inDesign Area 

    Hose Stream Allowance

    gpm L/min 

    Water

    SupplyDuration 

    CMDA & CMSA  Standard  Up to 12

    Over 12 to 15

    Over 15 to 25

    Over 25 

    250 950

    500 1900

    500 1900

    500 1900 

    60

    90

    120

    150 

    CMDA & CMSA  Extended

    Coverage 

    Up to 6

    Up to 8 (144ft2)

    Over 6 to 8

    Over 8 to 12

    Over 12 

    250 950

    250 950

    500 1900

    500 1900

    500 1900 

    60

    60

    90

    120

    150 

    ESFR  Standard  Up to 12

    Over 12 to 15

    Over 15 to 25

    Over 25 

    250 950

    500 1900

    500 1900

    500 1900 

    60

    90

    120

    150 

  • 8/17/2019 Sprinkler Design Presentation

    22/25

    Comparison of Design Requirements

    22

    Sprinkler Type 

    Number ofDesign

    Sprinklers 

    Hose Stream Allowance

    gpm L/min 

    WaterSupply

    Duration 

    CMDA  20 or More  500 1900  120 or More 

    EC/CMDA  11 or More  500 1900  120 or More 

    CMSA 

    15 or More 

    500 1900 

    90 or More 

    ESFR  12  250 950  60 

    Sprinkler Type  Number of

    Design

    Sprinklers 

    Hose Stream Allowance

    gpm L/min 

    Water

    Supply

    Duration 

    CMSA & ESFR  12  250 950  60 

    EC-CMSA

    (3.7m x 3.7m) 

    8  250 950  60 

    EC-CMSA

    (4.3m x 4.3m) 

    6  250 950  60 

    Chapters 12 through 19

    Chapter 21

  • 8/17/2019 Sprinkler Design Presentation

    23/25

    EC-CMSA

    • Nominal K-Factor – 25.2 (360)

    • Commodity Storage

     – Palletized, Solid pile and Open Rack Storage

     – Commodities of up to Cartoned, Expanded

    Group A Plastics

    • Maximum Storage Height

    • Coverage Areas

     – 12ft x 12ft (3.7m x 3.7m)

     – 14ft x 14ft (4.3m x 4.3m)

    23

  • 8/17/2019 Sprinkler Design Presentation

    24/25

    Minimum Obstruction Criteria

    • Based on the number of sprinklers included in

    the design.

    • Correlates to requirements for

    CMDA/CMSA/EC/ESFR

    • Number of sprinklers in the design area

    impacts the obstruction requirements

    • Options

    24

  • 8/17/2019 Sprinkler Design Presentation

    25/25