SOUTHWIRE’S MCAP®
Southwire's patented innovation will save contractors up to 30 percent ininstallation time and costs. This UL-listed and NEC compliant product replacesconventional MC cable in a broad range of applications because it eliminates theneed to make-up a ground in every box, in every outlet, every time. With its
superior bending and pulling performance, MCAP® assures a professional lookinginstallation in fewer steps, with less labor and in less time. It's another Southwire
innovation to help gain a competitive edge on every job.
MCAP®, the next generation in metal clad cable.
HOW ITÊS USEDÛ For certain applications:
- For branch, feeder, power, lighting, control, signal circuits and service power distribution in commercial,industrial, institutional and multi-residential buildings- Fished or embedded in plaster- For cable trays and approved raceways
Û For certain locations:- Environmental air-handling spaces, per NEC 300.22(C)- Under raised floors for information technology equipment conductors and cables, per NEC 645.5(D) and 645.5(D)(2)- For concealed or exposed installations
Armorlite®ACALUMINUM ARMORED CABLE
HOW ITÊS MADEÛ Conductors: Type THHN/THWN, soft-drawn copper, wrapped with a moisture-resistant, flame-retardant paper
covering and then aluminum armor is applied over the conductorsÛ A 16 AWG aluminum bond wire is placed inside the armor and runs longitudinally
HOW ITÊS CERTIFIEDÛ SouthwireÊs Armorlite® Type AC meets or exceeds the requirements of UL Standard 4 for Armored Cable,
UL Standard 83, Federal Specification A-A59544 (formerly J-C-30B) and the National Electrical Code.SouthwireÊs Armorlite® Type AC is listed for use in UL 1, 2 and 3 Hour Through-Penetration Firestop Systems.
54
Û AC: Aluminum CableÛ 600 VoltsÛ For Dry Locations
METAL CLAD& CONDUIT
Arm
orlit
e®A
CA
LUM
INU
MA
RMO
RED
CA
BLE
55
CONDUCTORSIZE
(AWG)CONDUCTOR
TYPE
ALUMINUMBONDINGWIRE SIZE
(AWG)OUTSIDE
DIAMETER(INCHES)
ALUMINUM INTERLOCKED ARMOR AMPACITIES+ (AMPS)
WEIGHT(LBS./1000 FT.) 60■C 75■C 90■C
14/214/314/412/212/312/410/210/310/48/28/38/46/26/36/44/34/43/33/42/32/4
SOLIDSOLIDSOLIDSOLIDSOLIDSOLIDSOLIDSOLIDSOLID
STRANDEDSTRANDEDSTRANDEDSTRANDEDSTRANDEDSTRANDEDSTRANDEDSTRANDEDSTRANDEDSTRANDEDSTRANDEDSTRANDED
16 SOLID16 SOLID16 SOLID16 SOLID16 SOLID16 SOLID16 SOLID16 SOLID16 SOLID16 SOLID16 SOLID16 SOLID16 SOLID16 SOLID16 SOLID16 SOLID16 SOLID16 SOLID16 SOLID16 SOLID16 SOLID
.464
.484
.517
.498
.521
.557
.560
.588
.632
.686
.749
.810
.783
.827
.8961.0951.1501.1751.2441.1901.310
8610512610713416314218422821131138731842453562579774610038981155
151515202020303030404040555555707085859595
1515152020203030305050506565658585100100115115
1515152020203030305555557575759595110110130130
WEIGHTS AND MEASUREMENTS
234
STANDARD COLOR 120/208Y SPECIAL COLOR 277/480YBROWN, ORANGE, YELLOW, PURPLE, GREYBROWN, ORANGE, YELLOW, PURPLE, GREYBROWN, ORANGE, YELLOW, PURPLE, GREY
BLACK, WHITEBLACK, WHITE, REDBLACK, WHITE, RED, BLUE
# OF CONDUCTORS
Grounding Conductor is Green.
14/2 14/3 14/4 12/2 12/3 12/4 10/2 10/3 10/4 8/2 8/3 8/4 6/2 6/3 6/4 4/3 4/4 3/3 3/4 2/42/3250 FTCOIL
1000 FTREEL
+Ampacities are based on Table 310.16 of the NEC, 2005 Edition. +Allowable ampacities shown are for general use as specified by the National Electrical Code, 2005 Edition, Section 310.15. If the equipment is marked for use at highertemperatures, the conductor ampacity shall be limited to the following per NEC 110.14(C).60■C - When terminated to equipment for circuits rated 100 amperes or less or marked for size 14 through 1 AWG conductors.75■C - When terminated to equipment for circuits rated over 100 amperes or marked for conductors larger than size 1 AWG.90■C - For ampacity derating purposes.Per NEC 310.15(B)(2)(a), the ampacity of 4/C cables shall be reduced by a factor of 0.80 when the neutral is considered a current-carrying conductor.
PACKAGING
COLOR CODING
HOW ITÊS USEDÛ For certain applications:
- For branch, feeder, power, lighting, control, signal circuits and service power distribution in commercial,industrial, institutional and multi-residential buildings- Fished or embedded in plaster- For cable trays and approved raceways
Û For certain locations:- Environmental air-handling spaces, per NEC 300.22(C)- Under raised floors for information technology equipment conductors and cables, per NEC 645.5(D) and 645.5(D)(2)- For concealed or exposed installations
Duraclad®ACSTEEL ARMORED CABLE
HOW ITÊS MADEÛ Conductors: Type ACTHH (THHN/THWN-singles), soft-drawn copper, wrapped with a moisture-resistant,
flame-retardant paper covering and then aluminum armor is applied over the conductorsÛ A 16 AWG aluminum bond wire is placed inside the armor and runs longitudinally
HOW ITÊS CERTIFIEDÛ SouthwireÊs Duraclad® Type AC Cable meets or exceeds the requirements of UL Standard 4 for Armored Cable,
UL Standard 83, Federal Specification A-A59544 (formerly J-C-30B) and the National Electrical Code.SouthwireÊs Duraclad® Type AC is listed for use in UL 1, 2 and 3 Hour Through-Penetration Firestop Systems.
HOW ITÊS DEFINEDÛ An armor assembly (combination of the interlocked armor & bonding strip) that is recognized as an equipment
grounding conductor per NEC 250.118(8)Û Reduces installation costs up to 50% over pipe and wireÛ UL Classified 1, 2, and 3 hour Through Penetration Firestop Systems: W-J-3037, W-L-3110, W-L-3113,
W-L-3117, W-L-3120, W-L-3121, W-L-3160, C-AJ-3115, C-AJ-3140, C-AJ-3142, C-AJ-3145, C-AJ-3173,C-AJ-3202, C-AJ-4065, C-AJ-4066, F-C-3038
Û Anti-short/insulating bushings supplied with every reel or coilÛ When pulling from coils, pull from inside to ensure proper installation - For easier installation and pulling,
cable reverse
56
Û AC: Aluminum CableÛ 600 VoltsÛ For Dry Locations Only
METAL CLAD& CONDUIT
Dur
acl
ad
®A
CST
EEL
ARM
ORE
DC
ABL
E
57
CONDUCTORSIZE
(AWG)CONDUCTOR
TYPE
ALUMINUMBONDINGWIRE SIZE
(AWG)OUTSIDE
DIAMETER(INCHES)
ALUMINUM INTERLOCKED ARMOR AMPACITIES+ (AMPS)
WEIGHT(LBS./1000 FT.) 60■C 75■C 90■C
14/214/314/412/212/312/410/210/310/48/28/38/46/26/36/44/34/42/32/4
SOLIDSOLIDSOLIDSOLIDSOLIDSOLIDSOLIDSOLIDSOLID
STRANDEDSTRANDEDSTRANDEDSTRANDEDSTRANDEDSTRANDEDSTRANDEDSTRANDEDSTRANDEDSTRANDED
16 SOLID16 SOLID16 SOLID16 SOLID16 SOLID16 SOLID16 SOLID16 SOLID16 SOLID16 SOLID16 SOLID16 SOLID16 SOLID16 SOLID16 SOLID16 SOLID16 SOLID16 SOLID16 SOLID
.490
.520
.530
.520
.550
.575
.580
.615
.655
.695
.825
.850
.880
.870
.9501.1601.1401.3101.632
192219241217251290270314380354605678619739888976123111701555
15151520202030303040404055555570709595
1515152020203030305050506565658585115115
1515152020203030305555557575759595130130
WEIGHTS AND MEASUREMENTS
COLOR CODING
234
STANDARD COLOR 120/208Y SPECIAL COLOR 277/480YBROWN, ORANGE, YELLOW, PURPLE, GREYBROWN, ORANGE, YELLOW, PURPLE, GREYBROWN, ORANGE, YELLOW, PURPLE, GREY
BLACK, WHITEBLACK, WHITE, REDBLACK, WHITE, RED, BLUE
# OF CONDUCTORS
Grounding Conductor is Green.
14/2 14/3 14/4 12/2 12/3 12/4 10/2 10/3 10/4 8/2 8/3 8/4 6/2 6/3 6/4 4/3 4/4 3/3 3/4 2/42/3250 FTCOIL
1000 FTREEL
Note: Ampacities are based on Table 310.16 of the NEC, 2005 Edition.+Allowable ampacities shown are for general use as specified by the National Electrical Code, 2005 Edition, Section 310.15.If the equipment is marked for use at higher temperatures, the conductor ampacity shall be limited to the following per NEC 110.14(C).60■C - When terminated to equipment for circuits rated 100 amperes or less or marked for size 14 through 1 AWG conductors.75■C - When terminated to equipment for circuits rated over 100 amperes or marked for conductors larger than size 1 AWG.90■C - For ampacity derating purposes.Per NEC 310.15(B)(2)(a), the ampacity of 4/C cables shall be reduced by a factor of 0.80 when the neutral is considered a current-carrying conductor.
PACKAGING
HOW ITÊS MADEÛ Conductors: Type ACTHH (THHN/THWN-singles), soft-drawn copper, wrapped with a moisture-resistant,
flame-retardant paper covering, then lightweight, steel interlocking armor is applied over the conductors andhas a green insulated copper grounding conductor
Û A 16 AWG aluminum bond wire is placed inside the armor
HOW ITÊS CERTIFIEDÛ SouthwireÊs Duraclad® Type AC HCF meets or exceeds the requirements of UL Standard 4 for Armored Cable, UL
Standard 83, Federal Specification A-A59544 (formerly J-C-30B) and the National Electrical Code. SouthwireÊsDuraclad® Type AC HCF is listed for use in UL 1, 2 and 3 Hour Through-PenetrationFirestop Systems.
58
Û AC: Aluminum CableÛ HCF: Hospital CareFacility
Û 600 VoltsÛ For Dry Locations
HOW ITÊS USEDÛ For certain applications:
- For branch, feeder, power, lighting, control, signal circuits and service power distribution in commercial,industrial, institutional and multi-residential buildings
- For branch-circuit wiring, electrical systems in patient care areas of hospitals, nursing homes, dental offices,outpatient facilities and other medical or health related facilities- Fished or embedded in plaster- For cable trays and approved raceways
Û For certain locations:- For Dry Locations only- Environmental air-handling spaces, per NEC 300.22(C)- Under raised floors for information technology equipment conductors and cables, per NEC 645.5(D) and 645.5(D)(2)- For concealed or exposed installations- For hazardous anesthetizing areas and essential electrical system circuits are prohibited, except aspermitted, per 2005 NEC 517.30(C)(3)(3)
Duraclad®AC HCFSTEEL ARMORED CABLE
HOW ITÊS DEFINEDÛ An armor assembly (combination of the interlocked armor & bonding strip) that is recognized as an equipment
grounding conductor per 2005 NEC Articles 250.118(8) and 517.30(A)Û An insulated equipment grounding conductor per NEC 517.13(B) and Table 250.122Û Reduces installation costs up to 50% over pipe and wireÛ UL Classified 1, 2 and 3 hour Through Penetration Firestop Systems: W-J-3037, W-L-3110, W-L-3113,
W-L-3117, W-L-3120, W-L-3121, W-L-3160, C-AJ-3115, C-AJ-3140, C-AJ-3142, C-AJ-3145, C-AJ-3173,C-AJ-3202, C-AJ-4065, C-AJ-4066, F-C-3038
Û Anti-short/insulating bushings supplied with every reel or coilÛ When pulling from coils, pull from inside to ensure proper installation. For easier installation and pulling,
cable reverse wound on reel.
METAL CLAD& CONDUIT
59
Dur
acl
ad
®A
CH
CFST
EEL
ARM
ORE
DC
ABL
E
PHASECONDUCTOR
SIZE(AWG)
CONDUCTORTYPE
ALUMINUMBONDING WIRE
SIZE(AWG)
OUTSIDEDIAMETER(INCHES)
AMPACITIES+ (AMPS)STEEL INTERLOCKED ARMOR
WEIGHT(LBS./1000 FT.) 60■C 75■C 90■C
.520
.530
.570
.550
.575
.640
.615
.655
.725
224241294251291335314380449
151515202020303030
151515202020303030
151515202020303030
14/314/314/412/212/312/410/210/310/4
SOLIDSOLIDSOLIDSOLIDSOLIDSOLIDSOLIDSOLIDSOLID
16 SOLID16 SOLID16 SOLID16 SOLID16 SOLID16 SOLID16 SOLID16 SOLID16 SOLID
COLOR CODING
234
STANDARD COLOR 120/208Y SPECIAL COLOR 277/480YBROWN, ORANGE, YELLOW, PURPLE, GREYBROWN, ORANGE, YELLOW, PURPLE, GREYBROWN, ORANGE, YELLOW, PURPLE, GREY
BLACK, WHITEBLACK, WHITE, REDBLACK, WHITE, RED, BLUE
# OF CONDUCTORS
Grounding Conductor is Green.
12/214/2 14/3 14/4 12/3 12/4 10/2 10/3 10/4250 FTCOIL
1000 FTREEL
Note: Ampacities are based on Table 310.16 of the NEC, 2005 Edition.+Allowable ampacities shown are for general use as specified by the National Electrical Code, 2005 Edition, Section 310.15.If the equipment is marked for use at higher temperatures, the conductor ampacity shall be limited to the following per NEC 110.14(C).60■C - When terminated to equipment for circuits rated 100 amperes or less or marked for size 14 through 1 AWG conductors.75■C - When terminated to equipment for circuits rated over 100 amperes or marked for conductors larger than size 1 AWG.90■C - For ampacity derating purposes.Per NEC 310.15(B)(2)(a), the ampacity of 4/C cables shall be reduced by a factor of 0.80 when the neutral is considered a current-carrying conductor.
WEIGHTS AND MEASUREMENTS
PACKAGING
HOW ITÊS USEDÛ For certain applications:
- For branch, feeder, power, lighting, control, signal circuits and service power distribution in commercial,industrial, institutional and multi-residential buildings- For aerial cable on a messenger- For cable trays and approved raceways
Û For certain locations:- Environmental air-handling spaces, per NEC 300.22(C)- Under raised floors for information technology equipment conductors and cables, per NEC 645.5(D) and 645.5(D)(2)- For places of assembly and theaters, per NEC Articles 518 and 520- For concealed or exposed installations- Hazardous locations: Class 1 Div. 2, Class 2 Div. 2, and Class 3 Div.1
Armorlite®MCALUMINUM ARMORED CABLE
HOW ITÊS MADEÛ Conductors: Type THHN/THWN, soft-drawn copper that is available in sizes 14 AWG through 750 kcmil and is
rated 90■C dry/75■C wetÛ Has a green insulated grounding conductor until size is 1/0 AWG and larger, then it has a bare grounding conductorÛ Cables are combined using binder tape and an aluminum interlocking armor is placed over the cables
HOW ITÊS CERTIFIEDÛ SouthwireÊs Armorlite® Type MC meets or exceeds the requirements of UL Standard 83, UL Standard 1063,
UL Standard 1569 for Type MC, Federal Specification A-A59544 (formerly J-C-30B), IEEE 1202 (70,000 Btu/hr)Vertical Cable Tray Flame Test and the National Electrical Code. SouthwireÊs Armorlite® Type MC is listed foruse in UL 1, 2 and 3 Hour Through Penetration Firestop Systems.
60
Û MC: Metal CladÛ 600 VoltsÛ For Wet and Dry LocationsÛ 90■C Heat Capacity
METAL CLAD& CONDUIT
Arm
orlit
e®M
CA
LUM
INU
MA
RMO
RED
CA
BLE
61
CONDUCTORSIZE*(AWG)
CONDUCTORTYPE
GROUNDINGCONDUCTORSIZE (AWG)
AND STRANDING
OVERALLDIAMETER(INCHES)
WEIGHT(lbs./1000 ft.) 60■C 75■C 90■C
AMPACITIES+
14/214/314/412/212/312/312/312/412/410/210/210/310/310/410/48/28/38/4
SOLIDSOLIDSOLID
19SOLID
19SOLID
19SOLID
19SOLID
19SOLID
19SOLID
191919
14 SOLID14 SOLID14 SOLID
12-1912 SOLID
12-1912 SOLID
12-1912 SOLID
10-1910 SOLID
10-1910 SOLID
10-1910 SOLID
10-1910-1910-19
.439
.464
.494
.494
.475
.527
.505564.539.566.542.607.58.653.623.678.678.732
7794112110104137129164155159150201189243229234298370
151515202020202020303030303030404040
151515202020202020303030303030505050
151515202020202020303030303030555555
14/2 14/3 14/4 12/2 12/3 12/4 10/2 10/3 10/4 8/2 8/3100 FTCOIL
125 FTCOIL
200 FTCOIL
250 FTCOIL
500 FTREEL
750 FTREEL
1000 FTREEL
234
STANDARD COLORS 120/208Y OPTIONAL COLORS 277/480YBROWN, ORANGE, YELLOW, PURPLE, GREYBROWN, ORANGE, YELLOW, PURPLE, GREYBROWN, ORANGE, YELLOW, PURPLE, GREY
BLACK, WHITEBLACK, WHITE, REDBLACK, WHITE, RED, BLUE
# OF CONDUCTORS
Grounding Conductor is Green.+Ampacities are based on Table 310.16 of the NEC, 2005 Edition. +Allowable ampacities shown are for general use as specified by the National Electrical Code, 2005 Edition, Section 310.15. If the equipment ismarked for use at higher temperatures, the conductor ampacity shall be limited to the following per NEC 110.14(C). 60■C - When terminated to equipment for circuits rated 100 amperes or less or marked for size14 through 1 AWG conductors. 75■C - When terminated to equipment for circuits rated over 100 amperes or marked for conductors larger than size 1 AWG. 90■C - For ampacity derating purposes.Per NEC 310.15(B)(2)(a), the ampacity of 4/C cables shall be reduced by a factor of 0.80 when the neutral is considered a current-carrying conductor. * Available in sizes up to 750 kcmil.
WEIGHTS AND MEASUREMENTS
PACKAGING
COLOR CODING
HOW ITÊS USEDÛ For certain applications:
- For branch, feeder, power, lighting, control, signal circuits and service power distribution in commercial,industrial, institutional and multi-residential buildings
- For aerial cable on a messenger- For cable trays and approved raceways
Û For certain locations:- For concealed or exposed installations- Environmental air-handling spaces, per NEC 300.22(C)- Under raised floors for information technology equipment conductors and cables, per NEC 645.5(D) and 645.5(D)(2)- For places of assembly and theaters, per NEC Articles 518 and 520- For concealed or exposed installations- Hazardous locations: Class 1 Div. 2, Class 2 Div. 2, and Class 3 Div.1
Duraclad®MCSTEEL ARMORED CABLE
HOW ITÊS MADEÛ Conductors: Type THHN/THWN (insulated singles), soft-drawn copper that is available in sizes 14 AWG through
750 kcmil and is rated 90■C dry/75■C wetÛ Has a green insulated grounding conductor until size is 1/0 AWG and larger, then it has a bare grounding conductorÛ Cables are combined using binder tape and an aluminum interlocking armor is placed over the cables
HOW ITÊS CERTIFIEDÛ SouthwireÊs Duraclad® Type MC meets or exceeds the requirements of UL Standard 83, UL Standard 1063,
UL Standard 1569 for Type MC, Federal Specification A-A59544 (formerly J-C-30B), IEEE 1202 (70,000 Btu/hr)Vertical Cable Tray Flame Test and the National Electrical Code. SouthwireÊs Duraclad® Type MC is listed for usein UL 1, 2 and 3 Hour Through-Penetration Firestop Systems.
62
Û MC: Metal CladÛ 600 VoltsÛ For Wet and Dry
LocationsÛ 90■C Heat Capacity
METAL CLAD& CONDUIT
Dur
acl
ad
®M
CST
EEL
ARM
ORE
DC
ABL
E
63
CONDUCTORSIZE +(AWG)
CONDUCTORTYPE
GROUNDINGCONDUCTORSIZE (AWG)
OVERALLDIAMETER(INCHES)
WEIGHT(LBS./1000 FT.) 60■C 75■C 90■C
AMPACITIES+
14/214/314/412/212/312/410/210/310/4
SOLIDSOLIDSOLIDSOLIDSOLIDSOLIDSOLIDSOLIDSOLID
141414121212101010
0.4470.4720.5020.4750.5130.5470.5500.5880.631
115134155142172201197240284
151515202020303030
151515202020303030
151515202020303030
14/2 14/3 14/4 12/2 12/3 12/4 10/2 10/3 10/4250 FTCOIL
1000 FTREEL
234
STANDARD COLORS 120/208Y OPTIONAL COLORS 277/480YBROWN, ORANGE, YELLOW, PURPLE, GREYBROWN, ORANGE, YELLOW, PURPLE, GREYBROWN, ORANGE, YELLOW, PURPLE, GREY
BLACK, WHITEBLACK, WHITE, REDBLACK, WHITE, RED, BLUE
# OF CONDUCTORS
Grounding Conductor is Green.+Ampacities are based on Table 310.16 of the NEC, 2005 Edition. ÚAllowable ampacities shown are for general use as specified by the National Electrical Code, 2005 Edition, Section 310.15. If the equipment ismarked for use at higher temperatures, the conductor ampacity shall be limited to the following per NEC 110.14(C). 60■C - When terminated to equipment for circuits rated 100 amperes or less or marked for size14 through 1 AWG conductors. 75■C - When terminated to equipment for circuits rated over 100 amperes or marked for cÚAllowable ampacities shown are for general use as specified by the National ElectricalCode, 2005 Edition, Section 310.15. If the equipment is marked for use at higher temperatures, the conductor ampacity shall be limited to the following per NEC 110.14(C). 60■C - When terminated to equipmentfor circuits rated 100 amperes or less or marked for size 14 through 1 AWG conductors. 75■C - When terminated to equipment for circuits rated over 100 amperes or marked for conductors larger than size 1 AWG.90■C - For ampacity derating purposes. Per NEC 310.15(B)(2)(a), the ampacity of 4/C cables shall be reduced by a factor of 0.80 when the neutral is considered a current-carrying conductor. *Circuit sizes 12 AWGand 10 AWG also available as stranded conductors.onductors larger than size 1 AWG. 90■C - For ampacity derating purposes. Per NEC 310.15(B)(2)(a), the ampacity of 4/C cables shall be reduced by a factor of0.80 when the neutral is considered a current-carrying conductor. + Available in sizes up to 750 kcmil.
WEIGHTS AND MEASUREMENTS
PACKAGING
COLOR CODING
HOW ITÊS MADEÛ Conductors: Type THHN/THWN, soft-drawn copper, has a green insulated grounding conductor and is rated
90■C dry/75■C wetÛ Cables are combined using binder tape and an aluminum interlocking armor is placed over the cablesÛ Black, flame-retardant PVC jacket is applied over the armor and is available in blue or grey, colors requested
subject to economic order quantities
HOW ITÊS DEFINEDÛ Reduces installation costs up to 50% over pipe and wireÛ Lightweight aluminum armor as much as 45% lighter than steel MC CableÛ UL Classified 1, 2 and 3 Hour Through-Penetration Firestop Systems: W-J-3037, W-L-3110, W-L-3113,
W-L-3117, W-L-3120, W-L-3121, W-L-3160, C-AJ-3115, C-AJ-3140, C-AJ-3142, C-AJ-3145, C-AJ-3173,C-AJ-3202, C-AJ-4065, C-AJ-4066, F-C-3038
HOW ITÊS CERTIFIEDÛ SouthwireÊs Armorlite® Feeder Type MC Cable (PVC Jacketed) meets or exceeds the requirements of UL
Standard 83, UL Standard 1063, UL Standard 1569 for Type MC, Federal Specification A-A59544(formerly J-C-30B), IEEE 1202 (70,000 BTU/hr) Vertical Cable Tray Flame Test and the National Electrical Code.SouthwireÊs Armorlite® Feeder Type MC (PVC Jacketed) is listed for use in UL Standard 1479 1, 2 and 3 HourThrough-Penetration Firestop Systems.
64
Û MC: Metal CladÛ 600 VoltsÛ Copper Power FeederConductors
HOW ITÊS USEDÛ For certain applications:
- For branch, feeder, power, lighting, control, signal circuits and service power distribution in commercial,industrial, institutional and multi-residential buildings
- Fished or embedded in plaster- For aerial cable on a messenger- For cable trays and approved raceways
Û For certain locations:- Environmental air-handling spaces, per NEC 300.22(C)- Under raised floors for information technology equipment conductors and cables, per NEC 645.5(D) and 645.5(D)(2)- For places of assembly and theaters, per NEC Articles 518 and 520- For concealed or exposed installations- Hazardous locations: Class 1 Div. 2, Class 2 Div. 2 and Class 3 Div. 1
Armorlite® Feeder MCALUMINUM ARMORED CABLE
?DID YOU KNOWSouthwireÊs Feeder MC was used inthe construction of Las VegasÊ veryown Wynn Resort and Casino.
METAL CLAD& CONDUIT
1-BLACK, 2-RED, 3-BLUE, WHITE1-BLACK, 2-RED, WHITE
65
CONDUCTOR SIZE/# OF COND.(AWG/kcmil)
GROUNDINGCONDUCTOR
(AWG)†
APPROXIMATEDIAMETER
OVER ARMOR(INCHES)
APPROXIMATEDIAMETER
OVER JACKET(INCHES)
AMPACITY+ (AMPS)
1/31/4
1/0-31/0-42/0-32/0-43/0-33/0-44/0-34/0-4250-3250-4350-3350-4500-3500-4600-3600-4750-3750-4
6 Green6 Green6 Bare6 Bare6 Bare6 Bare4 Bare4 Bare4 Bare4 Bare4 Bare4 Bare3 Bare3 Bare2 Bare2 Bare2 Bare2 Bare1 Bare1 Bare
1.2031.3511.2451.3621.3391.4911.4491.6141.5701.7491.7371.9131.9602.1622.2382.4772.4692.7142.6742.960
1.3034.4511.3421.4621.4391.5911.5491.7341.6901.8691.8572.0332.0802.2822.3582.6272.6192.8822.8243.110
1252158514631863175823322175289426623507317840864252549358297642707892818537
11,111
130130150150175175200200230230255255310310380380420420475475
150150170170195195225225260260290290350350430430475475535535
Arm
orlite®
Feed
erMC
ALU
MIN
UM
ARM
ORE
DC
ABL
E34
COLOR SEQUENCE 120/208Y*# OF CONDUCTORS
Grounding Conductor is Bare.
75■C 90■CWEIGHT
(LBS./1000 FT.)
Note: Ampacities are based on Table 310.16 of the NEC, 2005 Edition.+Allowable ampacities shown are for general use as specified by the National Electrical Code, 2005 Edition, Section 310.15.If the equipment is marked for use at higher temperatures, the conductor ampacity shall be limited to the following per NEC 110.14(C).75■C - When terminated to equipment for circuits rated over 100 amperes or marked for conductors larger than size 1 AWG.90■C - For ampacity derating purposes.Per NEC 310.15(B)(2)(a), the ampacity of 4/C cables shall be reduced by a factor of 0.80 when the neutral is considered a current-carrying conductor.Available with oversized grounding conductor when used for parallel feeds on special orders.
*Color sequence for 277V/480V systems and other special colors are available subject to economic order quantity.Note: Phase conductors are black with printed ID.
WEIGHTS AND MEASUREMENTS
COLOR CODING*
HOW ITÊS MADEÛ Conductors: Type THHN/THWN, solid soft-drawn copper that is available in sizes 14 AWG – 10 AWG, has a bare
aluminum, grounding conductor and is rated 90■C dryÛ Cables are combined using binder tape and a lightweight aluminum interlocking armor is placed over the cablesÛ The bare aluminum, grounding conductor is located outside of the binding tape and has the same lay as the
insulated conductors.
HOW ITÊS DEFINEDÛ An armor assembly that is an equipment grounding conductor per 2005 NEC 250.118(10)(a)Û Installation instructions included with every reel and coil.Û Simplified product application and installation compared to other armored productsÛ Faster conductor make-up, wiring device installation and trim-out when grounding/bonding conductor is
terminated per installation instructionsÛ Reduces installation costs up to 50% over pipe and wireÛ UL Classified 1, 2 and 3 hour Through Penetration Firestop Systems: W-J-3037, W-L-3110, W-L-3113, W-L-3117,
W-L-3120, W-L-3121, W-L-3160, C-AJ-3115, C-AJ-3140, C-AJ-3142, C-AJ-3145, C-AJ-3173, C-AJ-3202, C-AJ-4065,C-AJ-4066, F-C-3038
Û When pulling from coils, pull from inside to ensure ease of installation. For easier installation and pulling,cable is reverse wound on reel.
HOW ITÊS CERTIFIEDÛ SouthwireÊs Armorlite Type MCAP™ meets or exceeds the applicable requirements of UL 1569 Standard for Metal-Clad
Cables, NFPA 70 National Electrical Code, UL 83 Standard, UL 1063 Standard, Federal Specification A-A59544(formerly J-C-30B) and IEEE 1202 (70,000 Btu/hr) Vertical Cable Tray Flame Test. SouthwireÊs Armorlite Type MCAP™
is listed for use in UL 1, 2 and 3 Hour Through-Penetration Firestop Systems.
66
Û MCAP: Metal-CladAll-Purpose
Û 600 Volts
HOW ITÊS USEDÛ For certain applications:
- For branch, feeder, power, lighting, control, signal circuits and service power distribution in commercial,industrial, institutional and multi-residential buildings- Fished or embedded in plaster- For cable trays and approved raceways
Û For certain locations:- Environmental air-handling spaces, per NEC 300.22(C)- Under raised floors for information technology equipment conductors and cables, per NEC 645.5(D) and 645.5(D)(2)- For places of assembly and theaters, per NEC Articles 518 and 520- For concealed or exposed installations- For areas where standard AC or MC cable is permitted
MCAP ®
ALL-PURPOSE METAL CLAD
EquipmentGroundingConductor
METAL CLAD& CONDUIT
67
CONDUCTORSIZE (AWG) / #
OF PHASECONDUCTORS
CONDUCTORTYPE
GROUNDING/BONDING
CONDUCTOR
OVERALLDIAMETER(INCHES)
WEIGHT(LBS./1000FT.)
AMPACITY (AMPS)
14/214/314/412/212/312/410/210/3
SOLIDSOLIDSOLIDSOLIDSOLIDSOLIDSOLIDSOLID
12 SOLID AL12 SOLID AL12 SOLID AL10 SOLID AL10 SOLID AL10 SOLID AL8 SOLID AL8 SOLID AL
0.3850.4100.4350.4300.4450.4800.4850.520
63789688110134123162
1515152020203030
1515152020203030
1515152020203030
MCA
P®
ALL
-PU
RPO
SEM
ETA
LC
LAD2
34
STANDARD COLORS 120/208Y OPTIONAL COLORS 277/480YBROWN, ORANGE, YELLOW, PURPLE, GREYBROWN, ORANGE, YELLOW, PURPLE, GREYBROWN, ORANGE, YELLOW, PURPLE, GREY
BLACK, WHITEBLACK, WHITE, REDBLACK, WHITE, RED, BLUE
# OF CONDUCTORS
Grounding Conductor is Green.
60■C 75■C 90■C
14/414/2 14/3 12/2 12/3 12/4 10/2 10/3250 FT.COIL
1000 FT.REEL
WEIGHTS AND MEASUREMENTS
COLOR CODING
PACKAGING
HOW ITÊS USEDÛ For certain applications:
- For branch-circuit wiring, electrical systems in patient care areas of hospitals, nursing homes, dental offices,outpatient facilities and other medical or health related facilities- Fished or embedded in plaster- For cable trays and approved raceways- Applications require redundant, dedicated or isolated grounding paths
Û For certain locations:- Environmental air-handling spaces, per NEC 300.22(C)- Under raised floors for information technology equipment conductors and cables, per NEC 645.5(D) and 645.5(D)(2)- For places of assembly and theaters, per NEC Articles 518 and 520- Prohibited in hazardous anesthetizing areas and electrical system circuits, except where permitted,per 2005 NEC 517.30(C)(3)(3)
HOW ITÊS MADEÛ Conductors: Type THHN/THWN, solid soft-drawn copper that is available in sizes 12 AWG – 10 AWG and is rated 90■C dryÛ It has a green, insulated, copper ground wire and a bare aluminum, grounding conductorÛ Insulated cables are combined using binder tape and a green lightweight aluminum interlocking armor is
placed over the cablesÛ The bare aluminum, grounding conductor is located outside of the binding tape and has the same lay as the
insulated conductors
HOW ITÊS CERTIFIEDÛ SouthwireÊs Armorlite® HCF Type MCAP™meets or exceeds the requirements of UL 1569 Standard for Metal-Clad
Cables, NFPA 70 National Electrical Code, UL 83 Standard, UL 1063 Standard, Federal Specification A-A59544(formerly-C-30B) and IEEE 1202 (70,000 Btu/hr) Vertical Cable Tray Flame Test. SouthwireÊs Armorlite® HCFType MCAP™ is listed for use in UL 1, 2 and 3 Hour Through-Penetration Firestop Systems.
HOW ITÊS DEFINEDÛ An armor assembly that is an equipment grounding conductor per 2005 NEC 250.118(10)(A)Û Installation instructions included with every reel and coilÛ 350% better redundant ground path over traditional Type AC HCF cableÛ Reduces installation costs up to 50% over pipe and wireÛ Increased labor savings compared to Type AC HCFÛ UL Classified 1, 2, and 3 hour Through Penetration Firestop Systems: W-J-3037, W-L-3110, W-L-3113,
W-L-3117, W-L-3120, W-L-3121, W-L-3160, C-AJ-3115, C-AJ-3140, C-AJ-3142, C-AJ-3145, C-AJ-3173,C-AJ-3202, C-AJ-4065, C-AJ-4066, F-C-3038
Û When pulling from coils, pull from inside to ensure ease of installation. For easier installation and pulling cablereverse wound on reel.
68
Û MCAP: Metal Clad AllPurpose
Û HCF: Hospital CareFacility
Û 600 Volts
MCAP ®HCFALL-PURPOSE METAL CLAD
EquipmentGroundingConductor
METAL CLAD& CONDUIT
69
MCA
P®H
CFA
LL-P
URP
OSE
MET
AL
CLA
D
CONDUCTORSIZE (AWG)/#OF PHASE
CONDUCTORS
CONDUCTORTYPE
GROUNDINGBONDING
CONDUCTOR
GREEN THHNCOPPERGROUND(AWG)
AMPACITIES (AMPS)OVERALLDIAMETER(INCHES) 60■C 75■C 90■C
12/212/312/410/210/310/4
SOLIDSOLIDSOLIDSOLIDSOLIDSOLID
10 SOLID AL10 SOLID AL10 SOLID AL10 SOLID AL10 SOLID AL10 SOLID AL
121212101010
.445
.480
.515
.520
.565
.670
202020303030
202020303030
202020303030
COLOR CODING
234
STANDARD COLOR 120/208Y SPECIAL COLOR 277/480YBROWN, ORANGE, YELLOW, PURPLE, GREYBROWN, ORANGE, YELLOW, PURPLE, GREYBROWN, ORANGE, YELLOW, PURPLE, GREY
BLACK, WHITEBLACK, WHITE, REDBLACK, WHITE, RED, BLUE
# OF CONDUCTORS
Grounding Conductor is Green.
PACKAGING12/2 12/3 12/4 10/2 10/3 10/4
250 FTCOIL
1000 FTREEL
WEIGHTS AND MEASUREMENTS
HOW ITÊS MADEÛ Spiral wound strip of corrosion-resistant, hot-dipped galvanized steelÛ Steel has a heavy zinc coating
70
Û Data Flex: FlexibleMetal Conduit
Û Crush/Corrosion ResistantÛ Smooth Interior for Easy
Pulling
HOW ITÊS USEDÛ For concealed, exposed or approved racewaysÛ For use where listed products are not required
Data Flex®
FLEXIBLE METAL CONDUIT
METAL CLAD& CONDUIT
71
SIZE(INCHES)
APPROXIMATEWEIGHT
(LBS/100 FT)
INNER DIAMETERMIN./MAX.(INCHES)
OUTER DIAMETERMIN./MAX.(INCHES)
44568101215182124
3/81/23/41
1-1/41-1/2
22-1/2
33-1/2
4
1219.523.530376693150190220264
.585
.8751.0751.3401.5901.9002.4002.9603.4603.9604.460
Da
taFl
ex®
FLEX
IBLE
MET
AL
CO
ND
UIT
3/45/16 3/8 1/2 1 1-1/4 1-1/2 2 2-1/2 3 3-1/2 4
250FTCOIL
25FTCOIL50FTCOIL100FTCOIL
WEIGHTS AND MEASUREMENTS
PACKAGING
HOW ITÊS MADEÛ Lightweight, high strength aluminum alloyÛ Metal strip, helically formed, making continuously interlocked flexible metal conduit
HOW ITÊS CERTIFIEDÛ UL Listed per UL 1, Standard for Safety for Flexible Metal Conduit, ANSI/UL-1Û CSA Listed per CSA 22.2 No. 56 per Canadian Electrical Code C22.1 Section 12-1000 for 5/16" and 3/8"
trade sizes onlyÛ Meets federal specification WW-C-566cÛ NEC Type Designation - Article 348, Type FMC (flexible metal conduit)
72
Û RWA: Reduced WallAluminum
Û Highly FlexibleÛ 66% Lighter than SteelÛ Cuts 80% Faster than SteelÛ Corrosion and Crush
ResistantÛ Smooth Metal Interior for
Easy Wiring
HOW ITÊS USEDÛ For certain applications:
- For power and lighting branch circuit conductors and cables such as: receptacles, equipment and officepartitions, etc.- For voice, data, communications, video, CATV and optical fiber cables- For motor feeders, branch, control circuits and cables- For use with listed connectors for NEC type FMC (Flexible Metal Conduit)- Listed wire fixtures, per NEC 410.77(C)- Elevators and escalators, per NEC 620.21- Cranes and hoists, per NEC 610.11(C)- Electric signs and outline lighting supply and secondary circuit, per NEC 600.31 (1000 Volts or less) &NEC 600.32 (over 1000 Volts)- Metal raceway, per NEC (ANSI/NFPA-70) Article 348- Fire alarm systems of power-limited or non-power-limited fire alarm circuits- As a grounding conductor for lengths up to 6 feet, per 2005 NEC 205.118(5)- Class 1, Class 2 and Class 3 Remote-control, signaling and power-limited circuit conductors and cables- UL 1, 2 & 3 Hour Through-Penetration Firestop Systems: C-AJ-1462, C-AJ-1463 and C-AJ-1464 as well asW-L-1308 and W-L-1309
Û For certain locations:- For exposed or concealed locations, per NEC Article 348 and the applicable NEC provisions- Under raised floors for information technology, per NEC 645.5(D) and 645.5(D)(2)- For places of assembly and theaters, per NEC Articles 518 and 520- Hazardous locations: Class 1 Div. 2, for flexible conductors only, per 2005 NEC 501.10(B)(2) & 501.30(B)
Û For certain conditions:- For environmental air-handling spaces, per NEC 300.22(C)
Alflex®RWAFLEXIBLE METAL CONDUIT
METAL CLAD& CONDUIT
73
SIZE(INCHES)
APPROXIMATEWEIGHT
(LBS/100 FT)
INNER DIAMETERMIN./MAX.(INCHES)
OUTER DIAMETERMIN./MAX.(INCHES)
0.470 / 0.5100.560 / 0.6100.860 / 0.9201.045 / 1.1051.300 / 1.3801.550 / 1.6301.850 / 1.9502.350 / 2.4502.860 / 3.0603.360 / 3.5603.860 / 4.0604.360 / 4.560
3.546810
12.5152025303540
5/163/81/23/41
1-1/41-1/2
22-1/2
33-1/2
4
5.579
12.52532467092107125142
0.312/-0.375 / 0.3930.625 / 0.6450.812 / 0.8351.0000 / 1.0401.250 / 1.3001.500 / 1.5752.000 / 2.080
2.500 / -3.000 / -3.500 / -4.000 / -
Alflex
®RW
AFL
EXIB
LEM
ETA
LC
ON
DU
IT
MINIMUMBENDINGRADIUS
(INCHES)
PACKAGING3/45/16 3/8 1/2 1 1-1/4 1-1/2 2 2-1/2 3 3-1/2 4
250 FTCOIL
25 FTCOIL50 FTCOIL
100 FTCOIL
WEIGHTS AND MEASUREMENTS
HOW ITÊS MADEÛ Galvanized, corrosion resistant, high strength steel alloyÛ Metal strip, helically formed, making continuously interlocked flexible metal conduitÛ Built in flexibility for simplified positioningÛ Provides mechanical protection for conductors and cablesÛ For use with listed connectors intended for NEC Type FMC (Flexible Metal Conduit)
HOW ITÊS CERTIFIEDÛ UL Listed per UL 1, Standard for Safety for Flexible Metal Conduit, ANSI/UL-1 for 5/16" through 3‰Û CSA Listed for 5/16‰ and 3/8‰ sizesÛ Meets federal specification WW-C-566cÛ NEC Type Designation - Article 348, Type FMC (flexible metal conduit)
74
Û RWS: Reduced WallSteel
Û Highly FlexibleÛ High Strength Steel
ConstructionÛ Hot-Dipped, Heavy Zinc
CoatingÛ Corrosion and Crush
ResistantÛ Smooth Metal Interior for
Easy Wiring
HOW ITÊS USEDÛ For certain applications:
- For power and lighting branch circuit conductors and cables such as: receptacles, equipment and officepartitions, etc.- For voice, data, communications, video, CATV and optical fiber cables- For motor feeders, branch, control circuits and cables- For use with listed connectors for NEC type FMC (Flexible Metal Conduit)- Listed wire fixtures, per NEC 410.77(C)- Elevators and escalators, per NEC 620.21- Cranes and hoists, per NEC 610.11(C)- Electric signs and outline lighting supply and secondary circuit, per NEC 600.31 (1000 Volts or less) &NEC 600.32 (over 1000 Volts)- Metal raceway, per NEC (ANSI/NFPA-70) Article 348- Fire alarm systems of power-limited or non-power-limited fire alarm circuits- As a grounding conductor for lengths up to 6 feet, per 2005 NEC 205.118(5)- Class 1, Class 2 and Class 3 Remote-control, signaling and power-limited circuit conductors and cables- UL 1, 2 & 3 Hour Through-Penetration Firestop Systems: C-AJ-1462, C-AJ-1463 and C-AJ-1464 as wellas W-L-1308 and W-L-1309
Û For certain locations:- For exposed or concealed locations, per NEC Article 348 and the applicable NEC provisions- Under raised floors for information technology, per NEC 645.5(D) and 645.5(D)(2)- For places of assembly and theaters, per NEC Articles 518 and 520- Hazardous locations: Class 1 Div. 2, for flexible conductors only, per 2005 NEC 501.10(B)(2) & 501.30(B)
Û For certain conditions:- For environmental air-handling spaces, per NEC 300.22(C)
Galflex®RWSFLEXIBLE METAL CONDUIT
METAL CLAD& CONDUIT
75
SIZE(INCHES)
APPROXIMATEWEIGHT
(LBS/100 FT)
INNER DIAMETERMIN./MAX.(INCHES)
OUTER DIAMETERMIN./MAX.(INCHES)
0.470 / 0.5100.560 / 0.6100.860 / 0.9201.045 / 1.1051.300 / 1.3801.550 / 1.6301.850 / 1.9502.350 / 2.4502.860 / 3.0603.360 / 3.5603.860 / 4.0604.360 / 4.560
3.544568101215182124
5/163/81/23/41
1-1/41-1/2
22-1/2
33-1/2
4
161827
34.5576878133165197231264
0.312/-0.375 / 0.3930.625 / 0.6450.812 / 0.8351.000 / 1.0401.250 / 1.3001.500 / 1.5752.000 / 2.080
2.500 / -3.000 / -3.500 / -4.000 / -
Galflex
®RW
SFL
EXIB
LEM
ETA
LC
ON
DU
IT
MINIMUMBENDINGRADIUS
(INCHES)
PACKAGING3/45/16 3/8 1/2 1 1-1/4 1-1/2 2 2-1/2 3 3-1/2 4
250 FTCOIL
25 FTCOIL50 FTCOIL
100 FTCOIL
WEIGHTS AND MEASUREMENTS
HOW ITÊS MADEÛ Spiral wound strip of corrosion-resistant, hot dipped galvanized steelÛ Steel has a heavy zinc coatingÛ Superior crush resistant sheilding for floor, wall and ceiling cables
HOW ITÊS CERTIFIEDÛ UL Component Recognized.
76
Û Slinky Flex: ExtraFlexible Metal Conduit
Û Crush/Corrosion ResistantÛ Smooth Interior for Easy
Pulling
HOW ITÊS USEDÛ For office partition furniture, voice, data, CATV, signal transmissions, and other OEM applicationsÛ For concealed, exposed or approved racewaysÛ For applications where extra flexibility is needed
Slinky Flex®
EXTRA FLEXIBLE METAL CONDUIT
77
SIZE(INCHES)
APPROXIMATEWEIGHT
(LBS/100 FT)
INNER DIAMETERMIN./MAX.(INCHES)
OUTER DIAMETERMIN./MAX.(INCHES)
0.447 / 0.4720.515 / 0.5400.585 / 0.6100.640 / 0.6650.703 / 0.7280.890 / 0.915
APPROX. BENDRADIUS(INCHES)
1.51.75
24
4.55
5/163/87/161/29/163/4
12.514.5171921
27.5
0.312 / 0.3370.375 / 0.4000.437 / 0.4620.500 / 0.5250.563 / 0.5880.750 / 0.775
Slin
ky
Flex
®
EXTR
AFL
EXIB
LEM
ETA
LC
ON
DU
IT1/2‰, 3/4‰ conduit minimum bend radius based on NEC Chapter 9.
PACKAGING1/25/16 3/8 7/16 9/16 3/4
250FTCOIL
1000FTCOIL
50FTCOIL100FTCOIL
METAL CLAD& CONDUIT
WEIGHTS AND MEASUREMENTS
77
Slin
ky
Flex
®
EXTR
AFL
EXIB
LEM
ETA
LC
ON
DU
IT
HOW ITÊS MADEÛ Lightweight, high strength aluminum alloyÛ Metal strip, helically formed, making continuously interlocked flexible metal conduit
HOW ITÊS CERTIFIEDÛ UL Listed per UL 1, Standard for Safety for Flexible Metal Conduit, ANSI/UL-1Û CSA Listed per CSA 22.2 No. 56 per Canadian Electrical Code C22.1 Section 12-1000 for 5/16" and 3/8"trade sizes only
Û Meets federal specification WW-C-566cÛ NEC Type Designation - Article 348, Type FMC (flexible metal conduit)
78
Û SWA: Standard WallAluminum
Û Highly FlexibleÛ 66% Lighter than SteelÛ Cuts 80% Faster than SteelÛ Corrosion and Crush
ResistantÛ Smooth Metal Interior for
Easy Wiring
HOW ITÊS USEDÛ For certain applications:
- For power and lighting branch circuit conductors and cables such as: receptacles, equipment and officepartitions, etc.- For voice, data, communications, video, CATV and optical fiber cables- For motor feeders, branch, control circuits and cables- For use with listed connectors for NEC type FMC (Flexible Metal Conduit)- Listed wire fixtures, per NEC 410.77(C)- Elevators and escalators, per NEC 620.21- Cranes and hoists, per NEC 610.11(C)- Electric signs and outline lighting supply and secondary circuit, per NEC 600.31 (1000 Volts or less) &NEC 600.32 (over 1000 Volts)- Metal raceway, per NEC (ANSI/NFPA-70) Article 348- Fire alarm systems of power-limited or non-power-limited fire alarm circuits- As a grounding conductor for lengths up to 6 feet, per 2005 NEC 205.118(5)- Class 1, Class 2 and Class 3 Remote-control, signaling and power-limited circuit conductors and cables- UL 1, 2 & 3 Hour Through-Penetration Firestop Systems: C-AJ-1462, C-AJ-1463 and C-AJ-1464 as well as W-L-1308andW-L-1309
Û For certain locations:- For exposed or concealed locations, per NEC Article 348 and the applicable NEC provisions- Under raised floors for information technology, per NEC 645.5(D) and 645.5(D)(2)- For places of assembly and theaters, per NEC Articles 518 and 520- Hazardous locations: Class 1 Div. 2, for flexible conductors only, per 2005 NEC 501.10(B)(2) & 501.30(B)
Û For certain conditions:- For environmental air-handling spaces, per NEC 300.22(C)
Alflex®SWAFLEXIBLE METAL CONDUIT
METAL CLAD& CONDUIT
79
SIZE(INCHES)
APPROXIMATEWEIGHT
(LBS/100 FT)
INNER DIAMETERMIN./MAX.(INCHES)
OUTER DIAMETERMIN./MAX.(INCHES)
0.470 / 0.5100.560 / 0.6100.860 / 0.9201.045 / 1.1051.300 / 1.3801.550 / 1.6301.850 / 1.9502.350 / 2.4502.860 / 3.0603.360 / 3.5603.860 / 4.0604.360 / 4.560
3.544568101215182124
5/163/81/23/41
1-1/41-1/2
22-1/2
33-1/2
4
5.5715204049567092107125142
0.312/-0.375 / 0.3930.625 / 0.6450.812 / 0.8351.000 / 1.0401.250 / 1.3001.500 / 1.5752.000 / 2.080
2.500 / -3.000 / -3.500 / -4.000 / -
Alflex
®SW
AFL
EXIB
LEM
ETA
LC
ON
DU
IT
MINIMUMBENDINGRADIUS(INCHES)
3/45/16 3/8 1/2 1 1-1/4 1-1/2 2 2-1/2 3 3-1/2 4
250FTCOIL
25FTCOIL50FTCOIL100FTCOIL
WEIGHTS AND MEASUREMENTS
PACKAGING
HOW ITÊS MADEÛ Spiral wound strip of heavy gauge, corrosion-resistant, hot-dipped galvanized steelÛ For 3/8‰ through 1-1/4‰ sizes, the core has a square, locked, steel strip with a copper bonding strip enclosedwithin the steel convolutions
Û Jacket: Rugged, flame retardant, flexible, UV sunlight resistant, gray, PVC jacketÛ Other jacket colors are available; however, the blue color easily identifies raceways for uninterrupted computer power circuitsÛ Protects against liquids, alcohol, coolants, corrosive fumes and gases, dirt, grease, mineral acids, salt, air,alkalines, oil, certain chemicals, temperatures, sunlight and weather.
HOW ITÊS CERTIFIEDÛ CSA Listed to CSA 22.2 No.56 for use per the Canadian Electrical Code C22.1 Section 12-1300.Û UL Listed to Underwriters Laboratories Standard ANSI / UL-360 for Liquidtight Flexible Steel Conduit.Û NEC Type designation - Type LFMC (Liquidtight Flexible Metal Conduit).Û ANSI / NFPA-70, NEC Article 350.
80
Û CB: Computer BlueÛ Rated -30■C to 80■CÛ Crush/Corrosion, Oil and
Sunlight ResistantÛ Accepts Standard Metallic
Liquidtight FittingsÛ Rated for Direct BurialÛ Smooth Metal Interior for
Easy Pulling
HOW ITÊS USEDÛ For certain conditions:
- For extreme oil and solvent environments- Where conditions of installation, operation or maintenance require flexibility and/or protection fromliquids, vapors, solids or weather- For the installation and protection of electrical conductors in circuits or 600 Volts or less- For equipment grounding in sizes 3/8‰ through 1-1/4‰ in lengths not exceeding 6 feet, per NEC 250.118(6)
Û For certain locations:- For exposed or concealed locations- Under raised floors in data processing areas per NEC 645.5(D) and 645.5(D)(2)- Service entrances, up to 6 feet in length per NEC 230.43 (15)- Hazardous locations: where necessary for flexible connections, in accordance with the following:•Class 1, Div. 2 - NEC 501.10(B)(2) & 501.30(B)•Class 2, Div. 1 - NEC 502.10(A)(2) & 502.30(B)•Class 2, Div. 2 - NEC 502.10(B)(2)•Class 3, Div. 1 - NEC 503.10(A)(2) & 503.30(B)•Class 3, Div. 2 - NEC 503.10(A)(2)
Û For certain applications:- For applications requiring movement, crossover connections or tight bends- For industrial and commercial applications for conveyors, blowers, air conditioners, machine tooling andlubrication equipment- Elevators, escalators, moving walks, wheel chair lifts and stairway chair lifts, per NEC 620.01, where permitted- Cranes and hoists, per NEC 610.11(C)- Boatyards and marinas, per NEC 555.13- Electric signs and outline lighting supply and secondary circuit, per NEC 600.31 (1000 Volts or less) &NEC 600.32 (over 1000 volts)- Floating building feeders and services, per NEC 553.7(B)
Titan™ CBLIQUIDTIGHT FLEXIBLE METAL CONDUIT
METAL CLAD& CONDUIT
81
SIZE(INCHES)
APPROXIMATEWEIGHT
(LBS/100 FT)
INNER DIAMETERMIN./MAX.(INCHES)
OUTER DIAMETERMIN./MAX.(INCHES)
0.690 / 0.7100.820 / 0.8401.030 / 1.0501.290 / 1.3151.630 / 1.6601.865 / 1.9002.340 / 2.3752.840 / 2.8753.460 / 3.5003.960 / 4.0004.460 / 4.500
APPROX. BENDRADIUS*(INCHES)
44568101215182124
3/81/23/41
1-1/41-1/2
22-1/2
33-1/2
4
0.484 / 0.5040.622 / 0.6420.820 / 0.8401.041 / 1.0661.380 / 1.4101.575 / 1.6002.020 / 2.0452.480 / 2.5053.070 / 3.1003.500 / 3.5404.000 / 4.040
Titan™
CBLIQ
UID
TIG
HT
FLEX
IBLE
MET
AL
CO
ND
UIT
*Minimum bend radius based on NEC Chapter 9.
27314076102103145197265300333
3/45/16 3/8 1/2 1 1-1/4 1-1/2 2 2-1/2 3 3-1/2 4
250FTCOIL
25FTCOIL50FTCOIL100FTCOIL
WEIGHTS AND MEASUREMENTS
PACKAGING
HOW ITÊS MADEÛ Spiral wound, interlocked aluminum strip of corrosion-resistant galvanized steelÛ Gray PVC jacket is flexible, flame retardant and resists oils, mild acids as well as exposure to sunlight
82
Û EF: Extra-FlexibleÛ Rated -10■C to 60■CÛ Liquidtight Metal ConduitÛ Resistant to Weather,
Heat, Oil and ChemicalBreakdown
Û Smooth Metal Interior forEasy Pulling
HOW ITÊS USEDÛ For concealed or exposed installations requiring movement, crossover connections or tight bendsÛ Seals out alcohol, coolants, corrosive fumes and gases, dirt, grease, mineral acid, non-concentrated fixedalkalines, petroleum oils, salt air spray, water and various weather conditions
Û Used in industrial and commercial applications for conveyors, blowers, cranes, air conditioners, machinetooling and lubrication equipment where UL listing is not required
Û Provides wiring protection where listed products are not required
Titan™ EFLIQUIDTIGHT FLEXIBLE METAL CONDUIT
METAL CLAD& CONDUIT
83
SIZE(INCHES)
APPROXIMATEWEIGHT
(LBS/100 FT)
INNER DIAMETERMIN./MAX.(INCHES)
OUTER DIAMETERMIN./MAX.(INCHES)
0.690 / 0.7100.820 / 0.8401.030 / 1.0501.290 / 1.3151.630 / 1.6601.865 / 1.9002.340 / 2.3752.840 / 2.8753.460 / 3.5003.960 / 4.0004.460 / 4.500
APPROX.BENDRADIUS(INCHES)
44568101215182124
3/81/23/41
1-1/41-1/22
2-1/23
3-1/24
0.484 / 0.5040.622 / 0.6420.820 / 0.8401.041 / 1.0661.380 / 1.4101.575 / 1.6002.020 / 2.0452.480 / 2.5053.070 / 3.1003.500 / 3.5404.000 / 4.040
Tita
n™EF
LIQUIDTIGHTFLEXIBLEMETALCONDUIT
222329587395131156209259306
0.690 / 0.7100.820 / 0.8401.030 / 1.0501.290 / 1.3151.630 / 1.6601.865 / 1.9002.340 / 2.3752.840 / 2.8753.460 / 3.5003.960 / 4.0004.460 / 4.500
444.55.757.258.259.510.5131516
3/81/23/41
1-1/41-1/22
2-1/23
3-1/24
0.484 / 0.5040.622 / 0.6420.820 / 0.8401.041 / 1.0661.380 / 1.4101.575 / 1.6002.020 / 2.0452.480 / 2.5053.070 / 3.1003.500 / 3.5404.000 / 4.040
15162041516792109146181214
ALUMINUM CORE EXTRA FLEXIBLE LIQUIDTIGHT METALLIC CONDUIT
3/45/16 3/8 1/2 1 1-1/4 1-1/2 2 2-1/2 3 3-1/2 4
250FTCOIL
25FTCOIL50FTCOIL100FTCOIL
WEIGHTS AND MEASUREMENTS
PACKAGING
HOW ITÊS MADEÛ Spiral wound strip of heavy gauge, corrosion-resistant, hot-dipped galvanized steelÛ For 3/8‰ through 1-1/4‰ sizes, the core has a square, locked, steel strip with a copper bonding strip enclosedwithin the steel convolutions
Û Jacket: Rugged, flame retardant, flexible, PVC jacket that is rated for extreme hot and cold temperatureenvironments
Û Protects against liquids, alcohol, coolants, corrosive fumes and gases, dirt, grease, mineral acids, salt, air,alkalines, oil, certain chemicals, temperatures, sunlight and weather.
84
Û HC: Hot/ColdÛ Rated -40■C to 105■CÛ Oil and Sunlight ResistantÛ Accepts Standard Metallic
Liquidtight FittingsÛ Rated for direct burialÛ Smooth Metal Interior for
Easy Pulling
HOW ITÊS USEDÛ For certain conditions:
- For extreme oil and solvent environments- Where conditions of installation, operation or maintenance require flexibility and/or protection fromliquids, vapors, solids or weather- For the installation and protection of electrical conductors in circuits or 600 Volts or less- For equipment grounding in sizes 3/8‰ through 1-1/4‰ in lengths not exceeding 6 feet, per NEC 250.118(6)
Û For certain locations:- For exposed or concealed locations- Under raised floors in data processing areas per NEC 645.5(D) and 645.5(D)(2)- Service entrances, up to 6 feet in length per NEC 230.43 (15)- Hazardous locations: where necessary for flexible connections, in accordance with the following:•Class 1, Div. 2 - NEC 501.10(B)(2) & 501.30(B)•Class 2, Div. 1 - NEC 502.10(A)(2) & 502.30(B)•Class 2, Div. 2 - NEC 502.10(B)(2)•Class 3, Div. 1 - NEC 503.10(A)(2) & 503.30(B)•Class 3, Div. 2 - NEC 503.10(A)(2)
Û For certain applications:- For applications requiring movement, crossover connections or tight bends- For industrial and commercial applications for conveyors, blowers, air conditioners, machine tooling andlubrication equipment- Elevators, escalators, moving walks, wheel chair lifts and stairway chair lifts, per NEC 620.01, where permitted- Cranes and hoists, per NEC 610.11(C)- Boatyards and marinas, per NEC 555.13- Electric signs and outline lighting supply and secondary circuit, per NEC 600.31 (1000 Volts or less) &NEC 600.32 (over 1000 volts)- Floating building feeders and services, per NEC 553.7(B)
Titan™ HCLIQUIDTIGHT FLEXIBLE METAL CONDUIT
HOW ITÊS CERTIFIEDÛ UL Listed to Underwriters Laboratories Standard ANSI / UL-360 for Liquidtight Flexible Steel Conduit.Û CSA Listed to CSA 22.2 No.56 for use per the Canadian Electrical Code C22.1 Section 12-1300.Û NEC Type designation - Type LFMC (Liquidtight Flexible Metal Conduit).Û ANSI / NFPA-70, NEC Article 350.
METAL CLAD& CONDUIT
85
SIZE(INCHES)
APPROXIMATEWEIGHT
(lbs/100 ft)
INNER DIAMETERMIN./MAX.(INCHES)
OUTER DIAMETERMIN./MAX.(INCHES)
0.690 / 0.7100.820 / 0.8401.030 / 1.0501.290 / 1.3151.630 / 1.6601.865 / 1.9002.340 / 2.3752.840 / 2.8753.460 / 3.5003.960 / 4.0004.460 / 4.500
APPROX. INSIDEBEND DIAMETER
(INCHES)
46.58.5131618
22.2529.25
354048
3/81/23/41
1-1/41-1/2
22-1/2
33-1/2
4
0.484 / 0.5040.622 / 0.6420.820 / 0.8401.041 / 1.0661.380 / 1.4101.575 / 1.6002.020 / 2.0452.480 / 2.5053.070 / 3.1003.500 / 3.5404.000 / 4.040
Titan™
HC
LIQU
IDTI
GH
TFL
EXIB
LEM
ETA
LC
ON
DU
IT
27314076102103145197265300333
3/45/16 3/8 1/2 1 1-1/4 1-1/2 2 2-1/2 3 3-1/2 4
250FTCOIL
25FTCOIL50FTCOIL100FTCOIL
WEIGHTS AND MEASUREMENTS
PACKAGING
HOW ITÊS MADEÛ Spiral wound strip of heavy gauge, corrosion-resistant, hot-dipped galvanized steelÛ For 3/8‰ through 1-1/4‰ sizes, the core has a square, locked, steel strip with a copper bonding strip enclosed
within the steel convolutionsÛ Jacket: Rugged, flame retardant, flexible, PVC jacket that is rated for extreme oil and solvent environmentsÛ Protects against liquids, alcohol, coolants, corrosive fumes and gases, dirt, grease, mineral acids, salt, air,
alkalines, oil, certain chemicals, temperatures, sunlight and weather
HOW ITÊS CERTIFIEDÛ UL Listed to Underwriters Laboratories Standard ANSI / UL-360 for Liquidtight Flexible Steel Conduit.Û CSA Listed to CSA 22.2 No.56 for use per the Canadian Electrical Code C22.1 Section 12-1300.Û NEC Type designation - Type LFMC (Liquidtight Flexible Metal Conduit).Û ANSI / NFPA-70, NEC Article 350.
86
Û OR: Oil ResistantÛ Rated -30■C to 80■CÛ Sunlight ResistantÛ Rated for Extreme Oil and
Solvent EnvironmentsÛ Accepts standard metallic
liquid-tight fittingsÛ Rated for direct burial
applicationsÛ Smooth Metal Interior for
Easy Pulling
HOW ITÊS USEDÛ For certain conditions:
- For extreme oil and solvent environments- Where conditions of installation, operation or maintenance require flexibility and/or protection fromliquids, vapors, solids or weather- For the installation and protection of electrical conductors in circuits or 600 Volts or less- For equipment grounding in sizes 3/8‰ through 1-1/4‰ in lengths not exceeding 6 feet, per NEC 250.118(6)
Û For certain locations:- For exposed or concealed locations- Under raised floors in data processing areas per NEC 645.5(D) and 645.5(D)(2)- Service entrances, up to 6 feet in length per NEC 230.43 (15)- Hazardous locations: where necessary for flexible connections, in accordance with the following:
•Class 1, Div. 2 - NEC 501.10(B)(2) & 501.30(B)•Class 2, Div. 1 - NEC 502.10(A)(2) & 502.30(B)•Class 2, Div. 2 - NEC 502.10(B)(2)•Class 3, Div. 1 - NEC 503.10(A)(2) & 503.30(B)•Class 3, Div. 2 - NEC 503.10(A)(2)
Û For certain applications:- For applications requiring movement, crossover connections or tight bends- For industrial and commercial applications for conveyors, blowers, air conditioners, machine tooling andlubrication equipment- Elevators, escalators, moving walks, wheel chair lifts and stairway chair lifts, per NEC 620.01,where permitted- Cranes and hoists, per NEC 610.11(C)- Boatyards and marinas, per NEC 555.13- Electric signs and outline lighting supply and secondary circuit, per NEC 600.31 (1000 Volts or less) &NEC 600.32 (over 1000 volts)- Floating building feeders and services, per NEC 553.7(B)
Titan™ ORLIQUIDTIGHT FLEXIBLE METAL CONDUIT
METAL CLAD& CONDUIT
87
SIZE(INCHES)
APPROXIMATEWEIGHT
(LBS/100 FT)
INNER DIAMETERMIN./MAX.(INCHES)
OUTER DIAMETERMIN./MAX.(INCHES)
0.690 / 0.7100.820 / 0.8401.030 / 1.0501.290 / 1.3151.630 / 1.6601.865 / 1.9002.340 / 2.3752.840 / 2.8753.460 / 3.5003.960 / 4.0004.460 / 4.500
APPROX.BENDRADIUS(INCHES)
24568101215182124
3/81/23/41
1-1/41-1/22
2-1/23
3-1/24
0.484 / 0.5040.622 / 0.6420.820 / 0.8401.041 / 1.0661.380 / 1.4101.575 / 1.6002.020 / 2.0452.480 / 2.5053.070 / 3.1003.500 / 3.5404.000 / 4.040
Tita
n™O
RLIQUIDTIGHTFLEXIBLEMETALCONDUIT
27314076102103145197265300333
3/45/16 3/8 1/2 1 1-1/4 1-1/2 2 2-1/2 3 3-1/2 4
250FTCOIL
25FTCOIL50FTCOIL100FTCOIL
WEIGHTS AND MEASUREMENTS
PACKAGING
HOW ITÊS MADEÛ Spiral wound strip of heavy gauge, corrosion-resistant, hot-dipped galvanized steelÛ For 3/8‰ through 1-1/4‰ sizes, the core has a square, locked, steel strip with a copper bonding strip enclosed
within the steel convolutionsÛ Jacket: Rugged, flame retardant, flexible, UV sunlight resistant, grey, PVC jacketÛ Protects against liquids, alcohol, coolants, corrosive fumes and gases, dirt, grease, mineral acids, salt, air,
alkalines, oil, certain chemicals, temperatures, sunlight and weather
HOW ITÊS CERTIFIEDÛ UL Listed to Underwriters Laboratories Standard ANSI / UL-360 for Liquidtight Flexible Steel Conduit.Û CSA Listed to CSA 22.2 No.56 for use per the Canadian Electrical Code C22.1 Section 12-1300.Û NEC Type designation - Type LFMC (Liquidtight Flexible Metal Conduit).Û ANSI / NFPA-70, NEC Article 350.
88
Û UL: UnderwritersLaboratories
Û Rated for -30■C to80■C, 60■C for Oil
Û Crush/Corrosion, Oil andSunlight Resistant
Û Accepts Standard MetallicLiquidtight FittingsRated for Direct Burial
Û Smooth Metal Interior forEasy Pulling
HOW ITÊS USEDÛ For certain conditions:
- For extreme oil and solvent environments- Where conditions of installation, operation or maintenance require flexibility and/or protection fromliquids, vapors, solids or weather- For the installation and protection of electrical conductors in circuits or 600 Volts or less- For equipment grounding in sizes 3/8‰ through 1-1/4‰ in lengths not exceeding 6 feet, per NEC 250.118(6)
Û For certain locations:- For exposed or concealed locations- Under raised floors in data processing areas per NEC 645.5(D) and 645.5(D)(2)- Service entrances, up to 6 feet in length per NEC 230.43 (15)- Hazardous locations: where necessary for flexible connections, in accordance with the following:
•Class 1, Div. 2 - NEC 501.10(B)(2) & 501.30(B)•Class 2, Div. 1 - NEC 502.10(A)(2) & 502.30(B)•Class 2, Div. 2 - NEC 502.10(B)(2)•Class 3, Div. 1 - NEC 503.10(A)(2) & 503.30(B)•Class 3, Div. 2 - NEC 503.10(A)(2)
Û For certain applications:- For applications requiring movement, crossover connections or tight bends- For industrial and commercial applications for conveyors, blowers, air conditioners, machine tooling andlubrication equipment- Elevators, escalators, moving walks, wheel chair lifts and stairway chair lifts, per NEC 620.01,where permitted- Cranes and hoists, per NEC 610.11(C)- Boatyards and marinas, per NEC 555.13- Electric signs and outline lighting supply and secondary circuit, per NEC 600.31 (1000 Volts or less) &NEC 600.32 (over 1000 volts)- Floating building feeders and services, per NEC 553.7(B)
Titan™ ULLIQUIDTIGHT FLEXIBLE METAL CONDUIT
METAL CLAD& CONDUIT
89
SIZE(INCHES)
APPROXIMATEWEIGHT
(LBS/100 FT)
INNER DIAMETERMIN./MAX.(INCHES)
OUTER DIAMETERMIN./MAX.(INCHES)
0.690 / 0.7100.820 / 0.8401.030 / 1.0501.290 / 1.3151.630 / 1.6601.865 / 1.9002.340 / 2.3752.840 / 2.8753.460 / 3.5003.960 / 4.0004.460 / 4.500
APPROX. BENDRADIUS*(INCHES)
44568101215182124
3/81/23/41
1-1/41-1/2
22-1/2
33-1/2
4
0.484 / 0.5040.622 / 0.6420.820 / 0.8401.041 / 1.0661.380 / 1.4101.575 / 1.6002.020 / 2.0451.575 / 1.6001.575 / 1.6001.575 / 1.6001.575 / 1.600
Titan™UL
LIQU
IDTI
GH
TFL
EXIB
LEM
ETA
LC
ON
DU
IT
*Minimum bend radius based on NEC Chapter 9.
37314076102103145197265300333
3/45/16 3/8 1/2 1 1-1/4 1-1/2 2 2-1/2 3 3-1/2 4
250FTCOIL
25FTCOIL50FTCOIL100FTCOIL
WEIGHTS AND MEASUREMENTS
PACKAGING
HOW ITÊS MADEÛ Spiral of rigid PVC reinforcment imbedded within a flexible PVC wallÛ Thermoplastic materials protect and form the conduit which seals out water, liquids, alcohol, coolants,corrosive fumes and gases, dirt grease, oil, mild acids, non-concentrated fixed alkalines, various weatherconditions and exposure to sun
90
Û NM: Non-MetallicÛ For Dry LocationsÛ Rated -30■C to 80■C,
Rated 60■C OilÛ For Direct Burial &
Encased in ConcreteÛ Highly FlexibleÛ Crush ResistantÛ Smooth Metal Interior for
Easy Wiring
HOW ITÊS USEDÛ For certain conditions:
- Where conditions of installation, operation or maintenance require flexibility and/or protection fromliquids, vapors, solids or weather- For the installation and protection of electrical conductors in circuits of 600 Volts or less
Û For certain locations:- For exposed or concealed locations- Under raised floors in data processing areas per NEC 645.5(D) and 645.5(D)(2)- For use in lengths longer than 6 feet, per NEC 356.10(5)- Hazardous locations: where necessary for flexible connections, in accordance with the following:•Class 1, Div. 2 - NEC 501.10(B)(2) & 501.30(B)•Class 2, Div. 1 - NEC 502.10(A)(2) & 502.30(B)•Class 2, Div. 2 - NEC 502.10(B)(2)•Class 3, Div. 1 - NEC 503.10(A)(2) & 503.30(B)•Class 3, Div. 2 - NEC 503.10(A)(2)
Û For certain applications:- For motor circuits - motor feeders, branch and control circuits- For applications requiring movement, crossover connections or tight bends- For industrial and commercial applications for conveyors, blowers, air conditioners, machine tooling andlubrication equipment- Elevators, escalators, moving walks, wheel chair lifts and stairway chair lifts, per NEC 620.21, where permitted- Cranes and hoists, per NEC 610.11(C)- Boatyards and marinas, per NEC 555.13- Electric signs and outline lighting supply and secondary circuit, per NEC 600.31 (1000 Volts or less) &NEC 600.32 (over 1000 Volts)- Floating building feeders and services, per NEC 553.7(B)- Service entrances, up to 6 feet in length per NEC 230.43 (15)- Agricultural buildings, per NEC 547.5- Motor leads, per NEC 430.145(B)- Swimming pools, spa and hot tub motors, per NEC 680.21 (A)(E) & 680.42(A)(!)
Ultratite® NMLIQUIDTIGHT FLEXIBLE CONDUIT
HOW ITÊS CERTIFIEDÛ NEC Type designation - Type LFNC-B (Liquidtight Flexible Nonmetallic Conduit).Û ANSI / NFPA-70, NEC Article 356.Û UL Listed to Underwriters Laboratories Standard UL 1660.Û Approved by Canadian Standards Association.
METAL CLAD& CONDUIT
91
SIZE(INCHES)
APPROXIMATEWEIGHT
(LBS/100 FT)
INNER DIAMETERMIN./MAX.(INCHES)
OUTER DIAMETERMIN./MAX.(INCHES)
0.690 / 0.7100.820 / 0.8401.030 / 1.0501.290 / 1.3151.630 / 1.6601.865 / 1.9002.340 / 2.375
APPROX.BENDRADIUS(INCHES)
445681012
3/81/23/41
1-1/41-1/2
2
0.484 / 0.5040.622 / 0.6420.820 / 0.8401.041 / 1.0661.380 / 1.4101.575 / 1.6002.020 / 2.045
Ultr
atit
e®N
MLIQ
UID
TIG
HT
FLEX
IBLE
CO
ND
UIT
10.5131827344564
3/43/8 1/2 1 1-1/4 1-1/2 2
250FTREEL400FTREEL600FTREEL1000FTREEL
50FTCOIL100FTCOIL150FTCOIL
WEIGHTS AND MEASUREMENTS
PACKAGING
HOW ITÊS MADEÛ Spiral of rigid PVC imbedded in a flexible PVC wallÛ Provides excellent impact and crush strength
HOW ITÊS CERTIFIEDÛ UL component recognized per UL Standard for Safety, UL 1660.
92
Û NMEF: Non-MetallicExtra Flexible
Û Rated -10■C to 60■CÛ Resistant to Oil, Water,
Rust and Most ChemicalsÛ Smooth Interior for Easy
Pulling
HOW ITÊS USEDÛ For use where vibrations or harsh environments existÛ Seals out alcohol, coolants, corrosive fumes and gases, dirt, grease, mineral acids, non-concentrated
fixed alkalines, petroleum oils, salt, water and various weather conditionsÛ Provides wiring protection where listed products are not required
Ultratite® NMEFLIQUIDTIGHT FLEXIBLE CONDUIT
METAL CLAD& CONDUIT
93
SIZE(INCHES)
APPROXIMATEWEIGHT
(lbs/100 ft)
INNER DIAMETERMIN./MAX.(INCHES)
OUTER DIAMETERMIN./MAX.(INCHES)
0.690 / 0.7100.820 / 0.8401.030 / 1.0501.290 / 1.3151.630 / 1.6601.865 / 1.9002.340 / 2.375
APPROX.INSIDEBEND DIAMETER
(INCHES)
445681012
3/81/23/41
1-1/41-1/2
2
0.484 / 0.5040.622 / 0.6420.820 / 0.8401.041 / 1.0661.380 / 1.4101.575 / 1.6002.020 / 2.045
5.58.810.518.5202332
3/43/8 1/2 1 1-1/4 1-1/2 250FTCOIL100FTCOIL
Ultratite®NMEF
LIQU
IDTI
GH
TFL
EXIB
LEC
ON
DU
IT
WEIGHTS AND MEASUREMENTS
PACKAGING
HOW ITÊS MADEÛ Spiral of rigid PVC reinforcement imbedded within a flexible PVC wallÛ Thermoplastic materials protect and form the conduit which seals out water, liquids, alcohol, coolants,corrosive fumes and gases, dirt, grease, oil, mild acids, non-concentrated fixed alkalines, various weatherconditions and exposure to sun
HOW ITÊS CERTIFIEDÛ NEC Type designation - Type LFNC-B (Liquidtight Flexible Nonmetallic Conduit).Û ANSI / NFPA-70, NEC Article 356.Û UL Listed to Underwriters Laboratories Standard UL 1660.Û Approved by Canadian Standards Association.
94
Û NMHC: Non-MetallicHot/Cold
Û For Dry LocationsÛ Rated -30■C to 80■CÛ For Direct Burial &
Encased in ConcreteÛ Highly FlexibleÛ Crush ResistantÛ Smooth Metal Interior for
Easy Wiring
HOW ITÊS USEDÛ For certain conditions:
- For direct burial and concrete applications- For motor circuits - motor feeders, branch and control circuits- For applicaitons requiring movement, crossover connections or tight bends- For industrial and commerical applications for conveyors, blowers, air conditioners, machine tooling andlubrication equipment- Elevators, escalators, moving walks, wheel chair lifts and stairway chair lifts, per NEC 620.21,where permitted- Cranes and hoists, per NEC 610.11(C)- Boatyards and marinas, per NEC 555.13- Electric signs and outline lighting supply and secondary circuit, per NEC 600.31 (1000 Volts or less) &NEC 600.32 (over 1000 Volts)- Floating building feeders and services, per NEC 553.7(B)- Service entrances, up to 6 feet in length per NEC 230.43 (15)- Agricultural buildings, per NEC 547.5- Motor leads, per NEC 430.145(B)- Swimming pools, spa and hot tub motors, per NEC 680.21 (A)(E) & 680.42(A)(1)
Û For certain locations:- For exposed or concealed locations- Under raised floors in data processing areas per NEC 645.5(D) and 645.5(D)(2)- For use in lengths longer than 6 feet, per NEC 356.10(5)- Hazardous locations: where necessary for flexible connections, in accordance with the following:1. Class 1, Div. 2 - NEC 501.10(B)(2) & 501.30(B)2. Class 2, Div. 1 - NEC 502.10(A)(2) & 502.30(B)3. Class 2, Div. 2 - NEC 502.10(B)(2)4. Class 3, Div. 1 - NEC 503.10(A)(2) & 503.30 (B)5. Class 3, Div. 2 - NEC 503.10(A)(2)
Û For certain conditions:- For environments with extreme hot and cold temperatures- Where conditions of installation, operation maintence require flexiblity, and/or protection from liquids, vapors,solids, weather- For the installation and protection of electrical conductors in circuits of 600 Volts or less
Ultratite® NMHCLIQUIDTIGHT FLEXIBLE CONDUIT
METAL CLAD& CONDUIT
95
SIZE(INCHES)
APPROXIMATEWEIGHT
(lbs/100 ft)
INNER DIAMETERMIN./MAX.(INCHES)
OUTER DIAMETERMIN./MAX.(INCHES)
0.690 / 0.7100.820 / 0.8401.030 / 1.0501.290 / 1.3151.630 / 1.6601.865 / 1.9002.340 / 2.375
APPROX.INSIDEBEND DIAMETER
(INCHES)
46.58.5131618
22.2
3/81/23/41
1-1/41-1/2
2
0.484 / 0.5040.622 / 0.6420.820 / 0.8401.041 / 1.0661.380 / 1.4101.575 / 1.6002.020 / 2.045
Ultratite®NMHC
LIQU
IDTI
GH
TFL
EXIB
LEC
ON
DU
IT
10.5131827344564
3/43/8 1/2 1 1-1/4 1-1/2 2
250FTREEL400FTREEL600FTREEL1000FTREEL
50FTCOIL100FTCOIL150FTCOIL
WEIGHTS AND MEASUREMENTS
PACKAGING
HOW ITÊS MADEÛ Spiral of rigid PVC reinforcement imbedded within a flexible PVC wallÛ Thermoplastic materials protect and form the conduit which seals out water, liquids, alcohol, coolants,corrosive fumes and gases, dirt, grease, oil, mild acids, non-concentrated fixed alkalines, various weather.conditions and exposure to sun
HOW ITÊS CERTIFIEDÛ NEC Type designation - Type LFNC-B (Liquidtight Flexible Nonmetallic Conduit).Û ANSI / NFPA-70, NEC Article 356.Û UL Listed to Underwriters Laboratories Standard UL 1660.Û Approved by Canadian Standards Association.96
Û NMOR: Non-MetallicOil Resistant
Û For Dry LocationsÛ Rated -30■C to 80■CÛ For Direct Burial &
Encased in ConcreteÛ Highly FlexibleÛ Crush ResistantÛ Smooth Metal Interior for
Easy Wiring
HOW ITÊS USEDÛ For certain conditions:
- For direct burial and concrete applications- For motor circuits - motor feeders, branch and control circuits- For applicaitons requiring movement, crossover connections or tight bends- For industrial and commerical applications for conveyors, blowers, air conditioners, machine tooling andlubrication equipment- Elevators, escalators, moving walks, wheel chair lifts and stairway chair lifts, per NEC 620.21,where permitted- Cranes and hoists, per NEC 610.11(C)- Boatyards and marinas, per NEC 555.13- Electric signs and outline lighting supply and secondary circuit, per NEC 600.31 (1000 Volts or less) &NEC 600.32 (over 1000 Volts)- Floating building feeders and services, per NEC 553.7(B)- Service entrances, up to 6 feet in length per NEC 230.43 (15)- Agricultural buildings, per NEC 547.5- Motor leads, per NEC 430.145(B)- Swimming pools, spa and hot tub motors, per NEC 680.21 (A)(E) & 680.42(A)(1)
Û For certain locations:- For exposed or concealed locations- Under raised floors in data processing areas per NEC 645.5(D) and 645.5(D)(2)- For use in lengths longer than 6 feet, per NEC 356.10(5)- Hazardous locations: where necessary for flexible connections, in accordance with the following:1. Class 1, Div. 2 - NEC 501.10(B)(2) & 501.30(B)2. Class 2, Div. 1 - NEC 502.10(A)(2) & 502.30(B)3. Class 2, Div. 2 - NEC 502.10(B)(2)4. Class 3, Div. 1 - NEC 503.10(A)(2) & 503.30 (B)5. Class 3, Div. 2 - NEC 503.10(A)(2)
Û For certain conditions:- For extreme oil and solvent environments- Where conditions of installation, operation maintence require flexiblity, and/or protection from liquids, vapors,solids, weather- For the installation and protection of electrical conductors in circuits of 600 Volts or less
Ultratite® NMORLIQUIDTIGHT FLEXIBLE CONDUIT
METAL CLAD& CONDUIT
97
SIZE(INCHES)
APPROXIMATEWEIGHT
(LBS/100 FT)
INNER DIAMETERMIN./MAX.(INCHES)
OUTER DIAMETERMIN./MAX.(INCHES)
0.690 / 0.7100.820 / 0.8401.030 / 1.0501.290 / 1.3151.630 / 1.6601.865 / 1.9002.340 / 2.375
APPROX.INSIDEBEND DIAMETER
(INCHES)
445681012
3/81/23/41
1-1/41-1/2
2
0.484 / 0.5040.622 / 0.6420.820 / 0.8401.041 / 1.0661.380 / 1.4101.575 / 1.6002.020 / 2.045
Ultratite®NMOR
LIQU
IDTI
GH
TFL
EXIB
LEC
ON
DU
IT
10.5131827344564
3/43/8 1/2 1 1-1/4 1-1/2 2
250FTREEL400FTREEL600FTREEL1000FTREEL
50FTCOIL100FTCOIL150FTCOIL
WEIGHTS AND MEASUREMENTS
PACKAGING
HOW ITÊS MADEÛ Continously interlocked steel armorÛ Solid or stranded THHN/THWNÛ Solid TFN or stranded TFFN conductorsÛ Approved Lock-nut or Snap-in fittings for easy and hassle free hook-upsÛ 6‰ conductor leads at each endÛ 1/2‰ stripped insulationÛ Complete assembly, ready to install, from the factory
HOW ITÊS CERTIFIEDÛ Lite-Whip® is UL Listed under the Wiring Assemblies (QQYZ) category.
98
Û Lite-Whip: Pre-AssembledFixture Whips
Û 600 Volts
HOW ITÊS USEDÛ For connecting fluorescent lay-in fixtures and incandescent fixtures to suspended and accessible ceilings
Lite-Whip®
PRE-ASSEMBLED FIXTURE WHIPS
METAL CLAD& CONDUIT
LOCK-NUT FITTINGS WITH SOLID THHN/THWN OR TFN CONDUCTORS
99
PARTNUMBER
WIRE SIZE# OF COND. /SIZE
CONDUCTORTYPE
CARTON PACKAGEQUANTITY/WEIGHT
BARREL PACKAGEQUANTITY / WEIGHT
WEIGHTS AND MEASUREMENTS
LWL183LWL184LWL143LWL144LWL123
SOLIDSOLIDSOLIDSOLIDSOLID
30 UNITS/23 lbs30 UNITS/24 lbs30 UNITS/25 lbs30 UNITS/26 lbs30 UNITS/30 lbs
100 UNITS/80 lbs100 UNITS/84 lbs100 UNITS/85 lbs100 UNITS/90 lbs100 UNITS/95 lbs
Lite
-Whi
p®
PRE-ASSEM
BLED
FIXTURE
WHIPS
3x # 18 AWG4x # 18 AWG3x # 14 AWG4x # 14 AWG3x # 12 AWG
LWL183LWL184LWL143LWL144LWL123
SOLIDSOLIDSOLIDSOLIDSOLID
30 UNITS/23 lbs30 UNITS/24 lbs30 UNITS/25 lbs30 UNITS/26 lbs30 UNITS/30 lbs
100 UNITS/80 lbs100 UNITS/84 lbs100 UNITS/85 lbs100 UNITS/90 lbs100 UNITS/95 lbs
3x # 18 AWG4x # 18 AWG3x # 14 AWG4x # 14 AWG3x # 12 AWG
LWL183SLWL184SLWL143SLWL144SLWL123S
STRANDEDSTRANDEDSTRANDEDSTRANDEDSTRANDED
30 UNITS/23 lbs30 UNITS/24 lbs30 UNITS/25 lbs30 UNITS/26 lbs30 UNITS/30 lbs
100 UNITS/80 lbs100 UNITS/84 lbs100 UNITS/85 lbs100 UNITS/90 lbs100 UNITS/95 lbs
3x # 18 AWG4x # 18 AWG3x # 14 AWG4x # 14 AWG3x # 12 AWG
SNAP-IN FITTINGS WITH SOLID THHN/THWN OR TFN CONDUCTORS
SNAP-IN FITTINGS WITH STRANDED THHN/THWN OR TFN CONDUCTORS
COLOR CODING
234
STANDARD COLORS 120/208Y OPTIONAL COLORS 277/480YBROWN, ORANGE, YELLOW, PURPLE, GREYBROWN, ORANGE, YELLOW, PURPLE, GREYBROWN, ORANGE, YELLOW, PURPLE, GREY
BLACK, WHITEBLACK, WHITE, REDBLACK, WHITE, RED, BLUE
#OFCONDUCTORS
Grounding Conductor is Green.
HOW ITÊS MADEÛ Non-Metallic conduit with 2 different PVC materials that form the highly flexible productÛ A rigid material forms the stiff helical spring which is encapsulated by a second flexible compoundÛ Has stranded copper THHN/THWN conductorsÛ 12‰ wire leads are exposed at each end for hassle-free hook-ups with 1/2‰ stripped insulation
HOW ITÊS CERTIFIEDÛ Ultra-Whip® is UL Listed under the Wiring Assemblies (QQYZ) category. Ultra-Whip®complies with NEC Article 356,UL Standard 1660, and CSA Standard C22.2 No. 227.2 for Liquidtight Flexible Non-Metallic Conduit. The fittingsmeet UL Standard 514B, CSA Standard C22.2 No. 18 and NEMA FB-1.
100
Û NM: Non-MetallicÛ 600 VoltsÛ Resistant to Rust, Cracksand Separation
Û Intended for 208/240/480Volt Single Phase Circuits
Û Non-Metallic Raceway isNon-Conducting
HOW ITÊS USEDÛ For connecting air conditioners, pumps, motors, compressors, swimming pool devices and other similar equipmentÛ For electrical applicationsÛ Complete assembly, ready to install, from the factory
Ultra-Whip® NMPRE-ASSEMBLED HOOK-UP WHIPS
METAL CLAD& CONDUIT
101
PARTNUMBER
SIZE(INCHES)
WIRE SIZE# OF COND. /SIZE
AMPERE RATING(AMPS)
MASTER CARTONQUANTITY
(# OF PIECES)
MASTER CARTONWEIGHT(LBS.)
303040
40
666
6
121314
15
R124R126R344
R346
3x #10 AWG3x #10 AWG2x #8 AWG
1x #10 AWG Ground2x #8 AWG
1x #10 AWG Ground
1/2‰1/2‰3/4‰
3/4‰
234
STANDARD COLORS 120/208Y OPTIONAL COLORS 277/480YBROWN, ORANGE, YELLOW, PURPLE, GREYBROWN, ORANGE, YELLOW, PURPLE, GREYBROWN, ORANGE, YELLOW, PURPLE, GREY
BLACK, WHITEBLACK, WHITE, REDBLACK, WHITE, RED, BLUE
#OFCONDUCTORS
Grounding Conductor is Green.
3/4‰ R3441/2‰ R124 1/2‰ R126 3/4‰ R3464FT.
6 FT.
Ultr
a-W
hip
®N
MPR
E-A
SSEM
BLED
HO
OK-
UP
WH
IPS
WEIGHTS AND MEASUREMENTS
COLOR CODING
PACKAGING