2
SoundSens “i” Correlating Noise Loggers Halma Water Management USB communications with PC. Infra Red communications with loggers (no connections required). Simultaneous communications with all loggers for fast recording setup. LCD screen with backlight. Push button interface. Battery LED indicates when battery is running low. Case- typically 2 months between charges. Pods have 5 year typical battery life. Cases can be linked for simulta- neous set up and download. Introduction Soundsens “i” is the latest version of the popular Soundsens correlating loggers. The system, along with the latest software is designed for performance, versatility and speed of operations in the field, allowing for set up and download without a PC if preferred. The unit has the potential to store up to a weeks survey data for before the need for downloading to a PC, making work patterns more flexible. Loggers are downloaded via infra red and as there is no requirement for physical connection, deployment and download is much faster. Boxes of loggers can be connected together to allow simultaneous programming and downloading of data from all loggers. This, combined with communication to a PC via USB means that leak detection work is done quickly and efficiently. Now available in purpose designed mini-kits (2,3 and 4 pod options). Features User can setup loggers and download data without using PC. Quick recording setup for day or night Recordings. Custom recording setup available. Multiple downloads of data can be stored. Simultaneous download of data from all loggers. For more information call +44 (0) 1633 489479 or visit www.hwm-water.com A Halma Group Company g Company is ISO 9001 Registered No.06134A FLOW MEASUREMENT DATA LOGGING LEAK DETECTION PRESSURE MANAGEMENT INFRA RED PORTABLE 5 YEAR BATTERY LIFE CASE SET-UP

SoundSens i Tech Sheet - hydreka.fr data sheets/Leak... · USB means that leak detection work is done quickly and efficiently. ... Sensor Input Internal High Performance Accelerometer

Embed Size (px)

Citation preview

Page 1: SoundSens i Tech Sheet - hydreka.fr data sheets/Leak... · USB means that leak detection work is done quickly and efficiently. ... Sensor Input Internal High Performance Accelerometer

SoundSens “i”Correlating Noise Loggers Halma Water Management

■ USB communications with PC.

■ Infra Red communications withloggers (no connections required).

■ Simultaneous communicationswith all loggers for fast recordingsetup.

■ LCD screen with backlight.

■ Push button interface.

■ Battery LED indicates whenbattery is running low. Case-typically 2 months betweencharges. Pods have 5 year typicalbattery life.

■ Cases can be linked for simulta-neous set up and download.

IntroductionSoundsens “i” is the latestversion of the popularSoundsens correlating loggers.The system, along with thelatest software is designed forperformance, versatility andspeed of operations in thefield, allowing for set up anddownload without a PC ifpreferred. The unit has thepotential to store up to aweeks survey data for beforethe need for downloading to aPC, making work patternsmore flexible.

Loggers are downloaded viainfra red and as there is no

requirement for physical connection, deployment anddownload is much faster.

Boxes of loggers can be connected together to allowsimultaneous programming and downloading of data fromall loggers. This, combined with communication to a PC viaUSB means that leak detection work is done quickly andefficiently. Now available in purpose designed mini-kits (2,3and 4 pod options).

Features■ User can setup loggers and download data without using PC.

■ Quick recording setup for day or night Recordings.

■ Custom recording setup available.

■ Multiple downloads of data can be stored.

■ Simultaneous download of data from all loggers.

For more information call +44 (0) 1633 489479or visit www.hwm-water.com

A Halma Group Company g Company is ISO 9001 Registered No.06134A

F L OW M E A S U R E M E N T DATA L O G G I N G L E A K D E T E C T I O N P R E S S U R E M A NAG E M E N T

INFRA REDPORTABLE

5 YEARBATTERY

LIFE

CASESET-UP

Page 2: SoundSens i Tech Sheet - hydreka.fr data sheets/Leak... · USB means that leak detection work is done quickly and efficiently. ... Sensor Input Internal High Performance Accelerometer

SoundSens “i”Correlating Noise Loggers

P R O D U C T S P E C I F I C A T I O N

Halma Water Management

F L OW M E A S U R E M E N T DATA L O G G I N G L E A K D E T E C T I O N P R E S S U R E M A NAG E M E N T

g Halma Water Management a Division of Palmer EnvironmentalTy Coch House Llantarnam Park Way Cwmbran Gwent NP44 3AW United Kingdom

g Tel: +44 (0) 1633 489479 Fax: +44 (0) 1633 877857 g [email protected] www.hwm-water.comg Registered Address: Ty Coch House Llantarnam Park Way Cwmbran Gwent NP44 3AW

g Registered in England No: 1463016

HW

MSo

unds

ens6

/200

7

Sensor Input Internal High Performance Accelerometer to pickup audible noise in pipelineAttachment Powerful magnetic coupling to attach Correlator Pod toof logger/ sensor pipework / valveMemory Recording 650,000 readings. (memory expandable to 1.35 million readings on request)

Individual measurements can be pre-programmed into a series of 32 separate recordingsSample Rate User adjustable

Logging Delayed start Either start at a nominated time, or after set delay period, e.g; for unmannedFeatures night-time correlation

Logger ID Factory set Logger ID numberAlso user can enter another logger Identity number to simplify recognition for operators

Clock On board 24 hour real time clock with date facility.Software Compatible with Radcom “SoundSens” analysis softwareCase to PC Via USB connection to PC for faster download

Communications Case to Pods Simultaneous communication from case to pod viainfra redCase to Case Via 9 pin RS232Dimensions Individual Advanced Correlator Pod now with reduced dimensions:

160 H incl Magnet x 55Diam mm (6.3H x2.10D”)Construction CPod: Die-cast aluminium enclosure, powdercoat spray painted

Carry Case: Rugged construction with Aluminium CladdingPhysical Weight Individual Correlator Pod: 0.7 kg (1.54 lb)

Carry Case Supplied in 2 - 4 pod case or 6 - 8 pod case(Any number of cases can be connected together)

Operating temp -10 to +50°C (14 to +122°F)Ingress protection Individual Correlator Pods: IP68 submersiblePower Correlator pod has Lithium-ion cell operational for 5 years under normal

operating conditions.Carry Case interface unit contains NiCad battery which typically requirescharging monthly or less.240 /110v switch mode charger supplied in kit with mains lead.

HWM reserve the right to change the specification of any product without prior notice.