Instruction manual SolarMax P series 2000P / 3000P / 4000P / 4600P / 5000P

SolarMax P seriesen 7 Note Notes contain additional information or facilitate the inverter operation. 2 Safety 2 1 Intended use The SolarMax P series inverters are designed exclusively

  • Upload
    others

  • View
    6

  • Download
    1

Embed Size (px)

Citation preview

  • Instruction manual

    SolarMax P series2000P / 3000P / 4000P / 4600P / 5000P

  • SolarMax Produktions GmbH

    Zur Schönhalde 10

    D-89352 Ellzee

    E-Mail: [email protected]

    © SolarMax Produktions GmbH 2018

    mailto:info%40solarmax.com?subject=

  • 4

    Contents1 Notes on the present instruction manual � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 6

    1.1 Scope. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61.2 Target groups . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61.3 Where to keep this manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61.4 Symbols used. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

    2 Safety 72.1 Intended use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72.2 Safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72.3 Symbols on the inverter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

    3 Description 93.1 Identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93.2 Functionality. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93.3 Safety installations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93.4 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103.5 Views of the unit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .113.6 Block diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12

    4 Installation 134.1 Transporting and storing inverters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .134.2 Checking the delivery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .134.3 Selecting the installation location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .144.4 Mounting the inverter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

    5 Electrical connection � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �175.1 Opening the inverter. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17

    5.1.1 Removing the cover. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .175.1.2 Removing the contact protection. . . . . . . . . . . . . . . . . . . . . . . . . . .18

    5.2 Connection area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .195.3 Connecting the inverter to the mains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 205.4 Connecting the inverter to the PV generator . . . . . . . . . . . . . . . . . . . . . . . . 225.5 Network connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

    6 Commissioning � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 266.1 Activating the inverter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 266.2 Initial start-up. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26

    6.2.1 Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 266.2.2 Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 276.2.3 Description of country-specific menus . . . . . . . . . . . . . . . . . . . . . 28

    6.3 Auto-test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30

  • en

    5

    6.4 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 316.4.1 Setting the display language and system time. . . . . . . . . . . . . . . . 316.4.2 Setting the network parameters . . . . . . . . . . . . . . . . . . . . . . . . . . 32

    6.5 Displaying the configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 336.6 Displaying the measured values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 396.8 Update firmware. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40

    7 Operation� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 417.1 Graphics display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 417.2 Menu structure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 427.3 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 437.4 Main menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 437.5 Statistics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44

    7.5.1 Displaying the daily statistics . . . . . . . . . . . . . . . . . . . . . . . . . . . . 447.5.2 Displaying the monthly statistics . . . . . . . . . . . . . . . . . . . . . . . . . . 447.5.3 Displaying the annual statistics . . . . . . . . . . . . . . . . . . . . . . . . . . . 457.5.4 Displaying the total statistics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 457.5.5 Deleting the statistics values. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46

    7.6 Displaying information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 467.7 Operating status. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47

    7.7.1 Booting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 487.7.2 Mains operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48

    8 Troubleshooting 498.1 SolarMax Service Center . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 498.2 Diagnosis & measures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49

    8.2.1 General troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 498.2.2 Warnings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 508.2.3 Faults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 508.2.4 Error . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 518.2.5 Blockings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52

    9 Maintenance � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 52

    10 Decommissioning� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 5310.1 Instructions for inverter replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5310.2 Inverter removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5310.3 Disposing of the inverter. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54

    11 Technical data 55

    12 Accessories and options 60

    13 Warranty � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 61

  • 6

    1 Notes on the present instruction manual

    1�1 ScopeThis instruction manual is applicable to the Solarmax 2000P, 3000P, 4000P, 4600P and 5000P inverters.

    1�2 Target groupsThis instruction manual is intended for the operator of the plant and the installer of the PV power plant.

    The instructions in chapters 4, 5, 6, 8 (troubleshooting actions) and 10 may only be carried out by trained electricians (e.g. electricians, electric systems technicians, elec-trical mechanics, industrial electronics technicians).

    1�3 Where to keep this manualThe plant operator must ensure that this instruction manual is available to the relevant persons at all times. If this original document is lost, an up-to-date version of this instruc-tion manual can be downloaded from our website at any time (www.solarmax.com).

    1�4 Symbols usedThe following safety instructions and general information are used within this instruction manual.

    DANGER!Non-observance of these safety instructions may immediately cause serious injuries or death.

    WARNING!Non-observance of these safety instructions may cause serious injuries.

    CAUTION!Non-observance of these safety instructions may cause minor or medium injuries.

    ATTENTION!Non-observance of these safety instructions may cause material damage.

    http://www.solarmax.com/en/

  • en

    7

    Note

    Notes contain additional information or facilitate the inverter operation.

    2 Safety

    2�1 Intended useThe SolarMax P series inverters are designed exclusively to convert the direct current generated by PV modules into alternating current which conforms to the parameters of the public grid. Any other use, in particular the conversion of direct current from batteries or other storage elements into alternating current is not permissible.

    The inverters of the P series may only be connected to Class II PV generators.

    2�2 Safety instructions

    DANGER!Fatal electric shock hazard!In daylight the PV generator supplies the inverter with a dangerously high DC voltage.

    ■■ Make sure that all electrical feed-in lines to the inverter are de-energized before starting any work on the inverter or the feed-in lines.

    DANGER!Fatal electric shock hazard!Components within the inverter are charged with a high voltage.

    ■■ Never open the inverter while it is in operation.

    WARNING!Risk of injury from electric arc!Removing the DC connector when live can lead to dangerous electric arcs.

    ■■ Switch off the DC disconnector at the inverter before removing the DC connectors.

  • 8

    WARNING!A fire risk can result from inappropriate repair!

    ■■ The inverter does not contain any replaceable components. Defective inverters must be sent to the SolarMax Service Center for repair or dis-posed of in accordance with Section 10.3.

    2�3 Symbols on the inverter

    Symbol DescriptionProtective conductor connection

    The DC disconnector is switched off (the contacts are open).

    The DC disconnector is switched on (the contacts are closed).

    Risk of death through high voltages! Only qualified electricians may perform work on the inverter.

    Careful - hot surfaces!

    5 minRisk of death due to high voltages! De-energize the inverter. Proceed to wait for 5 minutes before opening the inverter.

    Only qualified electricians may perform work on the inverter.

    Read the operating instructions - Please read and follow the instruc-tions supplied with the inverter. Do not remove any symbols on the inverter. Replace damaged symbols.

    CE marking - The inverter complies with the requirements of the European EMC Directive 2004/108/EC and the Low Voltage Directive 2006/95/EC (see Section 11).

    Do not dispose of the inverter and its accessory components in the household waste.

  • en

    9

    3 Description

    3�1 IdentificationThe inverter can be identified on the basis of the information provided on the nameplate (see Section 3.5).

    3�2 FunctionalityInverter operation is completely automatic and depends on the available output of the PV generator. If there is enough power, the inverter starts mains operation and feeds into the power grid. If there is not enough power available from the PV generator, the inverter disconnects from the grid and shuts down.

    The graphics display with three function keys allows convenient inverter operation and reading of all important operating data. The graphics display is only switched on when the DC input voltage is high enough.

    The inverter has configurable functions for grid monitoring, limitation of output and reac-tive power control.

    For the purpose of monitoring the PV power plant remotely, the inverter can be connected directly to the Internet via Ethernet.

    The optional I/O module includes configurable interfaces for monitoring, remote control and the control of self-consumption of the inverter.

    3�3 Safety installations

    Overvoltage protection

    P series SolarMax inverters feature integrated surge arrestors (varistors) at both input and output. Each DC input (plus and minus connection) is fitted with a surge arrester. The surge arresters have a common gas discharge tube to ground. On the AC side a surge arrester is installed between the phase and neutral. A second surge arrester with gas discharge tube is fitted between neutral and ground (for details regarding the fitted surge arresters see section 11).

    When designing the PV system, it may be necessary to provide additional external light-ning protection. The optional I/O module can be used to monitor external lightning protec-tion modules.

  • 10

    Fault current monitoring

    The inverters in the SolarMax P series have an integrated AC/DC-sensitive fault current sensor. This sensor can distinguish between the operational capacitive stray currents (caused by capacities of the PV modules to ground) and leakage currents (caused by touching a pole of the PV generator). If the inverter detects an excess in the permissible leakage or stray currents, it will disconnect from the grid.

    Functions for current and power limitation

    The inverters of the P series limit the DC feed-in current, the output power and the AC output current.

    Temperature limitation

    At ambient temperatures of more than 45 °C the equipment temperature may reach more than 80 °C. In such cases, the maximum in-feed power is temporarily reduced. When the equipment temperature rises to over 85 °C, the inverter disconnects from the grid.

    3�4 Dimensions

    104.5

    480 189

    [mm]

    256.5

    361

  • en

    11

    3�5 Views of the unit

    4 1

    5

    7

    23

    6

    No� Description1 Cover2 Graphics display3 Type plate4 DC disconnector5 Cooling fins 6 Connection area7 Mounting rail

  • 12

    3�6 Block diagram

    −−+ +

    I

    0

    UU

    U

    Status signalling contact

    Ethernet

    DC m

    easu

    rem

    ent

    AC measurement

    Internal fan

    RS485

    External shutdown

    External energy meter

    Monitoringlightning protection

    Inverter control

    Boos

    ter c

    ontro

    l

    Inve

    rter

    LCL

    �lte

    r

    Boos

    ter 2

    Boos

    ter 1

    DC

    DC

    AC

    K2K1

    DC

    DC

    DC

    External power control

    Cont

    rol u

    nit

    Com

    mun

    icat

    ion

    mod

    ule

    Grap

    hics

    dis

    play

    * Tra

    cker

    2 o

    nly

    Sola

    rMax

    400

    0P /

    4600

    P / 5

    000P

    ***

    optio

    nal

    ** �

    tted

    ex w

    orks

    DC d

    isco

    nnec

    tor

    DC input tracker 1 DC input tracker 2 *

    I/O m

    odul

    e **

    *

    AC output

    EMC

    �lte

    r

    EMC

    �lte

    r

    EMC

    �lte

    r

    DC b

    ridge

    s **

  • en

    13

    4 Installation

    4�1 Transporting and storing invertersMake sure that the ambient conditions during transportation and storage are within the specified limits (for details see section 11).

    4�2 Checking the deliveryCheck the contents of the delivered package for completeness and possible damage. In the case of an inadequate delivery please contact your dealer or the SolarMax Service Center.

    3

    1

    2

    6 7

    8 9 11 12 13 1410

    54

    Gerätedokumentation

    SolarMax P-Serie2000P / 3000P / 4000P / 4600P / 5000P

    No� Quantity Description1 1 Inverter2 1 Instruction manual3 1 Mounting rail4 2 Plastic dowels 8 x 40 (for fixing in brickwork)

  • 14

    No� Quantity Description5 2 Washers M6 x 18 INOX (for the installation of the inverter)6 2 External hexagon wood screws 6 x 50 INOX (for the installation of the

    inverter)7 2 Phillips head sheet metal screws 4.8 x 13 (for locking the inverter on the

    mounting rail)8 3 Locking pins (for plugging unused holes in multiple cable connectors)9 4 Locking clips (for DC plugs)10 1 Toothed lock washer M5

    (for connection of 2nd protective conductor)

    11 1 Cable lug M5 x 10mm2

    12 1 Washer M513 1 Spring lock washer M514 1 Phillips head screw M5 x 12

    4�3 Selecting the installation location

    DANGER!Fatal fire or explosion hazard!The inverter is an electrical device with heat generation and the possibility of sparking.

    ■■ Install the inverter in an environment that is free of flammable gases and fluids.

    ■■ Never install the inverter near combustible materials. The installation base must be non-combustible.

    ■■ Follow the local fire safety regulations.

    The ambient conditions are specified in the specifications, see Section 11.

    Location and installation conditions

    ■■ Select a dry location protected from water and snow.■■ Install the inverter in an easily accessible location, so that maintenance work can be

    carried out easily.■■ Do not expose the inverter to direct sunlight.■■ Never install one inverter above another (this would reduce the cooling effect; see

    Section “Temperature dependent output reduction”; page 59).

  • en

    15

    ■■ Maintain the following installation distances:

    50

    50

    [cm]

    °C2020

    ■■ The installation base must be vertical.■■ Do not install the inverter in a horizontal or inclined position.

    OK !

    ■■ The optimal cooling of the inverter is only guaranteed when the cooling fins (see section 3.5) are absolutely free of dust and dirt.

    ■■ When installing the inverter on a mast, a mounting plate with at least the same dimensions as the back of the inverter is needed.

    ■■ The ambient air around the inverter must be free from dust, salt and ammonium vapors.

    ■■ The location must meet the requirements regarding electromagnetic immunity and interference emission.

  • 16

    4�4 Mounting the inverterThe inverter is fixed to the wall by a mounting rail. The mounting rail and the necessary fixing accessories are included in the delivery package.

    Procedure

    1. Use the mounting rail as a template for drilling the holes.2. Use a spirit level to position the mounting rail horizontally.3. Mark two drilling holes.

    446

    376

    26 [mm]

    26

    6.5

    6.5

    – For the other measurements see section 3.4.4. Drill two holes Ø 8 x 50 mm.5. Fix the mounting rail.

    – Assembly sequence: plastic dowels 8 x 40, mounting rail, M6 washers, hexagon head wood screws 6 x 50.

    6. Attach the inverter to the mounting rail (A).7. Fix the inverter on both sides with the Phillips head sheet metal screws 4.8 x 13 (B)

    and (C):

    (A)

    (B)

    (C)

  • en

    17

    5 Electrical connection5�1 Opening the inverterFor the purpose of connecting the AC and communication lines, the inverter has to be opened.

    DANGER!Fatal electric shock hazard!Components within the inverter are charged with dangerously high voltage.

    ■■ De-energize the inverter completely before carrying out installation work.

    5�1�1 Removing the coverOnce the cover is removed, the low voltage and communication terminals are accessible.

    Procedure

    1. Disconnect the AC power supply to the inverter.2. Disconnect all control cables connected to the inverter (status relays, external grid

    monitoring).3. Switch off the DC disconnector at the inverter.

    DANGER!Fatal electric shock hazard!After the inverter has been disconnected, high residual voltages remain in the inverter for approx. 5 minutes.

    ■■ Wait 5 minutes.

    4. Loosen the two M5 screws at the bottom of the cover.5. Remove the cover by gripping it at the bottom and pulling it away.

  • 18

    5 min

    5�1�2 Removing the contact protectionWhen the contact protection has been removed, the internal connections - with dan-gerous voltage charges - are accessible.

    Procedure

    1. Press slightly on the two side snap closures and take the contact protection out of the holder.

    2. Use a voltage tester to check that all connections at the inverter and, if applicable, at the I/O module, are de-energized.

  • en

    19

    5�2 Connection areaThe connection area with the cover removed and without contact protection.

    10 9 8

    7

    6

    5

    4

    3

    2

    1

    No� Description1 DC connections2 Left-hand cable pass-through (multiple cable gland for the communication cables)

    3 Right-hand cable pass-through (AC connection)

    4 Locking screw (the locking screw is replaced by the cable gland when the I/O module is installed)

    5 Connection option for 2nd protective conductor

    6 Slot for the optional I/O module

    7 AC connection

    8 RS485 socket

    9 Ethernet socket

    10 DC bridges for single tracking (fitted ex works)

  • 20

    5�3 Connecting the inverter to the mains

    DANGER!Fatal electric shock hazard!

    ■■ Make sure the AC line is not live during connection work.

    Connection conditions

    ■■ Comply with the connecting conditions set by the grid operator in charge.■■ Connectable cable diameter: min. 9.5 mm / max. 12.5 mm■■ Permissible conductor cross-sections:

    – flexible conductors (with or without ferrule) or rigid conductors: max. 16 mm2

    – flexible conductors with ferrules (with plastic sleeves): max. 10 mm2

    ■■ The AC feed cable must be fused.■■ Minimum conductor cross sections and suggested mains fuses:

    SM2000P SM3000P SM4000P SM4600P SM5000PMinimum conductor cross-section 1.5 mm2 1.5 mm2 2.5 mm2 4 mm2 4 mm2

    Mains fuses (characteristic C) 10 A 16 A 20 A 25 A 25 A

    ■■ Temperature resistance of the AC feed cable: ≥ 80 °C■■ Make sure the ambient temperatures for the mains fuses specified by the producer

    are not exceeded.

    WARNING!Risk of death by fire!

    ■■ Provide separate fuses for each inverter.■■ Do not attach any loads between inverter and fuse.

    ■■ If you use an external leakage current circuit breaker (RCD switch), you must comply with the following connection conditions:

    – Use an A or B type RCD (residual current device) switch with a rated fault current of at least 100 mA.

    – In PV power plants with high leakage capacities, an RCD switch with a rated fault current of at least 300 mA. must be used.

  • en

    21

    Procedure

    1. Open the inverter as described in section 5.1.2. Route the AC conductor through the right-hand cable gland to the AC connection

    terminals.3. Remove an 18 mm length of conductor isolation (A).4. Connect the wires in the following sequence:

    – the protective conductor to the "PE" terminal – the neutral conductor to the "N" terminal – the live conductor (phase L) to the "L" terminal – press and close the levers (B) and (C) completely. If a lever is not completely closed, the conductor connection is not secured.

    (C)

    (D)

    (B)(A)

    [mm]

    N PEL

    18

    Abbildungen Klemme: Phoenix Contact

    5. Check the cable connections for firm seating.6. Tighten the cable gland (wrench size: 34 mm).7. Check the cable strain relief.8. Connect the second protective conductor (D).

    – Assembly sequence: toothed lock washer M5, lug, washer M5, spring washer M5, Phillips head screw M5 x 12

    9. Close the inverter: – insert the contact protection until it engages; – then tighten the cover.

  • 22

    5�4 Connecting the inverter to the PV generatorThe inverters of the P series can be operated in single tracking or dual tracking mode, depending on the configuration of the PV plant. In the dual tracking mode a separate MPP tracker is available for each DC input (2 trackers). The ex works configuration of the P series inverters is for single tracking (1 tracker).

    Connection conditions

    ■■ Connection of maximum 2 strings (1 string in the case of SM2000P / SM3000P)

    DANGER!Risk of death by fire!High return currents can cause a fire risk for the PV generator.

    ■■ When Y plugs are used in order to connect more than 2 conductors (more than 1 conductor in the case of SM2000P and SM3000P), each DC con-ductor must be protected individually against dangerous return currents.

    ■■ Maximum DC input current: 10 A per DC input / 20 A when operating in single tracker mode (only SM4000P SM4600P and SM5000P)

    ■■ Maximum DC input voltage: 600 V■■ Select the conductor cross-section to suit the system configuration.■■ Exclusively use Wieland PST40i1C connectors (the mating connectors are not

    included in the package supplied)■■ Do not fit a ground connection to either the negative terminal or the positive terminal

    of the PV generator.

    Procedure

    1. Make sure the DC disconnector and the external AC disconnector are off.2. Connect the pre-fitted DC conductors (A).3. Use the locking clips (included in the delivery package) to secure the connectors

    against manual opening (B).

  • en

    23

    DC− DC+DC+ DC−

    (A) (B)

    Configure the inverter for dual tracking operation

    If necessary, configure the inverter for dual tracking operation (only SM4000P, SM4600P and SM5000P).4. Remove the cover as described in section 5.1.1.5. Remove both DC bridges (see Section 5.2 / No.10) using a size 2 screwdriver.

    6. Close the inverter by fitting and tightening the cover.

    Close off any unused DC connection points�

    Any unused DC connection points must be closed off to ensure that the installation com-plies with the IP65 protection rating requirements. Please use the following closing parts made by Wieland (www.wieland-electric.com):

    ■■ for plug components: order number 05.566.6380.0■■ for socket components: order number 05.566.6480.0

    http://www.wieland-electric.com

  • 24

    Increasing overvoltage protection

    If you want to increase the overvoltage protection on the DC side using additional external surge arresters, the following connection conditions must be met:

    ■■ Use a surge arrester with a response voltage of > 600 V.■■ Connect the external surge arresters as follows:

    > 600 V > 600 V > 600 V> 600 V

    ■■ Install the connector cables close together to avoid overvoltages in the case of a lightning strike.

    ■■ Avoid ground loops in the wiring.■■ Wire the earth connections in a star configuration with the neutral point close to the

    inverter.

  • en

    25

    5�5 Network connectionsThe inverter is fitted with two RJ45 sockets as standard to provide an interface to an Ethernet or RS485 network.

    Note

    You will find more details about data communications in the technical informa-tion “MaxComm network”. This document can be downloaded from our web-site at: www.solarmax.com/en/downloads/data-communication/maxcomm.

    Connection conditions

    ■■ Use shielded RJ45 cable■■ Connectable cable diameter: min. 5.5 mm / max. 7.0 mm

    Procedure

    1. Remove the cover of the inverter as described in section 5.1.1.2. Thread the network cables through the multiple cable gland (see Section 5.2) to the

    network terminals.

    Note

    The RJ45 connectors can be pulled through the multiple cable gland.

    3. Depending on the type of network, connect the cable either to the "Ethernet" or "RS485" connection.

    4. Close off any unused holes in the multiple cable gland using the locking pins (see No. 8 in Section 4.2).

    5. Tighten the multiple cable gland (wrench size: 34 mm).6. After that, check the cable strain relief.7. Close the inverter by installing and tightening the cover.

    http://www.solarmax.com/en/downloads/data-communication/maxcomm/

  • 26

    6 Commissioning

    6�1 Activating the inverter

    Procedure

    1. Check that the cover is installed. – If the cover is not fitted, close the inverter as follows: – insert the contact protection until you hear the two snap closures engage – then fit the cover and tighten.

    2. Switch on the DC disconnector at the inverter.

    – The graphics display shows the "Overview". The status message "Start up..." appears.

    3. Switch on the AC power supply to the inverter. – Wait for the "Mains operation" status message to be displayed. This indicates that the inverter is in mains operation.

    – During initial start-up of the inverter, instead of the “Overview” menu, an “Initial setup” menu appears (see Section 6.2).

    6�2 Initial start-upThis section describes the initial start-up of the inverter and the graphics display set-tings required for this purpose. Once initial start-up has been successfully completed, the inverter will start feeding into the public network.

    6�2�1 Requirements■■ The inverter has been installed and is fully connected.■■ The contact protection and cover of the inverter are fitted.■■ There is sufficient solar irradiation (sufficiently high DC input voltage).■■ When operating the inverter in dual tracking mode (2 trackers) the DC bridges have to

    be removed (see Section “Configure the inverter for dual tracking operation”; page 23).

  • en

    27

    Note

    ■■ Entering an incorrect country setting may lead to problems regarding inverter operation and to the withdrawal of the operating license by the respective grid operator.

    ■■ Contact your grid operator or the SolarMax Service Center if you have any doubt regarding the settings you must select.

    ■■ You can restart initial start-up by pressing in the "Confirmation" menu at any time.

    6�2�2 Procedure1. Switch on the inverter as described in section 6.1. The "Initial setup" menu will be

    displayed:

    2. Select the display language from the "Language" menu.3. If necessary, update the time and the date.

    – The inverter saves the date entered as the initial start-up date. – The "DC input config." menu will be displayed (only with the SM4000P, SM4600P and SM5000P):

    4. Select the required setting:

    Setting Description1 Tracker The inverter has been configured for single tracking mode operation.

    The DC bridges have been fitted in the inverter (default configuration ex works).

    2 Tracker The inverter has been configured for dual tracking mode operation. The DC bridges have been removed from the inverter.

  • 28

    5. Confirm that the DC bridges have been fitted (for "1 Tracker" setting) or that the DC bridges have been removed (for "2 Tracker" setting).

    Note

    ■■ If you select the "2 Tracker" setting while the DC bridges are still in place in the inverter, you must abort the start-up at this point.

    ■■ Open the inverter as described in Section 5.1 in order to remove the DC bridges as per Section 5.4.

    ■■ You can then carry out the initial start-up.

    – The "Country" menu will be displayed:

    6. Select the correct country setting. – Press to confirm your entry. – Depending on the country setting selected, additional menus may be displayed (see Section 6.2.3).

    – The "Confirmation" menu is then displayed.7. Check the data in the "Confirmation" menu.8. To complete initial start-up, press .

    – The main menu will then be displayed (see section 7.4). – Should commissioning be taking place in Italy, the auto-test must be carried out after the initial start-up (see Section 6.3).

    6�2�3 Description of country-specific menusDepending on the country setting, additional menus will be displayed during initial start-up. This section describes these menus.

  • en

    29

    Country setting "Germany"

    Menu Setting DescriptionSystem power ≤ 3.68 kVA The maximum plant system rating is 3.68 kVA.

    > 3.68 – 13.8 kVA The plant system rating is higher than 3.68 kVA and/or does not exceed 13.8 kVA.

    > 13.8 kVA – 30 kVA The plant system rating is higher than 13.8 kVA and/or does not exceed 30 kVA.

    > 30 kVA The plant system rating is higher than 30 kVA. An external grid monitoring and remote shut-down will be used.

    I/O module* Inactive The function for the external shutdown is deactivated (EISD-ENA status: Disabled).

    On The function for the external shutdown is activated (EISD-ENA status: Enabled).

    CosPhi(Pac) - QMCPP Inactive The "cosφ(Pac)" function is deactivated (no reactive power feed-in, cosφ=1).

    On The "cosφ(Pac)" function for the feed-in / input of reactive power is activated.

    * the menu is only displayed when the optional I/O module has been fitted.

    Country setting "Great Britain"

    Menu Setting DescriptionSystem power ≤ 16 A per phase The output current is max. 16 A (inverter

    settings in accordance with standard G83/2; available only for SM2000P, SM3000P and SM4000P.)

    > 16 A per phase The output current is greater than 16 A (inverter settings in accordance with standard G59/2; available only for SM4000P, SM4600P and SM5000P).

    Country setting "Italy"

    Menu Setting DescriptionSystem power ≤ 3 kW The maximum plant system rating is 3 kW.

    > 3 kW – 6 kW The plant system rating is higher than 3 kW and/or does not exceed 6 kW.

    I/O module* Inactive Remote control of the inverter via SPI logic is deactivated (SPIL-ENA status: Disabled).

    On Remote control of the inverter via SPI logic is activated (SPIL-ENA status: Enabled).

    * the menu is only displayed when the optional I/O module has been fitted.

  • 30

    Country setting “Greece”

    Menu Setting DescriptionLocation Mainland The PV power plant is to be installed on the

    Greek mainland.Islands The PV power plant is to be installed on an

    island in Greece.

    6�3 Auto-testThe auto-test (only available in the "Italy" country setting) checks the grid monitoring of the inverter. The auto-test consists of 7 test steps in which the triggering behavior is checked in the case that the voltage and frequency limits are exceeded.

    In the auto-test, the respective limit value is successively changed until it reaches the triggering threshold (i.e. the current reading). If the grid monitoring function is working, the inverter triggers the grid monitoring. For each step of the test, the graphics display shows the current reading, the trigger value, the trip time and the set limit. During the test of the frequency limits, the activation status of the limit value is also displayed.

    The auto-test is performed automatically. Following completion of the auto-test, the inverter returns to normal operation. If an error occurs or irradiation is insufficient during the auto-test, the auto-test is aborted. In this case the message "Auto-test aborted" is shown on the display. The auto-test takes approximately 5 minutes.

    Requirements

    ■■ Sufficient solar irradiation■■ The inverter has been connected to the mains and switched on for at least 10 minutes.

    Procedure

    1. In the main menu, select the "Auto Test" menu.2. To start the auto-test, press .3. Wait for the display of the successful completion of the auto-test:

    4. Ensure that the inverter resumes normal operation (in this case the status message "Mains operation" will be shown on the graphics display).

  • en

    31

    6�4 SettingsDifferent communication parameters and monitoring functions can be set in the "Set-tings" menu of the graphics display. All settings except the IP mode can also be made using the MaxTalk service software.

    In the "Main menu" select the "Settings" menu. The settings can then be made as follows:

    back to the main menu / select parameter (e.g. "Time")

    Edit parameter

    Confirm parameter / increase number / highlight next number

    6�4�1 Setting the display language and system timeAfter initial start-up, set the display language and check the system time of the inverter.

    In the "Settings" menu, select the following parameters and enter the desired values:

    Parameter DescriptionLanguage Selection of the display language: German, English, French, Italian or

    Spanish. The display language selection does not depend on the selected country.

    Time System time of the inverterDate The date displayed by the inverter

  • 32

    6�4�2 Setting the network parameters

    Device address

    In order to communicate via RS485 or Ethernet interface the inverter needs a unique device address on the network.

    1. In the “Main menu” select the “Network” menu.2. Select the “Device address” parameter.3. Configure the parameter:

    Parameter Description Value rangeDevice address Device address of inverter 1…249

    Configuring the Ethernet interface

    In addition to the device address, the following settings must be made to communicate via Ethernet:

    1. In the “Main menu” select the “Network” menu.2. In the “IP mode”, select the required setting:

    Setting DescriptionDHCP client The inverter is a DHCP client and is connected to a network with

    DHCP server (factory setting).Static The inverter is connected to a network with static IP addresses.

    3. If appropriate, configure the following parameters. These settings are only required in “Static” IP mode (see step 2):

    Parameter Description Value rangeIP IP address 192.168.1.123*

    Gateway Gateway of inverter 192.168.1.1*TCP port TCP port of inverter 12345*DNS1 Domain name server 1 192.168.1.1*DNS2 Domain name server 2 192.168.1.1*Netmask Subnet mask 255.255.255.0** Factory settings

    4. Check whether the indicator for the Ethernet connection appears on the graphicsdisplay (see Section 7.1).

  • en

    33

    6�5 Displaying the configurationAll available operating parameters, standard-specific functions and their parameteriza-tion can be retrieved in the "Configuration" menu. Configuration of the standard-specific function depends on the country setting selected.

    Note

    MaxTalk 2 Pro allows authorized qualified technicians to adjust the operating parameters individually (see section 12).

    In the main menu, select the "Configuration" menu.

    back to main menu / select parameter or menu / confirm selection

    The following parameters and menus are available:

    Menu / parameter DescriptionCountry Country setting selected at the time of initial start-up.DC input config. Configuration selected at initial start-up: 1 tracker (single

    tracking) or 2 trackers (dual tracking, only available with SM4000P, SM4600P and SM5000P).

    System power Plant rating selected at initial start-up (only available with "Ger-many", "Italy" and "Great Britain" country settings).

    I/O module Status display of I/O module

    Location Part of country selected at initial start-up (only available with "Greece" country setting).

    SSF Menu of standard-specific functions and parameters

    To display the menus of the standard-specific functions, select "SSF". The following menus are available:

    Menu DescriptionExternal input Display of external control functions (external shutdown and

    external output control). To use these functions, the optional I/O module is required.

    Inverter start-up Those functions are displayed which are active before the inverter is connected to the network (start conditions).

    Grid operation Those functions are displayed which are active during the inverter's grid operation (grid monitoring).

  • 34

    Menu DescriptionLimitation Those functions are displayed which limit the inverter‘s output

    values, such as active and reactive powers and AC output cur-rent (output limitation).

    Reactive power Those functions are displayed that have an impact on the reac-tive power taken up or given off by the inverter (reactive power control).

    Reference parameters Display of nominal values and reference parameters.

    External input

    Function / arameter Description Unit / statusEISD Monitoring the "external shutdown" input at the I/O

    module.-

    EISD-ENA EISD function status Disabled/enabledEISD-SL "External shutdown" input logic High active /

    low activeEPC Output control by radio ripple control receiver or

    similar external control unit.-

    EPC-ENA EPC function status Disabled/enabledSPIL Remote control using SPI logic (only available with

    "Italy" country setting)-

    SPIL-ENA SPIL function status Disabled/enabledSPIL-SESL Signal logic of input "Segnale Esterno" (Input "K6"

    on I/O module)High active / low active

    SPIL-CL Logic state of "Comando Locale" 0/1SPILFM1 SPI frequency monitoring mode 1 -SPILFM1-ENA SPILFM1 function status Disabled/enabledSPILFM1-THRMIN Minimum permissible mains frequency, mode 1 HzSPILFM1-DLYMIN Tripping time sSPILFM1-THRMAX Maximum permissible mains frequency, mode 1 HzSPILFM1-DLYMAX Tripping time sSPILFM2 SPI frequency monitoring mode 2 -SPILFM2-ENA SPILFM2 function status Disabled/enabledSPILFM2-THRMIN Minimum permissible mains frequency, mode 2 HzSPILFM2-DLYMIN Tripping time s

    SPILFM2-THRMAX Maximum permissible mains frequency, mode 2 HzSPILFM2-DLYMAX Tripping time sSPILFM3 SPI frequency monitoring mode 3 -SPILFM3-ENA SPILFM3 function status Disabled/enabledSPILFM3-THRMIN Minimum permissible mains frequency, mode 3 HzSPILFM3-DLYMIN Tripping time sSPILFM3-THRMAX Maximum permissible mains frequency, mode 3 Hz

  • en

    35

    Function / arameter Description Unit / statusSPILFM3-DLYMAX Tripping time s

    Inverter start-up

    Function / parameter Description Unit / statusPVGIT Checking the insulation resistance of the PV

    generator to ground-

    PVGIT-ENA PVGIT function status Disabled/enabledPVGIT-THR Minimum permissible insulation resistance ΩRCMUT Checking the integrated fault current monitoring -RCMUT-ENA RCMUT function status Disabled/enabledIST Checking the grid relayIST-ENA IST function status Disabled/enabledGPT Checking the grid parameters -GPT-ENA GPT function status Disabled/enabledGPTVMIN-THR Minimum permissible mains voltage VGPTVMAX-THR Maximum permissible mains voltage VGPTFMIN-THR Minimum permissible mains frequency HzGPTFMAX-THR Maximum permissible mains frequency HzGPT-MOT Checking duration s

    Grid operation

    Function / parameter Description Unit / statusGVMMIN1 Checking the minimum permissible mains voltage

    (limit 1)-

    GVMMIN1-ENA GVMMIN1 function status Disabled/enabledGVMMIN1-THR Limit value VGVMMIN1-DLY Tripping time sGVMMAX1 Checking the maximum permissible mains voltage

    (limit 1)-

    GVMMAX1-ENA GVMMAX1 function status Disabled/enabledGVMMAX1-THR Limit value VGVMMAX1-DLY Tripping time sGVMMIN2 Checking the minimum permissible mains voltage

    (limit 2)-

    GVMMIN2-ENA GVMMIN2 function status Disabled/enabledGVMMIN2-THR Limit value VGVMMIN2-DLY Tripping time sGVMMAX2 Checking the maximum permissible mains voltage

    (limit 2)-

  • 36

    Function / parameter Description Unit / statusGVMMAX2-ENA GVMMAX2 function status Disabled/enabledGVMMAX2-THR Limit value VGVMMAX2-DLY Tripping time sGVM10AMAX Checking the maximum permissible average value

    for mains voltage over the last 10 minutesV

    GVM10AMAX-ENA GVM10AMAX function status Disabled/enabledGVM10AMAX-THR Limit value VGVM10AMAX-DLY Tripping time sGFMMIN1 Checking the minimum permissible mains fre-

    quency (limit 1)-

    GFMMIN1-ENA GFMMIN1 function status Disabled/enabledGFMMIN1-THR Limit value HzGFMMIN1-DLY Tripping time sGFMMAX1 Checking the maximum permissible mains fre-

    quency (limit 1)-

    GFMMAX1-ENA GFMMAX1 function status Disabled/enabledGFMMAX1-THR Limit value HzGFMMAX1-DLY Tripping time sGFMMIN2 Checking the minimum permissible mains fre-

    quency (limit 2)-

    GFMMIN2-ENA GFMMIN2 function status Disabled/enabledGFMMIN2-THR Limit value HzGFMMIN2-DLY Tripping time sGFMMAX2 Checking the maximum permissible mains fre-

    quency (limit 2)-

    GFMMAX2-ENA GFMMAX2 function status Disabled/enabledGFMMAX2-THR Limit value HzGFMMAX2-DLY Tripping time sAIS Detection of island operation -AIS-ENA AiS function status Disabled/enabledAIS-DLY Tripping time sRSCD Detection of recurring short circuits on the AC side -RSCD-ENA RSCD function status Disabled/enabledRBCM Monitoring the continuous leakage current -RBCM-ENA RBCM function status Disabled/enabledRBCM-THR Maximum permissible leakage current ARSCM Monitoring the leakage current step value -RSCM-ENA RSCM function status Disabled/enabledAOT Auto-test (only available with the "Italy" country

    setting)-

    AOT-ENA AOT function status Disabled/enabled

  • en

    37

    Function / parameter Description Unit / statusDCCIM Monitoring the DC component in the AC current -DCCIM-ENA DCCIM function status Disabled/enabledDCCIM-THR Maximum permissible DC component in AC current ADCCIM-DLY Tripping time s

    Limitation

    Function / parameter Description Unit / statusACPPL Maximum increase of the active power during grid

    connection-

    ACPPL-ENA ACPPL function status Disabled/enabledACPPL-MGDT Increase % of Pac nom/

    minACPPL-INI ACPPL at every boot Disabled/enabledACPPL-RCN ACPPL at boot after grid disconnection through

    coupler breakerDisabled/enabled

    ACPL Limit of active output power -ACPL-LMT Limit value WAPPL Limit of the apparent power -APPL-LMT Limit value VAOCL Limit of the output current -OCL-LMT Limit value APFLM2 P(f) mode 2 -PFLM2-STRTFQ Start frequency HzPFLM2-RDN Reduction of active power % of PM/HzPFLM2-RNC Increase to rated output power % of Pac nom/

    minPFLM3 P(f) mode 3 -PFLM3-STRTFQ Start frequency HzPFLM3-STOPFQ Stop frequency HzPFLM3-RDN Reduction of active power % of PM/HzPFLM3-RNC Increase to rated output power % of Pac nom/

    minPFLM3-UFQTHR Maximum permissible mains frequency HzPFLM3-LFQTHR Minimum permissible mains frequency HzPFLM3-UVTHR Maximum permissible mains voltage VPFLM3-LVTHR Minimum permissible mains voltage VPFLM3-MOT Checking duration s

  • 38

    Reactive power

    Function / parameter Description Unit / statusQMO-AM Reactive power control 0=OFFQMCQ Reactive power mode constant "Q" -QMCQ-QSV Reactive power value % of Pac nom

    [OEX/UEX]QMCQ-VLE Status of the voltage-dependent reactive power

    control hysteresis for QMCQDisabled/enabled

    QMCQ-VLIH Upper limit value of the mains voltage VQMCQ-VLOL Lower limit value of the mains voltage VQMCQ-PLE Status of the active power-dependent reactive

    power control hysteresis for QMCQDisabled/enabled

    QMCQ-PLI Upper limit value of the active power W

    QMCQ-PLO Lower limit value of the active power WQMCPP Reactive power mode "cosφ(Pac)" -QMCPP-PSP1…PSP10 Characteristic values 1 to 10 of Pac active power % of Pac nomQMCPP-CPSP1…CPSP10

    Characteristic values 1 to 10 of power factor cosφ - [UEX/OEX]

    QMCPP-VLE Status of mains voltage-dependent reactive power control hysteresis for QMCPP

    Disabled/enabled

    QMCPP-VLIH Upper limit value of the mains voltage VQMCPP-VLOL Lower limit value of the mains voltage VQMCCP Reactive power mode "cosφ" -QMCCP-CPSV cosφ value - [UEX/OEX]QMCCP-VLE Status of mains voltage-dependent reactive power

    control hysteresis for QMCCPDisabled/enabled

    QMCCP-VLIH Upper limit value of the mains voltage VQMCCP-VLOL Lower limit value of the mains voltage VQMCCP-PLE Status of active power-dependent reactive power

    control hysteresis for QMCCP-

    QMCCP-PLI Upper limit value of the active power WQMCCP-PLO Lower limit value of the active power W

    Reference parameters

    Function / parameter Description UnitNAP Rated output power (Pac nom) -NAP-VAL Value WNOC Rated output current -NOC-VAL Value AGCD Switching delay of the coupler breaker -GCD-CDLY Tripping time s

  • en

    39

    6�6 Displaying the measured valuesThe current measured inverter values can be accessed in the “Measured values” menu.

    In the main menu, select the "Measured values" menu.

    back to the main menu / scrolling measured values

    Measured value Description UnitVdc / Vdc1 / Vdc2 Input voltage / at tracker 1* / at tracker 2* V

    Idc / Idc1 / Idc2 Input current / at tracker 1* / at tracker 2* A

    Pdc / Pdc1 / Pdc2 Input power / at tracker 1* / at tracker 2* W

    Vac Mains voltage V

    Iac Output current A

    Pac Output power W

    Q Reactive power (+: overexcited / −: underexcited) var

    cosφ Power factor (OEX: overexcited / UEX: underexcited) -Frequency Mains frequency Hz

    Pac electric meter** Measured value of external energy counter W

    Temperature Equipment temperature °C

    * in dual tracking mode operation (only with the SM4000P, SM4600P and SM5000P)** is only displayed when configured accordingly

    Note

    The measured inverter values are not suitable for billing purposes or calcu-lating the efficiency. The measuring error may amount to up to ±5% depending on the measured value. Only the measured values of a calibrated electricity meter can be relied upon for billing purposes.

    MaxTalk measured values

    The following additional values can be viewed with the MaxTalk 2 service software:

    Measured value Description UnitVac 10 min 10 minute average value of the mains voltage VIac mean Mean value of output current AIerr Effective value of leakage current mA

  • 40

    Measured value Description UnitIerr DC Direct current component of leakage current mA

    6�8 Update firmwareThe inverter firmware can be updated with the help of the MaxTalk 2 service software. For further information, please refer to the MaxTalk 2 operating manual, which you can download from our website (www.solarmax.com/en/maxtalk).

    http://www.solarmax.com/en/maxtalk/

  • en

    41

    7 Operation

    7�1 Graphics displayThe graphics display shows the system values, status information, and the inverter’s fault messages. The graphics display can be used for obtaining information on the current operating status, accessing the integrated data logger and entering various settings on the inverter.

    1

    2

    3

    45

    No� Description1 Graphics display with backlighting2 Status LED: operating status display (see section 7.7)

    3 Function keys (membrane keypad)

    4 Display with Ethernet connection (link display)

    5 Display when data transfer takes place (communication).

    The function keys can be used for navigating within the menu structure:

    Symbol DescriptionSelect menu or parameter

    Edit parameter

    Highlight number (parameter editing)

    Increase highlighted number / select menu or parameter

    Confirm

    Cancel

  • 42

    7�2 Menu structure

    Main menu

    Overview

    Statistics

    Con�guration

    Information

    Measured values

    Time

    Language

    Date

    Device adress

    Days

    Months

    Years

    Total

    Reset

    Network

    IP

    IP-Mode

    Netmask

    Gateway

    TCP Port

    DNS1

    DNS2

    MF Relay

    Status relay

    Selfconsumption

    Off

    SSF

    Settings

    Grid operation

    External input

    Inverter start-up

    Limitation

    Reactive power

    Reference parameter

    SPD Monitor

    Grid Feed-In limitation***

    Pac electric meter

    Pac inverter

    Auto-test*

    I/O module**

    * only for country setting “Italy”** only if I/O module is installed *** is only displayed when con�gured accordingly

  • en

    43

    7�3 OverviewThe overview shows the most important operating data of the inverter. The graphics display automatically switches to the "Overview" if no function button is pressed for 120 seconds.

    In the main menu, select the "Overview" menu.

    Display Description19.06.2013 / 11:44:35 Date and system time of inverter (examples) Pac Current output power [W]Today Daily yield [kWh]Total Total yield since commissioning [kWh]

    Status Current operating status (see section 7.7)

    7�4 Main menuFrom the "Main menu", you can open all menus.

    In order to switch from "Overview" to the "Main menu", press any function key.

    : select menu / confirm your selection

  • 44

    7�5 StatisticsThe "Statistics" menu can be used for accessing the inverter's data logger. The data logger saves the statistics values of the past 25 years. The daily, monthly, yearly and total statistics can be displayed. All statistics values can be deleted.

    7�5�1 Displaying the daily statisticsThe daily statistics displays the statistics values for the last 31 days.

    In the "Statistics" menu, select the "Day" sub-menu.

    Select day / back to the Statistics menu

    Statistics value DescriptionYield Daily yield [kWh]Maximum Fed-in maximum power [W]

    Hours Number of operating hours in the "Mains operation" operating status

    7�5�2 Displaying the monthly statisticsThe monthly statistics displays the statistics values for the last 12 months.

    In the "Statistics" menu, select the "Month" sub-menu.

    Select month / back to the Statistics menu

    Statistics value DescriptionYield Monthly yield [kWh]Maximum Fed-in maximum power [W]

  • en

    45

    Statistics value DescriptionHours Number of operating hours in the "Mains operation" operating status

    7�5�3 Displaying the annual statisticsThe annual statistics displays the statistics values for the last 25 years.

    In the "Statistics" menu, select the "Year" sub-menu.

    : select year / back to the Statistics menu

    Statistics value DescriptionYield Annual yield [kWh]Maximum Fed-in maximum power [W]

    Hours Number of operating hours in the "Mains operation" operating status

    7�5�4 Displaying the total statisticsThe total statistics shows the statistics values since commissioning.

    In the "Statistics" menu, select the "Total" sub-menu.

    back to the Statistics menu

    Statistics value DescriptionYield Total yield [kWh]Hours Total operating hours in the operating status "Mains operation"

  • 46

    7�5�5 Deleting the statistics valuesThe statistics values of the data logger can be deleted.

    In the "Statistics" menu, select the "Reset" sub-menu.

    Note

    The deletion process cannot be undone!

    Cancel / Confirm deletion

    7�6 Displaying informationThis menu displays information about the inverter. The menu can be used to identify the inverter.

    In the main menu, select the "Information" menu.

    back to the main menu / scroll display

    Display DescriptionDevice type Inverter typeSerial No. Inverter serial numberFirmware Firmware version installed in the inverterStatus Current operating statusWarning Current warning messageCommissioning Date of initial start-upOperating hours Total operating hours in mains operationMac address Mac address of the inverter

  • en

    47

    7�7 Operating statusThe status message displayed on the graphics display describes the current operating status of the inverter. Each status message relates to one of five possible operating sta-tuses. The status LED has different colors with which to indicate one of these operating statuses.

    In addition to the status messages, the inverter also displays warnings. Warnings result from device errors or external malfunctions. The inverter continues to feed power into the mains, but it is possible that yield is reduced. Warnings are independent of the oper-ating status and are displayed on the graphics display alternately with the current status message.

    Status LED Operating status Description

    Off - Inverter is switched off

    Flashes green Booting Inverter is starting up

    Green Mains operation Mains feed-in (normal operation)

    Flashes orange - Warning → no grid disconnection

    Orange Fault External fault → grid disconnection

    Red Error Device error → grid disconnection

    Flashes red Blocked Inverter is blocked → grid disconnection

    The "Fault", "Error", and "Blocked" operating status messages, as well as the warnings, usually require certain measures to be carried out by the qualified electrician in charge (see section 8).

  • 48

    7�7�1 BootingStatus LED: flashes green

    Status message DescriptionIrradiation too low The solar irradiation or rather the available output is too low for

    mains operation.Startup… The inverter checks the internal hardware and software compo-

    nents before connecting to the mains.Restart delay The inverter delays connection to the grid (after a disconnection

    from the grid or when starting up).

    7�7�2 Mains operationThe status LED lights up green.

    Status message DescriptionMaximum power The inverter limits the in-feed power to the maximum permissible

    value. This may occur if the PV generator is oversized.Mains operation The inverter is in feed mode.Idc limitation The inverter limits the PV generator current to the maximum

    permissible value. This may occur if the PV generator is designed such that the current at Maximum Power Point (MPP) exceeds the maximum permissible input current of the inverter.

    Iac limitation The inverter limits the output current to the maximum admissible value (where the PV generator is oversized).

    Restart limitation Following an external output limitation the inverter increases the active power with a defined progression (Pac progression and/or Soft Start).

    Frequency limitation The inverter temporarily limits the active power owing to an active frequency-dependent power reduction.

    External limitation The inverter's fed-in active power is limited by external output control.

    Temperature limitation The output power is temporarily reduced in order to limit the inverter‘s temperature.

  • en

    49

    8 Troubleshooting

    8�1 SolarMax Service CenterIf you have technical questions or difficulties, our Service Center will be happy to help you. To do that we need the following information:

    ■■ Device type■■ Serial number (S/N)■■ Installation location■■ Information about the failure you are experiencing (status message, etc.)

    Contacting the SolarMax Service Center

    The contact details of the SolarMax Service Center can be found on the back of this instruction manual.

    SolarMax Produktions GmbHZur Schönhalde 10D-89352 Ellzee

    8�2 Diagnosis & measuresThe following tables describe possible actions for remedying faults. If the actions sug-gested do not correct the fault, please contact the SolarMax Service Center.

    8�2�1 General troubleshooting

    Problem Cause ActionsThe graphics display remains blank

    The DC disconnector is switched off.

    Switch on the DC disconnector.

    The irradiation is too low. Wait until irradiation is high enough.

    The strings are interrupted. Check the PV generator and eliminate the interruption.

    It is possible that the inverter is defective.

    Contact the SolarMax Service Center.

    The graphics display only flashes briefly.

    The irradiation is too low. Wait until irradiation is high enough.

  • 50

    8�2�2 WarningsThe status LED flashes orange.

    Warning Cause ActionsTemperature limitation The output power is temporarily

    reduced in order to limit the inverter‘s temperature.

    Ensure that the recommended maximum ambient temperature is not exceeded; that the cooling fins are free from dust and dirt.

    Fan failure A fan is defective or soiled. Contact the SolarMax Service Center.

    RTC error Date and time in the RTC (real-time clock) were reset due to a malfunction.

    Set the date and time (see section 6.4.1). If this problem occurs frequently, contact the SolarMax Service Center.

    Firmware mismatch The firmware versions of the inverter controllers do not match.

    Contact the SolarMax Service Center.

    Flash error An error has occurred in the flash memory.

    Contact the SolarMax Service Center.

    SPD failure An active signal is present at the "SPD Monitor" input of the I/O module (monitoring lightning protection).

    Check the external lightning protection module (or the device connected to the "SPD Monitor" input).

    Electric meter failure The communication between energy counter and inverter is interrupted.

    Check the connection cable and/or the energy counter.

    8�2�3 FaultsThe status LED lights up orange.

    Note

    MaxTalk can be used to read out the last error messages.

    Status message Cause ActionsVdc too high The DC input voltage of the

    inverter is too high.Switch off the DC discon-nector. Check the PV genera-tor’s configuration.

    Ierr too high The ground leakage current has exceeded the permissible RBCM-THR limit value. Check the PV generator.

    Ierr step too high The leakage current has exceeded the admissible RSCM step value.

    No mains There is no mains voltage. Check the AC conductor (fuses).

  • en

    51

    Status message Cause ActionsFrequency too high The mains frequency is outside

    the GFMMAX1-THR, GFMMAX2-THR or GPTFMAX-THR limit values. If this problem recurs, contact

    the grid operator in charge.Frequency too low The mains frequency is outside

    the GFMMIN1-THR, GFMMIN2-THR or GPTFMIN-THR limit values.

    Mains error The inverter detects island mode. If this problem recurs, contact the grid operator in charge.

    Vac too high The mains voltage is outside the GVMMAX1-THR, GVMMAX2-THR or GPTVMAX-THR limit values.

    If this problem recurs, contact the grid operator in charge.

    Vac too low The mains voltage is outside the GVMMIN1-THR, GVMMIN2-THR or GPTVMIN-THR limit values.

    Vac 10 min too high The maximum 10-minute average value of the mains voltage GVM10AMAX-THR is too high.

    Insulation fault DC The insulation resistance of the PV generator to ground is too low.

    Check the PV generator.

    Phase and neutral conductor are interchanged.

    Connect the AC supply conductors as described in section 5.3.

    Error ext. input 1 The external grid monitoring (NA protection / Teledistacco) has disconnected the inverter from the grid. An active signal is present at the "NA" input (external shutdown) of the I/O module.

    If this problem recurs, contact the grid operator in charge.

    8�2�4 ErrorThe status LED lights up red.

    Status message Cause ActionsDevice error (+ error code) The inverter is defective. Note the displayed two-digit

    error code and contact the SolarMax Service Center.

  • 52

    8�2�5 BlockingsThe status LED will flash red.

    Status message Cause ActionProgramar firmware The inverter's firmware is being

    updated.None. The inverter automati-cally resumes mains operation once the firmware update is complete.

    9 MaintenanceThe following maintenance work should be carried out when required:

    ■■ Regularly check the operating status of the inverter on the graphics display, see sec-tion 7.7.

    ■■ Clean the graphics display with a damp cloth. Do not use harsh or abrasive cleansingagents.

    ■■ Check the inverter for external damage. If any damage is found, inform the respective qualified electrician.

  • en

    53

    10 Decommissioning

    10�1 Instructions for inverter replacementWhen replacing the inverter, note the following:

    ■■ Before replacing the inverter, write down the total yield. The procedure for viewing the total yield is described in Section 7.5.4.

    ■■ If an I/O module was used in the existing inverter, this can be re-used in the replace-ment inverter.

    10�2 Inverter removal

    DANGER!Fatal electric shock hazard!Components within the inverter are charged with dangerously high voltage.

    ■■ Before starting inverter disassembly, the inverter must be fully discon-nected in accordance with the procedure described in this chapter.

    WARNING!Risk of injury from electric arc!Dangerous electric arcs could occur when removing live DC conductors.

    ■■ Switch off the inverter DC disconnector before removing the DC conductors.

    ATTENTION!Electrostatic discharge can damage the inverter

    ■■ Do not touch any electronic components inside the inverter.

    Procedure

    1. Switch off the external AC disconnector. – The "No grid" status message is shown on the inverter.

    2. Switch off the DC disconnector at the inverter.

    3. Use a size 2 screwdriver to remove the locking clips on the DC plugs.4. Pull out the DC conductors to fully separate the inverter from the PV generator.

  • 54

    DANGER!Fatal electric shock hazard!After the inverter has been disconnected, high residual voltages remain in the inverter for approx. 5 minutes.

    ■■ Wait 5 minutes.

    5. Loosen the two M5 screws on the cover.6. Open the inverter as described in Section 5.1.7. Use a suitable charge indicator to check that all terminals are free from voltage.

    – When all terminals are de-energized, you can remove the AC supply conductor, the second protective conductor and all communication lines from the inverter.

    CAUTION!Risk of burns due to hot casing components!

    ■■ Wait until the back of the casing has cooled down.

    8. Close the inverter: – insert the contact protection until it engages; – then tighten the cover.

    9. Remove the 2 Phillips head sheet metal screws (4.8 x 13) on the side which secure the inverter on the mounting rail.

    10. Disengage the inverter from the mounting rail.11. Remove the I/O module if there is one.

    10�3 Disposing of the inverterDispose of the inverter as indicated by the local waste disposal regulations. You can also return the inverter, at your own cost, to SolarMax Produktions GmbH for professional disposal. The contact details of the SolarMax Service Center can be found on the back of this instruction manual.

  • en

    55

    11 Technical dataSM2000P SM3000P SM4000P SM4600P SM5000P

    Input values

    MPP voltage range1) 210…480 V 310…480 V 190…480 V 240…480 V 260…480 V

    Control range 120…580 V 120…580 V 120…580 V 120…580 V 120…580 V

    Minimum DC voltage 120 V 120 V 120 V 120 V 120 V

    Maximum DC voltage 600 V 600 V 600 V 600 V 600 V

    Maximum DC current 10 A 10 A 10 + 10 A 10 + 10 A 10 + 10 A

    Number of MPP trackers

    1 1 2 2 2

    Number of string connections

    1 1 2 2 2

    Connection type Wieland PST40i1 (identical to MC4)

    Overvoltage category II

    Output values

    Rated output power2) 2 000 W 3 000 W 4 000 W 4 600 W 5 000 W

    Maximum apparent output power2)

    2 000 VA 3 000 VA 4 000 VA 4 600 VA 5 000 VA

    Maximum AC current2)

    9 A 13.5 A 17.5 A 22 A 22 A

    Nominal mains voltage / range 230 / 184 … 276 V

    Mains nominal frequency / range 50 / 45…55 Hz

    Power factor cosφ adjustable from 0.8 overexcited to 0.8 underexcitedDistortion factor at rated output power < 3 %

    Connection type Terminal 2.5…10 mm2

    Grid connection Single phase (L / N / PE)

    Power input at night 0 W

    Overvoltage category III

    Efficiency Max. efficiency 97.5 % 97.5 % 98.0 % 98.0 % 98.0 %

    Europ. Efficiency 97.0 % 97.0 % 97.5 % 97.5 % 97.5 %

    Environ-ment

    Protection rating IP 65

    Ambient temperature range (for rated power output)

    −20 to +60 °C (−20 to +45 °C)

    Max. operating level above sea level 2 000 m (without derating)

    Relative humidity 0 … 100 % (condensation)Fire protection class V0

    Environmental category

    in the open

    Suitable for wet rooms

    yes

    Degree of soiling 3

    Noise emissions < 30 dB (A) (↔ 1.5 m)

  • 56

    SM2000P SM3000P SM4000P SM4600P SM5000P

    Configura-tion

    Display Graphics display with backlighting and status LED

    Inverter topology HERIC®, transformerless

    DC disconnector integrated

    Data logger Energy yields, peak output and operating duration of the last 31 days, 12 months, 10 years / output curves of the last 7 days

    Fault current monitoring

    internal, AC/DC sensitive

    Casing / cover Aluminum / plastic ASA+PC

    Overvoltage con-ductor, DC and AC Requirement class D (VDE 0675-6) and/or type 3 (EN 61643-11)

    Stan-dards & guidelines

    CE-compliant yes3)

    EMC EN 61000-3-2 / EN 61000-3-3 / EN 61000-3-11 / EN 61000-3-12 / EN 61000-6-2 / EN 61000-6-3

    Grid connection VDE 0126-1-1 A1:2012 / VDE-AR-N 41054) / CEI 0-21 / RD 661 / RD 1699 / G83/2 / G59/2 / PPC Guide / C10/11 / EN 50438 / AS4777

    Device safety IEC/ EN 62109-1/-2

    Interfaces Data communication RS 485 / Ethernet (Plug&Play)

    Status signaling contact

    with optional I/O module

    Ripple control signal receiver

    External lightning protection

    External grid monitoring

    External energy meter

    Weight & dimensions

    Weight 17 kg 17 kg 19 kg 19 kg 19 kg

    Dimensions (W x H x D) 476 x 360 x 180 mm

    Warranty Standard 5 years / extension to 10, 15, 20 or 25 years possible

    1) for rated output power2) depending on the country setting, deviating values are possible.

    Details can be found at www.solarmax.com3) the complete conformity declaration can be found on our website at www.solarmax.com4) not for SM5000P

    http://www.solarmax.com/en/http://www.solarmax.com/en/

  • en

    57

    Efficiency curve SM5000P

    100.0

    97.5

    95.0

    92.5

    90.0

    87.50 5 102 15 20 25 30 40 50 7060 80 75 90 100

    η 260 VDC

    η 400 VDC

    η 480 VDC

    Standardised output Pac/Pac max [%]

    Ef�c

    ienc

    y η [

    %]

    Pac/Pac max [%] η 260 VDC [%] η 400 VDC [%] η 480 VDC [%]5 92.21 92.32 91.7910 95.38 96.04 95.5720 96.66 97.52 97.2230 96.89 97.83 97.6350 96.92 97.88 97.78100 96.30 97.43 97.40

    Europ. Efficiency ηEU [%] 96.52 97.46 97.30

    Efficiency curve SM4600P

    100.0

    97.5

    95.0

    92.5

    90.0

    87.50 5 102 15 20 25 30 40 50 7060 80 75 90 100

    η 260 VDC

    η 400 VDC

    η 480 VDC

    Standardised output Pac/Pac max [%]

    Ef�c

    ienc

    y η [

    %]

  • 58

    Pac/Pac max [%] η 260 VDC [%] η 400 VDC [%] η 480 VDC [%]5 92.01 92.12 91.5810 94.92 95.52 95.0320 96.51 97.38 97.0330 96.88 97.77 97.5750 96.91 97.89 97.77100 96.45 97.52 97.48

    Europ. Efficiency ηEU [%] 96.50 97.42 97.25

    Efficiency curve SM4000P

    100.0

    97.5

    95.0

    92.5

    90.0

    87.50 5 102 15 20 25 30 40 50 7060 80 75 90 100

    η 260 VDC

    η 400 VDC

    η 480 VDC

    Standardised output Pac/Pac max [%]

    Ef�c

    ienc

    y η [

    %]

    Pac/Pac max [%] η 260 VDC [%] η 400 VDC [%] η 480 VDC [%]5 92.01 92.12 91.5810 94.92 95.52 95.0320 96.51 97.38 97.0330 96.88 97.77 97.5750 96.91 97.89 97.77100 96.45 97.52 97.48

    Europ. Efficiency ηEU [%] 96.50 97.42 97.25

  • en

    59

    Temperature dependent output reduction

    The inverter can feed 100 % of its rated output for an unlimited time up to an ambient temperature of 45 °C. When operating in ambient temperatures in excess of 45 °C it is possible that the yield is reduced. For this reason excessive ambient temperature should be avoided. In the specified ambient temperature range the power output of the SM2000P will be consistent.

    110

    100

    90

    80

    70

    60−20 −10 0 10 20 30 40 45 50 60

    SM5000PSM4600PSM4000P SM3000PSM2000P

    Outp

    ut P

    ac/P

    ac n

    om [%

    ]

    Ambient temperature [°C]

    Country-specific settings

    The factory's default settings for different countries can be viewed in the technical infor-mation "SSF - Standard specific functions and parameters - Factory settings". This document can be downloaded from our website at: www.solarmax.com/en/downloads/string-inverters/p-series.

    http://www.solarmax.com/en/downloads/string-inverters/p-series/http://www.solarmax.com/en/downloads/string-inverters/p-series/

  • 60

    12 Accessories and optionsAccessory/option DescriptionI/O module Communication module with the following interfaces: status signaling

    contact for the remote control of the inverter, interfaces for the remote control and control of self-consumption of the inverter and for monitoring external lightning protection modules.

    Y-type plug connectors Set consisting of two Y-type plug connectors for the parallel connec-tion of solar modules (1 plug connector socket/socket to plug, 1 plug connector plug/plug to socket, item No. 10 005 602).

    MaxView Free web-based application with various functions for remote call-up, graphic visualization and export of yield data.

    MaxTalk Free communication and service software for local monitoring of the PV plant.

    MaxTalk Pro Professional version of MaxTalk for the configuration of inverters. The required "SolarMax P series parameter configuration using MaxTalk 2 Pro" operating manual can be downloaded from our website; www.solarmax.com ("Downloads" area).

    MaxMonitoring Using the free MaxMonitoring software, you can display the per-formance data of your photovoltaic system at any time from home. MaxMonitoring is available for PC, MacOS and Linux and also as an app for Android and iOS.

    MaxDesign Free software for determining the size of PV plants.

    You can find further information on our website at www.solarmax.com.

    13 WarrantyGeneral Terms of Guarantee for SolarMax ProductsSolarMax Productions GmbH (herafter SOLARMAX) guarantees the correct function and absence of defects of your SolarMax tools for a particular, device -specific duration of guarantee. This duration of guarantee can be prolonged by an extension of guarantee according to these Terms of Guarantee.

    http://www.solarmax.com/en/http://www.solarmax.com/en/http://www.solarmax.com/en/

  • en

    61

    This manufacturer’s guarantee exists in addition to legal warranty obligations of the vendor. In case of a content overlap, the claim under the manufacturer’s guarantee takes precedence, to the extent permitted by law, over the claim from warranty.

    For the assertion of warranty claims please contact your vendor.

    1� Basic Guarantee BASIC

    The services of the Basic Guarantee are only provided free of charge in countries released by SOLARMAX at the time of installation. Please clarify this with your dealer. You will find a current list of these countries in the appendix or on our homepage. On request we are happy to send you this list.

    a) Duration of Guarantee BASIC

    String Inverters:

    ■■ 60 months starting from purchase date, but max. 72 months after delivery of the device bySOLARMAX

    Central Inverters:

    ■■ Series C/S/TS/TS-SV: 24 months from purchase date, but max. 30 months after delivery ofdevice by SOLARMAX

    ■■ Series RX: 60 months from purchase date, but max. 66 months after delivery of device bySOLARMAX

    Accessories:

    ■■ 24 months from purchase date, but max. 30 months after delivery of device by SOLARMAX■■ Junction-Box 32HT2: 60 months from purchase date, but 72 months after delivery of device by

    SOLARMAXDeviating written confirmation from SOLARMAX have priority.

    b) Scope of Guarantee BASIC

    If a device shows a defect or malfunction within the duration of guarantee and if the conditions for the assertion of warranty as defined below are met, the device or device parts will be repaired or replaced by SOLARMAX free of charge at its discretion within an appropriate period of time, as shown below, provided that this is not disproportionate or impossible.

    Free Replacement: This contains the provision of equivalent replacement devices or parts, which can be dispatched step by step against return of the defect devices or device parts or can be also delivered by order.

    Free On-Site-Replacement: This contains material cost as well as labor and travel expenses of SOLARMAX staff or staff authorized by SOLARMAX, insofar as it was send to the operation site by SOLARMAX.

    Further-reaching claims, especially claiming the replacement of direct and indirect damages, founded by the defect of the device or cost incurred by the implementation and removal or lost profit, are not covered by this guarantee.

    2� Assurance of Repair and Replacement

    SOLARMAX will provide repair material and replacement devices during the duration of guarantee in its discretion.

  • 62

    If repair material or replacement devices for particular devices are not available anymore, the fol-lowing applies:

    SOLARMAX is authorized to install the device, which needs to be replaced, with a comparable device with an equivalent or higher performance.

    Necessary technical adjustments of the replacement device for the installation of such a replace-ment device are covered by the guarantee for expenditure of time and material to the extent of up to 10 % of the list price of the replacement device.

    Not covered by the guarantee are, if need be, a required replacement and a connection of peripheral devices as well as, if need be, required adjustments of surrounding devices of an inverter (such as supply cord, ventilation and safety devices).

    SOLARMAX does its level best to minimize the extent of adjustment.

    If there is no replacement material available at a reasonable expense, SOLARMAX is authorized to replace the defect device. In this case the above mentioned terms of replacement are applicable.

    3� Duration of Guarantee for Device Repair/ Device Replacement

    In case of repair or replacement of devices within the scope of the guarantee, the remaining duration of guarantee of the original device applies to the repaired / replaced device.

    4� Exclusion of Guarantee Services

    Especially in following cases the guarantee claim is cancelled:

    ■■ In the event of transport damage or external influences■■ In the event of interference, changes, repairs by non-SOLARMAX-authorized staff or on one’s own■■ In the event of inappropriate use, incorrect operation and installation■■ In the event of neglecting operating, installation and maintenance instructions ■■ In the event of non-compliant surrounding conditions (such as lack of ventilation, humidity, dust

    pollution, etc.) ■■ In the event of higher force (such as lightning, overvoltage, water damage, fire etc.)

    Not covered by the guarantee are wear parts, especially fuses and overvoltage protection

    5� Assertion of Guarantee

    For the assertion of the guarantee the SOLARMAX hotline must be contacted by phone or in written form and their instructions must be followed carefully.

    You will find the Hotline number for your country on our homepage.

    Please hold the series number, the article description, a short description of the defect and the purchase receipt ready.

    Transactions in order to solve guarantee cases carried out by the buyer without the coordination with and approval by SOLAR MAX will not be compensated.

    In case of neglecting this procedure SOLARMAX reserves the right to decline the delivery of of the guarantee service.

    6� Exclusion of Guarantee

    SOLARMAX reserves the right to temporarily or finally exclude the guarantee, if the parameters of the plant do not allow a proper function of the devices (e.g. in the event of a parameter as set out in number 4)

  • en

    63

    The exclusion of guarantee can be cancelled in accordance with SOLARMAX.

    Therefore it is necessary to have a written confirmation by SOLARMAX, in order to restart the guarantee terms.

    7� Guarantee Extension

    For devices with the Basic Guarantee BASIC the duration of guarantee can be prolonged by purchasing a guarantee extension within the following time periods. An extension for specific devices can be purchased on the basis of limited services. The extensions being available per device can be found on our homepage. The purchase of a guarantee extension will be confirmed by SOLARMAX with a Guarantee Certificate (Series Number of Product).

    In case of a replacement this certificate will not be adjusted to the new series number. In this way the guarantee extension stays unaffected.

    a) Time Limit for entry into Guarantee Extension

    String Inverters / Junction-Box 32HT2: The extension of the guarantee can be purchased within 60 months starting from purchase date, but within max. 72 months after delivery of the device by SOLARMAX.

    Central Inverters: The extension of the guarantee can be purchased within 3 months starting from purchase date, but max. 12 months after delivery of the device by SOLARMAX

    b) Scope of the Guarantee Extension

    The Scope of the Guarantee Extension contains all services of the Basic Guarantee BASIC.

    c) Conclusion of a Guarantee Extension

    In order to purchase a Guarantee Extension, it is necessary to fully complete and hand in a Gua-rantee Extension form.

    The Guarantee Extension is completed with a written confirmation by SOLARMAX, the receipt of the Guarantee Certificate and the payment by the customer.

    Deviating written confirmation from SOLARMAX have priority.

    8� Conditions after the Extension of the Guarantee

    The cost for repair and replacement after the extension of the guarantee period will be charged at cost. SOLARMAX ensures the repair and replacement ability beyond the guarantee period at its own discretion.

    9� Applicable Law, Place of Jurisdiction

    The Law of the Federal Republic of Germany is applicable, Place of Jurisdiction shall exclusively be Augsburg / Germany, as far as this is permitted by law.

    Appendix Country List:

    Austria, Belgium, Bulgaria, Czech Republic, Denmark, France, Germany, Greece, Italy, Liechsten-stein, Luxembourg, Netherlands, Portugal, Slovakia, Slovenia, Spain, Sweden, Switzerland, United Kingdom

    (Issued 10/2015 – subject to modifications)

  • 2018

    / 10

    en

    SolarMax Service Center

    Please refer to our website for contact details:

    www.solarmax.com

    Hotline:

    DE + 49 3733 507840

    CH + 41 315281165

    ES + 34 93 2203859

    GB + 44 20 38080346

    IT + 39 0418520076

    FR + 33 820 420 684

    Fax + 49 3733 50784 99

    Mail [email protected]

    http://www.solarmax.com/en/services-warrantymailto:hotline%40solarmax.com?subject=

    Notes on the present instruction manualScopeTarget groupsWhere to keep this manualSymbols used

    SafetyIntended useSafety instructionsSymbols on the inverter

    DescriptionIdentificationFunctionalitySafety installationsDimensionsViews of the unitBlock diagram

    InstallationTransporting and storing invertersChecking the deliverySelecting the installation locationMounting the inverter

    Electrical connectionOpening the inverterRemoving the coverRemoving the contact protection

    Connection areaConnecting the inverter to the mainsConnecting the inverter to the PV generatorNetwork connections

    CommissioningActivating the inverterInitial start-upRequirementsProcedureDescription of country-specific menus

    Auto-testSettingsSetting the display language and system timeSetting the network parameters

    Displaying the configurationDisplaying the measured valuesRegistering for MaxViewUpdate firmware

    OperationGraphics displayMenu structureOverviewMain menuStatisticsDisplaying the daily statisticsDisplaying the monthly statisticsDisplaying the annual statisticsDisplaying the total statisticsDeleting the statistics values

    Displaying informationOperating statusBootingMains operation

    TroubleshootingSolarMax Service CenterDiagnosis & measuresGeneral troubleshootingWarningsFaultsErrorBlockings

    MaintenanceDecommissioningInstructions for inverter replacementInverter removalDisposing of the inverter

    Technical dataAccessories and optionsWarranty