L 2 x 2 x 3/16" (TYP.) AT EACH GSAS CABLE JACK 1 8 " TYP. NEAREST PANEL POINT ON BOTTOM CHORD CONCENTRATED LOAD OUTSIDE PANEL POINT STEEL JOIST (SEE PLAN) EXISTING ROOF DECK C10X20 FOR ENTIRE LENGTH OF BOT. CHORD OF EXIST. JST 3/16" TYP. 3 AT 12" O.C. STAGGERED EXIST STL. JOIST TYP. GSAS CABLE JACK ASSEMBLY L 2 x 2 x 3/16" 1 8 " TYP. 1 8 " TYP. TYP. GSAS CABLE JACK ASSEMBLY COPY RIGHT & INTELLECTUAL PROPERTY NOTICE THIS PLAN SET IS COPY RIGHT PROTECTED AND CONTAINS INTELLECTUAL PROPERTY WHICH BELONGS TO ALLEN GEZELMAN PE. ACCESS IS GIVEN TO THE INFORMATION HEREON SOLELY FOR THE PURPOSE OF COMPLETION OF THE PROJECT FOR WHICH IT IS INTENDED. NO OTHER USE MAY BE MADE OF THE INFORMATION, DRAWINGS, OR IDEAS HEREON WITHOUT THE EXPRESS , WRITTEN, PERMISSION OF ALLEN GEZELMAN PE ALL AFFIDAVITS, DESIGNS, OPINIONS, CALCULATIONS & OTHER ENGINEERING SERVICES PROVIDED BY ALLEN GEZELMAN PE AND HIS ASSOCIATES ON ANY AND ALL PROJECTS ARE SUBJECT TO THE PROVISIONS OF EJCDC C-700 (ENGINEERS JOINT CONSTRUCTION DOCUMENT COMMITTEE - STANDARD GENERAL CONDITIONS OF THE CONSTRUCTION CONTRACT) CURRENT AT THE TIME. THOSE OBJECTING TO SAID EJCDC C-700 OR PROVISIONS THEREOF ARE DIRECTED NOT TO USE THE AFFIDAVIT, DESIGN, OPINION, CALCULATION OR OTHER ENGINEERING SERVICE OFFERED BY ALLEN GEZELMAN PE AND HIS ASSOCIATES ON THE PROJECT. EJCDC C-700 MAY BE VIEWED AT: HTTP://GEZELMANPE.COM/REFERENCE/AG/C-700.PDF THIS PLAN IS VOID WITHOUT MY SIGNATURE & RAISED SEAL. THIS PLAN MAY NOT BE PLACED ON FILE FOR PULLING MULTIPLE PERMITS. EACH PERMIT PULLED REQUIRES ITS OWN RAISED SEAL COPY OF THIS PLAN. ALLEN GEZELMAN 16502 HANNA RD. LUTZ, FLORIDA 33549 PH. 813 650 7246 FX. 866 397 9050 Allen@Gezelman PE.COM www.GezelmanPE.com I CERTIFY THAT THIS DESIGN & SPECIFICATIONS MEET THE REQUIREMENTS OF THE CURRENT FLORIDA BUILDING CODE AND NATIONAL ELECTRICAL CODE. INSTALLATION OF A SOLAR THERMAL SYSTEM 421 N. Woodland Blvd. DeLand, FL 32723 ROOF MOUNT DESIGNED PER: ASCE 7-05,APPLICABLE CODE: FLORIDA BUILDING CODE 2007 W/09 SUPP. EXPOSURE: WIND LOAD: BLDG. IP. CATEGORY: 120 MPH B III I CERTIFY THAT THE FRAMING OF THIS STRUCTURE WILL SAFELY ACCOMMODATE CALCULATED WIND UPLIFT AND LATERAL FORCES AND EQUIPMENT DEAD LOADS. THIS IS ATTESTED TO BY MY SIGNATURE AND SEAL ON THIS DRAWING AT THE UPPER RIGHT. THIS PLAN ADAPTS TO PLAN AS.1.3 STANDARD INSTALLATION PLAN AND PLUMBING AND PLAN DETAILS PROVIDED BY OTHERS STRUCTURAL : GRAVITY LOAD FROM SOLAR EQUIPMENT LESS THAN _ PSF WIND FORCES: ASCE 7 PRESSURE ZONE DIAGRAM (PAGE 5 AT 1ST LINK) MAY BE VIEWED AT THE FOLLOWING LINKS: http://www.unirac.com/pdf/ii227.pdf http://www.unirac.com/pdf/ii206.pdf 4 PZ1_15.9-PSF; PZ2_18.9-PSF; PZ3_18.9-PSF OWNER: VOLUSIA COUNTY FLORIDA STETSON UNIVERSITY AHJ: 1523 RIDGEWOOD AVE HOLLY HILL, FL 32117 CVC 56690 CERTIFICATION#: 1983006A FSEC CERTIFICATION#: MODULE: http://www.fsec.ucf.edu/EN/certification-testing/STcollectors/pool_ratings/tprpoolap.htm HELICOIL - HC-50 98002 01 SCALE: 1/8"=1'-0" - ROOF PLAN PROVIDED BY OTHERS ROOF LAYOUT PLAN FREEZE PROTECTION: THIS DESIGN INCORPORATES AUTOMATIC FREEZE PROTECTION. HOWEVER, THAT DOES NOT GUARANTEE 100% FREEZE PROTECTION. OWNER AND CONTRACTOR ARE ADVISED THAT, SHOULD A HARD FREEZE WARNING BE ANNOUNCED, THE BEST PROTECTION IS TO DRAIN THE SOLAR LOOP IN ADVANCE OF THE FREEZE. A LESS DRASTIC AND NORMALLY SUCCESSFUL COURSE IS TO RELY UPON THE AUTOMATIC FREEZE PROTECTION TECHNOLOGY BUILT INTO THE SYSTEM. FREEZE VALVES ON THE ROOF WILL BEGIN TO DRIBBLE WATER AT NIGHT AT 45-DEGREES FAHRENHEIT AND THAT FLOW RATE WILL INCREASE AS TEMPERATURES GET LOWER. ALSO, THE PUMP CONTROLLER WILL AUTOMATICALLY COME ON PERIODICALLY TO “WARM UP” THE COLLECTORS BY CIRCULATING WARMER WATER OFF THE BOTTOM OF THE STORAGE TANKS. AN ADDITIONAL, EASILY-IMPLEMENTED FREEZE PROTECTION ENHANCEMENT MEASURE, IS TO RUN THE CIRCULATION PUMP CONTINUOUSLY ON NEAR FREEZING NIGHTS. ALL PARTIES ARE WARNED THAT FREEZING CAN OCCUR AND IS AN OWNER RISK THAT IS NOT COVERED BY WARRANTY. CONTRACTER RESPONSIBLE TO VERIFY THE FIT OF THIS ARRAY PRIOR TO INSTALLATION: THE SOLAR MODULE ARRAY SHOWN HERE IS BASED ON THE FIELD DATA PROVIDED BY THE CONTRACTOR. CONTRACTOR SHALL CONTACT THE ENGINEER IF THE ARRAY MAY NOT FIT AS PROJECTED AND CHANGES TO LOCATION AND STRINGS MAY BE NEEDED. STETSON-HOLLIS POOL, SOLAR HEATER INSTALLATION NOTES: 1. THIS PLAN SPECIFIES THE REQUIREMENTS FOR INSTALLING A SOLAR POOL HEATING SYSTEM CONSISTING OF APPROXIMATELY ONE HUNDRED, HELIOCOL 50, COLLECTORS (PANELS) ON THE FLAT ROOF BUILDING (ADJACENT TO THE STETSON UNIVERSITY HOLLIS SWIMMING POOL) AND CONNECTING SOLAR POOL HEATING SYSTEM TO SWIMMING POOL PLUMBING. 2. HELIOCOL 50, FSEC-CERTIFIED PANELS HTTP://WWW.FSEC.UCF.EDU/EN/CERTIFICATION-TESTING/STCOLLECTORS/POOL_RATINGS/TPRPOOLAP.HTM , SHALL BE MOUNTED ON THE ROOF(S) AS INDICATED IN FIGURE 01 3. GRAVITY LOAD FROM THE SOLAR POOL HEATING SYSTEM IS NEGLIGABLE. 4. THE DESIGN WIND SPEED FOR THIS INSTALLATION IS 120-MPH, EXPOSURE CATEGORY “B”, BUILDING IMPORTANCE III. UPLIFT IS THE ONLY WIND FORCE OF CONSEQUENCE. DESIGN WIND FORCES ON SOLAR ARE: 20-PSF. CALCULATED WIND FORCES ARE PZ1_15.9-PSF; PZ2_18.9-PSF; PZ3_18.9-PSF. WIDTH OF PZ2 IS 8-FT. PZ3 (ROOF CORNER AREAS) ARE 8-FT SQUARE. SOUTH EAST AND NORTH EAST ROOF CORNERS ARE TREATED AS PZ2 BECAUSE OF PARAPET HEIGHT AT THOSE LOCATIONS. 5. PANEL LAY OUT ON ROOF SHALL BE PER FIGURE 01 6. CONTROL PLUMBING SHALL BE PER FIGURE 01/P.10 7. PER FLORIDA MECHANICAL CODE, SOLAR POOL HEATING EQUIPMENT SHALL BE INSTALLED TO PREVENT DAMAGE FROM FREEZING. METHODOLOGY MAY BE BY DRAINDOWN (MANUAL OR AUTOMATIC), OR BY RECIRCULATION, OR THRU USE OF FREEZE PROTECTION BLEED VALVES, OR BY A COMBINATION OF THESE METHODS TO BE SELECTED BY OWNER & CONTRACTOR. 8. CONTRACTORS (BOTH SOLAR & ROOFING) SHALL ADHERE TO REQUIREMENTS OF FBC CHAPTER 15 (ROOFING) AND BEST PRACTICES OF THE NRCA ROOFING & WATERPROOFING MANUAL TO ENSURE THAT THE SOLAR INSTALLATION DOES NOT CAUSE ROOF LEAKS AT INITIAL INSTALLATION OR AS THE SYSTEM “AGES”. 9. OWNER, AHJ, CONTRACTOR, AND OTHERS HAVING QUESTIONS MAY CONTACT ENGINEER OF RECORD DIRECTLY - OFFICE: 813 909 1956; CELL: 813 650 7246; FAX: 866 397 9050; E-MAIL: [email protected] SHEET NO: PUBLISHED: SHEET NAME: DRAWN: CHECKED: SB AG REVISIONS: THIS PLAN IS ONLINE FOR REVIEW @: WWW.GEZELMANPE.COM/ST0109S_STETSON_DELAND_FL CONTACT DESIGN TEAM CONTACT @ WWW.GEZELMANPE.COM CLICK HERE IF PDF VERSION OF THIS PLAN 03 SCALE: N.T.S. GSAS - CABLE JACK ASSEMBLY CONTRACTOR: WATERPROOFING OF SOLAR ROOF PENETRATIONS IS RESPONSIBILITY OF ROOFING CONTRACTOR IN COORDINATION WITH ROOFING SYSTEM MANUFACTURER. 05 SCALE: N.T.S. TYP. HC 50 PANEL 06 SCALE: N.T.S ACTUAL ROOF PHOTOGRAPH 07 SCALE: N.T.S AERIAL PHOTOGRAPGH INSTALLATION AREA 304 STAINLESS STEEL WIRE ROPE 3/16", 7X19, 1000 FT REEL OR EQUAL. SPECIFICATION AND LINK: HTTP://WWW.PAMBINAIMPEX.COM/SERVLET/DETAIL?NO=348 04 SCALE: N.T.S. http://www.pambinaimpex.com/servlet/Detail?no=348 HOLD DOWN CABLE STANDARD WEIGHT 3-INCH PIPE, PROVIDES ADEQUATE CLEARANCE TO SLIDE GSAS CABLE JACK OVER FLASHED 2-INCH PIPE NIPPLE COMING UP FROM ROOF DECK. CONTRACTOR SHALL SPRAY ALL THREADS, NUTS,NICKS, BARE STEEL W/ COLD GALVANIZING. GENERAL CONCEPT OWNER/CONTRACTOR FABRICATE &SUBMIT FOR EOR APPROVAL. 02 SCALE: 3/4" = 1'-0" JOIST REINFORCEMENT SYMBOL INDICATES TRUSSES TO RECEIVE ADDITIONAL C- CHANNEL AS SHOWN ABOVE. STRUCTURAL NOTES: A. COORDINATE SPECIAL JOISTS LOCATIONS WITH SOLAR PANELS LOCATIONS AND FIELD CONDITIONS AS SHOWN ON LAYOUT. B. COORDINATE SPECIAL JOISTS MODIFICATIONS WITH JOISTS MANUFACTURER REQUIREMENTS. NOTIFY E.O.R IMMEDIATELY OF ANY CONFLICT OR DISCREPANCY. C. STRUCTURAL STEEL AND WELDING SHALL COMPLY WITH THE REQUIREMENTS OF THE LATEST EDITIONS OF: “ALLOWABLE STRESS DESIGN (ASD), AMERICAN INSTITUTE OF STEEL CONSTRUCTION (AISC)” AND “AMERICAN WELDING SOCIETY (AWS)”. D. WELDS NOT SPECIFIED SHALL BE FILLET WELD WITH THICKNESS EQUAL TO 1/16” LESS THE LEAST THICK MEMBER. ALL WELDS SHALL BE CLEANED AND PAINTED. E. STRUCTURAL STEEL MEMBERS SHALL RECEIVE AT LEAST ONE COAT OF SHOP PRIMER PAINT AS PER THE STEEL STRUCTURES PAINTING COUNCIL (SSPC). REFER TO OWNER FOR SPECIFICATIONS OF PREFERRED COLOR.

SOLAR THERMAL SYSTEM - gezelmanpe.com · design, opinion, calculation or other engineering service offered by allen gezelman pe and his associates on ... hollis swimming pool)

  • Upload
    doquynh

  • View
    229

  • Download
    0

Embed Size (px)

Citation preview

L 2 x 2 x 3/16"

(TYP.) AT EACH GSAS

CABLE JACK

18"

TYP. NEAREST PANEL POINT ON

BOTTOM CHORD

CONCENTRATED LOAD

OUTSIDE PANEL POINT

STEEL JOIST

(SEE PLAN)

EXISTING ROOF DECK

C10X20 FOR ENTIRE

LENGTH OF BOT. CHORD

OF EXIST. JST3/16"

TYP.

3 AT 12" O.C.

STAGGERED

EXIST STL. JOIST

TYP. GSAS

CABLE JACK

ASSEMBLY

L 2 x 2 x 3/16"

18"

TYP.

18"

TYP.

TYP. GSAS

CABLE JACK

ASSEMBLY

C

OP

Y R

IGH

T &

IN

TE

LLE

CT

UA

L P

RO

PE

RT

Y N

OT

ICE

•T

HIS

PLA

N S

ET

IS

CO

PY

RIG

HT

PR

OT

EC

TE

D A

ND

CO

NT

AIN

S I

NT

ELL

EC

TU

AL

PR

OP

ER

TY

WH

ICH

BE

LON

GS

TO

ALL

EN

GE

ZE

LMA

N P

E.

•A

CC

ES

S I

S G

IVE

N T

O T

HE

IN

FO

RM

AT

ION

HE

RE

ON

SO

LELY

FO

R T

HE

PU

RP

OS

E O

F C

OM

PLE

TIO

N O

F T

HE

PR

OJE

CT

FO

R W

HIC

H I

T I

S I

NT

EN

DE

D.

•N

O O

TH

ER

US

E M

AY

BE

MA

DE

OF

TH

E I

NF

OR

MA

TIO

N,

DR

AW

ING

S,

OR

ID

EA

S H

ER

EO

N W

ITH

OU

T T

HE

EX

PR

ES

S,

WR

ITT

EN,

PE

RM

ISS

ION

OF

ALL

EN

GE

ZE

LMA

N P

E

ALL AFFIDAVITS, DESIGNS, OPINIONS, CALCULATIONS & OTHER ENGINEERING SERVICES PROVIDED BY ALLEN GEZELMAN PE AND

HIS ASSOCIATES ON ANY AND ALL PROJECTS ARE SUBJECT TO THE PROVISIONS OF EJCDC C-700 (ENGINEERS JOINT

CONSTRUCTION DOCUMENT COMMITTEE - STANDARD GENERAL CONDITIONS OF THE CONSTRUCTION CONTRACT) CURRENT ATTHE TIME. THOSE OBJECTING TO SAID EJCDC C-700 OR PROVISIONS THEREOF ARE DIRECTED NOT TO USE THE AFFIDAVIT,DESIGN, OPINION, CALCULATION OR OTHER ENGINEERING SERVICE OFFERED BY ALLEN GEZELMAN PE AND HIS ASSOCIATES ON

THE PROJECT. EJCDC C-700 MAY BE VIEWED AT: HTTP://GEZELMANPE.COM/REFERENCE/AG/C-700.PDF

THIS PLAN IS VOID WITHOUT MY SIGNATURE & RAISED SEAL.THIS PLAN MAY NOT BE PLACED ON FILE FOR PULLING MULTIPLE PERMITS.EACH PERMIT PULLED REQUIRES ITS OWN RAISED SEAL COPY OF THIS PLAN.

ALLEN GEZELMAN16502 HANNA RD.LUTZ, FLORIDA 33549

PH. 813 650 7246FX. 866 397 9050Allen@Gezelman PE.COM

www.GezelmanPE.com

I CERTIFY THAT THIS DESIGN &SPECIFICATIONS MEET THEREQUIREMENTS OF THE CURRENTFLORIDA BUILDING CODE ANDNATIONAL ELECTRICAL CODE.

INS

TA

LLA

TIO

N O

F A

SO

LAR

TH

ER

MA

L S

YS

TE

M4

21

N.

Wo

od

lan

d B

lvd

. D

eLa

nd

, F

L 3

27

23

RO

OF

MO

UN

T

DESIGNED PER: ASCE 7-05,APPLICABLE CODE:

FLORIDA BUILDING CODE 2007 W/09 SUPP.EXPOSURE:

WIND LOAD:

BLDG. IP. CATEGORY:

120 MPHB

III

I CERTIFY THAT THE FRAMING OF THIS STRUCTURE WILL SAFELY ACCOMMODATE CALCULATED WIND UPLIFT AND LATERAL FORCES ANDEQUIPMENT DEAD LOADS. THIS IS ATTESTED TO BY MY SIGNATURE AND SEAL ON THIS DRAWING AT THE UPPER RIGHT.

THIS PLAN ADAPTS TO PLAN AS.1.3 STANDARD INSTALLATION PLAN AND PLUMBING AND PLAN DETAILS PROVIDED BY OTHERS

STRUCTURAL: GRAVITY LOAD FROM SOLAR EQUIPMENT LESS THAN _ PSFWIND FORCES:

ASCE 7 PRESSURE ZONE DIAGRAM (PAGE 5 AT 1ST LINK) MAY BE VIEWED AT THE FOLLOWING LINKS:

http://www.unirac.com/pdf/ii227.pdf http://www.unirac.com/pdf/ii206.pdf

4PZ1_15.9-PSF; PZ2_18.9-PSF; PZ3_18.9-PSF

OWNER:

VOLUSIA COUNTY FLORIDA

STETSON UNIVERSITY

AHJ:

1523 RIDGEWOOD AVE

HOLLY HILL, FL 32117

CVC 56690

CERTIFICATION#: 1983006A

FSEC CERTIFICATION#:MODULE:http://www.fsec.ucf.edu/EN/certification-testing/STcollectors/pool_ratings/tprpoolap.htm

HELICOIL - HC-50

98002

01SCALE: 1/8"=1'-0" - ROOF PLAN PROVIDED BY OTHERS

ROOF LAYOUT PLAN

FREE

ZE

PR

OT

EC

TIO

N:

TH

IS D

ES

IGN

IN

CO

RP

OR

AT

ES

AU

TO

MA

TIC

FR

EE

ZE

PR

OT

EC

TIO

N.

HO

WE

VE

R,

TH

AT

DO

ES

NO

T G

UA

RA

NT

EE

10

0%

FR

EE

ZE

PR

OT

EC

TIO

N.

OW

NE

R A

ND

CO

NT

RA

CT

OR

AR

E A

DV

ISE

D T

HA

T,

SH

OU

LD A

HA

RD

FR

EE

ZE

WA

RN

ING

BE

AN

NO

UN

CE

D,

TH

E B

EST

PR

OT

EC

TIO

N I

S T

O D

RA

IN T

HE

SO

LAR

LO

OP

IN

AD

VA

NC

E O

F T

HE

FR

EE

ZE

. A

LESS

DR

AS

TIC

AN

D N

OR

MA

LLY

SU

CC

ES

SFU

L C

OU

RSE

IS

TO

RE

LY U

PO

N T

HE

AU

TO

MA

TIC

FR

EE

ZE

PR

OT

EC

TIO

N T

EC

HN

OLO

GY

BU

ILT

IN

TO

TH

E S

YS

TE

M.

FR

EE

ZE

VA

LVE

S O

N T

HE

RO

OF

WIL

L B

EG

IN T

O D

RIB

BLE

WA

TE

R A

T N

IGH

T A

T 4

5-D

EG

RE

ES

FA

HR

EN

HE

IT A

ND

TH

AT

FLO

W R

AT

E W

ILL

INC

RE

ASE

AS

TE

MP

ER

AT

UR

ES

GE

T L

OW

ER

. A

LSO

, T

HE

PU

MP

CO

NT

RO

LLE

R W

ILL

AU

TO

MA

TIC

ALL

Y C

OM

E O

N P

ER

IOD

ICA

LLY

TO

“W

AR

M U

P”

TH

E C

OLL

EC

TO

RS

BY

CIR

CU

LAT

ING

WA

RM

ER

WA

TE

R O

FF

TH

E B

OT

TO

M O

F T

HE

ST

OR

AG

ET

AN

KS.

AN

AD

DIT

ION

AL,

EA

SIL

Y-I

MP

LEM

EN

TE

D F

RE

EZ

E P

RO

TE

CT

ION

EN

HA

NC

EM

EN

T

ME

AS

UR

E,

IS T

O R

UN

TH

E C

IRC

ULA

TIO

N P

UM

P C

ON

TIN

UO

USLY

ON

NE

AR

FR

EE

ZIN

GN

IGH

TS

. A

LL P

AR

TIE

S A

RE

WA

RN

ED

TH

AT

FR

EE

ZIN

G C

AN

OC

CU

R A

ND

IS A

N O

WN

ER

RIS

K T

HA

T I

S N

OT

CO

VE

RE

D B

Y W

AR

RA

NT

Y.

CONTRACTER RESPONSIBLE TO VERIFY THE FIT OF THIS ARRAY PRIOR TOINSTALLATION: THE SOLAR MODULE ARRAY SHOWN HERE IS BASED ONTHE FIELD DATA PROVIDED BY THE CONTRACTOR. CONTRACTOR SHALLCONTACT THE ENGINEER IF THE ARRAY MAY NOT FIT AS PROJECTED ANDCHANGES TO LOCATION AND STRINGS MAY BE NEEDED.

STETSON-HOLLIS POOL, SOLAR HEATER INSTALLATION NOTES:

1. THIS PLAN SPECIFIES THE REQUIREMENTS FOR INSTALLING A SOLAR POOL HEATING SYSTEM CONSISTING OF APPROXIMATELY

ONE HUNDRED, HELIOCOL 50, COLLECTORS (PANELS) ON THE FLAT ROOF BUILDING (ADJACENT TO THE STETSON UNIVERSITY

HOLLIS SWIMMING POOL) AND CONNECTING SOLAR POOL HEATING SYSTEM TO SWIMMING POOL PLUMBING.

2. HELIOCOL 50, FSEC-CERTIFIED PANELS

HTTP://WWW.FSEC.UCF.EDU/EN/CERTIFICATION-TESTING/STCOLLECTORS/POOL_RATINGS/TPRPOOLAP.HTM , SHALL BE

MOUNTED ON THE ROOF(S) AS INDICATED IN FIGURE 01

3. GRAVITY LOAD FROM THE SOLAR POOL HEATING SYSTEM IS NEGLIGABLE.

4. THE DESIGN WIND SPEED FOR THIS INSTALLATION IS 120-MPH, EXPOSURE CATEGORY “B”, BUILDING IMPORTANCE III. UPLIFT IS

THE ONLY WIND FORCE OF CONSEQUENCE. DESIGN WIND FORCES ON SOLAR ARE: 20-PSF. CALCULATED WIND FORCES ARE

PZ1_15.9-PSF; PZ2_18.9-PSF; PZ3_18.9-PSF. WIDTH OF PZ2 IS 8-FT. PZ3 (ROOF CORNER AREAS) ARE 8-FT SQUARE. SOUTH EAST

AND NORTH EAST ROOF CORNERS ARE TREATED AS PZ2 BECAUSE OF PARAPET HEIGHT AT THOSE LOCATIONS.

5. PANEL LAY OUT ON ROOF SHALL BE PER FIGURE 01

6. CONTROL PLUMBING SHALL BE PER FIGURE 01/P.10

7. PER FLORIDA MECHANICAL CODE, SOLAR POOL HEATING EQUIPMENT SHALL BE INSTALLED TO PREVENT DAMAGE FROM

FREEZING. METHODOLOGY MAY BE BY DRAINDOWN (MANUAL OR AUTOMATIC), OR BY RECIRCULATION, OR THRU USE OF

FREEZE PROTECTION BLEED VALVES, OR BY A COMBINATION OF THESE METHODS TO BE SELECTED BY OWNER & CONTRACTOR.

8. CONTRACTORS (BOTH SOLAR & ROOFING) SHALL ADHERE TO REQUIREMENTS OF FBC CHAPTER 15 (ROOFING) AND BEST

PRACTICES OF THE NRCA ROOFING & WATERPROOFING MANUAL TO ENSURE THAT THE SOLAR INSTALLATION DOES NOT CAUSE

ROOF LEAKS AT INITIAL INSTALLATION OR AS THE SYSTEM “AGES”.

9. OWNER, AHJ, CONTRACTOR, AND OTHERS HAVING QUESTIONS MAY CONTACT ENGINEER OF RECORD DIRECTLY

- OFFICE: 813 909 1956; CELL: 813 650 7246; FAX: 866 397 9050; E-MAIL: [email protected]

SHEET NO:

PUBLISHED:

SHEET NAME:

DRAWN: CHECKED:SB AG

REVISIONS:

THIS PLAN IS ONLINE FOR REVIEW @:WWW.GEZELMANPE.COM/ST0109S_STETSON_DELAND_FL

C O N T A C T D E S I G N T E A MCONTACT @ WWW.GEZELMANPE.COM

CLICK HERE IF PDF VERSION OF THIS PLAN

03SCALE: N.T.S.

GSAS - CABLE JACK ASSEMBLY

CONTRACTOR:

WATERPROOFING OF SOLAR ROOFPENETRATIONS IS RESPONSIBILITY OFROOFING CONTRACTOR IN COORDINATIONWITH ROOFING SYSTEM MANUFACTURER.

05SCALE: N.T.S.

TYP. HC 50 PANEL 06

SCALE: N.T.S

ACTUAL ROOF PHOTOGRAPH07

SCALE: N.T.S

AERIAL PHOTOGRAPGH

INSTALLATION AREA

304 STAINLESS STEEL WIRE ROPE 3/16", 7X19,1000 FT REEL OR EQUAL.

SPECIFICATION AND LINK:HTTP://WWW.PAMBINAIMPEX.COM/SERVLET/DETAIL?NO=348

04SCALE: N.T.S. http://www.pambinaimpex.com/servlet/Detail?no=348

HOLD DOWN CABLE

STANDARD WEIGHT 3-INCH PIPE, PROVIDES ADEQUATE CLEARANCE TO SLIDE GSASCABLE JACK OVER FLASHED 2-INCH PIPE NIPPLE COMING UP FROM ROOF DECK.

CONTRACTOR SHALL SPRAY ALL THREADS, NUTS,NICKS, BARE STEEL W/ COLDGALVANIZING.

GENERAL CONCEPT OWNER/CONTRACTOR FABRICATE&SUBMIT FOR EOR APPROVAL.

02SCALE: 3/4" = 1'-0"

JOIST REINFORCEMENT

SYMBOL INDICATES TRUSSES TO RECEIVEADDITIONAL C- CHANNEL AS SHOWN ABOVE.

STRUCTURAL NOTES:

A. COORDINATE SPECIAL JOISTS LOCATIONS WITH SOLAR PANELS LOCATIONS AND FIELD CONDITIONS AS SHOWNON LAYOUT.

B. COORDINATE SPECIAL JOISTS MODIFICATIONS WITH JOISTS MANUFACTURER REQUIREMENTS. NOTIFY E.O.RIMMEDIATELY OF ANY CONFLICT OR DISCREPANCY.

C. STRUCTURAL STEEL AND WELDING SHALL COMPLY WITH THE REQUIREMENTS OF THE LATEST EDITIONS OF:

“ALLOWABLE STRESS DESIGN (ASD), AMERICAN INSTITUTE OF STEEL CONSTRUCTION (AISC)” AND “AMERICAN

WELDING SOCIETY (AWS)”.

D. WELDS NOT SPECIFIED SHALL BE FILLET WELD WITH THICKNESS EQUAL TO 1/16” LESS THE LEAST THICKMEMBER. ALL WELDS SHALL BE CLEANED AND PAINTED.

E. STRUCTURAL STEEL MEMBERS SHALL RECEIVE AT LEAST ONE COAT OF SHOP PRIMER PAINT AS PER THE STEEL

STRUCTURES PAINTING COUNCIL (SSPC). REFER TO OWNER FOR SPECIFICATIONS OF PREFERRED COLOR.

05

01

02

02

03

01

06

04

10

01

DISCHARGE TO POOL INTAKE FROM D.E. FILTERS

VACUUM RELIEF

01

01

02

04

11

05

07

THERMOMETER

03

04

05

SENSOR

BALL VALVE

06

07

08

09CHECK VALVE

3-WAY VALVE

WATER SENSOR

FILTER

08 09

10

PUMP

AUXILLARY HEATER

11

GENERAL NOTE: ALL OPTIONAL EXCEPT FOR # 08 & #09

ALL OPTIONAL EXCEPTFOR # 08 & #09

Ø 2" Ø 2-1/2" Ø 3"

Ø 4"

Ø 6"

Ø 6"

Ø 2"Ø 2-1/2"Ø 3"Ø

4"

Ø 4"

Ø 2" Ø 2"

Ø 2"

Ø 2"

Ø 2" Ø 2"

Ø 2"

Ø 2"

Ø 2"

SUPPLY

RETURN

DRAIN DOWN DIRECTION

C

OP

Y R

IGH

T &

IN

TE

LLE

CT

UA

L P

RO

PE

RT

Y N

OT

ICE

•T

HIS

PLA

N S

ET

IS

CO

PY

RIG

HT

PR

OT

EC

TE

D A

ND

CO

NT

AIN

S I

NT

ELL

EC

TU

AL

PR

OP

ER

TY

WH

ICH

BE

LON

GS

TO

ALL

EN

GE

ZE

LMA

N P

E.

•A

CC

ES

S I

S G

IVE

N T

O T

HE

IN

FO

RM

AT

ION

HE

RE

ON

SO

LELY

FO

R T

HE

PU

RP

OS

E O

F C

OM

PLE

TIO

N O

F T

HE

PR

OJE

CT

FO

R W

HIC

H I

T I

S I

NT

EN

DE

D.

•N

O O

TH

ER

US

E M

AY

BE

MA

DE

OF

TH

E I

NF

OR

MA

TIO

N,

DR

AW

ING

S,

OR

ID

EA

S H

ER

EO

N W

ITH

OU

T T

HE

EX

PR

ES

S,

WR

ITT

EN,

PE

RM

ISS

ION

OF

ALL

EN

GE

ZE

LMA

N P

E

ALL AFFIDAVITS, DESIGNS, OPINIONS, CALCULATIONS & OTHER ENGINEERING SERVICES PROVIDED BY ALLEN GEZELMAN PE AND

HIS ASSOCIATES ON ANY AND ALL PROJECTS ARE SUBJECT TO THE PROVISIONS OF EJCDC C-700 (ENGINEERS JOINT

CONSTRUCTION DOCUMENT COMMITTEE - STANDARD GENERAL CONDITIONS OF THE CONSTRUCTION CONTRACT) CURRENT ATTHE TIME. THOSE OBJECTING TO SAID EJCDC C-700 OR PROVISIONS THEREOF ARE DIRECTED NOT TO USE THE AFFIDAVIT,DESIGN, OPINION, CALCULATION OR OTHER ENGINEERING SERVICE OFFERED BY ALLEN GEZELMAN PE AND HIS ASSOCIATES ON

THE PROJECT. EJCDC C-700 MAY BE VIEWED AT: HTTP://GEZELMANPE.COM/REFERENCE/AG/C-700.PDF

THIS PLAN IS VOID WITHOUT MY SIGNATURE & RAISED SEAL.THIS PLAN MAY NOT BE PLACED ON FILE FOR PULLING MULTIPLE PERMITS.EACH PERMIT PULLED REQUIRES ITS OWN RAISED SEAL COPY OF THIS PLAN.

ALLEN GEZELMAN16502 HANNA RD.LUTZ, FLORIDA 33549

PH. 813 650 7246FX. 866 397 9050Allen@Gezelman PE.COM

www.GezelmanPE.com

I CERTIFY THAT THIS DESIGN &SPECIFICATIONS MEET THEREQUIREMENTS OF THE CURRENTFLORIDA BUILDING CODE ANDNATIONAL ELECTRICAL CODE.

INS

TA

LLA

TIO

N O

F A

SO

LAR

TH

ER

MA

L S

YS

TE

M4

21

N.

Wo

od

lan

d B

lvd

. D

eLa

nd

, F

L 3

27

23

RO

OF

MO

UN

T

DESIGNED PER: ASCE 7-05,APPLICABLE CODE:

FLORIDA BUILDING CODE 2007 W/09 SUPP.EXPOSURE:

WIND LOAD:

BLDG. IP. CATEGORY:

120 MPHB

III

I CERTIFY THAT THE FRAMING OF THIS STRUCTURE WILL SAFELY ACCOMMODATE CALCULATED WIND UPLIFT AND LATERAL FORCES ANDEQUIPMENT DEAD LOADS. THIS IS ATTESTED TO BY MY SIGNATURE AND SEAL ON THIS DRAWING AT THE UPPER RIGHT.

THIS PLAN ADAPTS TO PLAN AS.1.3 STANDARD INSTALLATION PLAN AND PLUMBING AND PLAN DETAILS PROVIDED BY OTHERS

STRUCTURAL: GRAVITY LOAD FROM SOLAR EQUIPMENT LESS THAN _ PSFWIND FORCES:

ASCE 7 PRESSURE ZONE DIAGRAM (PAGE 5 AT 1ST LINK) MAY BE VIEWED AT THE FOLLOWING LINKS:

http://www.unirac.com/pdf/ii227.pdf http://www.unirac.com/pdf/ii206.pdf

4PZ1_15.9-PSF; PZ2_18.9-PSF; PZ3_18.9-PSF

OWNER:

VOLUSIA COUNTY FLORIDA

STETSON UNIVERSITY

AHJ:

CERTIFICATION#: 1983006A

FSEC CERTIFICATION#:MODULE:http://www.fsec.ucf.edu/EN/certification-testing/STcollectors/pool_ratings/tprpoolap.htm

HELICOIL - HC-50

98002

01SCALE: 1/8"=1'-0" - ROOF PLAN PROVIDED BY OTHERS

HYDRAULIC PLAN-SCHEMATIC

FREE

ZE

PR

OT

EC

TIO

N:

TH

IS D

ES

IGN

IN

CO

RP

OR

AT

ES

AU

TO

MA

TIC

FR

EE

ZE

PR

OT

EC

TIO

N.

HO

WE

VE

R,

TH

AT

DO

ES

NO

T G

UA

RA

NT

EE

10

0%

FR

EE

ZE

PR

OT

EC

TIO

N.

OW

NE

R A

ND

CO

NT

RA

CT

OR

AR

E A

DV

ISE

D T

HA

T,

SH

OU

LD A

HA

RD

FR

EE

ZE

WA

RN

ING

BE

AN

NO

UN

CE

D,

TH

E B

EST

PR

OT

EC

TIO

N I

S T

O D

RA

IN T

HE

SO

LAR

LO

OP

IN

AD

VA

NC

E O

F T

HE

FR

EE

ZE

. A

LESS

DR

AS

TIC

AN

D N

OR

MA

LLY

SU

CC

ES

SFU

L C

OU

RSE

IS

TO

RE

LY U

PO

N T

HE

AU

TO

MA

TIC

FR

EE

ZE

PR

OT

EC

TIO

N T

EC

HN

OLO

GY

BU

ILT

IN

TO

TH

E S

YS

TE

M.

FR

EE

ZE

VA

LVE

S O

N T

HE

RO

OF

WIL

L B

EG

IN T

O D

RIB

BLE

WA

TE

R A

T N

IGH

T A

T 4

5-D

EG

RE

ES

FA

HR

EN

HE

IT A

ND

TH

AT

FLO

W R

AT

E W

ILL

INC

RE

ASE

AS

TE

MP

ER

AT

UR

ES

GE

T L

OW

ER

. A

LSO

, T

HE

PU

MP

CO

NT

RO

LLE

R W

ILL

AU

TO

MA

TIC

ALL

Y C

OM

E O

N P

ER

IOD

ICA

LLY

TO

“W

AR

M U

P”

TH

E C

OLL

EC

TO

RS

BY

CIR

CU

LAT

ING

WA

RM

ER

WA

TE

R O

FF

TH

E B

OT

TO

M O

F T

HE

ST

OR

AG

ET

AN

KS.

AN

AD

DIT

ION

AL,

EA

SIL

Y-I

MP

LEM

EN

TE

D F

RE

EZ

E P

RO

TE

CT

ION

EN

HA

NC

EM

EN

T

ME

AS

UR

E,

IS T

O R

UN

TH

E C

IRC

ULA

TIO

N P

UM

P C

ON

TIN

UO

USLY

ON

NE

AR

FR

EE

ZIN

GN

IGH

TS

. A

LL P

AR

TIE

S A

RE

WA

RN

ED

TH

AT

FR

EE

ZIN

G C

AN

OC

CU

R A

ND

IS A

N O

WN

ER

RIS

K T

HA

T I

S N

OT

CO

VE

RE

D B

Y W

AR

RA

NT

Y.

EQUIPMENT LIST:

2- GOULDS/ MARLOW MODEL M4P1A22H5AOBCE SELF PRIMING COMMERCIAL PUMPS

208-3-60 / 20HP / 1800 RPM / TEFC PREMIUM EFFICIENCY PUMPS500 GPM @ 75 TDH

2- ELECTRIC WATER TO AIR POOL HEAT PUMPSBASES OF DESIGN AQUACAL MODEL SQ 155 OR APPROVED EQUAL208 -3-60

MOTOR OPERATED TRANSITION VALVES:2 - OR QUANTITY AS REQUIRED SHALL BE MANUFACTURED BY BELIMO - BFV'S OR BALL AS NEEDED

24 VOLT AC ACTUATOR MOTORS ,AND SWITCHES,

2-10 VOLT DC INPUTS SIGNALS- VALVE SEATS,SHAFTS,PLUG OR WAFER SELECTED FOR WATER SERVICE, VALVE BODY'S SHALL BEEPOXY COATED LUG OR FLANGE BODY CONFIGURATION, WEATHER PROOF COVERS FOR MOTOR ACTUATORS

LS - CONTROLS ( EXPANSION OF EXISTING ALC) I/O SCHEDULE WILL BE DEVELOPED AFTER FINAL DESIGN HAS BEENCOORDINATED AND SEQUENCE OF OPERATION DEVELOPED.

SHEET NO:

PUBLISHED:

SHEET NAME:

DRAWN: CHECKED:SB AG

REVISIONS:

THIS PLAN IS ONLINE FOR REVIEW @:WWW.GEZELMANPE.COM/ST0109S_STETSON_DELAND_FL

02SCALE: N.T.S.

HYDRAULICS SCHEMATIC

1523 RIDGEWOOD AVE

HOLLY HILL, FL 32117

CVC 56690

CONTRACTOR:

FILTER REMAINS IN PLACE

04SCALE: N.T.S

ACTUAL PHOTO - POOL EQUIPMENT03

SCALE: N.T.S

ACTUAL PHOTO - POOL

C O N T A C T D E S I G N T E A MCONTACT @ WWW.GEZELMANPE.COM

CLICK HERE IF PDF VERSION OF THIS PLAN

EQUIPMENT RELOCATESFROM ...>

<...TO

MARLOW PUMPS 4SPC SERIES

SELF-PRIMING CENTRIFUGAL SWIMMING POOL PUMPS WITH INTEGRAL SUCTIONSTRAINER FOR USE ON LARGER COMMERCIAL POOL AND WATERPARKAPPLICATIONS.

HYDRAULIC NOTE:

SOLAR CONTRACTOR IS FREE TO ADD UMA-OEM FLOW & THERMAL EXPANSION CONTROL DEVICES OF CHOICE.

3/8" x 2 1/2" x 3 1/2" PL welded to pedestal

Cable Jack 6 1/2" AFF drill flange to accept cable attachement hardware

3/16x 7/19 304 SS wire rope

Flashing 2 to 3" above header

4 1/2" 3.5" Heliocol solar panel

header hgt

Insulation 3 3/4"

roof deck 2''

2" Schedule 40 Galvanized Pipe pedestal 1/2 SS flashing Draw band with worm gear take up

welded to 5" X 5" x 5/16 Base plate

05SCALE: N.T.S

CABLE JACK ALTERNATE