SLOFEC TANK FLOOR INSPECTION REPORT Client: Client Facility: site Items Inspected: Tank123 Inspection Method: SLOFEC Commencement Date: 03 rd May 2016 Completion Date: 06 th May 2016 Type of Report: Final Report Report Number: K0xx-16 Job Number: Jxx86 Unit 1, Howemoss Avenue Unit 27 Kirkhill Industrial Estate, Dyce Webb Ellis Industrial Park Aberdeen, AB21 0GP Rugby, CV21 NP United Kingdom United Kingdom Tel : +44 (0)1224-724744 Tel : +44 (0)1788-547294 Fax : +44 (0)1224-774087 Fax : +44 (0)1788-547299 WWW.INNOSPECTION.COM

SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

  • Upload
    others

  • View
    2

  • Download
    0

Embed Size (px)

Citation preview

Page 1: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TANK FLOOR INSPECTION REPORT

Client: Client

Facility: site

Items Inspected: Tank123

Inspection Method: SLOFEC

Commencement Date: 03rd May 2016

Completion Date: 06th May 2016

Type of Report: Final Report

Report Number: K0xx-16

Job Number: Jxx86

Unit 1, Howemoss Avenue Unit 27 Kirkhill Industrial Estate, Dyce Webb Ellis Industrial Park Aberdeen, AB21 0GP Rugby, CV21 NP United Kingdom United Kingdom Tel : +44 (0)1224-724744 Tel : +44 (0)1788-547294 Fax : +44 (0)1224-774087 Fax : +44 (0)1788-547299 W W W . I N N O S P E C T I O N . C O M

Page 2: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

OPS135 – Rev. 4 © 2016 Innospection Ltd

Client a SLOFEC Tank Floor inspection Page 1 of 12

Tank 123 Final K0xx-16

SLOFECTM TANK INSPECTION REPORT (FS300)

Page 3: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

OPS135 – Rev. 4 © 2016 Innospection Ltd

Client a SLOFEC Tank Floor inspection Page 2 of 12

Tank 123 Final K0xx-16

Executive Summary Innospection Ltd was requested by Client to perform a SLOFECTM (Saturation Low Frequency Eddy Current) inspection on Tank 123 from the 03rd to 06th May 2016. This inspection report documents in detail the specific inspections that /have been conducted; the individual techniques and equipment utilised, and the results obtained.

The SLOFECTM inspection indicated only a few areas of localised underside corrosion

sporadically spread throughout the tank. However the greatest damage occurring was noted on the topside, where significant pits have developed and propagated due to the failure and degradation of the coal tar epoxy. Notably two plates (B24 & B45) had clear through wall pits that have propagated from the tops side. .

Summary of inspection finding Total number of plates : 61 Total number of plates inspected : 61 Number of damaged plates : 51 Number of plates identified with main indications on underside of tank floor Below 20% wall loss : 28 plates 20% - 30% wall loss : 14 plates 31% - 40% wall loss : 7 plates 41% - 50% wall loss : 4 plates Above 50%wall loss : 5 plates Number of plates identified with main indications on topside of tank floor Below 20% wall loss : 13 plates 20% - 30% wall loss : 4 plates 31% - 40% wall loss : 5 plates 41% - 50% wall loss : 13 plates Above 50%wall loss : 26 plates

Page 4: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

OPS135 – Rev. 4 © 2016 Innospection Ltd

Client a SLOFEC Tank Floor inspection Page 3 of 12

Tank 123 Final K0xx-16

Table of Contents 1. Test Object Data .............................................................................................................. 5

2. Inspection Task ................................................................................................................ 5

3. Inspection Personnel ........................................................................................................ 5

4. Inspection Volume ............................................................................................................ 6

5. Inspection Equipment ....................................................................................................... 6

5.1. SLOFECTM Equipment ........................................................................................... 6

5.2. Ultrasonic Equipment ............................................................................................. 7

6. SLOFECTM Equipment Setting .......................................................................................... 7

7. SLOFECTM Equipment Calibration .................................................................................... 8

7.1. Equipment Calibration ............................................................................................ 8

7.2. Calibration Control ................................................................................................. 8

7.3. Calibration Samples ............................................................................................... 8

7.4. Change of Settings ................................................................................................ 9

8. Inspection Procedures ...................................................................................................... 9

9. Inspection Performance ................................................................................................... 9

9.1. Scanner Movement ................................................................................................ 9

9.2. Scan Track Positioning .......................................................................................... 9

9.3. Parameter Storage ................................................................................................ 9

10. Defect Analysis ................................................................................................................ 9

11. Comments to Inspection ................................................................................................. 10

12. Result Overview ............................................................................................................. 10

12.1. Sensitivity Settings ............................................................................................... 10

12.2. Result Overview ................................................................................................... 11

13. Inspection Summary....................................................................................................... 12

14. Documentation ............................................................................................................... 12

15. Signature ........................................................................................................................ 12

Page 5: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

OPS135 – Rev. 4 © 2016 Innospection Ltd

Client a SLOFEC Tank Floor inspection Page 4 of 12

Tank 123 Final K0xx-16

Appendix 1 : Underside Condition Report - Scan Defect Map - Individual Plate Scan Report

Appendix 2 : Topside Condition Report

- Scan Defect Map - Individual Plate Scan Report

Appendix 3: Ultrasonic thickness Report

- Combined Underside & UT thickness Tank Report - Individual Plate wall thickness Measurements

Page 6: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

OPS135 – Rev. 4 © 2016 Innospection Ltd

Client a SLOFEC Tank Floor inspection Page 5 of 12

Tank 123 Final K0xx-16

1. Test Object Data Object Identification : Tank 123

Location of Object : Client a

Wall Thickness : Floor Plates 8.0mm

Annular Plates: 9.6mm

Material : Carbon Steel

Surface Condition :

Coal tar epoxy (400 microns)

2. Inspection Task As requested by Client a SLOFECTM (Saturation Low Frequency Eddy Current) inspection was performed on Tank 123 located at site b between the 03rd & 06th May 2016. The inspection was performed with a SLOFECTM technology scanner, type FS300. SLOFECTM is regarded as a fast corrosion screening technique for the detection of corrosion on either side of the inspected tank floor and under the coatings. The SLOFECTM inspection team consisted of qualified engineers from Innospection Ltd. All areas described in Section 4 – Inspection Volume were inspected with the SLOFECTM scanner. The inspection was carried out due to through wall perforations noted in the tank floor during a repair of the roof and annular plates of the tank.

3. Inspection Personnel Inspection Supervisor : Technician a

Certification / Certificate No. 000000

SLOFEC Operator : Technician b Certification / Certificate No. b

SLOFEC Assistant Assistant a

Page 7: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

OPS135 – Rev. 4 © 2016 Innospection Ltd

Client a SLOFEC Tank Floor inspection Page 6 of 12

Tank 123 Final K0xx-16

4. Inspection Volume All accessible areas on the bottom of the tank-floor including the annular ring were targeted for inspection.

The dead zones for each plate differed depending on the number of obstructions and shape of the plates encountered. Typically the dead zones for a clear plate with 90 deg corners had a dead zone of approximately 200 x 200 mm in each plate corner. Spot Ultrasonic thickness gauging was carried out in these dead areas depending of the surface condition on the floor plate in that location. In the attached scan reports, the scanner areas are displayed with its coloured condition images.

5. Inspection Equipment

5.1. SLOFECTM Equipment The inspection system consisted of the following SLOFECTM equipment and accessories: Scanner : SLOFECTM FS300 Scanner (width 300mm)

Description of Scanner : The SLOFECTM FS300 Scanner is a motorised scanner

system consisting of a permanent magnet for magnetisation and multiplexed electronics. Eight (8) sensors each with a width of 35mm are located between the pole-shoes. A trigger encoder is utilised

Scanning Speed : 50% (approx. 24m/min)

Eddy Current Instrument : IBM-AT-compatible computer with 2-frequency Eddy current plug-in cards Type : Beltronic Serial No. 10

Eddy Current Sensors : 8 x EC-B-35 mm

Software Version : SlofecTM V5 Software

Cable : 60 metres of specific cable connection, divided in 2 x 30m

Reference Plate : 8mmm and 10mm( Innospection stock),

Reference Defect : 20%, 40%, 60%, 80% FBH

Page 8: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

OPS135 – Rev. 4 © 2016 Innospection Ltd

Client a SLOFEC Tank Floor inspection Page 7 of 12

Tank 123 Final K0xx-16

5.2. Ultrasonic Equipment The Ultrasonic equipment consisted of the following accessories: USMGO Ultrasonic Unit Serial No. 90110981 Capable of both “A” scan display and digital thickness readout 5 MHz 10mm Ø twin crystal transducer 2mm – 12mm carbon steel calibration step wedge

6. SLOFECTM Equipment Setting In general, the SLOFECTM system is calibrated using sample test samples with artificial reference defects. The reference samples should be of the same material and thickness as the surface to be inspected. In the case of a coating being present on the surface to be inspected, the average thickness of the coating (if applicable) should also be simulated on the reference sample for the calibration. Typical reference defects that are used are flat bottom holes or conical bottom holes having a diameter of 5mm, 10mm and 20mm. The depths of the artificial reference defects are typically 20%, 40%, 60%, 80% and 100%. For calibration, the SLOFECTM system is driven over the reference defects and the channels are set (one sensor per channel) to give a sufficient sensitivity level for the detection of underside and topside corrosion defects. The calibration is performed at the beginning, after breaks, at the end of every shift and when significant changes are made to the settings of the equipment. The calibration results and reference defect data from the calibration sample is always stored in the system. The Eddy Current signal analysis is done online. The computerised equipment and the software allow the analysis of the signal amplitude [in div.] and signal phase [in °]. In discussion with the individual client, indications comparable with the reference defect indications can be marked on the floor and are usually recommended to be re-inspected by Ultrasonic (UT) examination.

Page 9: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

OPS135 – Rev. 4 © 2016 Innospection Ltd

Client a SLOFEC Tank Floor inspection Page 8 of 12

Tank 123 Final K0xx-16

7. SLOFECTM Equipment Calibration

7.1. Equipment Calibration For internal corrosion detection, the differential mode was used. Optimum signal / noise ratio and signal phase separation between the internal defect indications and other indications were considered when selecting a suitable test frequency. The differential channels of all the sensors were set so that internal defects were indicated in the vertical signal phase direction as shown in the diagram below. By moving the scanner in the positive forward direction, the internal defect signal would show the first peak down, followed by the second peak up with an upward movement.

7.2. Calibration Control The general setting and calibration was performed at the beginning of the inspection and all the calibration data was stored digitally. Calibration controls were performed at the beginning and end of each working shift as well as after any other significant interruption (i.e. breaks or lunch). Re-calibration is also deemed necessary when significant changes are made to the settings of the equipment. Calibration samples are used for the initial set-up and for the random check of operator’s settings. Full and accurate sensitivity settings are achieved only when the first indication found on the object undergoing the test is verified by an UT operator with the corresponding depth of indication and SLOFECTM sensitivity being adjusted accordingly.

7.3. Calibration Samples The calibration samples are manufactured by Innospection Ltd in accordance to the setting standard requirements.

Sample signal display of internal defect

Page 10: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

OPS135 – Rev. 4 © 2016 Innospection Ltd

Client a SLOFEC Tank Floor inspection Page 9 of 12

Tank 123 Final K0xx-16

7.4. Change of Settings In the event of any scanner adjustment, re-calibration is performed.

8. Inspection Procedures The inspection was performed according to the following valid procedure: SLOFECTM Tank Procedure No. InnoTSloTNK-001-08 – Current Issue

9. Inspection Performance

9.1. Scanner Movement The scanner assistant, who was in permanent communication with the SLOFECTM operator, was responsible for positioning and moving the scanner on the pipe surface. The SLOFECTM FS300 Scanner is marked clearly on the top with the FORWARD and BACKWARD directions so that all scan directions are made clear to the operator and assistant at all times. In addition, some visual contact between the operator and assistant was established during the inspection. The scanner was moved manually with the scanned tracks being overlapped at all times. All scans for the inspection were recorded in the forward position.

9.2. Scan Track Positioning Between the SLOFECTM engineers, a clear description of the track position was established.

9.3. Parameter Storage The Eddy Current testing parameter was set during the calibration and digitally stored according to the scan direction and lift off.

10. Defect Analysis All indications which showed a clear signal phase direction similar to that of the reference defects and had signal amplitude equivalent to that of the test piece were subjected to analysis. Signals that are clearly out of the corrosion phase direction were not reported.

Page 11: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

OPS135 – Rev. 4 © 2016 Innospection Ltd

Client a SLOFEC Tank Floor inspection Page 10 of 12

Tank 123 Final K0xx-16

11. Comments to Inspection The Tank was found in a general clean condition having been cleaned prior to the survey. The floor had been coated in a coal tar epoxy and it was noted that significant topside pitting was occurring in areas where the epoxy had failed.

12. Result Overview

12.1. Sensitivity Settings The general overview of the inspected areas with the results is presented in the attached colour scan reports with wall loss being represented in colour classes as shown in the Wall Loss Legend below:

Note Eddy Current inspection is an evaluation method of NDT; hence all results obtained are based upon the test piece used. Material and wall thickness of the test piece should be as near as reasonably practicable to the item under inspection. Artificial defects should be as near in size and shape as to the type sought. Because SLOFECTM signal amplitudes are an indication of defect depth and volume, the defect depth analysis by signal amplitude can only be done in comparison with artificial reference defects having varying depths.

Below 20% wall loss - Grey 20-30% wall loss - Green 31-40% wall loss - Blue 41-50% wall loss - Yellow Above 50% wall loss - Red

Page 12: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

OPS135 – Rev. 4 © 2016 Innospection Ltd

Client a SLOFEC Tank Floor inspection Page 11 of 12

Tank 123 Final K0xx-16

12.2. Result Overview All SLOFECTM scans are shown in Appendices 1 & 2. Ultrasonic wall thickness readings are shown in Appendix 3. A summary of the inspection findings in each of the scanned section is given below.

Summary of inspection finding Total number of plates : 61 Total number of plates inspected : 61 Number of damaged plates : 51 Number of plates identified with main indications on underside of tank floor Below 20% wall loss : 28 plates 20% - 30% wall loss : 14 plates 31% - 40% wall loss : 7 plates 41% - 50% wall loss : 4 plates Above 50%wall loss : 5 plates Number of plates identified with main indications on topside of tank floor Below 20% wall loss : 13 plates 20% - 30% wall loss : 4 plates 31% - 40% wall loss : 5 plates 41% - 50% wall loss : 13 plates Above 50%wall loss : 26 plates

Page 13: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

OPS135 – Rev. 4 © 2016 Innospection Ltd

Client a SLOFEC Tank Floor inspection Page 12 of 12

Tank 123 Final K0xx-16

13. Inspection Summary

The SLOFECTM inspection indicated only a few areas of localised underside corrosion

sporadically spread throughout the tank. However the greatest damage occurring was noted on the top side where significant pits have developed and propagated due to the failure and degradation of the coal tar epoxy. Notably two plates (B24 & B45) had clear through wall pits that have propagated from the tops side.

14. Documentation The inspection result, parameters and data are stored in the Innospection Limited archive database system.

15. Signature

Technician a Lead Technician Innospection Limited

Level 3 Senior Engineer Innospection Limited

Page 14: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

APPENDIX 01

Underside Condition Report

General Tank Floor Overview Individual Plate View

Page 15: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

::

:

:

:

::

Client asite b

Tank123

8.00 mm9.60 mm

0.00 mm0.00 mm

K0xx-1603/05/2016

: Jxx86

:: 452.39 qm

24.00 m

Underside-Differential

SLOFEC TM

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

1 1

SLOFEC V5 5.10.05.27

Page 16: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite a03/05/2016

:::

Tank 123K0xx-16Jxx86

: A 1Underside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 17: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: A 2Underside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 18: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: A 3Underside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 19: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite a03/05/2016

:::

Tank 123K0xx-16Jxx86

: A 4Underside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 20: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: A 5Underside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 21: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: A 6Underside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 22: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: A 7Underside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 23: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank bK0xx-16Jxx86

: A 8Underside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 24: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: A 9Underside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 25: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite a03/05/2016

:::

Tank 123K0xx-16Jxx86

: A 10Underside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 26: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: A 11Underside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 27: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: A 12Underside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 28: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 1Underside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 29: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 2Underside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 30: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 3Underside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 31: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 4Underside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 32: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank123K0xx-16Jxx86

: B 5Underside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 33: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 6Underside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 34: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

ClientSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 7Underside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 35: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 8Underside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 36: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite 12303/05/2016

:::

Tank 123K0xx-16Jxx86

: B 9Underside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 37: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 10Underside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 38: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 11Underside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 39: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client xSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 12Underside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 40: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 13Underside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 41: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 14Underside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 42: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 15Underside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 43: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 16Underside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 44: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 17Underside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 45: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 18Underside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 46: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 19Underside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 47: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 20Underside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 48: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 21Underside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 49: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 22Underside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 50: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 23Underside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 51: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 24Underside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 52: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 25Underside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 53: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 26Underside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 54: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 27Underside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 55: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client xSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 28Underside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 56: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 29Underside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 57: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 30Underside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 58: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 31Underside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 59: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 32Underside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 60: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 33Underside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 61: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 34Underside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 62: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 35Underside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 63: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 36Underside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 64: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client a Site b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 37Underside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 65: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 38Underside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 66: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 39Underside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 67: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 40Underside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 68: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

ClientSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 41Underside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 69: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 42Underside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 70: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 43Underside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 71: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 44Underside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 72: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 45Underside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 73: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 46Underside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 74: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 47Underside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 75: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank bK0xx-16Jxx86

: B 48Underside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 76: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 49Underside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 77: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

APPENDIX 02

Topside Condition Report

General Tank Floor Overview Individual Plate View

Page 78: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

::

:

:

:

::

Client aSite b

Tank 123

8.00 mm9.60 mm

0.00 mm0.00 mm

K0xx-1603/05/2016

: Jxx86

:: 452.39 qm

24.00 m

Topside-Differential

SLOFEC TM

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

1 1

SLOFEC V5 5.10.05.27

Page 79: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: A 1Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 80: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: A 2Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 81: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: A 3Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 82: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: A 4Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 83: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: A 5Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 84: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: A 6Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 85: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: A 7Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 86: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: A 8Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 87: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: A 9Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 88: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: A 10Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 89: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: A 11Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 90: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: A 12Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 91: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 1Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 92: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 2Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 93: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 3Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 94: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 4Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 95: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 5Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 96: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 6Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 97: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 7Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 98: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 8Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 99: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 9Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 100: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 10Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 101: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 11Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 102: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 12Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 103: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 13Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 104: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 14Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 105: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 15Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 106: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 16Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 107: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 17Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 108: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 18Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 109: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank bK0xx-16Jxx86

: B 19Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 110: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 20Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 111: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 21Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 112: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 22Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 113: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 23Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 114: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 24Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 115: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 25Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 116: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 26Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 117: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 27Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 118: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 28Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 119: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 29Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 120: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 30Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 121: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 31Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 122: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 32Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 123: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 33Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 124: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 34Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 125: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 35Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 126: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 36Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 127: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 37Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 128: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 38Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 129: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 39Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 130: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 40Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 131: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 41Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 132: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 42Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 133: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 43Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 134: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 44Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 135: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 45Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 136: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 46Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 137: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 47Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 138: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 48Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 139: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 49Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

Page 140: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

APPENDIX 03

Ultrasonic Thickness Gauging

Page 141: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

::

:

:

:

::

Client aSite b

Tank 123

8.00 mm9.60 mm

0.00 mm0.00 mm

K0xx-1603/05/2016

: Jxx86

:: 452.39 qm

24.00 m

Combined UT & Underside-Differential

SLOFEC TM

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

1 1

SLOFEC V5 5.10.05.27

A.vanvuuren
Rectangle
A.vanvuuren
Rectangle
A.vanvuuren
Rectangle
A.vanvuuren
Rectangle
A.vanvuuren
Rectangle
A.vanvuuren
Rectangle
A.vanvuuren
Rectangle
A.vanvuuren
Rectangle
A.vanvuuren
Rectangle
A.vanvuuren
Rectangle
A.vanvuuren
Rectangle
A.vanvuuren
Rectangle
Page 142: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: A 1Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

A.vanvuuren
Text Box
Ultrasonic Thickness Readings
A.vanvuuren
Text Box
9.2mm
A.vanvuuren
Text Box
9.5mm
A.vanvuuren
Text Box
9.8mm
A.vanvuuren
Text Box
9.7mm
Page 143: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: A 2Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

A.vanvuuren
Text Box
Ultrasonic Thickness Readings
A.vanvuuren
Text Box
8.3mm
A.vanvuuren
Text Box
8.6mm
A.vanvuuren
Text Box
9.1mm
A.vanvuuren
Text Box
9.5mm
Page 144: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: A 3Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

A.vanvuuren
Text Box
Ultrasonic Thickness Readings
A.vanvuuren
Text Box
9.3mm
A.vanvuuren
Text Box
8.9mm
A.vanvuuren
Text Box
9.2mm
A.vanvuuren
Text Box
9.5mm
Page 145: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: A 4Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

A.vanvuuren
Text Box
Ultrasonic Thickness Readings
A.vanvuuren
Text Box
8.5mm
A.vanvuuren
Text Box
8.0mm
A.vanvuuren
Text Box
9.0mm
A.vanvuuren
Text Box
8.6mm
A.vanvuuren
Text Box
9.5mm
Page 146: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: A 5Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

A.vanvuuren
Text Box
Ultrasonic Thickness Readings
A.vanvuuren
Text Box
8.4mm
A.vanvuuren
Text Box
8.6mm
A.vanvuuren
Text Box
9.2mm
A.vanvuuren
Text Box
8.7mm
Page 147: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: A 6Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

A.vanvuuren
Text Box
Ultrasonic Thickness Readings
A.vanvuuren
Text Box
8.6mm
A.vanvuuren
Text Box
9.7mm
A.vanvuuren
Text Box
9.1mm
A.vanvuuren
Text Box
8.2mm
Page 148: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: A 7Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

A.vanvuuren
Text Box
Ultrasonic Thickness Readings
A.vanvuuren
Text Box
8.7mm
A.vanvuuren
Text Box
9.5mm
A.vanvuuren
Text Box
7.2mm
A.vanvuuren
Text Box
9.9mm
Page 149: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client xSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: A 8Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

A.vanvuuren
Text Box
Ultrasonic Thickness Readings
A.vanvuuren
Text Box
9.6mm
A.vanvuuren
Text Box
9.5mm
A.vanvuuren
Text Box
8.8mm
A.vanvuuren
Text Box
9.9mm
Page 150: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: A 9Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

A.vanvuuren
Text Box
Ultrasonic Thickness Readings
A.vanvuuren
Text Box
9.6mm
A.vanvuuren
Text Box
9.1mm
A.vanvuuren
Text Box
9.3mm
A.vanvuuren
Text Box
8.6mm
Page 151: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: A 10Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

A.vanvuuren
Text Box
Ultrasonic Thickness Readings
A.vanvuuren
Text Box
9.9mm
A.vanvuuren
Text Box
9.3mm
A.vanvuuren
Text Box
9.9mm
A.vanvuuren
Text Box
9.9mm
Page 152: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: A 11Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

A.vanvuuren
Text Box
Ultrasonic Thickness Readings
A.vanvuuren
Text Box
9.0mm
A.vanvuuren
Text Box
9.3mm
A.vanvuuren
Text Box
8.7mm
A.vanvuuren
Text Box
9.1mm
Page 153: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: A 12Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

A.vanvuuren
Text Box
Ultrasonic Thickness Readings
A.vanvuuren
Text Box
9.9mm
A.vanvuuren
Text Box
9.6mm
A.vanvuuren
Text Box
9.7mm
A.vanvuuren
Text Box
9.8mm
Page 154: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 1Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

A.vanvuuren
Text Box
Ultrasonic Thickness Readings
A.vanvuuren
Text Box
8.1mm
A.vanvuuren
Text Box
7.8mm
A.vanvuuren
Text Box
7.5mm
Page 155: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 2Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

A.vanvuuren
Text Box
Ultrasonic Thickness Readings
A.vanvuuren
Text Box
7.6mm
A.vanvuuren
Text Box
7.8mm
A.vanvuuren
Text Box
7.6mm
A.vanvuuren
Text Box
8.1mm
A.vanvuuren
Text Box
7.8mm
Page 156: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 3Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

A.vanvuuren
Text Box
Ultrasonic Thickness Readings
A.vanvuuren
Text Box
7.5mm
A.vanvuuren
Text Box
7.6mm
A.vanvuuren
Text Box
7.5mm
A.vanvuuren
Text Box
7.9mm
Page 157: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 4Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

A.vanvuuren
Text Box
Ultrasonic Thickness Readings
A.vanvuuren
Text Box
8.1mm
A.vanvuuren
Text Box
7.8mm
A.vanvuuren
Text Box
8.1mm
A.vanvuuren
Text Box
7.8mm
Page 158: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 5Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

A.vanvuuren
Text Box
Ultrasonic Thickness Readings
A.vanvuuren
Text Box
7.6mm
A.vanvuuren
Text Box
7.6mm
A.vanvuuren
Text Box
8.0mm
A.vanvuuren
Text Box
7.7mm
A.vanvuuren
Text Box
8.0mm
Page 159: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 6Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

A.vanvuuren
Text Box
Ultrasonic Thickness Readings
A.vanvuuren
Text Box
7.8mm
A.vanvuuren
Text Box
7.9mm
A.vanvuuren
Text Box
7.9mm
Page 160: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 7Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

A.vanvuuren
Text Box
Ultrasonic Thickness Readings
A.vanvuuren
Text Box
7.8mm
A.vanvuuren
Text Box
7.8mm
A.vanvuuren
Text Box
7.9mm
A.vanvuuren
Text Box
7.9mm
A.vanvuuren
Text Box
7.9mm
Page 161: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client xSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 8Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

A.vanvuuren
Text Box
Ultrasonic Thickness Readings
A.vanvuuren
Text Box
7.9mm
A.vanvuuren
Text Box
7.9mm
A.vanvuuren
Text Box
7.9mm
A.vanvuuren
Text Box
7.7mm
Page 162: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 9Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

A.vanvuuren
Text Box
Ultrasonic Thickness Readings
A.vanvuuren
Text Box
7.4mm
A.vanvuuren
Text Box
7.6mm
A.vanvuuren
Text Box
7.4mm
A.vanvuuren
Text Box
7.9mm
A.vanvuuren
Text Box
7.9mm
Page 163: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 10Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

A.vanvuuren
Text Box
Ultrasonic Thickness Readings
A.vanvuuren
Text Box
7.5mm
A.vanvuuren
Text Box
7.7mm
A.vanvuuren
Text Box
7.5mm
A.vanvuuren
Text Box
7.6mm
Page 164: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 11Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

A.vanvuuren
Text Box
Ultrasonic Thickness Readings
A.vanvuuren
Text Box
7.9mm
A.vanvuuren
Text Box
7.9mm
A.vanvuuren
Text Box
7.9mm
A.vanvuuren
Text Box
7.9mm
Page 165: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 12Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

A.vanvuuren
Text Box
Ultrasonic Thickness Readings
A.vanvuuren
Text Box
7.9mm
A.vanvuuren
Text Box
7.9mm
A.vanvuuren
Text Box
7.9mm
A.vanvuuren
Text Box
7.9mm
Page 166: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 13Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

A.vanvuuren
Text Box
Ultrasonic Thickness Readings
A.vanvuuren
Text Box
7.8mm
A.vanvuuren
Text Box
7.8mm
A.vanvuuren
Text Box
7.9mm
A.vanvuuren
Text Box
7.8mm
Page 167: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 14Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

A.vanvuuren
Text Box
Ultrasonic Thickness Readings
A.vanvuuren
Text Box
7.4mm
A.vanvuuren
Text Box
8.1mm
A.vanvuuren
Text Box
7.8mm
A.vanvuuren
Text Box
7.5mm
Page 168: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 15Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

A.vanvuuren
Text Box
Ultrasonic Thickness Readings
A.vanvuuren
Text Box
7.8mm
A.vanvuuren
Text Box
7.9mm
A.vanvuuren
Text Box
7.9mm
A.vanvuuren
Text Box
7.9mm
Page 169: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 16Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

A.vanvuuren
Text Box
Ultrasonic Thickness Readings
A.vanvuuren
Text Box
7.9mm
A.vanvuuren
Text Box
7.7mm
A.vanvuuren
Text Box
7.7mm
A.vanvuuren
Text Box
7.9mm
Page 170: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 17Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

A.vanvuuren
Text Box
Ultrasonic Thickness Readings
A.vanvuuren
Text Box
7.4mm
A.vanvuuren
Text Box
7.6mm
A.vanvuuren
Text Box
7.8mm
A.vanvuuren
Text Box
7.9mm
Page 171: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 18Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

A.vanvuuren
Text Box
Ultrasonic Thickness Readings
A.vanvuuren
Text Box
7.5mm
A.vanvuuren
Text Box
7.8mm
A.vanvuuren
Text Box
7.5mm
A.vanvuuren
Text Box
7.3mm
A.vanvuuren
Text Box
7.6mm
A.vanvuuren
Text Box
7.2mm
A.vanvuuren
Text Box
7.3mm
Page 172: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 19Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

A.vanvuuren
Text Box
Ultrasonic Thickness Readings
A.vanvuuren
Text Box
7.9mm
A.vanvuuren
Text Box
7.9mm
A.vanvuuren
Text Box
7.8mm
A.vanvuuren
Text Box
7.7mm
A.vanvuuren
Text Box
7.7mm
A.vanvuuren
Text Box
7.9mm
Page 173: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 20Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

A.vanvuuren
Text Box
Ultrasonic Thickness Readings
A.vanvuuren
Text Box
7.9mm
A.vanvuuren
Text Box
7.9mm
A.vanvuuren
Text Box
7.7mm
A.vanvuuren
Text Box
7.7mm
Page 174: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 21Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

A.vanvuuren
Text Box
Ultrasonic Thickness Readings
A.vanvuuren
Text Box
7.6mm
A.vanvuuren
Text Box
7.8mm
A.vanvuuren
Text Box
7.7mm
A.vanvuuren
Text Box
7.9mm
Page 175: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 22Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

A.vanvuuren
Text Box
Ultrasonic Thickness Readings
A.vanvuuren
Text Box
7.8mm
A.vanvuuren
Text Box
7.7mm
A.vanvuuren
Text Box
7.9mm
A.vanvuuren
Text Box
7.9mm
Page 176: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 23Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

A.vanvuuren
Text Box
Ultrasonic Thickness Readings
A.vanvuuren
Text Box
7.7mm
A.vanvuuren
Text Box
7.6mm
A.vanvuuren
Text Box
7.6mm
A.vanvuuren
Text Box
7.9mm
Page 177: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 24Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

A.vanvuuren
Text Box
Ultrasonic Thickness Readings
A.vanvuuren
Text Box
7.9mm
A.vanvuuren
Text Box
7.9mm
A.vanvuuren
Text Box
8.0mm
A.vanvuuren
Text Box
7.9mm
A.vanvuuren
Text Box
7.8mm
A.vanvuuren
Text Box
7.6mm
Page 178: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 25Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

A.vanvuuren
Text Box
Ultrasonic Thickness Readings
A.vanvuuren
Text Box
7.9mm
A.vanvuuren
Text Box
7.7mm
A.vanvuuren
Text Box
7.8mm
A.vanvuuren
Text Box
7.9mm
Page 179: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 26Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

A.vanvuuren
Text Box
Ultrasonic Thickness Readings
A.vanvuuren
Text Box
7.9mm
A.vanvuuren
Text Box
7.9mm
A.vanvuuren
Text Box
8.0mm
A.vanvuuren
Text Box
8.0mm
Page 180: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 27Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

A.vanvuuren
Text Box
Ultrasonic Thickness Readings
A.vanvuuren
Text Box
7.6mm
A.vanvuuren
Text Box
7.9mm
A.vanvuuren
Text Box
7.6mm
A.vanvuuren
Text Box
7.8mm
Page 181: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 28Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

A.vanvuuren
Text Box
Ultrasonic Thickness Readings
A.vanvuuren
Text Box
7.8mm
A.vanvuuren
Text Box
7.9mm
A.vanvuuren
Text Box
7.9mm
A.vanvuuren
Text Box
7.9mm
Page 182: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 29Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

A.vanvuuren
Text Box
Ultrasonic Thickness Readings
A.vanvuuren
Text Box
7.7mm
A.vanvuuren
Text Box
7.9mm
A.vanvuuren
Text Box
7.7mm
A.vanvuuren
Text Box
7.8mm
Page 183: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 30Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

A.vanvuuren
Text Box
Ultrasonic Thickness Readings
A.vanvuuren
Text Box
7.9mm
A.vanvuuren
Text Box
7.9mm
A.vanvuuren
Text Box
8.0mm
A.vanvuuren
Text Box
7.6mm
Page 184: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 31Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

A.vanvuuren
Text Box
Ultrasonic Thickness Readings
A.vanvuuren
Text Box
8.0mm
A.vanvuuren
Text Box
7.7mm
A.vanvuuren
Text Box
7.9mm
A.vanvuuren
Text Box
7.9mm
Page 185: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 32Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

A.vanvuuren
Text Box
Ultrasonic Thickness Readings
A.vanvuuren
Text Box
7.4mm
A.vanvuuren
Text Box
7.7mm
A.vanvuuren
Text Box
7.8mm
A.vanvuuren
Text Box
7.8mm
Page 186: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 33Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

A.vanvuuren
Text Box
Ultrasonic Thickness Readings
A.vanvuuren
Text Box
7.7mm
A.vanvuuren
Text Box
7.8mm
A.vanvuuren
Text Box
7.9mm
A.vanvuuren
Text Box
7.9mm
Page 187: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 34Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

A.vanvuuren
Text Box
Ultrasonic Thickness Readings
A.vanvuuren
Text Box
7.6mm
A.vanvuuren
Text Box
7.4mm
A.vanvuuren
Text Box
7.9mm
A.vanvuuren
Text Box
7.9mm
Page 188: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 35Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

A.vanvuuren
Text Box
Ultrasonic Thickness Readings
A.vanvuuren
Text Box
7.4mm
A.vanvuuren
Text Box
7.5mm
A.vanvuuren
Text Box
7.4mm
A.vanvuuren
Text Box
7.8mm
Page 189: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 36Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

A.vanvuuren
Text Box
Ultrasonic Thickness Readings
A.vanvuuren
Text Box
7.3mm
A.vanvuuren
Text Box
7.6mm
A.vanvuuren
Text Box
7.7mm
A.vanvuuren
Text Box
7.8mm
Page 190: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 37Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

A.vanvuuren
Text Box
Ultrasonic Thickness Readings
A.vanvuuren
Text Box
7.6mm
A.vanvuuren
Text Box
7.8mm
A.vanvuuren
Text Box
7.9mm
A.vanvuuren
Text Box
7.9mm
A.vanvuuren
Text Box
7.8mm
Page 191: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 38Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

A.vanvuuren
Text Box
Ultrasonic Thickness Readings
A.vanvuuren
Text Box
7.8mm
A.vanvuuren
Text Box
7.4mm
A.vanvuuren
Text Box
7.6mm
A.vanvuuren
Text Box
7.8mm
Page 192: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 39Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

A.vanvuuren
Text Box
Ultrasonic Thickness Readings
A.vanvuuren
Text Box
7.7mm
A.vanvuuren
Text Box
7.5mm
A.vanvuuren
Text Box
7.6mm
A.vanvuuren
Text Box
7.8mm
Page 193: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 40Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

A.vanvuuren
Text Box
Ultrasonic Thickness Readings
A.vanvuuren
Text Box
7.8mm
A.vanvuuren
Text Box
7.9mm
A.vanvuuren
Text Box
7.9mm
A.vanvuuren
Text Box
7.9mm
Page 194: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 41Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

A.vanvuuren
Text Box
Ultrasonic Thickness Readings
A.vanvuuren
Text Box
7.9mm
A.vanvuuren
Text Box
7.9mm
A.vanvuuren
Text Box
7.9mm
A.vanvuuren
Text Box
7.9mm
A.vanvuuren
Text Box
7.5mm
Page 195: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 42Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

A.vanvuuren
Text Box
Ultrasonic Thickness Readings
A.vanvuuren
Text Box
7.6mm
A.vanvuuren
Text Box
7.4mm
A.vanvuuren
Text Box
7.7mm
A.vanvuuren
Text Box
7.8mm
Page 196: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 43Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

A.vanvuuren
Text Box
Ultrasonic Thickness Readings
A.vanvuuren
Text Box
7.7mm
A.vanvuuren
Text Box
7.6mm
A.vanvuuren
Text Box
7.7mm
A.vanvuuren
Text Box
7.8mm
A.vanvuuren
Text Box
7.9mm
Page 197: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 44Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

A.vanvuuren
Text Box
Ultrasonic Thickness Readings
A.vanvuuren
Text Box
7.9mm
A.vanvuuren
Text Box
7.6mm
A.vanvuuren
Text Box
7.9mm
A.vanvuuren
Text Box
7.9mm
Page 198: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 45Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

A.vanvuuren
Text Box
Ultrasonic Thickness Readings
A.vanvuuren
Text Box
7.3mm
A.vanvuuren
Text Box
7.7mm
A.vanvuuren
Text Box
8.0mm
A.vanvuuren
Text Box
7.9mm
A.vanvuuren
Text Box
7.9mm
Page 199: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 46Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

A.vanvuuren
Text Box
Ultrasonic Thickness Readings
A.vanvuuren
Text Box
8.0mm
A.vanvuuren
Text Box
7.8mm
A.vanvuuren
Text Box
7.9mm
A.vanvuuren
Text Box
7.9mm
Page 200: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 47Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

A.vanvuuren
Text Box
Ultrasonic Thickness Readings
A.vanvuuren
Text Box
8.0mm
A.vanvuuren
Text Box
7.6mm
A.vanvuuren
Text Box
8.0mm
A.vanvuuren
Text Box
8.0mm
Page 201: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 48Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

A.vanvuuren
Text Box
Ultrasonic Thickness Readings
A.vanvuuren
Text Box
8.0mm
A.vanvuuren
Text Box
8.0mm
A.vanvuuren
Text Box
8.0mm
A.vanvuuren
Text Box
8.0mm
A.vanvuuren
Text Box
7.9mm
Page 202: SLOFEC TANK FLOOR INSPECTION REPORT · The SLOFECTM inspection indicated only a few areas of localised underside corrosion sporadically spread throughout the tank. However the greatest

SLOFEC TM

:::

Client aSite b03/05/2016

:::

Tank 123K0xx-16Jxx86

: B 49Topside-Differential

0.0 0.5 1.0 1.5 2.0 2.5Signal Amplitude [div]

3.0 3.5 4.0 4.5 5.0

<20%

20-2

9%

30-3

9%

40-4

9%

>=50

%

SLOFEC V5 5.10.05.27

A.vanvuuren
Text Box
Ultrasonic Thickness Readings
A.vanvuuren
Text Box
7.6mm
A.vanvuuren
Text Box
7.6mm
A.vanvuuren
Text Box
7.9mm