Edco SLCP SeriesTwo Pair SLC Loop Protector (Modular)
Surge Protection For Business-Critical ContinuityTM
The Edco SLCP Series are four-wire modules designed to protect signaling linecircuits (SLC). The device has 0 ohms of resistance and offers line toground protection.
Features
■ Compatible with SLC circuits
■ Line-to-ground protection
■ State-of-the-art silicon technology
■ Over-current protection
■ UL listed 497B
■ Requires Edco PCB1B-WKEY base
■ PC642PTU (Pass Thru Unit)
available for troubleshooting
■ 5 year warranty
UL®497B
General Technical Specifications
Ordering InformationHow to Specify the Appropriate Model
Operating Voltage 5, 12, 18, 24, 32, 36, 48, 52 VDC
Clamping Voltage 8, 15, 20, 30, 36, 43, 50, 60 VDC
Operating Current 1 A
Peak Surge Current 250 A (8 x 20 µs)
Frequency Range 0 to 20 MHz
Insertion Loss < 0.1 dB at 20 MHz
SPD Technology Silicon Avalanche Diode (SAD)
Connection Type Terminal block w/compression lugsTerminals accept up to 10 AWG
Operating Temperature -40°C to +85°C
Dimensions (Inches) 2H x 1W x 2.5L (SLCP + PCB1B-WKEY Base)
Weight 1 oz
Certifications UL 497B
Warranty 5 years
EDCO PCB1B-WKEY BASE SOLD SEPARATELY
VOLTAGE CLAMP
43 Volts50 Volts60 Volts
36 Volts
30 Volts
20 Volts
15 Volts
8 Volts0 8
1 5
2 0
3 0
3 6
4 3
S L C P
5 0 6 0
Unprotected Pair 2
Unprotected Pair 1
Protected Pair 2
Protected Pair 1
Keying Pin
Even TerminalsOdd Terminals
Field SideElectronics Side
9
7
5
3
1
10
8
6
4
2
1.0
{ }
}{ 2.125" 2.4"
Ground Terminal 1 OR 10 (internally tied together) to Building Approved Ground.
DO NOT daisy chain grounds.
NOT intended for shield termination. Install ground in accordance with all applicable codes. PCB1B-WKEY accommodates 26 to 10 AWG wire.
Installation
AC Power
Connectivity
DC Power
Embedded Computing
Embedded Power
Monitoring
Outside Plant
Power Switching & Control
Racks and Integrated Cabinets
Services
Precision Cooling Surge Protection
Emerson Network Power.The global leader in enabling Business-Critical ContinuityTM.
IO-50116 2/09 Rev. 2 Printed in USABusiness-Critical Continuity, Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co. ©2009 Emerson Electric Co.
www.emersonnetworkpower.comEmerson Network Power Contact information
HeadquartersSurge Protection328 Water Street 650 SW 27th AvenueBinghamton, NY 13901 Ocala, FL 34471T: (607) 721-8840 T: (352) 732-3029T: (800) 288-6169 T: (800) 648-4076F: (607) 722-8713 F: (352) 867-1237E: [email protected]
Edco PCB1B-WKEY: