Recommended for applications that require silent switching
■ Features Greatly reduces noise during switching (10 to 15 dBA reduction compared with our previous products) Operating coil of AC/DC common-use type Built-in coil-surge suppression device
■ Application
SL Series
Silent Magnetic Contactor
■ Types and RatingsRating Type Auxiliary contact
arrangementCoil voltage(Voltage code)*1
Rated operational current (AC-3) Conventional free air thermal current(Rated thermal current)
AC 200 - 240 V AC 380 - 440 V
9 A 9 A 20 A SL09-11 1NO+1NC 24 V [E] *2
48 V [F]100 V [1]110 V [H]200 V [2]220 V [M]240 V [P]
SL09-22 2NO+2NC25 A 25 A 32 A SL25-11 1NO+1NC
SL25-22 2NO+2NC40 A 40 A 60 A SL40-11 1NO+1NC
SL40-22 2NO+2NC65 A 65A 100A SL65-11 1NO+1NC
SL65-22 2NO+2NC80A 80A 105A SL80-11 1NO+1NCNote 1: The coil voltage designation code is indicated inside the of the product code column.Note 2: AC-4 application is not applicable.*1 The designation code is indicated inside the [ ]. *2 For SL65 and SL80, 24V coil models cannot be manufactured.
■ Operating coil voltageCoilvoltage code
Designationcode
Coil voltage and frequencyAC DC
24 V *1 E 24 V, 50/60 Hz 24 V48 V F 48 V, 50/60 Hz 48 V100 V 1 100 V, 50/60 Hz 100 V110 V H 110 V, 50/60 Hz 110 V200 V 2 200 V, 50/60 Hz 200 V220 V M 220 V, 50/60 Hz 220 V240 V P 240 V, 50/60 Hz 240 V
■ Operating coil characteristicsType Coil (magnet) power consumption
110 V, 50 Hz 110 V DCSL09 7.5 VA 7 WSL25SL40 9.7 VA 9 WSL65 15 VA 12 WSL80
Note 1: The coil rating is 110 V, 50 Hz/60 Hz and 110 V DC.Note 2: The operating voltage fluctuation range is 85 to 110% of the rated voltage.
Elevator (No machine room) Electric water heater Hospitals, libraries, art galleries, museums,
movie theaters, etc.
New Product News
Operation noise level comparison is available from here
http://fujielectric-fa-movie.com/silent/video-nb/
NEW
NEW
NEW
SL65
NEW
SL09 SL40
*1 Cannot be manufactured for SL65 and SL80. 62C9-E-0178a
2214
13 21
6 T34 T22 T1
5 L33 L21 L1
1
2
6 T34 T22 T1
5 L33 L21 L1
4432
4331
22
21
14
13
145.5 (when rail height is 15)136
881.58.5
3549
13 10.5
96.5
2343
Mass: 0.61 kg (1NO+1NC) 0.62 kg (2NO+2NC)
35
(48
to) 5
2
34
Mounting hole2-M4
6030
34 (t
o 36
)
Mount using the two mounting holes located on the diagonal lines.
Main terminal M4
Coil terminal M3.5Panel drilling diagram
Main terminal M4Coil terminal M3.5
13 10.5
96.5
43
4935
1
2
13 21
14 22
1 L1 3 L2 5 L3
2 T1 4 T2 6 T3
1 L1 3 L2 5 L3
2 T1 4 T2 6 T3
13 21 31 43
44322214
Panel drilling diagram
45 (38 - 46)
Mounting hole2-M4
5 9.5
Mount using the two mounting holes located on the diagonal lines.
Mass: 0.86 kg (1NO+1NC) 0.88 kg (2NO+2NC)
75
45
80
23
54Main terminalM5
Coil terminalM3.5
59.5
34.5
107.
5
16.5 12.5
158.5 (when rail height is 15)
149.5
210.5
91
54
59.5
34.5
107.
516.5 12.5
Coil terminalM3.5
Main terminalM5
SL09SL25
SL40
(Auxiliary contact 1NO+1NC)
(Auxiliary contact 1NO+1NC)
(Auxiliary contact 1NO+1NC)
(Auxiliary contact 2NO+2NC)
(Auxiliary contact 2NO+2NC)
(Auxiliary contact 2NO+2NC)
Front and side mounting auxiliary contact units cannot be attached to one contactor together.
Auxiliary contact1NO+1NC 2NO+2NC
4/T2
3/L2 13 21A1 A2
2214
1/L1 5/L3
2/T1 6/T3 4/T2
3/L2 13 21A1 A2
2214
1/L1 5/L3
2/T1 6/T3
31
32
43
44
■ Dimensions, mm
■ Wiring diagrams
Information in this catalog is subject to change without notice.
5-7, Nihonbashi Odemma-cho, Chuo-ku, Tokyo, 103-0011, Japan
URL http://www.fujielectric.co.jp/fcs/eng
2017-7 PDF FOLS 62C9-E-0178a
SL65SL80
Mass: 1.35kg (1NO+1NC) 1.40kg (2NO+2NC)
67
23
35.5
128.
5
78
20.5 16.8
168 (when rail height is 15)157.5
2.591.5
10.5
10.5(54 to 60)
(55 to 60)
Mounting hole2-M4
90
Coil terminalM3.5
Main terminalM6
Panel drilling diagram
1
2
6 T34 T22 T1
1 L1 3 L2 5 L3
67
35.5
128.
5
78
20.5 16.8
43Coil terminalM3.5
Main terminalM6
6 T34 T22 T1
1 L1 3 L2 5 L3
13 21
14 22
13 21 31 43
44322214
Mount using the two mounting holes located on the diagonal lines.
NEW