Activating the Safety Integrated Extended Functions of the CU320-2 via PROFIsafe with PROFINET SINAMICS S120 Application Description October 2010 Applications & Tools Answers for industry.

SINAMICS S120 Application Description October 2010 · Activating the Safety Integrated Extended Functions of the CU320-2 via PROFIsafe with PROFINET SINAMICS S120 . Application Description

  • Upload
    others

  • View
    9

  • Download
    0

Embed Size (px)

Citation preview

Page 1: SINAMICS S120 Application Description October 2010 · Activating the Safety Integrated Extended Functions of the CU320-2 via PROFIsafe with PROFINET SINAMICS S120 . Application Description

Activating the Safety Integrated Extended Functions of the CU320-2 via PROFIsafe with PROFINET

SINAMICS S120

Application Description October 2010

Applications & Tools

Answers for industry.

Page 2: SINAMICS S120 Application Description October 2010 · Activating the Safety Integrated Extended Functions of the CU320-2 via PROFIsafe with PROFINET SINAMICS S120 . Application Description

2 Safety Integrated

V1.1, Article ID: 42939347

Co

pyr

igh

t S

iem

en

s A

G C

op

yrig

ht-

Jah

r A

ll rig

hts

re

serv

ed

Industry Automation and Drives Technologies Service & Support Portal

This article originates from the Internet service portal of Siemens AG, Industry Automation and Drives Technologies. You can directly access the download page of this document via the following link.

http://support.automation.siemens.com/WW/view/en/42939347

If you have any questions regarding this article, please send us an e-mail:

[email protected]

Page 3: SINAMICS S120 Application Description October 2010 · Activating the Safety Integrated Extended Functions of the CU320-2 via PROFIsafe with PROFINET SINAMICS S120 . Application Description

Safety Integrated V1.1, Article ID: 42939347 3

Co

pyr

igh

t S

iem

en

s A

G C

op

yrig

ht-

Jah

r A

ll rig

hts

re

serv

ed

1s Automation Task

2 Automation Solution

3 Fundamentals

4Installation SINAMICS S120 Safety Integrated 5Configuration and Design

Activating the Safety Integrated Extended Functions Application

Commissioning 6of the CU320-2 via PROFIsafe with PROFINET

7Application Operation

8 References

9 History

Page 4: SINAMICS S120 Application Description October 2010 · Activating the Safety Integrated Extended Functions of the CU320-2 via PROFIsafe with PROFINET SINAMICS S120 . Application Description

Warranty and liability

4 Safety Integrated

V1.1, Article ID: 42939347

Co

pyr

igh

t S

iem

en

s A

G C

op

yrig

ht-

Jah

r A

ll rig

hts

re

serv

ed

Warranty and liability Note The Application Examples are not binding and do not claim to be complete

regarding the circuits shown, equipping and any eventuality. The Application Examples do not represent customer-specific solutions. They are only intended to provide support for typical applications. You are responsible for ensuring that the described products are correctly used. These Application Examples do not relieve you of the responsibility in safely and professionally using, installing, operating and servicing equipment. When using these Application Examples, you recognize that Siemens cannot be made liable for any damage/claims beyond the liability clause described. We reserve the right to make changes to these Application Examples at any time without prior notice. If there are any deviations between the recommendations provided in these Application Examples and other Siemens publications - e.g. Catalogs - then the contents of the other documents have priority.

We do not accept any liability for the information contained in this document.

Any claims against us - based on whatever legal reason - resulting from the use of the examples, information, programs, engineering and performance data etc., described in these Application Examples shall be excluded. Such an exclusion shall not apply in the case of mandatory liability, e.g. under the German Product Liability Act (“Produkthaftungsgesetz”), in case of intent, gross negligence, or injury of life, body or health, guarantee for the quality of a product, fraudulent concealment of a deficiency or breach of a condition which goes to the root of the contract (“wesentliche Vertragspflichten”). However, claims arising from a breach of a condition which goes to the root of the contract shall be limited to the foreseeable damage which is intrinsic to the contract, unless caused by intent or gross negligence or based on mandatory liability for injury of life, body or health. The above provisions do not imply a change in the burden of proof to your detriment.

The reproduction or transmission of these standard applications or excerpts of them is not permitted without the express written permission of Siemens Industry Sector.

Page 5: SINAMICS S120 Application Description October 2010 · Activating the Safety Integrated Extended Functions of the CU320-2 via PROFIsafe with PROFINET SINAMICS S120 . Application Description

Contents

Safety Integrated V1.1, Article ID: 42939347 5

Co

pyr

igh

t S

iem

en

s A

G C

op

yrig

ht-

Jah

r A

ll rig

hts

re

serv

ed

Contents Warranty and liability................................................................................................... 4 1 Automation Task................................................................................................ 6

1.1 Introduction........................................................................................... 6 1.2 Overview of the automation task.......................................................... 7

2 Automation Solution ......................................................................................... 8 2.1 Overview of the overall solution ........................................................... 8 2.2 Description of the core functionality ................................................... 10 2.3 Hardware and software components used......................................... 11

3 Fundamentals .................................................................................................. 12 3.1 PROFINET communication................................................................ 12 3.2 PROFIsafe communication ................................................................ 13

4 Installation........................................................................................................ 14 5 Configuration and Design............................................................................... 16

5.1 Passwords.......................................................................................... 16 5.2 Preparation......................................................................................... 16 5.3 Hardware configuration ...................................................................... 19 5.4 Configuring the basic drive functions ................................................. 24 5.5 PROFIsafe configuration for activating the drive-integrated safety

functions ............................................................................................. 33 5.6 Parameterizing the drive-integrated safety functions......................... 35 5.7 Configuring the F-CPU....................................................................... 42 5.8 Acceptance test.................................................................................. 47

6 Application Commissioning ........................................................................... 48 6.1 Prerequisites ...................................................................................... 48 6.2 Preparation......................................................................................... 48 6.3 Commissioning................................................................................... 48

7 Application Operation ..................................................................................... 50 7.1 Overview ............................................................................................ 50 7.2 Description ......................................................................................... 51

8 References ....................................................................................................... 52 8.1 References ......................................................................................... 52 8.2 Internet link data................................................................................. 52

9 History............................................................................................................... 53

Page 6: SINAMICS S120 Application Description October 2010 · Activating the Safety Integrated Extended Functions of the CU320-2 via PROFIsafe with PROFINET SINAMICS S120 . Application Description

1 Automation Task

1.1 Introduction

6 Safety Integrated

V1.1, Article ID: 42939347

Co

pyr

igh

t S

iem

en

s A

G C

op

yrig

ht-

Jah

r A

ll rig

hts

re

serv

ed

1 Automation Task

1.1 Introduction

At present, the following safety functions are integrated in SINAMICS S120 drives according to IEC 61800-5-2:

Table 1-1: Overview of the safety functions integrated in SINAMICS S120

Name Function Description

STO Safe Torque Off Safe separation of the torque-forming energy supply to the motor.

Restart is disabled via the power-on disable (stop function of Category 0 according to EN 60204-1).

SBC Safe Brake Control

SBC is only used with existing motor brake, the motor brake is connected to the performance connector via the outputs.

SBC always reacts in combination with STO or responding internal safety monitoring with failsafe pulse suppression.

SS1 Safe Stop 1 Fast and safely monitored drive stopping along the OFF3 ramp.

Upon expiry of a delay time or reaching the creep speed, transition to STO (stop function of Category 1 according to EN 60204-1).

Braking is not monitored with basic safety functions. In addition, the transition to STO only depends on the expiry of the delay time.

SS2 Safe Stop 2 Fast and safely monitored drive stopping along the OFF3 ramp.

Upon expiry of a delay time, transition to SOS; the drive remains under control (stop function of Category 2 according to EN 60204-1).

SOS Safe Operating Stop

This function is used to safely monitor the standstill position of a drive; the drive remains under control.

SLS Safely-Limited Speed

Safe drive speed monitoring. Parameterizable cut-off reaction in case of limit

value violation.

SSM Safe Speed Monitor

Safe display of speed limit violation (n < nx).

These extended safety functions can be activated both via PROFIsafe with PROFIBUS or PROFINET and via a terminal extension module TM54F.

In the present example, the safety functions are activated from a SIMATIC F-CPU via the PROFIsafe telegram with PROFINET.

Page 7: SINAMICS S120 Application Description October 2010 · Activating the Safety Integrated Extended Functions of the CU320-2 via PROFIsafe with PROFINET SINAMICS S120 . Application Description

1 Automation Task

1.2 Overview of the automation task

Safety Integrated V1.1, Article ID: 42939347 7

Co

pyr

igh

t S

iem

en

s A

G C

op

yrig

ht-

Jah

r A

ll rig

hts

re

serv

ed

1.2 Overview of the automation task

Fig. 1-1: Safety function concept

Further considerations are based on the following safety functions.

Table 1-2: Safety functions of the application example

E. stop button -S1

Safety function

Description Reaction

SF1 Actuation of emergency stop button

Fast stopping of drive 1 and drive 2 (SS1) subsequent pulse suppression

SF2 With open protective door 1, the drive 1 may not exceed a maximum speed

Speed monitoring at drive 1 (SLS)

SF2 With open protective door 2, the drive 2 may not exceed a maximum speed

Speed monitoring at drive 2 (SLS)

The extended safety functions integrated in the SINAMICS S120 drives shall be activated via PROFIsafe with PROFINET.

M

Drive 1

Prot. door 1

- S2

M

Drive 2

Prot. door 2

-S3

Page 8: SINAMICS S120 Application Description October 2010 · Activating the Safety Integrated Extended Functions of the CU320-2 via PROFIsafe with PROFINET SINAMICS S120 . Application Description

2 Automation Solution

2.1 Overview of the overall solution

8 Safety Integrated

V1.1, Article ID: 42939347

Co

pyr

igh

t S

iem

en

s A

G C

op

yrig

ht-

Jah

r A

ll rig

hts

re

serv

ed

2 Automation Solution

2.1 Overview of the overall solution

Scheme

The following figure shows a schematic of the key solution components:

Fig. 2-1: Relevant safety function components

E.stopProt.door 1

ResetProt.door 2

This application example shows how to activate the safety functions SS1 and SLS via PROFIsafe with PROFINET within a SINAMICS S120 drive group.

The drive group of the booksize format comprises an infeed unit and a Double Motor Module (DMM). The motor is controlled via a Control Unit CU320-2. The extended setpoint channel is used to specify the speed. The two mutually independent servomotors are controlled via the Double Motor Module. A Smart Line Module (SLM) is used as infeed unit.

Both drives use different safety functions. The safety-related signals are sensed via the failsafe inputs of a F-CPU and evaluated in the F-CPU. The drive-integrated safety functions are individually activated in each drive belonging to the SINAMICS S120 drive group via failsafe PROFIsafe communication. The F-CPU serves both as F-Host and as PROFINET IO-Controller.

Page 9: SINAMICS S120 Application Description October 2010 · Activating the Safety Integrated Extended Functions of the CU320-2 via PROFIsafe with PROFINET SINAMICS S120 . Application Description

2 Automation Solution

2.1 Overview of the overall solution

Safety Integrated V1.1, Article ID: 42939347 9

Co

pyr

igh

t S

iem

en

s A

G C

op

yrig

ht-

Jah

r A

ll rig

hts

re

serv

ed

Configuration

This application example is based on the SINAMICS S120 training case (6ZB2 480-0BA00) + CU320-2 with CBE20 and the safety training case.

Distinction

This application does not include any description regarding

the safety functions of the SINAMICS S120,

the general drive functions of the SINAMICS S120 and

the hardware interfaces of the CU320-2.

It is a precondition that you have already acquired basic knowledge regarding these topics.

Information on these issues is provided in the documents listed under References.

Knowledge required

Basic knowledge regarding the configuration of SINAMICS S120 drives with STARTER engineering software resp. SIMOTION SCOUT is absolutely required.

Page 10: SINAMICS S120 Application Description October 2010 · Activating the Safety Integrated Extended Functions of the CU320-2 via PROFIsafe with PROFINET SINAMICS S120 . Application Description

2 Automation Solution

2.2 Description of the core functionality

10 Safety Integrated

V1.1, Article ID: 42939347

Co

pyr

igh

t S

iem

en

s A

G C

op

yrig

ht-

Jah

r A

ll rig

hts

re

serv

ed

2.2 Description of the core functionality

Overview and description of the core functionality

Fig. 2-2: Safety + SINAMICS S120 training case

If emergency stop (-S1) is requested, both drives are stopped by the drive-integrated safety function SS1.

A protective door (-S2 and -S3) is assigned to each drive. When the respective protective door is opened, the speed of the relevant motor is safely monitored with regard to the preset speed limit (SLS). The speed is reduced by the unsafe setpoint channel. The other drive is not influenced. STOP C (SS2) is triggered on the relevant drive as an error reaction by SLS when exceeding the safe speed.

Other possibilities to activate the drive-integrated safety functions using the terminal extension module TM54F and the activation via PROFIsafe with PROFIBUS are described in further application examples.

Advantages of this solution

The solution described here provides the following advantages:

Convenient activation of the drive-integrated safety functions

Convenient setup due to standardized technology

The existing system can be quickly and conveniently extended

Space-saving and cost-efficient setup through integrated safety functions – no additional hardware is required

This allows to implement highly complex safety concepts.

Page 11: SINAMICS S120 Application Description October 2010 · Activating the Safety Integrated Extended Functions of the CU320-2 via PROFIsafe with PROFINET SINAMICS S120 . Application Description

2 Automation Solution

2.3 Hardware and software components used

Safety Integrated V1.1, Article ID: 42939347 11

Co

pyr

igh

t S

iem

en

s A

G C

op

yrig

ht-

Jah

r A

ll rig

hts

re

serv

ed

2.3 Hardware and software components used

The application comprises the following components:

Hardware components

Table 2-1: Hardware components

Component Qty. MLFB/Order number Note

SITOP SMART 120W 1 6EP1 333-2AA01

Safety training case 1

SINAMICS training case 1 6ZB2 480-0BA00

CU320-2 1 6SL3040-1MA00-0AA0

CompactFlash Card 1 6SL3054-0ED00-1BA0 Firmware V4.3 SP1

CBE20 1 6SL3055-0AA00-2EB0

Note The application example was tested using the listed hardware components. Alternatively, you can also use other components providing the same functionality. In such a case, it might be necessary to parameterize and wire the components differently.

Standard software components

Table 2-2: Engineering software

Component MLFB/Order number Version

STEP 7 6ES7810-4CC08-0YA5 V5.4 SP5

S7 Distributed Safety 6ES7833-1FC02-0YA5 V5.4 SP5

S7 F Configuration Pack V5.5 SP5

STARTER 6SL3072-0AA00-0AG0 V4.1 SP5

Drive ES Basic 6SW1700-5JA00-4AA0 V5.4 SP4

SIMOTION SCOUT (alternatively) 6AU1810-1BA41-1XA0 V4.1 SP5

Note SIMOTION SCOUT can be used as an alternative to the STARTER & DRIVE ES Basic software.

Licenses

Table 2-3: Licenses

License MLFB/Order number Note

SINAMICS LICENSE SAFETY INTEGRATED EXTENDED FUNCTIONS

6SL3074-0AA10-0AA0 per axis

Sample files and projects

Table 2-4: Default setting of the application example

Component Note

MC_FE_I_013_V10.zip Packed STEP 7 project

42939347_MC_FE_I_013_V11_en.pdf This document

Page 12: SINAMICS S120 Application Description October 2010 · Activating the Safety Integrated Extended Functions of the CU320-2 via PROFIsafe with PROFINET SINAMICS S120 . Application Description

3 Fundamentals

3.1 PROFINET communication

12 Safety Integrated

V1.1, Article ID: 42939347

Co

pyr

igh

t S

iem

en

s A

G C

op

yrig

ht-

Jah

r A

ll rig

hts

re

serv

ed

3 Fundamentals

3.1 PROFINET communication

Besides the MAC and IP address, PROFINET uses additionally a communication name to identify the PROFINET devices. This communication name must be unambiguous within the PROFINET network. During commissioning, each PROFINET device is assigned once a communication name by means of the HW Config which is remanently stored in the PROFINET device (so-called node initialization).

If a device is replaced, for example due to a defect, the new device has another MAC address. If it is assigned the communication name of the replaced device (e.g. by replugging a removable medium that remanently stores the communication name), it can take over the function of the replaced unit without modifying the configuration.

Rules for assigning a name:

The letters a-z and digits 0-9 are permissible

Do not use special characters ! " § $ % & / ( ) = ? * ' _ : ; > < , # + | ~ \ } ] [ {

Do not use blanks

The maximum length of a name is 240 characters.

Reserved names "port-xyz" or "port-xyz-abcde“ a,b,c,d,e, x, y, z = 0...9

The name may only include lower case letters. Upper case letters are replaced by the engineering system through lower case letters.

Do not use the minus sign on a SIMOTION controller.

Impermissible signs are replaced by the engineering system through “x“.

Page 13: SINAMICS S120 Application Description October 2010 · Activating the Safety Integrated Extended Functions of the CU320-2 via PROFIsafe with PROFINET SINAMICS S120 . Application Description

3 Fundamentals

3.2 PROFIsafe communication

Safety Integrated V1.1, Article ID: 42939347 13

Co

pyr

igh

t S

iem

en

s A

G C

op

yrig

ht-

Jah

r A

ll rig

hts

re

serv

ed

3.2 PROFIsafe communication

Each drive with configured PROFIsafe slot in the drive device represents a F-device with failsafe communication to the F-Host via PROFINET.

A separate PROFIsafe telegram is created for each drive (PROFIsafe slot). This telegram has a length of 6 bytes for each drive. The first two bytes include the useful safety data.

F-CPU Drive

Fig. 3-1: The F-CPU sends the following control signals to the drive.

PROFIdrive Safety Block 1 (F Process Data)

Byte 0 Byte 1

0 1 2 3 4 5 6 7 0 1 2 3 4 5 6 7

STO SS1 SS2 SOS SLS Res. Res. Int. Ev.

ACK Res.

SLS Limit sel.

SLS Limit sel.

Res. Res. Res. Res. Res.

Drive F-CPU

Fig. 3-2: The drive returns the status of the safety functions to the F-CPU.

PROFIdrive Safety Block 1 (F Process Data)

Byte 0 Byte 1

0 1 2 3 4 5 6 7 0 1 2 3 4 5 6 7

Power rem.

SS1 act.

SS2 act.

SOS act.

SLS act.

Res. Res. Int. Ev.

Res. SLS- Limit

SLS- Limit

SOS sele-cted

Res. Res. Res. SSM

Note Non-used drive-integrated safety functions must be deselected via a high signal.

Page 14: SINAMICS S120 Application Description October 2010 · Activating the Safety Integrated Extended Functions of the CU320-2 via PROFIsafe with PROFINET SINAMICS S120 . Application Description

4 Installation

3.2 PROFIsafe communication

14 Safety Integrated

V1.1, Article ID: 42939347

Co

pyr

igh

t S

iem

en

s A

G C

op

yrig

ht-

Jah

r A

ll rig

hts

re

serv

ed

4 Installation

Hardware installation

The following pictures show the hardware configuration of the application.

Fig. 4-1: Overview of the hardware configuration

E. stopProt.door 1

ResetProt.door 2

Fig. 4-2: DRIVE-CLiQ wiring of the SINAMICS components

Encoder 1

Encoder 2

Page 15: SINAMICS S120 Application Description October 2010 · Activating the Safety Integrated Extended Functions of the CU320-2 via PROFIsafe with PROFINET SINAMICS S120 . Application Description

4 Installation

3.2 PROFIsafe communication

Safety Integrated V1.1, Article ID: 42939347 15

Co

pyr

igh

t S

iem

en

s A

G C

op

yrig

ht-

Jah

r A

ll rig

hts

re

serv

ed

Fig. 4-3: Wiring of the control voltage on the safety training case

E. stop

Prot. door 1

Prot. door 2

Page 16: SINAMICS S120 Application Description October 2010 · Activating the Safety Integrated Extended Functions of the CU320-2 via PROFIsafe with PROFINET SINAMICS S120 . Application Description

5 Configuration and Design

5.1 Passwords

16 Safety Integrated

V1.1, Article ID: 42939347

Co

pyr

igh

t S

iem

en

s A

G C

op

yrig

ht-

Jah

r A

ll rig

hts

re

serv

ed

5 Configuration and Design This chapter describes how to parameterize the individual components. Both STARTER & DRIVE ES Basic and SIMOTION SCOUT can be used as engineering software for the SINAMICS S120. SIMOTION SCOUT was used to create this sample project. STEP 7 and Distributed Safety are required to program the F-CPU.

Note In the following, the English language setting was used in the SIMATIC Manager. Other names may result with the German setting.

5.1 Passwords

For reasons of simplicity, a common program and hardware safety password is used within the project for the SIMATIC components. A common password is also used for the drives with the safety configuration of the SINAMICS components.

Safety password for F-CPU: "0"

Safety password for SINAMICS: "1"

These passwords should not be used in a real application!

5.2 Preparation

In this application example, the PROFINET interfaces of the F-CPU and SINAMICS S120 (CBE20) are used for programming and replacing the failsafe signals (PROFIdrive data).

Table 5-1: Set IP address and communication name

No. Action Remark

1. To go online onto the SIMATIC controller resp. the CU320-2, set the PG/PC Ethernet interface as follows. IP address: 192.168. 0 .3 Subnet mask: 255.255.255.0 Connect the PG/PC to the CBE20 of the CU320-2.

Page 17: SINAMICS S120 Application Description October 2010 · Activating the Safety Integrated Extended Functions of the CU320-2 via PROFIsafe with PROFINET SINAMICS S120 . Application Description

5 Configuration and Design

5.2 Preparation

Safety Integrated V1.1, Article ID: 42939347 17

Co

pyr

igh

t S

iem

en

s A

G C

op

yrig

ht-

Jah

r A

ll rig

hts

re

serv

ed

No. Action Remark

2. Node initialization To assign the required IP address and communication name to the device, open the HW Config. Under PLC Ethernet Edit Ethernet Node, you can initialize all reachable nodes

3. Node initialization The SIMATIC controller has the following IP address and communication name: IP address: 192.168. 0 .1 Subnet mask: 255.255.255.0 Communication name: PN-IO “pn-io“

Page 18: SINAMICS S120 Application Description October 2010 · Activating the Safety Integrated Extended Functions of the CU320-2 via PROFIsafe with PROFINET SINAMICS S120 . Application Description

5 Configuration and Design

5.2 Preparation

18 Safety Integrated

V1.1, Article ID: 42939347

Co

pyr

igh

t S

iem

en

s A

G C

op

yrig

ht-

Jah

r A

ll rig

hts

re

serv

ed

No. Action Remark

4. Communication name Devices being configured in the SIMOTION SCOUT (e.g. SIMOTION, SINAMICS) may not include a “-“ in the communication name. Devices such as the S7-300 are not affected. This limitation does not apply to Step7.

5. Node initialization The CU320-2 shall have the following IP address and communication name: IP address: 192.168. 0 .2 Subnet mask: 255.255.255.0 Communication name: S120xCU320x2xDPxCBE20 “s120xcu320x2xdpxcbe20“

Page 19: SINAMICS S120 Application Description October 2010 · Activating the Safety Integrated Extended Functions of the CU320-2 via PROFIsafe with PROFINET SINAMICS S120 . Application Description

5 Configuration and Design

5.3 Hardware configuration

Safety Integrated V1.1, Article ID: 42939347 19

Co

pyr

igh

t S

iem

en

s A

G C

op

yrig

ht-

Jah

r A

ll rig

hts

re

serv

ed

5.3 Hardware configuration

Table 5-2: Hardware configuration

No. Action Remark

1. In the SIMATIC Manager, insert a SIMATIC 300 station in the project.

2. In the HW Config, completely create and parameterize the station. For this, move the modules included in the Table 2-1 via Drag&Drop from the hardware catalog to the configuration screen.

3. Double-click on the PROFINET interface PN-IO (see line no. 2) to open the interface properties. The following properties are used in the sample project. IP address: 192.168. 0 .1 Subnet mask: 255.255.255.0 Communication name: PN-IO “pn-io“

Page 20: SINAMICS S120 Application Description October 2010 · Activating the Safety Integrated Extended Functions of the CU320-2 via PROFIsafe with PROFINET SINAMICS S120 . Application Description

5 Configuration and Design

5.3 Hardware configuration

20 Safety Integrated

V1.1, Article ID: 42939347

Co

pyr

igh

t S

iem

en

s A

G C

op

yrig

ht-

Jah

r A

ll rig

hts

re

serv

ed

No. Action Remark

4. Configuring the F-CPU In the Properties screen of the F-CPU,, activate the access protection for the F-CPU in the Protection tab and protect it with a password. Press "CPU contains safety program" to activate the safety program on the F-CPU. Safety password for F-CPU: "0"

5. Configuring the F-DI Activate safety mode Configure the PROFIsafe address according to the DIL switch.

Page 21: SINAMICS S120 Application Description October 2010 · Activating the Safety Integrated Extended Functions of the CU320-2 via PROFIsafe with PROFINET SINAMICS S120 . Application Description

5 Configuration and Design

5.3 Hardware configuration

Safety Integrated V1.1, Article ID: 42939347 21

Co

pyr

igh

t S

iem

en

s A

G C

op

yrig

ht-

Jah

r A

ll rig

hts

re

serv

ed

No. Action Remark

6. Configuring the F-DI F-DI 0 (Channel 0, 12; -S1) F-DI 1 (Channel 1, 13; -S2) F-DI 2 (Channel 2, 14; -S3) F-DI 3 (Channel 3, 15; -S4)

7. Configuring the F-DO Configure the PROFIsafe address according to the DIL switch.

Page 22: SINAMICS S120 Application Description October 2010 · Activating the Safety Integrated Extended Functions of the CU320-2 via PROFIsafe with PROFINET SINAMICS S120 . Application Description

5 Configuration and Design

5.3 Hardware configuration

22 Safety Integrated

V1.1, Article ID: 42939347

Co

pyr

igh

t S

iem

en

s A

G C

op

yrig

ht-

Jah

r A

ll rig

hts

re

serv

ed

No. Action Remark

8. Configuring the F-DO F-DO 7 (signal lamp of -S4)

9. In the device version 4.3, add SINAMICS S120 CU320-2 to the PROFINET.

10. Configuring the CU320-2 IP address: 192.168. 0 .2 Subnet mask: 255.255.255.0

Page 23: SINAMICS S120 Application Description October 2010 · Activating the Safety Integrated Extended Functions of the CU320-2 via PROFIsafe with PROFINET SINAMICS S120 . Application Description

5 Configuration and Design

5.3 Hardware configuration

Safety Integrated V1.1, Article ID: 42939347 23

Co

pyr

igh

t S

iem

en

s A

G C

op

yrig

ht-

Jah

r A

ll rig

hts

re

serv

ed

No. Action Remark

11. Configuring the CU320-2 Communication name: S120xCU320x2xDPxCBE20 “s120xcu320x2xdpxcbe20“ The setting “Assign IP address via IO Controller“ has been activated by default and should not be modified.

Note The PROFINET specification stipulates the use of DHCP. However this is currently not supported by the Siemens products for PROFINET. If a DHCP server was provided, this would assign the IP address to the device. At present, this task is assumed by the assigned controller.

12. Save and compile HW Config.

13. Load HW Config into the F-CPU.

Page 24: SINAMICS S120 Application Description October 2010 · Activating the Safety Integrated Extended Functions of the CU320-2 via PROFIsafe with PROFINET SINAMICS S120 . Application Description

5 Configuration and Design

5.4 Configuring the basic drive functions

24 Safety Integrated

V1.1, Article ID: 42939347

Co

pyr

igh

t S

iem

en

s A

G C

op

yrig

ht-

Jah

r A

ll rig

hts

re

serv

ed

5.4 Configuring the basic drive functions

First, the hardware provided must be installed in the drive system and the required motion functions must be set up.

Table 5-3: Configuring the basic functions

No. Action Remark

1. Double-click on Commissioning to open the STARTER resp. SIMOTON SCOUT program.

2. Go online

3. Restore factory settings on the SINAMICS S120.

Page 25: SINAMICS S120 Application Description October 2010 · Activating the Safety Integrated Extended Functions of the CU320-2 via PROFIsafe with PROFINET SINAMICS S120 . Application Description

5 Configuration and Design

5.4 Configuring the basic drive functions

Safety Integrated V1.1, Article ID: 42939347 25

Co

pyr

igh

t S

iem

en

s A

G C

op

yrig

ht-

Jah

r A

ll rig

hts

re

serv

ed

No. Action Remark

4. Configure drive unit automatically group (first commissioning).

5. Select "Servo" as drive object type.

6. Complete the automatic configuration.

7. Save

Page 26: SINAMICS S120 Application Description October 2010 · Activating the Safety Integrated Extended Functions of the CU320-2 via PROFIsafe with PROFINET SINAMICS S120 . Application Description

5 Configuration and Design

5.4 Configuring the basic drive functions

26 Safety Integrated

V1.1, Article ID: 42939347

Co

pyr

igh

t S

iem

en

s A

G C

op

yrig

ht-

Jah

r A

ll rig

hts

re

serv

ed

No. Action Remark

8. Reconfiguring both drives In the project navigator with drive 1 (SERVO_02), open the configuration screen. “Configure DDS“ starts the menu-assisted configuration. Note The following paragraphs only describe the screens to be modified.

9. Reconfiguring both drives Under control structure, activate the "Extended setpoint channel".

Page 27: SINAMICS S120 Application Description October 2010 · Activating the Safety Integrated Extended Functions of the CU320-2 via PROFIsafe with PROFINET SINAMICS S120 . Application Description

5 Configuration and Design

5.4 Configuring the basic drive functions

Safety Integrated V1.1, Article ID: 42939347 27

Co

pyr

igh

t S

iem

en

s A

G C

op

yrig

ht-

Jah

r A

ll rig

hts

re

serv

ed

No. Action Remark

10. Reconfiguring both drives Select the power unit

11. Reconfiguring both drives Configure a signal for “Infeed in operation“ (p0864). In the example, the fixed binector 1 is used. Note In a real application, you should not use the fixed binector 1 as a signal for “infeed in operation“ (p0864).

Page 28: SINAMICS S120 Application Description October 2010 · Activating the Safety Integrated Extended Functions of the CU320-2 via PROFIsafe with PROFINET SINAMICS S120 . Application Description

5 Configuration and Design

5.4 Configuring the basic drive functions

28 Safety Integrated

V1.1, Article ID: 42939347

Co

pyr

igh

t S

iem

en

s A

G C

op

yrig

ht-

Jah

r A

ll rig

hts

re

serv

ed

No. Action Remark

12. Reconfiguring drive 2 The second drive is not equipped with a DRIVE-CliQ encoder, the motor must be manually selected. The motor type 1FK7022-5AK71-1AG0 is used in the sample project.

13. Reconfiguring drive 2 Analogously to the motor, the encoder must also be selected manually. This is also performed via the type number (MLFB).

14. As the SLM 5 kW has no DRIVE-CLiQ interfaces, the infeed unit need not be parameterized.

Notice: When using a Single Line Module for 1AC 230V (SINAMICS S120 training case), adapt the dc link parameters as follows: p0210: 345V (both drives) p1244[0]: 401V (SERVO _02 only) p1248[0]: 240V (SERVO _02 only) See also the FAQ-ID: 27038754 Upgrading / replacing a Motor Module in the SINAMICS S120 training case http://support.automation.siemens.com/WW/view/de/27038754

Page 29: SINAMICS S120 Application Description October 2010 · Activating the Safety Integrated Extended Functions of the CU320-2 via PROFIsafe with PROFINET SINAMICS S120 . Application Description

5 Configuration and Design

5.4 Configuring the basic drive functions

Safety Integrated V1.1, Article ID: 42939347 29

Co

pyr

igh

t S

iem

en

s A

G C

op

yrig

ht-

Jah

r A

ll rig

hts

re

serv

ed

No. Action Remark

15. Reconfiguring both drives As the function "Safely-Limited Speed" (SLS) is parameterized in the following, the speed controller of the SINAMICS training case should be set as follows. A speed controller which is set to an excessively low value may cause the Alarm 30714 “Safely-Limited Speed exceeded“! P gain = 0.3 Nms/rad Reset time = 5.0 ms

16. Reconfiguring both drives Select the “Standard telegram 1“ for both drives.

17. Reconfiguring both drives Then change to “Free telegram configuration with BICO“, which retains the links of the “Standard telegram 1“. These may be adapted later for the example.

Page 30: SINAMICS S120 Application Description October 2010 · Activating the Safety Integrated Extended Functions of the CU320-2 via PROFIsafe with PROFINET SINAMICS S120 . Application Description

5 Configuration and Design

5.4 Configuring the basic drive functions

30 Safety Integrated

V1.1, Article ID: 42939347

Co

pyr

igh

t S

iem

en

s A

G C

op

yrig

ht-

Jah

r A

ll rig

hts

re

serv

ed

No. Action Remark

18. Configuring both drives Under Control logics, link the On/Off 1 enable to the digital input 0 (CU r722.0).

19. Configuring the CU320-2 Acknowledge all DO faults / warnings with the digital input 2 (r722.2). p2102 = r722.2

20. Configuring both drives Under Setpoint channel ramp-function generator, set the OFF3 ramp-down time and the (standard) ramp-down time. Press the button to parameterize the basic ramp-function generator.

Page 31: SINAMICS S120 Application Description October 2010 · Activating the Safety Integrated Extended Functions of the CU320-2 via PROFIsafe with PROFINET SINAMICS S120 . Application Description

5 Configuration and Design

5.4 Configuring the basic drive functions

Safety Integrated V1.1, Article ID: 42939347 31

Co

pyr

igh

t S

iem

en

s A

G C

op

yrig

ht-

Jah

r A

ll rig

hts

re

serv

ed

No. Action Remark

21. Configuring both drives Set the ramp-down time (p1121) such that the drive is below the SLS limit value when selecting SLS within p9551. The OFF3 ramp-down time (p1135) is used for braking with SS1.

22. Configuring drive 1 Specify the drive speeds for normal mode and for the safety function SLS. For this, open the respective setting screen under Drive Setpoint channel Fixed setpoints. Make the following interconnections: Bit0: Control Unit DI1 (r722.1) Bit1: r9720.4 (SLS deselected) Bit2: Control Unit DI4 (r722.4) Bit3: 0 Enter the following fixed values: Fixed value 1: 20 rpm Fixed value 3: 800 rpm Fixed value 5: 1000 rpm Fixed value 7: 1000 rpm The fixed setpoint effective p1024 must be connected to the p1070[0] main setpoint.

Explanation When the signal "SLS deselected" is active, the protective door is closed and the high speed is preset. With low signal, the system switches over from high speed to low speed. By actuating -S9 (DI4), a fixed speed of n = 1000 rpm is preset with running drive, independently of the status of the protective door.

Page 32: SINAMICS S120 Application Description October 2010 · Activating the Safety Integrated Extended Functions of the CU320-2 via PROFIsafe with PROFINET SINAMICS S120 . Application Description

5 Configuration and Design

5.4 Configuring the basic drive functions

32 Safety Integrated

V1.1, Article ID: 42939347

Co

pyr

igh

t S

iem

en

s A

G C

op

yrig

ht-

Jah

r A

ll rig

hts

re

serv

ed

No. Action Remark

23. Configuring drive 2 Specify the drive speeds for normal mode and for the safety function SLS. For this, open the respective setting screen under Drive Setpoint channel Fixed setpoints. Make the following interconnections: Bit0: Control Unit DI1 (r722.1) Bit1: r9720.4 (SLS deselected) Bit2: Control Unit DI4 (r722.4) Bit3: 0 Enter the following fixed values: Fixed value 1: 33 rpm Fixed value 3: 333 rpm Fixed value 5: 666 rpm Fixed value 7: 666 rpm The fixed setpoint effective p1024 must be connected to the p1070 main setpoint.

Explanation When the signal "SLS deselected" is active, the protective door is closed and the high speed is preset. With low signal, the system switches over from high speed to low speed. By actuating -S9 (DI4), a fixed speed of n = 666 rpm is preset with running drive, independently of the status of the protective door.

24. Save project

25. Go online

26. Load project into the target device

27. Copy RAM to ROM

Page 33: SINAMICS S120 Application Description October 2010 · Activating the Safety Integrated Extended Functions of the CU320-2 via PROFIsafe with PROFINET SINAMICS S120 . Application Description

5 Configuration and Design

5.5 PROFIsafe configuration for activating the drive-integrated safety functions

Safety Integrated V1.1, Article ID: 42939347 33

Co

pyr

igh

t S

iem

en

s A

G C

op

yrig

ht-

Jah

r A

ll rig

hts

re

serv

ed

5.5 PROFIsafe configuration for activating the drive-integrated safety functions

Table 5-4: PROFIsafe configuration

No. Action Remark

1. For both drives, press the buttons “Insert line“ and “PROFIsafe“ to create a PROFIsafe slot (6 bytes). Then transfer the telegram configuration to the HW Config.

2. Open the HW Config The telegram selection and address assignment have been automatically entered in the HW Config. The address assignment can be modified here.

Page 34: SINAMICS S120 Application Description October 2010 · Activating the Safety Integrated Extended Functions of the CU320-2 via PROFIsafe with PROFINET SINAMICS S120 . Application Description

5 Configuration and Design

5.5 PROFIsafe configuration for activating the drive-integrated safety functions

34 Safety Integrated

V1.1, Article ID: 42939347

Co

pyr

igh

t S

iem

en

s A

G C

op

yrig

ht-

Jah

r A

ll rig

hts

re

serv

ed

No. Action Remark

3. Double-click on PROFIsafe (see line no. 2) to open the PROFIsafe properties.

4. Further settings can be made under the “PROFIsafe“ tab. Then enter the value of F_Dest_Add in the STARTER for drive 1 and 2 in the hex format. In this example, C6hex stands for drive 1 and C5hex for drive 2. Note The watchdog time (F_WD_Time = 150ms) should not be an integer multiple of the OB35 cycle. In the example, the OB35 cycle is 100ms.

5. Save and compile the hardware configuration.

6. Then download the HW Config into the target system.

Page 35: SINAMICS S120 Application Description October 2010 · Activating the Safety Integrated Extended Functions of the CU320-2 via PROFIsafe with PROFINET SINAMICS S120 . Application Description

5 Configuration and Design

5.6 Parameterizing the drive-integrated safety functions

Safety Integrated V1.1, Article ID: 42939347 35

Co

pyr

igh

t S

iem

en

s A

G C

op

yrig

ht-

Jah

r A

ll rig

hts

re

serv

ed

5.6 Parameterizing the drive-integrated safety functions

Table 5-5: Parameterizing the drive-integrated safety functions

No. Action Remark

1. Go online with the STARTER.

2. Configuring both drives Open the “Safety integrated“ screen of drive 1 / drive 2 (SERVO_02 / SERVO_03) and press “Change settings“ to activate the commissioning mode. The password after first commissioning is “0“.

3. Configuring both drives Change the control selection to "Motion monitoring via PROFIsafe".

4. Configuring both drives Close the message

Page 36: SINAMICS S120 Application Description October 2010 · Activating the Safety Integrated Extended Functions of the CU320-2 via PROFIsafe with PROFINET SINAMICS S120 . Application Description

5 Configuration and Design

5.6 Parameterizing the drive-integrated safety functions

36 Safety Integrated

V1.1, Article ID: 42939347

Co

pyr

igh

t S

iem

en

s A

G C

op

yrig

ht-

Jah

r A

ll rig

hts

re

serv

ed

No. Action Remark

5. Configuring both drives Click on "configuration".

6. Configuring both drives In the example, configure the PROFIsafe addresses:

C6hex for drive 1 resp.

C5hex for drive 2 (see also Chapter 5.5, Table 5-4, No. 4). Drive type: Rotary axis / spindle Connect the signal source for test stop selection to the DI3 (r722.3) of the CU320-2.

7. Configuring both drives The drive encoder data are entered in the "Encoder parameterization" screen (see line no. 6). In this example, this need not be changed.

Page 37: SINAMICS S120 Application Description October 2010 · Activating the Safety Integrated Extended Functions of the CU320-2 via PROFIsafe with PROFINET SINAMICS S120 . Application Description

5 Configuration and Design

5.6 Parameterizing the drive-integrated safety functions

Safety Integrated V1.1, Article ID: 42939347 37

Co

pyr

igh

t S

iem

en

s A

G C

op

yrig

ht-

Jah

r A

ll rig

hts

re

serv

ed

No. Action Remark

8. Configuring both drives Copy parameters Click on "Activate settings".

9. Configuring both drives Upon first commissioning, you are requested to change the safety password. The password preset for first commissioning is "0". The new password in the example has the value “1“.

10. Configuring both drives Click on "Entire project" to save the changes made in the drive.

11. Configuring both drives Confirm the following message with "Yes". The data are copied from RAM to ROM.

12. Go offline

13. Then perform a Power On reset of the Control Unit.

POWER OFF/ON

14. Go online

15. Load the configuration into the PG

Page 38: SINAMICS S120 Application Description October 2010 · Activating the Safety Integrated Extended Functions of the CU320-2 via PROFIsafe with PROFINET SINAMICS S120 . Application Description

5 Configuration and Design

5.6 Parameterizing the drive-integrated safety functions

38 Safety Integrated

V1.1, Article ID: 42939347

Co

pyr

igh

t S

iem

en

s A

G C

op

yrig

ht-

Jah

r A

ll rig

hts

re

serv

ed

No. Action Remark

16. Save the project

From now on, “rpm” instead of “mm/min” will be displayed as the speed in the safety parameterization screens.

17. Checksum errors occur after POWER ON. These errors are caused by the modified data structure when toggling from linear axis to rotary axis. These errors can be eliminated by triggering parameter copying once more in the “Safety Integrated“ screen. In this example, parameters are copied when setting further parameters.

18. Configuring both drives Press “Change settings “ to activate input screens. Password: “1“

Page 39: SINAMICS S120 Application Description October 2010 · Activating the Safety Integrated Extended Functions of the CU320-2 via PROFIsafe with PROFINET SINAMICS S120 . Application Description

5 Configuration and Design

5.6 Parameterizing the drive-integrated safety functions

Safety Integrated V1.1, Article ID: 42939347 39

Co

pyr

igh

t S

iem

en

s A

G C

op

yrig

ht-

Jah

r A

ll rig

hts

re

serv

ed

No. Action Remark

19. Configuring both drives In the "Safe stops" screen, enter the following values for the example: Delay time STOP B / SS1 STO = 400 ms Delay time STOP C / SS2 SOS = 400 ms Creep speed SS1 = 0 rpm Standstill tolerance SOS = 1.0°

20. Configuring both drives In the screen "Acceleration monitoring", enter the following value for the example: Acceleration monitoring = 300 rpm

Page 40: SINAMICS S120 Application Description October 2010 · Activating the Safety Integrated Extended Functions of the CU320-2 via PROFIsafe with PROFINET SINAMICS S120 . Application Description

5 Configuration and Design

5.6 Parameterizing the drive-integrated safety functions

40 Safety Integrated

V1.1, Article ID: 42939347

Co

pyr

igh

t S

iem

en

s A

G C

op

yrig

ht-

Jah

r A

ll rig

hts

re

serv

ed

No. Action Remark

21. Configuring both drives Enter the max. limit speed in the screen "Safety reduced speed (SLS)". Only stage 1 is used for speed monitoring t, nmax with stage 1: 25 rpm for drive 1 40 rpm for drive 2 In addition, select the stop reaction initiated upon limit value violation. STOP C = internal SS2 Delay time SLS -> SLS active = 500 ms

Note Max. limit speed = still just permissible speed with open protective door. Within the delay time "selection SLS SLS active" (p9551), the drive speed must remain below the limit value nmax.

22. Configuring both drives Activate safety functions

23. Configuring both drives Copy parameters Click on "Activate settings"

Page 41: SINAMICS S120 Application Description October 2010 · Activating the Safety Integrated Extended Functions of the CU320-2 via PROFIsafe with PROFINET SINAMICS S120 . Application Description

5 Configuration and Design

5.6 Parameterizing the drive-integrated safety functions

Safety Integrated V1.1, Article ID: 42939347 41

Co

pyr

igh

t S

iem

en

s A

G C

op

yrig

ht-

Jah

r A

ll rig

hts

re

serv

ed

No. Action Remark

24. Configuring both drives Click on "Entire project" to save the changes made in the drive.

25. Configuring both drives Confirm the following message with "Yes". The data are copied from RAM to ROM.

26. Acknowledge all messages regarding the acceptance test Notice An acceptance test must be performed on a real machine (see also Chapter Fehler! Verweisquelle konnte nicht gefunden werden.).

27. Go offline

28. Then perform a Power On reset of the Control Unit.

POWER OFF/ON

29. Go online

30. Load the configuration into the PG

31. Save the project

Page 42: SINAMICS S120 Application Description October 2010 · Activating the Safety Integrated Extended Functions of the CU320-2 via PROFIsafe with PROFINET SINAMICS S120 . Application Description

5 Configuration and Design

5.7 Configuring the F-CPU

42 Safety Integrated

V1.1, Article ID: 42939347

Co

pyr

igh

t S

iem

en

s A

G C

op

yrig

ht-

Jah

r A

ll rig

hts

re

serv

ed

No. Action Remark

32. After performing the safety commissioning for all drives, you can traverse the drives with deselected emergency stop. The use of the drive-integrated safety functions is selected. These can be activated resp. deactivated via the control elements on the F-CPU. Only the following messages shall be displayed.

Note These messages do not influence the functionality described above. They only indicate that a test stop must be performed for the drive safety functions (A1697). These are warnings, that means the drives can be activated and traversed as soon as the configuration of the SIMATIC S7 has been completed. In this example, the test stop can be performed via the switch -S9 (DI3).

5.7 Configuring the F-CPU

No standard program is required for this application example as the drives are only controlled via BICO connections in the SINAMICS. In most of the real applications, a program which is independent from the safety program is to be expected, which is based on a standard telegram.

In this example, only the necessary enables are defined in the control word in OB1.

In this example, the safety program is executed in the F-CPU in the failsafe function block FB1. A basic program sequence has been selected to illustrate the functions. Please refer to the Distributed Safety manuals regarding complex safety logistics and supplementary conditions to be observed when creating the safety program.

Notice Such a program may not be used for real applications.

Start with the F-Call block which is used to call up the safety program. For this, insert a function (here FC1) in the block folder using the generation language F-Call. The alarm OB35 is required to cyclically call up the safety program.

In this example, the safety program is processed in a function block (here FB1), that means only the FB1 with the generation language F-KOP or F-FUP must be inserted.

Page 43: SINAMICS S120 Application Description October 2010 · Activating the Safety Integrated Extended Functions of the CU320-2 via PROFIsafe with PROFINET SINAMICS S120 . Application Description

5 Configuration and Design

5.7 Configuring the F-CPU

Safety Integrated V1.1, Article ID: 42939347 43

Co

pyr

igh

t S

iem

en

s A

G C

op

yrig

ht-

Jah

r A

ll rig

hts

re

serv

ed

Table 5-6: Configuring the F-CPU

No. Action Remark

1. OB1 Fixed writing of all enables onto the control word

2. OB35 Call-up of the safety program

3. FB1 Network 1: Activate automatic acknowledgement

Page 44: SINAMICS S120 Application Description October 2010 · Activating the Safety Integrated Extended Functions of the CU320-2 via PROFIsafe with PROFINET SINAMICS S120 . Application Description

5 Configuration and Design

5.7 Configuring the F-CPU

44 Safety Integrated

V1.1, Article ID: 42939347

Co

pyr

igh

t S

iem

en

s A

G C

op

yrig

ht-

Jah

r A

ll rig

hts

re

serv

ed

No. Action Remark

4. FB1 Drive 1 Address 15 corresponds to byte 0 on the PROFIsafe frame. Network 2: Fixed deselection of the function STO with VKE1 on the PROFIsafe control word Network 3: -S1 (emergency stop) is connected to the PROFIsafe control word with SS1. Network 4, 5: Fixed deselection of the functions SS2 and SOS with VKE1 on the PROFIsafe control word Network 6: -S2 (protective door 1) is connected to the PROFIsafe control word with SLS. Must be inverted as -S2 has been wired as NO contact / NC contact. Network 7: -S4 (acknowledgement) is connected to the PROFIsafe control word with “Internal Event Acknowledge“.

5. FB1 Drive 1 Address 16 corresponds to byte 1 on the PROFIsafe frame. Network 8 and 9: Fixed selection of the SLS speed stage 1 on the PROFIsafe control word

Page 45: SINAMICS S120 Application Description October 2010 · Activating the Safety Integrated Extended Functions of the CU320-2 via PROFIsafe with PROFINET SINAMICS S120 . Application Description

5 Configuration and Design

5.7 Configuring the F-CPU

Safety Integrated V1.1, Article ID: 42939347 45

Co

pyr

igh

t S

iem

en

s A

G C

op

yrig

ht-

Jah

r A

ll rig

hts

re

serv

ed

No. Action Remark

6. FB1 Drive 2 Address 21 corresponds to byte 0 on the PROFIsafe frame. Network 10: Fixed deselection of the function STO with VKE1 on the PROFIsafe control word Network 11: -S1 (emergency stop) is connected to the PROFIsafe control word with SS1. Network 12, 13: Fixed deselection of the functions SS2 and SOS with VKE1 on the PROFIsafe control word. Network 14: -S3 (protective door 2) is connected to the PROFIsafe control word with SLS. Network 15: -S4 (acknowledgement) is connected to the PROFIsafe control word with “Internal Event Acknowledge“.

7. FB1 Drive 2 Address 22 corresponds to byte 1 on the PROFIsafe frame. Network 16 and 17: Fixed selection of the SLS speed stage 1 on the PROFIsafe control word.

Page 46: SINAMICS S120 Application Description October 2010 · Activating the Safety Integrated Extended Functions of the CU320-2 via PROFIsafe with PROFINET SINAMICS S120 . Application Description

5 Configuration and Design

5.7 Configuring the F-CPU

46 Safety Integrated

V1.1, Article ID: 42939347

Co

pyr

igh

t S

iem

en

s A

G C

op

yrig

ht-

Jah

r A

ll rig

hts

re

serv

ed

No. Action Remark

8. FB1 Network 18: Signal lamp activation in -S4 with safe standstill detection. Network 19: -S4 is used to reintegrate the drive. (Acknowledge safety alarms)

9. Creating the F-runtime group For this, create a new function FC1 in the language F-CALL.

10. Creating the F-runtime group The safety program (FB1) is assigned to FC1, the corresponding I-DB is defined.

Page 47: SINAMICS S120 Application Description October 2010 · Activating the Safety Integrated Extended Functions of the CU320-2 via PROFIsafe with PROFINET SINAMICS S120 . Application Description

5 Configuration and Design

5.8 Acceptance test

Safety Integrated V1.1, Article ID: 42939347 47

Co

pyr

igh

t S

iem

en

s A

G C

op

yrig

ht-

Jah

r A

ll rig

hts

re

serv

ed

No. Action Remark

11. Then generate the safety program and load it into the CPU. In addition, load the standard blocks into the F-CPU.

5.8 Acceptance test

An acceptance test must be performed to verify the safety-relevant parameters upon first machine commissioning and changing the safety-relevant parameters. The acceptance test must be recorded accordingly. The acceptance certificates are to be stored and archived appropriately.

The acceptance test must be performed following successful parameterization and a Power On reset.

Information regarding the acceptance test, the acceptance certificate and an example for the relevant acceptance certificate is provided in the “Function Manual SINAMICS S120 Safety Integrated" (FHS) in the chapter “Acceptance Test and Acceptance Certificate“.

Page 48: SINAMICS S120 Application Description October 2010 · Activating the Safety Integrated Extended Functions of the CU320-2 via PROFIsafe with PROFINET SINAMICS S120 . Application Description

6 Application Commissioning

6.1 Prerequisites

48 Safety Integrated

V1.1, Article ID: 42939347

Co

pyr

igh

t S

iem

en

s A

G C

op

yrig

ht-

Jah

r A

ll rig

hts

re

serv

ed

6 Application Commissioning This documents describes the creation of the application example configuration has been described step by step. If you wish to load the sample project directly onto the hardware, please observe the following steps.

Fist of all, perform a general reset of all components (S7-F-CPU and SINAMICS S120) resp. restore factory settings.

6.1 Prerequisites

The SIMATIC components have been installed and interconnected. The PROFIsafe addresses of the failsafe input and output modules must be set via DIL switches (see Chapter 5.3, Table 5-2, No. 5 and 7).

All components have been connected according to Chapter 4.

The DRIVE-CLiQ topology of the SINAMICS components has been maintained.

The motors are connected to the Motor Module via performance and encoder cables.

The Motor Module has been properly connected to the infeed unit (DC link and control voltage DC 24 V).

The infeed unit has been connected to the power supply.

The components are supplied with DC 24 V.

6.2 Preparation

(See Chapter Fehler! Verweisquelle konnte nicht gefunden werden.)

6.3 Commissioning

Table 6-1: Commissioning the sample application

No. Action Remark

1. Loading the F-CPU configuration Download the hardware configuration of the S7-F-CPU. Double-click on “Hardware“ to open the hardware configuration.

Note

If a safety program was previously stored on the CPU, this is password-protected. This password must be known for the download. If it is not known, delete the memory card using a suitable device (e.g. SIEMENS PG).

Notice

The card will be destroyed when being deleted resp. formatted using a card reader!

Page 49: SINAMICS S120 Application Description October 2010 · Activating the Safety Integrated Extended Functions of the CU320-2 via PROFIsafe with PROFINET SINAMICS S120 . Application Description

6 Application Commissioning

6.3 Commissioning

Safety Integrated V1.1, Article ID: 42939347 49

Co

pyr

igh

t S

iem

en

s A

G C

op

yrig

ht-

Jah

r A

ll rig

hts

re

serv

ed

No. Action Remark

2. After successfully downloading the hardware configuration, the program blocks must be loaded onto the F-CPU. First, open the screen for loading the safety function via the “yellow“ button in the function bar. Press the “Load” button to start the download.

3. The remaining (non-safe) blocks are loaded as usual.

4. Loading the SINAMICS S120 configuration The project can be directly loaded into the SINAMICS S120. As the serial numbers of the encoder modules do not match those of the devices, various safety faults are output after the download. Enter the new serial numbers in the safety configuration analogously to series commissioning. This is done via “Confirm HW replacement“. The easiest way is to open the safety screens on both drives and press the button “Confirm HW replacement“.

5. Then initiate the backup from RAM to ROM for the SINAMICS and perform a restart (Power-On reset).

Page 50: SINAMICS S120 Application Description October 2010 · Activating the Safety Integrated Extended Functions of the CU320-2 via PROFIsafe with PROFINET SINAMICS S120 . Application Description

7 Application Operation

7.1 Overview

50 Safety Integrated

V1.1, Article ID: 42939347

Co

pyr

igh

t S

iem

en

s A

G C

op

yrig

ht-

Jah

r A

ll rig

hts

re

serv

ed

7 Application Operation

7.1 Overview

Fig. 7-1: Control elements of the sample application

The switches -S1 to -S4 are located on a switch box belonging to the safety training case. They are used to select the different safety functions.

The switches -S5 to -S9 are located on a switch box belonging to the SINAMICS training case. These switches are used to activate / deactivate the drives, specify different speeds, start the test function of the safety functions and acknowledge pending errors.

Page 51: SINAMICS S120 Application Description October 2010 · Activating the Safety Integrated Extended Functions of the CU320-2 via PROFIsafe with PROFINET SINAMICS S120 . Application Description

7 Application Operation

7.2 Description

Safety Integrated V1.1, Article ID: 42939347 51

Co

pyr

igh

t S

iem

en

s A

G C

op

yrig

ht-

Jah

r A

ll rig

hts

re

serv

ed

7.2 Description

Reintegration

The drives must be reintegrated following Power OFF/ON. After pressing the button -S4, all alarm messages are acknowledged and the signal lamp of -S4 is lit.

Activation / deactivation

The emergency stop button -S1 must be unlocked to traverse the drives. Press the switch -S5 to activate both drives (OFF1). -S6 allows to toggle between the speed setpoints 0 and 800 rpm on the drive 1 (resp. 333 rpm on the drive 2).

Alarm acknowledgement

Pending alarms on the SINAMICS can be acknowledged with -S7. This does not refer to safety alarms which must be acknowledged in failsafe mode via -S4. The test stop of the safety functions which must be performed cyclically is activated via -S8.

Protective door 1

With closed protective door 1 (switch -S2), the drive 1 is rotated with n = 800 rpm. When opening the protective door 1, a data record is switched over in drive 1 and the setpoint speed is n = 20 rpm. With open protective door 1, the safety function SLS in drive 1 is activated. By closing the protective door 1, the speed n = 800 rpm is preset again. Drive 2 is not influenced.

Protective door 2

With a closed protective door 2 (switch -S3), setpoint speed n = 333 rpm is specified for drive 2. When opening the protective door 2, drive 2 is set to n = 33 rpm via data block switchover. With open switch -S3, the safety function SLS in drive 2 is activated. When closing the protective door 2, the speed n = 333 rpm is preset. Drive 1 is not influenced.

Error simulation

When pressing the button -S9, the drives are set to a higher setpoint independently of the protective door setting. With drive 1, this is n = 1000 rpm and with drive 2, n = 666 rpm. With open protective door, the SLS limit value is violated and the affected drive is stopped with internal SS2 (STOP C), and switched to SOS upon expiry of the delay time “STOP C SOS“ (in the example 400 ms). For further traversal, press the reset button -S4 to acknowledge the reaction triggered by the internal SS2 (STOP C).

Page 52: SINAMICS S120 Application Description October 2010 · Activating the Safety Integrated Extended Functions of the CU320-2 via PROFIsafe with PROFINET SINAMICS S120 . Application Description

8 References

52 Safety Integrated

V1.1, Article ID: 42939347

Co

pyr

igh

t S

iem

en

s A

G C

op

yrig

ht-

Jah

r A

ll rig

hts

re

serv

ed

8 References

8.1 References

This list does not deem to be complete and only provides a selection of suitable references.

Table 8-1: References

Topic Title

/1/ SINAMICS S120 Function Manual 11/2009 Edition

/2/ SINAMICS S120 Equipment Manual 11/2009 Edition

/3/ SINAMICS S120 List Manual 11/2009 Edition

8.2 Internet link data

This list does not deem to be complete and only provides a selection of suitable references.

Table 8-2

Topic Title

\1\ Reference to the article

http://support.automation.siemens.com/WW/view/en/42939347

\2\ Siemens I IA/DT Customer Support

http://support.automation.siemens.com

Page 53: SINAMICS S120 Application Description October 2010 · Activating the Safety Integrated Extended Functions of the CU320-2 via PROFIsafe with PROFINET SINAMICS S120 . Application Description

9 History

Safety Integrated V1.1, Article ID: 42939347 53

Co

pyr

igh

t S

iem

en

s A

G C

op

yrig

ht-

Jah

r A

ll rig

hts

re

serv

ed

9 History

Table 9-1: History

Version Date Change

V1.0 July 1, 2010 First edition

V1.1 Oktober 12, 2010 Formatting