Alarm, Faults and System Messages SIMOCODE pro 15-2 GWA 4NEB 631 6050-22 DS 01 Event (alphabetical) Description Error processing Acknow- ledgement Contactor control Analog module open circuit A wire break has occurred in the analog value measuring circuit. Check the measuring transducer and the measuring circuit. Reset Switched off Another start permitted The start after the next one should not be carried out until the interlocking time has expired. Blocked positio- ner The torque switch has been acti- vated without or before the corre- sponding limit switch. The positioner is possi- bly blocked. Acknowledge the fault with "free-wheeling" with the counter com- mand "Open/Close". Check the slide appli- cation and the limit switches. Counter com- mand "Open/Close". Switched off Blocking The maximum motor current has exceeded the threshold for the blocking protection. Possible cause: The motor is blok- ked. Please check the applica- tion which is driven by the motor. Reset Switched off Changing of the parameters is not permissible in the current mode Changing of a least one parame- ter is not possible in the current operating state. A lot of parameters can only be changed when the motor feeder is swit- ched off and is not in the "Remote" operating mode. For an overview of the parameters that can always be changed: See chapter "Data For- mats and Data Records" on page B-1. Configuration fault The configured device configura- tion does not match the current configuration. Please check if all con- figured components are present. Check the actual confi- guration using "Confi- guration". Rectify the fault; Reset Switched off Double 0 Both torque switches have been activated simultaneously. The motor feeder was turned off. Open circuit torque switch. Torque switch is defec- tive. Switched off Double 1 Both limit switches have been activated simultaneously. Limit switch is defective. Switched off Execution ON command The motor feeder could not be turned on after an ON command. Main circuit is interrup- ted (fuse, circuit brea- ker). Motor contactor or contactor control is defective. Parameter execution time is too short. Reset Switched off

SIMOCODE ALARME.pdf

  • Upload
    ma-vio

  • View
    78

  • Download
    2

Embed Size (px)

Citation preview

Page 1: SIMOCODE ALARME.pdf

Alarm, Faults and System Messages

Event

(alphabetical)

Description

Error processing

Acknow-

ledgement

Contactor

control

Analog module open circuit

A wire break has occurred in the analog value measuring circuit.

Check the measuring transducer and the measuring circuit.

Reset Switched off

Another start permitted

The start after the next one should not be carried out until the interlocking time has expired.

Blocked positio-ner

The torque switch has been acti-vated without or before the corre-sponding limit switch.

• The positioner is possi-bly blocked.

• Acknowledge the fault with "free-wheeling" with the counter com-mand "Open/Close".

• Check the slide appli-cation and the limit switches.

Counter com-mand "Open/Close".

Switched off

Blocking The maximum motor current has exceeded the threshold for the blocking protection. Possible cause: The motor is blok-ked.

Please check the applica-tion which is driven by the motor.

Reset Switched off

Changing of the parameters is not permissible in the current mode

Changing of a least one parame-ter is not possible in the current operating state.

A lot of parameters can only be changed when the motor feeder is swit-ched off and is not in the "Remote" operating mode. For an overview of the parameters that can always be changed: See chapter "Data For-mats and Data Records" on page B-1.

Configuration fault

The configured device configura-tion does not match the current configuration.

• Please check if all con-figured components are present.

• Check the actual confi-guration using "Confi-guration".

Rectify the fault; Reset

Switched off

Double 0 Both torque switches have been activated simultaneously. The motor feeder was turned off.

• Open circuit torque switch.

• Torque switch is defec-tive.

Switched off

Double 1 Both limit switches have been activated simultaneously.

Limit switch is defective. Switched off

Execution ON command

The motor feeder could not be turned on after an ON command.

• Main circuit is interrup-ted (fuse, circuit brea-ker).

• Motor contactor or contactor control is defective.

• Parameter execution time is too short.

Reset Switched off

SIMOCODE pro 15-2 GWA 4NEB 631 6050-22 DS 01

Page 2: SIMOCODE ALARME.pdf

Alarm, Faults and System Messages

Execution stop command

The motor feeder could not be turned off after a Stop command.

• The contactor contact is welded.

• Parameter execution time is too short.

• The "Open" end posi-tion has not been rea-ched during the parameterized runtime (only in the case of the "Positioner" and "Valve" control functions).

Reset; Counter command

Switched off

External earth fault

The external earth-fault monito-ring has been activated. A fault current of too high a value is flo-wing.

Please check the motor connection cable for damage.

Reset Switched off

External fault 1, 2, 3, 4, 5 or 6

A signal is pending at the input (socket) of the standard function "External fault 1, 2, 3, 4, 5 or 6".

Check the motor feeder. Depends on the parameteriza-tion

Switched off

Fault - Antiva-lence

The limit switches are not registe-ring any antivalent signals.

• Open circuit of the limit switch.

• Please check the slide application and the limit switches.

Counter com-mand "OPEN/CLOSE".

Switched off

Fault - Bus The PROFIBUS DP communica-tion has been or is being interrup-ted

Check the PROFIBUS connection (plugs, cables, etc.)

Reset, Auto-reset

Switched off

Fault - End posi-tion

Positioner/solenoid valve has left the final position without a com-mand being issued. The motor feeder was turned off.

Acknowledge the fault with "free-wheeling" by the counter command "OPEN/CLOSE".

Reset; Counter command

Switched off

Fault - PLC/DCS The PLC which controls the fee-der was or is in the STOP state.

Please check the opera-ting status of the PLC.

Reset, Auto-reset

Switched off

Fault - Temporary components (e.g. memory module)

One of the following compon-ents is defective:• Addressing plug• Memory module• PC cable.

Please replace the defec-tive components. For this, see chapter 13 "Mounting, Wiring, Interfaces".

Rectify the fault; Reset

Switched off

Feedback (F) OFF The current flow in the motor fee-der was interrupted without the motor feeder being turned off.

• Main circuit is interrup-ted (fuse, circuit brea-ker, main switch).

• Motor contactor or contactor control is defective

Reset Switched off

Event

(alphabetical)

(cont.)

Description

(cont.)

Error processing

(cont.)

Acknow-

ledgement

(cont.)

Contactor

control

(cont.)

SIMOCODE proGWA 4NEB 631 6050-22 DS 01 15-3

Page 3: SIMOCODE ALARME.pdf

Alarm, Faults and System Messages

Feedback (F) ON The motor feeder could not be turned on after an ON command.

• Main circuit is interrup-ted (fuse, circuit brea-ker)

• Motor contactor or contactor control is defective, "Execution time" parameter is too short

• Only in the case of the "Positioner/Solenoid valve" control function: The end position "CLOSE" has not been reached during the parameterized runtime.

Reset; Counter command

Switched off

Hardware faults The hardware of the SIMOCODE pro basic device is defective.

Please replace the basic unit. See chapter 13 "Moun-ting, Wiring, Interfaces".

Rectify the fault Switched off

Internal earth fault

The internal earth-fault monitoring has been activated. A fault cur-rent of too high a value is flowing.

Please check the motor connection cable for damage.

Reset Switched off

Module fault At least one SIMOCODE pro module is not ready for use.

• Connecting cable is defective or has not been plugged in cor-rectly.

• Module is defective. Please replace the module. For this, see chapter 13 "Mounting, Wiring, Interfaces".

Rectify the fault; Reset

Switched off

Motor operating hours >

The configured limit value for the motor operating hours has been exceeded.

Please implement the maintenance measures planned for the feeder.

No start permis-sible

The permitted number of starts in the monitoring timeframe was achieved. The next start should not be carried out until the inter-locking time has expired.

Reset Switched off

Operational pro-tection off (OPO)

The "Operational Protection Off (OPO)" signal is pending. A switched-on motor feeder was switched off. Switching on is not possible as long as the OPO signal is pen-ding.

Reset Switched off; for positioners: QE1 or QE2 switched on until end posi-tion - indepen-dent of the configuration

Event

(alphabetical)

(cont.)

Description

(cont.)

Error processing

(cont.)

Acknow-

ledgement

(cont.)

Contactor

control

(cont.)

SIMOCODE pro 15-4 GWA 4NEB 631 6050-22 DS 01

Page 4: SIMOCODE ALARME.pdf

Alarm, Faults and System Messages

Overload The motor feeder was over-loaded.

Please check the motor and the application which is driven by the motor. The motor can only be switched on again after the cooling down time has expired or after an emergency start is car-ried out.

Reset, Auto-reset

Switched off

Overload and Unbalance

The motor feeder was overloaded asymmetrically. Possible causes:• Failure of a phase• Fault in the motor windings.

Check the motor feeder and the motor. The motor can only be switched on again after the cooling down time has expired or after an emergency start is car-ried out.

Reset or Auto reset

Switched off

Parameter blok-king during start-up active

The start-up parameter block pre-vents SIMOCODE pro parame-ters which could be saved in the DP Master from being accepted. The block must be set when• SIMOCODE ES

or• SIMATIC PDMis used for parameterizing. The block may not be set when• SIMOCODE pro C/V is integra-

ted in STEP 7 via the SIMOCODE pro object manager (OM) or

• SIMOCODE pro C was parame-terized via GSD.

Parameter is faulty ("Gen. fault" category)

There in an error in the parameter data.

The designation of the faulty parameter can be found on the basis of the number (byte No.) in the system manual chapter A "Tables".

Rectify the fault; Reset

Switched off

Parameter is faulty ("Gen. fault" category)

There is a fault in the parameter data transmitted to the device. Faults can occur in the parameter data, for example, if the device parameterization was not carried out with SIMOCODE ES or SIMATIC PDM.

Check the parameter data (data records 130 133) transmitted to the device to make sure that the contents are correct.

Event

(alphabetical)

(cont.)

Description

(cont.)

Error processing

(cont.)

Acknow-

ledgement

(cont.)

Contactor

control

(cont.)

Attention The parameter block is not active in the case of devices which are still set to the factory default set-tings or which have been reset to the factory default settings!

SIMOCODE proGWA 4NEB 631 6050-22 DS 01 15-5

Page 5: SIMOCODE ALARME.pdf

Alarm, Faults and System Messages

Permissible num-ber of starts exceeded

The permitted number of starts in the monitoring timeframe has already been exceeded. The next start should not be carried out until the interlocking time has expired.

Reset Switched off

Phase unbalance The limit value for the phase unbalance was exceeded. The phase unbalance can lead to an overload. Possible causes:• Failure of a phase• Fault in the motor

windings.

Check the motor feeder and the motor.

Reset Switched off

Power failure monitoring (UVO)

The network failure lasted longer than the configured network failure time.

Reset Switched off

Pre-warning overload (I > 115%)

The motor feeder is in overload operation. It will be tripped within a short period of time due to overloading if this condition continues to per-sist.

Please check the motor and the application which is driven by the motor.

Required function is not supported

At least one parameterized function is not supported by the product version of the basic unit.

Only activate functions that are supported by the product version of the basic unit. For example, SIMOCODE pro V basic units with the product version E01 do not sup-port the voltage measu-ring module, the temperature module and the analog module.

Status - Cooling down time active

The motor feeder was switched off due to overload.

The motor can only be switched on again after the cooling down time has expired.

Status - Emer-gency start exe-cuted

The thermal memory was deleted with the function "Emergency start".

The motor can immedia-tely be switched on again after an overload release.

Status - Test position Feed-back (TPF)

The motor feeder is in the test position. The main current circuit is inter-rupted and the "cold starting" of the feeder can be carried out.

Stop time > The configured limit value for the stop time has been exceeded.

Please implement the maintenance measures planned for the feeder. If possible, switch on the feeder.

Event

(alphabetical)

(cont.)

Description

(cont.)

Error processing

(cont.)

Acknow-

ledgement

(cont.)

Contactor

control

(cont.)

SIMOCODE pro 15-6 GWA 4NEB 631 6050-22 DS 01

Page 6: SIMOCODE ALARME.pdf

Alarm, Faults and System Messages

Temperature module - Warning level overshot

The temperature warning level was exceeded.

Check the temperature measuring station.

Temperature module Out of Range

The temperature sensor is yiel-ding values which are not permit-ted.

Check the temperature sensor.

Reset Switched off

Temperature module sensor fault

Either a short circuit or a wire break has occurred in the tempe-rature sensor circuit.

Check the temperature sensor nd the sensor cable.

Rectify the fault; Reset

Switched off

Test position feedback (TPF)

Current flows in the motor feeder even though the motor feeder is in the test position (TPF).

The main circuit is not interrupted in test opera-tion.

Reset Switched off

Test shutdown The motor feeder was checked and switched off by a test switch-off.

Reset Switched off

Thermistor open circuit

A wire break has occurred in the thermistor sensor cable.

Check the thermistor sensor cable and the thermistor.

Rectify the fault; Reset

Switched off

Thermistor short circuit

A short circuit has occurred in the thermistor sensor cable.

Check the thermistor sensor cable and the thermistor.

Rectify the fault; Reset

Switched off

Thermistor trip level

The thermistor protection has been activated. The temperature of the motor is too high.

Please check the motor and the application which is driven by the motor. The motor cannot be switched on again until the temperature has rea-ched the switch-back point of the thermistor.

Reset, Auto-reset

Switched off

Warning level cos phi <

The power factor has undershot the warning level. Possible cause: The motor is ope-rated without a load.

Please check the applica-tion which is driven by the motor.

Warning level I< undershot

The maximum current has undershot the warning level.

Please check the applica-tion which is driven by the motor.

Warning level I> overshot

The maximum current has overs-hot the warning level.

Please check the applica-tion which is driven by the motor.

Warning level P< undershot

The real power of the motor has undershot the warning level.

Please check the applica-tion which is driven by the motor.

Warning level P> overshot

The real power of the motor has overshot the warning level.

Please check the applica-tion which is driven by the motor.

Warning level U< undershot

The voltage in the motor feeder has undershot the warning level. Possible causes:• Undervoltage in the network• Fuse has tripped.

Check the motor feeder.

Event

(alphabetical)

(cont.)

Description

(cont.)

Error processing

(cont.)

Acknow-

ledgement

(cont.)

Contactor

control

(cont.)

SIMOCODE proGWA 4NEB 631 6050-22 DS 01 15-7

Page 7: SIMOCODE ALARME.pdf

Alarm, Faults and System Messages

Table 15-1: Alarm, Faults and System Messages

Warning level 0/4 - 20 mA< undershot

The measured value on the ana-log input has undershot the warning level.

Check the measuring station.

Warning level 0/4 - 20 mA> overshot

The measured value on the ana-log input has overshot the warning level.

Check the measuring station.

Wrong password The SIMOCODE pro parameters are protected by a password. An attempt was made to change the parameters without entering the password.

Please use the correct password for changing the parameters. If you do not know the password, new parame-ters cannot be set until the factory default set-tings have been reset. Please refer to chapter 14.3.4 "Resetting the Basic Factory Default Settings" for a descrip-tion of the factory default settings.

Event

(alphabetical)

(cont.)

Description

(cont.)

Error processing

(cont.)

Acknow-

ledgement

(cont.)

Contactor

control

(cont.)

SIMOCODE pro 15-8 GWA 4NEB 631 6050-22 DS 01