SILICON RUBBER - INSULATED EXTERIOR CURRENTTRANSFORMER FOR PROTECTION TYPE
CTP – 0,72; 100 ÷ 600 / 1 (5) ADATASHEET
CTP 200 / 1 (5) A … 600 / 1 (5) A
TypeCTP
CTP 100 / 1 (5) A … 150 / 1 (5) A
1. ApplicationThe dry, siliconic rubber moulded, toroid transformers are made for fitting on 3-phase, remote controlled, exteriortype, SF-6 insulated surge arresters, together with protection devices. The transformers comply with SR EN 60044-1:2002 / A2:2003
2. SymbolizationTransformer symbolization is made using letters and numbers representing the transformer type:
CTP – 0,72: Current Transformer for Protection, maximum voltage of 0,72 kV, followed by the transformation ratio, precision power and precision class.
3. Environmental requirementsThe transformer type CTP – 0,72 is designed to work under normal conditions, according to SR HD 478.2.1 S1:2002:a) maximum temperature of the working environment:b) average daily temperature of the working environment:c) minimum temperature of the working environment:d) maximum altitude:e) pollution level:f) maximum ice thickness:g) maximum wind pressure:h) external or earthquake-induced vibrations: i) protection level:j) maximum relative humidity at 20 ºC:k) atmospheric pressure:l) solar radiation:
+ 40 ºCmaximum +35 ºC- 45 ºC1000 m above sea levelgrade IV20 mm700 Pa (corresponding wind speed = 34 m/s)negligibleIP 54100%760 ± 30 mmHg1000 w/m²
4. Main technical properties- maximum working voltage:- nominal frequency:- nominal current în secondary winding:- nominal transformation ratio In1/In2:- precision power in VA:- precision class:- precision limit factor:- working regime:- state of grid neutral:- insulation class:- short-term thermal current of 1 sec (Ith):- dynamic current:- terminals for the secondary winding:- weight:
0,72 kV50 Hz1 A (5)100 / 1 (5) ... 600 / 1 (5)1,5 ÷ 55P; 10PALF5continuous (RC)- according to SREN 60044-1 item 2.1.18.A10 ÷ 30 kA75 kA max (2,5 x Ith)type MyF conductors, coloured S1 – red and S2 - blue1,85 ÷ 3,3 kg
Annex 1Current transformer for protection type CTP – 0,72; 200 / 1 (5) A ...
600 / 1 (5) A; 5VA; cl.: 5P5
Fig. A1 Size and mounting details
Annex 2Current transformer for protection type CTP – 0,72; 100 / 1 (5) A ...
150 / 1 (5) A; 5VA; cl.: 5P5
Fig. A2 Size and mounting details