HVAC SYSTEM SHOPPERS STOP & HYPERCITY
Objective
To reduce Capital Expenditure
To reduce Operating expenditure
To reduce fixed Charges
To optimize roof space to make it available as leasable area
l
1
8/3/2019 Shoppers Stop HVAC
2/7
2
HVAC SYSTEM
Earlier System Dedicated Air cooled screwchilled water system
Revised system Common Water cooled screwchilled water system along with Thermal storage
Tank system
8/3/2019 Shoppers Stop HVAC
3/7
HVAC SYSTEM SHOPPERS STOP & HYPERCITY
Advantage
Air cooled chilled water system operates at 1.35 IKW /TR
Water cooled chilled water system operates at 0.80 IKW /TR
Saving in power consumption(Approx.) - 40%
Advantage of Thermal storage system.
Dual tariff is available in Aurangabad as follows.
10.00 PM - 6.00 AM - (-)85 Paise / Unit
06.00 PM - 10.00 PM - (+)1.10 Rs. / Unit
Chillers are charged during less tariff period in night.
Total difference in power consumption when thermal storage is used is
Rs.1.95 / Unit.
Total capacity of Hyper city & Shoppers stop 1010TR Annual Saving in Rs. due to reduction in Power consumption to Shoppers stop &
Hyper city as per actual consumption pattern -12,376,739
(Rs. Twelve Million three hundred seventy six thousand seven hundred thirty
nine only)
3
8/3/2019 Shoppers Stop HVAC
4/7
4
HVAC SYSTEMCOMPARITIVE SHEET OF POWER CONSUMPTION & AMC BETWEEN WATER
COOLED & AIR COOLED SYSTEM
SR. NODESCRIPTIO
N
HVAC CAPACITY
IN - TR
ELECTRICAL POWER
CONSUMPTION IN KW/HR.
AMC CHARGES IN - RS
WATER COOLED
AIR
COOLED
WATER
COOLED
AIR
COOLED
1
SHOPPERS
STOP 340 272 459.00 442000 326400
2 HYPER CITY 670 536 904.50 871000 643200
TOTAL
1010 808 1363.50
1313000 969600
8/3/2019 Shoppers Stop HVAC
5/7
HVAC SYSTEM
5
8/3/2019 Shoppers Stop HVAC
6/7
HVAC SYSTEMSaving in Rs. Due to induction of water cooled system instead of Air-cooled system
Saving in Rs. Due to induction of water cooled system instead of Air-cooled system
Sr.No. Description
Water cooled Chilled
water System
Air cooled Chilled
water system
Annual Saving in
Rs.
1 Annual Per day Load-TRH 75,880
2 Avg.Per day Load - TRH 6,323
3 Yearly load -TRH 2,308,017
4 Power consumption -KWH 1,846,413 3,115,823
5
Annual Power saving due to
water cooled-KWH 1,269,409
6 Annual Saving in Rs.
7
15% of power generated by
DG sets 190,411 2,665,759
8
85% of Power generated by
MSEDC 1,078,998 9,710,980
9 Annual Saving in Rs. 12,376,739
8/3/2019 Shoppers Stop HVAC
7/7
HVAC SYSTEM SHOPPERS STOP & HYPERCITY
Concl
u
sion Maximum demand reduced to 694KVA i.e. saving of Maximum demand of
Rs.104,100.
Roof Space was utilized for Choki Dhani
Capital expenditure reduced by 10% on MEP i.e. reduction of
Approximately Rs.100,00,000.
Capacity of Chillers, transformer, DG set reduced.
Operating Expenses reduced by Rs.12,376,739.