    HVAC SYSTEM SHOPPERS STOP & HYPERCITY

    Objective

    To reduce Capital Expenditure

    To reduce Operating expenditure

    To reduce fixed Charges

    To optimize roof space to make it available as leasable area

    l

    1

  • 8/3/2019 Shoppers Stop HVAC

    2/7

    2

    HVAC SYSTEM

    Earlier System Dedicated Air cooled screwchilled water system

    Revised system Common Water cooled screwchilled water system along with Thermal storage

    Tank system

  • 8/3/2019 Shoppers Stop HVAC

    3/7

    HVAC SYSTEM SHOPPERS STOP & HYPERCITY

    Advantage

    Air cooled chilled water system operates at 1.35 IKW /TR

    Water cooled chilled water system operates at 0.80 IKW /TR

    Saving in power consumption(Approx.) - 40%

    Advantage of Thermal storage system.

    Dual tariff is available in Aurangabad as follows.

    10.00 PM - 6.00 AM - (-)85 Paise / Unit

    06.00 PM - 10.00 PM - (+)1.10 Rs. / Unit

    Chillers are charged during less tariff period in night.

    Total difference in power consumption when thermal storage is used is

    Rs.1.95 / Unit.

    Total capacity of Hyper city & Shoppers stop 1010TR Annual Saving in Rs. due to reduction in Power consumption to Shoppers stop &

    Hyper city as per actual consumption pattern -12,376,739

    (Rs. Twelve Million three hundred seventy six thousand seven hundred thirty

    nine only)

    3

  • 8/3/2019 Shoppers Stop HVAC

    4/7

    4

    HVAC SYSTEMCOMPARITIVE SHEET OF POWER CONSUMPTION & AMC BETWEEN WATER

    COOLED & AIR COOLED SYSTEM

    SR. NODESCRIPTIO

    N

    HVAC CAPACITY

    IN - TR

    ELECTRICAL POWER

    CONSUMPTION IN KW/HR.

    AMC CHARGES IN - RS

    WATER COOLED

    AIR

    COOLED

    WATER

    COOLED

    AIR

    COOLED

    1

    SHOPPERS

    STOP 340 272 459.00 442000 326400

    2 HYPER CITY 670 536 904.50 871000 643200

    TOTAL

    1010 808 1363.50

    1313000 969600

  • 8/3/2019 Shoppers Stop HVAC

    5/7

    HVAC SYSTEM

    5

  • 8/3/2019 Shoppers Stop HVAC

    6/7

    HVAC SYSTEMSaving in Rs. Due to induction of water cooled system instead of Air-cooled system

    Saving in Rs. Due to induction of water cooled system instead of Air-cooled system

    Sr.No. Description

    Water cooled Chilled

    water System

    Air cooled Chilled

    water system

    Annual Saving in

    Rs.

    1 Annual Per day Load-TRH 75,880

    2 Avg.Per day Load - TRH 6,323

    3 Yearly load -TRH 2,308,017

    4 Power consumption -KWH 1,846,413 3,115,823

    5

    Annual Power saving due to

    water cooled-KWH 1,269,409

    6 Annual Saving in Rs.

    7

    15% of power generated by

    DG sets 190,411 2,665,759

    8

    85% of Power generated by

    MSEDC 1,078,998 9,710,980

    9 Annual Saving in Rs. 12,376,739

  • 8/3/2019 Shoppers Stop HVAC

    7/7

    HVAC SYSTEM SHOPPERS STOP & HYPERCITY

    Concl

    u

    sion Maximum demand reduced to 694KVA i.e. saving of Maximum demand of

    Rs.104,100.

    Roof Space was utilized for Choki Dhani

    Capital expenditure reduced by 10% on MEP i.e. reduction of

    Approximately Rs.100,00,000.

    Capacity of Chillers, transformer, DG set reduced.

    Operating Expenses reduced by Rs.12,376,739.

    l

    7