Upload
vukiet
View
220
Download
4
Embed Size (px)
Citation preview
1© Copyright 2012 Zoeller Co. All rights reserved.
X611 X621 X631 X641 X651 X661 1.0 HP 1.5 HP 2.0 HP 3.0 HP 5.0 HP 7.5 HP
(For Pump Prefix Identification see News & Views 0052)
“SEWAGE-WASTE”
COMPARE THESE FEATURES• FM and cCSAus rated Class I, Division 1, Group C & D
• Dual vane semi-open ductile iron impeller• Class 30 epoxy-coated cast iron construction • All units are double seal for extra motor protection• Corrosionresistantpowdercoatedepoxyfinish• Finnedmotorhousingforsuperiorheatdissipation• Stainlesssteelscrews,washers,tagsandsealassembly• 25footULListedpowerandsensorcord.Cordlengthalso available in 50 foot• Singlephase-230Vcapacitorstart,capacitorrun• ThreePhase-200-230-460-575Volt• Explosionproofmotor-60Hz,1750RPM,hermeticallysealedandoil-filledforaddedheatdissipation
• Thermalsensor• Continuousdutyoperationinsubmergedconditions• Maximumtemperatureforsewageordewatering 104°F(40°C)with1.2service factor (1.0service factoronModel661)
• 416stainlesssteelmotorshaft• Tandemshaft seals - stainlesssteel fitted, carbon/ceramic
seal faces• Seal leak probes• Oversizedupper&lowerballbearingsrunninginanoilbath• Buna-Nsquareringseals• Allmodelspass2½"sphericalsolids• Specify3"NPTvertical,3"horizontalflangedor4" horizontalflangeddischarge• 100%computerizedtested• Majorwidth179/16".Height33¼"• Non-sparkingrailsystemsavailableforallmodels• Intrinsically safe control panels available
SECTION: 2.40.060FM2203
0312Supersedes
0810
SUBMERSIBLE SEWAGE OR DEWATERING NON-CLOG PUMP
3" Vertical Discharge
3" & 4" Horizontal Discharge
MODELS AVAILABLE•Nonautomatic(forintrinsicallysafevariablelevelcontrolsystems)• Double seal only•3"Vertical,3"Horizontalor4"Horizontalflangeddischarge•230V/1Phaseor200/230/460/575V/3Phase
Manufacturers of . . .
Productinformationpresentedherereflectsconditionsattimeof publication. Consult fac-toryregardingdiscrepanciesorinconsistencies. MAIL TO: P.O. BOX 16347 • Louisville, KY 40256-0347
SHIP TO: 3649 Cane Run Road • Louisville, KY 40211-1961(502) 778-2731 • 1 (800) 928-PUMP • FAX (502) 774-3624
visit our web site:www.zoeller.com
X600 SERIESHAZARDOUS ENVIRONMENT SERIES
CLASS I, DIVISION 1, GROUP C & D, 1 - 7½ HP / 1750 RPM
Certified to CSA StandardC22.2 No. 145
Standard 3600 & 3615Standard 3600 & 3615
Notforuseinacidicatmospheres
PatentNo.6,364,620appliestoX600series.
2© Copyright 2012 Zoeller Co. All rights reserved.
Standard all models - 25 ft. cord - 1.0 HP
Standard all models - 25 ft. cord - 1.5 HP
X611 Models Volts Phase Mode Amps *EX611 230 1 Nonauto 6.9 JX611 200 3 Nonauto 4.3 FX611 230 3 Nonauto 3.7 GX611 460 3 Nonauto 1.9 BAX611 575 3 Nonauto 1.6
Standard all models - 25 ft. cord - 2.0 HP
Standard all models - 25 ft. cord - 3.0 HP
X641 Models Volts Phase Mode Amps *EX641 230 1 Nonauto 17.0 JX641 200 3 Nonauto 11.0 FX641 230 3 Nonauto 9.6 GX641 460 3 Nonauto 4.8 BAX641 575 3 Nonauto 3.9
Standard all models - 25 ft. cord - 5.0 HP
X651 Models Volts Phase Mode Amps *EX651 230 1 Nonauto 28.0 JX651 200 3 Nonauto 17.5 FX651 230 3 Nonauto 15.2 GX651 460 3 Nonauto 7.6 BAX651 575 3 Nonauto 6.1
Standard all models - 25 ft. cord - 7.5 HP
X661 Models Volts Phase Mode Amps JX661 200 3 Nonauto 25.3 FX661 230 3 Nonauto 22.0 GX661 460 3 Nonauto 11.0 BAX661 575 3 Nonauto 9.0
For informationonadditionalZoellerproducts refer tocatalogonVariableControlSwitches,FM0526;ControlPanels,FM1705;Sump/SewageBasins,FM0487;RailSystems,FM0787.
All installation of controls, protection devices and wiring should be done by a qualified licensed electrician. All electrical and safety codes should be followed including the most recent National Electrical Code (NEC) and the Occupational Safety and Health Act (OSHA).
RESERVE POWERED DESIGNForunusualconditionsareservesafetyfactorisengineeredintothedesignofeveryZoellerpump.
*Allsinglephaseunitsrequireexternalstartingcapacityandrelaycircuits.
PUMP PERFORMANCE CURVEMODELS X611/X621/X631/X641/X651/X661
X611 X621 X631 X641 X651
X661
X641 1 PH
X651 1 PH
013859X
X611 X621 X631 X641 (1 PH)
X641 X651 (1 PH) X651 X661
MODEL
MODEL
X621 Models Volts Phase Mode Amps *EX621 230 1 Nonauto 8.9 JX621 200 3 Nonauto 5.9 FX621 230 3 Nonauto 5.1 GX621 460 3 Nonauto 2.6 BAX621 575 3 Nonauto 2.0
X631 Models Volts Phase Mode Amps *EX631 230 1 Nonauto 14.5 JX631 200 3 Nonauto 7.8 FX631 230 3 Nonauto 6.8 GX631 460 3 Nonauto 3.4 BAX631 575 3 Nonauto 2.7
3© Copyright 2012 Zoeller Co. All rights reserved.
SIMPLEX INSTALLATION
11
17 5/1617 5/8
6 5/16
ALL DIMENSIONS IN INCHES UNLESS OTHERWISE NOTED
48 INCH MINIMUM30 INCH MINIMUM
LARGER BASIN.VOLUME MAY REQUIREFOR SIZE ONLY.
DUPLEXSIMPLEX
BASIN DIAMETER
A
NI
T
O
RT O
11 3/4 5 1/4
2 5/8 FOR 2 1/2" SOLID HANDLING
33 1/4
STD. 4 INCH-90° ELBOW
4 INCH CHECK VALVE
P/N 6030-0194
DIAMETER
.96>20
FLA<20 .68ø .48
P/N 6030-0203
ZEPA0549A
ON
I
TA
T
RO
8 5/165 1/4 2 5/8
3"-8 NPT
9 1/8
17 9/16
6 5/16
33 1/4
SIMPLEX INSTALLATION
3 INCH CHECK VALVEP/N 30-0160
ALL DIMENSIONS ARE IN INCHES UNLESS OTHERWISE NOTED
.68<20FLA DIAMETER
>20 .96
ø.48
BASIN DIAMETERSIMPLEX 24 INCH MINIMUM
30 INCH MINIMUMDUPLEXFOR SIZE ONLYVOLUME MAY REQUIRELARGER BASIN
WEEP HOLE
ZEPA0548A
3” Vertical DischargeWeight 295 lbs.
4” Horizontal DischargeWeight 295 lbs.
3 INCH NIPPLE
FLANGED ELBOWSTANDARD 3 INCH 90°
(BY OTHERS)
10 3/4
HOLEWEEP
33 1/4
5 1/4
2 5/8
15 15/16
P/N 30-01603 INCH UNICHECK
15 1/8
SIMPLEX INSTALLATION
9 5/8
6 5/16
(BY OTHERS)3 INCH-8 NPT FLANGE
ALL DIMENSIONS IN INCHES UNLESS OTHERWISE NOTED
36 INCH MINIMUM30 INCH MINIMUM
LARGER BASIN.VOLUME MAY REQUIRE
FOR SIZE ONLY.
DUPLEXSIMPLEX
BASIN DIAMETER
DIAMETER
.96>20
FLA<20 .68
IO
OTA
T
R
N
ø.48
(BY OTHERS)
ZEPA0547A
3” Flanged DischargeWeight 295 lbs.
4© Copyright 2012 Zoeller Co. All rights reserved.
34 1/2
ø.48
12 5/817 1/8
1230 3/8
3/4
13 5/64
4 INCH-125 LBANSI FLANGE
7
2" GUIDE RAIL25
1
ø.1/2 - 2 HOLES
(BY OTHERS)
1 5/64 6 1/2
LIFTING CABLES.S. OR GALV. STL.
(OPTIONAL)
CABLE CONNECTORS.S. OR GALV. STL.
(OPTIONAL)
LIFT
ING
HEIG
HT =
44
1/8
(WIT
HOUT
CAB
LE C
ONNE
CTOR
)
(WIT
H CA
BLE
CONN
ECTO
R)LI
FTIN
G HE
IGHT
= 4
6 3/
4
2638 3/8
MINIMUM FOR SIZE ONLY.VOLUME MAY REQUIRELARGER BASIN.
60 INCH DIAMETER
DIMENSIONS BASED ON STANDARD ANSI FITTING SIZES
DUPLEX INSTALLATIONSIMPLEX INSTALLATION
VOLUME MAY REQUIREMINIMUM FOR SIZE ONLY.
LARGER BASIN.
36 INCH DIAMETER
4 INCH CHECK VALVE
CHECK VALVES REQUIRED, NOT SHOWN FOR CLARITY
20
ALL DIMENSIONS IN INCHES UNLESS OTHERWISE NOTED
.96>20
DIAMETERFLA<20 .68
DOOR FRAME REF. PLANE
DOOR FRAME REF. PLANE
24 3/4
5 1/16
AO R
T
N
T
IO
AT
RO
OI
T
N
AOT
R
ON
T
I
P/N 6030-0203
3 3/8 FOR 2 1/2" SOLID HANDLING PUMPS
42” MINIMUMDIAMETER
REFERENCE VIEWOF LIFTING LUGS
NON-SPARKING RAIL SYSTEM DIMENSIONAL DATA
LIFT
ING
HEIG
HT =
44
(WIT
HOUT
CAB
LE C
ONNE
CTOR
)
(WIT
H CA
BLE
CONN
ECTO
R)LI
FTIN
G HE
IGHT
= 4
7
(BY OTHERS)3 INCH COUPLING
3 INCH MALE NPT
3/8
4 1/16
34 11/16
6 11/16
(BY OTHERS)3 INCH NIPPLE
PIPE (BY OTHERS)3/4 INCH S.S. OR GALV. STL.
P/N 6030-01603 INCH UNICHECK
WEEP HOLE
1 1/2TWO 3/8 HOLES 3 1/4
DIAMETER
>20<20FLA
.96
.68
S.S. OR GALV. STL.
CABLE CONNECTORS.S. OR GALV. STL.(OPTIONAL)
LIFTING CABLE
(OPTIONAL)
9 1/8
17 13/1615 7/16
SIMPLEX INSTALLATION25 3/4
42 INCH MINIMUM36 INCH MINIMUM
FOR SIZE ONLY.VOLUME MAY REQUIRELARGER BASIN.
BASIN
DUPLEXSIMPLEX
6 5/16
DIAMETER
DOOR FRAMEREF. PLANE
22 5/8
IN
O
O R
AT
T
Ø .48
ZEPA0550A
3” Vertical39-0076
ZEPA0552B
4” Horizontal39-0017
3” Horizontal39-0095
ZEPA0551B
ZEPA0570