CONTENTS 1. TECHNICAL CHANGES ····································2 2. PART NAMES AND FUNCTIONS······················3 3. SPECIFICATION·················································3 4. OUTLINES AND DIMENSIONS ·························4 5. WIRING DIAGRAM ············································6 6. REFRIGERANT SYSTEM DIAGRAM ················8 7. PERFORMANCE CURVES ······························10 8. TROUBLESHOOTING······································12 9. DISASSEMBLY INSTRUCTIONS ····················21 10. PARTS LIST······················································27 11. RoHS PARTS LIST···········································30 SPLIT-TYPE AIR CONDITIONERS TM MU-A18ND MU-A18ND- MU-A18ND- MU-A24ND- MU-A24ND- MU-A30ND- MU-A30ND- S2 S1 S2 S1 S2 S1 Indoor unit service manual MS-AND Series (OB404) No. OB405 REVISED EDITION-E SERVICE MANUAL Models OUTDOOR UNIT NOTE: • This service manual describes technical data of the outdoor units. • RoHS compliant products have <G> mark on the spec name plate. For servicing of RoHS compliant products, refer to the RoHS Parts List. Please void OB405 REVISED EDITION-D. Revision E: SPECIFICATION has been modified.

SERVICE MANUAL No. OB405 - Mitsubishi Ar … 18-24... · No. OB405 SERVICE MANUAL REVISED EDITION-E Models OUTDOOR UNIT ... RH277NHD RH247NRAT Electricity receiving unit: Indoor unit

Embed Size (px)

Citation preview

Page 1: SERVICE MANUAL No. OB405 - Mitsubishi Ar … 18-24... · No. OB405 SERVICE MANUAL REVISED EDITION-E Models OUTDOOR UNIT ... RH277NHD RH247NRAT Electricity receiving unit: Indoor unit

CONTENTS

1. TECHNICAL CHANGES ····································22. PART NAMES AND FUNCTIONS······················33. SPECIFICATION·················································34. OUTLINES AND DIMENSIONS ·························45. WIRING DIAGRAM ············································66. REFRIGERANT SYSTEM DIAGRAM················87. PERFORMANCE CURVES······························108. TROUBLESHOOTING······································129. DISASSEMBLY INSTRUCTIONS ····················21

10. PARTS LIST······················································2711. RoHS PARTS LIST···········································30

SPLIT-TYPE AIR CONDITIONERS

TM

MU-A18ND

MU-A18ND-MU-A18ND-MU-A24ND-MU-A24ND-MU-A30ND-MU-A30ND- S2

S1

S2

S1

S2

S1

Indoor unit service manualMS-A• ND Series (OB404)

No. OB405REVISED EDITION-ESERVICE MANUAL

Models

OUTDOOR UNIT

NOTE:• This service manual describes technical data of the outdoor units.• RoHS compliant products have <G> mark on the spec name plate.

For servicing of RoHS compliant products, refer to the RoHS Parts List.

Please void OB405 REVISED EDITION-D.

Revision E:• SPECIFICATION has been modified.

OB405E.qxp 09.10.14 9:16 AM Page 1

Page 2: SERVICE MANUAL No. OB405 - Mitsubishi Ar … 18-24... · No. OB405 SERVICE MANUAL REVISED EDITION-E Models OUTDOOR UNIT ... RH277NHD RH247NRAT Electricity receiving unit: Indoor unit

2

TECHNICAL CHANGES1

2

Compressor: NH30VCD � RH247NRATCompressor: RH277NHD � RH247NRATElectricity receiving unit: Indoor unit � Outdoor unitGas pipe diameter: [15.88 � [12.7Rated voltage: 220V � 220-230V

FrequencyNew ModelOld Model MU-18TN - S1

w : change

MU-A18ND - S1

60Hz

MU-18SN - C1

w

www

wwww

Outdoor unit:Unit size:W850mmoH605mmoD290mm � W840mmoH850mmoD330mm Outdoor unit:Unit size:W870mmoH850mmoD295mm � W840mmoH850mmoD330mmCompressor: NH38NBD � PH33NPBT Electricity receiving unit: Indoor unit � Outdoor unitLiquid refrigerant pipe diameter: [9.52 � [6.35Rated voltage: 220V � 220-230V

FrequencyNew ModelOld Model MU-24TN - S1

MU-A24ND - S1

60Hz

MU-24SN - C2

wwwww

w

wwww

MU-A30ND -New model

S1

MU-A18ND - ➔ MU-A18ND -• Valve cover has been added.

S2S1

MU-A24ND - ➔ MU-A24ND -• Compressor contactor has been added.

S2S1

MU-A30ND - ➔ MU-A30ND -• Solenoid valve and solenoid valve coil have been changed.

S2S1

Revision A:• Check of solenoid valve coil has been partially modified.

Revision B:• MU-A24ND - has been added.S2

Revision C:• MU-A18ND - has been added.S2

Revision D:• MU-A30ND - has been added.S2

Revision E:• SPECIFICATION has been modified.

OB405E.qxp 09.10.14 9:16 AM Page 2

Page 3: SERVICE MANUAL No. OB405 - Mitsubishi Ar … 18-24... · No. OB405 SERVICE MANUAL REVISED EDITION-E Models OUTDOOR UNIT ... RH277NHD RH247NRAT Electricity receiving unit: Indoor unit

3

PART NAMES AND FUNCTIONS2

SPECIFICATION3

Outdoor model

Function

Power supply

CapacityDehumidificationAir flow (High/Low)Power outletRunning current (Total)Power input (Total)Power factor (Total)Starting current (Total)Compressor motor currentFan motor current

ModelOutputWindingresistance (at 20:)ModelWindingresistance (at 20:)Dimensions WOHODWeightSound level (High/Low)Fan speed (High/Low) Fan speed regulatorRefrigerant filling capacity (R22)Refrigeration oil (Model)

kWR/hK /h

AAW%AAA

W

"

"

mmkgdBrpm

kg

cc

CoolingSingle phase

220-230V, 60Hz

2,880

58

0.66

PH33NPBT1,500

C-R 0.84C-S 2.09

RA6N75-BAWHT-BLK 65.0 BLK-RED 65.4

6754

7901

2.20

900 (MS32N1)

Ele

ctric

alda

taC

ompr

esso

rFa

n m

otor

Spe

cial

rem

arks

Coefficient of performance (C.O.P) (Total)

Cap

acity

2,48015

40

0.55

RH247NRAT1,200

C-R 1.43C-S 2.06

RA6V60-MAWHT-BLK 71.2 BLK-RED 89.3850o605o290

4454

9451

1.40

520 (MS56)

ISO 51515.102.3

8.521,80096-92

7.60

2.83

SSA 3855.92.7

20( )12.422,650

97

11.39

2.23

ISO 51516.63.2

15( )10.542,25097-93

9.50

2.93

SSA 3856.63.2

17.523,700

96

16.49

1.78

ISO 51518.14.3

14.253,01096-92

13.22

2.69

SSA 3854.401.8

9.942,100

96

9.02

2.10

MU-A24ND MU-A30ND

2,880/1,38025

78

0.66

NH44NAVT2,000

C-R 0.62C-S 1.40

RA6N75-AAWHT-BLK 64.2 BLK-YLW 32.9

YLW-RED 32.7

7655/51

790/4902

2.40

1,300 (MS32N1)

840o850o330

S2

S1

MU-A18ND

NOTE: Test conditions are based on ISO 5151 / SSA 385Cooling : Indoor DB27°C WB19°C / DB29°C WB19°C

Outdoor DB35°C WB24°C / DB46°C WB24°CIndoor-Outdoor piping length: 5 / 7.5 m

OUTDOOR UNIT

Air inlet

Air outlet

Drain outlet

Piping

Drain hose

Air inlet

Air outlet

(back and side)

MU-A18ND MU-A24ND MU-A30ND

OB405E.qxp 09.10.14 9:16 AM Page 3

Page 4: SERVICE MANUAL No. OB405 - Mitsubishi Ar … 18-24... · No. OB405 SERVICE MANUAL REVISED EDITION-E Models OUTDOOR UNIT ... RH277NHD RH247NRAT Electricity receiving unit: Indoor unit

4

OUTLINES AND DIMENSIONS4

Unit: mm

100mm or more

350mm or more

100m

m o

r m

ore

100mm or more

REQUIRED SPACE

500mm or more

100

157

161

Liquid refrigerantpipe joint

Refrigerant pipe (Flared) [6.35

Service panel

183

500850

30

50

20350

35

248

605

292

20

310

290

345

Air in

Air outDrainage3holes [33

50

90

Air in

Drainagehole [16.2

355

74

30-

35-

Gas refrigerant pipe jointRefrigerant pipe(flared) [12.7

MU-A18ND - S1

OUTDOOR UNIT

100

157

161

Liquid refrigerantpipe joint

Refrigerant pipe (Flared) [6.35

Service panel

183

500850

30

50

20350

35

248

605

292

20

310

290

345

Air in

Air outDrainage3holes [33

50

90

Air in

Drainagehole [16.2

355

8174

30-

35-

Gas refrigerant pipe jointRefrigerant pipe(flared) [12.7

100mm or more

350mm or more

100m

m o

r m

ore

100mm or more

REQUIRED SPACE

500mm or more

MU-A18ND - S2

OB405E.qxp 09.10.14 9:16 AM Page 4

Page 5: SERVICE MANUAL No. OB405 - Mitsubishi Ar … 18-24... · No. OB405 SERVICE MANUAL REVISED EDITION-E Models OUTDOOR UNIT ... RH277NHD RH247NRAT Electricity receiving unit: Indoor unit

5

30-

35-

155

90

198

40

515299

66

345133

0

360

850

430

500

80121

840

REQUIRED SPACEOpen as a rule500mm or more ifthe front and bothsides are open

100mm or more 200mm or more if there are obstaclesto both sides

Open as a rule500mm or more if the back,both sides and top are open

Service panel

Gas refrigerant pipe jointRefrigerant pipe(flared) [15.88

Liquid refrigerant pipe jointRefrigerant pipe(flared) [6.35(MU-A24ND)

[9.52(MU-A30ND)

350mm or more

100mm or more

MU-A24ND MU-A30ND

OUTDOOR UNIT

OB405E.qxp 09.10.14 9:16 AM Page 5

Page 6: SERVICE MANUAL No. OB405 - Mitsubishi Ar … 18-24... · No. OB405 SERVICE MANUAL REVISED EDITION-E Models OUTDOOR UNIT ... RH277NHD RH247NRAT Electricity receiving unit: Indoor unit

6

WIRING DIAGRAM5

MU-A18ND

RS

2

N

L

TB2

RED

ORN

BLU

BRN

WHT

GRN/YLW

C2

RED

MFBLACK4

WHITEORANGE

32

1

BLK

L

N

TB1 BR

NBLU

C1RED

C

MCB

LU220-230V~CO

NN

EC

TIN

GT

O IN

DO

OR

UN

IT

PO

WE

R S

UP

PLY

220-

230V

~/N

60H

z

FB

LU

DS

AR

220-230V~

WHT

1.About the indoor side electric wiring refer to the indoor unit electric wiring diagram for servicing.2.Use copper conductors only (For field wiring).3.Symbols below indicate.

: Connector: Terminal block,

NOTES:

SYMBOLC1C2

DSAR

SYMBOLF

MCMF

SYMBOLTB1TB2

NAME NAME NAMECOMPRESSOR CAPACITOROUTDOOR FAN CAPACITORSURGE ABSORBER

FUSE (3.15A)COMPRESSOR(INNER PROTECTOR)OUTDOOR FAN MOTOR(INNER PROTECTOR)

TERMINAL BLOCKTERMINAL BLOCK

MU-A24ND- S1

L

N

2

BRN

RED

BLKWHT

BLUTB2

BLUWHT

RE

D

C2

OR

N

DS

AR

TB1

GR

N/Y

LWB

RN

F

MF21

ORNRED

34

N

L

PE

BLU

MC

WHT

BLU SC

R

C1

BLK

SYMBOLC1C2

DSAR

SYMBOLF

MCMF

SYMBOLTB1TB2

NAME NAME NAMECOMPRESSOR CAPACITOROUTDOOR FAN CAPACITORSURGE ABSORBER

FUSE(3.15A)COMPRESSOR(INNER PROTECTOR)OUTDOOR FAN MOTOR(INNER PROTECTOR)

TERMINAL BLOCKTERMINAL BLOCK

NOTES: 1.Use copper conductors only (For field wiring).2.Since the indoor and outdoor unit connecting wires have polarity, connect them according to the numbers (2,N,L). 3.Symbols below indicate.

: Terminal block, : Connector

TO

IND

OO

R U

NIT

CO

NN

EC

TIN

G

220-230V~

220-230V~

PO

WE

R S

UP

PLY

~/N

220

-230

V 6

0Hz

OUTDOOR UNIT

OUTDOOR UNIT

OB405E.qxp 09.10.14 9:16 AM Page 6

Page 7: SERVICE MANUAL No. OB405 - Mitsubishi Ar … 18-24... · No. OB405 SERVICE MANUAL REVISED EDITION-E Models OUTDOOR UNIT ... RH277NHD RH247NRAT Electricity receiving unit: Indoor unit

7

MU-A30ND

SYMBOLC1C2

DSARF61LEVMCMF

SYMBOLNR61RT62RT63SR61SR62TB1TB2

SYMBOLT61X52X63

21S252C

NAME

DEICERP.C. BOARD

2

N

3

N

L

12V

WH

T

BLU

RED

BLU

WH

T

WHT

T61

YLW

BLK

WH

T

RED

BLU

TB25

CN730

YLW

BLK

WH

T

1

52C2

REDC2ORN

A1 A2BLU 52C

DS

AR

WHT

C1

BLK

S

C

RMC

BLU

NR

61

31

TB1

GR

N/Y

LW

BRN

SR62

SR61

F61

TAB52

COM NO

X52

CN711CN724CN662

6

MFRT62 RT63

1 2 3

2 1

OR

NR

ED

3456

LEV

COM NO

X63321

CN722

X52

PE

220-230V~

TO IN

DO

OR

UN

IT C

ON

NE

CTI

NG

P

OW

ER

SU

PP

LY

~/N

220

-230

V 6

0Hz

X63 21S2

NAME NAMECOMPRESSOR CAPACITOROUTDOOR FAN CAPACITORSURGE ABSORBERFUSE(3.15A)EXPANSION VALVE COILCOMPRESSOR(INNER PROTECTOR)OUTDOOR FAN MOTOR(INNER PROTECTOR)

VARISTORDISCHARGE TEMPERATURE THERMISTORAMBIENT TEMPERATURE THERMISTORSOLID STATE RELAYSOLID STATE RELAYTERMINAL BLOCKTERMINAL BLOCK

TRANSFORMERCONTACTORSOLENOID VALVE COIL RELAYSOLENOID VALVE COILCOMPRESSOR CONTACTOR

NOTES: 1.Use copper conductors only (For field wiring).2.Since the indoor and outdoor unit connecting wires have polarity, connect them according to the numbers (3,N,2). 3.Symbols below indicate.

: Terminal block, : Connector

MU-A24ND- S2

OUTDOOR UNIT

OUTDOOR UNIT

SYMBOLC1C2

DSAR

SYMBOLF

MCMF

SYMBOLTB1TB252C

NAME NAME NAMECOMPRESSOR CAPACITOROUTDOOR FAN CAPACITORSURGE ABSORBER

FUSE(3.15A)COMPRESSOR(INNER PROTECTOR)OUTDOOR FAN MOTOR(INNER PROTECTOR)

TERMINAL BLOCKTERMINAL BLOCKCOMPRESSOR CONTACTOR

NOTES: 1.Use copper conductors only (For field wiring).2.Since the indoor and outdoor unit connecting wires have polarity, connect them according to the numbers (2,N,L). 3.Symbols below indicate.

: Terminal block, : Connector

BLKWHTORN

BLUWHTORN

RED

BLK

WH

T

BLU

BLU

BLU

WHT

BR

N

52CG

RN

/YLW

BLU

BRN

BRN

C2

C1

TO

IND

OO

R U

NIT

CO

NN

EC

TIN

G

220-230V~

220-230V~

PO

WE

R S

UP

PLY

~/N

220

-230

V 6

0Hz

5 6

DSAR

L

N

2

N

L

TB2

TB1

MF

MC

4

52C1

R

SC

RED REDF

4

3

2

1

PE

OB405E.qxp 09.10.14 9:16 AM Page 7

Page 8: SERVICE MANUAL No. OB405 - Mitsubishi Ar … 18-24... · No. OB405 SERVICE MANUAL REVISED EDITION-E Models OUTDOOR UNIT ... RH277NHD RH247NRAT Electricity receiving unit: Indoor unit

8

REFRIGERANT SYSTEM DIAGRAM6

MU-A24NDOUTDOOR UNIT

Outdoorheatexchanger

Flared connection

Flared connection

Stop valve

Stop valve(with service port)

Capillary tube[3.0 x [2.0 x 550

Refrigerant flow in cooling

Compressor

Refrigerant pipe [15.88 (with heat insulator)

Refrigerant pipe [6.35 (with heat insulator)

Strainer#100

Accumulator

MU-A18ND

OUTDOOR UNIT

Unit : mm

Refrigerant pipe{6.35 (with heat insulator)

Refrigerant pipe{12.7 (with heat insulator)

Compressor

Outdoor heatexchanger

Flaredconnection

Strainer #100

Stop Valve (with service port)

Stop Valve Capillary tube[3.0 x [1.8 x 400

OB405E.qxp 09.10.14 9:16 AM Page 8

Page 9: SERVICE MANUAL No. OB405 - Mitsubishi Ar … 18-24... · No. OB405 SERVICE MANUAL REVISED EDITION-E Models OUTDOOR UNIT ... RH277NHD RH247NRAT Electricity receiving unit: Indoor unit

9

Outdoorheatexchanger

Flared connection DischargetemperaturethermistorRT62

Flared connection

Stop valve

Stop valve(with service port)

Capillary tube[3.6 x [2.4 x 50

Refrigerant flow in cooling

Compressor

Refrigerant pipe [15.88 (with heat insulator)

Refrigerant pipe [9.52 (with heat insulator)

Strainer #100

Strainer #100

Accumulator

Ambient temperaturethermistorRT63

Capillary tube[4.0 x [2.4 x 200

Capillary tube[4.0 x [2.4 x 100

LEV(Expansion valve)

Solenoid valve[4.2 x [3.0 x 50

MU-A30ND

OUTDOOR UNIT

MAX.REFRIGERANT PIPING LENGTH and MAX.HEIGHT DIFFERENCE

Model

Piping size O.D : mmRefrigerant piping : m

Max. length A

Max. Heightdifference

BGas Liquid

30

MU-A18ND

MU-A24ND

MU-A30ND{15.88

{6.35

{9.52

15

{12.7

Indoor unit

Outdoor unit

Max. lengthA

Max. Heightdifference

B

ADDITIONAL REFRIGERANT CHARGE(R22 : g)

NOTE : Calculation : Xg=15g/m ✕ (Refrigerant piping length (m)-7)

Model Outdoor unit precharged Refrigerant piping length (one way)

15m

120

20m

195

30m

345

7m

0

10m

452,200

1,400

2,400

MU-A18ND

MU-A30ND

MU-A24ND

Unit : mm

OB405E.qxp 09.10.15 1:32 PM Page 9

Page 10: SERVICE MANUAL No. OB405 - Mitsubishi Ar … 18-24... · No. OB405 SERVICE MANUAL REVISED EDITION-E Models OUTDOOR UNIT ... RH277NHD RH247NRAT Electricity receiving unit: Indoor unit

10

PERFORMANCE CURVES7

The standard data contained in these specifications apply only to the operation of the air conditioner under normal conditions.Since operating conditions vary according to the areas where these units are installed. The following information has beenprovided to clarify the operating characteristics of the air conditioner under the conditions indicated by the performance curve.

(1) GUARANTEED VOLTAGE198 ~ 253V, 60Hz

(2) AIR FLOWAir flow should be set at MAX.

(3) MAIN READINGS(1) Indoor intake air wet-bulb temperature : °CWB(2) Indoor outlet air wet-bulb temperature : °CWB(3) Outdoor intake air dry-bulb temperature : °CDB(4) Total input: WIndoor air wet/dry-bulb temperature difference on the left side of the following chart shows the difference between theindoor intake air wet/dry-bulb temperature and the indoor outlet air wet/dry-bulb temperature for your reference at service.

MU-A18ND MU-A24ND MU-A30ND

Indoor intake air WB temperature (:)

Outdoor intake air DB temperature (:)

Indoor intake air WB temperature (:)

Outdoor intake air DB temperature (:)

MS

-A30

ND

MU

-A30

ND

MS

-A24

ND

MU

-A24

ND

MS

-A18

ND

MU

-A18

ND

9.9

9.1

8.3

7.5

6.7

5.9

12.5

11.4

10.3

9.3

8.3

7.3

18.6

16.8

15.1

13.5

12.0

10.5

Wet and dry-bulbthermometers

Wet-and dry-bulbthermometers

How to measure the indoor air wet/dry-bulb temperature difference1. Attach at least 2 sets of wet and-dry-bulb thermometers to the indoor air intake as shown in the figure, and at least 2 sets

of wet-and-dry-bulb thermometers to the indoor air outlet. The thermometers must be attached to the position where airspeed is high.

2. Attach at least 2 sets of wet and dry-bulb thermometers to the outdoor air intake.Cover the thermometers to prevent direct rays of the sun.

3. Check that the air filter is cleaned.4. Open windows and doors of the room.5. Press the EMERGENCY OPERATION switch once to start the EMERGENCY COOL MODE.6. When system stabilizes after more than 15 minutes, measure temperature and take an average temperature.7. 10 minutes later, measure temperature again and check that the temperature does not change.

INDOOR UNIT OUTDOOR UNIT

OB405E.qxp 09.10.14 9:16 AM Page 10

Page 11: SERVICE MANUAL No. OB405 - Mitsubishi Ar … 18-24... · No. OB405 SERVICE MANUAL REVISED EDITION-E Models OUTDOOR UNIT ... RH277NHD RH247NRAT Electricity receiving unit: Indoor unit

11

10.0

9.0

8.0

7.0

6.0

5.015 18 20

50 60 7025 30 32 35(:)

(%)

MU-A24ND MU-A24ND

Out

door

low

pre

ssur

e

Out

door

uni

t cu

rren

t (A

)

Ambient temperature (˚C)/Ambient humidity (%) Ambient temperature (˚C)/Ambient humidity (%)

0.8

0.7

0.6

0.5

0.4

0.315 18 20

50 60 7025 30 32

8.0

7.0

6.0

5.0

4.0

3.0 35(:) (%)

(kgf/F [Gauge])(MPa [Gauge])

� Both indoor and outdoor units are under the same temperature/humidity condition.

OUTDOOR LOW PRESSURE AND OUTDOOR UNIT CURRENTCOOL operation

➁ Air flow should be set at MAX.

Dry-bulb temperature (:) Relative humidity (%)

20 50

25 60

30 70

3 The unit of pressure has been changed to MPa on the international system of units(SI unit system).The conversion factor is : 1(MPa [Gauge]) =10.2(kgf/ff [Gauge])

18 50 60 70

32 35(:)(%)

15 20 25 304.0

5.0

6.0

7.0

8.0

MU-A18ND MU-A18ND

Out

door

low

pre

ssur

e

Out

door

uni

t cu

rren

t (A

)

Ambient temperature (˚C)/Ambient humidity (%) Ambient temperature (˚C)/Ambient humidity (%)

8.0

7.0

6.0

5.0

4.0

3.018

50 7032 (:)

(%)15 20 25 30 35

0.3

0.4

0.5

0.6

0.7

0.8

(kgf/F [Gauge])(MPa [Gauge])

OB405E.qxp 09.10.14 9:16 AM Page 11

Page 12: SERVICE MANUAL No. OB405 - Mitsubishi Ar … 18-24... · No. OB405 SERVICE MANUAL REVISED EDITION-E Models OUTDOOR UNIT ... RH277NHD RH247NRAT Electricity receiving unit: Indoor unit

12

MU-A30ND

15 18 2050

2560

30 32 70

35(:) (%)

0.2

0.3

0.4

0.5

0.6

2.0

3.0

4.0

5.0

6.0

15 18 20 50

2560

30 3270

35(:) (%)

9.0

10.0

11.0

12.0

13.0

14.0

15.0

Out

door

low

pre

ssur

e

Out

door

uni

t cu

rren

t(A

)

(kgf/F[Gauge])(MPa[Gauge]) MU-A30ND

Ambient temperature (˚C)/Ambient humidity (%) Ambient temperature (˚C)/Ambient humidity (%)

3. Troubleshooting procedure1) First, check if the OPERATION INDICATOR lamp on the indoor unit is flashing on and off to indicate an abnormality.

To make sure, check how many times the abnormality indication is flashing on and off before starting service work.2) Before servicing that the connector and terminal are connected properly.3) If the electronic control P.C. board is supposed to be defective, check the copper foil pattern for disconnection and the

components for bursting and discolouration.4) When troubleshooting, refer to 8-2.

TROUBLESHOOTING8

8-1. Cautions on troubleshooting1. Before troubleshooting, check the following:

1) Check the power supply voltage.2) Check the indoor/outdoor connecting wire for mis-wiring.

2. Take care the following during servicing.1) Before servicing the air conditioner, be sure to turn off the main unit first with the remote controller, and then after

confirming the horizontal vane is closed, turn off the breaker and / or disconnect the power plug.

2) Be sure to turn OFF the power supply before removing the front panel,the cabinet, the top panel and the electronic control P.C. board.

3) When removing the electronic control P.C. board, hold the edge of theboard with care NOT to apply stress on the components.

4) When connecting or disconnecting the connectors, hold the housing ofthe connector. DO NOT pull the lead wires. Lead wiring Housing point

MU-A18ND MU-A24ND MU-A30ND

OB405E.qxp 09.10.14 9:16 AM Page 12

Page 13: SERVICE MANUAL No. OB405 - Mitsubishi Ar … 18-24... · No. OB405 SERVICE MANUAL REVISED EDITION-E Models OUTDOOR UNIT ... RH277NHD RH247NRAT Electricity receiving unit: Indoor unit

13

Start

Indoor unit operates.Outdoor unit dose not operate.

Indoor unit dose not receive the signal from remote controller.

OPERATION INDICATORlamp on the indoor unit is flashing on and off.

Outdoor unit operates in only Test Run operation.

MU-A30NDOutdoor unit dose not operate even in Test Run operation.

Indoor unit operates, when EMERGENCY OPERATION switch is pressed.

Indoor unit dose not operate, when EMERGENCY OPERATION switch is pressed.

Check room temperature thermistor.Refer to "Test point diagram and voltage".

Refer to 8-4. A "Check of outdoor unit".

Refer to "Check of remote controller and receiver P.C. board".

MS-A30NDFlash on andoff at 0.5-second intervalsCause: Indoor/Outdoor unit• Mis-wiring

2-time flash Cause:Indoor unit• Trouble of room temp- erature/ indoor coil thermistor

3-time flash Cause:Indoor unit• Trouble of indoor fan motor

MU-A30ND6-time flash Cause: Outdoor unit• Trouble of thermistor in outdoor unit

MU-A30ND7-time flash Cause: Outdoor unit• Trouble of outdoor control system

Refer to 8-4. C"How to checkmis-wiring (When outdoor unit dose not work)" .

Check room temperature thermistor and indoor coil thermis-tor.Refer to "Test point diagram and voltage".

Refer to "Check of indoor fan motor".

Refer to 8-4. E "Check of outdoor thermistor".

Replace the deicer P.C. board.

MU-A30ND10-time flash Cause: Outdoor unit• Trouble of low discharge temperature protection

Refer to 8-4. D "Check of LEV".

4-time flash Cause:Indoor unit• Trouble of indoor control system

Replace the indoor electronic control P.C. board.

1. Check indoor / outdoor connecting wire.2. Check of outdoor fuse. (MU-A18/A24ND)3. Refer to "Check of indoor electronic control P.C. board".

MU-A24ND - S2

MU-A30NDOutdoor unit dose not stop even if indoor unit stop.

Refer to 8-4. B "Check of outdoor unit".

Indoor unit operates.Outdoor unit dose not operate normally.

MU-A30NDOutdoor unit repeats start and stop.

Refer to 8-4. F "Check of solenoid valve coil".

w

w

Refer to indoor unit service manual.

"Test Run operation" means the operation within 30 minutes after EMERGENCY OPERATION switch is pressed.w

8-2. Instruction of troubleshooting

OB405E.qxp 09.10.14 9:16 AM Page 13

Page 14: SERVICE MANUAL No. OB405 - Mitsubishi Ar … 18-24... · No. OB405 SERVICE MANUAL REVISED EDITION-E Models OUTDOOR UNIT ... RH277NHD RH247NRAT Electricity receiving unit: Indoor unit

14

8-3. Trouble criterion of main partsMU-A18ND MU-A24ND MU-A30ND

Part name FigureCheck method and criterion

Measure the resistance between the terminals with a tester.(Coil wiring temperature -10°C ~ 40°C)

Compressor (MC)

INNER PROTECTOR155i 5: OPEN 90i10: CLOSE

NormalMU-A18ND

Color of lead wire

C – RC – S

1.26 " ~ 1.55 "1.81 " ~ 2.23 "

MU-A24ND0.74 " ~ 0.91 "1.84 " ~ 2.26 "

MU-A30ND0.54 " ~ 0.67 "1.23 " ~ 1.52 "

LEV(Expansion valve)

MU-A30ND

Color of lead wireWHT – REDRED – ORNYLW – BRNBRN – BLU

Normal

37.4 " ~ 53.9 "

Measure the resistance with a tester.(Part temperature : 0˚C ~ 40˚C)

Measure the resistance with a tester.(Part temperature –10˚C ~ 40˚C)

Discharge temperaturethermistor(RT62)MU-A30ND

Ambient temperature thermistor(RT63)MU-A30ND

Measure the resistance with a tester. Before measurement, hold the thermistor with your hands to warm it up.(Part temperature 0˚C ~ 40˚C)Refer to 8-5. "Test point diagram and voltage", "Outdoor deicer P.C. board",the chart of thermistor.

Refer to 8-5. "Test point diagram and voltage", "Outdoor deicer P.C. board", the chart of thermistor.

MU-A18ND MU-A24ND MU-A30ND

Measure the resistance between the terminals with a tester.(Coil wiring temperature -10°C ~ 40°C)

Color oflead wire

WHT – BLKBLK – REDBLK – YLWYLW – RED

63 " ~ 77 " 79 " ~ 96 "

––

57 " ~ 70 "58 " ~ 71 "

––

57 " ~ 69 "–

29 " ~ 35 "29 " ~ 35 "

NormalOutdoor fan motor (MF)

INNER PROTECTOR135i 5: OPEN 87i15: CLOSE

Measure the resistance with a tester.(Part temperature : –10˚C ~ 40˚C)

Solenoid valve coil(21S2)MU-A30ND

NormalMU-A30ND - S1

1,738 " ~ 2,125 "MU-A30ND - S2

1,230 " ~ 1,330 "

WHTBLK YLW RED ORN

MAIN

AUX.

MAIN

AUX.

WHTBLK RED ORN

MU-A18/A24ND

MU-A30ND

RED

WHT

BLK

P

C

S R

:INNER PROTECTORP

LEV

WHT6

RED1

ORN4

YLW

5

BR

N2

BL

U3

OB405E.qxp 09.10.14 9:16 AM Page 14

Page 15: SERVICE MANUAL No. OB405 - Mitsubishi Ar … 18-24... · No. OB405 SERVICE MANUAL REVISED EDITION-E Models OUTDOOR UNIT ... RH277NHD RH247NRAT Electricity receiving unit: Indoor unit

15

Is there 220-230V AC to between L-N on the outdoor terminal block?

No Check the outdoor power supply and connection of wiring.

Yes

Check the deicer P.C. board. Refer to 8-5.Is there 5V DC?

Compressor dose not operate.

YesPress the EMERGENCY OPERATION switch. 3-minute time delay works. Test run operation operates for 30 minutes.

Outdoor fan motor dose not operate.

No Make the connectionof wiring correct.

Check the compressor.

Replace the compressorcontactor(52C).

Turn ON the power supply.

Yes

Is there 220-230V AC between 2 on the compressor contactor(52C) and N on the outdoor terminal block?

Yes

Is there 220-230V AC CN730 on the deicer P.C. board?

Replace thedeicer P.C. board.

Replace the deicer P.C. board.

No

No

No

Yes

Yes

Check the deicer P.C. board. Refer to 8-5.Is there 5V DC?

Yes

Is there 220-230V AC CN711 1-3 or 2-3 on the deicer P.C. board?

No Make the connectionof wiring correct.

Check the outdoor fan motor. Refer to 8-3.

Yes

Is there 220V AC CN730 on the deicer P.C. board?

Replace the deicer P.C. board.

Replace the deicer P.C. board.

No

No

Press the EMERGENCY OPERATION switch. 3-minute time delay works. Test run operation operates for 30 minutes.

Is there 220-230V AC between A1 and A2 on the compressor contactor (52C)?

Check of outdoor unitA

8-4. Troubleshooting flowCompressor and / or outdoor fan motor dose not operate.

MU-A30ND

OB405E.qxp 09.10.14 9:16 AM Page 15

Page 16: SERVICE MANUAL No. OB405 - Mitsubishi Ar … 18-24... · No. OB405 SERVICE MANUAL REVISED EDITION-E Models OUTDOOR UNIT ... RH277NHD RH247NRAT Electricity receiving unit: Indoor unit

16

Compressor and / or outdoor fan motor dose not stop.

After 30 seconds, did compressor stop?

No

Yes

Replace the deicer P.C. board.

Yes

1 Turn OFF the power supply.2 After 30 seconds, turn ON the power supply again.3 Operate the unit in COOL mode by pressing the EMERGENCY OPERATION switch.4 Operate the unit for 1 minute or more and stop it by pressing the EMERGENCY OPERATION switch again.

Ok

No

After 30 seconds, did outdoor fan stop?

Replace thedeicer P.C. board.

Yes

Ok

No

Is there 220-230V AC between 2 on the compressor contactor(52C) and N on the outdoor terminal block?

Yes

Replace the compressor contactor(52C).

No Make the connectionof wiring correct.

Is there 220-230V AC between A1 and A2 on the compressor contactor (52C)?

MU-A30ND

1 Turn OFF the power supply.2 After 30 seconds, turn ON the power supply again.3 Operate the unit in COOL mode by pressing the EMERGENCY OPERATION switch.4 Operate the unit for 1 minute or more and stop it by pressing the EMERGENCY OPERATION switch again.

After 30 seconds, does compressor stop ?

Yes

NoIs there 220-230V AC between 3-N on the outdoor terminal block?

Replace the indoor electronic control P.C. board.

No Make the connection of wiring correct.

Is there 220-230V AC between 3-N on the indoor terminal block?

Yes

Reconnect the continuity of indoor and outdoor unit connection.

Is there 220-230V AC between 1 on the compressor contactor(52C) and N on the outdoor terminal block?

No

Yes

Reconnect the continuity of indoor and outdoor unit connection.

Yes

Replace the compressor contactor(52C).

OK

No

After 30 seconds, does outdoor fan motor stop ?

Yes

Is there 220-230V AC between 3-N on the indoor terminal block?

No

OK

Replace the indoor electronic control P.C. board.

Yes

NoIs there 220-230V AC between 3-N on the outdoor terminal block?

Make the connection of wiring correct.

Is there 220-230V AC between 3 on the compressor contactor(52C) and N on the outdoor terminal block?

Yes

Replace the compressor contactor(52C).

No

Yes

No

MU-A24ND - S2

Check of outdoor unitB

OB405E.qxp 09.10.14 9:16 AM Page 16

Page 17: SERVICE MANUAL No. OB405 - Mitsubishi Ar … 18-24... · No. OB405 SERVICE MANUAL REVISED EDITION-E Models OUTDOOR UNIT ... RH277NHD RH247NRAT Electricity receiving unit: Indoor unit

17

How to check mis-wiringC

1. Turn OFF the power supply and disconnect only terminal block 3 of indoor/ outdoor connecting wire on indoor side.

2. Short-circuit terminal block N-3 by lead wire. 3. Turn ON the power supply and press EMERGENCY OPERATION switch once.

When EMERGENCY OPERATION is operated, is there 10V DC between both ends of R601 on the deicer P.C. board? (Refer to 8-5.)However the stylus of a tester would be between 5 ~10V.

Start

No

NoIs there 1V DC detected between both ends of PS132 on the indoor electronic control P.C. board ?However, the stylus of a tester would be between 0 and 20V.

• Turn ON the power supply.• Press EMERGENCY OPERATION switch once.

Is this mis-wiring, poor contact, or wire disconnection?Make them sure.

Replace the indoor electronic control P.C. board.

Is there 220-230V AC between L-N on the outdoor terminal block?

No Check the outdoor power supply and connection of wiring.

Is there 5V DC between J101 + -J401 - ?(Refer to 8-5.)

Yes

NoReplace the deicer P.C. board.

Yes

NoMake the wiring between CN730 on the deicer P.C. board and outdoor terminal block correct.(Refer to 8-5.)

Replace the deicer P.C. board.

Yes

Yes

Yes

When the unit has mis-wiring, in 3 minutes, OPERATION INDICATOR lamp on indoor unit flash on and off at 0.5 second intervals. w

w Short circuit of JPG and JPS on the indoor electronic control P.C. board enables self -check to be displayed in 3 seconds.

• Turn OFF the power supply. • Disconnect the lead wire that terminal block N-3 is short-circuited.• Connect ON indoor/outdoor connecting wire.

Turn ON the power supply.

Refer to indoor unitservice manual.

When OPERATION INDICATOR lamp flashes ON and OFF in every 0.5-second.Outdoor unit dose not operate.

MU-A30ND

OB405E.qxp 09.10.14 9:16 AM Page 17

Page 18: SERVICE MANUAL No. OB405 - Mitsubishi Ar … 18-24... · No. OB405 SERVICE MANUAL REVISED EDITION-E Models OUTDOOR UNIT ... RH277NHD RH247NRAT Electricity receiving unit: Indoor unit

18

Check of outdoor thermistor

Measure resistance between CN 662 3 and 4.

No

Yes

Replace the thermistor.

Measure resistance between CN 662 1 and 2.

Connect CN662.Turn ON the power supply and press the EMERGENCY OPERATION switch.

Does the resistances of thermistor have the characteristics on 8-5.?

No

Yes

Does the unit operate 10 minutes or more?

Replace the deicer P.C. board.

Ok W

Turn OFF the power supply.

Discharge temperature thermistor(RT62)

Ambient temperature thermistor(RT63)

W Defective contact of the connector is considered.

w Disconnect the connectors CN662 from the deicer P.C. board. (Check the characteristics of each thermistor.)

E

When OPERATION INDICATOR lamp flashes 6-time.Thermistors in the outdoor unit are abnormal.

Check of LEV (Expansion valve)D

With remote controller set toward the indoor unit, press OPERATE/ STOP(ON/ OFF) button and confirm one beep tone.

LEV operates in full-opening direction.

Is LEV properly fixed to the expansion valve?

Ok

Do you hear the expansion valve "click, click·······"?Do you feel the expansion valve vibrate on touching it?

Does the resistance of LEV have the characteristics on 8-3?

No

Yes

Yes

Yes

No

No Properly fix LEV coil to the expansion valve.

Replace the deicer P.C. board.

NOTE : After check of LEV, do the undermentioned operation.

1. Turn OFF the power supply and turn ON again.

2. Press the RESET button on the remote controller.Replace the LEV.

Remote controller model : KP0BTurn ON the power supply.1 While pressing OPERATION SELECT button on the remote controller, press RESET button.2 Release RESET button to confirm if all LCD in operation display section of the remote controller is displayed.3 Release OPERATION SELECT button.

Remote controller model : KM04BTurn ON the power supply.1 While pressing both OPERATION SELECT button and TOO COOL button on the remote controller at the same time, press RESET button.2 First, release RESET button. And release the other two buttons after all LCD in operation display section of the remote controller is displayed after 3 seconds.

KP0B KM04B

AMPMCLOCK

AMPM

AMPMCLOCK

AMPM

When OPERATION INDICATOR lamp flashes 10-time. Cooling mode dose not operate.

MU-A30ND

MU-A30ND

OB405E.qxp 09.10.14 9:16 AM Page 18

Page 19: SERVICE MANUAL No. OB405 - Mitsubishi Ar … 18-24... · No. OB405 SERVICE MANUAL REVISED EDITION-E Models OUTDOOR UNIT ... RH277NHD RH247NRAT Electricity receiving unit: Indoor unit

19

Ok

Do you hear "click" from the solenoid valve coil?

No

Yes

After 1minute or more has passed since the compressor started, operate the solenoid valve coil by heating or cooling the ambient temperature thermistor.(Refer to Solenoid valve control.)

Turn ON the power supply.Operate the unit in COOL mode by pressing the EMERGENCY OPERATION switch.

Yes

Check of the solenoid valve coil.(Refer to 8-3.)

Is there 220-230V AC CN722 on the deicer P.C. board?

Replace thedeicer P.C. board.

NoTurn ON the solenoid valve coil.(Refer to Solenoid valve control.)

Check of solenoid valve coilF

Outdoor unit repeats start and stop.

Solenoid valve controlThe solenoid valve opens when the ambient temperature thermistor RT63 temperature reaches 49.2: or more after 1minute has passed since the compressor turned on. Then, the solenoid valve maintains to open until the ambient tem-perature thermistor RT63 temperature falls 46.2: or less.

NOTE: The solenoid valve remains to close when the ambient temperature thermistor RT63 temperature is 49.2: orless after 1 minute has passed since the compressor turned on.

ONOFF

46.2:49.2:

Ambient temperature thermistor RT63 temperature

Solenoid valve

MU-A30ND

OB405E.qxp 09.10.14 9:16 AM Page 19

Page 20: SERVICE MANUAL No. OB405 - Mitsubishi Ar … 18-24... · No. OB405 SERVICE MANUAL REVISED EDITION-E Models OUTDOOR UNIT ... RH277NHD RH247NRAT Electricity receiving unit: Indoor unit

20

8-5. Test point diagram and voltage

MU-A30ND

Outdoor deicer P.C. board

Varistor(NR62)

Fuse 3.15A / 250V

} 12V DC

}5V DC

+

+

Temperature(:)

Discharge temperature thermistor(RT62)

Res

ista

nce

(k"

)

0 10 20 30 40 50 60 70 80 90 100 110 1200

100

200

300

400

500

600

700

800

900

Ambient temperature thermistor (RT63)

-20 -10 0 10 20 30 400

10

20

30

40

50

60

70

80

90

100

Temperature(:)

Res

ista

nce

(k"

)

CN662 1-2Discharge temperaturethermistor (RT62)(Refer to 8-4.E.)

CN662 3-4Ambient tempera-ture thermistor(RT63)(Refer to 8-4.E.)

LEV connector(CN724)

Fan motorconnector(CN711)

Varistor (NR61)CN7301-3220-230-240V AC

}(Refer to 8-4. C.)

}

R60110V DC

(Refer to 8-4. C.)

(Refer to 8-4. A or C.)

J101

J401

+

Solenoidvalve coil(CN722)

OB405E.qxp 09.10.14 9:16 AM Page 20

Page 21: SERVICE MANUAL No. OB405 - Mitsubishi Ar … 18-24... · No. OB405 SERVICE MANUAL REVISED EDITION-E Models OUTDOOR UNIT ... RH277NHD RH247NRAT Electricity receiving unit: Indoor unit

21

DISASSEMBLY INSTRUCTIONS9

(1) Slide the sleeve and check if there is a locking lever or not. (2) The terminal with this connector has the locking mechanism.

1Slide the sleeve.2Pull the terminal while pushing the locking lever.

1Hold the sleeve, and pull out the terminal slowly.

The terminal which has the locking mechanism can be detached as shown below.There are two types ( Refer to (1) and (2)) of the terminal with locking mechanism.The terminal without locking mechanism can be detached by pulling it out.Check the shape of the terminal before detaching.

<"Terminal with locking mechanism" Detaching points>

Connector

Sleeve

Locking lever

OPERATING PROCEDURE PHOTOS

1. Removing the cabinet(1) Remove the screws of the cabinet.(2) Hold the bottom of the cabinet on both sides to remove the

cabinet.(3) Remove the screws of the service panel and remove the

service panel.(4) Remove the screw of the valve cover and remove the valve

cover (MU-A18ND- ).S2

9-1. MU-A18NDOUTDOOR UNIT

Photo 1

Photo 2

Screwsof thecabinet

Screw ofthe valvecover

Screwsof theServicepanel

Photo : MU-A18ND - S2

Screwsof thecabinet

OB405E.qxp 09.10.14 9:16 AM Page 21

Page 22: SERVICE MANUAL No. OB405 - Mitsubishi Ar … 18-24... · No. OB405 SERVICE MANUAL REVISED EDITION-E Models OUTDOOR UNIT ... RH277NHD RH247NRAT Electricity receiving unit: Indoor unit

22

OPERATING PROCEDURE PHOTOS

2. Removing the electrical parts(1) Remove the service panel and the cabinet.(2) Remove the following parts.

•Compressor capacitor (C1)•Outdoor fan capacitor (C2)•Terminal blocks (TB1,TB2)

Photo 3

Compressor capacitor(C1)

3. Removing the outdoor fan motor(1) Remove the cabinet. (Refer to 1.)(2) Disconnect the connector remove the hooked lead wire

from the fan motor.(3) Remove the propeller nut and remove the propeller.(4) Remove screws fixing the fan motor.

4. Removing the compressor(1) Remove the cabinet. (Refer to 1.)(2) Remove the soundproof felt.(3) Remove the terminal cover on the compressor.(4) Disconnect lead wires from the glass terminal of the com-

pressor.(5) Recover gas from the refrigerant circuit.

NOTE:Recover gas from the pipes until the pressure gauge shows 0 kg/cm2 (0MPa).

(6) Disconnect the welded part of the discharge pipe.(7) Disconnect the welded part of the suction pipe.(8) Remove nuts fixing the compressor.(9) Remove the compressor.

Photo 4 Hook

Propeller

Propeller nut

Outdoor fan capacitor(C2)

Terminalblocks(TB1,TB2)

Set screws of Outdoor fan motor

Set screws of outdoor fan motor

Photo 5

Compressor

Dischargepipe

Suctionpipe

Compressor nuts

OB405E.qxp 09.10.14 9:16 AM Page 22

Page 23: SERVICE MANUAL No. OB405 - Mitsubishi Ar … 18-24... · No. OB405 SERVICE MANUAL REVISED EDITION-E Models OUTDOOR UNIT ... RH277NHD RH247NRAT Electricity receiving unit: Indoor unit

23

9-2. MU-A24NDOUTDOOR UNIT

OPERATING PROCEDURE PHOTOS

1.Removing the cabinet(1) Remove the screw of the service panel.(2) Remove the screws of the top panel.(3) Remove the screw of the valve cover.(4) Remove the service panel.(5) Remove the top panel.(6) Remove the valve cover.(7) Remove the screws of the front panel.(8) Remove the front panel.(9) Remove the screws of the back panel.(10) Remove the back panel.

Photo 2

Photo 1

Photo 3

Screw of the top panel

Screws of the cabinet

Screwsof thecabinet

Screwsof thetoppanel

Screw of the motor support

Set screws of the back panel

Screwsof thefrontpanel

2. Removing the electrical parts(1) Remove the service panel and the cabinet.(2) Remove the following parts.

•Compressor capacitor (C1)•Outdoor fan capacitor (C2)•Terminal blocks (TB1,TB2)•Compressor contactor (52C) (MU-A24ND- )S2

Screw of the service panel

Screwof thevalvecover

Screwsof thebackpanel

Photo 4

Screwsof therelaypanel

Compressorcapacitor (C1)

Outdoor fancapacitor (C2)

Terminalblocks

(TB1,TB2)

Screwsof therelaypanel

Screws of the relay panel

Photo : MU-A24ND - S2

Compressorcontactor(MU-A24ND- )S2

OB405E.qxp 09.10.14 9:16 AM Page 23

Page 24: SERVICE MANUAL No. OB405 - Mitsubishi Ar … 18-24... · No. OB405 SERVICE MANUAL REVISED EDITION-E Models OUTDOOR UNIT ... RH277NHD RH247NRAT Electricity receiving unit: Indoor unit

24

Photo 6

Suction pipe

Discharge pipe

Terminal cover

OPERATING PROCEDURE PHOTOS

3. Removing the propeller and the outdoor fan motor(1) Remove the cabinet. (Refer to 1.)(2) Remove the propeller nut and the propeller.NOTE : Loose the propeller in the rotating direction for

removal.When attaching the propeller, align the mark on the propeller and the motor shaft cut section.Set the propeller in position by using the cut on the shaft and the mark on the propeller.

(3) Remove the clamp of outdoor fan motor lead wire and disconnect the outdoor fan motor connector.

(4) Remove the screws fixing the outdoor fan motor.(5) Remove the outdoor fan motor.

4. Removing the compressor(1) Remove the cabinet. (Refer to 1.)(2) Remove the relay panel.(3) Remove the soundproof felt.(4) Remove the terminal cover on the compressor.(5) Disconnect lead wires from the compressor.(6) Recover gas from the refrigerant circuit.

NOTE:Recover gas from the pipes until the pressure gauge shows 0 kg/cm2 (0 MPa).

(7) Disconnect the welded part of the discharge pipe.(8) Disconnect the welded part of the suction pipe.(9) Remove nuts fixing the compressor.(10) Remove the compressor.

Compressor nuts

Photo 5

Set screws of theoutdoor fan motor

Propellernut

Propeller

Set screws of the outdoor fan motor

Photo : MU-A24ND - S2

OB405E.qxp 09.10.14 9:16 AM Page 24

Page 25: SERVICE MANUAL No. OB405 - Mitsubishi Ar … 18-24... · No. OB405 SERVICE MANUAL REVISED EDITION-E Models OUTDOOR UNIT ... RH277NHD RH247NRAT Electricity receiving unit: Indoor unit

25

9-3. MU-A30NDOUTDOOR UNIT

OPERATING PROCEDURE PHOTOS

1.Removing the cabinet(1) Remove the screw of the service panel.(2) Remove the screws of the top panel.(3) Remove the screw of the valve cover.(4) Remove the service panel.(5) Remove the top panel.(6) Remove the valve cover.(7) Remove the screws of the front panel.(8) Remove the front panel.(9) Remove the screws of the back panel.(10) Remove the back panel.

Photo 2

Photo 1

Photo 3

Screw of the top panel

Screws of the cabinet

Screwsof thecabinet

Screwsof thetoppanel

Screw of the motor support

Set screws of the back panel

Screwsof thefrontpanel

2. Removing the deicer P.C. board(1) Remove the service panel and the cabinet.(2) Disconnect all the connectors and the terminals on the

deicer P.C. board.(3) Remove the deicer P.C. board.

Screw of the service panel

Screwof thevalvecover

Screwsof thebackpanel

Photo 4 Deicer P.C. board

Screwsof therelaypanel

Terminal blocks(TB1,TB2)

Compressorcapacitor(C1)

Outdoor fancapacitor (C2)

Screwsof therelaypanel

Compressorcontactor(52C)

OB405E.qxp 09.10.14 9:16 AM Page 25

Page 26: SERVICE MANUAL No. OB405 - Mitsubishi Ar … 18-24... · No. OB405 SERVICE MANUAL REVISED EDITION-E Models OUTDOOR UNIT ... RH277NHD RH247NRAT Electricity receiving unit: Indoor unit

26

Photo 6

Suction pipe

Discharge pipe

Terminal cover

OPERATING PROCEDURE PHOTOS

3. Removing the propeller and the outdoor fan motor(1) Remove the cabinet. (Refer to 1.)(2) Remove the propeller nut and the propeller.NOTE : Loose the propeller in the rotating direction for

removal.When attaching the propeller, align the mark on the propeller and the motor shaft cut section.Set the propeller in position by using the cut on the shaft and the mark on the propeller.

(3) Remove the clamp of outdoor fan motor lead wire and disconnect the outdoor fan motor connector.

(4) Remove the screws fixing the outdoor fan motor.(5) Remove the outdoor fan motor.

Photo 5

Set screws of theoutdoor fan motor

Propellernut

4. Removing the compressor(1) Remove the cabinet. (Refer to 1.)(2) Remove the relay panel.(3) Remove the soundproof felt.(4) Remove the terminal cover on the compressor.(5) Disconnect lead wires from the compressor.(6) Recover gas from the refrigerant circuit.

NOTE:Recover gas from the pipes until the pressure gauge shows 0 kg/cm2 (0 MPa).

(7) Disconnect the welded part of the discharge pipe.(8) Disconnect the welded part of the suction pipe.(9) Remove nuts fixing the compressor.(10) Remove the compressor.

Propeller

Compressor nuts

Compressor

Set screws of theoutdoor fan motor

OB405E.qxp 09.10.14 9:16 AM Page 26

Page 27: SERVICE MANUAL No. OB405 - Mitsubishi Ar … 18-24... · No. OB405 SERVICE MANUAL REVISED EDITION-E Models OUTDOOR UNIT ... RH277NHD RH247NRAT Electricity receiving unit: Indoor unit

27

PARTS LIST (non-RoHS compliant)10

MU-A18ND10-1. OUTDOOR UNIT

STRUCTURAL PARTS, ELECTRICAL PARTS AND FUNCTIONAL PARTS

118

13

14

12

17

4 5 6

10

98

2

3

7

19

16

20

15

MU-A18ND - S1

Symbolin WiringDiagram

Q'ty/unit

RemarksPart No. Part NameNo.MU-A18ND - S2

E02 817 233E02 A27 233E02 817 232E02 817 521E02 141 501E02 496 515E02 075 506E02 949 900E02 817 290E02 A27 290E02 140 661E02 139 662E02 819 650E02 817 245E02 818 301E02 561 630E02 A27 630E02 890 383E02 795 374E02 798 374E02 895 351E02 816 353E02 817 009E02 627 936E02 A49 382E07 001 241

1

234567

8

910111213

14

151617181920212223

BACK PANELBACK PANELCABINETGRILLEPROPELLERMOTOR SUPPORTCOMPRESSOR RUBBER SETCOMPRESSORBASEBASESTOP VALVE(GAS)STOP VALVE(LIQUID)VALVE COVERSERVICE PANELOUTDOOR FAN MOTOROUTDOOR HEAT EXCHANGEROUTDOOR HEAT EXCHANGERSURGE ABSORBERTERMINAL BLOCKTERMINAL BLOCKOUTDOOR FAN CAPACITORCOMPRESSOR CAPACITORHANDLECAPILLARY TUBEFUSEFUSE HOLDER

1

1111311

11

111

111111111

3RUBBERS/SETRH247NRAT

{12.7{ 6.35

RA6V60 -

3P3P3.0+/440V AC35+/440V AC

{3.0o{1.8o4003.15A

MC

MF

DSARTB2TB1C2C1

F

1111131

111111

1111111111

Part numbers that are circled are not shown in the illustration.

11

OB405E.qxp 09.10.14 9:16 AM Page 27

Page 28: SERVICE MANUAL No. OB405 - Mitsubishi Ar … 18-24... · No. OB405 SERVICE MANUAL REVISED EDITION-E Models OUTDOOR UNIT ... RH277NHD RH247NRAT Electricity receiving unit: Indoor unit

28

MU-A24ND MU-A30ND10-2. OUTDOOR UNIT STRUCTURAL PARTS, ELECTRICAL PARTS

AND FUNCTIONAL PARTS

4

23

15

10

1

11 12

2

6

7

8

9

17

16

17

18

19

20

21

24252627

3

22

5

13

14

A

B

PARTS LIST (non-RoHS compliant)

OB405E.qxp 09.10.14 9:16 AM Page 28

Page 29: SERVICE MANUAL No. OB405 - Mitsubishi Ar … 18-24... · No. OB405 SERVICE MANUAL REVISED EDITION-E Models OUTDOOR UNIT ... RH277NHD RH247NRAT Electricity receiving unit: Indoor unit

29

MU-A24ND - S1

MU-A24ND - S2

MU-A30ND - S1

Symbolin WiringDiagram

Q'ty/unit

RemarksPart No.No. Part Name

E02 819 297E02 890 630E02 947 630E02 950 301E02 951 301E02 214 501E07 070 508E02 889 290E02 890 290E02 819 232E02 819 009E02 819 521E02 527 506E02 784 900E02 951 900E02 889 661E02 947 662E02 890 662E02 889 932E02 819 650E02 819 245E02 819 309E02 890 383E02 795 374E02 889 374E02 817 374E02 890 351E02 951 451E02 A19 340E02 951 340E02 889 353E02 816 353E02 819 233E02 817 009E02 726 515E02 890 640E02 819 493E02 A49 382E02 336 385E02 948 936E02 948 937E02 262 936E02 527 936E02 625 936E02 947 490E02 947 492E07 001 241

1

2

3

45

6

78910

11

12

13

1415161718

19

202122

23

24

25262728293031

32

33

343536

TOP PANELOUTDOOR HEAT EXCHANGEROUTDOOR HEAT EXCHANGEROUTDOOR FAN MOTOROUTDOOR FAN MOTORPROPELLER PROPELLER NUTBASEBASECABINETHANDLEFAN GUARDCOMPRESSOR RUBBER SETCOMPRESSOR COMPRESSORSTOP VALVE(GAS)STOP VALVE(LIQUID)STOP VALVE(LIQUID)ACCUMULATORVALVE COVERSERVICE PANELTHERMISTORSURGE ABSORBERTERMINAL BLOCKTERMINAL BLOCKTERMINAL BLOCKOUTDOOR FAN CAPACITORDEICER P.C. BOARDCOMPRESSOR CONTACTORCOMPRESSOR CONTACTORCOMPRESSOR CAPACITORCOMPRESSOR CAPACITORBACK PANEL(OUT)HANDLEMOTOR SUPPORTEXPANSION VALVEEXPANSION VALVE COILFUSEVARISTORCAPILLARY TUBE(TAPER PIPE)CAPILLARY TUBE(TAPER PIPE)CAPILLARY TUBECAPILLARY TUBECAPILLARY TUBESOLENOID VALVE COILSOLENOID VALEFUSE HOLDER

RA6N75-RA6N75-

4RUBBERS/SETPH33NPBTNH44NAVT{15.88{6.35{9.52

DISCHARGE, AMBIENT

3P3P3P4.0+/440V AC

FIGUREBFIGUREA55+/440V AC35+/440V AC

3.15A

{4.2x{3.0x50{3.6x{2.4x50{4.0x{2.4x200{4.0x{2.4x100{3.0x{2.0x550

MFMF

MCMC

RT62, RT63DSARTB2TB2TB1C2

52C52CC1C1

LEVF,F61NR61

21S2

1

11

111

11141

11

111

11

11

1111

1

1

1

1

11

111

11141

11

111

11

11

1

1111

1

1

1

11

111

11114

11

111111

1111

11

11111111111

11

Part numbers that are circled are not shown in the illustration.

MU-A24ND MU-A30ND10-2. OUTDOOR UNIT STRUCTURAL PARTS, ELECTRICAL PARTS

AND FUNCTIONAL PARTS

PARTS LIST (non-RoHS compliant)

OB405E.qxp 09.10.14 9:16 AM Page 29

Page 30: SERVICE MANUAL No. OB405 - Mitsubishi Ar … 18-24... · No. OB405 SERVICE MANUAL REVISED EDITION-E Models OUTDOOR UNIT ... RH277NHD RH247NRAT Electricity receiving unit: Indoor unit

30

RoHS PARTS LIST (RoHS compliant)11

MU-A18ND11-1. OUTDOOR UNIT

STRUCTURAL PARTS, ELECTRICAL PARTS AND FUNCTIONAL PARTS

118

13

14

12

17

4 5 6

10

98

2

3

7

19

16

20

15

11

OB405E.qxp 09.10.14 9:16 AM Page 30

Page 31: SERVICE MANUAL No. OB405 - Mitsubishi Ar … 18-24... · No. OB405 SERVICE MANUAL REVISED EDITION-E Models OUTDOOR UNIT ... RH277NHD RH247NRAT Electricity receiving unit: Indoor unit

31

MU-A18ND 11-1. OUTDOOR UNIT

STRUCTURAL PARTS, ELECTRICAL PARTS AND FUNCTIONAL PARTS

MU-A18ND - S1

Symbolin WiringDiagram

Q'ty/unit

RemarksPart No. Part NameNo.

RoH

S

MU-A18ND - S2

E12 817 233E12 A27 233E12 817 232E12 817 521E12 141 501E12 496 515E12 075 506E12 949 900E12 817 290E12 A27 290E12 140 661E12 139 662E12 819 650E12 817 245E12 818 301E12 561 630E12 A27 630E12 890 383E12 795 374E12 798 374E12 895 351E12 816 353E12 817 009E12 627 936E12 A49 382E17 001 241

1

234567

8

910111213

14

151617181920212223

BACK PANELBACK PANELCABINETGRILLEPROPELLERMOTOR SUPPORTCOMPRESSOR RUBBER SETCOMPRESSORBASEBASESTOP VALVE(GAS)STOP VALVE(LIQUID)VALVE COVERSERVICE PANELOUTDOOR FAN MOTOROUTDOOR HEAT EXCHANGEROUTDOOR HEAT EXCHANGERSURGE ABSORBERTERMINAL BLOCKTERMINAL BLOCKOUTDOOR FAN CAPACITORCOMPRESSOR CAPACITORHANDLECAPILLARY TUBEFUSEFUSE HOLDER

GGGGGGGGGGGGGGGGGGGGGGGGGG

1

1111311

11

111

111111111

3RUBBERS/SETRH247NRAT

{12.7{ 6.35

RA6V60 -

3P3P3.0+/440V AC35+/440V AC

{3.0o{1.8o4003.15A

MC

MF

DSARTB2TB1C2C1

F

1111131

111111

1111111111

Part numbers that are circled are not shown in the illustration.

RoHS PARTS LIST (RoHS compliant)

OB405E.qxp 09.10.14 9:16 AM Page 31

Page 32: SERVICE MANUAL No. OB405 - Mitsubishi Ar … 18-24... · No. OB405 SERVICE MANUAL REVISED EDITION-E Models OUTDOOR UNIT ... RH277NHD RH247NRAT Electricity receiving unit: Indoor unit

32

MU-A24ND MU-A30ND 11-2. OUTDOOR UNIT STRUCTURAL PARTS, ELECTRICAL PARTS

AND FUNCTIONAL PARTS

4

23

15

10

1

11 12

2

6

7

8

9

17

16

17

18

19

20

21

24252627

3

22

5

13

14

A

B

RoHS PARTS LIST (RoHS compliant)

OB405E.qxp 09.10.14 9:16 AM Page 32

Page 33: SERVICE MANUAL No. OB405 - Mitsubishi Ar … 18-24... · No. OB405 SERVICE MANUAL REVISED EDITION-E Models OUTDOOR UNIT ... RH277NHD RH247NRAT Electricity receiving unit: Indoor unit

33

MU-A24ND -

S1

MU-A24ND -

S2

MU-A30ND -

S1

MU-A30ND -

S2

Symbolin WiringDiagram

Q'ty/unit

RemarksPart No.

Ro

HS

No. Part Name

E12 819 297E12 890 630E12 947 630E12 950 301E12 951 301E12 214 501E17 070 508E12 889 290E12 890 290E12 819 232E12 819 009E12 819 521E12 527 506E12 784 900E12 951 900E12 889 661E12 947 662E12 890 662E12 889 932E12 819 650E12 819 245E12 819 309E12 890 383E12 795 374E12 889 374E12 817 374E12 890 351E12 951 451E12 B19 451E12 A19 340E12 951 340E12 889 353E12 816 353E12 819 233E12 817 009E12 726 515E12 890 640E12 819 493E12 A49 382E12 336 385E12 948 936E12 B18 936E12 948 937E12 262 936E12 527 936E12 625 936E12 947 490E12 B19 490E12 947 492E12 B18 492E17 001 241

1

2

3

45

6

78910

11

12

13

1415161718

19

2021

22

23

24

25262728293031

32

33

34

35

36

TOP PANELOUTDOOR HEAT EXCHANGEROUTDOOR HEAT EXCHANGEROUTDOOR FAN MOTOROUTDOOR FAN MOTORPROPELLER PROPELLER NUTBASEBASECABINETHANDLEFAN GUARDCOMPRESSOR RUBBER SETCOMPRESSOR COMPRESSORSTOP VALVE (GAS)STOP VALVE (LIQUID)STOP VALVE (LIQUID)ACCUMULATORVALVE COVERSERVICE PANELTHERMISTORSURGE ABSORBERTERMINAL BLOCKTERMINAL BLOCKTERMINAL BLOCKOUTDOOR FAN CAPACITORDEICER P.C. BOARDDEICER P.C. BOARDCOMPRESSOR CONTACTORCOMPRESSOR CONTACTORCOMPRESSOR CAPACITORCOMPRESSOR CAPACITORBACK PANEL (OUT)HANDLEMOTOR SUPPORTEXPANSION VALVEEXPANSION VALVE COILFUSEVARISTORCAPILLARY TUBE (TAPER PIPE)CAPILLARY TUBE (TAPER PIPE)CAPILLARY TUBE (TAPER PIPE)CAPILLARY TUBECAPILLARY TUBECAPILLARY TUBESOLENOID VALVE COILSOLENOID VALVE COILSOLENOID VALESOLENOID VALEFUSE HOLDER

RA6N75-RA6N75-

4RUBBERS/SETPH33NPBTNH44NAVT{15.88{6.35{9.52

DISCHARGE, AMBIENT

3P3P3P4.0+/440V AC

FIGUREBFIGUREA55+/440V AC35+/440V AC

3.15A

{4.2x{3.0x50{4.2x{3.0x50{3.6x{2.4x50{4.0x{2.4x200{4.0x{2.4x100{3.0x{2.0x550

MFMF

MCMC

RT62, RT63DSARTB2TB2TB1C2

52C52CC1C1

LEVF,F61NR61

21S221S2

1

11

111

11141

11

111

11

11

1111

1

1

1

GGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGG

1

11

111

11141

11

111

11

11

1

1111

1

1

1

11

111

11114

11

111111

1111

11

11111111

111

1

1

11

111

11114

11

111111

111

1

11

1111111

1111

1

1

Part numbers that are circled are not shown in the illustration.

MU-A24ND MU-A30ND11-2. OUTDOOR UNIT STRUCTURAL PARTS, ELECTRICAL PARTS

AND FUNCTIONAL PARTS

RoHS PARTS LIST (RoHS compliant)

OB405E.qxp 09.10.14 9:16 AM Page 33

Page 34: SERVICE MANUAL No. OB405 - Mitsubishi Ar … 18-24... · No. OB405 SERVICE MANUAL REVISED EDITION-E Models OUTDOOR UNIT ... RH277NHD RH247NRAT Electricity receiving unit: Indoor unit

34

OB405E.qxp 09.10.14 9:16 AM Page 34

Page 35: SERVICE MANUAL No. OB405 - Mitsubishi Ar … 18-24... · No. OB405 SERVICE MANUAL REVISED EDITION-E Models OUTDOOR UNIT ... RH277NHD RH247NRAT Electricity receiving unit: Indoor unit

35

OB405E.qxp 09.10.14 9:16 AM Page 35

Page 36: SERVICE MANUAL No. OB405 - Mitsubishi Ar … 18-24... · No. OB405 SERVICE MANUAL REVISED EDITION-E Models OUTDOOR UNIT ... RH277NHD RH247NRAT Electricity receiving unit: Indoor unit

HEAD OFFICE: TOKYO BLDG, 2-7-3, MARUNOUCHI, CHIYODAKU, TOKYO 100-8310, JAPAN

CC Copyright 2005 MITSUBISHI ELECTRIC ENGINEERING CO.,LTDDistributed in Oct. 2009. No.OB405 REVISED EDITION-E 5Distributed in May 2006. No.OB405 REVISED EDITION-D 106Distributed in Nov. 2005. No.OB405 REVISED EDITION-C 106Distributed in Jun. 2005. No.OB405 REVISED EDITION-B 106Distributed in May 2005. No.OB405 REVISED EDITION-A 106Reprinted in Apr. 2005. No.OB405 100Distributed in Mar. 2005. No.OB405 6Made in Japan