Service Facts © 2010 Trane NOTICE: Since the manufacturer has a policy of continuous product and product data improvement, it reserves the right to change design and specifications without notice. Product Specifications 1 MODEL TYPE RATINGS 2 1st Stage Input BTUH 1st Stage Capacity BTUH (ICS) 3 2nd Stage Input BTUH 2nd Stage Capacity BTUH (ICS) 3 Temp. rise (Min.-Max.) °F. BLOWER DRIVE Diameter - Width (In.) No. Used Speeds (No.) CFM vs. in. w.g. Motor HP R.P.M. Volts / Ph / Hz COMBUSTION FAN — Type Drive - No. Speeds Motor HP - RPM Volts / Ph / Hz FLA FILTER — Furnished? Type Recommended Hi Vel. (No.-Size-Thk.) VENT — Size (In.) HEAT EXCHANGER Type -Fired -Unfired Gauge (Fired) ORIFICES — Main Nat. Gas. Qty. — Drill Size L.P. Gas Qty. — Drill Size GAS VALVE PILOT SAFETY DEVICE Type BURNERS — Type Number POWER CONN. — V / Ph / Hz 4 Ampacity (In Amps) Max. Overcurrent Protection (Amps) PIPE CONN. SIZE (In.) DIMENSIONS Crated (In.) WEIGHT Shipping (Lbs.) / Net (Lbs.) Gas Furnace — Variable Speed — 2 Stage Heat Models: * - First letter may be “A” or “T” 1 Central Furnace heating designs are certified to ANSI Z21.47 / CSA 2.3. 2 For U.S. applications, above input ratings (BTUH) are up to 2,000 feet, derate 4% per 1,000 feet for elevations above 2,000 feet above sea level. For Canadian applications, above input ratings (BTUH) are up to 4,500 feet, derate 4% per 1,000 feet for elevations above 4,500 feet above sea level. 3 Based on U.S. government standard tests. 4 The above wiring specifications are in accordance with National Electrical Code; however, installations must comply with local codes. IMPORTANT — This document contains a wiring diagram and service information. This is customer property and is to remain with this unit. Please return to service information pack upon completion of work. DISCONNECT POWER BEFORE SERVICING WARNING *UD2B060A9V3VB *UD2B080A9V3VB *UD2C080A9V4VB *UD2C080B9V4VB *UD2B100A9V3VB *UD2C100A9V5VB *UD2C100B9V5VB *UD2D120A9V5VB *UD2D120B9V5VB *UD2D140A9V5VB *DD2B060A9V3VA *DD2B080A9V3VA *DD2C100A9V5VA *DD2D120A9V5VA *UD2B060A9V3VB Upflow / Horizontal 39,000 31,200 60,000 48,000 30 - 60 Direct 10 x 7 1 Variable See Airflow Table 1/2 Variable 115/1/60 Centrifugal Direct - 2 1/100 - 2543/1727 115/1/60 0.70/0.40 Yes High Velocity 1 - 17x25 - 1in. 4 Round Alum. Steel - Type 1 20 3 — 45 3 — 56 Redundant - Two Stage Hot Surface Ignition Multi-port In-shot 3 115/1/60 10.5 15 1/2 H x W x D 41-3/4 x 19-1/2 x 30-1/2 136 / 126 *UD2B080A9V3VB Upflow / Horizontal 52,000 41,600 80,000 64,000 30 - 60 Direct 10 x 7 1 Variable See Airflow Table 1/2 Variable 115/1/60 Centrifugal Direct - 2 1/100 - 2543/1727 115/1/60 0.70/0.40 Yes High Velocity 1 - 17x25 - 1in. 4 Round Alum. Steel - Type 1 20 4 — 45 4 — 56 Redundant - Two Stage Hot Surface Ignition Multi-port In-shot 4 115/1/60 10.5 15 1/2 H x W x D 41-3/4 x 19-1/2 x 30-1/2 142 / 132 *UD2C080A9V4VB Upflow / Horizontal 52,000 41,600 80,000 64,000 30 - 60 Direct 10 x 10 1 Variable See Airflow Table 3/4 Variable 115/1/60 Centrifugal Direct - 2 1/100 - 2543/1727 115/1/60 0.70/0.40 Yes High Velocity 1 - 20x25 - 1in. 4 Round Alum. Steel - Type 1 20 4 — 45 4 — 56 Redundant - Two Stage Hot Surface Ignition Multi-port In-shot 4 115/1/60 12.9 20 1/2 H x W x D 41-3/4 x 23 x 30-1/2 166 / 155 UD2-9V-SF-1C X340989P17

Service Facts UD2-9V-SF-1C Gas Furnace — Variable Speed ... · UD2-9V-SF-1C X340989P17. 2 X340989P17 Service Facts Product Specifications 1 MODEL TYPE RATINGS 2 1st Stage Input

  • Upload
    others

  • View
    26

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Service Facts UD2-9V-SF-1C Gas Furnace — Variable Speed ... · UD2-9V-SF-1C X340989P17. 2 X340989P17 Service Facts Product Specifications 1 MODEL TYPE RATINGS 2 1st Stage Input

Service Facts

© 2010 Trane

NOTICE: Since the manufacturer has a policy of continuous product and product data improvement, it reserves the right to change design and specifications without notice.

Product Specifications 1MODELTYPERATINGS 21st Stage Input BTUH 1st Stage Capacity BTUH (ICS) 32nd Stage Input BTUH 2nd Stage Capacity BTUH (ICS) 3Temp. rise (Min.-Max.) °F.BLOWER DRIVEDiameter - Width (In.)No. UsedSpeeds (No.)CFM vs. in. w.g.Motor HPR.P.M.Volts / Ph / HzCOMBUSTION FAN — TypeDrive - No. SpeedsMotor HP - RPMVolts / Ph / HzFLAFILTER — Furnished?Type RecommendedHi Vel. (No.-Size-Thk.)VENT — Size (In.)HEAT EXCHANGERType -Fired -UnfiredGauge (Fired)ORIFICES — MainNat. Gas. Qty. — Drill SizeL.P. Gas Qty. — Drill SizeGAS VALVEPILOT SAFETY DEVICETypeBURNERS — TypeNumberPOWER CONN. — V / Ph / Hz 4Ampacity (In Amps)Max. Overcurrent Protection (Amps)PIPE CONN. SIZE (In.)DIMENSIONSCrated (In.)WEIGHTShipping (Lbs.) / Net (Lbs.)

Gas Furnace — Variable Speed — 2 Stage HeatModels: * - First letter may be “A” or “T”

1 Central Furnace heating designs are certified to ANSI Z21.47 / CSA 2.3.2 For U.S. applications, above input ratings (BTUH) are up to 2,000 feet, derate 4% per 1,000 feet for elevations above 2,000 feet above sea level. For Canadian applications, above input ratings (BTUH) are up to 4,500 feet, derate 4% per 1,000 feet for elevations above 4,500 feet above sea level.3 Based on U.S. government standard tests.4 The above wiring specifications are in accordance with National Electrical Code; however, installations must comply with local codes.

IMPORTANT — This document contains a wiring diagram and service information. This is customer property and is to remain with this unit. Please return to service information pack upon completion of work.

DISCONNECT POWER BEFORE SERVICINGWARNING

*UD2B060A9V3VB*UD2B080A9V3VB*UD2C080A9V4VB*UD2C080B9V4VB*UD2B100A9V3VB

*UD2C100A9V5VB*UD2C100B9V5VB*UD2D120A9V5VB*UD2D120B9V5VB*UD2D140A9V5VB

*DD2B060A9V3VA*DD2B080A9V3VA*DD2C100A9V5VA*DD2D120A9V5VA

*UD2B060A9V3VBUpflow / Horizontal

39,00031,20060,00048,00030 - 60Direct10 x 7

1Variable

See Airflow Table1/2

Variable115/1/60

CentrifugalDirect - 2

1/100 - 2543/1727115/1/600.70/0.40

YesHigh Velocity

1 - 17x25 - 1in.4 Round

Alum. Steel - Type 1

20

3 — 453 — 56

Redundant - Two Stage

Hot Surface IgnitionMulti-port In-shot

3115/1/60

10.5151/2

H x W x D41-3/4 x 19-1/2 x 30-1/2

136 / 126

*UD2B080A9V3VBUpflow / Horizontal

52,00041,60080,00064,00030 - 60Direct10 x 7

1Variable

See Airflow Table1/2

Variable115/1/60

CentrifugalDirect - 2

1/100 - 2543/1727115/1/600.70/0.40

YesHigh Velocity

1 - 17x25 - 1in.4 Round

Alum. Steel - Type 1

20

4 — 454 — 56

Redundant - Two Stage

Hot Surface IgnitionMulti-port In-shot

4115/1/60

10.5151/2

H x W x D41-3/4 x 19-1/2 x 30-1/2

142 / 132

*UD2C080A9V4VBUpflow / Horizontal

52,00041,60080,00064,00030 - 60Direct

10 x 101

VariableSee Airflow Table

3/4Variable115/1/60

CentrifugalDirect - 2

1/100 - 2543/1727115/1/600.70/0.40

YesHigh Velocity

1 - 20x25 - 1in.4 Round

Alum. Steel - Type 1

20

4 — 454 — 56

Redundant - Two Stage

Hot Surface IgnitionMulti-port In-shot

4115/1/60

12.9201/2

H x W x D41-3/4 x 23 x 30-1/2

166 / 155

UD2-9V-SF-1C

X340989P17

Page 2: Service Facts UD2-9V-SF-1C Gas Furnace — Variable Speed ... · UD2-9V-SF-1C X340989P17. 2 X340989P17 Service Facts Product Specifications 1 MODEL TYPE RATINGS 2 1st Stage Input

2 X340989P17

Service FactsProduct Specifications 1

MODEL

TYPE

RATINGS 21st Stage Input BTUH 1st Stage Capacity BTUH (ICS) 32nd Stage Input BTUH 2nd Stage Capacity BTUH (ICS) 3Temp. rise (Min.-Max.) °F.

BLOWER DRIVEDiameter - Width (In.)No. UsedSpeeds (No.)CFM vs. in. w.g.Motor HPR.P.M.Volts / Ph / Hz

COMBUSTION FAN — TypeDrive - No. SpeedsMotor HP - RPMVolts / Ph / HzFLA

FILTER — Furnished?Type RecommendedHi Vel. (No.-Size-Thk.)

VENT — Size (In.)

HEAT EXCHANGERType -Fired -UnfiredGauge (Fired)

ORIFICES — MainNat. Gas. Qty. — Drill SizeL.P. Gas Qty. — Drill Size

GAS VALVE

PILOT SAFETY DEVICEType

BURNERS — TypeNumber

POWER CONN. — V / Ph / Hz 4Ampacity (In Amps)Max. Overcurrent Protection (Amps)

PIPE CONN. SIZE (In.)

DIMENSIONSCrated (In.)

WEIGHTShipping (Lbs.) / Net (Lbs.)

*UD2C100A9V5VB

Upflow / Horizontal

65,00052,000100,00079,00035 - 65

Direct10 x 10

1Variable

See Airflow Table1

Variable115/1/60

CentrifugalDirect - 2

1/75 - 2708/1868115/1/600.87/0.49

YesHigh Velocity

1 - 20x25 - 1in.

4 Round

Alum. Steel - Type 1

20

5 — 455 — 56

Redundant - Two Stage

Hot Surface Ignition

Multi-port In-shot5

115/1/6014.920

1/2

H x W x D41-3/4 x 23 x 30-1/2

166 / 155

*UD2B100A9V3VB

Upflow / Horizontal

65,00052,000100,00080,00040 - 70

Direct10 x 7

1Variable

See Airflow Table1/2

Variable115/1/60

CentrifugalDirect - 2

1/75 - 2708/1868115/1/600.87/0.49

YesHigh Velocity

1 - 17x25 - 1in.

4 Round

Alum. Steel - Type 1

20

5 — 455 — 56

Redundant - Two Stage

Hot Surface Ignition

Multi-port In-shot5

115/1/6010.815

1/2

H x W x D41-3/4 x 19-1/2 x 30-1/2

142 / 1321 Central Furnace heating designs are certified to ANSI Z21.47 / CSA 2.3.2 For U.S. applications, above input ratings (BTUH) are up to 2,000 feet, derate 4% per 1,000 feet for elevations above 2,000 feet above sea level. For Canadian applications, above input ratings (BTUH) are up to 4,500 feet, derate 4% per 1,000 feet for elevations above 4,500 feet above sea level.3 Based on U.S. government standard tests.4 The above wiring specifications are in accordance with National Electrical Code; however, installations must comply with local codes.

*UD2C080B9V4VB

Upflow / Horizontal

52,00041,60080,00064,00030 - 60

Direct10 x 10

1Variable

See Airflow Table3/4

Variable115/1/60

CentrifugalDirect - 2

1/100 - 2543/1727115/1/600.70/0.40

YesHigh Velocity

1 - 20x25 - 1in.

4 Round

Alum. Steel - Type 1

20

4 — 454 — 56

Redundant - Two Stage

Hot Surface Ignition

Multi-port In-shot4

115/1/6012.920

1/2

H x W x D41-3/4 x 23 x 30-1/2

166 / 155

Page 3: Service Facts UD2-9V-SF-1C Gas Furnace — Variable Speed ... · UD2-9V-SF-1C X340989P17. 2 X340989P17 Service Facts Product Specifications 1 MODEL TYPE RATINGS 2 1st Stage Input

X340989P17 3

Service FactsProduct Specifications 1

MODEL

TYPE

RATINGS 21st Stage Input BTUH 1st Stage Capacity BTUH (ICS) 32nd Stage Input BTUH 2nd Stage Capacity BTUH (ICS) 3Temp. rise (Min.-Max.) °F.

BLOWER DRIVEDiameter - Width (In.)No. UsedSpeeds (No.)CFM vs. in. w.g.Motor HPR.P.M.Volts / Ph / Hz

COMBUSTION FAN — TypeDrive - No. SpeedsMotor HP - RPMVolts / Ph / HzFLA

FILTER — Furnished?Type RecommendedHi Vel. (No.-Size-Thk.)

VENT — Size (In.)

HEAT EXCHANGERType -Fired -UnfiredGauge (Fired)

ORIFICES — MainNat. Gas. Qty. — Drill SizeL.P. Gas Qty. — Drill Size

GAS VALVE

PILOT SAFETY DEVICEType

BURNERS — TypeNumber

POWER CONN. — V / Ph / Hz 4Ampacity (In Amps)Max. Overcurrent Protection (Amps)

PIPE CONN. SIZE (In.)

DIMENSIONSCrated (In.)

WEIGHTShipping (Lbs.) / Net (Lbs.)

*UD2C100B9V5VB

Upflow / Horizontal

65,00052,000100,00079,00035 - 65

Direct10 x 10

1Variable

See Airflow Table1

Variable115/1/60

CentrifugalDirect - 2

1/75 - 2708/1868115/1/600.87/0.49

YesHigh Velocity

1 - 20x25 - 1in.

4 Round

Alum. Steel - Type 1

20

5 — 455 — 56

Redundant - Two Stage

Hot Surface Ignition

Multi-port In-shot5

115/1/6014.920

1/2

H x W x D41-3/4 x 23 x 30-1/2

166 / 155

*UD2D120A9V5VB

Upflow / Horizontal

78,00062,400120,00097,00035 - 65

Direct10 x 10

1Variable

See Airflow Table1

Variable115/1/60

CentrifugalDirect - 2

1/60 - 3090/2225115/1/601.14/0.51

YesHigh Velocity

1 - 24x25 - 1in.

4 Round

Alum. Steel - Type 1

20

6 — 456 — 56

Redundant - Two Stage

Hot Surface Ignition

Multi-port In-shot6

115/1/6015.320

1/2

H x W x D41-3/4 x 26-1/2 x 30-1/2

193 / 181

*UD2D120B9V5VB

Upflow / Horizontal

78,00062,400120,00097,00035 - 65

Direct10 x 10

1Variable

See Airflow Table1

Variable115/1/60

CentrifugalDirect - 2

1/60 - 3090/2225115/1/601.14/0.51

YesHigh Velocity

1 - 24x25 - 1in.

4 Round

Alum. Steel - Type 1

20

6 — 456 — 56

Redundant - Two Stage

Hot Surface Ignition

Multi-port In-shot6

115/1/6015.320

1/2

H x W x D41-3/4 x 26-1/2 x 30-1/2

193 / 181

*UD2D140A9V5VB

Upflow / Horizontal

91,00072,800140,000111,00040 - 70

Direct10 x 10

1Variable

See Airflow Table1

Variable115/1/60

CentrifugalDirect - 2

1/60 - 3100/2350115/1/601.16/0.54

YesHigh Velocity

1 - 24x25 - 1in.

4 Round

Alum. Steel - Type 1

20

7 — 457 — 56

Redundant - Two Stage

Hot Surface Ignition

Multi-port In-shot7

115/1/6015.320

1/2

H x W x D41-3/4 x 26-1/2 x 30-1/2

197 / 185

Page 4: Service Facts UD2-9V-SF-1C Gas Furnace — Variable Speed ... · UD2-9V-SF-1C X340989P17. 2 X340989P17 Service Facts Product Specifications 1 MODEL TYPE RATINGS 2 1st Stage Input

4 X340989P17

Service FactsProduct Specifications 1

MODEL

TYPE

RATINGS 21st Stage Input BTUH 1st Stage Capacity BTUH (ICS) 32nd Stage Input BTUH 2nd Stage Capacity BTUH (ICS) 3Temp. rise (Min.-Max.) °F.

BLOWER DRIVEDiameter - Width (In.)No. UsedSpeeds (No.)CFM vs. in. w.g.Motor HPR.P.M.Volts / Ph / Hz

COMBUSTION FAN — TypeDrive - No. SpeedsMotor HP - RPMVolts / Ph / HzFLA

FILTER — Furnished?Type RecommendedHi Vel. (No.-Size-Thk.)

VENT — Size (In.)

HEAT EXCHANGERType -Fired -UnfiredGauge (Fired)

ORIFICES — MainNat. Gas. Qty. — Drill SizeL.P. Gas Qty. — Drill Size

GAS VALVE

PILOT SAFETY DEVICEType

BURNERS — TypeNumber

POWER CONN. — V / Ph / Hz 4Ampacity (In Amps)Max. Overcurrent Protection (Amps)

PIPE CONN. SIZE (In.)

DIMENSIONSCrated (In.)

WEIGHTShipping (Lbs.) / Net (Lbs.)

*DD2B060A9V3VA

Downflow / Horizontal

39,00031,20060,00048,00035 - 65

Direct10 x 7

1Variable

See Airflow Table1/2

Variable115/1/60

CentrifugalDirect - 2

1/100 - 2543/1727115/1/600.70/0.40

YesHigh Velocity

2 - 14x20 - 1in.

4 Round

Alum. Steel - Type 1

20

3 — 453 — 56

Redundant - Two Stage

Hot Surface Ignition

Multi-port In-shot3

115/1/6010.515

1/2

H x W x D41-3/4 x 19-1/2 x 30-1/2

140 / 129

*DD2B080A9V3VA

Downflow / Horizontal

52,00041,60080,00063,00035 - 65

Direct10 x 7

1Variable

See Airflow Table1/2

Variable115/1/60

CentrifugalDirect - 2

1/100 - 2543/1727115/1/600.70/0.40

YesHigh Velocity

2 - 14x20 - 1in.

4 Round

Alum. Steel - Type 1

20

4 — 454 — 56

Redundant - Two Stage

Hot Surface Ignition

Multi-port In-shot4

115/1/6010.515

1/2

H x W x D41-3/4 x 19-1/2 x 30-1/2

146 / 135

*DD2C100A9V5VA

Downflow / Horizontal

65,00052,000100,00081,00035 - 65

Direct11 x 10

1Variable

See Airflow Table1

Variable115/1/60

CentrifugalDirect - 2

1/75 - 2708/1868115/1/600.87/0.49

YesHigh Velocity

2 - 16x20 - 1in.

4 Round

Alum. Steel - Type 1

20

5 — 455 — 56

Redundant - Two Stage

Hot Surface Ignition

Multi-port In-shot5

115/1/6014.920

1/2

H x W x D41-3/4 x 23 x 30-1/2

166 / 155

1 Central Furnace heating designs are certified to ANSI Z21.47 / CSA 2.3.2 For U.S. applications, above input ratings (BTUH) are up to 2,000 feet, derate 4% per 1,000 feet for elevations above 2,000 feet above sea level. For Canadian applications, above input ratings (BTUH) are up to 4,500 feet, derate 4% per 1,000 feet for elevations above 4,500 feet above sea level.3 Based on U.S. government standard tests.4 The above wiring specifications are in accordance with National Electrical Code; however, installations must comply with local codes.

DD2D120A9V5VA

Downflow / Horizontal

78,00062,400120,00095,00035 - 65

Direct11 x 10

1Variable

See Airflow Table1

Variable115/1/60

CentrifugalDirect - 2

1/60 - 3090/2225115/1/601.14/0.51

YesHigh Velocity

2 - 16x20 - 1in.

4 Round

Alum. Steel - Type 1

20

6 — 456 — 56

Redundant - Two Stage

Hot Surface Ignition

Multi-port In-shot6

115/1/6015.320

1/2

H x W x D41-3/4 x 26-1/2 x 30-1/2

197 / 185

Page 5: Service Facts UD2-9V-SF-1C Gas Furnace — Variable Speed ... · UD2-9V-SF-1C X340989P17. 2 X340989P17 Service Facts Product Specifications 1 MODEL TYPE RATINGS 2 1st Stage Input

X340989P17 5

Service FactsSafety Section

▲ WARNING!The cabinet must have an uninterrupted or unbroken ground according to National Electrical Code, ANSI/NFPA 70 - “latest edition” and Canadian Electrical Code, CSA C22.1 or local codes to minimize personal injury if an electrical fault should occur. A failure to follow this warn-ing could result in an electrical shock, fire, injury, or death.

CARBON MONOXIDE POISONING HAZARD

Failure to follow the steps outlined below for each appliance connected to the venting system being placed into operation could result in carbon monoxide poisoning or death.

The following steps shall be followed for each appliance connected to the venting system being placed into operation, while all other appliances connected to the venting system are not in operation:

1. Seal any unused openings in the venting system.

2. Inspect the venting system for proper size and horizontal pitch, as required in the National Fuel Gas Code, ANSI Z223.1/NFPA 54 or the CAN/CGA B149 Installation Codes and these instructions. Determine that there is no blockage or restriction, leakage, corrosion and other deficiencies which could cause an unsafe condition.

3. As far as practical, close all building doors and windows and all doors between the space in which the appliance(s) connected to the venting system are located and other deficiencies which could cause an unsafe condition.

4. Close fireplace dampers.

5. Turn on clothes dryers and any appliance not connected to the venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they are operating at maximum speed. Do not operate a summer exhaust fan.

6. Follow the lighting instructions. Place the appliance being inspected into operation. Adjust the thermostat so appliance is operating continuously.

7. If improper venting is observed during any of the above tests, the venting system must be corrected in accordance with the National Fuel Gas Code, ANSI Z221.1/NFPA 54 and/or CAN/CGA B149 Installation Codes.

8. After it has been determined that each appliance connected to the venting system properly vents where tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other gas-fired burning appliance to their previous conditions of use.

▲ WARNING! ▲ WARNING!CARBON MONOXIDE POISONING HAZARD

Failure to follow the installation instructions for the vent-ing system being placed into operation could result in carbon monoxide poisoning or death.

▲ WARNING!FIRE OR EXPLOSION HAZARD

Failure to follow the safety warnings exactly could result in serious injury, death or property damage.

Never test for gas leaks with an open flame. Use a com-mercially available soap solution made specifically for the detection of leaks to check all connections. A fire or explosion may result causing property damage, personal injury, or loss of life.

▲ WARNING!FIRE OR EXPLOSION HAZARD

Failure to follow the safety warnings exactly could result in serious injury, death or property damage.

Improper servicing could result in dangerous operation, serious injury, death, or property damage.

BODILY INJURY CAN RESULT FROM HIGH VOLTAGE ELECTRICAL COMPONENTS, FAST MOVING FANS, AND COMBUSTIBLE GAS. FOR PROTECTION FROM THESE INHERENT HAZARDS DURING INSTALLATION AND SERVICING, THE ELECTRICAL SUPPLY MUST BE DISCONNECTED AND THE MAIN GAS VALVE MUST BE TURNED OFF. IF OPERATING CHECKS MUST BE PERFORMED WITH THE UNIT OPERATING, IT IS THE TECHNICIANS RESPONSIBILITY TO RECOGNIZE THESE HAZARDS AND PROCEED SAFELY.

▲ WARNING!

▲ CAUTION!THE INTEGRATED FURNACE CONTROL IS POLARITY SENSITIVE. THE HOT LEG OF THE 115 VAC POWER MUST BE CONNECTED TO THE BLACK FIELD LEAD.

Page 6: Service Facts UD2-9V-SF-1C Gas Furnace — Variable Speed ... · UD2-9V-SF-1C X340989P17. 2 X340989P17 Service Facts Product Specifications 1 MODEL TYPE RATINGS 2 1st Stage Input

6 X340989P17

Service FactsSequence Of OperationThermostat call for heat (2-stage thermostat)Call for 1st stage only: R and W1 thermostat contacts close signaling the control module to run its self-check routine. After the control mod-ule has verified that the 1st stage pressure switch contacts are open and the limit switch(es) contacts are closed, the draft blower will be energized.

As the induced draft blower comes up to speed, the pres-sure switch contacts will close and the ignitor warm up period will begin. The igniter will heat for approx. 17 seconds, then the gas valve is energized in 1st stage to permit gas flow to the burners. The flame sensor confirms that ignition has been achieved within the 4 second ignition trial period.

As the flame sensor confirms that ignition has been achieved, the delay to fan ON period begins timing and after approx. 45 seconds the indoor blower motor will be energized at low speed and will continue to run during the heating cycle.

Call for 2nd stage after 1st stage: R and W2 thermostat contacts close signaling a call for 2nd stage heat. After a 30 second delay, the induced draft blower will be energized on high speed and the 2nd stage pressure switch contacts will close allowing the gas valve to be energized in 2nd stage and the indoor blower motor in high speed.

2nd stage satisfied, 1st stage still called: R and W2 thermostat contacts open signaling that 2nd stage heating requirements are satisfied. The induced draft blower is reduced to low speed allowing the 2nd stage pressure switch contacts to open and the gas valve is reduced to 1st stage. After approx. 30 seconds the indoor blower motor is reduced to low speed.

1st stage satisfied: R and W1 thermostat contacts open signaling that 1st stage heating requirements are satisfied. The gas valve will close and the induced draft blower will be de-energized. The indoor blower motor will continue to run for the heating fan off period (Field selectable at 90, 120, 150 or 180 seconds), then will be de-energized by the control module.

Thermostat call for heat (1-stage Thermostat)R and W thermostats close signaling a call for heat. 1st stage sequence of operation remains the same as above. 2nd stage delay will be reflective dip switch S7-1 and S7-2.

Reference the back of service facts for delay options.

Thermostat satisfied (1-stage Thermostat): Contacts open signaling the control module to close the gas valve and de-energize the induced draft blower. The indoor blower motor will continue to operate at high heat speed for approx. 30 seconds after the flames are extinguished and then is switched to low heat speed for the remaining FAN-OFF period.

Should overheating occur, or the gas supply fail to shut off, shut off the gas valve to the unit before shutting off the electrical supply. Failure to follow this warning could result in property damage, personal injury, or death.

▲ WARNING!

Indoor Blower TimingHeating: The ECM Fan Control controls the variable speed indoor blower. The blower “on” time is fixed at 45 seconds after ignition. The FAN-OFF period is field selectable by dip switches S7-3 and S7-4 on the Integrated Furnace Con-trol at 90, 120, 150, or 180 seconds. The factory setting is 90 seconds (See unit wiring diagram).

Cooling: The fan delay-off period is set by dip switches on the ECM Fan Control board connected to the Integrated Furnace Control. The options for cooling delay off is field selectable by dip switches S4-1 and S4-2.

The following table and graph explain the delay-off set-tings:

COOLING OFF - DELAY OPTIONS

SWITCH SETTINGS SELECTION NOMINALAIRFLOW

S4-1 - OFF S4-2 - OFF NONE SAME

S4-1 - ON S4-2 - OFF 1.5 MINUTES 100% *

S4-1 - OFF S4-2 - ON 3 MINUTES 50%

S4-1 - ON S4-2 - ON ** 50 - 100%

* - This setting is equivalent to BAY24X045 relay benefit

** - This selection provides ENHANCED MODE, which is a ramping up and ramping down of the blower speed to provide improved comfort, quietness, and potential energy savings. See Wiring Diagram notes on the unit or in the Ser-vice Facts for complete wiring setup for ENHANCED MODE. The graph which follows, shows the ramping process.

BODILY INJURY CAN RESULT FROM HIGH VOLTAGE ELECTRICAL COMPONENTS, FAST MOVING FANS, AND COMBUSTIBLE GAS. FOR PROTECTION FROM THESE INHERENT HAZARDS DURING INSTALLATION AND SERVICING, THE ELECTRICAL SUPPLY MUST BE DISCONNECTED AND THE MAIN GAS VALVE MUST BE TURNED OFF. IF OPERATING CHECKS MUST BE PERFORMED WITH THE UNIT OPERATING, IT IS THE TECHNICIANS RESPONSIBILITY TO RECOGNIZE THESE HAZARDS AND PROCEED SAFELY.

▲ WARNING!

▲ CAUTION!THE INTEGRATED FURNACE CONTROL IS POLARITY SENSITIVE. THE HOT LEG OF THE 115 VAC POWER MUST BE CONNECTED TO THE BLACK FIELD LEAD.

OFF

50%50%

80%

Dehumidify

EfficiencyFast Coil Cooling

1

minute

3

minutes

7.5

minutes

100% if necessary

OFF

Page 7: Service Facts UD2-9V-SF-1C Gas Furnace — Variable Speed ... · UD2-9V-SF-1C X340989P17. 2 X340989P17 Service Facts Product Specifications 1 MODEL TYPE RATINGS 2 1st Stage Input

X340989P17 7

Service FactsPeriodic Servicing Requirements

▲ WARNING!Disconnect power to the unit before removing the blower door. Failure to follow this warning could result in person-al injury from moving parts.

1. GENERAL INSPECTION – Examine the furnace installation annually for the following items:

a. All flue product carrying areas external to the fur-nace (i.e. chimney, vent connector) are clear and free of obstruction. A vent screen in the end of the vent (flue) pipe must be inspected for blockage annually.

b. The vent connector is in place, slopes upward and is physically sound without holes or excessive corro-sion.

c. The return air duct connection(s) is physically sound, is sealed to the furnace and terminates out-side the space containing the furnace.

d. The physical support of the furnace should be sound without sagging, cracks, gaps, etc., around the base so as to provide a seal between the support and the base.

e. There are no obvious signs of deterioration of the furnace.

2. FILTERS – Filters should be cleaned or replaced (with high velocity filters only), monthly and more frequently during high use times of the year such as midsummer or midwinter.

3. BLOWERS – The blower size and speed determine the air volume delivered by the furnace. The blower mo-tor bearings are factory lubricated and under normal operating conditions do not require servicing. If motor lubrication is required it should only be done by a qualified servicer. Annual cleaning of the blower wheel and housing is recommended for maximum air output, and this must be performed only by a qualified servicer or service agency.

4. IGNITER – This unit has a special hot surface direct ignition device that automatically lights the burners. Please note that it is very fragile and should be han-dled with care.

▲ CAUTION!Do not touch igniter. It is extremely hot.

5. BURNER – Gas burners do not normally require scheduled servicing, however, accumulation of foreign material may cause a yellowing flame or delayed igni-tion. Either condition indicates that a service call is required. For best operation, burners must be cleaned annually using brushes and vacuum cleaner.

Turn off gas and electric power supply. To clean burn-ers, remove burner box cover (6 to 8 screws) and top burner bracket. Lift burners from orifices.

NOTE: Be careful not to break igniter when removing burn-ers.

Clean burners with brush and/or vacuum cleaner. Re-assemble parts by reversal of the above procedure. The burner box must be resealed when replacing box cover.

NOTE: On LP (propane) units, some light yellow tipping of the outer mantle is normal. Inner mantle should be bright blue. Natural gas units should not have any yellow tipped flames. This condition indicates that a service call is required. For best operation, burners must be cleaned an-nually using brushes and vacuum cleaner.

NOTE: On LP (propane) units, due to variations in BTU content and altitude, servicing may be required at shorter inter-vals.

▲ WARNING!CARBON MONOXIDE POISONING HAZARD

Failure to follow the service and/or periodic maintenance instructions for the furnace and venting system, could result in carbon monoxide poisoning or death.

6. HEAT EXCHANGER/FLUE PIPE – These items must be inspected for signs of corrosion, and/or deteriora-tion at the beginning of each heating season by a quali-fied service technician and cleaned annually for best operation. To clean flue gas passages, follow recommen-dations below:

a. Turn off gas and electric power supply.

b. Inspect flue pipe exterior for cracks, leaks, holes or leaky joints. Some discoloration of PVC pipe is nor-mal.

c. Remove burner compartment door from furnace.

d. Inspect around insulation covering flue collector box. Inspect induced draft blower connections from recuperative cell and to the flue pipe connection.

e. Remove burners. (See 4.)

f. Use a mirror and flashlight to inspect interior of heat exchanger, be careful not to damage the igniter, flame sensor or other components.

g. If any corrosion is present, contact a service agency. Heat exchanger should be cleaned by a qualified service technician.

h. After inspection is complete replace burner box cover, burners, and furnace door.

i. Restore gas supply. Check for leaks using a soap solution. Restore electrical supply. Check unit for normal operation.

7. COOLING COIL CONDENSATE DRAIN – If a cooling coil is installed with the furnace, condensate drains should be checked and cleaned periodically to assure that condensate can drain freely from coil to drain. If condensate cannot drain freely water damage could oc-cur. (See Condensate Drain in Installer’s Guide)

▲ CAUTION!Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation.

Verify proper operation after servicing.

▲ WARNING!NEVER USE AN OPEN FLAME TO TEST FOR GAS LEAKS. AN EXPLOSION COULD OCCUR, CAUSING INJURY OR DEATH.

Page 8: Service Facts UD2-9V-SF-1C Gas Furnace — Variable Speed ... · UD2-9V-SF-1C X340989P17. 2 X340989P17 Service Facts Product Specifications 1 MODEL TYPE RATINGS 2 1st Stage Input

8 X340989P17

Service FactsWiring Diagram

(continued on next page)

Electrical Data

From Dwg. D344249P02

Page 9: Service Facts UD2-9V-SF-1C Gas Furnace — Variable Speed ... · UD2-9V-SF-1C X340989P17. 2 X340989P17 Service Facts Product Specifications 1 MODEL TYPE RATINGS 2 1st Stage Input

X340989P17 9

Service FactsSchematic Diagram

From Dwg. D344249P02

Page 10: Service Facts UD2-9V-SF-1C Gas Furnace — Variable Speed ... · UD2-9V-SF-1C X340989P17. 2 X340989P17 Service Facts Product Specifications 1 MODEL TYPE RATINGS 2 1st Stage Input

10 X340989P17

Service Facts

(continued on next page)

Wiring Diagram

From Dwg. D344248P02

Page 11: Service Facts UD2-9V-SF-1C Gas Furnace — Variable Speed ... · UD2-9V-SF-1C X340989P17. 2 X340989P17 Service Facts Product Specifications 1 MODEL TYPE RATINGS 2 1st Stage Input

X340989P17 11

Service FactsSchematic Diagram

From Dwg. D344248P02

Page 12: Service Facts UD2-9V-SF-1C Gas Furnace — Variable Speed ... · UD2-9V-SF-1C X340989P17. 2 X340989P17 Service Facts Product Specifications 1 MODEL TYPE RATINGS 2 1st Stage Input

12 X340989P17

Service FactsPerformance Data

*UD2B060A9V3VB FURNACE COOLING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER

OUTDOOR UNIT SIZE

(TONS)

AIRFLOWSETTING

DIP SWITCH SETTING EXTERNAL STATIC PRESSURE

S3-1 S3-2 S3-3 S3-4 0.1 0.3 0.5 0.7 0.9

1.5

LOW(350 CFM/ TON) ON ON OFF ON CFM

WATTS49950

53780

520110

520145

500175

NORMAL(400 CFM/ TON) ON ON OFF OFF CFM

WATTS60560

61080

610120

597155

593180

HIGH(450 CFM/ TON) ON ON ON OFF CFM

WATTS64975

681110

665145

665180

672220

2.0

LOW(350 CFM/ TON) OFF ON OFF ON CFM

WATTS68080

722125

680150

696190

696225

NORMAL(400 CFM/ TON) OFF ON OFF OFF CFM

WATTS798105

804145

809170

823235

818280

HIGH(450 CFM/ TON) OFF ON ON OFF CFM

WATTS884145

896180

924240

931280

931330

2.5

LOW(350 CFM/ TON) ON OFF OFF ON CFM

WATTS858125

863175

882220

894275

895320

NORMAL(400 CFM/ TON) ON OFF OFF OFF CFM

WATTS984170

1017225

1038295

1017330

1017375

HIGH(450 CFM/ TON) ON OFF ON OFF CFM

WATTS1125245

1138315

1150370

1161435

1161475

3.0 **

LOW(350 CFM/ TON) OFF OFF OFF ON CFM

WATTS1035205

1056265

1076330

1076370

1076430

NORMAL **(400 CFM/ TON) OFF OFF OFF OFF CFM

WATTS1208300

1247360

1268440

1278485

1200490

HIGH(450 CFM/ TON) OFF OFF ON OFF CFM

WATTS1380440

1410500

1402550

1350550

1235525

NOTES:1. *FIRST LETTER MAY BE "A" OR "T" 2. **FACTORY SETTING.3. CONTINUOUS FAN SETTING: HEATING OR COOLING AIRFLOW IS APPROXIMATELY 50% OF SELECTED COOLING VALUE.4. LOW 350 CFM/TON IS RECOMMENDED FOR VARIABLE SPEED APPLICATION FOR COMFORT & HUMID CLIMATE SETTING: NORMAL IS 400 CFM/TON: HIGH 450 CFM/TON IS FOR DRY CLIMATE SETTING.

*UD2B060A9V3VB FURNACE HEATING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER

AIRFLOWSETTING

DIP SWITCH SETTING EXTERNAL STATIC PRESSURE

S4-3 S4-4 0.1 0.3 0.5 0.7 0.9

HEATING1ST

STAGE

LOW ON ONCFM

TEMP. RISEWATTS

5894965

6044895

61947125

60448160

60748200

MEDIUM ** ON OFFCFM

TEMP. RISEWATTS

6634475

69442120

68442145

68142185

68642220

HIGH OFF OFFCFM

TEMP. RISEWATTS

77537105

78137145

77637180

80536230

81136270

HEATING2ND

STAGE

LOW ON ONCFM

TEMP. RISEWATTS

81355110

81854150

81854185

83753240

84253280

MEDIUM ** ON OFFCFM

TEMP. RISEWATTS

90749140

91948200

94247240

95846300

95946330

HIGH OFF OFFCFM

TEMP. RISEWATTS

103843190

106642260

108641325

108941365

107941415

Page 13: Service Facts UD2-9V-SF-1C Gas Furnace — Variable Speed ... · UD2-9V-SF-1C X340989P17. 2 X340989P17 Service Facts Product Specifications 1 MODEL TYPE RATINGS 2 1st Stage Input

X340989P17 13

Service Facts

*UD2B080A9V3VB FURNACE COOLING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER

OUTDOORUNIT SIZE

(TONS)

AIRFLOWSETTING

DIP SWITCH SETTING EXTERNAL STATIC PRESSURE

S3-1 S3-2 S3-3 S3-4 0.1 0.3 0.5 0.7 0.9

2.5

LOW(350 CFM/TON) OFF ON OFF ON CFM

WATTS880120

875155

860190

845225

840245

NORMAL (400 CFM/TON) OFF ON OFF OFF CFM

WATTS1020170

1000205

990240

980280

960320

HIGH(450 CFM/TON) OFF ON ON OFF CFM

WATTS1110210

110260

1110320

1100350

1100385

3.0

LOW(350 CFM/TON) ON OFF OFF ON CFM

WATTS1040190

1010220

1000260

1000310

990340

NORMAL (400 CFM/TON) ON OFF OFF OFF CFM

WATTS1200250

1200320

1190370

1190415

1175450

HIGH(450 CFM/TON) ON OFF ON OFF CFM

WATTS1340355

1340425

1330475

1320530

1300570

3.5 **

LOW(350 CFM/TON) OFF OFF OFF ON CFM

WATTS1215265

1210330

1210375

1200430

1185465

NORMAL **(400 CFM/TON) OFF OFF OFF OFF CFM

WATTS1430415

1415457

1410520

1385575

1330580

HIGH(450 CFM/TON) OFF OFF ON OFF CFM

WATTS1430415

1415475

1410520

1385575

1330580

NOTES:1. * First Letter may be "A" or "T"2. ** Factory setting3. Continuous Fan Setting: Heating or Cooling airflow is approximately 50% of selected Cooling value.4. LOW 350 cfm/ton is recommended for Variable Speed application for COMFORT & HUMID CLIMATE setting; NORMAL is 400 cfm/ton; HIGH 450 cfm/ton is for DRY CLIMATE setting

*UD2B080A9V3VB FURNACE HEATING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER

AIRFLOWSETTING

DIP SWITCH SETTING EXTERNAL STATIC PRESSURE

S4-3 S4-4 0.1 0.3 0.5 0.7 0.9

HEATING1ST

STAGE

LOW ON ONCFM

TEMP. RISEWATTS

80048100

79049135

76550155

75052200

73053230

MEDIUM ** ON OFFCFM

TEMP. RISEWATTS

91043130

89044170

87544210

86045240

82047280

HIGH OFF OFFCFM

TEMP. RISEWATTS

106037188

102038220

101039265

101039310

100039350

HEATING2ND

STAGE

LOW ON ONCFM

TEMP. RISEWATTS

111054210

109055260

109055310

108055350

106556400

MEDIUM ** ON OFFCFM

TEMP. RISEWATTS

124548300

124048355

124048410

123048460

121549500

HIGH OFF OFFCFM

TEMP. RISEWATTS

141542410

140042470

140042530

137543580

132045590

Page 14: Service Facts UD2-9V-SF-1C Gas Furnace — Variable Speed ... · UD2-9V-SF-1C X340989P17. 2 X340989P17 Service Facts Product Specifications 1 MODEL TYPE RATINGS 2 1st Stage Input

14 X340989P17

Service Facts*UD2C080A9V4VB FURNACE HEATING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER

AIRFLOWSETTING

DIP SWITCH SETTING EXTERNAL STATIC PRESSURE

S4-3 S4-4 0.1 0.3 0.5 0.7 0.9

HEATING1ST

STAGE

LOW ON ONCFM

TEMP. RISEWATTS

7824975

76251110

75151145

74851185

73752225

MEDIUM ** ON OFFCFM

TEMP. RISEWATTS

8704490

86545125

86145175

84845215

83146255

HIGH OFF OFFCFM

TEMP. RISEWATTS

96240110

97440155

96340200

93841245

91442290

HEATING2ND

STAGE

LOW ON ONCFM

TEMP. RISEWATTS

109154145

109254190

108755245

109254305

107755355

MEDIUM ** ON OFFCFM

TEMP. RISEWATTS

121149190

124348255

124348310

124448370

123548430

HIGH OFF OFFCFM

TEMP. RISEWATTS

137143255

138843325

139243395

138543455

137743515

*UD2C080A9V4VB FURNACE COOLING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER

OUTDOORUNIT SIZE

(TONS)

AIRFLOWSETTING

DIP SWITCH SETTING EXTERNAL STATIC PRESSURE

S3-1 S3-2 S3-3 S3-4 0.1 0.3 0.5 0.7 0.9

2.5

LOW(350 CFM/TON) ON ON OFF ON CFM

WATTS86390

865130

858175

843220

831255

NORMAL (400 CFM/TON) ON ON OFF OFF CFM

WATTS995115

1005170

989210

973260

956305

HIGH(450 CFM/TON) ON ON ON OFF CFM

WATTS1101150

1112200

1111255

1107305

1101360

3.0

LOW(350 CFM/TON) OFF ON OFF ON CFM

WATTS1031125

1031175

1026215

1013270

1003320

NORMAL (400 CFM/TON) OFF ON OFF OFF CFM

WATTS1163170

1178230

1188285

1183345

1178405

HIGH(450 CFM/TON) OFF ON ON OFF CFM

WATTS1319240

1337305

1344365

1340420

1336485

3.5 LOW

(350 CFM/TON) ON OFF OFF ON CFMWATTS

1182200

1206240

1211295

1211350

1211420

NORMAL(400 CFM/TON) ON OFF OFF OFF CFM

WATTS1380255

1401325

1402390

1402460

1399515

HIGH(450 CFM/TON) ON OFF ON OFF CFM

WATTS1553350

1566425

1557500

1558560

1559645

4.0 **

LOW(350 CFM/TON) OFF OFF OFF ON CFM

WATTS1386255

1401330

1408395

1402460

1390520

NORMAL **(400 CFM/TON) OFF OFF OFF OFF CFM

WATTS1590360

1593440

1591515

1588575

1576650

HIGH(450 CFM/TON) OFF OFF ON OFF CFM

WATTS1791360

1808615

1810615

1808775

1726800

NOTES:1. * First Letter may be "A" or "T"2. ** Factory setting3. Continuous Fan Setting: Heating or Cooling airflow is approximately 50% of selected Cooling value.4. LOW 350 cfm/ton is recommended for Variable Speed application for COMFORT & HUMID CLIMATE setting; NORMAL is 400 cfm/ton; HIGH 450 cfm/ton is for DRY CLIMATE setting

Page 15: Service Facts UD2-9V-SF-1C Gas Furnace — Variable Speed ... · UD2-9V-SF-1C X340989P17. 2 X340989P17 Service Facts Product Specifications 1 MODEL TYPE RATINGS 2 1st Stage Input

X340989P17 15

Service Facts*UD2C080B9V4VB FURNACE HEATING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER

AIRFLOWSETTING

DIP SWITCH SETTING EXTERNAL STATIC PRESSURE

S4-3 S4-4 0.1 0.3 0.5 0.7 0.9

HEATING1ST

STAGE

LOW ON ONCFM

TEMP. RISEWATTS

97449133

96849285

94950202

92551254

90652304

MEDIUM ** ON OFFCFM

TEMP. RISEWATTS

11024393

111243144

110343201

108344255

106645305

HIGH OFF OFFCFM

TEMP. RISEWATTS

119440119

121739180

121539243

120040304

118240362

HEATING2ND

STAGE

LOW ON ONCFM

TEMP. RISEWATTS

118958142

121057209

120957276

119358341

117558404

MEDIUM ** ON OFFCFM

TEMP. RISEWATTS

134651141

138849207

139849274

139049339

137250401

HIGH OFF OFFCFM

TEMP. RISEWATTS

146047186

151645263

153645335

153345407

151545477

*UD2C080B9V4VB FURNACE COOLING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER

OUTDOORUNIT SIZE

(TONS)

AIRFLOWSETTING

DIP SWITCH SETTING EXTERNAL STATIC PRESSURE

S3-1 S3-2 S3-3 S3-4 0.1 0.3 0.5 0.7 0.9

2.5

LOW(350 CFM/TON) ON ON OFF ON CFM

WATTS84271

819114

789163

756207

740249

NORMAL (400 CFM/TON) ON ON OFF OFF CFM

WATTS95690

948140

928196

901248

884298

HIGH(450 CFM/TON) ON ON ON OFF CFM

WATTS1071113

1078171

1067233

1045292

1028348

3.0

LOW(350 CFM/TON) OFF ON OFF ON CFM

WATTS100299

1000152

983210

958265

942318

NORMAL (400 CFM/TON) OFF ON OFF OFF CFM

WATTS1140128

1155191

1150256

1132319

1114379

HIGH(450 CFM/TON) OFF ON ON OFF CFM

WATTS1278165

1311238

1316308

1305377

1287444

3.5 LOW

(350 CFM/TON) ON OFF OFF ON CFMWATTS

1163134

1181199

1177265

1161328

1143389

NORMAL(400 CFM/TON) ON OFF OFF OFF CFM

WATTS1324179

1363255

1372326

1363397

1345466

HIGH(450 CFM/TON) ON OFF ON OFF CFM

WATTS1485234

1544319

1566396

1565472

1546550

4.0 **

LOW(350 CFM/TON) OFF OFF OFF ON CFM

WATTS1324179

1363255

1372326

1363397

1345466

NORMAL **(400 CFM/TON) OFF OFF OFF OFF CFM

WATTS1508243

1570329

1594407

1593483

1575562

HIGH(450 CFM/TON) OFF OFF ON OFF CFM

WATTS1691322

1777416

1816499

1824579

1805669

NOTES:1. * First Letter may be "A" or "T"2. ** Factory setting3. Continuous Fan Setting: Heating or Cooling airflow is approximately 50% of selected Cooling value.4. LOW 350 cfm/ton is recommended for Variable Speed application for COMFORT & HUMID CLIMATE setting; NORMAL is 400 cfm/ton; HIGH 450 cfm/ton is for DRY CLIMATE setting

Page 16: Service Facts UD2-9V-SF-1C Gas Furnace — Variable Speed ... · UD2-9V-SF-1C X340989P17. 2 X340989P17 Service Facts Product Specifications 1 MODEL TYPE RATINGS 2 1st Stage Input

16 X340989P17

Service Facts*UD2B100A9V3VB FURNACE HEATING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER

AIRFLOWSETTING

DIP SWITCH SETTING EXTERNAL STATIC PRESSURE

S4-3 S4-4 0.1 0.3 0.5 0.7 0.9

HEATING1ST

STAGE

LOW ON ONCFM

TEMP. RISEWATTS

7516486

79661132

81759175

83258218

83857263

MEDIUM ** ON OFFCFM

TEMP. RISEWATTS

86256121

92152185

95351233

96750285

95450322

HIGH OFF OFFCFM

TEMP. RISEWATTS

95950148

100248210

103646280

103646325

100348355

HEATING2ND

STAGE

LOW ON ONCFM

TEMP. RISEWATTS

109967227

112466287

114964355

115764415

105570395

MEDIUM ** ON OFFCFM

TEMP. RISEWATTS

128658365

132156450

131356455

121561475

111966450

HIGH OFF OFFCFM

TEMP. RISEWATTS

139953465

141952570

134755545

126559520

116364485

*UD2B100A9V3VB FURNACE COOLING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER

OUTDOORUNIT SIZE

(TONS)

AIRFLOWSETTING

DIP SWITCH SETTING EXTERNAL STATIC PRESSURE

S3-1 S3-2 S3-3 S3-4 0.1 0.3 0.5 0.7 0.9

1.5

LOW(350 CFM/TON) ON ON OFF ON CFM

WATTS51650

53675

551105

547135

530165

NORMAL(400 CFM/TON) ON ON OFF OFF CFM

WATTS58359

61592

633127

621157

61818

HIGH(450 CFM/TON) ON ON ON OFF CFM

WATTS68170

697110

701140

709180

712215

2.0

LOW(350 CFM/TON) OFF ON OFF ON CFM

WATTS68075

726120

735150

741190

745230

NORMAL(400 CFM/TON) OFF ON OFF OFF CFM

WATTS769103

819145

843190

858235

865286

HIGH(450 CFM/TON) OFF ON ON OFF CFM

WATTS882130

938190

961245

975300

970345

2.5

LOW(350 CFM/TON) ON OFF OFF ON CFM

WATTS831180

903180

928230

935275

935320

NORMAL(400 CFM/TON) ON OFF OFF OFF CFM

WATTS979167

1036240

1053295

1053345

1015368

HIGH(450 CFM/TON) ON OFF ON OFF CFM

WATTS1121245

1147310

1176383

1167442

1055396

3.0**

LOW(350 CFM/TON) OFF OFF OFF ON CFM

WATTS1061210

1081265

1095320

1101382

1032380

NORMAL **(400 CFM/TON) OFF OFF OFF OFF CFM

WATTS1185278

1223364

1251435

1205455

1101426

HIGH(450 CFM/TON) OFF OFF ON OFF CFM

WATTS1351425

1372503

1343535

1248505

1168480

NOTES:1. * First Letter may be "A" or "T"2. ** Factory setting3. Continuous Fan Setting: Heating or Cooling airflow is approximately 50% of selected Cooling value.4. LOW 350 cfm/ton is recommended for Variable Speed application for COMFORT & HUMID CLIMATE setting; NORMAL is 400 cfm/ton; HIGH 450 cfm/ton is for DRY CLIMATE setting

Page 17: Service Facts UD2-9V-SF-1C Gas Furnace — Variable Speed ... · UD2-9V-SF-1C X340989P17. 2 X340989P17 Service Facts Product Specifications 1 MODEL TYPE RATINGS 2 1st Stage Input

X340989P17 17

Service Facts*UD2C100A9V5VB FURNACE HEATING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER

AIRFLOWSETTING

DIP SWITCH SETTING EXTERNAL STATIC PRESSURE

S4-3 S4-4 0.1 0.3 0.5 0.7 0.9

HEATING1ST

STAGE

LOW ON ONCFM

TEMP. RISEWATTS

90053100

89054130

87055175

85057220

83558270

MEDIUM ** ON OFFCFM

TEMP. RISEWATTS

112543150

109044200

106046235

107045300

107045340

HIGH OFF OFFCFM

TEMP. RISEWATTS

130037220

130037290

132036365

135036430

134036490

HEATING2ND

STAGE

LOW ON ONCFM

TEMP. RISEWATTS

127059200

129058260

129058335

129058400

128058460

MEDIUM ** ON OFFCFM

TEMP. RISEWATTS

157547355

160046445

161046520

160046575

158047650

HIGH OFF OFFCFM

TEMP. RISEWATTS

187040560

189039665

186040710

187040830

173043760

*UD2C100A9V5VB FURNACE COOLING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER

OUTDOORUNIT SIZE

(TONS)

AIRFLOWSETTING

DIP SWITCH SETTING EXTERNAL STATIC PRESSURE

S3-1 S3-2 S3-3 S3-4 0.1 0.3 0.5 0.7 0.9

3.0

LOW(350 CFM/TON) ON ON OFF ON CFM

WATTS1075135

1055185

1015220

1000265

990325

NORMAL(400 CFM/TON) ON ON OFF OFF CFM

WATTS1220185

1200240

1210295

1210350

1210410

HIGH(450 CFM/TON) ON ON ON OFF CFM

WATTS1390245

1390320

1410391

1410470

1400510

3.5

LOW(350 CFM/TON) OFF ON OFF ON CFM

WATTS1214185

1210240

1215295

1210350

1210415

NORMAL(400 CFM/TON) OFF ON OFF OFF CFM

WATTS1430310

1460355

1470430

1460500

1440555

HIGH(450 CFM/TON) OFF ON ON OFF CFM

WATTS1640370

1665460

1650540

1640615

1610660

4.0

LOW(350 CFM/TON) ON OFF OFF ON CFM

WATTS1405270

1430310

1440375

1440480

1420550

NORMAL(400 CFM/TON) ON OFF OFF OFF CFM

WATTS1670395

1675490

1670550

1655630

1630700

HIGH(450 CFM/TON) ON OFF ON OFF CFM

WATTS1870540

1880635

1880730

1845800

1670640

5.0 **

LOW(350 CFM/TON) OFF OFF OFF ON CFM

WATTS1775480

1800580

1820680

1800750

1680740

NORMAL **(400 CFM/TON) OFF OFF OFF OFF CFM

WATTS2065755

2020840

1945900

1805880

1623800

HIGH(450 CFM/TON) OFF OFF ON OFF CFM

WATTS23101000

21001000

2100950

1965890

1800825

NOTES:1. * First letter may be "A" or "T"2. ** Factory setting3. Continuous Fan Setting: Heating or Cooling airflow is approximately 50% of selected Cooling value.4. LOW 350 cfm/ton is recommended for Variable Speed application for COMFORT & HUMID CLIMATE setting; NORMAL is 400 cfm/ton; HIGH 450 cfm/ton is for DRY CLIMATE setting

Page 18: Service Facts UD2-9V-SF-1C Gas Furnace — Variable Speed ... · UD2-9V-SF-1C X340989P17. 2 X340989P17 Service Facts Product Specifications 1 MODEL TYPE RATINGS 2 1st Stage Input

18 X340989P17

Service Facts*UD2C100B9V5VB FURNACE HEATING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER

AIRFLOWSETTING

DIP SWITCH SETTING EXTERNAL STATIC PRESSURE

S4-3 S4-4 0.1 0.3 0.5 0.7 0.9

HEATING1ST

STAGE

LOW ON ONCFM

TEMP. RISEWATTS

9535093

94450146

93651193

90852243

88754292

MEDIUM ** ON OFFCFM

TEMP. RISEWATTS

114242135

114142200

113542255

111243322

109843377

HIGH OFF OFFCFM

TEMP. RISEWATTS

125838169

126038240

125638302

123638378

122739437

HEATING2ND

STAGE

LOW ON ONCFM

TEMP. RISEWATTS

131252188

131752261

131452326

129453406

128753468

MEDIUM ** ON OFFCFM

TEMP. RISEWATTS

157744301

159243387

159243468

159743563

158243644

HIGH OFF OFFCFM

TEMP. RISEWATTS

173939392

176139486

176239575

175339675

176239774

*UD2C100B9V5VB FURNACE COOLING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER

OUTDOORUNIT SIZE

(TONS)

AIRFLOWSETTING

DIP SWITCH SETTING EXTERNAL STATIC PRESSURE

S3-1 S3-2 S3-3 S3-4 0.1 0.3 0.5 0.7 0.9

3.0

LOW(350 CFM/TON) ON ON OFF ON CFM

WATTS1056114

1050173

1044225

1019284

1002336

NORMAL(400 CFM/TON) ON ON OFF OFF CFM

WATTS1199151

1199219

1194277

1172349

1161405

HIGH(450 CFM/TON) ON ON ON OFF CFM

WATTS1342198

1348273

1345340

1326422

1320486

3.5

LOW(350 CFM/TON) OFF ON OFF ON CFM

WATTS1223158

1224227

1219287

1198361

1187418

NORMAL(400 CFM/TON) OFF ON OFF OFF CFM

WATTS1389217

1397294

1395363

1377449

1373515

HIGH(450 CFM/TON) OFF ON ON OFF CFM

WATTS1556291

1570376

1570455

1556549

1559629

4.0

LOW(350 CFM/TON) ON OFF OFF ON CFM

WATTS1389217

1397294

1395363

1377449

1373515

NORMAL(400 CFM/TON) ON OFF OFF OFF CFM

WATTS1580303

1595389

1595469

1582565

1585647

HIGH(450 CFM/TON) ON OFF ON OFF CFM

WATTS1770411

1793507

1795598

1787698

1797801

5.0 **

LOW(350 CFM/TON) OFF OFF OFF ON CFM

WATTS1723382

1744475

1754564

1735663

1744760

NORMAL **(400 CFM/TON) OFF OFF OFF OFF CFM

WATTS1961546

1991652

1996751

1991850

2010981

HIGH(450 CFM/TON) OFF OFF ON OFF CFM

WATTS2199754

2217875

2217983

21971067

1987943

NOTES:1. * First letter may be "A" or "T"2. ** Factory setting3. Continuous Fan Setting: Heating or Cooling airflow is approximately 50% of selected Cooling value.4. LOW 350 cfm/ton is recommended for Variable Speed application for COMFORT & HUMID CLIMATE setting; NORMAL is 400 cfm/ton; HIGH 450 cfm/ton is for DRY CLIMATE setting

Page 19: Service Facts UD2-9V-SF-1C Gas Furnace — Variable Speed ... · UD2-9V-SF-1C X340989P17. 2 X340989P17 Service Facts Product Specifications 1 MODEL TYPE RATINGS 2 1st Stage Input

X340989P17 19

Service Facts*UD2D120A9V5VB FURNACE HEATING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER

AIRFLOWSETTING

DIP SWITCH SETTING EXTERNAL STATIC PRESSURE

S4-3 S4-4 0.1 0.3 0.5 0.7 0.9

HEATING1ST

STAGE

LOW ON ONCFM

TEMP. RISEWATTS

100757114

106254177

108453285

106354303

106354350

MEDIUM ** ON OFFCFM

TEMP. RISEWATTS

115450167

121148230

121148277

122147344

121248417

HIGH OFF OFFCFM

TEMP. RISEWATTS

128845208

131944273

131044330

134943410

135843460

HEATING2ND

STAGE

LOW ON ONCFM

TEMP. RISEWATTS

138764250

142163320

145561400

148860460

149559540

MEDIUM ** ON OFFCFM

TEMP. RISEWATTS

158956350

163754440

166653535

167853600

154158575

HIGH OFF OFFCFM

TEMP. RISEWATTS

177150475

178850560

180449650

175151675

155457590

*UD2D120A9V5VB FURNACE COOLING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER

OUTDOOR UNIT SIZE

(TONS)

AIRFLOWSETTING

(See Notes)

DIP SWITCH SETTING EXTERNAL STATIC PRESSURE

S3-1 S3-2 S3-3 S3-4 0.1 0.3 0.5 0.7 0.9

3.5

LOW(350 CFM/ TON) OFF ON OFF ON CFM

WATTS1195150

1243225

1235275

1251325

1251410

NORMAL(400 CFM/ TON) OFF ON OFF OFF CFM

WATTS1353210

1403290

1417370

1437425

1458485

HIGH(450 CFM/ TON) OFF ON ON OFF CFM

WATTS1554315

1572410

1615480

1634570

1567575

4.0

LOW(350 CFM/ TON) ON OFF OFF ON CFM

WATTS1356200

1391280

1399370

1433420

1454510

NORMAL(400 CFM/ TON) ON OFF OFF OFF CFM

WATTS1565320

1584410

1633475

1639560

1554575

HIGH(450 CFM/ TON) ON OFF ON OFF CFM

WATTS1766450

1799550

1810650

1784685

1590600

5.0 **

LOW(350 CFM/ TON) OFF OFF OFF ON CFM

WATTS1708420

1758530

1759585

1775675

1575585

NORMAL **(400 CFM/ TON) OFF OFF OFF OFF CFM

WATTS1994665

2018775

1971785

1814725

1618625

HIGH(450 CFM/ TON) OFF OFF ON OFF CFM

WATTS2247975

2152925

2019860

1861765

1693680

NOTES: "CONTINUOUS FAN SETTING" IS THERMOSTAT FAN SWITCH "ON" AND DIP SWITCHS 5 AND 6 "ON".1. *FIRST LETTER MAY BE "A" OR "T"2. **FACTORY SETTING.3. CONTINUOUS FAN SETTING: HEATING OR COOLING AIRFLOW IS APPROXIMATELY 50% OF SELECTED COOLING VALUE.4. LOW 350 CFM/TON IS RECOMMENDED FOR VARIABLE SPEED APPLICATION FOR COMFORT & HUMID CLIMATE SETTING: NORMAL IS 400 CFM/TON: HIGH 450 CFM/TON IS FOR DRY CLIMATE SETTING.

Page 20: Service Facts UD2-9V-SF-1C Gas Furnace — Variable Speed ... · UD2-9V-SF-1C X340989P17. 2 X340989P17 Service Facts Product Specifications 1 MODEL TYPE RATINGS 2 1st Stage Input

20 X340989P17

Service Facts*UD2D120B9V5VB FURNACE HEATING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER

AIRFLOWSETTING

DIP SWITCH SETTING EXTERNAL STATIC PRESSURE

S4-3 S4-4 0.1 0.3 0.5 0.7 0.9

HEATING1ST

STAGE

LOW ON ONCFM

TEMP. RISEWATTS

10504599

104446146

103546208

100547252

98048310

MEDIUM ** ON OFFCFM

TEMP. RISEWATTS

121439129

121639188

121739262

119240252

116941310

HIGH OFF OFFCFM

TEMP. RISEWATTS

128837147

129337212

129837293

127537309

125438373

HEATING2ND

STAGE

LOW ON ONCFM

TEMP. RISEWATTS

142948191

144048267

145347363

143548340

141648406

MEDIUM ** ON OFFCFM

TEMP. RISEWATTS

167241310

169540402

172240528

171140409

169740480

HIGH OFF OFFCFM

TEMP. RISEWATTS

178239385

180938480

189036623

183537565

187137644

*UD2D120B9V5VB FURNACE COOLING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER

OUTDOOR UNIT SIZE

(TONS)

AIRFLOWSETTING

(See Notes)

DIP SWITCH SETTING EXTERNAL STATIC PRESSURE

S3-1 S3-2 S3-3 S3-4 0.1 0.3 0.5 0.7 0.9

3.5

LOW(350 CFM/ TON) OFF ON OFF ON CFM

WATTS1208128

1209186

1210260

1185306

1162370

NORMAL(400 CFM/ TON) OFF ON OFF OFF CFM

WATTS1343162

1350232

1358318

1337365

1317433

HIGH(450 CFM/ TON) OFF ON ON OFF CFM

WATTS1477210

1491290

1507391

1490436

1472508

4.0

LOW(350 CFM/ TON) ON OFF OFF ON CFM

WATTS1343162

1350232

1358318

1337365

1317433

NORMAL(400 CFM/ TON) ON OFF OFF OFF CFM

WATTS1496218

1511300

1528403

1511447

1494520

HIGH(450 CFM/ TON) ON OFF ON OFF CFM

WATTS1650296

1671387

1698511

1686548

1671626

5.0 **

LOW(350 CFM/ TON) OFF OFF OFF ON CFM

WATTS1612274

1631363

1655482

1642521

1627598

NORMAL **(400 CFM/ TON) OFF OFF OFF OFF CFM

WATTS1858403

1902533

1907624

1906714

1871755

HIGH(450 CFM/ TON) OFF OFF ON OFF CFM

WATTS1871585

2126711

2110797

2098888

2001953

NOTES: "CONTINUOUS FAN SETTING" IS THERMOSTAT FAN SWITCH "ON" AND DIP SWITCHS 5 AND 6 "ON".1. *FIRST LETTER MAY BE "A" OR "T"2. **FACTORY SETTING.3. CONTINUOUS FAN SETTING: HEATING OR COOLING AIRFLOW IS APPROXIMATELY 50% OF SELECTED COOLING VALUE.4. LOW 350 CFM/TON IS RECOMMENDED FOR VARIABLE SPEED APPLICATION FOR COMFORT & HUMID CLIMATE SETTING: NORMAL IS 400 CFM/TON: HIGH 450 CFM/TON IS FOR DRY CLIMATE SETTING.

Page 21: Service Facts UD2-9V-SF-1C Gas Furnace — Variable Speed ... · UD2-9V-SF-1C X340989P17. 2 X340989P17 Service Facts Product Specifications 1 MODEL TYPE RATINGS 2 1st Stage Input

X340989P17 21

Service Facts*UD2D140A9V5VB FURNACE HEATING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER

AIRFLOWSETTING

DIP SWITCH SETTING EXTERNAL STATIC PRESSURE

S4-3 S4-4 0.1 0.3 0.5 0.7 0.9

HEATING1ST

STAGE

LOW ON ONCFM

TEMP. RISEWATTS

109062130

110061175

107063215

108062255

106063290

MEDIUM ** ON OFFCFM

TEMP. RISEWATTS

123055180

126553235

128053315

130052380

130052455

HIGH OFF OFFCFM

TEMP. RISEWATTS

138049235

140548290

142547375

143047415

145047520

HEATING2ND

STAGE

LOW ON ONCFM

TEMP. RISEWATTS

154567320

155067385

156067475

156067540

157566605

MEDIUM ** ON OFFCFM

TEMP. RISEWATTS

176059435

179058545

181058620

180058695

172560725

HIGH OFF OFFCFM

TEMP. RISEWATTS

200052615

201052715

200052790

195054820

180058775

*UD2D140A9V5VB FURNACE COOLING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER

OUTDOORUNIT SIZE

(TONS)

AIRFLOWSETTING

DIP SWITCH SETTING EXTERNAL STATIC PRESSURE

S3-1 S3-2 S3-3 S3-4 0.1 0.3 0.5 0.7 0.9

3.5

LOW(350 CFM/TON) OFF ON OFF ON CFM

WATTS1175165

1165200

1180265

1170320

1150400

NORMAL(400 CFM/TON) OFF ON OFF OFF CFM

WATTS1345225

1370285

1400360

1405440

1380490

HIGH(450 CFM/TON) OFF ON ON OFF CFM

WATTS1525295

1565390

1585470

1575515

1530585

4.0

LOW(350 CFM/TON) ON OFF OFF ON CFM

WATTS1320220

1330275

1335355

1300435

1240490

NORMAL(400 CFM/TON) ON OFF OFF OFF CFM

WATTS1550310

1580400

1590475

1555540

1460610

HIGH(450 CFM/TON) ON OFF ON OFF CFM

WATTS1735430

1735510

1710600

1670675

1590710

5.0 **

LOW(350 CFM/TON) OFF OFF OFF ON CFM

WATTS1700415

1725470

1730560

1725640

1690700

NORMAL **(400 CFM/TON) OFF OFF OFF OFF CFM

WATTS1980616

1980710

1950770

1885780

1735735

HIGH(450 CFM/TON) OFF OFF ON OFF CFM

WATTS2190835

2150870

2075890

1905800

1735735

NOTES:1. * First Letter may be "A" or "T"2. ** Factory setting3. Continuous Fan Setting: Heating or Cooling airflow is approximately 50% of selected Cooling value.4. LOW 350 cfm/ton is recommended for Variable Speed application for COMFORT & HUMID CLIMATE setting; NORMAL is 400 cfm/ton; HIGH 450 cfm/ton is for DRY CLIMATE setting

Page 22: Service Facts UD2-9V-SF-1C Gas Furnace — Variable Speed ... · UD2-9V-SF-1C X340989P17. 2 X340989P17 Service Facts Product Specifications 1 MODEL TYPE RATINGS 2 1st Stage Input

22 X340989P17

Service Facts

*DD2B060A9V3VA FURNACE COOLING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER

OUTDOOR UNIT SIZE

(TONS)

AIRFLOWSETTING

DIP SWITCH SETTING EXTERNAL STATIC PRESSURE

S3-1 S3-2 S3-3 S3-4 0.1 0.3 0.5 0.7 0.9

1.5

LOW(350 CFM/ TON) ON ON OFF ON CFM

WATTS53345

56375

546100

534130

515160

NORMAL(400 CFM/ TON) ON ON OFF OFF CFM

WATTS60955

62790

624115

606150

607180

HIGH(450 CFM/ TON) ON ON ON OFF

CFM

WATTS66465

68395

690135

687165

680200

2.0

LOW(350 CFM/ TON) OFF ON OFF ON CFM

WATTS69365

714105

708135

706170

712210

NORMAL(400 CFM/ TON) OFF ON OFF OFF CFM

WATTS78085

821130

813165

810205

816245

HIGH(450 CFM/ TON) OFF ON ON OFF CFM

WATTS886110

896150

901200

925250

930285

2.5

LOW(350 CFM/ TON) ON OFF OFF ON CFM

WATTS865105

882145

869185

884275

885265

NORMAL(400 CFM/ TON) ON OFF OFF OFF CFM

WATTS977135

983180

1014235

1035290

1019330

HIGH(450 CFM/ TON) ON OFF ON OFF CFM

WATTS1097170

1125235

1155305

1169350

1169405

3.0 **

LOW(350 CFM/ TON) OFF OFF OFF ON CFM

WATTS1006145

1034200

1056255

1072315

1067352

NORMAL **(400 CFM/ TON) OFF OFF OFF OFF CFM

WATTS1169215

1202265

1226355

1221390

1217440

HIGH(450 CFM/ TON) OFF OFF ON OFF CFM

WATTS1313290

1339370

1360425

1369500

1357525

NOTES:1. *FIRST LETTER MAY BE "A" OR "T"2. **FACTORY SETTING.3. CONTINUOUS FAN SETTING: HEATING OR COOLING AIRFLOW IS APPROXIMATELY 50% OF SELECTED COOLING VALUE.4. LOW 350 CFM/TON IS RECOMMENDED FOR VARIABLE SPEED APPLICATION FOR COMFORT & HUMID CLIMATE SETTING: NORMAL IS 400 CFM/TON: HIGH 450 CFM/TON IS FOR DRY CLIMATE SETTING.

*DD2B060A9V3VA FURNACE HEATING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER

AIRFLOWSETTING

DIP SWITCH SETTING EXTERNAL STATIC PRESSURE

S4-3 S4-4 0.1 0.3 0.5 0.7 0.9

HEATING1ST

STAGE

LOW

ON

ON

CFMTEMP. RISE

WATTS

5475348

5934980

57151107

56751143

54453170

MEDIUM ** ON OFFCFM

TEMP. RISEWATTS

6584465

6644492

65844122

65844155

65244197

HIGH

OFF OFF

CFMTEMP. RISE

WATTS

7353975

76138120

76138155

76438190

76238230

HEATING2ND

STAGE

LOW ON ON

CFMTEMP. RISE

WATTS

7436075

77757120

77557155

78357195

77258230

MEDIUM ** ON OFFCFM

TEMP. RISEWATTS

87451105

88750150

88150185

89450230

89450270

HIGH OFF OFF

CFMTEMP. RISE

WATTS

99645143

101344192

104143250

105842307

106942337

Page 23: Service Facts UD2-9V-SF-1C Gas Furnace — Variable Speed ... · UD2-9V-SF-1C X340989P17. 2 X340989P17 Service Facts Product Specifications 1 MODEL TYPE RATINGS 2 1st Stage Input

X340989P17 23

Service Facts

*DD2B080A9V3VA FURNACE COOLING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER

OUTDOORUNIT SIZE

(TONS)

AIRFLOWSETTING

DIP SWITCH SETTING EXTERNAL STATIC PRESSURE

S3-1 S3-2 S3-3 S3-4 0.1 0.3 0.5 0.7 0.9

2.5

LOW(350 CFM/TON) OFF ON OFF ON CFM

WATTS840105

830135

830160

815220

750225

NORMAL (400 CFM/TON) OFF ON OFF OFF CFM

WATTS970140

950170

940210

925245

900270

HIGH(450 CFM/TON) OFF ON ON OFF CFM

WATTS1085185

1060220

1045260

1015300

1000325

3.0

LOW(350 CFM/TON) ON OFF OFF ON CFM

WATTS1015155

995190

990230

970260

920285

NORMAL (400 CFM/TON) ON OFF OFF OFF CFM

WATTS1150215

1140250

1120305

1100335

1085370

HIGH(450 CFM/TON) ON OFF ON OFF CFM

WATTS1290300

1290340

1270390

1260425

1235475

3.5 **

LOW(350 CFM/TON) OFF OFF OFF ON CFM

WATTS1160220

1150265

1140320

1115345

1100385

NORMAL **(400 CFM/TON) OFF OFF OFF OFF CFM

WATTS1355330

1340380

1330425

1320470

1280510

HIGH(450 CFM/TON) OFF OFF ON OFF CFM

WATTS1360330

1360380

1315425

1320470

1280510

NOTES:1. * First letter may be "A" or "T"2. ** Factory setting3. Continuous Fan Setting: Heating or Cooling airflow is approximately 50% of selected Cooling value.4. LOW 350 cfm/ton is recommended for Variable Speed application for COMFORT & HUMID CLIMATE setting; NORMAL is 400 cfm/ton; HIGH 450 cfm/ton is for DRY CLIMATE setting

*DD2B080A9V3VA FURNACE HEATING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER

AIRFLOWSETTING

DIP SWITCH SETTING EXTERNAL STATIC PRESSURE

S4-3 S4-4 0.1 0.3 0.5 0.7 0.9

HEATING1ST

STAGE

LOW ON ONCFM

TEMP. RISEWATTS

7755085

75051110

70055140

68556170

68057185

MEDIUM ** ON OFFCFM

TEMP. RISEWATTS

86545110

84046140

82047175

79548210

77050235

HIGH OFF OFFCFM

TEMP. RISEWATTS

101038160

98039190

97040230

94041260

91542285

HEATING2ND

STAGE

LOW ON ONCFM

TEMP. RISEWATTS

108055180

106056220

103557255

101059285

99560325

MEDIUM ** ON OFFCFM

TEMP. RISEWATTS

119050245

119050290

117051330

115551370

114052410

HIGH OFF OFFCFM

TEMP. RISEWATTS

134544330

133544380

132045425

131045475

127546505

Page 24: Service Facts UD2-9V-SF-1C Gas Furnace — Variable Speed ... · UD2-9V-SF-1C X340989P17. 2 X340989P17 Service Facts Product Specifications 1 MODEL TYPE RATINGS 2 1st Stage Input

24 X340989P17

Service Facts

*DD2C100A9V5VA FURNACE COOLING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER

OUTDOORUNIT SIZE

(TONS)

AIRFLOWSETTING

DIP SWITCH SETTING EXTERNAL STATIC PRESSURE

S3-1 S3-2 S3-3 S3-4 0.1 0.3 0.5 0.7 0.9

3.0

LOW(350 CFM/TON) ON ON OFF ON CFM

WATTS1025125

1050165

1035195

1030250

1005285

NORMAL(400 CFM/TON) ON ON OFF OFF CFM

WATTS1185165

1180210

1180250

1190315

1190365

HIGH(450 CFM/TON) ON ON ON OFF CFM

WATTS1300200

1345280

1355325

1375405

1370450

3.5

LOW(350 CFM/TON) OFF ON OFF ON CFM

WATTS1195165

1185215

1200270

1200320

1190370

NORMAL(400 CFM/TON) OFF ON OFF OFF CFM

WATTS1360230

1390315

1425380

1420430

1420495

HIGH(450 CFM/TON) OFF ON ON OFF CFM

WATTS1560320

1595425

1595460

1595540

1570585

4.0

LOW(350 CFM/TON) ON OFF OFF ON CFM

WATTS1350235

1385300

1410375

1420425

1410495

NORMAL(400 CFM/TON) ON OFF OFF OFF CFM

WATTS1575340

1615420

1625495

1610545

1585595

HIGH(450 CFM/TON) ON OFF ON OFF CFM

WATTS1800480

1795555

1790620

1760670

1690675

5.0 **

LOW(350 CFM/TON) OFF OFF OFF ON CFM

WATTS1745440

1760515

1755595

1735640

1670660

NORMAL **(400 CFM/TON) OFF OFF OFF OFF CFM

WATTS2010630

2000700

1940745

1865740

1760725

HIGH(450 CFM/TON) OFF OFF ON OFF CFM

WATTS2205830

2130835

2015800

1890760

1740720

NOTES:1. * First letter may be "A" or "T"2. ** Factory setting3. Continuous Fan Setting: Heating or Cooling airflow is approximately 50% of selected Cooling value.4. LOW 350 cfm/ton is recommended for Variable Speed application for COMFORT & HUMID CLIMATE setting; NORMAL is 400 cfm/ton; HIGH 450 cfm/ton is for DRY CLIMATE setting

*DD2C100A9V5VA FURNACE HEATING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER

AIRFLOWSETTING

DIP SWITCH SETTING EXTERNAL STATIC PRESSURE

S4-3 S4-4 0.1 0.3 0.5 0.7 0.9

HEATING1ST

STAGE

LOW ON ONCFM

TEMP. RISEWATTS

8905487

87055120

85556160

85057200

82558250

MEDIUM ** ON OFFCFM

TEMP. RISEWATTS

110044135

109044175

108045225

107045260

107045320

HIGH OFF OFFCFM

TEMP. RISEWATTS

127038195

129037260

129537315

130037365

130037425

HEATING2ND

STAGE

LOW ON ONCFM

TEMP. RISEWATTS

123060180

122061220

125059290

125559345

127558410

MEDIUM ** ON OFFCFM

TEMP. RISEWATTS

152049295

155048385

156047460

155548525

153048565

HIGH OFF OFFCFM

TEMP. RISEWATTS

182041475

182541570

182541625

180041685

174043695

Page 25: Service Facts UD2-9V-SF-1C Gas Furnace — Variable Speed ... · UD2-9V-SF-1C X340989P17. 2 X340989P17 Service Facts Product Specifications 1 MODEL TYPE RATINGS 2 1st Stage Input

X340989P17 25

Service Facts

DD2D120A9V5VA FURNACE COOLING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER

OUTDOOR UNIT SIZE

(TONS)

AIRFLOWSETTING

DIP SWITCH SETTING EXTERNAL STATIC PRESSURE

S3-1 S3-2 S3-3 S3-4 0.1 0.3 0.5 0.7 0.9

3.5

LOW(350 CFM/TON) OFF ON OFF ON CFM

WATTS1200150

1200185

1185235

1210290

1210350

NORMAL(400 CFM/TON) OFF ON OFF OFF CFM

WATTS1355190

1400265

1420335

1445385

1445440

HIGH(450 CFM/TON) OFF ON ON OFF CFM

WATTS1535255

1580345

1600415

1620490

1600530

4.0

LOW(350 CFM/TON) ON OFF OFF ON CFM

WATTS1350190

1370250

1400320

1415385

1420445

NORMAL(400 CFM/TON) ON OFF OFF OFF CFM

WATTS1570275

1600350

1630425

1640500

1630560

HIGH(450 CFM/TON) ON OFF ON OFF CFM

WATTS1800400

1800450

1815540

1820610

1810670

5.0 **

LOW(350 CFM/TON) OFF OFF OFF ON CFM

WATTS1725350

1750440

1770500

1790580

1775650

NORMAL **(400 CFM/TON) OFF OFF OFF OFF CFM

WATTS1970515

2015615

2035700

2010775

1960800

HIGH(450 CFM/TON) OFF OFF ON OFF CFM

WATTS2260730

2250830

2215885

2100860

1975810

NOTES:1. * First Letter may be "A" or "T"2. ** Factory setting3. Continuous Fan Setting: Heating or Cooling airflow is approximately 50% of selected Cooling value.4. LOW 350 cfm/ton is recommended for Variable Speed application for COMFORT & HUMID CLIMATE setting; NORMAL is 400 cfm/ton; HIGH 450 cfm/ton is for DRY CLIMATE setting

DD2D120A9V5VA FURNACE HEATING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER

AIRFLOWSETTING

DIP SWITCH SETTING EXTERNAL STATIC PRESSURE

S4-3 S4-4 0.1 0.3 0.5 0.7 0.9

HEATING1ST

STAGE

LOW ON ONCFM

TEMP. RISEWATTS

9706085

99058140

98059180

95561210

93062255

MEDIUM ** ON OFFCFM

TEMP. RISEWATTS

112052120

114051170

111552215

112052270

112052315

HIGH OFF OFFCFM

TEMP. RISEWATTS

124047150

124047210

124047250

124047300

124047360

HEATING2ND

STAGE

LOW ON ONCFM

TEMP. RISEWATTS

136065190

138064250

140063315

142562400

143062430

MEDIUM ** ON OFFCFM

TEMP. RISEWATTS

157057275

162055370

164054440

165054480

163554560

HIGH OFF OFFCFM

TEMP. RISEWATTS

172052360

173551425

176051515

176051585

176051650

Page 26: Service Facts UD2-9V-SF-1C Gas Furnace — Variable Speed ... · UD2-9V-SF-1C X340989P17. 2 X340989P17 Service Facts Product Specifications 1 MODEL TYPE RATINGS 2 1st Stage Input

26 X340989P17

Service Facts

▲ WARNING!

The following warning complies with State of California law, Proposition 65.

This product contains fiberglass wool insulation!

Fiberglass dust and ceramic fibers are believed by the State of California to cause cancer through inhalation. Glasswool fibers may also cause respiratory, skin, or eye irritation.

PRECAUTIONARY MEASURES

● Avoid breathing fiberglass dust.

● Use a NIOSH approved dust/mist respirator.

● Avoid contact with the skin or eyes. Wear long-sleeved, loose-fitting clothing, gloves, and eye protection.

● Wash clothes separately from other clothing: rinse washer thoroughly.

● Operations such as sawing, blowing, tear-out, and spraying may generate fiber concentrations requiring additional respiratory protection. Use the appropriate NIOSH approved respirator in these situations.

FIRST AID MEASURES

Eye Contact – Flush eyes with water to remove dust. If symptoms persist, seek medical attention.

Skin Contact – Wash affected areas gently with soap and warm water after handling.

GREEN LED AMBER LED RED LED ERRORFLASH FLASH FLASH

1 Flame Sensed when no flame should be present2 Pressure switch stuck closed3 1st stage pressure switch is open / not closing4 Open thermal limit or open rollout5 Open low voltage fuse6 1st stage pressure switch opened 5 times within one cycle--1 hour lockout7 System lockout Retry8 System lockout Recycle9 Reverse polarity or poor grounding10 Gas valve energized without call for heat12 Ignitor relay failure internal in board. Replace IFC

Solid Gas valve relay failure internal in board. Replace IFC3 Double 2nd stage pressure switch open; system reverts back to 1st stage heat

1 1st stage call for heat2 2nd stage call for heat3 W2 call present without W14 Y call present without G

Rapid Low flame sense current1 Standby mode or call for cooling

* The diagnostics will indicate the specific fault through the following code:

Page 27: Service Facts UD2-9V-SF-1C Gas Furnace — Variable Speed ... · UD2-9V-SF-1C X340989P17. 2 X340989P17 Service Facts Product Specifications 1 MODEL TYPE RATINGS 2 1st Stage Input

X340989P17 27

Service FactsTroubleshooting and Additional Information

S7 switch for W2 delay with single stage thermostat

and heating blower delays

S5-1 for HP or Non Heat pump selection

S5-2 for humidistat & BK enabling

Fault Retrieval

Board layout.

Status & Fault LED

CFM LED One flash equal 100 requested CFM

5 amp fuse CFM LED Jumper

Do not cut

Points for flame rectification

readings 1VDC = 1 uA

Blower air flow settings and

cooling time delays

Page 28: Service Facts UD2-9V-SF-1C Gas Furnace — Variable Speed ... · UD2-9V-SF-1C X340989P17. 2 X340989P17 Service Facts Product Specifications 1 MODEL TYPE RATINGS 2 1st Stage Input

28 X340989P17

Service Facts

Board layout.

S5 switches 1& 2

S4-3 & S4-4 control blower heating speeds. Reference blower tables for required

heating air flow.

S3-1 & S3-2 control system tonnage. These switches

configure air flow to match the tonnage of the condenser.

Reference door panel or blower performance tables for

settings

S3-3 & S3-4 control CFM per ton

S3-3 S3-4

S7 switches 3 & 4 for blower delay in heating

S7 switches 1 & 2 for W2 delay

Leave both switches off when using a 2- stage stat or enabling a W1 only call.

See Troubleshooting for details on Auto

Page 29: Service Facts UD2-9V-SF-1C Gas Furnace — Variable Speed ... · UD2-9V-SF-1C X340989P17. 2 X340989P17 Service Facts Product Specifications 1 MODEL TYPE RATINGS 2 1st Stage Input

X340989P17 29

Service Facts

W2 staging time delay options with single stage statThe auto mode can be used when employing a single stage heating thermostat. This mode allows the furnace to move into second stage based on the past three hour duty cycle of the furnace.*A furnace running in mild conditions will have a low duty cycle and a second stage delay of 10 to 12 minutes.*A furnace running in normal conditions will have an average duty cycle and a second stage delay of 5 to 7 minutes.*A furnace running in cold conditions will have a high duty cycle and a second stage delay of only 1 to 3 minutes.

Leave S7-1 & S7-2 to the off position when using a 2-stage thermostat.

The 50V51 Control board uses a 115 Silicone Nitride Igniter. This control board does not reduce the voltage to the igniter as other boards do. Do not use lower voltage igniters as replacement options. Only use the OEM igniter for replacement.

Fault Code RetrievalThe IFC has the ability to store fault codes in memory. To retrieve previous faults, push and release the last error button for 1 to 5 seconds. The LED will flash up to five stored fault codes beginning with the most recent. There is a two second delay between the faults displayed. The LED will flash two green flashes if there are no fault codes in memory.

Fault Code ResetPush and hold the last error button between 5 and 10 seconds to clear all faults from memory. The LED will flash three green flashes to confirm that memory has been cleared.

BK FeatureEnabling the BK feature is done through the S5-2 switch on the IFC. The switch comes in the de-activated “ON” position from the factory. Move this switch to the “OFF” position to enable the BK function of the board. Do not cut any jumpers on this board.The BK feature is used for blower modulation when us-ing a humidistat for de-humidification, a two step scroll compressor system, a 402 thermostat (with BK enabled), or residential zoning.A jumper must be placed between R & O on the low volt-age terminal board to engage the BK circuit

Page 30: Service Facts UD2-9V-SF-1C Gas Furnace — Variable Speed ... · UD2-9V-SF-1C X340989P17. 2 X340989P17 Service Facts Product Specifications 1 MODEL TYPE RATINGS 2 1st Stage Input

30 X340989P17