Server Technology Technical Data Sheet PRO2™ Switched CDU® STV-4501: 20-30A/16-32A 208V/230V input with (24)C13 and (6)C19 outlets The Server Technology® PRO2 Switched CDU provides control of outlet power and local LED input current monitoring, allowing IT personnel to determine safe levels of loading on a per-phase basis while installing equipment into the rack/cabinet. The integral PIPS® technology provides billing-grade accurate measurement of current, voltage, active power, apparent power, power factor, crest factor, and accumulated energy at the input. These power data points, along with temperature and humidity measurements (provided via optional probes), are accessible through the built-in Web and CLI interfaces as well as through SNMP. The PRO2 Switched "Master" CDU can be connected to as many as three PRO2 Switched "Link" CDUs to extend the network access to the redundant or secondary power feed without the risks of a daisy chain linking configuration. Oct. 2014 | Version 1.0

Server Technology Technical Data Sheet

  • Upload
    others

  • View
    4

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Server Technology Technical Data Sheet

Server TechnologyTechnical Data Sheet

PRO2™ Switched CDU®STV-4501: 20-30A/16-32A 208V/230V input with (24)C13 and (6)C19 outlets

The Server Technology® PRO2 Switched CDU provides control of outlet power and local LED input current monitoring, allowing IT personnel to determine safe levels of loading on a per-phase basis while installing equipment into the rack/cabinet. The integral PIPS® technology provides billing-grade accurate measurement of current, voltage, active power, apparent power, power factor, crest factor, and accumulated energy at the input. These power data points, along with temperature and humidity measurements (provided via optional probes), are accessible through the built-in Web and CLI interfaces as well as through SNMP. The PRO2 Switched "Master" CDU can be connected to as many as three PRO2 Switched "Link" CDUs to extend the network access to the redundant or secondary power feed without the risks of a daisy chain linking con�guration.

Oct. 2014 | Version 1.0

Page 2: Server Technology Technical Data Sheet

FeaturesNetwork MonitoringThe PRO2 hot-swappable network card provides for HTTP(S), SSH, Telnet, SNMP, (S)FTP, SMTP, Syslog, LDAP(S), RS-232 serial, and more.

Star Multi-LinkingPRO2 provides the ability to link up to four power circuits using one IP address. Primary link provides backup power to network card.

Hot-Swap Network CardNetwork access is ensured when power is lost to the Master unit with backup power provided by the prima-ry link unit.

Temperature/Humidity MonitoringPRO2 Master and Link units each support two external 10' (3m) T/H probes. Receive SNMP-based alerts and email noti�cations.

Outlet ControlOn PRO2 Switched CDUs, cycle power to individual outlets or groups of outlets to reboot servers. Or, power o� unused receptacles.

Auto-�ip Current DisplayEasy-to-read LEDs display current per phase to help prevent overloads and simplify three-phase load balancing in high-density cabinets.

Power Pivot™The 90 degree rotatable power cord allows for standardized deployment at any facility no matter where power must be routed.

High Retention Locking OutletsPRO2 receptacles have high retention and are compatible with Server Technology’s LockedIn™ power cords (sold separately).

ST Eye Bluetooth ReadyThe best CDU LCD is the one in your hand. Attach the ST Eye™ Bluetooth module to PRO2 for access to power data and system settings.

Branch Circuit ProtectionPRO2 meets the UL and IEC 60950-1 requirement for branch circuit protec-tion through use of UL489 rated magnetic-hydraulic circuit breakers.

Branch Current MonitoringPRO2 monitors current at each break-er branch and provides SNMP-based alerts and emails on high usage that risks a tripped circuit.

Per-Inlet Power SensingMeets ANSI C12.1 for billing-grade accuracy of Current per phase. PIPS includes voltage, active power, appar-ent power, power factor, and energy.

Color Identi�cationChoose from six colors to designate circuits for CDUs in the data center. Color options include Blue, Red, Green, White, Yellow, and Black

High Temperature RatingThis product has been tested and approved for safe and reliable opera-tion in 60°C (140°F) data center environments.

Cisco EnergyWise1 CompliantPRO2 meets the requirements set forth by Cisco System, Inc. for its EnergyWise program for monitoring of device energy.

Flexible MountingPRO2 includes standard button mounts along with provisions for custom mounting brackets (contact Server Technology for details).

Page 3: Server Technology Technical Data Sheet

Speci�cations

* Order PTCORD separately. Choose L6-20P, CEE 7/7 Schuko, IEC60309 2P+PE, or BS1363

Outputs• Connector: (24) x IEC 60320/C13 • North American Rating (C13): ≤ 12A @208-240V (15 peak) ; Global: ≤ 10A @220-240V• Connector: (6) x IEC 60320/C19 • North American Rating (C19): ≤ 16A @208-240V (20 peak) ; Global: ≤ 16A @220-240V• LockedIn™ compatible. Locking outlets provide high-retention even for non-locking cords

Input measurement accuracy• LED Current = ± 10% 0.1 amp (1.0 – 9.9amps) and 1 amp (>9.9amps) resolution• GUI Current = ± 1% at 0.01 amp resolution (above 0.5 amp)• Voltage = ± 1% at 0.1 volt resolution (nominal ± 10%)• Active Power = ± 1% at 1 watt resolution • Apparent Power = ± 1% at 1 volt-amp resolution• Power Factor = ± 3% at 0.01 resolution• Crest Factor = ± 10% at 0.1 resolution• Energy = ± 1% at 0.1 kilowatt-hour resolution

Branch measurement accuracy• Current = ± 3% at 0.01 amp resolution (above 0.5 amp)

Branch Circuit Protection• UL489 compliant 2-pole, 20A trip circuit breakers, Two (2) branches, Rating: ≤ 16A @208-240V

208-240V, L-L, 50/60HzSTV-4501C SEV-4501C ≤ 24A (30 peak)

Master CDU Link CDU Input VoltageInput CurrentInput Plug Rated Power

STV-4501A SEV-4501A IEC C20* 208-240V, L-L, 50/60Hz

3328W @208V≤ 16A (20 peak)

4992W @208VNEMA L6-30P, 10ft,3-C, 10AWG

STV-4501K SEV-4501K

Master CDU Link CDU Input VoltageInput CurrentInput Plug Rated Power

STV-4501A SEV-4501A IEC C20* 3680W @230V

7360W @230VIEC 60309 6hr

2P+PE Blue, 3m, H05VV-F, 4.0mm2

≤ 32A

≤ 16A 220-240, L-N,50/60Hz

220-240, L-N,50/60Hz

North America

Global

Page 4: Server Technology Technical Data Sheet

Speci�cations Cont.

Physical/Environmental• Dimensions: 69.00" (1753 mm) tall x 2.19” (56 mm) wide x 2.25" (57 mm) deep | Weight: 25 lbs (11.4 kg)• Shipping Dimensions: 73" x 7" x 3" (186 cm x 18 cm x 8 cm) | Weight: 26 lbs (11.8 kg)• Highlight Color: Choose Black, White, Red, Green, Blue, Yellow• Operating Environment: 32°F to 140°F / 0°C to 60°C | 8%RH to 90%RH non-condensing | 6,500ft/2000m elevation• Storage Environment: -40°F to 185°F / -40°C to 85°C | 8%RH to 90%RH non-condensing | 50,000ft/15km elevation• Quiescent / Unloaded Power Draw: < 10W for all con�gurations

Communications and Security • 10/100 Mbps Ethernet (RJ-45 connector), RS-232 serial (RJ-45 connector)• Two (2) temperature/humidity sensor inputs (4P4C), Link port (RJ-12) – {also on Link CDU}• Web-browser GUI and command-line-interface (CLI): HTTP/HTTPS, SSLv3/TLSv1, SSHv2, Telnet, SNMPv2c and v3

(GET, SET, Traps), IPv4 and IPv6, LDAPv3/LDAPS, TACACS+, RADIUS, FTP/SFTP

Certi�cations• cTUVus Mark to UL 60950-1:2007 and CAN/CSA 22.2 No. 60950-1-07 + A1:2011• TUV T-Mark to EN 60950-1:2006 + A11 + A1 + A12• EMC to EN 55022 Class A, EN 55024, CISPR 22 Class A• FCC Class A, Part 15• CE Mark• RoHS/WEEE

Optional Accessories• EMTH-1-1 Combination Temperature/Humidity Probe, 10ft (3m) • EMCU-1-1B Environmental Monitor adding:

- Two (2) EMTH-1-1 temperature/humidity ports (one probe included)- One (1) EMWS-1-1 water sensor port (probe sold separately)- Four (4) dry contact (NO/NC) monitoring points- One (1) 8-bit analog-to-digital converter (0 to 5VDC)

• SPM (Sentry® Power Manager):- Monitor and manage multiple PDUs from a single point- Monitor and manage alarm conditions- Create reports and trends on stored data- Analyze power usage per phase- Optional appliance or virtual version- VMware Ready2

• Mounting Brackets- Buttons (KIT-0020) included for tool-less mounting (see diagram).- See the Mounting Bracket Guide for further suggestions.- Custom mounting options available. Contact your local Server Technology representative.

• Cable Retention Devices for non-locking cords- EZip- Cable Sleeve- Wire Bails

Page 5: Server Technology Technical Data Sheet

Speci�cations Cont.

• Device / Output LockedIn™ Power Cords- UL Rated

• Device / Output LockedIn™ Power Cords- VDE Rated

- Additional sizes may be available. Contact your local Server Technology representative.

CAB-S1413-FA(FR)

Part Number Plug ColorLengthReceptacle

CAB-S1413-CA C14

C14 3.0 ft (0.9 m)

1.5 ft (0.45 m)

Black (Red)

Black

CAB-S1413-WA

CAB-S1413-NA(NR)

10.0 ft (3 m)

6.0 ft (1.8 m) Black (Red)

Black (Red)

Black (Red)

CAB-S1419-NA

CAB-S1419-FA

6.0 ft (1.8 m)

3.0 ft (0.9 m)

CAB-S2013-FA

CAB-S2013-CA C20

C20

C20

C20

C20

C20

3.0 ft (0.9 m)

1.5 ft (0.45 m)

CAB-S2019-CA

CAB-S2013-NA

1.5 ft (0.45 m)

6.0 ft (1.8 m)

CAB-S2019-NA(NR)

CAB-S2019-FA(FR)

6.0 ft (1.8 m)

3.0 ft (0.9 m)

C14

C14

C14

C14

C13

C13

C13

C13

C13

C19

C19

C19

C13

C13

C19

C19

Black

Black

Black

Black

Black

Black

Black

CAB-S1413-GV(GS)

Part Number Plug ColorLengthReceptacle

CAB-S1413-CV C14

C14 1.0 m (39 in)

0.5 m (20 in)

Black (Red)

Black

CAB-S2013-GV

CAB-S1413-PV(PS) 2.0 m (78 in)

2.0 m (78 in)

2.0 m (78 in)

Black (Red)

Black (Red)

Black (Red)

CAB-S2019-CV

CAB-S2013-PV

CAB-S2019-PV(PS)

CAB-S2019-GV(GS) C20

C20

C14

C14

C14

C14

C13

C13

C13

C13

C13

C19

C19

C19

Black

Black

Black0.5 m (20 in)

1.0 m (39 in)

1.0 m (39 in)

Page 6: Server Technology Technical Data Sheet

Dimensional Speci�cations

AA

BB

CC

DD

1 1

2 2

3 3

4 4

5 5

6 6

7 7

8 8

SE

RV

ER T

EC

HN

OLO

GY

, IN

CPR

OP

RIE

TAR

Y IN

FOR

MAT

ION

TH

IS D

OC

UM

ENT

IS T

HE

SO

LE P

RO

PER

TY O

F S

ERVE

R T

ECH

NO

LOG

Y, I

NC

.TH

E R

ELEA

SE O

F D

ATA

CO

NTA

INE

D IN

TH

IS D

OC

UM

EN

T AN

D T

HE

REP

RO

DU

CTI

ON

OF

THIS

DO

CU

MEN

T, IN

WH

OLE

OR

IN P

AR

T, W

ITH

OU

T TH

E W

RIT

TEN

PE

RM

ISS

ION

OF

SE

RV

ER T

ECH

NO

LOG

Y, IN

C IS

PR

OH

IBIT

ED

.

THES

E C

OM

MO

DIT

IES

, TE

CH

NO

LOG

Y O

R S

OFT

WA

RE

WER

E E

XPO

RTE

D F

RO

M T

HE

UN

ITE

D S

TATE

S IN

AC

CO

RD

AN

CE

WIT

H T

HE

EXP

OR

T A

DM

INIS

TRA

TIO

NR

EGU

LATI

ON

S.

DIV

ER

SIO

N C

ON

TRAR

Y TO

U.S

. LAW

IS P

RO

HIB

ITE

D.

RoH

S C

OM

PLIA

NT

FIN

ISH

:

MAT

ERIA

L:

SCAL

E:BSIZ

EC

AG

E C

OD

ED

WG

NO

.

SHEE

T

REV

SERV

ER T

ECHN

OLO

GY,

INC.

DR

AWIN

G T

ITLE

:

10

40 S

andh

ill D

rive

Ren

o, N

V 89

521

049V

0

THIR

D A

NG

LE P

RO

JEC

TIO

ND

O N

OT

SCAL

E D

RAW

ING

* R

EMO

VE A

LL B

UR

RS

AN

D S

HAR

P ED

GES

.2 R

MAX

* D

IMEN

SIO

NIN

G &

TO

LER

ANC

ING

IAW

ASM

E Y1

4.5M

-200

7*

INTE

RPR

ET

DR

AWIN

G IA

W A

SME

Y14.

100-

2000

* D

IMEN

SIO

NS

ARE

IN M

ILLI

MET

ERS

UN

LESS

OTH

ERW

ISE

SPEC

IFIE

D

NO

NE

412-

0761

-21

1

OU

TLIN

E D

RAW

ING

, SW

ITC

HED

, PI

PS/P

OPS

, V30

, (24

)C13

, (6)

C19

1 O

F 3

* DIM

ENSI

ON

AL L

IMIT

S AP

PLY

AFTE

R P

LATI

NG

/CO

ATIN

G.

TOLE

RAN

CES

(UN

LESS

OTH

ER

WIS

E S

PEC

IFIE

D)

LIN

EAR

DIM

ENSI

ON

S:.X

= ±

.500

.XX

= ±

.300

.XXX

= ±

.130

ANG

ULA

R D

IMEN

SIO

NS:

X =

± 1

°X.

X =

± .5

°X.

XX =

± .2

Q #

= C

RIT

ICAL

DIM

.

S=

CO

SM

ETIC

SU

RFA

CE

SYM

BOLS

REV

ISIO

N H

ISTO

RY

ZON

ER

EVD

ESC

RIP

TIO

ND

ATE

APPR

OVE

D-

GP/M

RJ3102/21/8

NGISE

D LAITINI

1

NO

TES:

1.

DIM

ENSI

ON

S AR

E IN

MIL

LIM

ETER

S AN

D [

] AR

E IN

INC

HES

.

2.

D

IMEN

SIO

NS

ARE

NO

MIN

AL. I

NFO

RM

ATIO

N S

UBJ

ECT

TO C

HAN

GE

WIT

HO

UT

NO

TIC

E.

933.

45 [3

6.75

]

86.15

[3.39

]

1752

.60 [6

9.00]

55.50

[2.19

]57

.15 [2

.25]

68.4

0 [2

.69]

12.7

0 [0

.50]

4X31

.25

[1.2

3]68

.40

[2.6

9]

98.4

3 [3

.88]

1555

.75

[61.

25]

98.4

3 [3

.88]

419.

60 [1

6.52

]39

9.55

[15.

73]

20.0

0 [0

.79]

31.2

5 [1

.23]

20.0

0 [0

.79]

399.

55 [1

5.73

]93

3.45

[36.

75]

419.

60 [1

6.52

]

Page 7: Server Technology Technical Data Sheet

Wiring and Breaker Trip Curve

BreakerTrip Curve

GND

GND

CB

PLUGL1

L2/NEUT

CBGNDGNDGND

CT

BRANCH 1 (1-15)

BRANCH 2(16-30)

Part Number Certification Input Output

Master Expansion Rating Standard Rating Input TypeTotal Output Rating

Outlet Type and Ratings

Branch Circuit Rating

C2W30VA-2ABA2SD8 (STV-4501A)

C2X30VA-2ABA2SD8 (SEV-4501A)

cTUVus and/or cULus

208-240V 2P+PE, 50/60Hz; 16A IEC C20

240V, 50/60Hz; <= 16A

IEC 60320: 6xC19 <= 16A each, 24xC13 <= 12A

2 branches, each <= 16A

TUVGS230V 2P+PE, 50/60Hz; 16A IEC C20

240V, 50/60Hz; <= 16A

IEC 60320: 6xC19 <= 16A each, 24xC13 <= 10A

2 branches, each <= 16A

C2W30VA-2CBA2SD8 (STV-4501C)

C2X30VA-2CBA2SD8 (SEV-4501C)

cTUVus and/or cULus

208-240V 2P+PE, 50/60Hz; 24A NEMA L6-30P

240V, 50/60Hz; <= 24A

IEC 60320: 6xC19 <= 16A each, 24xC13 <= 12A

2 branches, each <= 16A

C2W30VA-EPBA2SD8 (STV-4501K)

C2X30VA-EPBA2SD8 (SEV-4501K) TUVGS

230V 2P+PE, 50/60Hz; 32A IEC 60309 32A

240V, 50/60Hz; <= 32A

IEC 60320: 6xC19 <= 16A each, 24xC13 <= 10A

2 branches, each <= 16A

Page 8: Server Technology Technical Data Sheet

Warranty: Server Technology o�ers a standard 2-year limited parts & labor warranty. Extended support is available at the time of purchase. See the Support Options on the website, or contact your local Server Tech-nology representative for more information.

Patents: Information on Server Technology patents is available on the website at:

www.servertech.com/products/patents

PIPS, POPS, CDU, Sentry, Server Technology, and the globe logo are U.S. registered trademarks of Server Tech-nology, Inc. Power Pivot, ST Eye, LockedIn and PRO2 are trademarks of Server Technology, Inc.

Information in this document is current as of time of publishing. Contact your Server Technology representa-tive for the most up-to-date information. © 2014 Server Technology, Inc.

1 Cisco EnergyWise is a U.S. registered trademark of Cisco Technology, Inc.

2 VMware and VMware Ready is a registered trademark or trademark of VMware, Inc. in the United States and/or other jurisdictions.

Additional Information

Central Europe, Eastern Europe and RussiaNiederlassung DeutschlandServer Technology LLC42119 WuppertalGermanyTel: + 49 202 693917 x 0Fax: + 49 202 [email protected]

HEADQUARTERS - NORTH AMERICAServer Technology, Inc.1040 Sandhill DriveReno, NV 89521United States1.775.284.2000 Tel1.775.284.2065 [email protected]

Western Europe, Middle East and AfricaServer TechnologyFountain Court2 Victoria SquareVictoria StreetSt. AlbansAL1 3TFUnited Kingdom+44 (0) 1727 884676 Tel +44 (0) 1727 220815 [email protected]

APACServer TechnologyRoom 2301, 23/F, Future Plaza111-113 How Ming Street, Kwun Tong, Hong KongDirect line: +852 3916 2048Fax Line: +852 3916 [email protected]