Serv Matters 64

Embed Size (px)

Citation preview

  • 8/10/2019 Serv Matters 64

    1/2

    Issue 6 - Sept 2005

    Superheat is the temperature of the vapour

    above its boiling point.

    As you can see by the diagram in Fig 1 water

    boils at 100C. Any heat added to the steamabove this temperature superheats it (and anytemperature removed from the water below this

    temperature subcools it). Remember superheatdoes not mean Hot it simply means above itsboiling point. R134a boils at approx -26C at

    atmospheric pressure, so whenever R134a iswarmer than -26C and at atmospheric pressureit is superheated.

    Fig 1

    We calculate superheat by taking the difference between theactual exit temperature of the refrigerant from theevaporator (T2) and the saturated evaporating temperature

    (T1). It should be between 5 to 7K. Fig 2 shows us this.

    Fig 2

    Service Matters is produced for the IOR Service Engineers Section by Cool Concerns Ltd

    Please contact Stephen Benton with any feedback at [email protected]

    For more details of Section membershipo see the web site at www.ior.org.uk

    Technical information for the Institute of Refrigeration Service Engineers Section

    Welcome to this issue of Service Matters

    Welcome to this issue of Service Matters in which we cover the mystery of superheat. For reliable andefficient refrigeration the correct degree of superheat must be achieved in the evaporator. Too much andyou will have insufficient capacity, too little and you could carry liquid out of the evaporator into thecompressor leading to mechanical failures. Subcooling is also important and will be covered in a futureissue of Service Matters.

    Stephen Benton

    100C (Water boils)

    Superheated

    Subcooled

    100C (Water boils)

    Superheated

    Subcooled

    Measuring SuperheatThis is very simple, all you need arethe following tools: -

    A set of accurate gauges An accurate electronic

    thermometer with a suitabletouch/contact probe

    A refrigerant comparator

    (comparators are availablefree of charge to all SESmembers)

  • 8/10/2019 Serv Matters 64

    2/2

    Issue 6 - Sept 2005

    Fig 3

    Why is Superheat Important?

    Example Superheat - A

    R134a Evap pressure, 1.5 bar g Evap temp, -4 C Exit temp, 5C Superheat, 5 (-4) = 9K

    Open or close valve to correct

    superheat (5K)?

    5C5C

    Follow the steps below (also see Fig 3 & 4):

    1. Put you gauges on the suction pipe as close

    to the evaporator outlet as possible. Thereis usually a connection if you look.

    2. Take the suction pressure and using yourcomparator convert it into a saturated

    temperature (T1). Check you are using thegauge scale and NOT the Absolute

    scale. When measuring superheats ofblends make sure you use the Dew or

    Vapour scale.3. Take the actual temperature using your

    thermometer adjacent to the expansiondevice phial or sensing probe (T2).

    4. Take the saturated evaporatingtemperature (comparator) from themeasured evaporator outlet temperature,

    SH = T2 T1.

    A superheat of between 5 and 7K willensure that all the liquid refrigerant isboiled off in the evaporator and will not

    carry over to the compressor.

    Fi 4

    Answer:

    Open the valve to reduce the

    superheat check with

    manufacturers instructions on

    valve and always re measure the

    actual superheat after every

    adjustment. Allow time for the

    valve to settle after adjustments.

    Example Superheat - Q

    R134a

    Evap pressure, 1.5 bar g Exit temp, 5C

    Superheat? 5C5C

    Optimumevaporatorperformance

    Zero liquidreturn tocompressor

    Optimumevaporator

    performance

    Zero liquid

    return to

    compressor