FULL SERVICE VARIABLE SPEED (VFD)ELECTRIC FIRE PUMP CONTROLLERMICRO-PROCESSOR BASED
5 to 1505 to 200
5 to 350*5 to 4005 to 500
100,000 A.100,000 A.100,000 A.100,000 A.50,000 A.
150,000 A.150,000 A.150,000 A.150,000 A.100,000 A.
208240
380 - 416480600
STANDARDSHORT CIRCUIT
WITHSTANDRATING
HPVOLTAGE
OPTIONALSHORT CIRCUIT
WITHSTANDRATING
MODELNUMBER
ACROSS-THE-LINE
FULL
100%
STANDARD
3 WIRE
100%
6 X NORMALLOAD CURRENT
VOLTAGETYPICAL VOLTAGE APPLIED
MOTOR STARTINGINRUSH
CURRENTSTARTINGTORQUEMOTORTYPE
# OF WIRECONNECTIONS
VPA
AUTOTRANSFORMER
REDUCED
42%
STANDARD
3 WIRE
65%
42% OF NORMAL 30% (adjustable)
VPR
SOFT STARTSOFT STOP
REDUCED
30%
STANDARD
3 WIRE
30% (adjustable)
VPS
Based on NEMA B type motors.
Main Features :
• Micro-processor based - Display module and pressure adjustment accessible without opening main door• Built in Variable Frequency Drive (VFD)• Across-the-line or reduced voltage by-pass contactor• Variable-Preset-Bypass speed mode selector switch• Pressure transducer set (2) for reading of discharge pressure• Data/Pressure recorder accessible without opening main door• Drip proof enclosure NEMA 2
Also available with Model VPU automatic power transfer switch.
2015-2016
VPx
SER
IES
ANNUNCIATOR AND LCD DISPLAYVoltage and amperage moduleProvides for: • Phase sequence / Loss monitoring & alarms • Individual phase-to-phase voltage indication • Individual phase current indication • True elapsed run time • Motor run visual indication • Over & under current visual indication • Over & under voltage visual indication • Fail to start visual indication • Phase loss visual indication • Phase unbalance visual indication • Power available LED • Phase reversal LED
Pressure and Sequencer moduleProvides for: • Cut-In & Cut-Out pressure setting • System pressure indication • Run period timer • Sequential start timer • Weekly test setting • Pressure recording • Alarm & events recording • Pump on demand LED • Weekly test LED • USB (slave) communication port • Printer (optional) • Modem (optional)
FULL SERVICE PRESSURE LIMITINGVARIABLE FREQUENCY DRIVE (VFD)ELECTRIC FIRE PUMP CONTROLLERMICRO-PROCESSOR BASED
VPx SERIES
VPx-BRO-001/E Rev.10 February 2015 Printed in Canada tornatech.com
STANDARD FEATURES:MANUAL OPERATORS (FLANGE MOUNTED)• Single operator for both isolating switch and circuit breaker, door interlocked in the “ON” position complete with interlock defeater screw • Emergency manual start handle, providing for manual across-the-line starting• Start, Delayed Stop, Instant Stop and Silence/Rest push buttons• Variable-Preset-By-pass speed mode selector switch• Visual and Audible Indicators - By-pass mode pilot light - VFD Failure pilot light - Buzzer for By-pass mode and VFD failureELECTRICAL FEATURES• Molded case isolating switch• Molded case circuit breaker• Built In Variable Frequency Drive (VFD)• Line fuses for VFD protection• Line and load contactors for VFD isolation• Across the line or reduced voltage by-pass contactor• 5% Line reactor• 3 phase voltage surge suppressorCONTROL FEATURES• Micro-processor logic based•Factoryset(nofieldprogramming)• Locked rotor protection• Phase sequence / loss • Provision for remote or deluge valve start • Automatic start sequence• Programmable logic controller• Pressure transducer (0-300psi)• Manual and emergency control circuit independant of micro-processorINDIVIDUAL DRY ALARM CONTACTS 8A. 250VAC for:• Power or phase failure and/or circuit breaker in open position DPDT• Trouble (alarm conditions) DPDT• Phase reversal DPDT • Pump run 1 N/O – 1N/C• By pass mode DPDT • VFD failure DPDTOPTIONAL FEATURES:•Option Type A: Operationalmodifications• Option Type B: Additional annunciations• Option Type C: Extra alarm contacts• Option Type D: Miscellaneous• Option Type E: Load shedding provisions• Option Type F: Automatic transfer switch options• Option Type H: Export packing
Tornatech Inc.Head Office7075, Pl. Robert-Joncas Suite # 132Montreal, Canada H4M 2Z2Tel.: + 1 514 334 0523 + 1 800 363 8448Fax: + 1 514 334 5448
AmericasUSA SalesRepresentatives Toll Free: + 1 800 363-8448 Cincinnati, Ohio Cell: + 1 513 307 6766Birmingham, AlabamaCell: + 1 205 902 9331
EuropeTornatech S.P.R.L. Avenue Sabin 31300 WavreBelgium Tel.: + 32 (0) 10 84 40 01Fax: + 32 (0) 10 24 75 05
Middle EastTornatech FZEWarehouse RA08CC04Jebel Ali NorthPO Box 18435Dubai,United Arab Emirates Tel.: + 971 (0)4 887 0615Fax.: + 971 (0)4 887 0604
Tornatech Pte Ltd.3 Soon Lee Street #05-33Pioneer JunctionSingapore 627606Tel.: + 65 6795 8114 + 65 6795 7823Fax: + 65 6795 3201
Asia
Latin AmericaSales Representative Tel.: + 1 514 334 0523 Cell: + 1 514 945 4067