2
Occupied Unoccupied Unoccupied Override FRZ CT R TE DPT DA DA ASC CT FRZ TE DP HT DA DPT R SD ASC MECHANICAL CONTROL SEQUENCES - LEGEND Consulting Engineers GRIFFITH & VARY, INC. NONE JAJ M-1

Sequence of Operation Air-Cooled Chiller

  • Upload
    others

  • View
    9

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Sequence of Operation Air-Cooled Chiller

Occupied

Unoccupied

Unoccupied Override

FRZ

CT

R

TE

DPT DA

DA

ASC

CT

FRZ

TE

DP

HT

DA

DPT

R

SD

ASC

MECHANICAL CONTROL SEQUENCES - LEGEND

Consulting EngineersGRIFFITH & VARY, INC.

NONE

JAJ M-1

AutoCAD SHX Text
VOLTS
AutoCAD SHX Text
TEMP.
AutoCAD SHX Text
CAPACITY
AutoCAD SHX Text
TONS
AutoCAD SHX Text
NOM.
AutoCAD SHX Text
AMBIENT
AutoCAD SHX Text
CONDENSER FAN DATA
AutoCAD SHX Text
LRA (EA)
AutoCAD SHX Text
AIR COOLED CHILLER UNIT SCHEDULE
AutoCAD SHX Text
TYPE
AutoCAD SHX Text
RLA
AutoCAD SHX Text
NO.
AutoCAD SHX Text
LRA
AutoCAD SHX Text
NO.
AutoCAD SHX Text
COMPRESSOR DATA
AutoCAD SHX Text
REFRIG.
AutoCAD SHX Text
GPM
AutoCAD SHX Text
FLA (EA)
AutoCAD SHX Text
EWT
AutoCAD SHX Text
LWT
AutoCAD SHX Text
PD
AutoCAD SHX Text
CHILLED WATER
AutoCAD SHX Text
%%C
AutoCAD SHX Text
HZ
AutoCAD SHX Text
ELECTRICAL DATA
AutoCAD SHX Text
ITEM
AutoCAD SHX Text
MFG'R
AutoCAD SHX Text
MODEL
AutoCAD SHX Text
ACC-1
AutoCAD SHX Text
TRANE
AutoCAD SHX Text
CGAM 100
AutoCAD SHX Text
98.93
AutoCAD SHX Text
95.0%%DF
AutoCAD SHX Text
REMARKS
AutoCAD SHX Text
R410A
AutoCAD SHX Text
4
AutoCAD SHX Text
41.9 EA.
AutoCAD SHX Text
260 EA.
AutoCAD SHX Text
8
AutoCAD SHX Text
N/A
AutoCAD SHX Text
N/A
AutoCAD SHX Text
236.7
AutoCAD SHX Text
54.0%%DF
AutoCAD SHX Text
44.0%%DF
AutoCAD SHX Text
12.5'
AutoCAD SHX Text
460
AutoCAD SHX Text
3
AutoCAD SHX Text
60
AutoCAD SHX Text
114.4
AutoCAD SHX Text
15.4
AutoCAD SHX Text
SOUND DATA
AutoCAD SHX Text
kW
AutoCAD SHX Text
INPUT
AutoCAD SHX Text
(EER)
AutoCAD SHX Text
IPLV
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
ACCEPTABLE ALT. MANUFACTURERS: YORK/JCI, DAIKIN OR APPROVED EQUAL.
AutoCAD SHX Text
STEAM OR WATER
AutoCAD SHX Text
90 DEG. ELL. TOP
AutoCAD SHX Text
TYPICAL BRANCH PIPE TAKE-OFF DETAIL
AutoCAD SHX Text
TYPICAL FOR ALL WATER PIPING SYSTEMS
AutoCAD SHX Text
WATER ONLY
AutoCAD SHX Text
90 DEG. ELL. BOTTOM
AutoCAD SHX Text
N.T.S.
AutoCAD SHX Text
PITCH
AutoCAD SHX Text
PITCH
AutoCAD SHX Text
PITCH
AutoCAD SHX Text
PIPE MAIN
AutoCAD SHX Text
45 DEG. ELL. BOTTOM
AutoCAD SHX Text
WATER ONLY
AutoCAD SHX Text
45 DEG. ELL. TOP
AutoCAD SHX Text
PIPE MAIN
AutoCAD SHX Text
PITCH
AutoCAD SHX Text
STEAM OR WATER
AutoCAD SHX Text
%%UEND VIEW
AutoCAD SHX Text
%%USIDE VIEW
AutoCAD SHX Text
PIPE GUIDE DETAIL
AutoCAD SHX Text
N.T.S.
AutoCAD SHX Text
FOR PIPES W/ CENTERLINE LESS THAN 18" BELOW SLAB OR BEAM.
AutoCAD SHX Text
STEEL ATTACHMENTS SHALL BE WELDED OR BOLTED.
AutoCAD SHX Text
CONCRETE ATTACHMENTS SHALL BE HILTI OR APPROVED EQUAL.
AutoCAD SHX Text
%%UNOTES:
AutoCAD SHX Text
WELDED TO PIPE
AutoCAD SHX Text
PLATE TO BE TWO
AutoCAD SHX Text
PIPE DIAMETERS LONG
AutoCAD SHX Text
STRUCTURE
AutoCAD SHX Text
CONCRETE OR BLDG.
AutoCAD SHX Text
STEEL GUIDE RIBS
AutoCAD SHX Text
WELDED THRUOUT
AutoCAD SHX Text
1/2" THICK STEEL PLATE
AutoCAD SHX Text
INSULATION AS SPECIFIED
AutoCAD SHX Text
PIPE
AutoCAD SHX Text
RIGID INSULATION
AutoCAD SHX Text
SHEETMETAL SLEEVE OVER
AutoCAD SHX Text
CONSTRUCTION IN AN
AutoCAD SHX Text
SECURE TO BUILDING
AutoCAD SHX Text
PIPE GUIDE SLEEVE
AutoCAD SHX Text
APPROVED MANNER
AutoCAD SHX Text
3.
AutoCAD SHX Text
2.
AutoCAD SHX Text
1.
AutoCAD SHX Text
CONCRETE ATTACHMENTS SHALL BE HILTI OR APPROVED EQUAL
AutoCAD SHX Text
FOR PIPES W/ CENTERLINE LESS THAN 18" BELOW SLAB OR BEAM
AutoCAD SHX Text
%%UNOTES:
AutoCAD SHX Text
N.T.S.
AutoCAD SHX Text
PIPE ANCHOR DETAIL
AutoCAD SHX Text
STEEL ATTACHMENTS SHALL BE WELDED OR BOLTED
AutoCAD SHX Text
SECURE TO BUILDING
AutoCAD SHX Text
CONSTRUCTION IN AN
AutoCAD SHX Text
PIPE
AutoCAD SHX Text
INSULATION
AutoCAD SHX Text
APPROVED MANNER
AutoCAD SHX Text
PIPE DIAMETERS LONG
AutoCAD SHX Text
PLATE TO BE TWO
AutoCAD SHX Text
CONCRETE OR BLDG.
AutoCAD SHX Text
STRUCTURE
AutoCAD SHX Text
WELDED THRUOUT
AutoCAD SHX Text
1/2" THICK STEEL PLATE
AutoCAD SHX Text
1.
AutoCAD SHX Text
3.
AutoCAD SHX Text
2.
AutoCAD SHX Text
OVER 3'-0" LONG WITH
AutoCAD SHX Text
2"X2"X3/16" VERTICAL
AutoCAD SHX Text
BRACE HANGER RODS
AutoCAD SHX Text
ANGLE BRACE WELD 1"
AutoCAD SHX Text
AT 24" SPACING
AutoCAD SHX Text
OR INSERT
AutoCAD SHX Text
ANCHOR BOLT
AutoCAD SHX Text
TYPICAL SEISMIC BRACING FOR PIPE DETAIL
AutoCAD SHX Text
ANGLE CLIP (DOUBLE)
AutoCAD SHX Text
1/2
AutoCAD SHX Text
3/8"
AutoCAD SHX Text
3"X3"X1/4
AutoCAD SHX Text
3", 4"
AutoCAD SHX Text
2 1/2"X2 1/2" 16 GA.
AutoCAD SHX Text
3/4
AutoCAD SHX Text
2-3/4
AutoCAD SHX Text
2-5/8
AutoCAD SHX Text
3/4"
AutoCAD SHX Text
1/2"
AutoCAD SHX Text
5/8"
AutoCAD SHX Text
5"X3"X1/2
AutoCAD SHX Text
2-5"X3"X1/2
AutoCAD SHX Text
2-5"X3"X1/2
AutoCAD SHX Text
10"
AutoCAD SHX Text
5", 6"
AutoCAD SHX Text
8"
AutoCAD SHX Text
3"X3" 12 GA.
AutoCAD SHX Text
2 1/2"X2 1/2" 16 GA.
AutoCAD SHX Text
3"X3" 12 GA.
AutoCAD SHX Text
N.T.S.
AutoCAD SHX Text
* 1 5/8 X 1 5/8 X 12 GAGE CHANNEL MAY BE USED.
AutoCAD SHX Text
PIPE SLEEVE
AutoCAD SHX Text
OVER BOLT
AutoCAD SHX Text
INSULATION
AutoCAD SHX Text
3/8
AutoCAD SHX Text
ANGLE
AutoCAD SHX Text
BOLT TO
AutoCAD SHX Text
3/8"
AutoCAD SHX Text
CLIP
AutoCAD SHX Text
3"X3"X1/4
AutoCAD SHX Text
ANGLE
AutoCAD SHX Text
2 1/2"
AutoCAD SHX Text
SIZE
AutoCAD SHX Text
PIPE
AutoCAD SHX Text
* ANGLE BRACE
AutoCAD SHX Text
2"X2" 16 GA.
AutoCAD SHX Text
PIPE
AutoCAD SHX Text
SLOPE 1/1
AutoCAD SHX Text
TRANSVERSE
AutoCAD SHX Text
ANGLE BRACE
AutoCAD SHX Text
LONGITUDINAL
AutoCAD SHX Text
ANGLE BRACE
AutoCAD SHX Text
12 GA. CLIP
AutoCAD SHX Text
BOLT WITH
AutoCAD SHX Text
LOCK WASHER
AutoCAD SHX Text
ANCHOR BOLT
AutoCAD SHX Text
%%UNOTE:
AutoCAD SHX Text
6" AND LARGER USE DUAL ROD PIPE ROLL.
AutoCAD SHX Text
ADJUSTABLE YOKE PIPE ROLL SHALL BE USED ON 4" AND 5" PIPING. ON ALL PIPING
AutoCAD SHX Text
HANGERS TO THE STRUCTURE.
AutoCAD SHX Text
PIPE SIZE AS INDICATED IN THE SPECIFICATIONS.
AutoCAD SHX Text
PROVIDE INSULATION SHIELD OR PIPE SADDLE BASED ON THE PIPING SYSTEM AND
AutoCAD SHX Text
REFER TO "TYPICAL METHOD OF SECURING HANGER RODS DETAIL" FOR ATTACHING
AutoCAD SHX Text
PIPE ROLL TYPE PIPE HANGER
AutoCAD SHX Text
N.T.S.
AutoCAD SHX Text
INSTALLATION DETAIL
AutoCAD SHX Text
HANGER ROD SCHEDULE
AutoCAD SHX Text
PIPE SIZE
AutoCAD SHX Text
12"
AutoCAD SHX Text
10"
AutoCAD SHX Text
5"
AutoCAD SHX Text
6"
AutoCAD SHX Text
8"
AutoCAD SHX Text
4"
AutoCAD SHX Text
PIPE SADDLE
AutoCAD SHX Text
(SEE NOTE 3)
AutoCAD SHX Text
PIPE ROLL
AutoCAD SHX Text
DUAL ROD
AutoCAD SHX Text
PIPE SIZE
AutoCAD SHX Text
(SEE NOTE 2)
AutoCAD SHX Text
MAX. ALLOWABLE SPACING
AutoCAD SHX Text
HANGER ROD SPACING
AutoCAD SHX Text
ROD SIZE
AutoCAD SHX Text
10'
AutoCAD SHX Text
10'
AutoCAD SHX Text
10'
AutoCAD SHX Text
10'
AutoCAD SHX Text
10'
AutoCAD SHX Text
12"
AutoCAD SHX Text
10"
AutoCAD SHX Text
5"
AutoCAD SHX Text
6"
AutoCAD SHX Text
8"
AutoCAD SHX Text
7/8" DIA.
AutoCAD SHX Text
7/8" DIA.
AutoCAD SHX Text
7/8" DIA.
AutoCAD SHX Text
5/8" DIA.
AutoCAD SHX Text
3/4" DIA.
AutoCAD SHX Text
4"
AutoCAD SHX Text
5/8" DIA.
AutoCAD SHX Text
10'
AutoCAD SHX Text
SUPPORT NUT
AutoCAD SHX Text
AND WASHER
AutoCAD SHX Text
AND WASHER
AutoCAD SHX Text
HIGH DENSITY
AutoCAD SHX Text
PIPE
AutoCAD SHX Text
INSULATION 12" LONG
AutoCAD SHX Text
INSULATION SHIELD,
AutoCAD SHX Text
PIPE ROLL (SEE NOTE 3)
AutoCAD SHX Text
INSULATION
AutoCAD SHX Text
12" LONG (SEE NOTE 2)
AutoCAD SHX Text
ADJUSTABLE YOKE
AutoCAD SHX Text
LOCKING NUT
AutoCAD SHX Text
(SEE NOTE 1)
AutoCAD SHX Text
HANGER ROD
AutoCAD SHX Text
3.
AutoCAD SHX Text
2.
AutoCAD SHX Text
1.
AutoCAD SHX Text
TEMPERATURE CONTROL CONTRACTOR
AutoCAD SHX Text
EXPANSION TANK
AutoCAD SHX Text
CONDENSATE PUMP
AutoCAD SHX Text
ENTERING AIR TEMP. DEGREES F.
AutoCAD SHX Text
DRY BULB TEMP. DEGREES F.
AutoCAD SHX Text
GENERAL CONTRACTOR
AutoCAD SHX Text
ACCESS DOOR
AutoCAD SHX Text
ELECTRICAL CONTRACTOR
AutoCAD SHX Text
CLEAN OUT
AutoCAD SHX Text
ACCESS PANEL
AutoCAD SHX Text
ENTERING WATER TEMP. DEGREES F.
AutoCAD SHX Text
CUBIC FEET PER MINUTE
AutoCAD SHX Text
GALLONS PER MINUTE
AutoCAD SHX Text
GPM
AutoCAD SHX Text
GC
AutoCAD SHX Text
EWT
AutoCAD SHX Text
ET
AutoCAD SHX Text
EC
AutoCAD SHX Text
EAT
AutoCAD SHX Text
DB
AutoCAD SHX Text
CP
AutoCAD SHX Text
CO
AutoCAD SHX Text
ATC
AutoCAD SHX Text
CFM
AutoCAD SHX Text
AP
AutoCAD SHX Text
AD
AutoCAD SHX Text
WET BULB TEMP. DEGREES F.
AutoCAD SHX Text
VARIABLE FREQUENCY DRIVE
AutoCAD SHX Text
PRESSURE DROP (FEET OF WATER)
AutoCAD SHX Text
WB
AutoCAD SHX Text
VFD
AutoCAD SHX Text
PD
AutoCAD SHX Text
LEAVING AIR TEMP. DEGREES F.
AutoCAD SHX Text
LEAVING WATER TEMP. DEGREES F.
AutoCAD SHX Text
CONDITIONING CONTRACTOR
AutoCAD SHX Text
HEATING, VENTILATING & AIR
AutoCAD SHX Text
PUMP
AutoCAD SHX Text
MAXIMUM
AutoCAD SHX Text
OUTSIDE AIR
AutoCAD SHX Text
PLUMBING CONTRACTOR
AutoCAD SHX Text
MINIMUM
AutoCAD SHX Text
P
AutoCAD SHX Text
OA
AutoCAD SHX Text
PC
AutoCAD SHX Text
LWT
AutoCAD SHX Text
MIN
AutoCAD SHX Text
MAX
AutoCAD SHX Text
LAT
AutoCAD SHX Text
HVAC
AutoCAD SHX Text
ABBREVIATIONS
AutoCAD SHX Text
PIPING
AutoCAD SHX Text
DIRECTION OF FLOW
AutoCAD SHX Text
PITCH DOWN IN DIRECTION OF ARROW
AutoCAD SHX Text
HOT WATER RETURN
AutoCAD SHX Text
HOT WATER SUPPLY
AutoCAD SHX Text
HWS
AutoCAD SHX Text
HWR
AutoCAD SHX Text
EXPANSION COMPENSATOR
AutoCAD SHX Text
TOP CONNECTION 45 OR 90 DEGREES
AutoCAD SHX Text
BOTTOM CONNECTION 45 OR 90 DEGREES
AutoCAD SHX Text
CONCENTRIC REDUCER
AutoCAD SHX Text
CAPPED PIPE
AutoCAD SHX Text
ECCENTRIC REDUCER
AutoCAD SHX Text
SIDE CONNECTION
AutoCAD SHX Text
PIPE TURN TOWARDS
AutoCAD SHX Text
PIPE TURN AWAY
AutoCAD SHX Text
UNION
AutoCAD SHX Text
MANUAL AIR ELIMINATOR
AutoCAD SHX Text
GATE VALVE W/ HOSE BIBB END
AutoCAD SHX Text
FLOW MEASURING DEVICE
AutoCAD SHX Text
AUTOMATIC AIR ELIMINATOR
AutoCAD SHX Text
"Y" STRAINER W/ BLOW DOWN, H.W. SYSTEMS
AutoCAD SHX Text
2-WAY CONTROL VALVE
AutoCAD SHX Text
FD
AutoCAD SHX Text
BALL VALVE
AutoCAD SHX Text
PIPE GUIDE
AutoCAD SHX Text
PIPE ANCHOR
AutoCAD SHX Text
BALANCING VALVE
AutoCAD SHX Text
"Y" STRAINER
AutoCAD SHX Text
BUTTERFLY VALVE
AutoCAD SHX Text
GATE VALVE
AutoCAD SHX Text
VALVES
AutoCAD SHX Text
CHWR
AutoCAD SHX Text
CHILLED WATER RETURN
AutoCAD SHX Text
CHWS
AutoCAD SHX Text
CHILLED WATER SUPPLY
AutoCAD SHX Text
ABOVE FINISHED FLOOR
AutoCAD SHX Text
AFF
AutoCAD SHX Text
COMBINATION BALANCING SHUT-OFF
AutoCAD SHX Text
ABOVE FINISHED GRADE
AutoCAD SHX Text
AFG
AutoCAD SHX Text
STATIC PRESSURE SENSOR
AutoCAD SHX Text
REVERSE ACTING THERMOSTAT
AutoCAD SHX Text
SP
AutoCAD SHX Text
T
AutoCAD SHX Text
R
AutoCAD SHX Text
TEMPERATURE CONTROLLER
AutoCAD SHX Text
REMOTE SET POINT SPACE
AutoCAD SHX Text
THERMOSTAT - MOUNT 48" A.F.F.
AutoCAD SHX Text
SP
AutoCAD SHX Text
T
AutoCAD SHX Text
EQUIPMENT DESIGNATION
AutoCAD SHX Text
GENERAL
AutoCAD SHX Text
SENSOR THERMOSTAT - MOUNT 48" A.F.F.
AutoCAD SHX Text
S
AutoCAD SHX Text
AIR SEPARATOR
AutoCAD SHX Text
AS
AutoCAD SHX Text
AIR COOLED CHILLER
AutoCAD SHX Text
ACC
AutoCAD SHX Text
: Supply fan will run continuously. Outdoor air damper modulates (in conjunction with the return air damper) to maintain the minimum fresh air CFM set point. On a call for cooling: Economizer control shall use outside air for cooling upon sensing that ambient enthalpy meets the space cooling requirements. The outside air damper shall open 100%, the return air damper shall close fully and the exhaust fan shall run on high speed. On sensing that the ambient air is not appropriate to meet the cooling requirements, the chilled water control valve shall modulate as required to meet the space cooling set point.
AutoCAD SHX Text
: During cooling season unit will be off. : When override button on thermostat is activated, unit shall enter occupied mode for 2 hours (adj.). If outdoor air is less then 40°F, heating coil valve opens 100% and face and bypass dampers modulates to maintain unoccupied heating discharge temperature set point of 80°F. If outdoor air is greater then 40°F, face & bypass dampers position for full flow across the heating coil and heating coil valve modulates to maintain unoccupied heating discharge temperature set point.
AutoCAD SHX Text
SEQUENCE OF OPERATION
AutoCAD SHX Text
EXISTING UNIT VENTILATORS (TYPICAL FOR 29)
AutoCAD SHX Text
HWR/CHWR
AutoCAD SHX Text
HWS/CHWS
AutoCAD SHX Text
Hi
AutoCAD SHX Text
Lo
AutoCAD SHX Text
O.A.
AutoCAD SHX Text
N.C.
AutoCAD SHX Text
C
AutoCAD SHX Text
HW
AutoCAD SHX Text
S.A.
AutoCAD SHX Text
N.C.
AutoCAD SHX Text
N.O.
AutoCAD SHX Text
N.O.
AutoCAD SHX Text
TO BMS
AutoCAD SHX Text
T
AutoCAD SHX Text
R.A.
AutoCAD SHX Text
1. The existing BMS is a Alerton Controls system. The existing BMS is a Alerton Controls system. 2. The Automatic Temperature Control Contractor shall modify the existing unit The Automatic Temperature Control Contractor shall modify the existing unit ventilator sequence of operation to incorporate the following cooling sequence. The existing heating sequence of operation shall remain in affect and un-modified.
AutoCAD SHX Text
Existing controls shown for reference only.
AutoCAD SHX Text
1
AutoCAD SHX Text
NOTE:
AutoCAD SHX Text
KEYED NOTE:
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
1
AutoCAD SHX Text
EXIST. CONTROL
AutoCAD SHX Text
VALVE.
AutoCAD SHX Text
Hi
AutoCAD SHX Text
Low
AutoCAD SHX Text
T
AutoCAD SHX Text
T
AutoCAD SHX Text
DIFFERENTIAL PRESSURE SWITCH SET @ 1"WC
AutoCAD SHX Text
SPLIT CORE CURRENT SENSOR
AutoCAD SHX Text
FREEZESTAT
AutoCAD SHX Text
INDUCT TEMPERATURE SENSOR
AutoCAD SHX Text
BLANK STAINLESS STEEL WALL PLATE
AutoCAD SHX Text
THERMISTOR SENSOR.
AutoCAD SHX Text
USER ADJUSTABLE THERMOSTAT
AutoCAD SHX Text
2-WAY CONTROL VALVE
AutoCAD SHX Text
=
AutoCAD SHX Text
=
AutoCAD SHX Text
=
AutoCAD SHX Text
=
AutoCAD SHX Text
=
AutoCAD SHX Text
=
AutoCAD SHX Text
=
AutoCAD SHX Text
VFD
AutoCAD SHX Text
Hi
AutoCAD SHX Text
Lo
AutoCAD SHX Text
IN DUCT COMBINATION HUMIDITY/
AutoCAD SHX Text
=
AutoCAD SHX Text
SMOKE DETECTOR. INSTALLED BY
AutoCAD SHX Text
=
AutoCAD SHX Text
RELAY, SPDT
AutoCAD SHX Text
=
AutoCAD SHX Text
DAMPER ACTUATOR
AutoCAD SHX Text
=
AutoCAD SHX Text
DIFFERENTIAL PRESSURE TRANSDUCER
AutoCAD SHX Text
=
AutoCAD SHX Text
VARIABLE FREQUENCY DRIVE
AutoCAD SHX Text
=
AutoCAD SHX Text
TEMPERATURE SENSOR
AutoCAD SHX Text
MECHANICAL CONTRACTOR, FURNISHED AND
AutoCAD SHX Text
WIRED BY ELECTRICAL CONTRACTOR
AutoCAD SHX Text
T
AutoCAD SHX Text
REVERSE ACTING THERMOSTAT
AutoCAD SHX Text
=
AutoCAD SHX Text
R
AutoCAD SHX Text
APPLICATION SPECIFIC CONTROLLER
AutoCAD SHX Text
=
AutoCAD SHX Text
FURNISHED BY ATC
AutoCAD SHX Text
AUTOMATIC TEMPERATURE CONTROLS
AutoCAD SHX Text
=
AutoCAD SHX Text
BUILDING MANAGEMENT SYSTEM
AutoCAD SHX Text
=
AutoCAD SHX Text
ATC
AutoCAD SHX Text
BMS
AutoCAD SHX Text
68
AutoCAD SHX Text
MCA
AutoCAD SHX Text
MOCP
AutoCAD SHX Text
206.5
AutoCAD SHX Text
225
AutoCAD SHX Text
2
AutoCAD SHX Text
CHILLER SHALL BE FURNISHED WITH UNIT MOUNTED DISCONNECT AND SERVICE OUTLET.
AutoCAD SHX Text
2
AutoCAD SHX Text
SOUND PRESS. dB(A)@30'
AutoCAD SHX Text
Keyplan
AutoCAD SHX Text
Scale:
AutoCAD SHX Text
Job No.:
AutoCAD SHX Text
Drawn By:
AutoCAD SHX Text
Date:
AutoCAD SHX Text
Drawing Number:
AutoCAD SHX Text
Drawing Name:
AutoCAD SHX Text
North Arrow
AutoCAD SHX Text
January 31, 2019
AutoCAD SHX Text
1GV-223
AutoCAD SHX Text
Notes:
AutoCAD SHX Text
12 Kendrick Road
AutoCAD SHX Text
Wareham, MA 02571
AutoCAD SHX Text
508-295-0050 (T)
AutoCAD SHX Text
508-295-0003 (F)
AutoCAD SHX Text
www.griffithandvary.com
AutoCAD SHX Text
Town of Arlington, Massachusetts
AutoCAD SHX Text
DALLIN ELEMENTARY SCHOOL CHILLER PROJECT
AutoCAD SHX Text
MECHANICAL
AutoCAD SHX Text
LEGEND, DETAILS
AutoCAD SHX Text
AND SCHEDULES
Page 2: Sequence of Operation Air-Cooled Chiller

Sequence of Operation

Air-Cooled Chiller

Consulting EngineersGRIFFITH & VARY, INC.

AutoCAD SHX Text
UP
AutoCAD SHX Text
UP
AutoCAD SHX Text
CORRIDOR
AutoCAD SHX Text
175
AutoCAD SHX Text
TEACHER PLANNING
AutoCAD SHX Text
142
AutoCAD SHX Text
CUST.
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
176
AutoCAD SHX Text
EMERGENCY ELEC.
AutoCAD SHX Text
141
AutoCAD SHX Text
ELECTRICAL
AutoCAD SHX Text
139
AutoCAD SHX Text
MECHANICAL
AutoCAD SHX Text
138
AutoCAD SHX Text
STAIR # 2-1
AutoCAD SHX Text
192
AutoCAD SHX Text
6"
AutoCAD SHX Text
HWR
AutoCAD SHX Text
CHWR
AutoCAD SHX Text
CHWS
AutoCAD SHX Text
6"
AutoCAD SHX Text
6"
AutoCAD SHX Text
6"
AutoCAD SHX Text
6"
AutoCAD SHX Text
1-1/4"
AutoCAD SHX Text
6"
AutoCAD SHX Text
4"
AutoCAD SHX Text
D
AutoCAD SHX Text
C
AutoCAD SHX Text
B
AutoCAD SHX Text
A
AutoCAD SHX Text
1
AutoCAD SHX Text
2
AutoCAD SHX Text
2.1
AutoCAD SHX Text
3
AutoCAD SHX Text
3.1
AutoCAD SHX Text
3.3
AutoCAD SHX Text
CONCRETE PAD BY
AutoCAD SHX Text
MECHANICAL CONTRACTOR
AutoCAD SHX Text
COORDINATE PAD REQUIREMENTS
AutoCAD SHX Text
WITH CHILLER MANUFACTURER.
AutoCAD SHX Text
REFER TO PAD DETAIL (THIS DWG).
AutoCAD SHX Text
AIR COOLED CHILLER MOUNTED ON
AutoCAD SHX Text
6" HIGH CONCRETE PAD.
AutoCAD SHX Text
ACC
AutoCAD SHX Text
1
AutoCAD SHX Text
EXISTING VFD-1 TO REMAIN.
AutoCAD SHX Text
EXISTING VFD-2 TO REMAIN.
AutoCAD SHX Text
EXISTING P-1 TO REMAIN.
AutoCAD SHX Text
EXISTING P-2 TO REMAIN.
AutoCAD SHX Text
EXISTING B-1 TO REMAIN.
AutoCAD SHX Text
EXISTING B-2 TO REMAIN.
AutoCAD SHX Text
EXISTING B-3 TO REMAIN.
AutoCAD SHX Text
EXISTING UH-1 TO REMAIN.
AutoCAD SHX Text
4"
AutoCAD SHX Text
4"
AutoCAD SHX Text
6"
AutoCAD SHX Text
NEW 6" CHWS & CHWR DN.
AutoCAD SHX Text
INTO EXISTING PIT. MECH. CONT'R
AutoCAD SHX Text
SHALL MODIFY GRATE TO ACCOMMODATE
AutoCAD SHX Text
NEW PIPING.
AutoCAD SHX Text
CONNECT NEW 6" CHWS &
AutoCAD SHX Text
CHWR TO EXISTING VALVED
AutoCAD SHX Text
TAKE-OFFS.
AutoCAD SHX Text
EXISTING 6" CHWR
AutoCAD SHX Text
& CHWS
AutoCAD SHX Text
6"
AutoCAD SHX Text
MECHANICAL CONTRACTOR SHALL
AutoCAD SHX Text
EXCAVATE AREA TO INSTALL NEW
AutoCAD SHX Text
PRE-INSULATED PIPING IN THIS
AutoCAD SHX Text
AREA. AND SHALL PROPERLY
AutoCAD SHX Text
BACKFILL, COVER AND GRADE
AutoCAD SHX Text
AREA AFTER INSTALLATION AND
AutoCAD SHX Text
PRESSURE TESTING OF PIPING
AutoCAD SHX Text
NEW 6" CHWR & CHWS SHALL
AutoCAD SHX Text
PASS THROUGH EXISTING 10" DIA.
AutoCAD SHX Text
UNDERGROUND CONDUIT.
AutoCAD SHX Text
REFER TO CHILLED WATER
AutoCAD SHX Text
FLOW DIAGRAM FOR CHILLED
AutoCAD SHX Text
WATER PIPING WATER PIPING
AutoCAD SHX Text
AT CHILLER. (THIS DWG.)
AutoCAD SHX Text
MECHANICAL CONTRACTOR
AutoCAD SHX Text
SHALL FURNISHED AND
AutoCAD SHX Text
INSTALL NEW 8' HIGH
AutoCAD SHX Text
CHAIN LINK FENCE WITH
AutoCAD SHX Text
GATE TO PROTECT CHILLER.
AutoCAD SHX Text
MECHANICAL CONTRACTOR SHALL
AutoCAD SHX Text
VERIFY SERVICE CLEARANCE
AutoCAD SHX Text
REQUIREMENTS WITH CHILLER
AutoCAD SHX Text
MANUFACTURER PRIOR TO
AutoCAD SHX Text
INSTALLATION OF FENCE.
AutoCAD SHX Text
TYPICAL FOR ALL SIDES.
AutoCAD SHX Text
ELECTRICAL CONTRACTOR SHALL
AutoCAD SHX Text
CONFIRM EXACT LOCATION OF
AutoCAD SHX Text
INTEGRAL DISCONNECT SWITCH
AutoCAD SHX Text
IN FIELD.
AutoCAD SHX Text
UNDERGROUND PIPING
AutoCAD SHX Text
RIC-WIL "TERA-GARD"
AutoCAD SHX Text
INTEGRAL SERVICE
AutoCAD SHX Text
RECEPTACLE
AutoCAD SHX Text
PROVIDE 4#4/0+1#4G
AutoCAD SHX Text
- 2-1/2"C, 36" BELOW
AutoCAD SHX Text
FINISHED GRADE.
AutoCAD SHX Text
EXISTING 1200 AMP, 277/480 VOLT, THREE
AutoCAD SHX Text
PHASE FOUR WIRE SWITCHBOARD AS MANUFACTURED
AutoCAD SHX Text
BY G.E. PROVIDE NEW 225/3 CIRCUIT BREAKER IN
AutoCAD SHX Text
EXISTING SWITCHBOARD TO MATCH EXISTING, FOR
AutoCAD SHX Text
FEEDING AIR COOLED CHILLER ACC-1.
AutoCAD SHX Text
WP
AutoCAD SHX Text
PRESSURE GAUGE
AutoCAD SHX Text
W/ 1/4" BALL VALVE (TYP.)
AutoCAD SHX Text
THERMOMETER
AutoCAD SHX Text
FLEX. CONNECTION
AutoCAD SHX Text
BUTTERFLY VALVE (TYP.)
AutoCAD SHX Text
2" DRAIN OFF
AutoCAD SHX Text
VALVE W/CAP
AutoCAD SHX Text
& CHAIN
AutoCAD SHX Text
HIGH VENT 1/4" BALL
AutoCAD SHX Text
VALVE W/PLUGGED END
AutoCAD SHX Text
ACC
AutoCAD SHX Text
1
AutoCAD SHX Text
4"
AutoCAD SHX Text
4"
AutoCAD SHX Text
EXIST. EXPANSION TANKS
AutoCAD SHX Text
4"
AutoCAD SHX Text
4"
AutoCAD SHX Text
4"
AutoCAD SHX Text
SYSTEM PUMPS
AutoCAD SHX Text
EXIST. HEATING-COOLING
AutoCAD SHX Text
GV
AutoCAD SHX Text
4"
AutoCAD SHX Text
GV
AutoCAD SHX Text
4"
AutoCAD SHX Text
TO SYSTEM
AutoCAD SHX Text
1"
AutoCAD SHX Text
1"
AutoCAD SHX Text
4" SUCTION HEADER
AutoCAD SHX Text
4"
AutoCAD SHX Text
1"
AutoCAD SHX Text
1"
AutoCAD SHX Text
1
AutoCAD SHX Text
1"
AutoCAD SHX Text
/
AutoCAD SHX Text
2
AutoCAD SHX Text
1" BLOW
AutoCAD SHX Text
EXIST. AIR SEPARATOR
AutoCAD SHX Text
DOWN
AutoCAD SHX Text
4"
AutoCAD SHX Text
2
AutoCAD SHX Text
/
AutoCAD SHX Text
1"
AutoCAD SHX Text
1
AutoCAD SHX Text
PITCH UP
AutoCAD SHX Text
4"
AutoCAD SHX Text
AV
AutoCAD SHX Text
1"
AutoCAD SHX Text
4"
AutoCAD SHX Text
2"
AutoCAD SHX Text
2"
AutoCAD SHX Text
2"
AutoCAD SHX Text
CIRCUIT SETTER (TYP)
AutoCAD SHX Text
ATFL
AutoCAD SHX Text
ATFL
AutoCAD SHX Text
EXIST. BOILERS
AutoCAD SHX Text
6" CONCRETE PAD BY
AutoCAD SHX Text
MECHANICAL CONTRACTOR
AutoCAD SHX Text
GROUND
AutoCAD SHX Text
FROM SYSTEM
AutoCAD SHX Text
2" DRAIN VALVES
AutoCAD SHX Text
W/ CAPS & CHAINS.
AutoCAD SHX Text
EXISTING 4" CHWR CROSS
AutoCAD SHX Text
CONNECTION.
AutoCAD SHX Text
EXISTING VALVE OPEN
AutoCAD SHX Text
FOR HEATING, CLOSE
AutoCAD SHX Text
FOR COOLING.
AutoCAD SHX Text
EXISTING VALVES CLOSE
AutoCAD SHX Text
FOR HEATING, OPEN
AutoCAD SHX Text
FOR COOLING.
AutoCAD SHX Text
2" DRAIN OFF VALVE
AutoCAD SHX Text
W/CAP & CHAIN.
AutoCAD SHX Text
EXISTING VALVE. OPEN FOR
AutoCAD SHX Text
HEATING, CLOSE FOR COOLING.
AutoCAD SHX Text
EXISTING VALVE. CLOSE FOR HEATING,
AutoCAD SHX Text
OPEN FOR COOLING.
AutoCAD SHX Text
EXISTING VALVE. OPEN FOR
AutoCAD SHX Text
HEATING, CLOSE FOR COOLING.
AutoCAD SHX Text
EXISTING
AutoCAD SHX Text
DRAIN DN.
AutoCAD SHX Text
PIT
AutoCAD SHX Text
PRE-INSULATED PIPING
AutoCAD SHX Text
RIC-WIL "TERA-GARD"
AutoCAD SHX Text
PRE-INSULATED PIPING
AutoCAD SHX Text
RIC-WIL "TERA-GARD"
AutoCAD SHX Text
1. The chiller plant shall be controlled by a networked DDC system. Functions shall include The chiller plant shall be controlled by a networked DDC system. Functions shall include chiller plant shall be controlled by a networked DDC system. Functions shall include chiller plant shall be controlled by a networked DDC system. Functions shall include plant shall be controlled by a networked DDC system. Functions shall include plant shall be controlled by a networked DDC system. Functions shall include shall be controlled by a networked DDC system. Functions shall include shall be controlled by a networked DDC system. Functions shall include be controlled by a networked DDC system. Functions shall include be controlled by a networked DDC system. Functions shall include controlled by a networked DDC system. Functions shall include controlled by a networked DDC system. Functions shall include by a networked DDC system. Functions shall include by a networked DDC system. Functions shall include a networked DDC system. Functions shall include a networked DDC system. Functions shall include networked DDC system. Functions shall include networked DDC system. Functions shall include DDC system. Functions shall include DDC system. Functions shall include system. Functions shall include system. Functions shall include Functions shall include Functions shall include shall include shall include include include chiller sequencing, chilled water pump speed control and monitoring of all sensors. 2. All set points given in written sequence(s) of operation shall be field adjustable and All set points given in written sequence(s) of operation shall be field adjustable and set points given in written sequence(s) of operation shall be field adjustable and set points given in written sequence(s) of operation shall be field adjustable and points given in written sequence(s) of operation shall be field adjustable and points given in written sequence(s) of operation shall be field adjustable and given in written sequence(s) of operation shall be field adjustable and given in written sequence(s) of operation shall be field adjustable and in written sequence(s) of operation shall be field adjustable and in written sequence(s) of operation shall be field adjustable and written sequence(s) of operation shall be field adjustable and written sequence(s) of operation shall be field adjustable and sequence(s) of operation shall be field adjustable and sequence(s) of operation shall be field adjustable and of operation shall be field adjustable and of operation shall be field adjustable and operation shall be field adjustable and operation shall be field adjustable and shall be field adjustable and shall be field adjustable and be field adjustable and be field adjustable and field adjustable and field adjustable and adjustable and adjustable and and and subject to software reset. 3. Local chiller control panel provided by the chiller manufacturer shall control all operating Local chiller control panel provided by the chiller manufacturer shall control all operating chiller control panel provided by the chiller manufacturer shall control all operating chiller control panel provided by the chiller manufacturer shall control all operating control panel provided by the chiller manufacturer shall control all operating control panel provided by the chiller manufacturer shall control all operating panel provided by the chiller manufacturer shall control all operating panel provided by the chiller manufacturer shall control all operating provided by the chiller manufacturer shall control all operating provided by the chiller manufacturer shall control all operating by the chiller manufacturer shall control all operating by the chiller manufacturer shall control all operating the chiller manufacturer shall control all operating the chiller manufacturer shall control all operating chiller manufacturer shall control all operating chiller manufacturer shall control all operating manufacturer shall control all operating manufacturer shall control all operating shall control all operating shall control all operating control all operating control all operating all operating all operating operating operating functions associated with starting, stopping and unloading of the chiller. All safety and associated with starting, stopping and unloading of the chiller. All safety and associated with starting, stopping and unloading of the chiller. All safety and with starting, stopping and unloading of the chiller. All safety and with starting, stopping and unloading of the chiller. All safety and starting, stopping and unloading of the chiller. All safety and starting, stopping and unloading of the chiller. All safety and stopping and unloading of the chiller. All safety and stopping and unloading of the chiller. All safety and and unloading of the chiller. All safety and and unloading of the chiller. All safety and unloading of the chiller. All safety and unloading of the chiller. All safety and of the chiller. All safety and of the chiller. All safety and the chiller. All safety and the chiller. All safety and chiller. All safety and chiller. All safety and All safety and All safety and All safety and safety and safety and and and high/low limits shall be interlocked within the local chiller control panels. 4. Communication between BMS and chiller shall be via BACnet interface to the chillers' digital Communication between BMS and chiller shall be via BACnet interface to the chillers' digital between BMS and chiller shall be via BACnet interface to the chillers' digital between BMS and chiller shall be via BACnet interface to the chillers' digital BMS and chiller shall be via BACnet interface to the chillers' digital BMS and chiller shall be via BACnet interface to the chillers' digital and chiller shall be via BACnet interface to the chillers' digital and chiller shall be via BACnet interface to the chillers' digital chiller shall be via BACnet interface to the chillers' digital chiller shall be via BACnet interface to the chillers' digital shall be via BACnet interface to the chillers' digital shall be via BACnet interface to the chillers' digital be via BACnet interface to the chillers' digital be via BACnet interface to the chillers' digital via BACnet interface to the chillers' digital via BACnet interface to the chillers' digital BACnet interface to the chillers' digital BACnet interface to the chillers' digital interface to the chillers' digital interface to the chillers' digital to the chillers' digital to the chillers' digital the chillers' digital the chillers' digital chillers' digital chillers' digital digital digital control panels. Chiller shall be brought on line via a signal from the DDC system in panels. Chiller shall be brought on line via a signal from the DDC system in panels. Chiller shall be brought on line via a signal from the DDC system in Chiller shall be brought on line via a signal from the DDC system in Chiller shall be brought on line via a signal from the DDC system in Chiller shall be brought on line via a signal from the DDC system in shall be brought on line via a signal from the DDC system in shall be brought on line via a signal from the DDC system in be brought on line via a signal from the DDC system in be brought on line via a signal from the DDC system in brought on line via a signal from the DDC system in brought on line via a signal from the DDC system in on line via a signal from the DDC system in on line via a signal from the DDC system in line via a signal from the DDC system in line via a signal from the DDC system in via a signal from the DDC system in via a signal from the DDC system in a signal from the DDC system in a signal from the DDC system in signal from the DDC system in signal from the DDC system in from the DDC system in from the DDC system in the DDC system in the DDC system in DDC system in DDC system in system in system in in in addition, chilled water set point and demand limit levels shall be controlled by the DDC chilled water set point and demand limit levels shall be controlled by the DDC chilled water set point and demand limit levels shall be controlled by the DDC water set point and demand limit levels shall be controlled by the DDC water set point and demand limit levels shall be controlled by the DDC set point and demand limit levels shall be controlled by the DDC set point and demand limit levels shall be controlled by the DDC point and demand limit levels shall be controlled by the DDC point and demand limit levels shall be controlled by the DDC and demand limit levels shall be controlled by the DDC and demand limit levels shall be controlled by the DDC demand limit levels shall be controlled by the DDC demand limit levels shall be controlled by the DDC limit levels shall be controlled by the DDC limit levels shall be controlled by the DDC levels shall be controlled by the DDC levels shall be controlled by the DDC shall be controlled by the DDC shall be controlled by the DDC be controlled by the DDC be controlled by the DDC controlled by the DDC controlled by the DDC by the DDC by the DDC the DDC the DDC DDC DDC system. 5. The DDC system shall enable chilled water plant operation whenever outdoor ambient The DDC system shall enable chilled water plant operation whenever outdoor ambient DDC system shall enable chilled water plant operation whenever outdoor ambient DDC system shall enable chilled water plant operation whenever outdoor ambient system shall enable chilled water plant operation whenever outdoor ambient system shall enable chilled water plant operation whenever outdoor ambient shall enable chilled water plant operation whenever outdoor ambient shall enable chilled water plant operation whenever outdoor ambient enable chilled water plant operation whenever outdoor ambient enable chilled water plant operation whenever outdoor ambient chilled water plant operation whenever outdoor ambient chilled water plant operation whenever outdoor ambient water plant operation whenever outdoor ambient water plant operation whenever outdoor ambient plant operation whenever outdoor ambient plant operation whenever outdoor ambient operation whenever outdoor ambient operation whenever outdoor ambient whenever outdoor ambient whenever outdoor ambient outdoor ambient outdoor ambient ambient ambient temperature is above 65ºF (adj.) and a requirement for chilled water exists from the air is above 65ºF (adj.) and a requirement for chilled water exists from the air is above 65ºF (adj.) and a requirement for chilled water exists from the air above 65ºF (adj.) and a requirement for chilled water exists from the air above 65ºF (adj.) and a requirement for chilled water exists from the air 65ºF (adj.) and a requirement for chilled water exists from the air 65ºF (adj.) and a requirement for chilled water exists from the air (adj.) and a requirement for chilled water exists from the air (adj.) and a requirement for chilled water exists from the air and a requirement for chilled water exists from the air and a requirement for chilled water exists from the air a requirement for chilled water exists from the air a requirement for chilled water exists from the air requirement for chilled water exists from the air requirement for chilled water exists from the air for chilled water exists from the air for chilled water exists from the air chilled water exists from the air chilled water exists from the air water exists from the air water exists from the air exists from the air exists from the air from the air from the air the air the air air air handling units. 6. The DDC system shall continuously monitor chilled water demand and enable and stage The DDC system shall continuously monitor chilled water demand and enable and stage DDC system shall continuously monitor chilled water demand and enable and stage DDC system shall continuously monitor chilled water demand and enable and stage system shall continuously monitor chilled water demand and enable and stage system shall continuously monitor chilled water demand and enable and stage shall continuously monitor chilled water demand and enable and stage shall continuously monitor chilled water demand and enable and stage continuously monitor chilled water demand and enable and stage continuously monitor chilled water demand and enable and stage monitor chilled water demand and enable and stage monitor chilled water demand and enable and stage chilled water demand and enable and stage chilled water demand and enable and stage water demand and enable and stage water demand and enable and stage demand and enable and stage demand and enable and stage and enable and stage and enable and stage enable and stage enable and stage and stage and stage stage stage chiller capacity as needed. 7. The DDC system shall be capable of resetting chilled water supply temperature via operator The DDC system shall be capable of resetting chilled water supply temperature via operator DDC system shall be capable of resetting chilled water supply temperature via operator DDC system shall be capable of resetting chilled water supply temperature via operator system shall be capable of resetting chilled water supply temperature via operator system shall be capable of resetting chilled water supply temperature via operator shall be capable of resetting chilled water supply temperature via operator shall be capable of resetting chilled water supply temperature via operator be capable of resetting chilled water supply temperature via operator be capable of resetting chilled water supply temperature via operator capable of resetting chilled water supply temperature via operator capable of resetting chilled water supply temperature via operator of resetting chilled water supply temperature via operator of resetting chilled water supply temperature via operator resetting chilled water supply temperature via operator resetting chilled water supply temperature via operator chilled water supply temperature via operator chilled water supply temperature via operator water supply temperature via operator water supply temperature via operator supply temperature via operator supply temperature via operator temperature via operator temperature via operator via operator via operator operator operator command from the system front end. Normal chiller water supply temperature shall be from the system front end. Normal chiller water supply temperature shall be from the system front end. Normal chiller water supply temperature shall be the system front end. Normal chiller water supply temperature shall be the system front end. Normal chiller water supply temperature shall be system front end. Normal chiller water supply temperature shall be system front end. Normal chiller water supply temperature shall be front end. Normal chiller water supply temperature shall be front end. Normal chiller water supply temperature shall be end. Normal chiller water supply temperature shall be end. Normal chiller water supply temperature shall be Normal chiller water supply temperature shall be Normal chiller water supply temperature shall be Normal chiller water supply temperature shall be chiller water supply temperature shall be chiller water supply temperature shall be water supply temperature shall be water supply temperature shall be supply temperature shall be supply temperature shall be temperature shall be temperature shall be shall be shall be be be 44ºF.
AutoCAD SHX Text
a. When the chiller is brought online, its 2-way control valve shall modulate open. When the chiller is brought online, its 2-way control valve shall modulate open. b. The chilled water pump shall start and ramp up to 100% speed via its associated The chilled water pump shall start and ramp up to 100% speed via its associated variable frequency drive. c. By-pass control valve shall modulate open as necessary to maintain 100% design By-pass control valve shall modulate open as necessary to maintain 100% design flow rate through the chiller as sensed by flow meter. Refer to "Minimum Evaporator Control" below. d. Chillers chilled water D/P switch must prove "ON" to enable chiller. Chillers chilled water D/P switch must prove "ON" to enable chiller. e. If any of the status points fail to prove, an alarm shall be issued to the If any of the status points fail to prove, an alarm shall be issued to the operator's workstation. f. If the above status points all prove, the chiller shall be commanded to start. If the above status points all prove, the chiller shall be commanded to start. g. The chiller shall operate under control of its packaged control panel. The chiller shall operate under control of its packaged control panel. h. After the chiller has started, and the leaving chilled water temperature has After the chiller has started, and the leaving chilled water temperature has reached setpoint and is stable, the chilled water pump speed control shall switch to differential pressure control (See below). i. At the same time that the chilled water pump control switches to differential At the same time that the chilled water pump control switches to differential pressure control, the control of by-pass valve shall switch to minimum evaporator flow control (See below).
AutoCAD SHX Text
a. Chiller Operation Chiller Operation 1) After setpoint is achieved and chilled water temperature is stable, the by-pass After setpoint is achieved and chilled water temperature is stable, the by-pass valve shall modulate to maintain minimum chilled water flow through the evaporator of the lead chiller, as verified by chiller manufacturer. The flow rate shall be measured by the flow meter. 2) On a drop below minimum flow setpoint, the by-pass valve shall modulate open. On a drop below minimum flow setpoint, the by-pass valve shall modulate open. 3) If the by-pass valve reaches 100% open position and the flow rate remains If the by-pass valve reaches 100% open position and the flow rate remains below setpoint, differential pressure setpoints shall be reset to their initial settings (See "Differential Pressure Control" below). 4) On start up of the chiller, the setpoint for the evaporator flow shall be 100% of On start up of the chiller, the setpoint for the evaporator flow shall be 100% of design flow for that chiller.
AutoCAD SHX Text
a. Differential pressure sensors located at the ends of the chilled water mains shall be Differential pressure sensors located at the ends of the chilled water mains shall be the basis chilled water pump control. b. The differential pressure sensor shall have a distinct set point to be determined during The differential pressure sensor shall have a distinct set point to be determined during testing and balancing and confirmed during the commissioning phase of the project (Initially 10 psi). c. The chilled water pump speed shall be modulated via its associated variable frequency The chilled water pump speed shall be modulated via its associated variable frequency drive to maintain the sensor (As defined above) at its setpoint.
AutoCAD SHX Text
Keyplan
AutoCAD SHX Text
Scale:
AutoCAD SHX Text
Job No.:
AutoCAD SHX Text
Drawn By:
AutoCAD SHX Text
Date:
AutoCAD SHX Text
Drawing Number:
AutoCAD SHX Text
Drawing Name:
AutoCAD SHX Text
North Arrow
AutoCAD SHX Text
January 31, 2019
AutoCAD SHX Text
1GV-223
AutoCAD SHX Text
Notes:
AutoCAD SHX Text
12 Kendrick Road
AutoCAD SHX Text
Wareham, MA 02571
AutoCAD SHX Text
508-295-0050 (T)
AutoCAD SHX Text
508-295-0003 (F)
AutoCAD SHX Text
www.griffithandvary.com
AutoCAD SHX Text
Town of Arlington, Massachusetts
AutoCAD SHX Text
DALLIN ELEMENTARY SCHOOL CHILLER PROJECT
AutoCAD SHX Text
MECHANICAL
AutoCAD SHX Text
ROOM PART PLAN
AutoCAD SHX Text
& CHILLED WATER
AutoCAD SHX Text
FLOW DIAGRAM
AutoCAD SHX Text
As Noted
AutoCAD SHX Text
JAJ
AutoCAD SHX Text
M-2
AutoCAD SHX Text
MECHANICAL ROOM PART PLAN
AutoCAD SHX Text
SCALE: 1/4"=1'-0"
AutoCAD SHX Text
CHILLED WATER FLOW DIAGRAM
AutoCAD SHX Text
N.T.S.
AutoCAD SHX Text
CONCRETE EQUIPMENT PAD DETAIL
AutoCAD SHX Text
SCALE: N.T.S.
AutoCAD SHX Text
CHILLER SEQUENCE OF OPERATION
AutoCAD SHX Text
SCALE: N.T.S.