PR electronics A/S Lerbakken 10 . DK-8410 Rønde
Tl f . 8637 2677 . Fax. 8637 3085www.prelectronics.dk . [email protected]
PRetop 5335D
INMETRO
Segurança
OCP 0034
2-WIRE TRANSMITTER WITH HART® PROTOCOL
Application:
•LinearisedtemperaturemeasurementwithPt100...Pt1000, Ni100...Ni1000, or TC sensor.
•Differenceoraveragetemperaturemeasurementof2resistanceorTCsensors.
•Conversionoflinearresistancevariationtoastandardanaloguecurrentsignal,forinstancefromvalvesorOhmiclevelsensors.
•AmplificationofabipolarmVsignaltoastandard4...20mAcurrentsignal.
•Connectionofupto15transmitterstoadigital2-wiresignalwithHART®communication.
Technical characteristics:
•WithinafewsecondstheusercanprogramPR5335Dtomeasuretemperatureswithinallrangesdefinedbythenorms.
•TheRTDandresistanceinputshavecablecompensationfor2-,3-and4-wireconnection.
•The5335Dhasbeendesignedaccordingtostrictsafetyrequirementsandisthussuitablefor application in SIL 2 installations.
•Continuouscheckofvitalstoreddataforsafetyreasons.
•SensorerrordetectionaccordingtotheguidelinesinNAMURNE89.
Mounting / installation:
•ForDINformBsensorheadmounting.
•NB: AsExbarrierwerecommend5106B.
RTD, TC, Ohm, or mV input
Galvanic isolation
For DIN form B sensor head mounting
Extremely high measurement accuracy
HART® communication
+-
+-
V+
mA
V+
mA
+-
+-
V+
mA
+-
+-
V+
mA
V+
mA
+-
+-
+-
+-
+-
+-
+-
+-
+-
+-
21
2
21
1
RTD to 4...20 mA
TC to 4...20 mA
Resistance to 4...20 mA
Difference or averageRTD, TC or mV
2-wire installationin control room
2-wire installationin control room
2-wire installationin control room
2-wire installationin control room
mV to 4...20 mA2-wire installationin control room
Electrical specifications:Specifications range:-40°C to +85°CCommon specifications:Supplyvoltage ................................... 8.0...30VDC Voltagedrop ...................................... 8.0VDC Isolationvoltage,test/operation ...... 1.5kVAC/50VAC Communicationsinterface ................ LoopLink&HART® Signal/noiseratio ............................. Min.60dB Signaldynamics,input ...................... 22 bit Signaldynamics,output .................... 16 bit Calibrationtemperature ..................... 20...28°C Accuracy,thegreaterofgeneralandbasicvalues:
Vibration ............................................ IEC60068-2-6TestFC Lloyd’sspecificationno.1 ................. 4g/2...100Hz Humidity ............................................ <95%RH(non-cond.) Dimensions ........................................ Ø44x20.2mm Protectiondegree(encl./terminals) ... IP68 / IP00Electrical specifications, input:Max.offset ......................................... 50%ofselect.max.valueRTD and linear resistance input:
Cableresistanceperwire(max.) ....... 5 Ω (upto50Ωperwireispossiblewith reducedmeasurementaccuracy)Sensorcurrent ................................... Nom.0.2mA
Voltage input:Measurementrange .......................... -800...+800mVMin.span ........................................... 2.5mV Inputresistance ................................. 10MΩTC input:
Coldjunctioncompensation ............. < ±1.0°CCurrent output:Signalrange ...................................... 4...20mA Min.signalrange ............................... 16mA Updatingtime .................................... 440ms Load resistance ................................. ≤ (Vsupply-8)/0.023[Ω]Sensor error detection:Programmable ................................... 3.5...23mA
Of span=Ofthepresentlyselectedrange
Approvals:EMC2004/108/EC ............................ EN61326-1GOSTRMarine approval:DetNorskeVeritas,Ships&Offshore .. Stand. for Certific. No. 2.4I.S. / Ex:ATEX94/9/EC .................................... KEMA03ATEX1537 IECEx ................................................. KEM10.0083X FMcertificate ..................................... 2D5A7 CSA certificate................................... 1125003 INMETROcertificate .......................... NCC12.0844XGOSTExFunctional Safety:HardwareassessedforuseinSILapplicationsFMEDAreport-www.prelectronics.com
5335DY115-UK(1242)
5335D
Order: 5335D
Type
3 4 65
3 4 65
3 4 65
3 4 65
3 4 65
3 4 65
3 4 65
+-
3 4 65
+-
3 4 65
+-
1 2
mA -+
3 4 65
12
3 4 65
+
-1
+
-2
3 4 65
+
-
+
-
12
Connections:Output:
2-wire installation
Input:
Resistance, 2-wire Resistance, 3-wire Resistance, 4-wire
TC, internal CJC TC, external CJC mVRTD, 2-wire RTD, 3-wire RTD, 4-wire
TC, differenceor average
mV, differenceor average
RTD, differenceor average
RTD type
Min. value
Max. value
Min. span Standard
Pt100 Ni100 Lin. R
-200°C -60°C
0 Ω
+850°C +250°C 7000 Ω
10°C 10°C 25 Ω
IEC60751 DIN 43760
-----
Basic values
Inputtype
Basic accuracy
Temperature coefficient
Pt100 and Pt1000 ≤ ±0.1°C ≤ ±0.005°C/°C
Ni100 ≤ ±0.2°C ≤ ±0.005°C/°C
Lin. R ≤ ±0.1 Ω ≤±5mΩ / °C
Volt ≤ ±10 µV ≤ ±0.5 µV / °C
TCtype: E,J,K,L,N,T,U
≤ ±0.5°C
≤ ±0.025°C / °C
TCtype: B,R,S,W3,W5
≤ ±1°C
≤ ±0.1°C / °C
EMCimmunityinfluence ........................... <±0.1%ofspanExtendedEMCimmunity:NAMUR NE 21, Acriterion,burst .............. <±1%ofspan
General values
Inputtype
Absolute accuracy
Temperature coefficient
All ≤±0.05%ofspan ≤±0.005%ofspan/°C
Type
Min. temperature
Max. temperature
Min. span
Standard
B E J K L N R S T U W3 W5
+400°C -100°C -100°C -180°C -100°C -180°C
-50°C -50°C
-200°C -200°C
0°C 0°C
+1820°C +1000°C +1200°C +1372°C +900°C
+1300°C +1760°C +1760°C
+400°C +600°C
+2300°C +2300°C
100°C 50°C 50°C 50°C 50°C 50°C
100°C 100°C
50°C 50°C
100°C 100°C
IEC584 IEC584 IEC584 IEC584
DIN 43710 IEC584 IEC584 IEC584 IEC584
DIN 43710 ASTME988-90 ASTME988-90