Sectionalizing Presentation

Embed Size (px)

Citation preview

  • 7/27/2019 Sectionalizing Presentation

    1/82

    Sectionalizing

    Rick Seeling Introduction

    Philosophy

    Pete Malamen

    Three Phase Reclosers

    High-Side Protection Specific Applications

  • 7/27/2019 Sectionalizing Presentation

    2/82

    History Early 1970s

    Small Substation Transformers

  • 7/27/2019 Sectionalizing Presentation

    3/82

    History - Present

    Larger Substation Transformers >5,000 kVA Single Phase Reclosers 4H & L Three Phase Reclosers w/ Single Phase Trip

    Select Settings on Panel Sequential Coordination Standard

    Automation Multiple Options

    Switchgear w/ E fuses for UG Protection Three Phase Circuit Switcher/Transducer High-Side Protection Solid-State Relays w/ many Options 30 Ohm Minimum Fault resistance

    Larger Single Phase Reclosers

    Use Largest Recloser Possible

  • 7/27/2019 Sectionalizing Presentation

    4/82

    Sectionalizing Publications

    REA/RUS Bulletin 61-2 Guide for MakingSectionalizing Study on Rural Electric Systems

    1978 (Rescinded)

    Cooper/McGraw Distribution SystemProtection Manual

    Westinghouse Applied Protective Relaying

    CRN Bulletin 96-5 Ground Fault ImpedanceValues for System Protection

    Manufacturers Literature

  • 7/27/2019 Sectionalizing Presentation

    5/82

    Recloser Interruption &Control

    Hydraulic Interruption & Control Least Expensive ($1,200-2,300)

    Maintain @ 5 Year or Less Intervals

    Subject to Miscoordination in Winter

  • 7/27/2019 Sectionalizing Presentation

    6/82

    Recloser Interruption &Control

    Hydraulic Control & VacuumInterruption

    $100 More Expensive per Unit

    Maintain @ 10+ Year Intervals

    Same Miscoordination as Above

    Higher Interruption Ratings

  • 7/27/2019 Sectionalizing Presentation

    7/82

    Recloser Interruption &Control

    Vacuum Interruption & Solid-StateControl

    Limited Maintenance

    Most Expensive (1-ph: $5,700 &

    3-ph: $17,000)

    Coordination Not Affected by Temperature Most Options

    High Interruption Ratings

    Solid Type Insulations (e. g. Epoxy)

  • 7/27/2019 Sectionalizing Presentation

    8/82

    Recloser Selection

    Interrupting Rating Load

    Minimum Fault Coordination

    Simultaneous Trip

  • 7/27/2019 Sectionalizing Presentation

    9/82

    Recloser Ratings

    4000----10K4000--------400200

    4000----84004000--------280140

    40002500600040002000----20010040002500----40002000----14070

    30002500----30002000125010050

    -----2100----210014008757035

    ----1500----150010006255025

    ----900--------6003753015

    4EEWEL4HH

    Min.

    Trip

    Coil

    Size

  • 7/27/2019 Sectionalizing Presentation

    10/82

    Recloser TCC

    10 100

    1,000

    10,0

    00

    TimeInSeconds

    .1

    1

    10

    100

    1,000

    70,

    (A)

    70,

    (B)

    70,(C)

    70,

    (D)

  • 7/27/2019 Sectionalizing Presentation

    11/82

    Recloser-Recloser Coordination

    10

    100

    1,0

    00

    10,0

    00

    TimeInSeconds

    .1

    1

    10

    70,

    (B)

    50,

    (B)

    70,

    (A)

    50,L

    (A)

    50,4H

    (B)

    50,H(B)

  • 7/27/2019 Sectionalizing Presentation

    12/82

    Simultaneous Trip

    10 100

    1,000

    10,0

    00

    TimeInSeconds

    .1

    1

    10

    100

    1,000

    70,

    (B)

    50,L

    (B)

    70,L

    (A)

    50,L

    (A)

    600400

    10100

    1,0

    00

    0,0

    00

    TimeInSeconds

    .1

    1

    10

    100

    1,000

    70,(B)

    50,(B)

    70,L(A)

    50,(A)

    600400

  • 7/27/2019 Sectionalizing Presentation

    13/82

    Simultaneous Trip

    10 100

    1,000

    10,0

    00

    TimeInSeconds

    .1

    1

    10

    100

    70,(B)

    70,L(A)

    35,L(B)

    35,L(A)

    800

    650

  • 7/27/2019 Sectionalizing Presentation

    14/82

    Recloser-Recloser Coordination

    Summary

    One Size Smaller Recloser willCoordinate

    Skipping one Size will ReduceSimultaneous Trip

    May Run Out of Sizes

  • 7/27/2019 Sectionalizing Presentation

    15/82

    Rec oserFuse Coor ination

    Type T

    Current in Amperes

    10 100

    1,000

    10,0

    00

    TimeInSeconds

    .1

    1

    10

    100

    1,000

    70,L

    (B)

    70,L(A)

    25,T(TC)

    15,T

    (MM)

    12,T(MM)

  • 7/27/2019 Sectionalizing Presentation

    16/82

    Recloser-Fuse Coordination

    Type 200

    Current in Amperes

    10

    100

    1,0

    00

    10,0

    00

    TimeInSeconds

    .1

    1

    10

    100

    1,000

    70,L(B)

    70,L

    (A)

    30,(TC)

    15,N(MM)

    20,N(MM)

    Current in Amperes

    10

    100

    1,0

    00

    10,0

    00

    TimeInSeconds

    .1

    1

    10

    100

    1,000

    70,L(B)

    70,L(A)

    30,

    (TC)

    15,N

    (MM)

    20,N(MM)

  • 7/27/2019 Sectionalizing Presentation

    17/82

    Recloser-Fuse CoordinationType E

    Current in Am eres

    10

    100

    1,0

    00

    10,0

    00

    TimeInSeconds

    .1

    1

    10

    100

    1,000

    70,L

    (B)

    70,L

    (A)

    15

  • 7/27/2019 Sectionalizing Presentation

    18/82

    Recloser-Fuse Summary

    Fuse Total Clearing Faster than RecloserDelay

    Fuse Minimum Melt Slower thanRecloser Fast

    Pick a Standard Usually Largest Fuse

    Possible

  • 7/27/2019 Sectionalizing Presentation

    19/82

    Fuse-Fuse Coordination

    10

    100

    1,0

    00

    10,0

    00

    TimeInSeconds

    .1

    1

    10

    100

    1,000

    25,T(MM)20,T

    (TC)

  • 7/27/2019 Sectionalizing Presentation

    20/82

    Fuse-Fuse Coordination (T Type)

    Current in Amperes

    10

    100

    1,0

    00

    10,0

    00

    TimeInSeconds

    .1

    1

    10

    100

    1,000

    10,T 15,T 25,T 40,T

  • 7/27/2019 Sectionalizing Presentation

    21/82

    Fuse-Fuse Coordination (T Type)

    Current in Amperes

    10

    100

    1,0

    00

    10,0

    00

    TimeInSecond

    s

    .1

    1

    10

    100

    1,000

    30,T20,T12,T8,T

  • 7/27/2019 Sectionalizing Presentation

    22/82

    Fuse-Fuse Coordination (T-

    Bayonet)

    Current in Amperes

    10

    100

    1,0

    00

    10,0

    00

    TimeInSeconds

    .1

    1

    10

    100

    1,000

    25,T(MM)

    C10(25A.)Bayonet

  • 7/27/2019 Sectionalizing Presentation

    23/82

    Fuse-Fuse Coordination (T-E)

    Current in Amperes

    10

    100

    1,0

    00

    10,0

    00

    TimeInSeconds

    .1

    1

    10

    100

    1,000

    10,000

    25,T(MM)

    25,EMM)(Std&Slow)

    10

    100

    1,0

    00

    10,0

    00

    TimeInSeconds

    .1

    1

    10

    100

    1,000

    25,T(MM)

    25,EMM)(Std&Slow)

  • 7/27/2019 Sectionalizing Presentation

    24/82

    Fuse-Fuse Coordination (T-K)

    10

    100

    1,0

    00

    10,0

    00

    TimeInSeconds

    .1

    1

    10

    100

    1,000

    10,000

    25,T(MM)

    25,K(MM)

  • 7/27/2019 Sectionalizing Presentation

    25/82

    Fuse-Fuse Coordination (T-CL)

    10

    100

    1,0

    00

    10,0

    00

    TimeInSeconds

    .1

    1

    10

    100

    1,000

    10,000

    25,T(MM)

    25,NX C(MM)

    25NXII(MM)

    Current in Amperes

    10

    100

    1,0

    00

    10,0

    00

    TimeInSeconds

    .1

    1

    10

    100

    1,000

    25,T(MM)

    25,NX C(MM

    25NXII(MM)

  • 7/27/2019 Sectionalizing Presentation

    26/82

    Fuse-Fuse CoordinationSummary

    Total Clearing Faster than MinimumMelt

    Stick within a Series or Skip a Size

    Avoid Mixing Different Types

  • 7/27/2019 Sectionalizing Presentation

    27/82

    Sectionalizing Philosophy

    Compromise Compromise

    Compromise

  • 7/27/2019 Sectionalizing Presentation

    28/82

    Minimum Fault Resistance

    40 Ohm Old REA/RUS Standard

    Based on 1920s Bell Lab Studies

    Largest Single Phase Recloser - 70 Amp

    Smaller Reclosers and Fuses Overall

  • 7/27/2019 Sectionalizing Presentation

    29/82

    Minimum Fault Resistance

    30 Ohm Supported by CRN 96-5

    Less Conservative

    Largest Single Phase Recloser 100 Amp

    Larger Reclosers & Fuses

    Fewer Three Phase Reclosers

  • 7/27/2019 Sectionalizing Presentation

    30/82

    Minimum Fault Resistance

    Values Used by IOUs NSP/Excel 20 Ohms

    MP 0 Ohms or Twice Load Current

  • 7/27/2019 Sectionalizing Presentation

    31/82

    Sectionalizing PhilosophyRecloser Sizing

    Smallest vs. Largest vs. Hybrid Smallest

    Smallest Recloser which can carry load

    Faster Fault Clearing Smaller Load-Side Fuses

  • 7/27/2019 Sectionalizing Presentation

    32/82

    Recloser Sizing

    Largest Largest Recloser that Coordinates

    Larger Load-Side Fuses

    Fewer Changes in Future Hybrid

    Same as Largest, but Size Reclosers to

    Twice Load Level Less Simultaneous Tripping

  • 7/27/2019 Sectionalizing Presentation

    33/82

    Fast vs. Delay Operations

    Substation (1) Fast & (3) Delay

    85% Faults Temporary

    Better Coordination with Down-Stream Reclosers

    Fewer Consumers Affected by Interruption

    (0) Fast & (3 or 4) Delay Possibly More Outages for Temporary Faults

    Excellent Coordination with Down-Stream Reclosers No Interruption to Affect Electronic or Commercial Loads

  • 7/27/2019 Sectionalizing Presentation

    34/82

    Fast vs. Delay Operations

    Feeder Reclosers (2) Fast & (2) Delay

    Almost Universal

    Allows for Temporary Faults to Clear FewerOutages

    Affects Electronic Equipment Reset Clocks

  • 7/27/2019 Sectionalizing Presentation

    35/82

    Fast vs. Delay Operations

    Underground (1) Delay

    No Temporary Faults on UG Shouldnt Use If Overhead Beyond Least Amount of Cable Damage

    (2) Delay Good Coordination if Fuse Used for Overhead Beyond or

    Fuses on UG Limited Cable Damage

    (2) Fast & (2) Delay Necessary if Overhead Feeder Beyond Most Cable Damage

  • 7/27/2019 Sectionalizing Presentation

    36/82

    Recloser Spacing

    Mileage Between Reclosers on Three Phase 5 Miles

    Sectionalize Circuit More

    Shorter Outages

    Run Out of Sizes on Long Feeders 10 Miles

    More Line to Patrol for Outage Longer Outages

    Not as Likely to Run Out of Sizes Except at 24.9kV

    Longer Distance Difficulty Finding Fault

    Mostly Easily to Backfeed

  • 7/27/2019 Sectionalizing Presentation

    37/82

    Tap Protection w/ Recloser vs.Fuse

    Recloser Smaller Reclosers or Lightly Loaded Reclosers

    More Expensive if have to Purchases Reclosers

    One More Operation for Temporary Fault Fewer Outages Smaller Fuses on Taps Beyond Recloser

    Fuse Larger Fuses and on Tap

    Replace Fuse for Outage Possibly More Outages

  • 7/27/2019 Sectionalizing Presentation

    38/82

    Feeder Protection

    Reclosers Substation

    Taps with Load Larger than 20 amps or

    Longer than 5 Miles Every 10 Miles Along Three Phase

    Every 10 Miles Along Taps Where Load

    Larger than 20 Amps

    Beyond Special Loads

  • 7/27/2019 Sectionalizing Presentation

    39/82

    Feeder Protection

    FusesAll Taps or All Taps Longer than Three

    Spans

    Divide Taps Longer than 10 Miles

    Sectionalizers

    All Taps that Could be Fuses, But WouldOverload Fuse

  • 7/27/2019 Sectionalizing Presentation

    40/82

    Minimum Line Recloser & FuseSize

    What Size Transformer Fuse Do YouWant to Coordinate?

  • 7/27/2019 Sectionalizing Presentation

    41/82

    Minimum Recloser & Fuse Size

    What Size Transformer Fuse Do YouWant to Coordinate?

    25 kVA 6,T

  • 7/27/2019 Sectionalizing Presentation

    42/82

    Minimum Recloser & Fuse Size

    Current in Amperes

    10 100

    1,000

    10,0

    00

    TimeInSeconds

    .1

    1

    10

    100

    1,000

    6,T

    (TC)

    10,T

    Current in Amperes

    10 100

    1,000

    10,0

    00

    TimeInSeconds

    .1

    1

    10

    100

    1,000

    6,T

    (TC)

    10,T

  • 7/27/2019 Sectionalizing Presentation

    43/82

    Minimum Recloser & Fuse Size

    What Size Transformer Fuse Do YouWant to Coordinate?

    25 kVA 6,T

    Line Fuse 10,T

  • 7/27/2019 Sectionalizing Presentation

    44/82

    Minimum Recloser & Fuse Size

    10

    100

    1,0

    00

    10,0

    00

    TimeInSecond

    s

    .1

    1

    10

    100

    1,000

    6,T

    (TC)

    10,T

    25,4H

    (B)

    Current in Amperes

    10

    100

    1,0

    00

    10,0

    00

    TimeInSeco

    nds

    .1

    1

    10

    100

    1,000

    6,T

    (TC)

    10,T

    25,4H

    (B)

  • 7/27/2019 Sectionalizing Presentation

    45/82

    Minimum Recloser & Fuse Size

    What Size Transformer Fuse Do YouWant to Coordinate?

    25 kVA 6,T

    Line Fuse 10,T

    Recloser 25 amp

  • 7/27/2019 Sectionalizing Presentation

    46/82

    Fuses in Series

    Considerations Damage to Upstream Fuses

    Minimum Fuse Size

    Coordination Limitations

    Avoid as Much as Possible

  • 7/27/2019 Sectionalizing Presentation

    47/82

    Sectionalizing

    Rick Seeling Introduction

    Philosophy

    Pete Malamen

    Three Phase Reclosers

    High-Side Protection Specific Applications

  • 7/27/2019 Sectionalizing Presentation

    48/82

  • 7/27/2019 Sectionalizing Presentation

    49/82

    Three Phase Reclosers

  • 7/27/2019 Sectionalizing Presentation

    50/82

    Hydraulic Reclosers

  • 7/27/2019 Sectionalizing Presentation

    51/82

    Recloser with CTs & Solenoids

  • 7/27/2019 Sectionalizing Presentation

    52/82

    Electronic Control

  • 7/27/2019 Sectionalizing Presentation

    53/82

    Triple-Single Option

    1 Trip, 1 L.O.

    1 Trip, 3 L.O.

    3 Trip, 3 L.O.

  • 7/27/2019 Sectionalizing Presentation

    54/82

    Current in Amperes

    100

    1,0

    00

    10,0

    00

    100,0

    00

    TimeInSeconds

    .01

    .1

    1

    10

    100

    1,000

    100 A PU, TD=2

    U4-US Ext Inv

    300 A PU, TD=2U4-US Ext Inv

    200 A PU, TD=2

    U4-US Ext Inv

    Time Dial Settings

  • 7/27/2019 Sectionalizing Presentation

    55/82

    Current in Amperes

    100

    1,0

    00

    10,0

    00

    100,0

    00

    TimeInSeconds

    .01

    .1

    1

    10

    100

    1,000

    200 A PU, TD=4

    U4-US Ext Inv

    200 A PU, TD=1

    U4-US Ext Inv

    200 A PU, TD=2

    U4-US Ext Inv

    Pickup Settings

  • 7/27/2019 Sectionalizing Presentation

    56/82

    Current in Amperes

    100

    1,0

    00

    10,0

    00

    100,0

    00

    TimeInSeconds

    .01

    .1

    1

    10

    100

    1,000

    100 A PU, TD = 4

    U2-US Inverse

    300 A PU, TD = 2

    U4-US Ext I nv

    Phase Ground Coordination

  • 7/27/2019 Sectionalizing Presentation

    57/82

    ANSI StandardDevice Designation Numbers

    25) Synchronizing or Synchronism-Check Device Is a device that operates when two a-c circuits are within the desired limits of

    frequency, phase angle, or voltage, to permit or to cause the paralleling of these twocircuits.

    27) Undervoltage Relay Is a relay that functions on a given value of under-voltage.

    32) Directional Power Relay Is a device that functions on a desired value of power flow in a given direction or upon

    reverse power resulting from arcback in the anode or cathode circuits of a powerrectifier.

    50) Instantaneous Overcurrent or Rate-of-Rise Relay Is a relay that functions instantaneously on an excessive value of current or on an

    excessive rate of current rise, thus indicating a fault in the apparatus or circuit being

    protected.

    51) A-C Time Overcurrent Relay Is a relay with either a definite or inverse time characteristic that functions when the

    current in an a-c circuit exceed a predetermined value.

    d d

  • 7/27/2019 Sectionalizing Presentation

    58/82

    ANSI StandardDevice Designation Numbers

    52) A-C Circuit Breaker

    Is a device that is used to close and interrupt an a-c power circuit under normalconditions or to interrupt this circuit under fault of emergency conditions.

    59) Overvoltage Relay Is a relay that functions on a given value of over-voltage.

    67) A-C Directional Overcurrent Relay Is a relay that functions on a desired value of a-c overcurrent flowing in a

    predetermined direction.

    79) A-C Reclosing Relay Is a relay that controls the automatic reclosing and locking out of an a-c circuit

    interrupter.

    81) Frequency Relay Is a relay that functions on a predetermined value of frequency (either under or

    over or on normal system frequency) or rate of change of frequency.

    89) Line Switch Is a switch used as a disconnecting, load-interrupter, or isolating switch in an a-c

    or d-c power circuit, when this device is electrically operated or has electricalaccessories, such as an auxiliary switch, magnetic lock, etc.

  • 7/27/2019 Sectionalizing Presentation

    59/82

    One-line Diagram

  • 7/27/2019 Sectionalizing Presentation

    60/82

    Conductor Arcing through Asphalt

  • 7/27/2019 Sectionalizing Presentation

    61/82

    Conductor Breakage / Glassification

  • 7/27/2019 Sectionalizing Presentation

    62/82

    Steady State Harmonic Energy

  • 7/27/2019 Sectionalizing Presentation

    63/82

    Arcing Fault Harmonic Energy

  • 7/27/2019 Sectionalizing Presentation

    64/82

    Substation Protection

  • 7/27/2019 Sectionalizing Presentation

    65/82

    Current in Amperes

    100

    1,0

    00

    10,0

    00

    100,0

    00

    TimeInSeconds

    .01

    .1

    1

    10

    100

    1,000

    10,00065E SMD-Standard -T otal Clear A0.87 Low-Side Line to Line Fault

    Mechanical Damage

    Inrush

    Thermal Damage

    5,000 kVA, 69-12.47 kV

    Transformer

    65E SMD-Standard -To tal Clear A1.73 Low-Side Single Line to Ground Fault

    65E SMD-Standard -Tot al Clear Low-Side Three Phase Fault

    Substation Transformer

  • 7/27/2019 Sectionalizing Presentation

    66/82

    Current in Amperes

    100

    1,0

    00

    10,0

    00

    100,0

    00

    TimeInSeconds

    .01

    .1

    1

    10

    100

    1,000

    10,000

    Mechanical Damage

    Thermal Damage

    Inrush

    12/16/20 MVA, 69-12.47 kVTransformer

    150E SMD-Standard -T otal Clear

    150E SMD-Standard -Tot al Clear A1.73

    Low-Side Single Line to Ground Fault

    Low-Side Three Phase Fault

    Large Substation Transformers

  • 7/27/2019 Sectionalizing Presentation

    67/82

    Zones of Protection

  • 7/27/2019 Sectionalizing Presentation

    68/82

    Differential Relays

  • 7/27/2019 Sectionalizing Presentation

    69/82

    C.T. Curves

  • 7/27/2019 Sectionalizing Presentation

    70/82

    Transformer Protection

  • 7/27/2019 Sectionalizing Presentation

    71/82

    One-line Diagram

  • 7/27/2019 Sectionalizing Presentation

    72/82

    Specific Applications

  • 7/27/2019 Sectionalizing Presentation

    73/82

    Current in Amperes

    10

    100

    1,0

    00

    10,0

    00

    TimeInSecond

    s

    .001

    .01

    .1

    1

    10

    100

    1,000

    GE 10% Probability

    Case Rupture

    100 kVAr Units

    15 T -Tot al Clear

    15 T -Minimum Melt

    Capacitor Protection

  • 7/27/2019 Sectionalizing Presentation

    74/82

    Current in Amperes

    10

    100

    1,0

    00

    10,0

    00

    TimeInSeconds

    .001

    .01

    .1

    1

    10

    100

    1,000

    GE 10% Probability

    Case Rupture

    100 kVAr Units

    15 T -Total Clear

    15 T -Minimum Melt

    25 T -Tot al Clear

    25 T -Minimum Melt

    Parallel Capacitors

  • 7/27/2019 Sectionalizing Presentation

    75/82

    Current in Amperes

    10

    100

    1,0

    00

    10,0

    00

    TimeInSeconds

    .001

    .01

    .1

    1

    10

    100

    1,000

    100 kVAr Units

    GE 10% Probability

    Case Rupture

    25 T -Tot al Clear

    25 T -Minimum Melt

    25K NX Comp anion Fuses -Minimum Melt

    25K NX Companion Fuses -Total Clear

    Capacitor with C.L. Fuse

  • 7/27/2019 Sectionalizing Presentation

    76/82

    Current Limiting Fuses

    Partial range C.L. fuses Pad/Pole Transformer

    Overhead capacitors

    Underground applications Power quality

    Hard to coordinate areas

  • 7/27/2019 Sectionalizing Presentation

    77/82

    Step Down Transformer Protection

  • 7/27/2019 Sectionalizing Presentation

    78/82

  • 7/27/2019 Sectionalizing Presentation

    79/82

    Automatic Loop Restoration - 5 Reclosers

    Substation 1 3.3 miles

    R

    3.3 miles

    Substation 2

    R

    N.O.

    RecloserR

    N.C.

    Recloser

    N.C.

    Recloser

    N.C. - Normally-ClosedN.O. - Normally-Open

    R

    R

    N.C.

    Recloser

    N.C.

    Recloser

    3.3 miles

  • 7/27/2019 Sectionalizing Presentation

    80/82

    Loop Coordination

    Loss of V By # of recloses & loss of V

    Normal O.C. & comm.

    Current diff & comm.

  • 7/27/2019 Sectionalizing Presentation

    81/82

    Control Logic

  • 7/27/2019 Sectionalizing Presentation

    82/82

    Questions & comments