These drawings are published as an information guide only. These CAD drawings are intended as templates to assist the designer. They do not contain the full details required for construction and must be read in conjunction with the installation instructions on www.jameshardiecommercial.com. You should obtain architectural, engineering or other technical advice to assess the suitability of these drawings to the requirements of your particular project. James Hardie accepts no liability in respect to the use of these drawings. For fastener specifications and complete installation instructions refer to appropriate documentation at www.JamesHardieCommercial.com. DETAIL: Rev. 4 (2013) Reveal2.0™ 1.01 Hardie Reveal2.0™ Panel Vertical Siding (7/16Thick) • Wood Framing • OSB or Plywood Sheathing • Pressure-Treated Wood Furring (Minimum 3/4" Nominal, 23/32" Actual Thickness) having specific gravity of 0.42 or greater • Shown with Panhead Screws into Furring 0 SCALE: 1" = 4" 2" 4" SECTION DETAIL – FOUNDATION @ GRADE WATER RESISTIVE BARRIER EXTERIOR SHEATHING GRADE MINIMUM 3/4" FURRING VENT STRIP 1/2" SPACING MINIMUM DRAINAGE FLASHING CODE APPROVED SILL SEAL (AS REQ’D PER CODE) MIN. 6" UNFINISHED GRADE CLEARANCE, 2" SLAB, DECK, OR SIDEWALK CLEARANCE, OR CODE REQ'D, WHICHEVER IS SMALLER HARDIE REVEAL2.0™ PANEL VERTICAL SIDING #10-12 T20W PAN HEAD SCREW

SECTION DETAIL – PANEL WITH HORIZONTAL TRIM · scale: 1" = 4" 2" 4" section detail – foundation @ grade water resistive barrier exterior sheathing grade minimum 3/4" furring vent

  • Upload
    dokhue

  • View
    228

  • Download
    0

Embed Size (px)

Citation preview

Page 1: SECTION DETAIL – PANEL WITH HORIZONTAL TRIM · scale: 1" = 4" 2" 4" section detail – foundation @ grade water resistive barrier exterior sheathing grade minimum 3/4" furring vent

These drawings are published as an information guide only. These CAD drawings are intended as templates to assist the designer. They do not contain the full details required for construction and must be read in conjunction with the installation instructions on www.jameshardiecommercial.com. You should obtain architectural, engineering or other technical advice to assess the suitability of these drawings to the requirements of your particular project. James Hardie accepts no liability in respect to the use of these drawings.

For fastener specifications and complete installation instructions refer to appropriate documentation at www.JamesHardieCommercial.com.

DETAIL:

Rev. 4 (2013)

Reveal2.0™

1.01Hardie Reveal2.0™ Panel Vertical Siding (7/16" Thick)• Wood Framing• OSB or Plywood Sheathing• Pressure-Treated Wood Furring (Minimum 3/4" Nominal, 23/32" Actual Thickness) having specific gravity of 0.42 or greater• Shown with Panhead Screws into Furring

0

SCALE: 1" = 4"

2" 4"

SECTION DETAIL – FOUNDATION @ GRADE

WATER RESISTIVE BARRIER

EXTERIOR SHEATHING

GRADE

MINIMUM 3/4" FURRING

VENT STRIP

1/2" SPACING MINIMUM

DRAINAGE FLASHING

CODE APPROVED

SILL SEAL(AS REQ’D PER CODE) MIN. 6" UNFINISHED GRADE

CLEARANCE, 2" SLAB, DECK, ORSIDEWALK CLEARANCE, OR CODEREQ'D, WHICHEVER IS SMALLER

HARDIE REVEAL2.0™ PANELVERTICAL SIDING

#10-12 T20W PAN HEAD SCREW

Page 2: SECTION DETAIL – PANEL WITH HORIZONTAL TRIM · scale: 1" = 4" 2" 4" section detail – foundation @ grade water resistive barrier exterior sheathing grade minimum 3/4" furring vent

SECTION DETAIL – PANEL WITH HORIZONTAL TRIM

These drawings are published as an information guide only. These CAD drawings are intended as templates to assist the designer. They do not contain the full details required for construction and must be read in conjunction with the installation instructions on www.jameshardiecommercial.com. You should obtain architectural, engineering or other technical advice to assess the suitability of these drawings to the requirements of your particular project. James Hardie accepts no liability in respect to the use of these drawings.

For fastener specifications and complete installation instructions refer to appropriate documentation at www.JamesHardieCommercial.com.

DETAIL:

Rev. 4 (2013)

Reveal2.0™

1.02Hardie Reveal2.0™ Panel Vertical Siding• Wood Framing• OSB or Plywood Sheathing• Pressure-Treated Wood Furring (Minimum 3/4" Nominal, 23/32" Actual Thickness) having specific gravity of 0.42 or greater• Shown with Panhead Screws into Furring

0

SCALE: 1" = 2"

1" 2"

EXTERIOR SHEATHING

1/2" SPACING

HORIZONTAL TRIM

MINIMUM 3/4" FURRING

WATER RESISTIVE BARRIERCODE APPROVED

#10-12 T20W PAN HEAD SCREW

HARDIE REVEAL2.0™ PANELVERTICAL SIDING

Page 3: SECTION DETAIL – PANEL WITH HORIZONTAL TRIM · scale: 1" = 4" 2" 4" section detail – foundation @ grade water resistive barrier exterior sheathing grade minimum 3/4" furring vent

SECTION DETAIL – PANEL WITH HORIZONTALTRIM @ FLOOR BREAK

DETAIL:

Rev. 4 (2012)

Reveal2.0™

1.03Hardie Reveal2.0™ Panel Vertical Siding• Wood Framing• OSB or Plywood Sheathing• Pressure-Treated Wood Furring (Minimum 3/4" Nominal, 23/32" Actual Thickness) having specific gravity of 0.42 or greater• Shown with Panhead Screws into Furring

These drawings are published as an information guide only. These CAD drawings are intended as templates to assist the designer. They do not contain the full details required for construction and must be read in conjunction with the installation instructions on www.jameshardiecommercial.com. You should obtain architectural, engineering or other technical advice to assess the suitability of these drawings to the requirements of your particular project. James Hardie accepts no liability in respect to the use of these drawings.

For fastener specifications and complete installation instructions refer to appropriate documentation at www.JamesHardieCommercial.com.

0

SCALE: 1" = 4"

2" 4"

HARDIE REVEAL2.0™ PANEL VERTICAL SIDINGHORIZONTAL TRIM CAN ALSO BEUSED AT THE FLOOR BREAK;HOWEVER A DRAINAGE FLASHINGIS REQUIRED TO BE USED EVERYOTHER FLOOR.

CODE APPROVEDWATER RESISTIVE BARRIER

EXTERIOR SHEATHING

MINIMUM 3/4” FURRING

TAPE

1/2” GAP, DO NOT CAULK

DRAINAGE FLASHING

NOTE: DO NOT FASTEN PANELACROSS A BRIDGED FLOOR ASSURE ACOMPLIMENTARY BREAK EXISTS FORPLYWOOD FURRING AND PANEL

NOTE: THE PANEL JOINT CAN BE ATTHE TOP OR BOTTOM OF THE JOIST.

#10-12 T20W PAN HEAD SCREW

Page 4: SECTION DETAIL – PANEL WITH HORIZONTAL TRIM · scale: 1" = 4" 2" 4" section detail – foundation @ grade water resistive barrier exterior sheathing grade minimum 3/4" furring vent

PLAN DETAIL – PANEL WITH VERTICAL TRIM

These drawings are published as an information guide only. These CAD drawings are intended as templates to assist the designer. They do not contain the full details required for construction and must be read in conjunction with the installation instructions on www.jameshardiecommercial.com. You should obtain architectural, engineering or other technical advice to assess the suitability of these drawings to the requirements of your particular project. James Hardie accepts no liability in respect to the use of these drawings.

For fastener specifications and complete installation instructions refer to appropriate documentation at www.JamesHardieCommercial.com.

DETAIL:

Rev. 4 (2013)

Reveal2.0™

1.04Hardie Reveal2.0™ Panel Vertical Siding• Wood Framing• OSB or Plywood Sheathing• Pressure-Treated Wood Furring (Minimum 3/4" Nominal, 23/32" Actual Thickness) having specific gravity of 0.42 or greater• Shown with Countersunk Screws into Furring

0

SCALE: 1" = 2"

1" 2"

1/2"

CODE APPROVEDWATER RESISTIVE BARRIER

INTERIOR SHEATHING

EXTERIOR SHEATHING

MINIMUM 3/4” FURRINGVERTICAL TRIM

HARDIE REVEAL2.0™ PANEL VERTICAL SIDING

#10-12 T20W PAN HEAD SCREW

Page 5: SECTION DETAIL – PANEL WITH HORIZONTAL TRIM · scale: 1" = 4" 2" 4" section detail – foundation @ grade water resistive barrier exterior sheathing grade minimum 3/4" furring vent

PLAN DETAIL – OUTSIDE CORNER TRIM

These drawings are published as an information guide only. These CAD drawings are intended as templates to assist the designer. They do not contain the full details required for construction and must be read in conjunction with the installation instructions on www.jameshardiecommercial.com. You should obtain architectural, engineering or other technical advice to assess the suitability of these drawings to the requirements of your particular project. James Hardie accepts no liability in respect to the use of these drawings.

For fastener specifications and complete installation instructions refer to appropriate documentation at www.JamesHardieCommercial.com.

DETAIL:

Rev. 4 (2013)

Reveal2.0™

1.05Hardie Reveal2.0™ Panel Vertical Siding• Wood Framing• OSB or Plywood Sheathing• Pressure-Treated Wood Furring (Minimum 3/4" Nominal, 23/32" Actual Thickness) having specific gravity of 0.42 or greater• Shown with Panhead Screws into Furring

0

SCALE: 1" = 2"

1" 2"

EXTERIOR SHEATHING

OUTSIDE CORNER TRIM

MINIMUM 3/4" FURRING

WATER RESISTIVE BARRIERCODE APPROVED

HARDIE REVEAL2.0™ PANELVERTICAL SIDING

#10-12 T20WPAN HEAD SCREW

Page 6: SECTION DETAIL – PANEL WITH HORIZONTAL TRIM · scale: 1" = 4" 2" 4" section detail – foundation @ grade water resistive barrier exterior sheathing grade minimum 3/4" furring vent

PLAN DETAIL – INSIDE CORNER TRIM

These drawings are published as an information guide only. These CAD drawings are intended as templates to assist the designer. They do not contain the full details required for construction and must be read in conjunction with the installation instructions on www.jameshardiecommercial.com. You should obtain architectural, engineering or other technical advice to assess the suitability of these drawings to the requirements of your particular project. James Hardie accepts no liability in respect to the use of these drawings.

For fastener specifications and complete installation instructions refer to appropriate documentation at www.JamesHardieCommercial.com.

DETAIL:

Rev. 4 (2013)

Reveal2.0™

1.06Hardie Reveal2.0™ Panel Vertical Siding• Wood Framing• OSB or Plywood Sheathing• Pressure-Treated Wood Furring (Minimum 3/4" Nominal, 23/32" Actual Thickness) having specific gravity of 0.42 or greater• Shown with Panhead Screws into Furring

0

SCALE: 1" = 2"

1" 2"

VERTICAL F-TRIM

CODE APPROVED

EXTERIOR SHEATHING

MINIMUM 3/4" FURRING

WATER RESISTIVE BARRIER

HARDIE REVEAL2.0™ PANEL VERTICAL SIDING

#10-12 T20W PAN HEAD SCREW

Page 7: SECTION DETAIL – PANEL WITH HORIZONTAL TRIM · scale: 1" = 4" 2" 4" section detail – foundation @ grade water resistive barrier exterior sheathing grade minimum 3/4" furring vent

SECTION DETAIL – WALL & SOFFIT FORVENTED RAINSCREEN

These drawings are published as an information guide only. These CAD drawings are intended as templates to assist the designer. They do not contain the full details required for construction and must be read in conjunction with the installation instructions on www.jameshardiecommercial.com. You should obtain architectural, engineering or other technical advice to assess the suitability of these drawings to the requirements of your particular project. James Hardie accepts no liability in respect to the use of these drawings.

For fastener specifications and complete installation instructions refer to appropriate documentation at www.JamesHardieCommercial.com.

DETAIL:

Rev. 4 (2012)

Reveal2.0™

1.07Hardie Reveal2.0™ Panel Vertical Siding• Wood Framing• OSB or Plywood Sheathing• Pressure-Treated Wood Furring (Minimum 3/4" Nominal, 23/32" Actual Thickness) having specific gravity of 0.42 or greater• Shown with Panyhead Screws into Furring

0

SCALE: 1" = 2"

1" 2"

EXTERIOR SHEATHING

WATER RESISTIVE BARRIER

J-CHANNEL TRIM

MINIMUM 3/4" FURRING

SOFFIT

CODE APPROVED

HARDIE REVEAL2.0™ PANELVERTICAL SIDING

#10-12 T20W PAN HEAD SCREW

1/8" GAP

VENT STRIP

Page 8: SECTION DETAIL – PANEL WITH HORIZONTAL TRIM · scale: 1" = 4" 2" 4" section detail – foundation @ grade water resistive barrier exterior sheathing grade minimum 3/4" furring vent

SECTION DETAIL – WALL & SOFFIT FORVENTILATED RAINSCREEN

These drawings are published as an information guide only. These CAD drawings are intended as templates to assist the designer. They do not contain the full details required for construction and must be read in conjunction with the installation instructions on www.jameshardiecommercial.com. You should obtain architectural, engineering or other technical advice to assess the suitability of these drawings to the requirements of your particular project. James Hardie accepts no liability in respect to the use of these drawings.

For fastener specifications and complete installation instructions refer to appropriate documentation at www.JamesHardieCommercial.com.

DETAIL:

Rev. 4 (2013)

Reveal2.0™

1.08Hardie Reveal2.0™ Panel Vertical Siding• Wood Framing• OSB or Plywood Sheathing• Pressure-Treated Wood Furring (Minimum 3/4" Nominal, 23/32" Actual Thickness) having specific gravity of 0.42 or greate• Shown with Panhead Screws into Furring

0

SCALE: 1" = 2"

1" 2"

EXTERIOR SHEATHING

WATER RESISTIVE BARRIER

SOFFIT

HORIZONTAL TRIM

MINIMUM 3/4" FURRING

CODE APPROVED

FRIEZE BOARD

DISCONTINUOUS BLK'G REQ'D FOR VENTING

VENT STRIP

FRIEZE BLOCK INTAKE VENT @ 3/8"

HARDIE REVEAL2.0™ PANELVERTICAL SIDING

#10-12 T20W PAN HEAD SCREW

Page 9: SECTION DETAIL – PANEL WITH HORIZONTAL TRIM · scale: 1" = 4" 2" 4" section detail – foundation @ grade water resistive barrier exterior sheathing grade minimum 3/4" furring vent

SECTION DETAIL – SOFFIT FLASHINGINTERSECTION

These drawings are published as an information guide only. These CAD drawings are intended as templates to assist the designer. They do not contain the full details required for construction and must be read in conjunction with the installation instructions on www.jameshardiecommercial.com. You should obtain architectural, engineering or other technical advice to assess the suitability of these drawings to the requirements of your particular project. James Hardie accepts no liability in respect to the use of these drawings.

For fastener specifications and complete installation instructions refer to appropriate documentation at www.JamesHardieCommercial.com.

DETAIL:

Rev. 4 (2013)

Reveal2.0™

1.09Hardie Reveal2.0™ Panel Vertical Siding• Wood Framing• OSB or Plywood Sheathing• Pressure-Treated Wood Furring (Minimum 3/4" Nominal, 23/32" Actual Thickness) having specific gravity of 0.42 or greate• Shown with Panhead Screws into Furring

0

SCALE: 1" = 2"

1" 2"

WATER RESISTIVE BARRIERCODE APPROVED

SOFFIT

FLASHING

DO NOT CAULKMINIMUM 1/2" GAP,

TAPE

HARDIE REVEAL2.0™ PANELVERTICAL SIDING

#10-12 T20WPAN HEAD SCREW

Page 10: SECTION DETAIL – PANEL WITH HORIZONTAL TRIM · scale: 1" = 4" 2" 4" section detail – foundation @ grade water resistive barrier exterior sheathing grade minimum 3/4" furring vent

SECTION DETAIL – DOOR HEADERINTERSECTION

These drawings are published as an information guide only. These CAD drawings are intended as templates to assist the designer. They do not contain the full details required for construction and must be read in conjunction with the installation instructions on www.jameshardiecommercial.com. You should obtain architectural, engineering or other technical advice to assess the suitability of these drawings to the requirements of your particular project. James Hardie accepts no liability in respect to the use of these drawings.

For fastener specifications and complete installation instructions refer to appropriate documentation at www.JamesHardieCommercial.com.

DETAIL:

Rev. 4 (2013)

Reveal2.0™

1.10 Hardie Reveal2.0™ Panel Vertical Siding• Wood Framing• OSB or Plywood Sheathing• Pressure-Treated Wood Furring (Minimum 3/4" Nominal, 23/32" Actual Thickness) having specific gravity of 0.42 or greate• Shown with Panhead Screws into Furring

0

SCALE: 1" = 2"

1" 2"

CODE APPROVEDWATER RESISTIVE BARRIER

WRB TURNEDINTO OPENING

INCLUDE AN AIR SEALB/W DOOR AND WRB

MINIMUM 3/4” FURRING

1/2”

MIN

.

HARDIE REVEAL2.0™ PANELVERTICAL SIDING

DRAINAGE FLASHING

AIR SEAL

DOOR ORWINDOW HEADER

VENT STRIP

#10-12 T20WPAN HEAD SCREW

Page 11: SECTION DETAIL – PANEL WITH HORIZONTAL TRIM · scale: 1" = 4" 2" 4" section detail – foundation @ grade water resistive barrier exterior sheathing grade minimum 3/4" furring vent

SECTION DETAIL – ALUMINUM WINDOW HEAD

These drawings are published as an information guide only. These CAD drawings are intended as templates to assist the designer. They do not contain the full details required for construction and must be read in conjunction with the installation instructions on www.jameshardiecommercial.com. You should obtain architectural, engineering or other technical advice to assess the suitability of these drawings to the requirements of your particular project. James Hardie accepts no liability in respect to the use of these drawings.

For fastener specifications and complete installation instructions refer to appropriate documentation at www.JamesHardieCommercial.com.

DETAIL:

Rev. 4 (2013)

Reveal2.0™

1.11Hardie Reveal2.0™ Panel Vertical Siding• Wood Framing• OSB or Plywood Sheathing• Pressure-Treated Wood Furring (Minimum 3/4" Nominal, 23/32" Actual Thickness) having specific gravity of 0.42 or greate• Shown with Panhead Screws into Furring

0

SCALE: 1" = 2"

1" 2"

WINDOW FRAME

VENT STRIP

DRAINAGE FLASHING

SEALANT

MIN. 1/2" GAP

WINDOW FLASHING

WATER RESISTIVE BARRIERCODE APPROVED

NOTE:FACTORY SEALED EDGES ARE BEST ATBOTTOM HORIZONTAL, BUT NOT REQUIRED

HARDIE REVEAL2.0™ PANELVERTICAL SIDING

MINIMUM 3/4" FURRING

#10-12 T20W PAN HEAD SCREW

Page 12: SECTION DETAIL – PANEL WITH HORIZONTAL TRIM · scale: 1" = 4" 2" 4" section detail – foundation @ grade water resistive barrier exterior sheathing grade minimum 3/4" furring vent

SECTION DETAIL – ALUMINUM WINDOW HEAD

These drawings are published as an information guide only. These CAD drawings are intended as templates to assist the designer. They do not contain the full details required for construction and must be read in conjunction with the installation instructions on www.jameshardiecommercial.com. You should obtain architectural, engineering or other technical advice to assess the suitability of these drawings to the requirements of your particular project. James Hardie accepts no liability in respect to the use of these drawings.

For fastener specifications and complete installation instructions refer to appropriate documentation at www.JamesHardieCommercial.com.

DETAIL:

Rev. 4 (2013)

Reveal2.0™

1.11bHardie Reveal2.0™ Panel Vertical Siding• Wood Framing• OSB or Plywood Sheathing• Pressure-Treated Wood Furring (Minimum 3/4" Nominal, 23/32" Actual Thickness) having specific gravity of 0.42 or greate• Shown with Panhead Screws into Furring

0

SCALE: 1" = 2"

1" 2"

WINDOW FRAME

VENT STRIP

DRAINAGE FLASHING

MIN. 1/2" GAP

WINDOW FLASHING

WATER RESISTIVE BARRIERCODE APPROVED

NOTE:ALL CUT EDGES MUST BE SEALED.

HARDIE REVEAL2.0™ PANELVERTICAL SIDING

MINIMUM 3/4" FURRING

#10-12 T20W PAN HEAD SCREW

Page 13: SECTION DETAIL – PANEL WITH HORIZONTAL TRIM · scale: 1" = 4" 2" 4" section detail – foundation @ grade water resistive barrier exterior sheathing grade minimum 3/4" furring vent

SECTION DETAIL – ALUMINUM WINDOW SILL

These drawings are published as an information guide only. These CAD drawings are intended as templates to assist the designer. They do not contain the full details required for construction and must be read in conjunction with the installation instructions on www.jameshardiecommercial.com. You should obtain architectural, engineering or other technical advice to assess the suitability of these drawings to the requirements of your particular project. James Hardie accepts no liability in respect to the use of these drawings.

For fastener specifications and complete installation instructions refer to appropriate documentation at www.JamesHardieCommercial.com.

DETAIL:

Rev. 4 (2013)

Reveal2.0™

1.12Hardie Reveal2.0™ Panel Vertical Siding• Wood Framing• OSB or Plywood Sheathing• Pressure-Treated Wood Furring (Minimum 3/4" Nominal, 23/32" Actual Thickness) having specific gravity of 0.42 or greate• Shown with Panhead Screws into Furring

0

SCALE: 1" = 2"

1" 2"

SEALANT W/ BACKER ROD

WINDOW FRAME

SILL FLASHING

WATER RESISTIVE BARRIERCODE APPROVED

HORIZONTAL EDGE TRIM

HARDIE REVEAL2.0™ PANELVERTICAL SIDING

MINIMUM 3/4" FURRING

#10-12 T20W PAN HEAD SCREW

Page 14: SECTION DETAIL – PANEL WITH HORIZONTAL TRIM · scale: 1" = 4" 2" 4" section detail – foundation @ grade water resistive barrier exterior sheathing grade minimum 3/4" furring vent

SECTION DETAIL – FLANGED WINDOW SILL

These drawings are published as an information guide only. These CAD drawings are intended as templates to assist the designer. They do not contain the full details required for construction and must be read in conjunction with the installation instructions on www.jameshardiecommercial.com. You should obtain architectural, engineering or other technical advice to assess the suitability of these drawings to the requirements of your particular project. James Hardie accepts no liability in respect to the use of these drawings.

For fastener specifications and complete installation instructions refer to appropriate documentation at www.JamesHardieCommercial.com.

DETAIL:

Rev. 4 (2013)

Reveal2.0™

1.12bHardie Reveal2.0™ Panel Vertical Siding• Wood Framing• OSB or Plywood Sheathing• Pressure-Treated Wood Furring (Minimum 3/4" Nominal, 23/32" Actual Thickness) having specific gravity of 0.42 or greate• Shown with Panhead Screws into Furring

0

SCALE: 1" = 2"

1" 2"

SEALANT W/ BACKER ROD

WINDOW FRAME

SILL FLASHING

WATER RESISTIVE BARRIERCODE APPROVED

HORIZONTAL EDGE TRIM

HARDIE REVEAL2.0™ PANELVERTICAL SIDING

MINIMUM 3/4" FURRING

#10-12 T20W PAN HEAD SCREW

Page 15: SECTION DETAIL – PANEL WITH HORIZONTAL TRIM · scale: 1" = 4" 2" 4" section detail – foundation @ grade water resistive barrier exterior sheathing grade minimum 3/4" furring vent

PLAN DETAIL – ALUMINUM WINDOW FLANGEWITH METAL TRIM

These drawings are published as an information guide only. These CAD drawings are intended as templates to assist the designer. They do not contain the full details required for construction and must be read in conjunction with the installation instructions on www.jameshardiecommercial.com. You should obtain architectural, engineering or other technical advice to assess the suitability of these drawings to the requirements of your particular project. James Hardie accepts no liability in respect to the use of these drawings.

For fastener specifications and complete installation instructions refer to appropriate documentation at www.JamesHardieCommercial.com.

DETAIL:

Rev. 4 (2013)

Reveal2.0™

1.13Hardie Reveal2.0™ Panel Vertical Siding• Wood Framing• OSB or Plywood Sheathing• Pressure-Treated Wood Furring (Minimum 3/4" Nominal, 23/32" Actual Thickness) having specific gravity of 0.42 or greate• Shown with Panhead Screws into Furring

0

SCALE: 1" = 2"

1" 2"

#10-12 T20WPAN HEAD SCREW

WATER RESISTIVE BARRIERCODE APPROVED

DOOR / WINDOW JAMB

BACKER ROD & SEALANT

FLASHING TAPE

HARDIE REVEAL2.0™ PANELVERTICAL SIDING

MINIMUM 3/4" FURRING

VERTICAL F-TRIM

Page 16: SECTION DETAIL – PANEL WITH HORIZONTAL TRIM · scale: 1" = 4" 2" 4" section detail – foundation @ grade water resistive barrier exterior sheathing grade minimum 3/4" furring vent

PLAN DETAIL – ALUMINUM WINDOW FLANGEWITH METAL TRIM

These drawings are published as an information guide only. These CAD drawings are intended as templates to assist the designer. They do not contain the full details required for construction and must be read in conjunction with the installation instructions on www.jameshardiecommercial.com. You should obtain architectural, engineering or other technical advice to assess the suitability of these drawings to the requirements of your particular project. James Hardie accepts no liability in respect to the use of these drawings.

For fastener specifications and complete installation instructions refer to appropriate documentation at www.JamesHardieCommercial.com.

DETAIL:

Rev. 4 (2013)

Reveal2.0™

1.13bHardie Reveal2.0™ Panel Vertical Siding• Wood Framing• OSB or Plywood Sheathing• Pressure-Treated Wood Furring (Minimum 3/4" Nominal, 23/32" Actual Thickness) having specific gravity of 0.42 or greate• Shown with Panhead Screws into Furring

0

SCALE: 1" = 2"

1" 2"

#10-12 T20WPAN HEAD SCREW

WATER RESISTIVE BARRIERCODE APPROVED

DOOR / WINDOW JAMB

BACKER ROD & SEALANT

FLASHING TAPE

HARDIE REVEAL2.0™ PANELVERTICAL SIDING

MINIMUM 3/4" FURRING

VERTICAL F-TRIM

Page 17: SECTION DETAIL – PANEL WITH HORIZONTAL TRIM · scale: 1" = 4" 2" 4" section detail – foundation @ grade water resistive barrier exterior sheathing grade minimum 3/4" furring vent

PLAN DETAIL – ALUMINUM WINDOW FLANGEWITH TRIM BOARDS

These drawings are published as an information guide only. These CAD drawings are intended as templates to assist the designer. They do not contain the full details required for construction and must be read in conjunction with the installation instructions on www.jameshardiecommercial.com. You should obtain architectural, engineering or other technical advice to assess the suitability of these drawings to the requirements of your particular project. James Hardie accepts no liability in respect to the use of these drawings.

For fastener specifications and complete installation instructions refer to appropriate documentation at www.JamesHardieCommercial.com.

DETAIL:

Rev. 4 (2013)

Reveal2.0™

1.14Hardie Reveal2.0™ Panel Vertical Siding• Wood Framing• OSB or Plywood Sheathing• Pressure-Treated Wood Furring (Minimum 3/4" Nominal, 23/32" Actual Thickness) having specific gravity of 0.42 or greate• Shown with Panhead Screws into Furring

0

SCALE: 1" = 2"

1" 2"

CODE APPROVED

VERTICAL F-TRIM

WATER RESISTIVE BARRIER

JAMBDOOR / WINDOW

BACKER ROD & SEALANT

FLASHING TAPE

HARDIETRIM® BOARDSLEAVE MIN. 1/8" GAP & CAULK

HARDIE REVEAL2.0™ PANELVERTICAL SIDING

MINIMUM 3/4" FURRING

Page 18: SECTION DETAIL – PANEL WITH HORIZONTAL TRIM · scale: 1" = 4" 2" 4" section detail – foundation @ grade water resistive barrier exterior sheathing grade minimum 3/4" furring vent

SECTION DETAIL – 1 1/2" OR LESS HOLEPENETRATION TREATMENT

These drawings are published as an information guide only. These CAD drawings are intended as templates to assist the designer. They do not contain the full details required for construction and must be read in conjunction with the installation instructions on www.jameshardiecommercial.com. You should obtain architectural, engineering or other technical advice to assess the suitability of these drawings to the requirements of your particular project. James Hardie accepts no liability in respect to the use of these drawings.

For fastener specifications and complete installation instructions refer to appropriate documentation at www.JamesHardieCommercial.com.

DETAIL:

Rev. 4 (2013)

Reveal2.0™

1.15Hardie Reveal2.0™ Panel Vertical Siding• Wood Framing• OSB or Plywood Sheathing• Pressure-Treated Wood Furring (Minimum 3/4" Nominal, 23/32" Actual Thickness) having specific gravity of 0.42 or greate• Shown with Panhead Screws into Furring

0

SCALE: 1" = 2"

1" 2"

SEALANT W/ BACKER ROD

SEALANT

PIPE 1-1/2" OR LESS

EXTERIOR SHEATHING

FOAM SEALANT

MINIMUM 3/4" FURRING

MINIMUM 3/4" FURRING

WATER RESISTIVE BARRIERCODE APPROVED

SELF ADHERED FLASHING

NOTE:EXTERNAL BLOCKING IS RECOMMENDED WHEN PENETRATION OCCURS AFTER THE INSTALLATION OF PANEL

HARDIE REVEAL2.0™ PANELVERTICAL SIDING

Page 19: SECTION DETAIL – PANEL WITH HORIZONTAL TRIM · scale: 1" = 4" 2" 4" section detail – foundation @ grade water resistive barrier exterior sheathing grade minimum 3/4" furring vent

SECTION DETAIL – BLOCK PENETRATIONTREATMENT

These drawings are published as an information guide only. These CAD drawings are intended as templates to assist the designer. They do not contain the full details required for construction and must be read in conjunction with the installation instructions on www.jameshardiecommercial.com. You should obtain architectural, engineering or other technical advice to assess the suitability of these drawings to the requirements of your particular project. James Hardie accepts no liability in respect to the use of these drawings.

For fastener specifications and complete installation instructions refer to appropriate documentation at www.JamesHardieCommercial.com.

DETAIL:

Rev. 4 (2013)

Reveal2.0™

1.16Hardie Reveal2.0™ Panel Vertical Siding• Wood Framing• OSB or Plywood Sheathing• Pressure-Treated Wood Furring (Minimum 3/4" Nominal, 23/32" Actual Thickness) having specific gravity of 0.42 or greate• Shown with Panhead Screws into Furring

0

SCALE: 1" = 4"

2" 4"

EXTERIOR SHEATHING

BLOCKING AS REQ'D

FURRING AROUND FIXTURE

FLASHING

TRIM AROUND OPENING

MIN. 1/2" GAP, DO NOT CAULK

HARDIETRIM® BOARDS / BLOCKING

VENT OPENING

LEAVE MIN. 1/8" GAP AND CAULK

BENT DRYER FLANGE

MINIMUM 3/4" FURRING

WATER RESISTIVE BARRIERCODE APPROVED

OPTIONAL:USE HORIZONTAL EDGE TRIM ON SILL& VERTICAL F-TRIM ON SIDES

NOTE:CAULK 3 SIDES, BUT NOT TOP.J-CHANNEL TRIM IS OPTIONAL

HARDIE REVEAL2.0™ PANELVERTICAL SIDING

HARDIE REVEAL2.0™ PANELVERTICAL SIDING

#10-12 T20W PAN HEAD SCREW

Page 20: SECTION DETAIL – PANEL WITH HORIZONTAL TRIM · scale: 1" = 4" 2" 4" section detail – foundation @ grade water resistive barrier exterior sheathing grade minimum 3/4" furring vent

SECTION DETAIL – VENTED PARAPET WALL

These drawings are published as an information guide only. These CAD drawings are intended as templates to assist the designer. They do not contain the full details required for construction and must be read in conjunction with the installation instructions on www.jameshardiecommercial.com. You should obtain architectural, engineering or other technical advice to assess the suitability of these drawings to the requirements of your particular project. James Hardie accepts no liability in respect to the use of these drawings.

For fastener specifications and complete installation instructions refer to appropriate documentation at www.JamesHardieCommercial.com.

DETAIL:

Rev. 4 (2013)

Reveal2.0™

1.17Hardie Reveal2.0™ Panel Vertical Siding• Wood Framing• OSB or Plywood Sheathing• Pressure-Treated Wood Furring (Minimum 3/4" Nominal, 23/32" Actual Thickness) having specific gravity of 0.42 or greate• Shown with Panhead Screws into Furring

0

SCALE: 1" = 4"

2" 4"

VENT STRIP

CAPPINGUNDERLAY TO PROVIDE ISOLATIONOF METAL FLASHING TO TIMBER

EXTERIOR SHEATHING

SELF-ADHERED FLASHING

CODE APPROVEDWATER RESISTIVE BARRIER

1/8" GAP

HARDIE REVEAL2.0™ PANELVERTICAL SIDING

NOTE:DO NOT USE HARDIE TRIM OR BOARD AS CAP FLASHING

MINIMUM 3/4" FURRING

#10-12 T20WPAN HEAD SCREW

Page 21: SECTION DETAIL – PANEL WITH HORIZONTAL TRIM · scale: 1" = 4" 2" 4" section detail – foundation @ grade water resistive barrier exterior sheathing grade minimum 3/4" furring vent

HORIZONTAL TRIM - TERMINATIONDETAIL:

Rev. 4 (2013)

Reveal2.0™

1.18Hardie Reveal2.0™ Panel Vertical Siding• Wood Framing• OSB or Plywood Sheathing• Pressure-Treated Wood Furring (Minimum 3/4" Nominal, 23/32" Actual Thickness) having specific gravity of 0.42 or greate• Shown with Panhead Screws into Furring

FACTORY CUT ENDSHORIZONTAL TRIMTERMINATION END CUTS