12
REGION, STATE DATE SECT.PAGE LA 2018 10'-9" x 10'-9" OCTAGONAL ELECTRICAL MANHOLE 7" 7" PLAN VIEW SECTION A-A SECTION B-B 2'-8" 7" 7" 10'-9" 36"OPENING 5'-0" MAX. 5'-0" MAX. NOTE: -MADE IN ACCORDANCE WITH ASTM C858 -STEEL REINFORCEMENT: ASTM A615 GRADE 60 -JOINT SEALANT: ASTM C990 WIDTH 10.75 FT. LENGTH 10.75 FT. WT.VERT.FT. 3,105 LBS. BASE SLAB 9,015 LBS. TOP SLAB 8,400 LBS. 7" 9'-5 13 16 " 7" 5'-8 9 16 " 9'-5 13 16 " 7" 7" B-B B-B A-A A-A 7" 10'-9" 7" 14.4.1

SECTION A-A SECTION B-B · 2020. 9. 12. · la 2018 6'-0" x 9'-0" precast electrical manhole width 6 ft. length 9 ft. wt./vert. ft. 2,400 lbs. base slab 6,930 lbs. top slab 6,930

  • Upload
    others

  • View
    3

  • Download
    0

Embed Size (px)

Citation preview

Page 1: SECTION A-A SECTION B-B · 2020. 9. 12. · la 2018 6'-0" x 9'-0" precast electrical manhole width 6 ft. length 9 ft. wt./vert. ft. 2,400 lbs. base slab 6,930 lbs. top slab 6,930

REGION, STATE

DATE SECT.PAGE

LA

2018

10'-9" x 10'-9" OCTAGONAL ELECTRICAL MANHOLE

7"

7"

PLAN VIEW

SECTION A-A SECTION B-B

2'-8"

7" 7"10'-9"

36"∅ OPENING

5'-0"

MAX.

5'-0"

MAX.

NOTE:

-MADE IN ACCORDANCE WITH ASTM C858

-STEEL REINFORCEMENT: ASTM A615 GRADE 60

-JOINT SEALANT: ASTM C990

WIDTH 10.75 FT.LENGTH 10.75 FT.

WT.VERT.FT. 3,105 LBS.BASE SLAB 9,015 LBS.TOP SLAB 8,400 LBS.

7" 9'-51316

" 7"

5'-8

9

16"9'

-5

13

16"

7"

7"

B-B

B-B

A-AA-A

7"10'-9"7"

14.4.1

Page 2: SECTION A-A SECTION B-B · 2020. 9. 12. · la 2018 6'-0" x 9'-0" precast electrical manhole width 6 ft. length 9 ft. wt./vert. ft. 2,400 lbs. base slab 6,930 lbs. top slab 6,930

REGION, STATE

DATE SECT.PAGE

LA

2018

4'-0" x 6'-0"PRECAST ELECTRICAL MANHOLE

SIDE VIEW

WIDTH 4 FT.

LENGTH 6 FT.

WT./VERT/ FT 1,650 LBS.

BASE SLAB 3,465 LBS.

TOP SLAB 3,465 LBS.

PLAN VIEW

12" ∅ x 4" SUMP

8"

AS REQ'D

EJ V-1600-5 R/C

PULLING CABLE

6'-0"

4'-0"

8"

3'-0"∅

10"

7'-0"

5'-0"

UNDERGROUND

DUCTBANK

AS REQ'D.

ELECTRIC

NOTE:

-MADE WITH ACCORDANCE WITH ASTM C858

-REINFORCING STEEL: PER ASTM A-615, GRADE 60.

-REINFORCING TO MEET AASHTO HS 20-44 LOADING.

-PRECAST STRUCTURE TO MEET ASTM C-857-92.

-JOINT SEALANT: RAM-NEK GASKET MATERIAL.

*EXTENSIONS AVAILABLE UPON REQUEST.

*FRAME AND GRATE/COVER AS REQUIRED.

*REFER TO DETAIL PAGES FOR HARDWARE INFORMATION.

END VIEW

3'-0"∅UNDERGROUND

DUCTBANK

AS REQ'D.

14.4.2

Page 3: SECTION A-A SECTION B-B · 2020. 9. 12. · la 2018 6'-0" x 9'-0" precast electrical manhole width 6 ft. length 9 ft. wt./vert. ft. 2,400 lbs. base slab 6,930 lbs. top slab 6,930

REGION, STATE

DATE SECT.PAGE

LA

2018

4'-0" x 8'-0"PRECAST ELECTRICAL MANHOLE

WIDTH 4 FT.

LENGTH 8 FT.

WT./VERT. FT. 1,950 LBS.

BASE SLAB 4,455 LBS.

TOP SLAB 4,455 LBS.

SIDE VIEW

PLAN VIEW

12" ∅ x 4" SUMP

8"

AS REQ'D

PULLING CABLE

8'-0"

4'-0"

8"

3'-0"∅

EJ V-1600-5 R/C

ELECTRIC

9'-0"

5'-0"

10"

UNDERGROUND

DUCTBANK

AS REQ'D

NOTE:

-MADE WITH ACCORDANCE WITH ASTM C858

-REINFORCING STEEL: PER ASTM A-615, GRADE 60.

-REINFORCING TO MEET AASHTO HS 20-44 LOADING.

-PRECAST STRUCTURE TO MEET ASTM C-857-92.

-JOINT SEALANT: RAM-NEK GASKET MATERIAL.

*EXTENSIONS AVAILABLE UPON REQUEST.

*FRAME AND GRATE/COVER AS REQUIRED.

*REFER TO DETAIL PAGES FOR HARDWARE INFORMATION.

END VIEW

3'-0"∅

14.4.3

Page 4: SECTION A-A SECTION B-B · 2020. 9. 12. · la 2018 6'-0" x 9'-0" precast electrical manhole width 6 ft. length 9 ft. wt./vert. ft. 2,400 lbs. base slab 6,930 lbs. top slab 6,930

REGION, STATE

DATE SECT.PAGE

LA

2018

4'-0" x 10'-0"PRECAST ELECTRICAL MANHOLE

WIDTH 4 FT.

LENGTH 10 FT.

WT./VERT. FT. 2,250 LBS.

BASE SLAB 5,455 LBS.

TOP SLAB 5,455 LBS.

SIDE VIEW

PLAN VIEW

12" ∅ x 4" SUMP

8"

AS REQ'D

PULLING CABLE

10'-0"

4'-0"

8"

3'-0"∅

EJ V-1600-5 R/C

ELECTRIC

11'-0"

5'-0"

10"

UNDERGROUND

DUCTBANK

AS REQ'D.

NOTE:

-MADE WITH ACCORDANCE WITH ASTM C858

-REINFORCING STEEL: PER ASTM A-615, GRADE 60.

-REINFORCING TO MEET AASHTO HS 20-44 LOADING.

-PRECAST STRUCTURE TO MEET ASTM C-857-92.

-JOINT SEALANT: RAM-NEK GASKET MATERIAL.

*EXTENSIONS AVAILABLE UPON REQUEST.

*FRAME AND GRATE/COVER AS REQUIRED.

*REFER TO DETAIL PAGES FOR HARDWARE INFORMATION.

END VIEW

3'-0"∅

14.4.4

Page 5: SECTION A-A SECTION B-B · 2020. 9. 12. · la 2018 6'-0" x 9'-0" precast electrical manhole width 6 ft. length 9 ft. wt./vert. ft. 2,400 lbs. base slab 6,930 lbs. top slab 6,930

REGION, STATE

DATE SECT.PAGE

LA

2018

5'-0" x 5'-0"PRECAST ELECTRICAL MANHOLE

SIDE VIEW

WIDTH 5 FT.

LENGTH 5 FT.

WT./VERT/ FT 1,650 LBS.

BASE SLAB 3,564 LBS.

TOP SLAB 3,564 LBS.

5'-0"

6'-0"

6'-0"

5'-0"

12" ∅ x 4" SUMP

8"

8"

AS REQ'D

UNDERGROUND

DUCTBANK

AS REQ'D

PULLING CABLE

3'-0"∅

EJ V-1600-5 R/C

ELECTRIC

NOTE:

-MADE WITH ACCORDANCE WITH ASTM C858

-REINFORCING STEEL: PER ASTM A-615, GRADE 60.

-REINFORCING TO MEET AASHTO HS 20-44 LOADING.

-PRECAST STRUCTURE TO MEET ASTM C-857-92.

-JOINT SEALANT: RAM-NEK GASKET MATERIAL.

*EXTENSIONS AVAILABLE UPON REQUEST.

*FRAME AND GRATE/COVER AS REQUIRED.

*REFER TO DETAIL PAGES FOR HARDWARE INFORMATION.

PLAN VIEW

14.4.5

Page 6: SECTION A-A SECTION B-B · 2020. 9. 12. · la 2018 6'-0" x 9'-0" precast electrical manhole width 6 ft. length 9 ft. wt./vert. ft. 2,400 lbs. base slab 6,930 lbs. top slab 6,930

REGION, STATE

DATE SECT.PAGE

LA

2018

5'-0" x 8'-6"PRECAST ELECTRICAL MANHOLE

WIDTH 5 FT.

LENGTH 8.5 FT.

WT./VERT. FT. 2,175 LBS.

BASE SLAB 5,643 LBS.

TOP SLAB 5,643 LBS.

SIDE VIEW

PLAN VIEW

12" ∅ x 4" SUMP

8"

AS REQ'D

PULLING CABLE

8'-6"

5'-0"

8"

3'-0"∅

EJ V-1600-5 R/C

ELECTRIC

9'-6"

6'-0"

10"

UNDERGROUND

DUCTBANK

AS REQ'D

A

A

NOTE:

-MADE WITH ACCORDANCE WITH ASTM C858

-REINFORCING STEEL: PER ASTM A-615, GRADE 60.

-REINFORCING TO MEET AASHTO HS 20-44 LOADING.

-PRECAST STRUCTURE TO MEET ASTM C-857-92.

-JOINT SEALANT: RAM-NEK GASKET MATERIAL.

*EXTENSIONS AVAILABLE UPON REQUEST.

*FRAME AND GRATE/COVER AS REQUIRED.

*REFER TO DETAIL PAGES FOR HARDWARE INFORMATION.

END VIEW

3'-0"∅

14.4.6

Page 7: SECTION A-A SECTION B-B · 2020. 9. 12. · la 2018 6'-0" x 9'-0" precast electrical manhole width 6 ft. length 9 ft. wt./vert. ft. 2,400 lbs. base slab 6,930 lbs. top slab 6,930

REGION, STATE

DATE SECT.PAGE

LA

2018

6'-0" x 6'-0"PRECAST ELECTRICAL MANHOLE

WIDTH 6 FT.

LENGTH 6 FT.

WT./VERT. FT. 1,950 LBS.

BASE SLAB 4,851 LBS.

TOP SLAB 4,851 LBS.

SIDE VIEW

PLAN VIEW

12" ∅ x 4" SUMP

8"

AS REQ'D

PULLING CABLE

6'-0"

8"

3'-0"∅

EJ V-1600-5 R/C

ELECTRIC

7'-0"

7'-0"

10"

UNDERGROUND

DUCTBANK

AS REQ'D

6'-0"

(TYPICAL ALL 4 SIDES)

NOTE:

-MADE WITH ACCORDANCE WITH ASTM C858

-REINFORCING STEEL: PER ASTM A-615, GRADE 60.

-REINFORCING TO MEET AASHTO HS 20-44 LOADING.

-PRECAST STRUCTURE TO MEET ASTM C-857-92.

-JOINT SEALANT: RAM-NEK GASKET MATERIAL.

*EXTENSIONS AVAILABLE UPON REQUEST.

*FRAME AND GRATE/COVER AS REQUIRED.

*REFER TO DETAIL PAGES FOR HARDWARE INFORMATION.

14.4.7

Page 8: SECTION A-A SECTION B-B · 2020. 9. 12. · la 2018 6'-0" x 9'-0" precast electrical manhole width 6 ft. length 9 ft. wt./vert. ft. 2,400 lbs. base slab 6,930 lbs. top slab 6,930

REGION, STATE

DATE SECT.PAGE

LA

2018

6'-0" x 9'-0"PRECAST ELECTRICAL MANHOLE

WIDTH 6 FT.

LENGTH 9 FT.

WT./VERT. FT. 2,400 LBS.

BASE SLAB 6,930 LBS.

TOP SLAB 6,930 LBS.

SIDE VIEW

PLAN VIEW

12" ∅ x 4" SUMP

8"

AS REQ'D

PULLING CABLE

6'-0"

8"

3'-0"∅

EJ V-1600-5 R/C

ELECTRIC

10'-0"

7'-0"

10"

UNDERGROUND

DUCTBANK

AS REQ'D

9'-0"

END VIEW

3'-0"∅

NOTE:

-MADE WITH ACCORDANCE WITH ASTM C858

-REINFORCING STEEL: PER ASTM A-615, GRADE 60.

-REINFORCING TO MEET AASHTO HS 20-44 LOADING.

-PRECAST STRUCTURE TO MEET ASTM C-857-92.

-JOINT SEALANT: RAM-NEK GASKET MATERIAL.

*EXTENSIONS AVAILABLE UPON REQUEST.

*FRAME AND GRATE/COVER AS REQUIRED.

*REFER TO DETAIL PAGES FOR HARDWARE INFORMATION.

14.4.8

Page 9: SECTION A-A SECTION B-B · 2020. 9. 12. · la 2018 6'-0" x 9'-0" precast electrical manhole width 6 ft. length 9 ft. wt./vert. ft. 2,400 lbs. base slab 6,930 lbs. top slab 6,930

REGION, STATE

DATE SECT.PAGE

LA

2018

6'-0" x 12'-0"TELEPHONE MANHOLE TYPE A

6"

3'-9"

3'-3"

6"

SIDE VIEW

12" ∅ x 4" SUMPS

1'-0" COLLAR

WIDTH 6 FT.

LENGTH 12 FT.

WT./VERT. FT. 2,354 LBS.

BASE SLAB 6,577 LBS.

TOP SLAB 6,577 LBS.

EJ V-1600-5 R/C

ELECTRIC

PULLING IRON

5"

2"

3'-0"∅

PLAN VIEW

12'-0"

6'-0"

12'-10" 2"

6'-10"

2"

6"

3'-9"

3'-3"

6"

END VIEW

1'-0" COLLAR

PULLING IRON

5"

2"

3'-0"∅

NOTE:

-MADE WITH ACCORDANCE WITH ASTM C858

-REINFORCING STEEL: PER ASTM A-615, GRADE 60.

-REINFORCING TO MEET AASHTO HS 20-44 LOADING.

-PRECAST STRUCTURE TO MEET ASTM C-857-92.

-JOINT SEALANT: RAM-NEK GASKET MATERIAL.

*EXTENSIONS AVAILABLE UPON REQUEST.

*FRAME AND GRATE/COVER AS REQUIRED.

*REFER TO DETAIL PAGES FOR HARDWARE INFORMATION.

14.4.9

Page 10: SECTION A-A SECTION B-B · 2020. 9. 12. · la 2018 6'-0" x 9'-0" precast electrical manhole width 6 ft. length 9 ft. wt./vert. ft. 2,400 lbs. base slab 6,930 lbs. top slab 6,930

REGION, STATE

DATE SECT.PAGE

LA

2018

7'-0" x 7'-0"PRECAST ELECTRICAL MANHOLE

WIDTH 7 FT.

LENGTH 7 FT.

WT./VERT. FT. 2,250 LBS.

BASE SLAB 6,336 LBS.

TOP SLAB 6,336 LBS.

SIDE VIEW

PLAN VIEW

12" ∅ x 4" SUMP

8"

AS REQ'D

PULLING CABLE

7'-0"

8"

3'-0"∅

EJ V-1600-4 R/C

ELECTRIC

8'-0"

8'-0"

10"

UNDERGROUND

DUCTBANK

AS REQ'D

7'-0"

(TYPICAL ALL 4 SIDES)

NOTE:

-MADE WITH ACCORDANCE WITH ASTM C858

-REINFORCING STEEL: PER ASTM A-615, GRADE 60.

-REINFORCING TO MEET AASHTO HS 20-44 LOADING.

-PRECAST STRUCTURE TO MEET ASTM C-857-92.

-JOINT SEALANT: RAM-NEK GASKET MATERIAL.

*EXTENSIONS AVAILABLE UPON REQUEST.

*FRAME AND GRATE/COVER AS REQUIRED.

*REFER TO DETAIL PAGES FOR HARDWARE INFORMATION.

14.4.10

Page 11: SECTION A-A SECTION B-B · 2020. 9. 12. · la 2018 6'-0" x 9'-0" precast electrical manhole width 6 ft. length 9 ft. wt./vert. ft. 2,400 lbs. base slab 6,930 lbs. top slab 6,930

REGION, STATE

DATE SECT.PAGE

LA

2018

8'-0" x 10'-0"PRECAST ELECTRICAL MANHOLE

WIDTH 8 FT.

LENGTH 10 FT.

WT./VERT. FT. 2,850 LBS.

BASE SLAB 9,801 LBS.

TOP SLAB 9,801 LBS.

SIDE VIEW

PLAN VIEW

12" ∅ x 4" SUMP

8"

AS REQ'D

PULLING CABLE

10'-0"

8'-0"

8"

3'-0"∅

EJ V-1600-5 R/C

ELECTRIC

11'-0"

9'-0"

10"

UNDERGROUND

DUCTBANK

AS REQ'D

END VIEW

3'-0"∅

NOTE:

-MADE WITH ACCORDANCE WITH ASTM C858

-REINFORCING STEEL: PER ASTM A-615, GRADE 60.

-REINFORCING TO MEET AASHTO HS 20-44 LOADING.

-PRECAST STRUCTURE TO MEET ASTM C-857-92.

-JOINT SEALANT: RAM-NEK GASKET MATERIAL.

*EXTENSIONS AVAILABLE UPON REQUEST.

*FRAME AND GRATE/COVER AS REQUIRED.

*REFER TO DETAIL PAGES FOR HARDWARE INFORMATION.

14.4.11

Page 12: SECTION A-A SECTION B-B · 2020. 9. 12. · la 2018 6'-0" x 9'-0" precast electrical manhole width 6 ft. length 9 ft. wt./vert. ft. 2,400 lbs. base slab 6,930 lbs. top slab 6,930

REGION, STATE

DATE SECT.PAGE

LA

2018

10'-0" x 10'-0"PRECAST ELECTRICAL MANHOLE

WIDTH 10 FT.

LENGTH 10 FT.

WT./VERT. FT. 3,775 LBS.

BASE SLAB 14,300 LBS.

TOP SLAB 12,000 LBS.

SIDE VIEW

PLAN VIEW

12" ∅ x 4" SUMP

9"

AS REQ'D

PULLING CABLE

10'-0"

10'-0"

8"

3'-0"∅

EJ V-1600-5 RING &

ELECTRIC COVER

11'-2"

11'-2"

6"

UNDERGROUND

DUCTBANK

AS REQ'D.

NOTE:

-MADE WITH ACCORDANCE WITH ASTM C858

-REINFORCING STEEL: PER ASTM A-615, GRADE 60.

-REINFORCING TO MEET AASHTO HS 20-44 LOADING.

-PRECAST STRUCTURE TO MEET ASTM C-857-92.

-JOINT SEALANT: RAM-NEK GASKET MATERIAL.

*EXTENSIONS AVAILABLE UPON REQUEST.

*FRAME AND GRATE/COVER AS REQUIRED.

*REFER TO DETAIL PAGES FOR HARDWARE INFORMATION.

RACKING AS REQ'D

CONCRETE INCREASER

RINGS AS REQ'D

EAST JORDAN IRON WORKS

MADE IN USA

ELECTRIC

MO/D

AY/Y

R X

MADEI N

USA

EA

ST

JO

RD

AN

IR

ON

WO

RK

S

V-

16

00

-5

41

6 0 0 5 1 0

AS

T

M

A4

8CL

35B