SD Series User’s Manual
SD1500/2500/3500 PURE SINE WAVE INVERTER
EN [Page 3]
SD1500/2500/3500 Signal de sortie sinusoïdal pur
FR [Page 47]
Legal Provisions
Copyrights 2017 COTEK Electronic IND. CO. All Rights Reserved.
Any part of this document may not be reproduced in any form for any purpose without the prior
written permission of COTEK Electronic IND. CO. For the conditions of the permission to use this
manual for publication, contact COTEK Electronic IND. CO., LTD. In all related COTEK product
activities, Neither COTEK Electronic IND. CO., LTD. nor its distributors or dealers be liable to
anyone for indirect, incidental, or consequential damages under any circumstances. Specifications
are subject to change without notice. Every attempt has been made to make this document
complete, accurate and up-to-date. COTEK Electronic IND. CO., LTD reserve the right to make
changes without notice and shall not be responsible for any damages, including indirect, incidental
or consequential damages, caused by reliance on the material presented, including, but not limited
to, omissions, typographical errors, arithmetical errors or listing errors in the content material. All
trademarks are recognized even if these are not marked separately. Missing designations do not
mean that a product or brand is not a registered trademark.
Table of Content
1. IMPORTANT SAFETY INFORMATION 1
1-1. General Safety Precautions 1
1-2. Precautions When Working with Batteries 1
1-3. Installation 2
2. FUNCTIONAL CHARACTERISTICS 3
2-1. General Information 3
2-2. Application 3
2-3. Electrical Performance 4
2-4. Mechanical Drawings 10
3. INTRODUCTION 12
3-1. Power ON / OFF / REMOTE (Main) switch 13
3-2. LED Indicator 13
3-3. DIP Switch (S1~S8) Assignment 14
3-4. DC Input - (please refer to DC wiring connections on P.20) 15
3-5. DC Input + (please refer to DC wiring connections on P.20) 16
3-6. Chassis Ground:Connect the wire # 8 AWG to vehicle chassis 16
3-7. AC Output (Please refer to hard wiring installation on P.21) 16
3-8. By-pass AC input (please refer to hard wiring installation on P.21) 16
3-9. AC input circuit breaker 16
3-10. AC output socket (please refer to 4-2-3. on P.24) 16
3-11. Reset Button (only to be used for Ethernet interface) 16
3-12. CAN1 and CAN2 Port (only to be used in parallel mode) 16
3-13. LCM Port 17
3-14. Green terminal (Remote and Parallel select) 18
3-15. RS-232 Port 19
3-16. Fan Ventilation 19
3-17. Protections Features 19
4. DC WIRING CONNECTIONS 20
4-1. DC Input Terminals 21
4-2. Hard-wire Installation 22
5. PARALLEL MODE 28
5-1. Prepare for Parallel Usage 28
5-2. Industry Applications 29
5-3. Wiring for Parallel Usage 31
5-4. AC Wiring Diagram 33
5-5. Remote command for the parallel connection 37
5-6. Remove Parallel Connection 37
6. RS-232 COMMAND 38
6-1. RS-232 command introduction 38
7. TROUBLESHOOTING 46
8. WARRANTY 46
1
1. Important Safety Information
WARNING!
Before using the inverter, read and save the safety instructions.
1-1. General Safety Precautions
1-1-1. Do not expose the Inverter to rain, snow, spray, bilge or dust.
To reduce risk of hazard, do not cover or obstruct the ventilation openings. Do
not install the inverter in a zero-clearance compartment. Overheating may
take place.
1-1-2. To avoid a risk of fire and electric shock, please make sure that existing wiring
is in good electrical condition; and that wire size is not undersized. Do not
operate the Inverter with damaged or substandard wiring.
1-1-3. This equipment contains components which can produce arcs or sparks.
To prevent fire or explosion do not install in compartments containing batteries
or flammable materials or in locations which require ignition protected
equipment. This includes any space containing gasoline-powered machinery,
fuel tanks, joints, fittings, or other connection between components of the fuel
system.
1-1-4. An over current protection at the time of installation shall be provided by
others for the AC output circuit.
1-1-5. Additional breakers suitable for 20 A branch circuit protection shall be
provided for the GFCI receptacles.
1-2. Precautions When Working with Batteries
1-2-1. If battery acid contacts skin or clothing, wash immediately with soap and water.
If acid enters eye, immediately wash eyes with running cold water for at least
20 minutes and get medical attention immediately.
1-2-2. Never smoke or allow a spark or flame in vicinity of battery or engine.
1-2-3. Do not drop a metal tool on the battery. The resulting spark or short-circuit on
the battery or other electrical part may cause an explosion.
1-2-4. Remove personal metal items such as rings, bracelets, necklaces, and
watches when working with a lead-acid battery.
A lead-acid battery produces a short-circuit current high enough to weld a ring
or similar item to metal causing a severe burn.
2
EN
1-3. Installation
The power inverter should be installed in a location that meets the following
requirements:
Dry – Do not allow water to drip or splash on the inverter.
Cool – Ambient air temperature should be between -20℃ and 50℃, but he cooler
the better.
Safety – Do not install batteries in the compartment or other areas here flammable
fumes existence such as fuel storage areas or engine compartments.
Ventilated – Allow at least one feet of clearance around the Inverter for air flow.
Ensure the ventilation shafts on the rear and bottom of the unit are not
obstructed.
Dust-free – Do not install the Inverter in dusty environments here dust, wood
particles or other filings/shavings are present. The dust can be pulled
into the unit when the cooling fan is in operation.
Close to batteries – Avoid excessive cable lengths but do not install the inverter in
the same compartment as batteries.
Use the recommended wire lengths and sizes (refer to section 4.DC wiring
connections).
Do not mount the inverter where it is exposed to the gases produced by the battery.
These gases are very corrosive and prolonged exposure will damage the inverter.
WARNING!
Shock Hazard. Before proceeding further, carefully check that the inverter is
NOT connected to any batteries, and that all wiring is disconnected from any
electrical sources . Do not connect the output terminals of the inverter to an
incoming AC source.
3
2. Functional Characteristics
2-1. General Information SD-series is new generation power inverter equipped with N+1 parallel power
function , 3-phase capability, and AC transfer switch. SD series is suitable for RV,
Marine and Emergency appliances.
Features
Parallel redundancy design for power expansion
Multiple industrial applications that create 1Ф3W / 3Ф4W power systems
User-friendly remote control
Automatic master mechanism to eliminate single point failure and optimize
reliability
Built-in ATS and AC circuit breaker
Optional STS module, transfer time is less than 4ms.
RS-232 communication
Input & output fully isolation
Output voltage / power saving mode is selectable by DIP switch and remote
control (CR-10)
Input Protection:Reverse Polarity (Fuse) / Under Voltage / Over Voltage
Protection
Output Protection:Short Circuit / Overload / Over Temperature / Over Voltage
Protection
To get the most out of the power inverter, it must be installed and used properly.
Please read the instructions in this manual before installation and operation of this
model.
2-2. Application
2-2-1. Power tools–circular saws, drills, grinders, sanders, buffers, weed and hedge
trimmers, air compressors.
2-2-2. Office equipment – computers, printers, monitors, facsimile machines,
scanners.
2-2-3. Household items – vacuum cleaners, fans, fluorescent and incandescent
lights, shavers, sewing machines.
2-2-4. Kitchen appliances – coffee makers, blenders, ice markers, toasters.
2-2-5. Industrial equipment – metal halide lamp, high pressure sodium lamp.
2-2-6. Home entertainment electronics – television, VCRs, video games, stereos,
musical instruments, satellite equipment.
2-2-7. Vehicle, yacht and off-grid solar power systems.
4
EN
2-3. Electrical Performance
2-3-1. SD1500 Specification
MODEL SD1500-112 SD1500-124 SD1500-148 SD1500-212 SD1500-224 SD1500-248
Output
Rating Power 1500VA (de-rating after 40°C, refer to de-rating curve)
Output Power
(Max. 3 min.) 1500~1800VA
Peak Power
(Max. 3 sec.) 1800~2400VA
Surge Power
(Max. 0.2 sec.) >2400VA
Waveform Pure Sine Wave
Efficiency (Max.) 88% 89% 90% 88% 88% 90%
Output Voltage
(@rated VDC) 100 / 110 / 115 / 120VAC ± 3% 200 / 220 / 230 / 240VAC ± 3%
Output Frequency 50 / 60Hz ± 0.1%
Total Harmonic
Distortion (THD)
< 3% @ under condition:
greater than 1.15 times of the rated VDC,
110V / linear load)
< 3% @ under condition:
greater than 1.15 times of the rated VDC,
230V / linear load)
DC Input
DC Voltage 12VDC 24VDC 48VDC 12VDC 24VDC 48VDC
Voltage Range 10.0~16.0 VDC 20.0~32.0 VDC 40.0~64.0 VDC 10.0~16.0 VDC 20.0~32.0 VDC 40.0~64.0 VDC
No load Power
Consumption @12VDC @24VDC @48VDC @12VDC @24VDC @48VDC
On Mode @ Save Mode 0.9A 0.35A 0.3A 1.1A 0.7A 0.4A
On Mode @ No Load Mode < 2.4A < 1.2A < 0.6A < 3.3A < 1.6A < 0.8A
Fuse 40Ax6 20Ax6 15Ax4 40Ax6 20Ax6 15Ax4
AC Input
AC Range 100 / 110 / 115 / 120VAC ± 12.5% 200 / 220 / 230 / 240VAC ± 12.5%
Frequency Selectable 50 / 60 Hz
Synchronous
Frequency 47~57 / 53~63 Hz
Circuit Breaker 20A 10A
Transfer Switch①
Standard ATS:Inverter to utility AC:<5ms.; Utility AC to inverter:16-50ms.
Optional STS Module : Single < 4ms ; N+1 & 1P3W & 3P4W < 6ms
Protection
BAT.Low Alarm ± 3% 10.5VDC 21.0VDC 42.0VDC 10.5VDC 21.0VDC 42.0VDC
BAT.Low Shut-down ± 3% 10.0VDC 20.0VDC 40.0VDC 10.0VDC 20.0VDC 40.0VDC
BAT.Low Restart ± 3% 12.5VDC 25.0VDC 50.0VDC 12.5VDC 25.0VDC 50.0VDC
BAT.High Alarm ± 3% 15.5VDC 31.0VDC 62.0VDC 15.5VDC 31.0VDC 62.0VDC
BAT.High Shut-down ± 3% 16.0VDC 32.0VDC 64.0VDC 16.0VDC 32.0VDC 64.0VDC
BAT.High Restart ± 3% 15.0VDC 30.0VDC 60.0VDC 15.0VDC 30.0VDC 60.0VDC
Input Protection Reverse Polarity (Fuse) / Under Voltage / Over Voltage Protection / AC over current (Breaker)
5
MODEL SD1500-112 SD1500-124 SD1500-148 SD1500-212 SD1500-224 SD1500-248
Output Protection Short Circuit / Overload / Over Temperature / Over Voltage Protection
Environment
Working Temp. -20~+60°C; refer SD1500 power de-rating curve
Storage Temp. -40~+70°C
Relative Humidity Max. 90%, non-condensing
Safety & EMC
Safety Standards Certified UL 458
(UL only for hardwire) ---- Certified EN 62368-1
EMC Standards Certified FCC Class B Certified EN55032, EN55024
E-Mark ---- Certified CISPR 25; ISO 7637-2
Control & Signal
LED Indicator Input voltage level, faulty status
Remote Control CR-6, CR-8 and CR-10
Others
Dimension (WxHxD) 283x128x351 mm / 11.14x5.04x13.82 inch
Weight 5.5 kg
Cooling Load & Thermal control fan
Communication Port RS-232 (RJ-11 type connector), Ethernet (Optional)
Note
The specifications are subject to change without prior notice. All the test
environments are conducted under the rated power operation conditions.
① Please refer to P.10 Transfer-Time Table.
6
EN
2-3-2. SD2500 Specification
MODEL SD2500-112 SD2500-124 SD2500-148 SD2500-212 SD2500-224 SD2500-248
Output
Rating Power 2500VA (de-rating after 40°C, refer to de-rating curve)
Output Power
(Max. 3 min.) 2500~3000VA
Peak Power
(Max. 3 sec.) 3000~4000VA
Surge Power
(Max. 0.2 sec.) >4000VA
Waveform Pure Sine Wave
Efficiency (Max.) 88% 89% 90% 88% 88% 90%
Output Voltage
(@rated VDC) 100 / 110 / 115 / 120VAC ± 3% 200 / 220 / 230 / 240VAC ± 3%
Output Frequency 50 / 60Hz ± 0.1%
Total Harmonic
Distortion (THD)
< 3% @ under condition:
greater than 1.15 times of the rated VDC,
110V / linear load)
< 3% @ under condition:
greater than 1.15 times of the rated VDC,
230V / linear load)
DC Input
DC Voltage 12VDC 24VDC 48VDC 12VDC 24VDC 48VDC
Voltage Range 10.0~16.0 VDC 20.0~32.0 VDC 40.0~64.0 VDC 10.0~16.0 VDC 20.0~32.0 VDC 40.0~64.0 VDC
No load Power
Consumption @12VDC @24VDC @48VDC @12VDC @24VDC @48VDC
On Mode @ Save Mode 0.9A 0.35A 0.3A 1.1A 0.7A 0.4A
On Mode @ No Load Mode < 3.2A < 1.6A < 1.0A < 3.6A < 1.8A < 1A
Fuse 40Ax9 20Ax9 15Ax6 40Ax9 20Ax9 15Ax6
AC Input
AC Range 100 / 110 / 115 / 120VAC ± 12.5% 200 / 220 / 230 / 240VAC ± 12.5%
Frequency Selectable 50 / 60 Hz
Synchronous
Frequency 47~57 / 53~63 Hz
Circuit Breaker 35A 20A
Transfer Switch①
Standard ATS:Inverter to utility AC:8~10ms.; Utility AC to inverter:16~50ms.
Optional STS module:Single < 4ms; N+1 & 1P3W & 3P4W < 6ms
Protection
BAT.Low Alarm ± 3% 10.5VDC 21.0VDC 42.0VDC 10.5VDC 21.0VDC 42.0VDC
BAT.Low Shut-down ± 3% 10.0VDC 20.0VDC 40.0VDC 10.0VDC 20.0VDC 40.0VDC
BAT.Low Restart ± 3% 12.5VDC 25.0VDC 50.0VDC 12.5VDC 25.0VDC 50.0VDC
BAT.High Alarm ± 3% 15.5VDC 31.0VDC 62.0VDC 15.5VDC 31.0VDC 62.0VDC
BAT.High Shut-down ± 3% 16.0VDC 32.0VDC 64.0VDC 16.0VDC 32.0VDC 64.0VDC
BAT.High Restart ± 3% 15.0VDC 30.0VDC 60.0VDC 15.0VDC 30.0VDC 60.0VDC
7
MODEL SD2500-112 SD2500-124 SD2500-148 SD2500-212 SD2500-224 SD2500-248
Input Protection Reverse Polarity (Fuse) / Under Voltage / Over Voltage Protection / AC over current (Breaker)
Output Protection Short Circuit / Overload / Over Temperature / Over Voltage Protection
Environment
Working Temp. -20~+60°C; refer SD2500 power de-rating curve
Storage Temp. -40~+70°C
Relative Humidity Max. 90%, non-condensing
Safety & EMC
Safety Standards Certified UL 458
(UL only for hardwire) ---- Certified EN60950-1
EMC Standards Certified FCC Class B
②Certified EN 55014-1, EN 55014-2;
EN 61000-3-2, -3-3; EN61204-3;
EN 61000-6-1, -6-2, -6-3, -6-4
IEC 61000-4-2, 3, 4, 5, 6, 11
E-Mark ---- Certified CISPR 25; ISO 7637-2
Control & Signal
LED Indicator Input voltage level, faulty status
Remote Control CR-6, CR-8 and CR-10
Others
Dimension (WxHxD) 283x128x436 mm / 11.14x5.04x17.17 inch
Weight 8 kg
Cooling Load & Thermal control fan
Communication Port RS-232 (RJ-11 type connector), Ethernet (Optional)
Note
The specifications are subject to change without prior notice. All the test
environments are conducted under the rated power operation conditions.
① Please refer to P.10 Transfer-Time Table.
② EN 55014-1, EN 55014-2 Class B: output cable less than 2 meters.
8
EN
2-3-3. SD3500 Specification
MODEL SD3500-112 SD3500-124 SD3500-148 SD3500-212 SD3500-224 SD3500-248
Output
Rating Power
3500W
(de-rating after 35°C, refer to de-rating curve for 12V)
(de-rating after 40°C, refer to de-rating curve for 24V and 48V)
Output Power
(Max. 3 min.) 3500~4500 W
Peak Power
(Max. 3 sec.) 4500~6000 W
Surge Power
(Max. 0.2 sec.) >6000 VA
Waveform Pure Sine Wave
Efficiency (Max.) 90% 90% 91% 90% 91% 91%
Output Voltage
(@rated VDC) 100 / 110 / 115 / 120VAC ± 3% 200 / 220 / 230 / 240VAC ± 3%
Output Frequency 50 / 60Hz ± 0.1%
Total Harmonic
Distortion (THD)
< 3% @ under condition:
greater than 1.15 times of the rated VDC,
110V / linear load)
< 3% @ under condition:
greater than 1.15 times of the rated VDC,
110V / linear load)
DC Input
DC Voltage 12VDC 24VDC 48VDC 12VDC 24VDC 48VDC
Voltage Range 10.0~16.0 VDC 20.0~32.0 VDC 40.0~64.0 VDC 10.0~16.0 VDC 20.0~32.0 VDC 40.0~64.0 VDC
No load Power
Consumption @12VDC @24VDC @48VDC @12VDC @24VDC @48VDC
On Mode @ Save Mode 1.4A 0.5A 0.5A 1.4A 0.5A 0.5A
On Mode @ No Load Mode < 2.9A < 1.4A < 0.8A < 3.6A < 1.8A < 1A
Fuse 40Ax12 20Ax12 20Ax6 40Ax12 20Ax12 20Ax6
AC Input
AC Range 100 / 110 / 115 / 120VAC ± 12.5% 200 / 220 / 230 / 240VAC ± 12.5%
Frequency Selectable 50 / 60 Hz
Synchronous
Frequency 47~57 / 53~63 Hz
Circuit Breaker 35A 20A
Transfer Switch①
Standard ATS:Inverter to utility AC:8~10ms.; Utility AC to inverter:16~50ms.
Optional STS module:Single < 4ms; N+1 & 1P3W & 3P4W < 6ms
Protection
BAT.Low Alarm ± 3% 10.5VDC 21.0VDC 42.0VDC 10.5VDC 21.0VDC 42.0VDC
BAT.Low Shut-down ± 3% 10.0VDC 20.0VDC 40.0VDC 10.0VDC 20.0VDC 40.0VDC
BAT.Low Restart ± 3% 12.5VDC 25.0VDC 50.0VDC 12.5VDC 25.0VDC 50.0VDC
BAT.High Alarm ± 3% 15.5VDC 31.0VDC 62.0VDC 15.5VDC 31.0VDC 62.0VDC
BAT.High Shut-down ± 3% 16.0VDC 32.0VDC 64.0VDC 16.0VDC 32.0VDC 64.0VDC
BAT.High Restart ± 3% 15.0VDC 30.0VDC 60.0VDC 15.0VDC 30.0VDC 60.0VDC
9
MODEL SD3500-112 SD3500-124 SD3500-148 SD3500-212 SD3500-224 SD3500-248
Input Protection Reverse Polarity (Fuse) / Under Voltage / Over Voltage Protection / AC over current (Breaker)
Output Protection Short Circuit / Overload / Over Temperature / Over Voltage Protection
Environment
Working Temp. -20~+60°C; refer SD3500 power de-rating curve
Storage Temp. -40~+70°C
Relative Humidity Max. 90%, non-condensing
Safety & EMC
Safety Standards Certified UL 458
(UL only for hardwire) ---- Certified EN60950-1
EMC Standards Certified FCC Class B
②Certified EN 55014-1, EN 55014-2;
EN 61000-3-2, -3-3; EN61204-3;
EN 61000-6-1, -6-2, -6-3, -6-4
IEC 61000-4-2, 3, 4, 5, 6, 11
E-Mark ---- Certified CISPR 25; ISO 7637-2
Control & Signal
LED Indicator Input voltage level, faulty status
Remote Control CR-6, CR-8 and CR-10
Others
Dimension (WxHxD) 283x128x496 mm / 11.14x5.04x19.53 inch
Weight 10 kg
Cooling Load & Thermal control fan
Communication Port RS-232 (RJ-11 type connector), Ethernet (Optional)
Note
The specifications are subject to change without prior notice. All the test
environments are conducted under the rated power operation conditions.
① Please refer to P.10 Transfer-Time Table.
② EN 55014-1, EN 55014-2 Class B: output cable less than 2 meters.
De-rating Curve
Figure 1. SD1500 de-rating curve
10
EN
Figure 2. SD2500 de-rating curve
Figure 3. SD3500 de-rating curve
SD1500 Transfer-Time Table
Mode / Transfer Switch ATS STS
Haphazard Inverter to utility AC: <5ms.;
Utility AC to inverter: 16~50ms.
Frequency is synchronized: < 4ms.;
Frequency is not synchronized:
Inverter to utility AC: < 4ms.;
Utility AC to inverter: 16~50ms.
Normal Inverter to utility AC: <5ms.;
Utility AC to inverter: 16~25ms. < 4ms
Exacting Inverter to utility AC: <5ms.;
Utility AC to inverter: 16~50ms.
Inverter to utility AC: < 4ms.;
Utility AC to inverter: 16~50ms.
Online Inverter to utility AC: <5ms.;
Utility AC to inverter: 16~25ms. < 4ms
SD2500 / SD3500 Transfer-Time Table
Mode / Transfer Switch ATS STS
Haphazard Inverter to utility AC: 8~10ms.;
Utility AC to inverter: 16~50ms.
Frequency is synchronized: < 4ms.;
Frequency is not synchronized:
Inverter to utility AC: < 4ms.;
Utility AC to inverter: 16~50ms.
Normal Inverter to utility AC: 8~10ms.;
Utility AC to inverter: 16~25ms. < 4ms
Exacting Inverter to utility AC: 8~10ms.;
Utility AC to inverter: 16~50ms.
Inverter to utility AC: < 4ms.;
Utility AC to inverter: 16~50ms.
Online Inverter to utility AC: 8~10ms.;
Utility AC to inverter: 16~25ms. < 4ms
Table 1. SD series transfer-time
11
2-4. Mechanical Drawings
Figure 4. SD series mechanical drawings
Model A (mm) B (mm) C (mm) D (mm) E (mm) F (mm) G (mm) H (mm)
SD1500 351 160 93.1 268.6 8.5 11.5 128 283
SD2500 436 240.0 95.6 268.6 8.5 11.5 128 283
SD3500 496 240.0 125.6 268.6 8.5 11.5 128 283
Table 2. SD series dimension
12
EN
3. Introduction
【Version 1】General Model
Figure 5. SD general model front panel
【Version 2】UL Model
Figure 6. SD UL model front panel
Figure 7. SD series rear panel
13
Front Panel / Rear Panel
1 Power ON/OFF/REMOTE (Main) switch 10 AC output socket
2 Status LED 11 Reset Button
3 Dip Switch (S1~S8) 12 CAN2 Port (only to be used in parallel mode)
4 DC Input - 13 CAN1 Port (only to be used in parallel mode)
5 DC Input + 14 LCM Port (Connection for LCD remote control
panel)
6 Chassis Ground 15 Green terminal (Remote and Parallel select)
7 AC Output 16 Remote / RS-232 port
8 By-pass AC Input 17 FAN
9 AC input circuit breaker
Table 3. SD front panel / rear panel introduction
3-1. Power ON / OFF / REMOTE (Main) switch A. Before installing the inverter, please ensure the main switch is in the OFF position.
B. Before using the remote unit, please ensure the main switch is in the REMOTE
position.
C. Main switch ON / OFF will not control AC Grid input, therefore for any
maintenances please remove the AC Grid connection to prevent damage of SD
series, then turn off the Main switch to OFF position for maintenance service.
3-2. LED Indicator
Green LED LED Signal Status
Solid Power OK
Slow Blink Power Saving
Intermittent Blink Bypass
Orange LED LED Signal Status
Fast Blink OVP
Slow Blink UVP
Red LED LED Signal Status
Intermittent Blink OTP
Fast Blink OVP- Shut-down
Slow Blink UVP- Shut-down
Solid OLP
Intermittent Blink Fan Failure
Intermittent Blink Component Failure
Table 4. SD LED indicator
14
EN
3-3. DIP Switch (S1~S8) Assignment
Figure 8. DIP switch (S1~S8)
PIN# PIN Assignment
1 AC output voltage setting
2 AC output voltage setting
3 AC output frequency setting
4 To set-up 3 Phase output or Energy-saving level
5 To set-up 3 Phase output or Energy-saving level
6 To set-up 3 Phase output or Energy-saving level
7 To set-up DIP Switch S4~S6 for power saving or 3 Phase output
8 To set-up function parameters adjustment via LCM port or DIP switch
Table 5. DIP switch (S1~S8) PIN assignment
3-3-1. DIP switch set-up
S1 S2 S3 S4 S5 S6 S7 S8 Scenario
0 0 X X X X X X AC output voltage:100VAC/200VAC
1 0 X X X X X X AC output voltage:110VAC/220VAC
0 1 X X X X X X AC output voltage:115VAC/230VAC
1 1 X X X X X X AC output voltage:120VAC/240VAC
X X 0 X X X X X AC output frequency:50Hz
X X 1 X X X X X AC output frequency:60Hz
X X X X X X 0 X Power saving mode setting (S4~S6); No
master-slave in parallel
X X X X X X 1 X 3 Phase output setting (S4~S6)
X X X X X X X 0 Adjust function parameters via LCM port
X X X X X X X 1 Adjust function parameters via DIP switch
1=ON / 0=OFF
Table 6. DIP switch set-up
3-3-2. Power Saving Mode
Power Saving Mode is adjustable and set by the Dip Switches,S4, S5 and S6 on the
front panel. Example SD2500:Saving set 2%, the load is below 50W 10 sec. will into
saving mode, more than 150W or more leave saving mode.
A. Power device enter the saving mode
The rate power x setting % = the threshold enter the power saving model
In case the load less than threshold value 10 seconds, the power device will enter
the saving mode.
1=ON/0=OFF
15
B. Power device leaving saving mode(re-start)
Restart threshold = rate power x setting % x 2~3
In case the power over the restart threshold, the power device will re-start and
provide the AC power.
S1 S2 S3 S4 S5 S6 S7 S8 Scenario
X X X 0 0 0 0 X Power saving DISABLE
X X X 1 1 0 0 X Go in power saving mode when output load is
under 4% of rating power
X X X 0 0 1 0 X Go in power saving mode when output load is
under 5% of rating power
X X X 1 0 1 0 X Go in power saving mode when output load is
under 6% of rating power
X X X 0 1 1 0 X Go in power saving mode when output load is
under 7% of rating power
X X X 1 1 1 0 X Go in power saving mode when output load is
under 8% of rating power
1=ON / 0=OFF
Table 7. Power saving mode set-up
3-3-3. S4~S6 Set-up for parallel application
S1 S2 S3 S4 S5 S6 S7 S8 Scenario
X X X 0 0 0 1 X
Master (0°); "R" Phase
to be used for 1Ø 3W output in series
connection(Master) or 3Ø 4W output
connection("R" Phase)
X X X 0 0 1 1 X Slave (0°) with current sharing
to be used in parallel connection only
X X X 0 1 1 1 X Slave (180°), to be used for 1Ø 3W output in
series connection(L-NN-L)
X X X 1 0 0 1 X
Slave (-120°), "S" Phase
to support "S" Phase be(-120°) in 3Ø 4W
output connection
X X X 1 0 1 1 X
Slave (120°), "T" Phase
to support "T" Phase be(120°) in 3Ø 4W
output connection
X X X 1 1 1 1 X Disable parallel function
1=ON / 0=OFF
Table 8. Parallel application set-up
3-3-4. Parameter select: “S8” select SD’s parameter setting by dip switch or LCM port
Set Value S8
LCM port 0
DIP switch 1
1=ON / 0=OFF
Table 9. Parameter select
3-4. DC Input - (please refer to DC wiring connections on P.20)
16
EN
3-5. DC Input + (please refer to DC wiring connections on P.20)
3-6. Chassis Ground:Connect the wire # 8 AWG to vehicle chassis
WARNING!
Operating the inverter without a proper ground connection may cause electrical
safety hazard.
3-7. AC Output (Please refer to hard wiring installation on P.22)
3-8. By-pass AC input (please refer to hard wiring installation on P.22)
3-9. AC input circuit breaker The AC input circuit breaker protects the model from overload. When an overload
condition exists, the circuit breaker stops supplying output AC grid power. To reset it,
push the circuit breaker switch then the model will be back in normal operation. The
source fault should be corrected before you reset it.
3-10. AC output socket (please refer to 4-2-3. on P.24)
3-11. Reset Button (only to be used for Ethernet interface) The Reset Button is to be used to resume the IP address to factory default value:
IP:192.168.100.181
Subnet Mask:255.255.255.0
3-12. CAN1 and CAN2 Port (only to be used in parallel mode)
Figure 9. CAN1 and CAN2 port
1. Before using parallel mode, you need to ensure the green terminal’s parallel jump
status is set to ON.
2. Use the RJ-45 line (RJ-45 network cable:parallel connection) to link one of the
SD Series CAN1 (CAN2) port to the other CAN1 (CAN2) port.
PIN# LCM port CAN1 port CAN2 port
1 CANH CAN_H CAN_H
2 CANL CAN_L CAN_L
3 P1 Reserved Reserved
4 VCC- Reserved Reserved
5 VCC+ Reserved Reserved
6 DIS Reserved Reserved
7 5VS- RND RND
8 5VS+ Reserved Reserved
Table 10. LCM, CAN1, CAN2 port:PIN number and signal description
17
WARNING!
LCM port is for remote control connection only.
Please make sure the connection is correct. (CAN cable to CAN1 / CAN2
port , Remote cable to LCM port)
If CAN cable is connected to LCM port, or vice versa, the inverter will be
damaged.
3-13. LCM Port
Connection for LCD remote control panel, you can set and display the SD-series
operation status.
Figure 10. LCM port
Figure 11. LCM cable
LCD Remote Control Panel SD Series
PIN Num. Signal Description PIN Num.
1 CANH 1
2 CANL 2
3 PON 3
4 VCC- 4
5 VCC+ 5
6 DIS 6
7 5VS- 7
8 5VS+ 8
Table 11. PIN number and signal description for LCD remote control
Note
The cables should be as short as possible (less than 32.8 feet / 10 meters) so
that they can handle the signal.
18
EN
3-14. Green terminal (Remote and Parallel select)
Figure 12. Green terminal
PIN # PIN Assignment
1 GND
2 -ENB
3 ENB
4 Parallel Jump
5 Parallel Jump
Table 12. Green terminal PIN assignment
3-14-1. Parallel Jump Function (please refer to section 5 for further detailed info.)
1. Before installing the inverter, you need to ensure the main switch is in the
OFF position.
2. Use 20 ~ 24 #AWG wire to connect the parallel jump terminal.
3-14-2. Remote Control Function
1. Before installing the inverter, please ensure that the main switch is in the
OFF position.
2. Before using the remote control terminal, please ensure the main switch is
in the REMOTE position.
3. Use 20 ~ 24 #AWG wire to connect the remote control terminal.
4. Remote control ON/OFF inverter setup status.
Figure 13. Remote control function setting
Note
The above 4 methods can be used to turn ON/OFF.
19
3-15. RS-232 Port
RS-232 Port:Serial port monitoring and control through computer’s interface.
Figure 14. RS-232 port
Figure 15. RS-232 cable
SD Series Computer
PIN Num. Signal Description PIN Num. Signal Description
1 Not used 1 Not used
2 GND 5 GND
3 RXD 3 TXD
4 TXD 2 RXD
5 Not used Not used
6 Not used Not used
Table 13. The connection between SD series and computer
The connection between this SD-series and the computer is as follows:
Figure 16.
The connection between SD series and computer
3-16. Fan Ventilation
The rear panel must keep the distance at least 1 feet from any surrounding items.
3-17. Protections Features
Model
DC Input (VDC)
Over Voltage Over Voltage
Alarm
Under Voltage Under Voltage
Alarm Shut-down Restart Shut-down Restart
12V 16 ± 0.25 15 ± 0.25 15.5 ± 0.25 10 ± 0.25 12.5 ± 0.25 10.5 ± 0.25
24V 32 ± 0.5 30 ± 0.5 31 ± 0.5 20 ± 0.5 25 ± 0.5 21 ± 0.5
48V 64 ± 1 60 ± 1 62 ± 1 40 ± 1 50 ± 1 42 ± 1
OVA only LED prompt, no beeper alarm.
Table 14. Protections Features
20
EN
4. DC Wiring Connections
Follow the instructions to connect the battery cables to the DC input terminals of the
Inverter. The cable should be as short as possible (less than 6 feet / 1.8 meters ideally)
so that it can handle the required current in accordance with the electrical codes or
application regulations. Inappropriate length of cables will reduce the inverter
performance such as poor surge capability, frequent low-input voltage warnings, and
shut-down. When under voltage protect condition, please check the cable size and
specification (length and diameter should conform to manual requirements) between
battery and SD model.
The longer or the narrower the cable is, the more the voltage drops. Increasing your DC
cable diameter will help to improve the situation.
The following are recommended cable diameter for the best performance of the inverter.
(Applies to both 120V and 230V versions)
Model No. Wire AWG Inline Fuse
SD1500-112 / 212 # 0 250 A
SD1500-124 / 224 # 1 125A
SD1500-148 / 248 # 4 90A
SD2500-112 / 212 # 3/0 350 A
SD2500-124 / 224 # 1 175 A
SD2500-148 / 248 # 4 90A
SD3500-112 / 212 # 4/0 500 A
SD3500-124 / 224 # 0 250 A
SD3500-148 / 248 # 2 125 A
Table 15. SD series wiring cable diameter and inline fuse
Connect the cables to the power input terminals on the front panel of the inverter. The
red terminal is positive (+) and black terminal is negative (-).
Insert the cables into the terminals and tighten the screw to clamp the wires securely.
WARNING!
1. Make sure all the DC connections are tight (torque to 11 ft-lbs, 15 Nm Max.).
Loose connections could overheat and result in a potential hazard.
2. The installation of a fuse must be on the positive cable. Failure to place a
fuse on “+” cables running between the inverter and battery may cause
damage to the inverter and will void warranty.
Also, only use high quality copper wire and keep the cable length short - maximum of
3 - 6 feet.
21
Do not place anything
between battery cable lug
and terminal surface.
Assemble exactly as shown.
Figure 17. Battery cabling
WARNING!
During the first installation, a small spark is a normal phenomenon because
the internal capacitors charging. Do not be concerned.
4-1. DC Input Terminals
Connect DC input terminals to 12V / 24V / 48V battery or other power sources.
[ + ] represents positive, [ - ] represents negative. Reverse polarity connection can
blow the internal fuse and may damage the inverter permanently.
Model DC Input Voltage
Minimum Maximum
12V 10V 16V
24V 20V 32V
48V 40V 64V
Table 16. SD series DC input voltage range
22
EN
4-2. Hard-wire Installation
4-2-1. SD series provides the flexibility of hard-wire connection, and this function will
make external control panel wiring easier.
【Version 1】General model
Step 1.
Remove the four screws of AC wiring compartment and pull it out with care.
Figure 18. General model setting─Step 1
Step 2.
Pull the line through the snap bushing of the AC wiring compartment cover then
follow below picture operation.
Figure 19. General model setting─Step 2
100VAC~120VAC / 200VAC~240VAC System
Figure 20. General model setting─AC wiring
23
Note
The only difference between 110V and 220V is within the AC Input breaker
L or N and thus will not affect the wiring configuration.
Note
In case that user wants to install the earth-leakage circuit breaker, COTEK
recommend time delay type. The major specification of the circuit breaker
is as following:
Earth-leakage current:100mA, 300mA, 500mA
Time:0.45 second, 1 second, 2 seconds
Recommend model:NV50-SN, Time delay type of Shihin Electric
【Version 2】UL model
Step 1.
Use the screwdriver to remove the cover.
Figure 21. UL model setting─Step 1
Step 2.
AC cable pass through the ring. Wire the AC cable on the terminal.
Figure 22. UL model setting─Step 2
24
EN
Figure 23. UL model setting─AC wiring
Step 3.
Use the screwdriver to fix the cover.
Figure 24. UL model setting─Step 3
4-2-2. Connect AC output and AC input wiring to the SD series terminals.
Please take the following information as your reference.
Terminal Wire Color Wire Length / Gauge
AC OUTPUT Line (L) Black
Within 16 feet / AWG#
200-240VAC:12AWG
100-120VAC:10AWG
Neutral (N) White
AC INPUT Line (L) Brown
Neutral (N) Blue
Ground Green / Yellow or
Bare copper 26~32 feet / AWG#10~12
Table 17. Wire Color / Wire Length / Wire Gauge
25
4-2-3. Neutral Grounding Connection Setting (For SD1500 Only)
The default setting is option A: NO ONNECTION BETWEEN NEUTRAL
CONDUCTOR (N) OF THE AC OUTPUT AND SAFETY GROUND (PE/GND)
CAUTION!
It is advised that all the electrical installation should conform to the local electrical
codes and should be carried out by a certified technician.
When the unit is feeding the internally inverted voltage, the current carrying
conductors connected to the “L” and “N” terminals of the AC output will be isolated
from the metal chassis of the inverter. Hence, during this condition, when the metal
26
EN
chassis of the inverter is connected to the earth ground, the “N” terminal of the AC
output will not be grounded (bonded) to the earth ground. Under this condition, the
“N” terminal of the AC output will not be a Neutral in the true sense. Do not touch this
terminal as it will be at an elevated voltage (almost half the value the AC output
voltage) with respect to the metal chassis / earth ground and may produce an
electrical shock when touched!
When the unit is transferring power from the AC input source, the grounding
condition of the “N” terminal of the AC output will be the same as the condition of the
“N” terminal of the AC input source. If the AC input source is the power supplied from
the utility, the “N” terminal would be a Neutral in the true sense. It will normally be
bonded to the earth ground and will read almost 0 V with respect to the earth ground.
In this case, touching this terminal will not be a shock hazard.
4-2-4. For AC output and terminals of the SD series, you can use both the front
wiring terminal and outlet, as they are connected in parallel.
Type Number of outlet Voltage (VAC) Total Current (A)
GFCI
2 125 20
NEMA
2 125 15
Europe
1 250 16
Australia / New Zealand
1 250 15
U.K.
1 250 13
Wiring Terminal
1 100~250 35
①UL458
1 120 35
②Universal
1 100~250 16
① UL458 only support 112 and 124 model.
② Only CE (200-240V Type) and FCC (100-120V Type) standard approve.
Table 18. AC input socket / Wiring terminal
27
Note
In case the load current over the outlet rated current, please use the hared wire terminal next to the outlets.
Note
Recommend GFCI connector:
HUBBELL INC WIRING DEVICE DIV, Type GF20 and GFRST20. Rated 125V, 20A
COOPER WIRING DEVICES, Type VGF20 and SGF20. Rated 125V, 20A
LEVITON MFG CO INC, Type 7899-W and GFNT2. Rated 125V, 20A PASS & SEYMOUR INC, Type 2097. Rated 125V, 20A
WARNING!
When using full power, it is recommended to use the wiring terminal.
28
EN
5. Parallel Mode
5-1. Prepare for Parallel Usage
1. Before setting, you need to ensure that the main switch is ”OFF”.
2. Before using the parallel function, you need to set the parallel jump of the green
terminal the status of which must be “ON”, if the between in another SD is set
to ”OFF” which is termination resistors.
Figure 26. Parallel jump setting
Example:If three SD inverters are paralleled, setup green terminal.
Parallel Unit 1 Unit 2 Unit 3
Type Slave #1 Master Slave #2
Parallel Jump ON OFF ON
If you parallel N units, the first (unit 1) and the last unit (unit N) must set parallel jumper in ON
position.
Table 19. Jumper setting for parallel usage
Figure 27. Sample─three SD inverters are paralleled
29
Note
Please select one unit to be Master unit.
Use the cables to connect Master and Slave units.
The CAN1 and CAN2 port connection please refer to Figure 25.
Note
The simple method to determine the terminal resistor:No need to set the
terminal resistor when CAN1 and CAN2 port have wiring.
Note
SD series can be used for N+1 (N≦14) redundancy and the ability of
enlarge the capacity (Users can install maximum 15 units of inverters
together in parallel in order to provide the power expansion).
3. Before using the parallel function, you need to set voltage and frequency of all
units’ DIP switches to the same selection (refer to section 3-3).
4. Check RJ-45 line connects already.
5. SD series based on master-slave architecture and support auto master function.
User only set one SD parameters and other SDs will follow the master SD
setting.
5-2. Industry Applications
Type 1Φ2W 1Φ3W 3Φ4W
Drawing
The SD series create 1Ф3W
power system, L1-L2 Voltage
is L1-N double.
Example
Example:
SD2500-124 set output 100V /
50Hz
The L-N:100V / 50Hz
Example:
SD2500-124 set output 100V /
50Hz
The L1-N:100V / 50Hz
Example:
SD2500-124 set output 100V /
50Hz
The phase voltage is 100V /
50Hz (L1-N, L2-N, L3-N)
The line voltage:L1-L2, L1-L3,
L2-L3 ~ 173V/50Hz
30
EN
Type 1Φ2W 1Φ3W 3Φ4W
Waveform
Battery
Set up
Warning
Transfer Switch STS
module:Single < 4ms; N+1
& 1P3W & 3P4W < 6ms
Do not support N+1
operation, maximum of two
SD inverters, THD < 4%
Do not support N+1
operation, maximum of three
SD inverters, THD < 4%
DIP switch (S7) must be set to
“1”
DIP
Switch
Setting
Refer to 5-2-1. / 5-2-2. Refer to 5-2-3. Refer to 5-2-4.
Wiring
Diagram Refer to Figure 32. / Figure 33. Refer to Figure 34. Refer to Figure 35.
Table 20. Parallel industry applications
5-2-1. 1Φ2W Switch Table
Master Slave 0°
S4 0 0
S5 0 0
S6 0 1
S7 1 1
S8 1 1
Table 21. 1Φ2W switch table
31
5-2-2. 1Φ2W Switch Table ─ Auto Master
Auto Master
S4 0
S5 0
S6 0
S7 0
S8 1
Table 22. 1Φ2W switch table ─ auto master
5-2-3. 1Φ3W Switch Table
Master Slave 180°
S4 0 0
S5 0 1
S6 0 1
S7 1 1
S8 1 1
Table 23. 1Φ3W switch table
5-2-4. 3Φ4W Switch Table
L1 Master L2 -120° Slave L2 +120° Slave
S4 0 1 1
S5 0 0 0
S6 0 0 1
S7 1 1 1
S8 1 1 1
Table 24. 3Φ4W switch table
5-3. Wiring for Parallel Usage
5-3-1. Connection method
1. AC OUTPUT connector setup:Line link to Line; Neutral link to Neutral.
2. AC INPUT connector setup:Line link to Line; Neutral link to Neutral.
3. Battery connector setup:POS+ link to POS+; NEG - link to NEG –
5-3-2. Connection Diagram
Figure 28. Connection Diagram_1
32
EN
Figure 29. Connection Diagram_2
Figure 30. Connection Diagram_3
33
5-4. AC Wiring Diagram
Figure 31. SD series front panel introduction
【1Φ2W ─ Wiring Diagram】
Figure 32. 1Φ2W parallel AC wiring diagram
34
EN
【1Φ2W Auto Master ─ Wiring Diagram】
Figure 33. 1Φ2W parallel AC wiring diagram ─ auto master
Note
Auto master can be operated under 1Φ2W mode.
Under 1Φ2W auto master mode, please set up the inverter by Ethernet or
Remote control CR-10.
Note
1Φ2W system parallel Max. N+1=15
Note
If you parallel N units, the first (unit 1) and the last unit (unit N) must set
parallel jumper in ON position.
35
【1Φ3W ─ Wiring Diagram】
Figure 34. 1Φ3W parallel AC wiring diagram
36
EN
【3Φ4W ─ Wiring Diagram】
Figure 35. 3Φ4W parallel AC wiring diagram
Model Connection /
Output VAC 100V 110V 115V 120V 200V 220V 230V 240V
SD2500
L1-to-L2 173 191 199 208 346 381 398 416
L2-to-L3 173 191 199 208 346 381 398 416
L3-to-L1 173 191 199 208 346 381 398 416
L1-to-N 100 110 115 120 200 220 230 240
L2-to-N 100 110 115 120 200 220 230 240
L3-to-N 100 110 115 120 200 220 230 240
SD3500
L1-to-L2 173 191 199 208 346 381 398 416
L2-to-L3 173 191 199 208 346 381 398 416
L3-to-L1 173 191 199 208 346 381 398 416
L1-to-N 100 110 115 120 200 220 230 240
L2-to-N 100 110 115 120 200 220 230 240
L3-to-N 100 110 115 120 200 220 230 240
Table 25. Connection & output VAC under 3Φ4W
37
5-5. Remote command for the parallel connection
There are two ways for parallel connection remote setting:1. RS-232, 2. CAN-Bus.
The RS-232 communication protocol not support broadcast function. In case of
the remote control use the RS-232 port, please follow the setting steps for the SD
setting.
RS-232 remote communication setting:
1. Select one SD to be the Master and follow the setting:
Scenario S1 S2 S3 S4 S5 S6 S7 S8
Master X X X 0 0 0 1 X
Table 26. RS-232 remote communication setting
2. Please make sure the RS-232 communication cable connect to Master unit.
WARNING!
There is only one master in the system.
5-6. Remove Parallel Connection
1. Turn off the power.
2. Remove the RJ-45 cable (parallel connection signal cable).
3. Remove the AC parallel connection cable.
4. Remove the DC parallel connection cable.
38
EN
6. RS-232 Command
6-1. RS-232 command introduction
6-1-1. RS-232 command:
Command format:
This unit uses high-level language commands with a CR (0DH) and LF (0AH) as
the end of the command.
The system would interpret and execute the command only after these two
characters are received. After the unit execute the command, it would send a
response string to the computer. The response string is as follows:
= > CR LF:Command executed successfully ? > CR LF:Command error, not
accepted ! > CR LF:Command correct but execution error (e.g. parameters out
of range).
If the command needs any information from the unit, the unit would send the
information back to the computer (with CR and LF) and then send the response
string to the computer.
6-1-2. RS-232 Command format:
This unit supports the following command format.
There should always be a CR (0DH) and a LF (0AH) appended to the command
while sending commands to this unit.
Command Function Command Function
POWER 1 To enable power output VINV? Show voltage of SD
POWER 0 To stop power output IINV? Show current of SD
*RST Recovery default setting VGRID? Show voltage of grid
FRQ? Show frequency value VBAT? Show voltage of battery
PINV? Show power output
Table 27. RS-232 command table
Note:
Under parallel connection (more than 1 unit), RS232 command will only take
effect when RS232 cable is connected to Master unit. The connection please
refer to Figure25.
39
6-1-3. Command for accessing Setup Menus and adjusting values:
<Function Code> Setting Menu <Function Code> Setting Menu
FUNC0 OVP Setting FUNC10 Shut-down retry
FUNC1 OVP Recovery FUNC11 Saving Level
FUNC2 UVP Setting FUNC12 Saving Interval
FUNC3 UVP Recovery FUNC13 Bypass Relay
FUNC4 UV Alarm FUNC14 LCD Contrast
FUNC5 O/P Voltage FUNC15 LCD Auto-off
FUNC6 RS-232 Baud rate FUNC16 Buzzer Setting
FUNC7 O/P Frequency FUNC17 Alert Setting
FUNC8 Sync Frequency FUNC18 Language
FUNC9 Overload Alarm
Table 28. Command for accessing setup menus and adjusting values
1. Select the Setup Menus with the help of Function Codes:
Format:FUNC <Function Code>
After “Enter”, the Setup Menu for the Function Code will be called.
The <Function Code>= 0~18
2. Command to query the Functions No:
Format:FUNC?
After “Enter”, the unit’s “Function Code” appears on the PC screen.
3. Command to query the set value of the Function:
Format:SETT?
After “Enter”, the existing set value of the function appears on the PC
screen.
4. Command to set or adjust the value of the Function:
Format:SETT <value>
After “Enter”, the new value of the Function is set Choose the <value> of the
function.
6-1-4. Setting interface
1. OVP Setting <FUNC0>:Set the Over Voltage Protection (OVP) and
shutdown.
Default = 16 VDC @ 12V Model, 32 VDC @ 24V Model, 64 VDC @ 48V
Model
Model Setting value range
12 V 15 VDC ~ 16 VDC
24 V 30 VDC ~ 32 VDC
48 V 60 VDC ~ 64 VDC
Table 29. OVP Setting <FUNC0>
40
EN
2. OVP Recovery <FUNC1>:When the DC input voltage is higher than the
OVP setting, the SD-series shuts-down; once the input voltage falls below
the set OVP value, the SD-series will automatically restart.
Default = 15 VDC @ 12V Model, 30 VDC @ 24V Model, 60 VDC @ 48V
Model
Model Setting value range
12 V 13 VDC ~ 15 VDC
24 V 26 VDC ~ 30 VDC
48 V 52 VDC ~ 60 VDC
Table 30. OVP Recovery <FUNC1>
3. UVP Setting <FUNC2>:Setting Under Voltage
Protection (UVP) and Shut-down on the inverter operation.
Default = 10 VDC@ 12V Model, 20 VDC @ 24V Model, 40VDC @ 48V
Model
Model Setting value range
12 V 10.0 VDC ~ 12.5 VDC
24 V 20.0 VDC ~ 25.0 VDC
48 V 40.0 VDC ~ 50.0 VDC
Table 31. UVP Setting <FUNC2>
4. UVP Recovery <FUNC3>:When the DC input voltage is below the set UVP
value, the SD-series shuts-down; Once the input voltage rises above the set
UVP value, the SD-series will automatically restart.
Default = 12.5VDC @ 12V Model, 25 VDC @ 24V Model, 50VDC @ 48V
Model
Model Setting value range
12 V 11.5 VDC ~ 13.5 VDC
24 V 23.0 VDC ~ 27.0 VDC
48 V 46.0 VDC ~ 54.0 VDC
Table 32. UVP Recovery <FUNC3>
5. UV Alarm <FUNC4>:Setting Under Voltage (UV) alarm. When the input
voltage is lower than the set value, the SD-series will sound a “beep” to
remind you that the unit is going to shut-down.
Default = 10.5 VDC @ 12 V Model, 21 VDC @ 24 V Model, 42 VDC @ 48 V
Model
Model Setting value range
12 V 10.5 VDC ~ 13.0 VDC
24 V 21.0 VDC ~ 26.0 VDC
48 V 42.0 VDC ~ 52.0 VDC
Table 33. UV Alarm <FUNC4>
41
Note
The value of the voltage set for the “UV Alarm” should be equal to or
higher than the value set for “UVP” or else the unit will shut-down
without any audible warning.
6. O/P Voltage <FUNC5>:Setting the SD-series output voltage on the inverter
operation.
Default = 110 VAC @ 110 V Model, 230 VAC @ 230 V Model
Model Setting value range
110 V 97 VAC ~ 123 VAC
230 V 194 VAC ~ 246 VAC
Table 34. O/P Voltage <FUNC5>
7. RS-232 Baud rate <FUNC6>:
Default setting:4800
Setting Menu SETT<value>
RS-232
Baud rate
0 1200
1 2400
2 4800
3 9600
4 19200
Table 35. RS-232 Baud rate <FUNC6>
8. O/P Frequency <FUNC7>:Setting the SD-series output frequency on the
inverter operation.
Default = 60 Hz @ 110 V Model, 50 Hz @ 230 V Model.
Model Setting value range
110 V 47 Hz ~ 63 Hz
230 V 47 Hz ~ 63 Hz
Table 36. O/P Frequency <FUNC7>
9. Sync Frequency <FUNC8>:If a generator is distorted. The output waveform
(too low frequency) is used as AC source, the allowed frequency window for
the incoming AC power can be enlarged.
Example1:
AC input = 230 VAC / 50Hz, User setting Value= 7Hz
When the SD-series “Output frequency” is within The Range of 43 Hz~57 Hz,
the internal transfer relay will close. When the output frequency is less than
43 Hz or more than 57 Hz, the internal transfer relay will still open.
42
EN
Example2:
When user setting value= Disable, the SD-series “Output frequency” is
within the range of 47 Hz~63 Hz, the internal transfer relay will close.
Default= 7Hz
Model Setting value range
110 V 0 ~ 7 Hz
230 V 0 ~ 7 Hz
Table 37. Sync Frequency <FUNC8>
10. Overload Alarm <FUNC9>:Set the overload alarm. When the SD-series
output power is higher than the set value, the SD-series will sound a “beep”
to remind you that the unit is going to shut-down. At the same time, the
internal Dry Contact Relay will open/close.
Default = 104% Setting range = 50%~110%
11. Shut-down retry <FUNC10>:When SD-series is shut-down under OVP, UVP,
Overload or short circuit conditions, the inverter will automatically try to
restart according to below:
Protection type Retry default Setting value Range
OLP
Short-circuit protection 5 times after protection 0~15 times
OVP
UVP Auto-recovery continuously N/A
Table 38. Shut-down retry <FUNC10>
12. Saving Level <FUNC11>:Setting the SD-series to power saving to reduce
consumption from the batteries.
Default = 0 Setting range = 3 ~ 7
Setting Value Status
0 Default
3 4%
4 5%
5 6%
6 7%
7 8%
Table 39. Saving Level <FUNC11>
13. Saving Interval <FUNC12>:When SD-series inverter enters power saving
mode, it will detect AC Load periodically.
Default = 2.0 Seconds Setting range = 1.0S ~ 2.0S
If the AC Load is 3 times higher than Saving Level, inverter will recover and
output normally to AC Load.
43
14. Bypass Relay <FUNC13>:The setup is provided in one of the following two
ways. On-line Mode or Off-line Mode ( Exacting, Normal, Haphazard).
Default = Normal (Off line).
Mode SETT <value> Transfer Relay
Switching Feature
Haphazard 0
a. The transfer relay will switch “ON”
Conformance to voltage and frequency
b. The transfer relay will switch “OFF”
Conformance to voltage or frequency
Normal 1
a. The transfer relay will switch “ON”
Conformance to voltage , frequency and phase
b. The transfer relay will switch “OFF”
Conformance to voltage or frequency or phase
Exacting 2
a. The transfer relay will switch “ON”
Conformance to voltage , frequency and phase
b. The transfer relay will switch “OFF”
Conformance to voltage , frequency and phase
On-line 3
a. The transfer relay will switch “ON”
Conformance to voltage , frequency , phase and
inverter mode protection
b. The transfer relay will switch “OFF”
Conformance to voltage or frequency or phase or
inverter mode protection recovery
Table 40. Bypass Relay <FUNC13>
Figure 36. Frequency and phase synchronous
44
EN
SD1500 Transfer-Time Table
Mode / Transfer Switch ATS STS
Haphazard Inverter to utility AC: <5ms.;
Utility AC to inverter: 16~50ms.
Frequency is synchronized: < 4ms.;
Frequency is not synchronized:
Inverter to utility AC: < 4ms.;
Utility AC to inverter: 16~50ms.
Normal Inverter to utility AC: <5ms.;
Utility AC to inverter: 16~25ms. < 4ms
Exacting Inverter to utility AC: <5ms.;
Utility AC to inverter: 16~50ms.
Inverter to utility AC: < 4ms.;
Utility AC to inverter: 16~50ms.
Online Inverter to utility AC: <5ms.;
Utility AC to inverter: 16~25ms. < 4ms
SD2500 / SD3500 Transfer-Time Table
Mode / Transfer Switch ATS STS
Haphazard Inverter to utility AC: 8~10ms.;
Utility AC to inverter: 16~50ms.
Frequency is synchronized: < 4ms.;
Frequency is not synchronized:
Inverter to utility AC: < 4ms.;
Utility AC to inverter: 16~50ms.
Normal Inverter to utility AC: 8~10ms.;
Utility AC to inverter: 16~25ms. < 4ms
Exacting Inverter to utility AC: 8~10ms.;
Utility AC to inverter: 16~50ms.
Inverter to utility AC: < 4ms.;
Utility AC to inverter: 16~50ms.
Online Inverter to utility AC: 8~10ms.;
Utility AC to inverter: 16~25ms. < 4ms
Table 41. SD series transfer time
15. LCD contrast <FUNC14>:Sets the LCD screen contrast.
Default = 50%
Setting range = 0% ~ 100%
Setting Menu Status <value>
LCD Contrast 0 ~ 100
Table 42. LCD contrast <FUNC14>
16. LCD Auto-off <FUNC15>:Sets the LCD screen backlight auto off timer.
Default = 120 seconds
Setting range = 0 ~ 120 seconds.
Setting Menu Status <value>
LCD Auto-off 0 ~ 120
Table 43. LCD Auto-off <FUNC15>
17. Buzzer setting <FUNC16>:Set the LCD remote control for the buzzer sound
Default = MSG, Alert, SHDN
Setting range = 0~7
45
Setting Menu SETT <value> Buzzer (Beep sound)
Buzzer Setting
0 Disable
1 SHDN
2 Alert
3 Alert , SHDN
4 MSG
5 MSG , SHDN
6 MSG , Alert
7 MSG , Alert , SHDN
Table 44. Buzzer setting <FUNC16>
18. Alert Setting <FUNC17>:When alert occurs, the internal dry contact relay
will open/close.
Default = Alert, SHDN
Setting range = 0~3
Setting Menu SETT (RS-232) Alert (LCD)
Buzzer Setting
0 Disable
1 SHDN
2 Alert
3 Alert , SHDN
Table 45. Alert Setting <FUNC17>
19. Language <FUNC18>:The SD-series have different languages available
and are selectable.
Default = English
Setting:English / Italian / Spanish / French / German
Model Setting value
English 0
Italian 1
Spanish 2
French 3
German 4
Table 46. Language <FUNC18>
46
EN
7. Troubleshooting
Problems and Symptoms Possible Cause Solutions
A. Power status red light is
blinking fast. Over input voltage. (OVP)
Check input voltage.
Reduce input voltage.
B. Power status red light is
Blinking slowly. Low input voltage. (UVP)
Recharge battery. Check connections
and cables.
C. Power status red light is
blinking Intermittently. Thermal shut-down. (OTP)
Improve ventilation. Make sure
ventilation, shafts of the inverter are
not obstructed. Lower ambient
temperature.
D. Power status is solid red
Short circuit.
Wiring error.
Over Loading (OLP)
Check AC wiring for short circuit.
Reduce load.
Table 47. SD series Troubleshooting
8. Warranty
We guarantee this product against defects in materials and workmanship for a period of
24 months from the date of purchase. Please contact with your local COTEK authorized
distributor for RMA (Return material Authorization) service. Please note that COTEK will
ensure our products are operational before delivery and the warranty service is offered
to the unit which has defect caused under normal use, in the judgment of COTEK’s
technician. The warranty is null and void under the following circumstances:
(a) If the unit has been damaged through abuse, misuse, negligence (such as bumping,
wetting), fault voltage supply, air/water pollution accidents and natural calamities.
(b) If the serial number has been altered, effaced or removed.
47
Dispositions légales
Copyrights 2016 COTEK Electronic IND. CO. tous droits réservés.
Aucune partie de ce document ne peut être reproduite, quelle qu’en soit la manière et quel qu’en
soit le but, sans autorisation préalable écrite de COTEK Electronic IND. CO. Pour obtenir
l’autorisation de publier ce manuel, adressez-vous directement à COTEK Electronic IND. CO., LTD.
Pour l’ensemble des activités COTEK, ni COTEK Electronic IND. CO., LTD. ni ses distributeurs ou
revendeurs ne sauraient être tenus responsables, d’aucune manière, de tout dommage direct,
indirect ou accessoire. Les caractéristiques peuvent être modifiées sans notification préalable.
Tout a été mis en oeuvre pour que ce document soit complet, précis et à jour. COTEK Electronic
IND. CO., LTD. se réserve le droit d’apporter des modifications sans notification et ne saurait être
tenu responsable de tout dommage direct, indirect ou accessoire causé par l’utilisation de ce
contenu, y compris mais non limité à des omissions, des coquilles, des erreurs de calcul ou de
description. Toutes les marques sont protégées même sans indication spécifique. L’absence de
logo ne signifie pas que le produit ou la marque ne sont pas protégés.
48
FR
Table des matières
1. CONSIGNES DE SÉ CURITÉ 500
1-1. Consignes de sécurité 500
1-2. Précautions avec les batteries 500
1-3. Installation 51
2. CARACTÉ RISTIQUES FONCTIONNELLES 52
2-1. Système 52
2-2. Applications 52
2-3. Performances électriques 53
2-4. Schémas d’encombrement 60
3. INTRODUCTION 61
3-1. Interrupteur ON / OFF / REMOTE 62
3-2. Témoins lumineux à DEL 62
3-3. Interrupteurs DIP 63
3-4. Négatif (-) entrée courant continu 65
3-5. Positif (+) entrée courant continu 65
3-6. Masse (chassis ground) 65
3-7. Sortie courant alternatif 65
3-8. By-pass entrée courant alternatif 65
3-9. Disjoncteur entrée courant alternatif 65
3-10. Socle sortie CA 65
3-11. Bouton de réinitialisation 65
3-12. Ports CAN1 et CAN2 66
3-13. Port LCM 67
3-14. Bornier vert 67
3-15. Port de communication RS-232 68
3-16. Ventilateur 69
49
3-17. Protections 69
4. CONNEXIONS COURANT CONTINU (ALIMENTATION DE
L’ONDULEUR) 70
4-1. Entrées courant continu 71
4-2. Connexion fixe (câblage) 72
5. MODE PARALLÈ LE 77
5-1. Préparation 77
5-2. Applications Industrielles 78
5-3. Câblage 80
5-4. Connexions courant alternatif 82
5-5. Commande déportée des onduleurs montés en parallèle 86
5-6. Déposer les connexions de montage en parallèle 86
6. PROTOCOLE RS-232 87
6-1. Introduction au protocole RS-232 87
7. RECHERCHE DE PANNES 95
8. GARANTIE 95
50
FR
1. Consignes de sécurité
Attention !
Prendre le temps de lire les consignes de sécurité avant d’utiliser l’onduleur.
1-1. Consignes de sécurité
1-1-1. Ne pas exposer l'onduleur à la pluie, à la neige, aux projections d'eau ou à la
poussière. Pour réduire les risques électriques (incendie) ne pas couvrir ni
obstruer les grilles de ventilation. Ne pas installer l'onduleur dans un
compartiment non aéré au risque de provoquer une surchauffe.
1-1-2. Pour éviter les risques d'incendie et de chocs électriques, s'assurer que les
câbles sont en bon état et d'une section suffisante. Ne pas utiliser l’onduleur
avec des câbles endommagés ou de piètre qualité.
1-1-3. Certains composants de l'onduleur peuvent provoquer des arcs électriques
ou des étincelles. Pour éviter les risques d'incendie ou d'explosion, l'onduleur
ne doit pas être installé à proximité des batteries ou de matériaux
inflammables ni dans un local qui requiert une protection anti-déflagration.
Cette précaution s'étend aux locaux des machines à essence, des réservoirs
à carburant ou de leurs conduites.
1-1-4. En fonction de l’application, l’utilisateur peut être amené à monter une
protection (fusible ou disjoncteur) sur la sortie CA de l’onduleur. Les câbles et
connecteurs ne sont pas fournis pour ce branchement.
1-1-5. Selon l’application, une protection différentielle (20 A) supplémentaire sera
nécessaire.
1-2. Précautions avec les batteries
1-2-1. En cas de contact avec de l’acide (peau ou vêtements) laver immédiatement
à l’eau et au savon. En cas de contact avec les yeux, rincer immédiatement
l’œil à l’eau courante froide pendant au moins 20 minutes et consulter un
médecin sans tarder.
1-2-2. Ne JAMAIS fumer ni approcher une flamme ou une source d’étincelles à
proximité d’une batterie ou d’un moteur.
1-2-3. Ne pas poser ni laisser tomber un outil métallique sur la batterie. L’étincelle
résultante ou le court-circuit sur la batterie ou toute autre partie électrique
pourrait provoquer une explosion.
1-2-4. Ô ter vos effets personnels métalliques tels que bagues, bracelets, colliers et
montres lorsque vous travaillez avec une batterie plomb-acide. En cas de
court-circuit, ce type de batterie produit un courant suffisamment fort pour
souder une bague ou tout équivalent et causer une brûlure sévère.
51
1-3. Installation
Sec ─ Ne pas exposer l’onduleur au ruissellement ou aux projections d’eau.
Frais ─ La température ambiante de l’air doit être comprise entre 0°C et 33°C. Le
plus frais étant préférable.
Sûr ─ Ne pas installer l'onduleur à proximité des batteries ou dans un compartiment
où peuvent se produire des émanations inflammables tel que le compartiment de
stockage des combustibles ou le compartiment moteur.
Aéré ─ Prévoir un dégagement de 2,5 cm minimum autour de l'onduleur pour que
l'air puisse circuler. S'assurer que les grilles de ventilation à l’avant et à l’arrière de
l’appareil ne soient pas obstruées.
Propre ─ L'atmosphère autour de l'onduleur doit être propre, c'est-à-dire exempte
de poussières, particules de bois et autres résidus risquant d'être aspirés lorsque le
ventilateur de refroidissement fonctionne.
Pas trop éloigné des batteries ─ Éviter des longueurs de câbles excessives mais
ne pas installer l'onduleur dans le même compartiment que les batteries. Respecter
les longueurs et sections de câbles recommandées (voir chapitre 4 Connexions
courant continu). Ne pas non plus exposer l'onduleur aux émanations gazeuses
produites par les batteries. Celles-ci étant très corrosives, elles finiraient par
l'endommager.
Attention !
Risque de choc électrique. Avant de continuer, s’assurer que l’onduleur
n’est pas raccordé à une batterie ou autre source électrique. Ne pas
raccorder les bornes de sortie à une source courant alternatif.
52
FR
2. Caractéristiques fonctionnelles
2-1. Système Les onduleurs de la série SD font partie de la dernière génération d’onduleurs
acceptant un montage en parallèle (redondance N+1), compatible avec une
alimentation triphasée. Ils sont équipés d’un relais de transfert et conviennent aux
véhicules de loisirs, bateaux de plaisance et équipements de secours.
Caractéristiques
Conception permettant un montage en parallèle.
Permet d’obtenir une alimentation 1 phase 3 fils / 3 phases 4 fils, pour de
multiples applications industrielles.
Panneau de commande déporté intuitif.
Fonctionnement automatique maître/esclave pour pallier la défaillance
éventuelle d’un appareil et optimiser la fiabilité de l’installation.
Relais de transfert intégré (ATS) et protection par disjoncteur sortie CA.
Relais de transfert (STS) en option, temps de transfert inférieur à 4 ms.
Port de communication RS-232.
Entrée et sortie totalement isolées.
Tension de sortie et mode économie d’énergie sélectionnables par
interrupteurs DIP et par panneau de commande déporté (CR-10).
Protections en entrée : inversion de polarités (fusible), sous-tension,
surtension.
Protections en sortie : court-circuit, surcharge, surchauffe, surtension.
Pour obtenir des performances optimales, les onduleurs doivent être correctement
installés et utilisés. Prendre le temps de lire ce manuel en entier avant d’installer
ou d’utiliser les onduleurs.
2-2. Applications 2-2-1. Outillage électrique – scies circulaires, perceuses, rectifieuses, ponceuses,
taille-haies et taille-bordures, compresseurs à air.
2-2-2. É quipements de bureau – ordinateurs, imprimantes, moniteurs, fax,
scanners.
2-2-3. É lectro-ménager – aspirateurs, ventilateurs, lampes fluorescentes et à
incandescence, rasoirs, machines à coudre.
2-2-4. É quipements de cuisine – fours à micro-ondes, réfrigérateurs et congélateurs,
cafetières, mixeurs, machines à glaçons, grille-pain.
2-2-5. É quipements industriels – lampes métal halide ou sodium haute pression.
2-2-6. É quipements électroniques de loisirs – téléviseurs, magnétoscopes,
consoles de jeux vidéo, chaînes stéréo, instruments de musique,
équipements pour satellites.
2-2-7. Véhicules, yachts, réseaux auto producteurs à base de panneaux solaires.
53
2-3. Performances électriques 2-3-1. Caractéristiques SD1500
Modèle SD1500-112 SD1500-124 SD1500-148 SD1500-212 SD1500-224 SD1500-248
Sortie
Puissance Nominale 1 500 W (déclassement au-delà de 40°C, voir courbes de déclassement)
Puissance de Sortie
Maxi (3 s) 1 800 W
Puissance de Sortie en
Pointe (<0,2 s) 2 400 W
Signal de Sortie Onde Sinusoïdale Pure
Rendement (pleine
charge) 88 % 89 % 90 % 88 % 88 % 90 %
Tension de Sortie (@
tension CC nominale) 100 / 110 / 115 / 120 V CA ± 3 % 200 / 220 / 230 / 240 V CA ± 3 %
Fréquence 50 / 60 Hz ± 0,1 %
Distorsion Harmonique
(DHT)
< 3 % si :
Supérieur à 1,15 fois la tension CC nominale,
110 V / charge linéaire
< 3 % si :
Supérieur à 1,15 fois la tension CC nominale,
230 V / charge linéaire
Entrée Courant Continu
Tension Courant
Continu 12 V CC 24 V CC 48 V CC 12 V CC 24 V CC 48 V CC
Plage de Tensions CC 10,0~16,0 V CC 20,0~32,0 V CC 40,0~64,0 V CC 10,0~16,0 V CC 20,0~32,0 V CC 40,0~64,0 V CC
Consommation en mode
Économie d’énergie 0,9 A 0,35 A 0,3 A 1,1 A 0,7A 0,4 A
Consommation à Vide < 2,4 A < 1,2 A < 0,6 A < 3,3 A < 1,6 A < 0,8 A
Calibre Fusible 40 A x 6 20 A x 6 15 A x 4 40 A x 6 20 A x 6 15 A x 4
Entrée Courant Alternatif
Plage de Tensions CA 100 / 110 / 115 / 120 V CA ± 12,5 % 200 / 220 / 230 / 240 V CA ± 12,5%
Fréquence, commutable
par sélecteur (DIP) 50 / 60 Hz
Synchronisation de
fréquence 47~57 / 53~63 Hz
Calibre disjoncteur 20 A 10 A
Relais de transfert①
ATS de série : relais de transfert automatique
Onduleur-Consommateur CA : < 5 ms; Consommateur CA-onduleur : < 10 ms
Protections
Alarme Batterie Basse
± 3 % 10,5 V CC 21,0 V CC 42,0 V CC 10,5 V CC 21,0 V CC 42,0 V CC
Coupure Batterie Basse
± 3 % 10,0 V CC 20,0 V CC 40,0 V CC 10,0 V CC 20,0 V CC 40,0 V CC
Redémarrage Batterie
Basse ± 3 % 12,5 V CC 25,0 V CC 50,0 V CC 12,5 V CC 25,0 V CC 50,0 V CC
Alarme Batterie Haute
± 3 % 15,5 V CC 31,0 V CC 62,0 V CC 15,5 V CC 31,0 V CC 62,0 V CC
Coupure Batterie Haute
± 3 % 16,0 V CC 32,0 V CC 64,0 V CC 16,0 V CC 32,0 V CC 64,0 V CC
Redémarrage Batterie
Haute ± 3 % 15,0 V CC 30,0 V CC 60,0 V CC 15,0 V CC 30,0 V CC 60,0 V CC
Protections en Entrée Inversion de polarités (fusible), sous-tension, surtension, sur-intensité CA (disjoncteur)
Protections en Sortie Court-circuit, surcharge, surchauffe, surtension
54
FR
Modèle SD1500-112 SD1500-124 SD1500-148 SD1500-212 SD1500-224 SD1500-248
Environnement
Plage de Températures,
Fonctionnement -20 à +60 °C, voir courbes de déclassement du SD2500
Plage de Températures,
Stockage -40 à +70 °C
Humidité Relative 90 % maximum, sans condensation
Normes de Sécurité et Compatibilité É lectromagnétique
Sécurité UL 458
(connexion par câbles uniquement) ---- EN 62368-1
CEM FCC Class B EN 55032, EN 55024
Marquage CE ---- CISPR 25; ISO 7637-2
Panneaux de Contrô le et Indicateurs
Indicateur DEL Défaut, tension d’entrée
Panneaux déportés
compatibles CR-6, CR-8 et CR-10
Autres
Dimensions (LxHxP) 283x128x351 mm / 11.14x5.04x18.82 in.
Poids 5.5 kg
Refroidissement Ventilateur asservi à la charge et à la température
Communication RS-232 (connecteur RJ-11), Ethernet en option
Note
Ces caractéristiques peuvent être modifiées sans notification préalable. Tests
effectués à la puissance nominale de l’appareil.
① Merci de vous reporter page 59, Tableau « Temps de commutation ».
55
2-3-2. Caractéristiques SD2500
Modèle SD2500-112 SD2500-124 SD2500-148 SD2500-212 SD2500-224 SD2500-248
Sortie
Puissance Nominale 2 500 W (déclassement au-delà de 40°C, voir courbes de déclassement)
Puissance de Sortie
Maxi (3 s) 3 000 W
Puissance de Sortie en
Pointe (<0,2 s) 4 000 W
Signal de Sortie Onde Sinusoïdale Pure
Rendement (pleine
charge) 88 % 89 % 90 % 88 % 88 % 90 %
Tension de Sortie (@
tension CC nominale) 100 / 110 / 115 / 120 V CA ± 3 % 200 / 220 / 230 / 240 V CA ± 3 %
Fréquence 50 / 60 Hz ± 0,1 %
Distorsion Harmonique
(DHT)
< 3 % si :
Supérieur à 1,15 fois la tension CC nominale,
110 V / charge linéaire
< 3 % si :
Supérieur à 1,15 fois la tension CC nominale,
230 V / charge linéaire
Entrée Courant Continu
Tension Courant
Continu 12 V CC 24 V CC 48 V CC 12 V CC 24 V CC 48 V CC
Plage de Tensions CC 10,0~16,0 V CC 20,0~32,0 V CC 40,0~64,0 V CC 10,0~16,0 V CC 20,0~32,0 V CC 40,0~64,0 V CC
Consommation en mode
Économie d’énergie 0,9 A 0,35 A 0,3 A 1,1 A 0,7A 0,4 A
Consommation à Vide < 3,2 A < 1,6 A < 1,0 A < 3,6 A < 1,8 A < 1 A
Calibre Fusible 40 A x 9 20 A x 9 15 A x 6 40 A x 9 20 A x 9 15 A x 6
Entrée Courant Alternatif
Plage de Tensions CA 100 / 110 / 115 / 120 V CA ± 12,5 % 200 / 220 / 230 / 240 V CA ± 12,5%
Fréquence, commutable
par sélecteur (DIP) 50 / 60 Hz
Synchronisation de
fréquence 47~57 / 53~63 Hz
Calibre disjoncteur 35 A 20 A
Relais de transfert①
ATS de série : relais de transfert automatique
Onduleur-Consommateur CA : 8-10 ms; Consommateur CA-onduleur : 16-50 ms
Module STS en option:monophasé < 4 ms; N+1 & 1 phase 3 fils & 3 phases 4 fils < 6 ms
Protections
Alarme Batterie Basse
± 3 % 10,5 V CC 21,0 V CC 42,0 V CC 10,5 V CC 21,0 V CC 42,0 V CC
Coupure Batterie Basse
± 3 % 10,0 V CC 20,0 V CC 40,0 V CC 10,0 V CC 20,0 V CC 40,0 V CC
Redémarrage Batterie
Basse ± 3 % 12,5 V CC 25,0 V CC 50,0 V CC 12,5 V CC 25,0 V CC 50,0 V CC
Alarme Batterie Haute
± 3 % 15,5 V CC 31,0 V CC 62,0 V CC 15,5 V CC 31,0 V CC 62,0 V CC
Coupure Batterie Haute
± 3 % 16,0 V CC 32,0 V CC 64,0 V CC 16,0 V CC 32,0 V CC 64,0 V CC
Redémarrage Batterie
Haute ± 3 % 15,0 V CC 30,0 V CC 60,0 V CC 15,0 V CC 30,0 V CC 60,0 V CC
Protections en Entrée Inversion de polarités (fusible), sous-tension, surtension, sur-intensité CA (disjoncteur)
Protections en Sortie Court-circuit, surcharge, surchauffe, surtension
56
FR
Modèle SD2500-112 SD2500-124 SD2500-148 SD2500-212 SD2500-224 SD2500-248
Environnement
Plage de Températures,
Fonctionnement -20 à +60 °C, voir courbes de déclassement du SD2500.
Plage de Températures,
Stockage -40 à +70 °C
Humidité Relative 90 % maximum, sans condensation
Normes de Sécurité et Compatibilité É lectromagnétique
Sécurité UL 458
(connexion par câbles uniquement) ---- EN60950-1
CEM FCC Class B
②EN 55014-1, EN 55014-2;
EN 61000-3-2, -3-3; EN61204-3;
EN 61000-6-1, -6-2, -6-3, -6-4
IEC 61000-4-2, 3, 4, 5, 6, 11
Marquage CE ---- CISPR 25; ISO 7637-2
Panneaux de Contrô le et Indicateurs
Indicateur DEL Défaut, tension d’entrée
Panneaux déportés
compatibles CR-6, CR-8 et CR-10
Autres
Dimensions (LxHxP) 283x128x436 mm / 11.14x5.04x17.17 in.
Poids 8 kg
Refroidissement Ventilateur asservi à la charge et à la température
Communication RS-232 (connecteur RJ-11), Ethernet en option
Note
Ces caractéristiques peuvent être modifiées sans notification préalable. Tests
effectués à la puissance nominale de l’appareil.
① Merci de vous reporter page 59, Tableau « Temps de commutation ».
② EN 55014-1, EN 55014-2 classe B : avec câbles en sortie d’une longueur inférieure à
2 mètres.
57
2-3-3. Caractéristiques SD3500
Modèle SD3500-112 SD3500-124 SD3500-148 SD3500-212 SD3500-224 SD3500-248
Sortie
Puissance Nominale
3 500 W
(déclassement au-delà de 35°C, voir courbes de déclassement en 12 V)
(déclassement au-delà de 40°C, voir courbes de déclassement en 24 V et 48 V)
Puissance de Sortie
Maxi (3 s) 4 500 W
Puissance de Sortie en
Pointe (<0,2 s) 6 000 W
Signal de Sortie Onde Sinusoïdale Pure
Rendement (pleine
charge) 90 % 90 % 91% 90% 91% 91%
Tension de Sortie (@
tension CC nominale) 100 / 110 / 115 / 120 V CA ± 3 % 200 / 220 / 230 / 240 V CA ± 3 %
Fréquence 50 / 60 Hz ± 0,1%
Distorsion Harmonique
(DHT)
< 3 % si :
Supérieur à 1,15 fois la tension CC nominale,
110 V / charge linéaire
< 3 % si :
Supérieur à 1,15 fois la tension CC nominale,
230 V / charge linéaire
Entrée Courant Continu
Tension Courant
Continu 12 V CC 24 V CC 48 V CC 12 V CC 24 V CC 48 V CC
Plage de Tensions CC 10,0~16,0 V CC 20,0~32,0 V CC 40,0~64,0 V CC 10,0~16,0 V CC 20,0~32,0 V CC 40,0~64,0 V CC
Consommation en mode
Économie d’énergie 1,4 A 0,5 A 0,5 A 1,4 A 0,5 A 0,5 A
Consommation à Vide < 2,9 A < 1,4 A < 0,8 A < 3,6 A < 1,8 A < 1 A
Calibre Fusible 40 A x 12 20 A x 12 20 A x 6 40 A x 12 20 A x 12 20 A x 6
Entrée Courant Alternatif
Plage de Tensions CA 100 / 110 / 115 / 120 V CA ± 12,5 % 200 / 220 / 230 / 240 V CA ± 12,5 %
Fréquence, commutable
par sélecteur (DIP) 50 / 60 Hz
Synchronisation de
fréquence 47~57 / 53~63 Hz
Calibre disjoncteur 35 A 20 A
Relais de transfert①
ATS de série : relais de transfert automatique
Onduleur-Consommateur CA : 8-10 ms; Consommateur CA-onduleur : 16-50 ms
Module STS en option:monophasé < 4 ms; N+1 & 1 phase 3 fils & 3 phases 4 fils < 6 ms
Protections
Alarme Batterie Basse
± 3 % 10,5 V CC 21,0 V CC 42,0 V CC 10,5 V CC 21,0 V CC 42,0 V CC
Coupure Batterie Basse
± 3 % 10,0 V CC 20,0 V CC 40,0 V CC 10,0 V CC 20,0 V CC 40,0 V CC
Redémarrage Batterie
Basse ± 3 % 12,5 V CC 25,0 V CC 50,0 V CC 12,5 V CC 25,0 V CC 50,0 V CC
Alarme Batterie Haute
± 3 % 15,5 V CC 31,0 V CC 62,0 V CC 15,5 V CC 31,0 V CC 62,0 V CC
Coupure Batterie Haute
± 3 % 16,0 V CC 32,0 V CC 64,0 V CC 16,0 V CC 32,0 V CC 64,0 V CC
Redémarrage Batterie
Haute ± 3 % 15,0 V CC 30,0 V CC 60,0 V CC 15,0 V CC 30,0 V CC 60,0 V CC
Protections en Entrée Inversion de polarités (fusible), sous-tension, surtension, sur-intensité CA (disjoncteur)
Protections en Sortie Court-circuit, surcharge, surchauffe, surtension
58
FR
Modèle SD3500-112 SD3500-124 SD3500-148 SD3500-212 SD3500-224 SD3500-248
Environnement
Plage de Températures,
Fonctionnement -20 à +60 °C, voir courbes de déclassement du SD3500.
Plage de Températures,
Stockage -40 à +70 °C
Humidité Relative 90 % maximum, sans condensation
Normes de Sécurité et Compatibilité É lectromagnétique
Sécurité UL 458
(connexion par câbles uniquement) ---- EN60950-1
CEM FCC Class B
②EN 55014-1, EN 55014-2;
EN 61000-3-2, -3-3; EN61204-3;
EN 61000-6-1, -6-2, -6-3, -6-4
IEC 61000-4-2, 3, 4, 5, 6, 11
Marquage CE ---- CISPR 25; ISO 7637-2
Panneaux de Contrô le et Indicateurs
Indicateur DEL Défaut, tension d’entrée
Panneaux déportés
compatibles CR-6, CR-8 et CR-10
Autres
Dimensions (LxHxP) 283x128x496 mm / 11.14x5.04x19.53 in.
Poids 10 kg
Refroidissement Ventilateur asservi à la charge et à la température
Communication RS-232 (connecteur RJ-11), Ethernet en option
Note
Ces caractéristiques peuvent être modifiées sans notification préalable. Tests
effectués à la puissance nominale de l’appareil.
① Merci de vous reporter page 59, Tableau « Temps de commutation ».
② EN 55014-1, EN 55014-2 classe B : avec câbles en sortie d’une longueur inférieure à
2 mètres.
59
Courbes de déclassement
Schéma 1. SD1500 – Courbes de déclassement
Schéma 2. SD2500 – Courbes de déclassement
Schéma 3. SD3500 – Courbes de déclassement
Temps de commutation
Mode de commutation ATS STS*
Au hasard / à la demande Onduleur-Consommateur CA : 8-10 ms
Consommateur CA-onduleur : 16-50 ms
Si synchronisation : < 4 ms
Sans synchronisation :
Onduleur-Consommateur CA : < 4 ms
Consommateur CA-onduleur : 16-50 ms
Normal Onduleur-Consommateur CA : 8-10 ms
Consommateur CA-onduleur : 16-25 ms < 4 ms
Concordant Onduleur-Consommateur CA : 8-10 ms
Consommateur CA-onduleur : 16-50 ms
Onduleur-Consommateur CA : < 4 ms
Consommateur CA-onduleur : 16-50 ms
On-line Onduleur-Consommateur CA : 8-10 ms
Consommateur CA-onduleur : 16-25 ms < 4 ms
* Modèles SD2500 / SD3500 uniquement.
Tableau 1. Série SD - Temps de commutation
60
FR
2-4. Schémas d’encombrement
Schéma 4. Série SD – Schémas d’encombrement
Modèle A (mm) B (mm) C (mm) D (mm) E (mm) F (mm) G (mm) H (mm)
SD1500 351 160,0 93,1 268,6 8,5 11,5 128 283
SD2500 436 240,0 95,6 268,6 8,5 11,5 128 283
SD3500 496 240,0 125,6 268,6 8,5 11,5 128 283
Tableau 2. Série SD - Cotes
61
3. Introduction
Modèle standard
Schéma 5. Série SD – Vue du panneau avant
Version UL
Schéma 6. Série SD modèles UL – Vue du panneau avant
Schéma 7. Série SD – Vue du panneau arrière
62
FR
Présentation
1 Interrupteur On/Off/REMOTE
(panneau déporté) 10 Sortie CA
2 DEL d’état 11 Bouton Reset (réinitialisation)
3 Interrupteurs DIP (S1-S8) 12 Port CAN2 (utilisé si montage en parallèle)
4 Entrée négatif CC (-) 13 Port CAN1 (utilisé si montage en parallèle)
5 Entrée positif CC (+) 14 Port LCM (connexion panneau déporté avec
afficheur LCD)
6 Borne de masse (GND) 15 Bornier vert (sélection mode commande
déportée ou mode parallèle)
7 Sortie CA 16 Port RS-232 (connexion du panneau déporté)
8 By-pass entrée CA 17 Ventilateur
9 Disjoncteur, entrée CA
Tableau 3. Série SD – Description panneau avant / panneau arrière
3-1. Interrupteur ON / OFF / REMOTE Avant d’installer l’onduleur, s’assurer qu’il est hors tension (interrupteur en
position Off).
Avant d’utiliser le panneau déporté, placer l’interrupteur en position
« REMOTE ».
Lorsque l’onduleur est connecté au réseau public (courant alternatif),
l’interrupteur On/Off ne permet pas de le mettre hors tension. Avant toute
intervention, commencer par déposer la connexion au réseau sur l’onduleur
puis placer l’interrupteur sur Off.
3-2. Témoins lumineux à DEL
DEL Verte Signal DEL Etat
Fixe En Fonction
Clignotant (lent) Economie d’énergie
Clignotant (intermittent) Commutation relais (Bypass)
DEL Orange Signal DEL Etat
Clignotant (rapide) Sur-Tension (OVP)
Clignotant (lent) Sous-Tension (UVP)
DEL Rouge Signal DEL Etat
Clignotant (intermittent) Surchauffe (OTP)
Clignotant (rapide) Coupure OTP
Clignotant (lent) Coupure UVP
Fixe Surcharge
Clignotant (intermittent) Défaut ventilateur
Clignotant (intermittent) Défaut composant
Tableau 4. Série SD – Témoins lumineux à DEL
63
3-3. Interrupteurs DIP (S1-S8)
Schéma 8. Interrupteurs DIP (S1~S8)
Interrupteur Affectation
S1 Sélection de la tension de sortie CA
S2 Sélection de la tension de sortie CA
S3 Sélection de la fréquence
S4 Paramétrage de la sortie triphasée ou du mode économie d’énergie
S5 Paramétrage de la sortie triphasée ou du mode économie d’énergie
S6 Paramétrage de la sortie triphasée ou du mode économie d’énergie
S7 Paramétrage interrupteurs S4-S6 tension de sortie triphasée ou mode économie
d’énergie
S8 Paramétrage des fonctions de réglage via LCM ou interrupteurs DIP
Tableau 5. Affectation des interrupteurs DIP (S1~S8)
3-3-1. Paramétrage des interrupteurs DIP
S1 S2 S3 S4 S5 S6 S7 S8 Scénario
0 0 X X X X X X Tension sortie CA : 100 / 200 V CA
1 0 X X X X X X Tension sortie CA : 110 / 220 V CA
0 1 X X X X X X Tension sortie CA : 115 / 230 V CA
1 1 X X X X X X Tension sortie CA : 120 / 240 V CA
X X 0 X X X X X Fréquence sortie CA : 50 Hz
X X 1 X X X X X Fréquence sortie CA : 60 Hz
X X X X X X 0 X Paramétrage mode économie d’énergie (S4-S6) :
pas de maître-esclave en parallèle
X X X X X X 1 X Paramétrage sortie triphasée (S4-S6)
X X X X X X X 0 Paramètres des fonctions via LCM
X X X X X X X 1 Paramétrages des fonctions via interrupteurs DIP
1=ON / 0=OFF
Tableau 6. Paramétrage des interrupteurs DIP
3-3-2. Mode économie d’énergie
Il est possible de paramétrer le mode économie d’énergie via les interrupteurs DIP
S4, S5 et S6.
Exemple SD2500 – Économie d’énergie paramétrée à 2 % - Si la charge est
inférieure à 50 W pendant 10 secondes, l’onduleur bascule en mode économie
d’énergie. Lorsque la charge est supérieure à 150 W, l’onduleur sort du mode
économie d’énergie.
1=ON / 0=OFF
64
FR
A. Entrée en mode économie d’énergie
Puissance nominale x % paramétré = seuil de basculement en mode économie
d’énergie.
Si la charge est inférieure au seuil durant 5 secondes, l’onduleur bascule en mode
économie d’énergie.
B. Sortie du mode économie d’énergie
Puissance nominale x % paramétré x 2-3 = seuil de sortie du mode économie
d’énergie.
Lorsque la charge est supérieure au seuil paramétré, l’onduleur sort du mode
économie d’énergie.
S1 S2 S3 S4 S5 S6 S7 S8 Scénario
X X X 0 0 0 0 X Mode économie d’énergie désactivé
X X X 1 1 0 0 X
Bascule en mode économie d’énergie quand la
charge est inférieure à 4% de la puissance
nominale
X X X 0 0 1 0 X
Bascule en mode économie d’énergie quand la
charge est inférieure à 5 % de la puissance
nominale
X X X 1 0 1 0 X
Bascule en mode économie d’énergie quand la
charge est inférieure à 6 % de la puissance
nominale
X X X 0 1 1 0 X
Bascule en mode économie d’énergie quand la
charge est inférieure à 7 % de la puissance
nominale
X X X 1 1 1 0 X
Bascule en mode économie d’énergie quand la
charge est inférieure à 8 % de la puissance
nominale
1=ON / 0=OFF
Tableau 7. Paramétrage du mode économie d’énergie
3-3-3. S4-S6, paramétrage des montages en parallèle
S1 S2 S3 S4 S5 S6 S7 S8 Scénario
X X X 0 0 0 1 X
Maître (0°) ou « R » phase
Montage en série, 1 phase 3 fils ou 3 phases
4 fils
X X X 0 0 1 1 X Esclave (0°), pour partage de courant en
montage parallèle uniquement
X X X 0 1 1 1 X Esclave (180°), pour une sortie 1 phase 3 fils en
montage série (L-NN-L)
X X X 1 0 0 1 X Esclave (-120°), phase « S » / phase « S »
(-120°) en connexion 3 phases 4 fils
X X X 1 0 1 1 X Esclave (120°), phase « T » / phase « T » (120°)
en connexion 3 phases 4 fils
X X X 1 1 1 1 X Réservé
1=ON / 0=OFF
Tableau 8. Paramétrage des montages en parallèle
65
3-3-4. S8, paramétrage via interrupteur DIP ou LCM
Paramètre S8
LCM 0
Interrupteur DIP 1
1=ON / 0=OFF
Tableau 9. Sélection du mode de paramétrage
3-4. Négatif (-) entrée courant continu (voir chapitre 4, connexions
courant continu)
3-5. Positif (+) entrée courant continu (voir chapitre 4, connexions
courant continu)
3-6. Masse (chassis ground) : utiliser un conducteur 10 mm² (8 AWG) pour la liaison au châssis du véhicule
Attention !
Utiliser un onduleur qui n’est pas correctement relié à la terre présente des
risques.
3-7. Sortie courant alternatif (voir chapitre 5-4, connexions courant
alternatif)
3-8. By-pass entrée courant alternatif (voir chapitre 5-4, connexions
courant alternatif)
3-9. Disjoncteur entrée courant alternatif
L’entrée courant alternatif est protégée par un disjoncteur qui ouvre le circuit en
cas de surcharge.
Résoudre le problème puis réarmer manuellement le disjoncteur.
3-10. Socle sortie CA (voir chapitre 5-4, connexions courant alternatif)
3-11. Bouton de réinitialisation (RESET – avec interface Ethernet
exclusivement)
La réinitialisation restaure l’adressage IP d’origine.
IP:192.168.100.181
Subnet Mask:255.255.255.0
66
FR
3-12. Ports CAN1 et CAN2 (pour montage en parallèle uniquement)
Schéma 9. Ports CAN1 et CAN2
1. Pour un montage en parallèle, s’assurer que le cavalier sur le bornier vert est
paramétré sur ON.
2. Utiliser un câble RJ-45 pour raccorder les onduleurs entre eux : ports CAN1
(CAN2) à ports CAN1 (CAN2).
PIN# LCM CAN1 CAN2
1 CANH CAN_H CAN_H
2 CANL CAN_L CAN_L
3 P1 Réservé Réservé
4 VCC- Réservé Réservé
5 VCC+ Réservé Réservé
6 DIS Réservé Réservé
7 5VS- RND RND
8 5VS+ Réservé Réservé
Tableau 10. Ports LCM, CAN1, CAN2 – Broches et description du signal
Attention !
Le port LCM est dédié uniquement au panneau déporté.
Sur un montage en parallèle via les ports CAN1 & CAN2, ne pas utiliser
le port LCM.
67
3-13. Port LCM
Connecteur du panneau déporté avec afficheur LCD.
Schéma 10. Port LCM
Schéma 11. Câble LCM
Panneau déporté Onduleur SD
Broche Signal Broche
1 CANH 1
2 CANL 2
3 PON 3
4 VCC- 4
5 VCC+ 5
6 DIS 6
7 5VS- 7
8 5VS+ 8
Tableau 11. Connecteur panneau déporté – Broches et description du signal
Note
Les câbles doivent être le plus court possible (longueur inférieure à
10 mètres) pour que le signal soit correct.
3-14. Bornier vert (Mode commande déportée & Mode parallèle)
Schéma 12. Bornier vert
Broche Description
1 GND
2 -ENB
3 ENB
4 Cavalier – Mode parallèle
5 Cavalier – Mode parallèle
Tableau 12. Bornier vert – Affectation des broches
68
FR
3-14-1. Cavalier – Mode parallèle (voir chapitre 5 pour plus de détails)
1. Avant d’installer l’onduleur, s’assurer que l’interrupteur est sur OFF.
2. Utiliser un conducteur dont la section est comprise entre 0,5 mm² et
0,25 mm² pour cette connexion.
3-14-2. Mode commande déportée
1. Avant d’installer l’onduleur, s’assurer que l’interrupteur est sur OFF.
2. Pour utiliser l’onduleur dans ce mode, placer l’interrupteur en position
REMOTE (commande déportée).
3. Utiliser un conducteur dont la section est comprise entre 0,5 mm² et
0,25 mm² pour cette connexion.
Schéma 13. Panneau deportée – Paramétrage des fonctions
Note
Les méthodes ci-dessus peuvent être utilisées pour
active/désactiver le panneau déporté (ON/OFF).
3-15. Port de communication RS-232
Pour piloter l’onduleur via un ordinateur.
Schéma 14. Port RS-232
Schéma 15. Câble RS-232
Onduleur SD Ordinateur
69
Broche Signal Broche Signal
1 Non utilisé 1 Non utilisé
2 GND (masse) 5 GND (masse)
3 RXD (réception données) 3 TXD (transmission données)
4 TXD (transmission données) 2 RXD (réception données)
5 Non utilisé Non utilisé
6 Non utilisé Non utilisé
Tableau 13. Connexions onduleur SD/ordinateur
La connexion entre onduleur SD et ordinateur se présente comme suit:
Schéma 16. Connexion onduleur
SD / ordinateur
3-16. Ventilateur
Prévoir un dégagement de 2,5 cm minimum sur l’arrière de l’appareil.
3-17. Protections
Modèle
Entrée courant continu (V CC)
Surtension Alarme
surtension
Surtension Alarme sous
tension Coupure Reprise Coupure Reprise
12 V 16 ± 0,25 15 ± 0,25 15,5 ± 0,25 10 ± 0,25 12,5 ± 0,25 10,5 ± 0,25
24 V 32 ± 0,5 30 ± 0,5 31 ± 0,5 20 ± 0,5 25 ± 0,5 21 ± 0,5
48 V 64 ± 1 60 ± 1 62 ± 1 40 ± 1 50 ± 1 42 ± 1
Alarme surtension, indicateur DEL, pas de signal sonore.
Tableau 14. Caractéristiques des protections
70
FR
4. Connexions courant continu (alimentation de l’onduleur)
Les câbles de connexion à la batterie doivent être le plus court possible (idéalement, la
longueur devrait être inférieure à 1,80 m) et de section suffisante pour réaliser une
installation conforme aux normes en vigueur.
Les câbles de section insuffisante ou trop longs provoqueront une perte de
performances (faible capacité en pointe, alarmes tension basse et extinctions de
l’onduleur répétées).
Ces alarmes tension basse sont dues à la chute de tension continue dans les câbles
reliant l’onduleur à la batterie. Plus les câbles sont longs et de faible section, plus les
pertes en ligne sont importantes.
Choisir une section de câbles supérieure améliorera la situation.
Respecter les préconisations suivantes afin d’obtenir un fonctionnement optimal de
l’onduleur (applicables aux versions 120 V et 230 V).
Modèle Section de câble Calibre du fusible
SD1500-112 / 212 0 AWG – 70 mm² 250 A
SD1500-124 / 224 1 AWG – 50 mm² 175 A
SD1500-148 / 248 4 AWG – 25 mm² 90 A
SD2500-112 / 212 3/0 AWG – 95 mm² 350 A
SD2500-124 / 224 1 AWG – 50 mm² 175 A
SD2500-148 / 248 4 AWG – 25 mm² 90 A
SD3500-112 / 212 4/0 AWG – 120 mm² 500 A
SD3500-124 / 224 0 AWG – 70 mm² 250 A
SD3500-148 / 248 2 AWG – 35 mm² 125 A
Tableau 15. Série SD – Sections de câble et calibre du fusible en ligne
Connecter les câbles aux bornes d’entrée situées sur l’arrière de l’onduleur. Le bornier
rouge est l’entrée positive (+), et le bornier noir l’entrée négative (-). Insérer les câbles
dans les borniers et serrer les vis pour sécuriser la connexion.
Attention !
1. S’assurer que toutes les connexions CC sont fermement serrées (serrer à
15 Nm). Des connexions insuffisamment serrées peuvent chauffer et
entraîner un risque potentiel.
2. Monter un fusible sur le câble positif. Le non-respect de cette consigne
peut endommager l’onduleur et entraîne l’annulation de la garantie.
Utiliser des câbles cuivre de qualité et les maintenir le plus court possible (0,90 à
1,80 m maximum).
71
Ne rien placer entre la cosse
à œil et le contact sur la
borne.
Procéder comme indiqué sur
le schéma.
Schéma 17. Câblage batterie
AVERTISSEMENT !
Lors de la mise en service initiale, une étincelle peut se produire car les
condensateurs internes se chargent. Ceci est un phénomène normal.
4-1. Entrées courant continu
Raccorder les bornes d’entrée courant continu à une batterie 12 V, 24 V ou 48 V
ou à une autre source courant continu. [+] correspond à la borne positive et [-] à
la borne négative. Une inversion de polarités peut griller le fusible interne et
endommager irrémédiablement l’onduleur.
Modèle Tension d’entrée courant continu
Minimum Maximum
12 V 10 V 16 V
24 V 20 V 32 V
48 V 40 V 64 V
Tableau 16. Série SD - Plage de tensions admissibles (entrée courant continu)
72
FR
4-2. Connexion fixe (câblage)
4-2-1. Sur les onduleurs de la série SD, il est possible de réaliser une connexion fixe.
Cela rend plus aisé le câblage du panneau déporté.
【Modèle standard】
É tape 1. Déposer les 4 vis sur la sortie CA.
Schéma 18. É tape 1 – Modèle standard
É tape 2. Passer le câble dans le presse-étoupe et suivre les instructions de câblage
des schémas ci-dessous.
Schéma 19. É tape 2 – Modèle standard
Systèmes 100 V CA~120 V CA / 200 V CA~240 V CA
Schéma 20. Modèle standard – Câblage CA
Note
Il n’y a pas de différences de câblage entre le 110 V et le 220 V.
73
Note
Si l’installation requiert une protection différentielle, COTEK recommande
d’installer un disjoncteur avec temporisation.
Courant de fuite : 30 mA, 100 mA, 300 mA, 500 mA
Temporisation : 0,45 seconde, 1 seconde, 2 secondes
【Modèle UL】
É tape 1. Déposer les 4 vis sur la sortie CA.
Schéma 21. É tape 1 – Modèle UL
É tape 2. Passer le câble dans l’anneau et suivre les instructions de câblage des
schémas ci-dessous.
Schéma 22. É tape 2 – Modèle UL
Schéma 23. Modèle UL – Câblage CA
74
FR
É tape 3. Reposer les vis.
Schéma 24. É tape 3 – Modèle UL
4-2-2. Détail des connexions courant alternatif
Borne Couleur Longueur et section du câble
Sortie CA Phase (L) Noir
Jusqu’à 5 m:
200-240 V CA:4 mm²
100-120 V CA:6 mm²
Neutre (N) Blanc
Entrée CA Phase (L) Marron
Neutre (N) Bleu
Terre (GND) Vert/Jaune ou cuivre nu Entre 8 et 9 m:4 à 6 mm²
Tableau 17. Couleur câble / Longueur / Section
75
4-2-3. Connexion du neutre
La configuration par défaut est « A » : pas de connection du neutre (N) de la sortie
CA à la terre (PE/GND).
Schéma 25. Options SD1500
Attention !
L’installation doit être effectuée par un électricien qualifié, conformément aux
normes locales en vigueur.
Lorsque l’onduleur délivre uniquement la tension alternative issue de la conversion
de la source continue, le courant circulant dans les conducteurs « L » (phase) et
« N » (neutre) de la sortie courant alternatif est isolé du châssis de l’onduleur. Dans
cet état, lorsque le châssis de l’onduleur est relié à la terre, le neutre ne sera pas un
neutre au vrai sens du terme (non raccordé à la terre). Ne pas toucher ce
conducteur car il peut être à un potentiel élevé (quasiment la moitié de la tension
alternative de sortie) par rapport au châssis/terre et provoquer un choc électrique.
Lorsque l’onduleur transfère la puissance d’une source d’entrée courant alternatif, la
mise à la terre de la sortie courant alternatif est identique à celle de l’entrée courant
alternatif. Si la source CA est celle du réseau public, « N » est un neutre au vrai
sens du terme, normalement relié à la terre, et il n’est pas dangereux de le toucher.
76
FR
4-2-4. Socles disponibles et caractéristiques
Il est possible d’utiliser la sortie CA et les bornes de sortie CA étant données qu’elles
sont reliées en parallèle.
Type Nombre de sorties Tension
(V CA)
Courant
(A)
GFCI
2 125 20
NEMA
2 125 15
Europe
1 250 16
Australie/
Nlle Zélande
1 250 15
U.K.
1 250 13
Bornier
1 100~250 35
①UL458
1 120 35
②Universel
1 100~250 16
① UL458 sur modèles 112 et 124 exclusivement.
② Uniquement conforme aux normes CE (220-240 V) et FCC (100-120 V).
Tableau 18. Socles et borniers
Note
Si le courant de charge dépasse la capacité nominale du socle, utiliser le
bornier de câblage attenant.
Note
Socle GFCI – Connecteurs recommandés :
Hubbell, type GF20 et GFRST20, 125 V 20 A ; Cooper, type VFG20 et SGF20, 125 V 20 A ; Leviton, type 7899-W et GFNT2, 125 V 20 A ; Pass & Seymour, type 2097, 125 V 20 A
Attention !
Pour une utilisation à pleine puissance, il est préférable d’utiliser des
connexions fixes (câblées).
77
5. Mode Parallèle
5-1. Préparation
1. S’assurer que l’interrupteur est sur OFF.
2. Paramétrer le cavalier (mode parallèle) du bornier vert sur ON sur le premier
et sur le dernier onduleur (paramétrer les autres cavaliers sur OFF).
Schéma 26. Paramétrage du cavalier
Exemple:paramétrage du bornier vert pour le montage en parallèle de troix onduleurs SD.
Parallèle Onduleur 1 Onduleur 2 Onduleur 3
Type Esclave #1 Maître Esclave #2
Cavalier ON OFF ON
Sur un montage en parallèle, paramétrer le cavalier sur ON, pour le premier (unité 1) et le
dernier onduleur (unité N).
Tableau 19. Paramétrage du cavalier pour les montages en parallèle
Schéma 27. Exemple – Trois onduleurs SD montés en parallèle
78
FR
Note
Déterminer quel onduleur sera le maître.
Raccorder les onduleurs esclaves à l’onduleur maître.
Pour la connexion des ports CAN1 et CAN2, voir schéma 27.
Note
Il n’est pas nécessaire de monter une résistance de terminaison lorsque
CAN1 et CAN2 sont câblés.
Note
Afin d’augmenter la puissance, il est possible de monter au maximum
15 onduleurs de la série SD en parallèle : N+1 (N≦14).
3. Paramétrer la tension et la fréquence via les interrupteurs DIP sur chaque
onduleur (voir paragraphe 3-3).
4. S’assurer que les câbles RJ-45 sont correctement raccordés.
5. Les onduleurs de la série SD sont conçus pour une architecture
maître-esclave. Il suffit à l’utilisateur de paramétrer le maître et les onduleurs
esclaves reprendront automatiquement ses paramètres.
5-2. Applications Industrielles
Type 1 phase 2 fils 1 phase 3 fils 3 phases 4 fils
Schéma
La sortie CA des onduleurs de
la série SD peut être câblée
avec un câble 1 phase 3 fils.
Cela permet de doubler la
tension.
Exemple
Exemple:SD2500-124
Tension de sortie paramétrée :
100 V / 50 Hz
Tension de ligne L-N :
100 V / 50 Hz
Exemple:SD2500-124
Tension de sortie paramétrée :
100 V / 50 Hz
Tension de ligne L1-N :
100 V / 50 Hz
Exemple:SD2500-124
Tension de sortie paramétrée :
100 V / 50 Hz
Tension de phase L1-N, L2-N,
L3-N :
100 V / 50 Hz
Tension de ligne L1-L2, L1-L3,
L2-L3 :
~ 173 V / 50 Hz
79
Type 1 phase 2 fils 1 phase 3 fils 3 phases 4 fils
Forme du
signal
Connexion
batterie
Attention
Module de transfer STS:
Monophasé < 4 ms;
N+1 & 1 phase 3 fils & 3
phases 4 fils < 6 ms
Maximum deux onduleurs
SD en parallèle.
DHT < 4%
Maximum trois onduleurs SD
en parallèle.
DHT < 4%
L’interrupteur DIP S7 doit être
positionné sur 1 pour cette
configuration.
Inter.. DIP Voir § 5-2-1. / 5-2-2. Voir § 5-2-3. Voir § 5-2-4.
Câblage Voir schéma 32. / schéma 33. Voir schéma 34. Voir schéma 35.
Tableau 20. Montages en parallèle pour applications industrielles
5-2-1. 1 phase 2 fils – Configuration des interrupteurs DIP
Maître Esclave 0°
S4 0 0
S5 0 0
S6 0 1
S7 1 1
S8 1 1
Tableau 21. 1 phase 2 fils – Configuration des interrupteurs DIP
80
FR
5-2-2. 1 phase 2 fils ─ Auto Master (reconnaissance automatique onduleur maître)
Auto Master
S4 0
S5 0
S6 0
S7 0
S8 1
Tableau 22. 1 phase 2 fils ─ Auto Master – Configuration des interrupteurs DIP
5-2-3. 1 phase 3 fils – Configuration des interrupteurs DIP
Maître Esclave 180°
S4 0 0
S5 0 1
S6 0 1
S7 1 1
S8 1 1
Tableau 23. 1 phase 3 fils – Configuration des interrupteurs DIP
5-2-4. 3 phases 4 fils – Configuration des interrupteurs DIP
L1 Maître L2 -120° Esclave L2 +120° Esclave
S4 0 1 1
S5 0 0 0
S6 0 0 1
S7 1 1 1
S8 1 1 1
Tableau 24. 3 phases 4 fils – Configuration des interrupteurs DIP
5-3. Câblage
5-3-1. Séquence des connexions
1. Sortie CA : phase à phase / neutre à neutre.
2. Entrée CA : phase à phase / neutre à neutre.
3. Parc batteries : POS+ à POS+ / NEG- à NEG-.
5-3-2. Schémas
Schéma 28. Schéma de câblage_1
81
Schéma 29. Schéma de câblage_2
Schéma 30. Schéma de câblage_3
82
FR
5-4. Connexions courant alternatif
Schéma 31. Série SD – Présentation du panneau avant
【1 phase 2 fils ─ Schéma de câblage】
Schéma 32. 1 phase 2 fils – Câblage CA pour un montage en parallèle
83
【1 phase 2 fils Auto Master ─ Schéma de câblage】
Schéma 33. 1 phase 2 fils – Câblage CA pour un montage en parallèle en mode Auto Master
Note
La reconnaissance automatique de l’onduleur maître (Auto master) peut
fonctionner avec un câblage 1 phase 2 fils en paramétrant l’onduleur SD via
un réseau Ethernet ou un panneau déporté type CR-10.
Note
Pour un montage en parallèle via un câblage 1 phase 2 fils, relier entre eux
16 onduleurs maximum (Max. N+1=16).
Note
Sur un montage en parallèle, le cavalier doit être paramétré sur ON sur le
premier onduleur (unit 1) ainsi que sur le dernier (unit N).
84
FR
【1 phase 3 fils ─ Schéma de câblage】
Schéma 34. 1 phase 3 fils – Câblage CA pour un montage en parallèle
85
【3 phases 4 fils ─ Schéma de câblage】
Schéma 35. 3 phases 4 fils – Câblage CA pour un montage en parallèle
Modèle Sortie V CA 100 V 110 V 115 V 120 V 200 V 220 V 230 V 240 V
SD2500
L1-to-L2 173 191 199 208 346 381 398 416
L2-to-L3 173 191 199 208 346 381 398 416
L3-to-L1 173 191 199 208 346 381 398 416
L1-to-N 100 110 115 120 200 220 230 240
L2-to-N 100 110 115 120 200 220 230 240
L3-to-N 100 110 115 120 200 220 230 240
SD3500
L1-to-L2 173 191 199 208 346 381 398 416
L2-to-L3 173 191 199 208 346 381 398 416
L3-to-L1 173 191 199 208 346 381 398 416
L1-to-N 100 110 115 120 200 220 230 240
L2-to-N 100 110 115 120 200 220 230 240
L3-to-N 100 110 115 120 200 220 230 240
Tableau 25. 3 phases 4 fils – Tensions de sortie V CA
86
FR
5-5. Commande déportée des onduleurs montés en parallèle
Il y a deux manières de paramétrer la commande déportée:via le protocole
RS-232 ou CAN bus.
Le protocole RS-232 n’est pas compatible avec un montage en parallèle.
Si la commande déportée est raccordée via le port RS-232, suivre les instructions
de paramétrage ci-dessous.
Configuration du port RS-232:
1. Sélectionner un onduleur SD comme maître et le configurer comme indiqué
ci-dessous.
Scénario S1 S2 S3 S4 S5 S6 S7 S8
Maître X X X 0 0 0 1 X
Tableau 26. Configuration du port RS-232
2. S’assurer que le câble RS-232 est bien raccordé à l’onduleur maître.
Attention !
L’installation ne doit comporter qu’un onduleur maître.
5-6. Déposer les connexions de montage en parallèle
1. Mettre l’installation hors tension.
2. Déposer le câble RJ-45 (signal).
3. Déposer le câble de parallélisation courant alternatif.
4. Déposer le câble de parallélisation courant continu.
87
6. Protocole RS-232
6-1. Introduction au protocole RS-232
6-1-1. Format des commandes RS-232
Chaque commande commence par un code CR (0DH) et se termine par un
code LF (0AH).
Le système ne peut interpréter et exécuter une commande qu’une fois avoir
reçu ces deux codes. Il retourne alors une réponse à l’ordinateur, qui peut se
présenter comme suit :
= > CR LF : Command executed successfully? > CR LF : Command error, not
accepted! > CR LF : Command correct but execution error (ex : parameters out
of range).
= > CR LF : Commande exécutée avec succès? > CR LF : Erreur commande,
non acceptée ! > CR LF : Commande correcte mais erreur d’éxécution (ex :
paramètres hors limites admissibles).
Si la commande requiert des informations de la part de l’onduleur, celui-ci les
envoie à l’ordinateur (en utilisant les codes CR et LF) qui retourne la trame de
réponse.
6-1-2. Commandes utiles
Les onduleurs de la série SD gèrent le format de commandes suivant :
Une commande envoyée à l’onduleur doit toujours comporter un code CR (0DH)
et un code LF (0AH).
Commande Fonction Commande Fonction
POWER 1 Met l’onduleur en marche
(On) VINV?
Affiche la tension de
sortie de l’onduleur
POWER 0 Arrête l’onduleur (Off)
IINV? Affiche le courant de
sortie de l’onduleur
*RST Réinitialisation suite à un
défaut VGRID?
Affiche la tension du
réseau
FRQ? Affiche la fréquence de
l’onduleur VBAT?
Affiche la tension de la
batterie
PINV? Affiche la puissance de
l’onduleur
Tableau 27. Commandes du protocole RS-232
NB:en mode parallèle (plusieurs onduleurs raccordés entre eux), les
commandes du protocole RS232 ne sont disponibles que si le câble RS232 est
raccordé à l’onduleur maître. Pour les connexions, merci de vous reporter au
schéma 27.
88
FR
6-1-3. Fonctions de paramétrage
< Code Fonction > Paramètre
FUNC0 OVP Setting Coupure tension haute
FUNC1 OVP Recovery Reprise suite tension haute
FUNC2 UVP Setting Coupure tension basse
FUNC3 UVP Recovery Reprise suite tension basse
FUNC4 UV Alarm Alarme tension basse
FUNC5 O/P Voltage Tension de sortie
FUNC6 RS-232 Baud Rate Débit en bauds, port communication RS-232
FUNC7 O/P Frequency Fréquence de sortie
FUNC8 Sync Frequency Synchronisation de fréquence
FUNC9 Overload Alarm Alarme surcharge
FUNC10 Shut-down Retry Tentative de redémarrage après coupure
FUNC11 Saving Level Seuil du mode économie d’énergie en %
FUNC12 Saving Interval Temporisation mode économie d’énergie
FUNC13 Bypass relay Bypass du relais
FUNC14 LCD Contrast Contraste afficheur LCD
FUNC15 LCD Auto-Off Veille automatique afficheur LCD
FUNC16 Buzzer Setting Paramétrage de l’alarme sonore
FUNC17 Alert Setting Alarme sonore
FUNC18 Language Choix de la langue
Tableau 28. Fonctions et paramètres correspondants
1. Sélectionner un menu de paramétrage via les codes des fonctions :
Format : FUNC <code de la fonction>
Après validation, le menu correspondant s’affiche sur l’écran de l’ordinateur.
2. Afficher le code d’une fonction :
Format : FUNC?
Après validation, le numéro correspondant s’affiche sur l’écran de
l’ordinateur.
3. Afficher un paramètre :
Format : SETT?
Après validation, la valeur du paramètre s’affiche sur l’écran de l’ordinateur.
4. Définir ou modifier un paramètre :
Format SETT <valeur>
Après validation, la valeur est affectée au paramètre.
89
6-1-4. Détails des paramètres
1. <FUNC0> – OVP Setting – Coupure tension haute
Valeur par défaut : 16 V CC @ 12 V – 32 V CC @ 24 V – 64 V CC @ 48 V
Modèle Plage de valeurs admissibles
12 V 15 V CC – 16 V CC
24 V 30 V CC – 32 V CC
48 V 60 V CC – 64 V CC
Tableau 29. Coupure tension haute <FUNC0>
2. <FUNC1> – OVP Recovery – Reprise tension haute
Valeur par défaut : 15 V CC @ 12 V – 30 V CC @ 24 V – 60 V CC @ 48 V
Modèle Plage de valeurs admissibles
12 V 13 V CC – 15 V CC
24 V 26 V CC – 30 V CC
48 V 52 V CC – 60 V CC
Tableau 30. Reprise tension haute <FUNC1>
3. <FUNC2> – UVP Setting – Coupure tension basse
Valeur par défaut : 10 V CC @ 12 V – 20 V CC @ 24 V – 40 V CC @ 48 V
Modèle Plage de valeurs admissibles
12 V 10 V CC – 11 V CC
24 V 20 V CC – 22 V CC
48 V 40 V CC – 44 V CC
Tableau 31. Coupure tension basse <FUNC2>
4. <FUNC3> – UVP Recovery – Reprise tension basse
Valeur par défaut : 12,5 V CC @ 12 V – 30 V CC @ 24 V – 50 V CC @ 48 V
Modèle Plage de valeurs admissibles
12 V 11,5 V CC – 13,5 V CC
24 V 23 V CC – 27 V CC
48 V 46 V CC – 54 V CC
Tableau 32. Reprise tension basse <FUNC3>
90
FR
5. <FUNC4> – UV Alarm – Alarme sonore tension basse
Valeur par défaut : 10,5 V CC @ 12 V – 21 V CC @ 24 V – 42 V CC @ 48 V
Modèle Plage de valeurs admissibles
12 V 10,5 V CC – 11,5 V CC
24 V 21 V CC – 23 V CC
48 V 42 V CC – 46 V CC
Tableau 33. Alarme sonore tension basse <FUNC4>
Note
La valeur du paramètre Alarme tension basse (UV Alarm) doit être
égale ou supérieure à la valeur du paramètre Coupure tension
basse (UVP) sinon l’appareil s’éteindra sans avoir émis d’alarme
sonore.
6. <FUNC5> – O/P Voltage – Tension de sortie
Valeur par défaut : 110 V CA @ 110 V – 230 V CA @ 230 V
Modèle Plage de valeurs admissibles
110 V 97 V CA – 123 V CA
230 V 194 V CA – 245 V CA
Tableau 34. Tension de sortie <FUNC5>
7. <FUNC6> – RS-232 Baud rate – Débit en bauds port communication
RS-232
Valeur par défaut : 4 800 bauds
Paramètre SETT<value>
RS-232
Baud rate
0 1 200
1 2 400
2 4 800
3 9 600
4 19 200
Tableau 35. Débit en bauds port RS-232 <FUNC6>
8. <FUNC7> – O/P Frequency – Fréquence de sortie
Valeur par défaut : 60 Hz @ 110 V – 50 Hz @ 230 V
Modèle Plage de valeurs admissibles
110 V 47 Hz – 63 Hz
230 V 47 Hz – 63 Hz
Tableau 36. Fréquence de sortie <FUNC7>
91
9. <FUNC8> – Sync Frequency – Synchronisation de fréquence
Valeur par défaut : 7 Hz
En cas de dysfonctionnement du groupe électrogène. Le signal de sortie
(fréquence trop basse) est utilisé en tant que source courant alternatif, la
plage de fréquences de l’entrée CA peut être élargie.
Exemple 1 :
Entrée CA 230 V CA / 50 Hz – Valeur du paramètre : 7 Hz
Lorsque la fréquence de sortie de l’onduleur SD est comprise entre 43 Hz et
57 Hz, le relais de transfert ferme le circuit. Lorsqu’elle est inférieure à 43
Hz ou supérieure à 57 Hz, le relais maintient le circuit ouvert.
Exemple 2 :
Valeur du paramètre : désactivé (Disable)
Si la fréquence de sortie de l’onduleur est comprise entre 47 Hz et 63 Hz, le
relais de transfert ferme le circuit.
Modèle Plage de valeurs admissibles
110 V 0 Hz – 7 Hz
230 V 0 Hz – 7 Hz
Tableau 37. Synchronisation de fréquence <FUNC8>
10. <FUNC9> – Overload Alarm – Alarme surcharge
Valeur par défaut : 104 %
Plage de valeurs admissibles : 50 % - 110 %
Lorsque le courant de sortie est supérieur à la valeur paramétrée, l’onduleur
SD émet une alarme sonore pour prévenir de son arrêt imminent. Au même
moment, le relais interne à contact sec s’ouvre / se ferme.
11. <FUNC10> – Shut-down Retry – Tentative de redémarrage après arrêt
Valeur par défaut : 5
Plages de valeurs admissibles : 0 - 15
Lorsque l’onduleur a été arrêté (coupure tension haute / basse, surcharge
ou court-circuit), il va automatiquement tenter de redémarrer le nombre de
fois sélectionné.
Protection Redémarrage Plage de valeurs admissibles
OLP (surcharge)
Court-circuit 5 tentatives après arrêt 0~15 fois
OVP (tension haute)
UVP (tension basse) Automatique N/A
Tableau 38. Redémarrage après arrêt <FUNC10>
92
FR
12. <FUNC11> – Saving Level – Seuil de basculement en mode économie
d’énergie
Valeur par défaut : 0
Plage de valeurs admissibles : 3 – 7
Paramètre É tat
0 10BDéfaut
3 13B4 %
4 14B5 %
5 15B6 %
6 16B7 %
7 17B8 %
Tableau 39. Seuil de basculement en mode éco <FUNC11>
13. <FUNC12> – Saving Interval – Temporisation mode économie
d’énergie
Valeur par défaut : 2,0 secondes
Plage de valeurs admissibles : 1.0 s – 2.0 s
Lorsqu’il est en mode veille, l’onduleur SD vérifie régulièrement la charge, si
elle est trois fois présente et supérieure au seuil, il sort du mode économie
d’énergie.
14. <FUNC13> – Bypass Relay – Mode de commutation du relais
Valeur par défaut : Normal (Off-line)
Valeurs possibles : On-line ou Off-line (Exacting, Normal, Haphazard)
Mode Valeur Relais
Au hasard 0 Le relais commute (ON ou OFF) sans tenir compte
de la phase ni de la synchronisation de fréquence.
Normal 1
Le relais de transfert commute sur ON lorsque le
réseau (CA) est disponible. L’onduleur reste
synchronisé et est alimenté par le réseau.
Il ne commute pas sur OFF si la fréquence est
au-delà de la plage de synchronisation de fréquence
paramétrée.
Concordant 2 Le relais commute sur On ou OFF si la valeur de la
phase et de la fréquence sont identiques.
On-line 3
L’onduleur est toujours alimenté par la batterie. Il
bascule sur le réseau uniquement en cas de tension
basse (UVP).
Tableau 40. Mode de commutation du relais <FUNC13>
93
Schéma 36. Fréquence et phase synchronisées
Temps de commutation
Mode de commutation ATS STS*
Au hasard Onduleur-Consommateur CA : 8-10 ms
Consommateur CA-onduleur : 16-50 ms
Si synchronisation : < 4 ms
Sans synchronisation :
Onduleur-Consommateur CA : < 4 ms
Consommateur CA-onduleur : 16-50 ms
Normal Onduleur-Consommateur CA : 8-10 ms
Consommateur CA-onduleur : 16-25 ms < 4 ms
Concordant Onduleur-Consommateur CA : 8-10 ms
Consommateur CA-onduleur : 16-50 ms
Onduleur-Consommateur CA : < 4 ms
Consommateur CA-onduleur : 16-50 ms
On-line Onduleur-Consommateur CA : 8-10 ms
Consommateur CA-onduleur : 16-25 ms < 4 ms
* Modèles SD2500 / SD3500 uniquement.
Tableau 41. Série SD – Temps de commutation
15. <FUNC14> – LCD Contrast – Contraste afficheur LCD
Valeur par défaut : 50 %
Plage de valeurs admissibles : 0 % - 100 %
Paramètre SETT <value>
LCD Contrast 0 - 100
Tableau 42. Contraste afficheur LCD <FUNC14>
16. <FUNC15> – LCD Auto-Off – Veille automatique afficheur LCD
Valeur par défaut : 120 secondes
Plage de valeurs admissibles : 0 – 120 secondes
Paramètre SETT <value>
LCD Auto-Off 0 - 120
Tableau 43. Veille automatique afficheur LCD <FUNC15>
94
FR
17. <FUNC16> – Buzzer Setting – Paramétrage de l’alarme sonore
Valeur par défaut : MSG, Alert, SHDN
Message, alarme sonore, extinction
Plage de valeurs admissibles : 0 – 7
Paramètre SETT <value> Buzzer
Buzzer Setting
0 Désactivé
1 SHDN
2 Alert
3 Alert, SHDN
4 MSG
5 MSG, SHDN
6 MSG, Alert
7 MSG, Alert, SHDN
Tableau 44. Paramétrage de l’alarme sonore <FUNC16>
18. <FUNC17> – Alert Setting – Paramétrage du relais
En situation d’alarme, le relais interne à contact sec se ferme / s’ouvre.
Valeur par défaut : Alert, SHDN
Alarme sonore, extinction
Plage de valeurs admissibles : 0 – 3
Paramètre SETT (RS-232) Alert (LCD)
Buzzer Setting
0 Désactivé
1 SHDN
2 Alert
3 Alert, SHDN
Tableau 45. Paramétrage du relais <FUNC17>
19. <FUNC18> – Language – Choix de la langue
Valeur par défaut : English (Anglais)
Choix possibles : English, Italian, Spanish, French, German
Anglais, Italien, Espagnol, Français, Allemand
Paramètre SETT <value>
English 0
Italian 1
Spanish 2
French 3
German 4
Tableau 46. Choix de la langue <FUNC18>
95
7. Recherche de pannes Problème Cause possible Solution
Pas de courant en sortie - Cet état allume le voyant en rouge
A. Clignotement rapide Surtension en entrée (OVP) Vérifier la tension d’entrée et la
réduire
B. Clignotement lent Sous-tension en entrée
(UVP)
Recharger la batterie.
Vérifier les connexions et le câble
C. Clignotement intermittent
Coupure de surchauffe (OTP) Améliorer la ventilation.
S’assurer que les grilles d’aération de
l’onduleur ne sont pas obstruées.
Réduire la température ambiante
D. Allumé fixe
Court-circuit ou erreur de
câblage.
Surcharge (OLP)
Rechercher s’il y a un court-circuit sur
le câblage CA.
Réduire la charge
Tableau 47. Série SD – Recherche de pannes
8. Garantie
Nous garantissons que ce produit est exempt de défauts de matériel ou de
main-d’œuvre pour une durée de 24 mois à compter de la date d’achat. Merci de
contacter votre revendeur pour l’obtention d’une autorisation de retour. COTEK
s’assure que les produits sont opérationnels avant de les expédier et la garantie ne
s’applique que pour des défauts survenant sous des conditions normales d’utilisation,
après expertise de ses techniciens. Cette garantie est considérée comme nulle dans
les cas suivants :
(a) utilisation abusive, utilisation non conforme, négligence (choc, humidité), tension
d’alimentation inappropriée, incidents dus à de l’air/de l’eau pollués, catastrophe
naturelle.
(b) Numéro de série modifié, effacé ou enlevé.
No. 33, Sec. 2, Renhe Rd., Daxi Dist., Taoyuan City 33548, Taiwan
Phone:+886-3-3891999 FAX:+886-3-3802333
http:// www.cotek.com.tw
2019.06