Sauter TSHK 670...672 Fan-coil Room-temperature Controller, Heating-cooling Sequence

Embed Size (px)

Citation preview

  • 8/17/2019 Sauter TSHK 670...672 Fan-coil Room-temperature Controller, Heating-cooling Sequence

    1/3

      21.165/1 

    TSHK 670...672: Fan-coil room-temperature controller, heating-cooling sequence

    For flexible individual-room control in residential and business premises. For quasi-continuous

    temperature control of air-conditioning systems (fan-coil). Gradual change-over from heating to cooling

    via a sequence characteristic. For 2-point pulsed operation. Suitable for thermal drives, ventilators or

    cooling equipment in air-conditioning systems.

    Housing 127 × 75 mm of pure-white (RAL 9010), flame-retardant thermoplastic (fire class as per

    UL94 HB). Black baseplate with NTC sensor, electronic evaluation unit and switching relay. Setpointadjuster with scale and rear mechanical min./max. limitation of the setting range. Suitable for mounting

    onto walls or recessed junction boxes. Cable inlet at rear. Separate terminal compartment with screw

    terminals (for wire of max. 2,5 mm2).T

    Y01938  

    Type Operating mode Number of

    switches

    Power Weight

    kg

    TSHK 670 F001 Heating-cooling sequence; 4-pipe −  230 V~ 0,18

    TSHK 671 F001 Heating-cooling sequence; 4-pipe 1 230 V~ 0,18

    TSHK 672 F001 Heating-cooling sequence; 4-pipe 2 230 V~ 0,18

    TSHK 670 TSHK 671 TSHK 672

    Mains switch, on/off −  • •Mode switch −  − 

    1

    0,5

    0

    Xp

    T

    Xs

    E=0,25

    E=0,50

    E=0,75

    B09204

    E (control factor)

    Xp

     

    Fan speeds−

     −

     Indicator −  −  1 LED

    Wiring diagram A09161 A09162 A09163 

    Power supply 1)  ± 10%, 50...60 Hz Time behaviour in air: Dead time Time constant

    Switch rating 10(4) A, 230 V~ still 2 min 20 min

    Ventilator 6 (3) A, 230 V~ moving (0.2 m/s) 1 min 15 min

    Ambient temperature 0...55 °C

    Setting range 5...30 °C Degree of protection IP 30 (EN 60529)

    P-band Xp 2 × 3 K Protection class II (IEC 60730)

    Sequence dead zone 2 K ± 0,7

    Hysteresis1)  approx. ± 0,1...0,5 K Wiring diagram see table

    Shortest switching period approx. 19 min (E = 0,5) Dimension drawing M09206

      Fitting instructions MV 505680

    Accessories 0362239 001* Intermediate cover plate in pure white; fits various recessed junction boxes

    *)  Dimension drawing for accessory is available under the same number

    1)  The device is electronically made to pulse. The control factor initially falls to nought at the ‘heating’ output as the temperature rises. After adead zone, the control factor rises at the ‘cooling’ output. The pulsing causes a small temperature deviation of ± 0,1...0,5 K, depending on

    the time constant of the room.

    Operation

    The room temperature is measured using an internal NTC temperature sensor and then compared

    with the setpoint. An electric switching relay is operated in relation to the temperature deviation. When

    the setpoint has been reached, the switch moves to the mid-position (‘OFF’). The controller’s operating

    points are determined by the setpoint, the dead zone and the proportional band.

    Sauter Components 7121165003 02

  • 8/17/2019 Sauter TSHK 670...672 Fan-coil Room-temperature Controller, Heating-cooling Sequence

    2/3

    21.165/2 TSHK 

    Engineering and fitting notes

    Fitting position: horizontal on walls, avoiding draughts and insolation, at a height of approx. 1,5 m.

    The mechanical restriction on the setpoint adjuster permits adjustment but prevents extreme settings

    and, therefore, energy wastage.

    Wiring diagrams

    °C30

    25

    20

    15

    10 5

    TSHK 670

    B09201

    N 62

    N

    L

    7

    TSHK 670

    T

     A09161

     

    ON °C30

    25

    20

    15

    10 5

    TSHK 671

    OFF

    B09202

    N 62

    N

    L

    7

    TSHK 671

    8

    T

     A09162

     

    ON °C30

    25

    20

    15

    10 5

    TSHK 672

    OFF

    ON

    B09203

    N 62

    N

    L

    TSHK 672

    7 8 1 345

    I II III

    T

    T

     A09163

     

    Sauter Components 7121165003 02

  • 8/17/2019 Sauter TSHK 670...672 Fan-coil Room-temperature Controller, Heating-cooling Sequence

    3/3

      TSHK  21.165/3

    Dimension drawing

    127

            7        5

            2        8  ,

            6

    M09206

     

    Accessories

    135,5 11,5

            8        3

    362239

    M09152

     

    Sauter Components

    Printed in Switzerland

    Right of amendment reserved

    N.B.: A comma between cardinal

    numbers denotes a decimal point

     © Fr. Sauter AG, CH-4016 Basle

    7121165003 02