Upload
others
View
2
Download
0
Embed Size (px)
Citation preview
53.00'
128.7
5'
128.7
5'
53.75'
PV-1
PV SITE PLAN
OWNER
BUILDING
DATA
APPLICABLE
CODES
SYSTEM
MODULE
SPECS
CONTRACTOR
ROOF SPECS
PROJECT INFORMATION
PROJECT NOTES
NUMBER OF ARRAYS PROPOSED: 3
ARRAY # 3 DETAILS # OF MODULES: 5 TILT: 30° AZIMUTH: 180°
ARRAY # 2 DETAILS # OF MODULES: 6 TILT: 30° AZIMUTH: 180°
ARRAY # 1 DETAILS # OF MODULES: 8 TILT: 30° AZIMUTH: 270°
CONTRACTOR
Contractor# XXXXXDrawn by: Date:
Page:
Rev:
Ph:Ph:
System AC Size @ STC: System DC Size @ STC:YOUR LOGO
SAMPLE RESIDENCEResidential Grid Interactive Solar Installation1234 ANY STREET, ANY CITY, OR, 97007
(971)-240-7102
DA Sample Set 4/4/2018
4.56 kW 4.67 kW
(8) SOLARWORLD SW 295 MONO & (11) KYOCERA KD210GX-LPU SOLAR MODULES
(19) IQ6-60-2-US MICRO INVERTERS
123 ANY STREETANY CITY, WA 98660
(971)-240-7102
ANY INSTALLER
(E) RESIDENCE
S
W
N
E
(E) METER , (E) PANEL,(N) AC PV DISCONNECT,(N) AC IQ ENVOY
(N) ARRAY #1 (N) ARRAY #3
(N) ARRAY #2
NE HALSEY ST
SITE PLAN NOTE: CHECK WITH CITY/COUNTY OR LANDSURVEYOR FOR ACCURATE PROPERTY LOCATE.
SITE DETAILS
DRAWING LIST
PV-3: ELECTRICAL PLAN
PV-2: FRAMING PLAN
PV1: TITLE SHEET
PV-4: THREE LINE DIAGRAM
PV-5: LABELS
APPENDIX: DATA SHEETS
SAMPLE RESIDENCE1234 ANY STREET, ANY CITY, OR, 97007(971)-240-7102
SINGLE FAMILYRESIDENTIAL
2014 OREGON STRUCTURAL CODE (SECTION 3111)
(8) 295W SOLARWORLD SW 295 MONO = 2.36 KWdc @ STC(11) 210W KYOCERA KD210GX-LPU = 2.31 KWdc @ STCTOTAL: 4.67 KWdc @ STC
(19) IQ6-60-2-US MICRO INVERTERS
SOLARWORLD SW 295 MONO: (L) 65.94" X (W) 39.37" X (H) 1.30",WEIGHT = 39.7 LBSKYOCERA KD210GX-LPU: (L) 59.06" X (W) 39.37" X (H) 1.40",WEIGHT = 40.8 LBSCOMBINED WEIGHT OFMODULES AND RACKING ≤ 4.5 PSF
ANY INSTALLER123 ANY STREETANY CITY, WA 98660CONTACT: YOUR NAMEPHONE: (971)-240-7102
COMPOSITE SHINGLE ROOFING 2X4 RAFTERS@ 24" O.C., DOUGLAS FIR #2 (TRUE DIMENSION)TILT: 30°AZIMUTH: 270°, AND 180° (S)AREA OF ROOF(PLAN VIEW)= 1,946 SFAREA OF NEW ARRAY(S) = 279 SF (ARRAY< 14%OF ROOF AREA)
CLIMATE DATA SOURCE: PORTLANDINTERNATIONAL AP, OR, USA, 45.59N, 122.60WASHRAE EXTREME LOW: -6.4°CASHRAE 2% HIGH: 35°CWIND SPEED: 110 MPH (ASCE7-10)RISK CATEGORY: IIWIND EXPOSURE CATEGORY: BGROUND SNOW LOAD: 10 PSF
NE HALSEY ST-CLACKAMAS ST ALLEY
NE
25T
H A
VE
1. PV SYSTEMS AND SUPPORTING STRUCTURE SHALL COMPLYWITH REQUIREMENTS OF 2017 OESC & 2014 OSSC.
2. 3111.3.2 - PV RACKING AND ATTACHMENTS SHALL BE UL 1703CERTIFIED.
3. 3111.3.4 - PV SYSTEM SHALL HAVE A FIRE CLASSIFICATION THATIS EQUAL TO OR GREATER THAN THE ROOF ASSEMBLYREQUIRED BY OSSC SECTION 1505.1.
4. 3111.4.3 - 3111.4.7- PV LAYOUT SHALL NOT RESTRICT EGRESS,LIGHT VENTILATION, OR ROOF DRAINAGE REQUIREMENTS.
5. 3111.4.8.1 - GENERAL PATHWAY REQUIREMENTS:
36" WIDE PATHWAY SHALL NOT BE REQUIRED ON STRUCTURESWITH A PV ARRAY AREA OF 1,000 SF OR LESS INSTALLED ON AROOF WITH A SLOPE THAT EXCEEDS 2:12 AND WITH ANINTERSECTING ADJACENT ROOF AND WHERE NO SECTION ISLARGER THAN 150 FEET MEASURED IN LENGTH OR WIDTH.
WHERE PV ARRAY DOES NOT EXCEED 25% AS MEASURED INPLAN VIEW OF TOTAL ROOF AREA OF A STRUCTURE, A MINIMUMOF 12" UNOBSTRUCTED PATHWAY SHALL BE MAINTAINED ALONGEACH SIDE OF ANY HORIZONTAL RIDGE.
WHERE THE SOLAR ARRAY EXCEEDS 25% AS MEASURED IN PLANVIEW OF TOTAL ROOF AREA OF THE STRUCTURE, A MINIMUM OFONE 36" UNOBSTRUCTED PATHWAY SHALL BE PROVIDED INADDITION TO A MINIMUM 12" UNOBSTRUCTED ALONG EA. SIDEOF ANY HORIZONTAL RIDGE.
6. ROOF STRUCTURE IS CONVENTIONAL LIGHT FRAMED WOODCONSTRUCTION WITH 2X4 MANUFACTURED TRUSSES @ 24" O.C.REFER TO ALLOWABLE SPAN REQUIREMENTS IN TABLE 305.4.1.
7. 3111.4.8.5.1 - DISCONNECTS, J-BOXES, COMBINER BOXES ORGUTTERS SHALL NOT BE PLACED IN ANY REQUIRED PATHWAYOR CUTOUT.
8. 3111.5.3.1 - TOTAL SYSTEM WEIGHT SHALL NOT EXCEED 4.5 PSF.PV MODULES AND RACKING SHALL BE DIRECTLY ATTACHED TOROOF FRAMING AS SHOWN IN PV-2. ATTACHMENT SPACING WILLBE 48" O.C. MAX, AND WHEN ATTACHMENT LOCATED WITHIN 3'OF ROOF EDGE, HIP, EAVE, RIDGE SHALL BE 24" O.C. MAX.
9. 3111.5.4 - MAX MODULE HEIGHT < 18" OFF ROOF SURFACE.
FRAMING PLAN
PV-2
CONTRACTOR
Contractor# XXXXXDrawn by: Date:
Page:
Rev:
Ph:Ph:
System AC Size @ STC: System DC Size @ STC:YOUR LOGO
SAMPLE RESIDENCEResidential Grid Interactive Solar Installation1234 ANY STREET, ANY CITY, OR, 97007
(971)-240-7102
DA Sample Set 4/4/2018
4.56 kW 4.67 kW
(8) SOLARWORLD SW 295 MONO & (11) KYOCERA KD210GX-LPU SOLAR MODULES
(19) IQ6-60-2-US MICRO INVERTERS
123 ANY STREETANY CITY, WA 98660
(971)-240-7102
ANY INSTALLER
FRAMING CROSS SECTIONSCALE: N.T.S.
2X4 RAFTERS@ 24" O.C.
3' SETBACK
S
W
N
E
PV MODULE
SEE MOUNTING DETAILSUNMODO HELIO HR150
RAIL & EZ ROOF MOUNT KITW/STANDOFF
LEGEND:
FRAMING PLANSCALE: 1/8" = 1'-0"
EZ ROOF MOUNT KIT W/STANDOFFSPAN ~4FT. TO MEET
ASCE 7-10 WITH WIND
SPEED AT 110 MPH
EZ ROOF MOUNT KIT W/STANDOFFSPAN ~24" TO MEET
ASCE 7-10 WITH WIND
SPEED AT 110 MPH
33'-1"
19'-1
1"
LOW PROFILE ROOFPROTRUSION, TYP.
SUNMODOHELIO HR150 RAIL
5/16"x4.5" LAGSCREW WITH2.5" MIN.EMBEDMENT
COMPOSITESHINGLEROOFING
SUNMODO 3"STANDOFF
PV MODULE
2X4 RAFTERS@ 24" O.C.
MOUNTING DETAIL WITH STANDOFFSCALE: N.T.S.
30°
1
2
30°
1
1
1
12
30°
2
2
30°
1
RIDGE
EAVE
EAVE
2X4 RAFTERS @ 24" O.C.
16'-7"
43'-7
"
FLASHING
ELECTRICAL PLAN
PV-3
CONTRACTOR
Contractor# XXXXXDrawn by: Date:
Page:
Rev:
Ph:Ph:
System AC Size @ STC: System DC Size @ STC:YOUR LOGO
SAMPLE RESIDENCEResidential Grid Interactive Solar Installation1234 ANY STREET, ANY CITY, OR, 97007
(971)-240-7102
DA Sample Set 4/4/2018
4.56 kW 4.67 kW
(8) SOLARWORLD SW 295 MONO & (11) KYOCERA KD210GX-LPU SOLAR MODULES
(19) IQ6-60-2-US MICRO INVERTERS
123 ANY STREETANY CITY, WA 98660
(971)-240-7102
ANY INSTALLER
S
W
N
E
NON-FUSED ACDISCONNECT(EXTERIOR WALL)
(E) METER(EXTERIOR WALL)
(N) IQ ENVOY(EXTERIOR WALL)
IQ6-60-2-US MICROINVERTERS ARELOCATED UNDERSIDEOF EACH MODULESAND ARE INSTALLEDTO CONTINUOUSSUPPORT RAIL.
BR
AN
CH
# 1
(8
MO
DS
)
3/4" EMT
25'-1"
GENERAL NOTES:
1. CONDUIT IS DIAGRAMMATIC. FINAL ROUTING TO BEDETERMINED BY INSTALLER.
2. SUNEYE SHOTS S1, S2, AND S3 WERE COLLECTED INTHE SPECIFIED LOCATIONS.
3. SUNEYE SHOT S1 ON LOWER ROOF CORRESPONDSTO "DOROCHER RESIDENCE SHADE REPORT -LOWER ROOF" PDF.
4. SUNEYE SHOTS S1 AND S3 ON UPPER ROOFCORRESPONDS TO "XXX RESIDENCE SHADEREPORT - UPPER ROOF" PDF
ELECTRICAL PLANSCALE: 1/8" = 1'-0"
(E) PANEL(INTERIOR WALL)
S3
S1
S2
SOLARWORLD SW 295MONO MODULES
KYOCERA KD210GX-LPUMODULES
BRANCH # 2 (11 MODS)
32'-5
"
EXISTING AC DISTRIBUTION PANEL
120/240V, 1P, 3W
200A WITH
200A MAIN BREAKER3/4" EMT OR EQUIVALENT:(2) #10 AWG THWN-2 CONDUCTORS(1) #10 AWG THWN-2 GROUND
GROUND
NEUTRAL
METER
200A
LOCKABLE, NON-FUSEDAC DISCONNECT30A, 240V, 2-POLE
B
BM
D
O
C
25A
BRANCH TERMINATORQ-TERM-10 (TYP.)
ENPHASE Q CABLE (TYP.)BLACK - L1RED - L2
JUNCTION BOX (TYP.)
GROUND
A
A
LAY IN LUG
RAIL
LAY IN LUG
RAIL10A
15A
BRANCH CIRCUIT #2
(11) KYOCERA KD210GX-LPU
MODULES
(11) MICRO-INVERTERS
@ 240V VAC
ENPHASE IQ6-60-2-US
BRANCH CIRCUIT #1
(8) SOLARWORLD SW 295
MONO MODULES
(8) MICRO-INVERTERS
@ 240V VAC
ENPHASE IQ6-60-2-US
3/4" CONDUIT:(2) #10 AWG THWN-2 CONDUCTORS
(1) #10 AWG THWN-2 GROUND
3/4" CONDUIT:(2) #10 AWG THWN-2 CONDUCTORS
(1) #10 AWG THWN-2 GROUND
PATCH CABLE TONETWORK ROUTER
60A IQ ENVOY, NEMA-3R,
120/240V, 1ɸ
EXISTING 120VOUTLET
IQ ENVOY
25A
P
THREE LINE DIAGRAM
PV-4
GENERAL NOTES:
1. CONTRACTOR RESPONSIBLE FOR COMPLYING WITHALL LOCAL OR NATIONAL CODE REQUIREMENTS ANDEQUIPMENT INSTALLATION INSTRUCTIONS.
2. SEE PV-5 FOR LABELING REQUIREMENTS
WIRE RUN # OF MODS V (VOLTS) I (AMPS) L (FT) VD VD (%) WIRE SIZE RACEWAY
VOLTAGE DROP CALCULATIONS
BRANCH 1 8 240V 7.67A 53 0.9V 0.37% 12 AWG Q CABLE FREE AIR
BRANCH 2 11 240V 10.54A 72 1.64V 0.68% 12 AWG Q CABLE FREE AIR
BRANCH 1 HOMERUN 8 240V 7.67A 30 0.57V 0.24% 10 AWG THWN-2 3/4" EMT
MAX. POWER Pmax 240 W
MAX. INPUT VOLTAGE 48 V
SW 295 MONO Voc @ -6.4°C 43.8 V
43.8V < 48V YES
KD210GX-LPU Voc @ -6.4°C 36.6 V
36.6V < 48V YES
OUTPUT CURRENT 0.96 A
OUTPUT VOLTAGE 240 V, 1ɸDC/AC RATIO 1.23 & 0.88
INVERTER SPECS
CONTRACTOR
Contractor# XXXXXDrawn by: Date:
Page:
Rev:
Ph:Ph:
System AC Size @ STC: System DC Size @ STC:YOUR LOGO
SAMPLE RESIDENCEResidential Grid Interactive Solar Installation1234 ANY STREET, ANY CITY, OR, 97007
(971)-240-7102
DA Sample Set 4/4/2018
4.56 kW 4.67 kW
(8) SOLARWORLD SW 295 MONO & (11) KYOCERA KD210GX-LPU SOLAR MODULES
(19) IQ6-60-2-US MICRO INVERTERS
123 ANY STREETANY CITY, WA 98660
(971)-240-7102
ANY INSTALLER
BRANCH 2 HOMERUN 11 240V 10.54A 56 1.47V 0.61% 10 AWG THWN-2 3/4" EMT
IQ ENVOY 19 240V 18.24A 10 0.45V 0.19% 10 AWG THWN-2 3/4" EMT
MAX VOLTAGE DROP: 1.48%
CALCULATIONS NOTES: *WIRE SIZES INCLUDE DE-RATING FACTORS SUCH AS AMBIENT TEMPERATURE AND MORE THAN 3CURRENT CARRYING CONDUCTORS IN CONDUIT.
MODULE MAKE SOLARWORLD
MODULE MODEL SW 295 MONO
MAX. POWER Pmax 295 W
OPEN CIRCUIT VOLTAGE Voc 40 V
MAX. POWER POINT Vmp 31.4 A
SHORT CIRCUIT CURRENT Isc 10.1 A
MAX. POWER POINT Imp 9.45 A
Voc TEMP. COEFF. -0.30%/°C
Pmax TEMP. COEFF. -0.42%/°C
MODULE SPECS
KYOCERA
KD210GX-LPU
210 W
33.2 V
31.4 A
8.58 A
7.9 A
-0.33%/°C
-0.43%/°C
X
WARNING - PHOTOVOLTAIC
POWER SOURCE
LABEL EVERY 10'
CAUTION SOLAR CIRCUIT
LABEL EVERY 10'
CAUTION: SOLAR ELECTRIC
SYSTEM CONNECTED
DUAL POWER SUPPLY
SOURCES: UTILITY GRID ANDSOLAR PHOTOVOLTAIC SYSTEM
WARNING
M
OPERATING AMPS 18.24AOPERATING VOLTAGE 240V
ELECTRIC SHOCK HAZARDWARNING
AC DISCONNECT
LOCATION: MAIN AC DISCONNECT
PHOTOVOLTAIC SYSTEM
DO NOT TOUCH TERMINALS
TERMINALS ON BOTH LINE AND
LOAD SIDE MAY BE ENERGIZED IN
THE OPEN POSITION
LOCATION: MAIN SERVICE PANEL
LOCATION: MAIN SERVICE PANEL
SOLAR PV SYSTEM EQUIPPEDWITH RAPID SHUTDOWN
TURN RAPID SHUTDOWN
SWITCH TO THE "OFF"
POSITION TO SHUT DOWN
PV SYSTEM AND REDUCE
SHOCK HAZARD IN THE
ARRAY
NEC 2017 690.12, 690.56(C)(1)(a)
LABEL FOR PV SYSTEMS THAT SHUT DOWN THE ARRAY AND
THE CONDUCTORS LEAVING THE ARRAY.
NOTE: THE LABEL SHALL UTILIZE CAPITALIZED
CHARACTERS WITH A MINIMUM HEIGHT OF 3/8" IN BLACK
ON YELLOW BACKGROUND, AND THE REMAINING
CHARACTERS SHALL BE CAPITALIZED WITH A MINIMUM
HEIGHT OF 3/16" IN BLACK ON WHITE BACKGROUND.
A
B
C
D
P
LOCATION: BUILDING MAIN SERVICE PANEL
CAUTION
POWER TO THIS BUILDING IS SUPPLIED FROM THEFOLLOWING SOURCES WITH DISCONNECTS LOCATED ASSHOWN:
INPUT RATINGS
ELECTRIC SHOCK HAZARDWARNING
DO NOT TOUCH TERMINALS
TERMINALS ON BOTH LINE AND
LOAD SIDE MAY BE ENERGIZED IN
THE OPEN POSITION
O
N
LABELS
PV-5
CONTRACTOR
Contractor# XXXXXDrawn by: Date:
Page:
Rev:
Ph:Ph:
System AC Size @ STC: System DC Size @ STC:YOUR LOGO
SAMPLE RESIDENCEResidential Grid Interactive Solar Installation1234 ANY STREET, ANY CITY, OR, 97007
(971)-240-7102
DA Sample Set 4/4/2018
4.56 kW 4.67 kW
(8) SOLARWORLD SW 295 MONO & (11) KYOCERA KD210GX-LPU SOLAR MODULES
(19) IQ6-60-2-US MICRO INVERTERS
123 ANY STREETANY CITY, WA 98660
(971)-240-7102
ANY INSTALLER
SERVICEDISCONNECT
PV ACDISCONNECT
SOLAR ARRAYS
AC DISCONNECT IS THE
RAPID SHUTDOWN SWITCH