    Emergency Eyewash/Shower Accessories

    Emergency Eyewashes and Showers shall be installed in well lighted area

    (100 lux minimum)

    Emergency Eyewashes and Showers shall be at least three (3) meter from

    electrical equipment and power outlets that are not protected by GFCIs.

    Note: For Battery Rooms see item No. A11 in this SAIC.

    SAES-B-069

    Para 6.2

    A9Emergency Eyewashes and Showers shall be accessible from the hazard

    without the use of stairs, a ladder or a door.

    SAES-B-069

    Para 6.2

    SAES-B-069

    Para 4.1.5

    In permanent installations, hand-held drench hoses may be used only asauxiliary equipment in support of eyewash and shower units, not in place of

    eyewash and shower units

    SAES-B-069

    Para 4.1.5

    Emergency Eyewashes and Showers shall be no closer that 3 meter or

    further than 15 meter from a hazard.

    Note: For sever hazards consult with the Industrial Hygiene Unit and

    Medical Services to determine the proper distance

    SAES-B-069

    Para 6.2

    Eyewash Unit (plumbed or self contained) shall be positioned with water

    nozzles 33 inches to 45 inches from the floor and 6 inches minimum from

    the wall or the nearest obstruction. (ANSI Z358.1 Para 5.4.1)

    SAES-B-069

    Section 7

    Eye / face wash units shall be positioned with water nozzles 33 inches to 45

    inches from the floor and 6 inches minimum from the wall or the nearest

    obstruction. (ANSI Z358.1 Para 7.4.1)

    SAES-B-069

    Section 7

    SAES-B-069

    Section 7

    Emergency Eyewashes and Showers shall be permanently installed.

    Note: Temporary installations are permitted if approved by Chief Fire

    Prevention or his representative in consultation with the Environmental

    Compliance Division

    SAES-B-069

    Para 4.1.5

    A10

    A1

    A Emergency Eyewash/Shower

    A11

    A5

    A7

    A6Hand-held sprays are permitted in temporary installation in place of safety

    showers

    A8

    Emergency Eyewash (no Shower) in battery room shall be at least 1.5

    meter from electrical equipment and power outlets that are not protected byGFCIs.

    Note: Only an eyewash is required in the battery room, provided that there

    is no acid mixing activity to be done inside the battery room. If a shower is

    provided then 3 meter separation is required

    SAES-B-069

    Para 6.2

    B

    A12SAES-B-069

    Para 6.2

    A2

    A4

    Combination units (Shower and Eyewash) shall be assembled in

    accordance with the manufacturer's instruction (if shipped with thecomponents separate)

    SAES-B-069

    Section 7

    A3

    Emergency Shower head shall be located (installed) so that a water column

    is provided that is not less than 82 inches nor more than 96 inches.

    (ANSI Z358.1 Para 4.1)

    SAUDI ARAMCO ID/PID - 2/19/05 - REV 0 (Standards Cutoff - August 2004)

    SAUDI ARAMCO INSPECTION CHECKLISSAIC NUMBER DATE APPROVED QR NUMBER

    PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR

    Emergency Eyewash/Shower System Instal lat ion SAIC-B-4002 18-May-05 PLUMB

    EQUIPMENT DESCRIPTION EQPT CODE SYSTEM ID.

    LAYOUT DRAWING NUMBER

    PLANT NO.EQUIPMENT ID NUMBER(S)

    FAIL N/A RE-INSP DA

    MH's SPENT TRAVEL TIMQUANTITY INSP.

    WORK PERMIT REQUI

    SCHEDULED INSPECTION DATE & TIME

    ITEM

    No.PASSACCEPTANCE CRITERIA REFERENCE

    SAUDI ARAMCO TIP NUMBER SAUDI ARAMCO ACTIVITY NUMBER

    CONTRACTOR INSPECTION LEVELSAUDI ARAMCO INSPECTION LEVEL

    ACTUAL INSPECTION DATE & TIME

    EC / PMCC / MCC NO.REV. NO. PURCHASE ORDER NUMBER

    SAUDI ARAMCO USE ONLY

    Page 1 of 3

    YES

  • 7/23/2019 SAIC-B-4002

    2/3

    ACCEPTANCE CRITERIA REFERENCE

    2-SAES-B-067 -- Safety Identification and Color-Coding, 30 November 2003

    C4 Block valve (car-sealed open) shall be painted safety orangeSAES-B-067

    Para 4.2.4 b

    Block valve (car-sealed open) shall be provided in the water supply systemSAES-B-069

    Para 6.3.1

    Connection between dissimilar metal shall be by means of a dielectric union

    or insulating union

    SAES-S-070

    Para 604.11.2

    (b)

    C2Strainer shall be provided in the water supply to permanently installed

    eyewash.

    SAES-B-069

    Para 6.3.3

    Emergency Eyewash/Shower supply and drainage piping connection

    B9

    Water supply systems shall be certified as suitable for the purpose by

    Saudi Aramco Environmental Compliance Division/ Environmental

    Protection Division.

    SAES-B-069

    Para 6.7

    If an alarm is provided, the alarm shall show on a visual display board in the

    attended location to identify the location of the emergency.

    SAES-B-069

    Para 6.5.2

    Shower Enclosures, if used, shall provide for a minimum unobstructed area

    of 34 inches in diameter. (ANSI Z358.1 Para 4.4)

    SAES-B-069

    Section 7

    SAES-B-069

    Para 6.5.2

    B6If an alarm is provided, the alarm shall be activated by a flow switch or by

    microswitches on the operating valves.

    SAES-B-069

    Para 6.5.2

    If an alarm is provided, the alarm shall be activated when either the

    eyewash or safety shower is activated

    SAES-B-069

    Para 6.5.2

    B3

    Permanently installed safety shower and eyewash units shall have a

    vertical background area nominally 1 m wide by 2 m high painted with either

    alternating green and white stripes approximately 152 mm wide or a solid

    green color

    SAES-B-069

    Para 6.4.1

    ITEM

    No.

    4-ANSI Z-358.1 -- American National Standard for Emergency Eyewash and Shower Equipment, 1999

    REMARKS:

    C5

    PASS FAIL N/A

    C3

    RE-INSP DA

    1-SAES-B-069 -- Emergency Eyewash and Showers, 31 January, 2001

    3-SAES-S-070 -- Install ation of Utili ty Piping System, 28 January, 2004

    REFERENCE DOCUMENTS:

    PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR

    Emergency Eyewash/Shower System Instal lat ion SAIC-B-4002 18-May-05 PLUMB

    SAUDI ARAMCO ID/PID - 2/19/05 - REV 0 (Standards Cutoff - August 2004)

    SAUDI ARAMCO INSPECTION CHECKLISSAIC NUMBER DATE APPROVED QR NUMBER

    B2All permanently installed eyewashes and showers shall be provided with

    drainage for periodic testing, such as surface drainage to a catch basin

    SAES-B-069

    Para 6.6

    No permanent or temporary connections shall be made to the water supply

    for other purposes

    SAES-B-069

    Para 6.3.2

    B8

    B7

    B5

    If an alarm is provided, the alarm shall sound at a location that is attended

    during all working hours, such as a control room and the vicinity of the

    eyewash/shower

    B1

    B4

    An appropriate sign with words in Arabic and English shall be mounted in a

    clearly visible location near each permanent Emergency Shower and

    Eyewash. Words shall be as shown below:

    Emergency Shower: Emergency Eyewash:-Get into shower immediately -Flush Eye Immediately

    -Remove Contaminated clothing -Hold eyes open rolling them back and forth during flushing

    while showering -Flush for at least 15 minutes

    -Shower for at least 15 minutes -Summon medical assistance

    -Summon medical assistance

    SAES-B-069

    Para 6.3.2

    C

    C1

    Page 2 of 3

  • 7/23/2019 SAIC-B-4002

    3/3

    ACCEPTANCE CRITERIA REFERENCEITEM

    No.PASS FAIL N/A RE-INSP DA

    PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR

    Emergency Eyewash/Shower System Instal lat ion SAIC-B-4002 18-May-05 PLUMB

    SAUDI ARAMCO ID/PID - 2/19/05 - REV 0 (Standards Cutoff - August 2004)

    SAUDI ARAMCO INSPECTION CHECKLISSAIC NUMBER DATE APPROVED QR NUMBER

    Work Verified

    Saudi Aramco

    PMT RepresentativeT&I Wi tnessed QC Record Reviewed

    Name, Initials and Date:

    Performed Inspection Work / Rework May Proceed

    Name, Initials and Date:

    QC Inspector PID Representative

    Construction Representative*

    Name, Initials and Date:

    Work is Complete and Ready for Inspection:

    Name, Initials and Date:

    Work Verified

    QC Supervisor Proponent and Others

    Contractor / Third-Party

    QC Record Reviewed

    Name, Sign and Date:

    *Person Responsible for Completion of Quality Work / Test Y = YES N = NO F = FA

    T&I Witnessed Work Verified

    Quality Record Approved:Name, Organization,

    Initials and Date:

    T&I Wi tnessed QC Record Reviewed

    Page 3 of 3