SAFETY ISSUES IN SOLID FUEL HEATING PRACTICE IN SERBIA
Borivoj LJ. STEPANOV, Momčilo Đ. SPASOJEVIĆ, Aleksandar S. ANĐELKOVIĆ, Đorđije D. DODER, Vladimir RAJS, Željko VLAOVIĆ
49. Međunarodni kongres i izložba o KGH, Beograd, 5–7.12.201849th International HVAC&R Congress and Exhibition, Belgrade, 5–7 Dec. 2018
1
FACULTY OF TECHNICAL SCIENCES, NOVI SAD, SERBIA
Problem
•Due to economic situation in Serbia old design solid fuel boilers are being used.
•This design has been developed in 70s, is functioning, is cost-effective, although having lower efficiency and higher emissions then the state-of-the- art boilers.
•Often these boilers are installed in closed hydronic heating systems. This is not in accordance with the safety rules prescribed in standards. This practice can lead to explosions, and to loss of human life and property
49. Međunarodni kongres i izložba o KGH, Beograd, 5–7.12.201849th International HVAC&R Congress and Exhibition, Belgrade, 5–7 Dec. 2018
2
Open questions
•Does PROPERLY functioning safety valve prevent boiler explosion? •Does draught regulator can regulate boiler flow temperature at ALL regimes? •Can boiler be safe without system for removal (dissipation) of EXCESS heat? •Can there be a SAFE installation of boiler in a premises without water supply network access point? •What type of solid fuel boilers CAN be installed in closed heating system?
49. Međunarodni kongres i izložba o KGH, Beograd, 5–7.12.201849th International HVAC&R Congress and Exhibition, Belgrade, 5–7 Dec. 2018
3
Open questions
•Is BOILING allowed in closed system?
•Can we treat SAFETY as optional?
•FREQUENCY of heating boiler explosions?
49. Međunarodni kongres i izložba o KGH, Beograd, 5–7.12.201849th International HVAC&R Congress and Exhibition, Belgrade, 5–7 Dec. 2018
4
Old style boiler installed in closed heating system
49. Međunarodni kongres i izložba o KGH, Beograd, 5–7.12.201849th International HVAC&R Congress and Exhibition, Belgrade, 5–7 Dec. 2018
5
Elements of the closed heating system
49. Međunarodni kongres i izložba o KGH, Beograd, 5–7.12.201849th International HVAC&R Congress and Exhibition, Belgrade, 5–7 Dec. 2018
6
Picture from broshure Centrometal BIO-CET
49. Međunarodni kongres i izložba o KGH, Beograd, 5–7.12.201849th International HVAC&R Congress and Exhibition, Belgrade, 5–7 Dec. 2018
7
49. Međunarodni kongres i izložba o KGH, Beograd, 5–7.12.201849th International HVAC&R Congress and Exhibition, Belgrade, 5–7 Dec. 2018
8
49. Međunarodni kongres i izložba o KGH, Beograd, 5–7.12.201849th International HVAC&R Congress and Exhibition, Belgrade, 5–7 Dec. 2018
9
Steam explosion with overheated water(300 °F -148 °C) (75 psi – 5,2 bar)
49. Međunarodni kongres i izložba o KGH, Beograd, 5–7.12.201849th International HVAC&R Congress and Exhibition, Belgrade, 5–7 Dec. 2018
10
Vessel rupture when temperature of the water is under 100 °C (500 psi = 35 bar)
49. Međunarodni kongres i izložba o KGH, Beograd, 5–7.12.201849th International HVAC&R Congress and Exhibition, Belgrade, 5–7 Dec. 2018
11
BLEVEboiling liquid expanding vapor explosion
49. Međunarodni kongres i izložba o KGH, Beograd, 5–7.12.201849th International HVAC&R Congress and Exhibition, Belgrade, 5–7 Dec. 2018
12
49. Međunarodni kongres i izložba o KGH, Beograd, 5–7.12.201849th International HVAC&R Congress and Exhibition, Belgrade, 5–7 Dec. 2018
13
49. Međunarodni kongres i izložba o KGH, Beograd, 5–7.12.201849th International HVAC&R Congress and Exhibition, Belgrade, 5–7 Dec. 2018
14
49. Međunarodni kongres i izložba o KGH, Beograd, 5–7.12.201849th International HVAC&R Congress and Exhibition, Belgrade, 5–7 Dec. 2018
15
49. Međunarodni kongres i izložba o KGH, Beograd, 5–7.12.201849th International HVAC&R Congress and Exhibition, Belgrade, 5–7 Dec. 2018
16
49. Međunarodni kongres i izložba o KGH, Beograd, 5–7.12.201849th International HVAC&R Congress and Exhibition, Belgrade, 5–7 Dec. 2018
17
49. Međunarodni kongres i izložba o KGH, Beograd, 5–7.12.201849th International HVAC&R Congress and Exhibition, Belgrade, 5–7 Dec. 2018
18
Answers to Open questions
•Does PROPERLY functioning safety valve prevent boiler explosion? •No, it regulates pressure, it does not control the removal of excess heat. 1/20th of the overheat is removed.•Additionaly, it is projected to 110 °C.•Additionaly, system goes toward the boiling.•Does draught regulator can regulate boiler flow temperature at ALL regimes? •No, it regulates temperature in common changes which depend on atmospheric changes, which are slow. In case of electricity, power failure, air lock, it can not regulate temperature.
49. Međunarodni kongres i izložba o KGH, Beograd, 5–7.12.201849th International HVAC&R Congress and Exhibition, Belgrade, 5–7 Dec. 2018
19
49. Međunarodni kongres i izložba o KGH, Beograd, 5–7.12.201849th International HVAC&R Congress and Exhibition, Belgrade, 5–7 Dec. 2018
20
Temperature regulator (or draught regulator)
49. Međunarodni kongres i izložba o KGH, Beograd, 5–7.12.201849th International HVAC&R Congress and Exhibition, Belgrade, 5–7 Dec. 2018
21
Answers to Open questions•Can boiler be safe without system for removal (dissipation) of EXCESS heat? •It can if it passes the test, and it fits into category of with rapidly disconnecting firing system. Unfortunately, these are rare in Serbia.•Can there be a SAFE installation of boiler in a premises without water supply network access point? •Similar answer as the previos one. If safety heat exchanger is needed, then water access point is necessary.•What type of solid fuel boilers CAN be installed in closed heating system? •Pellet boilers can, for example. If they pass the test.
49. Međunarodni kongres i izložba o KGH, Beograd, 5–7.12.201849th International HVAC&R Congress and Exhibition, Belgrade, 5–7 Dec. 2018
22
Answers to Open questions
•Is BOILING allowed in closed system?•No, therefore there is a safety temperature difference, and control of temperature. Heating boilers should be called Heating non-boilers.•Can we treat SAFETY as optional?•No.•FREQUENCY of heating boiler explosions?•Low. But we are designing a boiler for worst case scenario.
49. Međunarodni kongres i izložba o KGH, Beograd, 5–7.12.201849th International HVAC&R Congress and Exhibition, Belgrade, 5–7 Dec. 2018
23
49. Međunarodni kongres i izložba o KGH, Beograd, 5–7.12.201849th International HVAC&R Congress and Exhibition, Belgrade, 5–7 Dec. 2018
24
Overheating should not be downplayed. Overheating in a closed system is a near explosion situation and it should be treated as such. So systems that prevent it cannot be optional.
CONCLUSIONS
49. Međunarodni kongres i izložba o KGH, Beograd, 5–7.12.201849th International HVAC&R Congress and Exhibition, Belgrade, 5–7 Dec. 2018
25
On the other hand a number of components in the system are working against overheating so frequency of explosion occurrence is low. There must be a perfect storm of failures to result in explosion.
CONCLUSIONS
49. Međunarodni kongres i izložba o KGH, Beograd, 5–7.12.201849th International HVAC&R Congress and Exhibition, Belgrade, 5–7 Dec. 2018
26
Our job as engineers is to apply all known rules. Standard clearly states: “Boilers with manual stoking shall be designed in such a way that, when the boiler is operated in accordance with the boiler manufacturer’s operating instructions, the operator does not run the risk of a hazardous operation mode”. So far the practice was such that played the probability card, and if there comes to explosion escape goat was safety valve.
CONCLUSIONS
49. Međunarodni kongres i izložba o KGH, Beograd, 5–7.12.201849th International HVAC&R Congress and Exhibition, Belgrade, 5–7 Dec. 2018
27
-Special gratitude to then third year students for doing the survey on solid fuel boilers in closed heating systems:
Semester 2016/17; Racić, Gagić, Jakovljević, Milošević, Oluški, Subić, Tojaga, Tomić, Vujanović and Jeremić .
Semester 2017/18; Đukić, Radanović, Bartula, Jovanov, Miletić and Zeljković.
49. Međunarodni kongres i izložba o KGH, Beograd, 5–7.12.201849th International HVAC&R Congress and Exhibition, Belgrade, 5–7 Dec. 2018