Safety Assessment of an Electrical System with AltaRica 3.0

Hala MORTADA (LIX, Ecole Polytechnique)

Tatiana PROSVIRNOVA (LIX, Ecole Polytechnique)

Antoine RAUZY (LGI, Ecole Centrale)

Page 2: Safety Assessment of an Electrical System with AltaRica 3 · 2014-11-05 · Safety Assessment of an Electrical System with AltaRica 3.0 Hala MORTADA (LIX, Ecole Polytechnique) Tatiana

2 IMBSA 2014 , October 27 – 29, 2014

• Case study: an Electrical System

• Structural constructs

• Behavior modeling

—Block diagrams

—Common cause failures

—Repairs, on demand failures and reconfigurations

—Shared resources

Outline

Starting from the same root model, different variants can be obtained by successive refinements.

Page 3: Safety Assessment of an Electrical System with AltaRica 3 · 2014-11-05 · Safety Assessment of an Electrical System with AltaRica 3.0 Hala MORTADA (LIX, Ecole Polytechnique) Tatiana

3 IMBSA 2014 , October 27 – 29, 2014

• Case study: an Electrical System

• Structural constructs

• Behavior modeling

—Block diagrams

—Common cause failures

—Repairs, on demand failures and reconfigurations

—Shared resources

Outline

Starting from the same root model, different variants can be obtained by successive refinements.

Page 4: Safety Assessment of an Electrical System with AltaRica 3 · 2014-11-05 · Safety Assessment of an Electrical System with AltaRica 3.0 Hala MORTADA (LIX, Ecole Polytechnique) Tatiana

4 IMBSA 2014 , October 27 – 29, 2014

Case study: an Electrical System

Transformer TR1

Transformer TR2

Diesel Generator DG

Circuit breaker CBD1

Circuit breaker CBD2

Circuit breaker CB3

Busbar

Grid GR

Circuit breaker CBU1

Circuit breaker CBU2

Backup Power Supply Primary Power Supply

Line1 Line2

Page 5: Safety Assessment of an Electrical System with AltaRica 3 · 2014-11-05 · Safety Assessment of an Electrical System with AltaRica 3.0 Hala MORTADA (LIX, Ecole Polytechnique) Tatiana

5 IMBSA 2014 , October 27 – 29, 2014

• Case study: an Electrical System

• Structural constructs

• Behavior modeling

—Block diagrams

—Common cause failures

—Repairs, on demand failures and reconfigurations

—Shared resources

Outline

Starting from the same root model, different variants can be obtained by successive refinements.

Page 6: Safety Assessment of an Electrical System with AltaRica 3 · 2014-11-05 · Safety Assessment of an Electrical System with AltaRica 3.0 Hala MORTADA (LIX, Ecole Polytechnique) Tatiana

6 IMBSA 2014 , October 27 – 29, 2014

• Blocks represent components having a unique occurrence in the model

• They are the basic construct to group model elements

• A model is thus a hierarchy of nested blocks

• Blocks come from prototype-oriented languages

Blocks

block DieselGenerator block CircuitBreaker

block BackupPowerSupplySystem

block BackupPowerSupplySystem block DieselGenerator // elements of the diesel generator end

block CircuitBreaker // elements of the circuit breaker end

/* elements to connect the diesel generator and the circuit breaker*/

end

Page 7: Safety Assessment of an Electrical System with AltaRica 3 · 2014-11-05 · Safety Assessment of an Electrical System with AltaRica 3.0 Hala MORTADA (LIX, Ecole Polytechnique) Tatiana

7 IMBSA 2014 , October 27 – 29, 2014

• A class is a separately defined, reusable (“on-the-shelf”) block

• A block can aggregate (contain) other blocks as well as instances, i.e. copies, of classes

• A class can aggregate blocks and instances of classes

• Definitions of classes cannot be recursive nor circular

• Classes come from object-oriented modeling languages

Classes

class DieselGenerator // elements of the diesel generator

end class CircuitBreaker // elements of the circuit breaker end block BackupPowerSupplySystem DiseselGenerator DG; CircuitBreaker CB3; /* elements to connect

the diesel generator DG and the circuit breaker CB3*/

end

DieselGenerator DG CircuitBreaker CB3

block BackupPowerSupplySystem

Page 8: Safety Assessment of an Electrical System with AltaRica 3 · 2014-11-05 · Safety Assessment of an Electrical System with AltaRica 3.0 Hala MORTADA (LIX, Ecole Polytechnique) Tatiana

8 IMBSA 2014 , October 27 – 29, 2014

• The semantics of AltaRica 3.0 is defined by means of flattening rules, i.e. that the hierarchy of blocks and instances of classes is collapsed into a single block

• Flattening rules depend on the type of hierarchical links:

—Aggregation

—Inheritance

—Reference (“embeds” clause)

Flattening

Page 9: Safety Assessment of an Electrical System with AltaRica 3 · 2014-11-05 · Safety Assessment of an Electrical System with AltaRica 3.0 Hala MORTADA (LIX, Ecole Polytechnique) Tatiana

9 IMBSA 2014 , October 27 – 29, 2014

• A hierarchical link: the is-a-part-of link

— e.g. the left-front wheel is a part of the car

• In AltaRica 3.0, a block or a class can aggregate blocks and instances of classes

• Flattening rules:

—Elements of the nested block (or the instance of class) are copied;

—Names of the elements are prefixed with the name of the block (or the instance of class)

Aggregation

class DieselGenerator Boolean working (init = true); event failure; transition failure : working -> working :=false; end block BackupPowerSupplySystem DieselGenerator DG; end

block BackupPowerSupplySystem Boolean DG.working (init = true); event DG.failure; transition DG.failure : DG.working -> DG.working :=false; end

flattening

Page 10: Safety Assessment of an Electrical System with AltaRica 3 · 2014-11-05 · Safety Assessment of an Electrical System with AltaRica 3.0 Hala MORTADA (LIX, Ecole Polytechnique) Tatiana

10 IMBSA 2014 , October 27 – 29, 2014

• A hierarchical link: the is-a-kind-of link

— e.g. a car is a kind of vehicle

• In AltaRica 3.0, a block or a class can inherit from another class.

• Flattening rules for inheritance are the same as those for aggregation, with the exception that the elements of the inherited components are copied without any prefix

Inheritance

class NonRepairableComponent Boolean working (init = true); event failure; transition failure : working -> working :=false; end class Pump extends NonRepairableComponent Boolean inflow (reset = false); Boolean outflow (reset = false); assertion outflow := inflow and working; end

class Pump Boolean working (init = true); Boolean inflow (reset = false); Boolean outflow (reset = false); event failure; transition failure : working -> working :=false; assertion outflow := inflow and working; end

flattening

Page 11: Safety Assessment of an Electrical System with AltaRica 3 · 2014-11-05 · Safety Assessment of an Electrical System with AltaRica 3.0 Hala MORTADA (LIX, Ecole Polytechnique) Tatiana

11 IMBSA 2014 , October 27 – 29, 2014

• Hierarchical decompositions are often thought only as tree-like structures. But in practice it is often convenient for two branches to share a component (especially when reasoning in functional terms).

• AltaRica 3.0 makes it possible to share blocks and instances of classes through the “embeds” clause.

Reference: the “embeds” clause

block PrimaryPowerSupplySystem

Transformer TR1

Grid GR

Transformer TR2

block Line1 block Line2

block PrimaryPowerSupplySystem Grid GR; block Line1 embeds GR; Transformer TR1; end block Line2 embeds GR; Transformer TR2; end end

Grid GR

Page 12: Safety Assessment of an Electrical System with AltaRica 3 · 2014-11-05 · Safety Assessment of an Electrical System with AltaRica 3.0 Hala MORTADA (LIX, Ecole Polytechnique) Tatiana

12 IMBSA 2014 , October 27 – 29, 2014

System architecture

block ElectricalSystem block PrimaryPowerSupplySystem Grid GR; block Line1 embeds GR; CircuitBreaker CBU1, CBD1; Transformer TR1; end block Line2 embeds GR; CircuitBreaker CBU2, CBD2; Transformer TR2; end end block BackupPowerSupplySystem DieselGenerator DG; CircuitBreaker CB3; end Busbar BB; end

Class instances Blocks

Page 13: Safety Assessment of an Electrical System with AltaRica 3 · 2014-11-05 · Safety Assessment of an Electrical System with AltaRica 3.0 Hala MORTADA (LIX, Ecole Polytechnique) Tatiana

13 IMBSA 2014 , October 27 – 29, 2014

• Case study: an Electrical System

• Structural constructs

• Behavior modeling

—Block diagrams

—Common cause failures

—Repairs, on demand failures and reconfigurations

—Shared resources

Outline

Starting from the same root model, different variants can be obtained by successive refinements.

Page 14: Safety Assessment of an Electrical System with AltaRica 3 · 2014-11-05 · Safety Assessment of an Electrical System with AltaRica 3.0 Hala MORTADA (LIX, Ecole Polytechnique) Tatiana

14 IMBSA 2014 , October 27 – 29, 2014

Behavior modeling

Block Diagram

Common cause Failures

Repairs, on demand failures and

reconfigurations

Shared resources

block ElectricalSystem block PrimaryPowerSupplySystem Grid GR; block Line1 embeds GR; CircuitBreaker CBU1, CBD1; Transformer TR1; end block Line2 embeds GR; CircuitBreaker CBU2, CBD2; Transformer TR2; end end block BackupPowerSupplySystem DieselGenerator DG; CircuitBreaker CB3; end Busbar BB; end

1

2

3

4

Page 15: Safety Assessment of an Electrical System with AltaRica 3 · 2014-11-05 · Safety Assessment of an Electrical System with AltaRica 3.0 Hala MORTADA (LIX, Ecole Polytechnique) Tatiana

15 IMBSA 2014 , October 27 – 29, 2014

Block diagram: modeling 1

domain ComponentState { WORKING, FAILED } class NonRepairableComponent ComponentState s (init = WORKING); event failure (delay = exponential(lambda)); parameter Real lambda = 0.001; transition failure: s == WORKING -> s := FAILED; end class Transformer extends NonRepairableComponent; Boolean inFlow, outFlow (reset = FALSE); assertion outFlow := (s == WORKING) and inFlow; end

failure

s == WORKING

s == FAILED

inFlow outFlow

All the components are represented by the class NonRepairableComponent with input and output flows

Page 16: Safety Assessment of an Electrical System with AltaRica 3 · 2014-11-05 · Safety Assessment of an Electrical System with AltaRica 3.0 Hala MORTADA (LIX, Ecole Polytechnique) Tatiana

16 IMBSA 2014 , October 27 – 29, 2014

Block diagram: modeling 1

block ElectricalSystem Boolean outFlow (reset = false); block PrimaryPowerSupply … block Line1 … assertion CBU1.inFlow := GR.outFlow; TR1.inFlow := CBU1.outFlow; CBD1.inFlow := TR1.outFlow; end block Line2 ... // similar to Line1 end assertion outFlow := Line1.outFlow or Line2.outFlow; end ... assertion outFlow := PrimaryPowerSupply.outFlow or BackupPowerSupply.outFlow; end

Page 17: Safety Assessment of an Electrical System with AltaRica 3 · 2014-11-05 · Safety Assessment of an Electrical System with AltaRica 3.0 Hala MORTADA (LIX, Ecole Polytechnique) Tatiana

17 IMBSA 2014 , October 27 – 29, 2014

• Static model

• Is compiled into Fault Trees

• Calculated Minimal cutsets (MCS):

Block diagram: assessment 1

MCS MCS

GR.failure, DG.failure GR.failure, CB3.failure

CBU1.failure, CBU2.failure, DG.failure CBU1.failure, CBU2.failure, CB3.failure

CBU1.failure, TR2.failure, DG.failure CBU1.failure, TR2.failure, CB3.failure

CBU1.failure, CBD2.failure, DG.failure CBU1.failure, CBD2.failure, CB3.failure

TR1.failure, CBU2.failure, DG.failure TR1.failure, CBU2.failure, CB3.failure

TR1.failure, TR2.failure, DG.failure TR1.failure, TR2.failure, CB3.failure

TR1.failure, CBD2.failure, DG.failure TR1.failure, CBD2.failure, CB3.failure

CBD1.failure, CBU2.failure, DG.failure CBD1.failure, CBU2.failure, CB3.failure

CBD1.failure, TR2.failure, DG.failure CBD1.failure, TR2.failure, CB3.failure

CBD1.failure, CBD2.failure, DG.failure CBD1.failure, CBD2.failure, CB3.failure

Page 18: Safety Assessment of an Electrical System with AltaRica 3 · 2014-11-05 · Safety Assessment of an Electrical System with AltaRica 3.0 Hala MORTADA (LIX, Ecole Polytechnique) Tatiana

18 IMBSA 2014 , October 27 – 29, 2014

• Consider that the two transformers have a common cause failure due to a fire propagation.

• Assume that the CCF failure rate lambdaCCF =1.0e-5.

Common cause failures

Fire propagation Failure of both transformers

2

Page 19: Safety Assessment of an Electrical System with AltaRica 3 · 2014-11-05 · Safety Assessment of an Electrical System with AltaRica 3.0 Hala MORTADA (LIX, Ecole Polytechnique) Tatiana

19 IMBSA 2014 , October 27 – 29, 2014

block PowerSupplySystem

block PrimaryPowerSupplySystem

Grid GR;

block Line1

end

block Line2

end

event TransformersCCF (delay = exponential (lambdaCCF));

parameter Real lambdaCCF = 1.0e–5;

transition

TransformersCCF: ?Line1.TR1.failure & ?Line2.TR2.failure;

end

end

Common cause failures: modeling 2

Page 20: Safety Assessment of an Electrical System with AltaRica 3 · 2014-11-05 · Safety Assessment of an Electrical System with AltaRica 3.0 Hala MORTADA (LIX, Ecole Polytechnique) Tatiana

20 IMBSA 2014 , October 27 – 29, 2014

• Static model

• Is compiled into Fault Trees

• Two additional minimal cutsets:

Common cause failures: assessment 2

MCS

TransformersCCF, DG.failure

TransformersCCF, CB3.failure

Page 21: Safety Assessment of an Electrical System with AltaRica 3 · 2014-11-05 · Safety Assessment of an Electrical System with AltaRica 3.0 Hala MORTADA (LIX, Ecole Polytechnique) Tatiana

21 IMBSA 2014 , October 27 – 29, 2014

• Consider that —The circuit breakers can be open, closed and can have on demand

failures (failure to open or failure to close) with a given probability gamma = 10-3.

—The diesel generator can be started or stopped and can have on demand failure (failure to start).

—In the initial state the power is transmitted to the Busbar via the Line 1, i.e. the circuit breakers CBU1 and CBD1 are closed, the circuit breakers CBU2 and CBD2 are open, the diesel generator DG is stopped, the circuit breaker CB3 is open.

—If the Line 1 fails, the system should be reconfigured to use the Line 2 (i.e. the circuit breakers CBU2 and CBD2 should be closed). If both lines are failed, the diesel generator DG is attempted to start and the circuit breaker CB3 is attempted to close.

Repairs, on demand failures and reconfigurations 3

Page 22: Safety Assessment of an Electrical System with AltaRica 3 · 2014-11-05 · Safety Assessment of an Electrical System with AltaRica 3.0 Hala MORTADA (LIX, Ecole Polytechnique) Tatiana

22 IMBSA 2014 , October 27 – 29, 2014

Repairs, on demand failures and reconfigurations: modeling

class RepairableComponent extends NonRepairableComponent; Boolean failed (reset = false); event repair (delay = exponential(mu)); parameter Real mu = 0.1; transition repair: s == FAILED -> s := WORKING; assertion failed := s == WORKING; end class Grid extends RepairableComponent; Boolean outFlow (reset = false); assertion outFlow := s==WORKING; end

repair failure

s == WORKING

s == FAILED

How to model a repairable component?

3

The grid GR and the transformers TR1 and TR2 are repairable components

Page 23: Safety Assessment of an Electrical System with AltaRica 3 · 2014-11-05 · Safety Assessment of an Electrical System with AltaRica 3.0 Hala MORTADA (LIX, Ecole Polytechnique) Tatiana

23 IMBSA 2014 , October 27 – 29, 2014

Repairs, on demand failures and reconfigurations: modeling

class CircuitBreaker extends RepairableComponent; Boolean isClosed (init = true); Boolean demanded (reset = false); event failToOpen (delay = 0, expectation = gamma1); event failToClose (delay = 0, expectation = gamma2); event open (delay = 0, expectation = 1 - gamma1); event close (delay = 0, expectation = 1 - gamma2); parameter Real gamma1 = 0.001; parameter Real gamma2 = 0.001; transition failToOpen: isClosed and (s == WORKING) and not demanded-> s := FAILED; open: isClosed and (s == WORKING) and not demanded-> isClosed := false; failToClose: not isClosed and (s == WORKING) and demanded-> s := FAILED; close: not isClosed and (s == WORKING) and demanded-> isClosed := true; assertion outFlow := isClosed and s == WORKING and inFlow; end

How to model a circuit breaker?

outFlow

demanded

inFlow

failure

s == WORKING isClosed

s == FAILED isClosed

s == WORKING not isClosed

s == FAILED not isClosed

failure

failToClose

close open

failToOpen

repair

repair

3

Page 24: Safety Assessment of an Electrical System with AltaRica 3 · 2014-11-05 · Safety Assessment of an Electrical System with AltaRica 3.0 Hala MORTADA (LIX, Ecole Polytechnique) Tatiana

24 IMBSA 2014 , October 27 – 29, 2014

Repairs, on demand failures and reconfigurations: modeling

domain SpareComponentState {STANDBY, WORKING, FAILED} class SpareComponent; SpareComponentState s (init = STANDBY); Boolean failed (reset = false); Boolean demanded (reset = FALSE); parameter Real lambda = 1.0e-4; parameter Real mu = 0.1; parameter Real gamma = 0.001; event failure (delay = exponential(lambda)); event repair (delay = exponential(mu)); event stop (delay = 0); event start (delay = 0, expectation = 1-gamma); event failureOnDemand (delay = 0, expectation = gamma); event repair (delay = exponential(mu)); transition stop: s == WORKING and not demanded -> s := STANDBY; start: s == STANDBY and demanded -> s := WORKING; failureOnDemand: s == STANDBY and demanded -> s := FAILED; repair: s == FAILED -> s := STANDBY; failure: s == WORKING -> s := FAILED; assertion failed := s == FAILED. end

How to model a spare component? demanded

failure

s == WORKING

s == FAILED repair

s == STANDBY

stop

start

failureOnDemand

3

The diesel generator DG is represented by a spare component

Page 25: Safety Assessment of an Electrical System with AltaRica 3 · 2014-11-05 · Safety Assessment of an Electrical System with AltaRica 3.0 Hala MORTADA (LIX, Ecole Polytechnique) Tatiana

25 IMBSA 2014 , October 27 – 29, 2014

Repairs, on demand failures and reconfigurations: modeling

How to represent reconfigurations?

block PowerSupplySystem block PrimaryPowerSupplySystem Boolean failed, demanded (reset = false); Grid GR; block Line1 Boolean failed, demanded (reset = false); … assertion CBU1.demanded := demanded; CBD1.demanded := demanded; failed := GR.failed or CBU1.failed or TR1.failed or CBD1.failed; end … assertion Line1.demanded := not Line1.failed and not Line2.outFlow; Line2.demanded := not Line2.failed and not Line1.outFlow; … end

Lin

e1

Lin

e2

demanded demanded

failed failed

outFlow outFlow

PrimaryPowerSupplySystem

demanded

failed outFlow

3

Page 26: Safety Assessment of an Electrical System with AltaRica 3 · 2014-11-05 · Safety Assessment of an Electrical System with AltaRica 3.0 Hala MORTADA (LIX, Ecole Polytechnique) Tatiana

26 IMBSA 2014 , October 27 – 29, 2014

• Dynamic model

• Is compiled into Markov chains

• Assessment of the generated Markov chain: unavailability calculation

On demand failures and reconfigurations: assessment

3

0.02E-06

0.02E-06

0.02E-06

0.02E-06

0.02E-06

0.02E-06

0.02E-06

0.02E-06

0.02E-06

0.02E-06

0.02E-06

20 30 40 50 60 70 80 90 100 200 300 400 500 600 700 800 900 1000

Pro

bab

ility

Mission time

Unavailability

Page 27: Safety Assessment of an Electrical System with AltaRica 3 · 2014-11-05 · Safety Assessment of an Electrical System with AltaRica 3.0 Hala MORTADA (LIX, Ecole Polytechnique) Tatiana

27 IMBSA 2014 , October 27 – 29, 2014

Shared resources

TR1 TR2 R

(Repair crew) GR

GR.failure

GR_startRepair

CCF

TR1_startRepair

GR_endRepair

TR2_startRepair

GR.startRepair R.startJob

TR1.failure TR2.failure

TR1.startRepair R.startJob

GR.endRepair R.endJob

TR1_endRepair TR1.endRepair R.endJob

TR2.startRepair R.startJob

TR2_endRepair TR2.endRepair R.endJob

4

Consider that a limited repair crew can work on at most two components at a time

Page 28: Safety Assessment of an Electrical System with AltaRica 3 · 2014-11-05 · Safety Assessment of an Electrical System with AltaRica 3.0 Hala MORTADA (LIX, Ecole Polytechnique) Tatiana

28 IMBSA 2014 , October 27 – 29, 2014

Shared resources: modeling

class RepairCrew Integer numberOfBusyRepairers (init = 0); parameter Integer totalNumberOfRepairers = 2; event startJob, endJob; transition startJob: numberOfBusyRepairers < totalNumberOfRepairers -> numberOfBusyRepairers := numberOfBusyRepairers + 1; endJob: numberOfBusyRepairers > 0 -> numberOfBusyRepairers := numberOfBusyRepairers - 1; end

0 1 N …

startJob startJob startJob

endJob endJob endJob

How to model a repair crew?

4

Page 29: Safety Assessment of an Electrical System with AltaRica 3 · 2014-11-05 · Safety Assessment of an Electrical System with AltaRica 3.0 Hala MORTADA (LIX, Ecole Polytechnique) Tatiana

29 IMBSA 2014 , October 27 – 29, 2014

Shared resources: modeling

endRepair

failure

s == WORKING

domain RepairableComponentState {WORKING, FAILED, UNDER_REPAIR} class RepairableComponent RepairableComponentState s (init = WORKING); Boolean failed (reset = false); event failure (delay = exponential(lambda)); event startRepair; event endRepair (delay = exponential(mu)); parameter Real mu = 0.; parameter Real lambda = 1.0 e-4; transition failure: s == WORKING -> s := FAILED; startRepair: s == FAILED -> s := UNDER_REPAIR ; endRepair: s == UNDER_REPAIR -> s := WORKING; assertion failed := s == FAILED or s == UNDER_REPAIR; end

s == FAILED

s == UNDER_REPAIR startRepair

How to model a repairable component?

4

Page 30: Safety Assessment of an Electrical System with AltaRica 3 · 2014-11-05 · Safety Assessment of an Electrical System with AltaRica 3.0 Hala MORTADA (LIX, Ecole Polytechnique) Tatiana

30 IMBSA 2014 , October 27 – 29, 2014

Shared resources: modeling

block PowerSupplySystem block PrimaryPowerSupplySystem … end block BackupPowerSupplySystem … end … RepairCrew R(totalNumberOfRepairers = 2); event GR_startRepair; event GR_endRepair; … transition GR_startRepair: !R.startJob & !PrimaryPowerSupplySystem.GR.startRepair; GR_endRepair: !R.endJob & !PrimaryPowerSupplySystem.GR.endRepair; hide R.startJob, R.endJob; hide PrimaryPowerSupplySystem.GR.startRepair, PrimaryPowerSupplySystem.GR.endRepair; … end

How to synchronize events?

4

Page 31: Safety Assessment of an Electrical System with AltaRica 3 · 2014-11-05 · Safety Assessment of an Electrical System with AltaRica 3.0 Hala MORTADA (LIX, Ecole Polytechnique) Tatiana

31 IMBSA 2014 , October 27 – 29, 2014

Shared resources: assessment

0.00E+00

0.02E-06

0.04E-06

0.06E-06

0.08E-06

0.10E-06

0.12E-06

0.14E-06

0.16E-06

20 30 40 50 60 70 80 90 100 200 300 400 500 600 700 800 900 1000

Pro

bab

ility

Mission time

Unavailability for different number of repairers

Proba (n=1) Proba (n=3) Proba (n=infinite)

ʎ 10-4

ɤ 10-3

µ 10-1

4

Dynamic model

Is compiled into Markov chains

Assessment of the generated Markov chain: unavailability calculation

Page 32: Safety Assessment of an Electrical System with AltaRica 3 · 2014-11-05 · Safety Assessment of an Electrical System with AltaRica 3.0 Hala MORTADA (LIX, Ecole Polytechnique) Tatiana

32 IMBSA 2014 , October 27 – 29, 2014

• Different variants of models of the case study have been defined

—The first series targeting a compilation into Fault Trees

—The second series targeting a compilation into Markov chains

• Each of these variants captures a particular aspect of the system under study

• A model is always a trade-off between the accuracy of the description and the ability to perform calculations

• Refining a model in successive variants is a good way to seek a good trade-off

• The approach made of successive derivation of variants is a solid ground to build a modeling methodology

Conclusion