    OPTICAL GROUND WIRESwith capacity up to 288

    optical fibresOPGW

    Ref: s011

    PRYSMIAN 2006, All Rights Reserved.The information contained within this document must not be copied, reprinted or reproduced in any form, either wholly or in part, without thewritten consent of Prysmian. The information is believed to be correct at the time of issue. Prysmian reserves the right to amend this specificationwithout prior notice. This specification is not contractually valid unless specifically authorised by Prysmian.

    Rev.:01

    Date:21-oct-2011

    Issued by:E. Castillo

    page 2 of 2

    Cable characteristics Optical unit composed by 1 to 6 stranded stainless steel tubes. Temperature range: -40C to 80C Lay direction armor: left (S) or right (Z)

    FAULT

    CURRENT

    TOTALCONDUCTOR

    AREA

    OVERALL

    DIAMETER WEIGHT RBS

    FIBER (max) OPGWREFERENCE(kA) sec in mm in mm lbs/ft kg/m lbs kg

    SAG10CHART #

    24 20A42Ds (7978) 41 0.1233 79.53 0.472 12.0 0.282 417 14947 6780 1-1461

    36 20A37Ds (7979) 41 0.1180 76.12 0.472 12.0 0.251 370 12269 5565 1-350

    24 41F47Ds (7975) 96 0.1764 113.81 0.555 14.1 0.320 473 15621 7086 1-1438

    24 46H47Ds (7976) 116 0.1896 122.32 0.575 14.6 0.321 474 14782 6705 1-430

    96 60J62Ds (7977) 137 0.2140 138.05 0.630 16.0 0.420 620 20091 9113 1-1170

    96 64J67Ds (7980) 152 0.2254 145.45 0.646 16.4 0.452 668 22191 10066 1-917

    96 70K71Ds (7981) 177 0.2412 155.63 0.669 17.0 0.478 706 23303 10570 1-917

    144 60H62Ds (7982) 118 0.2017 130.12 0.630 16.0 0.417 616 19866 9011 1-1440

    144 64J66Ds (7983) 132 0.2131 137.51 0.646 16.4 0.449 663 22059 10006 1-350144 70K70Ds (7984) 152 0.2289 147.7 0.669 17.0 0.474 700 23051 10456 1-1440

    192 60G61Ds (7985) 100 0.1894 122.18 0.630 16.0 0.415 612 19641 8909 1-536

    192 64H66Ds (7986) 114 0.2008 129.58 0.646 16.4 0.446 659 21642 9817 1-420

    192 70J70Ds (7987) 134 0.2166 139.76 0.669 17.0 0.472 697 22800 10342 1-536

    288 60D60Ds (7990) 71 0.1654 106.72 0.630 16.0 0.405 598 19048 8663 1-1166

    288 60E64Ds (7992) 80 0.1764 113.81 0.630 16.0 0.435 642 21131 9585 1-1461

    288 66G68Ds (7991) 98 0.1931 124.57 0.653 16.6 0.461 680 22300 10115 1-1166

    Please note that PLS-CADD files are available at http://www.powline.com/files/cables.html

    Routine tests100% of optical fibers will be measured by OTDR technique before leaving factory.

    Installation procedurePrysmian recommends to install the cable described in this specification following the latest version of our"Installation procedures for OPGW fiber optic cable" reference SIG-07-PE-PA-013, "Instruction for the installation of the EWMJ joint box" reference SIG-07-PE-PA-015 and "Instruction for the installation of the EWJ joint box"reference SIG-07-PE-PA-008.

    http://www.powline.com/files/cables.htmlhttp://www.powline.com/files/cables.html