36
RWM Control in ITER Presented by Gerald A. Navratil Including analysis by Jim Bialek & Oksana Katsuro-Hopkins

RWM Control in ITER - DIII-Dr,z = 8.85,0.45 m This models the Idealized n=1 RWM coil. 7/12 RWM response to coil current (transfer function) The RWM response to the coil current can

  • Upload
    others

  • View
    6

  • Download
    0

Embed Size (px)

Citation preview

Page 1: RWM Control in ITER - DIII-Dr,z = 8.85,0.45 m This models the Idealized n=1 RWM coil. 7/12 RWM response to coil current (transfer function) The RWM response to the coil current can

RWM Control in ITER

Presented by Gerald A. Navratil

Including analysis byJim Bialek &

Oksana Katsuro-Hopkins

Page 2: RWM Control in ITER - DIII-Dr,z = 8.85,0.45 m This models the Idealized n=1 RWM coil. 7/12 RWM response to coil current (transfer function) The RWM response to the coil current can

OUTLINE• PASSIVE STABILIZATION OF RWM IN ITER

+ ITER PASSIVE STABILIZER PERFORMANCE: IMPORTANT ROLEOF THE BLANKET MODULES

• ACTIVE CONTROL OF RWM WITH BASELINEERROR CORRECTION COILS+ BENCHMARKING OF MARS, VALEN/DCON, AND KINX

• IMPROVED COIL DESIGN OPTIONS & ADVANCEDCONTROL ALGORITHMS+ EXTERNAL ON-VESSEL COILS

+ INTERNAL COILS

+ OPTIMAL CONTROLLER AND OBSERVER

Page 3: RWM Control in ITER - DIII-Dr,z = 8.85,0.45 m This models the Idealized n=1 RWM coil. 7/12 RWM response to coil current (transfer function) The RWM response to the coil current can

Passive Stabilizing Structures in ITER

• Double Wall Vacuum Vesselwith ~190 ms time constantfor each wall for 1/1 fieldpattern.

• Blanket/Shield ModulesSpecified to have 5 ms to9 ms time constant fornormal B-field soak through

Page 4: RWM Control in ITER - DIII-Dr,z = 8.85,0.45 m This models the Idealized n=1 RWM coil. 7/12 RWM response to coil current (transfer function) The RWM response to the coil current can

ITER Blanket/Shield Plays Important MHD Role• Blanket/Shield Modules Specified

to have 5 to 9 ms time constant• Ulrickson finds longer time

constants: 40 ms to 100 msShould be ITER Issue to Clarify

Page 5: RWM Control in ITER - DIII-Dr,z = 8.85,0.45 m This models the Idealized n=1 RWM coil. 7/12 RWM response to coil current (transfer function) The RWM response to the coil current can

ITER Technical Basis G A0 FDR 1 00-07-13 R1.0

Plant Description Document Chapter 4 Page 12

Table 4.3.3-1 ITER Parameters for the Non-Inductive Scenario

Parameter WNS Parameter WNS Parameter WNS

R/a (m/m) 6.35/1.85 bN 2.95 fHe (%) 4.1

BT (T) 5.18 bp 1.49 fBe (%) 2

Ip (MA) 9.0 Pfus (MW) 356 fAr (%) 0.26k95/d95 1.85/0.4 PL-H + PNB (MW) 29 + 30 Zeff 2.07

<ne> (1019m-3) 6.7 Q 6.0 P rad (MW) 37.6n/nG 0.82 Wth (MJ) 287 P loss (MW) 92.5

<Ti > (keV) 12.5 Ploss/P thr. L-H 2.59 tE (s) 3.1

<Te> (KeV) 12.3 bT % 2.77 ta*/tE 5.0

ICD/Ip (%) 51.9 li (3) 0.72 HH98 (y2) 1.57

Ibs/ Ip (%) 48.1 q95/qo/qmin 5.3/3.5/2.2IOH/Ip (%) 0

Figure 4.3.3-1 Plasma Parameter Profiles at the Current Flat-top Phase(t > 1000 s) for the Steady State WNS Operational Scenario

Page 6: RWM Control in ITER - DIII-Dr,z = 8.85,0.45 m This models the Idealized n=1 RWM coil. 7/12 RWM response to coil current (transfer function) The RWM response to the coil current can

ITPA Benchmark Study Shows GoodAgreement Among Codes

• RWM Dispersion Relationfor 2D axisymmetric ITERVacuum Vessel withoutports or Blanket/Modules

Page 7: RWM Control in ITER - DIII-Dr,z = 8.85,0.45 m This models the Idealized n=1 RWM coil. 7/12 RWM response to coil current (transfer function) The RWM response to the coil current can

ITER Ports Cause Small Reduction in Ideal Limit

5.04.03.02.02.010 - 1

10 0

10 1

10 2

10 3

10 4

10 5

10 6

beta-n(new)

grow

th r

ate

[1/s

]

no blankets & no ports

no blankets45 ports

• No wall bN limit is 2.4; Ideal Wall Limit Drops to bN ~ 3.3

Page 8: RWM Control in ITER - DIII-Dr,z = 8.85,0.45 m This models the Idealized n=1 RWM coil. 7/12 RWM response to coil current (transfer function) The RWM response to the coil current can

VALEN Model of ITER Double Wall Vessel and Blanket Modules

XY

Z

Page 9: RWM Control in ITER - DIII-Dr,z = 8.85,0.45 m This models the Idealized n=1 RWM coil. 7/12 RWM response to coil current (transfer function) The RWM response to the coil current can

ITER Blanket Opens Up Large AT Regime

• No wall βN limit is 2.4; Ideal Wall Limit With Blanket is ~ 5

Page 10: RWM Control in ITER - DIII-Dr,z = 8.85,0.45 m This models the Idealized n=1 RWM coil. 7/12 RWM response to coil current (transfer function) The RWM response to the coil current can

Active Control in ITER:

Baseline External Error Correction Coils

ITPA MARS/VALEN Benchmarking

Page 11: RWM Control in ITER - DIII-Dr,z = 8.85,0.45 m This models the Idealized n=1 RWM coil. 7/12 RWM response to coil current (transfer function) The RWM response to the coil current can

ColumbiaUniversity

ITERPASSIVE STABILIZER AND ACTIVE CONTROL COILS

Inner Vacuum Vessel Wall (6 cm-thick stainless steel)

Outer VV Wall

The ITER vessel is modeled as two walls.

. Three sets of six saddle coils, outside the vessel, but the upper and lower coils couple weakly to the RWM. .

Page 12: RWM Control in ITER - DIII-Dr,z = 8.85,0.45 m This models the Idealized n=1 RWM coil. 7/12 RWM response to coil current (transfer function) The RWM response to the coil current can

VALEN Model of ITER Vessel and Control Coils:Base Case Feedback Control System

• Vacuum Vessel Modeled with and without wall penetrations.

Page 13: RWM Control in ITER - DIII-Dr,z = 8.85,0.45 m This models the Idealized n=1 RWM coil. 7/12 RWM response to coil current (transfer function) The RWM response to the coil current can

10-1

100

101

102

103

2.5 3 3.5

tarragona.2005

passive growth rate (bench)g Gp/Gd=e8/e8g+ Gp/Gd=e8/e8g Gp/Gd=e9/e9g+ Gp/gd=e9/e9

grow

th ra

te [

1/s]

βn

tarragona.2005

idea

l wal

l lim

it

passive

Gp [v/w] = 108

Gd [v/v] = 108

Gp [v/w] = 109

Gd [v/v] = 109

3.18

100

101

102

108 109 1010

tarragona.2005

g Gd scan Gp=e+9 s=0.1

grow

th ra

te [

1/s]

Gd [v/v] scan @ fixed βn = 3.22 & Gp [v/w] = 109

tarragona.2005

ITER Baseline Six External Coils with 10 s time ConstantsInvestigate combined Gp [v/w] & Gd [v/v] gain

Vcc = Gp x(sensor flux ) + Gd x( sensor voltage)

Stabilized to βn = 3.18When both Gp & Gd used

Could not reachβn = 3.22 with different Gd

Selectedgains

Page 14: RWM Control in ITER - DIII-Dr,z = 8.85,0.45 m This models the Idealized n=1 RWM coil. 7/12 RWM response to coil current (transfer function) The RWM response to the coil current can

6/12

RWM stabilization with PD controller: Results obtained in 2005

All codes have shown that proportional control algorithm for the current in feedback coils can stabilize RWM up to Cβ = 0.6-0.7. However effect of the feedback derivative gain (k2) on RWM stabilization was different. It is significant in MARS-F and KINX and very minor in VALEN. A proper choice of k1 and k2 in MARS-F and KINX allows stabilization of RWMs with Cβ ≈ 0.85. To clarify the reason of differences, comparison of the RWM response to the coil current was proposed (Y.Liu).

Page 15: RWM Control in ITER - DIII-Dr,z = 8.85,0.45 m This models the Idealized n=1 RWM coil. 7/12 RWM response to coil current (transfer function) The RWM response to the coil current can

Benchmarking model used in this analysis . below we show a cut away view of axisymmetric vacuum vessel (2 walls ) and VALEN approximation of continuous RWM coil

60 picture frame coilswith no overlap. Thetotal gap between allCoils = 1 toroidal degree

Each coil has adifferent current,this results in a n=1 distributionof current

No blanketModules

Coil top+3.9 m

Coil bottom-3.0 m

Br & Bz sensors atr,z = 8.85,0.45 m

This models theIdealized n=1 RWM coil

Page 16: RWM Control in ITER - DIII-Dr,z = 8.85,0.45 m This models the Idealized n=1 RWM coil. 7/12 RWM response to coil current (transfer function) The RWM response to the coil current can

7/12

RWM response to coil current (transfer function)

The RWM response to the coil current can be expressed via transfer function:

)()()(

0 sjbsbsP ϑ=

, bϑ(s), j(s) – Laplace transformations of the amplitudes of poloidal magnetic field, Bϑ(t), and current in 2D coils, J0(t). b0 - amplitude of radial component of magnetic field produced by unit DC current of the sinusoidal coil mode on the magnetic sensors.

Page 17: RWM Control in ITER - DIII-Dr,z = 8.85,0.45 m This models the Idealized n=1 RWM coil. 7/12 RWM response to coil current (transfer function) The RWM response to the coil current can

-0.6

-0.4

-0.2

0

0.2

0.4

0.6

-0.2 0 0.2 0.4 0.6 0.8 1 1.2ITERpolar.wrtI.01.2006

IM+IM-Im 3,3,48DB

Im [

P(jω

)]

Re[ P(jω)]

MARS(previous talk)

VALEN

withoutplasma

VALEN3 pole fit

VALEN / MARS quantitative comparison of ‘Msf ‘

MARSbr = 3.63e-8 [T/A] gaussian distributionbr = 8.02e-8 [T/A] cylindrical approximation

VALENbr = 9.369e-8 [T/A]

Page 18: RWM Control in ITER - DIII-Dr,z = 8.85,0.45 m This models the Idealized n=1 RWM coil. 7/12 RWM response to coil current (transfer function) The RWM response to the coil current can

Nyquist plots are consistent with previous VALENclosed loop (feedback) calculations. Nyquist diagramspredict stability up to Cβ > 58%. All Nyquist plots areup/down symmetric ( as expected from model ).

Cβ = 23.6%

Cβ = 46%

All curves shown have asingle counter clockwiseclosed path as jω is mappedfrom -infinity to +infinity.

Simple scaling by a positiveconstant (Kp) will make allthese curves enclose thepoint ( -1,0 ).

More scaling (gain) is neededfor higher Cβ

Curves shown are VALENtransfer functions, notcurve fits

Cβ = 58%

-1

-0.5

0

0.5

1

-1.5 -1 -0.5 0 0.5ITER.nyquist.02.2006

all 23% Imall 46% Imall 58% Im

Im P

(jω)

Re P(jω)

Page 19: RWM Control in ITER - DIII-Dr,z = 8.85,0.45 m This models the Idealized n=1 RWM coil. 7/12 RWM response to coil current (transfer function) The RWM response to the coil current can

VALEN Nyquist analysis as a function of Cβ isvery similar to published MARS results.

[Nucl. Fusion 44 (2004) 232-242 by Liu, Bondeson, Gribov & Polevoi]

Page 20: RWM Control in ITER - DIII-Dr,z = 8.85,0.45 m This models the Idealized n=1 RWM coil. 7/12 RWM response to coil current (transfer function) The RWM response to the coil current can

-0.3

-0.2

-0.1

0

0.1

0.2

0.3

-0.6 -0.5 -0.4 -0.3 -0.2 -0.1 0ITER.nyquist.02.2006

58% + Im58% - Im72% + Im72% - Im89.48% + Im89.48% - Im

Im P

(jω)

Re P(jω)

Nyquist plots derived fromVALEN are consistent withprevious VALEN closed loopfeedback calculations and MARSNyquist analysis at lower Cβ.

The direction of the curves haschanged at Cβ = 72%, where weobserve two clockwise rotations(unstable) as we map the line jω -not seen in MARS analysismaybe 3D eddy effect.

‘Simple’ feedback nolonger works!

Cβ = 58%

Cβ = 72%

Cβ = 89%

VALEN Shows More Complex Unstable Transfer Function at High Cβ

Page 21: RWM Control in ITER - DIII-Dr,z = 8.85,0.45 m This models the Idealized n=1 RWM coil. 7/12 RWM response to coil current (transfer function) The RWM response to the coil current can

Nyquist plots derived fromVALEN are consistent withprevious VALEN closed loopfeedback calculations and MARSNyquist analysis at lower Cβ.

The direction of the curves haschanged at Cβ = 72%, where weobserve two clockwise rotations(unstable) as we map the line jω -not seen in MARS analysismaybe 3D eddy effect.

Lead/Lag Compensation infeedback does not work!

VALEN Shows More Complex Unstable Transfer Function at High Cβ

[Y. Liu, 22 March 2006 Report]

Page 22: RWM Control in ITER - DIII-Dr,z = 8.85,0.45 m This models the Idealized n=1 RWM coil. 7/12 RWM response to coil current (transfer function) The RWM response to the coil current can

Improved Active Control in ITER:

Improved Coil Geometry

Improved Control Algorithms Beyond PID

Page 23: RWM Control in ITER - DIII-Dr,z = 8.85,0.45 m This models the Idealized n=1 RWM coil. 7/12 RWM response to coil current (transfer function) The RWM response to the coil current can

Proposed Alternative ITER RWM Control Coil Set:Nine Coils Located on Outer VV Wall

• Compare Performance with ITER Baseline Designboth with and without Blanket/Shield Modules

Page 24: RWM Control in ITER - DIII-Dr,z = 8.85,0.45 m This models the Idealized n=1 RWM coil. 7/12 RWM response to coil current (transfer function) The RWM response to the coil current can

VALEN Model of Alternative Control Coils With Gp

Performance Comparable to Baseline ITER Coil Set where

Best Stabilized βn with Proportional Gain ~ 3.18

Page 25: RWM Control in ITER - DIII-Dr,z = 8.85,0.45 m This models the Idealized n=1 RWM coil. 7/12 RWM response to coil current (transfer function) The RWM response to the coil current can

Internal vs External RWM Coils on ITER

• The study analyses the effect of a single turn coil in the 10 cm gap between theblanket shield module (BSM) and the port extension of a mid-plane port plug.

Page 26: RWM Control in ITER - DIII-Dr,z = 8.85,0.45 m This models the Idealized n=1 RWM coil. 7/12 RWM response to coil current (transfer function) The RWM response to the coil current can

RWM Coil Concept for ITER

• Baseline RWM coils located outside TF coils

Applying Internal RWM Feedback Coils to the Port Plugs in ITER Increases β−limit for n = 1 from βN = 2.5 to ~ 4

VALEN Analysis with Blanket Module

No-wall limit

• 7 RWM Coils mounted behind Port Plug Blanket Module with simple proportional gain Gp feedback control loop• Ulrickson “split” Blanket/Shield analysis Suggests βn > 4 possible

• Internal RWM coils would be located insidethe vacuum vessel behind shield modulebut inside the vacuum vessel on theremovable port plugs.

10-1

100

101

102

103

104

2.5 3 3.5 4 4.5 5 5.5

tarragona.2005

passive g ABMintc g #5 ABM e+7intc g #5 ABM e+8intc g+ #5 ABm e+8intc g #5 ABM e+9intc g+ #5 ABM e+9

grow

th ra

te [

1/s]

βn

tarragona.2005

best resultsβ

n = 3.94

Cβ = 53% ( 2.52 / 5.21 )

idea

l wal

l lim

it

Gp=107

Gp=108

Gp=109

Page 27: RWM Control in ITER - DIII-Dr,z = 8.85,0.45 m This models the Idealized n=1 RWM coil. 7/12 RWM response to coil current (transfer function) The RWM response to the coil current can

Proposed Approach to Combined RWM/ELM Control Coil• ITER Engineering VERY OPPOSED to any in-vessel coils behind the

blanket and shield modules.• Explore RWM and ELM Control performance of a hybrid internal port

plug set combined with an on-vessel (but external) set similar toDIII-D I-Coil set.

Page 28: RWM Control in ITER - DIII-Dr,z = 8.85,0.45 m This models the Idealized n=1 RWM coil. 7/12 RWM response to coil current (transfer function) The RWM response to the coil current can

Next Step: Go Beyond PID and Lead-Lag Compensation

• At 2005 ITPA MHD Group Meeting in Tarragona Joe Listeradvocated use of modern ‘state-space’ feedback controlmethods to better understand and optimize our modeling ofITER RWM active stabilization.

• Formulation of RWM Control Model in ‘State Space’ form isentry point to modern control theory that offers:+ Improved performance control loop using pure proportional gain+ Reduced noise using Optimal Observer and Kalman Filter+ Reduced dimension model for real-time application.

• This approach has been used in fusion modeling of n=0 stability, e.g.:D. J. N. Limebeer and J. P. Wainwright, IEEE Symposium on Industrial Electronics, p21-27 (1998).Al-Husari, Hendel, Jaimouka, Kasenally, Limebeer, Portone, 30th Conf. On Decision andControl, p 1165-1170 (1991)

Page 29: RWM Control in ITER - DIII-Dr,z = 8.85,0.45 m This models the Idealized n=1 RWM coil. 7/12 RWM response to coil current (transfer function) The RWM response to the coil current can

State Variables: A Dynamical Systems Approach

•Basic “state variable” or phase space representation using 1st order ODEs ratherthan transfer functions to describe system

r ˙ x =t A ⋅ r x unforced system dynamics (open loop γ)

r y =t C ⋅ r x output equations (what you what controlled)

•Can be nonlinear,

r ˙ x = f r x ( ), also

•Add feedback input control vector

r u (but do not close the loop yet)

r ˙ x =t A ⋅ r x +

t B ⋅ r u

t B gives coupling of

r u to system states

r y =t C ⋅ r x +

t D ⋅ r u

t D represents direct coupling of control

r u

What can we say about the open loop system dynamics without specifying afeedback law?

Controllability and Observability (solvability conditions)

Page 30: RWM Control in ITER - DIII-Dr,z = 8.85,0.45 m This models the Idealized n=1 RWM coil. 7/12 RWM response to coil current (transfer function) The RWM response to the coil current can

VALEN Circuit Equations Have A Built-in State Space

After including plasma stability effects the fluxes at the wall, plasma, andfeedback coils are given by (J. Bialek, et al., PoP 2001)

r Φ w =

t L ww ⋅

r I w +

t L wf ⋅

r I f +

t L wp ⋅ Id

r Φ f =

t L fw ⋅

r I w +

t L ff ⋅

r I f +

t L fp ⋅ Id

Φ =t

L pp ⋅ Id +t

L pw ⋅r I w +

t L pf ⋅

r I f

Using Faraday and Ohms law yields equations for system evolution

t L ww

t L wf

t L pwt

L fwt

L fft

L fpt L pw

t L pf

t L pp

ddt

r I wr I fId

=

t R w

t 0

r 0

t 0

t R f

r 0

r 0

r 0 Rd

r I wr I fId

+

r 0 r

V fr 0

This can easily be put in state space form…

Page 31: RWM Control in ITER - DIII-Dr,z = 8.85,0.45 m This models the Idealized n=1 RWM coil. 7/12 RWM response to coil current (transfer function) The RWM response to the coil current can

VALEN Mesh Current State Feedback

•The VALEN code, interestingly enough, has a “natural” intrinsic set of state variables. Theyare the circuit mesh currents used in the finite element model of the plasma,conductingwall, and feedback coil structures.

VALEN equations can be naturally written as,

r ˙ x =t A ⋅ r x +

t B ⋅ r u =

t A +

t B ⋅

t K ( ) ⋅ r x

The state vector of the system is given by:

r x =r I w ,

r I f , Id{ }

The control vector is the feedback coil voltages:

r u =r 0 ,

r V f ,0{ }

And with,

t A =

t L −1 ⋅

t R and

t B =

t L −1

Sensor flux as output

r y =r Φ s

with

r V f =

t G p

Φ ⋅r Φ s ≡

t K ⋅ r x and

r V f =

t G p

Φ ⋅t

L sw

t L sf

t L sp[ ]

r I wr I fId

Page 32: RWM Control in ITER - DIII-Dr,z = 8.85,0.45 m This models the Idealized n=1 RWM coil. 7/12 RWM response to coil current (transfer function) The RWM response to the coil current can

Apply DIII-D Noise Spectrum to ITER Baseline

Broadband white noise with amplitude of 10 Gauss[about 7 times level in DIII-D – ratio of IITER/IDIII-D]

No ELMs in applied noise spectrum

Page 33: RWM Control in ITER - DIII-Dr,z = 8.85,0.45 m This models the Idealized n=1 RWM coil. 7/12 RWM response to coil current (transfer function) The RWM response to the coil current can

Large Gd Leads to Very High Voltage Applied to Coils

Voltage Levels Reach ~ 1 MV: Need to Reduce

Page 34: RWM Control in ITER - DIII-Dr,z = 8.85,0.45 m This models the Idealized n=1 RWM coil. 7/12 RWM response to coil current (transfer function) The RWM response to the coil current can

Improved Stabilization of ITER RWM with NewOptimal Controller and Observer

• Optimal controller and observer were designed based on reduced to 20 modes ITERVALEN model for Cβ = 85%. In the presence of 10 Gauss sensor noise RWM wasstabilzed up to Cβ = 86%, as compared to Cβ = 68% reached by classical controller withderivative and proportional gains.• No derivative Gain is needed with Optimal Controller.• Significantly reduction in power requirements for Optimal Controller.

1.E-01

1.E+00

1.E+01

1.E+02

1.E+03

1.E+04

1.E+05

1.E+06

2.0 2.5 3.0 3.5 4.0 4.5 5.0

βn

γ, 1

/sec

PassiveGp/Gd=e9/e9OC_50%OC_85%Ideal Wall Limit

Page 35: RWM Control in ITER - DIII-Dr,z = 8.85,0.45 m This models the Idealized n=1 RWM coil. 7/12 RWM response to coil current (transfer function) The RWM response to the coil current can

ITER Optimal Controller Transient AnalysisControl Coil Voltage Measured Sensor Flux

• Modest Overshoot at Cβ ~ 80%

• Substantial Noise Reduction!

Page 36: RWM Control in ITER - DIII-Dr,z = 8.85,0.45 m This models the Idealized n=1 RWM coil. 7/12 RWM response to coil current (transfer function) The RWM response to the coil current can

Summary & Next Steps

• Baseline ITER External Coil Set can stabilize at βn ~ 3 level requiredfor basic Scenario 4 steady-state plasmas with RWM growth ratesγ~10/sec. Optimal Controller/Observer needed to reduce powerrequirements to acceptable levels and provide margin for RWMControl

• Blanket Modules in ITER extend the RWM reduced growth ratebranch up to βn ~ 5 and create an extended AT regime with importantDEMO implications.

• Accessibility of DEMO AT relevant βn ≥ 4 requires installation ofinternal control coils to stabilize RWM growth rates γ > 100/sec.

• USBPO & ITPA exploring possible combination RMP ELM Controland RWM Control normal conductor set trading off against BaselineSuperconducting Error Correction Coil Set & HV Power Supplies.